SlideShare une entreprise Scribd logo
1  sur  48
Télécharger pour lire hors ligne
A Unified PID Control
Methodology to Meet
Plant Objectives
Greg McMillan
CDI Process & Industrial
Hector Torres
Eastman Chemical
ISA Books
Topics
 PID Basics (contribution of each mode)
 Process and Loop Dynamics
 Ultimate Limits for Disturbance Rejection
 Practical Limits for Disturbance Rejection
 PID Form and Structure Options
 Setpoint Rate Limits and Lead-Lag
 Setpoint Rise Time
 Output Tracking Opportunities
 Enhanced PID for Wireless, Analyzer, and Valve Position Control
 PID Features and Optimization with Valve Position Control
 Lambda Tuning Rules
 Misunderstood Effect of Low PID Gain
 Unified Methodology
Sense of Direction
Kick
from filtered
derivative mode
α = 1/8
∆%CO2 = ∆%CO1
∆%SP
∆%CO1
Time
(seconds)
Signal
(%)
Step from
proportional
mode Repeat from
Integral mode
No setpoint filter or lead-lag
seconds/repeat
Contribution of Each PID Mode for
Setpoint Change (Filtered Rate)
Structure of PID on error (β=1 and γ=1)
Controller in auto
Block valve closed (PV not affected)
Contribution of Each PID Mode for
Setpoint Change (Unfiltered Rate)
Structure of PID on error (β=1 and γ=1)
Controller in auto
Block valve closed (PV not affected)
Spike
from unfiltered
derivative mode
α = 0
∆%CO2 = ∆%CO1
∆%SP
∆%CO1
Time
(seconds)
Signal
(%)
Step from
proportional
mode
Repeat from
Integral mode
No setpoint filter or lead-lag
seconds/repeat
Proportional Mode Basics
Note that many analog controllers used proportional band instead of gain for the proportional mode
tuning setting. Proportional band is the % change in the process variable (∆%PV) needed to cause a
100% change in controller output (∆%CO). A 100% proportional band means a 100% ∆%PV
would cause a 100 % ∆%CO (a gain of 1). It is critical that users know the units of their controller
gain setting and convert accordingly.
Gain = 100 % / Proportional Band
 Provides an immediate reaction to magnitude of measurement change to
minimize peak error and integrated error for a disturbance
 Too much gain action causes fast oscillations (close to ultimate period) and
can make noise and interactions worse
 Provides an immediate reaction to magnitude of setpoint change for P
action on Error to minimize rise time (time to reach setpoint)
 Too much gain causes falter in approach to setpoint
Integral Mode Basics
Note that many analog controllers used reset settings in repeats per minute instead of reset
time for the integral mode tuning setting. Repeats per minute indicate the number of repeats
of the proportional mode contribution in a minute. Today’s reset time settings are minutes per
repeat or seconds per repeat which gives the time to repeat the proportional mode
contribution. Often the “per repeat” term is dropped giving a reset time setting in minutes or
seconds. The smooth gradual response looking only at error is in tune with operator.
Seconds per repeat = 60 / repeats per minute
 Provides a ramping reaction to error (SP-PV) to eliminate offset and minimize
integrated error if stable (since error is hardly ever exactly zero, integral action
is always ramping the controller output)
 Too much integral action causes slow oscillations (slower than ultimate period)
 Too much integral action causes an overshoot (no sense of direction)
Derivative Mode Basics
Nearly all derivative tuning settings are given as a rate time in seconds or minutes. The
ISA Standard Form rate time setting must never be greater than the reset time setting. The
advantages and disadvantages of the derivative mode in terms of an abrupt response and
amplification of noise are similar to that of the proportional mode except the relative
advantages are less and the relative disadvantages are greater for the derivative
mode. Derivative mode is best used to cancel out the effect of a secondary time constant.
Seconds = 60 ∗ minutes
 Provides an immediate reaction to rate of change of measurement change
to minimize peak error and integrated error for a disturbance
 Too much rate action causes fast oscillations (faster than ultimate period)
and can make noise and interactions worse
 Provides an immediate reaction to rate of change of setpoint change for D
action on Error to minimize rise time (time to reach setpoint)
 Too much rate causes fast oscillation
Proportional Only (P only)
Response to Step Load Disturbance
Purple PV = 0.5 x Normal Gain
Green PV = 1.0 x Normal Gain
Red PV = 1.5 x Normal Gain
Brown PV = 2.0 x Normal Gain
Period = 40 sec
Ultimate Period = 40 sec
Proportional + Integral (PI)
Response to Step Load Disturbance
Purple PV = 1.5 x Normal Reset
Green PV = 1.0 x Normal Reset
Red PV = 0.75 x Normal Reset
Brown PV = 0.5 x Normal Reset
Period = 65 sec
Ultimate Period = 40 sec
Proportional + Integral + Derivative (PID)
Response to Step Load Disturbance
Purple PV = 0.5 x Normal Rate
Green PV = 1.0 x Normal Rate
Red PV = 2.0 x Normal Rate
Brown PV = 2.5 x Normal Rate
Period = 25 sec
Ultimate Period = 40 sec
Self-Regulating Process
Integrating Process
Runaway Process
Origin of Loop Dynamics
Ultimate Limit for Disturbance Rejection
Ultimate Limit for Disturbance Rejection
Practical Limit for Disturbance Rejection
External Reset (Dynamic Reset Limit)
 Prevents PID output changing faster than a valve, VFD, or secondary
loop can respond
– Secondary PID slow tuning
– Secondary PID SP Filter Time
– Secondary PID SP Rate Limit
– AO, DVC, VFD SP Rate Limit
– Slow Valve or VFD
– Use PV for BKCAL_OUT
– Position used as PV if valve is very slow and readback is fast
– Enables Enhanced PID for Wireless
 Stops Limit cycles from deadband, backlash, stiction, and threshold
sensitivity or resolution limits
 Key enabling feature that simplifies tuning and creates more
advanced opportunities for PID control
ISA Standard Form with External Reset
PID Structure Options
(1) PID action on error (β = 1 and γ = 1)
(2) PI action on error, D action on PV (β = 1 and γ = 0)
(3) I action on error, PD action on PV (β = 0 and γ = 0)
(4) PD action on error, no I action (β = 1 and γ = 1)
(5) P action on error, D action on PV, no I action (β = 1 and γ = 0)
(6) ID action on error, no P action (γ = 1)
(7) I action on error, D action on PV, no P action (γ = 0)
(8) Two degrees of freedom controller (β and γ adjustable 0 to 1)
PID Options Effect on Setpoint Response
Single Sided Batch Needs PD on Error
Setpoint Rate Limits and Lead-Lag
(Triple Cascade Loop)
Setpoint Filter and Lead-Lag
• PID SP filter reduces overshoot enabling tuning for load disturbances
– Setpoint filter time set equal reset time
• PID SP filter coordinates timing of flow ratio control
– Simultaneous changes in feeds for blending and reactions
– Consistent closed loop response for model predictive control
• PID SP filter sets closed loop time constant
• PID SP filter in secondary loop slows down cascade control system
rejection of primary loop disturbances
– Secondary loop should be > 4x faster than primary loop
• Primary PID must have dynamic reset limit enabled
• Setpoint Lead-Lag minimizes overshoot and rise time
– Lag time = reset time
– Lead time = 25% lag time
Setpoint Rate Limits
• AO & PID SP rate limits minimize disruption while protecting
equipment and optimizing processes
– Offers directional moves suppression
– Enables fast opening and slow closing surge valve
– VPC fast recovery for upset and slow approach to optimum
• AO SP rate limits minimize interaction between loops
– Less important loops are made 10x slower than critical loops
• PID driving AO SP or secondary PID SP rate limit must have
dynamic reset limit enabled so no retuning is needed
• PID faceplate should display PV of AO to show rate limiting
Rise Time for Setpoint Response
Output Tracking Opportunities
• “Bang-Bang” logic for startup & batch SP changes:
– For SP change PID tracks output limit until the predicted PV one
dead time into future gets close to setpoint, the output is then
set at best/last startup or batch value for one dead time
– Works best on slow batch and integrating processes
• “Open Loop Backup” to prevent compressor surge:
– When compressor flow drops below surge SP or a precipitous
drop occurs in flow, PID tracks an output that provides a flow
large enough to compensate for the loss in downstream flow for
a time larger than the loop dead time plus the surge period.
• “Open Loop Backup” to prevent RCRA violation:
– When an inline pH system PV approaches the RCRA pH limit
the PID tracks an incremental output (e.g. 0.25% per sec)
opening the reagent valve until the pH sufficiently backs away
Enhanced PID for Wireless
• Positive feedback implementation of reset with external-reset
feedback (dynamic reset limit)
• Immediate response to a setpoint change or feedforward signal or
mode change
• Suspension of integral action until change in PV
• Integral action is the exponential response of the positive feedback
filter to the change in controller output in elapsed time (the time
interval since last update)
• Derivative action is the PV or error change divided by elapsed time
rather than PID execution
