Effect of Superconducting Fault Current Limiter (SFCL) on
Triumphant Intrusion of Circuit Breakers
R. AKSHAYA K. BHARGAVA
IV B.Tech, EEE Electrical Engineer,
Ph. No: 09553406942 GERDAU STEEL INDIA PVT LTD, INDIA.
Email ID: akkidaddy96@gmail.com Email ID: kwtlbhargava.8@gmail.com
BHEEMA INSTITUTE OF TECHNOLOGY & SCIENCE (JNTUA),
ADONI-518301, KURNOOL DISTRICT, ANDHRA PRADESH.
ABSTRACT:
The applications of fault current limiter (FCL) will not only decrease the stress on network
equipments, but can also offer a link in improving the reliability of the power system. The
infiltration of distributed generation systems can result in increasing the short circuit current level.
There are various types of FLC’s that are made up of different superconducting materials with a
wide range of designs. Among these mainly used are resistive type, inductive type and bridge type
SFCL .In this paper, the transient recovery voltage(TRV) analysis, based on the electromagnetic
transient program(EMTP),is used to investigate the behavior of the three types of SFCL’s installed
in an electrical distribution grid. The results simulated shows that TRV can be damped during the
fault clearing period of resistive and bridge type SFCL.
KEYWORDS:
Superconducting Fault Current Limiter, Transient Recovery Voltage, Rate of Rise of Recovery
Voltage (RRRV), Circuit Breaker
INTRODUCTION:
With the growth of the demand for electric power, the electric power systems are interconnected
each other to increase the reliability of power supply. However, fault current levels increase
beyond capabilities of existing equipments in some points of grids. Therefore, all equipments
especially, circuit breakers have to have a short circuit rating capable of withstanding this level.
Usually, handling these increasing fault currents requires the costly replacement of equipments or
imposition of changes in the configuration. But, the splitting of substation may decrease the
operational flexibility and system reliability. An alternative solution is the usage of FCLs to reduce
the fault current to withstanding level of existing circuit breakers. So, the existing equipments can
still be used to protect the power system [1]-[2].
Also after being limited by the FCL, the current is interrupted at its current zero by a circuit
breaker. After the interruption of the fault current, a transient recovery voltage (TRV) appears
across the contacts of the circuit breaker. To perform a successful interruption, the circuit breaker
must withstand against the TRV without re-establishment of the arc between the contacts.
An ideal FCL should have the following features [1-3]:
• Zero impedance and power losses at normal operation,
ISBN-13: 978-1537584836
www.iaetsd.in
Proceedings of ICAER-2016
©IAETSD 201660
• Large impedance in fault conditions,
• Quick appearance of impedance when fault occurs,
• Fast recovery after fault removal,
• Reliable current limitation at determined fault current and
• Good reliability.
Superconducting Fault Current Limiter (SFCL) offers a solution to these problems with many
significant advantages. The application of the SFCL would not only decrease the stress on device
but also offer an interconnection to secure the network. They can improve reliability and stability
of power systems by reducing the fault current. There are several kinds of SFCLs, which can be
classified in three types such as the resistive type, the inductive type and bridge type SFCL. Each
type of SFCL has its merits and demerits. Many studies have focused on the topology and
capability of SFCLs. The inductive type SFCL is able to suppress the voltage drop and limit the
fault current. The resistive type SFCL can consume the energy of the fault current and limit it. This
capability can improve the power system stability. The bridge type SFCL is a kind of SFCL, which
has zero impedance under the normal condition and large impedance under fault condition. Its
advantage is the fault current limitation without any delay and smoothing the surge current
waveform. But, it cannot limit the steady state fault current. Among the parameters of the FCL,
the magnitude of the limiting impedance and its merits affects the current-limiting performance of
the FCL much more than the other parameters. In other words, depending upon the kind of the
FCL and its merits, the insertion of the FCL in to the power system can result in more severe
interrupting problems. Therefore, it is important to study the interrupting behavior of circuit
breakers in the presence of the kinds of FCLs. In this paper, a comparative study of the interrupting
behavior of circuit breakers in the presence of three types such as the resistive type, the inductive
type and bridge type SFCL have been carried out.
CONCEPT OF SFCL:
Several designs have been considered for the SFCL which are based on different superconducting
materials. The resistive SFCL is simply connected in series with the network; the inductive SFCL
is based on a transformer with a superconducting shielding tube in the secondary. The bridge-type
SFCL consists of a diode-bridge and superconductor as limiting function.
A. Resistive SFCL Model:
A resistive SFCL utilizes resistance increase upon quench of a superconductor. It has advantages
such as simpler structure, smaller size, and possibly lower capital cost than other types. During
normal operation, the superconducting element is in its superconducting state and the normal load
current passes with theoretically no loss. In the case of a short circuit, the circuit current rises
sharply and the superconductor undergoes a transition to its normal state, so a certain value of
nonlinear resistance is created by self-sensing and self-triggering, thus limiting the fault current
level. A non-linear resistive model was used to analyze the features of a resistive FCL prototype
with EMTP simulator in this paper. Its behavior under normal operation and short-circuit
conditions in a test circuit was investigated by computer simulation using the EMTP program. As
ISBN-13: 978-1537584836
www.iaetsd.in
Proceedings of ICAER-2016
©IAETSD 201661
the scaled I–V curve shown in Fig. 1, the resistance variation is represented by the gradient of the
curve [9-10].
Fig 1. V-I curve of resistive FCL
B. Inductive SFCL Model:
In the model of the inductive FCL, a capacitance CP
, is connected in parallel with the limiting coil
to simulate a stray capacitance appearing in the winding of the coil. The stray capacitance CP
, has
so much higher impedance than the inductance LFCL
that the impedance ZFCL
is equal to the
impedance of the inductance LFCL
. Fig. 2 shows the inductive SFCL model, used in this paper [11].
Fig 2. Inductive SFCL model
B. Bridge-Type SFCL Model:
Fig. 3 shows the three-phase bridge-type SFCL, which consists of the superconducting coil (SC),
series transformer and diode bridge circuit. The diode bridge converts three-phase AC to DC
current, which flows through the super- conducting coil. The current through the primary and
secondary winding of transformer are defined as ip
, is
, respectively, and the ratio of transformer is
N, as follows:
ISBN-13: 978-1537584836
www.iaetsd.in
Proceedings of ICAER-2016
©IAETSD 201662
Fig 3. Bridge-type SFCL schematic diagram
Fig 4. SC and fault current during fault and normal operation with using bridge-type
SFCL.
FCL IN DISTRIBUTION SYSTEM:
Most of the distribution systems have radial form. As a result in any branch of a radial system,
power only flows in one direction. The distribution voltage levels are in the range of 10kV to
30kV. It can be expected that there will be interactions between the FCL and power system, if FCL
is placed in the grid. A typical distribution system is represented in Fig. 5. The source impedance
includes the transformer impedance and the upstream short-circuit impedance. Parallel feeders are
connected to the Point of Common Coupling (PCC). The bus is supplied by a substation
transformer from a 110 kV network. The upstream source system is modeled as an infinite bus and
the source impedance is consists of an equivalent resistance and inductance connected to the local
distribution substation. The load is modeled as a lumped series R-L-C branch with a power factor
of 0.886. A 3-phase short circuit fault is simulated at the load side, on feeder 2 (F2), as shown in
Fig. 5. After one cycles, the circuit breaker opened to clear the fault. The circuit breaker is modeled
as an ideal time-controlled switch with a parallel capacitance. This capacitance is the total
ISBN-13: 978-1537584836
www.iaetsd.in
Proceedings of ICAER-2016
©IAETSD 201663
capacitance of the source side circuit, which includes the stray capacitance of circuit breaker to the
ground.
SIMULATION RESULTS:
The simulation has been carried out with a fault starting at t=140ms. The circuit breaker has been
opened after 1 cycle.
The total simulation time was 200ms according to the circuit breaker opening time, and the
