Method statement for cleaning and treating
existing domestic systems

Cleaning and treating an existing central heating system using
Fernox Cleaner F3 and Fernox Protector F1 in accordance
with Part L of the Building Regulations
Procedure
1. 	 Identify and rectify mechanical faults.                7.	   Repeat step six on all radiators, boiler and
                                                                  circulator pipes.
2. 	 Dump system water to a foul drain and refill with
     fresh plain water.                                     8. 	 Re-open all radiators, and circulate for a further 15
                                                                 minutes and take a further TDS reading.
3. 	 Add Fernox Cleaner F3 through a radiator
     using either a Fernox Injector, Express or             9. 	 Once the system has been cleaned thoroughly
     Superconcentrate at the recommended dose. One               add Fernox Protector F1 at the recommended
     500ml bottle of Cleaner F3 treats a 100 litre system        dose. Fernox Protector F1 will protect against
     or up to 10 single radiators. If you are unsure of          the formation of limescale, corrosion and
     the dose rate contact Fernox Technical Services on          microbiological growths. It is crucial however, for
     +44 (0) 870 870 0362.                                       a Protector to work correctly, the system must be
                                                                 properly cleaned and flushed.
4. 	 Turn on the boiler and Cleaner F3 for a minimum
     of one hour, hot or for a longer period of time for    10. 	 Fit a Fernox Total Filter TF1, a unique
     heavily sludged systems.                                     hydrocyclonic and magnetic in-line filter for
                                                                  continual long-term protection.
5. 	 Isolate all radiators except that furthest away
     from the appliance, starting upstairs if applicable.   11. 	 The retreatment sticker provided with all Fernox
     Circulate the product through the radiator until             Protectors should be correctly completed and
     efficiency is restored.                                      applied to the boiler casing.
	    Repeat step five throughout the system including       Note: For continual protection Fernox recommend
     boiler and circulator pipes.                           Protector levels are checked annually (usually during
                                                            the service) or sooner if the system content is lost. This
6. 	 Isolate all radiators except that furthest away from
                                                            should be carried out using a Fernox Protector Test Kit.
     the appliance. Open the full bore drain point;
     at the same time introduce fresh water via the
                                                            Fernox Technical Services can be contacted on +44
     feed and expansion cistern or via the temporary
                                                            (0) 870 870 0362 for further advice or please visit www.
     mains connection if not a system, or combination
                                                            fernox.com.
     appliance. Flush through thoroughly until the water
     runs clear.
                                                            NB: Motorised valves should be manually opened
	    Use a Fernox TDS Meter to ensure that the              during the flushing process and any anti-gravity
     total dissolved solids have been satisfactorily        valves should be by-passed or removed temporarily.
     removed. The system can be regarded as
     being thoroughly flushed when the system               If it is necessary to cap off the open vent during the
     water value is within 10% of the mains water           mains flush to prevent overflow ensure the cap is
     value. Differences over 10% mean that significant      removed prior to starting the appliance.
     cleaner residues have been left in the system and
     further flushing is required. If not removed cleaner
     residues will promote corrosion and negate the
     cleaning process.
                                                                                   www.fernox.com

Contenu connexe

Similaire à Method Statement Cleaning and Treating Existing Domestic Systems

Keraflo Tanktronic Tank Management System - Brochure
Keraflo Tanktronic Tank Management System - BrochureKeraflo Tanktronic Tank Management System - Brochure
Keraflo Tanktronic Tank Management System - Brochure
Thorne & Derrick UK
 
pond filters.pdf
pond filters.pdfpond filters.pdf
Parker TwinZapp | Treating Oil in Water (OIW) Emulsions for Discharge to Sea
Parker TwinZapp | Treating Oil in Water (OIW) Emulsions for Discharge to SeaParker TwinZapp | Treating Oil in Water (OIW) Emulsions for Discharge to Sea
Parker TwinZapp | Treating Oil in Water (OIW) Emulsions for Discharge to Sea
Parker Hannifin Corporation
 
Horne OPTITHERM Thermostatic Mixing Tap - Specification Manual
Horne OPTITHERM Thermostatic Mixing Tap - Specification ManualHorne OPTITHERM Thermostatic Mixing Tap - Specification Manual
Horne OPTITHERM Thermostatic Mixing Tap - Specification Manual
Thorne & Derrick UK
 
Cleaningand sanitizingprocedure
Cleaningand sanitizingprocedure Cleaningand sanitizingprocedure
Cleaningand sanitizingprocedure
Ka Jejen
 

