CORPORATE FOYER. PORTFOLIO.
1. 400 4100 400 4082 400
4500 4482
33453300
Construction plan
Scale 1:50
1609
RECEPTION
Tiles
20m2
Access to
recording studios
and offices
Toilet Kitchenette
BOARDROOM
Wooden flooring
17m2
Concrete column
Height of slab
above @ 3570UFFL
Wall with window from 1190mm height
Lift lobby
Main Entrance
Aluminium and glass door
-
---
-
---
-
---
-
---
3300
3643
40029004002945400
115481090159090
110 4245 90 4477
110 2200 90 965 90 2210 90 3167
470
40028364002859400
6695
8812
line of
bulkhead above
WAITING AREA
801780150849
line of
bulkhead above
849905280
40 880
1210
90140
616
393 1600 167
Site plan
Scale 1:200
RECEPTION AREA BOARDROOM
TOILET KITCHENNETE
OTHER OFFICES AND
RECORDING STUDIOS
Circulation plan
Scale 1:200
CIRCULATION LEGEND
LIGHT TRAFFIC
MEDUIM TRAFFIC
HEAVY TRAFFIC
WALL SCHEDULE
IMAGE FIXTURE TYPE DESCRIPTION SUPPLIER CODE SIZE MATERIAL QTY ROOM
WC GREY TOP FLUSH CORAL
TOILET.
WALL MOUNTED TOILET.
110mm WASTE OUTLET WITH
CISTERN CONNECTED
TO15mm
WATER SUPPLY. 90 DEGREE
OUTLET CLOSED RIM BACK
INLET PAN ELECTRONIC DUCT
VALVE. SHORT FLUSH AND
FULL FLUSH.
CTM GR500T 380(W) X 660(L) X
770(H)mm
VITREOUS
CHINA 1
TOILET
WHB WHITE FORLI’ OVAL BASIN.
WALL MOUNTED BASIN.
GALA SINGLE LEVER 15mm
CHROME SINGLE TAPHOLE
BASIN MIXER WITH CLASSIC
HANDLE
CTM BSBAFO216
585(W) X 390(D) X
210(H)mm
VITREOUS
CHINA 1
TOILET
Scale
Drawn by Mlungisi Mhlungu Date
100
Construction plan and site plan
IDDCIY3 CORPORATE FOYER
TAVGClient
NOTES
11.02.2016
11.02. 2016
No. Description. Date
REVISION TABLE
As indicated @A2
SANS 10400
1. ALL BUILDING CONVENTIONS MUST ADHERE TO THE
REQUIREMENTS OF THE SANS 10400 NATIONAL BUILDING
REGULATIONS.
2. NO OWNER OF ANY SITE SHALL DEMOLISH OR CAUSE PER MIT
DEMOLISHING ON ANY BUILDING WITHOUT THE PRIOR WRIT TEN
PERMISSION OF THE LOCAL AUTHORITY.
3. NO PERSON SHALL AT ANY TIME DURING THE COURSE OF OR
AFTER THE DEMOLITION OF A BUILDING LEAVE IT IN A CONDITION
DANGEROUS TO THE PUBLIC OR ADJOINING
PROPERTY.
4. THE LOCAL AUTHORITY MAY PROHIBIT THE USE OF ANY
METHOD TO BE APPLIED IN THE DEMOLITION OF ANY BUILDING
WHERE IN IT’S OPINION SUCH METHOD WILL CREATE OR CA USE
TO BE CREATED ON ANY DANGER TO ANY PERSON OR OTHER
BUILDING OR PROPERTY, AND AND WHERE IT SO PROHIBITS IT
SHALL, ON THE REQUEST OF THE OWNER OF SUCH BUILDING ,
GIVE IT REASONS, IN WRITING, FOR SUCH PROHIBITION.
5. IN THE CASE OF AN ADDITION IT MIGHT BE POSSIBLE TO TREAT
THE NEW PORTION AS AN ENTIRELY SEPERATE PART WHICH CAN
BE DESIGNED TO COMPLY WITH THE NATIONAL BUILDING
REGULATIONS WITHOUT HAVING ANY EFFECT ON THE ORIGINAL
PORTION OF THE BUILDING.
6. ANY BUILDING AND ANY STRUCTURAL ELEMENT OR COMPONENT
THEREOF SHALL BE DESIGNED TO PROVIDE STRENGTH, STABILITY,
SERVUCEABILITY AND DURABILITY IN ACCORDANCE WITH A CCEPTED
PRINCIPLES OF STRUCTURAL DESIGN, AND SO THAT IT WILL NOT
IMPAIR THE INTEGRITY OF ANY OTHER BUILDING OR PROPE RTY.
