NER Data Corporation White Paper

Thermal Monitoring Best Practices
Benefits gained through proper deployment and utilizing sensors that
work with evolving monitoring systems
Introduction
Data centers are dynamic environments that change based on evolving business requirements. Monitoring your
physical infrastructure is key ensuring business continuity, preventing disruption of service, meeting compliance
requirements, reducing costs and increasing ROI. Decisions made today affect your ability to monitor and
manage your future state. Monitoring and management requirements change over time, so best practices use the
deployment of tools that meet the needs of today while allowing for changes in the future.

Best Practice: Monitor Temperature at Multiple Rack Level Points
The 2013 Uptime Institute Data Center Industry Survey reported “..only 15% of the data center managers
responding to the survey said they were measuring and controlling air temperatures from the server inlet, which is
the most accurate location. Nearly a third of the respondents are managing inlet air temperature at the room
level, which is the least accurate method. Obviously there is room for some further cooling efficiency
improvements.”
Thermal monitoring should be conducted at the rack and key points
within the data center to properly protect equipment and to gather
data for cost saving optimization.
A goal in data center cooling is to maintain server rack exhaust temp
under 100*F and a Rack Delta temperature of around 20*F while
targeting the highest efficiency. In order to do this you must monitor
rack intake and exhaust tempertures at various heights. Rack inlet
and exhaust temperatures can vary over 10*F within just 8". The
American Society of Heating, Refrigerating and Air-Conditioning
Engineers (ASHRAE) recommends at least 6 temperature sensors
per rack (top, middle, bottom / front and back).
Monitoring return air temps at the CRAC unit provides valuable
information but only measures intermixed air. This method leaves
gaps for hot (under provisioned) areas and cold (over provisioned)
areas at the rack level. Measurements taken at multiple points at the
rack as described above and at the CRAC feed and return provide you with actionable information:
1. Divide each individual CRAC unit return air temperatures to the average rack exhaust temperature to
determine the return path efficiency. Example: CRAC unit 1 return air temperature average is 76°F. The
average server rack exhaust temperature is 88°F. There is a 12°FΔT so the return air path back to CRAC
1 is 86% efficient.
2. Next determine the cooling delivery efficiency. Divide the CRAC unit feed temperature by the average
rack inlet temperature for each CRAC unit. Example: CRAC unit 1 feed air temperature average is 52°F.
The Average server inlet temperature is 58°F. There is a 6°FΔT so the cool air distribution is 89%
efficient.
3. Finally determine the overall airflow distribution efficiency by averaging the efficiency rating for distribution
and return together. Example: CRAC unit 1 return airflow efficiency is 86% and the cool air distribution is
89% efficient. The overall airflow distribution efficiency for CRAC 1 is 87.5%.

Page 2
By measuring at the rack and key points within the data center you will know what is changing in your data center
and you can clearly see:
· where the highest capacity exist in the rack
· where available cooling capacity exist
· cooling effectiveness at the rack and data center levels
· whether you are over/under provisioning cooling per rack
· problem alerting
· seasonal and weather impacts on server cooling
· cooling policy and SLA enforcement
· local problem solving such as blanking panel placement
· proof of concept pre and post deployment

Temperature is Just Part of the Cooling Equation
There are four values which affect the cooling properties of air:
Temperature, Humidity, Pressure, and Flow
A change in any one of these values will effectively alter the air’s ability to cool an electrical heat load as
illustrated in the examples below:
Baseline server rack with a 12kW load is introduced cooling air with the following values:
Temperature: 70°F, Relative Humidity: 50%, Pressure, Sea Level @ 14.7 psi, Flow: 1900cfm = exhaust
temperature of 90°F and 20 Δ°F temperature
(Note: changing the temperature also changes the relative humidity)
.
· Example 1: Lower Temperature to 55°F, Relative Humidity: 50%, Pressure, Sea Level @ 14.7 psi,
Flow: 1900cfm = exhaust temperature of 74.3°F and 19.3Δ°F temperature rise.
·

Example 2: Temperature:70°F, Relative Humidity: 50%, Pressure, Sea Level @ 14.7 psi,
Reduce Flow to 1500cfm = exhaust temperature of 95.3°F and 25.3Δ°F temperature rise.

·

Example 3: Increase Temperature to 77°F, Relative Humidity: 50%, Pressure, Sea Level @ 14.7 psi,
Reduce Flow to 1750cfm = exhaust temperature of 99°F and 22Δ °F temperature rise.

·

Example 4: The same server rack and airflow values as the Baseline, only this time we reduce the air
pressure by placing the rack in Denver Co. with an elevation of 5,280 feet. The result is an exhaust
temperature of 94.3°F and 24.3 Δ °F temperature rise.