• Threshold sensitivity limit is used to prevent update from noise
Static Mixer pH Setpoint Response
Static Mixer pH Load Response
Static Mixer pH Failure Response
Optimization of Batch Reactor by
Valve Position Control (VPC)
Optimization Examples
by Valve Position Control (VPC)
Optimization VPC PID PV VPC PID SP VPC PID Out
Minimize Prime
Mover Energy
Reactor Feed
Flow PID Output
Maximum Throttle
Position
Compressor or Pump
Pressure SP
Minimize Boiler
Fuel Cost
Steam Flow PID Output Maximum Throttle
Position
Boiler
Pressure SP
Minimize Boiler
Fuel Cost
Equipment Temperature
PID Output
Maximum Throttle
Position
Boiler
Pressure SP
Minimize Chiller
or CTW Energy
Equipment Temperature
PID Output
Maximum Throttle
Position
Chiller or CTW
Temperature SP
Minimize Purchased
Reagent or Fuel Cost
Purchased Reagent or
Fuel Flow PID Output
Minimum Throttle
Position
Waste Reagent
Or Fuel Flow SP
Minimize Total Reagent
Use
Final Neutralization
Stage pH PID Output
Minimum Throttle
Position
First Neutralization
Stage pH PID SP
Maximize Reactor
Production Rate
Reactor or Condenser
Temperature PID Output
Maximum Throttle
Position
Feed Flow or Reaction
Temperature SP
Maximize Reactor
Production Rate
Reactor Vent
Pressure PID Output
Maximum Throttle
Position
Feed Flow or Reaction
Temperature SP
Maximize Column
Production Rate
Reboiler or Condenser
Flow PID Output
Maximum Throttle
Position
Feed Flow or Column
Pressure SP
PID Features for Valve Position Control
PID Feature Function Advantage 1 Advantage 2
Directional Velocity
Limits
Limit VPC Action Speed
Based on Direction
Prevent Running Out
of Valve
Minimize Disruption
to Process
Dynamic Reset
Limit
Limit VPC Action Speed
to Process Response
Directional Velocity
Limits
Prevent Burst of
Oscillations
Adaptive Tuning Automatically Identify
and Schedule Tuning
Eliminate Manual
Tuning
Compensation of
Nonlinearity
Feedforward Preemptively Set VPC
Out for Upset
Prevent Running Out
of Valve
Minimize Disruption
Enhanced PID Suspend Integral Action
until PV Update
Eliminate Limit Cycles
from Stiction &
Backlash
Minimize Oscillations
from Interaction &
Delay
Self-Regulating Process Lambda Tuning
Integrating Process Lambda Tuning
Often Misunderstood Low PID Gain Effect
Lag Dominant Self-Regulating Process
Period = 400 sec
Ultimate Period 40 sec
Often Misunderstood Low PID Gain Effect
Integrating Process
Period = 400 sec
Ultimate Period 40 sec
Often Misunderstood Low PID Gain Effect
Runaway Process
Period = 400 sec
Ultimate Period 40 sec
Low PID Gain and Reset Time Limit
Unified Methodology - 1
 Add a flow measurement to every important process and utility
stream to enable a secondary flow loop for cascade control.
– A secondary flow loop isolates pressure disturbances, and nonlinearities
of the installed characteristic of control valve and variable speed drives
from the control of a higher process variable.
– Flow measurement enable flow feedforward control and the possibility of
changing production rates by moving plant flows in unison per PFD.
– Flow measurements enable closing material and energy balances
leading to process knowledge eliminating uncertainties from pressure
flow relationships and valve backlash and stiction.
– Control valves and VSD normally have a greater rangeability than a
differential head or vortex meter. When this occurs, a calculated flow
based on the installed characteristic should be substituted for the
measurement flow before the signal becomes too noisy or in the case of
the vortex meter the signal drops out. An automatic pressure drop bias
enables smooth transition from measured to calculated flow
Unified Methodology - 2
 Set the output limits to keep the manipulated setpoints in the
desired operating range. For variable speed drives set the process
PID low output limit so the speed cannot cause the discharge head to
approach the static head in order to prevent excessive sensitivity to
pressure and to prevent reverse flow. In general, set the anti-reset
windup limit to match the output limit. If the output scale is
engineering units, the output limits and anti-reset windup must be
based on the output scale range and units.
 Choose the best structure for your application. Generally the best
choice is structure 2 with PI on error and D on PV. For a single
direction response (e.g. batch heating or neutralization), use structure
4 or structure 5 so that there is no integral action. For a highly
exothermic reaction, you might want structure 5 to help prevent a
runaway from integral action.
 Set the signal filter noise just large enough to keep the controller
output fluctuations from exceeding the resolution limit or deadband of
the final control element.
Unified Methodology - 3
 For near-integrating, true integrating, and runway processes use
the lambda integrating process tuning rules. To maximize the
transfer of variability from the process variable to the manipulated
variable, set the lambda (arrest time) equal to the maximum possible
dead time* and use the largest integrating process gain for all
operating conditions in the tuning. To maximize the absorption of
variability (e.g. surge tank level) use the minimum arrest time
computed from paper Equations 1 through 10 for all possible
operating conditions. If you decrease the PID gain, proportionally
increase the PID reset time to prevent slow rolling oscillations.
 For self-regulating processes with the open loop time constant
less than 4 times the dead time, use the lambda self-regulating
tuning rules. To maximize the transfer of variability from the process
variable to the manipulated variable set the lambda (closed loop time
constant) equal to the maximum possible dead time* and use the
largest process gain and smallest time constant for all operating
conditions in the tuning (worse case is often lowest production rate).
* Due to unknowns a more practical lambda is twice the max dead time
Unified Methodology - 4
 Turn on external reset feedback. Make sure the external reset
feedback signal is correctly propagated back to the PID (e.g. BKCAL
signal) especially if there are split range, signal characterizer, or
signal selector blocks on the PID output.
 For final control elements that are slow or that have deadband
or resolution limit, use a fast readback of the valve position or
variable frequency drive speed as the external reset feedback to
prevent a burst of oscillations from the PID output changing faster
than the final control element can respond.
 For final control elements that create limit cycles from
resolution limits and deadband, use a fast readback of the valve
position or variable frequency drive speed to stop the limit cycles
 For cascade control, use the PV of the secondary loop as the
external reset feedback to prevent a burst of oscillations from
violation of the cascade rule where the secondary loop must be
significantly faster than the primary loop.
Unified Methodology - 5
 For setpoint filters of secondary loops for coordination of flow
loops, use the PV of the secondary loop as the external reset
feedback to prevent the need to retune the PID.
 For setpoint rate limits use the PV of the analog output block or
secondary loop as the external reset feedback to prevent the
need to retune the PID. Add setpoint rate limits to minimize the
interaction between loops and in valve position control and to provide
directional move suppression to enable a fast getaway for abnormal
conditions and a slow approach to optimum. For valve position
control, use an enhanced PID developed for wireless with a threshold
sensitivity limit to ignore insignificant changes in the valve position to
be optimized.
 Add output tracking for equipment protection and a full throttle
(bang-bang control) strategy for the fastest possible time to reach
setpoint on startup and for batch operations.
 Use valve position control for simple and quick optimization by
just a PID configuration.
Unified Methodology - 6
 Add output tracking logic to momentarily track an output that
insures equipment and environmental protection. For compressor
surge protection track a sufficiently large opening of the surge valves.
To prevent a RCRA pH violation, track a rapidly incrementing reagent
valve position to prevent an effluent excursion < 2 pH or > 12 pH.
 Add feedforward control for large and fast measured
disturbances. For flow feedforward, use a ratio and bias station so
the operator can enter a desired flow ratio and see the actual flow
ratio. Setup the PID to provide a bias correction to the manipulated
flow. Add dynamic compensation (dead time and lead-lag blocks) to
the feedforward so the manipulated flow arrives at the same point in
the process at the same time as the measured disturbance.
 For wireless devices or analyzers (discontinuous PV update
delay) use an enhanced PID to eliminate the need to retune the
controller to prevent oscillations. If the delay is much larger than the
63% process response time, the PID gain can be set as large as the
inverse of the maximum open loop gain for self-regulating processes.

