CLASS-4: PHASOR MEASUREMENT UNIT
(PMU)
Prof. (Dr.) Pravat Kumar Rout
Department of EEE
ITER
Siksha ‘O’ Anusandhan
(Deemed to be University),
Bhubaneswar, Odisha, India
Course: Distribution Generation and Smart Grid
Swetalina Sarangi
(Research Scholar)
Department of EE
ITER
Siksha ‘O’ Anusandhan
(Deemed to be University),
Bhubaneswar, Odisha, India
WHAT IS PHASOR?
 Phasor is a quantity with
magnitude and phase (with
respect to a reference) that is used
to represent a sinusoidal signal.
 Here the phase or phase angle is
the distance between the signal’s
sinusoidal peak and a specified
reference and is expressed using
an angular measure.
 Here, the reference is a fixed point
in time (such as time = 0).
 The phasor magnitude is related to the
amplitude of the sinusoidal signal.
WHAT IS PHASOR MEASUREMENT UNIT?
 A phasor measurement unit (PMU) is a device used to estimate the
magnitude and phase angle of an electrical phasor quantity (such as
voltage or current) in the electric grid using a common time source for
synchronization.
 Time synchronization is usually provided by GPS and allows
synchronized real-time measurements of multiple remote points on the grid.
 PMUs are capable of capturing samples from a waveform in quick
succession and reconstructing the phasor quantity, made up of an angle
measurement and a magnitude measurement.
 The resulting measurement is known as a synchrophasor. These time
synchronized measurements are important because if the grid’s supply and
demand are not perfectly matched, frequency imbalances can cause stress on
the grid, which is a potential cause for power outages.
CONTINUE...
 PMUs can also be used to measure the frequency in the power
grid.
 A typical commercial PMU can report measurements with very high
temporal resolution in the order of 30-60 measurements per
second. This helps engineers in analyzing dynamic events in the grid
which is not possible with traditional SCADA measurements that
generate one measurement every 2 or 4 seconds.
 Therefore, PMUs equip utilities with enhanced monitoring and
control capabilities and are considered to be one of the most
important measuring devices in the future of power systems.
 A PMU can be a dedicated device, or the PMU function can be
incorporated into a protective relay or other device.
WHY PMU?
 PMU an essential component of Smart Grids.
 It provides Synchrophasor data
 Reports Magnitude, Phase and Frequency of an AC
waveform
 Makes the grid observable due to high reporting rates
 Preventive actions can be taken such as black outs
THE MAIN COMPONENTS OF PMU
 Analog Inputs
 GPS receiver
 Phase locked oscillator
 A/D converter
 Anti-aliasing filters
 Phasor micro-processor
 Modem
BLOCK DIAGRAM OF PMU
ANALOG INPUTS
 Current and potential
transformers are
employed at substation for
measurement of voltage
and current.
 The analog inputs to the
PMU are the voltages
and currents obtained
from the secondary
winding of potential and
current transformers.
ANTI-ALIASING FILTERS
 Anti-aliasing filter is an analog low
pass filter which is used to filter
out those components from the
actual signal whose frequencies
are greater than or equal to half
of nyquist rate to get the sampled
waveform.
 Nyquist rate is equal to twice the
highest frequency component of input
analog signal.
 If anti aliasing filters are not used,
error will be introduced in the
estimated phasor
PHASE LOCK OSCILLATOR
 Phase lock oscillator along
with Global Positioning
System reference source
provides the needed high
speed synchronized
sampling.
 Global Positioning System
(GPS) is a satellite-based
system for providing
position and time.
A/D CONVERTER
 It converts the analog signal to the
digital signal.
 Quantization of the input involves in ADC
that introduces a small amount of error.
 The output of ADC is a sequence of digital
values that convert a continuous time and
amplitude analog signal to a discrete time
and discrete amplitude signal.
 It is therefore required to define the rate at
which new digital values are sampled from
the analog signal.
 The rate of new values at which digital
values are sampled is called the sampling
rate of the converter.
GLOBAL POSITIONING SYSTEM
 The synchronized time is given by GPS uses
the high accuracy clock from satellite
technology.
 Without GPS providing the synchronized
time, it is hard to monitor whole grid at the
same time.
 The GPS satellites provide a very accurate
time synchronization signal, available, via
an antenna input, throughout the power
system. This means that that voltage and
current recordings from different substations
can be directly displayed on the same time
axis and in the same phasor diagram.
PROCESSOR
 The microprocessor calculates positive-
sequence estimates of all the current and
voltage signals using the DFT techniques.
 Certain other estimates of interest are
frequency and rate of change of frequency
measured locally, and these also are included
in the output of the PMU.
 The timestamp is created from two of the
signals derived from the GPS receiver.
 The time-stamp identifies the identity of the
“universal time coordinated (UTC) second and
the instant defining the boundary of one of the
power frequency periods.
MODEM
 A device that modulates an analog
