SlideShare une entreprise Scribd logo
1  sur  34
Télécharger pour lire hors ligne
VRF
Technical Data Book
DVM S Standard for Turkey (ODU, 50Hz, HP)
Model : AM***KXVAGH/TK
History
Version Modification Date Remark
Ver.1.0 Release DVM S 30HP Standard TDB for Turkey 16.01.12.
Nomenclature
Outdoor Units
Model Names
AM
(1)
140
(2)
K
(3)
X
(4)
V
(5)
A
(6)
G
(7)
H
(8)
EU
Buyer
(1) Classification
AM DVM
(2) Capacity
x 1/10 HP (3 digits)
(3) Version
F 2013
H 2014
J 2015
K 2016
(4) Product Type
X Outdoor Unit
N Indoor Unit
(5) Feature1
V Inverter
M DVM S Eco
(6) Feature2
A Standard + General Temp.+ Module
H High EER + Low Temp + Module
G High EER + General Temp + Module
(7) Rating Voltage
E 1Ø, 220~240V, 50Hz
G 3Ø, 380~415V, 50Hz
(8) Mode
H Heat Pump
R Heat Recovery
Outdoor
1 Line-up
2 Specifications
3 Operation limit
4 Dimensional drawing
5 Electrical wiring diagram
6 Sound pressure level
7 Sound power level
8 Cycle diagram
Line-up
Outdoor Units
System Model
Capacity System Model Code
Number
of
Modules
Outdoor Unit Selection
14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP
AM140KXVAG
H/TK
AM160KXVAG
H/TK
AM180KXVAG
H/TK
AM200KXVAG
H/TK
AM220KXVAG
H/TK
AM240KXVAG
H/TK
AM260KXVAG
H/TK
AM280KXVAG
H/TK
AM300KXVAG
H/TK
14HP AM140KXVAGH/TK 1
16HP AM160KXVAGH/TK 1
18HP AM180KXVAGH/TK 1
20HP AM200KXVAGH/TK 1
22HP AM220KXVAGH/TK 1
24HP AM240KXVAGH/TK 1
26HP AM260KXVAGH/TK 1
28HP AM280KXVAGH/TK 1
30HP AM300KXVAGH/TK 1
32HP AM320KXVAGH/TK 2
34HP AM340KXVAGH/TK 2
36HP AM360KXVAGH/TK 2
38HP AM380KXVAGH/TK 2
40HP AM400KXVAGH/TK 2
42HP AM420KXVAGH/TK 2
44HP AM440KXVAGH/TK 2
46HP AM460KXVAGH/TK 2
48HP AM480KXVAGH/TK 2
50HP AM500KXVAGH/TK 2
52HP AM520KXVAGH/TK 2
54HP AM540KXVAGH/TK 2
56HP AM560KXVAGH/TK 2
58HP AM580KXVAGH/TK 2
60HP AM600KXVAGH/TK 2
62HP AM620KXVAGH/TK 3
64HP AM640KXVAGH/TK 3
66HP AM660KXVAGH/TK 3
68HP AM680KXVAGH/TK 3
70HP AM700KXVAGH/TK 3
72HP AM720KXVAGH/TK 3
74HP AM740KXVAGH/TK 3
76HP AM760KXVAGH/TK 3
78HP AM780KXVAGH/TK 3
80HP AM800KXVAGH/TK 3
82HP AM820KXVAGH/TK 3
84HP AM840KXVAGH/TK 3
86HP AM860KXVAGH/TK 3
88HP AM880KXVAGH/TK 3
90HP AM900KXVAGH/TK 3
1
1
1
1
1
1
1
1
1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
2
1 1 1
1 1 1
2 1
1 1 1
1 1 1
1 1 1
2 1
1 1 1
1 1 1
1 1 1
1 2
1 2
1 2
1 2
3
1
Specifications
Outdoor
Type
Model Name
Power Supply Ø, #, V, Hz
Mode -
Performance
HP HP
Capacity
(Nominal)
Cooling
kW
Btu/h
Heating
kW
Btu/h
Power
Power Input
(Nominal)
Cooling 1) kW
Heating 2) kW
Current
Input
(Nominal)
Cooling 1) A
Heating 2) A
MCA A
MFA A
COP
EER (Nominal Cooling) -
COP (Nominal Heating) -
Energy Grade
-
-
Compressor
Type -
Output kW x n
Model Name -
Oil Type -
Fan
Type -
Output x n W
Air Flow Rate
CMM
l/s
External
Static
Max.
mmAQ
Pa
Piping
Connections
Liquid Pipe
Ø, mm
Ø, inch
Gas Pipe
Ø, mm
Ø, inch
Discharge Gas Pipe
Ø, mm
Ø, inch
Installation
Limitation
Max. Length m
Max. Height m
Field Wiring
Power Source Wire mm²
Transmission Cable mm²
Refrigerant
Type -
Factory Charging kg
Sound
Pressure
dBA
Power
External
Dimension
New Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions
(WxHxD)
mm
Operating
Temp.
Cooling ºC
Heating ºC
DVM S(NEW) DVM S(NEW) DVM S(NEW)
AM140KXVAGH/TK AM160KXVAGH/TK AM180KXVAGH/TK
3,4,380-415,50 3,4,380-415,50 3,4,380-415,50
HP HP HP
14.00 16.00 18.00
40.00 45.00 50.40
136,500 153,500 172,000
45.00 50.40 56.70
153,500 172,000 193,500
10.93 12.10 12.60
10.16 11.61 11.91
17.50 19.40 20.20
16.30 18.60 19.10
25.00 32.00 39.20
40.00 40.00 50.00
3.66 3.72 4.00
4.43 4.34 4.76
ESEER 7.02 ESEER 6.81 ESEER 6.61
- - -
SSC Scroll x 1 SSC Scroll x 1 SSC Scroll x 1
(6.39) (7.81) (7.81)
DS-GB066FAVBx1 DS4GJ5080FVAx1 DS4GJ5080FVAx1
PVE PVE PVE
Propeller Propeller Propeller
620.0x2 620.0x2 620.0x2
255 255 290
4,250.00 4,250.00 4,833.33
8.00 8.00 8.00
78.40 78.40 78.40
12.70 12.70 15.88
1/2" 1/2" 5/8"
28.58 28.58 28.58
1 1/8" 1 1/8" 1 1/8"
- - -
- - -
200 (220) 200 (220) 200 (220)
110 (40) 110 (40) 110 (40)
- - -
0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50
R410A R410A R410A
7.70 8.40 8.40
61 63 64
81 83 84
226.0 253.0 255.0
246.0 273.0 275.0
1,295x1,695x765 1,295x1,695x765 1,295x1,695x765
1,363x1,887x832 1,363x1,887x832 1,363x1,887x832
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
-25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0
* Specifications may be subject to change without prior notice.
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit
2
Specifications
Outdoor
Type
Model Name
Power Supply Ø, #, V, Hz
Mode -
Performance
HP HP
Capacity
(Nominal)
Cooling
kW
Btu/h
Heating
kW
Btu/h
Power
Power Input
(Nominal)
Cooling 1) kW
Heating 2) kW
Current
Input
(Nominal)
Cooling 1) A
Heating 2) A
MCA A
MFA A
COP
EER (Nominal Cooling) -
COP (Nominal Heating) -
Energy Grade
-
-
Compressor
Type -
Output kW x n
Model Name -
Oil Type -
Fan
Type -
Output x n W
Air Flow Rate
CMM
l/s
External
Static
Max.
mmAQ
Pa
Piping
Connections
Liquid Pipe
Ø, mm
Ø, inch
Gas Pipe
Ø, mm
Ø, inch
Discharge Gas Pipe
Ø, mm
Ø, inch
Installation
Limitation
Max. Length m
Max. Height m
Field Wiring
Power Source Wire mm²
Transmission Cable mm²
Refrigerant
Type -
Factory Charging kg
Sound
Pressure
dBA
Power
External
Dimension
New Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions
(WxHxD)
mm
Operating
Temp.
Cooling ºC
Heating ºC
DVM S(NEW) DVM S(NEW) DVM S(NEW)
AM200KXVAGH/TK AM220KXVAGH/TK AM240KXVAGH/TK
3,4,380-415,50 3,4,380-415,50 3,4,380-415,50
HP HP HP
20.00 22.00 24.00
56.00 61.60 67.20
191,100 210,200 229,300
63.00 69.30 75.60
215,000 236,500 258,000
14.18 17.35 17.10
13.91 16.70 17.42
22.70 27.80 27.40
22.30 26.80 27.90
42.00 44.60 55.00
75.00 75.00 75.00
3.95 3.55 3.93
4.53 4.15 4.34
ESEER 6.56 ESEER 6.25 ESEER 7.06
- - -
SSC Scroll x 2 SSC Scroll x 2 SSC Scroll x 2
(5.18 x 2) (6.39 x 2) (6.39 x 2)
DS-GB052FAVBx2 DS-GB066FAVBx2 DS-GB066FAVBx2
PVE PVE PVE
Propeller Propeller Propeller
620.0x2 620.0x2 620.0x2
290 290 340
4,833.33 4,833.33 5,666.67
8.00 8.00 8.00
78.40 78.40 78.40
15.88 15.88 15.88
5/8" 5/8" 5/8"
28.58 28.58 34.92
1 1/8" 1 1/8" 1 3/8"
- - -
- - -
200 (220) 200 (220) 200 (220)
110 (40) 110 (40) 110 (40)
- - -
0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50
R410A R410A R410A
8.40 8.40 12.50
65 65 66
87 89 89
277.0 285.0 333.0
297.0 305.0 355.0
1,295x1,695x765 1,295x1,695x765 1,295x1,795x765
1,363x1,887x832 1,363x1,887x832 1,363x1,987x832
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
-25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0
* Specifications may be subject to change without prior notice.
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit
2
Specifications
Outdoor
Type
Model Name
Power Supply Ø, #, V, Hz
Mode -
Performance
HP HP
Capacity
(Nominal)
Cooling
kW
Btu/h
Heating
kW
Btu/h
Power
Power Input
(Nominal)
Cooling 1) kW
Heating 2) kW
Current
Input
(Nominal)
Cooling 1) A
Heating 2) A
MCA A
MFA A
COP
EER (Nominal Cooling) -
COP (Nominal Heating) -
Energy Grade
-
-
Compressor
Type -
Output kW x n
Model Name -
Oil Type -
Fan
Type -
Output x n W
Air Flow Rate
CMM
l/s
External
Static
Max.
mmAQ
Pa
Piping
Connections
Liquid Pipe
Ø, mm
Ø, inch
Gas Pipe
Ø, mm
Ø, inch
Discharge Gas Pipe
Ø, mm
Ø, inch
Installation
Limitation
Max. Length m
Max. Height m
Field Wiring
Power Source Wire mm²
Transmission Cable mm²
Refrigerant
Type -
Factory Charging kg
Sound
Pressure
dBA
Power
External
Dimension
New Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions
(WxHxD)
mm
Operating
Temp.
Cooling ºC
Heating ºC
DVM S(NEW) DVM S(NEW) DVM S(NEW)
AM260KXVAGH/TK AM280KXVAGH/TK AM300KXVAGH/TK
3,4,380-415,50 3,4,380-415,50 3,4,380-415,50
HP HP HP
26.00 28.00 30.00
72.80 78.60 84.00
248,400 268,200 286,600
81.90 88.20 94.50
279,500 301,000 322,400
18.91 20.68 22.70
18.00 20.18 20.59
30.30 33.20 36.40
28.90 32.40 33.00
60.00 67.00 73.00
75.00 75.00 90.00
3.85 3.80 3.70
4.55 4.37 4.59
ESEER 6.92 ESEER 6.83 ESEER 6.65
- - -
SSC Scroll x 2 SSC Scroll x 2 SSC Scroll x 2
(6.39 x 2) (6.76 x 2) (7.81 x 2)
DS-GB066FAVBx2 DS-GB070FAVAx2 DS4GJ5080FVAx2
PVE PVE PVE
Propeller Propeller Propeller
620.0x2 620.0x2 620.0x2
340 340 340
5,666.67 5,666.67 5,666.67
8.00 8.00 8.00
78.40 78.40 78.40
19.05 19.05 19.05
3/4" 3/4" 3/4"
34.92 34.92 34.92
1 3/8" 1 3/8" 1 3/8"
- - -
- - -
200 (220) 200 (220) 200 (220)
110 (40) 110 (40) 110 (40)
- - -
0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50
R410A R410A R410A
12.50 14.00 14.00
66 69 69
89 90 90
333.0 342.0 350.0
355.0 364.0 372.0
1,295x1,795x765 1,295x1,795x765 1,295x1,795x765
1,363x1,987x832 1,363x1,987x832 1,363x1,987x832
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
-25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0
* Specifications may be subject to change without prior notice.
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit
2
Specifications
Outdoor
Type
Model Name
Power Supply Ø, #, V, Hz
Mode -
Performance
HP HP
Capacity
(Nominal)
Cooling
kW
Btu/h
Heating
kW
Btu/h
Power
Power Input
(Nominal)
Cooling 1) kW
Heating 2) kW
Current
Input
(Nominal)
Cooling 1) A
Heating 2) A
MCA A
MFA A
COP
EER (Nominal Cooling) -
COP (Nominal Heating) -
Energy Grade
-
-
Compressor
Type -
Output kW x n
Model Name -
Oil Type -
Fan
Type -
Output x n W
Air Flow Rate
CMM
l/s
External
Static
Max.
mmAQ
Pa
Piping
Connections
Liquid Pipe
Ø, mm
Ø, inch
Gas Pipe
Ø, mm
Ø, inch
Discharge Gas Pipe
Ø, mm
Ø, inch
Installation
Limitation
Max. Length m
Max. Height m
Field Wiring
Power Source Wire mm²
Transmission Cable mm²
Refrigerant
Type -
Factory Charging kg
Sound
Pressure
dBA
Power
External
Dimension
New Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions
(WxHxD)
mm
Operating
Temp.
Cooling ºC
Heating ºC
DVM S(NEW) DVM S(NEW) DVM S(NEW)
AM320KXVAGH/TK AM340KXVAGH/TK AM360KXVAGH/TK
3,4,380-415,50 3,4,380-415,50 3,4,380-415,50
HP HP HP
32.00 34.00 36.00
90.40 95.40 101.60
308,500 325,500 346,700
101.70 107.10 114.30
347,000 365,400 390,000
23.53 24.70 28.28
22.07 23.52 26.86
37.70 39.60 45.30
35.40 37.70 43.10
64.20 71.20 69.60
75.00 90.00 90.00
3.84 3.86 3.59
4.61 4.55 4.26
- - -
- - -
SSC Scroll x 2 SSC Scroll x 2 SSC Scroll x 3
(6.39) + (7.81) (7.81) + (7.81) (6.39) + (6.39x2)
DS-GB066FAVBx1 +
DS4GJ5080FVAx1
DS4GJ5080FVAx2 DS-GB066FAVBx3
PVE PVE PVE
Propeller Propeller Propeller
(620.0x2)x2 (620.0x2)x2 (620.0x2)x2
255.0 + 290.0 255.0 + 290.0 255.0 + 290.0
4,250.0 + 4,833.3 4,250.0 + 4,833.3 4,250.0 + 4,833.3
8.00 8.00 8.00
78.40 78.40 78.40
19.05 19.05 19.05
3/4" 3/4" 3/4"
34.92 34.92 41.28
1 3/8" 1 3/8" 1 5/8"
- - -
- - -
200 (220) 200 (220) 200 (220)
110 (40) 110 (40) 110 (40)
- - -
0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50
R410A R410A R410A
16.10 16.80 16.10
- - -
- - -
226.0 + 255.0 253.0 + 255.0 226.0 + 285.0
246.0 + 275.0 273.0 + 275.0 246.0 + 305.0
(1,295x1,695x765)x2 (1,295x1,695x765)x2 (1,295x1,695x765)x2
(1,363x1,887x832)x2 (1,363x1,887x832)x2 (1,363x1,887x832)x2
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
-25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0
* Specifications may be subject to change without prior notice.
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit
2
Specifications
Outdoor
Type
Model Name
Power Supply Ø, #, V, Hz
Mode -
Performance
HP HP
Capacity
(Nominal)
Cooling
kW
Btu/h
Heating
kW
Btu/h
Power
Power Input
(Nominal)
Cooling 1) kW
Heating 2) kW
Current
Input
(Nominal)
Cooling 1) A
Heating 2) A
MCA A
MFA A
COP
EER (Nominal Cooling) -
COP (Nominal Heating) -
Energy Grade
-
-
Compressor
Type -
Output kW x n
Model Name -
Oil Type -
Fan
Type -
Output x n W
Air Flow Rate
CMM
l/s
External
Static
Max.
mmAQ
Pa
Piping
Connections
Liquid Pipe
Ø, mm
Ø, inch
Gas Pipe
Ø, mm
Ø, inch
Discharge Gas Pipe
Ø, mm
Ø, inch
Installation
Limitation
Max. Length m
Max. Height m
Field Wiring
Power Source Wire mm²
Transmission Cable mm²
Refrigerant
Type -
Factory Charging kg
Sound
Pressure
dBA
Power
External
Dimension
New Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions
(WxHxD)
mm
Operating
Temp.
Cooling ºC
Heating ºC
DVM S(NEW) DVM S(NEW) DVM S(NEW)
AM380KXVAGH/TK AM400KXVAGH/TK AM420KXVAGH/TK
3,4,380-415,50 3,4,380-415,50 3,4,380-415,50
HP HP HP
38.00 40.00 42.00
106.60 112.00 117.60
363,700 382,200 401,300
119.70 126.00 132.30
408,400 429,900 451,400
29.45 29.95 31.53
28.31 28.61 30.61
47.20 48.00 50.50
45.40 45.90 49.10
76.60 83.80 86.60
90.00 100.00 100.00
3.62 3.74 3.73
4.23 4.40 4.32
- - -
- - -
SSC Scroll x 3 SSC Scroll x 3 SSC Scroll x 4
(7.81) + (6.39x2) (7.81) + (6.39x2) (5.18x2) + (6.39x2)
DS4GJ5080FVAx1 + DS-
GB066FAVBx2
DS4GJ5080FVAx1 + DS-
GB066FAVBx2
DS-GB052FAVBx2 + DS-
GB066FAVBx2
PVE PVE PVE
Propeller Propeller Propeller
(620.0x2)x2 (620.0x2)x2 (620.0x2)x2
255.0 + 290.0 290.0x2 290.0x2
4,250.0 + 4,833.3 4,833.3x2 4,833.3x2
8.00 8.00 8.00
78.40 78.40 78.40
19.05 19.05 19.05
3/4" 3/4" 3/4"
41.28 41.28 41.28
1 5/8" 1 5/8" 1 5/8"
- - -
- - -
200 (220) 200 (220) 200 (220)
110 (40) 110 (40) 110 (40)
- - -
0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50
R410A R410A R410A
16.80 16.80 16.80
- - -
- - -
253.0 + 285.0 255.0 + 285.0 277.0 + 285.0
273.0 + 305.0 275.0 + 305.0 297.0 + 305.0
(1,295x1,695x765)x2 (1,295x1,695x765)x2 (1,295x1,695x765)x2
(1,363x1,887x832)x2 (1,363x1,887x832)x2 (1,363x1,887x832)x2
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
-25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0
* Specifications may be subject to change without prior notice.
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit
2
Specifications
Outdoor
Type
Model Name
Power Supply Ø, #, V, Hz
Mode -
Performance
HP HP
Capacity
(Nominal)
Cooling
kW
Btu/h
Heating
kW
Btu/h
Power
Power Input
(Nominal)
Cooling 1) kW
Heating 2) kW
Current
Input
(Nominal)
Cooling 1) A
Heating 2) A
MCA A
MFA A
COP
EER (Nominal Cooling) -
COP (Nominal Heating) -
Energy Grade
-
-
Compressor
Type -
Output kW x n
Model Name -
Oil Type -
Fan
Type -
Output x n W
Air Flow Rate
CMM
l/s
External
Static
Max.
mmAQ
Pa
Piping
Connections
Liquid Pipe
Ø, mm
Ø, inch
Gas Pipe
Ø, mm
Ø, inch
Discharge Gas Pipe
Ø, mm
Ø, inch
Installation
Limitation
Max. Length m
Max. Height m
Field Wiring
Power Source Wire mm²
Transmission Cable mm²
Refrigerant
Type -
Factory Charging kg
Sound
Pressure
dBA
Power
External
Dimension
New Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions
(WxHxD)
mm
Operating
Temp.
Cooling ºC
Heating ºC
DVM S(NEW) DVM S(NEW) DVM S(NEW)
AM440KXVAGH/TK AM460KXVAGH/TK AM480KXVAGH/TK
3,4,380-415,50 3,4,380-415,50 3,4,380-415,50
HP HP HP
44.00 46.00 48.00
124.00 129.00 134.40
423,100 440,200 458,600
139.50 144.90 151.20
476,000 494,400 515,900
33.63 34.80 35.30
30.75 32.20 32.50
53.90 55.80 56.60
49.30 51.60 52.10
98.00 105.00 112.20
125.00 125.00 125.00
3.69 3.71 3.81
4.54 4.50 4.65
- - -
- - -
SSC Scroll x 3 SSC Scroll x 3 SSC Scroll x 3