Contenu connexe

Tendances

Gas Absorption & Stripping in Chemical Engineering (Part 2/4)
Gas Absorption & Stripping in Chemical Engineering (Part 2/4)Gas Absorption & Stripping in Chemical Engineering (Part 2/4)
Gas Absorption & Stripping in Chemical Engineering (Part 2/4)
Chemical Engineering Guy
 

Tendances (20)

Valve Selection & Sizing
Valve Selection & SizingValve Selection & Sizing
Valve Selection & Sizing
 
FAQ on chemical Reaction Engineering
FAQ on chemical Reaction EngineeringFAQ on chemical Reaction Engineering
FAQ on chemical Reaction Engineering
 
Design of condenser
Design of condenserDesign of condenser
Design of condenser
 
Calculation of Flowrate and Pressure Drop Relationship for Laminar Flow using...
Calculation of Flowrate and Pressure Drop Relationship for Laminar Flow using...Calculation of Flowrate and Pressure Drop Relationship for Laminar Flow using...
Calculation of Flowrate and Pressure Drop Relationship for Laminar Flow using...
 
Methanol Converter Types
Methanol Converter TypesMethanol Converter Types
Methanol Converter Types
 
Assignment 1
Assignment 1Assignment 1
Assignment 1
 
PSV Sizing - API Based
PSV Sizing - API BasedPSV Sizing - API Based
PSV Sizing - API Based
 
Minimal Requirements for Relief Systems Documentation
Minimal Requirements for Relief Systems DocumentationMinimal Requirements for Relief Systems Documentation
Minimal Requirements for Relief Systems Documentation
 
Che 412 cre 1 notes
Che 412 cre 1 notesChe 412 cre 1 notes
Che 412 cre 1 notes
 
Control valve
Control valveControl valve
Control valve
 
Process Engineer Training PID.ppt.pdf
Process Engineer Training PID.ppt.pdfProcess Engineer Training PID.ppt.pdf
Process Engineer Training PID.ppt.pdf
 
CONTROL VALVES: CHARACTERISTICS, GAIN & TRANSFER FUNCTION
CONTROL VALVES: CHARACTERISTICS, GAIN & TRANSFER FUNCTION CONTROL VALVES: CHARACTERISTICS, GAIN & TRANSFER FUNCTION
CONTROL VALVES: CHARACTERISTICS, GAIN & TRANSFER FUNCTION
 
