SlideShare une entreprise Scribd logo
1  sur  22
Télécharger pour lire hors ligne
TI00085D/06/EN/13.11
71136634
Technical Information
Proline Prosonic Flow 93T Portable
Portable ultrasonic flow measuring system
Volume flow measurement of liquids
Applications
The sensors are perfectly suited for the non-contact
measurement of pure or slightly contaminated liquids,
regardless of the pressure or electrical conductivity.
• Ideal solution for temporary use everywhere precise
measurement or verification is required
• Particularly suitable for retrofitting, monitoring
and verifying measuring points
• Suitable for pipe diameters
from DN 15 to 4000 (½ to 160")
• Suitable for fluid temperatures ranging
from –40 to +170 °C (–40 to +338 °F)
• Can be used with all metal and plastic pipes lined or
unlined and with composite pipes
• Ideal solution for all applications with sound-
conducting liquids, e.g. water, wastewater, oils,
solvents, acids, hydrocarbons and chemicals
Features and benefits
The Prosonic Flow ultrasonic clamp-on system allows
accurate and cost-effective flow measurement from
outside the pipe and without the need to interrupt the
process. The flow measurement is bidirectional and
causes no pressure loss.
• Easy, safe and menu-guided sensor mounting ensures
precise measuring results
• Easy and safe commissioning via Quick Setup menus
• Automatic frequency scan for optimized installation
and maximum measuring performance
• Current input for parallel data acquisition or for
verifying other devices
• Current output active or passive
• Remote configuration and measured value display
using Endress+Hauser's FieldCare software
• Integrated data logger/site manager
• Easy data transfer via USB stick without additional
software
Proline Prosonic Flow 93T Portable
2 Endress+Hauser
Table of contents
Function and system design. . . . . . . . . . . . . . . . . . . . . 3
Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Sensor selection and arrangement . . . . . . . . . . . . . . . . . . . . . . . . . 5
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Operable flow range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Input signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Low flow cut off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Power supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Measuring unit electrical connection . . . . . . . . . . . . . . . . . . . . . . . 7
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Connecting cable (sensor/transmitter) . . . . . . . . . . . . . . . . . . . . . 7
Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Performance characteristics. . . . . . . . . . . . . . . . . . . . . 8
Reference operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Maximum measured error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Repeatability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Operating conditions: installation . . . . . . . . . . . . . . . . 9
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Inlet and outlet runs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Operating conditions: environment . . . . . . . . . . . . . . 11
Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Shock and vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . 11
Operating conditions: process . . . . . . . . . . . . . . . . . . 12
Medium temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Medium pressure range (nominal pressure) . . . . . . . . . . . . . . . . . 12
Pressure loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 13
Design, dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Language group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Certificates and approvals . . . . . . . . . . . . . . . . . . . . . 19
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
C-Tick mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Other standards and guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Ordering information. . . . . . . . . . . . . . . . . . . . . . . . . 19
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Device-specific accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Measuring principle-specific accessories . . . . . . . . . . . . . . . . . . . 20
Service-specific accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Registered trademarks. . . . . . . . . . . . . . . . . . . . . . . . 21
Proline Prosonic Flow 93T Portable
Endress+Hauser 3
Function and system design
Measuring principle The measuring system operates on the principle of transit time difference. In this measurement method,
acoustic (ultrasonic) signals are transmitted between two sensors. The signals are sent in both directions,
i.e. the sensor in question works as both a sound transmitter and a sound receiver.
As the propagation velocity of the waves is less when the waves travel against the direction of flow than along
the direction of flow, a transit time difference occurs. This transit time difference is directly proportional to the
flow velocity.
A0011479
Principle of the transit time difference measurement method
Q = v · A
a Sensor
b Sensor
Q Volume flow
v Flow velocity (v & t )
t Transit time difference (t = ta – tb)
A Pipe cross-sectional area
The measuring system calculates the volume flow of the fluid from the measured transit time difference and
the pipe cross-sectional area. In addition to measuring the transit time difference, the system simultaneously
measures the sound velocity of the fluid. This additional measured variable can be used to distinguish different
fluids or as a measure of product quality.
The measuring device can be configured onsite to suit the specific application using Quick Setup menus.
Measuring system The measuring system consists of one transmitter and two sensors.
The transmitter is used both to control the sensors and to prepare, process and evaluate the measuring signals,
and to convert the signals to a desired output variable.
The sensors work as sound transmitters and sound receivers. Depending on the application and version, the
sensors can be arranged for measurement via one or two traverses  ä 5.
b
a
Q
ta
tb
Proline Prosonic Flow 93T Portable
4 Endress+Hauser
Transmitter
Sensor/Sensor holders
Mounting accessories
The requisite mounting distances must be determined for the sensors. Information on the fluid, the pipe
material used and the exact pipe dimensions is needed to determine these values. The values for the sound
velocity of the following fluids, pipe materials and lining materials are stored in the transmitter:
If you are using fluids, pipe materials or lining materials other than those listed in the table, and you do not
have the corresponding sound velocities for these fluids/materials, you can use the DDU18 and DDU20
sensors to determine the values.
Prosonic Flow 93T Portable
For mounting in non-hazardous zone
A0011478
Prosonic Flow P Prosonic Flow P
DN 15 to 65 (½ to 2½")
Model 1
A0011483
DN 15 to 65 (½ to 2½")
Model 2
A0013504
DN 50 to 4000 (2 to 160")
A0013475
Fluid Pipe material Lining
• Water
• Sea water
• Distilled water
• Ammonia
• Alcohol
• Benzene
• Bromide
• Ethanol
• Glycol
• Kerosene
• Milk
• Methanol
• Toluene
• Lube oil
• Diesel
• Gasoline
• Carbon steel
• Cast iron
• Stainless steel
• Alloy C
• PVC
• PE
• LDPE
• HDPE
• GRP
• PVDF
• PA
• PP
• PTFE
• Glass pyrex
• Cement asbestos
• Mortar
• Rubber
• Tar Epoxy
DDU18
(sound velocity measurement)
DDU20
(wall thickness measurement)
Nominal diameter range: DN 50 to 3000 (2 to 120")
A0009784
Wall thickness range:
• Steel pipes: 1.2 to 50 mm (0.05 to 2.0")
• Plastic pipes: 4 to 15 mm (0.16 to 0.60")
(only suitable for PTFE and PE pipes to a certain extent)
A0013478
Proline Prosonic Flow 93T Portable
Endress+Hauser 5
Sensor selection and
arrangement
The sensors can be arranged in two ways:
• Mounting arrangement for measurement via one traverse:
the sensors are located on opposite sides of the pipe.
• Mounting arrangement for measurement via two traverses:
the sensors are located on the same side of the pipe.
A0001108
Sensor mounting arrangement
A Mounting arrangement for measurement via one traverse
B Mounting arrangement for measurement via two traverses
The number of traverses required depends on the sensor type, the nominal diameter and the thickness of the
pipe wall. We recommend the following types of mounting:
BA
Sensor Type Nominal Diameter Sensor Frequency Sensor ID Type of Mounting 1)
Prosonic Flow P
DN 15 to 65 (½ to 2½") 6 MHz P-CL-6F* 2 (or 1) traverses 4)
DN 50 to 65 (2 to 2½") 6 MHz (or 2 MHz)
P-CL-6F*
P-CL-2F*
2 (or 1) traverses 2)
DN 80 (3") 2 MHz P-CL-2F* 2 traverses
DN 100 to 300 (4 to 12") 2 MHz (or 1 MHz)
P-CL-2F*
P-CL-1F*
2 traverses 3)
DN 300 to 600 (12 to 24") 1 MHz (or 2 MHz)
P-CL-1F*
P-CL-2F*
2 traverses 3)
DN 650 to 4000 (26 to 160") 1 MHz (or 0.5 MHz)
P-CL-1F*
W-CL-05F*
1 traverse 3)
1) The installation of clamp-on sensors is principally recommended in the 2 traverse type installation. This type of
installation allows the easiest and most comfortable type of mounting and means that a system can also be mounted
even if the pipe can only be accessed from one side. However, in certain applications a 1 traverse installation may be
preferred. These include:
• Certain plastic pipes with wall thickness > 4 mm (0.16")
• Pipes made of composite materials such as GRP
• Lined pipes
• Applications with fluids with high acoustic damping
2)
If the pipe nominal diameter is small (DN 65 / 2½" and smaller), the sensor spacing with Prosonic Flow P can be too
small for two traverse installation using sensor P-CL-2F*. In this case, the 1 traverse type of installation must be used.
3)
0.5 MHz sensors (Prosonic Flow W) are also recommended for applications with composite material pipes such as
GRP and may be recommended for certain lined pipes, pipes with wall thickness > 10 mm (0.4"), or applications with
media with high acoustic damping. In addition, for these applications we principally recommend mounting the
W sensors in a 1 traverse configuration.
4)
6 MHz sensors for applications with flow velocity < 10 m/s.
Proline Prosonic Flow 93T Portable
6 Endress+Hauser
Input
Measured variable Flow velocity (transit time difference proportional to flow velocity)
Measuring range Typically v = 0 to 15 m/s (0 to 50 ft/s)
Operable flow range Over 150 : 1
Input signal Current input
• Galvanically isolated
• Passive: 0/4 to 20 mA, Ri < 150 , max. 30 V DC
• Terminal voltage: min. 2 V DC to max. 30 V DC
• Time constant selectable (0.05 to 100 s)
• Full scale value adjustable
• Temperature coefficient: typ. 0.002 % o.r./°C (o.r. = of reading)
• Resolution: 0.82 μA
Output
Output signal Current Output
• Active/Passive selectable
– Active 0/4 to 20 mA, Ri < 700 
– Passive 4 to 20 mA, 30VDC, Ri < 150 
• Full Scale adjustable
• Temperature Coefficient type 0.005 % o.r./°C (o.r. = of reading)
• Time Constant Selectable (0.05 to 100 s)
Data logger function
The device has a data logger function. The measured values can be stored in CSV format on an external
USB storage device (FAT 16/FAT 32). A recording cycle of between 1 and 99999 seconds can be selected.
USB storage devices with a maximum capacity greater than 2 GB should not be used. Approx. 130 bytes are
needed per recording. The standard supplied USB storage device has a maximum capacity of 1 GB.
The following values are stored:
• Time (dd.mm.yyyy hh:mm:ss)
• Flow
• Sound velocity
• Flow velocity
• Signal strength
• Signal to noise ratio
• Totalizer (1 to 3)
• System status
• 0/4 to 20 mA current input (flow rate and active current value)
Each recording is marked with the tag name and device-specific information, such as the serial number for example.
Site Manager function
Allows for storage of programmed sites (pipe data, sensor data, fluid data, etc.) on an eternal USB storage device.
Up to 20 sites can be stored.
Low flow cut off Switch points for low flow cutoff are selectable.
Galvanic isolation All circuits for inputs, outputs, and power supply are galvanically isolated from each other.
Proline Prosonic Flow 93T Portable
Endress+Hauser 7
Power supply
Measuring unit electrical
connection
A0011480
Connecting the transmitter
1 ON/OFF switch (press switch  3 seconds)
2 Current input connection
3 USB plug connection
4 Connecting cable connection (CH-DN, downstream)
5 Connecting cable connection (CH-UP, upstream)
6 FXA193/FXA291 modem connection
7 Charger connection (a selection of detachable plug adapters is available)
8 Current Output connection
Supply voltage Transmitter
Power unit
• 100 to 240 V AC, 47 to 63 Hz to Power Adapter (12 V DC, 2.5 A)
! Note!
Do not exceed 16V input voltage!
NiMH accumulator
• Operating time: at least 8 hours
• Charge time: approx. 3.6 hours
Sensor
Powered by the transmitter
Connecting cable
(sensor/transmitter)
Only use the connecting cables supplied by Endress+Hauser.
Different versions of the connecting cables are available  ä 20.
• Cable material: PTFE
• Cable lengths: 5 m (16.4 ft), 10 m (32.8 ft)
! Note!
To ensure correct measuring results, route the connecting cable well clear of electrical machines and switching
elements.
Potential equalization For potential equalization, no special measures are necessary.
DATA
I-IN
12V DC SERVICE CH-UP CH-DN
1 2 3
7 6 5 4
I-OUT
8
Proline Prosonic Flow 93T Portable
8 Endress+Hauser
Performance characteristics
Reference operating
conditions
• Fluid temperature: +20 to +30 °C
• Ambient temperature: +22 °C ± 2 K
• Warm-up period: 30 minutes
• Sensors and transmitter are grounded
• The measuring sensors are correctly installed
Maximum measured error The measured error depends on a number of factors. A distinction is made between the measured error of the
device (Prosonic Flow 93T = 0.5 % of the measured value) and an additional installation-specific measured
error (typically 1.5 % of the measured value) that is independent of the device.
The installation-specific measured error depends on the installation conditions on site, such as the nominal
diameter, wall thickness, real pipe geometry, fluid, etc.
The sum of the two measured errors is the measured error at the measuring point.
A0011347
Example of the measured error in a pipe with a nominal diameter DN > 200 (8")
a Measured error of the device (0.5 % o.r. ± 3 mm/s)
b Measured error due to installation conditions (typically 1.5 % o.r.)
c Measured error at the measuring point: 0.5 % o.r. ± 3 mm/s + 1.5 % o.r. = 2 % o.r. ± 3 mm/s
Measured error at the measuring point
The measured error at the measuring point is made up of the measured error of the device (0.5 % o.r.) and the
measured error resulting from the installation conditions on site. Given a flow velocity > 0.3 m/s (1 ft/s) and
a Reynolds number > 10000, the following are typical error limits:
0
0.5
2.0
3.5
%
m/s2 4 6 8 10 12
b
c
a
Nominal diameter Device error limits +
Installation-specific
error limits (typical)

