Panduit Unified Physical InfrastructureSM Solutions
Network Identification
and TIA-606-B
2
Properly identified physical infrastructure is easier to
install, maintain, and repair
TIA-606 A TIA-606 A, Addendum 1
TIA-606-B
[ISO/IEC 14763-2-1]
fs-an fs.xy-r:P
+fs.xy+r:P
TIA-942-A
fs.xy-r:Pfs-an
TIA-606B Scope
• Accommodates the scalable needs of telecommunications infrastructure systems
• Deals with commercial, industrial, residential, and data center premises
• Allows modular implementation of different elements of the standard depending
on size of telecommunications infrastructure
• Specifies formats and requirements of records, identifiers, and labels for
infrastructure components
4
Three key elements of
TIA-606-B
Identifiers
Labeling
Records
DC1.AD04-30:04/DC1.AF04-23:16
Class 1 Identifiers
• The following infrastructure elements shall be
identified:
– Telecommunications Space (TS)
– Cabinet, rack, enclosure, wall segment
– Patch panels or termination blocks
– Patch panel ports and termination positions
– Cables between cabinets, racks, and enclosures
– Cabling Subsystem 1 (horizontal) links
– Equipment and work area outlets
– Telecommunications main grounding busbar (TMGB)
– Telecommunications grounding busbar (TGB)
– Rack grounding busbar (RGB)
– Bonding conductors (BCT, TBB, GE)
f = numeric character(s) identifying the floor
s = alpha character identifying TS on floor f
This Telecommunication Space is “2A”
Telecommunication Space Identifier
fs
Cabinet/Rack Identifier
• fs = space
• xy = location in the space
• Using the room grid in the
data center this cabinet is
located at the intersection
of row AY and column 15
fs.xy
Patch Panel Identifier
• fs = space
• xy = rack location
• r = panel position in rack
• This patch panel is
located in position B on
the rack located at the
intersection of row AR
and column 15
fs.xy-r
Port Identifiers
• fs = space
• xy = rack location
• r = panel position in rack
• P = port position
• This port is position 12
located on patch panel 24
in cabinet AB04
fs.xy-r:P
Identification Solutions
Panduit® Turn-Tell® Labels
• Allow labels to rotate for
visibility from any angle.
• Labels can be repositioned
once installed
• Enables compliance with
TIA-606-B

Contenu connexe

Tendances

Norma Ansi/Tia/Eia-607
Norma Ansi/Tia/Eia-607Norma Ansi/Tia/Eia-607
Norma Ansi/Tia/Eia-607
neyneyney
 

Tendances (20)

Outdoor Enclosure from Ericsson doubles radio capacity in same footprint
Outdoor Enclosure from Ericsson doubles radio capacity in same footprintOutdoor Enclosure from Ericsson doubles radio capacity in same footprint
Outdoor Enclosure from Ericsson doubles radio capacity in same footprint
 
Xpic implementation xpd alignment interference test
Xpic implementation xpd alignment interference testXpic implementation xpd alignment interference test
Xpic implementation xpd alignment interference test
 
Data Centre Design Guideline and Standards
Data Centre Design Guideline and StandardsData Centre Design Guideline and Standards
Data Centre Design Guideline and Standards
 
Network Adapter
Network AdapterNetwork Adapter
Network Adapter
 
Mobile communication concepts
Mobile communication conceptsMobile communication concepts
Mobile communication concepts
 
gsm-kpi-optimization
 gsm-kpi-optimization gsm-kpi-optimization
gsm-kpi-optimization
 
Introducción al cableado estructurado
Introducción al cableado estructuradoIntroducción al cableado estructurado
Introducción al cableado estructurado
 
Bss parameter huawei
Bss parameter huaweiBss parameter huawei
Bss parameter huawei
 
Norma Ansi/Tia/Eia-607
Norma Ansi/Tia/Eia-607Norma Ansi/Tia/Eia-607
Norma Ansi/Tia/Eia-607
 
Computer Networks Module I
Computer Networks Module IComputer Networks Module I
Computer Networks Module I
 