carrier signal and encodes digital
information from the signal and can
also demodulate the signal to decode
the transmitted information from
signal is called modem.
 The objective of modem is to produce a
signal that can be transmitted and
decoded to make a replica of the
original digital data.
 Modem can be used with no means of
transmitting analog signals
SYNCHROPHASOR
 A synchrophasor is a
phasor measurement
with respect to an
absolute time reference.
 With this measurement
we can determine the
absolute phase
relationship between
phase quantities at
different locations on
the power system.
CONTINUE...
Lagging Phase Angles
Leading Phase Angles
Leading Phase Angles
Reference Phase angle (0 Degree)
FEATURES OF PMUS
 PMUs are Measures 50/60 Hz AC waveforms (voltage and
current) typically at a rate of 48 samples per cycle.
 PMUs are then computed using DFT-like algorithms, and time
stamped with a GPS.
 The resultant time tagged PMUs can be transmitted to a local
or remote receiver at rates up to 60 samples per cycle.
APPLICATION OF PMU IN POWER SYSTEM
1. Adaptive relaying
2. Instability prediction
3. State estimation
4. Improved control
5. Fault recording
6. Disturbance recording
7. Transmission and generation modeling verification
8. Wide area Protection
9. Fault location
Adaptive Relaying
Adaptive relaying is a
protection philosophy which
permits and seeks to make
adjustments in various
protection functions in order to
make them more tuned to
prevailing power system
conditions
Instability prediction
The instability prediction can
be used to adapt load shedding
and/or out of step relays.
We can actually monitor the
progress of the transient in real
time by the technique of
synchronized phasor
measurements.
• The state estimator uses various measurements received from
different substations, and, through an iterative nonlinear
estimation procedure, calculates the power system state.
State estimation
• By maintaining a continuous stream of phasor data from the
substations to the control center, a state vector that can follow the
system dynamics can be constructed.
• For the first time in history, synchronized phasor measurements
have made possible the direct observation of system
oscillations following system disturbances.
The role of state estimation in power system operation
Contingency
Analysis
Security
Enhancement
Dynamic Security
Analysis
Optimal Power
Flow
Other
Applications
State
Estimation
Other
Data
Network
Model
SCADA
PDC
PMU PMUPMU
• Power system control elements use local feedback to achieve the control
objective.
Improved control
• The PMU was necessary to capture data during the staged
testing and accurately display this data and provide
comparisons to the system model.
• The shown figure shows a typical example of one of the output
plots from the PMU data
• They can capture and display actual 60/50 Hz wave form and
magnitude data on individual channels during power system fault
conditions.
Fault Recording
• Loss of generation, loss of load, or loss of major transmission lines
may lead to a power system disturbance, possibly affecting
customers and power system operations.
Disturbance Recording
• Computerized power system modeling and studies are now the
normal and accepted ways of ensuring that power system
parameters have been reviewed before large capital expenditures
on major system changes.
Transmission and Generation
Modeling Verification
• In years past, actual verification of computer models via
field tests would have been either impractical or even impossible
• The PMU class of monitoring equipment can now provide the
field verification required.
• The shown figure compares a remote substation 500 kV bus
voltage captured by the PMU to the stability program results
Continue …
Positive sequence voltage phasor on a 500 kv bus vs computer model
simulation of switching test
The introduction of the Phasor Measurement Unit (PMU) has
greatly improved the observability of the power system
dynamics. Based on PMUs, different kinds of wide area
protection, emergency control and optimization systems can be
designed
WIDE – AREA PROTECTION
Multilayered wide area protection architecture
A fault location algorithm based on synchronized sampling. A time
domain model of a transmission line is used as a basis for the
algorithm development. Samples of voltages and currents at the
ends of a transmission line are taken simultaneously
(synchronized) and used to calculate fault location.
Fault Location
Phasor measurement units are installed at both ends of the
transmission line. The three phase voltages and three phase currents
are measured by PMUs located at both ends of line simultaneously
 A pure sinusoid quantity given by 𝑥 𝑡 = 𝑋 𝑚cos(𝜔𝑡 + 𝜃) and its
phasor representation 𝑋 = Τ𝑋 𝑚 2 𝑒 𝑗𝜃 = Τ𝑋 𝑚 2 𝑐𝑜𝑠𝜃 + 𝑗𝑠𝑖𝑛𝜃
are illustrated in Figure. The aim of phasor estimation technique
is just to acquire the phasor representation.
 Samples of waveform data are collected over a data window which
is normally one period of the fundamental frequency of the power
system. In early days a sampling rate of 12 times a cycle (720 Hz
for the 60 Hz system) was commonly used. Much higher sampling
rates are currently used in commercial PMUs.
Phasor Measuremnet Techniques