simulation step is 1μs. The parameters for the simulation have been listed in table 1.
Fig. 5. Schematic diagram of study system
TABLE I. SYSTEM PARAMETERS
When the circuit breaker attempts to interrupt the limited fault current, an over voltage is developed
across contacts [13]. This voltage is called Transient Recovery Voltage (TRV) of the circuit
breaker. Circuit breakers may fail to interrupt fault currents when power systems have transient
recovery voltage levels, which exceed the rating of circuit breakers. The Rate of Raise of Recovery
Voltage (RRRV) is an important parameter in the power system operation, presented in IEEE
C37.41 standard. The simulations by the Electro-Magnetic Transients Program (ATP-EMTP) was
performed to determine the instantaneous values of the transient recovery voltage VCB appearing
PARAMETER VALUE
Supply Voltage 110kV,50Hz
Step down
Transformer
110/15kV,10MVA
Bridge-type FCL Inductance of SC 50 mH
Inductive
SFCL
Inductance (LFCL
) 64.4 mH
Stray Capacitance
(Cp)
1uF
Resistive SFCL Maximum
Resistance (Rmax
)
20 Ω
Load Load 1 P=6kW,PF=0.9
Load 2 P=5kW,PF=0.88
ISBN-13: 978-1537584836
www.iaetsd.in
Proceedings of ICAER-2016
©IAETSD 201664
after current zero and the current flowing ICB
through the contacts of the circuit breaker before
current zero for following cases:
A. Without Using Any FCL:
Fig. 6 shows the current flowing through the contacts of the circuit breaker before current zero
without FCL application. It is obvious in Fig. 6, which the peak value of the fault current is
about 3500A, which can damage the system devices. Fig. 7 shows the circuit breaker’s TRV
without installation of FCL. The TRV in the absence of the FCL reaches a peak value of 24
kV. The initial transient recovery voltage (ITRV) in the absence of the FCL reaches a first
peak value of 23.7 kV during 0.0044s. From these values, the RRRV was determined to be 55
kV/us.
Fig. 6. Circuit breaker current without using any FCL
ISBN-13: 978-1537584836
www.iaetsd.in
Proceedings of ICAER-2016
©IAETSD 201665
Fig. 7. Circuit breaker TRV without using any FCL
B. With Using Inductive SFCL:
Fig. 8 shows the current flowing through the contacts of the circuit breaker before current zero
with inductive SFCL application. It is obvious in Fig. 8, which the peak value of the fault current
is limited about 800A. Application of inductive SFCL creates an asymmetrical short-circuit
current. Fig. 9 shows the circuit breakers TRV with application of inductive SFCL. The TRV
reaches a peak value of 30 kV. The initial transient recovery voltage (ITRV) with inductive SFCL
reaches a first peak value of 10 kV during 0.00004s. From these values, the RRRV was determined
to be 250 kV/us.
Fig. 8. Circuit breaker current with using inductive SFCL
ISBN-13: 978-1537584836
www.iaetsd.in
Proceedings of ICAER-2016
©IAETSD 201666
Fig. 9. Circuit breaker TRV with using inductive SFCL
C. With Using Resistive SFCL
Fig. 10 shows the current flowing through the contacts of the circuit breaker before current zero
with resistive SFCL application. It is obvious in Fig. 10, which the peak value of the fault current
is limited about 650A. Application of resistive SFCL eliminates the asymmetrical component of
fault current. Fig. 11 shows the circuit breakers TRV with application of resistive SFCL. The TRV
reaches a peak value of 16 kV. The initial transient recovery voltage (ITRV) with inductive SFCL
reaches a first peak value of 7 kV during 0.0009s. From these values, the RRRV was decreased to
8 kV/us.
Fig. 10. Circuit breaker current with using resistive SFCL
Fig. 11. Circuit breaker TRV with using Resistive SFCL
ISBN-13: 978-1537584836
www.iaetsd.in
Proceedings of ICAER-2016
©IAETSD 201667
D. With Using Bridge-SFCL
Fig. 12 shows the current flowing through the contacts of the circuit breaker before current zero
with bridge-type SFCL application. It is obvious in Fig. 12, which the peak value of the fault
current is limited about 450A, but the fault current increases with a constant rate. Fig. 13 shows
the circuit breaker’s TRV with application of bridge-type SFCL. The TRV reaches a peak value
of 20 kV. The initial transient recovery voltage (ITRV) with inductive SFCL reaches a first peak
value of 7.5 kV during 0.00029s. From these values, the RRRV was decreased to 24 kV/us.
Fig. 12. The Circuit Breaker Current with Using Bridge-Type SFCL
Fig. 13. The Circuit Breaker transient Recovery Voltage with using Bridge-Type SFCL
ISBN-13: 978-1537584836
www.iaetsd.in
Proceedings of ICAER-2016
©IAETSD 201668
CONCLUSION:
In this paper, the effect of three types of SFCL on transient recovery voltage of circuit breaker
has been studied. The simulation results show that not only fault current has been limited, but also
the TRV and RRRV of the circuit breaker has been reduced effectively by using the resistive SFCL
and bridge type SFCL. By using inductive SFCL, the fault current has been limited, but the TRV
and RRRV of the circuit breaker has been increased. Also, by using the resistive SFCL, the TRV
and RRRV of circuit breaker was lower than the other types of SFCL.
PROPERTIES OF SFCL:
1. Self activating
2. Low maintenance
3. High impedance in fault operation
4. Low impedance in normal operation
5. Limits fault current before first peak
6. Environmentally friendly
ADVANTAGES:
1. Over 100 times faster response time
2. 10 to 20 times shorter recovery time
3. Time adjustable response functions
4. 1000 times number of full power protection cycles
APPLICATIONS:
Three main application areas are:
1. Fault current limiter in main position: The fault current limiter FCL protects the entire
bus.
2. Fault current limiter in feeder position: The fault current limiter FCL protects an
individual circuit on the bus, under rated equipment can be selectively protected as
needed in this manner.
3. Fault current limiter in bus tie position: Two buses are tied, yet a faulted bus receives the
full fault current of only one transformer. Finally the fault current limiter FCL protects
the entire bus.
DISADVANTAGES:
1. To show any properties, and be of any use they must operate at critical temperature which is
very costly.
2. They emit strong magnetic fields which effects human causing blindness, brain cancer etc.
ISBN-13: 978-1537584836
www.iaetsd.in
Proceedings of ICAER-2016
©IAETSD 201669
REFERENCES:
[1] CIGRE WG A3.10, “Fault Current Limiters Report on the Activities of CIGRE WG
3.16,”CIGRE Technical Brochure, 2006.
[2] CIGRE WG A3.10: “Fault Current Limiters in High Electrical Medium and Voltage
Systems”, CIGRE Technical Brochure, No. 239, 2003.
[3] E.Calixte, Y.Yokomizu, T.Matsumura and H.Fujita, “Reduction in Severity of Circuit
Breaker Duty Under Generator-Fed Fault Condition by Means of Resistive Fault Current
Limiter,” International Journal of Power Energy System, Power Con Special Issue 2004, pp.24-
31
[4] L. Z. Lin, K.P. Juengst, “Application studies of superconducting fault current limiter in
electric power systems ,” IEEE Trans. Appl. Superconduct. 12 (March (1)) (2002) 900–903.
[5] K . Arai, H. Tanaka, M. Inaba, H. Arai, T. Ishigohka, M. Furuse, and M. Umeda, “Test of
Resonance-Type Superconducting Fault Current Limiter,” IEEE Trans. Appl. Supercond.,
Vol.16, No. 2, June 2006
[6] S.H. Lim, H.S. Choi, and B.S. Han, “Fault Current Limiting Characteristics of DC Dual
Reactor Type SFCL Using Switching Operation of HTSC Elements,” IEEE Trans. Appl.
Supercond., Vol.16, No. 2, June 2006.
[7] M. C. Ahn, H. Kang, D. K. Bae, D. K. Park, Y. S. Yoon, S. J. Lee, and T. K. Ko, “The Short-
Circuit Characteristics of a DC Reactor Type Superconducting Fault Current Limiter With Fault
Detection and Signal control of the Power Converter,”IEEE Trans. Appl. Superconduct., Vol. 15,
No. 2, June. 2005
[8] B. Gromoll, G. Ries, W. Schmidt, H.-P. Kraemer, B. Seebacher, B. Utz, R. Nies, H.-W.
eumueller, E. Balzer, S. Fischer, and B. Heismann, “Resistive fault current limiters with YBCO
films-100 kVA functional model,” IEEE Trans. Appl. Superconduct., vol. 9, pp. 656–659,
Jun.1999.
[9] Lin Ye, K.P. Juengst, “Modeling and simulations of resistive type superconducting fault
current limiter,” IEEE Trans. Appl. Superconduct. 14 (June (2)) (2004) 839–842.
[10] A. Gyore, A. Szalay, V. Sokolovsky, and W. Gawalek, “Improved design and system
approach of a three phase inductive HTS fault current limiter for a 12 kVA synchronous
generator,” IEEE Trans. Appl. Superconduct., vol. 13, pp. 2000–2003, Jun. 2003.
[11] M. T. Hagh and M. Abapour, “Nonsuperconducting Fault Current Limiter With Controlling
the Magnitudes of Fault Currents,” IEEE Trans. Power Electronics, Vol.24, pp. 613–619, March
2009
[12] E.Calixte, Y.Yokomizu, T.Matsumura and H.Fujita “Reduction of Rating Required for
Circuit Breakers by Employing Series-Connected Fault Current Limiter,”Generation,
Transmission and Distributin IEE Proceedings, pp.36-42, Jan 2004
ISBN-13: 978-1537584836
www.iaetsd.in
Proceedings of ICAER-2016
©IAETSD 201670