Error limits at the measuring
point (typical)
DN 15 (½") ±0.5 % o.r. ± 5 mm/s + ±2.5 % o.r.  ±3 % o.r. ± 5 mm/s
DN 25 to 200 (1 to 8") ±0.5 % o.r. ± 7.5 mm/s + ±1.5 % o.r.  ±2 % o.r. ± 7.5 mm/s
> DN 200 (8") ±0.5 % o.r. ± 3 mm/s + ±1.5 % o.r.  ±2 % o.r. ± 3 mm/s
o.r. = of reading
Proline Prosonic Flow 93T Portable
Endress+Hauser 9
Measurement Report
If required, the device can be supplied with a factory measurement report. To certify the performance of the
device, a measurement is performed under reference conditions. Here, the sensors are mounted on a pipe with
a nominal diameter of DN 50 (2") or DN 100 (4") respectively.
The measurement report guarantees the following error limits of the device
[at a flow velocity > 0.3 m/s (1 ft/s) and a Reynolds number > 10000]:
Repeatability ±0.3 % for flow velocities > 0.3 m/s (1 ft/s)
Operating conditions: installation
Installation instructions Mounting location
Correct flow measurement is possible only if the pipe is full. It is preferable to install the sensors in a riser.
! Note!
Entrained air or gas bubbles in the measuring tube can result in an increase in measuring errors.
For this reason, avoid the following mounting locations:
• Highest point of a pipeline. Risk of air accumulating.
• Directly upstream of a free pipe outlet in a vertical pipe. Risk of partial pipe filling.
A0001103
Nominal diameter Guaranteed error limits of the device
DN 50 (2") ±0.5 % o.r. ± 5 mm/s
DN 100 (4") ±0.5 % o.r. ± 7.5 mm/s
o.r. = of reading
Proline Prosonic Flow 93T Portable
10 Endress+Hauser
Orientation
Vertical
Recommended orientation with upward direction of flow (View A). With this orientation, entrained solids will
sink and gases will rise away from the sensor when the fluid is stagnant. The piping can be completely drained
and protected against solids buildup.
Horizontal
In the recommended installation range in a horizontal installation position (View B), gas and air collections at
the pipe cover and problematic deposits at the bottom of the pipe have a smaller influence on measurement.
A0001105
A Recommended orientation with upward direction of flow
B Recommended installation range with horizontal orientation
C Recommended installation range max. 120°
Inlet and outlet runs If possible, install the sensor well clear of fittings such as valves, T-pieces, elbows, etc. Compliance with the
following inlet and outlet runs is required in order to ensure measuring accuracy.
A0013459
1 Valve (2/3 open)
2 Pump
3 Two pipe bends in different directions
A
B
C C
³ 15 x DN
³ 20 x DN
³ 20 x DN
³ 15 x DN
³ 3 x DN
1
2
3
Proline Prosonic Flow 93T Portable
Endress+Hauser 11
Operating conditions: environment
Ambient temperature range Transmitter
0 to +60 °C (+32 to +140 °F)
Prosonic Flow P sensor
DN 15 to 65 (½ to 2½")
• Standard: –40 to +100 °C (–40 to +212 °F)
• Optional: –40 to +150 °C (–40 to +302 °F)
DN 50 to 4000 (2 to 160")
• Standard: –40 to +80 °C (–40 to +176 °F)
• Optional: 0 to +170 °C (+32 to +338 °F)
DDU18 sensor (accessories: sound velocity measurement)
• Standard: –40 to +80 °C (–40 to +176 °F)
• Optional: 0 to +170 °C (+32 to +338 °F)
DDU20 sensor (accessories: wall thickness measurement)
–20 to +60 °C (–4 to +140 °F)
Connecting cable (sensor/transmitter)
–40 to +170 °C (–40 to +338 °F)
Storage temperature The storage temperature corresponds to the ambient temperature range.
Degree of protection Transmitter
IP 40
Sensor
IP 68 (NEMA 6P), connection IP 50
DDU18 sensor (accessories: sound velocity measurement)
IP 68 (NEMA 6P), connection IP 50
DDU20 sensor (accessories: wall thickness measurement)
IP 67 (NEMA 4X), connection IP 50
Shock and vibration resistance According to IEC 68-2-6
Electromagnetic compatibility
(EMC)
Electromagnetic compatibility (EMC requirements) according to IEC/EN 61326 "Emission to class A
requirements" and NAMUR Recommendation NE 21 and NE 43.
Proline Prosonic Flow 93T Portable
12 Endress+Hauser
Operating conditions: process
Medium temperature range Prosonic Flow P sensor
DN 15 to 65 (½ to 2½")
• Standard: –40 to +100 °C (–40 to +212 °F)
• Optional: –40 to +150 °C (–40 to +302 °F)
DN 50 to 4000 (2 to 160")
• Standard: –40 to +80 °C (–40 to +176 °F)
• Optional: 0 to +170 °C (+32 to +338 °F)
DDU18 sensor (accessories: sound velocity measurement)
• Standard: –40 to +80 °C (–40 to +176 °F)
• Optional: 0 to +170 °C (+32 to +338 °F)
DDU20 sensor (accessories: wall thickness measurement)
–10 to +60 °C (+14 to +140 °F)
Medium pressure range
(nominal pressure)
No pressure limitation, however perfect measurement requires that the static fluid pressure is higher than vapor
pressure.
Pressure loss There is no pressure loss.
Proline Prosonic Flow 93T Portable
Endress+Hauser 13
Mechanical construction
Design, dimensions Transmitter
A0011481
Dimensions in SI units
Dimensions in US units
Protective bag
The dimensions (length × width × height) of the protective bag for the transmitter are:
280 × 150 × 80 mm (11.0 × 5.90 × 3.15")
A B C
270 130 63
All dimensions in [mm]
A B C
10.6 5.12 2.48
All dimensions in [inch]
A
B C
Proline Prosonic Flow 93T Portable
14 Endress+Hauser
Prosonic Flow P sensor (DN 50 to 4000 / 2 to 160")
A0011401
Mounting arrangement for measurement via two traverses
Dimensions in SI units
Dimensions in US units
E
A
DB I
C
H
G
FA B C D E F G
56 62 145 111  58 max. 872 min. 0.5
H I
Depends on the measuring point conditions (pipe, fluid, etc.).
Dimension "H" can be determined:
• Via transmitter programming (Quick Setup or FieldCare)
• Online (Applicator)
Pipe outer diameter
All dimensions in [mm]
A B C D E F G
2.20 2.44 5.71 4.37  2.28 max. 34.3 min. 0.2
H I
Depends on the measuring point conditions (pipe, fluid, etc.).
Dimension "H" can be determined:
• Via transmitter programming (Quick Setup or FieldCare)
• Online (Applicator)
Pipe outer diameter
All dimensions in [inch]
Proline Prosonic Flow 93T Portable
Endress+Hauser 15
A0001155
Mounting arrangement for measurement via one traverse
Dimensions in SI units
Dimensions in US units
E
DH
A
B
G
C
F
A B C D E F
56 62 145 111  58 max. 872
G H
Depends on the measuring point conditions (pipe, fluid, etc.).
Dimension "G" can be determined:
• Via transmitter programming (Quick Setup or FieldCare)
• Online (Applicator)
Pipe outer diameter
All dimensions in [mm]
A B C D E F
2.20 2.44 5.71 4.37  2.28 max. 34.3
G H
Depends on the measuring point conditions (pipe, fluid, etc.).
Dimension "G" can be determined:
• Via transmitter programming (Quick Setup or FieldCare)
• Online (Applicator)
Pipe outer diameter
All dimensions in [inch]
Proline Prosonic Flow 93T Portable
16 Endress+Hauser
Prosonic Flow P sensor (DN 15 to 65 / ½ to 2½")
A0013505
Model 2
Dimensions in SI units
Dimensions in US units
B
A
C
DE
F
A B C (min./max.) D E F
285 110 210/255 35 75 110
All dimensions in [mm]
A B C (min./max.) D E F
11.2 4.33 8.27/10.0 1.38 2.95 4.33
All dimensions in [inch]
Proline Prosonic Flow 93T Portable
Endress+Hauser 17
Weight Transmitter
1.6 kg (3.53 lbs)
Sensor Prosonic Flow P
• DN 15 to 65 (½ to 2½") (incl. mounting material): 1.78 kg (3.9 lbs)
• DN 50 to 4000 (2 to 160") (incl. mounting material): 2.8 kg (6.2 lbs)
Sensor (accessories)
• Prosonic Flow DDU18 (incl. mounting material): 2.4 kg (5.3 lbs)