RMS
t
 tx
RMS

Imaginary Axis
Real Axis
(a) (b)
A sinusoid and its representation as a phasor
COMPARISON
 Digital measurement
 60 samples per cycle
(resolution)
 Dynamic (Observability)
 Wide area monitoring
 Phasor angle
measurement: Yes
SCADA PMU
 Analogue measurement
 2-4 samples per cycle
(resolution)
 Steady state
(Observability)
 Local monitoring
 Phasor angle
measurement: No
REFERENCES
 Phadke, A. G., & Thorp, J. S. (2006, October). History and
applications of phasor measurements. In 2006 IEEE PES Power
Systems Conference and Exposition (pp. 331-335). IEEE.
 Tholomier, D., Kang, H., & Cvorovic, B. (2009, March). Phasor
measurement units: Functionality and applications. In 2009
Power Systems Conference (pp. 1-12). IEEE.
 Phadke, A. G., & Tianshu, B. I. (2018). Phasor measurement
units, WAMS, and their applications in protection and control of
power systems. Journal of Modern Power Systems and Clean
Energy, 6(4), 619-629.
QUESTIONS
 How does a Phasor Measurement Unit (PMU) work?
 What are the main components of PMU? Explain
briefly with PMU Block Diagram.
 What is use of PMU in Smart Grid?
 Explain the application of PMU in power system.
 What is synchrophasor?
 What is phasor measurement techniques?

Contenu connexe

Tendances

Load Frequency Control of two area Power system
Load Frequency Control  of two area Power systemLoad Frequency Control  of two area Power system
Load Frequency Control of two area Power systemAnimesh Sachan
 
INTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERINTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERNitish NIT
 
Objectives of shunt compensation
Objectives of shunt compensationObjectives of shunt compensation
Objectives of shunt compensationAyyarao T S L V
 
Planning and modern trends in hvdc
Planning and modern trends in hvdcPlanning and modern trends in hvdc
Planning and modern trends in hvdcjawaharramaya
 
Hydrothermal scheduling
Hydrothermal schedulingHydrothermal scheduling
Hydrothermal schedulingASHIRBAD BARIK
 
Load Forecasting
Load ForecastingLoad Forecasting
Load Forecastinglinsstalex
 
Traction Motors and Control
Traction Motors and ControlTraction Motors and Control
Traction Motors and ControlSANTOSH GADEKAR
 
Electric drive
Electric driveElectric drive
Electric drivemishradiya
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptMamta Bagoria
 
Load dispatch center
Load dispatch centerLoad dispatch center
Load dispatch centerddxdharmesh
 
Protection and control of Microgrid
Protection and control of MicrogridProtection and control of Microgrid
Protection and control of MicrogridAmarjeet S Pandey
 
Power qualty conditioners
Power qualty conditionersPower qualty conditioners
Power qualty conditionersSudhanshu Goel
 
POWER QUALITY IMPROVEMENT AND FAULT RIDE THROUGH OF GRID CONNECTED WIND ENE...
POWER QUALITY IMPROVEMENT AND FAULT RIDE THROUGH OF   GRID CONNECTED WIND ENE...POWER QUALITY IMPROVEMENT AND FAULT RIDE THROUGH OF   GRID CONNECTED WIND ENE...
POWER QUALITY IMPROVEMENT AND FAULT RIDE THROUGH OF GRID CONNECTED WIND ENE...Bharadwaj S
 

Tendances (20)

Load Frequency Control of two area Power system
Load Frequency Control  of two area Power systemLoad Frequency Control  of two area Power system
Load Frequency Control of two area Power system
 
INTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERINTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLER
 
Objectives of shunt compensation
Objectives of shunt compensationObjectives of shunt compensation
Objectives of shunt compensation
 
Planning and modern trends in hvdc
Planning and modern trends in hvdcPlanning and modern trends in hvdc
Planning and modern trends in hvdc
 
Hvdc notes
Hvdc notesHvdc notes
Hvdc notes
 
Hydrothermal scheduling
Hydrothermal schedulingHydrothermal scheduling
Hydrothermal scheduling
 
Swing equation
Swing equationSwing equation
Swing equation
 
Two area system
Two area systemTwo area system
Two area system
 
Unit commitment
Unit commitmentUnit commitment
Unit commitment
 
Load Forecasting
Load ForecastingLoad Forecasting
Load Forecasting
 
Traction Motors and Control
Traction Motors and ControlTraction Motors and Control
Traction Motors and Control
 
