   Raised access floors


GAMMA industries France - 10/03/2009
Gamma         INDUSTRIES



                                                                YOUR PARTNER
                                                                • The leader in France for raised access flooring.
                                                                  A status obtained due to the quality of our installations.
                                                                • Prestigious references.
                                                                  Gamma Industries has taken part in some of the most
                                                                  outstanding projets in recent years.
                                                                • An experience recognized by all our customers.
                                                                • A total commitment from initial design,
                                                                  through installation to final use.
                                                                • At every stage, dedicated personnel.
    Issy les Moulineaux




    Grande Arche and CNIT - La Défense




    Cité des Sciences - La Villette



Summary

The guarantee of quality               Page 3
The response to your needs             Page 4
Accessories                            page 5
Detailed sketches                      Pages 6
Technical information                  Pages 7, 8
The families                           Page 9


                                                          CBX Tower
                                                                                          Gamma,
                                                       1
                                      GAMMA industries France - 10/03/2009
Raised
     access floors




                                        GAMMA INDUSTRIES has been designing,
                                        manufacturing and installing raised access
                                        floors from their origins.

                                        We offer :

                                        • Total commitment from initial design,
                                          through installation to final use.

                                        • A modern and efficient manufacturing
                                          plant.

                                        • The expertise of our teams.




the industrial dynamics
                                      2
                     GAMMA industries France - 10/03/2009
The guarantee of quality


              The Quality Management System of GAMMA
              INDUSTRIES is based on the International
              Standard ISO 9001 (version 2000).
              Strict controls at every stage of the production
              enable to guarantee the required level of quality.

              GAMMA INDUSTRIES has a reputation for
              quality products and services. This level of quality
    Quality   is achieved due to a strict and methodic
Management    organisation.
    System
              Quality policy and targets of GAMMA
              INDUSTRIES are defined within our Quality
              Assurance Guide.
              Identification and tracability are the key words
              of our system.
                                                                     Quality control and final control

              GAMMA INDUSTRIES can meet the criterias
              of “Haute Qualité Environnementale” (HQE)
              required by customers, due to :

              • Selection of the raw materials used.

              • Industrialization of our production processes.

              • Mechanical and acoustic performances of
                our products.

              • Policy for reduction of our packing products
                and industrial waste.




                                                                     Laboratory and testing apparatus




Gamma, a realistic approach
                                                 3
                                GAMMA industries France - 10/03/2009
The families
                                                              Offices
                                                              Raised floors with low finished height
OFFICE APPLICATIONS                                           Trading rooms - call centers - casinos
                                                              Light computers rooms




                                                              Heavy computers
                                                              Technical rooms - telephone or
TECHNICAL APPLICATIONS                                        network centers
                                                              Laboratories
                                                              Heavy loads - Important heights




                                                              Offices inside high buildings
                                                              Raised floors with low finished height
RANGE M0                                                      Technical rooms with M0 requirement
                                                              Offices with high acoustic performances




                                                              Scientific rooms
                                                              Special technical rooms
SPECIAL APPLICATIONS                                          Clean rooms




Gamma, a wide selection
                                        9
                       GAMMA industries France - 10/03/2009
The response
                                                                          to your needs
                                                                                    GAMMA INDUSTRIES has efficient technical and
                                                                                    sales departments ensuring the selection of the most
                                                                                    suitable raised floor to meet your requirements.
Headquarters



                                GAMMA INDUSTRIES
                                A wide range of products suitable to meet your requirements.
                                There is a family of panels to meet every requirement, and several panels to suit every room.




                                                                                                                         GAMMABOX M0
                                                                                       BUROBOX M0




                                                                                                                                       GAMMACORE
                                                                                                              GAMMABOX




                                                                                                                                                   GAMMAPAC
                                                                          BUROBOX




                                                                                                    BUROPAC




                                                                                                                                                                     MINIGAM
                                                                ALUCAST
               The families




                                                                                                                                                              GIM
               OFFICE APPLICATIONS
               Offices
               Raised floors with low finished height
               Trading rooms - call centers - casinos
               Light computers rooms


               TECHNICAL APPLICATIONS
               Heavy computers
               Technical rooms - telephone or network centers
               Laboratories
               Heavy loads - Important heights

               RANGE M0
               Offices inside high buildings
               Raised floors with low finished height
               Technical rooms with M0 requirement
               Offices with high acoustic performances


               SPECIAL APPLICATIONS
               Scientific rooms
               Special technical rooms
               Clean rooms




                                                 GAMMA INDUSTRIES refers to the European Standard NF EN 12825 for all its tests
                                                 and controls.




                                                             4
                                                                                                                                                                    Gamma      INDUSTRIES


                                            GAMMA industries France - 10/03/2009
Burobox     The Burobox panel is widely used in office buildings.
                                                                          It can be covered with textile tiles used with access flooring,
                                                                          free laid on site.




                                                                                       Composition
                                                                                       The Burobox panel is made up as follows :
                                                                                       • A high density resin bonded core, thickness 30 or 38 mm.
                                                                                       • A bottom tray of 0.5 mm thick galvanized steel turning
                                                                                         up the sides of the panel.

                                                                                       Coverings
                                                                                       The Burobox panel is available without covering.


                                                                                       Dimensions
                                                                                       Standard size : 600 mm.
                                                                                       Special size : 675 mm, for thickness 38 mm only.

                                                                                       Options
                                                                                       • Top varnished.
                                                                                       • Top plate of 0.5 mm thick galvanized steel.
                                                                                       • 19 mm thick core.


                                                                                       Fire classification
                                                                                       The Burobox panel is classed M1
                                                                                       (SNPE report n° 13149-07).


                                                                                       Electrical resistance
                                                                                       It varies from 5x108 to 2x1012 ohms, depending on the
                                                                                       properties of the covering.


                                                                                       Acoustic
                                                                                       The acoustic insulation measured between 2 adjacent rooms,
                                                                                       separated by a densely insulated partition, varies from 46 to
                                                                                       51 dBA, depending on the thickness of the panel and the
                                                                                       covering (Dn,f,w according to Standard EN ISO 140-12).




      Load classes
                                Framework                    Class                    Certificate
                                                                                                          NB : A system classed 1A is a system for
Burobox 30                      Self-supporting       1A (or 2B or 3C)              Nr. 03.10.30.07       which the ultimate load is at least 4kN
                                                                                                          (load class 1).
                               Stringers 30/15        2A (or 3B or 4C)              Nr. 03.10.30.04       The working load of this system is at least 2 kN,
                                                                                                          with a safety factor of 2, for a deflection less
Burobox 38                      Self-supporting       2A (or 4B or 5C)              Nr. 04.11.17.02       than 2.5 mm (deflection class A).
                               Stringers 30/15        4A (or 5B or 6C)              Nr. 04.11.17.01
                                                                                                          See tables below for the other classes.
Survey Institute : SOCOTEC CONSULTING.


Load classes according to NF EN 12825 and using safety factor = 2.0.
                         Class 1   Class 2    Class    Class 4    Class     Class
 Load class                1         2          3        4           5        6                 Deflection class            Maximum deflection
                                                                                           A (the most stringent)                2.5 mm
 Ultimate load           >4kN      >6kN      >8kN      >9kN      >10kN >12kN
                                                                                           B                                     3.0 mm
 Working load            >2kN      >3kN      >4kN >4.5kN >5kN               >6kN           C (the least stringent)               4.0 mm



Burobox                                                                                                                                  Gamma      INDUSTRIES


                                             GAMMA industries France - 10/03/2009
Buropac     The Buropac panel has been specially designed for use in offi-
                                                                          ces and computer rooms.
                                                                          This panel is also recommended for rooms with non-magnetic
                                                                          requirements. It is suitable for all the coverings used with access
                                                                          flooring.


                                                                                        Composition
                                                                                        The Buropac panel is made up as follows :
                                                                                        • A high density resin bonded core, thickness 38 mm.
                                                                                        • A bottom aluminium foil.
                                                                                        • An ABS surround, heat bonded to the edge of the core.


                                                                                        Dimensions
                                                                                        Standard size : 600 mm.


                                                                                        Options
                                                                                        • Bottom plate of 0.2 mm thick aluminium.
                                                                                        • Top varnished.


                                                                                        Fire classification
                                                                                        The Buropac panel is classed M1
                                                                                        (SNPE report n° 13148-07).


                                                                                        Electrical resistance
                                                                                        It varies from 5x105 to 2x1012 ohms, depending on the
                                                                                        properties of the covering.


                                                                                        Acoustic
                                                                                        The acoustic insulation measured between 2 adjacent rooms,
                                                                                        separated by a densely insulated partition, varies from 44 to
                                                                                        50 dBA, depending on the covering (Dn,f,w according to
                                                                                        Standard EN ISO 140-12).




      Load classes

                                Framework                    Class                    Certificate         NB : A system classed 1A is a system for
                                                                                                          which the ultimate load is at least 4 kN
Buropac                         Self-supporting       1A (or 1B or 2C)              Nr. 03.10.30.23       (load class 1).
                               Stringers 30/15        2A (or 3B or 4C)              Nr. 03.10.30.24       The working load of this system is at least 2 kN,
                                                                                                          with a safety factor of 2, for a deflection
                                                                                                          less than 2.5 mm (deflection class A).

                                                                                                          See tables below for the other classes.
Survey Institute : SOCOTEC CONSULTING.

Load classes according to NF EN 12825 and using safety factor = 2.0.
                         Class 1   Class 2    Class    Class 4    Class     Class
 Load class                1         2          3        4           5        6                 Deflection class            Maximum deflection
 Ultimate load           >4kN      >6kN      >8kN      >9kN      >10kN >12kN               A (the most stringent)                2.5 mm
                                                                                           B                                     3.0 mm
 Working load            >2kN      >3kN      >4kN >4.5kN >5kN               >6kN
                                                                                           C (the least stringent)               4.0 mm




Buropac                                                                                                                                   Gamma      INDUSTRIES


                                             GAMMA industries France - 10/03/2009
Gammabox                             The Gammabox panel has been specially designed to meet
                                                                          the requirements of technical, data processing and scientific
                                                                          applications.
                                                                          It is suitable for all the coverings used with access flooring,
                                                                          excepted textile and mineral coverings.



                                                                                        Composition
                                                                                        The Gammabox panel is made up as follows :
                                                                                        • A high density resin bonded core, thickness 30 or 38 mm.
                                                                                        • A bottom tray of 0.5 mm thick galvanized steel.
                                                                                        • A perimeter plastic edge trim slotted into the sides of the
                                                                                          panel.