7. ANY SUCH BUILDING SHALL BE SO DESIGNED THAT IN THE EVENT
OF ACCIDENTAL OVERLOADING THE STRUCTURL SYSTEM WILL NOT
SUFFER DISASTROUS OR PROGRESSSIVE COLLAPSE WHICH IS
DISPROPORTIONATE TO THE ORIGINAL CAUSE.
8. THE PROTECTION OF THE EDGE OF ANY BALCONY, BRIDGE, FLAT
ROOF OR SIMILAR PLACE SHALL BE DESIGNED TO PREVENT ANY
PERSON FROM FALLING FROM SUCH BALCONY, BRIDGE, FLAT ROOF
OR SIMILAR PLACE.
9. SANITARY FIXTURES SHALL BE SO SITED AS NOT TO BE OFFENSIVE.
10. BALUSTRADE AND PARAPET WALLS SHALL NOT BE LESS THAN
1,0m IN HEIGHT
UNLESS UNAUTHORISED ACCESS OF PERSONS TO THE EDGE O F A
FLAT ROOF OR SIMILAR STRUCTURE IS EXCLUDED BY A PHYSICAL
BARRIER PROPERLY ERECTED AND
MONITORED.
11. ANY WALL, SCREEN, RAILING OR BALUSTRADE TO SUCH TO SUCH
STAIRWAY MUST BE IN ACCORDANCE WITH THE REQUIREMENTS OF
EITHER SANS 10400-B OR SANS 10400-K AND SANS 10400- T.
12. SANS 10400-S REDUCES THE RISE OF THE STEP, INCR EASES THE
WIDTH OF THE STAIRWAY AND THE LENGTH OF THE LANDING,
REQUIRES SOLID RISERS WHERE STAIRS OVERLAP THE NEXT LOWER
TREAD, AND REQUIRES HANDRAILS ON BOTH SIDES OF THE
STAIRWAY.
13. THE HEADROOM AT ANY POINT ON ANY STAIRWAY SHALLBE NOT
LESS THAN 2,1m, MEASURED VERTICALLY FROM THE PITCH LINE,
AND THE WIDTH OF ANY STAIRWAY,MEASURED TO ANY ENCLOSING
WALL OR BALUSTRADE, SHALL BE NOT LESS THAN
700mm.
14. NO FLIGHT OF STAIRS SHALL HAVE A VERTICAL RISE GREATER
THAN 3m BETWEEN LANDINGS.
15. THE RISE OF ANY STEP SHALL NOT EXCEED 200m.
16. THE GOING AND WIDTH OF ANY TREAD SHALL BE NOT LESS THAN
250mm, PROVIDED THAT WHERE THE STAIRWAY DOES NOT HAVE
SOLID RISERS, EACH TREAD BY NOT LESS THAN 25mm.
17. ANY STAIRWAY, INCLUDING ANY WALL, SCREEN, RAILING OR
BALUSTRADE TO SUCH STAIRWAY, SHALL PERMIT SAFE MOVEMENT
OF PERSONS OF FROM FLOOR TO FLOOR.
MEM MADEART GRAPHICS DESIGN
2. -
---
-
---
-
---
-
---
400 4100 400 4082 400
4500 4482
33453300
Furniture Layout
Scale 1:50
RECEPTION
Tiles
20m2
Access to
recording studios
and offices
Toilet Kitchenette
BOARDROOM
Wooden flooring
17m2
Concrete column
Height of slab
above @ 3570UFFL
Wall with window from 1190mm height
Lift lobby
Main Entrance
Aluminium and glass door
F1
F2
F3
F4
F5
F6
F5
8812
915 1040
1444 1830 1203
61020859151200
FURNITURE AND FITTINGS SCHEDULE
SYMBOL FIXTURE DESCRIPTION SUPPLIER CODE SIZE QTY ROOM MATERIAL
F1
F2
F3
F5
F4
RECEPTION DESK WHITE WITH MARBLE
LOOK TOP
CUSTOM 1830Lx915Bx900H 1 RECEPTION HIGH PRESSURE
LAMINATES
HEMMAN MILLER
OFFICE CHAIR
FORWARD PIVOT
MECHANISM WITH A
5 POSITION LOCK
WITH ARMS
ALL OFFICE 74457 547X530mm 7 RECEPTION
BOARDROOM
LEATHER UPHOLSTERY
SEAT WITH
MOULDED FOAM
BOARDROOM TABLE CORPORATE
TABLE FOR SIX
CUSTOM 1830Lx915Bx900H 1 BOARDROOM CHROMATED TIBULAR
STEEL LEGS WITH
TINTED GLASS TOP
CREDENZA WHITE WITH MARBLE
LOOK TOP
CUSTOM 1830Lx610Bx900H 1 HIGH PRESSURE
LAMINATES
BOARDROOM
SOFA/COUCH TIMELESS CLASSIC
THREE SEATER
CASSINA LC2 1800X700X670 2 RECEPTION POLISHED TRIVALENT
CHROME PLATED ENAMEL
STEEL FRAME.
