Objective: PUE 1.069 Case Study
MODULAR DATA CENTER CONTAINER PARK WITH: ,[object Object]
  MOST efficient electrical infrastructure (UPS, PDU,..),[object Object]
 Maximum resiliency: Tier 3
 18 x IT Container 40´ with 280 racks in total and  4MW IT power.
 Natural Free Cooling.
 Ultra low TCO: due to low PUE and reasonable priced kw/h (€ 0,03), about 70% less than in continental Europe.
 Redundant Fiber Optic link to continental Europe with 40ms latency. ,[object Object]
MODULAR DATA CENTER THE CHALLENGE OF FREE COOLING IN ICELAND -    Ideal location for Free Cooling: temp year round does not exceeds 24ºC. ,[object Object]
 	A study done by IBM showed that direct air free cooling (even with EPA filter)  could damage processors after 6 months.,[object Object]
Cooling Container IT Container MODULAR DATA CENTER Power room
MNFC® System: Main Advantages No Cross Contamination 80% efficiency Low pressure drop 100% Sensible cooling transfer No moving parts No energy required No single points of failure No Maintenance Patent  P201030478
MODULAR DATA CENTER  COOLING OPERATION 15ºC 31ºC 40ºC 22ºC
MODULAR DATA CENTER NATURAL FREE COOLING®OPERATIONAL RANGE External temperatures < 19ºC  temperature at the cold corridor is 24 ºC or lower with no support of traditional cooling  19 ºC < External temperatures < 24 ºC  temperature at the cold corridor is 24 ºC or lower WITH evaporative cooling External temperatures > 24ºC  chilled water cooling
MODULAR DATA CENTER HOURS AVAILABLE
MODULAR DATA CENTER PUE AND COOLING EFFICIENCY
MODULAR DATA CENTER
MODULAR DATA CENTER EXAMPLE: YEARLY SAVING IN US CITIES (II) Example: 500KW Data Center  (IT Load) in  Boston (similar PUE as Detroit)
MODULAR DATA CENTER PHASE 1 DEPLOYED: IT container: 17 racks @ 14kW/rack  NATURAL FREE COOLING container SERVICES room: EATON UPS, model 9390, 2 x 160 kVA (2N) 2 x Genset 225 kVA (N+1)  ATS, Main Switch Boards
SERVICES room UPSMain advantages:  ,[object Object]
 Turn key solution, service and maintenance
 High efficiency UPS with Energy Advantage Architecture (Energy Saver System),[object Object]
MODULAR DATA CENTER SCALABLE POWER INFRASTRUCTURE  PHASE 1 PHASE 2
MODULAR DATA CENTER
MODULAR DATA CENTER Not just a sketch , but a reality.

Contenu connexe

Tendances

SDC IGS Turnkey Brochure
SDC IGS Turnkey BrochureSDC IGS Turnkey Brochure
SDC IGS Turnkey Brochure
ArleneECarvalho
 
The Sustainability Consortium: Making Carbon-Free Living a Reality (Carbon Fr...
The Sustainability Consortium: Making Carbon-Free Living a Reality (Carbon Fr...The Sustainability Consortium: Making Carbon-Free Living a Reality (Carbon Fr...
The Sustainability Consortium: Making Carbon-Free Living a Reality (Carbon Fr...
ecoconnect
 
Buildings as Power Stations - Pathway to a Resilient Future for Dorset - Work...
Buildings as Power Stations - Pathway to a Resilient Future for Dorset - Work...Buildings as Power Stations - Pathway to a Resilient Future for Dorset - Work...
Buildings as Power Stations - Pathway to a Resilient Future for Dorset - Work...
Ecological Sequestration Trust
 
Dcd 2012 liquid cooling presentation
Dcd 2012 liquid cooling presentationDcd 2012 liquid cooling presentation
Dcd 2012 liquid cooling presentation
Scicomm
 
Aurora hpc energy efficiency
Aurora hpc energy efficiencyAurora hpc energy efficiency
Aurora hpc energy efficiency
Eurotech Aurora
 
