SlideShare une entreprise Scribd logo
1  sur  12
Télécharger pour lire hors ligne
Pre-Engineered Buildings								 	 Standard Product Specifications
Standard Product Specifications								 		 Pre-Engineered Buildings
Standard Product Specifications
Index
1. 	 General
1.1	 Definition
1.2	 Standard Structural Framing Systems
1.3	 Standard Framing Features
1.4	 Building Components
2.	 Design
2.1	 Codes
2.2	 Loads
3.	 Material Specifications
3.1	 Structural Members
3.2	 Panels
3.3	 Trims & Gutters
3.4	 Bolts
3.5	 Fasteners
3.6	 Other Items
4.	 Shop Paint
4.1	 Structural Members
5.	 Building Accessories
5.1	 Heavy Duty Personnel Doors
5.2	 Steel Sliding Doors
5.3	 Steel Roll Up Doors
5.4	 Windows
5.5	 Adjustable Steel Louvers
5.6	 Gravity Ventilators
6.	 Structural Sub-Systems
6.1	 Roof Extensions
6.2	 Canopies
6.3	 Fascias and Parapets
7.	 Foundations and Anchorage
8.	 Submittals
8.1	 Approval Drawings
8.2	 Erection Drawings
8.3	 Design Calculations
8.4	 Design Certification
Pre-Engineered Buildings								 	 Standard Product Specifications
1.	 General
1.1	 Definition
1.1.1	 The building, as specified herein, consists of
	 columns, rafters, bracing, connection clips, roof
purlins, wall girters, roof and wall sheeting,
	 anchor bolts, flashing, trims, etc., or as specified.
All materials shall be new and free from defects.
1.1.2	 The main building structure comprises single or
multiple gable interior rigid frames with either
rigid or “post-and-beam” frames at the endwalls.
1.1.3	 The standard roof slopes are 0.5 or 1.0 unit of
	 vertical rise to 10 units of horizontal run. Other
slopes are available upon request.
1.1.4	 The sidewall steel line is the plane of the inside
vertical surface of the sidewall sheeting. It is also
the plane of the outside vertical surface of the
eave strut.
1.1.5	 The endwall steel line is the plane of the inside
vertical surface of the endwall sheeting. It is also
the plane of the outside vertical surface of the
	 outer flange of the endwall girters.
1.1.6	 The building width is the distance between the
steel lines of opposite sidewalls. Building width
does not include the width of Lean-To buildings or
roof extensions.
	 The width of a Lean-To building is the distance
from the steel line of the exterior sidewalls of the
Lean-To building to the (sidewalls or endwalls)
steel line of the main building to which the Lean-To
building is attached.
1.1.7	 The building length is the distance between the
steel lines of opposite endwalls. Building length
is a combination of several bay lengths.
	 Building length does not include the width of
	 endwall Lean-To buildings or roof extensions.
1.1.8	 End bay length is the distance from the outside of
the outer flange of endwall columns to the center
line of the first interior frame.
1.1.9	 Interior bay length is the distance between the
center lines of two adjacent interior rigid frame
columns.
1.1.10	The building eave height is the distance from
	 finished floor level (FFL) to the top of the eave strut
at the sidewalls steel line.
1.1.11	The building clear height is the distance from
finished floor level (FFL) to the bottom of the end
plate of the rafter at the knee.
1.2	 Standard Structural Framing Systems
1.2.1	 Clear Span (CS) buildings have a gable roof with
vertical sidewalls and endwalls. Interior bay
frames are clear span rigid frames without
	 interior columns.
1.2.2	 Multi-Span (MS) buildings have a gable roof with
vertical sidewalls and endwalls. Interior bay
frames are rigid frames, typically with tapered
exterior columns, tapered rafters and square tube
or built-up interior columns.
1.2.3	 Space Saver (SV) buildings have a gable roof
with vertical sidewalls and endwalls. Interior bay
frames are clear span rigid frames having
	 constant depth columns and tapered rafters
	 typically with horizontal bottom flanges.
1.2.4	 Lean-To (LT) buildings consist of outer sidewall
columns and simple span rafters attached to the
sidewall columns or the endwall posts of the main
building. Lean-To columns are of constant depth.
Lean-To rafters may be tapered or of constant
depth.
1.2.5	 Multi-Gable (MG) buildings have a roof with two
or more gables and vertical sidewalls and
	 endwalls. Interior bay frames are rigid frames
	 typically having tapered exterior columns,
	 tapered rafters and built-up interior columns.
1.3	 Standard Framing Features
1.3.1	 Main frames are typically constructed from
	 tapered or constant depth columns and rafters.
1.3.2	 Rigid frames for Clear Span (CS) and Multi-Span
(MS) buildings are most commonly spaced from
6000 mm to 10000 mm, center line to center line.
1.3.3	 Outside flanges of Clear Span (CS) and Multi-Span
(MS) rigid frame columns are inset 200 mm from
the sidewall steel line to allow for by-pass girts.
1.3.4	 Outside flanges of Space Saver (SV) rigid frame
columns shall be placed flush with the sidewalls
steel line.
1.3.5	 The top flanges of all rigid frame rafters are 200 mm
below the bottom of the roof sheeting.
1.3.6	 End frames are “post-and-beam” (P&B) load
1
Standard Product Specifications								 		 Pre-Engineered Buildings
	 bearing frames with endwall girts flush framed into
the webs of the endwall posts so that the outer
	 flanges of the girts are in the same vertical plane as
the outer flanges of the posts. Optional rigid frames
may be used at the building ends. The center line of
the endwalls rigid frame shall be 385 mm from the
endwalls steel line.
1.3.7	 Endwall posts are typically spaced at 6000 mm.
	 Depending on the width of the building and
	 endwall openings, other spacing may also be used.
	 When the building width is not evenly divisible by
6000 mm, the interior spacing of the endwall posts is
typically kept at 6000 mm with two equal end
	 spacings smaller or larger than 6000 mm.
1.3.8	 For Clear Span (CS) and Multi-Span (MS)
	 buildings, the sidewall girts are attached
	 (by-passed) to the outer flanges of exterior columns.
Sidewall girts are lapped at all interior frames.
	 For Space Saver (SV) and Lean-To (LT) buildings,
the sidewall girts are flush connected (flush framed)
so that the outer flange of the girters is in the same
vertical plane as the outer flange of the
	 exterior columns.
1.3.9	 The bottom flanges of roof purlins are attached to
the outer (top) flanges of the rafters. Purlins are
lapped at all interior frames in all structural
	 framing systems.
1.4	 Building Components
1.4.1	 Columns and rafters of rigid frames are tapered
built-up “I” sections. Interior columns of multi-span
frames may be square tube sections.
1.4.2	 All rigid frame connections are bolted. Columns
and rafters are provided with welded end plates for
anchoring to foundations and for member-to-
	 member attachment. Pre-punched holes or welded
clips are provided for attachment of purlins and
girters, bracing, and other components.
1.4.3	 Load bearing “post-and-beam” (P&B) end frames
may be constructed from cold-formed channels, hot
rolled sections or built-up welded plate sections, as
required.
1.4.4	 Purlins and girts are pre-punched cold-formed “Z”
shaped sections, 200 mm in depth with stiffened
flanges.
1.4.5	 Eave struts are pre-punched cold-formed “C”
shaped sections, 180 mm in depth with 85 mm
stiffened flanges. The eave strut serves as a
	 longitudinal structural bracing member in
	 addition to acting as a transition point for walls
and roof sheeting.
1.4.6	 Panels (roof and walls) are roll formed to the
maximum practical length (generally 9000 mm) to
minimize end laps in the field.
1.4.7	 The standard roof and walls panel is Profile “S”.
It is a roll formed panel having 4 major high ribs
and 4 minor ribs. The panel covers a width of 1000
mm. The lapped major rib has a siphon break to
prevent capillaric intrusion of water at the side
lap. The panel has an extended bearing leg to
provide stiffening during installation.
1.4.8	 Roof panels have a minimum end lap of 150 mm
over purlins and are fully protected from siphon
action by an end lap mastic.
1.4.9	 Wall panels have the same side lapping as the
roof panels. End lap is 100 mm over the girts.
Generally no side or end lap mastic is required.
1.4.10 Sandwich panels are factory-injected insulated 	
panels. They are constructed of a hard
	 polyurethane foam core between two single skin
panels. The rigid foam core has a density of
	 approximately 40 kg/m3
.
	 The standard roof sandwich panel is the Tempcon
(TC) panel. The outer panel is the
	 standard Profile “S” panel, described in section
1.4.7. The inner panel is a flat panel.
	 The standard wall sandwich panel is the Tem-
parch (TA) panel. Both the outer and inner panels
are flat panels.
	 All sandwich panels cover a width of 1000 mm.
1.4.11	Profiled ridge panels are provided at the ridge of
all buildings with single skin roof panels.
1.4.12	Eave gutters are supplied in lengths of 6000 mm.
They are cold-formed to a profiled cross-section
that is about 180 mm wide x 168 mm high.
1.4.13	Downspouts for eave gutters are supplied in
lengths of up to 9000 mm to minimize splicing.
They are cold-formed to a ribbed rectangular
cross section 105 mm wide x 73 mm deep.
1.4.14	 Valley gutters are supplied in maximum lengths
of 4500 mm. They are cold-formed in two standard
size classifications; 400 mm wide x 190 mm high
and 354 mm wide x 190 mm high.
1.4.15	 Downspouts for valley gutters in Multi-Gable
(MG) buildings are PVC pipes supplied in three
sizes; 110 mm, 160 mm and 200 mm (outside
	 diameter). Fiberglass or PVC outlets connecting
the valley gutter to the downspouts are also supplied.
2
Pre-Engineered Buildings								 	 Standard Product Specifications
1.4.16	 Diagonal bracing, providing longitudinal stability
against wind, seismic or other forces, is attached
to the web of the rigid frame near the outer flange
of columns and rafters. The standard diagonal
bracing is a galvanized steel 7-wire strand cable
with an eye bolt with an adjusting nut and hillside
washer at each end. Solid round bars or hot rolled
angles may be used as required by design.
1.4.17	 Flange braces, in the form of angles, are provided
to stabilize the interior flanges of rigid frame rafters
and columns at certain purlin and girter locations.
1.4.18	 Base angles are provided in fully sheeted walls
6000 mm in length for attachment of the wall panel
to the concrete slab. The concrete floor slab must
have a 40 mm x 40 mm notch at the perimeter
	 (below the finished floor level) to accommodate
the bottom of the wall panel to prevent ingress of
dust and water. The base angle is a light gauge
bent plate.
2.	 Design
2.1	 Codes
2.1.1	 Frame members (hot rolled or built-up) are
	 designed in accordance with the American
	 Institute of Steel Construction (AISC): “Manual of
Steel Construction, Allowable Stress Design.”
2.1.2	 Cold-formed members are designed in
	 accordance with the American Iron and Steel
	 Institute (AISI): “Cold-formed Steel Design
	 Manual.”
2.1.3	 All welds are designed in accordance with the
American Welding Society (AWS): “Structural
Welding Code - Steel”.
2.1.4	 Loads are applied in accordance with the
	 requirements of the Metal Building Manufacturers
Association (MBMA) of the USA: “Low Rise Building
Systems Manual”.
2.1.5	 Other codes can be accommodated if specified.
2.2	 Loads
2.2.1	 The building is designed to withstand the dead
load (DL) of the structure plus a specified live load
(LL) and wind load (WL).
2.2.2	 Auxiliary (Collateral) loads, if any, must be
	 specified by the customer at the time of request
for quotation.
2.2.3	 When snow load is of concern, the customer will
specify the snow load where applicable, in
	 accordance with local codes.
2.2.4	 Load combinations shall be in accordance with
the requirements of the “Low Rise Building
	 Systems Manual” published by MBMA.
2.2.5	 Other loads and load combinations can be
	 accommodated and must be specified at the time
of request for quotation.
2.2.6	 Zamil Steel will not be responsible for any static
or dynamic loads that are transferred to its
	 building from the plant machinery and equipment,
unless the loads are specifically requested at the
time of request for quotation.
3.	 Material Specifications
3.1	 Structural Members
3.1.1	 Built-up sections are fabricated from hot rolled
steel plates conforming to ASTM A 572M Grade
345 Type 1 (or equivalent), with a minimum yield
strength of 34.5 kN/cm2
(50 ksi). Flanges are
	 welded to the web by a continuous single side
	 fillet weld deposited by an automatic submerged
arc welding process.
3.1.2	 Hot rolled sections are mill produced according
to EN 10025-2 Grade S355JR (or equivalent) with a
minimum yield strength of 34.5 kN/cm2
(50 ksi).
3.1.3	 Tube sections, (used as interior columns in some
Multi-Span buildings) are mill formed steel sections
conforming to EN 10210-1 S355J2H or JIS 3466 STKR
490 (or equivalent), with a minimum yield strength of
32.5 kN/cm2
(47 ksi).
3.1.4	 Secondary members (comprised mostly of purlins
& girts) are cold-formed from hot rolled steel coils
ranging in thickness from 1.5 mm to 3.0 mm for “Z”
shapes, and in 2.0 mm and 2.5 mm for “C” shapes
(lipped channels).
3.1.4.1	Painted secondary members are cold-formed from
hot rolled steel coils conforming to ASTM A 607
Grade 50 or ASTM A 1011M HSLAS Grade 340
Class 1 Type 1 (or equivalent) having a minimum
yield strength of 34.0 kN/cm2
; and then factory
	 painted with Zamil Steel standard primer.
3.1.4.2	Galvanized secondary members are cold-formed
from steel coils conforming to ASTM A 653M Grade
3
Standard Product Specifications								 		 Pre-Engineered Buildings
SS 340 Class 1 (or equivalent), with zinc coating to
Z275 (G 90) designation (275 g/m2
), having a
	 minimum yield strength of 34.0 kN/cm2
(50 ksi).
3.1.5	 Bracing cables are 12 mm diameter, zinc coated
	 7-wire strand steel cables of extra high strength. The
strand wires conform to ASTM A 475 (or equivalent)
with a minimum breaking load of 119.7 kN.
3.1.6	 Bracing rods, used in sidewalls of buildings
	 supporting cranes, are solid plain round steel bars
conforming to ASTM A 36M (or equivalent) with a
minimum tensile strength of 40 kN/cm2
(58 ksi).
3.1.7	 Sagrods,usedtobracepurlinsandgirtsinbayslon-
ger than 8500 mm or in buildings with slopes larger
than 2.5 to 10, are 12 mm or 16 mm solid threaded,
round steel bars conforming to ASTM A 36M (or
equivalent) with a minimum tensile strength of 40 kN/
cm2
(58 ksi).
3.1.8	 Flange braces used to stabilize the inner flanges of
main frame columns and rafters are 50 mm x 50
mm x 4 mm steel angles conforming to ASTM A 36M
(or equivalent) with a minimum yield strength of 25
kN/cm2
(36 ksi).
3.1.9	 Base / gable angles are 45 mm x 73 mm x 1.5 mm
thick angles supplied in 6000 mm long pieces,
	 cold-formed from galvanized steel and conforming
to ASTM A 653M SS Grade 340 Class 1 (or equivalent),
with zinc coating to Z275 (G90) designation (275 g/
m2
) having a minimum yield strength of 34.0 kN/
cm2
(50 ksi).
3.2	 Panels
3.2.1	 Roof Panels are roll formed from 0.5 mm (nominal)
thick cold-rolled steel coated with an aluminum /
zinc alloy (Zincalume). The material conforms to
ASTM A 792M Grade 340 Class 2, with alloy (Alumi-
num / Zinc) coating AZM150 (or equivalent), having
a minimum yield strength of 34 kN/cm2
(50 ksi). The
coating is achieved through a hot dip process, which
is 55% aluminum and the balance zinc, by weight.
Pre-painted roof panels are optional.
3.2.2	 Wall Panels have the same specifications as the roof
panels (as described in section 3.2.1 above), but they
aremillpainted. Paintfinishfilmthickness shall be 25
microns of high durability polyester (ZSP) on the
	 exterior (weather) face and 12 microns of plain
	 polyester on the interior face.
3.2.3	 Interior liner panels have the same specifications as
the wall panels (as described in section 3.2.2 above).
3.2.4	 Standard colors for pre-painted wall panels are
those standard colors mentioned in Zamil Steel’s
product brochure and panel chart.
3.2.5	 Mezzanine deck panels are roll-formed from 0.7 mm
thick cold-rolled galvanized steel. The material
	 conforms to ASTM A 653M SS Grade 550, zinc
	 coatingZ180(G60),andhasaminimumyieldstrength
of 55.0 kN/cm2
(80 ksi).
3.2.6	 Roof and walls panel upgrades.
	 Other premium durability paint finishes are avail-
able upon request, such as Polyvinylidene Fluoride
finish (ZPF)
	
