Department of Electrical & Electronic Engineering
Assignment on
Switchgear Equipment in a Substation
Course Code: EEE-4229
Course Title: Power System Protection
Submission Date: 15.05.2014
Presented By
Md. Atiqur Rahman
Department of Electrical & Electronic Engineering
Leading University
2
Contents
Introduction of this Substation...............................................................................................................3
Sub-station..............................................................................................................................................4
Why we need Sub-station...................................................................................................................4
Schematic Power System Diagram .........................................................................................................5
Why we need to know about Switchgear...............................................................................................6
Switchgear equipment which is used in Amberkhana Substation..........................................................6
High & Low voltage switchgear panel.................................................................................................6
Incoming & Outgoing switchgear........................................................................................................6
Current Transformer (CT)........................................................................................................................7
Why we use C.T in a sub-station.........................................................................................................7
Potential Transformer (PT) .....................................................................................................................8
Why we use P.T in a sub-station.........................................................................................................8
Circuit Breakers.......................................................................................................................................9
Circuit breakers inter locking system at normal condition.................................................................9
Vacuum breakers ................................................................................................................................9
Sulfur Hexafluoride (SF6) Circuit Breaker .........................................................................................10
Fig: Sulfur Hexafluoride (SF6) Circuit Breaker ...................................................................................10
Air Breaker Switch.................................................................................................................................11
Isolator..................................................................................................................................................12
Oil Switch ..............................................................................................................................................13
Relays....................................................................................................................................................14
Surge arrester .......................................................................................................................................15
Fuses .....................................................................................................................................................16
Reference..............................................................................................................................................17
3
Introduction of this Substation
Substation Location: Division-1, Electric Supply, Amberkhana, Sylhet
Substation Rating: 33/11kv
Substation Type: Outdoor
Distributed Area: Amberkana, Shahi-Eidgah, Dorga-Mohalla, Mirermoydan, SubidBazar,
Patantula, Ahakalia, Airport, Baghbhari.
4
Sub-station
A substation may be defined as “assembly of apparatus which transfers characteristics of
electrical energy from one to another for example from alternating current to direct current or
from one to another.” Every electrical circuit needs a switching device and protective device.
They are together called Switchgear. These are located in the substation.
Why we need Sub-station
For economical transfer electrical energy or to meet various demand of the load, we require
sub-station.
Fig: an outdoor Substation
5
Schematic Power System Diagram
Fig: Schematic Power System Diagram
6
Why we need to know about Switchgear
All electrical equipment and circuits have to be protected by protective devices against
damages arising abnormal conditions.
Switchgear equipment which is used in Amberkhana Substation
High & Low voltage switchgear panel
 Current Transformer
 Potential Transformer
 Circuit Breaker
o Vacuum Breakers
o SF6 Breakers
 Air break Switch
 Isolator
 Oil switch
 Relays
Incoming & Outgoing switchgear
 Surge Arrestor
 Fuses
7
Current Transformer (CT)
A current transformer is an instrument transformer, used along with measuring or protective
devices, in which the secondary current is proportional to the primary current (under normal
conditions of operation) and differs from it by an angle which is approximately zero.
Fig: Current Transformer
Why we use C.T in a sub-station
Current T/F is used for protection and metering purposes. It steps down the current level of
the line for following purposes.
 Measurement: ammeter, kw meter, kwh meter, power factor meter
 Control and protection: current when exceeds the set value operates the relay which
senses the faulty condition.
8
Potential Transformer (PT)
Potential Transformer or Voltage Transformer gets used in electrical power system for
stepping down the system voltage to a safe value which can be fed to low ratings meters and
relays. Commercially available relays and meters used for protection and metering, are
designed for low voltage.
Fig: Potential Transformer
Why we use P.T in a sub-station
It steps down the voltage level of line for -
 Measurement: voltmeter, frequency meter , kw meter, kwh meter , power factor
meter
 Control & protection: used in directional over current protection and under
frequency relay operation (48.8 Hz , df/dt relay)
9
Circuit Breakers
A circuit breaker is equipment which can open or close a circuit under all conditions, such as:
no loads, full loads or fault condition.
Circuit breakers inter locking system at normal condition
When closing:
 Open earthlings switch
 Close isolator
 Then close circuit breaker
When opening
 First to open circuit breaker
