Key considerations for smoke shaft systems: 2. Natural or mechanical?1. Key considerations for smoke shaft systems: 2. Natural or
mechanical?
In this article, the second in our series about designing smoke shaft systems, we will look at the choice
of natural vs mechanical shafts.
Smoke shafts in multi-storey buildings take up potentially valuable space, so keeping the shafts as
small as possible is beneficial and has led to mechanical shafts becoming a popular choice.
But are they always the best choice? Let’s look at some of the issues.
Natural shafts
Prescriptive limits
For natural shaft systems there are prescriptive minimum shaft areas (3.0m2 and 1.5m2) and vent
areas (1.5m2 and 1m2respectively) and maximum aspect ratios (2:1 ratio between the length and
width). There are also limits on the permitted deviation from a straight vertical shaft arrangement and
the location of the shaft termination.
Key benefits
These prescriptive limits are the main reasons for considering mechanical shafts, but if you can live
with them, natural shafts have significant benefits:
• No fans. The primary benefit is that no fans are needed, together with their cabling and
controls and, of course, their standby power requirements.
• Low noise. The systems are virtually silent, although they can still be a source of noise
transmission in noisy areas, such as under flight paths.
• Low costs. Purchasing and operating costs are low, with a very small power requirement and
limited equipment to be tested and maintained.
• No roof top plant. Little roof space is required, simply room for the termination at the top of
the shaft.
Mechanical shafts
Key benefits
Mechanical shafts have 3 major benefits:
• Size. They can be small
• Flexibility. They can be more flexible in layout
• More ventilation. They can provide improved ventilation to compensate for extended travel
distances (but that’s for another blog)
Smaller shafts save space
© 2013 Colt International Licensing Ltd.
2. A smaller shaft can save a lot of space in a tall building. Typically shaft requirements vary between
about 0.5m2 and 1.2m2, depending upon flow rate and building height. We often quote a typical
0.6m2, simply because this shaft size is always suitable for buildings up to 30m height, covering the
majority of UK buildings.
Shape matters
Particularly with the smaller shaft sizes, the shape can be important as a minimum width is needed to
fit the shaft vents and a minimum depth is needed to avoid excessive obstruction of the shaft by the
vents and to allow vents to open fully and transfer smoke into the shaft.
If you really want to make the shaft an odd shape or have an aspect ratio greater than 2:1, I’d
recommend early discussion with your chosen specialist as this may restrict your choice of vent or
even prove impossible.
Smaller vents
The vents opening into the shaft can also be smaller, making them less obtrusive.
Mind the pressure drop
Flexibility is a key benefit, the addition of fans allowing the system to have a much higher pressure
drop, allowing bends, horizontal duct runs and less favourable termination locations. A key point to
remember, if taking advantage of this, is that systems don’t normally include VCD for balancing, so it is
important that the difference in total pressure drop between flow through the top and bottom vents is
kept reasonably low to avoid excessive differences in extract rates. Thus the actual builder’s work
shaft still needs to be as straight and unobstructed as possible.
Potential disadvantage: fixed flow
One potential disadvantage of mechanical systems is that they provide a fixed flow regardless of fire
size, whereas a natural system will provide a higher flow rate as the fire size and heat output
increases. The common design fire size for residential and sprinklered commercial fires is 2.5MW and
most systems are designed to operate correctly against this fire. However in unsprinklered commercial
buildings the fire size can be much greater. BR368 recommends 12MW for an unsprinklered open
plan office fire. While a natural shaft system will cope with this without change, a mechanical shaft
system would be overwhelmed unless upgraded. Colt offer such an upgrade as a standard option.
Conclusions
Well, as you might have expected, there’s no clear winner here. You have a choice of two alternative
systems with differing features and benefits to allow you the flexibility to incorporate the most suitable
one into your building.
Smoke shafts v pressurisation webinar
Watch out for further posts in this blog series, where we’ll look at other aspects of shaft system design.
In the meantime, register for our upcoming webinar on smoke shafts v pressurisation, where I will
cover:
• Features and benefits of both systems
• Common problems with both systems
© 2013 Colt International Licensing Ltd.
3. • How to choose which option is best for your project
The webinar is on June 27th at 12:30pm UK time and is CPD accredited. There will be the chance to
ask me questions at the end of the session and for those who register but can't make the seminar at
the last minute, the session will be recorded and made available online.
© 2013 Colt International Licensing Ltd.