ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F1 of 30
Protection in Transmission Networks
ABB
Protection
in
Transmission Networks
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F2 of 30
Protection in Transmission Networks
ABB
List of content Course C02EN, Part Application
of Line- and Transformer Protection
Introduction
Principles suitable for network protection
Short discussion of preferred principles depending on application
Current abbreviations
Line Protection
Kind of faults
Protection Schemes (redundancy, back-up)
Basic principle of distance protection
Autoreclosing
Transformer Protection
Kinds of faults
Protection Schemes (redundancy, back-up)
Basic principle of transformer differential protection
Example of distance protection setting
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F3 of 30
Protection in Transmission Networks
ABB
The data-flow
Data
Input
Data
Preparation
Data
Processing
Data
Evaluation
Data
Output
Data
Storage
Data Transfer (local and remote)
PROCESS
G
G
L
L
L
L
L
PROCESS
PROTECTION/CONTROL -
UNIT/SYSTEM
MMC
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F4 of 30
Protection in Transmission Networks
ABB
From the
problem to
the solution
Data
Input
Data
Preparation
Data
Processing
Data
Evaluation
Data
Output
Data
Storage
Data Transfer (local and remote)
PROCESS
G
G
L
L
L
L
L
PROCESS
PROTECTION/CONTROL - UNIT/SYSTEM
Problems Implications
- 3-phase faults
- 2-phase faults
- Earth-faults
- high impedance faults
- lightning
- evolving faults
- power swings
- power reversals
- swich-onto-faults
- load impedances
- CT saturation
- VT failure
- long lines
- short lines
- parallel lines
- intermediate infeeds
- week infeeds
- heavily loaded lines
- different grounding systems
- overheadlines and cables
etc.
- damage to living beings and material
- fire
- explosions
- overvoltages and overcurrents
- influence on neighbouring devices
- voltage increase during earthfaults
- high step and touch voltages
- loss of energy and black-outs
- semaphor effect
- influence of the zero-sequence impedance
- influence of the mutual zero-sequence impedance
etc.
MMC
Requirements
- Availability
- Simplicity
- Flexibility
- Reliability (Dependability, Security, Consistency)
- Selectivity
- Stability
- Speed
- Accuracy
- Sensitivity
Solutions
- Prot. functions (I, IN, Id, E/F, DEF, >U, TH, etc.)
- Control functions (AR, SYN, Interlocking, etc.)
- Monitoring functions (Selfsup., Trip circuit sup., etc.)
- Evaluation functions (Disturbance rec., Eventrec., etc.)
- Communication (Bay comm., Station comm., etc.)
- Calculations (Short circuit, Load flow, Setting calc., etc.)
- Engineering and Testing
- Filtering, galvanic separation
etc.
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F5 of 30
Protection in Transmission Networks
ABB
Measuring quantities and Measuring principles
Used for auxiliary functions,
such as stabilising features
Current
Phase quantities
Symmetrical
component
quantities
Phase
quantities
Symmetrical
component-
quantities
Mixed
phase-
quantities
Transient components Fundamental frequency components Higher harmonics
Voltage and current Voltage and current
Phase quantities
Distance prot.
Directional overcurrent prot.
Directional comparison prot. Line differential- or
Phase comparison prot.
Time-/
distance-
graded
Overcurrent prot.
Unit prot.
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F6 of 30
Protection in Transmission Networks
ABB
Types of protection, some definitions and abbreviations
¾ Overcurrent
¾ with current independent time delay (definite time)
¾ with current dependent time delay IDMTL
(Inverse time, with Definitive Minimum Time Lag)
0.1
1
10
100
1 10 30
20
8
6
4
2 3
Tripping
time
in seconds
1
I
I
β
k
t[s]
set
α
set
−






