SlideShare une entreprise Scribd logo
1  sur  23
Newport Fire Department
Department of Training
December 2009
Updated 07 March 2014
Purpose
 To provide a standardized operation and response to
Municipal Box and Local Alarms within the City of
Newport.
 To provide the reset procedures for the Control
Panel/Radio Box.
Radio Box Alarms Categories
 Master (Radio)Box Alarms (3 Rounds)
 Trouble Alarms
 AC Fail
 Low Battery
 Transmitter Failure
 Supervisory
 Tilt/Intruder
 Sprinkler Tamper
 No Function
Typical Alarm Zones
 Zone 1 – (Alarm) All fire detection devices
 Zone 2 – (Alarm) Main water flow
 Zone 3 – (Alarm) Ansul system
 Zone 9 – (Trouble) Supervisory
 Sprinkler tampers
 Generator running
 Miscellaneous
 Zone 0 (TEST ZONE) – Trouble with Radio Box (more
information later in presentation)
 Other Zones may be specific to occupancy hazard
areas
Procedure
 Local and Municipal Alarm Systems
 Upon arrival on the scene the Officer-In-Charge (OIC)
shall announce the zone and location of the alarm.
 Upon investigation of the Fire Alarm Control Panel
(FACP), the OIC shall perform four (4) steps:
1. Acknowledge
2. Silence
3. Reset
4. Inspect the Radio Box
(if applicable) to visualize the zone is clear
Acknowledge (“ACK”)
 This function is used to acknowledge an abnormal
situation such as an alarm, trouble or supervisory. The
acknowledge function tells the panel that emergency
responders are aware of the alarm, trouble, or supervisory
condition.
 Pressing acknowledge will identify the device or zone
in alarm, if not already identified on the FACP.
 Be aware when acknowledging the alarm that multiple
alarms may be indicated.
 Simply scroll through the alarms to identify them, and
investigate all zones and/or devices.
Silence
 Stops the bells from sounding, but also allows the
radio box to transmit further alarms.
 Press silence after the cause has been determined to
ensure that all occupants have exited the building.
 Acknowledge and Silence should release the zones in
the Radio Box.
Reset
 Reset will return the FACP to a normal state (after
pressing “acknowledge and silence” buttons).
 If the alarm does NOT reset, or a heat or smoke
detector will not clear:
 Acknowledge and Silence the system
 Do NOT press RESET. Issue an Impairment Notice.
 This will leave the detector or zone locked in alarm so the
Alarm Company technician can resolve the problem.
 You must issue the owner an Impairment Notice, and
notify the alarm company of the condition of the system
 Do not leave the notification up to the owner!
FCI Panel Zone will be indicated by a Red
alarm, or Yellow/Orange Trouble
light
• If no zone is indicated, a bulb
may be burned out.
• Hold the test lamp button, and
find the bulb that does NOT light.
It may be the zone in alarm.
“Acknowledge” “Silence”
• There is NO “Acknowledge
“Button
• Silence the Alarm
• Reset the Alarm – hold for 5
seconds
• After the alarm is reset, the
panel may beep or ring.
• This is to notify you that the
alarm is still in the “Silence”
mode.
• Put Alarm back to “Normal”
and the beep or ring will stop.
Lock Out Zone
• If the box will not reset.
You may “Lock Out” the
zone.
• Push/Pull the zone
card toggle to lock out
the zone.
• Then reset the system
as noted previously
Radio Box Inspection
 Open the radio box to ensure
that all zones are clear.
 This can be done by opening
the Radio Box and making
sure the lights for the
corresponding zones are off.
FAULT Indicator
Whenever the door is opened to the Radio
Box, the “Fault” Indicator light will turn
on.
• This is a Tilt/Intruder indicator.
To ensure that the radio box is truly clear,
you must push, and hold, the plunger by
hand when the door is open.
If the fault clears, the panel is normal.
If not, issue an impairment notice.
Trouble Alarms
 Trouble Alarms are related to an issue in the
RADIO BOX Only!
 Zone 0 (zero) is the TEST Zone (24 hr test)
 Response depends on the ZONE that comes in
 If the TROUBLE ALARM comes in as a Zone 0 (Zero),
then only 1 Engine is required.
 If the TROUBLE comes in as any other Zone, then a Full
Box Alarm Response is required. (whether it states
Trouble or Not).
Trouble Alarms
 All municipally connected fire alarm systems are required
to have a sixty (60) hour battery backup power supply.
 When the power to a Radio Box is interrupted for any
reason it will automatically switch to battery power –
indicating “Trouble”.
 Other Trouble Alarm indications:
 a contaminated smoke detector or an electrical problem
within the system.
 Disabled zones, low power on the backup battery, the
disabling of a notification appliance, or open circuits.
 In a trouble condition, the panel displays the zone or
devices causing the condition. The "Trouble" indicator
goes out automatically when the situation causing the
trouble condition is rectified.
AC Fail
 Nine (9) hours after an interruption of power, the
Radio Box is programmed to send out an “AC Fail”
signal.
 The nine hour delay is to give whoever interrupted the
power supply time to restore it.
 RESPONSE:
 An engine shall be dispatched at the nine hour point to
determine why the AC power has not been restored.
 If there is no attempt being made to restore the power,
you should contact the 24-hour emergency number on
the FACP and let them know the system is impaired, and
issue an Impairment Notice
Low Battery
 The Low Battery signal is for the Radio Box battery only, not the
FACP batteries.
 This signal can mean one of two things:
1. The level of the battery is getting to the point of not having
the power to transmit an alarm or trouble signal.
2. The newer Radio Boxes have a test feature that puts a load
test on the battery.
 RESPONSE:
 An engine shall be dispatched to see if AC power has been
interrupted, and if so, get the problem corrected
 IF AC power is OK, this usually means the battery needs to be
replaced.
 The 1st time you respond to this scenario, you may push the test
button in the Radio Box. This will reset the battery test feature.
 If you respond a 2nd time, issue an Impairment Notice.
Transmitter Failure
 The box may buzz or ring to indicate failure
 Response: Full Box Alarm Response (1st time)
 For Transmitter Failure, press the “Tx Reset” button to
reset the system.
 If you respond a 2nd time to the same location: DO NOT
reset the transmitter. This will enable the alarm
company to track down the problem.
 Issue an Impairment Notice, and notify the owner and
alarm company.
 Tx Trouble – indicates the transmitting signal is
drifting out of the optimal range.
Supervisory
 This signal indicates that a portion of the building's
fire protection system has been disabled (such as a fire
sprinkler control valve being closed or a sprinkler
tamper switch being activated)
 Depending on the system's design, the supervisory
point may be latching, meaning the panel must be
reset to clear the supervisory condition, or non-
latching, meaning the indicator automatically goes out
when the condition has cleared.
Impairment Notices
 When issuing an Impairment
Notice, it must be given
directly to the owner (not the
tenant) OR,
 You must notify the 24 hour
emergency contact (Alarm
Company), and let them
know what the problem is,
and where the Impairment
Notice form is located.
Equipment Ownership
 The property owner owns the Radio Box and all fire
alarm equipment.
 The owner is responsible to keep it 100% operational.
 Any time you issue an impairment notice, even if you
hand deliver it to someone on the scene, you are still
required to notify the alarm company of the
impairment.
 If the problem cannot be fixed, the OIC must issue an
impairment notice, and notify the alarm company of
the impairment
Other Information
 The owner of the fire alarm system is required to
provide a 24 hour emergency number for the owner or
the owner’s representative for the department to call in
the event of an alarm or trouble.
 The number must be conspicuously located at the
FACP.
Questions?