	 Roof and wall panels may be upgraded to 0.7 mm
(nominal) thickness as follows:
3.2.7	 Sandwich panels are available in two types:
	 (a)	 Tempcon Panels:
			 Tempcon sandwich panels are produced
			 using rigid polyurethane foam core with
			 external and internal sheets in steel or
			 aluminum of varying thickness, coatings
			 and colors. Tempcon is a durable sand		
		 wich panel, particularly in industrial build	
		 ings and are suitable for roof and wall for
			 all building applications.
	 (b)	 Temparch Panel:
			 Temparch sandwich panels are produced
			 using rigid polyurethane foam core with
			 external and internal sheets in steel or
			 aluminum of varying thickness, and are
			 suitable for walls for all building
			 applications, interior partition and
			 cold stores.
	 All the outer skins of Tempcon and Temparch pan-
els are Zincalume coated steel conforming to ASTM
A 792M Grade 340 Class 2, with zinc alloy coating
AZM150 and are available in all Zamil Steel stan-
dard colors.
	
	 All the inner skins of Tempcon and Temparch pan-
els are Zincalume coated steel conforming to ASTM
A 792M Grade 340 Class 2, with zinc alloy coating
4
Thickness
(mm)
0.7
Base Metal Paint Finish
Steel
Aluminum
Bare Zincalume
ZSP
ZPF
Plain
ZSP
Pre-Engineered Buildings								 	 Standard Product Specifications
AZM150, and are available in Frost White color.
	
	 Tempcon and Temparch skins may be upgraded as
per section 3.2.6.
3.3	 Trims & Gutters
3.3.1	 Walls flashing and trims (gable, corner, framed
opening, accessories, etc.) are cold-formed from
the same material (color & finish) as wall panels.
3.3.2	 Roof flashing and trims (parapet flashing,
	 transition trims, expansion joint trims and ridge
caps) are cold-formed from the same material
(color & finish) as roof panels.
3.3.3	 Eave gutters and downspouts are cold-formed
from the same material as wall panels.
3.3.4	 Valley gutters (used in parapet fascias and valley
conditions) are cold-formed from a 1.0 mm (minimum)
thick (nominal) bare Zincalume coated cold-rolled
steel coil, conforming to ASTM A 792M Grade 340
Class 2, with zinc alloy coating AZM150 or bare
	 Galvanized/Zinc coated cold rolled steel coil con-
forming to ASTM A 653M SS Grade 340 Class 1,
with Z275 coating (or equivalent) having a
	 minimum yield strength of 34.0 kN/cm2
(50 ksi).
	 A protective zinc phosphate pigmented epoxy
coating system is applied to the exposed surface,
having a total average dry film thickness of 150
microns on the exterior side and 50 microns on the
interior side.
3.4	 Bolts
3.4.1	 High strength bolts are hot-dip galvanized and
conform to ASTM A 325M (full thread), Type 1 (or
equivalent). They are used to connect primary
members.
3.4.2	 Machine bolts are electro-galvanized with a
	 yellow chromate color conversion coating and
	 conform to DIN 933 Class 4.6 (or equivalent). They
are used to connect secondary members (mainly
	 purlins and girts).
3.4.3	 Anchor bolts are manufactured from rods
	 conforming to ASTM F1554 grade 55 or ISO 898-1
Class 5.8 (or equivalent) with a minimum yield
strength of 38.0 kN/cm2
and an ultimate strength of
51.7 - 65.5 kN/cm2
.
3.5	 Fasteners
3.5.1	 Roof fasteners are metallic-polyester coated, heat
treated carbon steel, conforming to AS 3566 Class 3
(or equivalent). They are 5.5 mm diameter, hex-head,
self-drilling screws, assembled with galvanized steel
washers bonded with EPDM seals.
3.5.2	 Wall fasteners are metallic-polyester coated,
heat-treated carbon steel, conforming to AS 3566
Class 3 (or equivalent). They are 5.5 mm diameter,
hex-head, self-drilling screws with integral
	 washers bonded with EPDM seals. The heads of
wall fasteners are painted to match the color of the
wall panels (as per section 3.2.4).
3.5.3	 Sandwich panel fasteners
	 same as 3.5.2.
3.5.4	 Stitch fasteners for the roof are metallic-polyester
coated, heat-treated carbon steel, conforming to
AS 3566 Class 3 (or equivalent). They are 4.8 mm
diameter, hex-head, self-drilling screws,
	 assembled with galvanized steel washers bonded
with EPDM seals. They are used on the side laps
of roof panels, and in trim-to-trim and trim-to-
	 panel fixing applications.
3.5.5	 Stitch fasteners for the walls are metallic-polyester
coated, heat-treated carbon steel, conforming
to AS 3566 Class 3 (or equivalent). They are 4.8
mm diameter, hex-head, self-drilling screws with
hex-head integral washers bonded with EPDM
seals. The heads of stitch fasteners for the walls
are painted to match the color of the wall panels
(per section 3.2.4). They are used on the side laps
of panels, and in trim-to-trim and trim-to-panel
	 fixing applications.
3.5.6	 Mezzanine deck fasteners are 5.5 mm diameter,
metallic-polyester coated, heat-treated carbon
steel, self-drilling screws, with hex head, capable
of drilling through steel up to 12 mm thick. They
conform to AS 3566 Class 3 (or equivalent).
3.5.7	 Rivets are 4.0 mm diameter and made from
	 Aluminum. They are used in gutter splicing,
	 fixing trim-to-trim, or trim-to-panel, and fastening
	 accessories to roof or wall claddings. They are
available in all standard colors.
3.5.8	 Stainless steel fasteners, for Aluminum panels,
are 5.5 mm diameter, hex-head, self-drilling,
	 stainless steel screws, assembled with stainless
steel washers bonded with EPDM seals. Material
grade is AISI 304 (or equivalent).
3.6	 Other Items	
3.6.1	 Skylights and wall lights are made of translucent
white acrylic modified, ultra violet stabilized,
	 fiberglass with a tensile strength of 8.7 kN/cm2
(using ASTM D 638 test method) with a flexural
5
Standard Product Specifications								 		 Pre-Engineered Buildings6
strength of 13.83 kN/cm2
(using ASTM D 790 test
method). Translucent panels weigh 2.4 kg/m2
(nominal) and provide the same coverage as the
panel width with a maximum length of 3600 mm.
The profile of the translucent panels matches that
of the adjoining roof/wall panels so that weather
tightness is achieved through the same lapping
technique used for the panels themselves. The
	 translucent panels meet the light transmission
	 value of 75% (+5%) according to ASTM D 1494.
3.6.2	 Fall Shield (Skylight Fall Protection) is a fall pro-
tection system to safeguard people from tripping,
stepping and falling accidentally through skylights
on the roof. It is fabricated from hot-dip galvanized
wiremesh and rigidly supported by hat sections
and clips which are fixed directly on top of the pan-
el-purlin area on the roof with covering size/dimen-
sion conforming to the surface area of the skylight
panel.
3.6.3	 Foam closures match the panel profile. They are
made of expanded polyethylene or similar
	 material.
3.6.4	 Bead mastic is an extruded elastomeric butyl
rubber based sealant supplied in rolls on silicon
release paper conforming to Federal Specification
TT-C-1796 A Type II Class B (or equivalent).
3.6.5	 Flowable mastic (caulking sealant) is a neutral
cure silicone rubber sealant that is chemically
	 inert and non-corrosive. It is UV resistant and suitable
for exterior applications against weathering and
rainwater. When cured, it is non-toxic and will
	 accommodate high thermal and shrinkage
	 changes in structural movement joints.
3.6.6	 Fiberglass insulation meets UL 25/50 fire rating
and is supplied in 50 mm, 75 mm, 100 mm and 150
mm thicknesses with a factory laminated Rein-
forced White Metalized film Scrim Kraft (WMSK)
or Foil Reinforced Kraft (FRK) faced vapor barrier.
The fiberglass density is 10 kgm3
. Other facings,
densities and thicknesses are
	 available upon request.
	
