Critical Power Supplies has pleasure in bringing you this guide on how UPSSystems work. 
An uninterruptible power supply, also uninterruptible power source, UPS orbattery / flywheel backup, is an electrical apparatus that provides emergency power to a load when the 
input power source, typically the utility mains, fails. 
A UPS differs from an auxiliary or emergency power system or standby generator in that it will provide instantaneous or near-instantaneous protection from input power interruptions 
by means of one or more attached batteries and associated electronic circuitry for low power users, and or by means ofdiesel generators and flywheels for high power users. The on-battery 
runtime of most uninterruptible power sources is relatively short—5–15 minutes being typical for smaller units—but sufficient to allow time to bring an auxiliary power source 
on line, or to properly shut down the protected equipment. 
While not limited to protecting any particular type of equipment, a UPS is typically used to protect computers, data centers, telecommunication equipment or other electrical 
equipment where an unexpected power disruption could cause injuries, fatalities, serious business disruption and/or data loss. UPS units range in size from units designed to protect 
a single computer without a video monitor (around 200 VA rating) to large units powering entire data centers (>1MVA), buildings (>300kVA), or manufacturing processes. 
Different types of UPS design. 
the general categories of modern UPS systems are on-line, line-interactive or standby. 
A standby (off-line) UPS system the load is powered directly by the input power and the backup power circuitry is only invoked when the utility power fails. Most UPS below 1 kVA 
are of the line-interactive or standby variety which are usually less expensive. 
A line-interactive UPS maintains the inverter in line and redirects the battery’s DC current path from the normal charging mode to supplying current when power is lost. 
A on-line UPS uses a “double conversion” method of accepting AC input, rectifying to DC for passing through the rechargeable battery (or battery strings), then inverting back to 
120V/240V AC for powering the protected equipment. 
For large power units, dynamic uninterruptible power supplies are sometimes used. A synchronous motor/alternator is connected on the mains via a choke. Energy is stored in a 
flywheel. When the mains power fails, an Eddy-current regulation maintains the power on the load. DUPS are sometimes combined or integrated with a diesel-generator[clarification 
needed], forming a diesel rotary uninterruptible power supply, or DRUPS. 
A fuel cell UPS has been developed in recent years using hydrogen and a fuel cell as a power source, potentially providing long run times in a small space. 
Off-line UPS design 
The Offline / Standby UPS system (SPS) offers only the most basic features, providing surge protection and battery backup. With this type of UPS, a user’s equipment is normally 
connected directly to incoming utility power with the same voltage transient clamping devices used in a common surge protected plug strip connected across the power line. When 
the incoming utility voltage falls below a predetermined level the SPS turns on its internal DC-AC inverter circuitry, which is powered from an internal storage battery. The SPS then 
mechanically switches the connected equipment on to its DC-AC inverter output. The switchover time can be as long as 25 milliseconds depending on the amount of time it takes the 
Standby UPS to detect the lost utility voltage. Generally speaking, dependent on the size of UPS connected load and the sensitivity of the connected equipment to voltage variation, 
the UPS will be designed and/or offered (specification wise) to cover certain ranges of equipment, i.e. Personal Computer, without any obvious dip or brownout to that device. 
Line-interactive UPS design 
This type of UPS is able to tolerate continuous undervoltage brownouts and overvoltage surges without consuming the limited reserve battery power. It instead compensates by auto-selecting 
different power taps on the autotransformer. Changing the autotransformer tap can cause a very brief output power disruption,[citation needed] so the UPS may chirp for a 
moment, as it briefly switches to battery before changing the selected power tap.[dubious – discuss] 
This has become popular even in the cheapest UPS because it takes advantage of components already included. The main 50/60 Hz transformer used to convert between line voltage 
and battery voltage needs to provide two slightly different turns ratios: one to convert the battery output voltage (typically a multiple of 12 V) to line voltage, and a second one to 
convert the line voltage to a slightly higher battery charging voltage (such as a multiple of 14 V). Further, it is easier to do the switching on the line-voltage side of the transformer 
because of the lower currents on that side. 
To gain the buck/boost feature, all that is required is two separate switches so that the AC input can be connected to one of the two primary taps, while the load is connected to 