Contenu connexe

Tendances

Fire Extinguisher Safety Training
Fire Extinguisher Safety TrainingFire Extinguisher Safety Training
Fire Extinguisher Safety Training
shajukhan21
 
Fire Extinguisher Training
Fire Extinguisher TrainingFire Extinguisher Training
Fire Extinguisher Training
Jared Hiett
 

Tendances (20)

Fire detection and alarm system
Fire detection and alarm systemFire detection and alarm system
Fire detection and alarm system
 
Fm 200 system - working and isolation method
Fm 200 system - working and isolation method Fm 200 system - working and isolation method
Fm 200 system - working and isolation method
 
Fire alarm systems
Fire alarm systemsFire alarm systems
Fire alarm systems
 
FAS
FASFAS
FAS
 
fire alarm system
 fire alarm system fire alarm system
fire alarm system
 
Fire alarm system Research
Fire alarm system ResearchFire alarm system Research
Fire alarm system Research
 
Fire Detection and Alarm System (FDAS).pptx
Fire Detection and Alarm System (FDAS).pptxFire Detection and Alarm System (FDAS).pptx
Fire Detection and Alarm System (FDAS).pptx
 
Fire Detection and Alarm Systems
Fire Detection and Alarm SystemsFire Detection and Alarm Systems
Fire Detection and Alarm Systems
 
FIRE SAFETY - EMERGENCY ESCAPE PLAN
FIRE SAFETY - EMERGENCY ESCAPE PLANFIRE SAFETY - EMERGENCY ESCAPE PLAN
FIRE SAFETY - EMERGENCY ESCAPE PLAN
 
Fire_Fighting_Training-pdf
Fire_Fighting_Training-pdfFire_Fighting_Training-pdf
Fire_Fighting_Training-pdf
 