DCD London 2016 - OCP Data Center Project Engineering Workshop Presentation D...
DCD London 2016 - OCP Data Center Project Engineering Workshop Presentation D...DCD London 2016 - OCP Data Center Project Engineering Workshop Presentation D...
DCD London 2016 - OCP Data Center Project Engineering Workshop Presentation D...
Inflectiontech Ltd
 

Tendances (20)

High Efficiency technologies for Data Centre Air Conditioning
High Efficiency technologies for  Data Centre Air ConditioningHigh Efficiency technologies for  Data Centre Air Conditioning
High Efficiency technologies for Data Centre Air Conditioning
 
SDC42 Intergate.Seattle PDF
SDC42 Intergate.Seattle PDFSDC42 Intergate.Seattle PDF
SDC42 Intergate.Seattle PDF
 
Data Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationData Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure Optimization
 
SDC42 Brochure
SDC42 Brochure SDC42 Brochure
SDC42 Brochure
 
High Density Cooling Solutions for the Next Generation Data Center with Jen
High Density Cooling Solutions for the Next Generation Data Center with JenHigh Density Cooling Solutions for the Next Generation Data Center with Jen
High Density Cooling Solutions for the Next Generation Data Center with Jen
 
Data Center Cooling Strategies
Data Center Cooling StrategiesData Center Cooling Strategies
Data Center Cooling Strategies
 
SDC IGS Turnkey Brochure
SDC IGS Turnkey BrochureSDC IGS Turnkey Brochure
SDC IGS Turnkey Brochure
 
The Sustainability Consortium: Making Carbon-Free Living a Reality (Carbon Fr...
The Sustainability Consortium: Making Carbon-Free Living a Reality (Carbon Fr...The Sustainability Consortium: Making Carbon-Free Living a Reality (Carbon Fr...
The Sustainability Consortium: Making Carbon-Free Living a Reality (Carbon Fr...
 
Total Liquid Cooling
Total Liquid CoolingTotal Liquid Cooling
Total Liquid Cooling
 
Buildings as Power Stations - Pathway to a Resilient Future for Dorset - Work...
Buildings as Power Stations - Pathway to a Resilient Future for Dorset - Work...Buildings as Power Stations - Pathway to a Resilient Future for Dorset - Work...
Buildings as Power Stations - Pathway to a Resilient Future for Dorset - Work...
 
Data center hvac
Data center hvacData center hvac
Data center hvac
 
11 karytsas mare
11 karytsas mare11 karytsas mare
11 karytsas mare
 
Data Center Optimization Best Practices
Data Center Optimization Best PracticesData Center Optimization Best Practices
Data Center Optimization Best Practices
 
Infosys EC-53 (M & C Building), Bangalore – Making Energy Conservation a Habit
Infosys EC-53 (M & C Building), Bangalore – Making Energy Conservation a HabitInfosys EC-53 (M & C Building), Bangalore – Making Energy Conservation a Habit
Infosys EC-53 (M & C Building), Bangalore – Making Energy Conservation a Habit
 
Gross Hall Smart Labs For Sustainability Committee 04.02.10
Gross Hall Smart Labs For Sustainability Committee 04.02.10Gross Hall Smart Labs For Sustainability Committee 04.02.10
Gross Hall Smart Labs For Sustainability Committee 04.02.10
 
Dcd 2012 liquid cooling presentation
Dcd 2012 liquid cooling presentationDcd 2012 liquid cooling presentation
Dcd 2012 liquid cooling presentation
 
Aurora hpc energy efficiency
Aurora hpc energy efficiencyAurora hpc energy efficiency
Aurora hpc energy efficiency
 
Energy Systems Optimization
Energy Systems OptimizationEnergy Systems Optimization
Energy Systems Optimization
 
Liquid cooling package_lcp_cooling_systems
Liquid cooling package_lcp_cooling_systemsLiquid cooling package_lcp_cooling_systems
Liquid cooling package_lcp_cooling_systems
 
DCD London 2016 - OCP Data Center Project Engineering Workshop Presentation D...
DCD London 2016 - OCP Data Center Project Engineering Workshop Presentation D...DCD London 2016 - OCP Data Center Project Engineering Workshop Presentation D...
DCD London 2016 - OCP Data Center Project Engineering Workshop Presentation D...
 

