2. Overview
• Problem Statement
• Building Overview
• Mechanical System
• Electrical Plan
• Cost Analysis
• LEED Analysis
• Failure Analysis
• Marketing
2ELEMENT ENGINEERING -
Wayne State University Team 2
3. Problem Statement
• Design a state of the art building for State University of
New York (S.U.N.Y) using renewable resources and
hydrogen to produce electricity for the building’s energy
needs. The proposed design will use green technologies
and follow LEED standards to reduce the impact on the
environment and be more efficient than the baseline
energy load. This includes a design that is realistic,
practical, and reduce pollution while staying within the
$28 Million budget.
3ELEMENT ENGINEERING -
Wayne State University Team 2
5. Movie Slide
5ELEMENT ENGINEERING -
Wayne State University Team 2
•To Activate Movie, exit presentation
and right click on the ‘.wmv’ file
and select ‘Packaged Content’
and then select ‘Activate Content’
7. ELEMENT ENGINEERING -
Wayne State University Team 2
7
Building Floor Plan
Faculty Offices
(Southwest Corner)
Student Organization Offices
(Northwest Corner)
Kitchen and
Lounging Areas
Bookstore (SE Corner)
Auditorium (NE Corner)
Overall Building Floor Plan
9. Wind
Energy
• Inland Long Island Avg.
Wind Speed – 6 m/s (13
mph)
• Bergey 10 kW EXCEL
Horizontal Turbine.
• 10 Wind Turbines
generating 50 kW
• Total Cost $ 522,000.00
• Wind Energy Output –
1200 kWh/day
9ELEMENT ENGINEERING -
Wayne State University Team 2
11. Solar
Energy
• General Electric GEPV –
165 Photovoltaic cells
• 700 Panels
• Rated1 kW per 93 ft2
• Installation Cost – $5000
per kW
• Total Cost $1,379,490.00
• Solar Energy Output –
577.5 kWh/day
11ELEMENT ENGINEERING -
Wayne State University Team 2
16. Heating
• Natural gas boiler (906 kBtu/hr, flow rate of 45 gal/min)
• Boiler produces hot water for heat exchanger
• Supplies Energy to heat up outside air by ventilation fan
Cooling
• Building cooled by absorption chiller
• Help to alleviate the electrical load
• Absorption chiller use of Natural Gas
• Require a chilled water loop capacity of 1.56 MBTU/hr
• Flow rate of 315 gal/min
• Carrier 16DJ 108 ton absorption chiller meets these
requirements and is approved to meet ASHRAE 90.1
building energy standards
Heating, Ventilation & Air Conditioning
16ELEMENT ENGINEERING -
Wayne State University Team 2