the other, thus using the main transformer’s primary windings as an autotransformer. Note that the battery can still be charged while “bucking” an overvoltage, but while 
“boosting” an undervoltage, the transformer output is too low to charge the batteries. 
Autotransformers can be engineered to cover a wide range of varying input voltages, but this requires more taps and increases complexity, and expense of the UPS. It is common for 
the autotransformer to only cover a range from about 90 V to 140 V for 120 V power, and then switch to battery if the voltage goes much higher or lower than that range. 
In low-voltage conditions the UPS will use more current than normal so it may need a higher current circuit than a normal device. For example to power a 1000 watt device at 120 
volts, the UPS will draw 8.32 amps. If a brownout occurs and the voltage drops to 100 volts, the UPS will draw 10 amps to compensate. This also works in reverse, so that in an 
overvoltage condition, the UPS will need fewer amps of current. 
On-Line UPS Design 
The online UPS is ideal for environments where electrical isolation is necessary or for equipment that is very sensitive to power fluctuations. Although once previously reserved for 
very large installations of 10 kW or more, advances in technology have permitted it to now be available as a common consumer device, supplying 500 watts or less. The online UPS is 
generally more expensive but may be necessary when the power environment is “noisy” such as in industrial settings, for larger equipment loads like data centers, or when operation 
from an extended-run backup generator is necessary. 
The basic technology of the online UPS is the same as in a standby or Line-Interactive UPS. However it typically costs much more, due to it having a much greater current AC-to-DC 
battery-charger/rectifier, and with the rectifier and inverter designed to run continuously with improved cooling systems. It is called a Double-Conversion UPS due to the rectifier 
directly driving the inverter, even when powered from normal AC current.
In an online UPS the batteries are always connected to the inverter, so that no power transfer switches are necessary. When power loss occurs, the rectifier simply drops out of the 
circuit and the batteries keep the power steady and unchanged. When power is restored, the rectifier resumes carrying most of the load and begins charging the batteries, though 
the charging current may be limited to prevent the high-power rectifier from overheating the batteries and boiling off the electrolyte. 
The main advantage to the on-line UPS is its ability to provide an electrical firewall between the incoming utility power and sensitive electronic equipment. While the standby and 
Line-Interactive UPS merely filter the input utility power, the Double-Conversion UPS provides a layer of insulation from power quality problems. It allows control of output voltage 
and frequency regardless of input voltage and frequency. 
A second major advantage is the inbuilt bypass circuit in on-line UPS which ensures should any problems occur with the UPS or batteries as long as their is mains power the load will 
be powered. The bypass is either automatic or a combination of manual and automatic depending on the model / manufacturer. 
The working principle of UPS 
The working principle of UPS 
From basic principles in terms of application, UPS is a device that contains stored energy in order to inverter as the main component, regulated stable frequency output power 
protection equipment. Mainly by the rectifier, batteries, power inverters and static switch of several components. 
1) rectifier: rectifier is a rectifier device, simply means that the exchange of (AC) into direct current (DC) devices. It has two main functions: First, the alternating current (AC) 
into direct current (DC), through the supply of filtered load, or the supply inverter; second, to provide battery charging voltage. Therefore, it is also play a role in charger. 
2) Battery: UPS battery is used as a storage energy device, which consists of several cells in series, with a capacity to maintain its size determines the discharge (supply) time. 
Its main function is: When the electricity is normal, the energy converted into chemical energy stored in the battery internal; when the electricity fails, the chemical energy into 
electrical energy provided to the inverter or the load. 
3) Inverter: popular speaking, the inverter is a DC (DC) into alternating current (AC) device. It consists of inverter bridge control logic and filter circuit. 
4) Static Switch: static switch also known as static switch, which is a non-contact switch, is to use two SCR (SCR) reverse parallel composition of a communication switch, its 
closed and disconnected from the logic controller control. Conversion and the model is divided into two kinds of type and. Conversion-type switch is mainly used for two-way 
power supply system, its role is to achieve all the way to another road from the automatic switching; and model switch is mainly used for parallel inverters with electricity or 
more inverter. 
UPS's matching 