(6.39) + (7.81x2) (7.81) + (7.81x2) (7.81) + (7.81x2)
DS-GB066FAVBx1 +
DS4GJ5080FVAx2
DS4GJ5080FVAx3 DS4GJ5080FVAx3
PVE PVE PVE
Propeller Propeller Propeller
(620.0x2)x2 (620.0x2)x2 (620.0x2)x2
255.0 + 340.0 255.0 + 340.0 290.0 + 340.0
4,250.0 + 5,666.7 4,250.0 + 5,666.7 4,833.3 + 5,666.7
8.00 8.00 8.00
78.40 78.40 78.40
19.05 19.05 19.05
3/4" 3/4" 3/4"
41.28 41.28 41.28
1 5/8" 1 5/8" 1 5/8"
- - -
- - -
200 (220) 200 (220) 200 (220)
110 (40) 110 (40) 110 (40)
- - -
0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50
R410A R410A R410A
21.70 22.40 22.40
- - -
- - -
226.0 + 350.0 253.0 + 350.0 255.0 + 350.0
246.0 + 372.0 273.0 + 372.0 275.0 + 372.0
1,295x1,695x765 +
1,295x1,795x765
1,295x1,695x765 +
1,295x1,795x765
1,295x1,695x765 +
1,295x1,795x765
1,363x1,887x832 +
1,363x1,987x832
1,363x1,887x832 +
1,363x1,987x832
1,363x1,887x832 +
1,363x1,987x832
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
-25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0
* Specifications may be subject to change without prior notice.
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit
2
Specifications
Outdoor
Type
Model Name
Power Supply Ø, #, V, Hz
Mode -
Performance
HP HP
Capacity
(Nominal)
Cooling
kW
Btu/h
Heating
kW
Btu/h
Power
Power Input
(Nominal)
Cooling 1) kW
Heating 2) kW
Current
Input
(Nominal)
Cooling 1) A
Heating 2) A
MCA A
MFA A
COP
EER (Nominal Cooling) -
COP (Nominal Heating) -
Energy Grade
-
-
Compressor
Type -
Output kW x n
Model Name -
Oil Type -
Fan
Type -
Output x n W
Air Flow Rate
CMM
l/s
External
Static
Max.
mmAQ
Pa
Piping
Connections
Liquid Pipe
Ø, mm
Ø, inch
Gas Pipe
Ø, mm
Ø, inch
Discharge Gas Pipe
Ø, mm
Ø, inch
Installation
Limitation
Max. Length m
Max. Height m
Field Wiring
Power Source Wire mm²
Transmission Cable mm²
Refrigerant
Type -
Factory Charging kg
Sound
Pressure
dBA
Power
External
Dimension
New Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions
(WxHxD)
mm
Operating
Temp.
Cooling ºC
Heating ºC
DVM S(NEW) DVM S(NEW) DVM S(NEW)
AM500KXVAGH/TK AM520KXVAGH/TK AM540KXVAGH/TK
3,4,380-415,50 3,4,380-415,50 3,4,380-415,50
HP HP HP
50.00 52.00 54.00
140.00 145.60 151.20
477,700 496,800 515,900
157.50 163.80 170.10
537,400 558,900 580,400
36.88 40.05 39.80
34.50 37.29 38.01
59.10 64.20 63.80
55.30 59.80 60.90
115.00 117.60 128.00
150.00 150.00 150.00
3.80 3.64 3.80
4.57 4.39 4.48
- - -
- - -
SSC Scroll x 4 SSC Scroll x 4 SSC Scroll x 4
(5.18x2) + (7.81x2) (6.39x2) + (7.81x2) (6.39x2) + (7.81x2)
DS-GB052FAVBx2 +
DS4GJ5080FVAx2
DS-GB066FAVBx2 +
DS4GJ5080FVAx2
DS-GB066FAVBx2 +
DS4GJ5080FVAx2
PVE PVE PVE
Propeller Propeller Propeller
(620.0x2)x2 (620.0x2)x2 (620.0x2)x2
290.0 + 340.0 290.0 + 340.0 340.0x2
4,833.3 + 5,666.7 4,833.3 + 5,666.7 5,666.7x2
8.00 8.00 8.00
78.40 78.40 78.40
19.05 19.05 19.05
3/4" 3/4" 3/4"
41.28 41.28 41.28
1 5/8" 1 5/8" 1 5/8"
- - -
- - -
200 (220) 200 (220) 200 (220)
110 (40) 110 (40) 110 (40)
- - -
0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50
R410A R410A R410A
22.40 22.40 26.50
- - -
- - -
277.0 + 350.0 285.0 + 350.0 333.0 + 350.0
297.0 + 372.0 305.0 + 372.0 355.0 + 372.0
1,295x1,695x765 +
1,295x1,795x765
1,295x1,695x765 +
1,295x1,795x765
(1,295x1,795x765)x2
1,363x1,887x832 +
1,363x1,987x832
1,363x1,887x832 +
1,363x1,987x832
(1,363x1,987x832)x2
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
-25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0
* Specifications may be subject to change without prior notice.
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit
2
Specifications
Outdoor
Type
Model Name
Power Supply Ø, #, V, Hz
Mode -
Performance
HP HP
Capacity
(Nominal)
Cooling
kW
Btu/h
Heating
kW
Btu/h
Power
Power Input
(Nominal)
Cooling 1) kW
Heating 2) kW
Current
Input
(Nominal)
Cooling 1) A
Heating 2) A
MCA A
MFA A
COP
EER (Nominal Cooling) -
COP (Nominal Heating) -
Energy Grade
-
-
Compressor
Type -
Output kW x n
Model Name -
Oil Type -
Fan
Type -
Output x n W
Air Flow Rate
CMM
l/s
External
Static
Max.
mmAQ
Pa
Piping
Connections
Liquid Pipe
Ø, mm
Ø, inch
Gas Pipe
Ø, mm
Ø, inch
Discharge Gas Pipe
Ø, mm
Ø, inch
Installation
Limitation
Max. Length m
Max. Height m
Field Wiring
Power Source Wire mm²
Transmission Cable mm²
Refrigerant
Type -
Factory Charging kg
Sound
Pressure
dBA
Power
External
Dimension
New Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions
(WxHxD)
mm
Operating
Temp.
Cooling ºC
Heating ºC
DVM S(NEW) DVM S(NEW) DVM S(NEW)
AM560KXVAGH/TK AM580KXVAGH/TK AM600KXVAGH/TK
3,4,380-415,50 3,4,380-415,50 3,4,380-415,50
HP HP HP
56.00 58.00 60.00
156.80 162.60 168.00
535,000 554,800 573,200
176.40 182.70 189.00
601,900 623,400 644,900
41.61 43.39 45.41
38.59 40.77 41.18
66.70 69.60 72.80
61.90 65.40 66.00
133.00 140.00 146.00
150.00 200.00 200.00
3.77 3.75 3.70
4.57 4.48 4.59
- - -
- - -
SSC Scroll x 4 SSC Scroll x 4 SSC Scroll x 4
(6.39x2) + (7.81x2) (6.76x2) + (7.81x2) (7.81x2)x2
DS-GB066FAVBx2 +
DS4GJ5080FVAx2
DS-GB070FAVAx2 +
DS4GJ5080FVAx2
DS4GJ5080FVAx4
PVE PVE PVE
Propeller Propeller Propeller
(620.0x2)x2 (620.0x2)x2 (620.0x2)x2
340.0x2 340.0x2 340.0x2
5,666.7x2 5,666.7x2 5,666.7x2
8.00 8.00 8.00
78.40 78.40 78.40
19.05 19.05 19.05
3/4" 3/4" 3/4"
41.28 41.28 41.28
1 5/8" 1 5/8" 1 5/8"
- - -
- - -
200 (220) 200 (220) 200 (220)
110 (40) 110 (40) 110 (40)
- - -
0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50
R410A R410A R410A
26.50 28.00 28.00
- - -
- - -
333.0 + 350.0 342.0 + 350.0 350.0x2
355.0 + 372.0 364.0 + 372.0 372.0x2
(1,295x1,795x765)x2 (1,295x1,795x765)x2 (1,295x1,795x765)x2
(1,363x1,987x832)x2 (1,363x1,987x832)x2 (1,363x1,987x832)x2
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
-25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0
* Specifications may be subject to change without prior notice.
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit
2
Specifications
Outdoor
Type
Model Name
Power Supply Ø, #, V, Hz
Mode -
Performance
HP HP
Capacity
(Nominal)
Cooling
kW
Btu/h
Heating
kW
Btu/h
Power
Power Input
(Nominal)
Cooling 1) kW
Heating 2) kW
Current
Input
(Nominal)
Cooling 1) A
Heating 2) A
MCA A
MFA A
COP
EER (Nominal Cooling) -
COP (Nominal Heating) -
Energy Grade
-
-
Compressor
Type -
Output kW x n
Model Name -
Oil Type -
Fan
Type -
Output x n W
Air Flow Rate
CMM
l/s
External
Static
Max.
mmAQ
Pa
Piping
Connections
Liquid Pipe
Ø, mm
Ø, inch
Gas Pipe
Ø, mm
Ø, inch
Discharge Gas Pipe
Ø, mm
Ø, inch
Installation
Limitation
Max. Length m
Max. Height m
Field Wiring
Power Source Wire mm²
Transmission Cable mm²
Refrigerant
Type -
Factory Charging kg
Sound
Pressure
dBA
Power
External
Dimension
New Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions
(WxHxD)
mm
Operating
Temp.
Cooling ºC
Heating ºC
DVM S(NEW) DVM S(NEW) DVM S(NEW)
AM620KXVAGH/TK AM640KXVAGH/TK AM660KXVAGH/TK
3,4,380-415,50 3,4,380-415,50 3,4,380-415,50
HP HP HP
62.00 64.00 66.00
174.40 179.40 184.80
595,100 612,100 630,600
196.20 201.60 207.90
669,500 687,900 709,400
46.23 47.40 47.90
42.66 44.11 44.41
74.10 76.00 76.80
68.40 70.70 71.20
137.20 144.20 151.40
200.00 200.00 200.00
3.77 3.78 3.86
4.60 4.57 4.68
- - -
- - -
SSC Scroll x 4 SSC Scroll x 4 SSC Scroll x 4
(6.39) + (7.81) + (7.81x2) (7.81) + (7.81) + (7.81x2) (7.81)x2 + (7.81x2)
DS-GB066FAVBx1 +
DS4GJ5080FVAx3
DS4GJ5080FVAx4 DS4GJ5080FVAx4
PVE PVE PVE
Propeller Propeller Propeller
(620.0x2)x3 (620.0x2)x3 (620.0x2)x3
255.0 + 290.0 + 340.0 255.0 + 290.0 + 340.0 290.0x2 + 340.0
4,250.0 + 4,833.3 + 5,666.7 4,250.0 + 4,833.3 + 5,666.7 4,833.3x2 + 5,666.7
8.00 8.00 8.00
78.40 78.40 78.40
22.22 22.22 22.22
7/8" 7/8" 7/8"
53.98 53.98 53.98
2 1/8" 2 1/8" 2 1/8"
- - -
- - -
200 (220) 200 (220) 200 (220)
110 (40) 110 (40) 110 (40)
- - -
0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50
R410A R410A R410A
30.10 30.80 30.80
- - -
- - -
226.0 + 255.0 + 350.0 253.0 + 255.0 + 350.0 255.0x2 + 350.0
246.0 + 275.0 + 372.0 273.0 + 275.0 + 372.0 275.0x2 + 372.0
(1,295x1,695x765)x2 +
1,295x1,795x765
(1,295x1,695x765)x2 +
1,295x1,795x765
(1,295x1,695x765)x2 +
1,295x1,795x765
(1,363x1,887x832)x2 +
1,363x1,987x832
(1,363x1,887x832)x2 +
1,363x1,987x832
(1,363x1,887x832)x2 +
1,363x1,987x832
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
-25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0
* Specifications may be subject to change without prior notice.
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit
2
Specifications
Outdoor
Type
Model Name
Power Supply Ø, #, V, Hz
Mode -
Performance
HP HP
Capacity
(Nominal)
Cooling
kW
Btu/h
Heating
kW
Btu/h
Power
Power Input
(Nominal)
Cooling 1) kW
Heating 2) kW
Current
Input
(Nominal)
Cooling 1) A
Heating 2) A
MCA A
MFA A
COP
EER (Nominal Cooling) -
COP (Nominal Heating) -
Energy Grade
-
-
Compressor
Type -
Output kW x n
Model Name -
Oil Type -
Fan
Type -
Output x n W
Air Flow Rate
CMM
l/s
External
Static
Max.
mmAQ
Pa
Piping
Connections
Liquid Pipe
Ø, mm
Ø, inch
Gas Pipe
Ø, mm
Ø, inch
Discharge Gas Pipe
Ø, mm
Ø, inch
Installation
Limitation
Max. Length m
Max. Height m
Field Wiring
Power Source Wire mm²
Transmission Cable mm²
Refrigerant
Type -
Factory Charging kg
Sound
Pressure
dBA
Power
External
Dimension
New Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions
(WxHxD)
mm
Operating
Temp.
Cooling ºC
Heating ºC
DVM S(NEW) DVM S(NEW) DVM S(NEW)
AM680KXVAGH/TK AM700KXVAGH/TK AM720KXVAGH/TK
3,4,380-415,50 3,4,380-415,50 3,4,380-415,50
HP HP HP
68.00 70.00 72.00
190.40 196.00 201.60
649,700 668,800 687,900
214.20 220.50 226.80
730,900 752,400 773,900
49.48 52.65 54.23
46.41 49.20 51.19
79.30 84.40 86.90
74.40 78.90 82.10
154.20 156.80 159.60
200.00 200.00 200.00
3.85 3.72 3.72
4.62 4.48 4.43
- - -
- - -
SSC Scroll x 5 SSC Scroll x 5 SSC Scroll x 6
(7.81) + (5.18x2) + (7.81x2) (7.81) + (6.39x2) + (7.81x2) (5.18x2) + (6.39x2) + (7.81x2)
DS4GJ5080FVAx3 + DS-
GB052FAVBx2
DS4GJ5080FVAx3 + DS-
GB066FAVBx2
DS-GB052FAVBx2 + DS-
GB066FAVBx2 +
DS4GJ5080FVAx2
PVE PVE PVE
Propeller Propeller Propeller
(620.0x2)x3 (620.0x2)x3 (620.0x2)x3
290.0x2 + 340.0 290.0x2 + 340.0 290.0x2 + 340.0
4,833.3x2 + 5,666.7 4,833.3x2 + 5,666.7 4,833.3x2 + 5,666.7
8.00 8.00 8.00
78.40 78.40 78.40
22.22 22.22 22.22
7/8" 7/8" 7/8"
53.98 53.98 53.98
2 1/8" 2 1/8" 2 1/8"
- - -
- - -
200 (220) 200 (220) 200 (220)
110 (40) 110 (40) 110 (40)
- - -
0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50
R410A R410A R410A
30.80 30.80 30.80
- - -
- - -
255.0 + 277.0 + 350.0 255.0 + 285.0 + 350.0 277.0 + 285.0 + 350.0
275.0 + 297.0 + 372.0 275.0 + 305.0 + 372.0 297.0 + 305.0 + 372.0
(1,295x1,695x765)x2 +
1,295x1,795x765
(1,295x1,695x765)x2 +
1,295x1,795x765
(1,295x1,695x765)x2 +
1,295x1,795x765
(1,363x1,887x832)x2 +
1,363x1,987x832
(1,363x1,887x832)x2 +
1,363x1,987x832
(1,363x1,887x832)x2 +
1,363x1,987x832
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
-25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0
* Specifications may be subject to change without prior notice.
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit
2
Specifications
Outdoor
Type
Model Name
Power Supply Ø, #, V, Hz
Mode -
Performance
HP HP
Capacity
(Nominal)
Cooling
kW
Btu/h
Heating
kW
Btu/h
Power
Power Input
(Nominal)
Cooling 1) kW
Heating 2) kW
Current
Input
(Nominal)
Cooling 1) A
Heating 2) A
MCA A
MFA A
COP
EER (Nominal Cooling) -
COP (Nominal Heating) -
Energy Grade
-
-
Compressor
Type -
Output kW x n
Model Name -
Oil Type -
Fan
Type -
Output x n W
Air Flow Rate
CMM
l/s
External
Static
Max.
mmAQ
Pa
Piping
Connections
Liquid Pipe
Ø, mm
Ø, inch
Gas Pipe
Ø, mm
Ø, inch
Discharge Gas Pipe
Ø, mm
Ø, inch
Installation
Limitation
Max. Length m
Max. Height m
Field Wiring
Power Source Wire mm²
Transmission Cable mm²
Refrigerant
Type -
Factory Charging kg
Sound
Pressure
dBA
Power
External
Dimension
New Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions
(WxHxD)
mm
Operating
Temp.
Cooling ºC
Heating ºC
DVM S(NEW) DVM S(NEW) DVM S(NEW)
AM740KXVAGH/TK AM760KXVAGH/TK AM780KXVAGH/TK
3,4,380-415,50 3,4,380-415,50 3,4,380-415,50
HP HP HP
74.00 76.00 78.00
207.20 212.80 218.40
707,000 726,100 745,200
233.10 239.40 245.70
795,400 816,900 838,400
57.41 57.15 58.96
53.99 54.71 55.29
92.00 91.60 94.50
86.60 87.70 88.70
162.20 172.60 177.60
200.00 200.00 200.00
3.61 3.72 3.70
4.32 4.38 4.44
- - -
- - -
SSC Scroll x 6 SSC Scroll x 6 SSC Scroll x 6
(6.39x2)x2 + (7.81x2) (6.39x2) + (6.39x2) + (7.81x2) (6.39x2) + (6.39x2) + (7.81x2)
DS-GB066FAVBx4 +
DS4GJ5080FVAx2
DS-GB066FAVBx4 +
DS4GJ5080FVAx2
DS-GB066FAVBx4 +
DS4GJ5080FVAx2
PVE PVE PVE
Propeller Propeller Propeller
(620.0x2)x3 (620.0x2)x3 (620.0x2)x3
290.0x2 + 340.0 290.0 + 340.0x2 290.0 + 340.0x2
4,833.3x2 + 5,666.7 4,833.3 + 5,666.7x2 4,833.3 + 5,666.7x2
8.00 8.00 8.00
78.40 78.40 78.40
22.22 22.22 22.22
7/8" 7/8" 7/8"
53.98 53.98 53.98
2 1/8" 2 1/8" 2 1/8"
- - -
- - -
200 (220) 200 (220) 200 (220)
110 (40) 110 (40) 110 (40)
- - -
0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50
R410A R410A R410A
30.80 34.90 34.90
- - -
- - -
285.0x2 + 350.0 285.0 + 333.0 + 350.0 285.0 + 333.0 + 350.0
305.0x2 + 372.0 305.0 + 355.0 + 372.0 305.0 + 355.0 + 372.0
(1,295x1,695x765)x2 +
1,295x1,795x765
1,295x1,695x765 +
(1,295x1,795x765)x2
1,295x1,695x765 +
(1,295x1,795x765)x2
(1,363x1,887x832)x2 +
1,363x1,987x832
1,363x1,887x832 +
(1,363x1,987x832)x2
1,363x1,887x832 +
(1,363x1,987x832)x2
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
-25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0
* Specifications may be subject to change without prior notice.
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit
2
Specifications
Outdoor
Type
Model Name
Power Supply Ø, #, V, Hz
Mode -
Performance
HP HP
Capacity
(Nominal)
Cooling
kW
Btu/h
Heating
kW
Btu/h
Power
Power Input
(Nominal)
Cooling 1) kW
Heating 2) kW
Current
Input
(Nominal)
Cooling 1) A
Heating 2) A
MCA A
MFA A
COP
EER (Nominal Cooling) -
COP (Nominal Heating) -
Energy Grade
-
-
Compressor
Type -
Output kW x n
Model Name -
Oil Type -
Fan
Type -
Output x n W
Air Flow Rate
CMM
l/s
External
Static
Max.
mmAQ
Pa
Piping
Connections
Liquid Pipe
Ø, mm
Ø, inch
Gas Pipe
Ø, mm
Ø, inch
Discharge Gas Pipe
Ø, mm
Ø, inch
Installation
Limitation
Max. Length m
Max. Height m
Field Wiring
Power Source Wire mm²
Transmission Cable mm²
Refrigerant
Type -
Factory Charging kg
Sound
Pressure
dBA
Power
External
Dimension
New Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions
(WxHxD)
mm
Operating
Temp.
Cooling ºC
Heating ºC
DVM S(NEW) DVM S(NEW) DVM S(NEW)
AM800KXVAGH/TK AM820KXVAGH/TK AM840KXVAGH/TK
3,4,380-415,50 3,4,380-415,50 3,4,380-415,50
HP HP HP
80.00 82.00 84.00
224.20 229.60 235.20
765,000 783,400 802,500
252.00 258.30 264.60
859,900 881,400 902,900
60.74 62.76 62.50
57.47 57.88 58.60
97.40 100.60 100.20
92.20 92.80 93.90
184.60 190.60 201.00
250.00 250.00 250.00
3.69 3.66 3.76