⋅
=
Several inverse-time characteristics are
available, most of them follow the term:
I / Iset
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F7 of 30
Protection in Transmission Networks
ABB
Types of protection, some definitions and abbreviations
¾ Directional comparison functioning in POTT (tripping) or BLOCKING mode
¾ Phase comparison Phase-angles of the currents of both line ends are compared
¾ Differential Full currents, amplitudes and phase-angles compared
¾ Biased differential Diff. circuit with low impedance
Biased = restrained = pick-up value is current dependent
¾ High-impedance Diff. circuit with high impedance
differential Matched CT‘s required, exclusively for this protection
¾ REF Restricted Earth Fault
High-impedance differential earth fault function protects
one transformer winding (restricted to one winding)
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F8 of 30
Protection in Transmission Networks
ABB
Types of protection, some definitions and abbreviations
¾ Distance protection = Directional multi-zone impedance protection
Non-switched: 6 loops per zone and min. 3 zones simultaneously measured,
one or several time delayed zones (= state of the art)
Switched: 1 loop measured, zone switching by timer (= older conventional types)
Mho type: directional circular measuring characteristic
Offset Mho type: directional circular „open“ characteristic, healthy voltage and/or
memory voltage polarised for enhanced directionality
Polygon type: polygonal characteristic with healthy voltage and/or memory
voltage polarised directional function
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F9 of 30
Protection in Transmission Networks
ABB
Types of protection, some definitions and abbreviations
¾ Communication between line ends, by carrier (PLC), fibre optics or microwave
PUTT Permissive underreaching transfer trip
POTT Permissive overreaching transfer trip
with add. logic's to cover cases with one weak infeed end
ECHO: in case of weak infeed, a received signal is “echo-ed” back, and the
strong end will trip
WIE Trip: Trip of weak infeed-end by received comm. signal + add. logic’s
UNBLOCK: simulates „signal receive“ in case of a carrier fail during a fault on the line
(useful for overhead lines with PLC communication)
BLOCKING: Overreaching blocking
¾ Phase selector = used for single-pole autoreclosure and for events / alarms
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F10 of 30
Protection in Transmission Networks
ABB
Types of protection, some definitions and abbreviations
¾ DEF = Directional earth fault prot.
Zero-sequence directional prot., often functioning in a communication scheme
¾ AR = Autoreclosing
Single- or three-pole high speed AR and/or one- or multishot three-pole
delayed AR
¾ Distance to fault locator = displays the distance to the fault
Mutual compensation: compensated by 3I0 of the parallel overhead line
Load compensation: corrects the influence of load in case of resistive faults
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F11 of 30
Protection in Transmission Networks
ABB
Line Protection
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F12 of 30
Protection in Transmission Networks
ABB
Line fault types
< 230 kV >230 kV
Type of fault: Single Phase 60 % 85 %
Two Phase 30 % 10 %
Three Phase 10 % 5 %
---------- ----------
100 % 100 %
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F13 of 30
Protection in Transmission Networks
ABB
Typical line protection schemes
A. Distance function with communication scheme to the opposite line end
and time delayed overreaching back-up zones
B. Line differential function combined with a distance function for back-up
1. Non-redundant
schemes
Main 1 Main 2
C. Distance function Same as Main 1
with communication
and back-up zones
(same as A)
D. ditto Line differential function
combined with distance for back-up.
E. ditto Directional comparison prot.
F. ditto Phase comparison prot.
G. ditto Rate of change function in
directional comparison
2. Redundant
schemes
To detect high resistive ground faults, above protection schemes are often combined with a zero
sequence overcurrent protection with inverse time delay or by a directional comparison DEF scheme
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F14 of 30
Protection in Transmission Networks
ABB
Line Protection, Basic Versions
Protection 1 Protection 2 Control
(Main 1) (Main 2 / Back-up) (Option)
Medium Voltage High Voltage
<= 36kV <=72.5kV <=145kV <=245 kV <=765 kV
I> + IN AR/SYN
Dir I> + IN AR/SYN
Id I>+IN AR/SYN
Id Z< AR/SYN
Z< AR/SYN
Z< I>+IN AR/SYN
Z< Z<+IN AR/SYN
Z< + DEF Z<+IN AR/SYN
Z< + DEF+IN Z< +DEF+IN AR/SYN
DirComp+DEF Z<+IN AR/SYN
DirComp+DEF+IN Z<+DEF+IN AR/SYN
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F15 of 30
Protection in Transmission Networks
ABB
Line Protection
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F16 of 30
Protection in Transmission Networks
ABB
Line Protection
DEF
2- or 1 ½ - CB
arrangements
Single CB scheme in
single- or multi-busbar
arrangements
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F17 of 30
Protection in Transmission Networks
ABB
Selective line protection scheme with single end infeed
1,4s
0,8s
1,4s
1,4s
1,1s
1,1s
0s
0,5s
0s
0s
0,3s
1,1s
= Time overcurrent relays
= Time overcurrent relays and directional relays, which only permit
tripping, if the fault is in the direction of the line.
0,3s
0s
0,8s 0,5s
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F18 of 30