These cooling examples show that monitoring temperature at the rack intake is just a piece of the puzzle and a
change in any variable can affect cooling. Through continual monitoring and measuring it may be possible to
adjust temperature (and corresponding humidity) and flow while still staying within a desired server exhaust
temperature. Benefits come in cost savings through reduced compressor and fan energy usage.
To optimize monitoring and management, temperature sensors should be positioned along the front and rear of
each priority rack. Also barometric and humidity sensors should be placed within the aisle where these racks
reside.

Page 3
Aurora High Resolution Temperature Strip Enables Best-Practice
Rack Level Thermal Monitoring
The Aurora consists of innovative patent-pending technology that couples a series of 8 thermally
isolated temperature sensors with an array of high intensity LEDs. Aurora visually displays
temperature reading similar to a CFD through a range of cool (blue) to hot (red) and a blend of 129
colors in between.
With 8 sensors per strip, temperature is monitored over the entire height of the cabinet; perfect for
meeting ASHRAE recommendations, aisle containment and areas susceptible to temperature
stratification. Sensors start 4.5” from bottom of unit and end at 60.5” to provide measuring of
temperature fluctuations within 8” increments. Used as self-policing, real-time troubleshooting tool, it
clearly identifies potential cooling or heat-related issues and provides instantaneous feedback that is
invaluable when monitoring changes or validating best-practice improvements.
Aurora is extremely accurate because it measures air temperature, not surface temperature. Three
User-Selectable Sensitivity Settings allow for fine tuning of the monitored temperature range over the
full 129-color spectrum.
·

Low setting concentrates the color spectrum towards the colder end of the temperature
scale. The 129 colors will vary between 25 degrees F (50°F/10°C to 75°F/23.8°C). This
setting offers more color resolution for colder data centers such as cold aisle containment.

·

Medium setting closely reflects the ASHRAE standards for acceptable equipment inlet
temperatures. The 129 colors will vary between 25 degrees F (65°F/18.3°C to 90°F/32.2°C).

·

High setting concentrates the color spectrum towards the
hotter end of the temperature scale. The 129 colors will vary
between 25 degrees F (70°F/21.1°C to 95°F/35°C). This
setting offers more color resolution for data centers with
hotter temperature settings. This setting is also suitable for
positioning the Aurora Temperature Strip in the hot aisle.

.

Benefits of Visual Alerting
Studies on human behavior show that warnings are most effective
when they are presented proximate (in time and space) to the
hazard. By visually indicating the issue in both a Management
System interface and at the exact physical location, time to
remediation can be decreased. With automated alerts and easy to
comprehend alerts at the point of hazard,
every team member can insure that no
issue goes unnoticed.

Page 4
Managing Alerts
Centralized management systems provide a way to capture,
manage, and effectively use sensor data. Down-time causing
events can be avoided or minimized through monitoring systems
that allow IT staff to quickly respond to environmental changes
and alerts. In advanced systems, alerts can trigger automated
response such as adjusting VFD controllers for target areas
based on alert thresholds.
Through the use of real-time data, Monitoring Solutions take the
guess-work out of decision making and planning processes.
Sensors provide important inputs for establishing baseline
conditions, trending, capacity planning, validating best-practice
improvements, monitoring changes, and confirming compliance
with company mandates.

According to the Uptime Institute 2013
Data Center Industry Survey:
“Data center infrastructure management
(DCIM) software adoption seems to have
skyrocketed. An astounding 38% reported
that they have deployed DCIM software.”
“That’s not to say that the companies
have fully installed the tools, or are
reaping the rewards of the software’s
capabilities. For many companies, it’s just
the beginning of a long cycle of
implementation and maintenance of the
systems.”

Best Practice: Use Adaptable Sensors and Systems
The Aurora Strip is designed to work in any data center environment – from basic server rooms without
monitoring applications to Tier 4 data centers that deploy sophisticated DCiM systems. For data centers with
existing monitoring and DCiM solutions, Aurora can be integrated to provide data to these systems. Data from
the strips can interact with systems to provide automated remediation such as adjusting VFD controllers. In
addition, Aurora’s resource-saving communications require just one port to capture up to 800 different sensor
readings.
For data centers without existing monitoring systems, the Aurora strip can be used as a stand-alone visual
monitoring tool. However, a centralized monitoring system allows administrators to respond quickly and truly reap
the benefits of the sensor data. Deploying such a system can be costly and overwhelming, but the Aurora
Wireless Management Application (cloud-based and enterprise) is an easy avenue for data centers to move to the
next level of monitoring and management. The system provides for monitoring of additional sensor types
(humidity, fluid detection, airflow, etc.), automated alerts, powerful visual mapping tools, data trending/reporting,
and API commands for integrating with 3rd party applications.