En vedette

Data Center Migration to the AWS Cloud
Data Center Migration to the AWS CloudData Center Migration to the AWS Cloud
Data Center Migration to the AWS Cloud
Tom Laszewski
 

En vedette (7)

CSC Modular Datacenter
CSC Modular DatacenterCSC Modular Datacenter
CSC Modular Datacenter
 
ePlus and FlashStack Converged Data Center Infrastructure
ePlus and FlashStack Converged Data Center InfrastructureePlus and FlashStack Converged Data Center Infrastructure
ePlus and FlashStack Converged Data Center Infrastructure
 
Ctrls-Company Presentation
Ctrls-Company PresentationCtrls-Company Presentation
Ctrls-Company Presentation
 
project report on DATACENTER
project report on DATACENTERproject report on DATACENTER
project report on DATACENTER
 
Data Center Migration to the AWS Cloud
Data Center Migration to the AWS CloudData Center Migration to the AWS Cloud
Data Center Migration to the AWS Cloud
 
POWER POINT PRESENTATION ON DATA CENTER
POWER POINT PRESENTATION ON DATA CENTERPOWER POINT PRESENTATION ON DATA CENTER
POWER POINT PRESENTATION ON DATA CENTER
 
DataCenter:: Infrastructure Presentation
DataCenter:: Infrastructure PresentationDataCenter:: Infrastructure Presentation
DataCenter:: Infrastructure Presentation
 

Similaire à Case Study Caso Thor

Cirrascale forest container march 2011
Cirrascale forest container march 2011Cirrascale forest container march 2011
Cirrascale forest container march 2011
Muchamad Jainuri
 
Commercial Overview DC Session 3 The Greening Of The Data Centre
Commercial Overview   DC Session 3   The Greening Of The Data CentreCommercial Overview   DC Session 3   The Greening Of The Data Centre
Commercial Overview DC Session 3 The Greening Of The Data Centre
paul_mathews
 
Boris Shapiro Controls expeiences
Boris Shapiro Controls expeiencesBoris Shapiro Controls expeiences
Boris Shapiro Controls expeiences
Boris Shapiro PE
 
District Cooling Jenny Dahlberg, Fortum
District Cooling   Jenny Dahlberg, FortumDistrict Cooling   Jenny Dahlberg, Fortum
District Cooling Jenny Dahlberg, Fortum
Niklas Johnsson
 

Similaire à Case Study Caso Thor (20)

Telehousenorth2presentationford sd2015
Telehousenorth2presentationford sd2015Telehousenorth2presentationford sd2015
Telehousenorth2presentationford sd2015
 
Telehouse North Two Presentation 2015 - Adiabatic and Evaporative cooling
Telehouse North Two Presentation 2015 - Adiabatic and Evaporative coolingTelehouse North Two Presentation 2015 - Adiabatic and Evaporative cooling
Telehouse North Two Presentation 2015 - Adiabatic and Evaporative cooling
 
Energy Efficiency in Huawei solutions
Energy Efficiency in Huawei solutionsEnergy Efficiency in Huawei solutions
Energy Efficiency in Huawei solutions
 
Data Center Cooling Study on Liquid Cooling
Data Center Cooling Study on Liquid CoolingData Center Cooling Study on Liquid Cooling
Data Center Cooling Study on Liquid Cooling
 
Cirrascale forest container march 2011
Cirrascale forest container march 2011Cirrascale forest container march 2011
Cirrascale forest container march 2011
 
Slides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingSlides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for Cooling
 
PAC 2.5 Efficiency is Attainable, What are you Waiting for?
PAC 2.5 Efficiency is Attainable, What are you Waiting for?PAC 2.5 Efficiency is Attainable, What are you Waiting for?
PAC 2.5 Efficiency is Attainable, What are you Waiting for?
 