Control valve presentation
Control valve presentationControl valve presentation
Control valve presentation
 
Hp/ lp bypass system for steam turbines
Hp/ lp bypass system for steam turbinesHp/ lp bypass system for steam turbines
Hp/ lp bypass system for steam turbines
 
Valve sizing reference
Valve sizing referenceValve sizing reference
Valve sizing reference
 
Shell and Tube Heat Exchangers Using Cooling Water
Shell and Tube Heat Exchangers Using Cooling WaterShell and Tube Heat Exchangers Using Cooling Water
Shell and Tube Heat Exchangers Using Cooling Water
 
Catalyst Breakage in Reformer Tubes
Catalyst Breakage in Reformer TubesCatalyst Breakage in Reformer Tubes
Catalyst Breakage in Reformer Tubes
 
Dynamic Simulation of an LPG Storage Facility in Aspen HYSYS, along with a pu...
Dynamic Simulation of an LPG Storage Facility in Aspen HYSYS, along with a pu...Dynamic Simulation of an LPG Storage Facility in Aspen HYSYS, along with a pu...
Dynamic Simulation of an LPG Storage Facility in Aspen HYSYS, along with a pu...
 
Psv scenario-and-calculation
Psv scenario-and-calculationPsv scenario-and-calculation
Psv scenario-and-calculation
 
Gas Absorption & Stripping in Chemical Engineering (Part 2/4)
Gas Absorption & Stripping in Chemical Engineering (Part 2/4)Gas Absorption & Stripping in Chemical Engineering (Part 2/4)
Gas Absorption & Stripping in Chemical Engineering (Part 2/4)
 

Similaire à A Unified PID Control Methodology to Meet Plant Objectives

Proportional integral and derivative PID controller
Proportional integral and derivative PID controller Proportional integral and derivative PID controller
Proportional integral and derivative PID controller
Mostafa Ragab
 

Similaire à A Unified PID Control Methodology to Meet Plant Objectives (20)

ISA Effective Use of PID Controllers 3-7-2013
ISA Effective Use of PID Controllers 3-7-2013ISA Effective Use of PID Controllers 3-7-2013
ISA Effective Use of PID Controllers 3-7-2013
 
Exceptional Process Control Opportunities
Exceptional Process Control OpportunitiesExceptional Process Control Opportunities
Exceptional Process Control Opportunities
 
Isa saint-louis-exceptional-opportunities-short-course-day-3
Isa saint-louis-exceptional-opportunities-short-course-day-3Isa saint-louis-exceptional-opportunities-short-course-day-3
Isa saint-louis-exceptional-opportunities-short-course-day-3
 
Isa saint-louis-exceptional-opportunities-short-course-day-2
Isa saint-louis-exceptional-opportunities-short-course-day-2Isa saint-louis-exceptional-opportunities-short-course-day-2
Isa saint-louis-exceptional-opportunities-short-course-day-2
 
PID Control of Slow Valves and Secondary Loops Greg McMillan Deminar Series
PID Control of Slow Valves and Secondary Loops Greg McMillan Deminar SeriesPID Control of Slow Valves and Secondary Loops Greg McMillan Deminar Series
PID Control of Slow Valves and Secondary Loops Greg McMillan Deminar Series
 
Proportional integral and derivative PID controller
Proportional integral and derivative PID controller Proportional integral and derivative PID controller
Proportional integral and derivative PID controller
 
PID Control of Runaway Processes - Greg McMillan Deminar
PID Control of Runaway Processes - Greg McMillan DeminarPID Control of Runaway Processes - Greg McMillan Deminar
PID Control of Runaway Processes - Greg McMillan Deminar
 
Effects of Macrocycle Time and Sampling Rates on Control Loop Performance
Effects of Macrocycle Time and Sampling Rates on Control Loop PerformanceEffects of Macrocycle Time and Sampling Rates on Control Loop Performance
Effects of Macrocycle Time and Sampling Rates on Control Loop Performance
 
Guidelines for Setting Filter and Module Execution Rate
Guidelines for Setting Filter and Module Execution RateGuidelines for Setting Filter and Module Execution Rate
Guidelines for Setting Filter and Module Execution Rate
 
PID Tuning Rules
PID Tuning RulesPID Tuning Rules
PID Tuning Rules
 
PID Control Basics
PID Control BasicsPID Control Basics
PID Control Basics
 
PID Tuning for Near Integrating Processes - Greg McMillan Deminar
PID Tuning for Near Integrating Processes - Greg McMillan DeminarPID Tuning for Near Integrating Processes - Greg McMillan Deminar
PID Tuning for Near Integrating Processes - Greg McMillan Deminar
 
Split Range Control - Greg McMillan Deminar
Split Range Control - Greg McMillan DeminarSplit Range Control - Greg McMillan Deminar
Split Range Control - Greg McMillan Deminar
 
Mechatroincs universitty for students .ppt
Mechatroincs universitty for students .pptMechatroincs universitty for students .ppt
Mechatroincs universitty for students .ppt
 
Mechatroincs universitty for students .ppt
Mechatroincs universitty for students .pptMechatroincs universitty for students .ppt
Mechatroincs universitty for students .ppt
 
control technology of bachlor of engineering technology
control technology of bachlor of engineering technologycontrol technology of bachlor of engineering technology
control technology of bachlor of engineering technology
 
Ppt on simulink by vikas gupta
Ppt on simulink by vikas guptaPpt on simulink by vikas gupta
Ppt on simulink by vikas gupta
 
Isa saint-louis-exceptional-opportunities-short-course-day-1
Isa saint-louis-exceptional-opportunities-short-course-day-1Isa saint-louis-exceptional-opportunities-short-course-day-1
Isa saint-louis-exceptional-opportunities-short-course-day-1
 
How to Setup and Adjust the Dynamic Compensation of Feedforward Signals
How to Setup and Adjust the Dynamic Compensation of Feedforward SignalsHow to Setup and Adjust the Dynamic Compensation of Feedforward Signals
How to Setup and Adjust the Dynamic Compensation of Feedforward Signals
 
PID controller
PID controllerPID controller
PID controller
 

Plus de Jim Cahill

Process Control Improvement Primer - Greg McMillan Deminar
Process Control Improvement Primer - Greg McMillan DeminarProcess Control Improvement Primer - Greg McMillan Deminar
Process Control Improvement Primer - Greg McMillan Deminar
Jim Cahill
 

Plus de Jim Cahill (20)

New Kids on the I/O Block - Transferring Process Control Knowledge to Millenn...
New Kids on the I/O Block - Transferring Process Control Knowledge to Millenn...New Kids on the I/O Block - Transferring Process Control Knowledge to Millenn...
New Kids on the I/O Block - Transferring Process Control Knowledge to Millenn...
 