4.38 4.46 4.52
- - -
- - -
SSC Scroll x 6 SSC Scroll x 6 SSC Scroll x 6
(6.39x2) + (6.76x2) + (7.81x2) (6.39x2) + (7.81x2)x2 (6.39x2) + (7.81x2)x2
DS-GB066FAVBx2 + DS-
GB070FAVAx2 +
DS4GJ5080FVAx2
DS-GB066FAVBx2 +
DS4GJ5080FVAx4
DS-GB066FAVBx2 +
DS4GJ5080FVAx4
PVE PVE PVE
Propeller Propeller Propeller
(620.0x2)x3 (620.0x2)x3 (620.0x2)x3
290.0 + 340.0x2 290.0 + 340.0x2 340.0x3
4,833.3 + 5,666.7x2 4,833.3 + 5,666.7x2 5,666.7x3
8.00 8.00 8.00
78.40 78.40 78.40
22.22 22.22 22.22
7/8" 7/8" 7/8"
53.98 53.98 53.98
2 1/8" 2 1/8" 2 1/8"
- - -
- - -
200 (220) 200 (220) 200 (220)
110 (40) 110 (40) 110 (40)
- - -
0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50
R410A R410A R410A
36.40 36.40 40.50
- - -
- - -
285.0 + 342.0 + 350.0 285.0 + 350.0x2 333.0 + 350.0x2
305.0 + 364.0 + 372.0 305.0 + 372.0x2 355.0 + 372.0x2
1,295x1,695x765 +
(1,295x1,795x765)x2
1,295x1,695x765 +
(1,295x1,795x765)x2
(1,295x1,795x765)x3
1,363x1,887x832 +
(1,363x1,987x832)x2
1,363x1,887x832 +
(1,363x1,987x832)x2
(1,363x1,987x832)x3
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
-25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0
* Specifications may be subject to change without prior notice.
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit
2
Specifications
Outdoor
Type
Model Name
Power Supply Ø, #, V, Hz
Mode -
Performance
HP HP
Capacity
(Nominal)
Cooling
kW
Btu/h
Heating
kW
Btu/h
Power
Power Input
(Nominal)
Cooling 1) kW
Heating 2) kW
Current
Input
(Nominal)
Cooling 1) A
Heating 2) A
MCA A
MFA A
COP
EER (Nominal Cooling) -
COP (Nominal Heating) -
Energy Grade
-
-
Compressor
Type -
Output kW x n
Model Name -
Oil Type -
Fan
Type -
Output x n W
Air Flow Rate
CMM
l/s
External
Static
Max.
mmAQ
Pa
Piping
Connections
Liquid Pipe
Ø, mm
Ø, inch
Gas Pipe
Ø, mm
Ø, inch
Discharge Gas Pipe
Ø, mm
Ø, inch
Installation
Limitation
Max. Length m
Max. Height m
Field Wiring
Power Source Wire mm²
Transmission Cable mm²
Refrigerant
Type -
Factory Charging kg
Sound
Pressure
dBA
Power
External
Dimension
New Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions
(WxHxD)
mm
Operating
Temp.
Cooling ºC
Heating ºC
DVM S(NEW) DVM S(NEW) DVM S(NEW)
AM860KXVAGH/TK AM880KXVAGH/TK AM900KXVAGH/TK
3,4,380-415,50 3,4,380-415,50 3,4,380-415,50
HP HP HP
86.00 88.00 90.00
240.80 246.60 252.00
821,600 841,400 859,900
270.90 277.20 283.50
924,300 945,800 967,300
64.31 66.09 68.11
59.18 61.36 61.76
103.10 106.00 109.20
94.90 98.40 99.00
206.00 213.00 219.00
250.00 250.00 250.00
3.74 3.73 3.70
4.58 4.52 4.59
- - -
- - -
SSC Scroll x 6 SSC Scroll x 6 SSC Scroll x 6
(6.39x2) + (7.81x2)x2 (6.76x2) + (7.81x2)x2 (7.81x2)x3
DS-GB066FAVBx2 +
DS4GJ5080FVAx4
DS-GB070FAVAx2 +
DS4GJ5080FVAx4
DS4GJ5080FVAx6
PVE PVE PVE
Propeller Propeller Propeller
(620.0x2)x3 (620.0x2)x3 (620.0x2)x3
340.0x3 340.0x3 340.0x3
5,666.7x3 5,666.7x3 5,666.7x3
8.00 8.00 8.00
78.40 78.40 78.40
22.22 22.22 22.22
7/8" 7/8" 7/8"
53.98 53.98 53.98
2 1/8" 2 1/8" 2 1/8"
- - -
- - -
200 (220) 200 (220) 200 (220)
110 (40) 110 (40) 110 (40)
- - -
0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50
R410A R410A R410A
40.50 42.00 42.00
- - -
- - -
333.0 + 350.0x2 342.0 + 350.0x2 350.0x3
355.0 + 372.0x2 364.0 + 372.0x2 372.0x3
(1,295x1,795x765)x3 (1,295x1,795x765)x3 (1,295x1,795x765)x3
(1,363x1,987x832)x3 (1,363x1,987x832)x3 (1,363x1,987x832)x3
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
-25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0
* Specifications may be subject to change without prior notice.
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit
2
Operation limit
Outdoortemperature(℃DB)
10 14 20 25 27 30
50
40
30
20
10
-10
-20
-5
-15
-30
0
Continuous
Operation Range
“Expand operational
temperature range” Option
Indoor temperature(℃ WB)
Outdoortemperature(℃WB)
Indoor temperature(℃ DB)
10 15 20 25 27 30
30
20
24
10
-10
-20
-30
0
Continuous
Operation Range
Warming
Up
Operation
Range
℃
Cooling Heating
Defrosting correction factor
On heating operation, frost can be formed on heat exchanger according to outdoor temperature.
(Frost on heat exchanger results in decreasing the performance.)
To remove frost on heat exchanger of outdoor unit, defrost operation is carried out periodically.
During defrost operation, capacity of outdoor unit may decrease.
The decrement is not considered to the individual capacity tables.
3
Dimensional drawing
Outdoor
AM140KXVAGH/TK, AM160KXVAGH/TK, AM180KXVAGH/TK, AM200KXVAGH/TK, AM220KXVAGH/TK
Units : mm / inches
Table of descriptions
1 Gas Ref. pipe 7 Knock-out Hole for Ref. Piping
2 Liquid Ref. pipe 8 Anchor Bolt Hole
3 Power wiring conduit 9
4 Communication wiring conduit 10
5 Power wiring conduit 11
6 Communication wiring conduit 12
1295
[4'-3"]
765
[2'-6"]
616
[2'-01/4"]
671
[2'-21/2"]
241
[91/2"]
122
[4 3/4"]
51
[2"]
1695
[5'-63/4"]
36
[1 1/2"]
557
[1'-10"]
492
[1'-71/2"]172
[63/4"]
107
[4 1/4"]
575
[1'-10 3/4"]
761
[2'-6"]
1295
[4'-3"]
803
[2'-73/4"]
① ② ③④
⑤
⑥
⑤
⑥
③
⑧
4
Dimensional drawing
Outdoor
AM240KXVAGH/TK, AM260KXVAGH/TK, AM280KXVAGH/TK, AM300KXVAGH/TK
4
Electrical wiring diagram
Outdoor
AM140KXVAGH/TK, AM200KXVAGH/TK, AM220KXVAGH/TK
5
Electrical wiring diagram
Outdoor
AM160KXVAGH/TK, AM180KXVAGH/TK, AM240KXVAGH/TK, AM260KXVAGH/TK, AM280KXVAGH/TK, AM300KXVAGH/TK
5
Sound pressure level
Outdoor
Note
* Specifications may be subject to change without prior notice
1) These operation values were obtained in an anechoic room.
2) Sound pressure level will vary depending on a range of factors such as the construction of the particular room
3) Operation sound level may differ depending on operation and ambient conditions.
NC curve
Unit: dB(A)
Model Cooling
AM140KXVAGH/TK 61
AM160KXVAGH/TK 63
AM180KXVAGH/TK 64
AM200KXVAGH/TK 65
NC 65
NC 60
NC 55
NC 50
NC 45
NC 40
NC 35
NC 30
NC 25
NC 20
NC 15
Cooling
63 125 250 500 1000 2000 4000 8000
Octave band center frequency(Hz)
10
20
30
40
50
60
70
80
Soundpressurelevel(dB)
1) AM140KXVAGH/TK
NC 65
NC 60
NC 55
NC 50
NC 45
NC 40
NC 35
NC 30
NC 25
NC 20
NC 15
Cooling
63 125 250 500 1000 2000 4000 8000
Octave band center frequency(Hz)
10
20
30
40
50
60
70
80
Soundpressurelevel(dB)
2) AM160KXVAGH/TK
NC 65
NC 60
NC 55
NC 50
NC 45
NC 40
NC 35
NC 30
NC 25
NC 20
NC 15
Cooling
63 125 250 500 1000 2000 4000 8000
Octave band center frequency(Hz)
10
20
30
40
50
60
70
80
Soundpressurelevel(dB)
3) AM180KXVAGH/TK
NC 65
NC 60
NC 55
NC 50
NC 45
NC 40
NC 35
NC 30
NC 25
NC 20
NC 15
Cooling
63 125 250 500 1000 2000 4000 8000
Octave band center frequency(Hz)
10
20
30
40
50
60
70
80
Soundpressurelevel(dB)
4) AM200KXVAGH/TK
6
Sound pressure level
Outdoor
Note
* Specifications may be subject to change without prior notice
1) These operation values were obtained in an anechoic room.
2) Sound pressure level will vary depending on a range of factors such as the construction of the particular room
3) Operation sound level may differ depending on operation and ambient conditions.
NC curve
Unit: dB(A)
Model Cooling
AM220KXVAGH/TK 65
AM240KXVAGH/TK 66
AM260KXVAGH/TK 66
AM280KXVAGH/TK 69
NC 65
NC 60
NC 55
NC 50
NC 45
NC 40
NC 35
NC 30
NC 25
NC 20
NC 15
Cooling
63 125 250 500 1000 2000 4000 8000
Octave band center frequency(Hz)
10
20
30
40
50
60
70
80
Soundpressurelevel(dB)
1) AM220KXVAGH/TK
NC 65
NC 60
NC 55
NC 50
NC 45
NC 40
NC 35
NC 30
NC 25
NC 20
NC 15
Cooling
63 125 250 500 1000 2000 4000 8000
Octave band center frequency(Hz)
10
20
30
40
50
60
70
80
Soundpressurelevel(dB)
2) AM240KXVAGH/TK
NC 65
NC 60
NC 55
NC 50
NC 45
NC 40
NC 35
NC 30
NC 25
NC 20
NC 15
Cooling
63 125 250 500 1000 2000 4000 8000
Octave band center frequency(Hz)
10
20
30
40
50
60
70
80
Soundpressurelevel(dB)
3) AM260KXVAGH/TK
NC 65
NC 60
NC 55
NC 50
NC 45
NC 40
NC 35
NC 30
NC 25
NC 20
NC 15
Cooling
63 125 250 500 1000 2000 4000 8000
Octave band center frequency(Hz)
10
20
30
40
50
60
70
80
Soundpressurelevel(dB)
4) AM280KXVAGH/TK
6
Sound pressure level
Outdoor
Note
* Specifications may be subject to change without prior notice
1) These operation values were obtained in an anechoic room.
2) Sound pressure level will vary depending on a range of factors such as the construction of the particular room
3) Operation sound level may differ depending on operation and ambient conditions.
NC curve
Unit: dB(A)
Model Cooling
AM300KXVAGH/TK 69
NC 65
NC 60
NC 55
NC 50
NC 45
NC 40
NC 35
NC 30
NC 25
NC 20
NC 15
Cooling
63 125 250 500 1000 2000 4000 8000
Octave band center frequency(Hz)
10
20
30
40
50
60
70
80
Soundpressurelevel(dB)
1) AM300KXVAGH/TK
6
Sound power level
Outdoor
Note
125 250 500 1000 2000 4000 8000 A
Octave band center frequency(Hz)
0
10
20
30
40
50
60
70
80
90
100
Soundpowerlevel(dB)
1)AM140KXVAGH/TK
125 250 500 1000 2000 4000 8000 A
Octave band center frequency(Hz)
0
10
20
30
40
50
60
70
80
90
100
Soundpowerlevel(dB)
2)AM160KXVAGH/TK
125 250 500 1000 2000 4000 8000 A
Octave band center frequency(Hz)
0
10
20
30
40
50
60
70
80
90
100
Soundpowerlevel(dB)
3)AM180KXVAGH/TK
125 250 500 1000 2000 4000 8000 A
Octave band center frequency(Hz)
0
10
20
30
40
50
60
70
80
90
100
Soundpowerlevel(dB)
4)AM200KXVAGH/TK
Unit: dB(A)
Model Power
AM140KXVAGH/TK 81
AM160KXVAGH/TK 83
AM180KXVAGH/TK 84
AM200KXVAGH/TK 87
* Specifications may be subject to change
1) dBA = A-weighted sound power level.
2) Reference power : 1pW.
3) Measured according to ISO 3741.
7
Sound power level
Outdoor
Note
125 250 500 1000 2000 4000 8000 A
Octave band center frequency(Hz)
0
10
20
30
40
50
60
70
80
90
100
Soundpowerlevel(dB)
1)AM220KXVAGH/TK
125 250 500 1000 2000 4000 8000 A
Octave band center frequency(Hz)
0
10
20
30
40
50
60
70
80
90
100
Soundpowerlevel(dB)
2)AM240KXVAGH/TK
125 250 500 1000 2000 4000 8000 A
Octave band center frequency(Hz)
0
10
20
30
40
50
60
70
80
90
100
Soundpowerlevel(dB)
3)AM260KXVAGH/TK
125 250 500 1000 2000 4000 8000 A
Octave band center frequency(Hz)
0
10
20
30
40
50
60
70
80
90
100
Soundpowerlevel(dB)
4)AM280KXVAGH/TK
Unit: dB(A)
Model Power
AM220KXVAGH/TK 89
AM240KXVAGH/TK 89
AM260KXVAGH/TK 89
AM280KXVAGH/TK 90
* Specifications may be subject to change
1) dBA = A-weighted sound power level.
2) Reference power : 1pW.
3) Measured according to ISO 3741.
7
Sound power level
Outdoor
Note
125 250 500 1000 2000 4000 8000 A
Octave band center frequency(Hz)
0
10
20
30
40
50
60
70
80
90
100
Soundpowerlevel(dB)
1)AM300KXVAGH/TK
Unit: dB(A)
Model Power
AM300KXVAGH/TK 90
* Specifications may be subject to change
1) dBA = A-weighted sound power level.
2) Reference power : 1pW.
3) Measured according to ISO 3741.
7
Cycle diagram
Outdoor
AM140KXVAGH/TK, AM160KXVAGH/TK, AM180KXVAGH/TK
Abbreviation Explanation Abbreviation Explanation
INV Inveter Compressor V_AR Accumulator Oil Return Valve
OFM Outdoor Fan Motor CV_E EEV Bypass Check Valve
OHX Outdoor Heat Exchanger CV_D Discharge Check Valve
AC Accumulator T_D Discharge Temp. Sensor
OS Oil Separator T_S Suction Temp. Sensor
IC Intercooler T_CO Cond Out Temp. Sensor
IPMC IPM Cooler T_EI EVI In Temp. Sensor
HPS High Pressure Sensor T_EO EVI Out Temp. Sensor
LPS Low Pressure Sensor T_L Liquid Tube Temp. Sensor
HPSW High Pressure Switch T_CT Comp. Top Temp. Sensor
E_M Main EEV T_A Ambient Temp. Sensor
E_EV EVI EEV SV_G Gas Pipe Service Valve
V_ES EVI Sol. Valve SV_L Liquid Pipe Service Valve
V_EB EVI Bypass Valve
V_HG Hot Gas Bypass Valve
V_4W 4Way Valve
s
E
s
E
s
INV
OFM
OHX
AC
OS
IC
HPS
HPSW
E_M
E_EV
V_EB
V_HG
V_4W
V_AR
CV_E
CV_D
T_D
T_CO
T_EI
T_EO
T_L
T_CT
T_A
V_ES
SV_G
SV_L
IPMC
LPS
T_S
8
Cycle diagram
Outdoor
AM200KXVAGH/TK, AM220KXVAGH/TK
Abbreviation Explanation Abbreviation Explanation
INV1 Inveter Compressor V_4W 4Way Valve
INV2 Inveter Compressor V_AR Accumulator Oil Return Valve
OFM Outdoor Fan Motor CV_E EEV Bypass Check Valve
OHX Outdoor Heat Exchanger CV_D Discharge Check Valve
AC Accumulator T_D Discharge Temp. Sensor
OS Oil Separator T_S Suction Temp. Sensor
IC Intercooler T_CO Cond Out Temp. Sensor
IPMC IPM Cooler T_EI EVI In Temp. Sensor
HPS High Pressure Sensor T_EO EVI Out Temp. Sensor
LPS Low Pressure Sensor T_L Liquid Tube Temp. Sensor
HPSW High Pressure Switch T_CT Comp. Top Temp. Sensor
E_M Main EEV T_A Ambient Temp. Sensor
E_EV EVI EEV SV_G Gas Pipe Service Valve
V_ES EVI Sol. Valve SV_L Liquid Pipe Service Valve
V_EB EVI Bypass Valve
V_HG Hot Gas Bypass Valve
E
s
E
s
INV
OFM
OHX
AC
OS IC
HPS
HPSW
E_M
E_EV
V_ES
V_EB
V_HG
V_4W
CV_E
CV_D
T_D
T_CO
T_EI
T_EO
T_L
T_CT
T_A
INV
V_ES
CV_D
T_D
T_CT
OSHPSW
SV_G
SV_L
IPMC IPMC
s
V_AR1
LPS
T_S
8
Cycle diagram
Outdoor
AM240KXVAGH/TK, AM260KXVAGH/TK
Abbreviation Explanation Abbreviation Explanation
INV1 Inveter Compressor V_4W 4Way Valve
INV2 Inveter Compressor V_AR Accumulator Oil Return Valve
OFM Outdoor Fan Motor CV_E EEV Bypass Check Valve
OHX Outdoor Heat Exchanger CV_D Discharge Check Valve
AC Accumulator T_D Discharge Temp. Sensor
OS Oil Separator T_S Suction Temp. Sensor
IC Intercooler T_CO Cond Out Temp. Sensor
IPMC IPM Cooler T_EI EVI In Temp. Sensor
HPS High Pressure Sensor T_EO EVI Out Temp. Sensor
LPS Low Pressure Sensor T_L Liquid Tube Temp. Sensor
HPSW High Pressure Switch T_CT Comp. Top Temp. Sensor
E_M Main EEV T_A Ambient Temp. Sensor
E_EV EVI EEV SV_G Gas Pipe Service Valve
V_ES EVI Sol. Valve SV_L Liquid Pipe Service Valve
V_EB EVI Bypass Valve
V_HG Hot Gas Bypass Valve
s
E
s
INV1
OFM
OHX
AC
IC
HPS
HPSW1
E_EV
V_ES
V_EB
V_HG
V_4W
T_D1
T_S
T_EI
T_EO
T_L
T_CT1
T_A
V_ES
T_D2
T_CT2
HPSW2
SV_G
SV_L
IPMC1 IPMC2
E_M1
E_M2
LPS
V_AR1
CVD1 CVD2
CV_E1
T_CO
s
T_CI
E
E
CV_E2
OS2OS1
INV2
8
Cycle diagram
Outdoor
AM280KXVAGH/TK, AM300KXVAGH/TK
Abbreviation Explanation Abbreviation Explanation
INV1 Inveter Compressor V_4W 4Way Valve
INV2 Inveter Compressor V_AR Accumulator Oil Return Valve
OFM Outdoor Fan Motor CV_E EEV Bypass Check Valve
OHX Outdoor Heat Exchanger CV_D Discharge Check Valve
AC Accumulator T_D Discharge Temp. Sensor
OS Oil Separator T_S Suction Temp. Sensor
IC Intercooler T_CO Cond Out Temp. Sensor
IPMC IPM Cooler T_EI EVI In Temp. Sensor
HPS High Pressure Sensor T_EO EVI Out Temp. Sensor
LPS Low Pressure Sensor T_L Liquid Tube Temp. Sensor
HPSW High Pressure Switch T_CT Comp. Top Temp. Sensor
E_M Main EEV T_A Ambient Temp. Sensor
E_EV EVI EEV SV_G Gas Pipe Service Valve
V_ES EVI Sol. Valve SV_L Liquid Pipe Service Valve
V_EB EVI Bypass Valve
V_HG Hot Gas Bypass Valve
RE
3.0L
s
E
s
INV1
OFM
OHX
AC
IC
HPS
HPSW1
E_EV
V_ES
V_EB
V_HG
V_4W
T_D1
T_S
T_EI
T_EO
T_L
T_CT1
T_A
V_ES
T_D2
T_CT2
HPSW2
SV_G
SV_L
IPMC1 IPMC2
E_M1
E_M2
LPS
V_AR1
CVD1 CVD2
CV_E1
T_CO
s
T_CI
E
E
CV_E2
OS2OS1
INV2
8
2016.01
Ver.1.0
Samsung Electronics Co., LTD.
B2B PM / SE
Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 443-742
Website : www.samsung.com Email : airconditioner@samsung.com
Images and data in this book may subject to change without prior notice.

