IMEKO International Conference on
Metrology for Archaeology and Cultural Heritage
Lecce, Italy, October 23-25, 2017
Non-destructive tests for structural diagnosis of
the so-called Temple of Minerva Medica, Rome
Ivan Roselli1
, Angelo Tatì1
, Vincenzo Fioriti1
, Irene Bellagamba1
, Marialuisa Mongelli1
,
Mariarosaria Barbera2
, Marina Magnani Cinetti2
, Roberto Romano1
, Gerardo De Canio1
1
ENEA Casaccia Research Center, via Anguillarese 301 – 00123 Rome, Italy, ivan.roselli@enea.it
2
MIBACT, Soprintendenza speciale per i Beni Archeologici di Roma, Piazza dei Cinquecento, 67 –
00185 Rome, Italy
Abstract – The structural diagnosis of historic
buildings should integrate on-site and in-the-
laboratory experimental testing techniques, with no
harmful effects on the structural and aesthetic health
of the monument. In the present paper several non-
destructive tests (NDTs) were conducted to study an
archeological ruined building located in Rome, the so-
called Temple of Minerva Medica. In particular, the
experimental program comprised 3D geometric
surveys by laser scanning and stereo-
photogrammetry, thermal imaging, microclimatic
parameters acquisition, sonic testing and ambient
vibration monitoring. The above NDTs were executed
from summer of 2016 until summer of 2017, in order
to investigate the seasonal effects and/or the eventual
changes in the structural response of the building,
after the 2016-2017 Central Italy seismic sequence.
The acquired data were stored in a repository that is
available to the end-users for future studies and
analyses.
I. INTRODUCTION
The restoration and conservation of the archeological
heritage is a very crucial task in Italy, where the
concentration of historical and monumental buildings in
urban areas is the greatest worldwide, as documented by
UNESCO. In particular, in big cities rich in
archaeological assets, such as Rome, historic buildings
are subjected to potential degradation phenomena caused
by urban pollution, traffic vibrations and excavation
works that might threaten their structural stability.
Moreover, natural hazards, such as earthquakes can add
further concerns in seismic areas, like central Italy.
Consequently, a vital step to their preservation is a deep
knowledge of the mechanical behavior of such structures
through the study of their geometry, material properties
and state of conservation.
The relevance of obtaining data on the mechanical
behavior of historic buildings can guide in the choice of
appropriate mathematical models for structural analysis
and in the proposal of repair and strengthening
techniques. Such diagnosis of the state of the structure
should result from both on-site and in-the-laboratory
experimental investigation with no impact on structural
health and aesthetic of the monument. In this context,
non-destructive tests (NDTs) for structural diagnosis have
changed the way engineers approach structural
assessment studies, as a wide range of NDTs and in situ
diagnostics are available and becoming a common
component of structural evaluation projects.
In the present paper a variety of NDTs able to provide
valuable information on the mechanical behavior and
state of conservation of the structure were applied to the
so-called Temple of Minerva Medica. The experimental
program was conducted within the CO.B.RA. project,
which focuses on the development of advanced
technologies and methods for the conservation of cultural
heritage assets.
A particular focus was put on the dynamic
characterization of the main hall, as it is subjected to
relevant vibration intensity induced by the surrounding
tramways and railways traffic [1]. Firstly, a 3D geometric
reconstruction of the monument was obtained by
integrating information from laser scanner surveys and
stereo-photogrammetry. Subsequently, thermographic
images by infrared camera were collected, as well as
microclimatic parameters, such as air temperature and
humidity, in order to evaluate the thermal behavior of the
masonry, which is known to influence also the dynamic
behavior of the structure. Moreover, sonic testing was
performed to investigate the interior consistency of the
pillars masonry. Finally, ambient vibration acquisitions
were carried out to characterize the dynamic response of
the structure and its dependency on the microclimatic
conditions.
All the above parameters were stored into an integrated
information system (repository) that preserves the
collected data able to characterize the monument in terms
of dynamic response and mechanical properties.