Generally based on facilities in the electricity environment, and want to achieve power conservation purposes, select the appropriate UPS. For example: built-in switching power 
supply for low-power devices typically can choose Off-line UPS; in the electrical environment to poor areas should use on-line interactive type or on-line UPS; while the right does 
not allow the time or times required intermittent sine wave AC equipment that can only use on-line UPS. But also based on your device to select the general ordinary PC, or the 
IPC's power in the 200W or so; Apple machine is around 300W; server between 300W and 600W, other equipment, the power values refer to the device's instructions.
Secondly, we should understand the UPS's rated power of representation: apparent power (in VA); the actual output power (in W). Due to the presence of reactive power it had 
contributed to this difference, the conversion relationship between the two: Apparent Power * Power Factor = actual output power. Off-line, on-line interactive power factor 
between 0.5 and 0.7, on-line power factor is generally 0.8. With UPS for equipment should pay attention to: The UPS output power to match the actual basis, and some dealers 
intentionally or unintentionally, it will cause confusion (VA) and (W) the difference, which points to draw the user's attention. 
Use of UPS 
UPS should be noted that the use of items: 
1) UPS's use of the environment should pay attention to well-ventilated, which will help heat and keep the environment clean. 
2) Do not bring inductive load, such as the Counter, fluorescent lights, air-conditioning so as to avoid damage. 
3) UPS's output load control is about 60% of the best, most reliable. 
4) UPS with load is too light (for example, 1000VA, UPS with 100VA load) may cause the battery depth of discharge, will reduce the battery life, should be avoided. 
5) Appropriate discharge, contribute to the activation of cells, such as the long-term non-stop electricity, every three months to be artificially cut off electricity to use UPS with a 
load-discharge time, so you can extend battery life. 
6) For most small UPS, to work to open UPS, with load at boot time to avoid startup, work should be shut down UPS; for network computer room UPS, because most of the 
network is 24 hours, so UPS must also be running around the clock. 
7) UPS charge promptly after discharge to prevent battery damage due to excessive self-discharge. 
UPS maintenance and repair 
The use of an uninterruptible power supply system in the process, people tend to one-sided view that is maintenance-free battery and not take this seriously. However, there are 
data show that due to battery failure caused by the host UPS failure or an abnormal proportion of the work of about 1 / 3. Thus, to enhance the proper use of the UPS batteries 
and maintenance, to extend the battery life, lower failure rate UPS systems, has become increasingly important. In addition to matching the regular brand batteries other than 
the following aspects should be the proper use and maintenance of batteries:
1) Maintain the appropriate environmental temperature: an important factor affecting battery life is the ambient temperature, the general requirements of the battery 
manufacturers the best ambient temperature is between 20 ~ 25 ℃. Although the temperature of the battery discharge capacity has increased, but the cost is the battery life 
significantly shortened. According to test the determination of the ambient temperature whenever they exceed 25 ℃, is increased by 10 ℃, the battery life should be cut by half. 
UPS is currently used batteries are generally maintenance-free sealed lead-acid battery, universal design life is 5 years, which is required in battery manufacturers environment 
can be achieved. Not reach specified environmental requirements, the length of their life there is a huge difference. In addition, the ambient temperature increase will lead to 
increased chemical activity within the battery, resulting in a lot of heat, in turn prompted ambient temperature, this vicious cycle will accelerate to shorten battery life. 
2) periodic charge-discharge: UPS power supply in the float voltage and discharge voltage, in the factory have to debug into the rating, while the size of the discharge current 
increases as the load increases, the use of reasonable adjustments should be load, , such as controlling the use of computer and other electronic equipment, the number of units. 
Under normal circumstances, the load should not exceed 60% of rated load UPS. In this context, the battery discharge current will not over-discharge. 
UPS due to long-term and electricity connected, in the supply of high quality, rare use of mains power failure environment, the battery will be a long period of float charge state, 
the course of time will cause the battery chemical energy and electrical energy conversion activity decreased with each other to accelerate the shorten the life of aging. 
Therefore, generally every 2-3 months should be fully discharged once, discharge time can be battery capacity and load size of the set. After a full load discharge, according to 
the provisions of recharge for more than 8 hours.