Contenu connexe

En vedette

Samsung sac category catalogue cac tr
Samsung sac category catalogue cac trSamsung sac category catalogue cac tr
Samsung sac category catalogue cac trHaluk TOSUN
 
Samsung sac category catalogue multi fjm tr
Samsung sac category catalogue multi fjm trSamsung sac category catalogue multi fjm tr
Samsung sac category catalogue multi fjm trHaluk TOSUN
 
Презентация компании ADE Project.
Презентация компании ADE Project.Презентация компании ADE Project.
Презентация компании ADE Project.Alexander Vasilyev
 
Samsung cac salesguide_eng
Samsung cac salesguide_engSamsung cac salesguide_eng
Samsung cac salesguide_engHaluk TOSUN
 
Dvm hydro sales Presentation
Dvm hydro sales PresentationDvm hydro sales Presentation
Dvm hydro sales PresentationHaluk TOSUN
 
Samsung dvm s catalogue [60 hz.]
Samsung dvm s catalogue [60 hz.]Samsung dvm s catalogue [60 hz.]
Samsung dvm s catalogue [60 hz.]Haluk TOSUN
 
Samsung 2012 vrf [plus iv] catalog
Samsung 2012 vrf [plus iv] catalogSamsung 2012 vrf [plus iv] catalog
Samsung 2012 vrf [plus iv] catalogHaluk TOSUN
 
Samsung tdb-dvm-s-water e-outdoor_dbeu-13082_da1
Samsung tdb-dvm-s-water e-outdoor_dbeu-13082_da1Samsung tdb-dvm-s-water e-outdoor_dbeu-13082_da1
Samsung tdb-dvm-s-water e-outdoor_dbeu-13082_da1Haluk TOSUN
 
Samsung sac global reference catalogue
Samsung sac global reference catalogueSamsung sac global reference catalogue
Samsung sac global reference catalogueHaluk TOSUN
 
GADGET STUDIO sponsorship presentation
GADGET STUDIO sponsorship presentationGADGET STUDIO sponsorship presentation
GADGET STUDIO sponsorship presentationNickolay Turubar
 
Samsung 2009 dvm [plus III] catalogue
Samsung 2009 dvm [plus III] catalogueSamsung 2009 dvm [plus III] catalogue
Samsung 2009 dvm [plus III] catalogueHaluk TOSUN
 
Samsung Twin rotary compressor R-410A / R-22
Samsung Twin rotary compressor R-410A / R-22Samsung Twin rotary compressor R-410A / R-22
Samsung Twin rotary compressor R-410A / R-22Haluk TOSUN
 

En vedette (15)

Samsung sac category catalogue cac tr
Samsung sac category catalogue cac trSamsung sac category catalogue cac tr
Samsung sac category catalogue cac tr
 
Boreas Boya
Boreas Boya Boreas Boya
Boreas Boya
 
Samsung sac category catalogue multi fjm tr
Samsung sac category catalogue multi fjm trSamsung sac category catalogue multi fjm tr
Samsung sac category catalogue multi fjm tr
 
Презентация компании ADE Project.
Презентация компании ADE Project.Презентация компании ADE Project.
Презентация компании ADE Project.
 
Samsung cac salesguide_eng
Samsung cac salesguide_engSamsung cac salesguide_eng
Samsung cac salesguide_eng
 
Boreas AHU [EN]
Boreas AHU [EN]Boreas AHU [EN]
Boreas AHU [EN]
 
Dvm hydro sales Presentation
Dvm hydro sales PresentationDvm hydro sales Presentation
Dvm hydro sales Presentation
 
Boreas AHU [TR]
Boreas AHU [TR]Boreas AHU [TR]
Boreas AHU [TR]
 
Samsung dvm s catalogue [60 hz.]
Samsung dvm s catalogue [60 hz.]Samsung dvm s catalogue [60 hz.]
Samsung dvm s catalogue [60 hz.]
 
Samsung 2012 vrf [plus iv] catalog
Samsung 2012 vrf [plus iv] catalogSamsung 2012 vrf [plus iv] catalog
Samsung 2012 vrf [plus iv] catalog
 
Samsung tdb-dvm-s-water e-outdoor_dbeu-13082_da1
Samsung tdb-dvm-s-water e-outdoor_dbeu-13082_da1Samsung tdb-dvm-s-water e-outdoor_dbeu-13082_da1
Samsung tdb-dvm-s-water e-outdoor_dbeu-13082_da1
 
Samsung sac global reference catalogue
Samsung sac global reference catalogueSamsung sac global reference catalogue
Samsung sac global reference catalogue
 
GADGET STUDIO sponsorship presentation
GADGET STUDIO sponsorship presentationGADGET STUDIO sponsorship presentation
GADGET STUDIO sponsorship presentation
 
Samsung 2009 dvm [plus III] catalogue
Samsung 2009 dvm [plus III] catalogueSamsung 2009 dvm [plus III] catalogue
Samsung 2009 dvm [plus III] catalogue
 
Samsung Twin rotary compressor R-410A / R-22
Samsung Twin rotary compressor R-410A / R-22Samsung Twin rotary compressor R-410A / R-22
Samsung Twin rotary compressor R-410A / R-22
 

Similaire à Tdb vrf dvm s standard for turkey (odu 50 hz hp) ver.1.0

Ap 23 7900 001 (package air conditioning units) 2011 1206
Ap 23 7900 001 (package air conditioning units) 2011 1206Ap 23 7900 001 (package air conditioning units) 2011 1206
Ap 23 7900 001 (package air conditioning units) 2011 1206Dr. Haider alsenisal
 
T12 0636-e s16 r-y2ptaw2-1 std 60hz
T12 0636-e s16 r-y2ptaw2-1 std 60hzT12 0636-e s16 r-y2ptaw2-1 std 60hz
T12 0636-e s16 r-y2ptaw2-1 std 60hzJorge Gomez Flores
 
DMP Catalogue
DMP CatalogueDMP Catalogue
DMP CatalogueAdhyKeraf
 
Thermal and airflow modeling methodology for Desktop PC
Thermal and airflow modeling methodology for Desktop PCThermal and airflow modeling methodology for Desktop PC
Thermal and airflow modeling methodology for Desktop PCJeehoon Choi
 
2014 Googol gas generator introduction-googol(1)
2014 Googol gas generator introduction-googol(1)2014 Googol gas generator introduction-googol(1)
2014 Googol gas generator introduction-googol(1)Mike Renko
 
Nrp 0800-1800-hp-t y-un50_00
Nrp 0800-1800-hp-t y-un50_00Nrp 0800-1800-hp-t y-un50_00
Nrp 0800-1800-hp-t y-un50_00Oliverh Kalprit
 