Contenu connexe

Tendances

Surge current protection using superconductor ppt mahesh
Surge current protection using superconductor ppt maheshSurge current protection using superconductor ppt mahesh
Surge current protection using superconductor ppt mahesh
Kuldeep Singh
 
Surge arrester and surge suppressor on transformer
Surge arrester and surge suppressor on transformerSurge arrester and surge suppressor on transformer
Surge arrester and surge suppressor on transformer
VIKAS KUMAR MANJHI
 

Tendances (20)

Inductive shielded superconducting fault current limiter: test results for sc...
Inductive shielded superconducting fault current limiter: test results for sc...Inductive shielded superconducting fault current limiter: test results for sc...
Inductive shielded superconducting fault current limiter: test results for sc...
 
Technical seminar
Technical seminarTechnical seminar
Technical seminar
 
Surge current protection using superconductor ppt mahesh
Surge current protection using superconductor ppt maheshSurge current protection using superconductor ppt mahesh
Surge current protection using superconductor ppt mahesh
 
Surge current protection using super conductors
Surge current protection using super conductorsSurge current protection using super conductors
Surge current protection using super conductors
 
Super conductors as surge current protectors
Super conductors as surge current protectorsSuper conductors as surge current protectors
Super conductors as surge current protectors
 
Modeling and test validation of a 15 kV - 24 MVA superconducting fault curren...
Modeling and test validation of a 15 kV - 24 MVA superconducting fault curren...Modeling and test validation of a 15 kV - 24 MVA superconducting fault curren...
Modeling and test validation of a 15 kV - 24 MVA superconducting fault curren...
 
Feasibility Analysis of the Positioning of Superconducting Fault Current Limi...
Feasibility Analysis of the Positioning of Superconducting Fault Current Limi...Feasibility Analysis of the Positioning of Superconducting Fault Current Limi...
Feasibility Analysis of the Positioning of Superconducting Fault Current Limi...
 
Protection system
Protection systemProtection system
Protection system
 
Protection against over voltage
Protection against over voltageProtection against over voltage
Protection against over voltage
 
New bhgat ram ppt 7793005660
New bhgat ram ppt 7793005660New bhgat ram ppt 7793005660
New bhgat ram ppt 7793005660
 
Introduction to switchgear
Introduction to switchgearIntroduction to switchgear
Introduction to switchgear
 
Surge arrester and surge suppressor on transformer
Surge arrester and surge suppressor on transformerSurge arrester and surge suppressor on transformer
Surge arrester and surge suppressor on transformer
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
Omprakash mahawar ppt
Omprakash mahawar pptOmprakash mahawar ppt
Omprakash mahawar ppt
 
Earthing
EarthingEarthing
Earthing
 
Presentation on substations
Presentation on substationsPresentation on substations
Presentation on substations
 
400 KV GSS HEERAPURA, JAIPUR
400 KV GSS HEERAPURA, JAIPUR400 KV GSS HEERAPURA, JAIPUR
400 KV GSS HEERAPURA, JAIPUR
 
Power Transformer Parts And Functions
Power Transformer Parts And FunctionsPower Transformer Parts And Functions
Power Transformer Parts And Functions
 
Panel designing
Panel designingPanel designing
Panel designing
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 

En vedette

Ppt of ehv ac transmission
Ppt of ehv ac transmissionPpt of ehv ac transmission
Ppt of ehv ac transmission
Sumit Kumar
 

En vedette (16)

Ppt super
Ppt superPpt super
Ppt super
 
Surge current protection using superconductor ppt
Surge current protection using superconductor pptSurge current protection using superconductor ppt
Surge current protection using superconductor ppt
 
superconductivity and its applications
superconductivity and its applicationssuperconductivity and its applications
superconductivity and its applications
 
Saturated core fault current limiter field experience at a distribution subst...
Saturated core fault current limiter field experience at a distribution subst...Saturated core fault current limiter field experience at a distribution subst...
Saturated core fault current limiter field experience at a distribution subst...
 