POLYURETHANE FOAM
CUSHION WITH POLYESTER
PADDING.
FABRIC OR LEATHER
Scale
Drawn by Mlungisi Mhlungu Date
200
Furniture plan
IDDCIY3 CORPORATE FOYER
TAVGClient
NOTES
11.02.2016
11.02. 2016
No. Description. Date
REVISION TABLE
As indicated @A2
SANS 10400
1. ALL BUILDING CONVENTIONS MUST ADHERE TO THE
REQUIREMENTS OF THE SANS 10400 NATIONAL BUILDING
REGULATIONS.
2. NO OWNER OF ANY SITE SHALL DEMOLISH OR CAUSE PER MIT
DEMOLISHING ON ANY BUILDING WITHOUT THE PRIOR WRIT TEN
PERMISSION OF THE LOCAL AUTHORITY.
3. NO PERSON SHALL AT ANY TIME DURING THE COURSE OF OR
AFTER THE DEMOLITION OF A BUILDING LEAVE IT IN A CONDITION
DANGEROUS TO THE PUBLIC OR ADJOINING
PROPERTY.
4. THE LOCAL AUTHORITY MAY PROHIBIT THE USE OF ANY
METHOD TO BE APPLIED IN THE DEMOLITION OF ANY BUILDING
WHERE IN IT’S OPINION SUCH METHOD WILL CREATE OR CA USE
TO BE CREATED ON ANY DANGER TO ANY PERSON OR OTHER
BUILDING OR PROPERTY, AND AND WHERE IT SO PROHIBITS IT
SHALL, ON THE REQUEST OF THE OWNER OF SUCH BUILDING ,
GIVE IT REASONS, IN WRITING, FOR SUCH PROHIBITION.
5. IN THE CASE OF AN ADDITION IT MIGHT BE POSSIBLE TO TREAT
THE NEW PORTION AS AN ENTIRELY SEPERATE PART WHICH CAN
BE DESIGNED TO COMPLY WITH THE NATIONAL BUILDING
REGULATIONS WITHOUT HAVING ANY EFFECT ON THE ORIGINAL
PORTION OF THE BUILDING.
6. ANY BUILDING AND ANY STRUCTURAL ELEMENT OR COMPONENT
THEREOF SHALL BE DESIGNED TO PROVIDE STRENGTH, STABILITY,
SERVUCEABILITY AND DURABILITY IN ACCORDANCE WITH A CCEPTED
PRINCIPLES OF STRUCTURAL DESIGN, AND SO THAT IT WILL NOT
IMPAIR THE INTEGRITY OF ANY OTHER BUILDING OR PROPE RTY.
7. ANY SUCH BUILDING SHALL BE SO DESIGNED THAT IN THE EVENT
OF ACCIDENTAL OVERLOADING THE STRUCTURL SYSTEM WILL NOT
SUFFER DISASTROUS OR PROGRESSSIVE COLLAPSE WHICH IS
DISPROPORTIONATE TO THE ORIGINAL CAUSE.
8. THE PROTECTION OF THE EDGE OF ANY BALCONY, BRIDGE, FLAT
ROOF OR SIMILAR PLACE SHALL BE DESIGNED TO PREVENT ANY
PERSON FROM FALLING FROM SUCH BALCONY, BRIDGE, FLAT ROOF
OR SIMILAR PLACE.
9. SANITARY FIXTURES SHALL BE SO SITED AS NOT TO BE OFFENSIVE.
10. BALUSTRADE AND PARAPET WALLS SHALL NOT BE LESS THAN
1,0m IN HEIGHT
UNLESS UNAUTHORISED ACCESS OF PERSONS TO THE EDGE O F A
FLAT ROOF OR SIMILAR STRUCTURE IS EXCLUDED BY A PHYSICAL
BARRIER PROPERLY ERECTED AND
MONITORED.
