Distributed Generation & Power Quality
HARI MADHAVA REDDY.Y, (Ph.D)., M.Tech., MISTE.,IAENG.,SSI
Assistant Professor of Electrical Engineering
UNIVERSAL COLLEGE OF ENGINEERING & TECHNOLOGY
2/11/2021 1
CONTENTS
5.0. Introduction
5.1. Resurgence Of Distributed Generation
5.2. DG Technologies
5.3. Interface to utility system
5.4. PQ Issues & Operating Conflicts.
5.5. DG on low voltage Distribution network.
2/11/2021 2
5.0. Introduction
 DG uses smaller-sized generators(generator sizes
less than 10 MW) than does the typical central
station plant. They are distributed throughout the
power system closer to the loads. Generators
larger than this are typically interconnected at
transmission voltages where the system is designed
to accommodate many generators.
2/11/2021 3
5.0. Introduction
The normal distribution system delivers electric
energy through wires from a single source of
power to a multitude of loads. Thus, several power
quality issues arise when there are multiple
sources.
Will DG improve the power quality or will it
degrade the service end users have come to
expect?
2/11/2021 4
2/11/2021 5
 Most countries generate electricity in large
centralized facilities, such as fossil fuel (coal,
gas powered), nuclear, large solar power plants
or hydropower plants. These plants have
excellent economies of scale, but usually
transmit electricity long distances and can
negatively affect the environment.
 Distributed generation allows collection of
energy from many sources and may give lower
environmental impacts and improved security
of supply.
2/11/2021 6
5.1.Resurgence of DG
 The electric power industry in developed nations has been
to generate power in large, centralized generating stations
and to distribute the power to end users through
transformers, transmission lines, and distribution lines.
 The original electrical power systems, consisting of
relatively small generators configured in isolated islands,
used DG because of economies of scale.
 There was the desire to sequester (sI"kwes.tr) electricity
generation facilities away from population centers for
environmental reasons and to locate them closer to the
source of fuel and water.
2/11/2021 7
 The passage of the Public Utilities Regulatory Act of 1978
(PURPA) in the United States in 1978 was intended to foster
energy independence.
 Tax credits were given, and power was purchased at avoided-
cost rates to spur development of renewable and energy-
efficient, low-emissions technologies.
 This led to a spurt in the development of wind, solar, and
geothermal generation as well as gas-fired cogeneration
(combined heat and power) facilities.
 In the mid-1990s, interest in DG once again peaked with the
development of improved DG technologies and the deregulation
of the power industry allowing more power producers to
participate in the market.
 Also, the appearance of critical high-technology loads requiring
much greater reliability than can be achieved by wire delivery
alone has created a demand for local generation and storage to fill
the gap.
2/11/2021 8
 New technologies would allow the generation to be as widely
dispersed as the load and interconnected power grids could be small
(i.e., microgrids). The generation would be powered by renewable
resources or clean-burning, high-efficiency technologies. Energy
distribution will be shifted from wires to pipes containing some type
of fuel, which many think will ultimately be hydrogen.
 Recent efforts to deregulate electric power have been aimed not only
at achieving better prices for power but at enabling new
technologies.
2/11/2021 9
 Perspectives on DG Benefits
– End-User Perspective
• Back Generation to Provide Improved Reliability
• Reduce Energy Bill
• Participation in the Competitive Power Market
– Distribution Utility Perspective
• Transmission & Distribution Relief
• Hedge Against of Uncertain Load Growth
• DG serves as a Hedge Against Price Spikes.
– Commercial Power Producer Perspective
• Mainly interested in Selling Power or Ancillary (aen"sIl.@r.i) Service in
the Deregulated Market
• Integrated Resource Planning.
2/11/2021 10
 Disadvantages of DG
– Power Quality
– Cost of Operation and Maintenance
– Long Term Reliability of the Units
– Interconnection
 PERSPECTIVES ON INTERCONNECTION
Figure.1 End-user and
generator owner
perspectives on inter-
connection
Figure .2 Distribution planner
perspective on interconnection
2/11/2021 11
 DG is small compared to the grid, implied message
related to power quality.
 DG proponent literature often portrays DG as
improving the reliability of the system (including the
grid) and providing better-quality power.
 The perspective on interconnected DG of typical
utility distribution engineers, most of whom are very
conservative in their approach to planning and
operations.
 The size of customer owned DG is magnified to
appear much larger than its actual size, and it produces
dirty power. It is also a little off center in its design,
suggesting that it is not built and maintained as well as
utility equipment.
2/11/2021 12
5.2. DG Technologies
 Reciprocating Engine Gen-set
Combustion (gas) turbines
 Superconducting Magnetic Energy
Storage
Carbon Nanotube
 Fuel cells
 Wind turbines
Photovoltaic systems
2/11/2021 13
 A common application is to provide support for the
transmission and distribution system in emergencies.
The units are placed in substations and interconnected
to the grid through transformers that typically step up
the voltage from the 480 V produced by the
generators.
 Diesel gen-sets are quite popular with end users for
backup power
 Reciprocating Engine Gen-set
– The Least Expensive DG Technology
– High Nox and Sox Emission. This Severely Limits
the Number of Hours the Units, Particularly
Diesels, May Operate per Year.
– Natural Gas-Fire Engine Produce Fewer Emission.
However, the Natural Gas Price is Unpredictable.
Reciprocating Engine Gen-set
2/11/2021 14
 It is also common to find reciprocating engines with
induction generators. This is particularly true for
cogeneration applications of less than 300 kW because
it is often simpler to meet interconnection requirements
with induction machines that are not likely to support
islands.
 Reciprocating engine gen-sets have consistent
performance characteristics over a wide range of
environmental conditions with efficiencies in the range
of 35 to 40 percent. They are less sensitive to ambient
conditions than combustion turbines whose power
efficiency declines considerably as the outside air
temperature rises.
2/11/2021 15
 APPLICATIONS
 The main applications will be for peaking generation and
emergency backup.
 They are popular in combined heat and power
cogeneration applications in schools, government, and
commercial buildings where they operate at least for the
business day.
2/11/2021 16
Combustion (gas) Turbine
 Range from 1 to 10 MW
 High Speed: 8 – 12 kRPM
 Micro turbine
• 30 – 75 kW (small), 300-400KW
• 10 – 100 kRPM
• Efficiency: 25 – 30 %
 The waste heat from a combustion turbine is at a
much higher temperature than that from a
reciprocating engine. Thus, turbines are generally
the choice for combined heat and power applications
that require process steam.
 A micro turbine being employed in a combined heat
and power application with the heat exchanger shows
in Fig.
2/11/2021 17
 Net energy efficiencies exceeding 60 percent
 One of the major advantages of this technology is that
installations are clean and compact. This allows
deployment near living and working areas, although
there may be some issues with the high-pitched
turbine noise in some environments.
 This technology is best suited for combined heat and
power applications in small to medium sized
commercial and industrial facilities.
 Microturbines have compact packaging and low
emissions, they make convenient and environmentally
friendly standby and peaking generators. They are
also used in some base load applications, have the
ability to accept a wide variety and quality of fuels
and are a convenient means to extract energy from
bio- mass gas, flare gas, or natural gas that is not
economical to transport to pipelines.
2/11/2021 18
 A SMES device is a dc current device that stores energy in the
magnetic field. The dc current flowing through a
superconducting wire in a large magnet creates the
magnetic field. Generally it consists of the superconducting
coil, the cryogenic system, and the Power Conversion/Conditioning
System (PCS) with control and protection functions
Superconducting Magnetic
Energy Storage
2/11/2021 19
The total efficiency of a SMES system can be very high
(about 90% or greater )since it does not require energy
conversion from electrical to mechanical or chemical
energy. Depending on the control loop of its power
conversion unit and switching characteristics, the SMES
system can respond very rapidly (MWs/milliseconds).
The ability of injecting absorbing real or reactive power
can increase the effectiveness of the control, and enhance
system reliability and availability.
2/11/2021 20
2/11/2021 21
Carbon Nanotube
2/11/2021 22
 Carbon Nanotubes, long, thin cylinders of carbon, were
discovered in 1991 by Sumio Iijima.
 These are large macromolecules that are unique for their size,
shape, and remarkable physical properties.
 They can be thought of as a sheet of graphite (a hexagonal
lattice of carbon) rolled into a cylinder.
 These intriguing structures have sparked much excitement in
recent years and a large amount of research has been dedicated
to their understanding.
 Currently, the physical properties are still being discovered and
disputed.
 Nanotubes have a very broad range of electronic, thermal, and
structural properties that change depending on the different
kinds of nanotube (defined by its diameter, length, and chirality,
or twist). To make things more interesting, besides having a
single cylindrical wall (SWNTs), Nanotubes can have multiple
walls (MWNTs)--cylinders inside the other cylinders.
2/11/2021 23
Key properties of Carbon Nanotubes
 Extraordinary electrical conductivity, heat conductivity, and
mechanical properties.
 They are probably the best electron field-emitter known,
largely due to their high length-to- diameter ratios.
 As pure carbon polymers, they can be manipulated using the
well-known and the tremendously rich chemistry of that
element.
Key application areas
• Field Emitters/Emission
• Conductive or reinforced plastics
• Molecular electronics: CNT based non volatile RAM
• CNT based transistors
• Energy Storage
• CNT based fibers and fabrics
• CNT based ceramics
• Biomedical applications etc ...
2/11/2021 24
Fuel Cell
 A fuel cell is basically a battery powered by an electrochemical
process based on the conversion of hydrogen. It produces dc voltage,
and an inverter is required for interfacing to the ac power system.
 A fuel cell is an electrochemical device that produces electricity
without combustion by combining hydrogen and oxygen to produce
water and heat.
 The chief drawback to fuel cells at present is cost. Fuel cell
technologies are on the order of 10 times more expensive than
reciprocating gen sets.
2/11/2021 25
Working Principle
 A fuel cell is a device that uses hydrogen (or hydrogen-rich fuel) and
oxygen to create electricity by an electrochemical process.
 A single fuel cell consists of an electrolyte sandwiched between two
thin electrodes (a porous anode and cathode) Hydrogen, or a
hydrogen-rich fuel, is fed to the anode where a catalyst separates
hydrogen's negatively charged electrons from positively charged ions
(protons) .
 At the cathode, oxygen combines with electrons and, in some cases,
with species such as protons or water, resulting in water or hydroxide
ions, respectively.
2/11/2021 26
2/11/2021 27
2/11/2021 28
2/11/2021 29
 Fuel Cell
– Phosphoric Acid (PAFC)
• PAFCs generate electricity at more than 40% efficiency
• Operating temperatures are in the range of 300 to 400 degrees
F (150 - 200 degrees C)
• Existing PAFCs have outputs up to 200 kW, and 1 MW units
have been tested
• One of the main advantages to this type of fuel cell is that it
can use impure hydrogen as fuel. PAFCs can tolerate a CO
concentration of about 1.5 percent, which broadens the choice
of fuels they can use. If gasoline is used, the sulfur must be
removed.
• PAFCs are the most mature fuel cell technology.
2/11/2021 30
DG Technologies
 Fuel Cell
– Phosphoric Acid (PAFC)
• Disadvantages of PAFCs include: it uses expensive platinum
as a catalyst, it generates low current and power comparably to
other types of fuel cells, and it generally has a large size and
weight.
2/11/2021 31
DG Technologies
 Fuel Cell
– Proton Exchange Membrane (PEM)
• These cells operate at relatively low temperatures (about 175
degrees F or 80 degrees C), have high power density, can vary
their output quickly to meet shifts in power demand, and are
suited for applications, -- such as in automobiles -- where
quick startup is required.
• According to DOE, "they are the primary candidates for light-
duty vehicles, for buildings, and potentially for much smaller
applications such as replacements for rechargeable batteries.
• This type of fuel cell is sensitive to fuel impurities.
• Cell outputs generally range from 50 to 250 kW.
2/11/2021 32
DG Technologies
 Fuel Cell
– Molten Carbonate (MCFC)
• These fuel cells use a liquid solution of lithium, sodium and/or
potassium carbonates, soaked in a matrix for an electrolyte.
• They promise high fuel-to-electricity efficiencies, about 60%
normally or 85% with cogeneration, and operate at about 1,200
degrees F or 650 degrees C.
• To date, MCFCs have been operated on hydrogen, carbon
monoxide, natural gas, propane, landfill gas, marine diesel, and
simulated coal gasification products.
• 10 kW to 2 MW MCFCs have been tested on a variety of fuels
and are primarily targeted to electric utility applications.
• A disadvantage to this, however, is that high temperatures
enhance corrosion and the breakdown of cell components.
2/11/2021 33
DG Technologies
 Fuel Cell
– Solid Oxide (SOFC)
• This type could be used in big, high-power applications
including industrial and large-scale central electricity
generating stations.
• Some developers also see SOFC use in motor vehicles and are
developing fuel cell auxiliary power units (APUs) with SOFCs.
• A solid oxide system usually uses a hard ceramic material of
solid zirconium oxide and a small amount of ytrria, instead of a
liquid electrolyte, allowing operating temperatures to reach
1,800 degrees F or 1000 degrees C.
• Power generating efficiencies could reach 60% and 85% with
cogeneration and cell output is up to 100 kW.
2/11/2021 34
DG Technologies
 Fuel Cell
– Alkaline
• Long used by NASA on space missions, these cells can
achieve power generating efficiencies of up to 70 percent.
They were used on the Apollo spacecraft to provide both
electricity and drinking water.
• Their operating temperature is 150 to 200 degrees C (about
300 to 400 degrees F).
• They typically have a cell output from 300 watts to 5 kW.
2/11/2021 35
DG Technologies
 Fuel Cell
– Direct Methanol Fuel Cells (DMFC)
• These cells are similar to the PEM cells in that they both use a
polymer membrane as the electrolyte. However, in the DMFC,
the anode catalyst itself draws the hydrogen from the liquid
methanol, eliminating the need for a fuel reformer.
• Efficiencies of about 40% are expected with this type of fuel
cell, which would typically operate at a temperature between
120-190 degrees F or 50 -100 degrees C.
• This is a relatively low range, making this fuel cell attractive
for tiny to mid-sized applications, to power cellular phones and
laptops.
2/11/2021 36
DG Technologies
 Fuel Cell
– Regenerative Fuel Cells
• Still a very young member of the fuel cell family, regenerative
fuel cells would be attractive as a closed-loop form of power
generation.
• Water is separated into hydrogen and oxygen by a solar-
powered electrolyser. The hydrogen and oxygen are fed into
the fuel cell which generates electricity, heat and water. The
water is then recirculated back to the solar-powered
electrolyser and the process begins again.
• These types of fuel cells are currently being researched by
NASA and others worldwide.
2/11/2021 37
DG Technologies
 Fuel Cell
– Zinc-Air Fuel Cells (ZAFC)
• In a typical zinc/air fuel cell, there is a gas diffusion electrode
(GDE), a zinc anode separated by electrolyte, and some form
of mechanical separators.
• The GDE is a permeable membrane that allows atmospheric
oxygen to pass through. After the oxygen has converted into
hydroxyl ions and water, the hydroxyl ions will travel through
an electrolyte, and reaches the zinc anode. Here, it reacts with
the zinc, and forms zinc oxide. This process creates an
electrical potential.
2/11/2021 38
DG Technologies
 Fuel Cell
– Protonic Ceramic Fuel Cell (PCFC)
• This new type of fuel cell is based on a ceramic electrolyte
material that exhibits high protonic conductivity at elevated
temperatures.
• PCFCs share the thermal and kinetic advantages of high
temperature operation at 700 degrees Celsius with molten
carbonate and solid oxide fuel cells, while exhibiting all of the
intrinsic benefits of proton conduction in polymer electrolyte
and phosphoric acid fuel cells (PAFCs).
• The high operating temperature is necessary to achieve very
high electrical fuel efficiency with hydrocarbon fuels. PCFCs
can operate at high temperatures and electrochemically oxidize
fossil fuels directly to the anode. This eliminates the
intermediate step of producing hydrogen through the costly
reforming process. .
2/11/2021 39
Wind Generation
 Wind generation capacity has been increasing
rapidly and has become cost competitive with
other means of generation in some regions. A
common implementation is to group a number
of wind turbines ranging in size from 700 to
1200 kW each into a “wind farm” having a
total maximum capacity range of 200 to 500
MW.
 Large farms are interconnected to the
transmission sys- tem rather than the
distribution system. However, smaller farms
of 6 to 8 MW have been proposed for
applications such as ski resorts, and they
would be connected directly to distribution
feeders.
2/11/2021 40
 The chief power quality issue associated with wind
generation is voltage regulation.
 There are three main classes of generator technologies
used for the electrical system interface for wind
turbines:
1. Conventional squirrel-cage induction machines or
wound-rotor induction machines. These frequently are
supplemented by switched capacitors to compensate for
reactive power needs.
2. Doubly fed wound-rotor induction machines that
employ power converters to control the rotor current
to provide reactive power control.
3. Non–power frequency generation that requires an
inverter interface.
2/11/2021 41
Photovoltaic
 The recent power shortages in some states and the passage of net
metering legislation has spurred the installation of rooftop photo-
voltaic solar systems.
2/11/2021 42
 A typical size for a residential unit would be between
2 and 6 kW. Once installed, the incremental cost of
electricity is very low with the source of energy being
essentially free while it is available.
 However, the first cost is very substantial even with
buy- down incentives from government programs.
Installed costs currently range from $5000 to
$20,000/kW.
 Despite this high cost, photovoltaic solar technology is
favoured by many environmentalists and installed
capacity can be expected to continue growing.
 Photovoltaic solar systems generate dc power while the
sun is shining on them and are interfaced to the utility
system through inverters. Some systems do not have
the capability to operate stand-alone the inverters
operate only in the utility-interactive mode and
require the presence of the grid.
2/11/2021 43
5.3. Interface to the Utility
System
 The impact of DG on the distribution system power quality.
Some notable exceptions include:
1. The power variation from renewable sources such as wind and
solar can cause voltage fluctuations.
2. Some fuel cells and micro turbines do not follow step changes in
load well and must be supplemented with battery or flywheel
storage to achieve the improved reliability expected from standby
power applications.
3. Misfiring of reciprocating engines can lead to a persistent and
irritating type of flicker, particularly if it is magnified by the
response of the power system.
2/11/2021 44
Synchronous Machine
Asynchronous Machine