 Next to open isolator
 Then the earthlings switch to close
Vacuum breakers
Vacuum circuit breakers are used mostly for low and medium voltages. Vacuum interrupters
are developed for up to 36 kV and can be connected in series for higher voltages. The
interrupting chambers are made of porcelain and sealed. They cannot be open for
maintenance, but life is expected to be about 20 years, provided that the vacuum is
maintained. Because of the high dielectric strength of vacuum, the interrupters are small. The
gap between the contacts is about 1 cm for 15 kV interrupters, 2 mm for 3 kV interrupters.
Fig: Vacuum breakers
10
Advantage of Vacuum Circuit Breaker
 no oil is required for are quenching
 least maintenance
 compact size
 light in weight
Sulfur Hexafluoride (SF6) Circuit Breaker
Sulfur Hexafluoride (SF6) is an excellent gaseous dielectric for high voltage power
applications. It has been used extensively in high voltage circuit breakers and other
switchgears employed by the power industry. Applications for SF6 include gas insulated
transmission lines and gas insulated power distributions. The combined electrical, physical,
chemical and thermal properties offer many advantages when used in power switchgears.
Some of the outstanding properties of SF6 making it desirable to use in power applications
are:
 High dielectric strength
 Unique arc-quenching ability
 Excellent thermal stability
 Good thermal conductivity
Fig: Sulfur Hexafluoride (SF6) Circuit Breaker
11
Air Breaker Switch
An "air break switch' is a switching device that uses air the dielectric. Air break switches can
be single pole or 'gang operated', and can be operated manually (using either a handle/ratchet
mechanism or an insulated 'hook stick' made either of wood or fiberglass). Air break switches
are designed for switching under load, but there is often a noticeable arc associated with
switching. Air break switches can be found either in substations or out on the distribution
system - either pole top or in pad-mounted metal enclosures. Air-break switches at currents
up to 750 kV, which are generally used at high-voltage power plants and substations.
 It is operated on No Load Only.
 Rated Voltage :- 12 KV
 Normal Current :- 400 A
Fig: Air Breaker
Advantage:
 Air-break switches lie in the fact that they are fireproof and explosion proof.
 Have rapid connect and disconnect operation, and are relatively simple in design.
Disadvantage
 The presence of equipment for the production and storage of compressed-air supplies
12
Isolator
An isolator is a non load-breaking switch, and is provides a visible means of isolating a
component, such as a circuit breaker, transformer, etc., from the high-voltage lines, whenever
it is necessary to perform maintenance of that component. Normally, isolators come in pairs,
with one on each side of the component to be isolated. Isolators are only opened after the load
current has been broken using a circuit breaker, and must be closed before the circuit breaker
is reclosed. To work on, say, a h.v. circuit breaker, the breaker must be tripped, the isolators
on either side must be opened and locked off, temporary earths attached to either side of the
circuit breake- to-work card, detailing the maintenance work, must be issued to the crew by
the supervising engineer.
Fig: Isolator
Why we use it in Sub-station
 Its prime purpose is operator safety.
 It is physical and visual disconnection of the circuit from power supply.
 Isolators are usually used on both sides of the C.B in order to repair or replace the
C.B.
 It is used to separate any section from rest part of the power supply.
Maintenance of isolator
 oiling &greasing of moving parts
 check contact firmness
 check open / close trials
 Earthlings switch
13
Oil Switch
An oil switch is a high-voltage switch whose contacts are opened and closed in oil. The
switch is actually immersed in an oil bath and contained in a steel tank. The reason for
placing high-voltage switches in oil is that the oil will break the circuit when the switch is
opened with high voltages. A separation of the switch contacts does not always break the
current flow because an electric arc forms between the contacts if the contacts are opened in
oil. The oil will quench the arc. Further more if an arc should form in the oil. It will evaporate
part of the oil because of the high temperature and will partially fill the interrupters
surrounding the switch contacts with vaporized oil. This vapor develops a pressure in the
interrupters which assists in quenching or breaking the arc by elongating the arc.
Fig: Oil switch
14
Relays
Relay is a device when detects the fault supplies information to the breaker for circuit
interruption.
Working principal of relay
 Under normal load current a small current flows in the relay operating coil so breaker
remains unchanged.
 When fault occurs a large amount of current flows in the relay operating coil and it
energized the trip coil of the breaker. Hence the breaker is open.
Fig: Scheme of Relay
Why we use it in Sub-station
 Reliability
 Sensitivity
 Selectivity
 Quickness
 Non interference with future extension
 Protection for transformer
15
Surge arrester
Lightning Arresters or Surge Arresters are always connected in Shunt to the equipment to be
protected; they provide a low impedance path for the surge current to the ground. Wave trap
is a parallel tuned inductor - capacitor 'tank' circuit made to be resonant at the desired
communication frequency. It is the effort to utilize the same transmission line between two
substations for the purpose of communications. At this communication frequency the tank
circuit provides high impedance and does not allow passing through them & onto the
substation bus & into transformers.
 Lighting arrestor is used for lightning surge protection.
 Lighting arrestor is used in line side as well as T/F HV & LV side.
Fig: Surge arrester
16
Fuses
Fuse is a safety device. It is connected in series with the circuit and protects the electrical
apparatus and equipment from damage, when excess current flows. It is one of the simplest
protective devices and is used as circuit interrupting device under short circuit condition.
Fig: Fuse
Types of Fuse element
 Rewire able fuse
 Cartridge type fuse
 Drop out fuse
 High capacity H.R.C. fuse
 High voltage H.R.C. fuse
Drop Out Fuse Specification
 11 KV, 50 HZ.
 Rated Voltage :- 12 KV
 Rated Normal Current:- 100 A
17
Reference
 Training Institute for Chemical Industries(TICI)
o Electrical Substation & Distribution System
o Electrical Protective Devices & Electrical Symbols
 http://www.electrical4u.com/
 https://answers.yahoo.com
 http://wiki.answers.com/
 http://www.slideshare.net/

