ACEEE Int. J. on Electrical and Power Engineering, Vol. 02, No. 01, Feb 2011



       Simulation Studies of Shunt Passive Harmonic
       Filters: Six Pulse Rectifier Load – Power Factor
             Improvement and Harmonic Control
                                Seema P. Diwan, Dr. H. P. Inamdar, and Dr. A. P. Vaidya
                           Walchand College of Engineering, Electrical Department, Sangli, India
                                           Email: seemapdiwan@gmail.com


Abstract— This paper presents a study of harmonic filters              Most distribution systems require reactive power
design procedure to minimize harmonic distortion caused by a           compensation to improve the power factor, save demand
harmonic source such as drives. The non – linear load                  charges, or to release additional active power from existing
considered in this paper is six pulse rectifier load. Design and       equipment or for voltage support, i.e., the reactive power
simulation procedure with respect to this load is explained in
                                                                       support required to arrest the voltage drop on loss of a plant
details. Several types of shunt harmonic filters are presented.
Shunt filters are effective in minimizing voltage distortion           generator. The nonlinear loads are increasing, i.e., pulp and
caused by nonlinear loads in industrial power systems. Different       paper mill distribution systems invariably have adjustable-
alternatives of filter design should be considered before making       speed drive(ASD) systems [2], which may form a
the final decision on filter configuration. Among the criteria         considerable percentage of overall plant load. When power
used for performance evaluation are current, and voltage               capacitors are used for reactive power compensation, it
ratings of each of the filter components. The design and               becomes necessary to turn them in to filters to escape
performance of single-tuned and high-pass filters and the              harmonic resonance problems with one of the load-generated
methodology used for the analysis will be discussed.                   harmonics It is not uncommon to apply passive filters in the
    The major objectives in this study are to use shunt passive        megavar range and filters totaling some tens of megavars in
filters for following -(i) to improve the power factor, (ii) to
                                                                       a large installation may be required.The main contribution
reduce current and voltage distortion to standard limits, and
(iii) to reduce resonance problems, if any.                            of this paper is to presents an analysis and simulation of
                                                                       application of shunt harmonic filters. The study procedure
Index Terms— Harmonics, passive shunt filters, single tuned            adopted in this paper is outlined as follows:
filter, high pass filter, filter rating.                                1.      Problem definition and Simulation of a system with
                                                                                non linear loads.
                     I.INTRODUCTION
                                                                        2.      Design of Shunt Passive Filter(s) to provide reactive
          In an ideal power system, electrical energy is                        power compensation and minimize TDD at PCC.

supplied at a constant frequency and at a specified voltage             3.      Study different aspects of design of shunt passive
level of constant magnitude with sinusoidal wave shape.                         filter i.e. capacitor bank current and voltage loading,
However, in practice, none of these conditions is fulfilled to                  outage conditions of filters and resonance etc.
the fullest extent, due to the presence of voltage and current          4.      Comparison of analytical solution of the filter
harmonics of multiple orders. These harmonics may be                            design and results obtained from the simulation.
caused by nonlinear loads like controlled rectifiers and
inverters, luminous discharge lighting, magnetizing current                            II.SINGLE TUNED FILTER
drawn by transformers or phase belt, chording, skewing,
slotting and air gap irregularities in a rotating electrical              The most common type of shunt passive filters used in
machine [1]. The harmonics present in the electrical source             harmonic mitigation is the single tuned filter (STF) which
cause many ill-effects such as reduction in power generation,          is either a low pass or band pass filter. This type of filter is
transmission and utilization efficiency, resonance effects,              simplest to design and the least expensive to implement
malfunctioning of protective relays and interference with              [3]. The configuration of a single tuned filter is depicted in
                                                                                                  Fig.1.
communication equipment[2-4]. To overcome such
problems, harmonic mitigation is becoming important for
both utilities and customers. Filtering harmonics using
passive filter is one of the earliest methods used to address
harmonic mitigation issues. Passive filters have been used
in power system to mitigate harmonic distortions [5]                                       Fig.1 Single Tuned Filter
primarily due to their low cost.



© 2011 ACEEE                                                       1
DOI: 01.IJEPE.02.01.25
ACEEE Int. J. on Electrical and Power Engineering, Vol. 02, No. 01, Feb 2011


In an ST filter, the inductive and capacitive reactance at           Typical values of m are in the range of 0.5 and 2. For a given
the tuned frequency should be equal [3][4][5].                       capacitance these parameters are decided to achieve an
                                                                     approximately high admittance over the required frequency
                                                                     range.
                                                                              Impedance of filter as a function of harmonic
                                                                     frequency is given as




                                                                             IV.EVALUATION OF FILTER DUTY REQUIREMENTS
                                                                               Evaluation of filter duty requirements typically
                                                                     involves capacitor bank duties. These duties include peak
                                                                     voltage, current, kVAr produced, and rms voltage. IEEE
                                                                     Standard 18-1992, IEEE Standard for Shunt Power
                                                                     Capacitors, is used as the limiting standard to evaluate these
                                                                     duties. Computations of the duties are divided into three
                                                                     steps, i.e., computation for fundamental duties, harmonic
                                                                     duties, and rms current and peak voltage duties and
                                                                     evaluation of capacitor loading limits[4].
                                                                     1) Computation of fundamental duty requirements
           The sharpness of tuning is dependent on R as                 The computation is as follows:
well as X0 and reducing these can reduce the impedance of            The effective reactance of the combined capacitor and reactor
filter at resonant frequency.                                        at the fundamental frequency is [6]

         III.DAMPED OR HIGH-PASS FILTER
          High pass filter provides a low impedance for a wide
spectrum of harmonics without the need for subdivision of
parallel branches with increased switching and maintenance
problems [3].The sharpness of tuning in the second order             where
high-pass filter is the reciprocal of ST filters [4][5]              VS is the maximum system operating voltage, phase to
                                                                     neutral, XC is the capacitive reactance at fundamental
                                                                     frequency, XL is the inductive reactance at fundamental
                                                                     frequency. The nominal capacitor current based on rated
                                                                     voltage and rated kVAr is calculated to be [6][7][8].




                                                                 2
© 2011 ACEEE
DOI: 01.IJEPE.02.01.25
ACEEE Int. J. on Electrical and Power Engineering, Vol. 02, No. 01, Feb 2011

                                                                      A six pulse converter operates from three phase 6.6 kV, 50
                                                                      Hz, 650 kW at 0.75 power factor lagging. It is required to
                                                                      improve the power factor to 0.95 lagging. Short Circuit level
                                                                      is given as 20 MVA at PCC. Converter is the only load on
                                                                      PCC.
                                                                      Harmonic data is given in Table-II




                                                                      Fig. 3 shows the single line diagram of the system. 6.6 kV
                                                                      bus is the PCC. The short circuit MVA is given as 20 MVA
                                                                      at PCC. The power factor at PCC is 0.75. The active power
                                                                      drawn from the source is 650 kW. The rectifier rating is 610
                                                                      kW.

                                                                                           VI.ANALYTICAL SOLUTION
                                                                      Following steps are taken to obtain the analytical solution-
                                                                      1)Reactive Power Compensation
                                                                               The power factor is required to improve from 0.75
where                                                                 to 0.95. kVAr drawn by the converter before application of
          is the three-phase rating of capacitor bank (Mvar),         filter is 570 kVAr. kVAr drawn by the converter after
      is the impedance of capacitor bank per phase (&!).3)            application of filter is 214 kVAr. Total kVAr to be supplied
Evaluation of capacitor rating limits.The duties (peak voltage,       by the filter is the difference between kVAr requirement
rms voltage and current, and kvar produced) for the proposed          before and after application of filter = 570 – 214 = 360 kVAr
filter capacitor are compared to the various IEEE standard            The reactive power can be distributed in the filter elements
limits in Table I                                                     i.e. 5th , 7th and high pass filter branches as




                V.PROBLEM DEFINITION                                        1. 1:1:1 i. e. equally
        It is not a very practical distribution system but good             2. 3:2:1
from harmonic study point of view. The problem is defined             Tuned filters are subjected to less dielectric stress as
as –                                                                  compared to high pass filters. kVAr rating of high pass filter
                                                                      should be minimum to reduce the dielectric loss in it.
                                                                      Choosing 1:1:1 i.e equal distribution of reactive power in
                                                                      all filter branches. Table III shows the filter rating.