11. ANY WALL, SCREEN, RAILING OR BALUSTRADE TO SUCH TO SUCH
STAIRWAY MUST BE IN ACCORDANCE WITH THE REQUIREMENTS OF
EITHER SANS 10400-B OR SANS 10400-K AND SANS 10400- T.
12. SANS 10400-S REDUCES THE RISE OF THE STEP, INCR EASES THE
WIDTH OF THE STAIRWAY AND THE LENGTH OF THE LANDING,
REQUIRES SOLID RISERS WHERE STAIRS OVERLAP THE NEXT LOWER
TREAD, AND REQUIRES HANDRAILS ON BOTH SIDES OF THE
STAIRWAY.
13. THE HEADROOM AT ANY POINT ON ANY STAIRWAY SHALLBE NOT
LESS THAN 2,1m, MEASURED VERTICALLY FROM THE PITCH LINE,
AND THE WIDTH OF ANY STAIRWAY,MEASURED TO ANY ENCLOSING
WALL OR BALUSTRADE, SHALL BE NOT LESS THAN
700mm.
14. NO FLIGHT OF STAIRS SHALL HAVE A VERTICAL RISE GREATER
THAN 3m BETWEEN LANDINGS.
15. THE RISE OF ANY STEP SHALL NOT EXCEED 200m.
16. THE GOING AND WIDTH OF ANY TREAD SHALL BE NOT LESS THAN
250mm, PROVIDED THAT WHERE THE STAIRWAY DOES NOT HAVE
SOLID RISERS, EACH TREAD BY NOT LESS THAN 25mm.
17. ANY STAIRWAY, INCLUDING ANY WALL, SCREEN, RAILING OR
BALUSTRADE TO SUCH STAIRWAY, SHALL PERMIT SAFE MOVEMENT
OF PERSONS OF FROM FLOOR TO FLOOR.
MEM MADEART GRAPHICS DESIGN
3. -
---
-
---
-
---
-
---
33453300
Wall and Floor finishes
Scale 1:50
1609
RECEPTION
Tiles
20m2
Access to
recording studios
and offices
Toilet Kitchenette
BOARDROOM
Wooden flooring
17m2
Concrete column
Height of slab above @ 3570UFFL
Wall with window
from 1190mm height
Lift lobby
Main Entrance
Aluminium and glass door
450
FF1
FF2
FF3
FF4
FF5
4810
4245 4477
90 2210 90 3167
990
470
3255
demolished wall, make well
WALL LEGENG
EXISTING 230mm WALL
EXISTING 90mm WALL
NEW 90mm WALL
REMOVED WALL
FLOOR FINISH SCHEDULE
905280
SYMBOL FF DESCIPTION SUPPLIER CODE COLOUR ROOM QTY
FF1
FF2
FF3
FF4
CERAMIC FLOOR
TILE
VINYL FLOORING
CERAMIC FLOOR
TILE
BAMBOO FLOORING
TYPE
MINIMA ANTHRACITE CERAMIC TILES
FLOOR TILES WITH PEI CLASS 1 RATING
FIXED TO CEMENT AND SAND SCREED
WITH TILE ADHESIVE
3mm JOINTS CONTINOUOS IN BOTH
DIRECTIONS GROUTED WITH TILE GROUT
WITH TILE GROUT MINIMUM 5mm EXPANSION
JOINTS AT PERIMETER
HEAVY COMMERCIAL
15 PLANKS PER BOX
(DRY BACK) STICK DOWN
MINIMA ANTHRACITE CERAMIC TILES
FLOOR TILES WITH PEI CLASS 1 RATING
FIXED TO CEMENT AND SAND SCREED
WITH TILE ADHESIVE
3mm JOINTS CONTINOUOS IN BOTH
DIRECTIONS GROUTED WITH TILE GROUT
WITH TILE GROUT MINIMUM 5mm EXPANSION
JOINTS AT PERIMETER
HEAVY COMMERCIAL
15 PLANKS PER BOX
(DRY BACK) STICK DOWN
TILE AFRICA
BELGOTEX
FLOORS
TILE AFRICA
BELGOTEX
FLOORS
T0026294 ARCTIC WHITE RECEPTION
SIZE
600X600
BL26 CUMARU BOARDROOM
T0026285 ARCTIC WHITE TOILET 400X400
901D MODENA KITCHENETTE
WF1
WF2
WF3
WF1
WF2
WF3
WF4
TYPE MARK WF TYPE DESCRIPTION CODE SUPPLIER COLOUR ROOM
PROFFESSIONAL
WATER BASED PRIMER
WASH AND WEAR
MATT PAINT FINISH
INCL200R0001 CREAM/BEIGE RECEPTIONDULUX
PROFFESSIONAL
WATER BASED PRIMER
WASH AND WEAR
MATT PAINT FINISH
DULUXDC30 BLACK STENCIL BOARDROOM
CERAMIC FLOOR
TILE
TILE AFRICAT0026285 ARCTIC WHITE TOILET 400X400SEE FLOOR
SCHEDULE
WALL FINISHES LEGEND
SIZE
PERSPEX WALL
FEATURE
MOULDED
HYGEINIC
PERSPEX
KITCHENETTE
Scale
Drawn by Mlungisi Mhlungu Date
300
Wall and Floor finishes
IDDCIY3 CORPORATE FOYER
TAVGClient
NOTES
11.02.2016
11.02. 2016
No. Description. Date
REVISION TABLE
As indicated @A2
SANS 10400
1. ALL BUILDING CONVENTIONS MUST ADHERE TO THE
REQUIREMENTS OF THE SANS 10400 NATIONAL BUILDING
REGULATIONS.