Electronic Power Inverters
The main types of electrical system interfaces are
2/11/2021 45
Synchronous Machine
 They applied in grid parallel DG applications. They are the
primary type of electric machine used in backup generation
applications.
 With proper field and governor control, the machine can follow
any load within its design capability and inertia allows it to be
tolerant of step-load changes so this is good for backup power.
 This technology can easily sustain inadvertent islands that could
occur when the utility feeder breaker opens. It also can feed
faults and possibly interfere with utility overcurrent protection.
 Inter connected synchronous generators on distribution systems
are usually operated with a constant power factor or constant var
exciter control.
2/11/2021 46
1. Small DG does not have sufficient capacity to
regulate the voltage while interconnected.
2. This avoids having the voltage controls of several small
machines competing with each other and the utility
voltage regulation scheme.
3. This is done is to reduce the chances that an
inadvertent island will be sustained.
 Synchronous machine that is large relative to the
capacity of the system at the PCC to regulate the
utility system voltage.
 The subtransient reactance Xd″, which is seen by
harmonics, is often about 15 percent of the machine’s
rating. The transient reactance, Xd′, which governs
much of the fault contribution, might be around 25 per-
cent.
2/11/2021 47
Asynchronous Machine
 Simple to interface
 Induction generators are induction motors that are driven
slightly faster than synchronous speed. They require another
source to provide excitation, which greatly reduces the
chances of inadvertent islanding. No special synchronizing
equipment is necessary. In fact, if the capacity of the
electrical power system permits, induction generators can be
started across the line. For weaker systems, the prime mover
is started and brought to near-synchronous speed before the
machine is interconnected.
2/11/2021 48
 Induction generator requires reactive power
(vars) to excite the machine from the power
system to which it is connected.
 This is an advantage when there are high-
voltage problems, but more commonly there
will be low-voltage problems in induction
generator applications. The usual fix is to add
power factor correction capacitors to supply the
reactive power locally.
 One of the problems is that the capacitor bank
will yield resonances that coincide with
harmonics produced in the same facility.
2/11/2021 49
2/11/2021 50
♠ Another issue is self-excitation. An induction
generator that is suddenly isolated on a
capacitor bank can continue to generate for
some period of time. This is an unregulated
voltage and will likely deviate outside the
normal range quickly and be detected.
♠ This situation can often result in a Ferro
resonant condition with damaging voltages.
♠ The current contribution into a fault from an
induction machine dying out in 1.5 cycles.
Electronic Power Inverters
 All DG technologies that generate either dc or
non–power frequency ac must use an electronic
power inverter to interface with the electrical
power system.
 Line-commutated inverters quickly developed a
reputation for being undesirable on the power
system. These inverters produced harmonic
currents in similar proportion to loads with
traditional thyristor-based converters.
@ Contributing to the distortion on the feeders
@ little more than heat up wires
2/11/2021 51
2/11/2021 52
♠ To achieve better control and to avoid harmonics
problems, the inverter technology has changed to
switched, pulse-width modulated technologies.
♠ Below Figure shows the basic components of a utility
interactive inverter that meets the requirements of
IEEE Standard 929-2000.
2/11/2021 53
ʚ Direct current is supplied on the left side of the diagram either from a
conversion technology that produces direct current directly or from
the rectification of ac generator output. Variations of this type of
inverter are commonly employed on fuel cells, micro turbines,
photovoltaic solar systems, and some wind turbines.
ʚ DC voltage is switched at a very high rate with IGBT switch to create
a sinusoid voltage or current of power frequency, switching frequency
is 50 to 100 times the power frequency.
ʚ The filter on the output attenuates these high-frequency components to
a degree. The total harmonic distortion limit is 5%, based on the
requirements of IEEE Standard 519-1992, will exceed these limits
may skimp on filtering, or there may be a flaw in the switch control
algorithm.
2/11/2021 54
¥ While interconnected to the utility, commonly applied
inverters basically attempt to generate a sine-wave
current that follows the voltage waveform, would
produce power at unity power factor.
¥ It is possible to program other strategies into the
switching control.
¥ If the inverter has stand-alone capability, the control
objective would change to producing a sinusoidal
voltage waveform at power frequency and the current
would follow the load.
Advantages of an inverter for DG applications:
 Switched off very quickly when trouble is detected.
 Inverters typically exhibit very little inertia and changes can
take place in milliseconds. Rotating machines may require
several cycles to respond.
5.4. Power Quality Issues
 Sustained Interruptions
 Voltage Regulation
 Voltage Ride Through
 Harmonics
 Voltage Sags
 Load Following
 Power Variation
 Misfiring of Reciprocating Engines
2/11/2021 55
2/11/2021 56
 Much of the DG that is already in place was installed as backup
generation.
 The most common technology used for backup generation is diesel
gen-sets.
 The bulk of the capacity of this form of DG can be realized simply
by transferring the load to the backup system.
 However, there will be additional power that can be extracted by
paralleling with the power system. Many DG installations will
operate with better power quality while paralleled with the utility
system because of its large capacity.
 Not all DG technologies are capable of significant improvements in
reliability. To achieve improvement, the DG must be capable of
serving the load when the utility system cannot.
Sustained Interruptions:
2/11/2021 57
 For example, a homeowner may install a rooftop
photovoltaic solar system with the expectation of
being able to ride through rotating blackouts.
Unfortunately, the less costly systems do not
have the proper inverter and storage capacity to
operate stand-alone. Therefore, there is no
improvement in reliability
 Utilities may achieve improved reliability by employing DG to
cover contingencies when part of the delivery system is out of
service. In this case, the DG does not serve all the load, but only
enough to cover for the capacity that is out of service. This can
allow deferral of major construction expenses for a few years. The
downside is that reliance on this scheme for too many years can
ultimately lead to worse reliability.
The load growth will overtake the base capacity of the system,
requiring load shedding during peak load conditions or resulting in
the inability to operate the system at acceptable voltage after a fault.
2/11/2021 58
Voltage Regulation
 It may initially seem that DG should be able to improve
the voltage regulation on a feeder. Generator controls
are much faster and smoother than conventional tap-
changing transformers and switched capacitor banks.
 However, there are many problems associated with voltage
regulation. In cases where the DG is located relatively far from the
substation for the size of DG, voltage regulation issues are often the
most limiting for being able to accommodate the DG without
changes to the utility system.
 Some technologies are unsuitable for regulating voltages. This is
the case for simple induction machines and for most utility
interactive inverters that produce no reactive power. Secondly,
most utilities do not want the DG to attempt to regulate the
voltage because that would interfere with utility voltage regulation
equipment and increase the chances of supporting an island.
2/11/2021 59
 Small DG is simply not powerful enough to regulate
the voltage and will be dominated by the daily
voltage changes on the utility system. Small DG is
almost universally required to interconnect with a
fixed power factor or fixed reactive power control.
 Large DG greater than 30 percent of the feeder capacity that is set
to regulate the voltage will often require special communications
and control to work properly with the utility voltage-regulating
equipment.
 DG will take over the voltage-regulating duties and drive the
substation load tap changer (LTC) into a significant bucking
position as the load cycles up and down. This results in a
problem when the DG suddenly disconnects, as it would for a
fault. The voltage is then too low to support the load and takes a
minute or more to recover. One solution is to establish a control
scheme that locks the LTC at a preselected tap when the generator
is operating and interconnected.
2/11/2021 60
Harmonics
 Associate DG with bad experiences with harmonics
from electronic power converters. If thyristor-based,
line-commutated inverters were still the norm, this
would be a large problem.
 Technologies requiring inverters have adopted the switching
inverters, this has eliminated the bulk of the harmonics problems.
 One problem arises when a switching inverter is installed in a
system that is resonant at frequencies produced by the switching
process. High-frequency hash appearing on the voltage waveform.
 This problem is generally solved by adding a capacitor to the bus
that is of sufficient size to shunt off the high-frequency components
without causing additional resonances.
2/11/2021 61
 Harmonics from rotating machines are not always negligible,
particularly in grid parallel operation. The utility power system
acts as a short circuit to zero-sequence triplen harmonics in the
voltage, which can result in surprisingly high currents. For
grounded wye-wye or delta-wye service transformers, only
synchronous machines with 2/3 pitch can be paralleled without
special provisions to limit neutral current.
 For service transformer connections with a delta-connected
winding on the DG side, nearly any type of three-phase
alternator can be paralleled without this harmonic problem.
2/11/2021 62
Voltage Sags
 The most common power quality problem is a voltage sag, but
the ability of DG to help alleviate sags is very dependent on the
type of generation technology and the interconnection
location.
 DG is interconnected on the load side of the service transformer.
During a voltage sag, DG might act to counter the sag. Large
rotating machines can help support the voltage magnitudes and
phase relationships.
2/11/2021 63
2/11/2021 64
 The DG influence on sags at its own load bus is aided by the
impedance of the service transformer, which provides some
isolation from the source of the sag on the utility system.
 However, this impedance hinders the ability of the DG to
provide any relief to other loads on the same feeder. DG larger
than 1 MW will often be required to have its own service
transformer. The point of common coupling with any load is the
primary distribution system. Therefore, it is not likely that DG
connected in this manner will have any impact on the voltage sag
characteristic seen by other loads served from the feeder.
5.4. Operating Conflicts
 Deploying generation along utility distribution systems naturally
creates some conflicts because the design of the system
assumes only one source of power. A certain amount of
generation can be accommodated without making any changes.
At some point, the conflicts will be too great and changes must
be made.
2/11/2021 65
5.4. Operating Conflicts
 Utility Fault-Clearing Requirements
2/11/2021 66
2/11/2021 67
Figure shows the key components of the
overcurrent protection system of a radial feeder.
♠ The lowest-level component is the lateral fuse, and the other
devices (reclosers and breakers) are designed to conform to the
fuse characteristic.
♠ There will frequently be two to four feeders off the same
substation bus. This design is based mostly on economic concerns.
This is the least costly protection scheme that is able to achieve
acceptable reliability for distributing the power.
♠ One essential characteristic is that only one device has to operate
to clear and isolate a short circuit, and local intelligence can
accomplish the task satisfactorily.
♠ In contrast, faults on the transmission system, which easily
handles generation, usually require at least two breakers to operate
and local intelligence is insufficient in some cases.
2/11/2021 68
♠ With only one utility device operating to clear a fault, all
other DG devices must independently detect the fault and
separate to allow the utility protection system to complete the
clearing and isolation process.
♠ This is not always simple to do from the information that can
be sensed at the generator.
 Reclosing
 Most of the distribution lines are overhead, and it is common to
have temporary faults. Once the current is interrupted and the
arc dispersed, the line insulation is restored. Reclosing enables
the power to be restored to most of the customers within
seconds.
Reclosing presents two special problems with respect to
DG:
1. DG must disconnect early in the reclose interval to
allow time for the arc to dissipate so that the reclose will
be successful.
2. Reclosing on DG, particularly those systems using
rotating machine technologies, can cause damage to the
generator or prime mover.
2/11/2021 69
♠ Figure illustrates the reclose interval between the first two
operations of the utility breaker (this represents an unsuccessful
reclose because the fault is still present).
♠ The DG relaying must be able to detect the presence of the fault
followed by the opening of the utility fault interrupter so that it can
disconnect early in the reclose interval as shown.
♠ Detection and disconnection process should be straightforward.
However, some transformer connections make it difficult to detect
certain faults, which could delay disconnection.
2/11/2021 70
2/11/2021 71
 A reclose interval of at least 1.0 s is safer when there is DG on the
feeder. Many utilities use 2.0 or 5.0 s for the first reclose interval
when DG is installed.
 This minimizes the risk that the DG will not disconnect in time.
If it is deemed necessary to maintain the instantaneous reclose, it is
generally necessary to employ direct transfer trip so that the DG
breaker is tripped simultaneously with the utility breaker.
 This can be a very expensive proposition for smaller DG
installations. Thus, for some distribution systems it will be
necessary to compromise one aspect of power quality to
better accommodate significant amounts of DG.
 Interference With Relay
Three of the more common cases where
DG can interfere with the over- current protection
relaying on distribution feeders will be
1. Reduction of reach
2. Sympathetic tripping of feeder breakers
3. Defeat of fuse saving
2/11/2021 72
2/11/2021 73
1. Reduction of reach
Figure illustrates the reduction-of-reach concept. Each over- current
relay device has an assigned zone of protection that is determined by
its minimum pickup value. Some refer to this generically as the
“reach” of the relay. DG infeed can reduce the current that the relay
sees, thereby shortening its reach. When the total DG capacity
increases to a certain amount, the infeed into faults can desensitize
the relays and leave remote sections of the feeder unprotected.
2/11/2021 74
A low-current (high-impedance) fault near the end of the
feeder is more likely to go undetected until it does
sufficient damage to develop into a major fault.
The power quality consequences of this are that voltage sags will
be prolonged for some customers and the additional fault damage
will eventually lead to more sustained interruptions.
This issue can be a particular problem for peaking generation located
near the end of the feeder. This generation is on at peak load
level where the overcurrent relaying would normally be very
sensitive to a high-impedance fault. The DG infeed has the
potential to mask many faults that would otherwise be detected.
2/11/2021 75
Solutions include:
1. Decrease the relay minimum pickup current to increase the zone.
This may not be practical for ground relays that are already set to a
very sensitive level.
2. Add a line recloser to create another protection zone that extends far
past the end of the feeder.
3. Use a transformer connection that minimizes DG contribution to
ground faults, since high-impedance faults are likely to be ground
faults.
 Interference With Relay
– Sympathetic Tripping of Feeder Breaker
 It describes the condition where a breaker that does
not detect the fault current trips in sympathy with the
breaker that did. The common circuit condition on
utility distribution feeders is back feed into a ground
fault.(shown in fig.)
2/11/2021 76
 Most utility feeder breakers don’t have directional sensing. Thus
because of this ground relay detects the DG contribution as a fault
and trips the circuit breaker unnecessarily.
 Solution is using directional overcurrent relaying but this is very
expensive, if appropriate P T/Fs are not present.
 Interference With Relay
– Defeat of Fuse Saving
2/11/2021 77
 Fuse-saving action is a “horse race” in the best of circumstances. It
is a challenge for the mechanical recloser to detect the fault and
operate fast enough to prevent damage to the fuse element. DG
infeed adds to the current in the fuse and makes this race even
tighter. At some amount of DG capacity that is capable of feeding the
fault, it will no longer be possible to save the fuse.
 This phenomenon limits the amount of synchronous machine DG
that can be accommodated without making changes to the system.
Fuse-saving coordination fails for about the same level of
generation that causes voltage regulation problems.
2/11/2021 78
Solutions include:
1. Increase the size of the lateral fuses. All fused cutouts in the zone
would have to be changed, which could be quite expensive.
2. Choose to simply abandon fuse saving, particularly if the DG is
only connected intermittently.
3. Require DG to have transformer connections that do not feed single-
line-to-ground faults.
 Voltage Regulation Issues
2/11/2021 79
Concern for various dynamics and transients issues that
are difficult to analyze, voltage regulation issues are
more likely to occur and cause interconnection
problems.
Figure shows the voltage profile along the feeder prior to the
fault occurring. The intent of the voltage regulation scheme is to
keep the voltage magnitude between the two limits shown. In this
case, the DG helps keep the voltage above the minimum and, in
fact, is large enough to give a slight voltage rise toward the end of
the feeder.
2/11/2021 80
When the fault occurs, the DG disconnects and may
remain disconnected for up to 5 min. The breaker
recloses within a few seconds, resulting in the condition
shown in Fig. The load is now too great for the feeder
and the present settings of the voltage regulation devices.
The voltage at the end of the feeder below the minimum and will
remain low until voltage regulation equipment can react.
This can be the better part of a minute or longer, which increases the
risk of damage to load equipment due to excessively low voltages.
2/11/2021 81
It also suggests one test an analyst can perform to determine if a pro-
posed DG application will likely require changes on the utility system.
The test would be to compute the voltage change that occurs at peak
load if the DG suddenly disconnects. This change should be less than
about 5 percent unless there is fast-acting voltage regulation equip-
ment that can compensate for a larger change.
2/11/2021 82
The amount of generation that can
be accommodated by this test will
obviously vary with position on
the feeder. One useful analysis is
to determine how much DG
capacity can be accommodated
(without change) at various
distances along the feeder. For
example, if one were to establish a 5
percent change criterion for the
limit, there would be a curve of
generation limit versus distance
similar to that shown in Fig.
2/11/2021 83
solutions include:
1. Requiring customer load to disconnect with the DG. This may not
be practical for widespread residential and small commercial
loads. Also, it is difficult to make this transition seamlessly and the