                                                                                        Coverings
                                                                                        The Gammabox panel is available with the following
                                                                                        coverings :
                                                                                        • High pressure laminate • Linoleum
                                                                                        • Vinyl                  • Rubber

                                                                                        Dimensions
                                                                                        Standard size : 600 mm.

                                                                                        Fire classification
                                                                                        The Gammabox panel is classed M1
                                                                                        (SNPE report n° 13149-07).


                                                                                        Electrical resistance
                                                                                        It varies from 5x105 to 2x1012 ohms, depending on the
                                                                                        properties of the covering.


                                                                                        Acoustic
                                                                                        The acoustic insulation measured between 2 adjacent
                                                                                        rooms, separated by a densely insulated partition, varies
                                                                                        from 46 to 51 dBA, depending on the thickness of the
                                                                                        panel and the covering (Dn,f,w according to Standard EN
                                                                                        ISO 140-12).


      Load classes

                                Framework                    Class                    Certificate
Gammabox 30                     Self-supporting       1A (or 2B or 3C)              Nr. 03.10.30.10       NB : A system classed 1A is a system for
                                                                                                          which the ultimate load is at least 4kN
                               Stringers 30/15        2A (or 3B or 4C)              Nr. 03.10.30.01       (load class 1).
                                                      5A (or 5B or 5C)              Nr. 03.10.30.05       The working load of this system is at least 2 kN,
                               Stringers 45/15
                                                                                                          with a safety factor of 2, for a deflection
                                                                                                          less than 2.5 mm (deflection class A).
Gammabox 38                     Self-supporting       3A (or 5B or 5C)              Nr. 04.11.17.03
                               Stringers 30/15        5A (or 6B or 6C)              Nr. 04.11.17.04       See tables below for the other classes.


Survey Institute : SOCOTEC CONSULTING.

Load classes according to NF EN 12825 and using safety factor = 2.0.
                         Class 1   Class 2    Class    Class 4    Class     Class
Load class                 1         2          3        4           5        6                 Deflection class            Maximum deflection
Ultimate load            >4kN      >6kN      >8kN      >9kN      >10kN >12kN               A (the most stringent)                2.5 mm
                                                                                           B                                     3.0 mm
Working load             >2kN      >3kN      >4kN >4.5kN >5kN               >6kN
                                                                                           C (the least stringent)               4.0 mm




Gammabox                                                                                                                                 Gamma      INDUSTRIES


                                             GAMMA industries France - 10/03/2009
Gammacore                    The Gammacore panel is famous on the world market for its
                                                                          quality, design and finish.
                                                                          It is characterized by an extruded aluminium edging inserted
                                                                          into the core.
                                                                          This panel has been designed to meet the requirements of
                                                                          technical, data processing and scientific applications. It is suitable
                                                                          for all the coverings used with access flooring, except textile
                                                                          and mineral coverings.

                                                                                        Composition
                                                                                        The Gammacore panel is made up as follows :
                                                                                        • A high density resin bonded core, thickness 30 mm.
                                                                                        • A bottom plate of 0.5 mm thick galvanized steel.
                                                                                        • A peripheral extruded aluminium section inserted into
                                                                                          the core and holding the edge trim.
                                                                                        • A plastic edge trim slotted into the above mentioned
                                                                                          aluminium section.

                                                                                        Coverings
                                                                                        The Gammacore panel is available with the following
                                                                                        coverings :
                                                                                        • High pressure laminate         • Linoleum
                                                                                        • Vinyl                          • Rubber

                                                                                        Dimensions
                                                                                        Standard size : 600 mm.
                                                                                        Special sizes, on request.

                                                                                        Fire classification
                                                                                        The Gammacore panel is classed M1
                                                                                        (SNPE report n° 13149-07).

                                                                                        Electrical resistance
                                                                                        It varies from 5x105 to 2x1012 ohms, depending on the
                                                                                        properties of the covering.

                                                                                        Acoustic
                                                                                        The acoustic insulation measured between 2 adjacent rooms,
                                                                                        separated by a densely insulated partition, varies from 46 to 51
                                                                                        dBA, depending on the covering (Dn,f,w according to
                                                                                        Standard EN ISO 140-12).


      Load classes
                                Framework                    Class                     Certificate          NB : A system classed 1A is a system for
                                                                                                            which the ultimate load is at least 4 kN
Gammacore                       Self-supporting       1A (or 2B or 4C)               Nr. 03.10.30.12        (load class1).
                               Stringers 30/15        2A (or 3B or 5C)               Nr. 03.10.30.03        The working load of this system is at least 2 kN,
                                                                                                            with a safety factor of 2, for a deflection less
                                                                                                            than 2.5 mm (deflection class A).

                                                                                                            See tables below for the other classes.
Survey Institute : SOCOTEC CONSULTING.


Load classes according to NF EN 12825 and using safety factor = 2.0.
                         Class 1   Class 2    Class    Class 4    Class      Class
Load class                 1         2          3        4           5         6                 Deflection class             Maximum deflection
Ultimate load            >4kN      >6kN      >8kN      >9kN      >10kN >12kN                A (the most stringent)                 2.5 mm
                                                                                            B                                      3.0 mm
Working load             >2kN      >3kN      >4kN >4.5kN >5kN               >6kN
                                                                                            C (the least stringent)                4.0 mm




Gammacore                                                                                                                                   Gamma      INDUSTRIES


                                             GAMMA industries France - 10/03/2009
Gammapac                     Gammapac panels are multipurpose panels designed to
                                                                          meet a wide range of applications.
                                                                          They are suitable for all coverings used with access flooring.


                                                                                     Composition
                                                                                     The Gammapac panel is made up as follows :
                                                                                     • A high density resin bonded core, thickness 30 mm or
                                                                                      38 mm.
                                                                                     • A bottom plate of 0.5 mm thick galvanized steel.
                                                                                     • An ABS surround, heat bonded to the edge of the core.

                                                                                     Coverings
                                                                                     The Gammapac panel is available with the following
                                                                                     coverings :
                                                                                     • High pressure laminate    • Linoleum
                                                                                     • Vinyl                     • Textile covering
                                                                                                                 • Rubber
                                                                                     Dimensions
                                                                                     Standard size : 600 mm.
                                                                                     Size 675 mm for thickness 38 mm.
                                                                                     Special sizes, on request.

                                                                                     Options
                                                                                     For panels without covering only :
                                                                                     • Top varnished.
                                                                                     • Top plate of 0.5 mm thick galvanized steel.

                                                                                     Fire classification
                                                                                     The Gammapac panel is classed M1
                                                                                     (SNPE report n° 13149-07).
                                                                                     The Gammapac panel, 38mm thick, is classed F30,
                                                                                     according to DIN 4102.

                                                                                     Electrical resistance
                                                                                     It varies from 5x105 to 2x1012 Ohms, depending on the
                                                                                     properties of the covering.

                                                                                     Acoustic
                                                                                     The acoustic insulation measured between 2 adjacent rooms,
                                                                                     separated by a densely insulated partition, varies from 44 to
                                                                                     50 dBA, depending on the thickness of the panel and the
                                                                                     covering (Dn,f,w according to Standard EN ISO 140-12).

      Load classes
                                Framework                    Class                    Certificate
Gammapac 30                     Self-supporting       1A (or 1B or 2C)              Nr. 03.10.30.08        NB : A system classed 2A is a system for
without covering                                                                                           which the ultimate load is at least 6kN
                               Stringers 30/15        2A (or 3B or 4C)              Nr. 03.10.30.05
                                                                                                           (load class 2).
                                                                                                           The working load of this system is at least 3 kN,
Gammapac 30                     Self-supporting       2A (or 2B or 3C)              Nr. 03.10.30.11
                                                                                                           with a safety factor of 2, for a deflection
with HPL covering
                               Stringers 30/15        2A (or 3B or 4C)              Nr. 03.10.30.02        less than 2.5 mm (deflection class A).

Gammapac 38                     Self-supporting       2A (or 4B or 5C)              Nr. 03.07.10.06
                                                                                                           See tables below for the other classes.
                               Stringers 30/15        4A (or 5B or 5C)              Nr. 03.07.10.08
                               Stringers 45/15        5A (or 5B or 5C)              Nr. 03.07.10.10

Survey Institute : SOCOTEC CONSULTING.

Load classes according to NF EN 12825 and using safety factor = 2.0.
                         Class 1   Class 2    Class    Class 4    Class     Class
 Load class                1         2          3        4           5        6                 Deflection class            Maximum deflection
 Ultimate load           >4kN      >6kN      >8kN      >9kN      >10kN >12kN               A (the most stringent)                2.5 mm
                                                                                           B                                     3.0 mm
 Working load            >2kN      >3kN      >4kN >4.5kN >5kN               >6kN
                                                                                           C (the least stringent)               4.0 mm



Gammapac                                                                                                                                  Gamma      INDUSTRIES


                                             GAMMA industries France - 10/03/2009
Burobox     The Burobox M0 panel is widely used in office buildings.
                                                                                                                                   M0
                                                                         It can be covered with textile tiles used with access flooring,
                                                                         free laid on site.




                                                                                    Composition
                                                                                    The Burobox M0 panel is made up as follows :
                                                                                    • A mineral core, 19 to 30 mm thick.
                                                                                      If required, this core may be covered with galvanized
                                                                                      steel.

                                                                                    Coverings
                                                                                    The Burobox M0 panel is available without covering.

                                                                                    Dimensions
                                                                                    Standard size : 600 mm.
                                                                                    Special size : module 675 mm.

                                                                                    Options
                                                                                    • Bottom tray of 0.5 mm thick galvanized steel turning
                                                                                      up the sides of the panel.
                                                                                    • Top plate of 0.5 mm thick galvanized steel.


                                                                                    Fire classification
                                                                                    The Burobox M0 panel is classed M0
                                                                                    (SNPE reports n° 1152-03 and 12215-05).

                                                                                    Electrical resistance
                                                                                    It varies from 5x10 8 to 2x10 12 ohms, depending on
                                                                                    the properties of the covering.

                                                                                    Acoustic
                                                                                    The acoustic insulation measured between 2 adjacent
                                                                                    rooms, separated by a densely insulated partition,varies
                                                                                    from 49 to 54 dBA, depending on the thickness of the
                                                                                    panel and the covering (Dn,f,w according to Standard
                                                                                    EN ISO 140-12).