II. THE MONUMENT
The studied monument is an ancient ruined building
located in the city-center of Rome, on the Esquiline Hill,
between the via Labicana and Aurelian Walls.
Fig. 1. View from North of the so-called Temple of
Minerva Medica.
In 16th century, it was erroneously interpreted as a
temple dedicated to Minerva Medica (“Minerva the
Doctor”), as mentioned by Cicero and other ancient
sources. Recent studies hypothesized the structure might
be an ancient nymphaeum of Imperial Rome (early 4th
century A.D.), probably part of the Horti Liciniani, but
attribution is still discussed [2].
After initial misinterpretation it was widely known, and
still today, as the Temple of Minerva Medica. The
structure is a majestic building with decagonal polylobate
plan, a diameter of 25 m and a overall height originally of
32 m, currently reduced to only 24 m after the dome
partial collapses during the centuries (Fig. 1).
Initially, the structure was entirely built using the
typical roman technique called opus latericium. Soon
after the construction the building presented structural
problems. Consequently, it was restored and reinforced
through works in opus mixtum of tuff bricks and Roman
bricks. Also, the lateral niches were closed and some
walls with the function of buttresses were built in the
southeast side of the monument. The need for such
additional buttresses testify the presence of structural
weakness in this part of the structure. As a confirmation,
the major historically documented damages were
concentrated at the south side, where recent
investigations indicated the presence of weaker
foundations [2]. After several collapses during centuries
of abandon, a major restoration intervention was carried
out in 1846 for the reconstruction of first floor arcade of
the southeast side. More recently, another relevant
restoration intervention reconstructed also the upper floor
arcade of the southeast side in 2012-2013. As a
consequence of such a long history of collapses and
reconstructions the current masonry results quite
heterogeneous in materials and shapes.
III. NON-DESTRUCTIVE TESTING PROGRAM
The NDTs were executed in a period of time that went
from summer of 2016 until summer of 2017, in order to
investigate the seasonal effects and/or the eventual
changes in the structural response of the building, in
consideration also of the possible effects of the seismic
sequence that hit Central Italy from August 2016 to
February 2017.
The experimental program can be summarized as
follows:
 Geometric survey;
 Thermal images and microclimatic parameters;
 Sonic testing;
 Ambient vibration acquisitions.
A. Geometric survey
Laser scanner acquisitions and photogrammetric
mapping for 3D reconstruction and geometry survey of
the structure were performed. The laser scanner
measurements were acquired in summer of 2016 (August
5th
) and in winter of 2016 (December 20th
), when air
temperatures were supposed to be the highest and the
lowest of the year, respectively.
Both acquisitions were carried out in late morning at
similar daytime in order to analyze the seasonal effects
neglecting the day/night cycle effect in terms of thermal
expansion phenomena. In particular, they were performed
using a Riegl Z360 equipped with a Nikon D100 digital
camera (see Fig. 2a). The instrument nominal angular
resolution is 0.0025° horizontal and 0.002° vertical, while
range accuracy can achieve +/- 6 mm. Retro-reflecting
targets fixed at each pillar at the height 2.5 m from
ground level were used as reference positions in order to
compare the two surveys.
Such a detailed 3D geometrical survey was the base
both for measurements of distances between walls at
unreachable points and for the mathematical modelling
for successive structural analyses (see Fig. 2b). For
instance, several internal walls distances from summer
and winter surveys were compared in order to assess the
effects of masonry thermal expansion.
In addition, also a stereo-photogrammetric survey was
executed with the use of a Nikon D60 camera and
comprised about 500 digital images (10 Mpx each). The
above images were post-processed with Structure from
Motion (SfM) methodology [3].
Fig. 2. Laser scanner setup (a). 3D reconstruction of the
monument by acquisitions in summer 2016 (b).
a) b)
Fig. 3. Decagonal plan of the main hall.
Fig. 4. Thermal image of upper floor arcade on the
northwest side (S3) of the monument.