	 Fiberglass insulation is supplied with double face
tape, patching tape, stapler and staples.
	
4.	 Shop Paint
4.1	 Structural Members
4.1.1	 Primary and secondary steel is cleaned and prime
painted according to the Steel Structures Painting
Council SSPC-PS Guide 7.00 specification to a dry
film thickness of not less than 40 microns.
4.1.2	 Primer paint conforms to the performance
	 requirements of Steel Structures Painting Council
SSPC Paint 15 Type 1.
4.1.3	 Shop primer is intended to provide temporary
	 protection against weathering during transport
and erection. It is not intended to provide
	 permanent corrosion protection, especially in the
case of exposed steel.
4.1.4	 When special paint supplier is specified by the
consultant / client, and paint is found to have
	 application problems and (or) extended drying
times, Zamil Steel will recommend to substitute it
with an equivalent and suitable supplier, subject
to final approval by the consultant / client.
5.	 Building Accessories
5.1	 Personnel Doors
5.1.1	 Personnel doors are flush-finished and 44 mm
thick. Single leaf doors are 915 mm wide x 2135
mm high. Double leaf doors are 1830 mm wide x
2135 mm high.
5.1.2	 Door leaves are reinforced, stiffened and
	 soundproofed with an expanded polystyrene core,
laminated to the inside faces of door panels,
	 completely filling the inside cavity of the door leaf.
5.1.3	 Steel door panels are 0.9 mm (nominal) thick, hot
dip galvanized, 180 g/m2
, as per ASTM A 653M
(Z180) cold-rolled steel, thoroughly cleaned,
	 phosphated and painted with a white finish to
	 ensure optimal corrosion protection.
5.1.4	 A white or galvanized finished “Z” shaped
	 astragal is field attached to the inactive leaf of all
double doors.
5.1.5	 Doors are factory prepared for a cylindrical lockset.
5.1.6	 Door frames are 1.5 mm (nominal) thick hot-dip
galvanized steel, prepared to ASTM A 653M (Z180)
classification (or equivalent), thoroughly cleaned,
phosphated and painted with a modified alkyd
primer, plus a white finish coat.
5.1.7	 Door frames are delivered knocked-down. Mitered
corners have brackets with pre-drilled holes for
field assembly and are supplied with all fasteners
necessary for assembly.
5.1.8	 The lockset is a keyed cylindrical type with satin
chrome finish. Optional panic devices and auto
Pre-Engineered Buildings								 	 Standard Product Specifications 7
closer are available.
5.1.9	 Each door leaf has three mortise 115 mm x 115 mm
ball bearing hinges with a security set screw in
the barrel to prevent removal of the hinge pin with
the door in a closed position.
5.2	 Steel Sliding Doors
5.2.1	 The frames of horizontal steel sliding doors are
manufactured from 2 mm (nominal) thick, cold
formed channels and girts and are delivered
knocked-down for field assembly. All clips,
	 fasteners, etc., necessary for assembly are
	 provided.
5.2.2	 The exterior face of the door leaf is sheeted with
0.5 mm (nominal) thick, pre-painted profiled
	 panels. The panel ribs run vertically. The door
panel profile matches the profile and material of
the wall panels.
5.2.3	 Door leaves are either suspended from an exterior
mounted trolley rail attached to a structural header
beam or bottom, supported by rollers on a fixed track
anchored on the ground. The door hood trim, de-
signed to conceal and protect the header and rail,
is supplied with same material as the wall pan-
els.
5.2.4	 Doors are bottom or top guided by a specially
	 designed steel rail track.
5.2.5	 Door widths range from 1500 mm to 3000 mm, for
single sliding doors, and from 3000 mm to 6000
mm, for double sliding doors. The height of the
sliding doors range from 3000 mm to 6000 mm.
5.2.6	 Sliding doors may also be provided with
	 flush-hinged pilot doors. A pilot door is a
	 personnel door within a leaf of the sliding door.
5.3	 Steel Roll Up Doors
5.3.1	 Roll-up door sizes conform to the following table:
Width (mm) Length (mm)
3000 3000
3000 4000
4000 4000
4000 5000
5000 5000
5.3.2	 The door curtain is cold-formed from hot-dip
	 galvanized steel and painted with a polyester
paint in Frost White color. The bottom rail of the
door curtain is an extruded Aluminum angle.
5.3.3	 Guides are 95 mm deep channels roll formed from
2.5 mm (nominal) thick hot-dip galvanized steel.
5.3.4	 The door drum (supporting the door curtain) is a
165 mm (nominal) diameter and 3.2 mm (nominal)
thick pipe. The drum houses safety springs, end
shafts, collars and bearings and conforms to
	 Australian Standard AS 1905 for safety.
5.3.5	 Doors are supplied complete with guides, axle,
curtain and a manual chain and reduction gear
operating mechanism. Electric operators are
available as an option.
5.4	 Sectional Doors
5.4.1	 Sectional doors are available in normal/regular
sizes of 5000 mm Width x 5000 mm Height and be-
low. (Other and bigger door sizes can also be made
upon request.)
Width (mm) Height (mm)
3000 3000
3000 4000
4000 4000
4000 5000
5000 5000
5.4.2	 The sectional door’s panel or leaf is composed of
42 mm thick, double-skin and hot-dip galvanized
steel section, insulated with polyurethane core and
painted with primer-polyester coating.
5.4.3	 Track (or Door Guide) use 52 mm rail width/depth
for door sizes of 5000 mm Width x 5000 mm Height
and below. (For bigger door sizes, 91 mm rail width/
depth is used.)
5.4.4	 Sectional doors can be manually operated or elec-
trically operated using industrial duty motor with
manual override/operation in case power is off.
5.4.5	 Sectional doors can be supplied with optional ac-
cessories such as Ventilation Grills, Glazing and
Wicket Doors.
5.5	 Windows
	 Window frames are made of anodized Aluminum
extrusions with natural color finish conforming to
ASTM B 221M Alloy 6063-T5 tempered aluminum
alloy (or equivalent). Windows are horizontal
Standard Product Specifications								 		 Pre-Engineered Buildings8
	 double slide type, 1000 mm high and 1000 mm wide,
specifically designed for installation in profiled
	 exteriorwallpanels. Windowsarefactory glazed with
minimum 6 mm thick clear glass and are equipped
with latches and a removable insect screen.
5.6	 Adjustable / Fixed Steel Louvers
	 Adjustable steel louvers are 1000 mm wide x 1000
mm high. They are supplied complete with a
	 galvanized steel mesh, blades and framing. They
are made from the same material, finish and color
as wall panels. Fixed steel louvers are available
in 1000 mm wide x 1000 mm high, 1000 mm wide x
1500 mm high and 1500 mm wide x 1000 mm high.
5.7	 Gravity Ventilators
	 Gravity flow ridge ventilators are 3000 mm long
with a throat opening of 300 mm or 600 mm. They
are installed as either individual units or as
	 continuous (i.e. joined) units. The outer skin of
the ventilators is pre-painted Zincalume steel that
matches the color of roof panels. The ventilators
are supplied complete with bird screens. A damp-
er system to close the throat opening is optional on
300 mm throat ventilators.
	 For export shipments, ventilators are shipped
knocked-down to be field assembled by the
	 erector before installation.
6.	 Structural Sub-systems
6.1	 Roof Extensions
6.1.1	 Sidewall roof extensions extend beyond the
	 defined building width and are generally a
	 continuation of the main building roof slope.
6.1.2	 End wall roof extensions extend beyond the defined
building length and are constructed by extending
the end bay purlins and eave struts of the main
building past the endwall rafters.
6.1.3	 Standard widths for roof extensions range from 900
mm to 1500 mm. Wider roof extensions can be used
but may require heavier or additional framing.
6.1.4	 Soffit panels for roof extensions are optional.
6.1.5	 Main building eave gutters are normally relocated
to the edge of the roof extensions. Gutter drainage
is achieved by downspouts located at the building
sidewalls.
6.2	 Canopies
6.2.1	 Sidewall canopies are cantilevered rafters
	 attached to the sidewall columns at any point
	 below the eave and support 200 mm deep by-pass
“Z” purlins supporting the canopy roof panels.
6.2.2	 End wall canopies are cantilevered rafters along
a uniform elevation attached to the end wall posts
below the roof line and support by-passed 200 mm
deep “Z” purlins supporting the canopy roof panels.
6.2.3	 Optional canopy soffits conceal only the canopy
purlins, leaving rafters exposed, unless otherwise
specified.
6.2.4	 Unless otherwise specified, the roof panels of the
canopies shall match the color and profile of the
main building roof panels.
6.2.5	 The width of a canopy depends on the size of the
sidewall columns or end wall posts supporting it.
Practical widths range from 1500 mm to 3000 mm.
Wider canopies are possible but require heavier
sidewall columns or end wall posts.
6.2.6	 The length of a canopy is ideally a multiple of bay
lengths of the sidewalls or a multiple of column
	 spacings of the end walls.
6.3	 Fascias and Parapets
6.3.1	 Vertical fascias consist of 200 mm deep vertical posts
supported by brackets from sidewall columns or
	 endwall posts. Cold-formed 200 mm deep “C”
	 section top and bottom girts are flush-framed to the
vertical fascia posts. An intermediate “C” girt
	 positioned vertically is supplied to support a valley
gutter, when required.
	 Standard vertical fascias project 600 mm from the
building sidewall or end wall steel lines. Projections
exceeding 600 mm are possible but may require
heavier sidewall columns and end wall posts. The
height of the fascia varies depending on actual
	 requirements. Typical heights range between 1000
mm to 1600 mm.
	
	 Fasciasheetingissuppliedin0.5mm(nominal)thick,
pre-painted panels matching the sidewalls profile.
Soffit panels and back-up panels are
	 provided only when specified.
6.3.2	 Curveline fascias are of the same type of
	 construction as vertical fascias but are sheeted with
Pre-Engineered Buildings								 	 Standard Product Specifications 9
curved profiled panels and are available in three
types:
	 Bottom curved fascias that have a curved panel at
the bottom of the fascia only.
	
	 Top and bottom curved fascias that have a curved
panel at the top and bottom of the fascia.
	
