ULTRAFLOW® 54
DN150-250
ULTRAFLOW® 54 is a static flow sensor
based on the ultrasonic measuring
principle. It is primarily used as a
volume flow sensor for energy meters
such as MULTICAL®. ULTRAFLOW® 54
has been designed for use in heating
and cooling installations where water
is the heat-bearing medium.
ULTRAFLOW® 54 employs ultrasonic
measuring techniques and micropro-
cessor technology. All calculating and
flow measuring circuits are collected
on one single board, thus provid-
ing a compact and rational design
and, in addition, exceptionally high
measuring accuracy and reliability is
obtained.
The volume is measured using bidirec-
tional ultrasonic technique based on
the transit time method, with proven
long-term stability and accuracy. Four
ultrasonic transducers are used to
send sound signals both against and
with the flow. The ultrasonic signal
travelling with the flow reaches the
opposite transducer first. The time dif-
ference between the two signals can
be converted into flow velocity and
thereby also volume.
A three-wire signal cable is used
to connect ULTRAFLOW® 54 to the
Kamstrup MULTICAL® calculator. The
cable supplies the flow sensor and
also transfers the signal from sensor
to calculator. A signal correspond-
ing to the flow – or more correctly, a
number of pulses proportional to the
water volume flowing through – is
transmitted.
ULTRAFLOW® 54 is available with
internal supply, e.g. if the distance
between MULTICAL® and
ULTRAFLOW® 54 is 10 m or more.
If ULTRAFLOW® 54 is used for other
equipment (e.g. other brands of calcu-
lators), the meter must be fitted with a
galvanically separated output module
and a supply of its own.
Application
D A T A S H E E T
„„ For flow from 150 m3
/h up to 1000 m3
/h
„„ Ultrasonic flow sensor
„„ Compact design
„„ Static meter, no moving parts
„„ Large dynamic range
„„ No wear
„„ High accuracy
„„ Longevity 0200M12
MID-2004/22/EC
2. 2 5810835_F1_GB 07.2012
ULTRAFLOW® 54, DN150-250
D A T A S H E E T
Contents
Approvals3
Technical data 3
Material5
Type overview 5
Dimension sketches 6
Pressure loss 7
Pressure loss graph 7
Installation8
Straight inlet ULTRAFLOW® 54 9
Operating pressure 9
Connection to calculator 10
Type numbers of ULTRAFLOW® 54 for MULTICAL® 11
Type numbers for separate ULTRAFLOW® 54 11
Type number composition of separate ULTRAFLOW® 54 12
Type numbers of output and supply modules 12
Programming variants and pulse duration 13
Accessories14
3. 35810835_F1_GB 07.2012
ULTRAFLOW® 54, DN150-250
D A T A S H E E T
The Measuring Instruments Directive
ULTRAFLOW® 54 is available with CE-marking according to MID (2004/22/EC). The certificates have the
following numbers:
B-Module DK-0200-MI004-008
D-Module DK-0200-MIQA-001
Please contact Kamstrup A/S for further details on type approval and verification.
CE marking
ULTRAFLOW® 54 is marked according to the following directives:
EMC-directive 2004/108/EC
LV-directive 2006/95/EC (when fitted with 230 VAC power supply)
PE-directive 97/23/EC (DN150…DN250) category II
Electrical data
Supply voltage 3,6 V ± 0,1 V
Supply, galvanically coupled
output module (Y=1) Powered by MULTICAL®
Supply, galvanically separated
output module (Y=2) 1)
– Mains supply 230 VAC +15/-30%, 50 Hz
24 VAC ±50%, 50 Hz
- Power consumption 1 W
- Backup Integral SuperCap eliminates interruptions due to short-term
power failures
Supply, galvanically separated
output module (Y=3)
– Battery 3.65 VDC, D-cell lithium
- Replacement interval 6-years @ tBAT
30°C
– Mains supply 230 VAC +15/-30%, 50 Hz
24 VAC ±50%, 50 Hz
- Power consumption 1 W
- Backup Integral SuperCap eliminates interruptions due to short-term
power failures
Length of signal cable, flow sensor
electronics box
– galvanically coupled output
module (Y=1) Max. 10 m. (powered by calculator)
– galvanically separated output
module (Y=2 and Y=3) Depending on calculator (use of own supply)
EMC data Fulfils DS/EN 1434:2007 class C, MID E1 and E2
1) It is possible to use battery supply in combination with output module (Y=2), e.g. for temporary supply of flow
sensors installed at construction sites.