Storage In Smart Grids
Storage In Smart GridsStorage In Smart Grids
Storage In Smart Grids
 
Electric drive
Electric driveElectric drive
Electric drive
 
MTDC SYSTEMS
MTDC SYSTEMSMTDC SYSTEMS
MTDC SYSTEMS
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
 
Load dispatch center
Load dispatch centerLoad dispatch center
Load dispatch center
 
Protection and control of Microgrid
Protection and control of MicrogridProtection and control of Microgrid
Protection and control of Microgrid
 
HVDC & FACTS
HVDC & FACTSHVDC & FACTS
HVDC & FACTS
 
Power qualty conditioners
Power qualty conditionersPower qualty conditioners
Power qualty conditioners
 
POWER QUALITY IMPROVEMENT AND FAULT RIDE THROUGH OF GRID CONNECTED WIND ENE...
POWER QUALITY IMPROVEMENT AND FAULT RIDE THROUGH OF   GRID CONNECTED WIND ENE...POWER QUALITY IMPROVEMENT AND FAULT RIDE THROUGH OF   GRID CONNECTED WIND ENE...
POWER QUALITY IMPROVEMENT AND FAULT RIDE THROUGH OF GRID CONNECTED WIND ENE...
 

Similaire à Phasor Measurement Unit (PMU)

A overview on WAMS/PMU.
A overview on WAMS/PMU.A overview on WAMS/PMU.
A overview on WAMS/PMU.Rahul Singh
 
Phasor measurement unit
Phasor measurement unitPhasor measurement unit
Phasor measurement unitSathriGiridhar
 
International conference
International conferenceInternational conference
International conferenceSuresh Sampath
 
APPLICATION OF GPS IN POWER SECTOR@1.ppt
APPLICATION OF GPS IN POWER SECTOR@1.pptAPPLICATION OF GPS IN POWER SECTOR@1.ppt
APPLICATION OF GPS IN POWER SECTOR@1.pptAmitKumarSahu56
 
Reliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov modelReliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov modelamaresh1234
 
Joint State and Parameter Estimation by Extended Kalman Filter (EKF) technique
Joint State and Parameter Estimation by Extended Kalman Filter (EKF) techniqueJoint State and Parameter Estimation by Extended Kalman Filter (EKF) technique
Joint State and Parameter Estimation by Extended Kalman Filter (EKF) techniqueIJERD Editor
 
RAJPRASAD PAPER NO-127
RAJPRASAD PAPER NO-127RAJPRASAD PAPER NO-127
RAJPRASAD PAPER NO-127RAJPRASAD RS
 
Voltage Stability Assessment using Phasor Measurement Units in Power Network ...
Voltage Stability Assessment using Phasor Measurement Units in Power Network ...Voltage Stability Assessment using Phasor Measurement Units in Power Network ...
Voltage Stability Assessment using Phasor Measurement Units in Power Network ...Satyendra Singh
 
Phasor measurement unit and it's application ppt
Phasor measurement unit and it's application pptPhasor measurement unit and it's application ppt
Phasor measurement unit and it's application pptKhurshid Parwez
 
Wide area measurements (synchrophasor measurements) in Power Systems
Wide area measurements (synchrophasor measurements) in Power SystemsWide area measurements (synchrophasor measurements) in Power Systems
Wide area measurements (synchrophasor measurements) in Power SystemsNaila Syed
 
A Survey On Real Time State Estimation For Optimal Placement Of Phasor Measur...
A Survey On Real Time State Estimation For Optimal Placement Of Phasor Measur...A Survey On Real Time State Estimation For Optimal Placement Of Phasor Measur...
A Survey On Real Time State Estimation For Optimal Placement Of Phasor Measur...IJSRD
 
Real-Time Monitoring of Power Oscillations Modal Damping in the European System
Real-Time Monitoring of Power Oscillations Modal Damping in the European SystemReal-Time Monitoring of Power Oscillations Modal Damping in the European System
Real-Time Monitoring of Power Oscillations Modal Damping in the European SystemPower System Operation
 
DETECTION OF UNSYMMETRICAL FAULTS IN TRANSMISSION LINES USING PHASOR MEASUREM...
DETECTION OF UNSYMMETRICAL FAULTS IN TRANSMISSION LINES USING PHASOR MEASUREM...DETECTION OF UNSYMMETRICAL FAULTS IN TRANSMISSION LINES USING PHASOR MEASUREM...
DETECTION OF UNSYMMETRICAL FAULTS IN TRANSMISSION LINES USING PHASOR MEASUREM...IRJET Journal
 
Role of phasor measuring unit in power system
Role of phasor measuring unit in power systemRole of phasor measuring unit in power system
Role of phasor measuring unit in power systemHASEENA. M
 
Adaptive and inteligence
Adaptive and inteligenceAdaptive and inteligence
Adaptive and inteligenceFinitoTheEnd
 

Similaire à Phasor Measurement Unit (PMU) (20)

A overview on WAMS/PMU.
A overview on WAMS/PMU.A overview on WAMS/PMU.
A overview on WAMS/PMU.
 