Solar Ice Production
Solar Ice ProductionSolar Ice Production
Solar Ice Production
 
Solar Ice Maker
Solar Ice MakerSolar Ice Maker
Solar Ice Maker
 
Guest speaker presentation at 'Seminar Offshore Wind Energy' UGent – June 201...
Guest speaker presentation at 'Seminar Offshore Wind Energy' UGent – June 201...Guest speaker presentation at 'Seminar Offshore Wind Energy' UGent – June 201...
Guest speaker presentation at 'Seminar Offshore Wind Energy' UGent – June 201...
 
D-SMES
D-SMESD-SMES
D-SMES
 
Superconducting magnetic energy storage
Superconducting magnetic energy storageSuperconducting magnetic energy storage
Superconducting magnetic energy storage
 
Offshore wind energy in India Overview
Offshore wind energy in India OverviewOffshore wind energy in India Overview
Offshore wind energy in India Overview
 
The Connected Car: Driving Towards the Future
The Connected Car: Driving Towards the FutureThe Connected Car: Driving Towards the Future
The Connected Car: Driving Towards the Future
 
Superconductors
SuperconductorsSuperconductors
Superconductors
 
Ppt of ehv ac transmission
Ppt of ehv ac transmissionPpt of ehv ac transmission
Ppt of ehv ac transmission
 
bio battery ppt
bio battery pptbio battery ppt
bio battery ppt
 
SUPERCONDUCTING MAGNETIC ENERGY STORAGE SYSTEM (SMES)
SUPERCONDUCTING  MAGNETIC ENERGY  STORAGE  SYSTEM  (SMES)SUPERCONDUCTING  MAGNETIC ENERGY  STORAGE  SYSTEM  (SMES)
SUPERCONDUCTING MAGNETIC ENERGY STORAGE SYSTEM (SMES)
 
Anlysis of a pmsg based offshore wind farm fed to a onshore grid through hybr...
Anlysis of a pmsg based offshore wind farm fed to a onshore grid through hybr...Anlysis of a pmsg based offshore wind farm fed to a onshore grid through hybr...
Anlysis of a pmsg based offshore wind farm fed to a onshore grid through hybr...
 

Similaire à iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant intrusion of

Simulation, control and analysis of hts resistive and power electronic fcl
Simulation, control and analysis of hts resistive and power electronic fclSimulation, control and analysis of hts resistive and power electronic fcl
Simulation, control and analysis of hts resistive and power electronic fcl
IAEME Publication
 

Similaire à iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant intrusion of (20)

Surge Protection Devices Paper (SPD) SM54
Surge Protection Devices Paper (SPD) SM54Surge Protection Devices Paper (SPD) SM54
Surge Protection Devices Paper (SPD) SM54
 
98X- didier2013.pdf
98X- didier2013.pdf98X- didier2013.pdf
98X- didier2013.pdf
 
Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...
 
Aircraft Electrical Power Generation & Distribution System Units Through an A...
Aircraft Electrical Power Generation & Distribution System Units Through an A...Aircraft Electrical Power Generation & Distribution System Units Through an A...
Aircraft Electrical Power Generation & Distribution System Units Through an A...
 
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdfAzizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
 
Transient Recovery Voltage Test Results of a 25 MVA Saturable-Core Fault Curr...
Transient Recovery Voltage Test Results of a 25 MVA Saturable-Core Fault Curr...Transient Recovery Voltage Test Results of a 25 MVA Saturable-Core Fault Curr...
Transient Recovery Voltage Test Results of a 25 MVA Saturable-Core Fault Curr...
 
fault
faultfault
fault
 
Simulation, control and analysis of hts resistive and power electronic fcl
Simulation, control and analysis of hts resistive and power electronic fclSimulation, control and analysis of hts resistive and power electronic fcl
Simulation, control and analysis of hts resistive and power electronic fcl
 
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
 
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
 
Solid State Fault Current Limiter for Improvement of Smart Grid Performance
Solid State Fault Current Limiter for Improvement of Smart Grid PerformanceSolid State Fault Current Limiter for Improvement of Smart Grid Performance
Solid State Fault Current Limiter for Improvement of Smart Grid Performance
 
Improvement Transient Stability of Fixed Speed Wind Energy Conversion System ...
Improvement Transient Stability of Fixed Speed Wind Energy Conversion System ...Improvement Transient Stability of Fixed Speed Wind Energy Conversion System ...
Improvement Transient Stability of Fixed Speed Wind Energy Conversion System ...
 
Hq3513331337
Hq3513331337Hq3513331337
Hq3513331337
 
Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...
 
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfH7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
 
Performance Analysis of Three Phase Cascaded H-Bridge Multi Level Inverter fo...
Performance Analysis of Three Phase Cascaded H-Bridge Multi Level Inverter fo...Performance Analysis of Three Phase Cascaded H-Bridge Multi Level Inverter fo...
Performance Analysis of Three Phase Cascaded H-Bridge Multi Level Inverter fo...
 
IJET-V3I1P8
IJET-V3I1P8IJET-V3I1P8
IJET-V3I1P8
 
Short-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.pptShort-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.ppt
 
Transient Stability of Power System using Facts Device-UPFC
Transient Stability of Power System using Facts Device-UPFCTransient Stability of Power System using Facts Device-UPFC
Transient Stability of Power System using Facts Device-UPFC
 
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
 

Plus de Iaetsd Iaetsd

iaetsd Survey on cooperative relay based data transmission
iaetsd Survey on cooperative relay based data transmissioniaetsd Survey on cooperative relay based data transmission
iaetsd Survey on cooperative relay based data transmission
Iaetsd Iaetsd
 
iaetsd Software defined am transmitter using vhdl
iaetsd Software defined am transmitter using vhdliaetsd Software defined am transmitter using vhdl
iaetsd Software defined am transmitter using vhdl
Iaetsd Iaetsd
 
iaetsd Health monitoring system with wireless alarm
iaetsd Health monitoring system with wireless alarmiaetsd Health monitoring system with wireless alarm
iaetsd Health monitoring system with wireless alarm
Iaetsd Iaetsd
 
iaetsd Equalizing channel and power based on cognitive radio system over mult...
iaetsd Equalizing channel and power based on cognitive radio system over mult...iaetsd Equalizing channel and power based on cognitive radio system over mult...
iaetsd Equalizing channel and power based on cognitive radio system over mult...
Iaetsd Iaetsd
 
iaetsd Economic analysis and re design of driver’s car seat
iaetsd Economic analysis and re design of driver’s car seatiaetsd Economic analysis and re design of driver’s car seat
iaetsd Economic analysis and re design of driver’s car seat
Iaetsd Iaetsd
 
iaetsd Design of slotted microstrip patch antenna for wlan application
iaetsd Design of slotted microstrip patch antenna for wlan applicationiaetsd Design of slotted microstrip patch antenna for wlan application
iaetsd Design of slotted microstrip patch antenna for wlan application
Iaetsd Iaetsd
 