Datasheet SpruceTrigen 95 NG 60Hz
Datasheet SpruceTrigen 95 NG 60HzDatasheet SpruceTrigen 95 NG 60Hz
Datasheet SpruceTrigen 95 NG 60HzSNGE Heat&Power
 
Original PNP Transistors PZT2907A PZT2907 2907 P2F SOT22-3 New On Semiconductor
Original PNP Transistors PZT2907A PZT2907 2907 P2F SOT22-3 New On SemiconductorOriginal PNP Transistors PZT2907A PZT2907 2907 P2F SOT22-3 New On Semiconductor
Original PNP Transistors PZT2907A PZT2907 2907 P2F SOT22-3 New On Semiconductorauthelectroniccom
 
Yanmar 4 LH- DTP ANDREW BOWDEN DUBAI
Yanmar 4 LH- DTP ANDREW BOWDEN DUBAIYanmar 4 LH- DTP ANDREW BOWDEN DUBAI
Yanmar 4 LH- DTP ANDREW BOWDEN DUBAIAndrew Bowden Dubai
 
Brochure gas turbine sgt 300 for power generation
Brochure gas turbine sgt 300 for power generationBrochure gas turbine sgt 300 for power generation
Brochure gas turbine sgt 300 for power generationceshesol71
 

Similaire à Tdb vrf dvm s standard for turkey (odu 50 hz hp) ver.1.0 (20)

Ap 23 7900 001 (package air conditioning units) 2011 1206
Ap 23 7900 001 (package air conditioning units) 2011 1206Ap 23 7900 001 (package air conditioning units) 2011 1206
Ap 23 7900 001 (package air conditioning units) 2011 1206
 
T12 0636-e s16 r-y2ptaw2-1 std 60hz
T12 0636-e s16 r-y2ptaw2-1 std 60hzT12 0636-e s16 r-y2ptaw2-1 std 60hz
T12 0636-e s16 r-y2ptaw2-1 std 60hz
 
DMP Catalogue
DMP CatalogueDMP Catalogue
DMP Catalogue
 
T16K.pdf
T16K.pdfT16K.pdf
T16K.pdf
 
FPI 725P
FPI 725PFPI 725P
FPI 725P
 
Thermal and airflow modeling methodology for Desktop PC
Thermal and airflow modeling methodology for Desktop PCThermal and airflow modeling methodology for Desktop PC
Thermal and airflow modeling methodology for Desktop PC
 
R gz7 v1-databook
R gz7 v1-databookR gz7 v1-databook
R gz7 v1-databook
 
R gz7 v1-databook
R gz7 v1-databookR gz7 v1-databook
R gz7 v1-databook
 
2014 Googol gas generator introduction-googol(1)
2014 Googol gas generator introduction-googol(1)2014 Googol gas generator introduction-googol(1)
2014 Googol gas generator introduction-googol(1)
 
Nrp 0800-1800-hp-t y-un50_00
Nrp 0800-1800-hp-t y-un50_00Nrp 0800-1800-hp-t y-un50_00
Nrp 0800-1800-hp-t y-un50_00
 
D830.pdf
D830.pdfD830.pdf
D830.pdf
 
1800REOZM_8_12b
1800REOZM_8_12b1800REOZM_8_12b
1800REOZM_8_12b
 
Datasheet SpruceTrigen 95 NG 60Hz
Datasheet SpruceTrigen 95 NG 60HzDatasheet SpruceTrigen 95 NG 60Hz
Datasheet SpruceTrigen 95 NG 60Hz
 
Original PNP Transistors PZT2907A PZT2907 2907 P2F SOT22-3 New On Semiconductor
Original PNP Transistors PZT2907A PZT2907 2907 P2F SOT22-3 New On SemiconductorOriginal PNP Transistors PZT2907A PZT2907 2907 P2F SOT22-3 New On Semiconductor
Original PNP Transistors PZT2907A PZT2907 2907 P2F SOT22-3 New On Semiconductor
 
Arc900 v1.1.8en
Arc900 v1.1.8enArc900 v1.1.8en
Arc900 v1.1.8en
 
Yanmar 4 LH- DTP ANDREW BOWDEN DUBAI
Yanmar 4 LH- DTP ANDREW BOWDEN DUBAIYanmar 4 LH- DTP ANDREW BOWDEN DUBAI
Yanmar 4 LH- DTP ANDREW BOWDEN DUBAI
 
Tg section eqpt details
Tg section eqpt detailsTg section eqpt details
Tg section eqpt details
 
ABB Trio
ABB TrioABB Trio
ABB Trio
 
Brochure gas turbine sgt 300 for power generation
Brochure gas turbine sgt 300 for power generationBrochure gas turbine sgt 300 for power generation
Brochure gas turbine sgt 300 for power generation
 
KD1000-F.pdf
KD1000-F.pdfKD1000-F.pdf
KD1000-F.pdf
 

Plus de Haluk TOSUN

Rbm brass katalog
Rbm brass katalogRbm brass katalog
Rbm brass katalogHaluk TOSUN
 
The world's largest 250 construction companies - powerPoint
The world's largest 250 construction companies - powerPointThe world's largest 250 construction companies - powerPoint
The world's largest 250 construction companies - powerPointHaluk TOSUN
 
Samsung ehs catalogue
Samsung ehs catalogueSamsung ehs catalogue
Samsung ehs catalogueHaluk TOSUN
 
samsung vrf dvm s 2013 sac catalouge
samsung vrf dvm s 2013 sac catalougesamsung vrf dvm s 2013 sac catalouge
samsung vrf dvm s 2013 sac catalougeHaluk TOSUN
 
Sac usp-catalog-ver.1
Sac usp-catalog-ver.1Sac usp-catalog-ver.1
Sac usp-catalog-ver.1Haluk TOSUN
 
Samsun fjm salesguide_eng
Samsun fjm salesguide_engSamsun fjm salesguide_eng
Samsun fjm salesguide_engHaluk TOSUN
 
Boreas paketleme
Boreas paketlemeBoreas paketleme
Boreas paketlemeHaluk TOSUN
 
Boreas klima santral
Boreas klima santralBoreas klima santral
Boreas klima santralHaluk TOSUN
 
Eurovent sınıfları yurtiçi
Eurovent sınıfları yurtiçiEurovent sınıfları yurtiçi
Eurovent sınıfları yurtiçiHaluk TOSUN
 
Eurovent sınıfları yurtdısı
Eurovent sınıfları yurtdısıEurovent sınıfları yurtdısı
Eurovent sınıfları yurtdısıHaluk TOSUN
 
Dvm s full catalog
Dvm s full catalogDvm s full catalog
Dvm s full catalogHaluk TOSUN
 

Plus de Haluk TOSUN (14)

Rbm brass katalog
Rbm brass katalogRbm brass katalog
Rbm brass katalog
 
The world's largest 250 construction companies - powerPoint
The world's largest 250 construction companies - powerPointThe world's largest 250 construction companies - powerPoint
The world's largest 250 construction companies - powerPoint
 
Samsung ehs catalogue
Samsung ehs catalogueSamsung ehs catalogue
Samsung ehs catalogue
 
samsung vrf dvm s 2013 sac catalouge
samsung vrf dvm s 2013 sac catalougesamsung vrf dvm s 2013 sac catalouge
samsung vrf dvm s 2013 sac catalouge
 
Sac usp-catalog-ver.1
Sac usp-catalog-ver.1Sac usp-catalog-ver.1
Sac usp-catalog-ver.1
 
Samsun fjm salesguide_eng
Samsun fjm salesguide_engSamsun fjm salesguide_eng
Samsun fjm salesguide_eng
 
Boreas test
Boreas testBoreas test
Boreas test
 
Boreas paketleme
Boreas paketlemeBoreas paketleme
Boreas paketleme
 
Boreas boya
Boreas boya Boreas boya
Boreas boya
 
Boreas klima santral
Boreas klima santralBoreas klima santral
Boreas klima santral
 
Boreas test
Boreas testBoreas test
Boreas test
 
Eurovent sınıfları yurtiçi
Eurovent sınıfları yurtiçiEurovent sınıfları yurtiçi
Eurovent sınıfları yurtiçi
 
Eurovent sınıfları yurtdısı
Eurovent sınıfları yurtdısıEurovent sınıfları yurtdısı
Eurovent sınıfları yurtdısı
 
Dvm s full catalog
Dvm s full catalogDvm s full catalog
Dvm s full catalog
 

Dernier

ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityMorshed Ahmed Rahath
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxJuliansyahHarahap1
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapRishantSharmaFr
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Standamitlee9823
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...soginsider
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptMsecMca
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfRagavanV2
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayEpec Engineered Technologies
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptNANDHAKUMARA10
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086anil_gaur
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 

Dernier (20)

ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 

Tdb vrf dvm s standard for turkey (odu 50 hz hp) ver.1.0

  • 1. VRF Technical Data Book DVM S Standard for Turkey (ODU, 50Hz, HP) Model : AM***KXVAGH/TK
  • 2. History Version Modification Date Remark Ver.1.0 Release DVM S 30HP Standard TDB for Turkey 16.01.12.
  • 3. Nomenclature Outdoor Units Model Names AM (1) 140 (2) K (3) X (4) V (5) A (6) G (7) H (8) EU Buyer (1) Classification AM DVM (2) Capacity x 1/10 HP (3 digits) (3) Version F 2013 H 2014 J 2015 K 2016 (4) Product Type X Outdoor Unit N Indoor Unit (5) Feature1 V Inverter M DVM S Eco (6) Feature2 A Standard + General Temp.+ Module H High EER + Low Temp + Module G High EER + General Temp + Module (7) Rating Voltage E 1Ø, 220~240V, 50Hz G 3Ø, 380~415V, 50Hz (8) Mode H Heat Pump R Heat Recovery
  • 4. Outdoor 1 Line-up 2 Specifications 3 Operation limit 4 Dimensional drawing 5 Electrical wiring diagram 6 Sound pressure level 7 Sound power level 8 Cycle diagram
  • 5. Line-up Outdoor Units System Model Capacity System Model Code Number of Modules Outdoor Unit Selection 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP AM140KXVAG H/TK AM160KXVAG H/TK AM180KXVAG H/TK AM200KXVAG H/TK AM220KXVAG H/TK AM240KXVAG H/TK AM260KXVAG H/TK AM280KXVAG H/TK AM300KXVAG H/TK 14HP AM140KXVAGH/TK 1 16HP AM160KXVAGH/TK 1 18HP AM180KXVAGH/TK 1 20HP AM200KXVAGH/TK 1 22HP AM220KXVAGH/TK 1 24HP AM240KXVAGH/TK 1 26HP AM260KXVAGH/TK 1 28HP AM280KXVAGH/TK 1 30HP AM300KXVAGH/TK 1 32HP AM320KXVAGH/TK 2 34HP AM340KXVAGH/TK 2 36HP AM360KXVAGH/TK 2 38HP AM380KXVAGH/TK 2 40HP AM400KXVAGH/TK 2 42HP AM420KXVAGH/TK 2 44HP AM440KXVAGH/TK 2 46HP AM460KXVAGH/TK 2 48HP AM480KXVAGH/TK 2 50HP AM500KXVAGH/TK 2 52HP AM520KXVAGH/TK 2 54HP AM540KXVAGH/TK 2 56HP AM560KXVAGH/TK 2 58HP AM580KXVAGH/TK 2 60HP AM600KXVAGH/TK 2 62HP AM620KXVAGH/TK 3 64HP AM640KXVAGH/TK 3 66HP AM660KXVAGH/TK 3 68HP AM680KXVAGH/TK 3 70HP AM700KXVAGH/TK 3 72HP AM720KXVAGH/TK 3 74HP AM740KXVAGH/TK 3 76HP AM760KXVAGH/TK 3 78HP AM780KXVAGH/TK 3 80HP AM800KXVAGH/TK 3 82HP AM820KXVAGH/TK 3 84HP AM840KXVAGH/TK 3 86HP AM860KXVAGH/TK 3 88HP AM880KXVAGH/TK 3 90HP AM900KXVAGH/TK 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 2 1 2 1 2 1 2 3 1
  • 6. Specifications Outdoor Type Model Name Power Supply Ø, #, V, Hz Mode - Performance HP HP Capacity (Nominal) Cooling kW Btu/h Heating kW Btu/h Power Power Input (Nominal) Cooling 1) kW Heating 2) kW Current Input (Nominal) Cooling 1) A Heating 2) A MCA A MFA A COP EER (Nominal Cooling) - COP (Nominal Heating) - Energy Grade - - Compressor Type - Output kW x n Model Name - Oil Type - Fan Type - Output x n W Air Flow Rate CMM l/s External Static Max. mmAQ Pa Piping Connections Liquid Pipe Ø, mm Ø, inch Gas Pipe Ø, mm Ø, inch Discharge Gas Pipe Ø, mm Ø, inch Installation Limitation Max. Length m Max. Height m Field Wiring Power Source Wire mm² Transmission Cable mm² Refrigerant Type - Factory Charging kg Sound Pressure dBA Power External Dimension New Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Operating Temp. Cooling ºC Heating ºC DVM S(NEW) DVM S(NEW) DVM S(NEW) AM140KXVAGH/TK AM160KXVAGH/TK AM180KXVAGH/TK 3,4,380-415,50 3,4,380-415,50 3,4,380-415,50 HP HP HP 14.00 16.00 18.00 40.00 45.00 50.40 136,500 153,500 172,000 45.00 50.40 56.70 153,500 172,000 193,500 10.93 12.10 12.60 10.16 11.61 11.91 17.50 19.40 20.20 16.30 18.60 19.10 25.00 32.00 39.20 40.00 40.00 50.00 3.66 3.72 4.00 4.43 4.34 4.76 ESEER 7.02 ESEER 6.81 ESEER 6.61 - - - SSC Scroll x 1 SSC Scroll x 1 SSC Scroll x 1 (6.39) (7.81) (7.81) DS-GB066FAVBx1 DS4GJ5080FVAx1 DS4GJ5080FVAx1 PVE PVE PVE Propeller Propeller Propeller 620.0x2 620.0x2 620.0x2 255 255 290 4,250.00 4,250.00 4,833.33 8.00 8.00 8.00 78.40 78.40 78.40 12.70 12.70 15.88 1/2" 1/2" 5/8" 28.58 28.58 28.58 1 1/8" 1 1/8" 1 1/8" - - - - - - 200 (220) 200 (220) 200 (220) 110 (40) 110 (40) 110 (40) - - - 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 R410A R410A R410A 7.70 8.40 8.40 61 63 64 81 83 84 226.0 253.0 255.0 246.0 273.0 275.0 1,295x1,695x765 1,295x1,695x765 1,295x1,695x765 1,363x1,887x832 1,363x1,887x832 1,363x1,887x832 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0 * Specifications may be subject to change without prior notice. 1) Nominal cooling capacities are based on; - Indoor temperature : 27°C DB, 19°C WB - Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 2) Nominal heating capacities are based on; - Indoor temperature : 20°C DB, 15°C WB - Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. 4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.) *PDM kit: Pressure Drop Modulation kit 2
  • 7. Specifications Outdoor Type Model Name Power Supply Ø, #, V, Hz Mode - Performance HP HP Capacity (Nominal) Cooling kW Btu/h Heating kW Btu/h Power Power Input (Nominal) Cooling 1) kW Heating 2) kW Current Input (Nominal) Cooling 1) A Heating 2) A MCA A MFA A COP EER (Nominal Cooling) - COP (Nominal Heating) - Energy Grade - - Compressor Type - Output kW x n Model Name - Oil Type - Fan Type - Output x n W Air Flow Rate CMM l/s External Static Max. mmAQ Pa Piping Connections Liquid Pipe Ø, mm Ø, inch Gas Pipe Ø, mm Ø, inch Discharge Gas Pipe Ø, mm Ø, inch Installation Limitation Max. Length m Max. Height m Field Wiring Power Source Wire mm² Transmission Cable mm² Refrigerant Type - Factory Charging kg Sound Pressure dBA Power External Dimension New Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Operating Temp. Cooling ºC Heating ºC DVM S(NEW) DVM S(NEW) DVM S(NEW) AM200KXVAGH/TK AM220KXVAGH/TK AM240KXVAGH/TK 3,4,380-415,50 3,4,380-415,50 3,4,380-415,50 HP HP HP 20.00 22.00 24.00 56.00 61.60 67.20 191,100 210,200 229,300 63.00 69.30 75.60 215,000 236,500 258,000 14.18 17.35 17.10 13.91 16.70 17.42 22.70 27.80 27.40 22.30 26.80 27.90 42.00 44.60 55.00 75.00 75.00 75.00 3.95 3.55 3.93 4.53 4.15 4.34 ESEER 6.56 ESEER 6.25 ESEER 7.06 - - - SSC Scroll x 2 SSC Scroll x 2 SSC Scroll x 2 (5.18 x 2) (6.39 x 2) (6.39 x 2) DS-GB052FAVBx2 DS-GB066FAVBx2 DS-GB066FAVBx2 PVE PVE PVE Propeller Propeller Propeller 620.0x2 620.0x2 620.0x2 290 290 340 4,833.33 4,833.33 5,666.67 8.00 8.00 8.00 78.40 78.40 78.40 15.88 15.88 15.88 5/8" 5/8" 5/8" 28.58 28.58 34.92 1 1/8" 1 1/8" 1 3/8" - - - - - - 200 (220) 200 (220) 200 (220) 110 (40) 110 (40) 110 (40) - - - 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 R410A R410A R410A 8.40 8.40 12.50 65 65 66 87 89 89 277.0 285.0 333.0 297.0 305.0 355.0 1,295x1,695x765 1,295x1,695x765 1,295x1,795x765 1,363x1,887x832 1,363x1,887x832 1,363x1,987x832 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0 * Specifications may be subject to change without prior notice. 1) Nominal cooling capacities are based on; - Indoor temperature : 27°C DB, 19°C WB - Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 2) Nominal heating capacities are based on; - Indoor temperature : 20°C DB, 15°C WB - Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. 4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.) *PDM kit: Pressure Drop Modulation kit 2
  • 8. Specifications Outdoor Type Model Name Power Supply Ø, #, V, Hz Mode - Performance HP HP Capacity (Nominal) Cooling kW Btu/h Heating kW Btu/h Power Power Input (Nominal) Cooling 1) kW Heating 2) kW Current Input (Nominal) Cooling 1) A Heating 2) A MCA A MFA A COP EER (Nominal Cooling) - COP (Nominal Heating) - Energy Grade - - Compressor Type - Output kW x n Model Name - Oil Type - Fan Type - Output x n W Air Flow Rate CMM l/s External Static Max. mmAQ Pa Piping Connections Liquid Pipe Ø, mm Ø, inch Gas Pipe Ø, mm Ø, inch Discharge Gas Pipe Ø, mm Ø, inch Installation Limitation Max. Length m Max. Height m Field Wiring Power Source Wire mm² Transmission Cable mm² Refrigerant Type - Factory Charging kg Sound Pressure dBA Power External Dimension New Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Operating Temp. Cooling ºC Heating ºC DVM S(NEW) DVM S(NEW) DVM S(NEW) AM260KXVAGH/TK AM280KXVAGH/TK AM300KXVAGH/TK 3,4,380-415,50 3,4,380-415,50 3,4,380-415,50 HP HP HP 26.00 28.00 30.00 72.80 78.60 84.00 248,400 268,200 286,600 81.90 88.20 94.50 279,500 301,000 322,400 18.91 20.68 22.70 18.00 20.18 20.59 30.30 33.20 36.40 28.90 32.40 33.00 60.00 67.00 73.00 75.00 75.00 90.00 3.85 3.80 3.70 4.55 4.37 4.59 ESEER 6.92 ESEER 6.83 ESEER 6.65 - - - SSC Scroll x 2 SSC Scroll x 2 SSC Scroll x 2 (6.39 x 2) (6.76 x 2) (7.81 x 2) DS-GB066FAVBx2 DS-GB070FAVAx2 DS4GJ5080FVAx2 PVE PVE PVE Propeller Propeller Propeller 620.0x2 620.0x2 620.0x2 340 340 340 5,666.67 5,666.67 5,666.67 8.00 8.00 8.00 78.40 78.40 78.40 19.05 19.05 19.05 3/4" 3/4" 3/4" 34.92 34.92 34.92 1 3/8" 1 3/8" 1 3/8" - - - - - - 200 (220) 200 (220) 200 (220) 110 (40) 110 (40) 110 (40) - - - 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 R410A R410A R410A 12.50 14.00 14.00 66 69 69 89 90 90 333.0 342.0 350.0 355.0 364.0 372.0 1,295x1,795x765 1,295x1,795x765 1,295x1,795x765 1,363x1,987x832 1,363x1,987x832 1,363x1,987x832 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0 * Specifications may be subject to change without prior notice. 1) Nominal cooling capacities are based on; - Indoor temperature : 27°C DB, 19°C WB - Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 2) Nominal heating capacities are based on; - Indoor temperature : 20°C DB, 15°C WB - Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. 4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.) *PDM kit: Pressure Drop Modulation kit 2
  • 9. Specifications Outdoor Type Model Name Power Supply Ø, #, V, Hz Mode - Performance HP HP Capacity (Nominal) Cooling kW Btu/h Heating kW Btu/h Power Power Input (Nominal) Cooling 1) kW Heating 2) kW Current Input (Nominal) Cooling 1) A Heating 2) A MCA A MFA A COP EER (Nominal Cooling) - COP (Nominal Heating) - Energy Grade - - Compressor Type - Output kW x n Model Name - Oil Type - Fan Type - Output x n W Air Flow Rate CMM l/s External Static Max. mmAQ Pa Piping Connections Liquid Pipe Ø, mm Ø, inch Gas Pipe Ø, mm Ø, inch Discharge Gas Pipe Ø, mm Ø, inch Installation Limitation Max. Length m Max. Height m Field Wiring Power Source Wire mm² Transmission Cable mm² Refrigerant Type - Factory Charging kg Sound Pressure dBA Power External Dimension New Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Operating Temp. Cooling ºC Heating ºC DVM S(NEW) DVM S(NEW) DVM S(NEW) AM320KXVAGH/TK AM340KXVAGH/TK AM360KXVAGH/TK 3,4,380-415,50 3,4,380-415,50 3,4,380-415,50 HP HP HP 32.00 34.00 36.00 90.40 95.40 101.60 308,500 325,500 346,700 101.70 107.10 114.30 347,000 365,400 390,000 23.53 24.70 28.28 22.07 23.52 26.86 37.70 39.60 45.30 35.40 37.70 43.10 64.20 71.20 69.60 75.00 90.00 90.00 3.84 3.86 3.59 4.61 4.55 4.26 - - - - - - SSC Scroll x 2 SSC Scroll x 2 SSC Scroll x 3 (6.39) + (7.81) (7.81) + (7.81) (6.39) + (6.39x2) DS-GB066FAVBx1 + DS4GJ5080FVAx1 DS4GJ5080FVAx2 DS-GB066FAVBx3 PVE PVE PVE Propeller Propeller Propeller (620.0x2)x2 (620.0x2)x2 (620.0x2)x2 255.0 + 290.0 255.0 + 290.0 255.0 + 290.0 4,250.0 + 4,833.3 4,250.0 + 4,833.3 4,250.0 + 4,833.3 8.00 8.00 8.00 78.40 78.40 78.40 19.05 19.05 19.05 3/4" 3/4" 3/4" 34.92 34.92 41.28 1 3/8" 1 3/8" 1 5/8" - - - - - - 200 (220) 200 (220) 200 (220) 110 (40) 110 (40) 110 (40) - - - 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 R410A R410A R410A 16.10 16.80 16.10 - - - - - - 226.0 + 255.0 253.0 + 255.0 226.0 + 285.0 246.0 + 275.0 273.0 + 275.0 246.0 + 305.0 (1,295x1,695x765)x2 (1,295x1,695x765)x2 (1,295x1,695x765)x2 (1,363x1,887x832)x2 (1,363x1,887x832)x2 (1,363x1,887x832)x2 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0 * Specifications may be subject to change without prior notice. 1) Nominal cooling capacities are based on; - Indoor temperature : 27°C DB, 19°C WB - Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 2) Nominal heating capacities are based on; - Indoor temperature : 20°C DB, 15°C WB - Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. 4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.) *PDM kit: Pressure Drop Modulation kit 2
  • 10. Specifications Outdoor Type Model Name Power Supply Ø, #, V, Hz Mode - Performance HP HP Capacity (Nominal) Cooling kW Btu/h Heating kW Btu/h Power Power Input (Nominal) Cooling 1) kW Heating 2) kW Current Input (Nominal) Cooling 1) A Heating 2) A MCA A MFA A COP EER (Nominal Cooling) - COP (Nominal Heating) - Energy Grade - - Compressor Type - Output kW x n Model Name - Oil Type - Fan Type - Output x n W Air Flow Rate CMM l/s External Static Max. mmAQ Pa Piping Connections Liquid Pipe Ø, mm Ø, inch Gas Pipe Ø, mm Ø, inch Discharge Gas Pipe Ø, mm Ø, inch Installation Limitation Max. Length m Max. Height m Field Wiring Power Source Wire mm² Transmission Cable mm² Refrigerant Type - Factory Charging kg Sound Pressure dBA Power External Dimension New Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Operating Temp. Cooling ºC Heating ºC DVM S(NEW) DVM S(NEW) DVM S(NEW) AM380KXVAGH/TK AM400KXVAGH/TK AM420KXVAGH/TK 3,4,380-415,50 3,4,380-415,50 3,4,380-415,50 HP HP HP 38.00 40.00 42.00 106.60 112.00 117.60 363,700 382,200 401,300 119.70 126.00 132.30 408,400 429,900 451,400 29.45 29.95 31.53 28.31 28.61 30.61 47.20 48.00 50.50 45.40 45.90 49.10 76.60 83.80 86.60 90.00 100.00 100.00 3.62 3.74 3.73 4.23 4.40 4.32 - - - - - - SSC Scroll x 3 SSC Scroll x 3 SSC Scroll x 4 (7.81) + (6.39x2) (7.81) + (6.39x2) (5.18x2) + (6.39x2) DS4GJ5080FVAx1 + DS- GB066FAVBx2 DS4GJ5080FVAx1 + DS- GB066FAVBx2 DS-GB052FAVBx2 + DS- GB066FAVBx2 PVE PVE PVE Propeller Propeller Propeller (620.0x2)x2 (620.0x2)x2 (620.0x2)x2 255.0 + 290.0 290.0x2 290.0x2 4,250.0 + 4,833.3 4,833.3x2 4,833.3x2 8.00 8.00 8.00 78.40 78.40 78.40 19.05 19.05 19.05 3/4" 3/4" 3/4" 41.28 41.28 41.28 1 5/8" 1 5/8" 1 5/8" - - - - - - 200 (220) 200 (220) 200 (220) 110 (40) 110 (40) 110 (40) - - - 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 R410A R410A R410A 16.80 16.80 16.80 - - - - - - 253.0 + 285.0 255.0 + 285.0 277.0 + 285.0 273.0 + 305.0 275.0 + 305.0 297.0 + 305.0 (1,295x1,695x765)x2 (1,295x1,695x765)x2 (1,295x1,695x765)x2 (1,363x1,887x832)x2 (1,363x1,887x832)x2 (1,363x1,887x832)x2 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0 * Specifications may be subject to change without prior notice. 1) Nominal cooling capacities are based on; - Indoor temperature : 27°C DB, 19°C WB - Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 2) Nominal heating capacities are based on; - Indoor temperature : 20°C DB, 15°C WB - Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. 4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.) *PDM kit: Pressure Drop Modulation kit 2