• Prosonic Flow DDU20 (incl. mounting material): 0.23 kg (0.5 lbs)
! Note!
Weight information without packaging material.
Materials Transmitter
Plastic
Sensor Prosonic Flow P
DN 15 to 65 (½ to 2½")
• Sensor holder: corrosion protected aluminum, stainless steel 1.4301/304
• Sensor housing: stainless steel 1.4301/304
• Sensor contact surfaces: chemically stable plastic
DN 50 to 4000 (2 to 160")
• Sensor holder: stainless steel 1.4308/CF-08
• Sensor housing: stainless steel 1.4301/304
• Strapping bands/bracket: textile or stainless steel 1.4301/304
• Sensor contact surfaces: chemically stable plastic
Sensor (accessories)
Prosonic Flow DDU18; Prosonic Flow DDU20
• Sensor holder: stainless steel 1.4308/CF-08
• Sensor housing: stainless steel 1.4301/304
• Strapping bands/bracket: textile or stainless steel 1.4301/304
• Sensor contact surfaces: chemically stable plastic
Connecting cable (sensor/transmitter)
PTFE connecting cable
• Cable sheath: PTFE
• Cable connector: stainless steel
Proline Prosonic Flow 93T Portable
18 Endress+Hauser
Human interface
Display elements • Liquid crystal display: illuminated, four lines each with 16 characters
• Custom configuration for presenting different measured values and status variables
Operating elements • Local operation with three optical keys
• Application specific Quick Setup menus for straightforward commissioning
Language group Language groups available for operation in different countries:
• Western Europe and America (WEA):
English, German, Spanish, Italian, French, Dutch and Portuguese
• Eastern Europe/Scandinavia (EES):
English, Russian, Polish, Norwegian, Finnish, Swedish and Czech
• South and Eastern Asia (SEA):
English, Japanese, Indonesian
• China (CN):
English, Chinese
You can change the language group via the FieldCare operating program.
Remote operation Operation via FieldCare, with:
• Option of loading or saving preprogrammed measuring points
• Configuration logging
• Measured value visualization
Proline Prosonic Flow 93T Portable
Endress+Hauser 19
Certificates and approvals
CE mark The measuring system is in conformity with the statutory requirements of the EC Directives.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
C-Tick mark The measuring system is in conformity with the EMC requirements of the "Australian Communications and
Media Authority (ACMA)".
Other standards and
guidelines
• EN 60529
Degrees of protection provided by enclosures (IP code).
• EN 61010-1
Safety requirements for electrical equipment for measurement, control and laboratory use.
• IEC/EN 61326
"Emission in accordance with Class A requirements".
Electromagnetic compatibility (EMC requirements).
• ANSI/ISA-S82.01
Safety Standard for Electrical and Electronic Test, Measuring, Controlling and
Related Equipment - General Requirements. Pollution Degree 2, Installation Category II.
• CAN/CSA-C22.2 No. 1010.1-92
Safety Requirements for Electrical Equipment for Measurement and Control and Laboratory Use.
Pollution degree 2.
Ordering information
The Endress+Hauser service organization can provide detailed ordering information and information on the
order codes on request.
Proline Prosonic Flow 93T Portable
20 Endress+Hauser
Accessories
Various accessories, which can be ordered separately from Endress+Hauser, are available for the transmitter
and the sensor. The Endress+Hauser service organization can provide detailed information on the order codes
on request.
Device-specific accessories
Measuring principle-specific
accessories
Accessory Description Order code
Sensor P
(DN 15 to 65 / ½ to 2½")
Clamp-on version
DN 15 to 65 (½ to 2½")
• –40 to +100 °C (–40 to +212 °F)
• –40 to +150 °C (–40 to +302 °F)
DK9PT - 1A
DK9PT - 2A
Sensor P
(DN 50 to 4000 / 2 to 160")
Clamp-on version
DN 50 to 300 (2 to 12")
• –40 to +80 °C (–40 to +176 °F)
• –40 to +170 °C (–40 to +338 °F)
DK9PT - BA
DK9PT - FA
DN 100 to 4000 (4 to 160")
• –40 to +80 °C (–40 to +176 °F)
• 0 to +170 °C (+32 to +338 °F)
DK9PT - AA
DK9PT - EA
Sensor DDU18 Sensor for sound velocity measurement
–40 to +80 °C (–40 to +176 °F)
0 to +170 °C (+32 to +338 °F)
50091703
50091704
Sensor DDU20 Sensor for wall thickness measurement.
• –20 to +60 °C (–4 to +140 °F) 71112217
Accessory Description Order code
Sensor holder set • Prosonic Flow P (DN 15 to 65 / ½ to 2½"):
Sensor holder, clamp-on version DK9SH - 2
• Prosonic Flow P (DN 50 to 4000 / 2 to 160")
– Sensor holder, fixed retaining nut, clamp-on version
– Sensor holder, removable retaining nut, clamp-on version
DK9SH - A
DK9SH - B
Clamp-on installation set • DN < 1500 (60") (textile strapping)
• DN  1500 (60") (textile strapping)
• DN 50 to 300 (2 to 12"): 0 to +170 °C (+32 to +338 °F)
(stainless steel strapping)
DK9ZT - D
DK9ZT - E
DK9ZT - B
Connecting cable 5 m (16.4 ft) sensor cable, PTFE, –40 to +170 °C (–40 to +338 °F)
10 m (32.8 ft) sensor cable, PTFE, –40 to +170 °C (–40 to +338 °F)
DK9SS - CEE
DK9SS - CEF
Acoustic coupling fluid • Coupling fluid: –40 to +170 °C (–40 to +338 °F), standard,
high temperature
• Adhesive coupling fluid: –40 to +80 °C (–40 to +176 °F)
• Water-soluble coupling fluid: –20 to +80 °C (–4 to +176 °F)
• Coupling fluid DDU20: –20 to +60 °C (–4 to +140 °F)
• Coupling fluid: –40 to +100 °C (–40 to +212 °F), standard,
type MBG2000
DK9CM - 2
DK9CM - 3
DK9CM - 4
DK9CM - 6
DK9CM - 7
Proline Prosonic Flow 93T Portable
Endress+Hauser 21
Service-specific accessories
Documentation
• Flow measurement (FA005D/06)
• Operating Instructions for Prosonic Flow 93T Portable (BA136D/06)
Registered trademarks
FieldCare®, Fieldcheck®
Registered or registration-pending trademarks of Endress+Hauser Flowtec AG, Reinach, CH
Accessory Description Order code
Applicator Software for selecting and planning flowmeters.
The Applicator can be downloaded from the Internet or ordered on
CD-ROM for installation on a local PC.
Contact your Endress+Hauser representative for more information.
DXA80 - *
Fieldcheck Tester/simulator for testing flowmeters in the field.
When used in conjunction with the "FieldCare" software package,
test results can be imported into a database, printed out and used for
official certification.
Contact your Endress+Hauser representative for more information.
50098801
FieldCare FieldCare is Endress+Hauser's FDT-based plant asset management
tool. It can configure all intelligent field units in your system and
helps you manage them.
By using the status information, it is also a simple but effective way
of checking their status and condition.
See the product
page on the
Endress+Hauser
website:
www.endress.com
FXA193 Service interface from the measuring device to the PC for operation
via FieldCare.
FXA193 - *
Communication cable Communication cable for connecting the Prosonic Flow 93T
transmitter to the FXA193 service interface.
DK9ZT - I
FXA291 Service interface from the measuring device to the PC for operation
via FieldCare.
FXA291 - *
Communication cable Communication cable for connecting the Prosonic Flow 93T
transmitter to the FXA291 service interface.
DK9ZT - 8
Instruments International
Endress+Hauser
Instruments International AG
Kaegenstrasse 2
4153 Reinach
Switzerland
Tel.+41 61 715 81 00
Fax+41 61 715 25 00
www.endress.com
info@ii.endress.com
TI00085D/06/EN/13.11
71136634
FM+SGML6.0 ProMoDo