load may suffer downtime anyway, negating positive reliability
benefits of DG.
2. Installing more voltage regulators, each with the ability to bypass
the normal time delay of 30 to 45 s and begin changing taps
immediately. This will minimize the inconvenience to other
customers.
3. Allow DG to reconnect more quickly than the standard 5-min dis-
connect time. This would be done more safely by using direct
communications between the DG and utility system control.
4. Limit the amount of DG on the feeder.
Operating Conflicts
 Excess DG Can Fool Reverse Power Setting on
Line Voltage Regulator
2/11/2021 84
Another voltage regulation issue involving step-voltage regulators
2/11/2021 85
Utility voltage regulators commonly come with a reverse-power feature
that allows the regulators to be used when a feeder is supplied from its
alternate source. The logic is that when the net power through the
regulator is in the reverse direction, the regulator control switches
direction and regulates the original source terminal so that the
regulator can work properly. Otherwise, the control will attempt to
regulate the alternate source side, which would not be possible. The
tap position would generally move to one extreme or the other and
stay there.
Operating Conflicts
 Varying DG Output can Cause Excess Duty
on Utility Voltage Regulation Equipment
2/11/2021 86
2/11/2021 87
Generation technologies whose output varies rapidly
can be difficult to handle on a distribution feeder. Wind-
turbine generation is the most difficult because there is
seldom a substation near the proposed site. The
generation is typically sited several miles from the
nearest sub- station on a feeder that already may have
several switched capacitors and a voltage regulator.
 One solution is to increase the bandwidth on the controls
 While the magnitude variation in this case exceeded 2
percent, it is not changing fast enough to likely cause volt- age
fluctuation complaints.
 When the fluctuation is too great, the main recourse is to build a
sep- arate feeder for the wind generation. Also, some wind
generators employ doubly fed wound-rotor induction machines
that can control reactive power very quickly. With proper control,
this can help tame the voltage fluctuations.
Operating Conflicts
Harmonics
 Harmonics from DG come from inverters and some
synchronous machines.
 The PWM switching inverters produce a much lower harmonic
current content than earlier line-commutated, thyristor-based
inverters.
 In IEEE Standard 519-1992, generators are limited to the most
restrictive values in the tables on the allowable amount of
harmonic current injection.
2/11/2021 88
2/11/2021 89
One new distortion problem that arises with the modern inverters is
that the switching frequencies will occasionally excite resonances in
the primary distribution system. This creates nonharmonic frequency
signals typically at the 35th harmonic and higher riding on the
voltage waveform.
This has an impact on clocks and other circuitry that depend on a
clean voltage zero crossing.
2/11/2021 90
2/11/2021 91
Harmonics problems related to zero-sequence triplen harmonics shown
in fig. The facility where the generator is located is served at 480 V by
a common delta-wye transformer. When the generator is paralleled to
the utility system through this transformer, the operator is frequently
surprised to find a large amount of current circulating in the neutral. In
the example shown, the current is 26 percent of the machine’s rated
current and is entirely third-harmonic current. This can adversely
affect the operation and efficiency of the machine and may result in
the failure of some circuit element. In this case, the problem is
confined to the generator side of the transformer and does not affect
the primary distribution system because the triplen harmonics are
trapped by the delta winding.
Operating Conflicts
Islanding
Main Utility Grid
DG
2/11/2021 92
DG protective relays will generally perform their function
independently of any outside knowledge of the system to
which they are connected.
2/11/2021 93
Perhaps the greatest fear of the utility protection
engineer is that DG relaying will fail to detect the fact
that the utility breaker has opened and will continue to
energize a portion of the feeder.
Attention has been paid to detecting islands
or forcing islands to become unstable so they can be
detected.
Another concern is the DG itself. Since reclosing is
common, it is essential that the DG detect the island promptly and
disconnect. If it is still connected when the utility breaker recloses,
damage can occur to prime movers, shafts, and components of
machines due to the shock from out-of-phase reclosing.
Operating Conflicts
Ferroresonance
 Ferroresonance is a special kind of resonance in which the
inductive element is the nonlinear characteristic of an iron-core
device.
 Ferroresonance occurs when the magnetizing reactance of a
transformer inadvertently is in series with cable or power factor
capacitance.
 One interesting case occurs for DG served by cable-fed
transformers. It is common practice for the larger DG
installations to have their own transformer. Also, it is nearly
universal to require DG to disconnect at the first sign of trouble on
the utility system. This combination of requirements can lead to a
common ferroresonant condition.
2/11/2021 94
2/11/2021 95
The circuit is shown in Fig. 9.21. Underground cable runs are
normally fused at the point where they are tapped off the
overhead feeder line. This is variously called the riser pole or dip
pole. Should some- thing happen that causes one or two fuses to
blow, the relaying on the DG will detect an unbalanced
condition and trip the generator breaker. This leaves the
transformer isolated on the cable with one or two open phases
and no load. Either condition is conducive to ferroresonance
because the cable capacitance in an open phase, or phases,
now appears in series with the transformer’s magnetizing
impedance (Fig. 9.22).
2/11/2021 96
2/11/2021 97
The type of ferroresonance shown in Fig. 9.23 is very sensitive to the
amount of load. If the system can be arranged so that there is always a
resistive load attached to the secondary bus, the resonance can be
damped out. The load need not always be large, but must be significant.
Operating Conflicts
 Shunt Capacitor Interaction (Overvoltage due to
capacitor)
2/11/2021 98
2/11/2021 99
Utilities use switched capacitors to help support the
voltage during high-load periods. These banks are
mostly controlled by local intelligence, switching at
predetermined times or at loading levels as measured
by either voltage, current, or kvar. Some types of DG
can also produce reactive power (vars), and this can
create control hunting and other difficulties.
The capacitors switch independently of the generator control unless
special communications and control have been added to coordinate
dispatch. A 2 to 3 percent increase in the voltage is common when a
typical capacitor bank is energized.
Generators in parallel operation are generally maintaining a constant
power and power factor. The reactive power of the machine is con-
trolled by the exciter field, which will have certain minimum and
maximum voltage or field excitation limits as indicated on the diagram.
The generator control attempts to maintain a constant reactive power
output until it bumps up against one of these limits.
2/11/2021 100
when capacitors are switched by time clock or by current magnitude
(without voltage override). There are at least three things that can
happen at this point to trip the generator:
1. The generator control senses overvoltage at its terminals and
attempts to back down the field to compensate. However, the
utility system overpowers the generator and the field reduces to a
level deemed to be too low for safe operation of the machine.
2. When the generator reaches its voltage limit, reactive power flows
back into the machine. When it reaches a certain level, the
generator protection interprets this as a malfunction.
3. DG that does not produce reactive power simply trips on
overvoltage.
Operating Conflicts
 Transformer Connections
– Grounded Y-Y Connection
It is favoured because of its reduced susceptibility to ferro resonance
on cable-fed loads and fewer operating restrictions when being
switched for maintenance. It is also generally well behaved with
respect to DG interconnection, but there are a couple of issues.
Advantages include:
• No Phase Shift
• Less Concern for Ferroresonance
Disadvantages include:
• Allow DG to Feed All Types of Faults on the Utility System
• Back Feed of the Triplen Harmonic
• Should Insert Ground Impedance to Limit the Current
2/11/2021 101
Operating Conflicts
 Transformer Connections
– D-Y Connection
2/11/2021 102
2/11/2021 103
It would probably be favoured for serving loads in nearly all cases if it
were not for the susceptibility of the connection to ferro resonance in
cable-fed systems.
Advantages include:
■ There is less infeed into utility-side ground faults.
■ Third harmonics from the DG do not reach the utility system.
■ Some isolation from voltage sags due to utility-side SLG faults is
provided.
Disadvantages include:
■ It is difficult to detect some SLG faults from the secondary side by
voltage relaying alone.
2/11/2021 104
It is susceptible to ferro resonance in cable-fed installations.
■ Third harmonics in the DG may cause excessive current in the
secondary-side neutral.
■ If islanded on an SLG fault, utility arresters can be subjected to
over voltages ■ If arresters are islanded on an SLG fault and there
is little load, resonant over voltages can result
Operating Conflicts
 Transformer Connection
– Delta-Delta Connection
2/11/2021 105
2/11/2021 106
While not in the majority, these connections are still common for
commercial and industrial loads. Both have similar behaviour with
respect to serving DG. Neither would be the preferred connection
for serving most new DG installations, but could be encountered in
legacy systems where a customer wishes to parallel DG. Some
inverter-based systems (fuel cells, photovoltaics, microturbines,
etc.) require an ungrounded connection on the DG side because
the dc side of the inverter is grounded. This is often
accomplished by use of a separate isolation transformer rather than
the main service
transformer.
2/11/2021 107
Advantages include:
■ More economical transformer installation for smaller three-phase
service with some single-phase loads is possible.
■ The load is isolated from ground faults on the utility side.
■ DG would not typically feed utility-side ground faults except
when resonance occurs.
■ Ungrounded interconnection can be provided for inverter-based
systems requiring it.
Disadvantages include:
■ Utility-side SLG faults are difficult to detect.
■ Utility arresters are subjected to high steady-state over voltages
if islanded on an SLG fault (see Fig. 9.26). This is true for delta-
wye connections as well.
Operating Conflicts
 Transformer Connection
– Grounded Y-D Connection
2/11/2021 108
2/11/2021 109
This is an interesting connection because of the conflicting
application considerations. Many utility engineers believe this is the
best winding connection for interconnecting generation to the utility
system. This is the connection used for nearly all central station
generation. There are many advantages, including:
1. Utility-side faults are easily detected partly because the
transformer itself actively participates in ground faults.
2. Triplen harmonic voltages produced by the generator do not cause any
current to flow because it is blocked by the delta winding. Therefore,
nearly any generator can be paralleled with this connection.
3. Protection schemes are well understood based on many years of
experience with utility generation.
2/11/2021 110
5.5. DG on Low-Voltage
Distribution Networks
Focus on DG interconnected to radial primary or secondary distribution
circuits, which is the most common distribution configuration.
However, in large cities a number of utilities use a low-voltage
network method of distribution.
These low-voltage network systems are of two major subtypes, the
secondary network (also referred to as an area network, grid network,
or street network) and the spot network.
2/11/2021 111
Secondary networks serve numerous sites, usually
several city blocks, from a grid of low-voltage mains at
120/208 V, three-phase.
Spot networks serve a single site, usually a large building or even a
portion of a large building. The secondary voltage of spot networks is
often 277/480 V, three-phase, but 120/208-V spot networks are also
used.
Street networks and spot networks are supplied from two or more
primary distribution feeders through integrated transformer / breaker /
protection combinations called network units. These network units
are often located in transformer vaults within the building or in
under- ground vaults in the street.
2/11/2021 112
Figure 9.28 shows a spot network arrangement with three
primary feeders. The primary feeders may be dedicated to the spot
network, may serve other network units at different sites, or may serve
ordinary radial distribution loads as well.
The objective of the network distribution design is to achieve
high service reliability with high power quality. To accomplish this, the
primary feeders are often chosen so that they originate at different
substations or, at least at different bus sections of the same substation.
The high power quality is achieved by having full service capability
with any feeder out of service and rapidly removing any faulted
feeder from connection to the low-voltage network.
2/11/2021 113
Spot Network Arrangement
DG on Low-Voltage
Distribution Networks
 Spot Network Arrangement
Underground Network
NPR
NPR
NPR
NPR
NPR
NPR
NPR
2/11/2021 114
DG on Low-Voltage
Distribution Networks
 Arrangement of Network Protector Relay
Source
Network
Transformer
Network
Protector
Network
2/11/2021 115
2/11/2021 116
Fundamentals of network operation
We will concentrate on the spot network. In normal operation,
the spot network is supplied simultaneously from all the primary
feeders, by paralleling the low-voltage secondaries of the network
transformers on the spot network bus.
In order that the spot network can continue to operate if a
primary feeder becomes faulted, the network units are each equipped
with a low-voltage circuit breaker, called the network protector, and
a directional-power relay called the network relay or master relay.
2/11/2021 117
When a primary feeder is faulted, the network relay senses reverse
power flow (from the network toward the primary feeder) and opens
the network protector, thereby isolating the network bus from the
faulted feeder and allowing service on the network to continue without
interruption. This function is the reason for the name network
protector and the reason why DG interconnection to networks becomes a
complex issue.
Figure 9.29 shows the operation of a network protector in isolating a
faulted primary feeder. Later, when the faulted primary feeder is
repaired and returned to service, the network relay senses voltage at
the transformer side of the open network protector.
2/11/2021 118
Figure 9.29 Network primary feeder fault.
2/11/2021 119
If this voltage is such that power will flow
from the network unit to the bus when the protector is
closed, the network relay commands the protector
switch to reclose.
Determining when this reclose will take place
may become an interconnection issue.
The network relay is a very sensitive reverse-power relay, with
a pickup level on the order of 0.1 percent of the rated power of the
network transformer. These settings can be as low as 1 to 2 kW.
It is the mission of the reverse-power relay to be capable of
sensing reverse power flow with no other feeder loads than the core
losses of its own network transformer.
This great sensitivity is necessary because the network
protector must operate for all types of faults on the primary feeder,
including ground faults.
2/11/2021 120
A delta-connected primary is commonly used on
network transformers, no ground fault current will flow
from the network toward the primary feeder once the
source sub- station feeder circuit breaker has opened.
Thus the network relay must be capable of sensing reverse
power using only its own transformer’s losses.
This sensitive reverse-power function means that no DG can
be connected to the network with the intent to export power to the
utility system. It further means that even momentary power
reversals under abnormal conditions must be considered in the
interconnection design.
2/11/2021 121
The traditional network relay is an electromechanical device
and has no intentional time delay. The typical operating time is about
0.05 s (3 cycles) at normal voltage levels, thus the reason that even
momentary power reversals caused by the DG are of concern.
Microprocessor based network relays have replaced the
electromechanical types in new network units, and these relays can be
retrofitted into many types of existing network units. The basic
performance of the microprocessor types is similar to the electro
mechanicals, but they have more flexibility and new features.
DG on Low-Voltage
Distribution Networks
 A Microcomputer Based Network Protector Relay
2/11/2021 122
DG on Low-Voltage
Distribution Networks
 Operation of A Microcomputer Based Network
Protector Relay
– Network protector relays are used to monitor and
control the power flow of low voltage AC to secondary
network systems.
– The purpose of the network protector is to prevent the
system from back feeding and initiate automatic
reclosing when the system returns to normal.
2/11/2021 123
DG on Low-Voltage Distribution
Networks
 Tripping Characteristics of A Microcomputer Based
Network Protector Relay
0
o
90
o
270
o
180
o
Tripping
Region
Non-Tripping
Region
Non-Tripping
Region
Tripping
Region
Network
Phase Voltage
(Unity PF)
Current into
Network
Current into
Network
(Lagging PF)
(Unity PF)
Current out of
Network
Fault
Current
Max. Torque
2/11/2021 124
 Reclosing Characteristics of A Microcomputer
Based Network Protector Relay
0o
1V
2V
3V
4V
5V
6V
7V
8V
Phase Relay
Characteristic
Master Relay
Characteristic
Offset Voltage
Phase Relay
Reclosed
Region
2/11/2021 125
2/11/2021 126
The network protector is an air circuit breaker specifically designed
for the fault current conditions encountered on low-voltage network
systems. It operates only under the control of the network relay. The
network protector has no overcurrent protection and does not open
for faults on the low-voltage secondary system. Low-voltage faults
are cleared by fuses or by circuit breakers within the served facility
 Fault Current Contribution From Synchronous
Local DG
2/11/2021 127
The fault current delivery from synchronous DG to external faults
can cause network protectors to open, potentially isolating the
network. Above Figure shows an example of how this can happen.
 Inverter Based DG on a Spot Network
(Possible Solution)
2/11/2021 128
2/11/2021 129
Despite this daunting list of problems, there are some ways that
DG may be accommodated on spot networks, by taking advantage
of new technology. Inverter-based DG has the advantages that
fault current is very limited, to about 100 to 200 percent of the
normal inverter load current, and that an inverter can respond
very rapidly to signals con- trolling its power output level.
Because the most critical aspect of DG on networks is that
the local generation must never exceed the local load, this
example uses a tie- line load control scheme that senses the total
incoming power to the facility and adjusts the DG power output
to ensure that power flow is always inward.
2/11/2021 130
Other approaches that might be used are
■ Size the DG to be less than the minimum load that ever exists on
the network, with a margin for sudden loss of a large load.
■ Total the incoming power to the network and trip the DG
whenever the inward power flow falls below a safe value.
DG on Low-Voltage
Distribution Networks
 Adjustable Reverse Power Characteristics
2/11/2021 131
Blame nobody
Expect nothing
Do something
YOURSELF
“Never doubt
that a small group of
committed people
can change the world.
Indeed it is the only thing
that ever has.”
--Margaret Mead
To live
is the rarest thing in the world.
Most people exist, that is all.
--Oscar Wilde
THANKING YOU
FOR YOUR ATTENTION