© 2011 ACEEE                                                      3
DOI: 01.IJEPE.02.01.25
ACEEE Int. J. on Electrical and Power Engineering, Vol. 02, No. 01, Feb 2011

 2)Calculation of Short-Circuit Level and Load Demand                             Table V shows the harmonic loading of filter bank.
at PCC                                                                   It is seen that the 7th harmonic current is amplified due to
          To calculate the permissible TDD, the short-circuit            parallel resonance present.The harmonic loading on the
level at the PCC and the load demand over a period of 15 or              capacitor banks is calculated using Eq. (13) as 80.05 A
30 min is required [8]. For this example, the 6.6-kV bus is              capacitor current is 31.5 A and rms Current in capacitors is
PCC. The three phase symmetrical short circuit current                   80.05 A. The permissible rms current in the capacitors
is calculated as 3.03 kA. The maximum load demand current                including harmonics is 1.8 times the rated current. The
                                                                         current loading is exceeded
  is 80 Amps. The ratio         comes as 37.8. The permissible
                                                                                  The voltage loading is 4020 V, Vrms rated is 3810
IEEE TDD distortion limits is 8.                                         V, Vrms permissible is 110% i.e. 4191 V. The voltage rating
 3)Harmonic analysis without capacitor banks Following                   is not exceeded. The kVAr loading is calculated from Eq.
steps are taken to find out the voltage and current distortion           (15) and is 212.2 kVAr / phase. The rated kVAr per phase is
factors.                                                                 120 kVAr and the limit is 135%. The kVAr loading is
                                                                         exceeded. Overall TDD is 110.2%. The harmonic voltage
 a) The current distortion is found out by modeling the                  distortion is 33.5% . The total harmonic current demand
    system represented in Fig. 2 in MATLAB ® /                           distortion factor is 110.2%. Overall TDD for this system
    SIMULINK.The current distortions are given in Table                  should not exceed 8%.
    IV.
 b) The system is represented by Norton’s equivalent circuit             5)5th Harmonic Filter Design
    shown in Fig. 5; A current source in parallel with the                        Initial capacitor rating selected is 37.5 kVAr / phase
    source impedance as viewed from the terminals of non-                at 3.81 kV / phase in star connection. The harmonic voltage
    linear load.                                                         distortion at PCC is 7.72% . TDD comes as 15%. Total
 c) The source impedance is recalculated at each harmonic                TDD for this system should not exceed 8%.
    frequency
 d) As the harmonic currents are known, the bus harmonic
    voltages can be calculated, by IZ multiplication
4)Harmonic analysis with capacitor banks




                                                                         TDD for 5th Harmonic is reduced to 2.0 as on limit of 7.0.
                                                                         But overall TDD exceeds the limit. Therefore selecting
                                                                         higher capacitor rating 85 kVAr, 4.16 Kv /phase . Capacitive
                                                                         reactance at power frequency is 203.59 &!. The filter reactor
                                                                         size is selected to tune the capacitor to the desired frequency
  Fig 4 : Impedance modulus showing resonance at h = 7.44 harmonic
                                                                         of 250 Hz i.e. h = 5. The inductive reactance at power
               with addition of 120 kVAr capacitor bank.                 frequency is 8.14 &!.
                                                                                   Effective reactance of Filter Xeff is 195.45 &!.
Estimation of resonance with capacitors                                  Effective three phase reactive power provided by the filter
  The parallel resonant frequency can be estimated as                    is 265.7 kVAr (3 phase rating). The harmonic voltage
                                                           (20)          distortion at PCC is 6.81%

where         is the short circuit kVA rating at the PCC and
kVAr is the capacitor kVAr rating. The parallel resonance
frequency comes as 7.45. Fig 4 shows the impedance
modulus of system. The parallel resonance occurs at the
frequency of nearly 370 Hz.


                                                                     4
© 2011 ACEEE
DOI: 01.IJEPE.02.01.25
ACEEE Int. J. on Electrical and Power Engineering, Vol. 02, No. 01, Feb 2011

                                                                6)7th Harmonic filter Design
                                                                   The capacitor rating of 7th harmonic filter is 30 kVAr /
                                                                phase and 4.16 V/phase. Capacitive reactance at power
                                                                frequency is 576.85 &!.
                                                                         The filter reactor size is selected to tune the
                                                               capacitor to the desired frequency of 350 Hz. The inductive
                                                               reactance at power frequency is           . Effective reactance
                                                               of Filter               . Effective three phase reactive power
                                                               provided by the filter is                     ( 3 phase rating)
                                                                        The harmonic voltage distortion at PCC is reduced
                                                               to 5.04%. Overall TDD comes as 8.4%. TDD for 5 th
                                                               Harmonic is reduced to 0.64 as on limit of 7.0. TDD for 17th
                                                               harmonic is 3.85 as on limit of 3.0 and 19th harmonics is 3.0
                                                               as on limit of 2.5. It shows necessary of high pass filter to
                                                               limit the higher harmonics TDD. 7) High Pass Harmonic
                                                               filter Design.Capacitor Rating is selected as 30 kVAr, 4.16
         TDD comes as 13.06 %. TDD for 5th Harmonic            kV ,                / phase.Tuning frequency f0 = 11 and
is reduced to 1.13 as on limit of 7.0. To reduce overall
                                                               Quality factor of filter as 11.5. Resistor rating: 602.85 &!
TDD within limit it is necessary to have a 7th harmonic
filter.                                                        and Reactor rating: 0.0152 H, 4.16 kV / phaseThe harmonic
                                                               voltage distortion at PCC is 2.67 % .Overall TDD comes as
                                                               4%.




© 2011 ACEEE                                               5
DOI: 01.IJEPE.02.01.25
ACEEE Int. J. on Electrical and Power Engineering, Vol. 02, No. 01, Feb 2011

The analytical solution obtained for the TDD is compared                       - The voltage distortion factor is reduced from
with the simulation results in Table VI.                                          11.3% to 6.4 %.
 7) Effective Reactive power provided by filter and net power                  - The 7th harmonic current TDD is reduced to
factor improvement                                                                  0.64 from 11.6 analytically and simulation
   Finally the effective reactive power contribution of each                        shows the reduction to 0.9.
star connected filter at fundamental frequency is                       3) After installation of high pass filter
          5th ST Filter -   265.7 kVAr                                     A. analytical calculation shows that the overall TDD
          7th ST Filter –   77 kVAr                                        is reduced to 4% from 35.5%. The voltage distortion
          HP Filter -       75 kVAr                                        factor is reduced from 11.3 % to 3 %.
Total compensation provided is - 417.7 kVAr. Net Power                     B. Simulation results shows that the overall TDD is
Factor improvement after installation of filter will be 0.99               reduced to 5.5 % from 35.5 %.The voltage
i.e. near unity.                                                           distortion factor is reduced from 11.3% to 4%.