Page 5
Aurora Wireless Management Application Features
·

Complete configuration and customization at a sensor, local network, or client wide level

·

Notifications via SMS text and email

·

Unlimited sensor data storage and trending

·

Unlimited user accounts for system configuration, monitoring and notifications

·

Sensor heartbeats (check-ins) down to 10 minutes:
o Timed sensors (i.e. temperature) can be user-set to check against alert thresholds up to 256
times between heartbeats
o Triggered sensors (i.e. motion, door/window, etc.) record data as it happens, regardless of
heartbeat

·

Advanced sensor configuration options:
o Automatic sensor recovery attempts
o Sensor inactivity alerts
o Sub-heartbeat assessments with alert thresholds
o Sensor aware state reporting

·

Advanced Thermographic Sensor Mapping tool

·

Sensor Grouping feature allows onscreen sensors to easily be arranged to exactly match physical strip
deployments

·

API commands for integrating into 3rd party applications

Page 6
Summary
Environmental monitoring and management systems are crucial to running efficient data centers. The data
provided is used to avoid downtime, increase efficiency, aid in capacity planning, and lower operating costs. At
the root of these systems are sensors that collect the data for analysis. Best practices involve utilizing sensors
that are scalable, flexible, and can be deployed as stand-alone systems or can be integrated into existing
monitoring systems. The Aurora Solution allows you easily achieve a best practice deployment.
More information including an overview video can be found at www.nerdata.com/Aurora

About NER Data Corporation
NER Data Corporation is an innovative leader in the demanding, growing, and continually changing Data Center
Infrastructure Management and Managed Print businesses. NER offers unique value-add solutions that truly solve
business issues and allow reseller partners to develop and maintain stronger relationships with their end-users.
Our approach has earned NER a loyal following with North America’s leading Resellers, Integrators, VARS, and
their Fortune 2000 end-user customers. For more information, visit www.nerdata.com.

www.nerdata.com
888-NER-DATA  637-3282

Copyright © 2014 NER Data Corporation

Page 7

Contenu connexe

Tendances

2008 09-16-presentation
2008 09-16-presentation2008 09-16-presentation
2008 09-16-presentation
greenlane
 
AMD 00.DMP.1014 R3 6-2015
AMD 00.DMP.1014 R3 6-2015AMD 00.DMP.1014 R3 6-2015
AMD 00.DMP.1014 R3 6-2015
Julie Bernett
 
Basic Mechanical Engineering - Air conditioning
Basic Mechanical Engineering - Air conditioningBasic Mechanical Engineering - Air conditioning
Basic Mechanical Engineering - Air conditioning
Steve M S
 

Tendances (20)

Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
 
How IT Decisions Impact Facilities: The Importance of Mutual Understanding
How IT Decisions Impact Facilities: The Importance of Mutual UnderstandingHow IT Decisions Impact Facilities: The Importance of Mutual Understanding
How IT Decisions Impact Facilities: The Importance of Mutual Understanding
 
Myths of Data Center Containment:Whats's True and What's Not
Myths of Data Center Containment:Whats's True and What's NotMyths of Data Center Containment:Whats's True and What's Not
Myths of Data Center Containment:Whats's True and What's Not
 
Psychrometrics
PsychrometricsPsychrometrics
Psychrometrics
 
2008 09-16-presentation
2008 09-16-presentation2008 09-16-presentation
2008 09-16-presentation
 
For Most Data Centers, Liquid and Air Cooling Will Not be Mutually Exclusive
For Most Data Centers, Liquid and Air Cooling Will Not be Mutually ExclusiveFor Most Data Centers, Liquid and Air Cooling Will Not be Mutually Exclusive
For Most Data Centers, Liquid and Air Cooling Will Not be Mutually Exclusive
 
I Work for free
I Work for freeI Work for free
I Work for free
 
Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's
Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T'sData Center Cooling Efficiency: Understanding the Science of the 4 Delta T's
Data Center Cooling Efficiency: Understanding the Science of the 4 Delta T's
 
AMD 00.DMP.1014 R3 6-2015
AMD 00.DMP.1014 R3 6-2015AMD 00.DMP.1014 R3 6-2015
AMD 00.DMP.1014 R3 6-2015
 
The Science Behind Airflow Management Best Practices
The Science Behind Airflow Management Best PracticesThe Science Behind Airflow Management Best Practices
The Science Behind Airflow Management Best Practices
 
Hvac psychrometry and concepts
Hvac psychrometry and conceptsHvac psychrometry and concepts
Hvac psychrometry and concepts
 