Hyper efficient data centres – key ingredient intelligence networkshop44
Hyper efficient data centres – key ingredient intelligence   networkshop44Hyper efficient data centres – key ingredient intelligence   networkshop44
Hyper efficient data centres – key ingredient intelligence networkshop44
 
Commercial Overview DC Session 3 The Greening Of The Data Centre
Commercial Overview   DC Session 3   The Greening Of The Data CentreCommercial Overview   DC Session 3   The Greening Of The Data Centre
Commercial Overview DC Session 3 The Greening Of The Data Centre
 
Colocation.green presentation
Colocation.green presentationColocation.green presentation
Colocation.green presentation
 
Pmdc Smdc Technical Overview 24 Mar2010
Pmdc Smdc Technical Overview 24 Mar2010Pmdc Smdc Technical Overview 24 Mar2010
Pmdc Smdc Technical Overview 24 Mar2010
 
Raritan Presents Green Data Centers Around the World
Raritan Presents Green Data Centers Around the WorldRaritan Presents Green Data Centers Around the World
Raritan Presents Green Data Centers Around the World
 
Lenovo HPC: Energy Efficiency and Water-Cool-Technology Innovations
Lenovo HPC: Energy Efficiency and Water-Cool-Technology InnovationsLenovo HPC: Energy Efficiency and Water-Cool-Technology Innovations
Lenovo HPC: Energy Efficiency and Water-Cool-Technology Innovations
 
Datacentre Uk
Datacentre UkDatacentre Uk
Datacentre Uk
 
Bits, Bytes and BTUs: Warm Water Liquid Cooling at NREL
Bits, Bytes and BTUs: Warm Water Liquid Cooling at NRELBits, Bytes and BTUs: Warm Water Liquid Cooling at NREL
Bits, Bytes and BTUs: Warm Water Liquid Cooling at NREL
 
DC inverter technology in HVAC-R business
DC inverter technology in HVAC-R businessDC inverter technology in HVAC-R business
DC inverter technology in HVAC-R business
 
DCW 2014 Presentation
DCW 2014 PresentationDCW 2014 Presentation
DCW 2014 Presentation
 
Boris Shapiro Controls expeiences
Boris Shapiro Controls expeiencesBoris Shapiro Controls expeiences
Boris Shapiro Controls expeiences
 
District Cooling Jenny Dahlberg, Fortum
District Cooling   Jenny Dahlberg, FortumDistrict Cooling   Jenny Dahlberg, Fortum
District Cooling Jenny Dahlberg, Fortum
 
Vejen til lav PUE- optimering og stordrift - Flemming Søeberg, Interxion
Vejen til lav PUE- optimering og stordrift - Flemming Søeberg, InterxionVejen til lav PUE- optimering og stordrift - Flemming Søeberg, Interxion
Vejen til lav PUE- optimering og stordrift - Flemming Søeberg, Interxion
 

Plus de Data Center Consultores

Una visión a las tendencias y nuevas tenologías en Centros de Datos
Una visión a las tendencias y nuevas tenologías en Centros de DatosUna visión a las tendencias y nuevas tenologías en Centros de Datos
Una visión a las tendencias y nuevas tenologías en Centros de Datos
Data Center Consultores
 

Plus de Data Center Consultores (16)

Tiers (Un vistazo a los Tiers, Mitos y concepciones erróneas)
Tiers (Un vistazo a los Tiers, Mitos y concepciones erróneas)Tiers (Un vistazo a los Tiers, Mitos y concepciones erróneas)
Tiers (Un vistazo a los Tiers, Mitos y concepciones erróneas)
 
Proyección del Uptime Institute hacia Latinoamérica
Proyección del Uptime Institute hacia LatinoaméricaProyección del Uptime Institute hacia Latinoamérica
Proyección del Uptime Institute hacia Latinoamérica
 