EMERGENCY RESPONSE TEAM (ERT).pptx
EMERGENCY RESPONSE TEAM (ERT).pptxEMERGENCY RESPONSE TEAM (ERT).pptx
EMERGENCY RESPONSE TEAM (ERT).pptx
 
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire ProtectionExit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection
 
Portable fire extinguisher training
Portable fire extinguisher trainingPortable fire extinguisher training
Portable fire extinguisher training
 
Firefighting training
Firefighting trainingFirefighting training
Firefighting training
 
Fire Extinguisher Safety Training
Fire Extinguisher Safety TrainingFire Extinguisher Safety Training
Fire Extinguisher Safety Training
 
Fire alarm protection & alarm detection system
Fire alarm protection & alarm detection systemFire alarm protection & alarm detection system
Fire alarm protection & alarm detection system
 
Fire Extinguisher Training
Fire Extinguisher TrainingFire Extinguisher Training
Fire Extinguisher Training
 
Fire Drill
Fire DrillFire Drill
Fire Drill
 
Fundamental training on Fire Detection & Alarm System
Fundamental training on Fire Detection & Alarm SystemFundamental training on Fire Detection & Alarm System
Fundamental training on Fire Detection & Alarm System
 
Fire safety new.pptx
Fire safety new.pptxFire safety new.pptx
Fire safety new.pptx
 

En vedette

4010 front-panel-installing,-operating-and-programming-manual
4010 front-panel-installing,-operating-and-programming-manual4010 front-panel-installing,-operating-and-programming-manual
4010 front-panel-installing,-operating-and-programming-manual
Heru Heru
 
Basic Fire Alarm Systems
Basic Fire Alarm SystemsBasic Fire Alarm Systems
Basic Fire Alarm Systems
malcolmfd
 
4 materi pendekatan model pemb kur'13 -edit syahril 290914
4 materi pendekatan model pemb kur'13 -edit syahril 2909144 materi pendekatan model pemb kur'13 -edit syahril 290914
4 materi pendekatan model pemb kur'13 -edit syahril 290914
EKO SUPRIYADI
 
Metis by Mircom presentation 2016 08 16
Metis by Mircom presentation 2016 08 16Metis by Mircom presentation 2016 08 16
Metis by Mircom presentation 2016 08 16
Howard Ryan
 
TDX - TDH800 Brochure.PDF
TDX - TDH800 Brochure.PDFTDX - TDH800 Brochure.PDF
TDX - TDH800 Brochure.PDF
Jason Bull
 
Lte tdd-the-global-solution-for-unpaired-spectrum
Lte tdd-the-global-solution-for-unpaired-spectrumLte tdd-the-global-solution-for-unpaired-spectrum
Lte tdd-the-global-solution-for-unpaired-spectrum
Muhammad Rauf Akram
 

En vedette (20)

4010 front-panel-installing,-operating-and-programming-manual
4010 front-panel-installing,-operating-and-programming-manual4010 front-panel-installing,-operating-and-programming-manual
4010 front-panel-installing,-operating-and-programming-manual
 
Basic Fire Alarm Systems
Basic Fire Alarm SystemsBasic Fire Alarm Systems
Basic Fire Alarm Systems
 
Fire Alarm, Smoke Detector and Automatic Sprinkle System
Fire Alarm, Smoke Detector and Automatic Sprinkle SystemFire Alarm, Smoke Detector and Automatic Sprinkle System
Fire Alarm, Smoke Detector and Automatic Sprinkle System
 
Programa oficial reunion n°5 28 08-2016
Programa oficial reunion n°5 28 08-2016Programa oficial reunion n°5 28 08-2016
Programa oficial reunion n°5 28 08-2016
 
Fire Fighting Enterprises Presentation
Fire Fighting Enterprises PresentationFire Fighting Enterprises Presentation
Fire Fighting Enterprises Presentation
 
4 materi pendekatan model pemb kur'13 -edit syahril 290914
4 materi pendekatan model pemb kur'13 -edit syahril 2909144 materi pendekatan model pemb kur'13 -edit syahril 290914
4 materi pendekatan model pemb kur'13 -edit syahril 290914
 
Clifford & Snell - Manual Call Point, Hazardous Area (ATEX) - Yodalex MCP
Clifford & Snell - Manual Call Point, Hazardous Area (ATEX) - Yodalex MCPClifford & Snell - Manual Call Point, Hazardous Area (ATEX) - Yodalex MCP
Clifford & Snell - Manual Call Point, Hazardous Area (ATEX) - Yodalex MCP
 
Metis by Mircom presentation 2016 08 16
Metis by Mircom presentation 2016 08 16Metis by Mircom presentation 2016 08 16
Metis by Mircom presentation 2016 08 16
 