Contenu connexe

Tendances

POWER DISTRIBUTION 2.docx
POWER DISTRIBUTION 2.docxPOWER DISTRIBUTION 2.docx
POWER DISTRIBUTION 2.docx
Jeffrey Dorsey
 
400kv sub-station-final-ppt-by-mohit
400kv sub-station-final-ppt-by-mohit400kv sub-station-final-ppt-by-mohit
400kv sub-station-final-ppt-by-mohit
Mohit Awasthi
 

Tendances (20)

Power system protection
Power system protectionPower system protection
Power system protection
 
Switchgear and protection lecture 1
Switchgear and protection lecture 1Switchgear and protection lecture 1
Switchgear and protection lecture 1
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devices
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
24620708 feeder-protection (1)
24620708 feeder-protection (1)24620708 feeder-protection (1)
24620708 feeder-protection (1)
 
POWER DISTRIBUTION 2.docx
POWER DISTRIBUTION 2.docxPOWER DISTRIBUTION 2.docx
POWER DISTRIBUTION 2.docx
 
BUSBAR PROTECTION
BUSBAR PROTECTIONBUSBAR PROTECTION
BUSBAR PROTECTION
 
Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protection
 
Inplant training about 110kv/11kv substation
Inplant training about 110kv/11kv substationInplant training about 110kv/11kv substation
Inplant training about 110kv/11kv substation
 
Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 
On load tap changer
On load tap changerOn load tap changer
On load tap changer
 
400kv sub-station-final-ppt-by-mohit
400kv sub-station-final-ppt-by-mohit400kv sub-station-final-ppt-by-mohit
400kv sub-station-final-ppt-by-mohit
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
132 kv substation
132 kv substation132 kv substation
132 kv substation
 
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
BUS BAR  PROTECTION PPT BY:-R.K.PANDITBUS BAR  PROTECTION PPT BY:-R.K.PANDIT
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
 
INSULATORS AND ITS TYPES
INSULATORS AND ITS TYPESINSULATORS AND ITS TYPES
INSULATORS AND ITS TYPES
 
Electrical 132kv substation project .. shakir
Electrical 132kv substation project .. shakirElectrical 132kv substation project .. shakir
Electrical 132kv substation project .. shakir
 
Power Line Carrier Communication PLCC
Power Line Carrier Communication PLCCPower Line Carrier Communication PLCC
Power Line Carrier Communication PLCC
 
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentation
 

En vedette

SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
Partha Parida
 
Typical layout of a Sub-Station
Typical layout of a Sub-StationTypical layout of a Sub-Station
Typical layout of a Sub-Station
Towfiqur Rahman
 
Rotating machine fault detection using principal component analysis of vibrat...
Rotating machine fault detection using principal component analysis of vibrat...Rotating machine fault detection using principal component analysis of vibrat...
Rotating machine fault detection using principal component analysis of vibrat...
Tristan Plante
 
Circuit breaker arc phenomena
Circuit breaker arc phenomenaCircuit breaker arc phenomena
Circuit breaker arc phenomena
Bhavin Pradhan
 
Transmission line protection principles
Transmission line protection principlesTransmission line protection principles
Transmission line protection principles
Jhon Miranda Ramos
 

En vedette (20)

Substation equipment and its function 2
Substation equipment and its function 2Substation equipment and its function 2
Substation equipment and its function 2
 
Switch yard & Protection
Switch yard & ProtectionSwitch yard & Protection
Switch yard & Protection
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
 
Gis substation
Gis substationGis substation
Gis substation
 
presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.
 