Contenu connexe

Tendances

social and environmental importance of hybrid and electric.ppt
social and environmental importance of hybrid and electric.pptsocial and environmental importance of hybrid and electric.ppt
social and environmental importance of hybrid and electric.pptGomathy Sengottaiyan
 
Modeling of a single phase Grid-connected PV system by using Matlab/Simulink
Modeling of a single phase Grid-connected PV system by using Matlab/SimulinkModeling of a single phase Grid-connected PV system by using Matlab/Simulink
Modeling of a single phase Grid-connected PV system by using Matlab/SimulinkSai Divvela
 
Basic types of facts controllers
Basic types of facts controllersBasic types of facts controllers
Basic types of facts controllersAyyarao T S L V
 
MicroGrid and Energy Storage System COMPLETE DETAILS NEW PPT
MicroGrid and Energy Storage System COMPLETE DETAILS NEW PPTMicroGrid and Energy Storage System COMPLETE DETAILS NEW PPT
MicroGrid and Energy Storage System COMPLETE DETAILS NEW PPT Abin Baby
 
importance of reactive power in power system
importance of reactive power in power systemimportance of reactive power in power system
importance of reactive power in power systemsneh pratap singh
 
Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)RP6997
 
Grid integration issues and solutions
Grid integration issues and solutionsGrid integration issues and solutions
Grid integration issues and solutionsSwathi Venugopal
 
ABCB(air blast circuit breaker)
ABCB(air blast circuit breaker)ABCB(air blast circuit breaker)
ABCB(air blast circuit breaker)AB Amit
 
Solar wind hybrid power system ppt
Solar wind hybrid power system pptSolar wind hybrid power system ppt
Solar wind hybrid power system pptVihar Modi
 
Economic load dispatch
Economic load  dispatchEconomic load  dispatch
Economic load dispatchDeepak John
 
An introduction to FACTS
An introduction to FACTSAn introduction to FACTS
An introduction to FACTSAyyarao T S L V
 
Distributed generation b 3
Distributed generation b 3Distributed generation b 3
Distributed generation b 3Naresh Thakur
 
Hvdc transmission seminar
Hvdc transmission seminar Hvdc transmission seminar
Hvdc transmission seminar Utkarsh Jambhule
 
Gcsc gto thyristor controlled series capacitor
Gcsc   gto thyristor controlled series capacitorGcsc   gto thyristor controlled series capacitor
Gcsc gto thyristor controlled series capacitorLEOPAUL23
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
 

Tendances (20)

Wind turbine power
Wind turbine powerWind turbine power
Wind turbine power
 
social and environmental importance of hybrid and electric.ppt
social and environmental importance of hybrid and electric.pptsocial and environmental importance of hybrid and electric.ppt
social and environmental importance of hybrid and electric.ppt
 
Modeling of a single phase Grid-connected PV system by using Matlab/Simulink
Modeling of a single phase Grid-connected PV system by using Matlab/SimulinkModeling of a single phase Grid-connected PV system by using Matlab/Simulink
Modeling of a single phase Grid-connected PV system by using Matlab/Simulink
 
Basic types of facts controllers
Basic types of facts controllersBasic types of facts controllers
Basic types of facts controllers
 
MicroGrid and Energy Storage System COMPLETE DETAILS NEW PPT
MicroGrid and Energy Storage System COMPLETE DETAILS NEW PPTMicroGrid and Energy Storage System COMPLETE DETAILS NEW PPT
MicroGrid and Energy Storage System COMPLETE DETAILS NEW PPT
 
importance of reactive power in power system
importance of reactive power in power systemimportance of reactive power in power system
importance of reactive power in power system
 
Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)
 
Grid integration issues and solutions
Grid integration issues and solutionsGrid integration issues and solutions
Grid integration issues and solutions
 
ABCB(air blast circuit breaker)
ABCB(air blast circuit breaker)ABCB(air blast circuit breaker)
ABCB(air blast circuit breaker)
 
HVDC & FACTS
HVDC & FACTSHVDC & FACTS
HVDC & FACTS
 
Solar wind hybrid power system ppt
Solar wind hybrid power system pptSolar wind hybrid power system ppt
Solar wind hybrid power system ppt
 
Demand Side Management
Demand Side ManagementDemand Side Management
Demand Side Management
 
Economic load dispatch
Economic load  dispatchEconomic load  dispatch
Economic load dispatch
 
An introduction to FACTS
An introduction to FACTSAn introduction to FACTS
An introduction to FACTS
 
Distributed generation b 3
Distributed generation b 3Distributed generation b 3
Distributed generation b 3
 
Solar pv connected to grid
Solar pv connected to gridSolar pv connected to grid
Solar pv connected to grid
 
Hvdc transmission seminar
Hvdc transmission seminar Hvdc transmission seminar
Hvdc transmission seminar
 
Gcsc gto thyristor controlled series capacitor
Gcsc   gto thyristor controlled series capacitorGcsc   gto thyristor controlled series capacitor
Gcsc gto thyristor controlled series capacitor
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Chapter 02- Breakdown in liquid dielectrics
Chapter 02- Breakdown in liquid dielectricsChapter 02- Breakdown in liquid dielectrics
Chapter 02- Breakdown in liquid dielectrics
 

Similaire à Distributed generation & power quality unit 5

seminar report on optimal placement and optimal sizing of DG
seminar report on optimal placement and optimal sizing of DGseminar report on optimal placement and optimal sizing of DG
seminar report on optimal placement and optimal sizing of DGkhemraj298
 
OPTIMAL PLACEMENT OF DISTRIBUTED GENERATION FOR LOSS REDUCTION IN DISTRIBUTIO...
OPTIMAL PLACEMENT OF DISTRIBUTED GENERATION FOR LOSS REDUCTION IN DISTRIBUTIO...OPTIMAL PLACEMENT OF DISTRIBUTED GENERATION FOR LOSS REDUCTION IN DISTRIBUTIO...
OPTIMAL PLACEMENT OF DISTRIBUTED GENERATION FOR LOSS REDUCTION IN DISTRIBUTIO...ijiert bestjournal
 
Presentation to Baran Group Ltd. in summer 2015
 Presentation to Baran Group Ltd. in summer 2015 Presentation to Baran Group Ltd. in summer 2015
Presentation to Baran Group Ltd. in summer 2015Haim R. Branisteanu
 
Distributed dispersed generation_J.B. Essuman
Distributed dispersed generation_J.B. EssumanDistributed dispersed generation_J.B. Essuman
Distributed dispersed generation_J.B. EssumanKj_ss
 
Distributed dispersed generation
Distributed dispersed generationDistributed dispersed generation
Distributed dispersed generationKj_ss
 