Data center cooling ahmed abdel-salam (2019)
Data center cooling   ahmed abdel-salam (2019)Data center cooling   ahmed abdel-salam (2019)
Data center cooling ahmed abdel-salam (2019)
 
Air conditioning
Air conditioningAir conditioning
Air conditioning
 
Basic Mechanical Engineering - Air conditioning
Basic Mechanical Engineering - Air conditioningBasic Mechanical Engineering - Air conditioning
Basic Mechanical Engineering - Air conditioning
 
Chapter 6 Psychrometry & Air-Conditioning
Chapter 6  Psychrometry & Air-ConditioningChapter 6  Psychrometry & Air-Conditioning
Chapter 6 Psychrometry & Air-Conditioning
 
HERS Test Raters
HERS Test Raters HERS Test Raters
HERS Test Raters
 
Understanding cqi9 iss3 (intermediate)
Understanding cqi9 iss3 (intermediate)Understanding cqi9 iss3 (intermediate)
Understanding cqi9 iss3 (intermediate)
 
A digital hygrometer for trace moisture
A digital hygrometer for trace moistureA digital hygrometer for trace moisture
A digital hygrometer for trace moisture
 
Thermal Mass Flow Meters Reduce Energy Costs and Enhance Emissions Monitoring
Thermal Mass Flow Meters Reduce Energy Costs and Enhance Emissions MonitoringThermal Mass Flow Meters Reduce Energy Costs and Enhance Emissions Monitoring
Thermal Mass Flow Meters Reduce Energy Costs and Enhance Emissions Monitoring
 
Understanding AMS2750E (intermediate) v2
Understanding AMS2750E (intermediate) v2Understanding AMS2750E (intermediate) v2
Understanding AMS2750E (intermediate) v2
 

En vedette

Optimize power and cooling final 1
Optimize power and cooling final 1Optimize power and cooling final 1
Optimize power and cooling final 1
Viridity Software
 
Artrosis tratamiento
Artrosis tratamientoArtrosis tratamiento
Artrosis tratamiento
tamief2
 
TCP over 6LoWPAN for Industrial Applications
TCP over 6LoWPAN for Industrial ApplicationsTCP over 6LoWPAN for Industrial Applications
TCP over 6LoWPAN for Industrial Applications
Ahmed Ayadi
 
Zigbee wireless control made easy
Zigbee wireless control made easyZigbee wireless control made easy
Zigbee wireless control made easy
rajrayala
 

En vedette (20)

ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICESASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
 
Optimize power and cooling final 1
Optimize power and cooling final 1Optimize power and cooling final 1
Optimize power and cooling final 1
 
Artrosis tratamiento
Artrosis tratamientoArtrosis tratamiento
Artrosis tratamiento
 
Data Center Ethernet
Data Center EthernetData Center Ethernet
Data Center Ethernet
 
Us patent cases weekly update august 4th august 11th 2015
Us patent cases weekly update  august 4th august 11th 2015Us patent cases weekly update  august 4th august 11th 2015
Us patent cases weekly update august 4th august 11th 2015
 
RFID Asset Tracking to Rack Unit for DCIM
RFID Asset Tracking to Rack Unit for DCIMRFID Asset Tracking to Rack Unit for DCIM
RFID Asset Tracking to Rack Unit for DCIM
 
Slides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingSlides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for Cooling
 
Data Center Monitoring
Data Center MonitoringData Center Monitoring
Data Center Monitoring
 
Wireless Sensors and Control Networks
Wireless Sensors and Control NetworksWireless Sensors and Control Networks
Wireless Sensors and Control Networks
 
TCP over 6LoWPAN for Industrial Applications
TCP over 6LoWPAN for Industrial ApplicationsTCP over 6LoWPAN for Industrial Applications
TCP over 6LoWPAN for Industrial Applications
 
Powering Virtualization, Applications, and Data Center Transformation with Co...
Powering Virtualization, Applications, and Data Center Transformation with Co...Powering Virtualization, Applications, and Data Center Transformation with Co...
Powering Virtualization, Applications, and Data Center Transformation with Co...
 
Data center & wireless lan
Data center & wireless lanData center & wireless lan
Data center & wireless lan
 
Zigbee wireless control made easy
Zigbee wireless control made easyZigbee wireless control made easy
Zigbee wireless control made easy
 
Avoiding Data Center Disasters
Avoiding Data Center DisastersAvoiding Data Center Disasters
Avoiding Data Center Disasters
 
Managing the Impact and Cost of the IOT Data Explosion - Data Centre Converge...
Managing the Impact and Cost of the IOT Data Explosion - Data Centre Converge...Managing the Impact and Cost of the IOT Data Explosion - Data Centre Converge...
Managing the Impact and Cost of the IOT Data Explosion - Data Centre Converge...
 