Contenu connexe

Tendances

2. station transformer 100 mva 230kv-datasheet revb
2. station transformer 100 mva 230kv-datasheet revb2. station transformer 100 mva 230kv-datasheet revb
2. station transformer 100 mva 230kv-datasheet revb
Van Phuong Pham
 

Tendances (20)

NAPS Tank Grounding Lightning and Static Protection
NAPS Tank Grounding Lightning and Static ProtectionNAPS Tank Grounding Lightning and Static Protection
NAPS Tank Grounding Lightning and Static Protection
 
2. station transformer 100 mva 230kv-datasheet revb
2. station transformer 100 mva 230kv-datasheet revb2. station transformer 100 mva 230kv-datasheet revb
2. station transformer 100 mva 230kv-datasheet revb
 
311l testing procedure
311l testing procedure311l testing procedure
311l testing procedure
 
Tube expansion
Tube expansionTube expansion
Tube expansion
 
Piping and Insruementaion Diagrams
Piping and Insruementaion DiagramsPiping and Insruementaion Diagrams
Piping and Insruementaion Diagrams
 
Heat Exchanger Inspection.pdf
Heat Exchanger Inspection.pdfHeat Exchanger Inspection.pdf
Heat Exchanger Inspection.pdf
 
178680732 pipe-hanger-design
178680732 pipe-hanger-design178680732 pipe-hanger-design
178680732 pipe-hanger-design
 
Pipe Basics and Formulas
Pipe Basics and  FormulasPipe Basics and  Formulas
Pipe Basics and Formulas
 
Inspection of Heat exchanger .pdf
Inspection of Heat exchanger .pdfInspection of Heat exchanger .pdf
Inspection of Heat exchanger .pdf
 
LEVEL MEASUREMENT: DIRECT METHOD
LEVEL MEASUREMENT: DIRECT METHODLEVEL MEASUREMENT: DIRECT METHOD
LEVEL MEASUREMENT: DIRECT METHOD
 
Valves pipe fittings
Valves pipe fittingsValves pipe fittings
Valves pipe fittings
 
Boiler Process Instrumentation and controls
Boiler Process Instrumentation and controlsBoiler Process Instrumentation and controls
Boiler Process Instrumentation and controls
 
Heat recovery steam generator
Heat recovery steam generatorHeat recovery steam generator
Heat recovery steam generator
 
Fuses vs. Circuit Breakers
Fuses vs. Circuit BreakersFuses vs. Circuit Breakers
Fuses vs. Circuit Breakers
 
ARMACO STANDARD
ARMACO STANDARDARMACO STANDARD
ARMACO STANDARD
 
A Presentation on Field Instrumentation.
A Presentation on Field Instrumentation.A Presentation on Field Instrumentation.
A Presentation on Field Instrumentation.
 
Steel stacks guide
Steel stacks guideSteel stacks guide
Steel stacks guide
 
I&C Technical Note
I&C Technical NoteI&C Technical Note
I&C Technical Note
 
Asmesectionix
Asmesectionix Asmesectionix
Asmesectionix
 
Heat tracing ppt
Heat tracing pptHeat tracing ppt
Heat tracing ppt
 

Similaire à Ultrasonic flowmeter-Clamp on flow measurement

Similaire à Ultrasonic flowmeter-Clamp on flow measurement (20)

Ultrasonic flowmeter-Drinking water and process water
Ultrasonic flowmeter-Drinking water and process waterUltrasonic flowmeter-Drinking water and process water
Ultrasonic flowmeter-Drinking water and process water
 
Proline prosonic flow 91 w endress+hauser datasheet-ultrasonic flowmeter
Proline prosonic flow 91 w endress+hauser datasheet-ultrasonic flowmeterProline prosonic flow 91 w endress+hauser datasheet-ultrasonic flowmeter
Proline prosonic flow 91 w endress+hauser datasheet-ultrasonic flowmeter
 
Ultrasonic flowmeter- Drinking water, wastewater
Ultrasonic flowmeter- Drinking water, wastewaterUltrasonic flowmeter- Drinking water, wastewater
Ultrasonic flowmeter- Drinking water, wastewater
 
Ultrasonic flowmeter-Chemical or process applications
Ultrasonic flowmeter-Chemical or process applicationsUltrasonic flowmeter-Chemical or process applications
Ultrasonic flowmeter-Chemical or process applications
 
Ultrasonic flowmeter-Proline Prosonic Flow 92F
Ultrasonic flowmeter-Proline Prosonic Flow 92FUltrasonic flowmeter-Proline Prosonic Flow 92F
Ultrasonic flowmeter-Proline Prosonic Flow 92F
 
Electromagnetic flowmeter - Proline Promag 50D
Electromagnetic flowmeter - Proline Promag 50DElectromagnetic flowmeter - Proline Promag 50D
Electromagnetic flowmeter - Proline Promag 50D
 
Ga dat cam bien
Ga dat cam bien Ga dat cam bien
Ga dat cam bien
 
Electromagnetic flowmeter - Proline Promag 10H
Electromagnetic flowmeter - Proline Promag 10HElectromagnetic flowmeter - Proline Promag 10H
Electromagnetic flowmeter - Proline Promag 10H
 
Proline Promag 50L-Electromagnetic Flowmeter
Proline Promag 50L-Electromagnetic FlowmeterProline Promag 50L-Electromagnetic Flowmeter
Proline Promag 50L-Electromagnetic Flowmeter
 
Proline promag 10 l endress+hauser datasheet-electromagnetic flowmeter
Proline promag 10 l endress+hauser datasheet-electromagnetic flowmeterProline promag 10 l endress+hauser datasheet-electromagnetic flowmeter
Proline promag 10 l endress+hauser datasheet-electromagnetic flowmeter
 
Proline Promag 10L-Electromagnetic Flowmeter
Proline Promag 10L-Electromagnetic FlowmeterProline Promag 10L-Electromagnetic Flowmeter
Proline Promag 10L-Electromagnetic Flowmeter
 
Proline promag 10 p endress+hauser datasheet-electromagnetic flowmeter
Proline promag 10 p endress+hauser datasheet-electromagnetic flowmeterProline promag 10 p endress+hauser datasheet-electromagnetic flowmeter
Proline promag 10 p endress+hauser datasheet-electromagnetic flowmeter
 
Proline Promag 10P-Electromagnetic Flowmeter
Proline Promag 10P-Electromagnetic FlowmeterProline Promag 10P-Electromagnetic Flowmeter
Proline Promag 10P-Electromagnetic Flowmeter
 
Dosimag. Electromagnetic Flow Measuring System
Dosimag. Electromagnetic Flow Measuring SystemDosimag. Electromagnetic Flow Measuring System
Dosimag. Electromagnetic Flow Measuring System
 
Proline promag 50 l endress+hauser datasheet-electromagnetic flowmeter
Proline promag 50 l endress+hauser datasheet-electromagnetic flowmeterProline promag 50 l endress+hauser datasheet-electromagnetic flowmeter
Proline promag 50 l endress+hauser datasheet-electromagnetic flowmeter
 
Proline t mass b 150-endress+hauser datasheet-thermal mass flow measuring system
Proline t mass b 150-endress+hauser datasheet-thermal mass flow measuring systemProline t mass b 150-endress+hauser datasheet-thermal mass flow measuring system
Proline t mass b 150-endress+hauser datasheet-thermal mass flow measuring system
 
Ultrasonic flowmeter-Drinking water, wastewater and process water.
Ultrasonic flowmeter-Drinking water, wastewater and process water.Ultrasonic flowmeter-Drinking water, wastewater and process water.
Ultrasonic flowmeter-Drinking water, wastewater and process water.
 