Contenu connexe

Dernier

Histor y of HAM Radio presentation slide
Histor y of HAM Radio presentation slideHistor y of HAM Radio presentation slide
Histor y of HAM Radio presentation slide
vu2urc
 
Artificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsArtificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and Myths
Joaquim Jorge
 
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
Earley Information Science
 

Dernier (20)

Slack Application Development 101 Slides
Slack Application Development 101 SlidesSlack Application Development 101 Slides
Slack Application Development 101 Slides
 
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘
 
Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
 
Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organization
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...
 
Histor y of HAM Radio presentation slide
Histor y of HAM Radio presentation slideHistor y of HAM Radio presentation slide
Histor y of HAM Radio presentation slide
 
Handwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsHandwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed texts
 
08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men
 
Artificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsArtificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and Myths
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024
 
Factors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptxFactors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptx
 
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024
 
A Year of the Servo Reboot: Where Are We Now?
A Year of the Servo Reboot: Where Are We Now?A Year of the Servo Reboot: Where Are We Now?
A Year of the Servo Reboot: Where Are We Now?
 
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
 
Breaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountBreaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path Mount
 

En vedette

Social Media Marketing Trends 2024 // The Global Indie Insights
Social Media Marketing Trends 2024 // The Global Indie InsightsSocial Media Marketing Trends 2024 // The Global Indie Insights
Social Media Marketing Trends 2024 // The Global Indie Insights
Kurio // The Social Media Age(ncy)
 
Good Stuff Happens in 1:1 Meetings: Why you need them and how to do them well
Good Stuff Happens in 1:1 Meetings: Why you need them and how to do them wellGood Stuff Happens in 1:1 Meetings: Why you need them and how to do them well
Good Stuff Happens in 1:1 Meetings: Why you need them and how to do them well
Saba Software
 

En vedette (20)

Content Methodology: A Best Practices Report (Webinar)
Content Methodology: A Best Practices Report (Webinar)Content Methodology: A Best Practices Report (Webinar)
Content Methodology: A Best Practices Report (Webinar)
 
How to Prepare For a Successful Job Search for 2024
How to Prepare For a Successful Job Search for 2024How to Prepare For a Successful Job Search for 2024
How to Prepare For a Successful Job Search for 2024
 
Social Media Marketing Trends 2024 // The Global Indie Insights
Social Media Marketing Trends 2024 // The Global Indie InsightsSocial Media Marketing Trends 2024 // The Global Indie Insights
Social Media Marketing Trends 2024 // The Global Indie Insights
 
Trends In Paid Search: Navigating The Digital Landscape In 2024
Trends In Paid Search: Navigating The Digital Landscape In 2024Trends In Paid Search: Navigating The Digital Landscape In 2024
Trends In Paid Search: Navigating The Digital Landscape In 2024
 
5 Public speaking tips from TED - Visualized summary
5 Public speaking tips from TED - Visualized summary5 Public speaking tips from TED - Visualized summary
5 Public speaking tips from TED - Visualized summary
 
ChatGPT and the Future of Work - Clark Boyd
ChatGPT and the Future of Work - Clark Boyd ChatGPT and the Future of Work - Clark Boyd
ChatGPT and the Future of Work - Clark Boyd
 
Getting into the tech field. what next
Getting into the tech field. what next Getting into the tech field. what next
Getting into the tech field. what next
 
Google's Just Not That Into You: Understanding Core Updates & Search Intent
Google's Just Not That Into You: Understanding Core Updates & Search IntentGoogle's Just Not That Into You: Understanding Core Updates & Search Intent
Google's Just Not That Into You: Understanding Core Updates & Search Intent
 
How to have difficult conversations
How to have difficult conversations How to have difficult conversations
How to have difficult conversations
 
Introduction to Data Science
Introduction to Data ScienceIntroduction to Data Science
Introduction to Data Science
 
Time Management & Productivity - Best Practices
Time Management & Productivity -  Best PracticesTime Management & Productivity -  Best Practices
Time Management & Productivity - Best Practices
 
The six step guide to practical project management
The six step guide to practical project managementThe six step guide to practical project management
The six step guide to practical project management
 
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
 
Unlocking the Power of ChatGPT and AI in Testing - A Real-World Look, present...
Unlocking the Power of ChatGPT and AI in Testing - A Real-World Look, present...Unlocking the Power of ChatGPT and AI in Testing - A Real-World Look, present...
Unlocking the Power of ChatGPT and AI in Testing - A Real-World Look, present...
 