Electric Power Management for a Grid Connected Renewable Energy Sources
Electric Power Management for a Grid Connected Renewable Energy SourcesElectric Power Management for a Grid Connected Renewable Energy Sources
Electric Power Management for a Grid Connected Renewable Energy Sourcestheijes
 
An Overview of Distributed Generation
An Overview of Distributed GenerationAn Overview of Distributed Generation
An Overview of Distributed GenerationIJMER
 
A distributed networked Monitoring and Electrical Energy Storage System to pr...
A distributed networked Monitoring and Electrical Energy Storage System to pr...A distributed networked Monitoring and Electrical Energy Storage System to pr...
A distributed networked Monitoring and Electrical Energy Storage System to pr...Haim R. Branisteanu
 
Corporate-Profile-Investors-2
Corporate-Profile-Investors-2Corporate-Profile-Investors-2
Corporate-Profile-Investors-2Fabio Magnani
 
IRJET- Management of Smart Grid Power System using Zigbee Technology
IRJET- Management of Smart Grid Power System using Zigbee TechnologyIRJET- Management of Smart Grid Power System using Zigbee Technology
IRJET- Management of Smart Grid Power System using Zigbee TechnologyIRJET Journal
 
Design and Modeling of Grid Connected Hybrid Renewable Energy Power Generation
Design and Modeling of Grid Connected Hybrid Renewable Energy Power GenerationDesign and Modeling of Grid Connected Hybrid Renewable Energy Power Generation
Design and Modeling of Grid Connected Hybrid Renewable Energy Power GenerationIJERA Editor
 
FORMULATION AND EXECUTION OF A DC TO DC BOOST CONVERTER WITH NON-CONVENTIONAL...
FORMULATION AND EXECUTION OF A DC TO DC BOOST CONVERTER WITH NON-CONVENTIONAL...FORMULATION AND EXECUTION OF A DC TO DC BOOST CONVERTER WITH NON-CONVENTIONAL...
FORMULATION AND EXECUTION OF A DC TO DC BOOST CONVERTER WITH NON-CONVENTIONAL...IRJET Journal
 
IRJET- Review Paper Hybrid Energy Storage System Micro Grid Integration with ...
IRJET- Review Paper Hybrid Energy Storage System Micro Grid Integration with ...IRJET- Review Paper Hybrid Energy Storage System Micro Grid Integration with ...
IRJET- Review Paper Hybrid Energy Storage System Micro Grid Integration with ...IRJET Journal
 
2007-Iovetal.-Powerelectronicsandcontrolofrenewableenergysystems2.pdf
2007-Iovetal.-Powerelectronicsandcontrolofrenewableenergysystems2.pdf2007-Iovetal.-Powerelectronicsandcontrolofrenewableenergysystems2.pdf
2007-Iovetal.-Powerelectronicsandcontrolofrenewableenergysystems2.pdfMuammerAlakary
 

Similaire à Distributed generation & power quality unit 5 (20)

seminar report on optimal placement and optimal sizing of DG
seminar report on optimal placement and optimal sizing of DGseminar report on optimal placement and optimal sizing of DG
seminar report on optimal placement and optimal sizing of DG
 
OPTIMAL PLACEMENT OF DISTRIBUTED GENERATION FOR LOSS REDUCTION IN DISTRIBUTIO...
OPTIMAL PLACEMENT OF DISTRIBUTED GENERATION FOR LOSS REDUCTION IN DISTRIBUTIO...OPTIMAL PLACEMENT OF DISTRIBUTED GENERATION FOR LOSS REDUCTION IN DISTRIBUTIO...
OPTIMAL PLACEMENT OF DISTRIBUTED GENERATION FOR LOSS REDUCTION IN DISTRIBUTIO...
 
Jm3417081729
Jm3417081729Jm3417081729
Jm3417081729
 
DISTRIBUTE GENERATION
DISTRIBUTE GENERATIONDISTRIBUTE GENERATION
DISTRIBUTE GENERATION
 
L41028287
L41028287L41028287
L41028287
 
Presentation to Baran Group Ltd. in summer 2015
 Presentation to Baran Group Ltd. in summer 2015 Presentation to Baran Group Ltd. in summer 2015
Presentation to Baran Group Ltd. in summer 2015
 
Unit2
Unit2Unit2
Unit2
 
Distributed dispersed generation_J.B. Essuman
Distributed dispersed generation_J.B. EssumanDistributed dispersed generation_J.B. Essuman
Distributed dispersed generation_J.B. Essuman
 
Distributed dispersed generation
Distributed dispersed generationDistributed dispersed generation
Distributed dispersed generation
 
Electric Power Management for a Grid Connected Renewable Energy Sources
Electric Power Management for a Grid Connected Renewable Energy SourcesElectric Power Management for a Grid Connected Renewable Energy Sources
Electric Power Management for a Grid Connected Renewable Energy Sources
 
An Overview of Distributed Generation
An Overview of Distributed GenerationAn Overview of Distributed Generation
An Overview of Distributed Generation
 
A distributed networked Monitoring and Electrical Energy Storage System to pr...
A distributed networked Monitoring and Electrical Energy Storage System to pr...A distributed networked Monitoring and Electrical Energy Storage System to pr...
A distributed networked Monitoring and Electrical Energy Storage System to pr...
 
Corporate-Profile-Investors-2
Corporate-Profile-Investors-2Corporate-Profile-Investors-2
Corporate-Profile-Investors-2
 
IRJET- Management of Smart Grid Power System using Zigbee Technology
IRJET- Management of Smart Grid Power System using Zigbee TechnologyIRJET- Management of Smart Grid Power System using Zigbee Technology
IRJET- Management of Smart Grid Power System using Zigbee Technology
 
Design and Modeling of Grid Connected Hybrid Renewable Energy Power Generation
Design and Modeling of Grid Connected Hybrid Renewable Energy Power GenerationDesign and Modeling of Grid Connected Hybrid Renewable Energy Power Generation
Design and Modeling of Grid Connected Hybrid Renewable Energy Power Generation
 
FORMULATION AND EXECUTION OF A DC TO DC BOOST CONVERTER WITH NON-CONVENTIONAL...
FORMULATION AND EXECUTION OF A DC TO DC BOOST CONVERTER WITH NON-CONVENTIONAL...FORMULATION AND EXECUTION OF A DC TO DC BOOST CONVERTER WITH NON-CONVENTIONAL...
FORMULATION AND EXECUTION OF A DC TO DC BOOST CONVERTER WITH NON-CONVENTIONAL...
 
IRJET- Review Paper Hybrid Energy Storage System Micro Grid Integration with ...
IRJET- Review Paper Hybrid Energy Storage System Micro Grid Integration with ...IRJET- Review Paper Hybrid Energy Storage System Micro Grid Integration with ...
IRJET- Review Paper Hybrid Energy Storage System Micro Grid Integration with ...
 
2007-Iovetal.-Powerelectronicsandcontrolofrenewableenergysystems2.pdf
2007-Iovetal.-Powerelectronicsandcontrolofrenewableenergysystems2.pdf2007-Iovetal.-Powerelectronicsandcontrolofrenewableenergysystems2.pdf
2007-Iovetal.-Powerelectronicsandcontrolofrenewableenergysystems2.pdf
 
06200347
0620034706200347
06200347
 
fuel system
fuel systemfuel system
fuel system
 

Dernier

Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...jabtakhaidam7
 
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Call Girls Mumbai
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueBhangaleSonal
 
Moment Distribution Method For Btech Civil
Moment Distribution Method For Btech CivilMoment Distribution Method For Btech Civil
Moment Distribution Method For Btech CivilVinayVitekari
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapRishantSharmaFr
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationBhangaleSonal
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxSCMS School of Architecture
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXssuser89054b
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdfKamal Acharya
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptDineshKumar4165
 
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxOrlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxMuhammadAsimMuhammad6
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityMorshed Ahmed Rahath
 
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxmaisarahman1
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxSCMS School of Architecture
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdfKamal Acharya
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsvanyagupta248
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdfKamal Acharya
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VDineshKumar4165
 

Dernier (20)

Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
 
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Moment Distribution Method For Btech Civil
Moment Distribution Method For Btech CivilMoment Distribution Method For Btech Civil
Moment Distribution Method For Btech Civil
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxOrlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 