2. NO OWNER OF ANY SITE SHALL DEMOLISH OR CAUSE PER MIT
DEMOLISHING ON ANY BUILDING WITHOUT THE PRIOR WRIT TEN
PERMISSION OF THE LOCAL AUTHORITY.
3. NO PERSON SHALL AT ANY TIME DURING THE COURSE OF OR
AFTER THE DEMOLITION OF A BUILDING LEAVE IT IN A CONDITION
DANGEROUS TO THE PUBLIC OR ADJOINING
PROPERTY.
4. THE LOCAL AUTHORITY MAY PROHIBIT THE USE OF ANY
METHOD TO BE APPLIED IN THE DEMOLITION OF ANY BUILDING
WHERE IN IT’S OPINION SUCH METHOD WILL CREATE OR CA USE
TO BE CREATED ON ANY DANGER TO ANY PERSON OR OTHER
BUILDING OR PROPERTY, AND AND WHERE IT SO PROHIBITS IT
SHALL, ON THE REQUEST OF THE OWNER OF SUCH BUILDING ,
GIVE IT REASONS, IN WRITING, FOR SUCH PROHIBITION.
5. IN THE CASE OF AN ADDITION IT MIGHT BE POSSIBLE TO TREAT
THE NEW PORTION AS AN ENTIRELY SEPERATE PART WHICH CAN
BE DESIGNED TO COMPLY WITH THE NATIONAL BUILDING
REGULATIONS WITHOUT HAVING ANY EFFECT ON THE ORIGINAL
PORTION OF THE BUILDING.
6. ANY BUILDING AND ANY STRUCTURAL ELEMENT OR COMPONENT
THEREOF SHALL BE DESIGNED TO PROVIDE STRENGTH, STABILITY,
SERVUCEABILITY AND DURABILITY IN ACCORDANCE WITH A CCEPTED
PRINCIPLES OF STRUCTURAL DESIGN, AND SO THAT IT WILL NOT
IMPAIR THE INTEGRITY OF ANY OTHER BUILDING OR PROPE RTY.
7. ANY SUCH BUILDING SHALL BE SO DESIGNED THAT IN THE EVENT
OF ACCIDENTAL OVERLOADING THE STRUCTURL SYSTEM WILL NOT
SUFFER DISASTROUS OR PROGRESSSIVE COLLAPSE WHICH IS
DISPROPORTIONATE TO THE ORIGINAL CAUSE.
8. THE PROTECTION OF THE EDGE OF ANY BALCONY, BRIDGE, FLAT
ROOF OR SIMILAR PLACE SHALL BE DESIGNED TO PREVENT ANY
PERSON FROM FALLING FROM SUCH BALCONY, BRIDGE, FLAT ROOF
OR SIMILAR PLACE.
9. SANITARY FIXTURES SHALL BE SO SITED AS NOT TO BE OFFENSIVE.
10. BALUSTRADE AND PARAPET WALLS SHALL NOT BE LESS THAN
1,0m IN HEIGHT
UNLESS UNAUTHORISED ACCESS OF PERSONS TO THE EDGE O F A
FLAT ROOF OR SIMILAR STRUCTURE IS EXCLUDED BY A PHYSICAL
BARRIER PROPERLY ERECTED AND
MONITORED.