Protection in Transmission Networks
ABB
The stepped time / distance characteristic of a distance relay
T = Protected line length
t1...t4 = Time steps
t = Operating time
I = Distance from relay
= Distance relay
A, B = Stations
A
t1
t3
t4
t
t2
T
B I
0,85...0,9 T
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F19 of 30
Protection in Transmission Networks
ABB
Distance relay grading diagram
t
A
B C D
= Distance relay
t = Operating time
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F20 of 30
Protection in Transmission Networks
ABB
Principle of the distance function (simplified)
≈
I Relay
ZS ZL
UG U
k0
3I0
I
U
Z
ph
ground
ph
L
⋅
+
=
−
L
S
G
Z
Z
U
I
+
=
S
R
ph
ph
L
I
I
U
Z
−
=
−
for 2- and 3-phase faults for single-phase to
ground faults
Operation will take place, if:
I > Iset AND ZL < Zset AND Fault forward
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F21 of 30
Protection in Transmission Networks
ABB
Distance characteristic
Polygon - type
ZONE 3
ZONE 2
ZONE 1
OVERREACHING-
ZONE
REVERSE DIRECTED
ZONE
R1
UNDERIMPEDANCE-
CHARACTERISTC
jX1
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F22 of 30
Protection in Transmission Networks
ABB
Line data, required for protection setting
Bundle
conductor
with 2, 3, 4
conductors
Zm0
= mutual zero sequence impedance
Ground-conductor
Positive sequence impedance = Z1 = R1+j·X1
Negative sequence impedance = Z2 = Z1
Zero sequence impedance of a single line Z0 = R0+j·X0
For parallel overhead lines on common towers additionally:
Mutual zero sequence impedance Zm0 = Rm0+j·X0
or
Zero sequence impedance of a double circuit line
Z0’’ = Z0 + Zm0
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F23 of 30
Protection in Transmission Networks
ABB
Impedance - grading
Z3 < 0.85 (a+k·b2)
1.2 a < Z2 < 0.85 (a+k·b1)
Z1 ≈ 0.85·a
ZOR ≈ 1,2·a
a b
A B C
b2
b1
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F24 of 30
Protection in Transmission Networks
ABB
Infeed factor k
≈
Impedance measured by
overreaching zones of relay A
la
d·Zc
Ia + Ib
Ib
A Za
≈
Ia
Z = Za +
d·Zc (la + Ib)
la
Z = Za + k ·d·Zc
where k = 1 +
Ib
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F25 of 30
Protection in Transmission Networks
ABB
Due to load-flow, the fault resistance RF appears as an
enlarged and complex impedance (so called „Semaphor- effect“)
≈ ≈
IphA UF
B
ZL IphB
RF
UA UB
UF = RF (IphA+ IphB)
Z as „seen“ by the distance protection =
With load-flow from A Æ B
With load-flow from B Æ A
RF as for single end infeed
jX
R
ZL
phA
phB
phA
I
I
I
RF
+
⋅
( )
phA
phB
phA
I
I
I
RF
ZL
Z
+
⋅
+
=
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F26 of 30
Protection in Transmission Networks
ABB
Permissive Underreaching Transfer Tripping (PUTT)
Tripping criterion in B Zone 1 of the distance function AND phase-selector
Tripping time in B no intentional delay
Tripping criterion in C Receive of signal from B AND overreaching zone AND phase-selector
Tripping time in C Zone 1 in B plus signal transmission time
This mode is widely used, since unequal characteristics of relays in A and B do not
harm the protection system performance
Tone Rx/Tx = NSD
Relay B
NSD (Tone)
Relay C
Protected line
Zone 1 of relay in B
Zone 1 of relay in C
B C
PLC
PLC = power line carrier
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F27 of 30
Protection in Transmission Networks
ABB
Permissive Overreaching Transfer Tripping (POTT)
Protected line
B C
Tripping criteria = {Zone 1 OR [receive_of_signal AND overreaching_zone]} AND (phase-selector)
Tripping time = No intentional delay for fault in zone 1
Measuring time of overreaching zone in opposite relay plus signal transmission time.
Additional logic's to cover weak infeed conditions :
• “Echo”-Logic allows fast tripping of the end with strong infeed
• Weak-infeed logic allows tripping of the end with weak infeed
Preferred mode for cable lines, short overhead lines and for series compensated lines.
Overreaching zone of relay B
Relay B
Overreaching zone of relay C
Relay C
NSD
NSD
PLC
PLC
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F28 of 30
Protection in Transmission Networks
ABB
Line differential protection
with fibre-optical communication 800/1A
1000/1A
E
O
E
O A
D
DIFF
A
D
E
O
E
O
DIFF
F.O.
< 28 km
With FOX (MUX) up to approx. 120 km
REL 316 REL 316
A/D = analogue / digital converter
E/O = electrical / optical converter
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F29 of 30
Protection in Transmission Networks
ABB
Autoreclosing on overhead lines (AR)
HSAR, single pole DAR, always three pole
Start 1-phase
Trip 3-pole 3-pole discriminating time
DAR open time
Start
Trip 3-pole
High speed HSAR Delayed DAR
Start 1-phase
Trip 1-pole
1-pole discriminating time
Close pulse, interrupted by new trip
Single-pole open time
Q0 Phase R
Q0 Phase S
Q0 Phase T
ABB Power Automation Ltd
T2313 / C02e_2001.ppt / F30 of 30
Protection in Transmission Networks
ABB
Zone 1 used as underreaching PLC-independent trip
X (Zone 1) = 37.1Ω ·0.8 = 29.7 Ω primary ⇒ 12.9 Ω secondary; k0 = 0.74; t1 = 0.0 s
set to 80% of full line instead of the usual 85%, since CVT’s (capacitive voltage transformers) are used
R (Zone 1) = 30 Ω primary ⇒ 13.0 Ω secondary
Zone OR used for the PUTT-scheme
X (Zone OR) >37.1 Ω ·1.5 = 55.6 Ω primary ⇒ 24.2 Ω secondary; k0 = 0.74; tOR = 0.0 s
R (Zone OR) = 40 Ω primary ⇒ 17.4 Ω secondary
this zone shall cover the full line A- B with a good safety margin
Note: To simplify we assume X ≈ Z.