Hawke Universal Cable Glands - Installation Instruction
Hawke Universal Cable Glands - Installation InstructionHawke Universal Cable Glands - Installation Instruction
Hawke Universal Cable Glands - Installation Instruction
 
Presentacion cable estructurado
Presentacion cable estructurado Presentacion cable estructurado
Presentacion cable estructurado
 
Bluetooth Low Energy - A Case Study
Bluetooth Low Energy - A Case StudyBluetooth Low Energy - A Case Study
Bluetooth Low Energy - A Case Study
 
Routing over ericsson mini link
Routing over ericsson mini linkRouting over ericsson mini link
Routing over ericsson mini link
 
Gsm optimization
Gsm optimizationGsm optimization
Gsm optimization
 
BTLE (Bluetooth Low Energy) and CoreBluetooth
BTLE (Bluetooth Low Energy) and CoreBluetooth BTLE (Bluetooth Low Energy) and CoreBluetooth
BTLE (Bluetooth Low Energy) and CoreBluetooth
 
ICT. DIMENSIONADO DE LA RED DE CABLE DE PARES
ICT. DIMENSIONADO DE LA RED DE CABLE DE PARESICT. DIMENSIONADO DE LA RED DE CABLE DE PARES
ICT. DIMENSIONADO DE LA RED DE CABLE DE PARES
 
Sdcch drop rate
Sdcch drop rateSdcch drop rate
Sdcch drop rate
 
Ericsson commond list, BSS+NSS=OSS
Ericsson commond list, BSS+NSS=OSSEricsson commond list, BSS+NSS=OSS
Ericsson commond list, BSS+NSS=OSS
 
Cableado estructurado
Cableado estructuradoCableado estructurado
Cableado estructurado
 

En vedette

Tia eia-568-b.3
Tia eia-568-b.3Tia eia-568-b.3
Tia eia-568-b.3
Isidro Ska
 
Normas de Cabeamento
Normas de CabeamentoNormas de Cabeamento
Normas de Cabeamento
Mary Kelly
 

En vedette (10)

Panduit EMEA SI Webinar 9
Panduit EMEA SI Webinar 9Panduit EMEA SI Webinar 9
Panduit EMEA SI Webinar 9
 
Introducing new labels in label market
Introducing new labels in label marketIntroducing new labels in label market
Introducing new labels in label market
 
Redes
RedesRedes
Redes
 
Tia eia-568-b.3
Tia eia-568-b.3Tia eia-568-b.3
Tia eia-568-b.3
 
Cableado estructurado
Cableado estructuradoCableado estructurado
Cableado estructurado
 
Tecmax cap 7 español
Tecmax cap 7 españolTecmax cap 7 español
Tecmax cap 7 español
 
Structured cabling
Structured cablingStructured cabling
Structured cabling
 
Managing the Impact and Cost of the IOT Data Explosion - Data Centre Converge...
Managing the Impact and Cost of the IOT Data Explosion - Data Centre Converge...Managing the Impact and Cost of the IOT Data Explosion - Data Centre Converge...
Managing the Impact and Cost of the IOT Data Explosion - Data Centre Converge...
 
Estandares deCableado Estructurado
Estandares deCableado EstructuradoEstandares deCableado Estructurado
Estandares deCableado Estructurado
 
Normas de Cabeamento
Normas de CabeamentoNormas de Cabeamento
Normas de Cabeamento
 

Similaire à Network Identification and TIA-606-B

Assembling And Cabling
Assembling And CablingAssembling And Cabling
Assembling And Cabling
scooby_doo
 
Advanced motion controls mc4xdzp01
Advanced motion controls mc4xdzp01Advanced motion controls mc4xdzp01
Advanced motion controls mc4xdzp01
Electromate
 
Advanced motion controls mc4xdzp01
Advanced motion controls mc4xdzp01Advanced motion controls mc4xdzp01
Advanced motion controls mc4xdzp01
Electromate
 

Similaire à Network Identification and TIA-606-B (11)

DC labeling convention
DC labeling conventionDC labeling convention
DC labeling convention
 