    VII.SIMULATION OF SYSTEM AND SIMULATION RESULTS                 Thus, the TDD at PCC is within the limit specified by
                                                                    IEEE standard 519 -1992.[9]
         The single line diagram of the system is simulated
using MATLAB ® /SIMULINK - platform to study the                                         VIII.CONCLUSION
distortions in the voltage and current waveforms due to
presence of nonlinear load in the system .The actual system           This paper has presented a harmonic mitigation study in
can be modeled with a high degree of accuracy in this               the simple distribution system. An investigation has been
package. It provides a user interactive platform and a wide         carried out to examine the effectiveness of filters using the
variety of numerical algorithms.                                    two types of passive filters namely, single tuned and High
  Fig. 6 shows the system modeled in SIMULINK. The                  pass filters in eliminating harmonics.
system consists of six pulse Rectifier model as the nonlinear
                                                                                               REFERENCES
load to the system, gate signal generator block and three
phase source.                                                       [1] Subrata De, and G. Bhuvaneswari, “Investigations on the
 Fig. 7 shows simulation results of distortions present in               impact of VAR rating and quality factor on the effectiveness
phase voltage and phase currents with and without filter                 of a shunt passive filter,” 0-7803-9525-5/06J. 2006 IEEE.
assembly.                                                           [2] J. C. Das, “Power System Analysis-Short-circuit, Load Flow
                                                                         and Harmonics”. New York: Marcel Dekker, 2002.
   The comparison of simulation and analytical results is as
                                                                    [3] J. Arrillaga, D. A. Bradley, and P. S. Bodger, “Power System
follows-                                                                 Harmonics” New York: Wiley, 1985
   1)With installation of 5th harmonic filter assembly:             [4] D. A. Gonzalez and J. C. McCall, “Design of filters to reduce
       A. Analytical calculation                                         harmonic
            - Overall TDD reduction to 13.88 % from                 distortion in industrial power systems,” IEEE Trans. Ind. Applicat.,
                35.5%.                                                   vol.
            - The voltage distortion factor is reduced from         IA-23, pp. 504–512, May/June 1987
                11.3 % to 6.75%.                                    [5] J. C. Das,” Passive Filter Potentialities and Limitations” IEEE
       B. Simulation results show that The overall TDD is                Transactions on Industry Applications, Vol 40, No.. 1, Jan /
                                                                         Feb 2004
       reduced to 14.8 % from 35.5%.
                                                                    [6] Dugan, E.C., McGranagham, M.F., Santoso, S., Beaty, H.W.,
   2) With installation of 5th and 7th harmonic filters:                 “Elecirical power systems quality”, McGraw-Hill, 2002
                                                                    [7] IEEE Standard for Shunt Power Capacitors. IEEE Standard
      A. Analytical calculation - Overall TDD is reduced                 18- 1992
     to 8.4% from 35.5%.                                            [8] “IEEE Guide for Application and Specification of Harmonic
           - The voltage distortion factor is reduced from               Filters”, IEEE Std. 1531-2003
            11.3% to 5.04%.                                         [9] Recommended Practice and Requirements for Harmonic
                                                                         Control in Electrical Systems, IEEE Std. 519-1992.
      B. Simulation results
           - The overall TDD is reduced to 10.55 % from
               35.5 %.




© 2011 ACEEE                                                    6
DOI: 01.IJEPE.02.01.25

Contenu connexe

Tendances

Regulatory Guidelines to set up Voltage Quality Monitoring
Regulatory Guidelines to set up Voltage Quality MonitoringRegulatory Guidelines to set up Voltage Quality Monitoring
Regulatory Guidelines to set up Voltage Quality MonitoringLeonardo ENERGY
 
Modeling and simulation of dynamic voltage restorer for voltage sag mitigatio...
Modeling and simulation of dynamic voltage restorer for voltage sag mitigatio...Modeling and simulation of dynamic voltage restorer for voltage sag mitigatio...
Modeling and simulation of dynamic voltage restorer for voltage sag mitigatio...IJRRR
 
Fuzzy Bang-Bang Control Scheme of USSC for Voltage Sag Mitigation due to Shor...
Fuzzy Bang-Bang Control Scheme of USSC for Voltage Sag Mitigation due to Shor...Fuzzy Bang-Bang Control Scheme of USSC for Voltage Sag Mitigation due to Shor...
Fuzzy Bang-Bang Control Scheme of USSC for Voltage Sag Mitigation due to Shor...IAES-IJPEDS
 
Design and Implementation of an Efficient Soft Switching Inverter Fed Ac Drive
Design and Implementation of an Efficient Soft Switching Inverter Fed Ac DriveDesign and Implementation of an Efficient Soft Switching Inverter Fed Ac Drive
Design and Implementation of an Efficient Soft Switching Inverter Fed Ac DriveIRJET Journal
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Scienceresearchinventy
 
A practical design of lumped, semi lumped & microwave cavity filters
A practical design of lumped, semi lumped & microwave cavity filtersA practical design of lumped, semi lumped & microwave cavity filters
A practical design of lumped, semi lumped & microwave cavity filtersSpringer
 
A novel low power high dynamic threshold swing limited repeater insertion for...
A novel low power high dynamic threshold swing limited repeater insertion for...A novel low power high dynamic threshold swing limited repeater insertion for...
A novel low power high dynamic threshold swing limited repeater insertion for...VLSICS Design
 
Design and Analysis of Active Bandpass Filter
Design and Analysis of Active Bandpass FilterDesign and Analysis of Active Bandpass Filter
Design and Analysis of Active Bandpass FilterKyla Marino
 
Pq unit ii
Pq unit iiPq unit ii
Pq unit iivenki249
 
Study Of Different Passive Filter- A Review
Study Of Different Passive Filter- A ReviewStudy Of Different Passive Filter- A Review
Study Of Different Passive Filter- A ReviewIRJET Journal
 
An Overview of Constant-k Type Filters
An Overview of Constant-k Type FiltersAn Overview of Constant-k Type Filters
An Overview of Constant-k Type Filterspaperpublications3
 
Power Quality Identification Using Wavelet Transform: A Review
Power Quality Identification Using Wavelet Transform: A ReviewPower Quality Identification Using Wavelet Transform: A Review
Power Quality Identification Using Wavelet Transform: A Reviewpaperpublications3
 
power factor controlling using intregarted device controller
power factor controlling using intregarted device controllerpower factor controlling using intregarted device controller
power factor controlling using intregarted device controllerusic123
 
Qualitative Analysis of Darlington Feedback Amplifier at 45nm Technology
Qualitative Analysis of Darlington Feedback Amplifier at 45nm TechnologyQualitative Analysis of Darlington Feedback Amplifier at 45nm Technology
Qualitative Analysis of Darlington Feedback Amplifier at 45nm TechnologyjournalBEEI
 

Tendances (18)

Mk2420552059
Mk2420552059Mk2420552059
Mk2420552059
 
call for papers, research paper publishing, where to publish research paper, ...
call for papers, research paper publishing, where to publish research paper, ...call for papers, research paper publishing, where to publish research paper, ...
call for papers, research paper publishing, where to publish research paper, ...
 
Regulatory Guidelines to set up Voltage Quality Monitoring
Regulatory Guidelines to set up Voltage Quality MonitoringRegulatory Guidelines to set up Voltage Quality Monitoring
Regulatory Guidelines to set up Voltage Quality Monitoring
 
Modeling and simulation of dynamic voltage restorer for voltage sag mitigatio...
Modeling and simulation of dynamic voltage restorer for voltage sag mitigatio...Modeling and simulation of dynamic voltage restorer for voltage sag mitigatio...
Modeling and simulation of dynamic voltage restorer for voltage sag mitigatio...
 