Contenu connexe

Similaire à 03_Prot.transmission_Line.pdf

Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme Samuel Okhuegbe
 
Lec6 impact of embedded generation (1)
Lec6 impact of embedded generation (1)Lec6 impact of embedded generation (1)
Lec6 impact of embedded generation (1)iqra26279
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 
three phase fault analysis with auto reset for temporary fault and trip for p...
three phase fault analysis with auto reset for temporary fault and trip for p...three phase fault analysis with auto reset for temporary fault and trip for p...
three phase fault analysis with auto reset for temporary fault and trip for p...Vikram Rawani
 
Data Teknis Gossen Metrawatt : PROFITEST EMOBILITY
Data Teknis Gossen Metrawatt : PROFITEST EMOBILITYData Teknis Gossen Metrawatt : PROFITEST EMOBILITY
Data Teknis Gossen Metrawatt : PROFITEST EMOBILITYPT. Siwali Swantika
 
Lineprotection basics june2008
Lineprotection basics june2008Lineprotection basics june2008
Lineprotection basics june2008lankeshdb
 
Analysis of distance protection relay in presence of static synchronous compe...
Analysis of distance protection relay in presence of static synchronous compe...Analysis of distance protection relay in presence of static synchronous compe...
Analysis of distance protection relay in presence of static synchronous compe...IAEME Publication
 
Project_Kaveh & Mohammad
Project_Kaveh & MohammadProject_Kaveh & Mohammad
Project_Kaveh & MohammadKaveh Dehno
 
A Study on Protection of Cables by Solkor Differential Protection Relay with ...
A Study on Protection of Cables by Solkor Differential Protection Relay with ...A Study on Protection of Cables by Solkor Differential Protection Relay with ...
A Study on Protection of Cables by Solkor Differential Protection Relay with ...IJERA Editor
 
Switchgear and protection 3
Switchgear and protection 3Switchgear and protection 3
Switchgear and protection 3Md Irshad Ahmad
 
IRJET- Overhead Line Protection with Automatic Switch by using PLC Automation
IRJET- Overhead Line Protection with Automatic Switch by using PLC AutomationIRJET- Overhead Line Protection with Automatic Switch by using PLC Automation
IRJET- Overhead Line Protection with Automatic Switch by using PLC AutomationIRJET Journal
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersThorne & Derrick International
 
substation protection basics.ppt
substation protection basics.pptsubstation protection basics.ppt
substation protection basics.pptSalim Palayi
 
Platform touch voltage protection membrane system and other railways buildin...
Platform touch voltage protection membrane system  and other railways buildin...Platform touch voltage protection membrane system  and other railways buildin...
Platform touch voltage protection membrane system and other railways buildin...Mahesh Chandra Manav
 
Digital transformer protection systems
Digital transformer protection systemsDigital transformer protection systems
Digital transformer protection systemsmichaeljmack
 
Power system protection seminar report
Power system protection seminar reportPower system protection seminar report
Power system protection seminar reportRahul Aman
 

Similaire à 03_Prot.transmission_Line.pdf (20)

Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme
 
Lec6 impact of embedded generation (1)
Lec6 impact of embedded generation (1)Lec6 impact of embedded generation (1)
Lec6 impact of embedded generation (1)
 
Minor project
Minor projectMinor project
Minor project
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
three phase fault analysis with auto reset for temporary fault and trip for p...
three phase fault analysis with auto reset for temporary fault and trip for p...three phase fault analysis with auto reset for temporary fault and trip for p...
three phase fault analysis with auto reset for temporary fault and trip for p...
 