Edwards Signaling SA-CLA Data Sheet
Edwards Signaling SA-CLA Data SheetEdwards Signaling SA-CLA Data Sheet
Edwards Signaling SA-CLA Data Sheet
 
Edwards Signaling SA-ETH Data Sheet
Edwards Signaling SA-ETH Data SheetEdwards Signaling SA-ETH Data Sheet
Edwards Signaling SA-ETH Data Sheet
 
Asterisk Passive Voice Loggers
Asterisk Passive Voice LoggersAsterisk Passive Voice Loggers
Asterisk Passive Voice Loggers
 
Assembling And Cabling
Assembling And CablingAssembling And Cabling
Assembling And Cabling
 
How to document campus IT infrastructures
How to document campus IT infrastructuresHow to document campus IT infrastructures
How to document campus IT infrastructures
 
Discover the Mircom FleX-Net system
Discover the Mircom FleX-Net systemDiscover the Mircom FleX-Net system
Discover the Mircom FleX-Net system
 
cisco-air-cap3702i-t-k9-datasheet.pdf
cisco-air-cap3702i-t-k9-datasheet.pdfcisco-air-cap3702i-t-k9-datasheet.pdf
cisco-air-cap3702i-t-k9-datasheet.pdf
 
cisco-air-cap3702i-t-k9-datasheet.pdf
cisco-air-cap3702i-t-k9-datasheet.pdfcisco-air-cap3702i-t-k9-datasheet.pdf
cisco-air-cap3702i-t-k9-datasheet.pdf
 
Advanced motion controls mc4xdzp01
Advanced motion controls mc4xdzp01Advanced motion controls mc4xdzp01
Advanced motion controls mc4xdzp01
 
Advanced motion controls mc4xdzp01
Advanced motion controls mc4xdzp01Advanced motion controls mc4xdzp01
Advanced motion controls mc4xdzp01
 

Plus de Panduit

Plus de Panduit (20)

Managing the Impact and Cost of the IOT Data Explosion - Data Centre Converge...
Managing the Impact and Cost of the IOT Data Explosion - Data Centre Converge...Managing the Impact and Cost of the IOT Data Explosion - Data Centre Converge...
Managing the Impact and Cost of the IOT Data Explosion - Data Centre Converge...
 
Enterprise Business
Enterprise BusinessEnterprise Business
Enterprise Business
 
Industrial Automation Infrastructure
Industrial Automation InfrastructureIndustrial Automation Infrastructure
Industrial Automation Infrastructure
 
IntraVUE: Providing advanced analytics for Industrial Ethernet Applications
IntraVUE: Providing advanced analytics for Industrial Ethernet ApplicationsIntraVUE: Providing advanced analytics for Industrial Ethernet Applications
IntraVUE: Providing advanced analytics for Industrial Ethernet Applications
 
Realise the Value in modern Data Center Infrastructure
Realise the Value in modern Data Center InfrastructureRealise the Value in modern Data Center Infrastructure
Realise the Value in modern Data Center Infrastructure
 
Plant Wide Benefits of Ethernet IP
Plant Wide Benefits of Ethernet IPPlant Wide Benefits of Ethernet IP
Plant Wide Benefits of Ethernet IP
 
Tomorrow’s Data Centre, Today
Tomorrow’s Data Centre, TodayTomorrow’s Data Centre, Today
Tomorrow’s Data Centre, Today
 
The Building Blocks of the Industrial Network
The Building Blocks of the Industrial NetworkThe Building Blocks of the Industrial Network
The Building Blocks of the Industrial Network
 
Next Generation Copper Applications Introduction
Next Generation Copper Applications IntroductionNext Generation Copper Applications Introduction
Next Generation Copper Applications Introduction
 
Industrial Automation Infrastructure
Industrial Automation InfrastructureIndustrial Automation Infrastructure
Industrial Automation Infrastructure
 
Data Center Architecture Trends
Data Center Architecture TrendsData Center Architecture Trends
Data Center Architecture Trends
 
Panduit Smartzone™ DCIM Solution Details
Panduit Smartzone™ DCIM Solution DetailsPanduit Smartzone™ DCIM Solution Details
Panduit Smartzone™ DCIM Solution Details
 
SMARTCITY –a hype or reality ?
SMARTCITY –a hype or reality ?SMARTCITY –a hype or reality ?
SMARTCITY –a hype or reality ?
 