Approvals
Technical data
4. 4 5810835_F1_GB 07.2012
ULTRAFLOW® 54, DN150-250
D A T A S H E E T
Nom. flow qp
[m3
/h]
Nom.
diameter
[mm]
Pulse
figures 1)
[imp./l]
Dynamic
range
qi
:qp
qs
:qp
Flow @125 Hz 2)
[m3
/h]
∆p@qp
[bar]
Min. cut off
[l/h]
150 DN150 1 1:100 2:1 450 0.02 300
250 DN150 0.6 1:100 2:1 750 0.055 500
400 DN150 0.4 1:100 2:1 1125 0.04 800
400 DN200 0.4 1:100 2:1 1125 0.01 800
400 DN250 0.4 1:100 2:1 1125 0.01 800
600 DN200 0.25 1:100 2:1 1800 0.022 1200
600 DN250 0.25 1:100 2:1 1800 0.022 1200
1000 DN250 0.15 1:100 2:1 3000 0.015 2000
1)
Standard pulse figures. Appears from the ULTRAFLOW® label.
2)
Saturation flow. Max. pulse frequency 128 Hz is maintained at higher flow rates.
Mechanical data
Metrological class 2 or 3
Environmental class Fulfils DS/EN 1434 class C
Ambient temperature 5…55°C (indoors)
Protection class IP67
Humidity 93% RF non-condensing
Mechanical environment MID M1 and M2
Medium temperature 2…150°C (Heat and heat/cooling meters)
2…50°C (Cooling meters)
Technical data
At medium temperatures above 90°C (Tmed
90°C) or
medium temperature more than 5°C below ambient
temperature (Tmed
Tamb
- 5°C) the electronics box must
be wall-mounted or mounted via the enclosed distance
piece.
Storage temp. empty sensor -25…70°C, 60°C if battery mounted/enclosed
Pressure stage PN25
5. 55810835_F1_GB 07.2012
ULTRAFLOW® 54, DN150-250
D A T A S H E E T
Flange EN 1092, PN25
Material
Type overview
Nom.flow qp
[m³/h]
Sizes
150 DN150 x 500 mm
250 DN150 x 500 mm
400 DN150 x 500 mm DN200 x 500 mm DN250 x 600 mm
600 DN200 x 500 mm DN250 x 600 mm
1000 DN250 x 600 mm
Wetted parts
Housing Stainless steel, W.no. 1.4307
Transducer holder Stainless steel, W.no. 1.4308
Transducer Titanium
Gaskets Fibre
Electronics box
Base Thermoplastic, PC 10% GF
Cover Thermoplastic, PC 10% GF
Fitting hardware distance piece
for electronics box Thermoplastic, PPS 40% GF
Signal cable (optional for separate ULTRAFLOW® 54)
Silicone cable (3 x 0.5 mm²)
Power supply cable 24/230 VAC (optional)
Cable with PVC mantle (2 x 0.75 mm²)
6. 6 5810835_F1_GB 07.2012
ULTRAFLOW® 54, DN150-250
D A T A S H E E T
Flange EN 1092, PN25
Nom. diameter Nom. flow
qp
E
[mm] [m³/h] [mm]
DN150 150 250 282
DN150 400 303
DN200 400 600 329
DN250 400 600 329
DN250 1000 357
Dimension sketches
Flange EN 1092, PN25
Nom. diameter Nom. flow
qp
L D k B1 Bolts Steel tube
length C
Approx.