16 9 болдырев в.и
16 9 болдырев в.и16 9 болдырев в.и
16 9 болдырев в.и
 
Recomandare PwC
Recomandare PwCRecomandare PwC
Recomandare PwC
 
Triax
TriaxTriax
Triax
 
Smart Batteries
Smart BatteriesSmart Batteries
Smart Batteries
 
Some Interesting Marketing Charts about Technology 2013
Some Interesting Marketing Charts about Technology 2013Some Interesting Marketing Charts about Technology 2013
Some Interesting Marketing Charts about Technology 2013
 
TDX - TDH800 Brochure.PDF
TDX - TDH800 Brochure.PDFTDX - TDH800 Brochure.PDF
TDX - TDH800 Brochure.PDF
 
Whats my address
Whats my addressWhats my address
Whats my address
 
Lte tdd-the-global-solution-for-unpaired-spectrum
Lte tdd-the-global-solution-for-unpaired-spectrumLte tdd-the-global-solution-for-unpaired-spectrum
Lte tdd-the-global-solution-for-unpaired-spectrum
 
LS-RDIO0404 Wireless I/O module
LS-RDIO0404 Wireless I/O moduleLS-RDIO0404 Wireless I/O module
LS-RDIO0404 Wireless I/O module
 
Scaling the Network - Rise of the Thing
Scaling the Network - Rise of the ThingScaling the Network - Rise of the Thing
Scaling the Network - Rise of the Thing
 
Hanwha introduction pt(may)
Hanwha introduction pt(may)Hanwha introduction pt(may)
Hanwha introduction pt(may)
 
Tenow
TenowTenow
Tenow
 

Similaire à Fire Alarm Control Panel Operations

cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
nipunwijewardhana
 
Omni Guard 660 Flame Detector Presentation
Omni Guard 660 Flame Detector PresentationOmni Guard 660 Flame Detector Presentation
Omni Guard 660 Flame Detector Presentation
Mustafa Ali
 

Similaire à Fire Alarm Control Panel Operations (20)

Mini 2 zones Conventional Fire Alarm Control Panel
Mini 2 zones Conventional Fire Alarm Control PanelMini 2 zones Conventional Fire Alarm Control Panel
Mini 2 zones Conventional Fire Alarm Control Panel
 
SenseTek Fireray 3000 installers handbook
SenseTek Fireray 3000 installers handbookSenseTek Fireray 3000 installers handbook
SenseTek Fireray 3000 installers handbook
 
Manual pop 004308
Manual pop 004308Manual pop 004308
Manual pop 004308
 
B 737NG Warning systems.
B 737NG Warning systems.B 737NG Warning systems.
B 737NG Warning systems.
 
3 in 1 multi sensor Philio PSM01 (door, window, temperature, lightness) manual
3 in 1 multi sensor Philio PSM01 (door, window, temperature, lightness) manual3 in 1 multi sensor Philio PSM01 (door, window, temperature, lightness) manual
3 in 1 multi sensor Philio PSM01 (door, window, temperature, lightness) manual
 
HST New Fire Alarm System
HST New Fire Alarm SystemHST New Fire Alarm System
HST New Fire Alarm System
 
Everspring sp816 user manual
Everspring sp816 user manualEverspring sp816 user manual
Everspring sp816 user manual
 
500plus
500plus500plus
500plus
 
gersgtsedgdfgsrqw3terydrh
gersgtsedgdfgsrqw3terydrhgersgtsedgdfgsrqw3terydrh
gersgtsedgdfgsrqw3terydrh
 
Fire detection system operation
Fire detection system operationFire detection system operation
Fire detection system operation
 
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
 
02 - HQManual.pdf
02 - HQManual.pdf02 - HQManual.pdf
02 - HQManual.pdf
 
Manual de instalacion detector honeywell
Manual de instalacion detector honeywellManual de instalacion detector honeywell
Manual de instalacion detector honeywell
 
Evespring ST812 Z-Wave flood sendor manual in English
Evespring ST812 Z-Wave flood sendor manual in EnglishEvespring ST812 Z-Wave flood sendor manual in English
Evespring ST812 Z-Wave flood sendor manual in English
 
Portable radios 2
Portable radios 2Portable radios 2
Portable radios 2
 
Installation problems
Installation problemsInstallation problems
Installation problems
 
Lecture 5 Fire Alarm System.pdf
Lecture 5 Fire Alarm System.pdfLecture 5 Fire Alarm System.pdf
Lecture 5 Fire Alarm System.pdf
 
Omni Guard 660 Flame Detector Presentation
Omni Guard 660 Flame Detector PresentationOmni Guard 660 Flame Detector Presentation
Omni Guard 660 Flame Detector Presentation
 