REVIEW PAPER- ON ENHANCEMENT OF HEAT TRANSFER USING RIBS
REVIEW PAPER- ON ENHANCEMENT OF HEAT TRANSFER USING RIBSREVIEW PAPER- ON ENHANCEMENT OF HEAT TRANSFER USING RIBS
REVIEW PAPER- ON ENHANCEMENT OF HEAT TRANSFER USING RIBS
Iaetsd Iaetsd
 
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...
Iaetsd Iaetsd
 
iirdem The Livable Planet – A Revolutionary Concept through Innovative Street...
iirdem The Livable Planet – A Revolutionary Concept through Innovative Street...iirdem The Livable Planet – A Revolutionary Concept through Innovative Street...
iirdem The Livable Planet – A Revolutionary Concept through Innovative Street...
Iaetsd Iaetsd
 
iirdem Surveillance aided robotic bird
iirdem Surveillance aided robotic birdiirdem Surveillance aided robotic bird
iirdem Surveillance aided robotic bird
Iaetsd Iaetsd
 
iirdem Growing India Time Monopoly – The Key to Initiate Long Term Rapid Growth
iirdem Growing India Time Monopoly – The Key to Initiate Long Term Rapid Growthiirdem Growing India Time Monopoly – The Key to Initiate Long Term Rapid Growth
iirdem Growing India Time Monopoly – The Key to Initiate Long Term Rapid Growth
Iaetsd Iaetsd
 
iirdem Design of Efficient Solar Energy Collector using MPPT Algorithm
iirdem Design of Efficient Solar Energy Collector using MPPT Algorithmiirdem Design of Efficient Solar Energy Collector using MPPT Algorithm
iirdem Design of Efficient Solar Energy Collector using MPPT Algorithm
Iaetsd Iaetsd
 
iirdem CRASH IMPACT ATTENUATOR (CIA) FOR AUTOMOBILES WITH THE ADVOCATION OF M...
iirdem CRASH IMPACT ATTENUATOR (CIA) FOR AUTOMOBILES WITH THE ADVOCATION OF M...iirdem CRASH IMPACT ATTENUATOR (CIA) FOR AUTOMOBILES WITH THE ADVOCATION OF M...
iirdem CRASH IMPACT ATTENUATOR (CIA) FOR AUTOMOBILES WITH THE ADVOCATION OF M...
Iaetsd Iaetsd
 
iirdem ADVANCING OF POWER MANAGEMENT IN HOME WITH SMART GRID TECHNOLOGY AND S...
iirdem ADVANCING OF POWER MANAGEMENT IN HOME WITH SMART GRID TECHNOLOGY AND S...iirdem ADVANCING OF POWER MANAGEMENT IN HOME WITH SMART GRID TECHNOLOGY AND S...
iirdem ADVANCING OF POWER MANAGEMENT IN HOME WITH SMART GRID TECHNOLOGY AND S...
Iaetsd Iaetsd
 
iaetsd Shared authority based privacy preserving protocol
iaetsd Shared authority based privacy preserving protocoliaetsd Shared authority based privacy preserving protocol
iaetsd Shared authority based privacy preserving protocol
Iaetsd Iaetsd
 
iaetsd Secured multiple keyword ranked search over encrypted databases
iaetsd Secured multiple keyword ranked search over encrypted databasesiaetsd Secured multiple keyword ranked search over encrypted databases
iaetsd Secured multiple keyword ranked search over encrypted databases
Iaetsd Iaetsd
 
iaetsd Robots in oil and gas refineries
iaetsd Robots in oil and gas refineriesiaetsd Robots in oil and gas refineries
iaetsd Robots in oil and gas refineries
Iaetsd Iaetsd
 
iaetsd Modeling of solar steam engine system using parabolic
iaetsd Modeling of solar steam engine system using paraboliciaetsd Modeling of solar steam engine system using parabolic
iaetsd Modeling of solar steam engine system using parabolic
Iaetsd Iaetsd
 

Plus de Iaetsd Iaetsd (20)

iaetsd Survey on cooperative relay based data transmission
iaetsd Survey on cooperative relay based data transmissioniaetsd Survey on cooperative relay based data transmission
iaetsd Survey on cooperative relay based data transmission
 
iaetsd Software defined am transmitter using vhdl
iaetsd Software defined am transmitter using vhdliaetsd Software defined am transmitter using vhdl
iaetsd Software defined am transmitter using vhdl
 
iaetsd Health monitoring system with wireless alarm
iaetsd Health monitoring system with wireless alarmiaetsd Health monitoring system with wireless alarm
iaetsd Health monitoring system with wireless alarm
 
iaetsd Equalizing channel and power based on cognitive radio system over mult...
iaetsd Equalizing channel and power based on cognitive radio system over mult...iaetsd Equalizing channel and power based on cognitive radio system over mult...
iaetsd Equalizing channel and power based on cognitive radio system over mult...
 
iaetsd Economic analysis and re design of driver’s car seat
iaetsd Economic analysis and re design of driver’s car seatiaetsd Economic analysis and re design of driver’s car seat
iaetsd Economic analysis and re design of driver’s car seat
 
iaetsd Design of slotted microstrip patch antenna for wlan application
iaetsd Design of slotted microstrip patch antenna for wlan applicationiaetsd Design of slotted microstrip patch antenna for wlan application
iaetsd Design of slotted microstrip patch antenna for wlan application
 
REVIEW PAPER- ON ENHANCEMENT OF HEAT TRANSFER USING RIBS
REVIEW PAPER- ON ENHANCEMENT OF HEAT TRANSFER USING RIBSREVIEW PAPER- ON ENHANCEMENT OF HEAT TRANSFER USING RIBS
REVIEW PAPER- ON ENHANCEMENT OF HEAT TRANSFER USING RIBS
 
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...
 