Data Teknis Gossen Metrawatt : PROFITEST EMOBILITY
Data Teknis Gossen Metrawatt : PROFITEST EMOBILITYData Teknis Gossen Metrawatt : PROFITEST EMOBILITY
Data Teknis Gossen Metrawatt : PROFITEST EMOBILITY
 
Abb ethernet-expansion-board
Abb ethernet-expansion-boardAbb ethernet-expansion-board
Abb ethernet-expansion-board
 
Lineprotection basics june2008
Lineprotection basics june2008Lineprotection basics june2008
Lineprotection basics june2008
 
Analysis of distance protection relay in presence of static synchronous compe...
Analysis of distance protection relay in presence of static synchronous compe...Analysis of distance protection relay in presence of static synchronous compe...
Analysis of distance protection relay in presence of static synchronous compe...
 
Project_Kaveh & Mohammad
Project_Kaveh & MohammadProject_Kaveh & Mohammad
Project_Kaveh & Mohammad
 
A Study on Protection of Cables by Solkor Differential Protection Relay with ...
A Study on Protection of Cables by Solkor Differential Protection Relay with ...A Study on Protection of Cables by Solkor Differential Protection Relay with ...
A Study on Protection of Cables by Solkor Differential Protection Relay with ...
 
Switchgear and protection 3
Switchgear and protection 3Switchgear and protection 3
Switchgear and protection 3
 
IRJET- Overhead Line Protection with Automatic Switch by using PLC Automation
IRJET- Overhead Line Protection with Automatic Switch by using PLC AutomationIRJET- Overhead Line Protection with Automatic Switch by using PLC Automation
IRJET- Overhead Line Protection with Automatic Switch by using PLC Automation
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment Designers
 
substation protection basics.ppt
substation protection basics.pptsubstation protection basics.ppt
substation protection basics.ppt
 
1 transmission
1 transmission1 transmission
1 transmission
 
ABB uno TL Plus
ABB uno TL PlusABB uno TL Plus
ABB uno TL Plus
 
Platform touch voltage protection membrane system and other railways buildin...
Platform touch voltage protection membrane system  and other railways buildin...Platform touch voltage protection membrane system  and other railways buildin...
Platform touch voltage protection membrane system and other railways buildin...
 
Digital transformer protection systems
Digital transformer protection systemsDigital transformer protection systems
Digital transformer protection systems
 
Power system protection seminar report
Power system protection seminar reportPower system protection seminar report
Power system protection seminar report
 

Dernier

A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxmaisarahman1
 
kiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal loadkiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal loadhamedmustafa094
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXssuser89054b
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxJuliansyahHarahap1
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptxJIT KUMAR GUPTA
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startQuintin Balsdon
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"mphochane1998
 
Online electricity billing project report..pdf
Online electricity billing project report..pdfOnline electricity billing project report..pdf
Online electricity billing project report..pdfKamal Acharya
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwaitjaanualu31
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityMorshed Ahmed Rahath
 
Wadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptxWadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptxNadaHaitham1
 
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdfAldoGarca30
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesMayuraD1
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Arindam Chakraborty, Ph.D., P.E. (CA, TX)
 
Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersMairaAshraf6
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdfKamal Acharya
 
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Servicemeghakumariji156
 
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Call Girls Mumbai
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTbhaskargani46
 

Dernier (20)

A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
 
kiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal loadkiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal load
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
 
Online electricity billing project report..pdf
Online electricity billing project report..pdfOnline electricity billing project report..pdf
Online electricity billing project report..pdf
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
Wadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptxWadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptx
 
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to Computers
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
 