4 in 1 multi sensor Philio PSM02 (motion, door/window, temperature, lightness)
4 in 1 multi sensor Philio PSM02 (motion, door/window, temperature, lightness)4 in 1 multi sensor Philio PSM02 (motion, door/window, temperature, lightness)
4 in 1 multi sensor Philio PSM02 (motion, door/window, temperature, lightness)
 
3 in 1 multisensor Philio PSP01 manual (motion, Temperature, lightness)
3 in 1 multisensor Philio PSP01 manual (motion, Temperature, lightness)3 in 1 multisensor Philio PSP01 manual (motion, Temperature, lightness)
3 in 1 multisensor Philio PSP01 manual (motion, Temperature, lightness)
 

Plus de Newport Fire Department

Plus de Newport Fire Department (19)

2014 NFD Incident Command # 4 Deployment
2014 NFD Incident Command # 4 Deployment2014 NFD Incident Command # 4 Deployment
2014 NFD Incident Command # 4 Deployment
 
2017 RI EMS Statewide Protocols - 2017-01
2017  RI EMS Statewide Protocols - 2017-012017  RI EMS Statewide Protocols - 2017-01
2017 RI EMS Statewide Protocols - 2017-01
 
2017 RI Statewide EMS Protocols Education Module - Section 9
2017 RI Statewide EMS Protocols Education Module - Section 92017 RI Statewide EMS Protocols Education Module - Section 9
2017 RI Statewide EMS Protocols Education Module - Section 9
 
2017 RI Statewide EMS Protocols Education Module - Section 8
2017 RI Statewide EMS Protocols Education Module - Section 82017 RI Statewide EMS Protocols Education Module - Section 8
2017 RI Statewide EMS Protocols Education Module - Section 8
 
2017 RI Statewide EMS Protocols Education Module - Section 7
2017 RI Statewide EMS Protocols Education Module - Section 72017 RI Statewide EMS Protocols Education Module - Section 7
2017 RI Statewide EMS Protocols Education Module - Section 7
 
2017 RI Statewide EMS Protocols Education Module - Section 6
2017 RI Statewide EMS Protocols Education Module - Section 62017 RI Statewide EMS Protocols Education Module - Section 6
2017 RI Statewide EMS Protocols Education Module - Section 6
 
2017 RI Statewide EMS Protocols Education Modules - Section 4
2017 RI Statewide EMS Protocols Education Modules - Section 42017 RI Statewide EMS Protocols Education Modules - Section 4
2017 RI Statewide EMS Protocols Education Modules - Section 4
 
2017 RI Statewide EMS Protocols Education Module - Section 3
2017 RI Statewide EMS Protocols Education Module - Section 32017 RI Statewide EMS Protocols Education Module - Section 3
2017 RI Statewide EMS Protocols Education Module - Section 3
 
2017 RI Statewide EMS Protocols Education Module - Section 2
2017 RI Statewide EMS Protocols Education Module - Section 22017 RI Statewide EMS Protocols Education Module - Section 2
2017 RI Statewide EMS Protocols Education Module - Section 2
 
2017 RI Statewide EMS Protocols Education Modules - Section 1
2017 RI Statewide EMS Protocols Education Modules - Section 12017 RI Statewide EMS Protocols Education Modules - Section 1
2017 RI Statewide EMS Protocols Education Modules - Section 1
 
2017 RI Statewide EMS Protocols Education Module - Introduction
2017 RI Statewide EMS Protocols Education Module - Introduction2017 RI Statewide EMS Protocols Education Module - Introduction
2017 RI Statewide EMS Protocols Education Module - Introduction
 
2013.05.02 NFD Driver training introduction
2013.05.02   NFD Driver training introduction2013.05.02   NFD Driver training introduction
2013.05.02 NFD Driver training introduction
 
Strip Mall Fire Tactics & Strategies
Strip Mall Fire Tactics & StrategiesStrip Mall Fire Tactics & Strategies
Strip Mall Fire Tactics & Strategies
 
NBMTF search patterns
NBMTF search patternsNBMTF search patterns
NBMTF search patterns
 
GAR Model
GAR ModelGAR Model
GAR Model
 
NBMTF Communications Overview
NBMTF Communications OverviewNBMTF Communications Overview
NBMTF Communications Overview
 
NFD Incident Command # 3 Communications
NFD Incident Command # 3 CommunicationsNFD Incident Command # 3 Communications
NFD Incident Command # 3 Communications
 
Fire Officer Detail Training Program
Fire Officer Detail Training ProgramFire Officer Detail Training Program
Fire Officer Detail Training Program
 