  • 11. Specifications Outdoor Type Model Name Power Supply Ø, #, V, Hz Mode - Performance HP HP Capacity (Nominal) Cooling kW Btu/h Heating kW Btu/h Power Power Input (Nominal) Cooling 1) kW Heating 2) kW Current Input (Nominal) Cooling 1) A Heating 2) A MCA A MFA A COP EER (Nominal Cooling) - COP (Nominal Heating) - Energy Grade - - Compressor Type - Output kW x n Model Name - Oil Type - Fan Type - Output x n W Air Flow Rate CMM l/s External Static Max. mmAQ Pa Piping Connections Liquid Pipe Ø, mm Ø, inch Gas Pipe Ø, mm Ø, inch Discharge Gas Pipe Ø, mm Ø, inch Installation Limitation Max. Length m Max. Height m Field Wiring Power Source Wire mm² Transmission Cable mm² Refrigerant Type - Factory Charging kg Sound Pressure dBA Power External Dimension New Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Operating Temp. Cooling ºC Heating ºC DVM S(NEW) DVM S(NEW) DVM S(NEW) AM440KXVAGH/TK AM460KXVAGH/TK AM480KXVAGH/TK 3,4,380-415,50 3,4,380-415,50 3,4,380-415,50 HP HP HP 44.00 46.00 48.00 124.00 129.00 134.40 423,100 440,200 458,600 139.50 144.90 151.20 476,000 494,400 515,900 33.63 34.80 35.30 30.75 32.20 32.50 53.90 55.80 56.60 49.30 51.60 52.10 98.00 105.00 112.20 125.00 125.00 125.00 3.69 3.71 3.81 4.54 4.50 4.65 - - - - - - SSC Scroll x 3 SSC Scroll x 3 SSC Scroll x 3 (6.39) + (7.81x2) (7.81) + (7.81x2) (7.81) + (7.81x2) DS-GB066FAVBx1 + DS4GJ5080FVAx2 DS4GJ5080FVAx3 DS4GJ5080FVAx3 PVE PVE PVE Propeller Propeller Propeller (620.0x2)x2 (620.0x2)x2 (620.0x2)x2 255.0 + 340.0 255.0 + 340.0 290.0 + 340.0 4,250.0 + 5,666.7 4,250.0 + 5,666.7 4,833.3 + 5,666.7 8.00 8.00 8.00 78.40 78.40 78.40 19.05 19.05 19.05 3/4" 3/4" 3/4" 41.28 41.28 41.28 1 5/8" 1 5/8" 1 5/8" - - - - - - 200 (220) 200 (220) 200 (220) 110 (40) 110 (40) 110 (40) - - - 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 R410A R410A R410A 21.70 22.40 22.40 - - - - - - 226.0 + 350.0 253.0 + 350.0 255.0 + 350.0 246.0 + 372.0 273.0 + 372.0 275.0 + 372.0 1,295x1,695x765 + 1,295x1,795x765 1,295x1,695x765 + 1,295x1,795x765 1,295x1,695x765 + 1,295x1,795x765 1,363x1,887x832 + 1,363x1,987x832 1,363x1,887x832 + 1,363x1,987x832 1,363x1,887x832 + 1,363x1,987x832 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0 * Specifications may be subject to change without prior notice. 1) Nominal cooling capacities are based on; - Indoor temperature : 27°C DB, 19°C WB - Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 2) Nominal heating capacities are based on; - Indoor temperature : 20°C DB, 15°C WB - Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. 4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.) *PDM kit: Pressure Drop Modulation kit 2
  • 12. Specifications Outdoor Type Model Name Power Supply Ø, #, V, Hz Mode - Performance HP HP Capacity (Nominal) Cooling kW Btu/h Heating kW Btu/h Power Power Input (Nominal) Cooling 1) kW Heating 2) kW Current Input (Nominal) Cooling 1) A Heating 2) A MCA A MFA A COP EER (Nominal Cooling) - COP (Nominal Heating) - Energy Grade - - Compressor Type - Output kW x n Model Name - Oil Type - Fan Type - Output x n W Air Flow Rate CMM l/s External Static Max. mmAQ Pa Piping Connections Liquid Pipe Ø, mm Ø, inch Gas Pipe Ø, mm Ø, inch Discharge Gas Pipe Ø, mm Ø, inch Installation Limitation Max. Length m Max. Height m Field Wiring Power Source Wire mm² Transmission Cable mm² Refrigerant Type - Factory Charging kg Sound Pressure dBA Power External Dimension New Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Operating Temp. Cooling ºC Heating ºC DVM S(NEW) DVM S(NEW) DVM S(NEW) AM500KXVAGH/TK AM520KXVAGH/TK AM540KXVAGH/TK 3,4,380-415,50 3,4,380-415,50 3,4,380-415,50 HP HP HP 50.00 52.00 54.00 140.00 145.60 151.20 477,700 496,800 515,900 157.50 163.80 170.10 537,400 558,900 580,400 36.88 40.05 39.80 34.50 37.29 38.01 59.10 64.20 63.80 55.30 59.80 60.90 115.00 117.60 128.00 150.00 150.00 150.00 3.80 3.64 3.80 4.57 4.39 4.48 - - - - - - SSC Scroll x 4 SSC Scroll x 4 SSC Scroll x 4 (5.18x2) + (7.81x2) (6.39x2) + (7.81x2) (6.39x2) + (7.81x2) DS-GB052FAVBx2 + DS4GJ5080FVAx2 DS-GB066FAVBx2 + DS4GJ5080FVAx2 DS-GB066FAVBx2 + DS4GJ5080FVAx2 PVE PVE PVE Propeller Propeller Propeller (620.0x2)x2 (620.0x2)x2 (620.0x2)x2 290.0 + 340.0 290.0 + 340.0 340.0x2 4,833.3 + 5,666.7 4,833.3 + 5,666.7 5,666.7x2 8.00 8.00 8.00 78.40 78.40 78.40 19.05 19.05 19.05 3/4" 3/4" 3/4" 41.28 41.28 41.28 1 5/8" 1 5/8" 1 5/8" - - - - - - 200 (220) 200 (220) 200 (220) 110 (40) 110 (40) 110 (40) - - - 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 R410A R410A R410A 22.40 22.40 26.50 - - - - - - 277.0 + 350.0 285.0 + 350.0 333.0 + 350.0 297.0 + 372.0 305.0 + 372.0 355.0 + 372.0 1,295x1,695x765 + 1,295x1,795x765 1,295x1,695x765 + 1,295x1,795x765 (1,295x1,795x765)x2 1,363x1,887x832 + 1,363x1,987x832 1,363x1,887x832 + 1,363x1,987x832 (1,363x1,987x832)x2 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0 * Specifications may be subject to change without prior notice. 1) Nominal cooling capacities are based on; - Indoor temperature : 27°C DB, 19°C WB - Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 2) Nominal heating capacities are based on; - Indoor temperature : 20°C DB, 15°C WB - Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. 4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.) *PDM kit: Pressure Drop Modulation kit 2
  • 13. Specifications Outdoor Type Model Name Power Supply Ø, #, V, Hz Mode - Performance HP HP Capacity (Nominal) Cooling kW Btu/h Heating kW Btu/h Power Power Input (Nominal) Cooling 1) kW Heating 2) kW Current Input (Nominal) Cooling 1) A Heating 2) A MCA A MFA A COP EER (Nominal Cooling) - COP (Nominal Heating) - Energy Grade - - Compressor Type - Output kW x n Model Name - Oil Type - Fan Type - Output x n W Air Flow Rate CMM l/s External Static Max. mmAQ Pa Piping Connections Liquid Pipe Ø, mm Ø, inch Gas Pipe Ø, mm Ø, inch Discharge Gas Pipe Ø, mm Ø, inch Installation Limitation Max. Length m Max. Height m Field Wiring Power Source Wire mm² Transmission Cable mm² Refrigerant Type - Factory Charging kg Sound Pressure dBA Power External Dimension New Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Operating Temp. Cooling ºC Heating ºC DVM S(NEW) DVM S(NEW) DVM S(NEW) AM560KXVAGH/TK AM580KXVAGH/TK AM600KXVAGH/TK 3,4,380-415,50 3,4,380-415,50 3,4,380-415,50 HP HP HP 56.00 58.00 60.00 156.80 162.60 168.00 535,000 554,800 573,200 176.40 182.70 189.00 601,900 623,400 644,900 41.61 43.39 45.41 38.59 40.77 41.18 66.70 69.60 72.80 61.90 65.40 66.00 133.00 140.00 146.00 150.00 200.00 200.00 3.77 3.75 3.70 4.57 4.48 4.59 - - - - - - SSC Scroll x 4 SSC Scroll x 4 SSC Scroll x 4 (6.39x2) + (7.81x2) (6.76x2) + (7.81x2) (7.81x2)x2 DS-GB066FAVBx2 + DS4GJ5080FVAx2 DS-GB070FAVAx2 + DS4GJ5080FVAx2 DS4GJ5080FVAx4 PVE PVE PVE Propeller Propeller Propeller (620.0x2)x2 (620.0x2)x2 (620.0x2)x2 340.0x2 340.0x2 340.0x2 5,666.7x2 5,666.7x2 5,666.7x2 8.00 8.00 8.00 78.40 78.40 78.40 19.05 19.05 19.05 3/4" 3/4" 3/4" 41.28 41.28 41.28 1 5/8" 1 5/8" 1 5/8" - - - - - - 200 (220) 200 (220) 200 (220) 110 (40) 110 (40) 110 (40) - - - 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 R410A R410A R410A 26.50 28.00 28.00 - - - - - - 333.0 + 350.0 342.0 + 350.0 350.0x2 355.0 + 372.0 364.0 + 372.0 372.0x2 (1,295x1,795x765)x2 (1,295x1,795x765)x2 (1,295x1,795x765)x2 (1,363x1,987x832)x2 (1,363x1,987x832)x2 (1,363x1,987x832)x2 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0 * Specifications may be subject to change without prior notice. 1) Nominal cooling capacities are based on; - Indoor temperature : 27°C DB, 19°C WB - Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 2) Nominal heating capacities are based on; - Indoor temperature : 20°C DB, 15°C WB - Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. 4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.) *PDM kit: Pressure Drop Modulation kit 2
  • 14. Specifications Outdoor Type Model Name Power Supply Ø, #, V, Hz Mode - Performance HP HP Capacity (Nominal) Cooling kW Btu/h Heating kW Btu/h Power Power Input (Nominal) Cooling 1) kW Heating 2) kW Current Input (Nominal) Cooling 1) A Heating 2) A MCA A MFA A COP EER (Nominal Cooling) - COP (Nominal Heating) - Energy Grade - - Compressor Type - Output kW x n Model Name - Oil Type - Fan Type - Output x n W Air Flow Rate CMM l/s External Static Max. mmAQ Pa Piping Connections Liquid Pipe Ø, mm Ø, inch Gas Pipe Ø, mm Ø, inch Discharge Gas Pipe Ø, mm Ø, inch Installation Limitation Max. Length m Max. Height m Field Wiring Power Source Wire mm² Transmission Cable mm² Refrigerant Type - Factory Charging kg Sound Pressure dBA Power External Dimension New Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Operating Temp. Cooling ºC Heating ºC DVM S(NEW) DVM S(NEW) DVM S(NEW) AM620KXVAGH/TK AM640KXVAGH/TK AM660KXVAGH/TK 3,4,380-415,50 3,4,380-415,50 3,4,380-415,50 HP HP HP 62.00 64.00 66.00 174.40 179.40 184.80 595,100 612,100 630,600 196.20 201.60 207.90 669,500 687,900 709,400 46.23 47.40 47.90 42.66 44.11 44.41 74.10 76.00 76.80 68.40 70.70 71.20 137.20 144.20 151.40 200.00 200.00 200.00 3.77 3.78 3.86 4.60 4.57 4.68 - - - - - - SSC Scroll x 4 SSC Scroll x 4 SSC Scroll x 4 (6.39) + (7.81) + (7.81x2) (7.81) + (7.81) + (7.81x2) (7.81)x2 + (7.81x2) DS-GB066FAVBx1 + DS4GJ5080FVAx3 DS4GJ5080FVAx4 DS4GJ5080FVAx4 PVE PVE PVE Propeller Propeller Propeller (620.0x2)x3 (620.0x2)x3 (620.0x2)x3 255.0 + 290.0 + 340.0 255.0 + 290.0 + 340.0 290.0x2 + 340.0 4,250.0 + 4,833.3 + 5,666.7 4,250.0 + 4,833.3 + 5,666.7 4,833.3x2 + 5,666.7 8.00 8.00 8.00 78.40 78.40 78.40 22.22 22.22 22.22 7/8" 7/8" 7/8" 53.98 53.98 53.98 2 1/8" 2 1/8" 2 1/8" - - - - - - 200 (220) 200 (220) 200 (220) 110 (40) 110 (40) 110 (40) - - - 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 R410A R410A R410A 30.10 30.80 30.80 - - - - - - 226.0 + 255.0 + 350.0 253.0 + 255.0 + 350.0 255.0x2 + 350.0 246.0 + 275.0 + 372.0 273.0 + 275.0 + 372.0 275.0x2 + 372.0 (1,295x1,695x765)x2 + 1,295x1,795x765 (1,295x1,695x765)x2 + 1,295x1,795x765 (1,295x1,695x765)x2 + 1,295x1,795x765 (1,363x1,887x832)x2 + 1,363x1,987x832 (1,363x1,887x832)x2 + 1,363x1,987x832 (1,363x1,887x832)x2 + 1,363x1,987x832 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0 * Specifications may be subject to change without prior notice. 1) Nominal cooling capacities are based on; - Indoor temperature : 27°C DB, 19°C WB - Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 2) Nominal heating capacities are based on; - Indoor temperature : 20°C DB, 15°C WB - Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. 4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.) *PDM kit: Pressure Drop Modulation kit 2
  • 15. Specifications Outdoor Type Model Name Power Supply Ø, #, V, Hz Mode - Performance HP HP Capacity (Nominal) Cooling kW Btu/h Heating kW Btu/h Power Power Input (Nominal) Cooling 1) kW Heating 2) kW Current Input (Nominal) Cooling 1) A Heating 2) A MCA A MFA A COP EER (Nominal Cooling) - COP (Nominal Heating) - Energy Grade - - Compressor Type - Output kW x n Model Name - Oil Type - Fan Type - Output x n W Air Flow Rate CMM l/s External Static Max. mmAQ Pa Piping Connections Liquid Pipe Ø, mm Ø, inch Gas Pipe Ø, mm Ø, inch Discharge Gas Pipe Ø, mm Ø, inch Installation Limitation Max. Length m Max. Height m Field Wiring Power Source Wire mm² Transmission Cable mm² Refrigerant Type - Factory Charging kg Sound Pressure dBA Power External Dimension New Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Operating Temp. Cooling ºC Heating ºC DVM S(NEW) DVM S(NEW) DVM S(NEW) AM680KXVAGH/TK AM700KXVAGH/TK AM720KXVAGH/TK 3,4,380-415,50 3,4,380-415,50 3,4,380-415,50 HP HP HP 68.00 70.00 72.00 190.40 196.00 201.60 649,700 668,800 687,900 214.20 220.50 226.80 730,900 752,400 773,900 49.48 52.65 54.23 46.41 49.20 51.19 79.30 84.40 86.90 74.40 78.90 82.10 154.20 156.80 159.60 200.00 200.00 200.00 3.85 3.72 3.72 4.62 4.48 4.43 - - - - - - SSC Scroll x 5 SSC Scroll x 5 SSC Scroll x 6 (7.81) + (5.18x2) + (7.81x2) (7.81) + (6.39x2) + (7.81x2) (5.18x2) + (6.39x2) + (7.81x2) DS4GJ5080FVAx3 + DS- GB052FAVBx2 DS4GJ5080FVAx3 + DS- GB066FAVBx2 DS-GB052FAVBx2 + DS- GB066FAVBx2 + DS4GJ5080FVAx2 PVE PVE PVE Propeller Propeller Propeller (620.0x2)x3 (620.0x2)x3 (620.0x2)x3 290.0x2 + 340.0 290.0x2 + 340.0 290.0x2 + 340.0 4,833.3x2 + 5,666.7 4,833.3x2 + 5,666.7 4,833.3x2 + 5,666.7 8.00 8.00 8.00 78.40 78.40 78.40 22.22 22.22 22.22 7/8" 7/8" 7/8" 53.98 53.98 53.98 2 1/8" 2 1/8" 2 1/8" - - - - - - 200 (220) 200 (220) 200 (220) 110 (40) 110 (40) 110 (40) - - - 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 R410A R410A R410A 30.80 30.80 30.80 - - - - - - 255.0 + 277.0 + 350.0 255.0 + 285.0 + 350.0 277.0 + 285.0 + 350.0 275.0 + 297.0 + 372.0 275.0 + 305.0 + 372.0 297.0 + 305.0 + 372.0 (1,295x1,695x765)x2 + 1,295x1,795x765 (1,295x1,695x765)x2 + 1,295x1,795x765 (1,295x1,695x765)x2 + 1,295x1,795x765 (1,363x1,887x832)x2 + 1,363x1,987x832 (1,363x1,887x832)x2 + 1,363x1,987x832 (1,363x1,887x832)x2 + 1,363x1,987x832 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0 * Specifications may be subject to change without prior notice. 1) Nominal cooling capacities are based on; - Indoor temperature : 27°C DB, 19°C WB - Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 2) Nominal heating capacities are based on; - Indoor temperature : 20°C DB, 15°C WB - Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. 4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.) *PDM kit: Pressure Drop Modulation kit 2
  • 16. Specifications Outdoor Type Model Name Power Supply Ø, #, V, Hz Mode - Performance HP HP Capacity (Nominal) Cooling kW Btu/h Heating kW Btu/h Power Power Input (Nominal) Cooling 1) kW Heating 2) kW Current Input (Nominal) Cooling 1) A Heating 2) A MCA A MFA A COP EER (Nominal Cooling) - COP (Nominal Heating) - Energy Grade - - Compressor Type - Output kW x n Model Name - Oil Type - Fan Type - Output x n W Air Flow Rate CMM l/s External Static Max. mmAQ Pa Piping Connections Liquid Pipe Ø, mm Ø, inch Gas Pipe Ø, mm Ø, inch Discharge Gas Pipe Ø, mm Ø, inch Installation Limitation Max. Length m Max. Height m Field Wiring Power Source Wire mm² Transmission Cable mm² Refrigerant Type - Factory Charging kg Sound Pressure dBA Power External Dimension New Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Operating Temp. Cooling ºC Heating ºC DVM S(NEW) DVM S(NEW) DVM S(NEW) AM740KXVAGH/TK AM760KXVAGH/TK AM780KXVAGH/TK 3,4,380-415,50 3,4,380-415,50 3,4,380-415,50 HP HP HP 74.00 76.00 78.00 207.20 212.80 218.40 707,000 726,100 745,200 233.10 239.40 245.70 795,400 816,900 838,400 57.41 57.15 58.96 53.99 54.71 55.29 92.00 91.60 94.50 86.60 87.70 88.70 162.20 172.60 177.60 200.00 200.00 200.00 3.61 3.72 3.70 4.32 4.38 4.44 - - - - - - SSC Scroll x 6 SSC Scroll x 6 SSC Scroll x 6 (6.39x2)x2 + (7.81x2) (6.39x2) + (6.39x2) + (7.81x2) (6.39x2) + (6.39x2) + (7.81x2) DS-GB066FAVBx4 + DS4GJ5080FVAx2 DS-GB066FAVBx4 + DS4GJ5080FVAx2 DS-GB066FAVBx4 + DS4GJ5080FVAx2 PVE PVE PVE Propeller Propeller Propeller (620.0x2)x3 (620.0x2)x3 (620.0x2)x3 290.0x2 + 340.0 290.0 + 340.0x2 290.0 + 340.0x2 4,833.3x2 + 5,666.7 4,833.3 + 5,666.7x2 4,833.3 + 5,666.7x2 8.00 8.00 8.00 78.40 78.40 78.40 22.22 22.22 22.22 7/8" 7/8" 7/8" 53.98 53.98 53.98 2 1/8" 2 1/8" 2 1/8" - - - - - - 200 (220) 200 (220) 200 (220) 110 (40) 110 (40) 110 (40) - - - 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 R410A R410A R410A 30.80 34.90 34.90 - - - - - - 285.0x2 + 350.0 285.0 + 333.0 + 350.0 285.0 + 333.0 + 350.0 305.0x2 + 372.0 305.0 + 355.0 + 372.0 305.0 + 355.0 + 372.0 (1,295x1,695x765)x2 + 1,295x1,795x765 1,295x1,695x765 + (1,295x1,795x765)x2 1,295x1,695x765 + (1,295x1,795x765)x2 (1,363x1,887x832)x2 + 1,363x1,987x832 1,363x1,887x832 + (1,363x1,987x832)x2 1,363x1,887x832 + (1,363x1,987x832)x2 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0 * Specifications may be subject to change without prior notice. 1) Nominal cooling capacities are based on; - Indoor temperature : 27°C DB, 19°C WB - Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 2) Nominal heating capacities are based on; - Indoor temperature : 20°C DB, 15°C WB - Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. 4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.) *PDM kit: Pressure Drop Modulation kit 2