Gr3412151231
Gr3412151231Gr3412151231
Gr3412151231
 
Fuzzy Bang-Bang Control Scheme of USSC for Voltage Sag Mitigation due to Shor...
Fuzzy Bang-Bang Control Scheme of USSC for Voltage Sag Mitigation due to Shor...Fuzzy Bang-Bang Control Scheme of USSC for Voltage Sag Mitigation due to Shor...
Fuzzy Bang-Bang Control Scheme of USSC for Voltage Sag Mitigation due to Shor...
 
Design and Implementation of an Efficient Soft Switching Inverter Fed Ac Drive
Design and Implementation of an Efficient Soft Switching Inverter Fed Ac DriveDesign and Implementation of an Efficient Soft Switching Inverter Fed Ac Drive
Design and Implementation of an Efficient Soft Switching Inverter Fed Ac Drive
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
 
A practical design of lumped, semi lumped & microwave cavity filters
A practical design of lumped, semi lumped & microwave cavity filtersA practical design of lumped, semi lumped & microwave cavity filters
A practical design of lumped, semi lumped & microwave cavity filters
 
A novel low power high dynamic threshold swing limited repeater insertion for...
A novel low power high dynamic threshold swing limited repeater insertion for...A novel low power high dynamic threshold swing limited repeater insertion for...
A novel low power high dynamic threshold swing limited repeater insertion for...
 
Kj2518171824
Kj2518171824Kj2518171824
Kj2518171824
 
Design and Analysis of Active Bandpass Filter
Design and Analysis of Active Bandpass FilterDesign and Analysis of Active Bandpass Filter
Design and Analysis of Active Bandpass Filter
 
Pq unit ii
Pq unit iiPq unit ii
Pq unit ii
 
Study Of Different Passive Filter- A Review
Study Of Different Passive Filter- A ReviewStudy Of Different Passive Filter- A Review
Study Of Different Passive Filter- A Review
 
An Overview of Constant-k Type Filters
An Overview of Constant-k Type FiltersAn Overview of Constant-k Type Filters
An Overview of Constant-k Type Filters
 
Power Quality Identification Using Wavelet Transform: A Review
Power Quality Identification Using Wavelet Transform: A ReviewPower Quality Identification Using Wavelet Transform: A Review
Power Quality Identification Using Wavelet Transform: A Review
 
power factor controlling using intregarted device controller
power factor controlling using intregarted device controllerpower factor controlling using intregarted device controller
power factor controlling using intregarted device controller
 
Qualitative Analysis of Darlington Feedback Amplifier at 45nm Technology
Qualitative Analysis of Darlington Feedback Amplifier at 45nm TechnologyQualitative Analysis of Darlington Feedback Amplifier at 45nm Technology
Qualitative Analysis of Darlington Feedback Amplifier at 45nm Technology
 

En vedette

En vedette (7)

Harmonics and mitigation techniques
Harmonics and mitigation techniquesHarmonics and mitigation techniques
Harmonics and mitigation techniques
 
Hormonics impact and_mitigation
Hormonics impact and_mitigationHormonics impact and_mitigation
Hormonics impact and_mitigation
 
Shunt active power filter
Shunt active power filterShunt active power filter
Shunt active power filter
 
Active_Power_Filter
Active_Power_FilterActive_Power_Filter
Active_Power_Filter
 
Harmonics in power system
Harmonics in power systemHarmonics in power system
Harmonics in power system
 
Filters
FiltersFilters
Filters
 
Solar inverter
Solar inverterSolar inverter
Solar inverter
 

Similaire à Simulation Studies of Shunt Passive Harmonic Filters: Six Pulse Rectifier Load – Power Factor Improvement and Harmonic Control

Harmonic Analysis of Non-Linear Loads in Distribution System and Mitigation U...
Harmonic Analysis of Non-Linear Loads in Distribution System and Mitigation U...Harmonic Analysis of Non-Linear Loads in Distribution System and Mitigation U...
Harmonic Analysis of Non-Linear Loads in Distribution System and Mitigation U...IRJET Journal
 
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear LoadsHarmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear LoadsIJAPEJOURNAL
 
IRJET-Harmonic Elimination in Three Phase System by Means of a Shunt Active F...
IRJET-Harmonic Elimination in Three Phase System by Means of a Shunt Active F...IRJET-Harmonic Elimination in Three Phase System by Means of a Shunt Active F...
IRJET-Harmonic Elimination in Three Phase System by Means of a Shunt Active F...IRJET Journal
 
Mitigation of Harmonic Current through Hybrid Power Filter in Single Phase Re...
Mitigation of Harmonic Current through Hybrid Power Filter in Single Phase Re...Mitigation of Harmonic Current through Hybrid Power Filter in Single Phase Re...
Mitigation of Harmonic Current through Hybrid Power Filter in Single Phase Re...IDES Editor
 
report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...Vikram Rawani
 
Neuro-Fuzzy Five-level Cascaded Multilevel Inverter for Active Power Filter
Neuro-Fuzzy Five-level Cascaded Multilevel Inverter for Active Power FilterNeuro-Fuzzy Five-level Cascaded Multilevel Inverter for Active Power Filter
Neuro-Fuzzy Five-level Cascaded Multilevel Inverter for Active Power FilterIDES Editor
 
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...ijtsrd
 
Application of Active Power Filter for Power Factor Correction of Nonlinear L...
Application of Active Power Filter for Power Factor Correction of Nonlinear L...Application of Active Power Filter for Power Factor Correction of Nonlinear L...
Application of Active Power Filter for Power Factor Correction of Nonlinear L...Pravin Sonwane
 
Power System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power FilterPower System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power FilterIJERA Editor
 
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...IDES Editor
 
Power system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filterPower system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filtereSAT Publishing House
 
The Harmonic Mitigation in Induction Furnace Using Hybrid Filter
The Harmonic Mitigation in Induction Furnace Using Hybrid FilterThe Harmonic Mitigation in Induction Furnace Using Hybrid Filter
The Harmonic Mitigation in Induction Furnace Using Hybrid Filterpaperpublications3
 
Harmonic enhancement in microgrid with applications on sensitive loads
Harmonic enhancement in microgrid with applications on sensitive loadsHarmonic enhancement in microgrid with applications on sensitive loads
Harmonic enhancement in microgrid with applications on sensitive loadsIJECEIAES
 
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...IJERD Editor
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)ijceronline
 

Similaire à Simulation Studies of Shunt Passive Harmonic Filters: Six Pulse Rectifier Load – Power Factor Improvement and Harmonic Control (20)

2
22
2
 
Harmonic Analysis of Non-Linear Loads in Distribution System and Mitigation U...
Harmonic Analysis of Non-Linear Loads in Distribution System and Mitigation U...Harmonic Analysis of Non-Linear Loads in Distribution System and Mitigation U...
Harmonic Analysis of Non-Linear Loads in Distribution System and Mitigation U...
 
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear LoadsHarmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
 
Fx2410731080
Fx2410731080Fx2410731080
Fx2410731080
 
IRJET-Harmonic Elimination in Three Phase System by Means of a Shunt Active F...
IRJET-Harmonic Elimination in Three Phase System by Means of a Shunt Active F...IRJET-Harmonic Elimination in Three Phase System by Means of a Shunt Active F...
IRJET-Harmonic Elimination in Three Phase System by Means of a Shunt Active F...
 
Mitigation of Harmonic Current through Hybrid Power Filter in Single Phase Re...
Mitigation of Harmonic Current through Hybrid Power Filter in Single Phase Re...Mitigation of Harmonic Current through Hybrid Power Filter in Single Phase Re...
Mitigation of Harmonic Current through Hybrid Power Filter in Single Phase Re...
 
report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...
 