Rope rescue set up
Rope rescue set upRope rescue set up
Rope rescue set up
 

Dernier

If this Giant Must Walk: A Manifesto for a New Nigeria
If this Giant Must Walk: A Manifesto for a New NigeriaIf this Giant Must Walk: A Manifesto for a New Nigeria
If this Giant Must Walk: A Manifesto for a New Nigeria
Kayode Fayemi
 
No Advance 8868886958 Chandigarh Call Girls , Indian Call Girls For Full Nigh...
No Advance 8868886958 Chandigarh Call Girls , Indian Call Girls For Full Nigh...No Advance 8868886958 Chandigarh Call Girls , Indian Call Girls For Full Nigh...
No Advance 8868886958 Chandigarh Call Girls , Indian Call Girls For Full Nigh...
Sheetaleventcompany
 
Chiulli_Aurora_Oman_Raffaele_Beowulf.pptx
Chiulli_Aurora_Oman_Raffaele_Beowulf.pptxChiulli_Aurora_Oman_Raffaele_Beowulf.pptx
Chiulli_Aurora_Oman_Raffaele_Beowulf.pptx
raffaeleoman
 

Dernier (20)

Report Writing Webinar Training
Report Writing Webinar TrainingReport Writing Webinar Training
Report Writing Webinar Training
 
Dreaming Music Video Treatment _ Project & Portfolio III
Dreaming Music Video Treatment _ Project & Portfolio IIIDreaming Music Video Treatment _ Project & Portfolio III
Dreaming Music Video Treatment _ Project & Portfolio III
 
lONG QUESTION ANSWER PAKISTAN STUDIES10.
lONG QUESTION ANSWER PAKISTAN STUDIES10.lONG QUESTION ANSWER PAKISTAN STUDIES10.
lONG QUESTION ANSWER PAKISTAN STUDIES10.
 
Re-membering the Bard: Revisiting The Compleat Wrks of Wllm Shkspr (Abridged)...
Re-membering the Bard: Revisiting The Compleat Wrks of Wllm Shkspr (Abridged)...Re-membering the Bard: Revisiting The Compleat Wrks of Wllm Shkspr (Abridged)...
Re-membering the Bard: Revisiting The Compleat Wrks of Wllm Shkspr (Abridged)...
 
Busty Desi⚡Call Girls in Sector 51 Noida Escorts >༒8448380779 Escort Service-...
Busty Desi⚡Call Girls in Sector 51 Noida Escorts >༒8448380779 Escort Service-...Busty Desi⚡Call Girls in Sector 51 Noida Escorts >༒8448380779 Escort Service-...
Busty Desi⚡Call Girls in Sector 51 Noida Escorts >༒8448380779 Escort Service-...
 
ANCHORING SCRIPT FOR A CULTURAL EVENT.docx
ANCHORING SCRIPT FOR A CULTURAL EVENT.docxANCHORING SCRIPT FOR A CULTURAL EVENT.docx
ANCHORING SCRIPT FOR A CULTURAL EVENT.docx
 
Causes of poverty in France presentation.pptx
Causes of poverty in France presentation.pptxCauses of poverty in France presentation.pptx
Causes of poverty in France presentation.pptx
 
If this Giant Must Walk: A Manifesto for a New Nigeria
If this Giant Must Walk: A Manifesto for a New NigeriaIf this Giant Must Walk: A Manifesto for a New Nigeria
If this Giant Must Walk: A Manifesto for a New Nigeria
 
No Advance 8868886958 Chandigarh Call Girls , Indian Call Girls For Full Nigh...
No Advance 8868886958 Chandigarh Call Girls , Indian Call Girls For Full Nigh...No Advance 8868886958 Chandigarh Call Girls , Indian Call Girls For Full Nigh...
No Advance 8868886958 Chandigarh Call Girls , Indian Call Girls For Full Nigh...
 
BDSM⚡Call Girls in Sector 97 Noida Escorts >༒8448380779 Escort Service
BDSM⚡Call Girls in Sector 97 Noida Escorts >༒8448380779 Escort ServiceBDSM⚡Call Girls in Sector 97 Noida Escorts >༒8448380779 Escort Service
BDSM⚡Call Girls in Sector 97 Noida Escorts >༒8448380779 Escort Service
 
Thirunelveli call girls Tamil escorts 7877702510
Thirunelveli call girls Tamil escorts 7877702510Thirunelveli call girls Tamil escorts 7877702510
Thirunelveli call girls Tamil escorts 7877702510
 
Chiulli_Aurora_Oman_Raffaele_Beowulf.pptx
Chiulli_Aurora_Oman_Raffaele_Beowulf.pptxChiulli_Aurora_Oman_Raffaele_Beowulf.pptx
Chiulli_Aurora_Oman_Raffaele_Beowulf.pptx
 