  • 17. Specifications Outdoor Type Model Name Power Supply Ø, #, V, Hz Mode - Performance HP HP Capacity (Nominal) Cooling kW Btu/h Heating kW Btu/h Power Power Input (Nominal) Cooling 1) kW Heating 2) kW Current Input (Nominal) Cooling 1) A Heating 2) A MCA A MFA A COP EER (Nominal Cooling) - COP (Nominal Heating) - Energy Grade - - Compressor Type - Output kW x n Model Name - Oil Type - Fan Type - Output x n W Air Flow Rate CMM l/s External Static Max. mmAQ Pa Piping Connections Liquid Pipe Ø, mm Ø, inch Gas Pipe Ø, mm Ø, inch Discharge Gas Pipe Ø, mm Ø, inch Installation Limitation Max. Length m Max. Height m Field Wiring Power Source Wire mm² Transmission Cable mm² Refrigerant Type - Factory Charging kg Sound Pressure dBA Power External Dimension New Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Operating Temp. Cooling ºC Heating ºC DVM S(NEW) DVM S(NEW) DVM S(NEW) AM800KXVAGH/TK AM820KXVAGH/TK AM840KXVAGH/TK 3,4,380-415,50 3,4,380-415,50 3,4,380-415,50 HP HP HP 80.00 82.00 84.00 224.20 229.60 235.20 765,000 783,400 802,500 252.00 258.30 264.60 859,900 881,400 902,900 60.74 62.76 62.50 57.47 57.88 58.60 97.40 100.60 100.20 92.20 92.80 93.90 184.60 190.60 201.00 250.00 250.00 250.00 3.69 3.66 3.76 4.38 4.46 4.52 - - - - - - SSC Scroll x 6 SSC Scroll x 6 SSC Scroll x 6 (6.39x2) + (6.76x2) + (7.81x2) (6.39x2) + (7.81x2)x2 (6.39x2) + (7.81x2)x2 DS-GB066FAVBx2 + DS- GB070FAVAx2 + DS4GJ5080FVAx2 DS-GB066FAVBx2 + DS4GJ5080FVAx4 DS-GB066FAVBx2 + DS4GJ5080FVAx4 PVE PVE PVE Propeller Propeller Propeller (620.0x2)x3 (620.0x2)x3 (620.0x2)x3 290.0 + 340.0x2 290.0 + 340.0x2 340.0x3 4,833.3 + 5,666.7x2 4,833.3 + 5,666.7x2 5,666.7x3 8.00 8.00 8.00 78.40 78.40 78.40 22.22 22.22 22.22 7/8" 7/8" 7/8" 53.98 53.98 53.98 2 1/8" 2 1/8" 2 1/8" - - - - - - 200 (220) 200 (220) 200 (220) 110 (40) 110 (40) 110 (40) - - - 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 R410A R410A R410A 36.40 36.40 40.50 - - - - - - 285.0 + 342.0 + 350.0 285.0 + 350.0x2 333.0 + 350.0x2 305.0 + 364.0 + 372.0 305.0 + 372.0x2 355.0 + 372.0x2 1,295x1,695x765 + (1,295x1,795x765)x2 1,295x1,695x765 + (1,295x1,795x765)x2 (1,295x1,795x765)x3 1,363x1,887x832 + (1,363x1,987x832)x2 1,363x1,887x832 + (1,363x1,987x832)x2 (1,363x1,987x832)x3 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0 * Specifications may be subject to change without prior notice. 1) Nominal cooling capacities are based on; - Indoor temperature : 27°C DB, 19°C WB - Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 2) Nominal heating capacities are based on; - Indoor temperature : 20°C DB, 15°C WB - Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. 4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.) *PDM kit: Pressure Drop Modulation kit 2
  • 18. Specifications Outdoor Type Model Name Power Supply Ø, #, V, Hz Mode - Performance HP HP Capacity (Nominal) Cooling kW Btu/h Heating kW Btu/h Power Power Input (Nominal) Cooling 1) kW Heating 2) kW Current Input (Nominal) Cooling 1) A Heating 2) A MCA A MFA A COP EER (Nominal Cooling) - COP (Nominal Heating) - Energy Grade - - Compressor Type - Output kW x n Model Name - Oil Type - Fan Type - Output x n W Air Flow Rate CMM l/s External Static Max. mmAQ Pa Piping Connections Liquid Pipe Ø, mm Ø, inch Gas Pipe Ø, mm Ø, inch Discharge Gas Pipe Ø, mm Ø, inch Installation Limitation Max. Length m Max. Height m Field Wiring Power Source Wire mm² Transmission Cable mm² Refrigerant Type - Factory Charging kg Sound Pressure dBA Power External Dimension New Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Operating Temp. Cooling ºC Heating ºC DVM S(NEW) DVM S(NEW) DVM S(NEW) AM860KXVAGH/TK AM880KXVAGH/TK AM900KXVAGH/TK 3,4,380-415,50 3,4,380-415,50 3,4,380-415,50 HP HP HP 86.00 88.00 90.00 240.80 246.60 252.00 821,600 841,400 859,900 270.90 277.20 283.50 924,300 945,800 967,300 64.31 66.09 68.11 59.18 61.36 61.76 103.10 106.00 109.20 94.90 98.40 99.00 206.00 213.00 219.00 250.00 250.00 250.00 3.74 3.73 3.70 4.58 4.52 4.59 - - - - - - SSC Scroll x 6 SSC Scroll x 6 SSC Scroll x 6 (6.39x2) + (7.81x2)x2 (6.76x2) + (7.81x2)x2 (7.81x2)x3 DS-GB066FAVBx2 + DS4GJ5080FVAx4 DS-GB070FAVAx2 + DS4GJ5080FVAx4 DS4GJ5080FVAx6 PVE PVE PVE Propeller Propeller Propeller (620.0x2)x3 (620.0x2)x3 (620.0x2)x3 340.0x3 340.0x3 340.0x3 5,666.7x3 5,666.7x3 5,666.7x3 8.00 8.00 8.00 78.40 78.40 78.40 22.22 22.22 22.22 7/8" 7/8" 7/8" 53.98 53.98 53.98 2 1/8" 2 1/8" 2 1/8" - - - - - - 200 (220) 200 (220) 200 (220) 110 (40) 110 (40) 110 (40) - - - 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 R410A R410A R410A 40.50 42.00 42.00 - - - - - - 333.0 + 350.0x2 342.0 + 350.0x2 350.0x3 355.0 + 372.0x2 364.0 + 372.0x2 372.0x3 (1,295x1,795x765)x3 (1,295x1,795x765)x3 (1,295x1,795x765)x3 (1,363x1,987x832)x3 (1,363x1,987x832)x3 (1,363x1,987x832)x3 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -25.0 ~ 24.0 -25.0 ~ 24.0 -25.0 ~ 24.0 * Specifications may be subject to change without prior notice. 1) Nominal cooling capacities are based on; - Indoor temperature : 27°C DB, 19°C WB - Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 2) Nominal heating capacities are based on; - Indoor temperature : 20°C DB, 15°C WB - Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m 3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. 4) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.) *PDM kit: Pressure Drop Modulation kit 2
  • 19. Operation limit Outdoortemperature(℃DB) 10 14 20 25 27 30 50 40 30 20 10 -10 -20 -5 -15 -30 0 Continuous Operation Range “Expand operational temperature range” Option Indoor temperature(℃ WB) Outdoortemperature(℃WB) Indoor temperature(℃ DB) 10 15 20 25 27 30 30 20 24 10 -10 -20 -30 0 Continuous Operation Range Warming Up Operation Range ℃ Cooling Heating Defrosting correction factor On heating operation, frost can be formed on heat exchanger according to outdoor temperature. (Frost on heat exchanger results in decreasing the performance.) To remove frost on heat exchanger of outdoor unit, defrost operation is carried out periodically. During defrost operation, capacity of outdoor unit may decrease. The decrement is not considered to the individual capacity tables. 3
  • 20. Dimensional drawing Outdoor AM140KXVAGH/TK, AM160KXVAGH/TK, AM180KXVAGH/TK, AM200KXVAGH/TK, AM220KXVAGH/TK Units : mm / inches Table of descriptions 1 Gas Ref. pipe 7 Knock-out Hole for Ref. Piping 2 Liquid Ref. pipe 8 Anchor Bolt Hole 3 Power wiring conduit 9 4 Communication wiring conduit 10 5 Power wiring conduit 11 6 Communication wiring conduit 12 1295 [4'-3"] 765 [2'-6"] 616 [2'-01/4"] 671 [2'-21/2"] 241 [91/2"] 122 [4 3/4"] 51 [2"] 1695 [5'-63/4"] 36 [1 1/2"] 557 [1'-10"] 492 [1'-71/2"]172 [63/4"] 107 [4 1/4"] 575 [1'-10 3/4"] 761 [2'-6"] 1295 [4'-3"] 803 [2'-73/4"] ① ② ③④ ⑤ ⑥ ⑤ ⑥ ③ ⑧ 4
  • 22. Electrical wiring diagram Outdoor AM140KXVAGH/TK, AM200KXVAGH/TK, AM220KXVAGH/TK 5
  • 23. Electrical wiring diagram Outdoor AM160KXVAGH/TK, AM180KXVAGH/TK, AM240KXVAGH/TK, AM260KXVAGH/TK, AM280KXVAGH/TK, AM300KXVAGH/TK 5
  • 24. Sound pressure level Outdoor Note * Specifications may be subject to change without prior notice 1) These operation values were obtained in an anechoic room. 2) Sound pressure level will vary depending on a range of factors such as the construction of the particular room 3) Operation sound level may differ depending on operation and ambient conditions. NC curve Unit: dB(A) Model Cooling AM140KXVAGH/TK 61 AM160KXVAGH/TK 63 AM180KXVAGH/TK 64 AM200KXVAGH/TK 65 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Cooling 63 125 250 500 1000 2000 4000 8000 Octave band center frequency(Hz) 10 20 30 40 50 60 70 80 Soundpressurelevel(dB) 1) AM140KXVAGH/TK NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Cooling 63 125 250 500 1000 2000 4000 8000 Octave band center frequency(Hz) 10 20 30 40 50 60 70 80 Soundpressurelevel(dB) 2) AM160KXVAGH/TK NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Cooling 63 125 250 500 1000 2000 4000 8000 Octave band center frequency(Hz) 10 20 30 40 50 60 70 80 Soundpressurelevel(dB) 3) AM180KXVAGH/TK NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Cooling 63 125 250 500 1000 2000 4000 8000 Octave band center frequency(Hz) 10 20 30 40 50 60 70 80 Soundpressurelevel(dB) 4) AM200KXVAGH/TK 6
  • 25. Sound pressure level Outdoor Note * Specifications may be subject to change without prior notice 1) These operation values were obtained in an anechoic room. 2) Sound pressure level will vary depending on a range of factors such as the construction of the particular room 3) Operation sound level may differ depending on operation and ambient conditions. NC curve Unit: dB(A) Model Cooling AM220KXVAGH/TK 65 AM240KXVAGH/TK 66 AM260KXVAGH/TK 66 AM280KXVAGH/TK 69 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Cooling 63 125 250 500 1000 2000 4000 8000 Octave band center frequency(Hz) 10 20 30 40 50 60 70 80 Soundpressurelevel(dB) 1) AM220KXVAGH/TK NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Cooling 63 125 250 500 1000 2000 4000 8000 Octave band center frequency(Hz) 10 20 30 40 50 60 70 80 Soundpressurelevel(dB) 2) AM240KXVAGH/TK NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Cooling 63 125 250 500 1000 2000 4000 8000 Octave band center frequency(Hz) 10 20 30 40 50 60 70 80 Soundpressurelevel(dB) 3) AM260KXVAGH/TK NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Cooling 63 125 250 500 1000 2000 4000 8000 Octave band center frequency(Hz) 10 20 30 40 50 60 70 80 Soundpressurelevel(dB) 4) AM280KXVAGH/TK 6
  • 26. Sound pressure level Outdoor Note * Specifications may be subject to change without prior notice 1) These operation values were obtained in an anechoic room. 2) Sound pressure level will vary depending on a range of factors such as the construction of the particular room 3) Operation sound level may differ depending on operation and ambient conditions. NC curve Unit: dB(A) Model Cooling AM300KXVAGH/TK 69 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Cooling 63 125 250 500 1000 2000 4000 8000 Octave band center frequency(Hz) 10 20 30 40 50 60 70 80 Soundpressurelevel(dB) 1) AM300KXVAGH/TK 6
  • 27. Sound power level Outdoor Note 125 250 500 1000 2000 4000 8000 A Octave band center frequency(Hz) 0 10 20 30 40 50 60 70 80 90 100 Soundpowerlevel(dB) 1)AM140KXVAGH/TK 125 250 500 1000 2000 4000 8000 A Octave band center frequency(Hz) 0 10 20 30 40 50 60 70 80 90 100 Soundpowerlevel(dB) 2)AM160KXVAGH/TK 125 250 500 1000 2000 4000 8000 A Octave band center frequency(Hz) 0 10 20 30 40 50 60 70 80 90 100 Soundpowerlevel(dB) 3)AM180KXVAGH/TK 125 250 500 1000 2000 4000 8000 A Octave band center frequency(Hz) 0 10 20 30 40 50 60 70 80 90 100 Soundpowerlevel(dB) 4)AM200KXVAGH/TK Unit: dB(A) Model Power AM140KXVAGH/TK 81 AM160KXVAGH/TK 83 AM180KXVAGH/TK 84 AM200KXVAGH/TK 87 * Specifications may be subject to change 1) dBA = A-weighted sound power level. 2) Reference power : 1pW. 3) Measured according to ISO 3741. 7
  • 28. Sound power level Outdoor Note 125 250 500 1000 2000 4000 8000 A Octave band center frequency(Hz) 0 10 20 30 40 50 60 70 80 90 100 Soundpowerlevel(dB) 1)AM220KXVAGH/TK 125 250 500 1000 2000 4000 8000 A Octave band center frequency(Hz) 0 10 20 30 40 50 60 70 80 90 100 Soundpowerlevel(dB) 2)AM240KXVAGH/TK 125 250 500 1000 2000 4000 8000 A Octave band center frequency(Hz) 0 10 20 30 40 50 60 70 80 90 100 Soundpowerlevel(dB) 3)AM260KXVAGH/TK 125 250 500 1000 2000 4000 8000 A Octave band center frequency(Hz) 0 10 20 30 40 50 60 70 80 90 100 Soundpowerlevel(dB) 4)AM280KXVAGH/TK Unit: dB(A) Model Power AM220KXVAGH/TK 89 AM240KXVAGH/TK 89 AM260KXVAGH/TK 89 AM280KXVAGH/TK 90 * Specifications may be subject to change 1) dBA = A-weighted sound power level. 2) Reference power : 1pW. 3) Measured according to ISO 3741. 7
  • 29. Sound power level Outdoor Note 125 250 500 1000 2000 4000 8000 A Octave band center frequency(Hz) 0 10 20 30 40 50 60 70 80 90 100 Soundpowerlevel(dB) 1)AM300KXVAGH/TK Unit: dB(A) Model Power AM300KXVAGH/TK 90 * Specifications may be subject to change 1) dBA = A-weighted sound power level. 2) Reference power : 1pW. 3) Measured according to ISO 3741. 7
  • 30. Cycle diagram Outdoor AM140KXVAGH/TK, AM160KXVAGH/TK, AM180KXVAGH/TK Abbreviation Explanation Abbreviation Explanation INV Inveter Compressor V_AR Accumulator Oil Return Valve OFM Outdoor Fan Motor CV_E EEV Bypass Check Valve OHX Outdoor Heat Exchanger CV_D Discharge Check Valve AC Accumulator T_D Discharge Temp. Sensor OS Oil Separator T_S Suction Temp. Sensor IC Intercooler T_CO Cond Out Temp. Sensor IPMC IPM Cooler T_EI EVI In Temp. Sensor HPS High Pressure Sensor T_EO EVI Out Temp. Sensor LPS Low Pressure Sensor T_L Liquid Tube Temp. Sensor HPSW High Pressure Switch T_CT Comp. Top Temp. Sensor E_M Main EEV T_A Ambient Temp. Sensor E_EV EVI EEV SV_G Gas Pipe Service Valve V_ES EVI Sol. Valve SV_L Liquid Pipe Service Valve V_EB EVI Bypass Valve V_HG Hot Gas Bypass Valve V_4W 4Way Valve s E s E s INV OFM OHX AC OS IC HPS HPSW E_M E_EV V_EB V_HG V_4W V_AR CV_E CV_D T_D T_CO T_EI T_EO T_L T_CT T_A V_ES SV_G SV_L IPMC LPS T_S 8
  • 31. Cycle diagram Outdoor AM200KXVAGH/TK, AM220KXVAGH/TK Abbreviation Explanation Abbreviation Explanation INV1 Inveter Compressor V_4W 4Way Valve INV2 Inveter Compressor V_AR Accumulator Oil Return Valve OFM Outdoor Fan Motor CV_E EEV Bypass Check Valve OHX Outdoor Heat Exchanger CV_D Discharge Check Valve AC Accumulator T_D Discharge Temp. Sensor OS Oil Separator T_S Suction Temp. Sensor IC Intercooler T_CO Cond Out Temp. Sensor IPMC IPM Cooler T_EI EVI In Temp. Sensor HPS High Pressure Sensor T_EO EVI Out Temp. Sensor LPS Low Pressure Sensor T_L Liquid Tube Temp. Sensor HPSW High Pressure Switch T_CT Comp. Top Temp. Sensor E_M Main EEV T_A Ambient Temp. Sensor E_EV EVI EEV SV_G Gas Pipe Service Valve V_ES EVI Sol. Valve SV_L Liquid Pipe Service Valve V_EB EVI Bypass Valve V_HG Hot Gas Bypass Valve E s E s INV OFM OHX AC OS IC HPS HPSW E_M E_EV V_ES V_EB V_HG V_4W CV_E CV_D T_D T_CO T_EI T_EO T_L T_CT T_A INV V_ES CV_D T_D T_CT OSHPSW SV_G SV_L IPMC IPMC s V_AR1 LPS T_S 8
  • 32. Cycle diagram Outdoor AM240KXVAGH/TK, AM260KXVAGH/TK Abbreviation Explanation Abbreviation Explanation INV1 Inveter Compressor V_4W 4Way Valve INV2 Inveter Compressor V_AR Accumulator Oil Return Valve OFM Outdoor Fan Motor CV_E EEV Bypass Check Valve OHX Outdoor Heat Exchanger CV_D Discharge Check Valve AC Accumulator T_D Discharge Temp. Sensor OS Oil Separator T_S Suction Temp. Sensor IC Intercooler T_CO Cond Out Temp. Sensor IPMC IPM Cooler T_EI EVI In Temp. Sensor HPS High Pressure Sensor T_EO EVI Out Temp. Sensor LPS Low Pressure Sensor T_L Liquid Tube Temp. Sensor HPSW High Pressure Switch T_CT Comp. Top Temp. Sensor E_M Main EEV T_A Ambient Temp. Sensor E_EV EVI EEV SV_G Gas Pipe Service Valve V_ES EVI Sol. Valve SV_L Liquid Pipe Service Valve V_EB EVI Bypass Valve V_HG Hot Gas Bypass Valve s E s INV1 OFM OHX AC IC HPS HPSW1 E_EV V_ES V_EB V_HG V_4W T_D1 T_S T_EI T_EO T_L T_CT1 T_A V_ES T_D2 T_CT2 HPSW2 SV_G SV_L IPMC1 IPMC2 E_M1 E_M2 LPS V_AR1 CVD1 CVD2 CV_E1 T_CO s T_CI E E CV_E2 OS2OS1 INV2 8
  • 33. Cycle diagram Outdoor AM280KXVAGH/TK, AM300KXVAGH/TK Abbreviation Explanation Abbreviation Explanation INV1 Inveter Compressor V_4W 4Way Valve INV2 Inveter Compressor V_AR Accumulator Oil Return Valve OFM Outdoor Fan Motor CV_E EEV Bypass Check Valve OHX Outdoor Heat Exchanger CV_D Discharge Check Valve AC Accumulator T_D Discharge Temp. Sensor OS Oil Separator T_S Suction Temp. Sensor IC Intercooler T_CO Cond Out Temp. Sensor IPMC IPM Cooler T_EI EVI In Temp. Sensor HPS High Pressure Sensor T_EO EVI Out Temp. Sensor LPS Low Pressure Sensor T_L Liquid Tube Temp. Sensor HPSW High Pressure Switch T_CT Comp. Top Temp. Sensor E_M Main EEV T_A Ambient Temp. Sensor E_EV EVI EEV SV_G Gas Pipe Service Valve V_ES EVI Sol. Valve SV_L Liquid Pipe Service Valve V_EB EVI Bypass Valve V_HG Hot Gas Bypass Valve RE 3.0L s E s INV1 OFM OHX AC IC HPS HPSW1 E_EV V_ES V_EB V_HG V_4W T_D1 T_S T_EI T_EO T_L T_CT1 T_A V_ES T_D2 T_CT2 HPSW2 SV_G SV_L IPMC1 IPMC2 E_M1 E_M2 LPS V_AR1 CVD1 CVD2 CV_E1 T_CO s T_CI E E CV_E2 OS2OS1 INV2 8
  • 34. 2016.01 Ver.1.0 Samsung Electronics Co., LTD. B2B PM / SE Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 443-742 Website : www.samsung.com Email : airconditioner@samsung.com Images and data in this book may subject to change without prior notice.