Prosonic flow 91 wa1 clamp on endress+hauser datasheet-ultrasonic flowmeter
Prosonic flow 91 wa1 clamp on endress+hauser datasheet-ultrasonic flowmeterProsonic flow 91 wa1 clamp on endress+hauser datasheet-ultrasonic flowmeter
Prosonic flow 91 wa1 clamp on endress+hauser datasheet-ultrasonic flowmeter
 
Electromagnetic flowmeter - Proline Promag 55H
Electromagnetic flowmeter - Proline Promag 55HElectromagnetic flowmeter - Proline Promag 55H
Electromagnetic flowmeter - Proline Promag 55H
 
Flowmeter Promag 10W-Electromagnetic-Water and Waste Water
Flowmeter Promag 10W-Electromagnetic-Water and Waste WaterFlowmeter Promag 10W-Electromagnetic-Water and Waste Water
Flowmeter Promag 10W-Electromagnetic-Water and Waste Water
 

Plus de Edress Hauser: Flow Meter, Level, Pressure, Temperature

Plus de Edress Hauser: Flow Meter, Level, Pressure, Temperature (20)

Liquiphant M Density and Density Computer FML621
Liquiphant M Density and Density Computer FML621Liquiphant M Density and Density Computer FML621
Liquiphant M Density and Density Computer FML621
 
Microwave barrier- Soliwave FQR56/FDR56
Microwave barrier- Soliwave FQR56/FDR56Microwave barrier- Soliwave FQR56/FDR56
Microwave barrier- Soliwave FQR56/FDR56
 
Microwave barrier-Soliwave M FQR50 / FDR50
Microwave barrier-Soliwave M FQR50 / FDR50Microwave barrier-Soliwave M FQR50 / FDR50
Microwave barrier-Soliwave M FQR50 / FDR50
 
Level Limit Switch-Soliswitch FTE31
Level Limit Switch-Soliswitch FTE31Level Limit Switch-Soliswitch FTE31
Level Limit Switch-Soliswitch FTE31
 
Level limit switch-Soliswitch FTE30
Level limit switch-Soliswitch FTE30Level limit switch-Soliswitch FTE30
Level limit switch-Soliswitch FTE30
 
Flow indicator for bulk solids-Solimotion FTR20
Flow indicator for bulk solids-Solimotion FTR20Flow indicator for bulk solids-Solimotion FTR20
Flow indicator for bulk solids-Solimotion FTR20
 
Level measurement with Prothermo NMT532
Level measurement with Prothermo NMT532 Level measurement with Prothermo NMT532
Level measurement with Prothermo NMT532
 
High accuracy liquid level measurement-Proservo NMS5
High accuracy liquid level measurement-Proservo NMS5High accuracy liquid level measurement-Proservo NMS5
High accuracy liquid level measurement-Proservo NMS5
 
Conductive Limit Detection-Rod Probe 11263
Conductive Limit Detection-Rod Probe 11263Conductive Limit Detection-Rod Probe 11263
Conductive Limit Detection-Rod Probe 11263
 
FTW360 compact pump protector
FTW360 compact pump protectorFTW360 compact pump protector
FTW360 compact pump protector
 
Conductive-Point level switch for multiple point
Conductive-Point level switch for multiple pointConductive-Point level switch for multiple point
Conductive-Point level switch for multiple point
 
Level limit switch compact design-Liquiphant T FTL20H
Level limit switch compact design-Liquiphant T FTL20HLevel limit switch compact design-Liquiphant T FTL20H
Level limit switch compact design-Liquiphant T FTL20H
 
Vibronic-Point level switch for all kinds of liquids
Vibronic-Point level switch for all kinds of liquidsVibronic-Point level switch for all kinds of liquids
Vibronic-Point level switch for all kinds of liquids
 
Vibronic-Point level switch-Liquiphant M FTL51C
Vibronic-Point level switch-Liquiphant M FTL51CVibronic-Point level switch-Liquiphant M FTL51C
Vibronic-Point level switch-Liquiphant M FTL51C
 
Level limit switch for liquids-Liquiphant T FTL20
Level limit switch for liquids-Liquiphant T FTL20Level limit switch for liquids-Liquiphant T FTL20
Level limit switch for liquids-Liquiphant T FTL20
 
Radiometric measuring technology-Gammapilot FTG20
Radiometric measuring technology-Gammapilot FTG20Radiometric measuring technology-Gammapilot FTG20
Radiometric measuring technology-Gammapilot FTG20
 
Differential pressure measurement-Level transmiter
Differential pressure measurement-Level transmiterDifferential pressure measurement-Level transmiter
Differential pressure measurement-Level transmiter
 
Hydrostatic Level Measurement-Deltapilot S DB50/50L/51/52/53
Hydrostatic Level Measurement-Deltapilot S DB50/50L/51/52/53Hydrostatic Level Measurement-Deltapilot S DB50/50L/51/52/53
Hydrostatic Level Measurement-Deltapilot S DB50/50L/51/52/53
 
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
 
Capacitance level measurement-Liquicap M FMI51, FMI52
Capacitance level measurement-Liquicap M FMI51, FMI52Capacitance level measurement-Liquicap M FMI51, FMI52
Capacitance level measurement-Liquicap M FMI51, FMI52
 

Dernier

Challenges and Opportunities: A Qualitative Study on Tax Compliance in Pakistan
Challenges and Opportunities: A Qualitative Study on Tax Compliance in PakistanChallenges and Opportunities: A Qualitative Study on Tax Compliance in Pakistan
Challenges and Opportunities: A Qualitative Study on Tax Compliance in Pakistan
vineshkumarsajnani12
 
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
daisycvs
 

Dernier (20)

Organizational Transformation Lead with Culture
Organizational Transformation Lead with CultureOrganizational Transformation Lead with Culture
Organizational Transformation Lead with Culture
 
CROSS CULTURAL NEGOTIATION BY PANMISEM NS
CROSS CULTURAL NEGOTIATION BY PANMISEM NSCROSS CULTURAL NEGOTIATION BY PANMISEM NS
CROSS CULTURAL NEGOTIATION BY PANMISEM NS
 
QSM Chap 10 Service Culture in Tourism and Hospitality Industry.pptx
QSM Chap 10 Service Culture in Tourism and Hospitality Industry.pptxQSM Chap 10 Service Culture in Tourism and Hospitality Industry.pptx
QSM Chap 10 Service Culture in Tourism and Hospitality Industry.pptx
 
Putting the SPARK into Virtual Training.pptx
Putting the SPARK into Virtual Training.pptxPutting the SPARK into Virtual Training.pptx
Putting the SPARK into Virtual Training.pptx
 
GUWAHATI 💋 Call Girl 9827461493 Call Girls in Escort service book now
GUWAHATI 💋 Call Girl 9827461493 Call Girls in  Escort service book nowGUWAHATI 💋 Call Girl 9827461493 Call Girls in  Escort service book now
GUWAHATI 💋 Call Girl 9827461493 Call Girls in Escort service book now
 
HomeRoots Pitch Deck | Investor Insights | April 2024
HomeRoots Pitch Deck | Investor Insights | April 2024HomeRoots Pitch Deck | Investor Insights | April 2024
HomeRoots Pitch Deck | Investor Insights | April 2024
 
Falcon Invoice Discounting: The best investment platform in india for investors
Falcon Invoice Discounting: The best investment platform in india for investorsFalcon Invoice Discounting: The best investment platform in india for investors
Falcon Invoice Discounting: The best investment platform in india for investors
 
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDINGParadip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
 
Buy gmail accounts.pdf buy Old Gmail Accounts
Buy gmail accounts.pdf buy Old Gmail AccountsBuy gmail accounts.pdf buy Old Gmail Accounts
Buy gmail accounts.pdf buy Old Gmail Accounts
 
Falcon Invoice Discounting: Unlock Your Business Potential
Falcon Invoice Discounting: Unlock Your Business PotentialFalcon Invoice Discounting: Unlock Your Business Potential
Falcon Invoice Discounting: Unlock Your Business Potential
 
Cannabis Legalization World Map: 2024 Updated
Cannabis Legalization World Map: 2024 UpdatedCannabis Legalization World Map: 2024 Updated
Cannabis Legalization World Map: 2024 Updated
 
Berhampur CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Berhampur CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDINGBerhampur CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Berhampur CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
 
Challenges and Opportunities: A Qualitative Study on Tax Compliance in Pakistan
Challenges and Opportunities: A Qualitative Study on Tax Compliance in PakistanChallenges and Opportunities: A Qualitative Study on Tax Compliance in Pakistan
Challenges and Opportunities: A Qualitative Study on Tax Compliance in Pakistan
 
PHX May 2024 Corporate Presentation Final
PHX May 2024 Corporate Presentation FinalPHX May 2024 Corporate Presentation Final
PHX May 2024 Corporate Presentation Final
 
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
 
How to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League CityHow to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League City
 
Kalyan Call Girl 98350*37198 Call Girls in Escort service book now
Kalyan Call Girl 98350*37198 Call Girls in Escort service book nowKalyan Call Girl 98350*37198 Call Girls in Escort service book now
Kalyan Call Girl 98350*37198 Call Girls in Escort service book now
 
Marel Q1 2024 Investor Presentation from May 8, 2024
Marel Q1 2024 Investor Presentation from May 8, 2024Marel Q1 2024 Investor Presentation from May 8, 2024
Marel Q1 2024 Investor Presentation from May 8, 2024
 
Falcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business GrowthFalcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business Growth
 
Phases of Negotiation .pptx
 Phases of Negotiation .pptx Phases of Negotiation .pptx
Phases of Negotiation .pptx
 