Distributed generation & power quality unit 5

  • 1. Distributed Generation & Power Quality HARI MADHAVA REDDY.Y, (Ph.D)., M.Tech., MISTE.,IAENG.,SSI Assistant Professor of Electrical Engineering UNIVERSAL COLLEGE OF ENGINEERING & TECHNOLOGY 2/11/2021 1
  • 2. CONTENTS 5.0. Introduction 5.1. Resurgence Of Distributed Generation 5.2. DG Technologies 5.3. Interface to utility system 5.4. PQ Issues & Operating Conflicts. 5.5. DG on low voltage Distribution network. 2/11/2021 2
  • 3. 5.0. Introduction  DG uses smaller-sized generators(generator sizes less than 10 MW) than does the typical central station plant. They are distributed throughout the power system closer to the loads. Generators larger than this are typically interconnected at transmission voltages where the system is designed to accommodate many generators. 2/11/2021 3
  • 4. 5.0. Introduction The normal distribution system delivers electric energy through wires from a single source of power to a multitude of loads. Thus, several power quality issues arise when there are multiple sources. Will DG improve the power quality or will it degrade the service end users have come to expect? 2/11/2021 4
  • 6.  Most countries generate electricity in large centralized facilities, such as fossil fuel (coal, gas powered), nuclear, large solar power plants or hydropower plants. These plants have excellent economies of scale, but usually transmit electricity long distances and can negatively affect the environment.  Distributed generation allows collection of energy from many sources and may give lower environmental impacts and improved security of supply. 2/11/2021 6
  • 7. 5.1.Resurgence of DG  The electric power industry in developed nations has been to generate power in large, centralized generating stations and to distribute the power to end users through transformers, transmission lines, and distribution lines.  The original electrical power systems, consisting of relatively small generators configured in isolated islands, used DG because of economies of scale.  There was the desire to sequester (sI"kwes.tr) electricity generation facilities away from population centers for environmental reasons and to locate them closer to the source of fuel and water. 2/11/2021 7
  • 8.  The passage of the Public Utilities Regulatory Act of 1978 (PURPA) in the United States in 1978 was intended to foster energy independence.  Tax credits were given, and power was purchased at avoided- cost rates to spur development of renewable and energy- efficient, low-emissions technologies.  This led to a spurt in the development of wind, solar, and geothermal generation as well as gas-fired cogeneration (combined heat and power) facilities.  In the mid-1990s, interest in DG once again peaked with the development of improved DG technologies and the deregulation of the power industry allowing more power producers to participate in the market.  Also, the appearance of critical high-technology loads requiring much greater reliability than can be achieved by wire delivery alone has created a demand for local generation and storage to fill the gap. 2/11/2021 8
  • 9.  New technologies would allow the generation to be as widely dispersed as the load and interconnected power grids could be small (i.e., microgrids). The generation would be powered by renewable resources or clean-burning, high-efficiency technologies. Energy distribution will be shifted from wires to pipes containing some type of fuel, which many think will ultimately be hydrogen.  Recent efforts to deregulate electric power have been aimed not only at achieving better prices for power but at enabling new technologies. 2/11/2021 9
  • 10.  Perspectives on DG Benefits – End-User Perspective • Back Generation to Provide Improved Reliability • Reduce Energy Bill • Participation in the Competitive Power Market – Distribution Utility Perspective • Transmission & Distribution Relief • Hedge Against of Uncertain Load Growth • DG serves as a Hedge Against Price Spikes. – Commercial Power Producer Perspective • Mainly interested in Selling Power or Ancillary (aen"sIl.@r.i) Service in the Deregulated Market • Integrated Resource Planning. 2/11/2021 10
  • 11.  Disadvantages of DG – Power Quality – Cost of Operation and Maintenance – Long Term Reliability of the Units – Interconnection  PERSPECTIVES ON INTERCONNECTION Figure.1 End-user and generator owner perspectives on inter- connection Figure .2 Distribution planner perspective on interconnection 2/11/2021 11
  • 12.  DG is small compared to the grid, implied message related to power quality.  DG proponent literature often portrays DG as improving the reliability of the system (including the grid) and providing better-quality power.  The perspective on interconnected DG of typical utility distribution engineers, most of whom are very conservative in their approach to planning and operations.  The size of customer owned DG is magnified to appear much larger than its actual size, and it produces dirty power. It is also a little off center in its design, suggesting that it is not built and maintained as well as utility equipment. 2/11/2021 12
  • 13. 5.2. DG Technologies  Reciprocating Engine Gen-set Combustion (gas) turbines  Superconducting Magnetic Energy Storage Carbon Nanotube  Fuel cells  Wind turbines Photovoltaic systems 2/11/2021 13
  • 14.  A common application is to provide support for the transmission and distribution system in emergencies. The units are placed in substations and interconnected to the grid through transformers that typically step up the voltage from the 480 V produced by the generators.  Diesel gen-sets are quite popular with end users for backup power  Reciprocating Engine Gen-set – The Least Expensive DG Technology – High Nox and Sox Emission. This Severely Limits the Number of Hours the Units, Particularly Diesels, May Operate per Year. – Natural Gas-Fire Engine Produce Fewer Emission. However, the Natural Gas Price is Unpredictable. Reciprocating Engine Gen-set 2/11/2021 14
  • 15.  It is also common to find reciprocating engines with induction generators. This is particularly true for cogeneration applications of less than 300 kW because it is often simpler to meet interconnection requirements with induction machines that are not likely to support islands.  Reciprocating engine gen-sets have consistent performance characteristics over a wide range of environmental conditions with efficiencies in the range of 35 to 40 percent. They are less sensitive to ambient conditions than combustion turbines whose power efficiency declines considerably as the outside air temperature rises. 2/11/2021 15
  • 16.  APPLICATIONS  The main applications will be for peaking generation and emergency backup.  They are popular in combined heat and power cogeneration applications in schools, government, and commercial buildings where they operate at least for the business day. 2/11/2021 16
  • 17. Combustion (gas) Turbine  Range from 1 to 10 MW  High Speed: 8 – 12 kRPM  Micro turbine • 30 – 75 kW (small), 300-400KW • 10 – 100 kRPM • Efficiency: 25 – 30 %  The waste heat from a combustion turbine is at a much higher temperature than that from a reciprocating engine. Thus, turbines are generally the choice for combined heat and power applications that require process steam.  A micro turbine being employed in a combined heat and power application with the heat exchanger shows in Fig. 2/11/2021 17
  • 18.  Net energy efficiencies exceeding 60 percent  One of the major advantages of this technology is that installations are clean and compact. This allows deployment near living and working areas, although there may be some issues with the high-pitched turbine noise in some environments.  This technology is best suited for combined heat and power applications in small to medium sized commercial and industrial facilities.  Microturbines have compact packaging and low emissions, they make convenient and environmentally friendly standby and peaking generators. They are also used in some base load applications, have the ability to accept a wide variety and quality of fuels and are a convenient means to extract energy from bio- mass gas, flare gas, or natural gas that is not economical to transport to pipelines. 2/11/2021 18
  • 19.  A SMES device is a dc current device that stores energy in the magnetic field. The dc current flowing through a superconducting wire in a large magnet creates the magnetic field. Generally it consists of the superconducting coil, the cryogenic system, and the Power Conversion/Conditioning System (PCS) with control and protection functions Superconducting Magnetic Energy Storage 2/11/2021 19
  • 20. The total efficiency of a SMES system can be very high (about 90% or greater )since it does not require energy conversion from electrical to mechanical or chemical energy. Depending on the control loop of its power conversion unit and switching characteristics, the SMES system can respond very rapidly (MWs/milliseconds). The ability of injecting absorbing real or reactive power can increase the effectiveness of the control, and enhance system reliability and availability. 2/11/2021 20
  • 23.  Carbon Nanotubes, long, thin cylinders of carbon, were discovered in 1991 by Sumio Iijima.  These are large macromolecules that are unique for their size, shape, and remarkable physical properties.  They can be thought of as a sheet of graphite (a hexagonal lattice of carbon) rolled into a cylinder.  These intriguing structures have sparked much excitement in recent years and a large amount of research has been dedicated to their understanding.  Currently, the physical properties are still being discovered and disputed.  Nanotubes have a very broad range of electronic, thermal, and structural properties that change depending on the different kinds of nanotube (defined by its diameter, length, and chirality, or twist). To make things more interesting, besides having a single cylindrical wall (SWNTs), Nanotubes can have multiple walls (MWNTs)--cylinders inside the other cylinders. 2/11/2021 23
  • 24. Key properties of Carbon Nanotubes  Extraordinary electrical conductivity, heat conductivity, and mechanical properties.  They are probably the best electron field-emitter known, largely due to their high length-to- diameter ratios.  As pure carbon polymers, they can be manipulated using the well-known and the tremendously rich chemistry of that element. Key application areas • Field Emitters/Emission • Conductive or reinforced plastics • Molecular electronics: CNT based non volatile RAM • CNT based transistors • Energy Storage • CNT based fibers and fabrics • CNT based ceramics • Biomedical applications etc ... 2/11/2021 24
  • 25. Fuel Cell  A fuel cell is basically a battery powered by an electrochemical process based on the conversion of hydrogen. It produces dc voltage, and an inverter is required for interfacing to the ac power system.  A fuel cell is an electrochemical device that produces electricity without combustion by combining hydrogen and oxygen to produce water and heat.  The chief drawback to fuel cells at present is cost. Fuel cell technologies are on the order of 10 times more expensive than reciprocating gen sets. 2/11/2021 25
  • 26. Working Principle  A fuel cell is a device that uses hydrogen (or hydrogen-rich fuel) and oxygen to create electricity by an electrochemical process.  A single fuel cell consists of an electrolyte sandwiched between two thin electrodes (a porous anode and cathode) Hydrogen, or a hydrogen-rich fuel, is fed to the anode where a catalyst separates hydrogen's negatively charged electrons from positively charged ions (protons) .  At the cathode, oxygen combines with electrons and, in some cases, with species such as protons or water, resulting in water or hydroxide ions, respectively. 2/11/2021 26
  • 30.  Fuel Cell – Phosphoric Acid (PAFC) • PAFCs generate electricity at more than 40% efficiency • Operating temperatures are in the range of 300 to 400 degrees F (150 - 200 degrees C) • Existing PAFCs have outputs up to 200 kW, and 1 MW units have been tested • One of the main advantages to this type of fuel cell is that it can use impure hydrogen as fuel. PAFCs can tolerate a CO concentration of about 1.5 percent, which broadens the choice of fuels they can use. If gasoline is used, the sulfur must be removed. • PAFCs are the most mature fuel cell technology. 2/11/2021 30
  • 31. DG Technologies  Fuel Cell – Phosphoric Acid (PAFC) • Disadvantages of PAFCs include: it uses expensive platinum as a catalyst, it generates low current and power comparably to other types of fuel cells, and it generally has a large size and weight. 2/11/2021 31
  • 32. DG Technologies  Fuel Cell – Proton Exchange Membrane (PEM) • These cells operate at relatively low temperatures (about 175 degrees F or 80 degrees C), have high power density, can vary their output quickly to meet shifts in power demand, and are suited for applications, -- such as in automobiles -- where quick startup is required. • According to DOE, "they are the primary candidates for light- duty vehicles, for buildings, and potentially for much smaller applications such as replacements for rechargeable batteries. • This type of fuel cell is sensitive to fuel impurities. • Cell outputs generally range from 50 to 250 kW. 2/11/2021 32
  • 33. DG Technologies  Fuel Cell – Molten Carbonate (MCFC) • These fuel cells use a liquid solution of lithium, sodium and/or potassium carbonates, soaked in a matrix for an electrolyte. • They promise high fuel-to-electricity efficiencies, about 60% normally or 85% with cogeneration, and operate at about 1,200 degrees F or 650 degrees C. • To date, MCFCs have been operated on hydrogen, carbon monoxide, natural gas, propane, landfill gas, marine diesel, and simulated coal gasification products. • 10 kW to 2 MW MCFCs have been tested on a variety of fuels and are primarily targeted to electric utility applications. • A disadvantage to this, however, is that high temperatures enhance corrosion and the breakdown of cell components. 2/11/2021 33
  • 34. DG Technologies  Fuel Cell – Solid Oxide (SOFC) • This type could be used in big, high-power applications including industrial and large-scale central electricity generating stations. • Some developers also see SOFC use in motor vehicles and are developing fuel cell auxiliary power units (APUs) with SOFCs. • A solid oxide system usually uses a hard ceramic material of solid zirconium oxide and a small amount of ytrria, instead of a liquid electrolyte, allowing operating temperatures to reach 1,800 degrees F or 1000 degrees C. • Power generating efficiencies could reach 60% and 85% with cogeneration and cell output is up to 100 kW. 2/11/2021 34
  • 35. DG Technologies  Fuel Cell – Alkaline • Long used by NASA on space missions, these cells can achieve power generating efficiencies of up to 70 percent. They were used on the Apollo spacecraft to provide both electricity and drinking water. • Their operating temperature is 150 to 200 degrees C (about 300 to 400 degrees F). • They typically have a cell output from 300 watts to 5 kW. 2/11/2021 35
  • 36. DG Technologies  Fuel Cell – Direct Methanol Fuel Cells (DMFC) • These cells are similar to the PEM cells in that they both use a polymer membrane as the electrolyte. However, in the DMFC, the anode catalyst itself draws the hydrogen from the liquid methanol, eliminating the need for a fuel reformer. • Efficiencies of about 40% are expected with this type of fuel cell, which would typically operate at a temperature between 120-190 degrees F or 50 -100 degrees C. • This is a relatively low range, making this fuel cell attractive for tiny to mid-sized applications, to power cellular phones and laptops. 2/11/2021 36
  • 37. DG Technologies  Fuel Cell – Regenerative Fuel Cells • Still a very young member of the fuel cell family, regenerative fuel cells would be attractive as a closed-loop form of power generation. • Water is separated into hydrogen and oxygen by a solar- powered electrolyser. The hydrogen and oxygen are fed into the fuel cell which generates electricity, heat and water. The water is then recirculated back to the solar-powered electrolyser and the process begins again. • These types of fuel cells are currently being researched by NASA and others worldwide. 2/11/2021 37
  • 38. DG Technologies  Fuel Cell – Zinc-Air Fuel Cells (ZAFC) • In a typical zinc/air fuel cell, there is a gas diffusion electrode (GDE), a zinc anode separated by electrolyte, and some form of mechanical separators. • The GDE is a permeable membrane that allows atmospheric oxygen to pass through. After the oxygen has converted into hydroxyl ions and water, the hydroxyl ions will travel through an electrolyte, and reaches the zinc anode. Here, it reacts with the zinc, and forms zinc oxide. This process creates an electrical potential. 2/11/2021 38
  • 39. DG Technologies  Fuel Cell – Protonic Ceramic Fuel Cell (PCFC) • This new type of fuel cell is based on a ceramic electrolyte material that exhibits high protonic conductivity at elevated temperatures. • PCFCs share the thermal and kinetic advantages of high temperature operation at 700 degrees Celsius with molten carbonate and solid oxide fuel cells, while exhibiting all of the intrinsic benefits of proton conduction in polymer electrolyte and phosphoric acid fuel cells (PAFCs). • The high operating temperature is necessary to achieve very high electrical fuel efficiency with hydrocarbon fuels. PCFCs can operate at high temperatures and electrochemically oxidize fossil fuels directly to the anode. This eliminates the intermediate step of producing hydrogen through the costly reforming process. . 2/11/2021 39
  • 40. Wind Generation  Wind generation capacity has been increasing rapidly and has become cost competitive with other means of generation in some regions. A common implementation is to group a number of wind turbines ranging in size from 700 to 1200 kW each into a “wind farm” having a total maximum capacity range of 200 to 500 MW.  Large farms are interconnected to the transmission sys- tem rather than the distribution system. However, smaller farms of 6 to 8 MW have been proposed for applications such as ski resorts, and they would be connected directly to distribution feeders. 2/11/2021 40
  • 41.  The chief power quality issue associated with wind generation is voltage regulation.  There are three main classes of generator technologies used for the electrical system interface for wind turbines: 1. Conventional squirrel-cage induction machines or wound-rotor induction machines. These frequently are supplemented by switched capacitors to compensate for reactive power needs. 2. Doubly fed wound-rotor induction machines that employ power converters to control the rotor current to provide reactive power control. 3. Non–power frequency generation that requires an inverter interface. 2/11/2021 41
  • 42. Photovoltaic  The recent power shortages in some states and the passage of net metering legislation has spurred the installation of rooftop photo- voltaic solar systems. 2/11/2021 42
  • 43.  A typical size for a residential unit would be between 2 and 6 kW. Once installed, the incremental cost of electricity is very low with the source of energy being essentially free while it is available.  However, the first cost is very substantial even with buy- down incentives from government programs. Installed costs currently range from $5000 to $20,000/kW.  Despite this high cost, photovoltaic solar technology is favoured by many environmentalists and installed capacity can be expected to continue growing.  Photovoltaic solar systems generate dc power while the sun is shining on them and are interfaced to the utility system through inverters. Some systems do not have the capability to operate stand-alone the inverters operate only in the utility-interactive mode and require the presence of the grid. 2/11/2021 43
  • 44. 5.3. Interface to the Utility System  The impact of DG on the distribution system power quality. Some notable exceptions include: 1. The power variation from renewable sources such as wind and solar can cause voltage fluctuations. 2. Some fuel cells and micro turbines do not follow step changes in load well and must be supplemented with battery or flywheel storage to achieve the improved reliability expected from standby power applications. 3. Misfiring of reciprocating engines can lead to a persistent and irritating type of flicker, particularly if it is magnified by the response of the power system. 2/11/2021 44