Virtualización para la Eficiencia
Virtualización para la EficienciaVirtualización para la Eficiencia
Virtualización para la Eficiencia
 
Diseñando el Data Center del Futuro
Diseñando el Data Center del FuturoDiseñando el Data Center del Futuro
Diseñando el Data Center del Futuro
 
Estado actual y proyecciones futuras de PUE/DCiE
Estado actual y proyecciones futuras de PUE/DCiEEstado actual y proyecciones futuras de PUE/DCiE
Estado actual y proyecciones futuras de PUE/DCiE
 
Nueva generación de enfriamiento en Data Centers: Smart Aisle
Nueva generación de enfriamiento en Data Centers: Smart AisleNueva generación de enfriamiento en Data Centers: Smart Aisle
Nueva generación de enfriamiento en Data Centers: Smart Aisle
 
Cómo proteger su activo más importante: la Información
Cómo proteger su activo más importante: la InformaciónCómo proteger su activo más importante: la Información
Cómo proteger su activo más importante: la Información
 
Infraestructura TI en armonía
Infraestructura TI en armoníaInfraestructura TI en armonía
Infraestructura TI en armonía
 
Gamatronics Solutions for Data Centers
Gamatronics Solutions for Data CentersGamatronics Solutions for Data Centers
Gamatronics Solutions for Data Centers
 
Estrategias para ahorro de energía en applicaciones de misión crítica de IT
Estrategias para ahorro de energía en applicaciones de misión crítica de ITEstrategias para ahorro de energía en applicaciones de misión crítica de IT
Estrategias para ahorro de energía en applicaciones de misión crítica de IT
 
Claves para el diseño conceptual de Centro de Datos
Claves para el diseño conceptual de Centro de DatosClaves para el diseño conceptual de Centro de Datos
Claves para el diseño conceptual de Centro de Datos
 
Sistemas de Seguridad para Centros de Datos de Alta Disponibilidad
Sistemas de Seguridad para Centros de Datos de Alta DisponibilidadSistemas de Seguridad para Centros de Datos de Alta Disponibilidad
Sistemas de Seguridad para Centros de Datos de Alta Disponibilidad
 
Data Center as a Service
Data Center as a ServiceData Center as a Service
Data Center as a Service
 
Nuevo estándar para diseño de data center ANSI/BICSI-002
Nuevo estándar para diseño de data center ANSI/BICSI-002Nuevo estándar para diseño de data center ANSI/BICSI-002
Nuevo estándar para diseño de data center ANSI/BICSI-002
 
Una visión a las tendencias y nuevas tenologías en Centros de Datos
Una visión a las tendencias y nuevas tenologías en Centros de DatosUna visión a las tendencias y nuevas tenologías en Centros de Datos
Una visión a las tendencias y nuevas tenologías en Centros de Datos
 
Data Center Green
Data Center GreenData Center Green
Data Center Green
 

Dernier

Dernier (20)

Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processors
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)
 
Deploy with confidence: VMware Cloud Foundation 5.1 on next gen Dell PowerEdg...
Deploy with confidence: VMware Cloud Foundation 5.1 on next gen Dell PowerEdg...Deploy with confidence: VMware Cloud Foundation 5.1 on next gen Dell PowerEdg...
Deploy with confidence: VMware Cloud Foundation 5.1 on next gen Dell PowerEdg...
 