Phasor measurement unit
Phasor measurement unitPhasor measurement unit
Phasor measurement unit
 
International conference
International conferenceInternational conference
International conference
 
APPLICATION OF GPS IN POWER SECTOR@1.ppt
APPLICATION OF GPS IN POWER SECTOR@1.pptAPPLICATION OF GPS IN POWER SECTOR@1.ppt
APPLICATION OF GPS IN POWER SECTOR@1.ppt
 
Reliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov modelReliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov model
 
Joint State and Parameter Estimation by Extended Kalman Filter (EKF) technique
Joint State and Parameter Estimation by Extended Kalman Filter (EKF) techniqueJoint State and Parameter Estimation by Extended Kalman Filter (EKF) technique
Joint State and Parameter Estimation by Extended Kalman Filter (EKF) technique
 
RAJPRASAD PAPER NO-127
RAJPRASAD PAPER NO-127RAJPRASAD PAPER NO-127
RAJPRASAD PAPER NO-127
 
Voltage Stability Assessment using Phasor Measurement Units in Power Network ...
Voltage Stability Assessment using Phasor Measurement Units in Power Network ...Voltage Stability Assessment using Phasor Measurement Units in Power Network ...
Voltage Stability Assessment using Phasor Measurement Units in Power Network ...
 
Phasor measurement unit and it's application ppt
Phasor measurement unit and it's application pptPhasor measurement unit and it's application ppt
Phasor measurement unit and it's application ppt
 
Wide area measurements (synchrophasor measurements) in Power Systems
Wide area measurements (synchrophasor measurements) in Power SystemsWide area measurements (synchrophasor measurements) in Power Systems
Wide area measurements (synchrophasor measurements) in Power Systems
 
Unit 6 power quality
Unit 6 power qualityUnit 6 power quality
Unit 6 power quality
 
A Survey On Real Time State Estimation For Optimal Placement Of Phasor Measur...
A Survey On Real Time State Estimation For Optimal Placement Of Phasor Measur...A Survey On Real Time State Estimation For Optimal Placement Of Phasor Measur...
A Survey On Real Time State Estimation For Optimal Placement Of Phasor Measur...
 
Real-Time Monitoring of Power Oscillations Modal Damping in the European System
Real-Time Monitoring of Power Oscillations Modal Damping in the European SystemReal-Time Monitoring of Power Oscillations Modal Damping in the European System
Real-Time Monitoring of Power Oscillations Modal Damping in the European System
 
WAM.ppt
WAM.pptWAM.ppt
WAM.ppt
 
PMU
PMUPMU
PMU
 
DETECTION OF UNSYMMETRICAL FAULTS IN TRANSMISSION LINES USING PHASOR MEASUREM...
DETECTION OF UNSYMMETRICAL FAULTS IN TRANSMISSION LINES USING PHASOR MEASUREM...DETECTION OF UNSYMMETRICAL FAULTS IN TRANSMISSION LINES USING PHASOR MEASUREM...
DETECTION OF UNSYMMETRICAL FAULTS IN TRANSMISSION LINES USING PHASOR MEASUREM...
 
Role of phasor measuring unit in power system
Role of phasor measuring unit in power systemRole of phasor measuring unit in power system
Role of phasor measuring unit in power system
 
Thesis Presentation_Pulok_v1
Thesis Presentation_Pulok_v1Thesis Presentation_Pulok_v1
Thesis Presentation_Pulok_v1
 
Adaptive and inteligence
Adaptive and inteligenceAdaptive and inteligence
Adaptive and inteligence
 
Wide area monitoring, protection and control in future smart grid
Wide area monitoring, protection and control in future smart gridWide area monitoring, protection and control in future smart grid
Wide area monitoring, protection and control in future smart grid
 

Plus de Siksha 'O' Anusandhan (Deemed to be University )

Plus de Siksha 'O' Anusandhan (Deemed to be University ) (20)

Defining the Research Problem .pdf
Defining the Research Problem .pdfDefining the Research Problem .pdf
Defining the Research Problem .pdf
 
phd Thesis and Paper writing.pdf
phd Thesis and Paper writing.pdfphd Thesis and Paper writing.pdf
phd Thesis and Paper writing.pdf
 
Presentation.pdf
Presentation.pdfPresentation.pdf
Presentation.pdf
 
An Introduction to Research Methodology.pdf
An Introduction to Research Methodology.pdfAn Introduction to Research Methodology.pdf
An Introduction to Research Methodology.pdf
 