Ultrasonic flowmeter-Clamp on flow measurement

  • 1. TI00085D/06/EN/13.11 71136634 Technical Information Proline Prosonic Flow 93T Portable Portable ultrasonic flow measuring system Volume flow measurement of liquids Applications The sensors are perfectly suited for the non-contact measurement of pure or slightly contaminated liquids, regardless of the pressure or electrical conductivity. • Ideal solution for temporary use everywhere precise measurement or verification is required • Particularly suitable for retrofitting, monitoring and verifying measuring points • Suitable for pipe diameters from DN 15 to 4000 (½ to 160") • Suitable for fluid temperatures ranging from –40 to +170 °C (–40 to +338 °F) • Can be used with all metal and plastic pipes lined or unlined and with composite pipes • Ideal solution for all applications with sound- conducting liquids, e.g. water, wastewater, oils, solvents, acids, hydrocarbons and chemicals Features and benefits The Prosonic Flow ultrasonic clamp-on system allows accurate and cost-effective flow measurement from outside the pipe and without the need to interrupt the process. The flow measurement is bidirectional and causes no pressure loss. • Easy, safe and menu-guided sensor mounting ensures precise measuring results • Easy and safe commissioning via Quick Setup menus • Automatic frequency scan for optimized installation and maximum measuring performance • Current input for parallel data acquisition or for verifying other devices • Current output active or passive • Remote configuration and measured value display using Endress+Hauser's FieldCare software • Integrated data logger/site manager • Easy data transfer via USB stick without additional software
  • 2. Proline Prosonic Flow 93T Portable 2 Endress+Hauser Table of contents Function and system design. . . . . . . . . . . . . . . . . . . . . 3 Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Sensor selection and arrangement . . . . . . . . . . . . . . . . . . . . . . . . . 5 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Operable flow range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Input signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Low flow cut off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Power supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Measuring unit electrical connection . . . . . . . . . . . . . . . . . . . . . . . 7 Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Connecting cable (sensor/transmitter) . . . . . . . . . . . . . . . . . . . . . 7 Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Performance characteristics. . . . . . . . . . . . . . . . . . . . . 8 Reference operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Maximum measured error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Repeatability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Operating conditions: installation . . . . . . . . . . . . . . . . 9 Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Inlet and outlet runs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Operating conditions: environment . . . . . . . . . . . . . . 11 Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Shock and vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . 11 Operating conditions: process . . . . . . . . . . . . . . . . . . 12 Medium temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Medium pressure range (nominal pressure) . . . . . . . . . . . . . . . . . 12 Pressure loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 13 Design, dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Language group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Certificates and approvals . . . . . . . . . . . . . . . . . . . . . 19 CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 C-Tick mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Other standards and guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Ordering information. . . . . . . . . . . . . . . . . . . . . . . . . 19 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Device-specific accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Measuring principle-specific accessories . . . . . . . . . . . . . . . . . . . 20 Service-specific accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Registered trademarks. . . . . . . . . . . . . . . . . . . . . . . . 21
  • 3. Proline Prosonic Flow 93T Portable Endress+Hauser 3 Function and system design Measuring principle The measuring system operates on the principle of transit time difference. In this measurement method, acoustic (ultrasonic) signals are transmitted between two sensors. The signals are sent in both directions, i.e. the sensor in question works as both a sound transmitter and a sound receiver. As the propagation velocity of the waves is less when the waves travel against the direction of flow than along the direction of flow, a transit time difference occurs. This transit time difference is directly proportional to the flow velocity. A0011479 Principle of the transit time difference measurement method Q = v · A a Sensor b Sensor Q Volume flow v Flow velocity (v & t ) t Transit time difference (t = ta – tb) A Pipe cross-sectional area The measuring system calculates the volume flow of the fluid from the measured transit time difference and the pipe cross-sectional area. In addition to measuring the transit time difference, the system simultaneously measures the sound velocity of the fluid. This additional measured variable can be used to distinguish different fluids or as a measure of product quality. The measuring device can be configured onsite to suit the specific application using Quick Setup menus. Measuring system The measuring system consists of one transmitter and two sensors. The transmitter is used both to control the sensors and to prepare, process and evaluate the measuring signals, and to convert the signals to a desired output variable. The sensors work as sound transmitters and sound receivers. Depending on the application and version, the sensors can be arranged for measurement via one or two traverses  ä 5. b a Q ta tb
  • 4. Proline Prosonic Flow 93T Portable 4 Endress+Hauser Transmitter Sensor/Sensor holders Mounting accessories The requisite mounting distances must be determined for the sensors. Information on the fluid, the pipe material used and the exact pipe dimensions is needed to determine these values. The values for the sound velocity of the following fluids, pipe materials and lining materials are stored in the transmitter: If you are using fluids, pipe materials or lining materials other than those listed in the table, and you do not have the corresponding sound velocities for these fluids/materials, you can use the DDU18 and DDU20 sensors to determine the values. Prosonic Flow 93T Portable For mounting in non-hazardous zone A0011478 Prosonic Flow P Prosonic Flow P DN 15 to 65 (½ to 2½") Model 1 A0011483 DN 15 to 65 (½ to 2½") Model 2 A0013504 DN 50 to 4000 (2 to 160") A0013475 Fluid Pipe material Lining • Water • Sea water • Distilled water • Ammonia • Alcohol • Benzene • Bromide • Ethanol • Glycol • Kerosene • Milk • Methanol • Toluene • Lube oil • Diesel • Gasoline • Carbon steel • Cast iron • Stainless steel • Alloy C • PVC • PE • LDPE • HDPE • GRP • PVDF • PA • PP • PTFE • Glass pyrex • Cement asbestos • Mortar • Rubber • Tar Epoxy DDU18 (sound velocity measurement) DDU20 (wall thickness measurement) Nominal diameter range: DN 50 to 3000 (2 to 120") A0009784 Wall thickness range: • Steel pipes: 1.2 to 50 mm (0.05 to 2.0") • Plastic pipes: 4 to 15 mm (0.16 to 0.60") (only suitable for PTFE and PE pipes to a certain extent) A0013478
  • 5. Proline Prosonic Flow 93T Portable Endress+Hauser 5 Sensor selection and arrangement The sensors can be arranged in two ways: • Mounting arrangement for measurement via one traverse: the sensors are located on opposite sides of the pipe. • Mounting arrangement for measurement via two traverses: the sensors are located on the same side of the pipe. A0001108 Sensor mounting arrangement A Mounting arrangement for measurement via one traverse B Mounting arrangement for measurement via two traverses The number of traverses required depends on the sensor type, the nominal diameter and the thickness of the pipe wall. We recommend the following types of mounting: BA Sensor Type Nominal Diameter Sensor Frequency Sensor ID Type of Mounting 1) Prosonic Flow P DN 15 to 65 (½ to 2½") 6 MHz P-CL-6F* 2 (or 1) traverses 4) DN 50 to 65 (2 to 2½") 6 MHz (or 2 MHz) P-CL-6F* P-CL-2F* 2 (or 1) traverses 2) DN 80 (3") 2 MHz P-CL-2F* 2 traverses DN 100 to 300 (4 to 12") 2 MHz (or 1 MHz) P-CL-2F* P-CL-1F* 2 traverses 3) DN 300 to 600 (12 to 24") 1 MHz (or 2 MHz) P-CL-1F* P-CL-2F* 2 traverses 3) DN 650 to 4000 (26 to 160") 1 MHz (or 0.5 MHz) P-CL-1F* W-CL-05F* 1 traverse 3) 1) The installation of clamp-on sensors is principally recommended in the 2 traverse type installation. This type of installation allows the easiest and most comfortable type of mounting and means that a system can also be mounted even if the pipe can only be accessed from one side. However, in certain applications a 1 traverse installation may be preferred. These include: • Certain plastic pipes with wall thickness > 4 mm (0.16") • Pipes made of composite materials such as GRP • Lined pipes • Applications with fluids with high acoustic damping 2) If the pipe nominal diameter is small (DN 65 / 2½" and smaller), the sensor spacing with Prosonic Flow P can be too small for two traverse installation using sensor P-CL-2F*. In this case, the 1 traverse type of installation must be used. 3) 0.5 MHz sensors (Prosonic Flow W) are also recommended for applications with composite material pipes such as GRP and may be recommended for certain lined pipes, pipes with wall thickness > 10 mm (0.4"), or applications with media with high acoustic damping. In addition, for these applications we principally recommend mounting the W sensors in a 1 traverse configuration. 4) 6 MHz sensors for applications with flow velocity < 10 m/s.