Fabrication of dual power bike
Fabrication of dual power bikeFabrication of dual power bike
Fabrication of dual power bike
 
Blue brain technology
Blue brain technologyBlue brain technology
Blue brain technology
 
iirdem The Livable Planet – A Revolutionary Concept through Innovative Street...
iirdem The Livable Planet – A Revolutionary Concept through Innovative Street...iirdem The Livable Planet – A Revolutionary Concept through Innovative Street...
iirdem The Livable Planet – A Revolutionary Concept through Innovative Street...
 
iirdem Surveillance aided robotic bird
iirdem Surveillance aided robotic birdiirdem Surveillance aided robotic bird
iirdem Surveillance aided robotic bird
 
iirdem Growing India Time Monopoly – The Key to Initiate Long Term Rapid Growth
iirdem Growing India Time Monopoly – The Key to Initiate Long Term Rapid Growthiirdem Growing India Time Monopoly – The Key to Initiate Long Term Rapid Growth
iirdem Growing India Time Monopoly – The Key to Initiate Long Term Rapid Growth
 
iirdem Design of Efficient Solar Energy Collector using MPPT Algorithm
iirdem Design of Efficient Solar Energy Collector using MPPT Algorithmiirdem Design of Efficient Solar Energy Collector using MPPT Algorithm
iirdem Design of Efficient Solar Energy Collector using MPPT Algorithm
 
iirdem CRASH IMPACT ATTENUATOR (CIA) FOR AUTOMOBILES WITH THE ADVOCATION OF M...
iirdem CRASH IMPACT ATTENUATOR (CIA) FOR AUTOMOBILES WITH THE ADVOCATION OF M...iirdem CRASH IMPACT ATTENUATOR (CIA) FOR AUTOMOBILES WITH THE ADVOCATION OF M...
iirdem CRASH IMPACT ATTENUATOR (CIA) FOR AUTOMOBILES WITH THE ADVOCATION OF M...
 
iirdem ADVANCING OF POWER MANAGEMENT IN HOME WITH SMART GRID TECHNOLOGY AND S...
iirdem ADVANCING OF POWER MANAGEMENT IN HOME WITH SMART GRID TECHNOLOGY AND S...iirdem ADVANCING OF POWER MANAGEMENT IN HOME WITH SMART GRID TECHNOLOGY AND S...
iirdem ADVANCING OF POWER MANAGEMENT IN HOME WITH SMART GRID TECHNOLOGY AND S...
 
iaetsd Shared authority based privacy preserving protocol
iaetsd Shared authority based privacy preserving protocoliaetsd Shared authority based privacy preserving protocol
iaetsd Shared authority based privacy preserving protocol
 
iaetsd Secured multiple keyword ranked search over encrypted databases
iaetsd Secured multiple keyword ranked search over encrypted databasesiaetsd Secured multiple keyword ranked search over encrypted databases
iaetsd Secured multiple keyword ranked search over encrypted databases
 
iaetsd Robots in oil and gas refineries
iaetsd Robots in oil and gas refineriesiaetsd Robots in oil and gas refineries
iaetsd Robots in oil and gas refineries
 
iaetsd Modeling of solar steam engine system using parabolic
iaetsd Modeling of solar steam engine system using paraboliciaetsd Modeling of solar steam engine system using parabolic
iaetsd Modeling of solar steam engine system using parabolic
 

Dernier

DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
MayuraD1
 
Verification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptxVerification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptx
chumtiyababu
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
Kamal Acharya
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
mphochane1998
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ssuser89054b
 

Dernier (20)

COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxOrlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
 
Wadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptxWadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptx
 
Moment Distribution Method For Btech Civil
Moment Distribution Method For Btech CivilMoment Distribution Method For Btech Civil
Moment Distribution Method For Btech Civil
 
Verification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptxVerification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptx
 
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKARHAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
GEAR TRAIN- BASIC CONCEPTS AND WORKING PRINCIPLE
GEAR TRAIN- BASIC CONCEPTS AND WORKING PRINCIPLEGEAR TRAIN- BASIC CONCEPTS AND WORKING PRINCIPLE
GEAR TRAIN- BASIC CONCEPTS AND WORKING PRINCIPLE
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 

iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant intrusion of

  • 1. Effect of Superconducting Fault Current Limiter (SFCL) on Triumphant Intrusion of Circuit Breakers R. AKSHAYA K. BHARGAVA IV B.Tech, EEE Electrical Engineer, Ph. No: 09553406942 GERDAU STEEL INDIA PVT LTD, INDIA. Email ID: akkidaddy96@gmail.com Email ID: kwtlbhargava.8@gmail.com BHEEMA INSTITUTE OF TECHNOLOGY & SCIENCE (JNTUA), ADONI-518301, KURNOOL DISTRICT, ANDHRA PRADESH. ABSTRACT: The applications of fault current limiter (FCL) will not only decrease the stress on network equipments, but can also offer a link in improving the reliability of the power system. The infiltration of distributed generation systems can result in increasing the short circuit current level. There are various types of FLC’s that are made up of different superconducting materials with a wide range of designs. Among these mainly used are resistive type, inductive type and bridge type SFCL .In this paper, the transient recovery voltage(TRV) analysis, based on the electromagnetic transient program(EMTP),is used to investigate the behavior of the three types of SFCL’s installed in an electrical distribution grid. The results simulated shows that TRV can be damped during the fault clearing period of resistive and bridge type SFCL. KEYWORDS: Superconducting Fault Current Limiter, Transient Recovery Voltage, Rate of Rise of Recovery Voltage (RRRV), Circuit Breaker INTRODUCTION: With the growth of the demand for electric power, the electric power systems are interconnected each other to increase the reliability of power supply. However, fault current levels increase beyond capabilities of existing equipments in some points of grids. Therefore, all equipments especially, circuit breakers have to have a short circuit rating capable of withstanding this level. Usually, handling these increasing fault currents requires the costly replacement of equipments or imposition of changes in the configuration. But, the splitting of substation may decrease the operational flexibility and system reliability. An alternative solution is the usage of FCLs to reduce the fault current to withstanding level of existing circuit breakers. So, the existing equipments can still be used to protect the power system [1]-[2]. Also after being limited by the FCL, the current is interrupted at its current zero by a circuit breaker. After the interruption of the fault current, a transient recovery voltage (TRV) appears across the contacts of the circuit breaker. To perform a successful interruption, the circuit breaker must withstand against the TRV without re-establishment of the arc between the contacts. An ideal FCL should have the following features [1-3]: • Zero impedance and power losses at normal operation, ISBN-13: 978-1537584836 www.iaetsd.in Proceedings of ICAER-2016 ©IAETSD 201660
  • 2. • Large impedance in fault conditions, • Quick appearance of impedance when fault occurs, • Fast recovery after fault removal, • Reliable current limitation at determined fault current and • Good reliability. Superconducting Fault Current Limiter (SFCL) offers a solution to these problems with many significant advantages. The application of the SFCL would not only decrease the stress on device but also offer an interconnection to secure the network. They can improve reliability and stability of power systems by reducing the fault current. There are several kinds of SFCLs, which can be classified in three types such as the resistive type, the inductive type and bridge type SFCL. Each type of SFCL has its merits and demerits. Many studies have focused on the topology and capability of SFCLs. The inductive type SFCL is able to suppress the voltage drop and limit the fault current. The resistive type SFCL can consume the energy of the fault current and limit it. This capability can improve the power system stability. The bridge type SFCL is a kind of SFCL, which has zero impedance under the normal condition and large impedance under fault condition. Its advantage is the fault current limitation without any delay and smoothing the surge current waveform. But, it cannot limit the steady state fault current. Among the parameters of the FCL, the magnitude of the limiting impedance and its merits affects the current-limiting performance of the FCL much more than the other parameters. In other words, depending upon the kind of the FCL and its merits, the insertion of the FCL in to the power system can result in more severe interrupting problems. Therefore, it is important to study the interrupting behavior of circuit breakers in the presence of the kinds of FCLs. In this paper, a comparative study of the interrupting behavior of circuit breakers in the presence of three types such as the resistive type, the inductive type and bridge type SFCL have been carried out. CONCEPT OF SFCL: Several designs have been considered for the SFCL which are based on different superconducting materials. The resistive SFCL is simply connected in series with the network; the inductive SFCL is based on a transformer with a superconducting shielding tube in the secondary. The bridge-type SFCL consists of a diode-bridge and superconductor as limiting function. A. Resistive SFCL Model: A resistive SFCL utilizes resistance increase upon quench of a superconductor. It has advantages such as simpler structure, smaller size, and possibly lower capital cost than other types. During normal operation, the superconducting element is in its superconducting state and the normal load current passes with theoretically no loss. In the case of a short circuit, the circuit current rises sharply and the superconductor undergoes a transition to its normal state, so a certain value of nonlinear resistance is created by self-sensing and self-triggering, thus limiting the fault current level. A non-linear resistive model was used to analyze the features of a resistive FCL prototype with EMTP simulator in this paper. Its behavior under normal operation and short-circuit conditions in a test circuit was investigated by computer simulation using the EMTP program. As ISBN-13: 978-1537584836 www.iaetsd.in Proceedings of ICAER-2016 ©IAETSD 201661
  • 3. the scaled I–V curve shown in Fig. 1, the resistance variation is represented by the gradient of the curve [9-10]. Fig 1. V-I curve of resistive FCL B. Inductive SFCL Model: In the model of the inductive FCL, a capacitance CP , is connected in parallel with the limiting coil to simulate a stray capacitance appearing in the winding of the coil. The stray capacitance CP , has so much higher impedance than the inductance LFCL that the impedance ZFCL is equal to the impedance of the inductance LFCL . Fig. 2 shows the inductive SFCL model, used in this paper [11]. Fig 2. Inductive SFCL model B. Bridge-Type SFCL Model: Fig. 3 shows the three-phase bridge-type SFCL, which consists of the superconducting coil (SC), series transformer and diode bridge circuit. The diode bridge converts three-phase AC to DC current, which flows through the super- conducting coil. The current through the primary and secondary winding of transformer are defined as ip , is , respectively, and the ratio of transformer is N, as follows: ISBN-13: 978-1537584836 www.iaetsd.in Proceedings of ICAER-2016 ©IAETSD 201662
  • 4. Fig 3. Bridge-type SFCL schematic diagram Fig 4. SC and fault current during fault and normal operation with using bridge-type SFCL. FCL IN DISTRIBUTION SYSTEM: Most of the distribution systems have radial form. As a result in any branch of a radial system, power only flows in one direction. The distribution voltage levels are in the range of 10kV to 30kV. It can be expected that there will be interactions between the FCL and power system, if FCL is placed in the grid. A typical distribution system is represented in Fig. 5. The source impedance includes the transformer impedance and the upstream short-circuit impedance. Parallel feeders are connected to the Point of Common Coupling (PCC). The bus is supplied by a substation transformer from a 110 kV network. The upstream source system is modeled as an infinite bus and the source impedance is consists of an equivalent resistance and inductance connected to the local distribution substation. The load is modeled as a lumped series R-L-C branch with a power factor of 0.886. A 3-phase short circuit fault is simulated at the load side, on feeder 2 (F2), as shown in Fig. 5. After one cycles, the circuit breaker opened to clear the fault. The circuit breaker is modeled as an ideal time-controlled switch with a parallel capacitance. This capacitance is the total ISBN-13: 978-1537584836 www.iaetsd.in Proceedings of ICAER-2016 ©IAETSD 201663