Accelerating Operational Excellence with IT/OT Convergence
Accelerating Operational Excellence with IT/OT ConvergenceAccelerating Operational Excellence with IT/OT Convergence
Accelerating Operational Excellence with IT/OT Convergence
 
The New and Improved Partner Program
The New and Improved Partner ProgramThe New and Improved Partner Program
The New and Improved Partner Program
 
Data Center Evolution: From Cabinets to Colocation, Cloud Computing and Beyond
Data Center Evolution: From Cabinets to Colocation, Cloud Computing and BeyondData Center Evolution: From Cabinets to Colocation, Cloud Computing and Beyond
Data Center Evolution: From Cabinets to Colocation, Cloud Computing and Beyond
 
Integrated Data Center Solution
Integrated Data Center SolutionIntegrated Data Center Solution
Integrated Data Center Solution
 
Cisco Internet of Things
Cisco Internet of ThingsCisco Internet of Things
Cisco Internet of Things
 
Turning Business Drivers into Business
Turning Business Drivers into BusinessTurning Business Drivers into Business
Turning Business Drivers into Business
 
Panduit EMEA SI Webinar 10
Panduit EMEA SI Webinar 10Panduit EMEA SI Webinar 10
Panduit EMEA SI Webinar 10
 

Dernier

Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Safe Software
 
Why Teams call analytics are critical to your entire business
Why Teams call analytics are critical to your entire businessWhy Teams call analytics are critical to your entire business
Why Teams call analytics are critical to your entire business
panagenda
 
Finding Java's Hidden Performance Traps @ DevoxxUK 2024
Finding Java's Hidden Performance Traps @ DevoxxUK 2024Finding Java's Hidden Performance Traps @ DevoxxUK 2024
Finding Java's Hidden Performance Traps @ DevoxxUK 2024
Victor Rentea
 

Dernier (20)

Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
 
AI+A11Y 11MAY2024 HYDERBAD GAAD 2024 - HelloA11Y (11 May 2024)
AI+A11Y 11MAY2024 HYDERBAD GAAD 2024 - HelloA11Y (11 May 2024)AI+A11Y 11MAY2024 HYDERBAD GAAD 2024 - HelloA11Y (11 May 2024)
AI+A11Y 11MAY2024 HYDERBAD GAAD 2024 - HelloA11Y (11 May 2024)
 
FWD Group - Insurer Innovation Award 2024
FWD Group - Insurer Innovation Award 2024FWD Group - Insurer Innovation Award 2024
FWD Group - Insurer Innovation Award 2024
 
Spring Boot vs Quarkus the ultimate battle - DevoxxUK
Spring Boot vs Quarkus the ultimate battle - DevoxxUKSpring Boot vs Quarkus the ultimate battle - DevoxxUK
Spring Boot vs Quarkus the ultimate battle - DevoxxUK
 
CNIC Information System with Pakdata Cf In Pakistan
CNIC Information System with Pakdata Cf In PakistanCNIC Information System with Pakdata Cf In Pakistan
CNIC Information System with Pakdata Cf In Pakistan
 
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, AdobeApidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
 
JohnPollard-hybrid-app-RailsConf2024.pptx
JohnPollard-hybrid-app-RailsConf2024.pptxJohnPollard-hybrid-app-RailsConf2024.pptx
JohnPollard-hybrid-app-RailsConf2024.pptx
 
ICT role in 21st century education and its challenges
ICT role in 21st century education and its challengesICT role in 21st century education and its challenges
ICT role in 21st century education and its challenges
 
Vector Search -An Introduction in Oracle Database 23ai.pptx
Vector Search -An Introduction in Oracle Database 23ai.pptxVector Search -An Introduction in Oracle Database 23ai.pptx
Vector Search -An Introduction in Oracle Database 23ai.pptx
 
[BuildWithAI] Introduction to Gemini.pdf
[BuildWithAI] Introduction to Gemini.pdf[BuildWithAI] Introduction to Gemini.pdf
[BuildWithAI] Introduction to Gemini.pdf
 
Apidays New York 2024 - APIs in 2030: The Risk of Technological Sleepwalk by ...
Apidays New York 2024 - APIs in 2030: The Risk of Technological Sleepwalk by ...Apidays New York 2024 - APIs in 2030: The Risk of Technological Sleepwalk by ...
Apidays New York 2024 - APIs in 2030: The Risk of Technological Sleepwalk by ...
 