Social Media Impact on Emerson B2B World of Process Automation
Social Media Impact on Emerson B2B World of Process AutomationSocial Media Impact on Emerson B2B World of Process Automation
Social Media Impact on Emerson B2B World of Process Automation
 
Social Media and Collaboration in Automation and Manufacturing
Social Media and Collaboration in Automation and ManufacturingSocial Media and Collaboration in Automation and Manufacturing
Social Media and Collaboration in Automation and Manufacturing
 
Social Media for Process Automation - Why?
Social Media for Process Automation - Why?Social Media for Process Automation - Why?
Social Media for Process Automation - Why?
 
Social Media: Perspectives from the Trenches
Social Media: Perspectives from the TrenchesSocial Media: Perspectives from the Trenches
Social Media: Perspectives from the Trenches
 
Foundation Fieldbus - Control in the Field
Foundation Fieldbus - Control in the FieldFoundation Fieldbus - Control in the Field
Foundation Fieldbus - Control in the Field
 
pH Control Solutions - Greg McMillan
pH Control Solutions - Greg McMillanpH Control Solutions - Greg McMillan
pH Control Solutions - Greg McMillan
 
Wireless Measurement and Control - AIChE New Orleans
Wireless Measurement and Control - AIChE New OrleansWireless Measurement and Control - AIChE New Orleans
Wireless Measurement and Control - AIChE New Orleans
 
Isa saint-louis-advanced-p h-short-course-day-2
Isa saint-louis-advanced-p h-short-course-day-2Isa saint-louis-advanced-p h-short-course-day-2
Isa saint-louis-advanced-p h-short-course-day-2
 
Isa saint-louis-advanced-p h-short-course-day-1
Isa saint-louis-advanced-p h-short-course-day-1Isa saint-louis-advanced-p h-short-course-day-1
Isa saint-louis-advanced-p h-short-course-day-1
 
Social Media and Communities - Part 1
Social Media and Communities - Part 1Social Media and Communities - Part 1
Social Media and Communities - Part 1
 
Process Control Improvement Primer - Greg McMillan Deminar
Process Control Improvement Primer - Greg McMillan DeminarProcess Control Improvement Primer - Greg McMillan Deminar
Process Control Improvement Primer - Greg McMillan Deminar
 
Social Media: Should We, Should We Not, or Should We Ignore the Whole Thing
Social Media: Should We, Should We Not, or Should We Ignore the Whole ThingSocial Media: Should We, Should We Not, or Should We Ignore the Whole Thing
Social Media: Should We, Should We Not, or Should We Ignore the Whole Thing
 
PID Tuning for Self Regulating Processes - Greg McMillan Deminar
PID Tuning for Self Regulating Processes - Greg McMillan DeminarPID Tuning for Self Regulating Processes - Greg McMillan Deminar
PID Tuning for Self Regulating Processes - Greg McMillan Deminar
 
On-line Process Control Lab Access and Use Deminar
On-line Process Control Lab Access and Use DeminarOn-line Process Control Lab Access and Use Deminar
On-line Process Control Lab Access and Use Deminar
 
PID Control of Valve Sticktion and Backlash - Greg McMillan Deminar Series
PID Control of Valve Sticktion and Backlash - Greg McMillan Deminar SeriesPID Control of Valve Sticktion and Backlash - Greg McMillan Deminar Series
PID Control of Valve Sticktion and Backlash - Greg McMillan Deminar Series
 
Opportunities in Social Media
Opportunities in Social MediaOpportunities in Social Media
Opportunities in Social Media
 
PID Control Of Sampled Measurements - Greg McMillan Deminar Series
PID Control Of Sampled Measurements - Greg McMillan Deminar SeriesPID Control Of Sampled Measurements - Greg McMillan Deminar Series
PID Control Of Sampled Measurements - Greg McMillan Deminar Series
 
Process Profiling: Investigation And Prediction Of Process Upsets With Advanc...
Process Profiling: Investigation And Prediction Of Process Upsets With Advanc...Process Profiling: Investigation And Prediction Of Process Upsets With Advanc...
Process Profiling: Investigation And Prediction Of Process Upsets With Advanc...
 
Advances In Digital Automation Within Refining
Advances In Digital Automation Within RefiningAdvances In Digital Automation Within Refining
Advances In Digital Automation Within Refining
 

Dernier

Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
ZurliaSoop
 

Dernier (20)

Kodo Millet PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...
Kodo Millet  PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...Kodo Millet  PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...
Kodo Millet PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...
 
Understanding Accommodations and Modifications
Understanding  Accommodations and ModificationsUnderstanding  Accommodations and Modifications
Understanding Accommodations and Modifications
 
NO1 Top Black Magic Specialist In Lahore Black magic In Pakistan Kala Ilam Ex...
NO1 Top Black Magic Specialist In Lahore Black magic In Pakistan Kala Ilam Ex...NO1 Top Black Magic Specialist In Lahore Black magic In Pakistan Kala Ilam Ex...
NO1 Top Black Magic Specialist In Lahore Black magic In Pakistan Kala Ilam Ex...
 
ICT Role in 21st Century Education & its Challenges.pptx
ICT Role in 21st Century Education & its Challenges.pptxICT Role in 21st Century Education & its Challenges.pptx
ICT Role in 21st Century Education & its Challenges.pptx
 
This PowerPoint helps students to consider the concept of infinity.
This PowerPoint helps students to consider the concept of infinity.This PowerPoint helps students to consider the concept of infinity.
This PowerPoint helps students to consider the concept of infinity.
 
ICT role in 21st century education and it's challenges.
ICT role in 21st century education and it's challenges.ICT role in 21st century education and it's challenges.
ICT role in 21st century education and it's challenges.
 