11. ANY WALL, SCREEN, RAILING OR BALUSTRADE TO SUCH TO SUCH
STAIRWAY MUST BE IN ACCORDANCE WITH THE REQUIREMENTS OF
EITHER SANS 10400-B OR SANS 10400-K AND SANS 10400- T.
12. SANS 10400-S REDUCES THE RISE OF THE STEP, INCR EASES THE
WIDTH OF THE STAIRWAY AND THE LENGTH OF THE LANDING,
REQUIRES SOLID RISERS WHERE STAIRS OVERLAP THE NEXT LOWER
TREAD, AND REQUIRES HANDRAILS ON BOTH SIDES OF THE
STAIRWAY.
13. THE HEADROOM AT ANY POINT ON ANY STAIRWAY SHALLBE NOT
LESS THAN 2,1m, MEASURED VERTICALLY FROM THE PITCH LINE,
AND THE WIDTH OF ANY STAIRWAY,MEASURED TO ANY ENCLOSING
WALL OR BALUSTRADE, SHALL BE NOT LESS THAN
700mm.
14. NO FLIGHT OF STAIRS SHALL HAVE A VERTICAL RISE GREATER
THAN 3m BETWEEN LANDINGS.
15. THE RISE OF ANY STEP SHALL NOT EXCEED 200m.
16. THE GOING AND WIDTH OF ANY TREAD SHALL BE NOT LESS THAN
250mm, PROVIDED THAT WHERE THE STAIRWAY DOES NOT HAVE
SOLID RISERS, EACH TREAD BY NOT LESS THAN 25mm.
17. ANY STAIRWAY, INCLUDING ANY WALL, SCREEN, RAILING OR
BALUSTRADE TO SUCH STAIRWAY, SHALL PERMIT SAFE MOVEMENT
OF PERSONS OF FROM FLOOR TO FLOOR.
MEM MADEART GRAPHICS DESIGN
4. -
---
-
---
-
---
-
---
400 4100 400 4082 400
4500 4482
33453300
Electrical Plan
Scale 1:50
RECEPTION
Tiles
20m2
Access to
recording studios
and offices
Toilet Kitchenette
BOARDROOM
Wooden flooring
17m2
Concrete column
Height of slab
above @ 3570UFFL
Wall with window from 1190mm height
Lift lobby
Main Entrance
Aluminium and glass door
8812
2
2
ELECTRICAL LEGEND
DESCRIPTION SYMBOL QTY ROOM
TELEPHONE CABLE (@900)
WIFI DATA POINT (@2600)
WHITE ELECTRIC PLUG (NORMAL
SOCKET OUTLET) (@350
ELECTRIC POP UP BOX (FIXED TO TABLE)
2
2
2
2
2
RECEPTION AREA
& BOARDROOM
RECEPTION AREA
& BOARDROOM
RECEPTION AREA
& BOARDROOM
RECEPTION AREA
& BOARDROOM
RECEPTION AREA
& BOARDROOM
RED ELECTRIC PLUG (DEDICATED
SOCKET OUTLET) FIXED TO TABLE
2
2 RECEPTION AREA
& BOARDROOM
RED ELECTRIC PLUG (DEDICATED
SOCKET OUTLET) (@800)
2
2 2
1268
Scale
Drawn by Mlungisi Mhlungu Date
400
Electrical plan
IDDCIY3 CORPORATE FOYER
TAVGClient
NOTES
11.02.2016
11.02. 2016
No. Description. Date
REVISION TABLE
As indicated @A2
SANS 10400
1. ALL BUILDING CONVENTIONS MUST ADHERE TO THE
REQUIREMENTS OF THE SANS 10400 NATIONAL BUILDING
REGULATIONS.
2. NO OWNER OF ANY SITE SHALL DEMOLISH OR CAUSE PER MIT
DEMOLISHING ON ANY BUILDING WITHOUT THE PRIOR WRIT TEN
PERMISSION OF THE LOCAL AUTHORITY.
3. NO PERSON SHALL AT ANY TIME DURING THE COURSE OF OR
AFTER THE DEMOLITION OF A BUILDING LEAVE IT IN A CONDITION
DANGEROUS TO THE PUBLIC OR ADJOINING
PROPERTY.
4. THE LOCAL AUTHORITY MAY PROHIBIT THE USE OF ANY
METHOD TO BE APPLIED IN THE DEMOLITION OF ANY BUILDING
WHERE IN IT’S OPINION SUCH METHOD WILL CREATE OR CA USE
TO BE CREATED ON ANY DANGER TO ANY PERSON OR OTHER
BUILDING OR PROPERTY, AND AND WHERE IT SO PROHIBITS IT
SHALL, ON THE REQUEST OF THE OWNER OF SUCH BUILDING ,
GIVE IT REASONS, IN WRITING, FOR SUCH PROHIBITION.