	 Center curved fascias that haave a single panel
curved at the mid height of the fascia.
6.3.3	 A parapet fascia is an extension of the sidewalls and
endwalls above the roof line. The wall sheeting of the
building will continue to the top of the parapet.
6.3.4	 Standard eave gutters and downspouts are used
in buildings with sidewall vertical fascias.
	 Valley gutters are used in buildings having
	 sidewall parapet fascias.
7.	 Foundation and Anchorage
7.1.1	 Foundations, tie beams and concrete floor slabs
should be designed by a licensed engineer.
	 Zamil Steel does not provide this service.
7.1.2	 The design should be based on the building
	 column specifications stated on “Issued For
	 Construction” anchor bolt setting Plans.
7.1.3	 Anchor bolts must be set in strict accordance with
Zamil Steel anchor bolt setting plans. Zamil Steel is
not be responsible for incorrectly set anchor bolts.
8.	 Submittals
8.1	 Approval Drawings
8.1.1	 Approval drawings are submitted upon request.
If approval drawings are requested, fabrication
will not start until one set of the approval drawings
has been signed by the buyer or his representative
as “Approved As Is” or “Approved As Noted” and
returned to Zamil Steel.
8.1.2	 Approval drawings are issued as “Not For
	 Construction” drawings; the contractor is
	 specifically instructed not to use dimensions
shown on approval drawings for his civil work,
	 foundation work, etc. Zamil Steel shall not be
	 responsible for any consequences arising from the
premature use of information provided in
	 drawings that are not issued for construction.
8.2	 Erection Drawings
8.2.1	 Erection Drawings, “Issued For Construction”,
are provided for the assembly of the building(s)
and consist of an anchor bolt setting plan, a frame
cross-section, a roof framing plan, walls framing
details and roof and wall sheeting details. Part
designations for all Bill of Materials (BOM)
	 components are shown on erection drawings.
8.2.2	 Bolt schedules identifying the required bolt
	 diameter and length for specific connections are
shown on erection drawings.
8.3	 Design Calculations
	 Structural calculations may be provided upon
	 request, duly certified by the Engineering
	 Manager.
8.4	 Design Certification
	 A letter of certification, in lieu of design
	 calculations, may be provided upon request, duly
certified by the Engineering Manager.
Statements, descriptions, specifications and dimensions
contained herein are in effect as of the date of this issue.
Zamil Steel reserves the right to make material substitutions,
enhencement and changes in specifications and construction
methodology as and when deemed necessary.
Standard Product Specifications								 		 Pre-Engineered Buildings
AREA OFFICES
Saudi Arabia (Dammam, Riyadh & Jeddah) Kuwait (Kuwait City) Bahrain (Manama) Qatar (Doha)
UAE (Dubai & Abu Dhabi) Oman (Muscat) Yemen (Sanaa) Jordan (Amman) Syria (Damascus) Iraq (Basra)
Bangladesh (Dhaka) Pakistan (Lahore) Sri Lanka (Colombo) India (Chennai & Bangalore) Greece (Athens)
Romania (Bucharest) Hungary (Budapest) Poland (Warsaw) Czech Rep. (Prague) Spain (Madrid) Luxembourg
Egypt (Cairo) Sudan (Khartoum) Libya (Tripoli) Algeria (Algiers) Senagal (Dakar) Ethiopia (Addis Ababa)
Tanzania (Dar-es-Salaam) Nigeria (Lagos) Vietnam (Ho Chi Minh City, Hanoi, Haiphong & Da Nang)
Thailand (Bangkok) Malaysia (Kuala Lumpur, Johor & Kota Kinabalu) Singapore Philippines (Manila)
Myanmar (Yangon, Mandalay & Pyinmana) Indonesia (Jakarta & Batam) Philippines (Manila) Laos (Vientiane)
Cambodia (Phnompenh) China (Shanghai, Qingdao & Dalian) Japan (Tokyo)
HEAD OFFICE
PO Box 877
Dammam 31421
Saudi Arabia
Phone (966 3) 847 1840
Fax (966 3) 847 1291
E-Mail pebmarketing@zamilsteel.com
www.zamilsteel.com January 2012

Contenu connexe

Tendances

Structural steel
Structural steelStructural steel
Structural steelvinod singh
 
Connections in steel structures
Connections in steel structuresConnections in steel structures
Connections in steel structuresRizwan Khurram
 
ANALYSIS AND DESIGN OF HIGH RISE BUILDING BY USING ETABS
ANALYSIS AND DESIGN OF HIGH RISE BUILDING BY USING ETABSANALYSIS AND DESIGN OF HIGH RISE BUILDING BY USING ETABS
ANALYSIS AND DESIGN OF HIGH RISE BUILDING BY USING ETABSila vamsi krishna
 
Structural Steel Welding Inspection
Structural Steel Welding InspectionStructural Steel Welding Inspection
Structural Steel Welding InspectionAsirul Hoq
 
Analysis, Design and Estimation of Basement +G+2 Residential Building
Analysis, Design and Estimation of Basement +G+2 Residential BuildingAnalysis, Design and Estimation of Basement +G+2 Residential Building
Analysis, Design and Estimation of Basement +G+2 Residential BuildingIRJET Journal
 
Raft foundations _design_and_analysis_with_a_practical_approach
Raft foundations _design_and_analysis_with_a_practical_approachRaft foundations _design_and_analysis_with_a_practical_approach
Raft foundations _design_and_analysis_with_a_practical_approachAlmotasem Darawish
 
P.e.b. mini project report
P.e.b. mini project reportP.e.b. mini project report
P.e.b. mini project reportShubham Parab
 
Chimney present
Chimney presentChimney present
Chimney presentmathusaran
 
DESIGN OF G+20 MULTISTOREY BUILDING
DESIGN OF G+20 MULTISTOREY BUILDINGDESIGN OF G+20 MULTISTOREY BUILDING
DESIGN OF G+20 MULTISTOREY BUILDINGAnjneya Srivastava
 
Analysis and design of commercial building
Analysis and design of commercial buildingAnalysis and design of commercial building
Analysis and design of commercial buildingSatrudhan11240
 
Designing for long spans 2
Designing for long spans 2Designing for long spans 2
Designing for long spans 2SADEQ ALSALAMI
 
Sp 34-1987 handbook on reinforcement and detailing
Sp 34-1987 handbook on reinforcement and detailingSp 34-1987 handbook on reinforcement and detailing
Sp 34-1987 handbook on reinforcement and detailingjemmabarsby
 
Chapter 7 DESIGN OF FOOTING
Chapter 7 DESIGN OF FOOTINGChapter 7 DESIGN OF FOOTING
Chapter 7 DESIGN OF FOOTINGKavitaSingh219
 
Steel members of the building
Steel members of the buildingSteel members of the building
Steel members of the buildingKsuhail156
 

Tendances (20)

Structural steel
Structural steelStructural steel
Structural steel
 
Peb
PebPeb
Peb
 
Connections in steel structures
Connections in steel structuresConnections in steel structures
Connections in steel structures
 
Steel structures
Steel structuresSteel structures
Steel structures
 
ANALYSIS AND DESIGN OF HIGH RISE BUILDING BY USING ETABS
ANALYSIS AND DESIGN OF HIGH RISE BUILDING BY USING ETABSANALYSIS AND DESIGN OF HIGH RISE BUILDING BY USING ETABS
ANALYSIS AND DESIGN OF HIGH RISE BUILDING BY USING ETABS
 
Structural Steel Welding Inspection
Structural Steel Welding InspectionStructural Steel Welding Inspection
Structural Steel Welding Inspection
 
Analysis, Design and Estimation of Basement +G+2 Residential Building
Analysis, Design and Estimation of Basement +G+2 Residential BuildingAnalysis, Design and Estimation of Basement +G+2 Residential Building
Analysis, Design and Estimation of Basement +G+2 Residential Building
 
Raft foundations _design_and_analysis_with_a_practical_approach
Raft foundations _design_and_analysis_with_a_practical_approachRaft foundations _design_and_analysis_with_a_practical_approach
Raft foundations _design_and_analysis_with_a_practical_approach
 
P.e.b. mini project report
P.e.b. mini project reportP.e.b. mini project report
P.e.b. mini project report
 
Chimney present
Chimney presentChimney present
Chimney present
 
DESIGN OF G+20 MULTISTOREY BUILDING
DESIGN OF G+20 MULTISTOREY BUILDINGDESIGN OF G+20 MULTISTOREY BUILDING
DESIGN OF G+20 MULTISTOREY BUILDING
 
Analysis and design of commercial building
Analysis and design of commercial buildingAnalysis and design of commercial building
Analysis and design of commercial building
 
Column design: as per bs code
Column design: as per bs codeColumn design: as per bs code
Column design: as per bs code
 
Designing for long spans 2
Designing for long spans 2Designing for long spans 2
Designing for long spans 2
 
Jacketing
JacketingJacketing
Jacketing
 
Steel code book
Steel code bookSteel code book
Steel code book
 
Sp 34-1987 handbook on reinforcement and detailing
Sp 34-1987 handbook on reinforcement and detailingSp 34-1987 handbook on reinforcement and detailing
Sp 34-1987 handbook on reinforcement and detailing
 
Bolted connections
Bolted connectionsBolted connections
Bolted connections
 
Chapter 7 DESIGN OF FOOTING
Chapter 7 DESIGN OF FOOTINGChapter 7 DESIGN OF FOOTING
Chapter 7 DESIGN OF FOOTING
 
Steel members of the building
Steel members of the buildingSteel members of the building
Steel members of the building
 

En vedette

Quality Assurance in PEB - Pre Engineered steel buildings
Quality Assurance in PEB - Pre Engineered steel buildingsQuality Assurance in PEB - Pre Engineered steel buildings
Quality Assurance in PEB - Pre Engineered steel buildingsmbphenix
 
Standard specifications
Standard specificationsStandard specifications
Standard specificationshlksd
 
Indira paryavaran bhawan and griha
Indira paryavaran bhawan and grihaIndira paryavaran bhawan and griha
Indira paryavaran bhawan and grihaAnchal Garg
 
Water for textile industry
Water for textile industryWater for textile industry
Water for textile industryAzmir Latif Beg
 
ERECTION METHOD STATEMENT
ERECTION METHOD STATEMENTERECTION METHOD STATEMENT
ERECTION METHOD STATEMENTmustafa hussain
 
10 warehouse management
10 warehouse management10 warehouse management
10 warehouse managementDEBAYAN GHOSH
 
WASTE WATER AND ITS TREATMENT IN TEXTILE INDUSTRY
WASTE WATER AND ITS TREATMENT IN TEXTILE INDUSTRYWASTE WATER AND ITS TREATMENT IN TEXTILE INDUSTRY
WASTE WATER AND ITS TREATMENT IN TEXTILE INDUSTRYVANDANA TRIPATHI NAUTIYAL
 
Warehousing layout-design-and-processes-setup
Warehousing layout-design-and-processes-setupWarehousing layout-design-and-processes-setup
Warehousing layout-design-and-processes-setupPuneet Mishra
 
Effluent Treatment Plant Design, Operation And Analysis Of Waste Water
Effluent Treatment Plant Design, Operation And Analysis Of Waste Water Effluent Treatment Plant Design, Operation And Analysis Of Waste Water
Effluent Treatment Plant Design, Operation And Analysis Of Waste Water Jaidev Singh
 

En vedette (13)

Quality Assurance in PEB - Pre Engineered steel buildings
Quality Assurance in PEB - Pre Engineered steel buildingsQuality Assurance in PEB - Pre Engineered steel buildings
Quality Assurance in PEB - Pre Engineered steel buildings
 
Standard specifications
Standard specificationsStandard specifications
Standard specifications
 
Peb
PebPeb
Peb
 
Indira paryavaran bhawan and griha
Indira paryavaran bhawan and grihaIndira paryavaran bhawan and griha
Indira paryavaran bhawan and griha
 
Water for textile industry
Water for textile industryWater for textile industry
Water for textile industry
 
ERECTION METHOD STATEMENT
ERECTION METHOD STATEMENTERECTION METHOD STATEMENT
ERECTION METHOD STATEMENT
 
02 water demand
02 water demand02 water demand
02 water demand
 
10 warehouse management
10 warehouse management10 warehouse management
10 warehouse management
 
Water requirements
Water requirementsWater requirements
Water requirements
 
WASTE WATER AND ITS TREATMENT IN TEXTILE INDUSTRY
WASTE WATER AND ITS TREATMENT IN TEXTILE INDUSTRYWASTE WATER AND ITS TREATMENT IN TEXTILE INDUSTRY
WASTE WATER AND ITS TREATMENT IN TEXTILE INDUSTRY
 
Warehousing layout-design-and-processes-setup
Warehousing layout-design-and-processes-setupWarehousing layout-design-and-processes-setup
Warehousing layout-design-and-processes-setup
 
Waste water from textile industry
Waste water from textile industryWaste water from textile industry
Waste water from textile industry
 