Neuro-Fuzzy Five-level Cascaded Multilevel Inverter for Active Power Filter
Neuro-Fuzzy Five-level Cascaded Multilevel Inverter for Active Power FilterNeuro-Fuzzy Five-level Cascaded Multilevel Inverter for Active Power Filter
Neuro-Fuzzy Five-level Cascaded Multilevel Inverter for Active Power Filter
 
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...
 
Application of Active Power Filter for Power Factor Correction of Nonlinear L...
Application of Active Power Filter for Power Factor Correction of Nonlinear L...Application of Active Power Filter for Power Factor Correction of Nonlinear L...
Application of Active Power Filter for Power Factor Correction of Nonlinear L...
 
Ps harmonics
Ps harmonicsPs harmonics
Ps harmonics
 
Power System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power FilterPower System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power Filter
 
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
 
Power system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filterPower system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filter
 
The Harmonic Mitigation in Induction Furnace Using Hybrid Filter
The Harmonic Mitigation in Induction Furnace Using Hybrid FilterThe Harmonic Mitigation in Induction Furnace Using Hybrid Filter
The Harmonic Mitigation in Induction Furnace Using Hybrid Filter
 
Harmonic enhancement in microgrid with applications on sensitive loads
Harmonic enhancement in microgrid with applications on sensitive loadsHarmonic enhancement in microgrid with applications on sensitive loads
Harmonic enhancement in microgrid with applications on sensitive loads
 
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
 
S25096101
S25096101S25096101
S25096101
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)
 
J0361059064
J0361059064J0361059064
J0361059064
 

Plus de IDES Editor

Power System State Estimation - A Review
Power System State Estimation - A ReviewPower System State Estimation - A Review
Power System State Estimation - A ReviewIDES Editor
 
Artificial Intelligence Technique based Reactive Power Planning Incorporating...
Artificial Intelligence Technique based Reactive Power Planning Incorporating...Artificial Intelligence Technique based Reactive Power Planning Incorporating...
Artificial Intelligence Technique based Reactive Power Planning Incorporating...IDES Editor
 
Design and Performance Analysis of Genetic based PID-PSS with SVC in a Multi-...
Design and Performance Analysis of Genetic based PID-PSS with SVC in a Multi-...Design and Performance Analysis of Genetic based PID-PSS with SVC in a Multi-...
Design and Performance Analysis of Genetic based PID-PSS with SVC in a Multi-...IDES Editor
 
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...IDES Editor
 
Line Losses in the 14-Bus Power System Network using UPFC
Line Losses in the 14-Bus Power System Network using UPFCLine Losses in the 14-Bus Power System Network using UPFC
Line Losses in the 14-Bus Power System Network using UPFCIDES Editor
 
Study of Structural Behaviour of Gravity Dam with Various Features of Gallery...
Study of Structural Behaviour of Gravity Dam with Various Features of Gallery...Study of Structural Behaviour of Gravity Dam with Various Features of Gallery...
Study of Structural Behaviour of Gravity Dam with Various Features of Gallery...IDES Editor
 
Assessing Uncertainty of Pushover Analysis to Geometric Modeling
Assessing Uncertainty of Pushover Analysis to Geometric ModelingAssessing Uncertainty of Pushover Analysis to Geometric Modeling
Assessing Uncertainty of Pushover Analysis to Geometric ModelingIDES Editor
 
Secure Multi-Party Negotiation: An Analysis for Electronic Payments in Mobile...
Secure Multi-Party Negotiation: An Analysis for Electronic Payments in Mobile...Secure Multi-Party Negotiation: An Analysis for Electronic Payments in Mobile...
Secure Multi-Party Negotiation: An Analysis for Electronic Payments in Mobile...IDES Editor
 
Selfish Node Isolation & Incentivation using Progressive Thresholds
Selfish Node Isolation & Incentivation using Progressive ThresholdsSelfish Node Isolation & Incentivation using Progressive Thresholds
Selfish Node Isolation & Incentivation using Progressive ThresholdsIDES Editor
 
Various OSI Layer Attacks and Countermeasure to Enhance the Performance of WS...
Various OSI Layer Attacks and Countermeasure to Enhance the Performance of WS...Various OSI Layer Attacks and Countermeasure to Enhance the Performance of WS...
Various OSI Layer Attacks and Countermeasure to Enhance the Performance of WS...IDES Editor
 
Responsive Parameter based an AntiWorm Approach to Prevent Wormhole Attack in...
Responsive Parameter based an AntiWorm Approach to Prevent Wormhole Attack in...Responsive Parameter based an AntiWorm Approach to Prevent Wormhole Attack in...
Responsive Parameter based an AntiWorm Approach to Prevent Wormhole Attack in...IDES Editor
 
Cloud Security and Data Integrity with Client Accountability Framework
Cloud Security and Data Integrity with Client Accountability FrameworkCloud Security and Data Integrity with Client Accountability Framework
Cloud Security and Data Integrity with Client Accountability FrameworkIDES Editor
 
Genetic Algorithm based Layered Detection and Defense of HTTP Botnet
Genetic Algorithm based Layered Detection and Defense of HTTP BotnetGenetic Algorithm based Layered Detection and Defense of HTTP Botnet
Genetic Algorithm based Layered Detection and Defense of HTTP BotnetIDES Editor
 
Enhancing Data Storage Security in Cloud Computing Through Steganography
Enhancing Data Storage Security in Cloud Computing Through SteganographyEnhancing Data Storage Security in Cloud Computing Through Steganography
Enhancing Data Storage Security in Cloud Computing Through SteganographyIDES Editor
 
Low Energy Routing for WSN’s
Low Energy Routing for WSN’sLow Energy Routing for WSN’s
Low Energy Routing for WSN’sIDES Editor
 
Permutation of Pixels within the Shares of Visual Cryptography using KBRP for...
Permutation of Pixels within the Shares of Visual Cryptography using KBRP for...Permutation of Pixels within the Shares of Visual Cryptography using KBRP for...
Permutation of Pixels within the Shares of Visual Cryptography using KBRP for...IDES Editor
 
Rotman Lens Performance Analysis
Rotman Lens Performance AnalysisRotman Lens Performance Analysis
Rotman Lens Performance AnalysisIDES Editor
 
Band Clustering for the Lossless Compression of AVIRIS Hyperspectral Images
Band Clustering for the Lossless Compression of AVIRIS Hyperspectral ImagesBand Clustering for the Lossless Compression of AVIRIS Hyperspectral Images
Band Clustering for the Lossless Compression of AVIRIS Hyperspectral ImagesIDES Editor
 
Microelectronic Circuit Analogous to Hydrogen Bonding Network in Active Site ...
Microelectronic Circuit Analogous to Hydrogen Bonding Network in Active Site ...Microelectronic Circuit Analogous to Hydrogen Bonding Network in Active Site ...
Microelectronic Circuit Analogous to Hydrogen Bonding Network in Active Site ...IDES Editor
 
Texture Unit based Monocular Real-world Scene Classification using SOM and KN...
Texture Unit based Monocular Real-world Scene Classification using SOM and KN...Texture Unit based Monocular Real-world Scene Classification using SOM and KN...
Texture Unit based Monocular Real-world Scene Classification using SOM and KN...IDES Editor
 

Plus de IDES Editor (20)

Power System State Estimation - A Review
Power System State Estimation - A ReviewPower System State Estimation - A Review
Power System State Estimation - A Review
 
Artificial Intelligence Technique based Reactive Power Planning Incorporating...
Artificial Intelligence Technique based Reactive Power Planning Incorporating...Artificial Intelligence Technique based Reactive Power Planning Incorporating...
Artificial Intelligence Technique based Reactive Power Planning Incorporating...
 