      Load classes

                                                                                                      NB : A system classed 1A is a system for
Burobox M0                     From 1 A à 3 A depending on thickness of the mineral and
                                                                                                      which the ultimate load is at least 4kN
                                                                                                      (load class1).
                               steel plates used.                                                     The working load of this system is at least 2 kN,
                                                                                                      with a safety factor of 2, for a deflection
                                                                                                      less than 2.5 mm (deflection class A).


                                                                                                      See tables below for the other classes.
Survey Institute : SOCOTEC CONSULTING.


Load classes according to NF EN 12825 and using safety factor = 2.0.
                         Class 1   Class 2    Class   Class 4    Class     Class
Load class                 1        2           3      4          5          6              Deflection class            Maximum deflection
                                                                                       A (the most stringent)                2.5 mm
Ultimate load            >4kN      >6kN      >8kN     >9kN      >10kN >12kN
                                                                                       B                                     3.0 mm
Working load             >2kN      >3kN      >4kN >4.5kN >5kN              >6kN        C (the least stringent)               4.0 mm



Burobox M0                                                                                                                           Gamma      INDUSTRIES


                                             GAMMA industries France - 10/03/2009
Gammapac                                               M0

                                                                        The family Gammapac M0 panels are multipurpose panels
                                                                        designed to meet a wide range of applications.
                                                                        They are widely used to suit access floors in High Rise
                                                                        Buildings.

                                                                           Composition
                                                                        The Gammapac M0 panel is made up as follows :
                                                                              A mineral core 30 mm thick.
                                                                              A bottom 0.5mm thick galvanized steel plate.
                                                                              A PVC/ABS surround heat bonded to the edge of the
                                                                           mineral core.

                                                                            Coverings
                                                                        The Gammapac M0 panel is available with the following
                                                                        coverings :
                                                                                High Pressure Laminate
                                                                                Vinyl or Linoleum
                                                                                Carpet in free laid tiles
                                                                        This panel may be supplied without covering.

                                                                            Dimensions
                                                                        Standard size : 600 mm

                                                                            Options
                                                                        For panels without covering only:
                                                                               Top varnished

                                                                           Fire classification
                                                                        The Gammapac M0 panel is classed M0.

                                                                            Electrical Résistance
                                                                        Depending on the properties of the covering, it varies from
                                                                        5.105 to 2.1012 ohms, measured with the covering.

                                                                            Acoustic
                                                                        The acoustic insulation measured between 2 adjacent rooms
                                                                        separated by a densely insulated partition, varies from 49 to
                                                                        54 dBA depending on the covering (Dn,f,w according to
                                                                        Standard NF EN ISO 10848-2).

Load Classes
                        Framework                    Class              Certificate      NB : A system classed 1A is a system for which the
                                                                                         ultimate load is at least 4 kN (load class 1).
GAMMAPAC              Self-supporting           1A (or 1B or 1C)       Nr. 08.12.0205    The working load of this system is at least 2kN with a
   M0                                                                                    safety factor equal to 2, for a deflection less than 2.5mm
                      Stringers 30/15           2A (or 2B or 2C)       Nr. 08.12.2205    (Deflection Class A).
                                                                                         See tables below for the other classes.
                      Stringers 45/15           2A (or 2B or 2C)       Nr. 08.12.3205

Load classes according to NF EN 12825 – Safety factor = 2
Load Class                    1           2            3           4           5          6          Deflection Class               Maximum
                                                                                                                                    Deflection
Ultimate load              > 4kN        > 6kN       > 8kN      > 9kN        > 10kN      > 12kN       A (the more stringent)          2.5 mm
Working load               > 2kN        > 3kN       > 4kN     > 4.5kN       > 5kN       > 6kN        B                               3.0 mm
                                                                                                     C (the least stringent)         4.0 mm




Gammapac M0




                                               GAMMA industries France - 10/03/2009
Minigam      The Minigam panel has been designed for offices where the
                                                                          available height for access floors is limited.
                                                                          The Minigam panel is classed M0 (incombustible), and is
                                                                          characterized by a thickness of 19mm only.
                                                                          It can be covered with textile tiles used with access flooring,
                                                                          free laid on site.



                                                                                        Composition
                                                                                        The Minigam panel is made up as follows :
                                                                                        • A mineral core 18 mm thick.
                                                                                        • A steel tray 0,5 mm thick.
                                                                                        • A top steel sheet 0,5 mm thick.


                                                                                        Coverings
                                                                                        The Minigam panel is available without covering.



                                                                                        Dimensions
                                                                                        Standard size : 500 mm.


                                                                                        Fire classification
                                                                                        Minigam panel is classed M0 (SNPE 11152-03).


                                                                                        Electrical resistance
                                                                                        It varies from 5x108 to 2x1012 ohms, depending on the
                                                                                        properties of the covering.


                                                                                        Acoustic
                                                                                        The acoustic insulation measured between 2 adjacent
                                                                                        rooms, separated by a densely insulated partition, varies
                                                                                        from 47 to 50 dBA, depending on the covering (Dn,f,w
                                                                                        according to Standard EN ISO 140-12).




      Load classes


                                                                                                          NB : A system classed 1A is a system for
                                                                                                          which the ultimate load is at least 4kN
                                                                                                          (load class 1).
                                Framework                    Class                    Certificate         The working load of this system is at least 2 kN,
                                                                                                          with a safety factor of 2, for a deflection
Minigam                         Self-supporting       1A (or 1B or 1C)              Nr. 03.10.30.20       less than 2.5 mm (deflection class A).


                                                                                                          See tables below for the other classes.

Survey Institute : SOCOTEC CONSULTING.



Load classes according to NF EN 12825 and using safety factor = 2.0.
                         Class 1   Class 2    Class    Class 4    Class     Class
Load class                 1         2          3        4           5        6                 Deflection class           Maximum deflection
Ultimate load            >4kN      >6kN      >8kN      >9kN      >10kN >12kN               A (the most stringent)               2.5 mm
                                                                                           B                                    3.0 mm
Working load             >2kN      >4kN      >4kN >4.5kN >5kN               >6kN
                                                                                           C (the least stringent)              4.0 mm




Minigam                                                                                                                                  Gamma      INDUSTRIES


                                             GAMMA industries France - 10/03/2009
Alucast     Alucast is an aluminium die-cast panel of great strength.
                                                                              Alucast is suitable for industrial and high-tech clean room
                                                                              installations, and for rooms with non-magnetic requirements.
                                                                              The panel is suitable for all the soft coverings normally used for
                                                                              access flooring.


                                                                                            Composition
                                                                                            The Alucast aluminium is made up as follows :
                                                                                            • A top distributor plate, 3 mm thick.
                                                                                            • A double peripheral reinforced rib.
                                                                                            • A network of central ribs.
                                                                                            The monolithic conception of Alucast panels enables to
                                                                                            reach the levels of performance and accuracy required
                                                                                            for high-tech applications.


                                                                                            Coverings
                                                                                            The Alucast panel, plain or perforated, is available with
                                                                                            the following finishes :
                                                                                            • vinyl.
                                                                                            • rubber
                                    Alucast PF2 : Perforated panel 11 %                     The Alucast grating (AF6) is available rough or epoxy
                                                                                            painted.


                                                                                            Dimensions
                                                                                            Standard size : 600 mm.

                                                                                            Fire classification
                                                                                            Without covering, the Alucast panel is classed M0
                                                                                            (incombustible), by nature.

                                    Alucast PF4 : Perforated panel 22 %
                                                                                            Electrical Resistance
                                                                                            It varies from 5x105 to 2x1012 ohms, depending on the
                                                                                            properties of the covering.


                                                                                            Range of perforations
                                                                                            •   Alucast   PF1 : Perforated panel, 7 % free area.
                                                                                            •   Alucast   PF2 : Perforated panel, 11 % free area.
                                                                                            •   Alucast   PF3 : Perforated panel, 15 % free area.
                                                                                            •   Alucast   PF4 : Perforated panel, 22 % free area.
                                    Alucast AF6 : Grating 60 %
                                                                                            •   Alucast   AF5 : Perforated panel, 40 % free area.
                                                                                            •   Alucast   AF6 : Grating,          60 % free area.
      Load classes

                                   Framework                     Class                    Certificate             NB : A system classed 6A is a system for which
                                                                                                                  the ultimate load is at least 12 kN
Alucast plain panel             Self-supporting         6A (or 6B or 6C)                Nr. 03.10.30.13           (load class 6).
                                                                                                                  The working load of this system is at least 6kN,
Alucast PF4 (22%)               Self-supporting         6A (or 6B or 6C)                Nr. 03.10.30.14
                                                                                                                  with a safety factor of 2, for a deflection less
                                                                                                                  than 2.5 mm (deflection class A).

                                                                                                                  See tables below for the other classes
Survey Institute : SOCOTEC CONSULTING.

Load classes according to NF EN 12825 and using safety factor = 2.0.
                         Class 1    Class 2    Class       Class 4    Class     Class
Load class                 1          2          3          4             5       6                   Deflection class              Maximum deflection
                                                                                                 A (the most stringent)                  2.5 mm
Ultimate load            >4kN       >6kN       >8kN       >9kN       >10kN >12kN
                                                                                                 B                                       3.0 mm
Working load             >2kN       >3kN       >4kN >4.5kN >5kN                 >6kN             C (the least stringent)                 4.0 mm




Alucast                                                                                                                                         Gamma      INDUSTRIES


                                              GAMMA industries France - 10/03/2009
Gim
                                                                          The Gim Panel, made of a robust welded steel structure, is
                                                                          designed for use in heavy duty industry : offshore platforms,
                                                                          Navy, clean rooms, or machinery rooms.
                                                                          It is suitable for all the coverings used with access flooring.




                                                                                     Composition
                                                                                     The Gim panel is made up as follows :
                                                                                     • A top distributor plate of 3 mm thick steel.
                                                                                     • A peripheral steel hollow section welded to the
                                                                                       distributor plate.
                                                                                     • Central steel bars welded to the distributor plate.
                                                                                     • A plastic edge fixed to the distributor plate.
                                                                                     All the visible surfaces of the Gim panel are painted.


                                                                                     Coverings
                                                                                     The Gim panel is available with the following coverings :
                                                                                     • High pressure laminate     • Linoleum
                                                                                     • Vinyl                      • Rubber

                                                                                     The Gim panel is also available without covering.