Dr. P.K. Rout Final_my jouney.pdf
Dr. P.K. Rout Final_my jouney.pdfDr. P.K. Rout Final_my jouney.pdf
Dr. P.K. Rout Final_my jouney.pdf
 
VIRTUAL POWER PLANT (VPP).pdf
VIRTUAL POWER PLANT (VPP).pdfVIRTUAL POWER PLANT (VPP).pdf
VIRTUAL POWER PLANT (VPP).pdf
 
Robust Active Power Filter Controller Design for Microgrid and Electric Vehic...
Robust Active Power Filter Controller Design for Microgrid and Electric Vehic...Robust Active Power Filter Controller Design for Microgrid and Electric Vehic...
Robust Active Power Filter Controller Design for Microgrid and Electric Vehic...
 
Robust Active Power Filter Controller Design for Microgrid and Electric Vehic...
Robust Active Power Filter Controller Design for Microgrid and Electric Vehic...Robust Active Power Filter Controller Design for Microgrid and Electric Vehic...
Robust Active Power Filter Controller Design for Microgrid and Electric Vehic...
 
Design and implementation of active power filter for harmonic elimination and...
Design and implementation of active power filter for harmonic elimination and...Design and implementation of active power filter for harmonic elimination and...
Design and implementation of active power filter for harmonic elimination and...
 
Topologies and Controls for Optimal Energy Bifurcation in AC, DC, and Hybrid ...
Topologies and Controls for Optimal Energy Bifurcation in AC, DC, and Hybrid ...Topologies and Controls for Optimal Energy Bifurcation in AC, DC, and Hybrid ...
Topologies and Controls for Optimal Energy Bifurcation in AC, DC, and Hybrid ...
 
Final talk trident-05-10-2021- dr p k rout-converted
Final talk trident-05-10-2021- dr p k rout-convertedFinal talk trident-05-10-2021- dr p k rout-converted
Final talk trident-05-10-2021- dr p k rout-converted
 
Role of teachers in technical education
Role of teachers in technical educationRole of teachers in technical education
Role of teachers in technical education
 
Technical presentation format for M.Tech, Ph.D. students
Technical presentation format for M.Tech, Ph.D. students Technical presentation format for M.Tech, Ph.D. students
Technical presentation format for M.Tech, Ph.D. students
 
Integrated protection and control strategies for microgrid
Integrated protection and control strategies for microgrid Integrated protection and control strategies for microgrid
Integrated protection and control strategies for microgrid
 
Integrated protection and control strategies for microgrid
Integrated protection and control strategies for microgridIntegrated protection and control strategies for microgrid
Integrated protection and control strategies for microgrid
 
Differential evolution optimization technique
Differential evolution optimization techniqueDifferential evolution optimization technique
Differential evolution optimization technique
 
Hebb network
Hebb networkHebb network
Hebb network
 
Mc culloch pitts neuron
Mc culloch pitts neuronMc culloch pitts neuron
Mc culloch pitts neuron
 
Defuzzification
DefuzzificationDefuzzification
Defuzzification
 
Fuzzy relations and fuzzy compositional rules
Fuzzy relations  and fuzzy compositional rulesFuzzy relations  and fuzzy compositional rules
Fuzzy relations and fuzzy compositional rules
 

Dernier

SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 

Dernier (20)

SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 

Phasor Measurement Unit (PMU)