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 

03_Prot.transmission_Line.pdf

  • 1. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F1 of 30 Protection in Transmission Networks ABB Protection in Transmission Networks
  • 2. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F2 of 30 Protection in Transmission Networks ABB List of content Course C02EN, Part Application of Line- and Transformer Protection Introduction Principles suitable for network protection Short discussion of preferred principles depending on application Current abbreviations Line Protection Kind of faults Protection Schemes (redundancy, back-up) Basic principle of distance protection Autoreclosing Transformer Protection Kinds of faults Protection Schemes (redundancy, back-up) Basic principle of transformer differential protection Example of distance protection setting
  • 3. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F3 of 30 Protection in Transmission Networks ABB The data-flow Data Input Data Preparation Data Processing Data Evaluation Data Output Data Storage Data Transfer (local and remote) PROCESS G G L L L L L PROCESS PROTECTION/CONTROL - UNIT/SYSTEM MMC
  • 4. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F4 of 30 Protection in Transmission Networks ABB From the problem to the solution Data Input Data Preparation Data Processing Data Evaluation Data Output Data Storage Data Transfer (local and remote) PROCESS G G L L L L L PROCESS PROTECTION/CONTROL - UNIT/SYSTEM Problems Implications - 3-phase faults - 2-phase faults - Earth-faults - high impedance faults - lightning - evolving faults - power swings - power reversals - swich-onto-faults - load impedances - CT saturation - VT failure - long lines - short lines - parallel lines - intermediate infeeds - week infeeds - heavily loaded lines - different grounding systems - overheadlines and cables etc. - damage to living beings and material - fire - explosions - overvoltages and overcurrents - influence on neighbouring devices - voltage increase during earthfaults - high step and touch voltages - loss of energy and black-outs - semaphor effect - influence of the zero-sequence impedance - influence of the mutual zero-sequence impedance etc. MMC Requirements - Availability - Simplicity - Flexibility - Reliability (Dependability, Security, Consistency) - Selectivity - Stability - Speed - Accuracy - Sensitivity Solutions - Prot. functions (I, IN, Id, E/F, DEF, >U, TH, etc.) - Control functions (AR, SYN, Interlocking, etc.) - Monitoring functions (Selfsup., Trip circuit sup., etc.) - Evaluation functions (Disturbance rec., Eventrec., etc.) - Communication (Bay comm., Station comm., etc.) - Calculations (Short circuit, Load flow, Setting calc., etc.) - Engineering and Testing - Filtering, galvanic separation etc.
  • 5. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F5 of 30 Protection in Transmission Networks ABB Measuring quantities and Measuring principles Used for auxiliary functions, such as stabilising features Current Phase quantities Symmetrical component quantities Phase quantities Symmetrical component- quantities Mixed phase- quantities Transient components Fundamental frequency components Higher harmonics Voltage and current Voltage and current Phase quantities Distance prot. Directional overcurrent prot. Directional comparison prot. Line differential- or Phase comparison prot. Time-/ distance- graded Overcurrent prot. Unit prot.
  • 6. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F6 of 30 Protection in Transmission Networks ABB Types of protection, some definitions and abbreviations ¾ Overcurrent ¾ with current independent time delay (definite time) ¾ with current dependent time delay IDMTL (Inverse time, with Definitive Minimum Time Lag) 0.1 1 10 100 1 10 30 20 8 6 4 2 3 Tripping time in seconds 1 I I β k t[s] set α set −       ⋅ = Several inverse-time characteristics are available, most of them follow the term: I / Iset
  • 7. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F7 of 30 Protection in Transmission Networks ABB Types of protection, some definitions and abbreviations ¾ Directional comparison functioning in POTT (tripping) or BLOCKING mode ¾ Phase comparison Phase-angles of the currents of both line ends are compared ¾ Differential Full currents, amplitudes and phase-angles compared ¾ Biased differential Diff. circuit with low impedance Biased = restrained = pick-up value is current dependent ¾ High-impedance Diff. circuit with high impedance differential Matched CT‘s required, exclusively for this protection ¾ REF Restricted Earth Fault High-impedance differential earth fault function protects one transformer winding (restricted to one winding)