Typical layout of a Sub-Station
Typical layout of a Sub-StationTypical layout of a Sub-Station
Typical layout of a Sub-Station
 
Rotating machine fault detection using principal component analysis of vibrat...
Rotating machine fault detection using principal component analysis of vibrat...Rotating machine fault detection using principal component analysis of vibrat...
Rotating machine fault detection using principal component analysis of vibrat...
 
Statistical Evaluation of Standardization in Substation Maintenance
Statistical Evaluation of Standardization in Substation MaintenanceStatistical Evaluation of Standardization in Substation Maintenance
Statistical Evaluation of Standardization in Substation Maintenance
 
132 KV GSS CHAMBAL JAIPUR
132 KV GSS CHAMBAL JAIPUR132 KV GSS CHAMBAL JAIPUR
132 KV GSS CHAMBAL JAIPUR
 
ELVIS substation maintenance Hannu Hätönen
ELVIS substation maintenance Hannu HätönenELVIS substation maintenance Hannu Hätönen
ELVIS substation maintenance Hannu Hätönen
 
Circuit breaker arc phenomena
Circuit breaker arc phenomenaCircuit breaker arc phenomena
Circuit breaker arc phenomena
 
Transmission line protection principles
Transmission line protection principlesTransmission line protection principles
Transmission line protection principles
 
Power system protection
Power system protectionPower system protection
Power system protection
 
SWITCH GEAR
SWITCH   GEARSWITCH   GEAR
SWITCH GEAR
 
SWITCH GEAR PADA SISTEM TENAGA LISTRIK
SWITCH GEAR  PADA  SISTEM TENAGA LISTRIK SWITCH GEAR  PADA  SISTEM TENAGA LISTRIK
SWITCH GEAR PADA SISTEM TENAGA LISTRIK
 
FAULT ANALYSIS OF HVDC TRANSMISSION SYSTEMS
FAULT ANALYSIS OF HVDC TRANSMISSION SYSTEMSFAULT ANALYSIS OF HVDC TRANSMISSION SYSTEMS
FAULT ANALYSIS OF HVDC TRANSMISSION SYSTEMS
 
HV Substation Earthing Guide - Central Networks
HV Substation Earthing Guide - Central NetworksHV Substation Earthing Guide - Central Networks
HV Substation Earthing Guide - Central Networks
 
Substation Maintenance
Substation MaintenanceSubstation Maintenance
Substation Maintenance
 
Planning for Substation Maintenance and Reliability
Planning for Substation Maintenance and ReliabilityPlanning for Substation Maintenance and Reliability
Planning for Substation Maintenance and Reliability
 
Switchgear
SwitchgearSwitchgear
Switchgear
 

Similaire à Switchgear Equipment in a Substation

changwon MVP, EMDB, SMDB & DB
changwon MVP, EMDB, SMDB & DBchangwon MVP, EMDB, SMDB & DB
changwon MVP, EMDB, SMDB & DB
Sheikh Imran
 

Similaire à Switchgear Equipment in a Substation (20)

“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
 
ms ppt.ppt
ms ppt.pptms ppt.ppt
ms ppt.ppt
 
Electrical Saftey.pptx
Electrical Saftey.pptxElectrical Saftey.pptx
Electrical Saftey.pptx
 
Summer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Summer Training presentation on 132/33 KV sub-station Minto park, AllahabadSummer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Summer Training presentation on 132/33 KV sub-station Minto park, Allahabad
 
Industrial training 220 KV moradabad
Industrial training 220 KV moradabadIndustrial training 220 KV moradabad
Industrial training 220 KV moradabad
 
132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptx132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptx
 
protection scheme of a grid substation prsentation
protection scheme of a grid substation prsentationprotection scheme of a grid substation prsentation
protection scheme of a grid substation prsentation
 