12 Ways to Increase Your Influence at Work
12 Ways to Increase Your Influence at Work12 Ways to Increase Your Influence at Work
12 Ways to Increase Your Influence at Work
 
ChatGPT webinar slides
ChatGPT webinar slidesChatGPT webinar slides
ChatGPT webinar slides
 
More than Just Lines on a Map: Best Practices for U.S Bike Routes
More than Just Lines on a Map: Best Practices for U.S Bike RoutesMore than Just Lines on a Map: Best Practices for U.S Bike Routes
More than Just Lines on a Map: Best Practices for U.S Bike Routes
 
Ride the Storm: Navigating Through Unstable Periods / Katerina Rudko (Belka G...
Ride the Storm: Navigating Through Unstable Periods / Katerina Rudko (Belka G...Ride the Storm: Navigating Through Unstable Periods / Katerina Rudko (Belka G...
Ride the Storm: Navigating Through Unstable Periods / Katerina Rudko (Belka G...
 
Barbie - Brand Strategy Presentation
Barbie - Brand Strategy PresentationBarbie - Brand Strategy Presentation
Barbie - Brand Strategy Presentation
 
Good Stuff Happens in 1:1 Meetings: Why you need them and how to do them well
Good Stuff Happens in 1:1 Meetings: Why you need them and how to do them wellGood Stuff Happens in 1:1 Meetings: Why you need them and how to do them well
Good Stuff Happens in 1:1 Meetings: Why you need them and how to do them well
 