Effluent Treatment Plant Design, Operation And Analysis Of Waste Water
Effluent Treatment Plant Design, Operation And Analysis Of Waste Water Effluent Treatment Plant Design, Operation And Analysis Of Waste Water
Effluent Treatment Plant Design, Operation And Analysis Of Waste Water
 

Similaire à PEB - Standard Product Specifications

Primasteel Roofs - Everest Industries Limited
Primasteel Roofs - Everest Industries LimitedPrimasteel Roofs - Everest Industries Limited
Primasteel Roofs - Everest Industries LimitedVyas Jayesh K
 
New Life Steel Structures, Mumbai, Sheds and Steel Structures
 New Life Steel Structures, Mumbai, Sheds and Steel Structures New Life Steel Structures, Mumbai, Sheds and Steel Structures
New Life Steel Structures, Mumbai, Sheds and Steel StructuresIndiaMART InterMESH Limited
 
Pre - Engineered Metal Buildings - The Latest Trend In Building construction
Pre - Engineered Metal Buildings - The Latest Trend In Building constructionPre - Engineered Metal Buildings - The Latest Trend In Building construction
Pre - Engineered Metal Buildings - The Latest Trend In Building constructionmustafa hussain
 
Pre engineered metal buildings - the latest trend in building construction
Pre   engineered metal buildings - the latest trend in building constructionPre   engineered metal buildings - the latest trend in building construction
Pre engineered metal buildings - the latest trend in building constructionhlksd
 
Pre - Engineered Metal Buildings - The Latest Trend In Building construction
Pre - Engineered Metal Buildings - The Latest Trend In Building constructionPre - Engineered Metal Buildings - The Latest Trend In Building construction
Pre - Engineered Metal Buildings - The Latest Trend In Building constructionmustafa hussain
 
mild steel
 mild steel mild steel
mild steelAnu Dang
 
Steel shed manufacturer noida
Steel shed manufacturer noidaSteel shed manufacturer noida
Steel shed manufacturer noidaaccumechprefab
 
Portal frame 1
Portal  frame 1Portal  frame 1
Portal frame 1Est
 
Prefabrication & Pre-CASTING, Advanced Structural Concretes Materials for Pre...
Prefabrication & Pre-CASTING, Advanced Structural Concretes Materials for Pre...Prefabrication & Pre-CASTING, Advanced Structural Concretes Materials for Pre...
Prefabrication & Pre-CASTING, Advanced Structural Concretes Materials for Pre...Deepak Verma
 
Assignment 2 (techniqes construction of mass building)
Assignment  2 (techniqes construction of mass building)Assignment  2 (techniqes construction of mass building)
Assignment 2 (techniqes construction of mass building)rajitk97
 
Portal Frame Construction & Pre Engineered Building System
Portal Frame Construction & Pre Engineered Building SystemPortal Frame Construction & Pre Engineered Building System
Portal Frame Construction & Pre Engineered Building SystemIan Toisa
 
Pre enginnered buildings master-builder_july08, pp.48-62
Pre enginnered buildings master-builder_july08, pp.48-62Pre enginnered buildings master-builder_july08, pp.48-62
Pre enginnered buildings master-builder_july08, pp.48-62hlksd
 

Similaire à PEB - Standard Product Specifications (20)

Primasteel Roofs - Everest Industries Limited
Primasteel Roofs - Everest Industries LimitedPrimasteel Roofs - Everest Industries Limited
Primasteel Roofs - Everest Industries Limited
 
New Life Steel Structures, Mumbai, Sheds and Steel Structures
 New Life Steel Structures, Mumbai, Sheds and Steel Structures New Life Steel Structures, Mumbai, Sheds and Steel Structures
New Life Steel Structures, Mumbai, Sheds and Steel Structures
 
Cl newlifesteel
Cl newlifesteelCl newlifesteel
Cl newlifesteel
 
Pre - Engineered Metal Buildings - The Latest Trend In Building construction
Pre - Engineered Metal Buildings - The Latest Trend In Building constructionPre - Engineered Metal Buildings - The Latest Trend In Building construction
Pre - Engineered Metal Buildings - The Latest Trend In Building construction
 
Pre engineered metal buildings - the latest trend in building construction
Pre   engineered metal buildings - the latest trend in building constructionPre   engineered metal buildings - the latest trend in building construction
Pre engineered metal buildings - the latest trend in building construction
 
Pre - Engineered Metal Buildings - The Latest Trend In Building construction
Pre - Engineered Metal Buildings - The Latest Trend In Building constructionPre - Engineered Metal Buildings - The Latest Trend In Building construction
Pre - Engineered Metal Buildings - The Latest Trend In Building construction
 
Industrial buildings
Industrial buildingsIndustrial buildings
Industrial buildings
 
Company Profile - NEW
Company Profile - NEWCompany Profile - NEW
Company Profile - NEW
 
Company Profile
Company ProfileCompany Profile
Company Profile
 
mild steel
 mild steel mild steel
mild steel
 
FALSE CEILING
FALSE CEILINGFALSE CEILING
FALSE CEILING
 
Steel shed manufacturer noida
Steel shed manufacturer noidaSteel shed manufacturer noida
Steel shed manufacturer noida
 
Lintels and Beams
Lintels and BeamsLintels and Beams
Lintels and Beams
 
Portal frame 1
Portal  frame 1Portal  frame 1
Portal frame 1
 
Prefabrication & Pre-CASTING, Advanced Structural Concretes Materials for Pre...
Prefabrication & Pre-CASTING, Advanced Structural Concretes Materials for Pre...Prefabrication & Pre-CASTING, Advanced Structural Concretes Materials for Pre...
Prefabrication & Pre-CASTING, Advanced Structural Concretes Materials for Pre...
 
Assignment 2 (techniqes construction of mass building)
Assignment  2 (techniqes construction of mass building)Assignment  2 (techniqes construction of mass building)
Assignment 2 (techniqes construction of mass building)
 
Portal Frame Construction & Pre Engineered Building System
Portal Frame Construction & Pre Engineered Building SystemPortal Frame Construction & Pre Engineered Building System
Portal Frame Construction & Pre Engineered Building System
 
Roof truss
Roof trussRoof truss
Roof truss
 
Pre Bid Conference
Pre Bid ConferencePre Bid Conference
Pre Bid Conference
 
Pre enginnered buildings master-builder_july08, pp.48-62
Pre enginnered buildings master-builder_july08, pp.48-62Pre enginnered buildings master-builder_july08, pp.48-62
Pre enginnered buildings master-builder_july08, pp.48-62
 

Dernier

Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncr
Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / NcrCall Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncr
Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncrdollysharma2066
 
Innovation Conference 5th March 2024.pdf
Innovation Conference 5th March 2024.pdfInnovation Conference 5th March 2024.pdf
Innovation Conference 5th March 2024.pdfrichard876048
 
Investment in The Coconut Industry by Nancy Cheruiyot
Investment in The Coconut Industry by Nancy CheruiyotInvestment in The Coconut Industry by Nancy Cheruiyot
Investment in The Coconut Industry by Nancy Cheruiyotictsugar
 
Marketplace and Quality Assurance Presentation - Vincent Chirchir
Marketplace and Quality Assurance Presentation - Vincent ChirchirMarketplace and Quality Assurance Presentation - Vincent Chirchir
Marketplace and Quality Assurance Presentation - Vincent Chirchirictsugar
 
Buy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail AccountsBuy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail AccountsBuy Verified Accounts
 
Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Seta Wicaksana
 
Kenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby AfricaKenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby Africaictsugar
 
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckPitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckHajeJanKamps
 
Market Sizes Sample Report - 2024 Edition
Market Sizes Sample Report - 2024 EditionMarket Sizes Sample Report - 2024 Edition
Market Sizes Sample Report - 2024 EditionMintel Group
 
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCRashishs7044
 
Global Scenario On Sustainable and Resilient Coconut Industry by Dr. Jelfina...
Global Scenario On Sustainable  and Resilient Coconut Industry by Dr. Jelfina...Global Scenario On Sustainable  and Resilient Coconut Industry by Dr. Jelfina...
Global Scenario On Sustainable and Resilient Coconut Industry by Dr. Jelfina...ictsugar
 
FULL ENJOY Call girls in Paharganj Delhi | 8377087607
FULL ENJOY Call girls in Paharganj Delhi | 8377087607FULL ENJOY Call girls in Paharganj Delhi | 8377087607
FULL ENJOY Call girls in Paharganj Delhi | 8377087607dollysharma2066
 
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...ShrutiBose4
 
India Consumer 2024 Redacted Sample Report
India Consumer 2024 Redacted Sample ReportIndia Consumer 2024 Redacted Sample Report
India Consumer 2024 Redacted Sample ReportMintel Group
 
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607dollysharma2066
 
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCRashishs7044
 
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort ServiceCall US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Servicecallgirls2057
 

Dernier (20)

Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncr
Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / NcrCall Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncr
Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncr
 
No-1 Call Girls In Goa 93193 VIP 73153 Escort service In North Goa Panaji, Ca...
No-1 Call Girls In Goa 93193 VIP 73153 Escort service In North Goa Panaji, Ca...No-1 Call Girls In Goa 93193 VIP 73153 Escort service In North Goa Panaji, Ca...
No-1 Call Girls In Goa 93193 VIP 73153 Escort service In North Goa Panaji, Ca...
 
Japan IT Week 2024 Brochure by 47Billion (English)
Japan IT Week 2024 Brochure by 47Billion (English)Japan IT Week 2024 Brochure by 47Billion (English)
Japan IT Week 2024 Brochure by 47Billion (English)
 
Innovation Conference 5th March 2024.pdf
Innovation Conference 5th March 2024.pdfInnovation Conference 5th March 2024.pdf
Innovation Conference 5th March 2024.pdf
 
Investment in The Coconut Industry by Nancy Cheruiyot
Investment in The Coconut Industry by Nancy CheruiyotInvestment in The Coconut Industry by Nancy Cheruiyot
Investment in The Coconut Industry by Nancy Cheruiyot
 
Marketplace and Quality Assurance Presentation - Vincent Chirchir
Marketplace and Quality Assurance Presentation - Vincent ChirchirMarketplace and Quality Assurance Presentation - Vincent Chirchir
Marketplace and Quality Assurance Presentation - Vincent Chirchir
 
Buy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail AccountsBuy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail Accounts
 
Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...
 
Kenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby AfricaKenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby Africa
 
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckPitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
 
Market Sizes Sample Report - 2024 Edition
Market Sizes Sample Report - 2024 EditionMarket Sizes Sample Report - 2024 Edition
Market Sizes Sample Report - 2024 Edition
 
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
 
Global Scenario On Sustainable and Resilient Coconut Industry by Dr. Jelfina...
Global Scenario On Sustainable  and Resilient Coconut Industry by Dr. Jelfina...Global Scenario On Sustainable  and Resilient Coconut Industry by Dr. Jelfina...
Global Scenario On Sustainable and Resilient Coconut Industry by Dr. Jelfina...
 
FULL ENJOY Call girls in Paharganj Delhi | 8377087607
FULL ENJOY Call girls in Paharganj Delhi | 8377087607FULL ENJOY Call girls in Paharganj Delhi | 8377087607
FULL ENJOY Call girls in Paharganj Delhi | 8377087607
 
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...
 