  • 8. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F8 of 30 Protection in Transmission Networks ABB Types of protection, some definitions and abbreviations ¾ Distance protection = Directional multi-zone impedance protection Non-switched: 6 loops per zone and min. 3 zones simultaneously measured, one or several time delayed zones (= state of the art) Switched: 1 loop measured, zone switching by timer (= older conventional types) Mho type: directional circular measuring characteristic Offset Mho type: directional circular „open“ characteristic, healthy voltage and/or memory voltage polarised for enhanced directionality Polygon type: polygonal characteristic with healthy voltage and/or memory voltage polarised directional function
  • 9. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F9 of 30 Protection in Transmission Networks ABB Types of protection, some definitions and abbreviations ¾ Communication between line ends, by carrier (PLC), fibre optics or microwave PUTT Permissive underreaching transfer trip POTT Permissive overreaching transfer trip with add. logic's to cover cases with one weak infeed end ECHO: in case of weak infeed, a received signal is “echo-ed” back, and the strong end will trip WIE Trip: Trip of weak infeed-end by received comm. signal + add. logic’s UNBLOCK: simulates „signal receive“ in case of a carrier fail during a fault on the line (useful for overhead lines with PLC communication) BLOCKING: Overreaching blocking ¾ Phase selector = used for single-pole autoreclosure and for events / alarms
  • 10. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F10 of 30 Protection in Transmission Networks ABB Types of protection, some definitions and abbreviations ¾ DEF = Directional earth fault prot. Zero-sequence directional prot., often functioning in a communication scheme ¾ AR = Autoreclosing Single- or three-pole high speed AR and/or one- or multishot three-pole delayed AR ¾ Distance to fault locator = displays the distance to the fault Mutual compensation: compensated by 3I0 of the parallel overhead line Load compensation: corrects the influence of load in case of resistive faults
  • 11. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F11 of 30 Protection in Transmission Networks ABB Line Protection
  • 12. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F12 of 30 Protection in Transmission Networks ABB Line fault types < 230 kV >230 kV Type of fault: Single Phase 60 % 85 % Two Phase 30 % 10 % Three Phase 10 % 5 % ---------- ---------- 100 % 100 %
  • 13. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F13 of 30 Protection in Transmission Networks ABB Typical line protection schemes A. Distance function with communication scheme to the opposite line end and time delayed overreaching back-up zones B. Line differential function combined with a distance function for back-up 1. Non-redundant schemes Main 1 Main 2 C. Distance function Same as Main 1 with communication and back-up zones (same as A) D. ditto Line differential function combined with distance for back-up. E. ditto Directional comparison prot. F. ditto Phase comparison prot. G. ditto Rate of change function in directional comparison 2. Redundant schemes To detect high resistive ground faults, above protection schemes are often combined with a zero sequence overcurrent protection with inverse time delay or by a directional comparison DEF scheme
  • 14. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F14 of 30 Protection in Transmission Networks ABB Line Protection, Basic Versions Protection 1 Protection 2 Control (Main 1) (Main 2 / Back-up) (Option) Medium Voltage High Voltage <= 36kV <=72.5kV <=145kV <=245 kV <=765 kV I> + IN AR/SYN Dir I> + IN AR/SYN Id I>+IN AR/SYN Id Z< AR/SYN Z< AR/SYN Z< I>+IN AR/SYN Z< Z<+IN AR/SYN Z< + DEF Z<+IN AR/SYN Z< + DEF+IN Z< +DEF+IN AR/SYN DirComp+DEF Z<+IN AR/SYN DirComp+DEF+IN Z<+DEF+IN AR/SYN
  • 15. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F15 of 30 Protection in Transmission Networks ABB Line Protection
  • 16. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F16 of 30 Protection in Transmission Networks ABB Line Protection DEF 2- or 1 ½ - CB arrangements Single CB scheme in single- or multi-busbar arrangements
  • 17. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F17 of 30 Protection in Transmission Networks ABB Selective line protection scheme with single end infeed 1,4s 0,8s 1,4s 1,4s 1,1s 1,1s 0s 0,5s 0s 0s 0,3s 1,1s = Time overcurrent relays = Time overcurrent relays and directional relays, which only permit tripping, if the fault is in the direction of the line. 0,3s 0s 0,8s 0,5s
  • 18. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F18 of 30 Protection in Transmission Networks ABB The stepped time / distance characteristic of a distance relay T = Protected line length t1...t4 = Time steps t = Operating time I = Distance from relay = Distance relay A, B = Stations A t1 t3 t4 t t2 T B I 0,85...0,9 T
  • 19. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F19 of 30 Protection in Transmission Networks ABB Distance relay grading diagram t A B C D = Distance relay t = Operating time