  • 1. CLASS-4: PHASOR MEASUREMENT UNIT (PMU) Prof. (Dr.) Pravat Kumar Rout Department of EEE ITER Siksha ‘O’ Anusandhan (Deemed to be University), Bhubaneswar, Odisha, India Course: Distribution Generation and Smart Grid Swetalina Sarangi (Research Scholar) Department of EE ITER Siksha ‘O’ Anusandhan (Deemed to be University), Bhubaneswar, Odisha, India
  • 2. WHAT IS PHASOR?  Phasor is a quantity with magnitude and phase (with respect to a reference) that is used to represent a sinusoidal signal.  Here the phase or phase angle is the distance between the signal’s sinusoidal peak and a specified reference and is expressed using an angular measure.  Here, the reference is a fixed point in time (such as time = 0).  The phasor magnitude is related to the amplitude of the sinusoidal signal.
  • 3. WHAT IS PHASOR MEASUREMENT UNIT?  A phasor measurement unit (PMU) is a device used to estimate the magnitude and phase angle of an electrical phasor quantity (such as voltage or current) in the electric grid using a common time source for synchronization.  Time synchronization is usually provided by GPS and allows synchronized real-time measurements of multiple remote points on the grid.  PMUs are capable of capturing samples from a waveform in quick succession and reconstructing the phasor quantity, made up of an angle measurement and a magnitude measurement.  The resulting measurement is known as a synchrophasor. These time synchronized measurements are important because if the grid’s supply and demand are not perfectly matched, frequency imbalances can cause stress on the grid, which is a potential cause for power outages.
  • 4. CONTINUE...  PMUs can also be used to measure the frequency in the power grid.  A typical commercial PMU can report measurements with very high temporal resolution in the order of 30-60 measurements per second. This helps engineers in analyzing dynamic events in the grid which is not possible with traditional SCADA measurements that generate one measurement every 2 or 4 seconds.  Therefore, PMUs equip utilities with enhanced monitoring and control capabilities and are considered to be one of the most important measuring devices in the future of power systems.  A PMU can be a dedicated device, or the PMU function can be incorporated into a protective relay or other device.
  • 5. WHY PMU?  PMU an essential component of Smart Grids.  It provides Synchrophasor data  Reports Magnitude, Phase and Frequency of an AC waveform  Makes the grid observable due to high reporting rates  Preventive actions can be taken such as black outs
  • 6. THE MAIN COMPONENTS OF PMU  Analog Inputs  GPS receiver  Phase locked oscillator  A/D converter  Anti-aliasing filters  Phasor micro-processor  Modem
  • 8. ANALOG INPUTS  Current and potential transformers are employed at substation for measurement of voltage and current.  The analog inputs to the PMU are the voltages and currents obtained from the secondary winding of potential and current transformers.
  • 9. ANTI-ALIASING FILTERS  Anti-aliasing filter is an analog low pass filter which is used to filter out those components from the actual signal whose frequencies are greater than or equal to half of nyquist rate to get the sampled waveform.  Nyquist rate is equal to twice the highest frequency component of input analog signal.  If anti aliasing filters are not used, error will be introduced in the estimated phasor
  • 10. PHASE LOCK OSCILLATOR  Phase lock oscillator along with Global Positioning System reference source provides the needed high speed synchronized sampling.  Global Positioning System (GPS) is a satellite-based system for providing position and time.
  • 11. A/D CONVERTER  It converts the analog signal to the digital signal.  Quantization of the input involves in ADC that introduces a small amount of error.  The output of ADC is a sequence of digital values that convert a continuous time and amplitude analog signal to a discrete time and discrete amplitude signal.  It is therefore required to define the rate at which new digital values are sampled from the analog signal.  The rate of new values at which digital values are sampled is called the sampling rate of the converter.
  • 12. GLOBAL POSITIONING SYSTEM  The synchronized time is given by GPS uses the high accuracy clock from satellite technology.  Without GPS providing the synchronized time, it is hard to monitor whole grid at the same time.  The GPS satellites provide a very accurate time synchronization signal, available, via an antenna input, throughout the power system. This means that that voltage and current recordings from different substations can be directly displayed on the same time axis and in the same phasor diagram.
  • 13. PROCESSOR  The microprocessor calculates positive- sequence estimates of all the current and voltage signals using the DFT techniques.  Certain other estimates of interest are frequency and rate of change of frequency measured locally, and these also are included in the output of the PMU.  The timestamp is created from two of the signals derived from the GPS receiver.  The time-stamp identifies the identity of the “universal time coordinated (UTC) second and the instant defining the boundary of one of the power frequency periods.
  • 14. MODEM  A device that modulates an analog carrier signal and encodes digital information from the signal and can also demodulate the signal to decode the transmitted information from signal is called modem.  The objective of modem is to produce a signal that can be transmitted and decoded to make a replica of the original digital data.  Modem can be used with no means of transmitting analog signals
  • 15. SYNCHROPHASOR  A synchrophasor is a phasor measurement with respect to an absolute time reference.  With this measurement we can determine the absolute phase relationship between phase quantities at different locations on the power system.
  • 16.