Call Us ➥9319373153▻Call Girls In North Goa
Call Us ➥9319373153▻Call Girls In North GoaCall Us ➥9319373153▻Call Girls In North Goa
Call Us ➥9319373153▻Call Girls In North Goa
 
India Consumer 2024 Redacted Sample Report
India Consumer 2024 Redacted Sample ReportIndia Consumer 2024 Redacted Sample Report
India Consumer 2024 Redacted Sample Report
 
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
 
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR
 
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort ServiceCall US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
 

PEB - Standard Product Specifications

  • 1. Pre-Engineered Buildings Standard Product Specifications
  • 2. Standard Product Specifications Pre-Engineered Buildings Standard Product Specifications Index 1. General 1.1 Definition 1.2 Standard Structural Framing Systems 1.3 Standard Framing Features 1.4 Building Components 2. Design 2.1 Codes 2.2 Loads 3. Material Specifications 3.1 Structural Members 3.2 Panels 3.3 Trims & Gutters 3.4 Bolts 3.5 Fasteners 3.6 Other Items 4. Shop Paint 4.1 Structural Members 5. Building Accessories 5.1 Heavy Duty Personnel Doors 5.2 Steel Sliding Doors 5.3 Steel Roll Up Doors 5.4 Windows 5.5 Adjustable Steel Louvers 5.6 Gravity Ventilators 6. Structural Sub-Systems 6.1 Roof Extensions 6.2 Canopies 6.3 Fascias and Parapets 7. Foundations and Anchorage 8. Submittals 8.1 Approval Drawings 8.2 Erection Drawings 8.3 Design Calculations 8.4 Design Certification
  • 3. Pre-Engineered Buildings Standard Product Specifications 1. General 1.1 Definition 1.1.1 The building, as specified herein, consists of columns, rafters, bracing, connection clips, roof purlins, wall girters, roof and wall sheeting, anchor bolts, flashing, trims, etc., or as specified. All materials shall be new and free from defects. 1.1.2 The main building structure comprises single or multiple gable interior rigid frames with either rigid or “post-and-beam” frames at the endwalls. 1.1.3 The standard roof slopes are 0.5 or 1.0 unit of vertical rise to 10 units of horizontal run. Other slopes are available upon request. 1.1.4 The sidewall steel line is the plane of the inside vertical surface of the sidewall sheeting. It is also the plane of the outside vertical surface of the eave strut. 1.1.5 The endwall steel line is the plane of the inside vertical surface of the endwall sheeting. It is also the plane of the outside vertical surface of the outer flange of the endwall girters. 1.1.6 The building width is the distance between the steel lines of opposite sidewalls. Building width does not include the width of Lean-To buildings or roof extensions. The width of a Lean-To building is the distance from the steel line of the exterior sidewalls of the Lean-To building to the (sidewalls or endwalls) steel line of the main building to which the Lean-To building is attached. 1.1.7 The building length is the distance between the steel lines of opposite endwalls. Building length is a combination of several bay lengths. Building length does not include the width of endwall Lean-To buildings or roof extensions. 1.1.8 End bay length is the distance from the outside of the outer flange of endwall columns to the center line of the first interior frame. 1.1.9 Interior bay length is the distance between the center lines of two adjacent interior rigid frame columns. 1.1.10 The building eave height is the distance from finished floor level (FFL) to the top of the eave strut at the sidewalls steel line. 1.1.11 The building clear height is the distance from finished floor level (FFL) to the bottom of the end plate of the rafter at the knee. 1.2 Standard Structural Framing Systems 1.2.1 Clear Span (CS) buildings have a gable roof with vertical sidewalls and endwalls. Interior bay frames are clear span rigid frames without interior columns. 1.2.2 Multi-Span (MS) buildings have a gable roof with vertical sidewalls and endwalls. Interior bay frames are rigid frames, typically with tapered exterior columns, tapered rafters and square tube or built-up interior columns. 1.2.3 Space Saver (SV) buildings have a gable roof with vertical sidewalls and endwalls. Interior bay frames are clear span rigid frames having constant depth columns and tapered rafters typically with horizontal bottom flanges. 1.2.4 Lean-To (LT) buildings consist of outer sidewall columns and simple span rafters attached to the sidewall columns or the endwall posts of the main building. Lean-To columns are of constant depth. Lean-To rafters may be tapered or of constant depth. 1.2.5 Multi-Gable (MG) buildings have a roof with two or more gables and vertical sidewalls and endwalls. Interior bay frames are rigid frames typically having tapered exterior columns, tapered rafters and built-up interior columns. 1.3 Standard Framing Features 1.3.1 Main frames are typically constructed from tapered or constant depth columns and rafters. 1.3.2 Rigid frames for Clear Span (CS) and Multi-Span (MS) buildings are most commonly spaced from 6000 mm to 10000 mm, center line to center line. 1.3.3 Outside flanges of Clear Span (CS) and Multi-Span (MS) rigid frame columns are inset 200 mm from the sidewall steel line to allow for by-pass girts. 1.3.4 Outside flanges of Space Saver (SV) rigid frame columns shall be placed flush with the sidewalls steel line. 1.3.5 The top flanges of all rigid frame rafters are 200 mm below the bottom of the roof sheeting. 1.3.6 End frames are “post-and-beam” (P&B) load 1
  • 4. Standard Product Specifications Pre-Engineered Buildings bearing frames with endwall girts flush framed into the webs of the endwall posts so that the outer flanges of the girts are in the same vertical plane as the outer flanges of the posts. Optional rigid frames may be used at the building ends. The center line of the endwalls rigid frame shall be 385 mm from the endwalls steel line. 1.3.7 Endwall posts are typically spaced at 6000 mm. Depending on the width of the building and endwall openings, other spacing may also be used. When the building width is not evenly divisible by 6000 mm, the interior spacing of the endwall posts is typically kept at 6000 mm with two equal end spacings smaller or larger than 6000 mm. 1.3.8 For Clear Span (CS) and Multi-Span (MS) buildings, the sidewall girts are attached (by-passed) to the outer flanges of exterior columns. Sidewall girts are lapped at all interior frames. For Space Saver (SV) and Lean-To (LT) buildings, the sidewall girts are flush connected (flush framed) so that the outer flange of the girters is in the same vertical plane as the outer flange of the exterior columns. 1.3.9 The bottom flanges of roof purlins are attached to the outer (top) flanges of the rafters. Purlins are lapped at all interior frames in all structural framing systems. 1.4 Building Components 1.4.1 Columns and rafters of rigid frames are tapered built-up “I” sections. Interior columns of multi-span frames may be square tube sections. 1.4.2 All rigid frame connections are bolted. Columns and rafters are provided with welded end plates for anchoring to foundations and for member-to- member attachment. Pre-punched holes or welded clips are provided for attachment of purlins and girters, bracing, and other components. 1.4.3 Load bearing “post-and-beam” (P&B) end frames may be constructed from cold-formed channels, hot rolled sections or built-up welded plate sections, as required. 1.4.4 Purlins and girts are pre-punched cold-formed “Z” shaped sections, 200 mm in depth with stiffened flanges. 1.4.5 Eave struts are pre-punched cold-formed “C” shaped sections, 180 mm in depth with 85 mm stiffened flanges. The eave strut serves as a longitudinal structural bracing member in addition to acting as a transition point for walls and roof sheeting. 1.4.6 Panels (roof and walls) are roll formed to the maximum practical length (generally 9000 mm) to minimize end laps in the field. 1.4.7 The standard roof and walls panel is Profile “S”. It is a roll formed panel having 4 major high ribs and 4 minor ribs. The panel covers a width of 1000 mm. The lapped major rib has a siphon break to prevent capillaric intrusion of water at the side lap. The panel has an extended bearing leg to provide stiffening during installation. 1.4.8 Roof panels have a minimum end lap of 150 mm over purlins and are fully protected from siphon action by an end lap mastic. 1.4.9 Wall panels have the same side lapping as the roof panels. End lap is 100 mm over the girts. Generally no side or end lap mastic is required. 1.4.10 Sandwich panels are factory-injected insulated panels. They are constructed of a hard polyurethane foam core between two single skin panels. The rigid foam core has a density of approximately 40 kg/m3 . The standard roof sandwich panel is the Tempcon (TC) panel. The outer panel is the standard Profile “S” panel, described in section 1.4.7. The inner panel is a flat panel. The standard wall sandwich panel is the Tem- parch (TA) panel. Both the outer and inner panels are flat panels. All sandwich panels cover a width of 1000 mm. 1.4.11 Profiled ridge panels are provided at the ridge of all buildings with single skin roof panels. 1.4.12 Eave gutters are supplied in lengths of 6000 mm. They are cold-formed to a profiled cross-section that is about 180 mm wide x 168 mm high. 1.4.13 Downspouts for eave gutters are supplied in lengths of up to 9000 mm to minimize splicing. They are cold-formed to a ribbed rectangular cross section 105 mm wide x 73 mm deep. 1.4.14 Valley gutters are supplied in maximum lengths of 4500 mm. They are cold-formed in two standard size classifications; 400 mm wide x 190 mm high and 354 mm wide x 190 mm high. 1.4.15 Downspouts for valley gutters in Multi-Gable (MG) buildings are PVC pipes supplied in three sizes; 110 mm, 160 mm and 200 mm (outside diameter). Fiberglass or PVC outlets connecting the valley gutter to the downspouts are also supplied. 2
  • 5. Pre-Engineered Buildings Standard Product Specifications 1.4.16 Diagonal bracing, providing longitudinal stability against wind, seismic or other forces, is attached to the web of the rigid frame near the outer flange of columns and rafters. The standard diagonal bracing is a galvanized steel 7-wire strand cable with an eye bolt with an adjusting nut and hillside washer at each end. Solid round bars or hot rolled angles may be used as required by design. 1.4.17 Flange braces, in the form of angles, are provided to stabilize the interior flanges of rigid frame rafters and columns at certain purlin and girter locations. 1.4.18 Base angles are provided in fully sheeted walls 6000 mm in length for attachment of the wall panel to the concrete slab. The concrete floor slab must have a 40 mm x 40 mm notch at the perimeter (below the finished floor level) to accommodate the bottom of the wall panel to prevent ingress of dust and water. The base angle is a light gauge bent plate. 2. Design 2.1 Codes 2.1.1 Frame members (hot rolled or built-up) are designed in accordance with the American Institute of Steel Construction (AISC): “Manual of Steel Construction, Allowable Stress Design.” 2.1.2 Cold-formed members are designed in accordance with the American Iron and Steel Institute (AISI): “Cold-formed Steel Design Manual.” 2.1.3 All welds are designed in accordance with the American Welding Society (AWS): “Structural Welding Code - Steel”. 2.1.4 Loads are applied in accordance with the requirements of the Metal Building Manufacturers Association (MBMA) of the USA: “Low Rise Building Systems Manual”. 2.1.5 Other codes can be accommodated if specified. 2.2 Loads 2.2.1 The building is designed to withstand the dead load (DL) of the structure plus a specified live load (LL) and wind load (WL). 2.2.2 Auxiliary (Collateral) loads, if any, must be specified by the customer at the time of request for quotation. 2.2.3 When snow load is of concern, the customer will specify the snow load where applicable, in accordance with local codes. 2.2.4 Load combinations shall be in accordance with the requirements of the “Low Rise Building Systems Manual” published by MBMA. 2.2.5 Other loads and load combinations can be accommodated and must be specified at the time of request for quotation. 2.2.6 Zamil Steel will not be responsible for any static or dynamic loads that are transferred to its building from the plant machinery and equipment, unless the loads are specifically requested at the time of request for quotation. 3. Material Specifications 3.1 Structural Members 3.1.1 Built-up sections are fabricated from hot rolled steel plates conforming to ASTM A 572M Grade 345 Type 1 (or equivalent), with a minimum yield strength of 34.5 kN/cm2 (50 ksi). Flanges are welded to the web by a continuous single side fillet weld deposited by an automatic submerged arc welding process. 3.1.2 Hot rolled sections are mill produced according to EN 10025-2 Grade S355JR (or equivalent) with a minimum yield strength of 34.5 kN/cm2 (50 ksi). 3.1.3 Tube sections, (used as interior columns in some Multi-Span buildings) are mill formed steel sections conforming to EN 10210-1 S355J2H or JIS 3466 STKR 490 (or equivalent), with a minimum yield strength of 32.5 kN/cm2 (47 ksi). 3.1.4 Secondary members (comprised mostly of purlins & girts) are cold-formed from hot rolled steel coils ranging in thickness from 1.5 mm to 3.0 mm for “Z” shapes, and in 2.0 mm and 2.5 mm for “C” shapes (lipped channels). 3.1.4.1 Painted secondary members are cold-formed from hot rolled steel coils conforming to ASTM A 607 Grade 50 or ASTM A 1011M HSLAS Grade 340 Class 1 Type 1 (or equivalent) having a minimum yield strength of 34.0 kN/cm2 ; and then factory painted with Zamil Steel standard primer. 3.1.4.2 Galvanized secondary members are cold-formed from steel coils conforming to ASTM A 653M Grade 3
