12. MNFC® System: Main Advantages No Cross Contamination 80% efficiency Low pressure drop 100% Sensible cooling transfer No moving parts No energy required No single points of failure No Maintenance Patent P201030478
14. MODULAR DATA CENTER NATURAL FREE COOLING®OPERATIONAL RANGE External temperatures < 19ºC temperature at the cold corridor is 24 ºC or lower with no support of traditional cooling 19 ºC < External temperatures < 24 ºC temperature at the cold corridor is 24 ºC or lower WITH evaporative cooling External temperatures > 24ºC chilled water cooling
18. MODULAR DATA CENTER EXAMPLE: YEARLY SAVING IN US CITIES (II) Example: 500KW Data Center (IT Load) in Boston (similar PUE as Detroit)
19. MODULAR DATA CENTER PHASE 1 DEPLOYED: IT container: 17 racks @ 14kW/rack NATURAL FREE COOLING container SERVICES room: EATON UPS, model 9390, 2 x 160 kVA (2N) 2 x Genset 225 kVA (N+1) ATS, Main Switch Boards
31. CONCLUSIONS - Security Vs. catastrophic events is a must: fire and water are main risks. DC thermal stability must be ensured! - Modularity: essential to adapt to the future. Modular “Smart Shelter” building technique is ideal. - Scalability: importance of planning ahead for added power and cooling equipment. - Mobility and Outdoors DC: the future. Containerized or Smart Shelter modular. - Power Efficient: thermal insulation provides great side benefit; DC consolidation and virtualization. GREEN