Ashwani kumar
Ashwani kumarAshwani kumar
Ashwani kumar
 
Report on 220kv substation at Jassure
Report on 220kv substation at JassureReport on 220kv substation at Jassure
Report on 220kv substation at Jassure
 
changwon MVP, EMDB, SMDB & DB
changwon MVP, EMDB, SMDB & DBchangwon MVP, EMDB, SMDB & DB
changwon MVP, EMDB, SMDB & DB
 
Anurag Attri.pptx
Anurag Attri.pptxAnurag Attri.pptx
Anurag Attri.pptx
 
rough.pptx
rough.pptxrough.pptx
rough.pptx
 
West bengal state electricity distribution limited vocational traning
West bengal state electricity distribution limited vocational traningWest bengal state electricity distribution limited vocational traning
West bengal state electricity distribution limited vocational traning
 
Standing type outdoor full sf6 gas insualted ring main unit
Standing type outdoor full sf6 gas insualted ring main unitStanding type outdoor full sf6 gas insualted ring main unit
Standing type outdoor full sf6 gas insualted ring main unit
 
Standing type GIS RMU
Standing type GIS RMUStanding type GIS RMU
Standing type GIS RMU
 
Switchgears and protection devices
Switchgears and protection devicesSwitchgears and protection devices
Switchgears and protection devices
 
Ashish.pptx
Ashish.pptxAshish.pptx
Ashish.pptx
 
Basic electrical comp upload1
Basic electrical comp upload1Basic electrical comp upload1
Basic electrical comp upload1
 
A vocational summer training at Jindal Steel and Power Limited
A vocational summer training at Jindal Steel and Power LimitedA vocational summer training at Jindal Steel and Power Limited
A vocational summer training at Jindal Steel and Power Limited
 
substation internship report
substation internship report substation internship report
substation internship report
 

Plus de Md. Atiqur Rahman

Plus de Md. Atiqur Rahman (8)

PCA Based Face Recognition System
PCA Based Face Recognition SystemPCA Based Face Recognition System
PCA Based Face Recognition System
 
Face Recognition Proposal Presentation
Face Recognition Proposal PresentationFace Recognition Proposal Presentation
Face Recognition Proposal Presentation
 
Aminoglycosides
AminoglycosidesAminoglycosides
Aminoglycosides
 
Optical Fiber Communication & Bangladesh
Optical Fiber Communication & BangladeshOptical Fiber Communication & Bangladesh
Optical Fiber Communication & Bangladesh
 
Collective bargaining
Collective bargainingCollective bargaining
Collective bargaining
 
Function of commercial banks in bangladesh
Function of commercial banks in bangladeshFunction of commercial banks in bangladesh
Function of commercial banks in bangladesh
 
Power genaration in bangladesh
Power genaration in bangladeshPower genaration in bangladesh
Power genaration in bangladesh
 
Cyber crime
Cyber crimeCyber crime
Cyber crime
 

Dernier

VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Christo Ananth
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Christo Ananth
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Dr.Costas Sachpazis
 

Dernier (20)

Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICSUNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Vivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design SpainVivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design Spain
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 