Similaire à Method Statement Cleaning and Treating Existing Domestic Systems (20)

Method Statement - Gold Clean
Method Statement - Gold CleanMethod Statement - Gold Clean
Method Statement - Gold Clean
 
Method Statement for Powerflushing Domestic Systems
Method Statement for Powerflushing Domestic SystemsMethod Statement for Powerflushing Domestic Systems
Method Statement for Powerflushing Domestic Systems
 
Taurus SC Insecticide / Termiticide
Taurus SC Insecticide / TermiticideTaurus SC Insecticide / Termiticide
Taurus SC Insecticide / Termiticide
 
Microplate washer
Microplate washerMicroplate washer
Microplate washer
 
Foam Extinguisher
Foam ExtinguisherFoam Extinguisher
Foam Extinguisher
 
Keraflo Tanktronic Tank Management System - Brochure
Keraflo Tanktronic Tank Management System - BrochureKeraflo Tanktronic Tank Management System - Brochure
Keraflo Tanktronic Tank Management System - Brochure
 
pond filters.pdf
pond filters.pdfpond filters.pdf
pond filters.pdf
 
Algae Capstone S.O.P.
Algae Capstone S.O.P.Algae Capstone S.O.P.
Algae Capstone S.O.P.
 
Dialysis Water Treatment
 Dialysis Water Treatment  Dialysis Water Treatment
Dialysis Water Treatment
 
Colorado Water Purification US Water Fusion Backwashing Filter Manual 1110 8 14
Colorado Water Purification US Water Fusion Backwashing Filter Manual 1110 8 14Colorado Water Purification US Water Fusion Backwashing Filter Manual 1110 8 14
Colorado Water Purification US Water Fusion Backwashing Filter Manual 1110 8 14
 
ASATT – American Society of Anesthesia Technologist and Technicians
ASATT – American Society of Anesthesia Technologist and TechniciansASATT – American Society of Anesthesia Technologist and Technicians
ASATT – American Society of Anesthesia Technologist and Technicians
 
Dsr 12 20
Dsr 12 20Dsr 12 20
Dsr 12 20
 
TR19 Regulations - B&ES Guide to Good Practice - London & Midland Cleaning C...
TR19 Regulations - B&ES Guide to Good Practice -  London & Midland Cleaning C...TR19 Regulations - B&ES Guide to Good Practice -  London & Midland Cleaning C...
TR19 Regulations - B&ES Guide to Good Practice - London & Midland Cleaning C...
 
Parker TwinZapp | Treating Oil in Water (OIW) Emulsions for Discharge to Sea
Parker TwinZapp | Treating Oil in Water (OIW) Emulsions for Discharge to SeaParker TwinZapp | Treating Oil in Water (OIW) Emulsions for Discharge to Sea
Parker TwinZapp | Treating Oil in Water (OIW) Emulsions for Discharge to Sea
 
Horne OPTITHERM Thermostatic Mixing Tap - Specification Manual
Horne OPTITHERM Thermostatic Mixing Tap - Specification ManualHorne OPTITHERM Thermostatic Mixing Tap - Specification Manual
Horne OPTITHERM Thermostatic Mixing Tap - Specification Manual
 
Cleaningand sanitizingprocedure
Cleaningand sanitizingprocedure Cleaningand sanitizingprocedure
Cleaningand sanitizingprocedure
 
Importance of Ducted Heating Repair in Melbourne by Experts
Importance of Ducted Heating Repair in Melbourne by ExpertsImportance of Ducted Heating Repair in Melbourne by Experts
Importance of Ducted Heating Repair in Melbourne by Experts
 
Pellicon 3 biomax membrane
Pellicon 3 biomax membranePellicon 3 biomax membrane
Pellicon 3 biomax membrane
 
Training materials for students final r4-uf-ro-1
Training materials for students final r4-uf-ro-1Training materials for students final r4-uf-ro-1
Training materials for students final r4-uf-ro-1
 
Bosch
BoschBosch
Bosch
 

Plus de Fernox

Fernox Limescale Preventer
Fernox Limescale PreventerFernox Limescale Preventer
Fernox Limescale Preventer
Fernox
 

Plus de Fernox (13)

How To Prevent Corrosion
How To Prevent CorrosionHow To Prevent Corrosion
How To Prevent Corrosion
 
How to Dose A Central Heating System with Fernox Express
How to Dose A Central Heating System with Fernox ExpressHow to Dose A Central Heating System with Fernox Express
How to Dose A Central Heating System with Fernox Express
 