Data processing for SfM was performed by Agisoft
PhotoScan software via ENEAGRID, available on
CRESCO (Computational Research Center for Complex
Systems) HPC infrastructure [4].
A dense cloud of 30 million points was obtained and
mesh returned more than 200,000 tria element.
Stereo-photogrammetry by SfM is complementary to
laser scanning, since it is less accurate in 3D geometry
reconstruction, but is able to provide more detailed
documentation of the crack pattern [5].
B. Thermal images and microclimatic parameters
Thermographic data of the inner walls of the monument
were acquired using a Flir T440 thermal infrared camera
from the center of the main hall at around midday. The
building images were subdivided in 10 ground floor and
10 upper floor views, corresponding to the sides of the
decagonal plan (Fig. 3). The thermal images were
captured on the same two dates as the laser scanner
surveys and in August 2017.
The thermographic measurements were calibrated by
correlation with the temperatures resulting from two
microclimatic monitoring stations, which provided also
the air humidity and pressure data. In particular, air
temperature and humidity were monitored by two
MSR145 mini data loggers positioned on the west side
(pillar P4) and on the east side (pillar P8), respectively.
A difference of about 30° C was recorded between the
maximum temperature values of the masonry in August
and in December surveys.
A temperature diagram was obtained as a function of
the walls solar exposure (ground and upper floor sides)
for all three acquired seasons, putting into evidence the
thermal differences between walls. The temperature of
the walls was higher in the upper arcade and particularly
in sides S1, S2 and S3 (northwestern sides of the
monument), where temperatures reached 40° C in August
(Fig. 4), as a result of the direct solar beam exposure of
their upper inner wall-faces due to the big hole left by the
collapsed dome. Walls on the eastern and southern sides
(S7, S8, S9 and S10) revealed maximum values of only
34-35° C. In December the walls temperature resulted
more uniform, increasing only slightly, from 8° C at the
bottom to 12° C at the upper arcade.
C. Sonic testing
The base of each pillar was investigated through sonic
tests in order to verify the state of compacity of the
masonry and to estimate its compression strength. The
sonic tests were executed in February 2017 using the
sonic transmission procedure, i.e. through the thickness
of the wall [6]. This technique is especially useful for
investigating heterogeneities in construction materials,
such as historic masonry, allowing the identification of
layering of the sections, the presence of voids, cavities
and anomalies in material density. Equipment comprised
an instrumented hammer with a PCB ICP accelerometer,
as well as the probe, both cabled to the acquisition unit.
Data were acquired with a sampling frequency of 500
kHz. the sonic measurements was made reference to the
UNI 10627-1997 [7].
In (Fig. 5) a diagram showing the sonic test velocity
recorded at each pillar, labeled as in Fig 3, in function of
the distance d from internal pillar face (see measurement
configurations in Fig. 6), is depicted. Initial values (d = 0)
tend to decrease at higher values of d, indicating poorer
material properties of the core (opus caementicium) with
respect to the wall-face brickwork layers (opus latericium
or mixtum). The low initial value of pillar P4 is due to a
crack in the wall-face layer. The lowest values were
measured in pillars P9 and P10 at d in the range 80-120
cm. For d > 120 cm the lowest values were obtained for
pillars P1 and P2, which were rebuilt in mid-19th
century.
D. Ambient vibration acquisitions
Ambient vibrations were acquired by digital recorders
equipped with triaxial velocimeters provided with a GPS
antenna for time synchronization.
Fig. 5. Sonic test velocity recorded at each pillar in
function of the distance from internal face (d).
Fig. 6. Sonic test configurations at pillar P1.
Data were acquired both at ground level, to obtain
indications on the points where the base excitation due to
the nearby traffic (road, trains and trams) is stronger, and
on the façade, to assess the amplification to the structure
and the dynamic behavior of the building. Each position
was acquired for at least 20 minutes at a sampling
frequency of 200 Hz.