Switchgear Equipment in a Substation

  • 1. Department of Electrical & Electronic Engineering Assignment on Switchgear Equipment in a Substation Course Code: EEE-4229 Course Title: Power System Protection Submission Date: 15.05.2014 Presented By Md. Atiqur Rahman Department of Electrical & Electronic Engineering Leading University
  • 2. 2 Contents Introduction of this Substation...............................................................................................................3 Sub-station..............................................................................................................................................4 Why we need Sub-station...................................................................................................................4 Schematic Power System Diagram .........................................................................................................5 Why we need to know about Switchgear...............................................................................................6 Switchgear equipment which is used in Amberkhana Substation..........................................................6 High & Low voltage switchgear panel.................................................................................................6 Incoming & Outgoing switchgear........................................................................................................6 Current Transformer (CT)........................................................................................................................7 Why we use C.T in a sub-station.........................................................................................................7 Potential Transformer (PT) .....................................................................................................................8 Why we use P.T in a sub-station.........................................................................................................8 Circuit Breakers.......................................................................................................................................9 Circuit breakers inter locking system at normal condition.................................................................9 Vacuum breakers ................................................................................................................................9 Sulfur Hexafluoride (SF6) Circuit Breaker .........................................................................................10 Fig: Sulfur Hexafluoride (SF6) Circuit Breaker ...................................................................................10 Air Breaker Switch.................................................................................................................................11 Isolator..................................................................................................................................................12 Oil Switch ..............................................................................................................................................13 Relays....................................................................................................................................................14 Surge arrester .......................................................................................................................................15 Fuses .....................................................................................................................................................16 Reference..............................................................................................................................................17
  • 3. 3 Introduction of this Substation Substation Location: Division-1, Electric Supply, Amberkhana, Sylhet Substation Rating: 33/11kv Substation Type: Outdoor Distributed Area: Amberkana, Shahi-Eidgah, Dorga-Mohalla, Mirermoydan, SubidBazar, Patantula, Ahakalia, Airport, Baghbhari.
  • 4. 4 Sub-station A substation may be defined as “assembly of apparatus which transfers characteristics of electrical energy from one to another for example from alternating current to direct current or from one to another.” Every electrical circuit needs a switching device and protective device. They are together called Switchgear. These are located in the substation. Why we need Sub-station For economical transfer electrical energy or to meet various demand of the load, we require sub-station. Fig: an outdoor Substation
  • 5. 5 Schematic Power System Diagram Fig: Schematic Power System Diagram
  • 6. 6 Why we need to know about Switchgear All electrical equipment and circuits have to be protected by protective devices against damages arising abnormal conditions. Switchgear equipment which is used in Amberkhana Substation High & Low voltage switchgear panel  Current Transformer  Potential Transformer  Circuit Breaker o Vacuum Breakers o SF6 Breakers  Air break Switch  Isolator  Oil switch  Relays Incoming & Outgoing switchgear  Surge Arrestor  Fuses
  • 7. 7 Current Transformer (CT) A current transformer is an instrument transformer, used along with measuring or protective devices, in which the secondary current is proportional to the primary current (under normal conditions of operation) and differs from it by an angle which is approximately zero. Fig: Current Transformer Why we use C.T in a sub-station Current T/F is used for protection and metering purposes. It steps down the current level of the line for following purposes.  Measurement: ammeter, kw meter, kwh meter, power factor meter  Control and protection: current when exceeds the set value operates the relay which senses the faulty condition.
  • 8. 8 Potential Transformer (PT) Potential Transformer or Voltage Transformer gets used in electrical power system for stepping down the system voltage to a safe value which can be fed to low ratings meters and relays. Commercially available relays and meters used for protection and metering, are designed for low voltage. Fig: Potential Transformer Why we use P.T in a sub-station It steps down the voltage level of line for -  Measurement: voltmeter, frequency meter , kw meter, kwh meter , power factor meter  Control & protection: used in directional over current protection and under frequency relay operation (48.8 Hz , df/dt relay)