  • 20. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F20 of 30 Protection in Transmission Networks ABB Principle of the distance function (simplified) ≈ I Relay ZS ZL UG U k0 3I0 I U Z ph ground ph L ⋅ + = − L S G Z Z U I + = S R ph ph L I I U Z − = − for 2- and 3-phase faults for single-phase to ground faults Operation will take place, if: I > Iset AND ZL < Zset AND Fault forward
  • 21. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F21 of 30 Protection in Transmission Networks ABB Distance characteristic Polygon - type ZONE 3 ZONE 2 ZONE 1 OVERREACHING- ZONE REVERSE DIRECTED ZONE R1 UNDERIMPEDANCE- CHARACTERISTC jX1
  • 22. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F22 of 30 Protection in Transmission Networks ABB Line data, required for protection setting Bundle conductor with 2, 3, 4 conductors Zm0 = mutual zero sequence impedance Ground-conductor Positive sequence impedance = Z1 = R1+j·X1 Negative sequence impedance = Z2 = Z1 Zero sequence impedance of a single line Z0 = R0+j·X0 For parallel overhead lines on common towers additionally: Mutual zero sequence impedance Zm0 = Rm0+j·X0 or Zero sequence impedance of a double circuit line Z0’’ = Z0 + Zm0
  • 23. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F23 of 30 Protection in Transmission Networks ABB Impedance - grading Z3 < 0.85 (a+k·b2) 1.2 a < Z2 < 0.85 (a+k·b1) Z1 ≈ 0.85·a ZOR ≈ 1,2·a a b A B C b2 b1
  • 24. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F24 of 30 Protection in Transmission Networks ABB Infeed factor k ≈ Impedance measured by overreaching zones of relay A la d·Zc Ia + Ib Ib A Za ≈ Ia Z = Za + d·Zc (la + Ib) la Z = Za + k ·d·Zc where k = 1 + Ib
  • 25. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F25 of 30 Protection in Transmission Networks ABB Due to load-flow, the fault resistance RF appears as an enlarged and complex impedance (so called „Semaphor- effect“) ≈ ≈ IphA UF B ZL IphB RF UA UB UF = RF (IphA+ IphB) Z as „seen“ by the distance protection = With load-flow from A Æ B With load-flow from B Æ A RF as for single end infeed jX R ZL phA phB phA I I I RF + ⋅ ( ) phA phB phA I I I RF ZL Z + ⋅ + =
  • 26. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F26 of 30 Protection in Transmission Networks ABB Permissive Underreaching Transfer Tripping (PUTT) Tripping criterion in B Zone 1 of the distance function AND phase-selector Tripping time in B no intentional delay Tripping criterion in C Receive of signal from B AND overreaching zone AND phase-selector Tripping time in C Zone 1 in B plus signal transmission time This mode is widely used, since unequal characteristics of relays in A and B do not harm the protection system performance Tone Rx/Tx = NSD Relay B NSD (Tone) Relay C Protected line Zone 1 of relay in B Zone 1 of relay in C B C PLC PLC = power line carrier
  • 27. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F27 of 30 Protection in Transmission Networks ABB Permissive Overreaching Transfer Tripping (POTT) Protected line B C Tripping criteria = {Zone 1 OR [receive_of_signal AND overreaching_zone]} AND (phase-selector) Tripping time = No intentional delay for fault in zone 1 Measuring time of overreaching zone in opposite relay plus signal transmission time. Additional logic's to cover weak infeed conditions : • “Echo”-Logic allows fast tripping of the end with strong infeed • Weak-infeed logic allows tripping of the end with weak infeed Preferred mode for cable lines, short overhead lines and for series compensated lines. Overreaching zone of relay B Relay B Overreaching zone of relay C Relay C NSD NSD PLC PLC
  • 28. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F28 of 30 Protection in Transmission Networks ABB Line differential protection with fibre-optical communication 800/1A 1000/1A E O E O A D DIFF A D E O E O DIFF F.O. < 28 km With FOX (MUX) up to approx. 120 km REL 316 REL 316 A/D = analogue / digital converter E/O = electrical / optical converter
  • 29. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F29 of 30 Protection in Transmission Networks ABB Autoreclosing on overhead lines (AR) HSAR, single pole DAR, always three pole Start 1-phase Trip 3-pole 3-pole discriminating time DAR open time Start Trip 3-pole High speed HSAR Delayed DAR Start 1-phase Trip 1-pole 1-pole discriminating time Close pulse, interrupted by new trip Single-pole open time Q0 Phase R Q0 Phase S Q0 Phase T
  • 30. ABB Power Automation Ltd T2313 / C02e_2001.ppt / F30 of 30 Protection in Transmission Networks ABB Zone 1 used as underreaching PLC-independent trip X (Zone 1) = 37.1Ω ·0.8 = 29.7 Ω primary ⇒ 12.9 Ω secondary; k0 = 0.74; t1 = 0.0 s set to 80% of full line instead of the usual 85%, since CVT’s (capacitive voltage transformers) are used R (Zone 1) = 30 Ω primary ⇒ 13.0 Ω secondary Zone OR used for the PUTT-scheme X (Zone OR) >37.1 Ω ·1.5 = 55.6 Ω primary ⇒ 24.2 Ω secondary; k0 = 0.74; tOR = 0.0 s R (Zone OR) = 40 Ω primary ⇒ 17.4 Ω secondary this zone shall cover the full line A- B with a good safety margin Note: To simplify we assume X ≈ Z.