weight
Quantity Thread d2
[mm] [m³/h] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [kg]
DN150 150 250 500 300 250 119 8 M24 26 650 37
DN150 400 500 300 250 140 8 M24 26 625 36
DN200 400 600 500 360 310 166 12 M24 26 570 49
DN250 400 600 600 425 370 166 12 M27 30 570 79
DN250 1000 600 425 370 194 12 M27 30 500 75
7. 75810835_F1_GB 07.2012
ULTRAFLOW® 54, DN150-250
D A T A S H E E T
Pressure loss
Graph Nominal flow qp
[m³/h]
Nom. diameter
[mm]
kv
Q@0.25 bar
[m³/h]
A 150 250 DN150 1060 530
B 400 DN150 2000 1000
C 400 600 DN200 DN250 4040 2020
D 1000 DN250 8160 4080
Pressure loss graph
∆p ULTRAFLOW®
54 DN150-250
0,01
0,1
1
100 1000 10000
Flow [m³/h]
∆p[bar]
A B C D
8. 8 5810835_F1_GB 07.2012
ULTRAFLOW® 54, DN150-250
D A T A S H E E T
Installation
Installation angle of ULTRAFLOW® 54
ULTRAFLOW® 54 can be installed horizontally,
vertically, or at an angle.
ULTRAFLOW® 54 is normally installed horizon-
tally, with the lifting rings oriented vertically. The
ultrasound paths in the flow sensor tube will thus
be vertical, which is optimal in connection with
possible stratification of the medium.
Prior to installation of the flow sensor, the system should be flushed.
Correct flow sensor position (flow or return) appears from the front label of MULTICAL®. The flow direc-
tion is indicated by an arrow on the side of the flow sensor.
Please note: ULTRAFLOW® 54 may be lifted in the lifting rings only.
Pressure stage ULTRAFLOW® 54: PN25
Temperature of medium, ULTRAFLOW® 54: 2…150°C/2…50°C. See marking on label.
Mechanical environment: M1 and M2 (fixed installation with minimum vibration and fixed installation
with considerable or high vibration level respectively). See marking on label.
Electromagnetic environment: E1 and E2 (housing/light industry and industry respectively). See mar-
king on label.
The meter’s signal cables must be drawn at min. 25 cm distance to other installations.
Climatic environment: Must be installed in environments with non-condensing humidity as well as in
closed locations (indoors).
The ambient temperature must be within 5…55°C.
Maintenance and repair: The flow sensor is verified separately and can, therefore, be separated from
the calculator. It is permitted to replace the supply and change the supply type. For battery supply a
lithium battery with connector from Kamstrup A/S must be used. Lithium batteries must be correctly
handled and disposed of (see Kamstrup document 5510-408, ”Lithium batteries - Handling and dispo-
sal”). Other repairs require subsequent reverification in an accredited laboratory.
If ULTRAFLOW® 54 is connected via a galvanically coupled output module, the flow sensor may be con-
nected to a Kamstrup MULTICAL® calculator only.
If other calculator types are connected, ULTRAFLOW® 54 must be fitted with a galvanically separated
output module and a power supply of its own.
Please note: Please make sure that pulse figures of flow sensor and calculator are identical.
The steel tube between flow sensor housing and electronics box must not be disassembled.
At medium temperatures above 90°C (Tmed
90°C) or medium temperature more than 5°C below ambi-
ent temperature (Tmed
Tamb
- 5°C) the flow sensor's electronics box must be mounted via the enclosed
distance piece. Alternatively, the electronics box can be wall-mounted at a distance of minimum 170
mm from the sensor.
In order to prevent cavitation, the back pressure at ULTRAFLOW® 54 must be min. 1.5 bar at qp
and min.
2.5 bar at qs
. This applies to temperatures up to approx. 80o
C.
When the installation has been completed, water flow can be turned on. The valve on the inlet side
must be opened first.
9. 95810835_F1_GB 07.2012
ULTRAFLOW® 54, DN150-250
D A T A S H E E T
Straight inlet ULTRAFLOW® 54
ULTRAFLOW® 54 requires neither straight inlet nor outlet in order to fulfil the Measuring Instruments
Directive (MID) 2004/22/ EC and EN 1434:2007. A straight inlet section will only be necessary in case
of heavy flow disturbances before the meter. We recommend that the guidelines of CEN CR 13582 are
followed.