How To Reduce Boiler Noise
How To Reduce Boiler NoiseHow To Reduce Boiler Noise
How To Reduce Boiler Noise
 
How To Combat Limescale
How To Combat LimescaleHow To Combat Limescale
How To Combat Limescale
 
Fernox Infographic
Fernox InfographicFernox Infographic
Fernox Infographic
 
FERNOX APPOINTS NEW TECHNICAL & PRODUCT DIRECTOR
FERNOX APPOINTS NEW TECHNICAL & PRODUCT DIRECTORFERNOX APPOINTS NEW TECHNICAL & PRODUCT DIRECTOR
FERNOX APPOINTS NEW TECHNICAL & PRODUCT DIRECTOR
 
£50k Anniversary Promotion
£50k Anniversary Promotion£50k Anniversary Promotion
£50k Anniversary Promotion
 
FERNOX: CELEBRATING 50 YEARS OF INNOVATION
FERNOX: CELEBRATING 50 YEARS OF INNOVATION FERNOX: CELEBRATING 50 YEARS OF INNOVATION
FERNOX: CELEBRATING 50 YEARS OF INNOVATION
 
TF1 Quick Reference Installation and Cleaning Guide
TF1 Quick Reference Installation and Cleaning GuideTF1 Quick Reference Installation and Cleaning Guide
TF1 Quick Reference Installation and Cleaning Guide
 
Fernox TF1 Compact Advert
Fernox TF1 Compact AdvertFernox TF1 Compact Advert
Fernox TF1 Compact Advert
 
Energy Saver F6
Energy Saver F6 Energy Saver F6
Energy Saver F6
 
Fernox Limescale Preventer
Fernox Limescale PreventerFernox Limescale Preventer
Fernox Limescale Preventer
 
Fernox Product Presentation
Fernox Product PresentationFernox Product Presentation
Fernox Product Presentation
 

Method Statement Cleaning and Treating Existing Domestic Systems

  • 1. Method statement for cleaning and treating existing domestic systems Cleaning and treating an existing central heating system using Fernox Cleaner F3 and Fernox Protector F1 in accordance with Part L of the Building Regulations Procedure 1. Identify and rectify mechanical faults. 7. Repeat step six on all radiators, boiler and circulator pipes. 2. Dump system water to a foul drain and refill with fresh plain water. 8. Re-open all radiators, and circulate for a further 15 minutes and take a further TDS reading. 3. Add Fernox Cleaner F3 through a radiator using either a Fernox Injector, Express or 9. Once the system has been cleaned thoroughly Superconcentrate at the recommended dose. One add Fernox Protector F1 at the recommended 500ml bottle of Cleaner F3 treats a 100 litre system dose. Fernox Protector F1 will protect against or up to 10 single radiators. If you are unsure of the formation of limescale, corrosion and the dose rate contact Fernox Technical Services on microbiological growths. It is crucial however, for +44 (0) 870 870 0362. a Protector to work correctly, the system must be properly cleaned and flushed. 4. Turn on the boiler and Cleaner F3 for a minimum of one hour, hot or for a longer period of time for 10. Fit a Fernox Total Filter TF1, a unique heavily sludged systems. hydrocyclonic and magnetic in-line filter for continual long-term protection. 5. Isolate all radiators except that furthest away from the appliance, starting upstairs if applicable. 11. The retreatment sticker provided with all Fernox Circulate the product through the radiator until Protectors should be correctly completed and efficiency is restored. applied to the boiler casing. Repeat step five throughout the system including Note: For continual protection Fernox recommend boiler and circulator pipes. Protector levels are checked annually (usually during the service) or sooner if the system content is lost. This 6. Isolate all radiators except that furthest away from should be carried out using a Fernox Protector Test Kit. the appliance. Open the full bore drain point; at the same time introduce fresh water via the Fernox Technical Services can be contacted on +44 feed and expansion cistern or via the temporary (0) 870 870 0362 for further advice or please visit www. mains connection if not a system, or combination fernox.com. appliance. Flush through thoroughly until the water runs clear. NB: Motorised valves should be manually opened Use a Fernox TDS Meter to ensure that the during the flushing process and any anti-gravity total dissolved solids have been satisfactorily valves should be by-passed or removed temporarily. removed. The system can be regarded as being thoroughly flushed when the system If it is necessary to cap off the open vent during the water value is within 10% of the mains water mains flush to prevent overflow ensure the cap is value. Differences over 10% mean that significant removed prior to starting the appliance. cleaner residues have been left in the system and further flushing is required. If not removed cleaner residues will promote corrosion and negate the cleaning process. www.fernox.com