Critical power supplies

  • 1. Critical Power Supplies has pleasure in bringing you this guide on how UPSSystems work. An uninterruptible power supply, also uninterruptible power source, UPS orbattery / flywheel backup, is an electrical apparatus that provides emergency power to a load when the input power source, typically the utility mains, fails. A UPS differs from an auxiliary or emergency power system or standby generator in that it will provide instantaneous or near-instantaneous protection from input power interruptions by means of one or more attached batteries and associated electronic circuitry for low power users, and or by means ofdiesel generators and flywheels for high power users. The on-battery runtime of most uninterruptible power sources is relatively short—5–15 minutes being typical for smaller units—but sufficient to allow time to bring an auxiliary power source on line, or to properly shut down the protected equipment. While not limited to protecting any particular type of equipment, a UPS is typically used to protect computers, data centers, telecommunication equipment or other electrical equipment where an unexpected power disruption could cause injuries, fatalities, serious business disruption and/or data loss. UPS units range in size from units designed to protect a single computer without a video monitor (around 200 VA rating) to large units powering entire data centers (>1MVA), buildings (>300kVA), or manufacturing processes. Different types of UPS design. the general categories of modern UPS systems are on-line, line-interactive or standby. A standby (off-line) UPS system the load is powered directly by the input power and the backup power circuitry is only invoked when the utility power fails. Most UPS below 1 kVA are of the line-interactive or standby variety which are usually less expensive. A line-interactive UPS maintains the inverter in line and redirects the battery’s DC current path from the normal charging mode to supplying current when power is lost. A on-line UPS uses a “double conversion” method of accepting AC input, rectifying to DC for passing through the rechargeable battery (or battery strings), then inverting back to 120V/240V AC for powering the protected equipment. For large power units, dynamic uninterruptible power supplies are sometimes used. A synchronous motor/alternator is connected on the mains via a choke. Energy is stored in a flywheel. When the mains power fails, an Eddy-current regulation maintains the power on the load. DUPS are sometimes combined or integrated with a diesel-generator[clarification needed], forming a diesel rotary uninterruptible power supply, or DRUPS. A fuel cell UPS has been developed in recent years using hydrogen and a fuel cell as a power source, potentially providing long run times in a small space. Off-line UPS design The Offline / Standby UPS system (SPS) offers only the most basic features, providing surge protection and battery backup. With this type of UPS, a user’s equipment is normally connected directly to incoming utility power with the same voltage transient clamping devices used in a common surge protected plug strip connected across the power line. When the incoming utility voltage falls below a predetermined level the SPS turns on its internal DC-AC inverter circuitry, which is powered from an internal storage battery. The SPS then mechanically switches the connected equipment on to its DC-AC inverter output. The switchover time can be as long as 25 milliseconds depending on the amount of time it takes the Standby UPS to detect the lost utility voltage. Generally speaking, dependent on the size of UPS connected load and the sensitivity of the connected equipment to voltage variation, the UPS will be designed and/or offered (specification wise) to cover certain ranges of equipment, i.e. Personal Computer, without any obvious dip or brownout to that device. Line-interactive UPS design This type of UPS is able to tolerate continuous undervoltage brownouts and overvoltage surges without consuming the limited reserve battery power. It instead compensates by auto-selecting different power taps on the autotransformer. Changing the autotransformer tap can cause a very brief output power disruption,[citation needed] so the UPS may chirp for a moment, as it briefly switches to battery before changing the selected power tap.[dubious – discuss] This has become popular even in the cheapest UPS because it takes advantage of components already included. The main 50/60 Hz transformer used to convert between line voltage and battery voltage needs to provide two slightly different turns ratios: one to convert the battery output voltage (typically a multiple of 12 V) to line voltage, and a second one to convert the line voltage to a slightly higher battery charging voltage (such as a multiple of 14 V). Further, it is easier to do the switching on the line-voltage side of the transformer because of the lower currents on that side. To gain the buck/boost feature, all that is required is two separate switches so that the AC input can be connected to one of the two primary taps, while the load is connected to the other, thus using the main transformer’s primary windings as an autotransformer. Note that the battery can still be charged while “bucking” an overvoltage, but while “boosting” an undervoltage, the transformer output is too low to charge the batteries. Autotransformers can be engineered to cover a wide range of varying input voltages, but this requires more taps and increases complexity, and expense of the UPS. It is common for the autotransformer to only cover a range from about 90 V to 140 V for 120 V power, and then switch to battery if the voltage goes much higher or lower than that range. In low-voltage conditions the UPS will use more current than normal so it may need a higher current circuit than a normal device. For example to power a 1000 watt device at 120 volts, the UPS will draw 8.32 amps. If a brownout occurs and the voltage drops to 100 volts, the UPS will draw 10 amps to compensate. This also works in reverse, so that in an overvoltage condition, the UPS will need fewer amps of current. On-Line UPS Design The online UPS is ideal for environments where electrical isolation is necessary or for equipment that is very sensitive to power fluctuations. Although once previously reserved for very large installations of 10 kW or more, advances in technology have permitted it to now be available as a common consumer device, supplying 500 watts or less. The online UPS is generally more expensive but may be necessary when the power environment is “noisy” such as in industrial settings, for larger equipment loads like data centers, or when operation from an extended-run backup generator is necessary. The basic technology of the online UPS is the same as in a standby or Line-Interactive UPS. However it typically costs much more, due to it having a much greater current AC-to-DC battery-charger/rectifier, and with the rectifier and inverter designed to run continuously with improved cooling systems. It is called a Double-Conversion UPS due to the rectifier directly driving the inverter, even when powered from normal AC current.