Design and Performance Analysis of Genetic based PID-PSS with SVC in a Multi-...
Design and Performance Analysis of Genetic based PID-PSS with SVC in a Multi-...Design and Performance Analysis of Genetic based PID-PSS with SVC in a Multi-...
Design and Performance Analysis of Genetic based PID-PSS with SVC in a Multi-...
 
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
 
Line Losses in the 14-Bus Power System Network using UPFC
Line Losses in the 14-Bus Power System Network using UPFCLine Losses in the 14-Bus Power System Network using UPFC
Line Losses in the 14-Bus Power System Network using UPFC
 
Study of Structural Behaviour of Gravity Dam with Various Features of Gallery...
Study of Structural Behaviour of Gravity Dam with Various Features of Gallery...Study of Structural Behaviour of Gravity Dam with Various Features of Gallery...
Study of Structural Behaviour of Gravity Dam with Various Features of Gallery...
 
Assessing Uncertainty of Pushover Analysis to Geometric Modeling
Assessing Uncertainty of Pushover Analysis to Geometric ModelingAssessing Uncertainty of Pushover Analysis to Geometric Modeling
Assessing Uncertainty of Pushover Analysis to Geometric Modeling
 
Secure Multi-Party Negotiation: An Analysis for Electronic Payments in Mobile...
Secure Multi-Party Negotiation: An Analysis for Electronic Payments in Mobile...Secure Multi-Party Negotiation: An Analysis for Electronic Payments in Mobile...
Secure Multi-Party Negotiation: An Analysis for Electronic Payments in Mobile...
 
Selfish Node Isolation & Incentivation using Progressive Thresholds
Selfish Node Isolation & Incentivation using Progressive ThresholdsSelfish Node Isolation & Incentivation using Progressive Thresholds
Selfish Node Isolation & Incentivation using Progressive Thresholds
 
Various OSI Layer Attacks and Countermeasure to Enhance the Performance of WS...
Various OSI Layer Attacks and Countermeasure to Enhance the Performance of WS...Various OSI Layer Attacks and Countermeasure to Enhance the Performance of WS...
Various OSI Layer Attacks and Countermeasure to Enhance the Performance of WS...
 
Responsive Parameter based an AntiWorm Approach to Prevent Wormhole Attack in...
Responsive Parameter based an AntiWorm Approach to Prevent Wormhole Attack in...Responsive Parameter based an AntiWorm Approach to Prevent Wormhole Attack in...
Responsive Parameter based an AntiWorm Approach to Prevent Wormhole Attack in...
 
Cloud Security and Data Integrity with Client Accountability Framework
Cloud Security and Data Integrity with Client Accountability FrameworkCloud Security and Data Integrity with Client Accountability Framework
Cloud Security and Data Integrity with Client Accountability Framework
 
Genetic Algorithm based Layered Detection and Defense of HTTP Botnet
Genetic Algorithm based Layered Detection and Defense of HTTP BotnetGenetic Algorithm based Layered Detection and Defense of HTTP Botnet
Genetic Algorithm based Layered Detection and Defense of HTTP Botnet
 
Enhancing Data Storage Security in Cloud Computing Through Steganography
Enhancing Data Storage Security in Cloud Computing Through SteganographyEnhancing Data Storage Security in Cloud Computing Through Steganography
Enhancing Data Storage Security in Cloud Computing Through Steganography
 
Low Energy Routing for WSN’s
Low Energy Routing for WSN’sLow Energy Routing for WSN’s
Low Energy Routing for WSN’s
 
Permutation of Pixels within the Shares of Visual Cryptography using KBRP for...
Permutation of Pixels within the Shares of Visual Cryptography using KBRP for...Permutation of Pixels within the Shares of Visual Cryptography using KBRP for...
Permutation of Pixels within the Shares of Visual Cryptography using KBRP for...
 
Rotman Lens Performance Analysis
Rotman Lens Performance AnalysisRotman Lens Performance Analysis
Rotman Lens Performance Analysis
 
Band Clustering for the Lossless Compression of AVIRIS Hyperspectral Images
Band Clustering for the Lossless Compression of AVIRIS Hyperspectral ImagesBand Clustering for the Lossless Compression of AVIRIS Hyperspectral Images
Band Clustering for the Lossless Compression of AVIRIS Hyperspectral Images
 
Microelectronic Circuit Analogous to Hydrogen Bonding Network in Active Site ...
Microelectronic Circuit Analogous to Hydrogen Bonding Network in Active Site ...Microelectronic Circuit Analogous to Hydrogen Bonding Network in Active Site ...
Microelectronic Circuit Analogous to Hydrogen Bonding Network in Active Site ...
 
Texture Unit based Monocular Real-world Scene Classification using SOM and KN...
Texture Unit based Monocular Real-world Scene Classification using SOM and KN...Texture Unit based Monocular Real-world Scene Classification using SOM and KN...
Texture Unit based Monocular Real-world Scene Classification using SOM and KN...
 

Dernier

Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024The Digital Insurer
 
Advantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your BusinessAdvantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your BusinessPixlogix Infotech
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘RTylerCroy
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)Gabriella Davis
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...Martijn de Jong
 
Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationRadu Cotescu
 
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc
 
Breaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountBreaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountPuma Security, LLC
 
Artificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsArtificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsJoaquim Jorge
 
Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)wesley chun
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024Rafal Los
 
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...apidays
 
Understanding Discord NSFW Servers A Guide for Responsible Users.pdf
Understanding Discord NSFW Servers A Guide for Responsible Users.pdfUnderstanding Discord NSFW Servers A Guide for Responsible Users.pdf
Understanding Discord NSFW Servers A Guide for Responsible Users.pdfUK Journal
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processorsdebabhi2
 
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEarley Information Science
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Igalia
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfEnterprise Knowledge
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024Results
 
Slack Application Development 101 Slides
Slack Application Development 101 SlidesSlack Application Development 101 Slides
Slack Application Development 101 Slidespraypatel2
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Enterprise Knowledge
 

Dernier (20)

Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024
 
Advantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your BusinessAdvantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your Business
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...
 
Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organization
 
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
 
Breaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountBreaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path Mount
 
Artificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsArtificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and Myths
 
Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024
 
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
 
Understanding Discord NSFW Servers A Guide for Responsible Users.pdf
Understanding Discord NSFW Servers A Guide for Responsible Users.pdfUnderstanding Discord NSFW Servers A Guide for Responsible Users.pdf
Understanding Discord NSFW Servers A Guide for Responsible Users.pdf
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processors
 
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024
 
Slack Application Development 101 Slides
Slack Application Development 101 SlidesSlack Application Development 101 Slides
Slack Application Development 101 Slides
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...
 