                                                                                     Dimensions
                                                                                     Standard size : 600 mm.
                                                                                     Special sizes, on request.



                                                                                     Fire classification
                                                                                     Without covering, the Gim panel is classed M0 (incombustible),
                                                                                     by nature.

                                                                                     Electrical resistance
                                                                                     It varies from 5x105 to 2x1012 ohms, depending on the
                                                                                     properties of the covering.




      Load classes
                                Framework                  Class                     Certificate
                                                                                                           NB : A system classed 5B is a system for
Gim                             Self-supporting              5B                     Nr. 06.10.0905         which the ultimate load is at least 10 kN
                               Stringers 30/15               6C                                            (load class 5).
                                                                                    Nr. 06.10.4917
                                                                                                           The working load of this system is at least 5kN,
                                                                                                           with a safety factor of 2, for a deflection
                                                                                                           less than 3 mm (deflection class B).


                                                                                                           See tables below for the other classes.
Survey Institute : SOCOTEC CONSULTING.
Load classes according to NF EN 12825 and using safety factor = 2.0.
                         Class 1   Class 2    Class   Class 4     Class     Class
 Load class                1         2          3      4           5          6                 Deflection class            Maximum deflection
 Ultimate load           >4kN      >6kN      >8kN     >9kN      >10kN >12kN                A (the most stringent)                2.5 mm
                                                                                           B                                     3.0 mm
 Working load            >2kN      >3kN      >4kN >4.5kN >5kN               >6kN
                                                                                           C (the least stringent)               4.0 mm




Gim                                                                                                                                      Gamma       INDUSTRIES


                                             GAMMA industries France - 10/03/2009
Pedestals
                                                                The pedestals are made up of :
                                                                • a square baseplate of galvanized steel.
                                                                • a steel galvanized column welded to the baseplate.
                                                                • a die-cast aluminium or steel head, according to the type of pedestal.
                                                                • a locking nut for height adjustment.

                                                                Standard pedestal
                                                                The head has a sufficient length to adjust the height + or - 20 mm.
                                                                Ridges moulded on the head allow a positive location of the panels.


                                                                Pedestal for low finished height
                                                                The threaded steel head allows an adjustment of + or - 7 mm.
                                                                The panels lay directly on a conductive pad. These pedestals allow a
                                                                minimum finished height of 70 mm.


                                                                Pedestal for great finished height (more than 800 mm)
                                                                The column is a square hollow section of galvanized steel.
                                                                The base, the head and the locking nut are the same as for the
 Standard pedestal                                              standard pedestal.


                                                                Installation
                                                                The pedestals are bonded to the concrete by way of a special
                                                                adhesive, or may be mechanically fixed.
                                                                A device on the baseplate permits a quick and safe fixing of the copper
                                                                earthing strap.




Pedestal low height                Pedestal great height




Stringers                                                       Lockable stringers
                                                                They are made of galvanized steel . They are designed for location
                                                                on pedestal heads.
                                                                The stringers provide rigidity to the understructure, and stability
                                                                against lateral strain.
                                                                The depth of the section is adapted to the required performances :
                                                                          • 30 mm deep : type 30/15.
                                                                          • 45 mm deep : type 45/15.



                                                                Special stringers
                                                                When pedestals are omitted due to obstructions, i.e. electrical services,
                         Lockable stringer                      air ducting, etc., special bridging stringers may be used.
                                                                Within these particular areas, its is admitted that the deflection may
                                                                be 20% more than for the rest of the raised floor.




                                                31bis, rue des Longs Prés 92100 Boulogne - Billancourt (France)
Gamma                 INDUSTRIES
                                                Tel. : 33 (0)1 41 23 10 21 - Fax : 33 (0)1 41 23 10 01

Raised access floors                            www.gamma-industries.com


                                            GAMMA industries France - 10/03/2009
Detailed                                                                                            Gim-Pf
  sketches                                                                                          The Gim-Pf panels allow air supply at any loca-
                                                                                                    tion of the access floor.
                                                                                                    These panels are entirely made of steel and
                                                                                                    compatible with all other Gamma panels.




Riser                        Standard perimeter detail
                             Minimum width of perimeter cuts :
                             100mm




                                                                                                    Loading performances
                                                                                                    The load classes of the Gim-Pf panels are identical to
                                                                                                    the classes of the panels they are mixed with.


                                                                                                    Air flow Characteristics
Special perimeter detail     Special perimeter detail
Minimum free height : 50mm   Maximum void width : 60mm                                              The total free area per panel is 8 dm2.
                                                                                                    Optional adjustable sliding dampers can be fitted for
                                                                                                    adjustment of the air flow.

                                                                                                    The graph below shows the possible air flow according
                                                                                                    to the air pressure in the plenum and the air pressure
                                                                                                    drop according to the air flow.


                                                                                                     100
                                                                                                                                                        With fully open damper
                                                                                                      90
                                                                 Overpressure in the plenum in Pa




                                                                                                      80

                                                                                                      70

                                                                                                      60

                                                                                                      50                                                            Without damper

                                                                                                      40

                                                                                                      30

                                                                                                      20

                                                                                                      10
Dilatation joint             Detail of profile over void along                                                                                                           Flow m3/ h
Standard case                facade                                                                    0
                                                                                                               20
                                                                                                                 0
                                                                                                                         40
                                                                                                                           0
                                                                                                                               60
                                                                                                                                 0
                                                                                                                                     80
                                                                                                                                       0         00 200     00     00     00     00         00
                                                                                                                                               10   1     14     16     18     20         22
                             Void greater than 60mm
                                                                                                           0         1         2           3        4        5          6             7
                                                                                                                               Free section airspeed in m/s




                                                  6
                                                                                                                                                                   Gamma          INDUSTRIES


                                 GAMMA industries France - 10/03/2009
Accessories

  Ramps                                                                   Steps and risers
                           The ramps are generally made of a wooden                              Steps and risers are made of white melamine
                           frame, and finished with a black anti-slip                            boards and their top edging is finished with
                           rubber.                                                               an anti-slip aluminium nosing.
                           The junction between the ramp and the                                 The steps are covered with an anti-slip rubber
                           access floor is a metallic profile. The ramp                          covering.
                           nosing is made of an aluminium profile.
                           The recommended slope of a ramp is 5%,
                           with a maximum of 10%.
                           Handling of loads on the ramps must be
                           made with appropriate means, under the
                           responsability of the user.




  Installation with stringers                                             Bridging profiles
                           For this type of installation, panels lay on                          Bridging profiles are used when a raised
                             metallic stringers. Stringers are used :                            floor must be installed over ducts, channels,
                                                                                                 conduits, or holes of large sizes.
                           • For finished heights greater than 500mm.
                           • For raised floors which are not surrounded                          These bridging profiles enable to suppress
                             by walls, or which have to take loads with                          one or several pedestals.
                             frequent removals.
                           • For important point loads or distributed
                             loads.
                           • For raised floors including a large number
                             of cut-outs.




  Plenum dividers                                                         Coverings
                           When required by regulations, plenum                                  Some of our panels are suitable for the
                           dividers made of non combustible materials                            following coverings :
                           can be supplied.
                                                                                                 High pressure laminate
                                                                                                 Vinyl
                                                                                                 Linoleum
                                                                                                 Textile
                                                                                                 Rubber
                                                                                                 Wood
                                                                                                 Some others are available without covering.
                                                                                                 They can be covered with textile tiles used
                                                                                                 with access flooring, free laid on site.




  Panel lifting device                                                    Outlets, type brush or type PVC




Gamma, an easy technology
                                              5
                             GAMMA industries France - 10/03/2009
Technical information
 Requirements for rooms to be installed with access floors (DTU 57-1)
 • Rooms must not be exposed to bad weather.
 • Rooms must be equipped with outside glazing.
 • Concrete slab and plaster walls must be dry.
 • Concrete slab must be conform to article 5.2.2 of DTU 21: the raw concrete is not allowed. The upper part of the concrete must resist when trying
   to tear up manually a pedestal base bonded to the concrete. The concrete must be able to take the weight of the raised floor and the loads
   transmitted by the pedestals bases.
 • Rooms must not be encumbered with materials or tools and get a dry and clean concrete.
 • Rooms must be free of any of the other trade during installation.
 • All rooms adjacent to the access floor must have the same floor height.
 • The ambient temperature of the rooms where the access floor is to be installed should be kept between 5°C and 24°C and the relative humidity
   between 45% and 70 %. If the temperature is above 24°C (but never above 30°C) the relative humidity should not be over 50%. The subfloor
   temperature should not be below 5°C.
 • No water or any other liquid should be spread under or on top of the access floor.
 • No other trade is allowed to walk on the raised floor during its installation, for at least 48 hours.



 Installation
 • The required finished level of the raised floor must be materialized by the architect or the building owner. The location of the first panel to be
   installed is determined by the drawings, in such a way that the width of the panels cut along the walls will be more than 100 mm, providing a
   good stability.
 • Handling and installation of any equipment or heavy material must be done on an added boarded flooring or load-spreading plates, rigid enough
   to spread the loads, to prevent overloading, tearing or scratching of the floor covering.


 Coverings
 Coverings to be used
 • High pressure laminates : these coverings must not be used within rooms where abrasive dust may lay on the floor.
 • Soft coverings : vinyl, rubber or linoleum.
 • Textile coverings : needlepunch carpets, cut-piles carpets.
 • Parquets, mineral coverings and ceramics : the technical characteristics of these coverings must be checked carefully in order to determine if they
   can be used with raised floors.

 Suitability of coverings
 High pressure laminates must be conform to Standard NF EN 438, NF EN 685 and NF EN 14041.
 The resilient floor coverings used with raised floors must be classed minimum 32 according to the classification of the Standard NF EN 685.
 Textile coverings to be used with raised floors must be classed 3 or 4 according to the classification of Standards NF EN 1470 or NF EN 1307,
 according to the type of covering.
 The design of the covering must not require any joint or centering, and tiles of covering must be interchangeable.

 Factory bonded coverings
 Floor coverings with a foam backing must be excluded.

 Free laid coverings
 It concerns carpets tiles, free laid on site. Their dimensions, squareness, stability and installation must be conform to the requirements of the Standard
 NFP 62.202.1 (reference DTU 53.1).
 The use of a permanent adhesive between the raised floor and the carpet tiles must not make dismantling of the raised floor panels difficult. It is
 recommended not to aline carpet tiles and raised floor panels.