  • 45. Synchronous Machine Asynchronous Machine Electronic Power Inverters The main types of electrical system interfaces are 2/11/2021 45
  • 46. Synchronous Machine  They applied in grid parallel DG applications. They are the primary type of electric machine used in backup generation applications.  With proper field and governor control, the machine can follow any load within its design capability and inertia allows it to be tolerant of step-load changes so this is good for backup power.  This technology can easily sustain inadvertent islands that could occur when the utility feeder breaker opens. It also can feed faults and possibly interfere with utility overcurrent protection.  Inter connected synchronous generators on distribution systems are usually operated with a constant power factor or constant var exciter control. 2/11/2021 46
  • 47. 1. Small DG does not have sufficient capacity to regulate the voltage while interconnected. 2. This avoids having the voltage controls of several small machines competing with each other and the utility voltage regulation scheme. 3. This is done is to reduce the chances that an inadvertent island will be sustained.  Synchronous machine that is large relative to the capacity of the system at the PCC to regulate the utility system voltage.  The subtransient reactance Xd″, which is seen by harmonics, is often about 15 percent of the machine’s rating. The transient reactance, Xd′, which governs much of the fault contribution, might be around 25 per- cent. 2/11/2021 47
  • 48. Asynchronous Machine  Simple to interface  Induction generators are induction motors that are driven slightly faster than synchronous speed. They require another source to provide excitation, which greatly reduces the chances of inadvertent islanding. No special synchronizing equipment is necessary. In fact, if the capacity of the electrical power system permits, induction generators can be started across the line. For weaker systems, the prime mover is started and brought to near-synchronous speed before the machine is interconnected. 2/11/2021 48
  • 49.  Induction generator requires reactive power (vars) to excite the machine from the power system to which it is connected.  This is an advantage when there are high- voltage problems, but more commonly there will be low-voltage problems in induction generator applications. The usual fix is to add power factor correction capacitors to supply the reactive power locally.  One of the problems is that the capacitor bank will yield resonances that coincide with harmonics produced in the same facility. 2/11/2021 49
  • 50. 2/11/2021 50 ♠ Another issue is self-excitation. An induction generator that is suddenly isolated on a capacitor bank can continue to generate for some period of time. This is an unregulated voltage and will likely deviate outside the normal range quickly and be detected. ♠ This situation can often result in a Ferro resonant condition with damaging voltages. ♠ The current contribution into a fault from an induction machine dying out in 1.5 cycles.
  • 51. Electronic Power Inverters  All DG technologies that generate either dc or non–power frequency ac must use an electronic power inverter to interface with the electrical power system.  Line-commutated inverters quickly developed a reputation for being undesirable on the power system. These inverters produced harmonic currents in similar proportion to loads with traditional thyristor-based converters. @ Contributing to the distortion on the feeders @ little more than heat up wires 2/11/2021 51
  • 52. 2/11/2021 52 ♠ To achieve better control and to avoid harmonics problems, the inverter technology has changed to switched, pulse-width modulated technologies. ♠ Below Figure shows the basic components of a utility interactive inverter that meets the requirements of IEEE Standard 929-2000.
  • 53. 2/11/2021 53 ʚ Direct current is supplied on the left side of the diagram either from a conversion technology that produces direct current directly or from the rectification of ac generator output. Variations of this type of inverter are commonly employed on fuel cells, micro turbines, photovoltaic solar systems, and some wind turbines. ʚ DC voltage is switched at a very high rate with IGBT switch to create a sinusoid voltage or current of power frequency, switching frequency is 50 to 100 times the power frequency. ʚ The filter on the output attenuates these high-frequency components to a degree. The total harmonic distortion limit is 5%, based on the requirements of IEEE Standard 519-1992, will exceed these limits may skimp on filtering, or there may be a flaw in the switch control algorithm.
  • 54. 2/11/2021 54 ¥ While interconnected to the utility, commonly applied inverters basically attempt to generate a sine-wave current that follows the voltage waveform, would produce power at unity power factor. ¥ It is possible to program other strategies into the switching control. ¥ If the inverter has stand-alone capability, the control objective would change to producing a sinusoidal voltage waveform at power frequency and the current would follow the load. Advantages of an inverter for DG applications:  Switched off very quickly when trouble is detected.  Inverters typically exhibit very little inertia and changes can take place in milliseconds. Rotating machines may require several cycles to respond.
  • 55. 5.4. Power Quality Issues  Sustained Interruptions  Voltage Regulation  Voltage Ride Through  Harmonics  Voltage Sags  Load Following  Power Variation  Misfiring of Reciprocating Engines 2/11/2021 55
  • 56. 2/11/2021 56  Much of the DG that is already in place was installed as backup generation.  The most common technology used for backup generation is diesel gen-sets.  The bulk of the capacity of this form of DG can be realized simply by transferring the load to the backup system.  However, there will be additional power that can be extracted by paralleling with the power system. Many DG installations will operate with better power quality while paralleled with the utility system because of its large capacity.  Not all DG technologies are capable of significant improvements in reliability. To achieve improvement, the DG must be capable of serving the load when the utility system cannot. Sustained Interruptions:
  • 57. 2/11/2021 57  For example, a homeowner may install a rooftop photovoltaic solar system with the expectation of being able to ride through rotating blackouts. Unfortunately, the less costly systems do not have the proper inverter and storage capacity to operate stand-alone. Therefore, there is no improvement in reliability  Utilities may achieve improved reliability by employing DG to cover contingencies when part of the delivery system is out of service. In this case, the DG does not serve all the load, but only enough to cover for the capacity that is out of service. This can allow deferral of major construction expenses for a few years. The downside is that reliance on this scheme for too many years can ultimately lead to worse reliability. The load growth will overtake the base capacity of the system, requiring load shedding during peak load conditions or resulting in the inability to operate the system at acceptable voltage after a fault.
  • 58. 2/11/2021 58 Voltage Regulation  It may initially seem that DG should be able to improve the voltage regulation on a feeder. Generator controls are much faster and smoother than conventional tap- changing transformers and switched capacitor banks.  However, there are many problems associated with voltage regulation. In cases where the DG is located relatively far from the substation for the size of DG, voltage regulation issues are often the most limiting for being able to accommodate the DG without changes to the utility system.  Some technologies are unsuitable for regulating voltages. This is the case for simple induction machines and for most utility interactive inverters that produce no reactive power. Secondly, most utilities do not want the DG to attempt to regulate the voltage because that would interfere with utility voltage regulation equipment and increase the chances of supporting an island.
  • 59. 2/11/2021 59  Small DG is simply not powerful enough to regulate the voltage and will be dominated by the daily voltage changes on the utility system. Small DG is almost universally required to interconnect with a fixed power factor or fixed reactive power control.  Large DG greater than 30 percent of the feeder capacity that is set to regulate the voltage will often require special communications and control to work properly with the utility voltage-regulating equipment.  DG will take over the voltage-regulating duties and drive the substation load tap changer (LTC) into a significant bucking position as the load cycles up and down. This results in a problem when the DG suddenly disconnects, as it would for a fault. The voltage is then too low to support the load and takes a minute or more to recover. One solution is to establish a control scheme that locks the LTC at a preselected tap when the generator is operating and interconnected.
  • 60. 2/11/2021 60 Harmonics  Associate DG with bad experiences with harmonics from electronic power converters. If thyristor-based, line-commutated inverters were still the norm, this would be a large problem.  Technologies requiring inverters have adopted the switching inverters, this has eliminated the bulk of the harmonics problems.  One problem arises when a switching inverter is installed in a system that is resonant at frequencies produced by the switching process. High-frequency hash appearing on the voltage waveform.  This problem is generally solved by adding a capacitor to the bus that is of sufficient size to shunt off the high-frequency components without causing additional resonances.
  • 61. 2/11/2021 61  Harmonics from rotating machines are not always negligible, particularly in grid parallel operation. The utility power system acts as a short circuit to zero-sequence triplen harmonics in the voltage, which can result in surprisingly high currents. For grounded wye-wye or delta-wye service transformers, only synchronous machines with 2/3 pitch can be paralleled without special provisions to limit neutral current.  For service transformer connections with a delta-connected winding on the DG side, nearly any type of three-phase alternator can be paralleled without this harmonic problem.
  • 62. 2/11/2021 62 Voltage Sags  The most common power quality problem is a voltage sag, but the ability of DG to help alleviate sags is very dependent on the type of generation technology and the interconnection location.  DG is interconnected on the load side of the service transformer. During a voltage sag, DG might act to counter the sag. Large rotating machines can help support the voltage magnitudes and phase relationships.
  • 64. 2/11/2021 64  The DG influence on sags at its own load bus is aided by the impedance of the service transformer, which provides some isolation from the source of the sag on the utility system.  However, this impedance hinders the ability of the DG to provide any relief to other loads on the same feeder. DG larger than 1 MW will often be required to have its own service transformer. The point of common coupling with any load is the primary distribution system. Therefore, it is not likely that DG connected in this manner will have any impact on the voltage sag characteristic seen by other loads served from the feeder.
  • 65. 5.4. Operating Conflicts  Deploying generation along utility distribution systems naturally creates some conflicts because the design of the system assumes only one source of power. A certain amount of generation can be accommodated without making any changes. At some point, the conflicts will be too great and changes must be made. 2/11/2021 65
  • 66. 5.4. Operating Conflicts  Utility Fault-Clearing Requirements 2/11/2021 66
  • 67. 2/11/2021 67 Figure shows the key components of the overcurrent protection system of a radial feeder. ♠ The lowest-level component is the lateral fuse, and the other devices (reclosers and breakers) are designed to conform to the fuse characteristic. ♠ There will frequently be two to four feeders off the same substation bus. This design is based mostly on economic concerns. This is the least costly protection scheme that is able to achieve acceptable reliability for distributing the power. ♠ One essential characteristic is that only one device has to operate to clear and isolate a short circuit, and local intelligence can accomplish the task satisfactorily. ♠ In contrast, faults on the transmission system, which easily handles generation, usually require at least two breakers to operate and local intelligence is insufficient in some cases.
  • 68. 2/11/2021 68 ♠ With only one utility device operating to clear a fault, all other DG devices must independently detect the fault and separate to allow the utility protection system to complete the clearing and isolation process. ♠ This is not always simple to do from the information that can be sensed at the generator.
  • 69.  Reclosing  Most of the distribution lines are overhead, and it is common to have temporary faults. Once the current is interrupted and the arc dispersed, the line insulation is restored. Reclosing enables the power to be restored to most of the customers within seconds. Reclosing presents two special problems with respect to DG: 1. DG must disconnect early in the reclose interval to allow time for the arc to dissipate so that the reclose will be successful. 2. Reclosing on DG, particularly those systems using rotating machine technologies, can cause damage to the generator or prime mover. 2/11/2021 69
  • 70. ♠ Figure illustrates the reclose interval between the first two operations of the utility breaker (this represents an unsuccessful reclose because the fault is still present). ♠ The DG relaying must be able to detect the presence of the fault followed by the opening of the utility fault interrupter so that it can disconnect early in the reclose interval as shown. ♠ Detection and disconnection process should be straightforward. However, some transformer connections make it difficult to detect certain faults, which could delay disconnection. 2/11/2021 70
  • 71. 2/11/2021 71  A reclose interval of at least 1.0 s is safer when there is DG on the feeder. Many utilities use 2.0 or 5.0 s for the first reclose interval when DG is installed.  This minimizes the risk that the DG will not disconnect in time. If it is deemed necessary to maintain the instantaneous reclose, it is generally necessary to employ direct transfer trip so that the DG breaker is tripped simultaneously with the utility breaker.  This can be a very expensive proposition for smaller DG installations. Thus, for some distribution systems it will be necessary to compromise one aspect of power quality to better accommodate significant amounts of DG.
  • 72.  Interference With Relay Three of the more common cases where DG can interfere with the over- current protection relaying on distribution feeders will be 1. Reduction of reach 2. Sympathetic tripping of feeder breakers 3. Defeat of fuse saving 2/11/2021 72
  • 73. 2/11/2021 73 1. Reduction of reach Figure illustrates the reduction-of-reach concept. Each over- current relay device has an assigned zone of protection that is determined by its minimum pickup value. Some refer to this generically as the “reach” of the relay. DG infeed can reduce the current that the relay sees, thereby shortening its reach. When the total DG capacity increases to a certain amount, the infeed into faults can desensitize the relays and leave remote sections of the feeder unprotected.
  • 74. 2/11/2021 74 A low-current (high-impedance) fault near the end of the feeder is more likely to go undetected until it does sufficient damage to develop into a major fault. The power quality consequences of this are that voltage sags will be prolonged for some customers and the additional fault damage will eventually lead to more sustained interruptions. This issue can be a particular problem for peaking generation located near the end of the feeder. This generation is on at peak load level where the overcurrent relaying would normally be very sensitive to a high-impedance fault. The DG infeed has the potential to mask many faults that would otherwise be detected.
  • 75. 2/11/2021 75 Solutions include: 1. Decrease the relay minimum pickup current to increase the zone. This may not be practical for ground relays that are already set to a very sensitive level. 2. Add a line recloser to create another protection zone that extends far past the end of the feeder. 3. Use a transformer connection that minimizes DG contribution to ground faults, since high-impedance faults are likely to be ground faults.
  • 76.  Interference With Relay – Sympathetic Tripping of Feeder Breaker  It describes the condition where a breaker that does not detect the fault current trips in sympathy with the breaker that did. The common circuit condition on utility distribution feeders is back feed into a ground fault.(shown in fig.) 2/11/2021 76  Most utility feeder breakers don’t have directional sensing. Thus because of this ground relay detects the DG contribution as a fault and trips the circuit breaker unnecessarily.  Solution is using directional overcurrent relaying but this is very expensive, if appropriate P T/Fs are not present.
  • 77.  Interference With Relay – Defeat of Fuse Saving 2/11/2021 77  Fuse-saving action is a “horse race” in the best of circumstances. It is a challenge for the mechanical recloser to detect the fault and operate fast enough to prevent damage to the fuse element. DG infeed adds to the current in the fuse and makes this race even tighter. At some amount of DG capacity that is capable of feeding the fault, it will no longer be possible to save the fuse.  This phenomenon limits the amount of synchronous machine DG that can be accommodated without making changes to the system. Fuse-saving coordination fails for about the same level of generation that causes voltage regulation problems.
  • 78. 2/11/2021 78 Solutions include: 1. Increase the size of the lateral fuses. All fused cutouts in the zone would have to be changed, which could be quite expensive. 2. Choose to simply abandon fuse saving, particularly if the DG is only connected intermittently. 3. Require DG to have transformer connections that do not feed single- line-to-ground faults.
  • 79.  Voltage Regulation Issues 2/11/2021 79 Concern for various dynamics and transients issues that are difficult to analyze, voltage regulation issues are more likely to occur and cause interconnection problems. Figure shows the voltage profile along the feeder prior to the fault occurring. The intent of the voltage regulation scheme is to keep the voltage magnitude between the two limits shown. In this case, the DG helps keep the voltage above the minimum and, in fact, is large enough to give a slight voltage rise toward the end of the feeder.
  • 80. 2/11/2021 80 When the fault occurs, the DG disconnects and may remain disconnected for up to 5 min. The breaker recloses within a few seconds, resulting in the condition shown in Fig. The load is now too great for the feeder and the present settings of the voltage regulation devices. The voltage at the end of the feeder below the minimum and will remain low until voltage regulation equipment can react. This can be the better part of a minute or longer, which increases the risk of damage to load equipment due to excessively low voltages.
  • 81. 2/11/2021 81 It also suggests one test an analyst can perform to determine if a pro- posed DG application will likely require changes on the utility system. The test would be to compute the voltage change that occurs at peak load if the DG suddenly disconnects. This change should be less than about 5 percent unless there is fast-acting voltage regulation equip- ment that can compensate for a larger change.
  • 82. 2/11/2021 82 The amount of generation that can be accommodated by this test will obviously vary with position on the feeder. One useful analysis is to determine how much DG capacity can be accommodated (without change) at various distances along the feeder. For example, if one were to establish a 5 percent change criterion for the limit, there would be a curve of generation limit versus distance similar to that shown in Fig.