Simulation Studies of Shunt Passive Harmonic Filters: Six Pulse Rectifier Load – Power Factor Improvement and Harmonic Control

  • 1. ACEEE Int. J. on Electrical and Power Engineering, Vol. 02, No. 01, Feb 2011 Simulation Studies of Shunt Passive Harmonic Filters: Six Pulse Rectifier Load – Power Factor Improvement and Harmonic Control Seema P. Diwan, Dr. H. P. Inamdar, and Dr. A. P. Vaidya Walchand College of Engineering, Electrical Department, Sangli, India Email: seemapdiwan@gmail.com Abstract— This paper presents a study of harmonic filters Most distribution systems require reactive power design procedure to minimize harmonic distortion caused by a compensation to improve the power factor, save demand harmonic source such as drives. The non – linear load charges, or to release additional active power from existing considered in this paper is six pulse rectifier load. Design and equipment or for voltage support, i.e., the reactive power simulation procedure with respect to this load is explained in support required to arrest the voltage drop on loss of a plant details. Several types of shunt harmonic filters are presented. Shunt filters are effective in minimizing voltage distortion generator. The nonlinear loads are increasing, i.e., pulp and caused by nonlinear loads in industrial power systems. Different paper mill distribution systems invariably have adjustable- alternatives of filter design should be considered before making speed drive(ASD) systems [2], which may form a the final decision on filter configuration. Among the criteria considerable percentage of overall plant load. When power used for performance evaluation are current, and voltage capacitors are used for reactive power compensation, it ratings of each of the filter components. The design and becomes necessary to turn them in to filters to escape performance of single-tuned and high-pass filters and the harmonic resonance problems with one of the load-generated methodology used for the analysis will be discussed. harmonics It is not uncommon to apply passive filters in the The major objectives in this study are to use shunt passive megavar range and filters totaling some tens of megavars in filters for following -(i) to improve the power factor, (ii) to a large installation may be required.The main contribution reduce current and voltage distortion to standard limits, and (iii) to reduce resonance problems, if any. of this paper is to presents an analysis and simulation of application of shunt harmonic filters. The study procedure Index Terms— Harmonics, passive shunt filters, single tuned adopted in this paper is outlined as follows: filter, high pass filter, filter rating. 1. Problem definition and Simulation of a system with non linear loads. I.INTRODUCTION 2. Design of Shunt Passive Filter(s) to provide reactive In an ideal power system, electrical energy is power compensation and minimize TDD at PCC. supplied at a constant frequency and at a specified voltage 3. Study different aspects of design of shunt passive level of constant magnitude with sinusoidal wave shape. filter i.e. capacitor bank current and voltage loading, However, in practice, none of these conditions is fulfilled to outage conditions of filters and resonance etc. the fullest extent, due to the presence of voltage and current 4. Comparison of analytical solution of the filter harmonics of multiple orders. These harmonics may be design and results obtained from the simulation. caused by nonlinear loads like controlled rectifiers and inverters, luminous discharge lighting, magnetizing current II.SINGLE TUNED FILTER drawn by transformers or phase belt, chording, skewing, slotting and air gap irregularities in a rotating electrical The most common type of shunt passive filters used in machine [1]. The harmonics present in the electrical source harmonic mitigation is the single tuned filter (STF) which cause many ill-effects such as reduction in power generation, is either a low pass or band pass filter. This type of filter is transmission and utilization efficiency, resonance effects, simplest to design and the least expensive to implement malfunctioning of protective relays and interference with [3]. The configuration of a single tuned filter is depicted in Fig.1. communication equipment[2-4]. To overcome such problems, harmonic mitigation is becoming important for both utilities and customers. Filtering harmonics using passive filter is one of the earliest methods used to address harmonic mitigation issues. Passive filters have been used in power system to mitigate harmonic distortions [5] Fig.1 Single Tuned Filter primarily due to their low cost. © 2011 ACEEE 1 DOI: 01.IJEPE.02.01.25
  • 2. ACEEE Int. J. on Electrical and Power Engineering, Vol. 02, No. 01, Feb 2011 In an ST filter, the inductive and capacitive reactance at Typical values of m are in the range of 0.5 and 2. For a given the tuned frequency should be equal [3][4][5]. capacitance these parameters are decided to achieve an approximately high admittance over the required frequency range. Impedance of filter as a function of harmonic frequency is given as IV.EVALUATION OF FILTER DUTY REQUIREMENTS Evaluation of filter duty requirements typically involves capacitor bank duties. These duties include peak voltage, current, kVAr produced, and rms voltage. IEEE Standard 18-1992, IEEE Standard for Shunt Power Capacitors, is used as the limiting standard to evaluate these duties. Computations of the duties are divided into three steps, i.e., computation for fundamental duties, harmonic duties, and rms current and peak voltage duties and evaluation of capacitor loading limits[4]. 1) Computation of fundamental duty requirements The sharpness of tuning is dependent on R as The computation is as follows: well as X0 and reducing these can reduce the impedance of The effective reactance of the combined capacitor and reactor filter at resonant frequency. at the fundamental frequency is [6] III.DAMPED OR HIGH-PASS FILTER High pass filter provides a low impedance for a wide spectrum of harmonics without the need for subdivision of parallel branches with increased switching and maintenance problems [3].The sharpness of tuning in the second order where high-pass filter is the reciprocal of ST filters [4][5] VS is the maximum system operating voltage, phase to neutral, XC is the capacitive reactance at fundamental frequency, XL is the inductive reactance at fundamental frequency. The nominal capacitor current based on rated voltage and rated kVAr is calculated to be [6][7][8]. 2 © 2011 ACEEE DOI: 01.IJEPE.02.01.25
  • 3. ACEEE Int. J. on Electrical and Power Engineering, Vol. 02, No. 01, Feb 2011 A six pulse converter operates from three phase 6.6 kV, 50 Hz, 650 kW at 0.75 power factor lagging. It is required to improve the power factor to 0.95 lagging. Short Circuit level is given as 20 MVA at PCC. Converter is the only load on PCC. Harmonic data is given in Table-II Fig. 3 shows the single line diagram of the system. 6.6 kV bus is the PCC. The short circuit MVA is given as 20 MVA at PCC. The power factor at PCC is 0.75. The active power drawn from the source is 650 kW. The rectifier rating is 610 kW. VI.ANALYTICAL SOLUTION Following steps are taken to obtain the analytical solution- 1)Reactive Power Compensation The power factor is required to improve from 0.75 where to 0.95. kVAr drawn by the converter before application of is the three-phase rating of capacitor bank (Mvar), filter is 570 kVAr. kVAr drawn by the converter after is the impedance of capacitor bank per phase (&!).3) application of filter is 214 kVAr. Total kVAr to be supplied Evaluation of capacitor rating limits.The duties (peak voltage, by the filter is the difference between kVAr requirement rms voltage and current, and kvar produced) for the proposed before and after application of filter = 570 – 214 = 360 kVAr filter capacitor are compared to the various IEEE standard The reactive power can be distributed in the filter elements limits in Table I i.e. 5th , 7th and high pass filter branches as V.PROBLEM DEFINITION 1. 1:1:1 i. e. equally It is not a very practical distribution system but good 2. 3:2:1 from harmonic study point of view. The problem is defined Tuned filters are subjected to less dielectric stress as as – compared to high pass filters. kVAr rating of high pass filter should be minimum to reduce the dielectric loss in it. Choosing 1:1:1 i.e equal distribution of reactive power in all filter branches. Table III shows the filter rating. © 2011 ACEEE 3 DOI: 01.IJEPE.02.01.25