 Maintenance
          Excessive use of liquid products must be avoided.
          The use of water can provoke swelling, oxidizing or destruction of the components of the panels.
          Cleaning products can damage the adhesives on the edges and corners. Even small quantities of a product can laminate the covering.
          Every covering has a data sheet for maintenance.




Gamma, total safety
                                                                  7
                                                 GAMMA industries France - 10/03/2009
Technical information




Mechanical performances and loading

A raised floor must be designed and produced in such a way to ensure the required mechanical resistance and stability. The required wor-
king load must not cause deformation or failure of the raised floor.
All systems must be tested according to requirements of the Standard NF EN 12825, and classifcations obtained after these tests
must be certified by an official test report from an independant body.




Acoustic insulation
When tested according to Standard EN ISO 140-12, our access floors can reach airborne sound insulation values from 44 to 54 dbA.
The insulation to impact sound depends mainly on the type of coverings bonded on the panels. The textile coverings are the most
efficient.




Fire protection
The regulations for access flooring refer to :
• the reaction to fire
• the partitioning of the plenum
• the calorific potential
They vary according to the use of the rooms and the classification of the building inside which the access floors are installed.

Reaction to fire
In France, the Decree dated June 30 th, 1983 defines 5 classes for the materials : M0, M1, M2, M3, M4.
The test method used is the radiation test. The tested side is the bottom of the panel.
The classification of the superior part of the panel is the same as for the covering.

Partitioning of the plenum
When required by regulation, plenum dividers made of non combustible materials can be supplied.
Every partitioned area has a maximum surface of 300m2 and a maximum length of 30 meters. In case of fire, the partitioning limits
the air circulation inside the plenum.




Electrostatic properties
The ability of a covering to accumulate electrostatic loads, and its ability to eliminate these loads are essential for the antistatic properties of an
access floor. The measurement of the transversal resistivity (Ret) enables the estimation of the ability to eliminate electrostatic loads.
Coverings are classed according to NF P 62.001 (Resilient floor coverings - Electrostatic behaviour) :

Class 1 :             Astatic covering                 :     RET > 1.109     (ohms) and electrostatic charging potential < 2 KV.
                                                                  7
Class 2 :             Dissipative covering             :     1.10     < RET < 1.109     (ohms) and electrostatic charging potential < 2 KV.
                                                                        7
Class 3 :             Conductive covering              :     RET < 1.10      (ohms) and electrostatic charging potential < 2 KV.

All raised floors must have a transversal resitivity between 5.105 and 2.1012 ohms.

The equipotential connection is made by a copper strap network connecting certain pedestals to each other. This network is earthed by the
companies in charge of the electrical wiring.




                                                                 8
                                                                                                                                                    Gamma INDUSTRIES


                                                GAMMA industries France - 10/03/2009

Contenu connexe

En vedette (7)

Gamma camera
Gamma cameraGamma camera
Gamma camera
 
Gamma Camera Image Quality
Gamma Camera Image QualityGamma Camera Image Quality
Gamma Camera Image Quality
 
Scanner & IRM dans le RAC
Scanner & IRM dans le RACScanner & IRM dans le RAC
Scanner & IRM dans le RAC
 
Gamma Camera
Gamma CameraGamma Camera
Gamma Camera
 
Gamma industries
Gamma industriesGamma industries
Gamma industries
 
présentation soutenance PFE.ppt
présentation soutenance PFE.pptprésentation soutenance PFE.ppt
présentation soutenance PFE.ppt
 
Soutenance mémoire de fin d'études
Soutenance mémoire de fin d'étudesSoutenance mémoire de fin d'études
Soutenance mémoire de fin d'études
 

Similaire à Doc complete-eng

Streamcore's pitch
Streamcore's pitchStreamcore's pitch
Streamcore's pitch
i7
 
Damco Corporate Presentation
Damco Corporate PresentationDamco Corporate Presentation
Damco Corporate Presentation
amargupta27
 
ANALYSTS‘ TRIP: Paint and Final Assembly Systems, Application Technology, Cle...
ANALYSTS‘ TRIP: Paint and Final Assembly Systems, Application Technology, Cle...ANALYSTS‘ TRIP: Paint and Final Assembly Systems, Application Technology, Cle...
ANALYSTS‘ TRIP: Paint and Final Assembly Systems, Application Technology, Cle...
Dürr
 

Similaire à Doc complete-eng (20)

Why Matrix
Why MatrixWhy Matrix
Why Matrix
 
MRONet.it
MRONet.itMRONet.it
MRONet.it
 
Streamcore's pitch
Streamcore's pitchStreamcore's pitch
Streamcore's pitch
 
Dimasimma Group: general presentation aluminium field
Dimasimma Group: general presentation aluminium fieldDimasimma Group: general presentation aluminium field
Dimasimma Group: general presentation aluminium field
 
Gamma industries
Gamma industries Gamma industries
Gamma industries
 
MroNet.it - the Italian Network for MRO
MroNet.it - the Italian Network for MROMroNet.it - the Italian Network for MRO
MroNet.it - the Italian Network for MRO
 
Fama presentazione aziendale slim en
Fama presentazione aziendale slim enFama presentazione aziendale slim en
Fama presentazione aziendale slim en
 
Fama presentazione aziendale slim en
Fama presentazione aziendale slim enFama presentazione aziendale slim en
Fama presentazione aziendale slim en
 
Damco Corporate Presentation
Damco Corporate PresentationDamco Corporate Presentation
Damco Corporate Presentation
 
Beamit aeronautics a&dss
Beamit aeronautics a&dssBeamit aeronautics a&dss
Beamit aeronautics a&dss
 
Formtech Composites Lightweight Concepts Short Introduction
Formtech Composites   Lightweight Concepts   Short IntroductionFormtech Composites   Lightweight Concepts   Short Introduction
Formtech Composites Lightweight Concepts Short Introduction
 
Fpi Presentation Comp.2009
Fpi Presentation Comp.2009Fpi Presentation Comp.2009
Fpi Presentation Comp.2009
 
ANALYSTS‘ TRIP: Paint and Final Assembly Systems, Application Technology, Cle...
ANALYSTS‘ TRIP: Paint and Final Assembly Systems, Application Technology, Cle...ANALYSTS‘ TRIP: Paint and Final Assembly Systems, Application Technology, Cle...
ANALYSTS‘ TRIP: Paint and Final Assembly Systems, Application Technology, Cle...
 
BEAMIT aeronautics final
BEAMIT aeronautics finalBEAMIT aeronautics final
BEAMIT aeronautics final
 
BEAMIT aeronautics
BEAMIT aeronautics BEAMIT aeronautics
BEAMIT aeronautics
 
Inbuilding antennas 2015 silex &amp; panorama antenna v01
Inbuilding antennas 2015 silex &amp; panorama antenna v01Inbuilding antennas 2015 silex &amp; panorama antenna v01
Inbuilding antennas 2015 silex &amp; panorama antenna v01
 
Storm Interface[1]
Storm Interface[1]Storm Interface[1]
Storm Interface[1]
 
New Fixed Outdoor Wireless Broadband: Connect the under or unconnected
New Fixed Outdoor Wireless Broadband: Connect the under or unconnectedNew Fixed Outdoor Wireless Broadband: Connect the under or unconnected
New Fixed Outdoor Wireless Broadband: Connect the under or unconnected
 
Présentation de Dardenne S.A.
Présentation de Dardenne S.A.Présentation de Dardenne S.A.
Présentation de Dardenne S.A.
 
Sheth Enterprise, Ahmedabad, Communication Equipment
Sheth Enterprise, Ahmedabad, Communication Equipment Sheth Enterprise, Ahmedabad, Communication Equipment
Sheth Enterprise, Ahmedabad, Communication Equipment
 

Dernier

IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI Solutions
Enterprise Knowledge
 
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
Earley Information Science
 

Dernier (20)

08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
 
08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI Solutions
 
Data Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonData Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt Robison
 
Handwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsHandwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed texts
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
 
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
 
GenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdfGenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdf
 
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
 
Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)
 
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivity
 
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024
 
Evaluating the top large language models.pdf
Evaluating the top large language models.pdfEvaluating the top large language models.pdf
Evaluating the top large language models.pdf
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processors
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day Presentation
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
 