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
 
How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17
 
REMIFENTANIL: An Ultra short acting opioid.pptx
REMIFENTANIL: An Ultra short acting opioid.pptxREMIFENTANIL: An Ultra short acting opioid.pptx
REMIFENTANIL: An Ultra short acting opioid.pptx
 
How to Create and Manage Wizard in Odoo 17
How to Create and Manage Wizard in Odoo 17How to Create and Manage Wizard in Odoo 17
How to Create and Manage Wizard in Odoo 17
 
Beyond_Borders_Understanding_Anime_and_Manga_Fandom_A_Comprehensive_Audience_...
Beyond_Borders_Understanding_Anime_and_Manga_Fandom_A_Comprehensive_Audience_...Beyond_Borders_Understanding_Anime_and_Manga_Fandom_A_Comprehensive_Audience_...
Beyond_Borders_Understanding_Anime_and_Manga_Fandom_A_Comprehensive_Audience_...
 
Towards a code of practice for AI in AT.pptx
Towards a code of practice for AI in AT.pptxTowards a code of practice for AI in AT.pptx
Towards a code of practice for AI in AT.pptx
 
How to setup Pycharm environment for Odoo 17.pptx
How to setup Pycharm environment for Odoo 17.pptxHow to setup Pycharm environment for Odoo 17.pptx
How to setup Pycharm environment for Odoo 17.pptx
 
How to Manage Global Discount in Odoo 17 POS
How to Manage Global Discount in Odoo 17 POSHow to Manage Global Discount in Odoo 17 POS
How to Manage Global Discount in Odoo 17 POS
 
Jamworks pilot and AI at Jisc (20/03/2024)
Jamworks pilot and AI at Jisc (20/03/2024)Jamworks pilot and AI at Jisc (20/03/2024)
Jamworks pilot and AI at Jisc (20/03/2024)
 
2024-NATIONAL-LEARNING-CAMP-AND-OTHER.pptx
2024-NATIONAL-LEARNING-CAMP-AND-OTHER.pptx2024-NATIONAL-LEARNING-CAMP-AND-OTHER.pptx
2024-NATIONAL-LEARNING-CAMP-AND-OTHER.pptx
 
Sensory_Experience_and_Emotional_Resonance_in_Gabriel_Okaras_The_Piano_and_Th...
Sensory_Experience_and_Emotional_Resonance_in_Gabriel_Okaras_The_Piano_and_Th...Sensory_Experience_and_Emotional_Resonance_in_Gabriel_Okaras_The_Piano_and_Th...
Sensory_Experience_and_Emotional_Resonance_in_Gabriel_Okaras_The_Piano_and_Th...
 
Plant propagation: Sexual and Asexual propapagation.pptx
Plant propagation: Sexual and Asexual propapagation.pptxPlant propagation: Sexual and Asexual propapagation.pptx
Plant propagation: Sexual and Asexual propapagation.pptx
 
UGC NET Paper 1 Mathematical Reasoning & Aptitude.pdf
UGC NET Paper 1 Mathematical Reasoning & Aptitude.pdfUGC NET Paper 1 Mathematical Reasoning & Aptitude.pdf
UGC NET Paper 1 Mathematical Reasoning & Aptitude.pdf
 
Micro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdfMicro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdf
 