Platformless Horizons for Digital Adaptability
Platformless Horizons for Digital AdaptabilityPlatformless Horizons for Digital Adaptability
Platformless Horizons for Digital Adaptability
 
Why Teams call analytics are critical to your entire business
Why Teams call analytics are critical to your entire businessWhy Teams call analytics are critical to your entire business
Why Teams call analytics are critical to your entire business
 
Finding Java's Hidden Performance Traps @ DevoxxUK 2024
Finding Java's Hidden Performance Traps @ DevoxxUK 2024Finding Java's Hidden Performance Traps @ DevoxxUK 2024
Finding Java's Hidden Performance Traps @ DevoxxUK 2024
 
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWEREMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
 
Apidays New York 2024 - The value of a flexible API Management solution for O...
Apidays New York 2024 - The value of a flexible API Management solution for O...Apidays New York 2024 - The value of a flexible API Management solution for O...
Apidays New York 2024 - The value of a flexible API Management solution for O...
 
Strategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a FresherStrategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a Fresher
 
DEV meet-up UiPath Document Understanding May 7 2024 Amsterdam
DEV meet-up UiPath Document Understanding May 7 2024 AmsterdamDEV meet-up UiPath Document Understanding May 7 2024 Amsterdam
DEV meet-up UiPath Document Understanding May 7 2024 Amsterdam
 
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
 
"I see eyes in my soup": How Delivery Hero implemented the safety system for ...
"I see eyes in my soup": How Delivery Hero implemented the safety system for ..."I see eyes in my soup": How Delivery Hero implemented the safety system for ...
"I see eyes in my soup": How Delivery Hero implemented the safety system for ...
 

Network Identification and TIA-606-B

  • 1. Panduit Unified Physical InfrastructureSM Solutions Network Identification and TIA-606-B
  • 2. 2 Properly identified physical infrastructure is easier to install, maintain, and repair
  • 3. TIA-606 A TIA-606 A, Addendum 1 TIA-606-B [ISO/IEC 14763-2-1] fs-an fs.xy-r:P +fs.xy+r:P TIA-942-A fs.xy-r:Pfs-an
  • 4. TIA-606B Scope • Accommodates the scalable needs of telecommunications infrastructure systems • Deals with commercial, industrial, residential, and data center premises • Allows modular implementation of different elements of the standard depending on size of telecommunications infrastructure • Specifies formats and requirements of records, identifiers, and labels for infrastructure components 4
  • 5. Three key elements of TIA-606-B Identifiers Labeling Records DC1.AD04-30:04/DC1.AF04-23:16
  • 6. Class 1 Identifiers • The following infrastructure elements shall be identified: – Telecommunications Space (TS) – Cabinet, rack, enclosure, wall segment – Patch panels or termination blocks – Patch panel ports and termination positions – Cables between cabinets, racks, and enclosures – Cabling Subsystem 1 (horizontal) links – Equipment and work area outlets – Telecommunications main grounding busbar (TMGB) – Telecommunications grounding busbar (TGB) – Rack grounding busbar (RGB) – Bonding conductors (BCT, TBB, GE)
  • 7. f = numeric character(s) identifying the floor s = alpha character identifying TS on floor f This Telecommunication Space is “2A” Telecommunication Space Identifier fs
  • 8. Cabinet/Rack Identifier • fs = space • xy = location in the space • Using the room grid in the data center this cabinet is located at the intersection of row AY and column 15 fs.xy
  • 9. Patch Panel Identifier • fs = space • xy = rack location • r = panel position in rack • This patch panel is located in position B on the rack located at the intersection of row AR and column 15 fs.xy-r
  • 10. Port Identifiers • fs = space • xy = rack location • r = panel position in rack • P = port position • This port is position 12 located on patch panel 24 in cabinet AB04 fs.xy-r:P
  • 11. Identification Solutions Panduit® Turn-Tell® Labels • Allow labels to rotate for visibility from any angle. • Labels can be repositioned once installed • Enables compliance with TIA-606-B