Doc complete-eng

  • 1. INDUSTRIES Raised access floors GAMMA industries France - 10/03/2009
  • 2. Gamma INDUSTRIES YOUR PARTNER • The leader in France for raised access flooring. A status obtained due to the quality of our installations. • Prestigious references. Gamma Industries has taken part in some of the most outstanding projets in recent years. • An experience recognized by all our customers. • A total commitment from initial design, through installation to final use. • At every stage, dedicated personnel. Issy les Moulineaux Grande Arche and CNIT - La Défense Cité des Sciences - La Villette Summary The guarantee of quality Page 3 The response to your needs Page 4 Accessories page 5 Detailed sketches Pages 6 Technical information Pages 7, 8 The families Page 9 CBX Tower Gamma, 1 GAMMA industries France - 10/03/2009
  • 3. Raised access floors GAMMA INDUSTRIES has been designing, manufacturing and installing raised access floors from their origins. We offer : • Total commitment from initial design, through installation to final use. • A modern and efficient manufacturing plant. • The expertise of our teams. the industrial dynamics 2 GAMMA industries France - 10/03/2009
  • 4. The guarantee of quality The Quality Management System of GAMMA INDUSTRIES is based on the International Standard ISO 9001 (version 2000). Strict controls at every stage of the production enable to guarantee the required level of quality. GAMMA INDUSTRIES has a reputation for quality products and services. This level of quality Quality is achieved due to a strict and methodic Management organisation. System Quality policy and targets of GAMMA INDUSTRIES are defined within our Quality Assurance Guide. Identification and tracability are the key words of our system. Quality control and final control GAMMA INDUSTRIES can meet the criterias of “Haute Qualité Environnementale” (HQE) required by customers, due to : • Selection of the raw materials used. • Industrialization of our production processes. • Mechanical and acoustic performances of our products. • Policy for reduction of our packing products and industrial waste. Laboratory and testing apparatus Gamma, a realistic approach 3 GAMMA industries France - 10/03/2009
  • 5. The families Offices Raised floors with low finished height OFFICE APPLICATIONS Trading rooms - call centers - casinos Light computers rooms Heavy computers Technical rooms - telephone or TECHNICAL APPLICATIONS network centers Laboratories Heavy loads - Important heights Offices inside high buildings Raised floors with low finished height RANGE M0 Technical rooms with M0 requirement Offices with high acoustic performances Scientific rooms Special technical rooms SPECIAL APPLICATIONS Clean rooms Gamma, a wide selection 9 GAMMA industries France - 10/03/2009
  • 6. The response to your needs GAMMA INDUSTRIES has efficient technical and sales departments ensuring the selection of the most suitable raised floor to meet your requirements. Headquarters GAMMA INDUSTRIES A wide range of products suitable to meet your requirements. There is a family of panels to meet every requirement, and several panels to suit every room. GAMMABOX M0 BUROBOX M0 GAMMACORE GAMMABOX GAMMAPAC BUROBOX BUROPAC MINIGAM ALUCAST The families GIM OFFICE APPLICATIONS Offices Raised floors with low finished height Trading rooms - call centers - casinos Light computers rooms TECHNICAL APPLICATIONS Heavy computers Technical rooms - telephone or network centers Laboratories Heavy loads - Important heights RANGE M0 Offices inside high buildings Raised floors with low finished height Technical rooms with M0 requirement Offices with high acoustic performances SPECIAL APPLICATIONS Scientific rooms Special technical rooms Clean rooms GAMMA INDUSTRIES refers to the European Standard NF EN 12825 for all its tests and controls. 4 Gamma INDUSTRIES GAMMA industries France - 10/03/2009
  • 7. Burobox The Burobox panel is widely used in office buildings. It can be covered with textile tiles used with access flooring, free laid on site. Composition The Burobox panel is made up as follows : • A high density resin bonded core, thickness 30 or 38 mm. • A bottom tray of 0.5 mm thick galvanized steel turning up the sides of the panel. Coverings The Burobox panel is available without covering. Dimensions Standard size : 600 mm. Special size : 675 mm, for thickness 38 mm only. Options • Top varnished. • Top plate of 0.5 mm thick galvanized steel. • 19 mm thick core. Fire classification The Burobox panel is classed M1 (SNPE report n° 13149-07). Electrical resistance It varies from 5x108 to 2x1012 ohms, depending on the properties of the covering. Acoustic The acoustic insulation measured between 2 adjacent rooms, separated by a densely insulated partition, varies from 46 to 51 dBA, depending on the thickness of the panel and the covering (Dn,f,w according to Standard EN ISO 140-12). Load classes Framework Class Certificate NB : A system classed 1A is a system for Burobox 30 Self-supporting 1A (or 2B or 3C) Nr. 03.10.30.07 which the ultimate load is at least 4kN (load class 1). Stringers 30/15 2A (or 3B or 4C) Nr. 03.10.30.04 The working load of this system is at least 2 kN, with a safety factor of 2, for a deflection less Burobox 38 Self-supporting 2A (or 4B or 5C) Nr. 04.11.17.02 than 2.5 mm (deflection class A). Stringers 30/15 4A (or 5B or 6C) Nr. 04.11.17.01 See tables below for the other classes. Survey Institute : SOCOTEC CONSULTING. Load classes according to NF EN 12825 and using safety factor = 2.0. Class 1 Class 2 Class Class 4 Class Class Load class 1 2 3 4 5 6 Deflection class Maximum deflection A (the most stringent) 2.5 mm Ultimate load >4kN >6kN >8kN >9kN >10kN >12kN B 3.0 mm Working load >2kN >3kN >4kN >4.5kN >5kN >6kN C (the least stringent) 4.0 mm Burobox Gamma INDUSTRIES GAMMA industries France - 10/03/2009
  • 8. Buropac The Buropac panel has been specially designed for use in offi- ces and computer rooms. This panel is also recommended for rooms with non-magnetic requirements. It is suitable for all the coverings used with access flooring. Composition The Buropac panel is made up as follows : • A high density resin bonded core, thickness 38 mm. • A bottom aluminium foil. • An ABS surround, heat bonded to the edge of the core. Dimensions Standard size : 600 mm. Options • Bottom plate of 0.2 mm thick aluminium. • Top varnished. Fire classification The Buropac panel is classed M1 (SNPE report n° 13148-07). Electrical resistance It varies from 5x105 to 2x1012 ohms, depending on the properties of the covering. Acoustic The acoustic insulation measured between 2 adjacent rooms, separated by a densely insulated partition, varies from 44 to 50 dBA, depending on the covering (Dn,f,w according to Standard EN ISO 140-12). Load classes Framework Class Certificate NB : A system classed 1A is a system for which the ultimate load is at least 4 kN Buropac Self-supporting 1A (or 1B or 2C) Nr. 03.10.30.23 (load class 1). Stringers 30/15 2A (or 3B or 4C) Nr. 03.10.30.24 The working load of this system is at least 2 kN, with a safety factor of 2, for a deflection less than 2.5 mm (deflection class A). See tables below for the other classes. Survey Institute : SOCOTEC CONSULTING. Load classes according to NF EN 12825 and using safety factor = 2.0. Class 1 Class 2 Class Class 4 Class Class Load class 1 2 3 4 5 6 Deflection class Maximum deflection Ultimate load >4kN >6kN >8kN >9kN >10kN >12kN A (the most stringent) 2.5 mm B 3.0 mm Working load >2kN >3kN >4kN >4.5kN >5kN >6kN C (the least stringent) 4.0 mm Buropac Gamma INDUSTRIES GAMMA industries France - 10/03/2009
  • 9. Gammabox The Gammabox panel has been specially designed to meet the requirements of technical, data processing and scientific applications. It is suitable for all the coverings used with access flooring, excepted textile and mineral coverings. Composition The Gammabox panel is made up as follows : • A high density resin bonded core, thickness 30 or 38 mm. • A bottom tray of 0.5 mm thick galvanized steel. • A perimeter plastic edge trim slotted into the sides of the panel. Coverings The Gammabox panel is available with the following coverings : • High pressure laminate • Linoleum • Vinyl • Rubber Dimensions Standard size : 600 mm. Fire classification The Gammabox panel is classed M1 (SNPE report n° 13149-07). Electrical resistance It varies from 5x105 to 2x1012 ohms, depending on the properties of the covering. Acoustic The acoustic insulation measured between 2 adjacent rooms, separated by a densely insulated partition, varies from 46 to 51 dBA, depending on the thickness of the panel and the covering (Dn,f,w according to Standard EN ISO 140-12). Load classes Framework Class Certificate Gammabox 30 Self-supporting 1A (or 2B or 3C) Nr. 03.10.30.10 NB : A system classed 1A is a system for which the ultimate load is at least 4kN Stringers 30/15 2A (or 3B or 4C) Nr. 03.10.30.01 (load class 1). 5A (or 5B or 5C) Nr. 03.10.30.05 The working load of this system is at least 2 kN, Stringers 45/15 with a safety factor of 2, for a deflection less than 2.5 mm (deflection class A). Gammabox 38 Self-supporting 3A (or 5B or 5C) Nr. 04.11.17.03 Stringers 30/15 5A (or 6B or 6C) Nr. 04.11.17.04 See tables below for the other classes. Survey Institute : SOCOTEC CONSULTING. Load classes according to NF EN 12825 and using safety factor = 2.0. Class 1 Class 2 Class Class 4 Class Class Load class 1 2 3 4 5 6 Deflection class Maximum deflection Ultimate load >4kN >6kN >8kN >9kN >10kN >12kN A (the most stringent) 2.5 mm B 3.0 mm Working load >2kN >3kN >4kN >4.5kN >5kN >6kN C (the least stringent) 4.0 mm Gammabox Gamma INDUSTRIES GAMMA industries France - 10/03/2009
  • 10. Gammacore The Gammacore panel is famous on the world market for its quality, design and finish. It is characterized by an extruded aluminium edging inserted into the core. This panel has been designed to meet the requirements of technical, data processing and scientific applications. It is suitable for all the coverings used with access flooring, except textile and mineral coverings. Composition The Gammacore panel is made up as follows : • A high density resin bonded core, thickness 30 mm. • A bottom plate of 0.5 mm thick galvanized steel. • A peripheral extruded aluminium section inserted into the core and holding the edge trim. • A plastic edge trim slotted into the above mentioned aluminium section. Coverings The Gammacore panel is available with the following coverings : • High pressure laminate • Linoleum • Vinyl • Rubber Dimensions Standard size : 600 mm. Special sizes, on request. Fire classification The Gammacore panel is classed M1 (SNPE report n° 13149-07). Electrical resistance It varies from 5x105 to 2x1012 ohms, depending on the properties of the covering. Acoustic The acoustic insulation measured between 2 adjacent rooms, separated by a densely insulated partition, varies from 46 to 51 dBA, depending on the covering (Dn,f,w according to Standard EN ISO 140-12). Load classes Framework Class Certificate NB : A system classed 1A is a system for which the ultimate load is at least 4 kN Gammacore Self-supporting 1A (or 2B or 4C) Nr. 03.10.30.12 (load class1). Stringers 30/15 2A (or 3B or 5C) Nr. 03.10.30.03 The working load of this system is at least 2 kN, with a safety factor of 2, for a deflection less than 2.5 mm (deflection class A). See tables below for the other classes. Survey Institute : SOCOTEC CONSULTING. Load classes according to NF EN 12825 and using safety factor = 2.0. Class 1 Class 2 Class Class 4 Class Class Load class 1 2 3 4 5 6 Deflection class Maximum deflection Ultimate load >4kN >6kN >8kN >9kN >10kN >12kN A (the most stringent) 2.5 mm B 3.0 mm Working load >2kN >3kN >4kN >4.5kN >5kN >6kN C (the least stringent) 4.0 mm Gammacore Gamma INDUSTRIES GAMMA industries France - 10/03/2009