A Unified PID Control Methodology to Meet Plant Objectives

  • 1. A Unified PID Control Methodology to Meet Plant Objectives Greg McMillan CDI Process & Industrial Hector Torres Eastman Chemical
  • 3. Topics  PID Basics (contribution of each mode)  Process and Loop Dynamics  Ultimate Limits for Disturbance Rejection  Practical Limits for Disturbance Rejection  PID Form and Structure Options  Setpoint Rate Limits and Lead-Lag  Setpoint Rise Time  Output Tracking Opportunities  Enhanced PID for Wireless, Analyzer, and Valve Position Control  PID Features and Optimization with Valve Position Control  Lambda Tuning Rules  Misunderstood Effect of Low PID Gain  Unified Methodology
  • 5. Kick from filtered derivative mode α = 1/8 ∆%CO2 = ∆%CO1 ∆%SP ∆%CO1 Time (seconds) Signal (%) Step from proportional mode Repeat from Integral mode No setpoint filter or lead-lag seconds/repeat Contribution of Each PID Mode for Setpoint Change (Filtered Rate) Structure of PID on error (β=1 and γ=1) Controller in auto Block valve closed (PV not affected)
  • 6. Contribution of Each PID Mode for Setpoint Change (Unfiltered Rate) Structure of PID on error (β=1 and γ=1) Controller in auto Block valve closed (PV not affected) Spike from unfiltered derivative mode α = 0 ∆%CO2 = ∆%CO1 ∆%SP ∆%CO1 Time (seconds) Signal (%) Step from proportional mode Repeat from Integral mode No setpoint filter or lead-lag seconds/repeat
  • 7. Proportional Mode Basics Note that many analog controllers used proportional band instead of gain for the proportional mode tuning setting. Proportional band is the % change in the process variable (∆%PV) needed to cause a 100% change in controller output (∆%CO). A 100% proportional band means a 100% ∆%PV would cause a 100 % ∆%CO (a gain of 1). It is critical that users know the units of their controller gain setting and convert accordingly. Gain = 100 % / Proportional Band  Provides an immediate reaction to magnitude of measurement change to minimize peak error and integrated error for a disturbance  Too much gain action causes fast oscillations (close to ultimate period) and can make noise and interactions worse  Provides an immediate reaction to magnitude of setpoint change for P action on Error to minimize rise time (time to reach setpoint)  Too much gain causes falter in approach to setpoint
  • 8. Integral Mode Basics Note that many analog controllers used reset settings in repeats per minute instead of reset time for the integral mode tuning setting. Repeats per minute indicate the number of repeats of the proportional mode contribution in a minute. Today’s reset time settings are minutes per repeat or seconds per repeat which gives the time to repeat the proportional mode contribution. Often the “per repeat” term is dropped giving a reset time setting in minutes or seconds. The smooth gradual response looking only at error is in tune with operator. Seconds per repeat = 60 / repeats per minute  Provides a ramping reaction to error (SP-PV) to eliminate offset and minimize integrated error if stable (since error is hardly ever exactly zero, integral action is always ramping the controller output)  Too much integral action causes slow oscillations (slower than ultimate period)  Too much integral action causes an overshoot (no sense of direction)
  • 9. Derivative Mode Basics Nearly all derivative tuning settings are given as a rate time in seconds or minutes. The ISA Standard Form rate time setting must never be greater than the reset time setting. The advantages and disadvantages of the derivative mode in terms of an abrupt response and amplification of noise are similar to that of the proportional mode except the relative advantages are less and the relative disadvantages are greater for the derivative mode. Derivative mode is best used to cancel out the effect of a secondary time constant. Seconds = 60 ∗ minutes  Provides an immediate reaction to rate of change of measurement change to minimize peak error and integrated error for a disturbance  Too much rate action causes fast oscillations (faster than ultimate period) and can make noise and interactions worse  Provides an immediate reaction to rate of change of setpoint change for D action on Error to minimize rise time (time to reach setpoint)  Too much rate causes fast oscillation
  • 10. Proportional Only (P only) Response to Step Load Disturbance Purple PV = 0.5 x Normal Gain Green PV = 1.0 x Normal Gain Red PV = 1.5 x Normal Gain Brown PV = 2.0 x Normal Gain Period = 40 sec Ultimate Period = 40 sec
  • 11. Proportional + Integral (PI) Response to Step Load Disturbance Purple PV = 1.5 x Normal Reset Green PV = 1.0 x Normal Reset Red PV = 0.75 x Normal Reset Brown PV = 0.5 x Normal Reset Period = 65 sec Ultimate Period = 40 sec
  • 12. Proportional + Integral + Derivative (PID) Response to Step Load Disturbance Purple PV = 0.5 x Normal Rate Green PV = 1.0 x Normal Rate Red PV = 2.0 x Normal Rate Brown PV = 2.5 x Normal Rate Period = 25 sec Ultimate Period = 40 sec
  • 16. Origin of Loop Dynamics
  • 17. Ultimate Limit for Disturbance Rejection
  • 18. Ultimate Limit for Disturbance Rejection
  • 19. Practical Limit for Disturbance Rejection
  • 20. External Reset (Dynamic Reset Limit)  Prevents PID output changing faster than a valve, VFD, or secondary loop can respond – Secondary PID slow tuning – Secondary PID SP Filter Time – Secondary PID SP Rate Limit – AO, DVC, VFD SP Rate Limit – Slow Valve or VFD – Use PV for BKCAL_OUT – Position used as PV if valve is very slow and readback is fast – Enables Enhanced PID for Wireless  Stops Limit cycles from deadband, backlash, stiction, and threshold sensitivity or resolution limits  Key enabling feature that simplifies tuning and creates more advanced opportunities for PID control
  • 21. ISA Standard Form with External Reset
  • 22. PID Structure Options (1) PID action on error (β = 1 and γ = 1) (2) PI action on error, D action on PV (β = 1 and γ = 0) (3) I action on error, PD action on PV (β = 0 and γ = 0) (4) PD action on error, no I action (β = 1 and γ = 1) (5) P action on error, D action on PV, no I action (β = 1 and γ = 0) (6) ID action on error, no P action (γ = 1) (7) I action on error, D action on PV, no P action (γ = 0) (8) Two degrees of freedom controller (β and γ adjustable 0 to 1)
  • 23. PID Options Effect on Setpoint Response
  • 24. Single Sided Batch Needs PD on Error
  • 25. Setpoint Rate Limits and Lead-Lag (Triple Cascade Loop)
  • 26. Setpoint Filter and Lead-Lag • PID SP filter reduces overshoot enabling tuning for load disturbances – Setpoint filter time set equal reset time • PID SP filter coordinates timing of flow ratio control – Simultaneous changes in feeds for blending and reactions – Consistent closed loop response for model predictive control • PID SP filter sets closed loop time constant • PID SP filter in secondary loop slows down cascade control system rejection of primary loop disturbances – Secondary loop should be > 4x faster than primary loop • Primary PID must have dynamic reset limit enabled • Setpoint Lead-Lag minimizes overshoot and rise time – Lag time = reset time – Lead time = 25% lag time
  • 27. Setpoint Rate Limits • AO & PID SP rate limits minimize disruption while protecting equipment and optimizing processes – Offers directional moves suppression – Enables fast opening and slow closing surge valve – VPC fast recovery for upset and slow approach to optimum • AO SP rate limits minimize interaction between loops – Less important loops are made 10x slower than critical loops • PID driving AO SP or secondary PID SP rate limit must have dynamic reset limit enabled so no retuning is needed • PID faceplate should display PV of AO to show rate limiting
  • 28. Rise Time for Setpoint Response
  • 29. Output Tracking Opportunities • “Bang-Bang” logic for startup & batch SP changes: – For SP change PID tracks output limit until the predicted PV one dead time into future gets close to setpoint, the output is then set at best/last startup or batch value for one dead time – Works best on slow batch and integrating processes • “Open Loop Backup” to prevent compressor surge: – When compressor flow drops below surge SP or a precipitous drop occurs in flow, PID tracks an output that provides a flow large enough to compensate for the loss in downstream flow for a time larger than the loop dead time plus the surge period. • “Open Loop Backup” to prevent RCRA violation: – When an inline pH system PV approaches the RCRA pH limit the PID tracks an incremental output (e.g. 0.25% per sec) opening the reagent valve until the pH sufficiently backs away
  • 30. Enhanced PID for Wireless • Positive feedback implementation of reset with external-reset feedback (dynamic reset limit) • Immediate response to a setpoint change or feedforward signal or mode change • Suspension of integral action until change in PV • Integral action is the exponential response of the positive feedback filter to the change in controller output in elapsed time (the time interval since last update) • Derivative action is the PV or error change divided by elapsed time rather than PID execution • Threshold sensitivity limit is used to prevent update from noise