  • 6. Standard Product Specifications Pre-Engineered Buildings SS 340 Class 1 (or equivalent), with zinc coating to Z275 (G 90) designation (275 g/m2 ), having a minimum yield strength of 34.0 kN/cm2 (50 ksi). 3.1.5 Bracing cables are 12 mm diameter, zinc coated 7-wire strand steel cables of extra high strength. The strand wires conform to ASTM A 475 (or equivalent) with a minimum breaking load of 119.7 kN. 3.1.6 Bracing rods, used in sidewalls of buildings supporting cranes, are solid plain round steel bars conforming to ASTM A 36M (or equivalent) with a minimum tensile strength of 40 kN/cm2 (58 ksi). 3.1.7 Sagrods,usedtobracepurlinsandgirtsinbayslon- ger than 8500 mm or in buildings with slopes larger than 2.5 to 10, are 12 mm or 16 mm solid threaded, round steel bars conforming to ASTM A 36M (or equivalent) with a minimum tensile strength of 40 kN/ cm2 (58 ksi). 3.1.8 Flange braces used to stabilize the inner flanges of main frame columns and rafters are 50 mm x 50 mm x 4 mm steel angles conforming to ASTM A 36M (or equivalent) with a minimum yield strength of 25 kN/cm2 (36 ksi). 3.1.9 Base / gable angles are 45 mm x 73 mm x 1.5 mm thick angles supplied in 6000 mm long pieces, cold-formed from galvanized steel and conforming to ASTM A 653M SS Grade 340 Class 1 (or equivalent), with zinc coating to Z275 (G90) designation (275 g/ m2 ) having a minimum yield strength of 34.0 kN/ cm2 (50 ksi). 3.2 Panels 3.2.1 Roof Panels are roll formed from 0.5 mm (nominal) thick cold-rolled steel coated with an aluminum / zinc alloy (Zincalume). The material conforms to ASTM A 792M Grade 340 Class 2, with alloy (Alumi- num / Zinc) coating AZM150 (or equivalent), having a minimum yield strength of 34 kN/cm2 (50 ksi). The coating is achieved through a hot dip process, which is 55% aluminum and the balance zinc, by weight. Pre-painted roof panels are optional. 3.2.2 Wall Panels have the same specifications as the roof panels (as described in section 3.2.1 above), but they aremillpainted. Paintfinishfilmthickness shall be 25 microns of high durability polyester (ZSP) on the exterior (weather) face and 12 microns of plain polyester on the interior face. 3.2.3 Interior liner panels have the same specifications as the wall panels (as described in section 3.2.2 above). 3.2.4 Standard colors for pre-painted wall panels are those standard colors mentioned in Zamil Steel’s product brochure and panel chart. 3.2.5 Mezzanine deck panels are roll-formed from 0.7 mm thick cold-rolled galvanized steel. The material conforms to ASTM A 653M SS Grade 550, zinc coatingZ180(G60),andhasaminimumyieldstrength of 55.0 kN/cm2 (80 ksi). 3.2.6 Roof and walls panel upgrades. Other premium durability paint finishes are avail- able upon request, such as Polyvinylidene Fluoride finish (ZPF) Roof and wall panels may be upgraded to 0.7 mm (nominal) thickness as follows: 3.2.7 Sandwich panels are available in two types: (a) Tempcon Panels: Tempcon sandwich panels are produced using rigid polyurethane foam core with external and internal sheets in steel or aluminum of varying thickness, coatings and colors. Tempcon is a durable sand wich panel, particularly in industrial build ings and are suitable for roof and wall for all building applications. (b) Temparch Panel: Temparch sandwich panels are produced using rigid polyurethane foam core with external and internal sheets in steel or aluminum of varying thickness, and are suitable for walls for all building applications, interior partition and cold stores. All the outer skins of Tempcon and Temparch pan- els are Zincalume coated steel conforming to ASTM A 792M Grade 340 Class 2, with zinc alloy coating AZM150 and are available in all Zamil Steel stan- dard colors. All the inner skins of Tempcon and Temparch pan- els are Zincalume coated steel conforming to ASTM A 792M Grade 340 Class 2, with zinc alloy coating 4 Thickness (mm) 0.7 Base Metal Paint Finish Steel Aluminum Bare Zincalume ZSP ZPF Plain ZSP
  • 7. Pre-Engineered Buildings Standard Product Specifications AZM150, and are available in Frost White color. Tempcon and Temparch skins may be upgraded as per section 3.2.6. 3.3 Trims & Gutters 3.3.1 Walls flashing and trims (gable, corner, framed opening, accessories, etc.) are cold-formed from the same material (color & finish) as wall panels. 3.3.2 Roof flashing and trims (parapet flashing, transition trims, expansion joint trims and ridge caps) are cold-formed from the same material (color & finish) as roof panels. 3.3.3 Eave gutters and downspouts are cold-formed from the same material as wall panels. 3.3.4 Valley gutters (used in parapet fascias and valley conditions) are cold-formed from a 1.0 mm (minimum) thick (nominal) bare Zincalume coated cold-rolled steel coil, conforming to ASTM A 792M Grade 340 Class 2, with zinc alloy coating AZM150 or bare Galvanized/Zinc coated cold rolled steel coil con- forming to ASTM A 653M SS Grade 340 Class 1, with Z275 coating (or equivalent) having a minimum yield strength of 34.0 kN/cm2 (50 ksi). A protective zinc phosphate pigmented epoxy coating system is applied to the exposed surface, having a total average dry film thickness of 150 microns on the exterior side and 50 microns on the interior side. 3.4 Bolts 3.4.1 High strength bolts are hot-dip galvanized and conform to ASTM A 325M (full thread), Type 1 (or equivalent). They are used to connect primary members. 3.4.2 Machine bolts are electro-galvanized with a yellow chromate color conversion coating and conform to DIN 933 Class 4.6 (or equivalent). They are used to connect secondary members (mainly purlins and girts). 3.4.3 Anchor bolts are manufactured from rods conforming to ASTM F1554 grade 55 or ISO 898-1 Class 5.8 (or equivalent) with a minimum yield strength of 38.0 kN/cm2 and an ultimate strength of 51.7 - 65.5 kN/cm2 . 3.5 Fasteners 3.5.1 Roof fasteners are metallic-polyester coated, heat treated carbon steel, conforming to AS 3566 Class 3 (or equivalent). They are 5.5 mm diameter, hex-head, self-drilling screws, assembled with galvanized steel washers bonded with EPDM seals. 3.5.2 Wall fasteners are metallic-polyester coated, heat-treated carbon steel, conforming to AS 3566 Class 3 (or equivalent). They are 5.5 mm diameter, hex-head, self-drilling screws with integral washers bonded with EPDM seals. The heads of wall fasteners are painted to match the color of the wall panels (as per section 3.2.4). 3.5.3 Sandwich panel fasteners same as 3.5.2. 3.5.4 Stitch fasteners for the roof are metallic-polyester coated, heat-treated carbon steel, conforming to AS 3566 Class 3 (or equivalent). They are 4.8 mm diameter, hex-head, self-drilling screws, assembled with galvanized steel washers bonded with EPDM seals. They are used on the side laps of roof panels, and in trim-to-trim and trim-to- panel fixing applications. 3.5.5 Stitch fasteners for the walls are metallic-polyester coated, heat-treated carbon steel, conforming to AS 3566 Class 3 (or equivalent). They are 4.8 mm diameter, hex-head, self-drilling screws with hex-head integral washers bonded with EPDM seals. The heads of stitch fasteners for the walls are painted to match the color of the wall panels (per section 3.2.4). They are used on the side laps of panels, and in trim-to-trim and trim-to-panel fixing applications. 3.5.6 Mezzanine deck fasteners are 5.5 mm diameter, metallic-polyester coated, heat-treated carbon steel, self-drilling screws, with hex head, capable of drilling through steel up to 12 mm thick. They conform to AS 3566 Class 3 (or equivalent). 3.5.7 Rivets are 4.0 mm diameter and made from Aluminum. They are used in gutter splicing, fixing trim-to-trim, or trim-to-panel, and fastening accessories to roof or wall claddings. They are available in all standard colors. 3.5.8 Stainless steel fasteners, for Aluminum panels, are 5.5 mm diameter, hex-head, self-drilling, stainless steel screws, assembled with stainless steel washers bonded with EPDM seals. Material grade is AISI 304 (or equivalent). 3.6 Other Items 3.6.1 Skylights and wall lights are made of translucent white acrylic modified, ultra violet stabilized, fiberglass with a tensile strength of 8.7 kN/cm2 (using ASTM D 638 test method) with a flexural 5
  • 8. Standard Product Specifications Pre-Engineered Buildings6 strength of 13.83 kN/cm2 (using ASTM D 790 test method). Translucent panels weigh 2.4 kg/m2 (nominal) and provide the same coverage as the panel width with a maximum length of 3600 mm. The profile of the translucent panels matches that of the adjoining roof/wall panels so that weather tightness is achieved through the same lapping technique used for the panels themselves. The translucent panels meet the light transmission value of 75% (+5%) according to ASTM D 1494. 3.6.2 Fall Shield (Skylight Fall Protection) is a fall pro- tection system to safeguard people from tripping, stepping and falling accidentally through skylights on the roof. It is fabricated from hot-dip galvanized wiremesh and rigidly supported by hat sections and clips which are fixed directly on top of the pan- el-purlin area on the roof with covering size/dimen- sion conforming to the surface area of the skylight panel. 3.6.3 Foam closures match the panel profile. They are made of expanded polyethylene or similar material. 3.6.4 Bead mastic is an extruded elastomeric butyl rubber based sealant supplied in rolls on silicon release paper conforming to Federal Specification TT-C-1796 A Type II Class B (or equivalent). 3.6.5 Flowable mastic (caulking sealant) is a neutral cure silicone rubber sealant that is chemically inert and non-corrosive. It is UV resistant and suitable for exterior applications against weathering and rainwater. When cured, it is non-toxic and will accommodate high thermal and shrinkage changes in structural movement joints. 3.6.6 Fiberglass insulation meets UL 25/50 fire rating and is supplied in 50 mm, 75 mm, 100 mm and 150 mm thicknesses with a factory laminated Rein- forced White Metalized film Scrim Kraft (WMSK) or Foil Reinforced Kraft (FRK) faced vapor barrier. The fiberglass density is 10 kgm3 . Other facings, densities and thicknesses are available upon request. Fiberglass insulation is supplied with double face tape, patching tape, stapler and staples. 4. Shop Paint 4.1 Structural Members 4.1.1 Primary and secondary steel is cleaned and prime painted according to the Steel Structures Painting Council SSPC-PS Guide 7.00 specification to a dry film thickness of not less than 40 microns. 4.1.2 Primer paint conforms to the performance requirements of Steel Structures Painting Council SSPC Paint 15 Type 1. 4.1.3 Shop primer is intended to provide temporary protection against weathering during transport and erection. It is not intended to provide permanent corrosion protection, especially in the case of exposed steel. 4.1.4 When special paint supplier is specified by the consultant / client, and paint is found to have application problems and (or) extended drying times, Zamil Steel will recommend to substitute it with an equivalent and suitable supplier, subject to final approval by the consultant / client. 5. Building Accessories 5.1 Personnel Doors 5.1.1 Personnel doors are flush-finished and 44 mm thick. Single leaf doors are 915 mm wide x 2135 mm high. Double leaf doors are 1830 mm wide x 2135 mm high. 5.1.2 Door leaves are reinforced, stiffened and soundproofed with an expanded polystyrene core, laminated to the inside faces of door panels, completely filling the inside cavity of the door leaf. 5.1.3 Steel door panels are 0.9 mm (nominal) thick, hot dip galvanized, 180 g/m2 , as per ASTM A 653M (Z180) cold-rolled steel, thoroughly cleaned, phosphated and painted with a white finish to ensure optimal corrosion protection. 5.1.4 A white or galvanized finished “Z” shaped astragal is field attached to the inactive leaf of all double doors. 5.1.5 Doors are factory prepared for a cylindrical lockset. 5.1.6 Door frames are 1.5 mm (nominal) thick hot-dip galvanized steel, prepared to ASTM A 653M (Z180) classification (or equivalent), thoroughly cleaned, phosphated and painted with a modified alkyd primer, plus a white finish coat. 5.1.7 Door frames are delivered knocked-down. Mitered corners have brackets with pre-drilled holes for field assembly and are supplied with all fasteners necessary for assembly. 5.1.8 The lockset is a keyed cylindrical type with satin chrome finish. Optional panic devices and auto