  • 11. Gammapac Gammapac panels are multipurpose panels designed to meet a wide range of applications. They are suitable for all coverings used with access flooring. Composition The Gammapac panel is made up as follows : • A high density resin bonded core, thickness 30 mm or 38 mm. • A bottom plate of 0.5 mm thick galvanized steel. • An ABS surround, heat bonded to the edge of the core. Coverings The Gammapac panel is available with the following coverings : • High pressure laminate • Linoleum • Vinyl • Textile covering • Rubber Dimensions Standard size : 600 mm. Size 675 mm for thickness 38 mm. Special sizes, on request. Options For panels without covering only : • Top varnished. • Top plate of 0.5 mm thick galvanized steel. Fire classification The Gammapac panel is classed M1 (SNPE report n° 13149-07). The Gammapac panel, 38mm thick, is classed F30, according to DIN 4102. Electrical resistance It varies from 5x105 to 2x1012 Ohms, depending on the properties of the covering. Acoustic The acoustic insulation measured between 2 adjacent rooms, separated by a densely insulated partition, varies from 44 to 50 dBA, depending on the thickness of the panel and the covering (Dn,f,w according to Standard EN ISO 140-12). Load classes Framework Class Certificate Gammapac 30 Self-supporting 1A (or 1B or 2C) Nr. 03.10.30.08 NB : A system classed 2A is a system for without covering which the ultimate load is at least 6kN Stringers 30/15 2A (or 3B or 4C) Nr. 03.10.30.05 (load class 2). The working load of this system is at least 3 kN, Gammapac 30 Self-supporting 2A (or 2B or 3C) Nr. 03.10.30.11 with a safety factor of 2, for a deflection with HPL covering Stringers 30/15 2A (or 3B or 4C) Nr. 03.10.30.02 less than 2.5 mm (deflection class A). Gammapac 38 Self-supporting 2A (or 4B or 5C) Nr. 03.07.10.06 See tables below for the other classes. Stringers 30/15 4A (or 5B or 5C) Nr. 03.07.10.08 Stringers 45/15 5A (or 5B or 5C) Nr. 03.07.10.10 Survey Institute : SOCOTEC CONSULTING. Load classes according to NF EN 12825 and using safety factor = 2.0. Class 1 Class 2 Class Class 4 Class Class Load class 1 2 3 4 5 6 Deflection class Maximum deflection Ultimate load >4kN >6kN >8kN >9kN >10kN >12kN A (the most stringent) 2.5 mm B 3.0 mm Working load >2kN >3kN >4kN >4.5kN >5kN >6kN C (the least stringent) 4.0 mm Gammapac Gamma INDUSTRIES GAMMA industries France - 10/03/2009
  • 12. Burobox The Burobox M0 panel is widely used in office buildings. M0 It can be covered with textile tiles used with access flooring, free laid on site. Composition The Burobox M0 panel is made up as follows : • A mineral core, 19 to 30 mm thick. If required, this core may be covered with galvanized steel. Coverings The Burobox M0 panel is available without covering. Dimensions Standard size : 600 mm. Special size : module 675 mm. Options • Bottom tray of 0.5 mm thick galvanized steel turning up the sides of the panel. • Top plate of 0.5 mm thick galvanized steel. Fire classification The Burobox M0 panel is classed M0 (SNPE reports n° 1152-03 and 12215-05). Electrical resistance It varies from 5x10 8 to 2x10 12 ohms, depending on the properties of the covering. Acoustic The acoustic insulation measured between 2 adjacent rooms, separated by a densely insulated partition,varies from 49 to 54 dBA, depending on the thickness of the panel and the covering (Dn,f,w according to Standard EN ISO 140-12). Load classes NB : A system classed 1A is a system for Burobox M0 From 1 A à 3 A depending on thickness of the mineral and which the ultimate load is at least 4kN (load class1). steel plates used. The working load of this system is at least 2 kN, with a safety factor of 2, for a deflection less than 2.5 mm (deflection class A). See tables below for the other classes. Survey Institute : SOCOTEC CONSULTING. Load classes according to NF EN 12825 and using safety factor = 2.0. Class 1 Class 2 Class Class 4 Class Class Load class 1 2 3 4 5 6 Deflection class Maximum deflection A (the most stringent) 2.5 mm Ultimate load >4kN >6kN >8kN >9kN >10kN >12kN B 3.0 mm Working load >2kN >3kN >4kN >4.5kN >5kN >6kN C (the least stringent) 4.0 mm Burobox M0 Gamma INDUSTRIES GAMMA industries France - 10/03/2009
  • 13. Gammapac M0 The family Gammapac M0 panels are multipurpose panels designed to meet a wide range of applications. They are widely used to suit access floors in High Rise Buildings. Composition The Gammapac M0 panel is made up as follows : A mineral core 30 mm thick. A bottom 0.5mm thick galvanized steel plate. A PVC/ABS surround heat bonded to the edge of the mineral core. Coverings The Gammapac M0 panel is available with the following coverings : High Pressure Laminate Vinyl or Linoleum Carpet in free laid tiles This panel may be supplied without covering. Dimensions Standard size : 600 mm Options For panels without covering only: Top varnished Fire classification The Gammapac M0 panel is classed M0. Electrical Résistance Depending on the properties of the covering, it varies from 5.105 to 2.1012 ohms, measured with the covering. Acoustic The acoustic insulation measured between 2 adjacent rooms separated by a densely insulated partition, varies from 49 to 54 dBA depending on the covering (Dn,f,w according to Standard NF EN ISO 10848-2). Load Classes Framework Class Certificate NB : A system classed 1A is a system for which the ultimate load is at least 4 kN (load class 1). GAMMAPAC Self-supporting 1A (or 1B or 1C) Nr. 08.12.0205 The working load of this system is at least 2kN with a M0 safety factor equal to 2, for a deflection less than 2.5mm Stringers 30/15 2A (or 2B or 2C) Nr. 08.12.2205 (Deflection Class A). See tables below for the other classes. Stringers 45/15 2A (or 2B or 2C) Nr. 08.12.3205 Load classes according to NF EN 12825 – Safety factor = 2 Load Class 1 2 3 4 5 6 Deflection Class Maximum Deflection Ultimate load > 4kN > 6kN > 8kN > 9kN > 10kN > 12kN A (the more stringent) 2.5 mm Working load > 2kN > 3kN > 4kN > 4.5kN > 5kN > 6kN B 3.0 mm C (the least stringent) 4.0 mm Gammapac M0 GAMMA industries France - 10/03/2009
  • 14. Minigam The Minigam panel has been designed for offices where the available height for access floors is limited. The Minigam panel is classed M0 (incombustible), and is characterized by a thickness of 19mm only. It can be covered with textile tiles used with access flooring, free laid on site. Composition The Minigam panel is made up as follows : • A mineral core 18 mm thick. • A steel tray 0,5 mm thick. • A top steel sheet 0,5 mm thick. Coverings The Minigam panel is available without covering. Dimensions Standard size : 500 mm. Fire classification Minigam panel is classed M0 (SNPE 11152-03). Electrical resistance It varies from 5x108 to 2x1012 ohms, depending on the properties of the covering. Acoustic The acoustic insulation measured between 2 adjacent rooms, separated by a densely insulated partition, varies from 47 to 50 dBA, depending on the covering (Dn,f,w according to Standard EN ISO 140-12). Load classes NB : A system classed 1A is a system for which the ultimate load is at least 4kN (load class 1). Framework Class Certificate The working load of this system is at least 2 kN, with a safety factor of 2, for a deflection Minigam Self-supporting 1A (or 1B or 1C) Nr. 03.10.30.20 less than 2.5 mm (deflection class A). See tables below for the other classes. Survey Institute : SOCOTEC CONSULTING. Load classes according to NF EN 12825 and using safety factor = 2.0. Class 1 Class 2 Class Class 4 Class Class Load class 1 2 3 4 5 6 Deflection class Maximum deflection Ultimate load >4kN >6kN >8kN >9kN >10kN >12kN A (the most stringent) 2.5 mm B 3.0 mm Working load >2kN >4kN >4kN >4.5kN >5kN >6kN C (the least stringent) 4.0 mm Minigam Gamma INDUSTRIES GAMMA industries France - 10/03/2009
  • 15. Alucast Alucast is an aluminium die-cast panel of great strength. Alucast is suitable for industrial and high-tech clean room installations, and for rooms with non-magnetic requirements. The panel is suitable for all the soft coverings normally used for access flooring. Composition The Alucast aluminium is made up as follows : • A top distributor plate, 3 mm thick. • A double peripheral reinforced rib. • A network of central ribs. The monolithic conception of Alucast panels enables to reach the levels of performance and accuracy required for high-tech applications. Coverings The Alucast panel, plain or perforated, is available with the following finishes : • vinyl. • rubber Alucast PF2 : Perforated panel 11 % The Alucast grating (AF6) is available rough or epoxy painted. Dimensions Standard size : 600 mm. Fire classification Without covering, the Alucast panel is classed M0 (incombustible), by nature. Alucast PF4 : Perforated panel 22 % Electrical Resistance It varies from 5x105 to 2x1012 ohms, depending on the properties of the covering. Range of perforations • Alucast PF1 : Perforated panel, 7 % free area. • Alucast PF2 : Perforated panel, 11 % free area. • Alucast PF3 : Perforated panel, 15 % free area. • Alucast PF4 : Perforated panel, 22 % free area. Alucast AF6 : Grating 60 % • Alucast AF5 : Perforated panel, 40 % free area. • Alucast AF6 : Grating, 60 % free area. Load classes Framework Class Certificate NB : A system classed 6A is a system for which the ultimate load is at least 12 kN Alucast plain panel Self-supporting 6A (or 6B or 6C) Nr. 03.10.30.13 (load class 6). The working load of this system is at least 6kN, Alucast PF4 (22%) Self-supporting 6A (or 6B or 6C) Nr. 03.10.30.14 with a safety factor of 2, for a deflection less than 2.5 mm (deflection class A). See tables below for the other classes Survey Institute : SOCOTEC CONSULTING. Load classes according to NF EN 12825 and using safety factor = 2.0. Class 1 Class 2 Class Class 4 Class Class Load class 1 2 3 4 5 6 Deflection class Maximum deflection A (the most stringent) 2.5 mm Ultimate load >4kN >6kN >8kN >9kN >10kN >12kN B 3.0 mm Working load >2kN >3kN >4kN >4.5kN >5kN >6kN C (the least stringent) 4.0 mm Alucast Gamma INDUSTRIES GAMMA industries France - 10/03/2009
  • 16. Gim The Gim Panel, made of a robust welded steel structure, is designed for use in heavy duty industry : offshore platforms, Navy, clean rooms, or machinery rooms. It is suitable for all the coverings used with access flooring. Composition The Gim panel is made up as follows : • A top distributor plate of 3 mm thick steel. • A peripheral steel hollow section welded to the distributor plate. • Central steel bars welded to the distributor plate. • A plastic edge fixed to the distributor plate. All the visible surfaces of the Gim panel are painted. Coverings The Gim panel is available with the following coverings : • High pressure laminate • Linoleum • Vinyl • Rubber The Gim panel is also available without covering. Dimensions Standard size : 600 mm. Special sizes, on request. Fire classification Without covering, the Gim panel is classed M0 (incombustible), by nature. Electrical resistance It varies from 5x105 to 2x1012 ohms, depending on the properties of the covering. Load classes Framework Class Certificate NB : A system classed 5B is a system for Gim Self-supporting 5B Nr. 06.10.0905 which the ultimate load is at least 10 kN Stringers 30/15 6C (load class 5). Nr. 06.10.4917 The working load of this system is at least 5kN, with a safety factor of 2, for a deflection less than 3 mm (deflection class B). See tables below for the other classes. Survey Institute : SOCOTEC CONSULTING. Load classes according to NF EN 12825 and using safety factor = 2.0. Class 1 Class 2 Class Class 4 Class Class Load class 1 2 3 4 5 6 Deflection class Maximum deflection Ultimate load >4kN >6kN >8kN >9kN >10kN >12kN A (the most stringent) 2.5 mm B 3.0 mm Working load >2kN >3kN >4kN >4.5kN >5kN >6kN C (the least stringent) 4.0 mm Gim Gamma INDUSTRIES GAMMA industries France - 10/03/2009