5. IN THE CASE OF AN ADDITION IT MIGHT BE POSSIBLE TO TREAT
THE NEW PORTION AS AN ENTIRELY SEPERATE PART WHICH CAN
BE DESIGNED TO COMPLY WITH THE NATIONAL BUILDING
REGULATIONS WITHOUT HAVING ANY EFFECT ON THE ORIGINAL
PORTION OF THE BUILDING.
6. ANY BUILDING AND ANY STRUCTURAL ELEMENT OR COMPONENT
THEREOF SHALL BE DESIGNED TO PROVIDE STRENGTH, STABILITY,
SERVUCEABILITY AND DURABILITY IN ACCORDANCE WITH A CCEPTED
PRINCIPLES OF STRUCTURAL DESIGN, AND SO THAT IT WILL NOT
IMPAIR THE INTEGRITY OF ANY OTHER BUILDING OR PROPE RTY.
7. ANY SUCH BUILDING SHALL BE SO DESIGNED THAT IN THE EVENT
OF ACCIDENTAL OVERLOADING THE STRUCTURL SYSTEM WILL NOT
SUFFER DISASTROUS OR PROGRESSSIVE COLLAPSE WHICH IS
DISPROPORTIONATE TO THE ORIGINAL CAUSE.
8. THE PROTECTION OF THE EDGE OF ANY BALCONY, BRIDGE, FLAT
ROOF OR SIMILAR PLACE SHALL BE DESIGNED TO PREVENT ANY
PERSON FROM FALLING FROM SUCH BALCONY, BRIDGE, FLAT ROOF
OR SIMILAR PLACE.
9. SANITARY FIXTURES SHALL BE SO SITED AS NOT TO BE OFFENSIVE.
10. BALUSTRADE AND PARAPET WALLS SHALL NOT BE LESS THAN
1,0m IN HEIGHT
UNLESS UNAUTHORISED ACCESS OF PERSONS TO THE EDGE O F A
FLAT ROOF OR SIMILAR STRUCTURE IS EXCLUDED BY A PHYSICAL
BARRIER PROPERLY ERECTED AND
MONITORED.
11. ANY WALL, SCREEN, RAILING OR BALUSTRADE TO SUCH TO SUCH
STAIRWAY MUST BE IN ACCORDANCE WITH THE REQUIREMENTS OF
EITHER SANS 10400-B OR SANS 10400-K AND SANS 10400- T.
12. SANS 10400-S REDUCES THE RISE OF THE STEP, INCR EASES THE
WIDTH OF THE STAIRWAY AND THE LENGTH OF THE LANDING,
REQUIRES SOLID RISERS WHERE STAIRS OVERLAP THE NEXT LOWER
TREAD, AND REQUIRES HANDRAILS ON BOTH SIDES OF THE
STAIRWAY.
13. THE HEADROOM AT ANY POINT ON ANY STAIRWAY SHALLBE NOT
LESS THAN 2,1m, MEASURED VERTICALLY FROM THE PITCH LINE,
AND THE WIDTH OF ANY STAIRWAY,MEASURED TO ANY ENCLOSING
WALL OR BALUSTRADE, SHALL BE NOT LESS THAN
700mm.
14. NO FLIGHT OF STAIRS SHALL HAVE A VERTICAL RISE GREATER
THAN 3m BETWEEN LANDINGS.
15. THE RISE OF ANY STEP SHALL NOT EXCEED 200m.
16. THE GOING AND WIDTH OF ANY TREAD SHALL BE NOT LESS THAN
250mm, PROVIDED THAT WHERE THE STAIRWAY DOES NOT HAVE
SOLID RISERS, EACH TREAD BY NOT LESS THAN 25mm.
17. ANY STAIRWAY, INCLUDING ANY WALL, SCREEN, RAILING OR
BALUSTRADE TO SUCH STAIRWAY, SHALL PERMIT SAFE MOVEMENT
OF PERSONS OF FROM FLOOR TO FLOOR.