  • 2. In an online UPS the batteries are always connected to the inverter, so that no power transfer switches are necessary. When power loss occurs, the rectifier simply drops out of the circuit and the batteries keep the power steady and unchanged. When power is restored, the rectifier resumes carrying most of the load and begins charging the batteries, though the charging current may be limited to prevent the high-power rectifier from overheating the batteries and boiling off the electrolyte. The main advantage to the on-line UPS is its ability to provide an electrical firewall between the incoming utility power and sensitive electronic equipment. While the standby and Line-Interactive UPS merely filter the input utility power, the Double-Conversion UPS provides a layer of insulation from power quality problems. It allows control of output voltage and frequency regardless of input voltage and frequency. A second major advantage is the inbuilt bypass circuit in on-line UPS which ensures should any problems occur with the UPS or batteries as long as their is mains power the load will be powered. The bypass is either automatic or a combination of manual and automatic depending on the model / manufacturer. The working principle of UPS The working principle of UPS From basic principles in terms of application, UPS is a device that contains stored energy in order to inverter as the main component, regulated stable frequency output power protection equipment. Mainly by the rectifier, batteries, power inverters and static switch of several components. 1) rectifier: rectifier is a rectifier device, simply means that the exchange of (AC) into direct current (DC) devices. It has two main functions: First, the alternating current (AC) into direct current (DC), through the supply of filtered load, or the supply inverter; second, to provide battery charging voltage. Therefore, it is also play a role in charger. 2) Battery: UPS battery is used as a storage energy device, which consists of several cells in series, with a capacity to maintain its size determines the discharge (supply) time. Its main function is: When the electricity is normal, the energy converted into chemical energy stored in the battery internal; when the electricity fails, the chemical energy into electrical energy provided to the inverter or the load. 3) Inverter: popular speaking, the inverter is a DC (DC) into alternating current (AC) device. It consists of inverter bridge control logic and filter circuit. 4) Static Switch: static switch also known as static switch, which is a non-contact switch, is to use two SCR (SCR) reverse parallel composition of a communication switch, its closed and disconnected from the logic controller control. Conversion and the model is divided into two kinds of type and. Conversion-type switch is mainly used for two-way power supply system, its role is to achieve all the way to another road from the automatic switching; and model switch is mainly used for parallel inverters with electricity or more inverter. UPS's matching Generally based on facilities in the electricity environment, and want to achieve power conservation purposes, select the appropriate UPS. For example: built-in switching power supply for low-power devices typically can choose Off-line UPS; in the electrical environment to poor areas should use on-line interactive type or on-line UPS; while the right does not allow the time or times required intermittent sine wave AC equipment that can only use on-line UPS. But also based on your device to select the general ordinary PC, or the IPC's power in the 200W or so; Apple machine is around 300W; server between 300W and 600W, other equipment, the power values refer to the device's instructions.
  • 3. Secondly, we should understand the UPS's rated power of representation: apparent power (in VA); the actual output power (in W). Due to the presence of reactive power it had contributed to this difference, the conversion relationship between the two: Apparent Power * Power Factor = actual output power. Off-line, on-line interactive power factor between 0.5 and 0.7, on-line power factor is generally 0.8. With UPS for equipment should pay attention to: The UPS output power to match the actual basis, and some dealers intentionally or unintentionally, it will cause confusion (VA) and (W) the difference, which points to draw the user's attention. Use of UPS UPS should be noted that the use of items: 1) UPS's use of the environment should pay attention to well-ventilated, which will help heat and keep the environment clean. 2) Do not bring inductive load, such as the Counter, fluorescent lights, air-conditioning so as to avoid damage. 3) UPS's output load control is about 60% of the best, most reliable. 4) UPS with load is too light (for example, 1000VA, UPS with 100VA load) may cause the battery depth of discharge, will reduce the battery life, should be avoided. 5) Appropriate discharge, contribute to the activation of cells, such as the long-term non-stop electricity, every three months to be artificially cut off electricity to use UPS with a load-discharge time, so you can extend battery life. 6) For most small UPS, to work to open UPS, with load at boot time to avoid startup, work should be shut down UPS; for network computer room UPS, because most of the network is 24 hours, so UPS must also be running around the clock. 7) UPS charge promptly after discharge to prevent battery damage due to excessive self-discharge. UPS maintenance and repair The use of an uninterruptible power supply system in the process, people tend to one-sided view that is maintenance-free battery and not take this seriously. However, there are data show that due to battery failure caused by the host UPS failure or an abnormal proportion of the work of about 1 / 3. Thus, to enhance the proper use of the UPS batteries and maintenance, to extend the battery life, lower failure rate UPS systems, has become increasingly important. In addition to matching the regular brand batteries other than the following aspects should be the proper use and maintenance of batteries:
  • 4. 1) Maintain the appropriate environmental temperature: an important factor affecting battery life is the ambient temperature, the general requirements of the battery manufacturers the best ambient temperature is between 20 ~ 25 ℃. Although the temperature of the battery discharge capacity has increased, but the cost is the battery life significantly shortened. According to test the determination of the ambient temperature whenever they exceed 25 ℃, is increased by 10 ℃, the battery life should be cut by half. UPS is currently used batteries are generally maintenance-free sealed lead-acid battery, universal design life is 5 years, which is required in battery manufacturers environment can be achieved. Not reach specified environmental requirements, the length of their life there is a huge difference. In addition, the ambient temperature increase will lead to increased chemical activity within the battery, resulting in a lot of heat, in turn prompted ambient temperature, this vicious cycle will accelerate to shorten battery life. 2) periodic charge-discharge: UPS power supply in the float voltage and discharge voltage, in the factory have to debug into the rating, while the size of the discharge current increases as the load increases, the use of reasonable adjustments should be load, , such as controlling the use of computer and other electronic equipment, the number of units. Under normal circumstances, the load should not exceed 60% of rated load UPS. In this context, the battery discharge current will not over-discharge. UPS due to long-term and electricity connected, in the supply of high quality, rare use of mains power failure environment, the battery will be a long period of float charge state, the course of time will cause the battery chemical energy and electrical energy conversion activity decreased with each other to accelerate the shorten the life of aging. Therefore, generally every 2-3 months should be fully discharged once, discharge time can be battery capacity and load size of the set. After a full load discharge, according to the provisions of recharge for more than 8 hours.