  • 17. Pedestals The pedestals are made up of : • a square baseplate of galvanized steel. • a steel galvanized column welded to the baseplate. • a die-cast aluminium or steel head, according to the type of pedestal. • a locking nut for height adjustment. Standard pedestal The head has a sufficient length to adjust the height + or - 20 mm. Ridges moulded on the head allow a positive location of the panels. Pedestal for low finished height The threaded steel head allows an adjustment of + or - 7 mm. The panels lay directly on a conductive pad. These pedestals allow a minimum finished height of 70 mm. Pedestal for great finished height (more than 800 mm) The column is a square hollow section of galvanized steel. The base, the head and the locking nut are the same as for the Standard pedestal standard pedestal. Installation The pedestals are bonded to the concrete by way of a special adhesive, or may be mechanically fixed. A device on the baseplate permits a quick and safe fixing of the copper earthing strap. Pedestal low height Pedestal great height Stringers Lockable stringers They are made of galvanized steel . They are designed for location on pedestal heads. The stringers provide rigidity to the understructure, and stability against lateral strain. The depth of the section is adapted to the required performances : • 30 mm deep : type 30/15. • 45 mm deep : type 45/15. Special stringers When pedestals are omitted due to obstructions, i.e. electrical services, Lockable stringer air ducting, etc., special bridging stringers may be used. Within these particular areas, its is admitted that the deflection may be 20% more than for the rest of the raised floor. 31bis, rue des Longs Prés 92100 Boulogne - Billancourt (France) Gamma INDUSTRIES Tel. : 33 (0)1 41 23 10 21 - Fax : 33 (0)1 41 23 10 01 Raised access floors www.gamma-industries.com GAMMA industries France - 10/03/2009
  • 18. Detailed Gim-Pf sketches The Gim-Pf panels allow air supply at any loca- tion of the access floor. These panels are entirely made of steel and compatible with all other Gamma panels. Riser Standard perimeter detail Minimum width of perimeter cuts : 100mm Loading performances The load classes of the Gim-Pf panels are identical to the classes of the panels they are mixed with. Air flow Characteristics Special perimeter detail Special perimeter detail Minimum free height : 50mm Maximum void width : 60mm The total free area per panel is 8 dm2. Optional adjustable sliding dampers can be fitted for adjustment of the air flow. The graph below shows the possible air flow according to the air pressure in the plenum and the air pressure drop according to the air flow. 100 With fully open damper 90 Overpressure in the plenum in Pa 80 70 60 50 Without damper 40 30 20 10 Dilatation joint Detail of profile over void along Flow m3/ h Standard case facade 0 20 0 40 0 60 0 80 0 00 200 00 00 00 00 00 10 1 14 16 18 20 22 Void greater than 60mm 0 1 2 3 4 5 6 7 Free section airspeed in m/s 6 Gamma INDUSTRIES GAMMA industries France - 10/03/2009
  • 19. Accessories Ramps Steps and risers The ramps are generally made of a wooden Steps and risers are made of white melamine frame, and finished with a black anti-slip boards and their top edging is finished with rubber. an anti-slip aluminium nosing. The junction between the ramp and the The steps are covered with an anti-slip rubber access floor is a metallic profile. The ramp covering. nosing is made of an aluminium profile. The recommended slope of a ramp is 5%, with a maximum of 10%. Handling of loads on the ramps must be made with appropriate means, under the responsability of the user. Installation with stringers Bridging profiles For this type of installation, panels lay on Bridging profiles are used when a raised metallic stringers. Stringers are used : floor must be installed over ducts, channels, conduits, or holes of large sizes. • For finished heights greater than 500mm. • For raised floors which are not surrounded These bridging profiles enable to suppress by walls, or which have to take loads with one or several pedestals. frequent removals. • For important point loads or distributed loads. • For raised floors including a large number of cut-outs. Plenum dividers Coverings When required by regulations, plenum Some of our panels are suitable for the dividers made of non combustible materials following coverings : can be supplied. High pressure laminate Vinyl Linoleum Textile Rubber Wood Some others are available without covering. They can be covered with textile tiles used with access flooring, free laid on site. Panel lifting device Outlets, type brush or type PVC Gamma, an easy technology 5 GAMMA industries France - 10/03/2009
  • 20. Technical information Requirements for rooms to be installed with access floors (DTU 57-1) • Rooms must not be exposed to bad weather. • Rooms must be equipped with outside glazing. • Concrete slab and plaster walls must be dry. • Concrete slab must be conform to article 5.2.2 of DTU 21: the raw concrete is not allowed. The upper part of the concrete must resist when trying to tear up manually a pedestal base bonded to the concrete. The concrete must be able to take the weight of the raised floor and the loads transmitted by the pedestals bases. • Rooms must not be encumbered with materials or tools and get a dry and clean concrete. • Rooms must be free of any of the other trade during installation. • All rooms adjacent to the access floor must have the same floor height. • The ambient temperature of the rooms where the access floor is to be installed should be kept between 5°C and 24°C and the relative humidity between 45% and 70 %. If the temperature is above 24°C (but never above 30°C) the relative humidity should not be over 50%. The subfloor temperature should not be below 5°C. • No water or any other liquid should be spread under or on top of the access floor. • No other trade is allowed to walk on the raised floor during its installation, for at least 48 hours. Installation • The required finished level of the raised floor must be materialized by the architect or the building owner. The location of the first panel to be installed is determined by the drawings, in such a way that the width of the panels cut along the walls will be more than 100 mm, providing a good stability. • Handling and installation of any equipment or heavy material must be done on an added boarded flooring or load-spreading plates, rigid enough to spread the loads, to prevent overloading, tearing or scratching of the floor covering. Coverings Coverings to be used • High pressure laminates : these coverings must not be used within rooms where abrasive dust may lay on the floor. • Soft coverings : vinyl, rubber or linoleum. • Textile coverings : needlepunch carpets, cut-piles carpets. • Parquets, mineral coverings and ceramics : the technical characteristics of these coverings must be checked carefully in order to determine if they can be used with raised floors. Suitability of coverings High pressure laminates must be conform to Standard NF EN 438, NF EN 685 and NF EN 14041. The resilient floor coverings used with raised floors must be classed minimum 32 according to the classification of the Standard NF EN 685. Textile coverings to be used with raised floors must be classed 3 or 4 according to the classification of Standards NF EN 1470 or NF EN 1307, according to the type of covering. The design of the covering must not require any joint or centering, and tiles of covering must be interchangeable. Factory bonded coverings Floor coverings with a foam backing must be excluded. Free laid coverings It concerns carpets tiles, free laid on site. Their dimensions, squareness, stability and installation must be conform to the requirements of the Standard NFP 62.202.1 (reference DTU 53.1). The use of a permanent adhesive between the raised floor and the carpet tiles must not make dismantling of the raised floor panels difficult. It is recommended not to aline carpet tiles and raised floor panels. Maintenance Excessive use of liquid products must be avoided. The use of water can provoke swelling, oxidizing or destruction of the components of the panels. Cleaning products can damage the adhesives on the edges and corners. Even small quantities of a product can laminate the covering. Every covering has a data sheet for maintenance. Gamma, total safety 7 GAMMA industries France - 10/03/2009
  • 21. Technical information Mechanical performances and loading A raised floor must be designed and produced in such a way to ensure the required mechanical resistance and stability. The required wor- king load must not cause deformation or failure of the raised floor. All systems must be tested according to requirements of the Standard NF EN 12825, and classifcations obtained after these tests must be certified by an official test report from an independant body. Acoustic insulation When tested according to Standard EN ISO 140-12, our access floors can reach airborne sound insulation values from 44 to 54 dbA. The insulation to impact sound depends mainly on the type of coverings bonded on the panels. The textile coverings are the most efficient. Fire protection The regulations for access flooring refer to : • the reaction to fire • the partitioning of the plenum • the calorific potential They vary according to the use of the rooms and the classification of the building inside which the access floors are installed. Reaction to fire In France, the Decree dated June 30 th, 1983 defines 5 classes for the materials : M0, M1, M2, M3, M4. The test method used is the radiation test. The tested side is the bottom of the panel. The classification of the superior part of the panel is the same as for the covering. Partitioning of the plenum When required by regulation, plenum dividers made of non combustible materials can be supplied. Every partitioned area has a maximum surface of 300m2 and a maximum length of 30 meters. In case of fire, the partitioning limits the air circulation inside the plenum. Electrostatic properties The ability of a covering to accumulate electrostatic loads, and its ability to eliminate these loads are essential for the antistatic properties of an access floor. The measurement of the transversal resistivity (Ret) enables the estimation of the ability to eliminate electrostatic loads. Coverings are classed according to NF P 62.001 (Resilient floor coverings - Electrostatic behaviour) : Class 1 : Astatic covering : RET > 1.109 (ohms) and electrostatic charging potential < 2 KV. 7 Class 2 : Dissipative covering : 1.10 < RET < 1.109 (ohms) and electrostatic charging potential < 2 KV. 7 Class 3 : Conductive covering : RET < 1.10 (ohms) and electrostatic charging potential < 2 KV. All raised floors must have a transversal resitivity between 5.105 and 2.1012 ohms. The equipotential connection is made by a copper strap network connecting certain pedestals to each other. This network is earthed by the companies in charge of the electrical wiring. 8 Gamma INDUSTRIES GAMMA industries France - 10/03/2009