Wireless Sensor Network with Mobile Integration
Wireless Sensor Network with Mobile IntegrationWireless Sensor Network with Mobile Integration
Wireless Sensor Network with Mobile Integration
 
Wireless Mesh Networks
Wireless Mesh NetworksWireless Mesh Networks
Wireless Mesh Networks
 
Data Center Heat Monitoring Using Wireless Sensor Networks
Data Center Heat Monitoring Using Wireless Sensor NetworksData Center Heat Monitoring Using Wireless Sensor Networks
Data Center Heat Monitoring Using Wireless Sensor Networks
 
Tracxn Research: Energy Efficiency Landscape, August 2016
Tracxn Research: Energy Efficiency Landscape, August 2016Tracxn Research: Energy Efficiency Landscape, August 2016
Tracxn Research: Energy Efficiency Landscape, August 2016
 
From Device to Data Center to Insights
From Device to Data Center to InsightsFrom Device to Data Center to Insights
From Device to Data Center to Insights
 

Similaire à NER Aurora Thermal_Monitoring_Whitepaper

Selecting air conditioners for enclosure
Selecting air conditioners for enclosureSelecting air conditioners for enclosure
Selecting air conditioners for enclosure
erdinc klima
 
Afcom air control solution presentation
Afcom air control solution presentation Afcom air control solution presentation
Afcom air control solution presentation
stacygriggs
 
Mitch cfd video demo
Mitch cfd video demoMitch cfd video demo
Mitch cfd video demo
plzandthx
 
Optimizing The Data Centre Environment
Optimizing The Data Centre EnvironmentOptimizing The Data Centre Environment
Optimizing The Data Centre Environment
mixalisg
 
Server room cooling report
Server room cooling reportServer room cooling report
Server room cooling report
ommuruga ps
 

Similaire à NER Aurora Thermal_Monitoring_Whitepaper (20)

CPD Presentation Evaporative cooling in data centres
CPD Presentation   Evaporative cooling in data centresCPD Presentation   Evaporative cooling in data centres
CPD Presentation Evaporative cooling in data centres
 
75F Outside Air Optimization and Economizer Control
75F Outside Air Optimization and Economizer Control75F Outside Air Optimization and Economizer Control
75F Outside Air Optimization and Economizer Control
 
Datacenters
DatacentersDatacenters
Datacenters
 
Selecting air conditioners for enclosure
Selecting air conditioners for enclosureSelecting air conditioners for enclosure
Selecting air conditioners for enclosure
 
In the Data Center: Five Keys to Achieving Ultra-Low PUEs
In the Data Center: Five Keys to Achieving Ultra-Low PUEsIn the Data Center: Five Keys to Achieving Ultra-Low PUEs
In the Data Center: Five Keys to Achieving Ultra-Low PUEs
 
Afcom air control solution presentation
Afcom air control solution presentation Afcom air control solution presentation
Afcom air control solution presentation
 
temp mapping .pdf
temp mapping .pdftemp mapping .pdf
temp mapping .pdf
 
Temperature Mapping (WHO).pdf
Temperature Mapping (WHO).pdfTemperature Mapping (WHO).pdf
Temperature Mapping (WHO).pdf
 
Article lior yosef
Article  lior yosefArticle  lior yosef
Article lior yosef
 
Data center-server-cooling-power-management-paper
Data center-server-cooling-power-management-paperData center-server-cooling-power-management-paper
Data center-server-cooling-power-management-paper
 
Mitch cfd video demo
Mitch cfd video demoMitch cfd video demo
Mitch cfd video demo
 
How To Keep Your Server Rack Cool And Its Benefits?
How To Keep Your Server Rack Cool And Its Benefits?How To Keep Your Server Rack Cool And Its Benefits?
How To Keep Your Server Rack Cool And Its Benefits?
 
Optimizing The Data Centre Environment
Optimizing The Data Centre EnvironmentOptimizing The Data Centre Environment
Optimizing The Data Centre Environment
 
Thermal cycling screen development
Thermal cycling screen developmentThermal cycling screen development
Thermal cycling screen development
 
Asphalt Testing For Precision, Accuracy And Maximum Throughput
Asphalt Testing For Precision, Accuracy And Maximum ThroughputAsphalt Testing For Precision, Accuracy And Maximum Throughput
Asphalt Testing For Precision, Accuracy And Maximum Throughput
 
Server room cooling report
Server room cooling reportServer room cooling report
Server room cooling report
 
Aircondition energy saver
Aircondition energy saverAircondition energy saver
Aircondition energy saver
 