  • 17. CONTINUE... Lagging Phase Angles Leading Phase Angles Leading Phase Angles Reference Phase angle (0 Degree)
  • 18. FEATURES OF PMUS  PMUs are Measures 50/60 Hz AC waveforms (voltage and current) typically at a rate of 48 samples per cycle.  PMUs are then computed using DFT-like algorithms, and time stamped with a GPS.  The resultant time tagged PMUs can be transmitted to a local or remote receiver at rates up to 60 samples per cycle.
  • 19. APPLICATION OF PMU IN POWER SYSTEM 1. Adaptive relaying 2. Instability prediction 3. State estimation 4. Improved control 5. Fault recording 6. Disturbance recording 7. Transmission and generation modeling verification 8. Wide area Protection 9. Fault location
  • 20. Adaptive Relaying Adaptive relaying is a protection philosophy which permits and seeks to make adjustments in various protection functions in order to make them more tuned to prevailing power system conditions
  • 21. Instability prediction The instability prediction can be used to adapt load shedding and/or out of step relays. We can actually monitor the progress of the transient in real time by the technique of synchronized phasor measurements.
  • 22. • The state estimator uses various measurements received from different substations, and, through an iterative nonlinear estimation procedure, calculates the power system state. State estimation • By maintaining a continuous stream of phasor data from the substations to the control center, a state vector that can follow the system dynamics can be constructed. • For the first time in history, synchronized phasor measurements have made possible the direct observation of system oscillations following system disturbances.
  • 23. The role of state estimation in power system operation Contingency Analysis Security Enhancement Dynamic Security Analysis Optimal Power Flow Other Applications State Estimation Other Data Network Model SCADA PDC PMU PMUPMU
  • 24. • Power system control elements use local feedback to achieve the control objective. Improved control • The PMU was necessary to capture data during the staged testing and accurately display this data and provide comparisons to the system model. • The shown figure shows a typical example of one of the output plots from the PMU data
  • 25.
  • 26. • They can capture and display actual 60/50 Hz wave form and magnitude data on individual channels during power system fault conditions. Fault Recording
  • 27. • Loss of generation, loss of load, or loss of major transmission lines may lead to a power system disturbance, possibly affecting customers and power system operations. Disturbance Recording
  • 28. • Computerized power system modeling and studies are now the normal and accepted ways of ensuring that power system parameters have been reviewed before large capital expenditures on major system changes. Transmission and Generation Modeling Verification • In years past, actual verification of computer models via field tests would have been either impractical or even impossible • The PMU class of monitoring equipment can now provide the field verification required.
  • 29. • The shown figure compares a remote substation 500 kV bus voltage captured by the PMU to the stability program results Continue … Positive sequence voltage phasor on a 500 kv bus vs computer model simulation of switching test
  • 30. The introduction of the Phasor Measurement Unit (PMU) has greatly improved the observability of the power system dynamics. Based on PMUs, different kinds of wide area protection, emergency control and optimization systems can be designed WIDE – AREA PROTECTION
  • 31. Multilayered wide area protection architecture
  • 32. A fault location algorithm based on synchronized sampling. A time domain model of a transmission line is used as a basis for the algorithm development. Samples of voltages and currents at the ends of a transmission line are taken simultaneously (synchronized) and used to calculate fault location. Fault Location Phasor measurement units are installed at both ends of the transmission line. The three phase voltages and three phase currents are measured by PMUs located at both ends of line simultaneously
  • 33.  A pure sinusoid quantity given by 𝑥 𝑡 = 𝑋 𝑚cos(𝜔𝑡 + 𝜃) and its phasor representation 𝑋 = Τ𝑋 𝑚 2 𝑒 𝑗𝜃 = Τ𝑋 𝑚 2 𝑐𝑜𝑠𝜃 + 𝑗𝑠𝑖𝑛𝜃 are illustrated in Figure. The aim of phasor estimation technique is just to acquire the phasor representation.  Samples of waveform data are collected over a data window which is normally one period of the fundamental frequency of the power system. In early days a sampling rate of 12 times a cycle (720 Hz for the 60 Hz system) was commonly used. Much higher sampling rates are currently used in commercial PMUs. Phasor Measuremnet Techniques
  • 34.  RMS t  tx RMS  Imaginary Axis Real Axis (a) (b) A sinusoid and its representation as a phasor
  • 35. COMPARISON  Digital measurement  60 samples per cycle (resolution)  Dynamic (Observability)  Wide area monitoring  Phasor angle measurement: Yes SCADA PMU  Analogue measurement  2-4 samples per cycle (resolution)  Steady state (Observability)  Local monitoring  Phasor angle measurement: No
  • 36. REFERENCES  Phadke, A. G., & Thorp, J. S. (2006, October). History and applications of phasor measurements. In 2006 IEEE PES Power Systems Conference and Exposition (pp. 331-335). IEEE.  Tholomier, D., Kang, H., & Cvorovic, B. (2009, March). Phasor measurement units: Functionality and applications. In 2009 Power Systems Conference (pp. 1-12). IEEE.  Phadke, A. G., & Tianshu, B. I. (2018). Phasor measurement units, WAMS, and their applications in protection and control of power systems. Journal of Modern Power Systems and Clean Energy, 6(4), 619-629.
  • 37. QUESTIONS  How does a Phasor Measurement Unit (PMU) work?  What are the main components of PMU? Explain briefly with PMU Block Diagram.  What is use of PMU in Smart Grid?  Explain the application of PMU in power system.  What is synchrophasor?  What is phasor measurement techniques?