  • 6. Proline Prosonic Flow 93T Portable 6 Endress+Hauser Input Measured variable Flow velocity (transit time difference proportional to flow velocity) Measuring range Typically v = 0 to 15 m/s (0 to 50 ft/s) Operable flow range Over 150 : 1 Input signal Current input • Galvanically isolated • Passive: 0/4 to 20 mA, Ri < 150 , max. 30 V DC • Terminal voltage: min. 2 V DC to max. 30 V DC • Time constant selectable (0.05 to 100 s) • Full scale value adjustable • Temperature coefficient: typ. 0.002 % o.r./°C (o.r. = of reading) • Resolution: 0.82 μA Output Output signal Current Output • Active/Passive selectable – Active 0/4 to 20 mA, Ri < 700  – Passive 4 to 20 mA, 30VDC, Ri < 150  • Full Scale adjustable • Temperature Coefficient type 0.005 % o.r./°C (o.r. = of reading) • Time Constant Selectable (0.05 to 100 s) Data logger function The device has a data logger function. The measured values can be stored in CSV format on an external USB storage device (FAT 16/FAT 32). A recording cycle of between 1 and 99999 seconds can be selected. USB storage devices with a maximum capacity greater than 2 GB should not be used. Approx. 130 bytes are needed per recording. The standard supplied USB storage device has a maximum capacity of 1 GB. The following values are stored: • Time (dd.mm.yyyy hh:mm:ss) • Flow • Sound velocity • Flow velocity • Signal strength • Signal to noise ratio • Totalizer (1 to 3) • System status • 0/4 to 20 mA current input (flow rate and active current value) Each recording is marked with the tag name and device-specific information, such as the serial number for example. Site Manager function Allows for storage of programmed sites (pipe data, sensor data, fluid data, etc.) on an eternal USB storage device. Up to 20 sites can be stored. Low flow cut off Switch points for low flow cutoff are selectable. Galvanic isolation All circuits for inputs, outputs, and power supply are galvanically isolated from each other.
  • 7. Proline Prosonic Flow 93T Portable Endress+Hauser 7 Power supply Measuring unit electrical connection A0011480 Connecting the transmitter 1 ON/OFF switch (press switch  3 seconds) 2 Current input connection 3 USB plug connection 4 Connecting cable connection (CH-DN, downstream) 5 Connecting cable connection (CH-UP, upstream) 6 FXA193/FXA291 modem connection 7 Charger connection (a selection of detachable plug adapters is available) 8 Current Output connection Supply voltage Transmitter Power unit • 100 to 240 V AC, 47 to 63 Hz to Power Adapter (12 V DC, 2.5 A) ! Note! Do not exceed 16V input voltage! NiMH accumulator • Operating time: at least 8 hours • Charge time: approx. 3.6 hours Sensor Powered by the transmitter Connecting cable (sensor/transmitter) Only use the connecting cables supplied by Endress+Hauser. Different versions of the connecting cables are available  ä 20. • Cable material: PTFE • Cable lengths: 5 m (16.4 ft), 10 m (32.8 ft) ! Note! To ensure correct measuring results, route the connecting cable well clear of electrical machines and switching elements. Potential equalization For potential equalization, no special measures are necessary. DATA I-IN 12V DC SERVICE CH-UP CH-DN 1 2 3 7 6 5 4 I-OUT 8
  • 8. Proline Prosonic Flow 93T Portable 8 Endress+Hauser Performance characteristics Reference operating conditions • Fluid temperature: +20 to +30 °C • Ambient temperature: +22 °C ± 2 K • Warm-up period: 30 minutes • Sensors and transmitter are grounded • The measuring sensors are correctly installed Maximum measured error The measured error depends on a number of factors. A distinction is made between the measured error of the device (Prosonic Flow 93T = 0.5 % of the measured value) and an additional installation-specific measured error (typically 1.5 % of the measured value) that is independent of the device. The installation-specific measured error depends on the installation conditions on site, such as the nominal diameter, wall thickness, real pipe geometry, fluid, etc. The sum of the two measured errors is the measured error at the measuring point. A0011347 Example of the measured error in a pipe with a nominal diameter DN > 200 (8") a Measured error of the device (0.5 % o.r. ± 3 mm/s) b Measured error due to installation conditions (typically 1.5 % o.r.) c Measured error at the measuring point: 0.5 % o.r. ± 3 mm/s + 1.5 % o.r. = 2 % o.r. ± 3 mm/s Measured error at the measuring point The measured error at the measuring point is made up of the measured error of the device (0.5 % o.r.) and the measured error resulting from the installation conditions on site. Given a flow velocity > 0.3 m/s (1 ft/s) and a Reynolds number > 10000, the following are typical error limits: 0 0.5 2.0 3.5 % m/s2 4 6 8 10 12 b c a Nominal diameter Device error limits + Installation-specific error limits (typical)  Error limits at the measuring point (typical) DN 15 (½") ±0.5 % o.r. ± 5 mm/s + ±2.5 % o.r.  ±3 % o.r. ± 5 mm/s DN 25 to 200 (1 to 8") ±0.5 % o.r. ± 7.5 mm/s + ±1.5 % o.r.  ±2 % o.r. ± 7.5 mm/s > DN 200 (8") ±0.5 % o.r. ± 3 mm/s + ±1.5 % o.r.  ±2 % o.r. ± 3 mm/s o.r. = of reading
  • 9. Proline Prosonic Flow 93T Portable Endress+Hauser 9 Measurement Report If required, the device can be supplied with a factory measurement report. To certify the performance of the device, a measurement is performed under reference conditions. Here, the sensors are mounted on a pipe with a nominal diameter of DN 50 (2") or DN 100 (4") respectively. The measurement report guarantees the following error limits of the device [at a flow velocity > 0.3 m/s (1 ft/s) and a Reynolds number > 10000]: Repeatability ±0.3 % for flow velocities > 0.3 m/s (1 ft/s) Operating conditions: installation Installation instructions Mounting location Correct flow measurement is possible only if the pipe is full. It is preferable to install the sensors in a riser. ! Note! Entrained air or gas bubbles in the measuring tube can result in an increase in measuring errors. For this reason, avoid the following mounting locations: • Highest point of a pipeline. Risk of air accumulating. • Directly upstream of a free pipe outlet in a vertical pipe. Risk of partial pipe filling. A0001103 Nominal diameter Guaranteed error limits of the device DN 50 (2") ±0.5 % o.r. ± 5 mm/s DN 100 (4") ±0.5 % o.r. ± 7.5 mm/s o.r. = of reading
  • 10. Proline Prosonic Flow 93T Portable 10 Endress+Hauser Orientation Vertical Recommended orientation with upward direction of flow (View A). With this orientation, entrained solids will sink and gases will rise away from the sensor when the fluid is stagnant. The piping can be completely drained and protected against solids buildup. Horizontal In the recommended installation range in a horizontal installation position (View B), gas and air collections at the pipe cover and problematic deposits at the bottom of the pipe have a smaller influence on measurement. A0001105 A Recommended orientation with upward direction of flow B Recommended installation range with horizontal orientation C Recommended installation range max. 120° Inlet and outlet runs If possible, install the sensor well clear of fittings such as valves, T-pieces, elbows, etc. Compliance with the following inlet and outlet runs is required in order to ensure measuring accuracy. A0013459 1 Valve (2/3 open) 2 Pump 3 Two pipe bends in different directions A B C C ³ 15 x DN ³ 20 x DN ³ 20 x DN ³ 15 x DN ³ 3 x DN 1 2 3
  • 11. Proline Prosonic Flow 93T Portable Endress+Hauser 11 Operating conditions: environment Ambient temperature range Transmitter 0 to +60 °C (+32 to +140 °F) Prosonic Flow P sensor DN 15 to 65 (½ to 2½") • Standard: –40 to +100 °C (–40 to +212 °F) • Optional: –40 to +150 °C (–40 to +302 °F) DN 50 to 4000 (2 to 160") • Standard: –40 to +80 °C (–40 to +176 °F) • Optional: 0 to +170 °C (+32 to +338 °F) DDU18 sensor (accessories: sound velocity measurement) • Standard: –40 to +80 °C (–40 to +176 °F) • Optional: 0 to +170 °C (+32 to +338 °F) DDU20 sensor (accessories: wall thickness measurement) –20 to +60 °C (–4 to +140 °F) Connecting cable (sensor/transmitter) –40 to +170 °C (–40 to +338 °F) Storage temperature The storage temperature corresponds to the ambient temperature range. Degree of protection Transmitter IP 40 Sensor IP 68 (NEMA 6P), connection IP 50 DDU18 sensor (accessories: sound velocity measurement) IP 68 (NEMA 6P), connection IP 50 DDU20 sensor (accessories: wall thickness measurement) IP 67 (NEMA 4X), connection IP 50 Shock and vibration resistance According to IEC 68-2-6 Electromagnetic compatibility (EMC) Electromagnetic compatibility (EMC requirements) according to IEC/EN 61326 "Emission to class A requirements" and NAMUR Recommendation NE 21 and NE 43.
  • 12. Proline Prosonic Flow 93T Portable 12 Endress+Hauser Operating conditions: process Medium temperature range Prosonic Flow P sensor DN 15 to 65 (½ to 2½") • Standard: –40 to +100 °C (–40 to +212 °F) • Optional: –40 to +150 °C (–40 to +302 °F) DN 50 to 4000 (2 to 160") • Standard: –40 to +80 °C (–40 to +176 °F) • Optional: 0 to +170 °C (+32 to +338 °F) DDU18 sensor (accessories: sound velocity measurement) • Standard: –40 to +80 °C (–40 to +176 °F) • Optional: 0 to +170 °C (+32 to +338 °F) DDU20 sensor (accessories: wall thickness measurement) –10 to +60 °C (+14 to +140 °F) Medium pressure range (nominal pressure) No pressure limitation, however perfect measurement requires that the static fluid pressure is higher than vapor pressure. Pressure loss There is no pressure loss.