MEM MADEART GRAPHICS DESIGN
5. S S
3251200375
300 900 900 300
5280
1590904810
2210 90 3167
28671900512
12029101780
300 1400 1400 300
4245 90 4477
1781 2400
64 90600 3400 477
500955955500495600495
1210 500 90 983 1200 983
N
SUSPENDED GRID CEILING
PLASTERBOARD CEILING TILES
600mm X 1200mm
50mm THICK
20mm SHADOW LINE
FLUSH PLASTERED
CUSTOM BULK HEAD
FLUSH PLASTERED
CUSTOM BULK HEAD
SUSPENDED GRID CEILING
PLASTERBOARD CEILING TILES
600mm X 1200mm
50mm THICK
20mm SHADOW LINE
1130
842
842
FLUSH PLASTERED
CUSTOM BULK HEAD
C1
C2
C1
C1
C1
C2
C2
1120 886 904
CEILING LEGEND
SUSPENDED GRID CEILING
PLASTERBOARD CEILING TILES
600mm X 1200mm
50mm THICK
@2970
FLUSH PLASTERED
CUSTOM BULK HEAD
@2800
LIGHTING LEGEND
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
C1
C2
ALUMINIUM TILT CIRCLE
LED DOWNLIGHT
SIZE: 60 X 31mm HIGH
SUPPLIER: RADIANT LIGHTING
CODE: CL23
CNC ALUMINIUM BODY COLOUR
ALUMINIUM WITH WARM WHITE
LED WITH 54mm DIAMETER CUTOUT
CEILING LIGHT
SIZE: 600 X 600mm
SUPPLIER: RADIANT LIGHTING
CODE: KR30
METAL BODY WITH PERSPEX
DIFFUSER
WHITE COLOUR
FLOURESCENT TUBE
CEILING CASSETTER 4 WAY
INVERTED
AIR CONDITIONER
SUPPLIER: SAMSUNG
CODE: R 410 A
48000 BTU
P
P
S
2
2 WAY LIGHT
SWITCH @ 1400
2
2
2
2
2
EPSON Ex7235
CEILING MOUNT PROJECTOR
SMOKE DETECTOR
CEILING AND LIGHTING PLAN
Scale 1:50
Scale
Drawn by Mlungisi Mhlungu Date
500
CEILING AND LIGHTING
IDDCIY3 CORPORATE FOYER
TAVGClient
NOTES
23.03.2016
23. 03 2016
No. Description. Date
REVISION TABLE
As indicated @A2
1. WHERE IN ANY BUILDING THE REQUIREMENTS FOR LIGHT ING
CONTAINED IN REGULATION O1 OF THE NATIONAL BUILDING
REGULATIONS SHALL BE COMPLIED WITH BY THE INSTALLATION
OF A SYSTEM OF ARTIFICIAL LIGHTNG, SUCH LIGHTING SHALL
BE IN ACCORDANCE WITH THE RELEVANT RECOMMENDATIONS
CONTAINED IN SANS 10400-1.
2. ANY ROOM CONTAINING A TOILET PAN OR URINAL SHALLBE
PROVIDED WITH A MEANS OF LIGHTING AND VENTILATION
WHICH WILL ENABLE SUCH ROOM TO BE USED, WITHOUT
DETRIMENT TO HEALTH OR SAFTEY OR CAUSING ANY
NUISANCE , FOR THE PURPOSE FOR WHICH IT IS DESIGNED .
THIS REQUIREMENT SHALL BE DEEMED TO BE STATISFIED
WHERE THE LIGHTING AND VENTILATION ARE IN ACCORDANCE
WITH SANS 10400-O.
3. NO PERSON SHALL WITHOUT PRIOR WRITTEN APPROVAL OF
THE LOCAL AUTHORITY INSTALL ANY ARTIFICIAL VENTILATION
SYSTEM IN ANY BUILDING: PROVIDED THAT THIS PROIBITION
SHALL NOT APPLY IN THE CASE OF ROOM AIR CONDITIONERS
OR OTHER INDIVIDUAL APPLIANCES INSTALLED FOR COMFOR T.
4. THE MINIMUM ILLUMINATION LEVELS OF LIGHTING SHAL L
COMPLY WITH THE REQUIREMENTS OF SANS 10400-O AND SA NS
10389-1.
5. ANY BUILDING THAT CONTAINS ARTIFICIAL LIGHTING MUST
COMPLY WITH THE SANS 10400 NATIONAL BUILDING
REGULATIONS SYSTEM OF ARTIFICIAL LIGHTING INSTALLATION.
6. ARTIFICIAL LIGHTING IS CALCULATED WITH THE DESIGN
OCCUPANCY TIMES IN ACCORDANCE WITH TABLE 4 OF THE
SANS 10400 BUILDNG REGULATIONS.
MEM MADEART GRAPHICS DESIGN