  • 31. Static Mixer pH Setpoint Response
  • 32. Static Mixer pH Load Response
  • 33. Static Mixer pH Failure Response
  • 34. Optimization of Batch Reactor by Valve Position Control (VPC)
  • 35. Optimization Examples by Valve Position Control (VPC) Optimization VPC PID PV VPC PID SP VPC PID Out Minimize Prime Mover Energy Reactor Feed Flow PID Output Maximum Throttle Position Compressor or Pump Pressure SP Minimize Boiler Fuel Cost Steam Flow PID Output Maximum Throttle Position Boiler Pressure SP Minimize Boiler Fuel Cost Equipment Temperature PID Output Maximum Throttle Position Boiler Pressure SP Minimize Chiller or CTW Energy Equipment Temperature PID Output Maximum Throttle Position Chiller or CTW Temperature SP Minimize Purchased Reagent or Fuel Cost Purchased Reagent or Fuel Flow PID Output Minimum Throttle Position Waste Reagent Or Fuel Flow SP Minimize Total Reagent Use Final Neutralization Stage pH PID Output Minimum Throttle Position First Neutralization Stage pH PID SP Maximize Reactor Production Rate Reactor or Condenser Temperature PID Output Maximum Throttle Position Feed Flow or Reaction Temperature SP Maximize Reactor Production Rate Reactor Vent Pressure PID Output Maximum Throttle Position Feed Flow or Reaction Temperature SP Maximize Column Production Rate Reboiler or Condenser Flow PID Output Maximum Throttle Position Feed Flow or Column Pressure SP
  • 36. PID Features for Valve Position Control PID Feature Function Advantage 1 Advantage 2 Directional Velocity Limits Limit VPC Action Speed Based on Direction Prevent Running Out of Valve Minimize Disruption to Process Dynamic Reset Limit Limit VPC Action Speed to Process Response Directional Velocity Limits Prevent Burst of Oscillations Adaptive Tuning Automatically Identify and Schedule Tuning Eliminate Manual Tuning Compensation of Nonlinearity Feedforward Preemptively Set VPC Out for Upset Prevent Running Out of Valve Minimize Disruption Enhanced PID Suspend Integral Action until PV Update Eliminate Limit Cycles from Stiction & Backlash Minimize Oscillations from Interaction & Delay
  • 39. Often Misunderstood Low PID Gain Effect Lag Dominant Self-Regulating Process Period = 400 sec Ultimate Period 40 sec
  • 40. Often Misunderstood Low PID Gain Effect Integrating Process Period = 400 sec Ultimate Period 40 sec
  • 41. Often Misunderstood Low PID Gain Effect Runaway Process Period = 400 sec Ultimate Period 40 sec
  • 42. Low PID Gain and Reset Time Limit
  • 43. Unified Methodology - 1  Add a flow measurement to every important process and utility stream to enable a secondary flow loop for cascade control. – A secondary flow loop isolates pressure disturbances, and nonlinearities of the installed characteristic of control valve and variable speed drives from the control of a higher process variable. – Flow measurement enable flow feedforward control and the possibility of changing production rates by moving plant flows in unison per PFD. – Flow measurements enable closing material and energy balances leading to process knowledge eliminating uncertainties from pressure flow relationships and valve backlash and stiction. – Control valves and VSD normally have a greater rangeability than a differential head or vortex meter. When this occurs, a calculated flow based on the installed characteristic should be substituted for the measurement flow before the signal becomes too noisy or in the case of the vortex meter the signal drops out. An automatic pressure drop bias enables smooth transition from measured to calculated flow
  • 44. Unified Methodology - 2  Set the output limits to keep the manipulated setpoints in the desired operating range. For variable speed drives set the process PID low output limit so the speed cannot cause the discharge head to approach the static head in order to prevent excessive sensitivity to pressure and to prevent reverse flow. In general, set the anti-reset windup limit to match the output limit. If the output scale is engineering units, the output limits and anti-reset windup must be based on the output scale range and units.  Choose the best structure for your application. Generally the best choice is structure 2 with PI on error and D on PV. For a single direction response (e.g. batch heating or neutralization), use structure 4 or structure 5 so that there is no integral action. For a highly exothermic reaction, you might want structure 5 to help prevent a runaway from integral action.  Set the signal filter noise just large enough to keep the controller output fluctuations from exceeding the resolution limit or deadband of the final control element.
  • 45. Unified Methodology - 3  For near-integrating, true integrating, and runway processes use the lambda integrating process tuning rules. To maximize the transfer of variability from the process variable to the manipulated variable, set the lambda (arrest time) equal to the maximum possible dead time* and use the largest integrating process gain for all operating conditions in the tuning. To maximize the absorption of variability (e.g. surge tank level) use the minimum arrest time computed from paper Equations 1 through 10 for all possible operating conditions. If you decrease the PID gain, proportionally increase the PID reset time to prevent slow rolling oscillations.  For self-regulating processes with the open loop time constant less than 4 times the dead time, use the lambda self-regulating tuning rules. To maximize the transfer of variability from the process variable to the manipulated variable set the lambda (closed loop time constant) equal to the maximum possible dead time* and use the largest process gain and smallest time constant for all operating conditions in the tuning (worse case is often lowest production rate). * Due to unknowns a more practical lambda is twice the max dead time
  • 46. Unified Methodology - 4  Turn on external reset feedback. Make sure the external reset feedback signal is correctly propagated back to the PID (e.g. BKCAL signal) especially if there are split range, signal characterizer, or signal selector blocks on the PID output.  For final control elements that are slow or that have deadband or resolution limit, use a fast readback of the valve position or variable frequency drive speed as the external reset feedback to prevent a burst of oscillations from the PID output changing faster than the final control element can respond.  For final control elements that create limit cycles from resolution limits and deadband, use a fast readback of the valve position or variable frequency drive speed to stop the limit cycles  For cascade control, use the PV of the secondary loop as the external reset feedback to prevent a burst of oscillations from violation of the cascade rule where the secondary loop must be significantly faster than the primary loop.
  • 47. Unified Methodology - 5  For setpoint filters of secondary loops for coordination of flow loops, use the PV of the secondary loop as the external reset feedback to prevent the need to retune the PID.  For setpoint rate limits use the PV of the analog output block or secondary loop as the external reset feedback to prevent the need to retune the PID. Add setpoint rate limits to minimize the interaction between loops and in valve position control and to provide directional move suppression to enable a fast getaway for abnormal conditions and a slow approach to optimum. For valve position control, use an enhanced PID developed for wireless with a threshold sensitivity limit to ignore insignificant changes in the valve position to be optimized.  Add output tracking for equipment protection and a full throttle (bang-bang control) strategy for the fastest possible time to reach setpoint on startup and for batch operations.  Use valve position control for simple and quick optimization by just a PID configuration.
  • 48. Unified Methodology - 6  Add output tracking logic to momentarily track an output that insures equipment and environmental protection. For compressor surge protection track a sufficiently large opening of the surge valves. To prevent a RCRA pH violation, track a rapidly incrementing reagent valve position to prevent an effluent excursion < 2 pH or > 12 pH.  Add feedforward control for large and fast measured disturbances. For flow feedforward, use a ratio and bias station so the operator can enter a desired flow ratio and see the actual flow ratio. Setup the PID to provide a bias correction to the manipulated flow. Add dynamic compensation (dead time and lead-lag blocks) to the feedforward so the manipulated flow arrives at the same point in the process at the same time as the measured disturbance.  For wireless devices or analyzers (discontinuous PV update delay) use an enhanced PID to eliminate the need to retune the controller to prevent oscillations. If the delay is much larger than the 63% process response time, the PID gain can be set as large as the inverse of the maximum open loop gain for self-regulating processes.