  • 13. Proline Prosonic Flow 93T Portable Endress+Hauser 13 Mechanical construction Design, dimensions Transmitter A0011481 Dimensions in SI units Dimensions in US units Protective bag The dimensions (length × width × height) of the protective bag for the transmitter are: 280 × 150 × 80 mm (11.0 × 5.90 × 3.15") A B C 270 130 63 All dimensions in [mm] A B C 10.6 5.12 2.48 All dimensions in [inch] A B C
  • 14. Proline Prosonic Flow 93T Portable 14 Endress+Hauser Prosonic Flow P sensor (DN 50 to 4000 / 2 to 160") A0011401 Mounting arrangement for measurement via two traverses Dimensions in SI units Dimensions in US units E A DB I C H G FA B C D E F G 56 62 145 111  58 max. 872 min. 0.5 H I Depends on the measuring point conditions (pipe, fluid, etc.). Dimension "H" can be determined: • Via transmitter programming (Quick Setup or FieldCare) • Online (Applicator) Pipe outer diameter All dimensions in [mm] A B C D E F G 2.20 2.44 5.71 4.37  2.28 max. 34.3 min. 0.2 H I Depends on the measuring point conditions (pipe, fluid, etc.). Dimension "H" can be determined: • Via transmitter programming (Quick Setup or FieldCare) • Online (Applicator) Pipe outer diameter All dimensions in [inch]
  • 15. Proline Prosonic Flow 93T Portable Endress+Hauser 15 A0001155 Mounting arrangement for measurement via one traverse Dimensions in SI units Dimensions in US units E DH A B G C F A B C D E F 56 62 145 111  58 max. 872 G H Depends on the measuring point conditions (pipe, fluid, etc.). Dimension "G" can be determined: • Via transmitter programming (Quick Setup or FieldCare) • Online (Applicator) Pipe outer diameter All dimensions in [mm] A B C D E F 2.20 2.44 5.71 4.37  2.28 max. 34.3 G H Depends on the measuring point conditions (pipe, fluid, etc.). Dimension "G" can be determined: • Via transmitter programming (Quick Setup or FieldCare) • Online (Applicator) Pipe outer diameter All dimensions in [inch]
  • 16. Proline Prosonic Flow 93T Portable 16 Endress+Hauser Prosonic Flow P sensor (DN 15 to 65 / ½ to 2½") A0013505 Model 2 Dimensions in SI units Dimensions in US units B A C DE F A B C (min./max.) D E F 285 110 210/255 35 75 110 All dimensions in [mm] A B C (min./max.) D E F 11.2 4.33 8.27/10.0 1.38 2.95 4.33 All dimensions in [inch]
  • 17. Proline Prosonic Flow 93T Portable Endress+Hauser 17 Weight Transmitter 1.6 kg (3.53 lbs) Sensor Prosonic Flow P • DN 15 to 65 (½ to 2½") (incl. mounting material): 1.78 kg (3.9 lbs) • DN 50 to 4000 (2 to 160") (incl. mounting material): 2.8 kg (6.2 lbs) Sensor (accessories) • Prosonic Flow DDU18 (incl. mounting material): 2.4 kg (5.3 lbs) • Prosonic Flow DDU20 (incl. mounting material): 0.23 kg (0.5 lbs) ! Note! Weight information without packaging material. Materials Transmitter Plastic Sensor Prosonic Flow P DN 15 to 65 (½ to 2½") • Sensor holder: corrosion protected aluminum, stainless steel 1.4301/304 • Sensor housing: stainless steel 1.4301/304 • Sensor contact surfaces: chemically stable plastic DN 50 to 4000 (2 to 160") • Sensor holder: stainless steel 1.4308/CF-08 • Sensor housing: stainless steel 1.4301/304 • Strapping bands/bracket: textile or stainless steel 1.4301/304 • Sensor contact surfaces: chemically stable plastic Sensor (accessories) Prosonic Flow DDU18; Prosonic Flow DDU20 • Sensor holder: stainless steel 1.4308/CF-08 • Sensor housing: stainless steel 1.4301/304 • Strapping bands/bracket: textile or stainless steel 1.4301/304 • Sensor contact surfaces: chemically stable plastic Connecting cable (sensor/transmitter) PTFE connecting cable • Cable sheath: PTFE • Cable connector: stainless steel
  • 18. Proline Prosonic Flow 93T Portable 18 Endress+Hauser Human interface Display elements • Liquid crystal display: illuminated, four lines each with 16 characters • Custom configuration for presenting different measured values and status variables Operating elements • Local operation with three optical keys • Application specific Quick Setup menus for straightforward commissioning Language group Language groups available for operation in different countries: • Western Europe and America (WEA): English, German, Spanish, Italian, French, Dutch and Portuguese • Eastern Europe/Scandinavia (EES): English, Russian, Polish, Norwegian, Finnish, Swedish and Czech • South and Eastern Asia (SEA): English, Japanese, Indonesian • China (CN): English, Chinese You can change the language group via the FieldCare operating program. Remote operation Operation via FieldCare, with: • Option of loading or saving preprogrammed measuring points • Configuration logging • Measured value visualization
  • 19. Proline Prosonic Flow 93T Portable Endress+Hauser 19 Certificates and approvals CE mark The measuring system is in conformity with the statutory requirements of the EC Directives. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. C-Tick mark The measuring system is in conformity with the EMC requirements of the "Australian Communications and Media Authority (ACMA)". Other standards and guidelines • EN 60529 Degrees of protection provided by enclosures (IP code). • EN 61010-1 Safety requirements for electrical equipment for measurement, control and laboratory use. • IEC/EN 61326 "Emission in accordance with Class A requirements". Electromagnetic compatibility (EMC requirements). • ANSI/ISA-S82.01 Safety Standard for Electrical and Electronic Test, Measuring, Controlling and Related Equipment - General Requirements. Pollution Degree 2, Installation Category II. • CAN/CSA-C22.2 No. 1010.1-92 Safety Requirements for Electrical Equipment for Measurement and Control and Laboratory Use. Pollution degree 2. Ordering information The Endress+Hauser service organization can provide detailed ordering information and information on the order codes on request.
  • 20. Proline Prosonic Flow 93T Portable 20 Endress+Hauser Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the transmitter and the sensor. The Endress+Hauser service organization can provide detailed information on the order codes on request. Device-specific accessories Measuring principle-specific accessories Accessory Description Order code Sensor P (DN 15 to 65 / ½ to 2½") Clamp-on version DN 15 to 65 (½ to 2½") • –40 to +100 °C (–40 to +212 °F) • –40 to +150 °C (–40 to +302 °F) DK9PT - 1A DK9PT - 2A Sensor P (DN 50 to 4000 / 2 to 160") Clamp-on version DN 50 to 300 (2 to 12") • –40 to +80 °C (–40 to +176 °F) • –40 to +170 °C (–40 to +338 °F) DK9PT - BA DK9PT - FA DN 100 to 4000 (4 to 160") • –40 to +80 °C (–40 to +176 °F) • 0 to +170 °C (+32 to +338 °F) DK9PT - AA DK9PT - EA Sensor DDU18 Sensor for sound velocity measurement –40 to +80 °C (–40 to +176 °F) 0 to +170 °C (+32 to +338 °F) 50091703 50091704 Sensor DDU20 Sensor for wall thickness measurement. • –20 to +60 °C (–4 to +140 °F) 71112217 Accessory Description Order code Sensor holder set • Prosonic Flow P (DN 15 to 65 / ½ to 2½"): Sensor holder, clamp-on version DK9SH - 2 • Prosonic Flow P (DN 50 to 4000 / 2 to 160") – Sensor holder, fixed retaining nut, clamp-on version – Sensor holder, removable retaining nut, clamp-on version DK9SH - A DK9SH - B Clamp-on installation set • DN < 1500 (60") (textile strapping) • DN  1500 (60") (textile strapping) • DN 50 to 300 (2 to 12"): 0 to +170 °C (+32 to +338 °F) (stainless steel strapping) DK9ZT - D DK9ZT - E DK9ZT - B Connecting cable 5 m (16.4 ft) sensor cable, PTFE, –40 to +170 °C (–40 to +338 °F) 10 m (32.8 ft) sensor cable, PTFE, –40 to +170 °C (–40 to +338 °F) DK9SS - CEE DK9SS - CEF Acoustic coupling fluid • Coupling fluid: –40 to +170 °C (–40 to +338 °F), standard, high temperature • Adhesive coupling fluid: –40 to +80 °C (–40 to +176 °F) • Water-soluble coupling fluid: –20 to +80 °C (–4 to +176 °F) • Coupling fluid DDU20: –20 to +60 °C (–4 to +140 °F) • Coupling fluid: –40 to +100 °C (–40 to +212 °F), standard, type MBG2000 DK9CM - 2 DK9CM - 3 DK9CM - 4 DK9CM - 6 DK9CM - 7
  • 21. Proline Prosonic Flow 93T Portable Endress+Hauser 21 Service-specific accessories Documentation • Flow measurement (FA005D/06) • Operating Instructions for Prosonic Flow 93T Portable (BA136D/06) Registered trademarks FieldCare®, Fieldcheck® Registered or registration-pending trademarks of Endress+Hauser Flowtec AG, Reinach, CH Accessory Description Order code Applicator Software for selecting and planning flowmeters. The Applicator can be downloaded from the Internet or ordered on CD-ROM for installation on a local PC. Contact your Endress+Hauser representative for more information. DXA80 - * Fieldcheck Tester/simulator for testing flowmeters in the field. When used in conjunction with the "FieldCare" software package, test results can be imported into a database, printed out and used for official certification. Contact your Endress+Hauser representative for more information. 50098801 FieldCare FieldCare is Endress+Hauser's FDT-based plant asset management tool. It can configure all intelligent field units in your system and helps you manage them. By using the status information, it is also a simple but effective way of checking their status and condition. See the product page on the Endress+Hauser website: www.endress.com FXA193 Service interface from the measuring device to the PC for operation via FieldCare. FXA193 - * Communication cable Communication cable for connecting the Prosonic Flow 93T transmitter to the FXA193 service interface. DK9ZT - I FXA291 Service interface from the measuring device to the PC for operation via FieldCare. FXA291 - * Communication cable Communication cable for connecting the Prosonic Flow 93T transmitter to the FXA291 service interface. DK9ZT - 8
  • 22. Instruments International Endress+Hauser Instruments International AG Kaegenstrasse 2 4153 Reinach Switzerland Tel.+41 61 715 81 00 Fax+41 61 715 25 00 www.endress.com info@ii.endress.com TI00085D/06/EN/13.11 71136634 FM+SGML6.0 ProMoDo