SaaStr Workshop Wednesday w/ Lucas Price, Yardstick
SaaStr Workshop Wednesday w/ Lucas Price, YardstickSaaStr Workshop Wednesday w/ Lucas Price, Yardstick
SaaStr Workshop Wednesday w/ Lucas Price, Yardstick
 
Dreaming Marissa Sánchez Music Video Treatment
Dreaming Marissa Sánchez Music Video TreatmentDreaming Marissa Sánchez Music Video Treatment
Dreaming Marissa Sánchez Music Video Treatment
 
Call Girl Number in Khar Mumbai📲 9892124323 💞 Full Night Enjoy
Call Girl Number in Khar Mumbai📲 9892124323 💞 Full Night EnjoyCall Girl Number in Khar Mumbai📲 9892124323 💞 Full Night Enjoy
Call Girl Number in Khar Mumbai📲 9892124323 💞 Full Night Enjoy
 
Introduction to Prompt Engineering (Focusing on ChatGPT)
Introduction to Prompt Engineering (Focusing on ChatGPT)Introduction to Prompt Engineering (Focusing on ChatGPT)
Introduction to Prompt Engineering (Focusing on ChatGPT)
 
ICT role in 21st century education and it's challenges.pdf
ICT role in 21st century education and it's challenges.pdfICT role in 21st century education and it's challenges.pdf
ICT role in 21st century education and it's challenges.pdf
 
Air breathing and respiratory adaptations in diver animals
Air breathing and respiratory adaptations in diver animalsAir breathing and respiratory adaptations in diver animals
Air breathing and respiratory adaptations in diver animals
 
Presentation on Engagement in Book Clubs
Presentation on Engagement in Book ClubsPresentation on Engagement in Book Clubs
Presentation on Engagement in Book Clubs
 
Mohammad_Alnahdi_Oral_Presentation_Assignment.pptx
Mohammad_Alnahdi_Oral_Presentation_Assignment.pptxMohammad_Alnahdi_Oral_Presentation_Assignment.pptx
Mohammad_Alnahdi_Oral_Presentation_Assignment.pptx
 