  • 5. capacitance of the source side circuit, which includes the stray capacitance of circuit breaker to the ground. SIMULATION RESULTS: The simulation has been carried out with a fault starting at t=140ms. The circuit breaker has been opened after 1 cycle. The total simulation time was 200ms according to the circuit breaker opening time, and the simulation step is 1μs. The parameters for the simulation have been listed in table 1. Fig. 5. Schematic diagram of study system TABLE I. SYSTEM PARAMETERS When the circuit breaker attempts to interrupt the limited fault current, an over voltage is developed across contacts [13]. This voltage is called Transient Recovery Voltage (TRV) of the circuit breaker. Circuit breakers may fail to interrupt fault currents when power systems have transient recovery voltage levels, which exceed the rating of circuit breakers. The Rate of Raise of Recovery Voltage (RRRV) is an important parameter in the power system operation, presented in IEEE C37.41 standard. The simulations by the Electro-Magnetic Transients Program (ATP-EMTP) was performed to determine the instantaneous values of the transient recovery voltage VCB appearing PARAMETER VALUE Supply Voltage 110kV,50Hz Step down Transformer 110/15kV,10MVA Bridge-type FCL Inductance of SC 50 mH Inductive SFCL Inductance (LFCL ) 64.4 mH Stray Capacitance (Cp) 1uF Resistive SFCL Maximum Resistance (Rmax ) 20 Ω Load Load 1 P=6kW,PF=0.9 Load 2 P=5kW,PF=0.88 ISBN-13: 978-1537584836 www.iaetsd.in Proceedings of ICAER-2016 ©IAETSD 201664
  • 6. after current zero and the current flowing ICB through the contacts of the circuit breaker before current zero for following cases: A. Without Using Any FCL: Fig. 6 shows the current flowing through the contacts of the circuit breaker before current zero without FCL application. It is obvious in Fig. 6, which the peak value of the fault current is about 3500A, which can damage the system devices. Fig. 7 shows the circuit breaker’s TRV without installation of FCL. The TRV in the absence of the FCL reaches a peak value of 24 kV. The initial transient recovery voltage (ITRV) in the absence of the FCL reaches a first peak value of 23.7 kV during 0.0044s. From these values, the RRRV was determined to be 55 kV/us. Fig. 6. Circuit breaker current without using any FCL ISBN-13: 978-1537584836 www.iaetsd.in Proceedings of ICAER-2016 ©IAETSD 201665
  • 7. Fig. 7. Circuit breaker TRV without using any FCL B. With Using Inductive SFCL: Fig. 8 shows the current flowing through the contacts of the circuit breaker before current zero with inductive SFCL application. It is obvious in Fig. 8, which the peak value of the fault current is limited about 800A. Application of inductive SFCL creates an asymmetrical short-circuit current. Fig. 9 shows the circuit breakers TRV with application of inductive SFCL. The TRV reaches a peak value of 30 kV. The initial transient recovery voltage (ITRV) with inductive SFCL reaches a first peak value of 10 kV during 0.00004s. From these values, the RRRV was determined to be 250 kV/us. Fig. 8. Circuit breaker current with using inductive SFCL ISBN-13: 978-1537584836 www.iaetsd.in Proceedings of ICAER-2016 ©IAETSD 201666
  • 8. Fig. 9. Circuit breaker TRV with using inductive SFCL C. With Using Resistive SFCL Fig. 10 shows the current flowing through the contacts of the circuit breaker before current zero with resistive SFCL application. It is obvious in Fig. 10, which the peak value of the fault current is limited about 650A. Application of resistive SFCL eliminates the asymmetrical component of fault current. Fig. 11 shows the circuit breakers TRV with application of resistive SFCL. The TRV reaches a peak value of 16 kV. The initial transient recovery voltage (ITRV) with inductive SFCL reaches a first peak value of 7 kV during 0.0009s. From these values, the RRRV was decreased to 8 kV/us. Fig. 10. Circuit breaker current with using resistive SFCL Fig. 11. Circuit breaker TRV with using Resistive SFCL ISBN-13: 978-1537584836 www.iaetsd.in Proceedings of ICAER-2016 ©IAETSD 201667
  • 9. D. With Using Bridge-SFCL Fig. 12 shows the current flowing through the contacts of the circuit breaker before current zero with bridge-type SFCL application. It is obvious in Fig. 12, which the peak value of the fault current is limited about 450A, but the fault current increases with a constant rate. Fig. 13 shows the circuit breaker’s TRV with application of bridge-type SFCL. The TRV reaches a peak value of 20 kV. The initial transient recovery voltage (ITRV) with inductive SFCL reaches a first peak value of 7.5 kV during 0.00029s. From these values, the RRRV was decreased to 24 kV/us. Fig. 12. The Circuit Breaker Current with Using Bridge-Type SFCL Fig. 13. The Circuit Breaker transient Recovery Voltage with using Bridge-Type SFCL ISBN-13: 978-1537584836 www.iaetsd.in Proceedings of ICAER-2016 ©IAETSD 201668
  • 10. CONCLUSION: In this paper, the effect of three types of SFCL on transient recovery voltage of circuit breaker has been studied. The simulation results show that not only fault current has been limited, but also the TRV and RRRV of the circuit breaker has been reduced effectively by using the resistive SFCL and bridge type SFCL. By using inductive SFCL, the fault current has been limited, but the TRV and RRRV of the circuit breaker has been increased. Also, by using the resistive SFCL, the TRV and RRRV of circuit breaker was lower than the other types of SFCL. PROPERTIES OF SFCL: 1. Self activating 2. Low maintenance 3. High impedance in fault operation 4. Low impedance in normal operation 5. Limits fault current before first peak 6. Environmentally friendly ADVANTAGES: 1. Over 100 times faster response time 2. 10 to 20 times shorter recovery time 3. Time adjustable response functions 4. 1000 times number of full power protection cycles APPLICATIONS: Three main application areas are: 1. Fault current limiter in main position: The fault current limiter FCL protects the entire bus. 2. Fault current limiter in feeder position: The fault current limiter FCL protects an individual circuit on the bus, under rated equipment can be selectively protected as needed in this manner. 3. Fault current limiter in bus tie position: Two buses are tied, yet a faulted bus receives the full fault current of only one transformer. Finally the fault current limiter FCL protects the entire bus. DISADVANTAGES: 1. To show any properties, and be of any use they must operate at critical temperature which is very costly. 2. They emit strong magnetic fields which effects human causing blindness, brain cancer etc. ISBN-13: 978-1537584836 www.iaetsd.in Proceedings of ICAER-2016 ©IAETSD 201669
  • 11. REFERENCES: [1] CIGRE WG A3.10, “Fault Current Limiters Report on the Activities of CIGRE WG 3.16,”CIGRE Technical Brochure, 2006. [2] CIGRE WG A3.10: “Fault Current Limiters in High Electrical Medium and Voltage Systems”, CIGRE Technical Brochure, No. 239, 2003. [3] E.Calixte, Y.Yokomizu, T.Matsumura and H.Fujita, “Reduction in Severity of Circuit Breaker Duty Under Generator-Fed Fault Condition by Means of Resistive Fault Current Limiter,” International Journal of Power Energy System, Power Con Special Issue 2004, pp.24- 31 [4] L. Z. Lin, K.P. Juengst, “Application studies of superconducting fault current limiter in electric power systems ,” IEEE Trans. Appl. Superconduct. 12 (March (1)) (2002) 900–903. [5] K . Arai, H. Tanaka, M. Inaba, H. Arai, T. Ishigohka, M. Furuse, and M. Umeda, “Test of Resonance-Type Superconducting Fault Current Limiter,” IEEE Trans. Appl. Supercond., Vol.16, No. 2, June 2006 [6] S.H. Lim, H.S. Choi, and B.S. Han, “Fault Current Limiting Characteristics of DC Dual Reactor Type SFCL Using Switching Operation of HTSC Elements,” IEEE Trans. Appl. Supercond., Vol.16, No. 2, June 2006. [7] M. C. Ahn, H. Kang, D. K. Bae, D. K. Park, Y. S. Yoon, S. J. Lee, and T. K. Ko, “The Short- Circuit Characteristics of a DC Reactor Type Superconducting Fault Current Limiter With Fault Detection and Signal control of the Power Converter,”IEEE Trans. Appl. Superconduct., Vol. 15, No. 2, June. 2005 [8] B. Gromoll, G. Ries, W. Schmidt, H.-P. Kraemer, B. Seebacher, B. Utz, R. Nies, H.-W. eumueller, E. Balzer, S. Fischer, and B. Heismann, “Resistive fault current limiters with YBCO films-100 kVA functional model,” IEEE Trans. Appl. Superconduct., vol. 9, pp. 656–659, Jun.1999. [9] Lin Ye, K.P. Juengst, “Modeling and simulations of resistive type superconducting fault current limiter,” IEEE Trans. Appl. Superconduct. 14 (June (2)) (2004) 839–842. [10] A. Gyore, A. Szalay, V. Sokolovsky, and W. Gawalek, “Improved design and system approach of a three phase inductive HTS fault current limiter for a 12 kVA synchronous generator,” IEEE Trans. Appl. Superconduct., vol. 13, pp. 2000–2003, Jun. 2003. [11] M. T. Hagh and M. Abapour, “Nonsuperconducting Fault Current Limiter With Controlling the Magnitudes of Fault Currents,” IEEE Trans. Power Electronics, Vol.24, pp. 613–619, March 2009 [12] E.Calixte, Y.Yokomizu, T.Matsumura and H.Fujita “Reduction of Rating Required for Circuit Breakers by Employing Series-Connected Fault Current Limiter,”Generation, Transmission and Distributin IEE Proceedings, pp.36-42, Jan 2004 ISBN-13: 978-1537584836 www.iaetsd.in Proceedings of ICAER-2016 ©IAETSD 201670