Optimal position can be obtained by taking the below-mentioned installation methods into considera-
tion:
A. Recommended flow sensor position.
B. Recommended flow sensor position.
C. Unacceptable position due to risk of air build-up
D. Acceptable in closed systems.
Unacceptable position in open systems due to risk of air build-up in the system
E. A flow sensor ought not to be placed immediately after a valve, with the exception of block valves
(ball valve type) which must be fully open when not used for blocking.
F. A flow sensor must never be placed on the inlet side of a pump
G. A flow sensor ought not to be placed after a double bend in two levels.
For general information concerning installation, see CEN report DS/CEN/CR 13582, Heat meter installa-
tion. Instructions in selection, installation and use of heat meters.
Operating pressure
In order to prevent cavitation, the back pressure at ULTRAFLOW® 54 must be min. 1.5 bar at qp
and min.
2.5 bar at qs
. This applies to temperatures up to approx. 80o
C.
10. 10 5810835_F1_GB 07.2012
ULTRAFLOW® 54, DN150-250
D A T A S H E E T
Connection to calculator
ULTRAFLOW® 54 and MULTICAL®, galvanically coupled
If ULTRAFLOW® 54 and MULTICAL® are connected via output module (Y=1), ULTRAFLOW® 54 is galvani-
cally coupled with MULTICAL® and is powered via the three-wire signal cable (cable length up to 10 m).
Battery life time in e.g. MULTICAL® 602 is approximately 10 years depending on data communication to
the calculator.
Note: It is not permitted to mount a supply module or battery in ULTRAFLOW® 54.
ULTRAFLOW® 54 → MULTICAL®
11 → 11 GND (Blue)
9 → 9 + 3,6 V (Red)
10 → 10 (Yellow)
When using long signal cables, careful consideration is required in connection with installation. Due to
EMC there must be a distance of min. 25 cm between signal cables and all other cables.
ULTRAFLOW® 54 and MULTICAL®, galvanically separated
If ULTRAFLOW® 54 and MULTICAL® are connected via output module (Y=2 or 3), ULTRAFLOW® 54 is
galvanically separated from MULTICAL®.
Note: Flow info cannot be read.
Three-wire connection, MULTICAL® 602
og 801 via output module (Y=2 or 3).
Cable length up to 25 metres.
Two-wire connection, MULTICAL® 801
via output module (Y=2). Cable length
up to 100 metres.
Two-wire connection, MULTICAL® 602-D
via output module (Y=2) and external
24 VDC supply. Cable length up to 100
metres.
11. 115810835_F1_GB 07.2012
ULTRAFLOW® 54, DN150-250
D A T A S H E E T
Type number Nom. flow
qp
Min. flow
qi
Max. flow
qS
Connection PN Length Pulse
figure
CCC Material flow
sensor housing
[m³/h] [m3
/h] [m3
/h] [mm] [bar] [mm] [imp/l]
65-5-FCCN-XXX 150 1.5 300 DN150 25 500 1 447 (489) Stainless steel
65-5-FDCN-XXX 250 2.5 500 DN150 25 500 0.6 481 Stainless steel
65-5-FECN-XXX 400 4.0 800 DN150 25 500 0.4 491 Stainless steel
65-5-FECP-XXX 400 4.0 800 DN200 25 500 0.4 491 Stainless steel
65-5-FECR-XXX 400 4.0 800 DN250 25 600 0.4 491 Stainless steel
65-5-FFCP-XXX *) 600 6.0 1200 DN200 25 500 0.25 492 Stainless steel
65-5-FFCR-XXX *) 600 6.0 1200 DN250 25 600 0.25 492 Stainless steel
65-5-FGCR-XXX *) 1000 10.0 2000 DN250 25 600 0.15 493 Stainless steel
Type numbers of ULTRAFLOW® 54 for MULTICAL®
xxx, code pertaining to marking and final assembly
*) Cannot be delivered with MID approval
Type number Nom. flow
qp
Min. flow
qi
Max. flow