Fire Alarm Control Panel Operations

  • 1. Newport Fire Department Department of Training December 2009 Updated 07 March 2014
  • 2. Purpose  To provide a standardized operation and response to Municipal Box and Local Alarms within the City of Newport.  To provide the reset procedures for the Control Panel/Radio Box.
  • 3. Radio Box Alarms Categories  Master (Radio)Box Alarms (3 Rounds)  Trouble Alarms  AC Fail  Low Battery  Transmitter Failure  Supervisory  Tilt/Intruder  Sprinkler Tamper  No Function
  • 4. Typical Alarm Zones  Zone 1 – (Alarm) All fire detection devices  Zone 2 – (Alarm) Main water flow  Zone 3 – (Alarm) Ansul system  Zone 9 – (Trouble) Supervisory  Sprinkler tampers  Generator running  Miscellaneous  Zone 0 (TEST ZONE) – Trouble with Radio Box (more information later in presentation)  Other Zones may be specific to occupancy hazard areas
  • 5. Procedure  Local and Municipal Alarm Systems  Upon arrival on the scene the Officer-In-Charge (OIC) shall announce the zone and location of the alarm.  Upon investigation of the Fire Alarm Control Panel (FACP), the OIC shall perform four (4) steps: 1. Acknowledge 2. Silence 3. Reset 4. Inspect the Radio Box (if applicable) to visualize the zone is clear
  • 6. Acknowledge (“ACK”)  This function is used to acknowledge an abnormal situation such as an alarm, trouble or supervisory. The acknowledge function tells the panel that emergency responders are aware of the alarm, trouble, or supervisory condition.  Pressing acknowledge will identify the device or zone in alarm, if not already identified on the FACP.  Be aware when acknowledging the alarm that multiple alarms may be indicated.  Simply scroll through the alarms to identify them, and investigate all zones and/or devices.
  • 7. Silence  Stops the bells from sounding, but also allows the radio box to transmit further alarms.  Press silence after the cause has been determined to ensure that all occupants have exited the building.  Acknowledge and Silence should release the zones in the Radio Box.
  • 8. Reset  Reset will return the FACP to a normal state (after pressing “acknowledge and silence” buttons).  If the alarm does NOT reset, or a heat or smoke detector will not clear:  Acknowledge and Silence the system  Do NOT press RESET. Issue an Impairment Notice.  This will leave the detector or zone locked in alarm so the Alarm Company technician can resolve the problem.  You must issue the owner an Impairment Notice, and notify the alarm company of the condition of the system  Do not leave the notification up to the owner!
  • 9. FCI Panel Zone will be indicated by a Red alarm, or Yellow/Orange Trouble light • If no zone is indicated, a bulb may be burned out. • Hold the test lamp button, and find the bulb that does NOT light. It may be the zone in alarm.
  • 10. “Acknowledge” “Silence” • There is NO “Acknowledge “Button • Silence the Alarm • Reset the Alarm – hold for 5 seconds • After the alarm is reset, the panel may beep or ring. • This is to notify you that the alarm is still in the “Silence” mode. • Put Alarm back to “Normal” and the beep or ring will stop.
  • 11. Lock Out Zone • If the box will not reset. You may “Lock Out” the zone. • Push/Pull the zone card toggle to lock out the zone. • Then reset the system as noted previously
  • 12. Radio Box Inspection  Open the radio box to ensure that all zones are clear.  This can be done by opening the Radio Box and making sure the lights for the corresponding zones are off.
  • 13. FAULT Indicator Whenever the door is opened to the Radio Box, the “Fault” Indicator light will turn on. • This is a Tilt/Intruder indicator. To ensure that the radio box is truly clear, you must push, and hold, the plunger by hand when the door is open. If the fault clears, the panel is normal. If not, issue an impairment notice.
  • 14. Trouble Alarms  Trouble Alarms are related to an issue in the RADIO BOX Only!  Zone 0 (zero) is the TEST Zone (24 hr test)  Response depends on the ZONE that comes in  If the TROUBLE ALARM comes in as a Zone 0 (Zero), then only 1 Engine is required.  If the TROUBLE comes in as any other Zone, then a Full Box Alarm Response is required. (whether it states Trouble or Not).
  • 15. Trouble Alarms  All municipally connected fire alarm systems are required to have a sixty (60) hour battery backup power supply.  When the power to a Radio Box is interrupted for any reason it will automatically switch to battery power – indicating “Trouble”.  Other Trouble Alarm indications:  a contaminated smoke detector or an electrical problem within the system.  Disabled zones, low power on the backup battery, the disabling of a notification appliance, or open circuits.  In a trouble condition, the panel displays the zone or devices causing the condition. The "Trouble" indicator goes out automatically when the situation causing the trouble condition is rectified.
  • 16. AC Fail  Nine (9) hours after an interruption of power, the Radio Box is programmed to send out an “AC Fail” signal.  The nine hour delay is to give whoever interrupted the power supply time to restore it.  RESPONSE:  An engine shall be dispatched at the nine hour point to determine why the AC power has not been restored.  If there is no attempt being made to restore the power, you should contact the 24-hour emergency number on the FACP and let them know the system is impaired, and issue an Impairment Notice
  • 17. Low Battery  The Low Battery signal is for the Radio Box battery only, not the FACP batteries.  This signal can mean one of two things: 1. The level of the battery is getting to the point of not having the power to transmit an alarm or trouble signal. 2. The newer Radio Boxes have a test feature that puts a load test on the battery.  RESPONSE:  An engine shall be dispatched to see if AC power has been interrupted, and if so, get the problem corrected  IF AC power is OK, this usually means the battery needs to be replaced.  The 1st time you respond to this scenario, you may push the test button in the Radio Box. This will reset the battery test feature.  If you respond a 2nd time, issue an Impairment Notice.
  • 18. Transmitter Failure  The box may buzz or ring to indicate failure  Response: Full Box Alarm Response (1st time)  For Transmitter Failure, press the “Tx Reset” button to reset the system.  If you respond a 2nd time to the same location: DO NOT reset the transmitter. This will enable the alarm company to track down the problem.  Issue an Impairment Notice, and notify the owner and alarm company.  Tx Trouble – indicates the transmitting signal is drifting out of the optimal range.
  • 19. Supervisory  This signal indicates that a portion of the building's fire protection system has been disabled (such as a fire sprinkler control valve being closed or a sprinkler tamper switch being activated)  Depending on the system's design, the supervisory point may be latching, meaning the panel must be reset to clear the supervisory condition, or non- latching, meaning the indicator automatically goes out when the condition has cleared.
  • 20. Impairment Notices  When issuing an Impairment Notice, it must be given directly to the owner (not the tenant) OR,  You must notify the 24 hour emergency contact (Alarm Company), and let them know what the problem is, and where the Impairment Notice form is located.
  • 21. Equipment Ownership  The property owner owns the Radio Box and all fire alarm equipment.  The owner is responsible to keep it 100% operational.  Any time you issue an impairment notice, even if you hand deliver it to someone on the scene, you are still required to notify the alarm company of the impairment.  If the problem cannot be fixed, the OIC must issue an impairment notice, and notify the alarm company of the impairment
  • 22. Other Information  The owner of the fire alarm system is required to provide a 24 hour emergency number for the owner or the owner’s representative for the department to call in the event of an alarm or trouble.  The number must be conspicuously located at the FACP.