  • 9. Pre-Engineered Buildings Standard Product Specifications 7 closer are available. 5.1.9 Each door leaf has three mortise 115 mm x 115 mm ball bearing hinges with a security set screw in the barrel to prevent removal of the hinge pin with the door in a closed position. 5.2 Steel Sliding Doors 5.2.1 The frames of horizontal steel sliding doors are manufactured from 2 mm (nominal) thick, cold formed channels and girts and are delivered knocked-down for field assembly. All clips, fasteners, etc., necessary for assembly are provided. 5.2.2 The exterior face of the door leaf is sheeted with 0.5 mm (nominal) thick, pre-painted profiled panels. The panel ribs run vertically. The door panel profile matches the profile and material of the wall panels. 5.2.3 Door leaves are either suspended from an exterior mounted trolley rail attached to a structural header beam or bottom, supported by rollers on a fixed track anchored on the ground. The door hood trim, de- signed to conceal and protect the header and rail, is supplied with same material as the wall pan- els. 5.2.4 Doors are bottom or top guided by a specially designed steel rail track. 5.2.5 Door widths range from 1500 mm to 3000 mm, for single sliding doors, and from 3000 mm to 6000 mm, for double sliding doors. The height of the sliding doors range from 3000 mm to 6000 mm. 5.2.6 Sliding doors may also be provided with flush-hinged pilot doors. A pilot door is a personnel door within a leaf of the sliding door. 5.3 Steel Roll Up Doors 5.3.1 Roll-up door sizes conform to the following table: Width (mm) Length (mm) 3000 3000 3000 4000 4000 4000 4000 5000 5000 5000 5.3.2 The door curtain is cold-formed from hot-dip galvanized steel and painted with a polyester paint in Frost White color. The bottom rail of the door curtain is an extruded Aluminum angle. 5.3.3 Guides are 95 mm deep channels roll formed from 2.5 mm (nominal) thick hot-dip galvanized steel. 5.3.4 The door drum (supporting the door curtain) is a 165 mm (nominal) diameter and 3.2 mm (nominal) thick pipe. The drum houses safety springs, end shafts, collars and bearings and conforms to Australian Standard AS 1905 for safety. 5.3.5 Doors are supplied complete with guides, axle, curtain and a manual chain and reduction gear operating mechanism. Electric operators are available as an option. 5.4 Sectional Doors 5.4.1 Sectional doors are available in normal/regular sizes of 5000 mm Width x 5000 mm Height and be- low. (Other and bigger door sizes can also be made upon request.) Width (mm) Height (mm) 3000 3000 3000 4000 4000 4000 4000 5000 5000 5000 5.4.2 The sectional door’s panel or leaf is composed of 42 mm thick, double-skin and hot-dip galvanized steel section, insulated with polyurethane core and painted with primer-polyester coating. 5.4.3 Track (or Door Guide) use 52 mm rail width/depth for door sizes of 5000 mm Width x 5000 mm Height and below. (For bigger door sizes, 91 mm rail width/ depth is used.) 5.4.4 Sectional doors can be manually operated or elec- trically operated using industrial duty motor with manual override/operation in case power is off. 5.4.5 Sectional doors can be supplied with optional ac- cessories such as Ventilation Grills, Glazing and Wicket Doors. 5.5 Windows Window frames are made of anodized Aluminum extrusions with natural color finish conforming to ASTM B 221M Alloy 6063-T5 tempered aluminum alloy (or equivalent). Windows are horizontal
  • 10. Standard Product Specifications Pre-Engineered Buildings8 double slide type, 1000 mm high and 1000 mm wide, specifically designed for installation in profiled exteriorwallpanels. Windowsarefactory glazed with minimum 6 mm thick clear glass and are equipped with latches and a removable insect screen. 5.6 Adjustable / Fixed Steel Louvers Adjustable steel louvers are 1000 mm wide x 1000 mm high. They are supplied complete with a galvanized steel mesh, blades and framing. They are made from the same material, finish and color as wall panels. Fixed steel louvers are available in 1000 mm wide x 1000 mm high, 1000 mm wide x 1500 mm high and 1500 mm wide x 1000 mm high. 5.7 Gravity Ventilators Gravity flow ridge ventilators are 3000 mm long with a throat opening of 300 mm or 600 mm. They are installed as either individual units or as continuous (i.e. joined) units. The outer skin of the ventilators is pre-painted Zincalume steel that matches the color of roof panels. The ventilators are supplied complete with bird screens. A damp- er system to close the throat opening is optional on 300 mm throat ventilators. For export shipments, ventilators are shipped knocked-down to be field assembled by the erector before installation. 6. Structural Sub-systems 6.1 Roof Extensions 6.1.1 Sidewall roof extensions extend beyond the defined building width and are generally a continuation of the main building roof slope. 6.1.2 End wall roof extensions extend beyond the defined building length and are constructed by extending the end bay purlins and eave struts of the main building past the endwall rafters. 6.1.3 Standard widths for roof extensions range from 900 mm to 1500 mm. Wider roof extensions can be used but may require heavier or additional framing. 6.1.4 Soffit panels for roof extensions are optional. 6.1.5 Main building eave gutters are normally relocated to the edge of the roof extensions. Gutter drainage is achieved by downspouts located at the building sidewalls. 6.2 Canopies 6.2.1 Sidewall canopies are cantilevered rafters attached to the sidewall columns at any point below the eave and support 200 mm deep by-pass “Z” purlins supporting the canopy roof panels. 6.2.2 End wall canopies are cantilevered rafters along a uniform elevation attached to the end wall posts below the roof line and support by-passed 200 mm deep “Z” purlins supporting the canopy roof panels. 6.2.3 Optional canopy soffits conceal only the canopy purlins, leaving rafters exposed, unless otherwise specified. 6.2.4 Unless otherwise specified, the roof panels of the canopies shall match the color and profile of the main building roof panels. 6.2.5 The width of a canopy depends on the size of the sidewall columns or end wall posts supporting it. Practical widths range from 1500 mm to 3000 mm. Wider canopies are possible but require heavier sidewall columns or end wall posts. 6.2.6 The length of a canopy is ideally a multiple of bay lengths of the sidewalls or a multiple of column spacings of the end walls. 6.3 Fascias and Parapets 6.3.1 Vertical fascias consist of 200 mm deep vertical posts supported by brackets from sidewall columns or endwall posts. Cold-formed 200 mm deep “C” section top and bottom girts are flush-framed to the vertical fascia posts. An intermediate “C” girt positioned vertically is supplied to support a valley gutter, when required. Standard vertical fascias project 600 mm from the building sidewall or end wall steel lines. Projections exceeding 600 mm are possible but may require heavier sidewall columns and end wall posts. The height of the fascia varies depending on actual requirements. Typical heights range between 1000 mm to 1600 mm. Fasciasheetingissuppliedin0.5mm(nominal)thick, pre-painted panels matching the sidewalls profile. Soffit panels and back-up panels are provided only when specified. 6.3.2 Curveline fascias are of the same type of construction as vertical fascias but are sheeted with
  • 11. Pre-Engineered Buildings Standard Product Specifications 9 curved profiled panels and are available in three types: Bottom curved fascias that have a curved panel at the bottom of the fascia only. Top and bottom curved fascias that have a curved panel at the top and bottom of the fascia. Center curved fascias that haave a single panel curved at the mid height of the fascia. 6.3.3 A parapet fascia is an extension of the sidewalls and endwalls above the roof line. The wall sheeting of the building will continue to the top of the parapet. 6.3.4 Standard eave gutters and downspouts are used in buildings with sidewall vertical fascias. Valley gutters are used in buildings having sidewall parapet fascias. 7. Foundation and Anchorage 7.1.1 Foundations, tie beams and concrete floor slabs should be designed by a licensed engineer. Zamil Steel does not provide this service. 7.1.2 The design should be based on the building column specifications stated on “Issued For Construction” anchor bolt setting Plans. 7.1.3 Anchor bolts must be set in strict accordance with Zamil Steel anchor bolt setting plans. Zamil Steel is not be responsible for incorrectly set anchor bolts. 8. Submittals 8.1 Approval Drawings 8.1.1 Approval drawings are submitted upon request. If approval drawings are requested, fabrication will not start until one set of the approval drawings has been signed by the buyer or his representative as “Approved As Is” or “Approved As Noted” and returned to Zamil Steel. 8.1.2 Approval drawings are issued as “Not For Construction” drawings; the contractor is specifically instructed not to use dimensions shown on approval drawings for his civil work, foundation work, etc. Zamil Steel shall not be responsible for any consequences arising from the premature use of information provided in drawings that are not issued for construction. 8.2 Erection Drawings 8.2.1 Erection Drawings, “Issued For Construction”, are provided for the assembly of the building(s) and consist of an anchor bolt setting plan, a frame cross-section, a roof framing plan, walls framing details and roof and wall sheeting details. Part designations for all Bill of Materials (BOM) components are shown on erection drawings. 8.2.2 Bolt schedules identifying the required bolt diameter and length for specific connections are shown on erection drawings. 8.3 Design Calculations Structural calculations may be provided upon request, duly certified by the Engineering Manager. 8.4 Design Certification A letter of certification, in lieu of design calculations, may be provided upon request, duly certified by the Engineering Manager. Statements, descriptions, specifications and dimensions contained herein are in effect as of the date of this issue. Zamil Steel reserves the right to make material substitutions, enhencement and changes in specifications and construction methodology as and when deemed necessary.
  • 12. Standard Product Specifications Pre-Engineered Buildings AREA OFFICES Saudi Arabia (Dammam, Riyadh & Jeddah) Kuwait (Kuwait City) Bahrain (Manama) Qatar (Doha) UAE (Dubai & Abu Dhabi) Oman (Muscat) Yemen (Sanaa) Jordan (Amman) Syria (Damascus) Iraq (Basra) Bangladesh (Dhaka) Pakistan (Lahore) Sri Lanka (Colombo) India (Chennai & Bangalore) Greece (Athens) Romania (Bucharest) Hungary (Budapest) Poland (Warsaw) Czech Rep. (Prague) Spain (Madrid) Luxembourg Egypt (Cairo) Sudan (Khartoum) Libya (Tripoli) Algeria (Algiers) Senagal (Dakar) Ethiopia (Addis Ababa) Tanzania (Dar-es-Salaam) Nigeria (Lagos) Vietnam (Ho Chi Minh City, Hanoi, Haiphong & Da Nang) Thailand (Bangkok) Malaysia (Kuala Lumpur, Johor & Kota Kinabalu) Singapore Philippines (Manila) Myanmar (Yangon, Mandalay & Pyinmana) Indonesia (Jakarta & Batam) Philippines (Manila) Laos (Vientiane) Cambodia (Phnompenh) China (Shanghai, Qingdao & Dalian) Japan (Tokyo) HEAD OFFICE PO Box 877 Dammam 31421 Saudi Arabia Phone (966 3) 847 1840 Fax (966 3) 847 1291 E-Mail pebmarketing@zamilsteel.com www.zamilsteel.com January 2012