MINDCTI Revenue Release Quarter One 2024
MINDCTI Revenue Release Quarter One 2024MINDCTI Revenue Release Quarter One 2024
MINDCTI Revenue Release Quarter One 2024
 
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost SavingRepurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
 
GenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdfGenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdf
 
Polkadot JAM Slides - Token2049 - By Dr. Gavin Wood
Polkadot JAM Slides - Token2049 - By Dr. Gavin WoodPolkadot JAM Slides - Token2049 - By Dr. Gavin Wood
Polkadot JAM Slides - Token2049 - By Dr. Gavin Wood
 
Artificial Intelligence Chap.5 : Uncertainty
Artificial Intelligence Chap.5 : UncertaintyArtificial Intelligence Chap.5 : Uncertainty
Artificial Intelligence Chap.5 : Uncertainty
 
Top 5 Benefits OF Using Muvi Live Paywall For Live Streams
Top 5 Benefits OF Using Muvi Live Paywall For Live StreamsTop 5 Benefits OF Using Muvi Live Paywall For Live Streams
Top 5 Benefits OF Using Muvi Live Paywall For Live Streams
 
Understanding Discord NSFW Servers A Guide for Responsible Users.pdf
Understanding Discord NSFW Servers A Guide for Responsible Users.pdfUnderstanding Discord NSFW Servers A Guide for Responsible Users.pdf
Understanding Discord NSFW Servers A Guide for Responsible Users.pdf
 
Top 10 Most Downloaded Games on Play Store in 2024
Top 10 Most Downloaded Games on Play Store in 2024Top 10 Most Downloaded Games on Play Store in 2024
Top 10 Most Downloaded Games on Play Store in 2024
 
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time AutomationFrom Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
 
Strategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a FresherStrategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a Fresher
 
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
 
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data DiscoveryTrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
 

Case Study Caso Thor

  • 1. Objective: PUE 1.069 Case Study
  • 2.
  • 3.
  • 5. 18 x IT Container 40´ with 280 racks in total and 4MW IT power.
  • 6. Natural Free Cooling.
  • 7. Ultra low TCO: due to low PUE and reasonable priced kw/h (€ 0,03), about 70% less than in continental Europe.
  • 8.
  • 9.
  • 10.
  • 11. Cooling Container IT Container MODULAR DATA CENTER Power room
  • 12. MNFC® System: Main Advantages No Cross Contamination 80% efficiency Low pressure drop 100% Sensible cooling transfer No moving parts No energy required No single points of failure No Maintenance Patent P201030478
  • 13. MODULAR DATA CENTER COOLING OPERATION 15ºC 31ºC 40ºC 22ºC
  • 14. MODULAR DATA CENTER NATURAL FREE COOLING®OPERATIONAL RANGE External temperatures < 19ºC  temperature at the cold corridor is 24 ºC or lower with no support of traditional cooling 19 ºC < External temperatures < 24 ºC  temperature at the cold corridor is 24 ºC or lower WITH evaporative cooling External temperatures > 24ºC  chilled water cooling
  • 15. MODULAR DATA CENTER HOURS AVAILABLE
  • 16. MODULAR DATA CENTER PUE AND COOLING EFFICIENCY
  • 18. MODULAR DATA CENTER EXAMPLE: YEARLY SAVING IN US CITIES (II) Example: 500KW Data Center (IT Load) in Boston (similar PUE as Detroit)
  • 19. MODULAR DATA CENTER PHASE 1 DEPLOYED: IT container: 17 racks @ 14kW/rack NATURAL FREE COOLING container SERVICES room: EATON UPS, model 9390, 2 x 160 kVA (2N) 2 x Genset 225 kVA (N+1) ATS, Main Switch Boards
  • 20.
  • 21. Turn key solution, service and maintenance
  • 22.
  • 23. MODULAR DATA CENTER SCALABLE POWER INFRASTRUCTURE PHASE 1 PHASE 2
  • 25.
  • 26.
  • 27. MODULAR DATA CENTER Not just a sketch , but a reality.
  • 31. CONCLUSIONS - Security Vs. catastrophic events is a must: fire and water are main risks. DC thermal stability must be ensured! - Modularity: essential to adapt to the future. Modular “Smart Shelter” building technique is ideal. - Scalability: importance of planning ahead for added power and cooling equipment. - Mobility and Outdoors DC: the future. Containerized or Smart Shelter modular. - Power Efficient: thermal insulation provides great side benefit; DC consolidation and virtualization. GREEN