25985 (1).pdf
25985 (1).pdf25985 (1).pdf
25985 (1).pdf
 
Labs21 CDCV 9.8.2010
Labs21 CDCV 9.8.2010Labs21 CDCV 9.8.2010
Labs21 CDCV 9.8.2010
 
Data center cooling infrastructure slide
Data center cooling infrastructure slideData center cooling infrastructure slide
Data center cooling infrastructure slide
 

Plus de Greg Stover

Plus de Greg Stover (7)

Five key emerging trends impacting Data Centers in 2016
Five key emerging trends impacting Data Centers in 2016 Five key emerging trends impacting Data Centers in 2016
Five key emerging trends impacting Data Centers in 2016
 
Emerson converged infrastructure (thermal-power-mgt.-security (gs)
Emerson   converged infrastructure (thermal-power-mgt.-security (gs)Emerson   converged infrastructure (thermal-power-mgt.-security (gs)
Emerson converged infrastructure (thermal-power-mgt.-security (gs)
 
Trellis DCIM Platform
Trellis DCIM PlatformTrellis DCIM Platform
Trellis DCIM Platform
 
NER Containment Solutions - Hot & Cold Aisle, Passive and Managed/Intelligent
NER Containment Solutions - Hot & Cold Aisle, Passive and Managed/IntelligentNER Containment Solutions - Hot & Cold Aisle, Passive and Managed/Intelligent
NER Containment Solutions - Hot & Cold Aisle, Passive and Managed/Intelligent
 
NER & Emerson Infrastructure Optimization Capabilties Storyboard
NER & Emerson   Infrastructure Optimization Capabilties StoryboardNER & Emerson   Infrastructure Optimization Capabilties Storyboard
NER & Emerson Infrastructure Optimization Capabilties Storyboard
 
Data Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationData Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure Optimization
 
Tcc cooling
Tcc coolingTcc cooling
Tcc cooling
 

Dernier

Dernier (20)

Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
 
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...
 
Handwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsHandwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed texts
 
Advantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your BusinessAdvantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your Business
 
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
 
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, AdobeApidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024
 
Understanding Discord NSFW Servers A Guide for Responsible Users.pdf
Understanding Discord NSFW Servers A Guide for Responsible Users.pdfUnderstanding Discord NSFW Servers A Guide for Responsible Users.pdf
Understanding Discord NSFW Servers A Guide for Responsible Users.pdf
 
presentation ICT roal in 21st century education
presentation ICT roal in 21st century educationpresentation ICT roal in 21st century education
presentation ICT roal in 21st century education
 
Real Time Object Detection Using Open CV
Real Time Object Detection Using Open CVReal Time Object Detection Using Open CV
Real Time Object Detection Using Open CV
 
Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organization
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...
 
What Are The Drone Anti-jamming Systems Technology?
What Are The Drone Anti-jamming Systems Technology?What Are The Drone Anti-jamming Systems Technology?
What Are The Drone Anti-jamming Systems Technology?
 
Data Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonData Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt Robison
 
GenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdfGenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdf
 
Strategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a FresherStrategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a Fresher
 
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot TakeoffStrategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
 
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemkeProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdf
 