  • 83. 2/11/2021 83 solutions include: 1. Requiring customer load to disconnect with the DG. This may not be practical for widespread residential and small commercial loads. Also, it is difficult to make this transition seamlessly and the load may suffer downtime anyway, negating positive reliability benefits of DG. 2. Installing more voltage regulators, each with the ability to bypass the normal time delay of 30 to 45 s and begin changing taps immediately. This will minimize the inconvenience to other customers. 3. Allow DG to reconnect more quickly than the standard 5-min dis- connect time. This would be done more safely by using direct communications between the DG and utility system control. 4. Limit the amount of DG on the feeder.
  • 84. Operating Conflicts  Excess DG Can Fool Reverse Power Setting on Line Voltage Regulator 2/11/2021 84 Another voltage regulation issue involving step-voltage regulators
  • 85. 2/11/2021 85 Utility voltage regulators commonly come with a reverse-power feature that allows the regulators to be used when a feeder is supplied from its alternate source. The logic is that when the net power through the regulator is in the reverse direction, the regulator control switches direction and regulates the original source terminal so that the regulator can work properly. Otherwise, the control will attempt to regulate the alternate source side, which would not be possible. The tap position would generally move to one extreme or the other and stay there.
  • 86. Operating Conflicts  Varying DG Output can Cause Excess Duty on Utility Voltage Regulation Equipment 2/11/2021 86
  • 87. 2/11/2021 87 Generation technologies whose output varies rapidly can be difficult to handle on a distribution feeder. Wind- turbine generation is the most difficult because there is seldom a substation near the proposed site. The generation is typically sited several miles from the nearest sub- station on a feeder that already may have several switched capacitors and a voltage regulator.  One solution is to increase the bandwidth on the controls  While the magnitude variation in this case exceeded 2 percent, it is not changing fast enough to likely cause volt- age fluctuation complaints.  When the fluctuation is too great, the main recourse is to build a sep- arate feeder for the wind generation. Also, some wind generators employ doubly fed wound-rotor induction machines that can control reactive power very quickly. With proper control, this can help tame the voltage fluctuations.
  • 88. Operating Conflicts Harmonics  Harmonics from DG come from inverters and some synchronous machines.  The PWM switching inverters produce a much lower harmonic current content than earlier line-commutated, thyristor-based inverters.  In IEEE Standard 519-1992, generators are limited to the most restrictive values in the tables on the allowable amount of harmonic current injection. 2/11/2021 88
  • 89. 2/11/2021 89 One new distortion problem that arises with the modern inverters is that the switching frequencies will occasionally excite resonances in the primary distribution system. This creates nonharmonic frequency signals typically at the 35th harmonic and higher riding on the voltage waveform. This has an impact on clocks and other circuitry that depend on a clean voltage zero crossing.
  • 91. 2/11/2021 91 Harmonics problems related to zero-sequence triplen harmonics shown in fig. The facility where the generator is located is served at 480 V by a common delta-wye transformer. When the generator is paralleled to the utility system through this transformer, the operator is frequently surprised to find a large amount of current circulating in the neutral. In the example shown, the current is 26 percent of the machine’s rated current and is entirely third-harmonic current. This can adversely affect the operation and efficiency of the machine and may result in the failure of some circuit element. In this case, the problem is confined to the generator side of the transformer and does not affect the primary distribution system because the triplen harmonics are trapped by the delta winding.
  • 92. Operating Conflicts Islanding Main Utility Grid DG 2/11/2021 92 DG protective relays will generally perform their function independently of any outside knowledge of the system to which they are connected.
  • 93. 2/11/2021 93 Perhaps the greatest fear of the utility protection engineer is that DG relaying will fail to detect the fact that the utility breaker has opened and will continue to energize a portion of the feeder. Attention has been paid to detecting islands or forcing islands to become unstable so they can be detected. Another concern is the DG itself. Since reclosing is common, it is essential that the DG detect the island promptly and disconnect. If it is still connected when the utility breaker recloses, damage can occur to prime movers, shafts, and components of machines due to the shock from out-of-phase reclosing.
  • 94. Operating Conflicts Ferroresonance  Ferroresonance is a special kind of resonance in which the inductive element is the nonlinear characteristic of an iron-core device.  Ferroresonance occurs when the magnetizing reactance of a transformer inadvertently is in series with cable or power factor capacitance.  One interesting case occurs for DG served by cable-fed transformers. It is common practice for the larger DG installations to have their own transformer. Also, it is nearly universal to require DG to disconnect at the first sign of trouble on the utility system. This combination of requirements can lead to a common ferroresonant condition. 2/11/2021 94
  • 95. 2/11/2021 95 The circuit is shown in Fig. 9.21. Underground cable runs are normally fused at the point where they are tapped off the overhead feeder line. This is variously called the riser pole or dip pole. Should some- thing happen that causes one or two fuses to blow, the relaying on the DG will detect an unbalanced condition and trip the generator breaker. This leaves the transformer isolated on the cable with one or two open phases and no load. Either condition is conducive to ferroresonance because the cable capacitance in an open phase, or phases, now appears in series with the transformer’s magnetizing impedance (Fig. 9.22).
  • 97. 2/11/2021 97 The type of ferroresonance shown in Fig. 9.23 is very sensitive to the amount of load. If the system can be arranged so that there is always a resistive load attached to the secondary bus, the resonance can be damped out. The load need not always be large, but must be significant.
  • 98. Operating Conflicts  Shunt Capacitor Interaction (Overvoltage due to capacitor) 2/11/2021 98
  • 99. 2/11/2021 99 Utilities use switched capacitors to help support the voltage during high-load periods. These banks are mostly controlled by local intelligence, switching at predetermined times or at loading levels as measured by either voltage, current, or kvar. Some types of DG can also produce reactive power (vars), and this can create control hunting and other difficulties. The capacitors switch independently of the generator control unless special communications and control have been added to coordinate dispatch. A 2 to 3 percent increase in the voltage is common when a typical capacitor bank is energized. Generators in parallel operation are generally maintaining a constant power and power factor. The reactive power of the machine is con- trolled by the exciter field, which will have certain minimum and maximum voltage or field excitation limits as indicated on the diagram. The generator control attempts to maintain a constant reactive power output until it bumps up against one of these limits.
  • 100. 2/11/2021 100 when capacitors are switched by time clock or by current magnitude (without voltage override). There are at least three things that can happen at this point to trip the generator: 1. The generator control senses overvoltage at its terminals and attempts to back down the field to compensate. However, the utility system overpowers the generator and the field reduces to a level deemed to be too low for safe operation of the machine. 2. When the generator reaches its voltage limit, reactive power flows back into the machine. When it reaches a certain level, the generator protection interprets this as a malfunction. 3. DG that does not produce reactive power simply trips on overvoltage.
  • 101. Operating Conflicts  Transformer Connections – Grounded Y-Y Connection It is favoured because of its reduced susceptibility to ferro resonance on cable-fed loads and fewer operating restrictions when being switched for maintenance. It is also generally well behaved with respect to DG interconnection, but there are a couple of issues. Advantages include: • No Phase Shift • Less Concern for Ferroresonance Disadvantages include: • Allow DG to Feed All Types of Faults on the Utility System • Back Feed of the Triplen Harmonic • Should Insert Ground Impedance to Limit the Current 2/11/2021 101
  • 102. Operating Conflicts  Transformer Connections – D-Y Connection 2/11/2021 102
  • 103. 2/11/2021 103 It would probably be favoured for serving loads in nearly all cases if it were not for the susceptibility of the connection to ferro resonance in cable-fed systems. Advantages include: ■ There is less infeed into utility-side ground faults. ■ Third harmonics from the DG do not reach the utility system. ■ Some isolation from voltage sags due to utility-side SLG faults is provided. Disadvantages include: ■ It is difficult to detect some SLG faults from the secondary side by voltage relaying alone.
  • 104. 2/11/2021 104 It is susceptible to ferro resonance in cable-fed installations. ■ Third harmonics in the DG may cause excessive current in the secondary-side neutral. ■ If islanded on an SLG fault, utility arresters can be subjected to over voltages ■ If arresters are islanded on an SLG fault and there is little load, resonant over voltages can result
  • 105. Operating Conflicts  Transformer Connection – Delta-Delta Connection 2/11/2021 105
  • 106. 2/11/2021 106 While not in the majority, these connections are still common for commercial and industrial loads. Both have similar behaviour with respect to serving DG. Neither would be the preferred connection for serving most new DG installations, but could be encountered in legacy systems where a customer wishes to parallel DG. Some inverter-based systems (fuel cells, photovoltaics, microturbines, etc.) require an ungrounded connection on the DG side because the dc side of the inverter is grounded. This is often accomplished by use of a separate isolation transformer rather than the main service transformer.
  • 107. 2/11/2021 107 Advantages include: ■ More economical transformer installation for smaller three-phase service with some single-phase loads is possible. ■ The load is isolated from ground faults on the utility side. ■ DG would not typically feed utility-side ground faults except when resonance occurs. ■ Ungrounded interconnection can be provided for inverter-based systems requiring it. Disadvantages include: ■ Utility-side SLG faults are difficult to detect. ■ Utility arresters are subjected to high steady-state over voltages if islanded on an SLG fault (see Fig. 9.26). This is true for delta- wye connections as well.
  • 108. Operating Conflicts  Transformer Connection – Grounded Y-D Connection 2/11/2021 108
  • 109. 2/11/2021 109 This is an interesting connection because of the conflicting application considerations. Many utility engineers believe this is the best winding connection for interconnecting generation to the utility system. This is the connection used for nearly all central station generation. There are many advantages, including: 1. Utility-side faults are easily detected partly because the transformer itself actively participates in ground faults. 2. Triplen harmonic voltages produced by the generator do not cause any current to flow because it is blocked by the delta winding. Therefore, nearly any generator can be paralleled with this connection. 3. Protection schemes are well understood based on many years of experience with utility generation.
  • 110. 2/11/2021 110 5.5. DG on Low-Voltage Distribution Networks Focus on DG interconnected to radial primary or secondary distribution circuits, which is the most common distribution configuration. However, in large cities a number of utilities use a low-voltage network method of distribution. These low-voltage network systems are of two major subtypes, the secondary network (also referred to as an area network, grid network, or street network) and the spot network.
  • 111. 2/11/2021 111 Secondary networks serve numerous sites, usually several city blocks, from a grid of low-voltage mains at 120/208 V, three-phase. Spot networks serve a single site, usually a large building or even a portion of a large building. The secondary voltage of spot networks is often 277/480 V, three-phase, but 120/208-V spot networks are also used. Street networks and spot networks are supplied from two or more primary distribution feeders through integrated transformer / breaker / protection combinations called network units. These network units are often located in transformer vaults within the building or in under- ground vaults in the street.
  • 112. 2/11/2021 112 Figure 9.28 shows a spot network arrangement with three primary feeders. The primary feeders may be dedicated to the spot network, may serve other network units at different sites, or may serve ordinary radial distribution loads as well. The objective of the network distribution design is to achieve high service reliability with high power quality. To accomplish this, the primary feeders are often chosen so that they originate at different substations or, at least at different bus sections of the same substation. The high power quality is achieved by having full service capability with any feeder out of service and rapidly removing any faulted feeder from connection to the low-voltage network.
  • 114. DG on Low-Voltage Distribution Networks  Spot Network Arrangement Underground Network NPR NPR NPR NPR NPR NPR NPR 2/11/2021 114
  • 115. DG on Low-Voltage Distribution Networks  Arrangement of Network Protector Relay Source Network Transformer Network Protector Network 2/11/2021 115
  • 116. 2/11/2021 116 Fundamentals of network operation We will concentrate on the spot network. In normal operation, the spot network is supplied simultaneously from all the primary feeders, by paralleling the low-voltage secondaries of the network transformers on the spot network bus. In order that the spot network can continue to operate if a primary feeder becomes faulted, the network units are each equipped with a low-voltage circuit breaker, called the network protector, and a directional-power relay called the network relay or master relay.
  • 117. 2/11/2021 117 When a primary feeder is faulted, the network relay senses reverse power flow (from the network toward the primary feeder) and opens the network protector, thereby isolating the network bus from the faulted feeder and allowing service on the network to continue without interruption. This function is the reason for the name network protector and the reason why DG interconnection to networks becomes a complex issue. Figure 9.29 shows the operation of a network protector in isolating a faulted primary feeder. Later, when the faulted primary feeder is repaired and returned to service, the network relay senses voltage at the transformer side of the open network protector.
  • 118. 2/11/2021 118 Figure 9.29 Network primary feeder fault.
  • 119. 2/11/2021 119 If this voltage is such that power will flow from the network unit to the bus when the protector is closed, the network relay commands the protector switch to reclose. Determining when this reclose will take place may become an interconnection issue. The network relay is a very sensitive reverse-power relay, with a pickup level on the order of 0.1 percent of the rated power of the network transformer. These settings can be as low as 1 to 2 kW. It is the mission of the reverse-power relay to be capable of sensing reverse power flow with no other feeder loads than the core losses of its own network transformer. This great sensitivity is necessary because the network protector must operate for all types of faults on the primary feeder, including ground faults.
  • 120. 2/11/2021 120 A delta-connected primary is commonly used on network transformers, no ground fault current will flow from the network toward the primary feeder once the source sub- station feeder circuit breaker has opened. Thus the network relay must be capable of sensing reverse power using only its own transformer’s losses. This sensitive reverse-power function means that no DG can be connected to the network with the intent to export power to the utility system. It further means that even momentary power reversals under abnormal conditions must be considered in the interconnection design.
  • 121. 2/11/2021 121 The traditional network relay is an electromechanical device and has no intentional time delay. The typical operating time is about 0.05 s (3 cycles) at normal voltage levels, thus the reason that even momentary power reversals caused by the DG are of concern. Microprocessor based network relays have replaced the electromechanical types in new network units, and these relays can be retrofitted into many types of existing network units. The basic performance of the microprocessor types is similar to the electro mechanicals, but they have more flexibility and new features.
  • 122. DG on Low-Voltage Distribution Networks  A Microcomputer Based Network Protector Relay 2/11/2021 122
  • 123. DG on Low-Voltage Distribution Networks  Operation of A Microcomputer Based Network Protector Relay – Network protector relays are used to monitor and control the power flow of low voltage AC to secondary network systems. – The purpose of the network protector is to prevent the system from back feeding and initiate automatic reclosing when the system returns to normal. 2/11/2021 123
  • 124. DG on Low-Voltage Distribution Networks  Tripping Characteristics of A Microcomputer Based Network Protector Relay 0 o 90 o 270 o 180 o Tripping Region Non-Tripping Region Non-Tripping Region Tripping Region Network Phase Voltage (Unity PF) Current into Network Current into Network (Lagging PF) (Unity PF) Current out of Network Fault Current Max. Torque 2/11/2021 124
  • 125.  Reclosing Characteristics of A Microcomputer Based Network Protector Relay 0o 1V 2V 3V 4V 5V 6V 7V 8V Phase Relay Characteristic Master Relay Characteristic Offset Voltage Phase Relay Reclosed Region 2/11/2021 125
  • 126. 2/11/2021 126 The network protector is an air circuit breaker specifically designed for the fault current conditions encountered on low-voltage network systems. It operates only under the control of the network relay. The network protector has no overcurrent protection and does not open for faults on the low-voltage secondary system. Low-voltage faults are cleared by fuses or by circuit breakers within the served facility
  • 127.  Fault Current Contribution From Synchronous Local DG 2/11/2021 127 The fault current delivery from synchronous DG to external faults can cause network protectors to open, potentially isolating the network. Above Figure shows an example of how this can happen.
  • 128.  Inverter Based DG on a Spot Network (Possible Solution) 2/11/2021 128
  • 129. 2/11/2021 129 Despite this daunting list of problems, there are some ways that DG may be accommodated on spot networks, by taking advantage of new technology. Inverter-based DG has the advantages that fault current is very limited, to about 100 to 200 percent of the normal inverter load current, and that an inverter can respond very rapidly to signals con- trolling its power output level. Because the most critical aspect of DG on networks is that the local generation must never exceed the local load, this example uses a tie- line load control scheme that senses the total incoming power to the facility and adjusts the DG power output to ensure that power flow is always inward.
  • 130. 2/11/2021 130 Other approaches that might be used are ■ Size the DG to be less than the minimum load that ever exists on the network, with a margin for sudden loss of a large load. ■ Total the incoming power to the network and trip the DG whenever the inward power flow falls below a safe value.
  • 131. DG on Low-Voltage Distribution Networks  Adjustable Reverse Power Characteristics 2/11/2021 131
  • 132. Blame nobody Expect nothing Do something YOURSELF