  • 4. ACEEE Int. J. on Electrical and Power Engineering, Vol. 02, No. 01, Feb 2011 2)Calculation of Short-Circuit Level and Load Demand Table V shows the harmonic loading of filter bank. at PCC It is seen that the 7th harmonic current is amplified due to To calculate the permissible TDD, the short-circuit parallel resonance present.The harmonic loading on the level at the PCC and the load demand over a period of 15 or capacitor banks is calculated using Eq. (13) as 80.05 A 30 min is required [8]. For this example, the 6.6-kV bus is capacitor current is 31.5 A and rms Current in capacitors is PCC. The three phase symmetrical short circuit current 80.05 A. The permissible rms current in the capacitors is calculated as 3.03 kA. The maximum load demand current including harmonics is 1.8 times the rated current. The current loading is exceeded is 80 Amps. The ratio comes as 37.8. The permissible The voltage loading is 4020 V, Vrms rated is 3810 IEEE TDD distortion limits is 8. V, Vrms permissible is 110% i.e. 4191 V. The voltage rating 3)Harmonic analysis without capacitor banks Following is not exceeded. The kVAr loading is calculated from Eq. steps are taken to find out the voltage and current distortion (15) and is 212.2 kVAr / phase. The rated kVAr per phase is factors. 120 kVAr and the limit is 135%. The kVAr loading is exceeded. Overall TDD is 110.2%. The harmonic voltage a) The current distortion is found out by modeling the distortion is 33.5% . The total harmonic current demand system represented in Fig. 2 in MATLAB ® / distortion factor is 110.2%. Overall TDD for this system SIMULINK.The current distortions are given in Table should not exceed 8%. IV. b) The system is represented by Norton’s equivalent circuit 5)5th Harmonic Filter Design shown in Fig. 5; A current source in parallel with the Initial capacitor rating selected is 37.5 kVAr / phase source impedance as viewed from the terminals of non- at 3.81 kV / phase in star connection. The harmonic voltage linear load. distortion at PCC is 7.72% . TDD comes as 15%. Total c) The source impedance is recalculated at each harmonic TDD for this system should not exceed 8%. frequency d) As the harmonic currents are known, the bus harmonic voltages can be calculated, by IZ multiplication 4)Harmonic analysis with capacitor banks TDD for 5th Harmonic is reduced to 2.0 as on limit of 7.0. But overall TDD exceeds the limit. Therefore selecting higher capacitor rating 85 kVAr, 4.16 Kv /phase . Capacitive reactance at power frequency is 203.59 &!. The filter reactor size is selected to tune the capacitor to the desired frequency Fig 4 : Impedance modulus showing resonance at h = 7.44 harmonic of 250 Hz i.e. h = 5. The inductive reactance at power with addition of 120 kVAr capacitor bank. frequency is 8.14 &!. Effective reactance of Filter Xeff is 195.45 &!. Estimation of resonance with capacitors Effective three phase reactive power provided by the filter The parallel resonant frequency can be estimated as is 265.7 kVAr (3 phase rating). The harmonic voltage (20) distortion at PCC is 6.81% where is the short circuit kVA rating at the PCC and kVAr is the capacitor kVAr rating. The parallel resonance frequency comes as 7.45. Fig 4 shows the impedance modulus of system. The parallel resonance occurs at the frequency of nearly 370 Hz. 4 © 2011 ACEEE DOI: 01.IJEPE.02.01.25
  • 5. ACEEE Int. J. on Electrical and Power Engineering, Vol. 02, No. 01, Feb 2011 6)7th Harmonic filter Design The capacitor rating of 7th harmonic filter is 30 kVAr / phase and 4.16 V/phase. Capacitive reactance at power frequency is 576.85 &!. The filter reactor size is selected to tune the capacitor to the desired frequency of 350 Hz. The inductive reactance at power frequency is . Effective reactance of Filter . Effective three phase reactive power provided by the filter is ( 3 phase rating) The harmonic voltage distortion at PCC is reduced to 5.04%. Overall TDD comes as 8.4%. TDD for 5 th Harmonic is reduced to 0.64 as on limit of 7.0. TDD for 17th harmonic is 3.85 as on limit of 3.0 and 19th harmonics is 3.0 as on limit of 2.5. It shows necessary of high pass filter to limit the higher harmonics TDD. 7) High Pass Harmonic filter Design.Capacitor Rating is selected as 30 kVAr, 4.16 TDD comes as 13.06 %. TDD for 5th Harmonic kV , / phase.Tuning frequency f0 = 11 and is reduced to 1.13 as on limit of 7.0. To reduce overall Quality factor of filter as 11.5. Resistor rating: 602.85 &! TDD within limit it is necessary to have a 7th harmonic filter. and Reactor rating: 0.0152 H, 4.16 kV / phaseThe harmonic voltage distortion at PCC is 2.67 % .Overall TDD comes as 4%. © 2011 ACEEE 5 DOI: 01.IJEPE.02.01.25
  • 6. ACEEE Int. J. on Electrical and Power Engineering, Vol. 02, No. 01, Feb 2011 The analytical solution obtained for the TDD is compared - The voltage distortion factor is reduced from with the simulation results in Table VI. 11.3% to 6.4 %. 7) Effective Reactive power provided by filter and net power - The 7th harmonic current TDD is reduced to factor improvement 0.64 from 11.6 analytically and simulation Finally the effective reactive power contribution of each shows the reduction to 0.9. star connected filter at fundamental frequency is 3) After installation of high pass filter 5th ST Filter - 265.7 kVAr A. analytical calculation shows that the overall TDD 7th ST Filter – 77 kVAr is reduced to 4% from 35.5%. The voltage distortion HP Filter - 75 kVAr factor is reduced from 11.3 % to 3 %. Total compensation provided is - 417.7 kVAr. Net Power B. Simulation results shows that the overall TDD is Factor improvement after installation of filter will be 0.99 reduced to 5.5 % from 35.5 %.The voltage i.e. near unity. distortion factor is reduced from 11.3% to 4%. VII.SIMULATION OF SYSTEM AND SIMULATION RESULTS Thus, the TDD at PCC is within the limit specified by IEEE standard 519 -1992.[9] The single line diagram of the system is simulated using MATLAB ® /SIMULINK - platform to study the VIII.CONCLUSION distortions in the voltage and current waveforms due to presence of nonlinear load in the system .The actual system This paper has presented a harmonic mitigation study in can be modeled with a high degree of accuracy in this the simple distribution system. An investigation has been package. It provides a user interactive platform and a wide carried out to examine the effectiveness of filters using the variety of numerical algorithms. two types of passive filters namely, single tuned and High Fig. 6 shows the system modeled in SIMULINK. The pass filters in eliminating harmonics. system consists of six pulse Rectifier model as the nonlinear REFERENCES load to the system, gate signal generator block and three phase source. [1] Subrata De, and G. Bhuvaneswari, “Investigations on the Fig. 7 shows simulation results of distortions present in impact of VAR rating and quality factor on the effectiveness phase voltage and phase currents with and without filter of a shunt passive filter,” 0-7803-9525-5/06J. 2006 IEEE. assembly. [2] J. C. Das, “Power System Analysis-Short-circuit, Load Flow and Harmonics”. New York: Marcel Dekker, 2002. The comparison of simulation and analytical results is as [3] J. Arrillaga, D. A. Bradley, and P. S. Bodger, “Power System follows- Harmonics” New York: Wiley, 1985 1)With installation of 5th harmonic filter assembly: [4] D. A. Gonzalez and J. C. McCall, “Design of filters to reduce A. Analytical calculation harmonic - Overall TDD reduction to 13.88 % from distortion in industrial power systems,” IEEE Trans. Ind. Applicat., 35.5%. vol. - The voltage distortion factor is reduced from IA-23, pp. 504–512, May/June 1987 11.3 % to 6.75%. [5] J. C. Das,” Passive Filter Potentialities and Limitations” IEEE B. Simulation results show that The overall TDD is Transactions on Industry Applications, Vol 40, No.. 1, Jan / Feb 2004 reduced to 14.8 % from 35.5%. [6] Dugan, E.C., McGranagham, M.F., Santoso, S., Beaty, H.W., 2) With installation of 5th and 7th harmonic filters: “Elecirical power systems quality”, McGraw-Hill, 2002 [7] IEEE Standard for Shunt Power Capacitors. IEEE Standard A. Analytical calculation - Overall TDD is reduced 18- 1992 to 8.4% from 35.5%. [8] “IEEE Guide for Application and Specification of Harmonic - The voltage distortion factor is reduced from Filters”, IEEE Std. 1531-2003 11.3% to 5.04%. [9] Recommended Practice and Requirements for Harmonic Control in Electrical Systems, IEEE Std. 519-1992. B. Simulation results - The overall TDD is reduced to 10.55 % from 35.5 %. © 2011 ACEEE 6 DOI: 01.IJEPE.02.01.25