  • 9. 9 Circuit Breakers A circuit breaker is equipment which can open or close a circuit under all conditions, such as: no loads, full loads or fault condition. Circuit breakers inter locking system at normal condition When closing:  Open earthlings switch  Close isolator  Then close circuit breaker When opening  First to open circuit breaker  Next to open isolator  Then the earthlings switch to close Vacuum breakers Vacuum circuit breakers are used mostly for low and medium voltages. Vacuum interrupters are developed for up to 36 kV and can be connected in series for higher voltages. The interrupting chambers are made of porcelain and sealed. They cannot be open for maintenance, but life is expected to be about 20 years, provided that the vacuum is maintained. Because of the high dielectric strength of vacuum, the interrupters are small. The gap between the contacts is about 1 cm for 15 kV interrupters, 2 mm for 3 kV interrupters. Fig: Vacuum breakers
  • 10. 10 Advantage of Vacuum Circuit Breaker  no oil is required for are quenching  least maintenance  compact size  light in weight Sulfur Hexafluoride (SF6) Circuit Breaker Sulfur Hexafluoride (SF6) is an excellent gaseous dielectric for high voltage power applications. It has been used extensively in high voltage circuit breakers and other switchgears employed by the power industry. Applications for SF6 include gas insulated transmission lines and gas insulated power distributions. The combined electrical, physical, chemical and thermal properties offer many advantages when used in power switchgears. Some of the outstanding properties of SF6 making it desirable to use in power applications are:  High dielectric strength  Unique arc-quenching ability  Excellent thermal stability  Good thermal conductivity Fig: Sulfur Hexafluoride (SF6) Circuit Breaker
  • 11. 11 Air Breaker Switch An "air break switch' is a switching device that uses air the dielectric. Air break switches can be single pole or 'gang operated', and can be operated manually (using either a handle/ratchet mechanism or an insulated 'hook stick' made either of wood or fiberglass). Air break switches are designed for switching under load, but there is often a noticeable arc associated with switching. Air break switches can be found either in substations or out on the distribution system - either pole top or in pad-mounted metal enclosures. Air-break switches at currents up to 750 kV, which are generally used at high-voltage power plants and substations.  It is operated on No Load Only.  Rated Voltage :- 12 KV  Normal Current :- 400 A Fig: Air Breaker Advantage:  Air-break switches lie in the fact that they are fireproof and explosion proof.  Have rapid connect and disconnect operation, and are relatively simple in design. Disadvantage  The presence of equipment for the production and storage of compressed-air supplies
  • 12. 12 Isolator An isolator is a non load-breaking switch, and is provides a visible means of isolating a component, such as a circuit breaker, transformer, etc., from the high-voltage lines, whenever it is necessary to perform maintenance of that component. Normally, isolators come in pairs, with one on each side of the component to be isolated. Isolators are only opened after the load current has been broken using a circuit breaker, and must be closed before the circuit breaker is reclosed. To work on, say, a h.v. circuit breaker, the breaker must be tripped, the isolators on either side must be opened and locked off, temporary earths attached to either side of the circuit breake- to-work card, detailing the maintenance work, must be issued to the crew by the supervising engineer. Fig: Isolator Why we use it in Sub-station  Its prime purpose is operator safety.  It is physical and visual disconnection of the circuit from power supply.  Isolators are usually used on both sides of the C.B in order to repair or replace the C.B.  It is used to separate any section from rest part of the power supply. Maintenance of isolator  oiling &greasing of moving parts  check contact firmness  check open / close trials  Earthlings switch
  • 13. 13 Oil Switch An oil switch is a high-voltage switch whose contacts are opened and closed in oil. The switch is actually immersed in an oil bath and contained in a steel tank. The reason for placing high-voltage switches in oil is that the oil will break the circuit when the switch is opened with high voltages. A separation of the switch contacts does not always break the current flow because an electric arc forms between the contacts if the contacts are opened in oil. The oil will quench the arc. Further more if an arc should form in the oil. It will evaporate part of the oil because of the high temperature and will partially fill the interrupters surrounding the switch contacts with vaporized oil. This vapor develops a pressure in the interrupters which assists in quenching or breaking the arc by elongating the arc. Fig: Oil switch
  • 14. 14 Relays Relay is a device when detects the fault supplies information to the breaker for circuit interruption. Working principal of relay  Under normal load current a small current flows in the relay operating coil so breaker remains unchanged.  When fault occurs a large amount of current flows in the relay operating coil and it energized the trip coil of the breaker. Hence the breaker is open. Fig: Scheme of Relay Why we use it in Sub-station  Reliability  Sensitivity  Selectivity  Quickness  Non interference with future extension  Protection for transformer
  • 15. 15 Surge arrester Lightning Arresters or Surge Arresters are always connected in Shunt to the equipment to be protected; they provide a low impedance path for the surge current to the ground. Wave trap is a parallel tuned inductor - capacitor 'tank' circuit made to be resonant at the desired communication frequency. It is the effort to utilize the same transmission line between two substations for the purpose of communications. At this communication frequency the tank circuit provides high impedance and does not allow passing through them & onto the substation bus & into transformers.  Lighting arrestor is used for lightning surge protection.  Lighting arrestor is used in line side as well as T/F HV & LV side. Fig: Surge arrester
  • 16. 16 Fuses Fuse is a safety device. It is connected in series with the circuit and protects the electrical apparatus and equipment from damage, when excess current flows. It is one of the simplest protective devices and is used as circuit interrupting device under short circuit condition. Fig: Fuse Types of Fuse element  Rewire able fuse  Cartridge type fuse  Drop out fuse  High capacity H.R.C. fuse  High voltage H.R.C. fuse Drop Out Fuse Specification  11 KV, 50 HZ.  Rated Voltage :- 12 KV  Rated Normal Current:- 100 A
  • 17. 17 Reference  Training Institute for Chemical Industries(TICI) o Electrical Substation & Distribution System o Electrical Protective Devices & Electrical Symbols  http://www.electrical4u.com/  https://answers.yahoo.com  http://wiki.answers.com/  http://www.slideshare.net/