NER Aurora Thermal_Monitoring_Whitepaper

  • 1. NER Data Corporation White Paper Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems
  • 2. Introduction Data centers are dynamic environments that change based on evolving business requirements. Monitoring your physical infrastructure is key ensuring business continuity, preventing disruption of service, meeting compliance requirements, reducing costs and increasing ROI. Decisions made today affect your ability to monitor and manage your future state. Monitoring and management requirements change over time, so best practices use the deployment of tools that meet the needs of today while allowing for changes in the future. Best Practice: Monitor Temperature at Multiple Rack Level Points The 2013 Uptime Institute Data Center Industry Survey reported “..only 15% of the data center managers responding to the survey said they were measuring and controlling air temperatures from the server inlet, which is the most accurate location. Nearly a third of the respondents are managing inlet air temperature at the room level, which is the least accurate method. Obviously there is room for some further cooling efficiency improvements.” Thermal monitoring should be conducted at the rack and key points within the data center to properly protect equipment and to gather data for cost saving optimization. A goal in data center cooling is to maintain server rack exhaust temp under 100*F and a Rack Delta temperature of around 20*F while targeting the highest efficiency. In order to do this you must monitor rack intake and exhaust tempertures at various heights. Rack inlet and exhaust temperatures can vary over 10*F within just 8". The American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) recommends at least 6 temperature sensors per rack (top, middle, bottom / front and back). Monitoring return air temps at the CRAC unit provides valuable information but only measures intermixed air. This method leaves gaps for hot (under provisioned) areas and cold (over provisioned) areas at the rack level. Measurements taken at multiple points at the rack as described above and at the CRAC feed and return provide you with actionable information: 1. Divide each individual CRAC unit return air temperatures to the average rack exhaust temperature to determine the return path efficiency. Example: CRAC unit 1 return air temperature average is 76°F. The average server rack exhaust temperature is 88°F. There is a 12°FΔT so the return air path back to CRAC 1 is 86% efficient. 2. Next determine the cooling delivery efficiency. Divide the CRAC unit feed temperature by the average rack inlet temperature for each CRAC unit. Example: CRAC unit 1 feed air temperature average is 52°F. The Average server inlet temperature is 58°F. There is a 6°FΔT so the cool air distribution is 89% efficient. 3. Finally determine the overall airflow distribution efficiency by averaging the efficiency rating for distribution and return together. Example: CRAC unit 1 return airflow efficiency is 86% and the cool air distribution is 89% efficient. The overall airflow distribution efficiency for CRAC 1 is 87.5%. Page 2
  • 3. By measuring at the rack and key points within the data center you will know what is changing in your data center and you can clearly see: · where the highest capacity exist in the rack · where available cooling capacity exist · cooling effectiveness at the rack and data center levels · whether you are over/under provisioning cooling per rack · problem alerting · seasonal and weather impacts on server cooling · cooling policy and SLA enforcement · local problem solving such as blanking panel placement · proof of concept pre and post deployment Temperature is Just Part of the Cooling Equation There are four values which affect the cooling properties of air: Temperature, Humidity, Pressure, and Flow A change in any one of these values will effectively alter the air’s ability to cool an electrical heat load as illustrated in the examples below: Baseline server rack with a 12kW load is introduced cooling air with the following values: Temperature: 70°F, Relative Humidity: 50%, Pressure, Sea Level @ 14.7 psi, Flow: 1900cfm = exhaust temperature of 90°F and 20 Δ°F temperature (Note: changing the temperature also changes the relative humidity) . · Example 1: Lower Temperature to 55°F, Relative Humidity: 50%, Pressure, Sea Level @ 14.7 psi, Flow: 1900cfm = exhaust temperature of 74.3°F and 19.3Δ°F temperature rise. · Example 2: Temperature:70°F, Relative Humidity: 50%, Pressure, Sea Level @ 14.7 psi, Reduce Flow to 1500cfm = exhaust temperature of 95.3°F and 25.3Δ°F temperature rise. · Example 3: Increase Temperature to 77°F, Relative Humidity: 50%, Pressure, Sea Level @ 14.7 psi, Reduce Flow to 1750cfm = exhaust temperature of 99°F and 22Δ °F temperature rise. · Example 4: The same server rack and airflow values as the Baseline, only this time we reduce the air pressure by placing the rack in Denver Co. with an elevation of 5,280 feet. The result is an exhaust temperature of 94.3°F and 24.3 Δ °F temperature rise. These cooling examples show that monitoring temperature at the rack intake is just a piece of the puzzle and a change in any variable can affect cooling. Through continual monitoring and measuring it may be possible to adjust temperature (and corresponding humidity) and flow while still staying within a desired server exhaust temperature. Benefits come in cost savings through reduced compressor and fan energy usage. To optimize monitoring and management, temperature sensors should be positioned along the front and rear of each priority rack. Also barometric and humidity sensors should be placed within the aisle where these racks reside. Page 3