qS
Connection PN Length Material
flow sensor housing
[m³/h] [m3
/h] [m3
/h] [mm] [bar] [mm]
65-5-FCCN -YZ -XXX 150 1.5 300 DN150 25 500 Stainless steel
65-5-FDCN -YZ -XXX 250 2.5 500 DN150 25 500 Stainless steel
65-5-FECN -YZ -XXX 400 4.0 800 DN150 25 500 Stainless steel
65-5-FECP -YZ -XXX 400 4.0 800 DN200 25 500 Stainless steel
65-5-FECR -YZ -XXX 400 4.0 800 DN250 25 600 Stainless steel
65-5-FFCP -YZ -XXX *) 600 6.0 1200 DN200 25 500 Stainless steel
65-5-FFCR -YZ -XXX *) 600 6.0 1200 DN250 25 600 Stainless steel
65-5-FGCR -YZ -XXX *) 1000 10.0 2000 DN250 25 600 Stainless steel
Type numbers for separate ULTRAFLOW® 54
xxx, code pertaining to marking and final assembly
*) Cannot be delivered with MID approval
12. 12 5810835_F1_GB 07.2012
ULTRAFLOW® 54, DN150-250
D A T A S H E E T
Type numbers of output and supply modules
Type number overview of output modules (Y) as well as supply modules (Z) for separate ULTRAFLOW® 54
Y Output module Corresponding supply module
1 Galvanically coupled module 0 (powered by MULTICAL®)
2 Galvanically separated module 0, 7, 8
3 Galvanically separated module, ”Low power” 0, 2, 7, 8
Z Supply module Corresponding output module
0 No supply 1, 2, 3
2 Battery, D-cell 3
7 230 VAC supply module 2, 3
8 24 VAC supply module 2, 3
Type number composition of separate ULTRAFLOW® 54
In addition to the basic variants output module (Y), sup-
ply module (Z) as well as pulse figure programming (CC)
and pulse duration (E) must be selected.
The variant with galvanically coupled output module
(Y=1) is solely for use together with MULTICAL®.
The variant with galvanically separated output module
(Y=2 or 3) is used in the following situations:
1. More than 10 m cable length between MULTICAL® and
ULTRAFLOW® 54 is required.
2. As flow sensor no. 2 in connection with MULTICAL®. If
two flow sensors are used together with MULTICAL®,
one must include a galvanically separated output
module (Y=2 or 3).
3. Together with other equipment/foreign calculators.
Please note: Flow info cannot be read if output module
with galvanic separation is used.
ULTRAFLOW® 54 Type 65-5- - Y Z -
Dynamic range and flow
Connection and overall length
Output module
Supply module
Final assembly and marking
14. 14 5810835_F1_GB 07.2012
ULTRAFLOW® 54, DN150-250
D A T A S H E E T
Accessories
Description Type number
Flange gaskets (PN25)
DN150 (1 pc.) 1150-140
DN200 (1 pc.) 1150-139
DN250 (1 pc.) 1150-141
Short distance piece 6561-332
Supply
D-cell lithium battery with two-pole connector 65000000-2000
230 VAC supply module 65000000-7000
24 VAC supply module 65000000-8000
Cables
ULTRAFLOW® 54 DN150-250, when ordered with MULTICAL®, is delivered with 2.5 m signal cable, optio-
nally 5 or 10 m. The cable is mounted in the ULTRAFLOW® 54 electronics box and in MULTICAL® 6xx.
When ULTRAFLOW® 54 is ordered with MULTICAL® 8xx, the calculator is delivered separately. Hence the
cable is only mounted in the ULTRAFLOW® 54 electronics box.
ULTRAFLOW® 54 DN150-250, when ordered as a separate flow sensor, is optionally available with signal
cable in lengths of 2.5, 5 or 10 m. The cable is mounted in the ULTRAFLOW® 54 electronics box.
If 24/230 VAC supply module is selected, the sensor is optionally available with power cable. The cable
is mounted in the sensor's electronics box from the factory.