Notes de l'éditeur

  1. [Read Slide]The advantage of a properly labeled infrastructure is that system components can be quickly and accurately identified which will reduce the time to repair and ensure maximum availability of business IT services.
  2. TIA-606-A, originally introduced as TIA-606 in 1993, established guidelines for the administration of telecommunications infrastructure. Using a scalable and modular implementation of different elements of the standard the TIA-606-A specified identifier formats, administration of network components, and the formats and requirements of labels. The identification scheme for a specific connection included the floor and space, rack designation, and port number.TIA-942 was introduced in 2005 to specify the minimum requirements for telecommunications infrastructure of data centers and computer rooms. The standard provided an informative reference to TIA/EIA-606-A for guidance on data center infrastructure administration and labeling.In practice, using TIA-606-A for the administration of data centers was not adequate. The standard did not accommodate the huge amount of structured cabling in a data center. As a result of this limitation an addendum was added to TIA-606-A, known as TIA-606-A, Addendum 1. This addendum, published in 2008, introduced an identification scheme that provided the locations of racks and panels in the data center.In 2012 the TIA-606-B standard was introduced. This completely new standard combines the requirements ofTIA-606A and the Addendum 1 alongwith additional telecommunications infrastructure elements. The standard allows for use of legacy TIA-606-A identifier schemes and provides ISO/IEC compatible identifier schemes for multi-region facilities. Some of the elements of TIA-606-B are the expanded administration of grounding and bonding systems, addressing the use of Automated Infrastructure Management (AIM) systems for administration, and introducing the administration of individual pair groups and fiber strands.
  3. Read Slide
  4. These are the primary identifiers required in a class 1 administration
  5. A telecommunication space (TS) identifier, unique within the building, shall be assigned to the space. The identifier consists of the floor and room or area designation on that floor. In this example the space is located on the second floor in room A. Another example could be 1DC to represent the data center on floor 1.
  6. The floor tile or grid designations are used to identify each cabinet or rack location in the data center. The cabinet/rack location is based on which floor tile the right front corner of the cabinet/rackrests upon.Cabinets and racks should have location labels applied to the top and bottom of both the front and rear of the device. These labels should be visible whether or not doors are closed or opened on the cabinets.This identifier would define that the cabinet/rack is located with its right front corner at the intersection of row AY and column 15.The standard also addresses situations where floor tiles are not in use. For these situations rows and cabinet position in the row can be assigned in the datacenter. For example row B cabinet 3.In telecommunications rooms floor mounted racks and wall-mounted termination blocks can be assigned a sequential number.
  7. The designation for the panel positions in a cabinet/rack can be either an alphabetic designation or a two-digit number that represent the rack unit number (RU) where the top-left mounting screw lands in the cabinet/rack. Using the RU method provides the data center manager with greater flexibility since it allows for panels and equipment to be added or removed later and not disrupt the designation of panel identifiers.This identifier would define that the top left mounting screw of the panel is located at the rack position Bin the cabinet/rack located at the intersection of row AR and column15 in the data center.
  8. Port identifiers are very important in that they will define the connectivity of cabling within the data center infrastructure.If the patch panels are not pre-printed with port numbers then labels will need to be created to identify the port numbers.The numbering sequence should proceed from left to right and top to bottom for all ports on a patch panel.The number of digits used for all numbers on a patch panel should be consistent with the total number of ports on that patch panel. For example a 48-port patch panel should be labeled 01 through 48 and a 144-port fiber panel should be labeled 001 through 144.This identifier defines that this is port 12 located on panel 24 in cabinet/rack AB04.