  • 4. Aurora High Resolution Temperature Strip Enables Best-Practice Rack Level Thermal Monitoring The Aurora consists of innovative patent-pending technology that couples a series of 8 thermally isolated temperature sensors with an array of high intensity LEDs. Aurora visually displays temperature reading similar to a CFD through a range of cool (blue) to hot (red) and a blend of 129 colors in between. With 8 sensors per strip, temperature is monitored over the entire height of the cabinet; perfect for meeting ASHRAE recommendations, aisle containment and areas susceptible to temperature stratification. Sensors start 4.5” from bottom of unit and end at 60.5” to provide measuring of temperature fluctuations within 8” increments. Used as self-policing, real-time troubleshooting tool, it clearly identifies potential cooling or heat-related issues and provides instantaneous feedback that is invaluable when monitoring changes or validating best-practice improvements. Aurora is extremely accurate because it measures air temperature, not surface temperature. Three User-Selectable Sensitivity Settings allow for fine tuning of the monitored temperature range over the full 129-color spectrum. · Low setting concentrates the color spectrum towards the colder end of the temperature scale. The 129 colors will vary between 25 degrees F (50°F/10°C to 75°F/23.8°C). This setting offers more color resolution for colder data centers such as cold aisle containment. · Medium setting closely reflects the ASHRAE standards for acceptable equipment inlet temperatures. The 129 colors will vary between 25 degrees F (65°F/18.3°C to 90°F/32.2°C). · High setting concentrates the color spectrum towards the hotter end of the temperature scale. The 129 colors will vary between 25 degrees F (70°F/21.1°C to 95°F/35°C). This setting offers more color resolution for data centers with hotter temperature settings. This setting is also suitable for positioning the Aurora Temperature Strip in the hot aisle. . Benefits of Visual Alerting Studies on human behavior show that warnings are most effective when they are presented proximate (in time and space) to the hazard. By visually indicating the issue in both a Management System interface and at the exact physical location, time to remediation can be decreased. With automated alerts and easy to comprehend alerts at the point of hazard, every team member can insure that no issue goes unnoticed. Page 4
  • 5. Managing Alerts Centralized management systems provide a way to capture, manage, and effectively use sensor data. Down-time causing events can be avoided or minimized through monitoring systems that allow IT staff to quickly respond to environmental changes and alerts. In advanced systems, alerts can trigger automated response such as adjusting VFD controllers for target areas based on alert thresholds. Through the use of real-time data, Monitoring Solutions take the guess-work out of decision making and planning processes. Sensors provide important inputs for establishing baseline conditions, trending, capacity planning, validating best-practice improvements, monitoring changes, and confirming compliance with company mandates. According to the Uptime Institute 2013 Data Center Industry Survey: “Data center infrastructure management (DCIM) software adoption seems to have skyrocketed. An astounding 38% reported that they have deployed DCIM software.” “That’s not to say that the companies have fully installed the tools, or are reaping the rewards of the software’s capabilities. For many companies, it’s just the beginning of a long cycle of implementation and maintenance of the systems.” Best Practice: Use Adaptable Sensors and Systems The Aurora Strip is designed to work in any data center environment – from basic server rooms without monitoring applications to Tier 4 data centers that deploy sophisticated DCiM systems. For data centers with existing monitoring and DCiM solutions, Aurora can be integrated to provide data to these systems. Data from the strips can interact with systems to provide automated remediation such as adjusting VFD controllers. In addition, Aurora’s resource-saving communications require just one port to capture up to 800 different sensor readings. For data centers without existing monitoring systems, the Aurora strip can be used as a stand-alone visual monitoring tool. However, a centralized monitoring system allows administrators to respond quickly and truly reap the benefits of the sensor data. Deploying such a system can be costly and overwhelming, but the Aurora Wireless Management Application (cloud-based and enterprise) is an easy avenue for data centers to move to the next level of monitoring and management. The system provides for monitoring of additional sensor types (humidity, fluid detection, airflow, etc.), automated alerts, powerful visual mapping tools, data trending/reporting, and API commands for integrating with 3rd party applications. Page 5
  • 6. Aurora Wireless Management Application Features · Complete configuration and customization at a sensor, local network, or client wide level · Notifications via SMS text and email · Unlimited sensor data storage and trending · Unlimited user accounts for system configuration, monitoring and notifications · Sensor heartbeats (check-ins) down to 10 minutes: o Timed sensors (i.e. temperature) can be user-set to check against alert thresholds up to 256 times between heartbeats o Triggered sensors (i.e. motion, door/window, etc.) record data as it happens, regardless of heartbeat · Advanced sensor configuration options: o Automatic sensor recovery attempts o Sensor inactivity alerts o Sub-heartbeat assessments with alert thresholds o Sensor aware state reporting · Advanced Thermographic Sensor Mapping tool · Sensor Grouping feature allows onscreen sensors to easily be arranged to exactly match physical strip deployments · API commands for integrating into 3rd party applications Page 6
  • 7. Summary Environmental monitoring and management systems are crucial to running efficient data centers. The data provided is used to avoid downtime, increase efficiency, aid in capacity planning, and lower operating costs. At the root of these systems are sensors that collect the data for analysis. Best practices involve utilizing sensors that are scalable, flexible, and can be deployed as stand-alone systems or can be integrated into existing monitoring systems. The Aurora Solution allows you easily achieve a best practice deployment. More information including an overview video can be found at www.nerdata.com/Aurora About NER Data Corporation NER Data Corporation is an innovative leader in the demanding, growing, and continually changing Data Center Infrastructure Management and Managed Print businesses. NER offers unique value-add solutions that truly solve business issues and allow reseller partners to develop and maintain stronger relationships with their end-users. Our approach has earned NER a loyal following with North America’s leading Resellers, Integrators, VARS, and their Fortune 2000 end-user customers. For more information, visit www.nerdata.com. www.nerdata.com 888-NER-DATA 637-3282 Copyright © 2014 NER Data Corporation Page 7