Vibrations were acquired in four sessions carried out on
separate dates over a one-year span in order to evaluate
the seasonal effects, listed in chronological order as
follows:
 Session 1: summer 2016 (4 July 2016);
 Session 2: winter 2017 (1 February 2017);
 Session 3: spring 2017 (19 April 2017);
 Session 4: summer 2017 (13 July 2017).
Several time/frequency domain calculations and modal
analysis techniques were applied for mutual validation of
results. In particular, the Frequency Response Function
(FRF) was calculated using the Transmissibility Function
H [8], the Frequency Domain Decomposition (FDD), the
Enhanced Frequency Domain Decomposition (EFDD),
the Cristal Clear Subspace Stochastic Identification (CCI-
SSI) [9] and the Horizontal Vertical Spectral Ratios
(HVSR) [10] were calculated at windows and on top of
the façade.
Fig. 7. Modal frequencies of the monument from July
2016 (session 1) to July 2017 (Session 4).
Fig. 8. Influence of air temperature on the second modal
frequency of the monument.
In Fig. 7 the average values of the calculated modal
frequencies are depicted for each acquisition session,
demonstrating the substantial seasonal stability of the
dynamic response of the structure. In fact, the modal
frequencies slightly increase with the temperature (Fig.
8), but recorded variations are limited in the range of 2-6
%. A remarkable correlation was found between modal
frequencies and air temperature, as showed in Fig. 8.
E. Repository
The architecture of COBRA repository is designed so
that acquired data are transferred to a storage area by
synchronization with the dedicated OwnCloud partition
specifically created for the project. This mechanism runs
automatically allowing researchers to acquire their data in
the usual modes and formats. In this way the great
amount of data produced during the surveys is stored in
full safety and integrity.
Stored data can be permanently retrieved by the
authorized users. A staging area is provided, where raw
data can be enriched with metadata and then be stored in
the repository as structured data to be possibly submitted
to dedicated analysis software. Further, a software system
that allows real-time remote monitoring of monument’s
parameters and image flows was developed.
The CO.B.RA. repository is accessible upon
registration from the CO.B.RA. project site
(http://cobra.enea.it/). The end-user is provided with
credentials to freely download data of the monitoring
campaigns and other useful information on the
monument.
IV. CONCLUSIONS
In the present paper the results of a variety of NDT
techniques applied to the study of the so-called Temple of
Minerva Medica are shown. The several investigated
physical properties of the monument were integrated in
an effective database for a comprehensive understanding
of the overall structural behavior. On the one hand, the
influence of the geometry and of the environmental
conditions (especially, in terms of solar exposure) on the
thermal behavior of the structure was highlighted. On the
other hand, the thermal properties resulted the main factor
affecting the dynamic behavior of the structure, as proved
by slight variations of modal parameters highly correlated
with the air temperature. Consequently, no evidence was
found of any relevant impact of the Central Italy seismic
sequence on the dynamic behavior of the monument.
The mechanical properties of the masonry, investigated
by sonic tests and the surveyed crack pattern will be
fundamental for the production of representative
numerical models, e.g. finite element models (FEMs), to
be used for future structural analysis.
REFERENCES
[1] I.Roselli, V.Fioriti, I.Bellagamba, M.Mongelli,
A.Tatì, M.Barbera, M.Magnani Cianetti, G.De
Canio, “Impact of traffic vibration on the temple of
Minerva Medica, Rome: preliminary study within
the CO.B.RA. project”, International Journal of
Heritage Architecture, vol.2, No.1, 2018, pp.102-
114.
[2] M.Barbera, M.Magnani Cianetti, S.Barrano, “Da
Massenzio a Costantino: le indagini in corso nel c. d.
tempio di Minerva Medica”, Proc. of the
International Conference of CISEM - La villa
restaurata e i nuovi studi sull'edilizia residenziale
tardoantica (in Italian), 2014, pp.1613-1624.
[3] M.Mongelli, G.De Canio, I.Roselli, M.Malena,
A.Nacuzi, G.De Felice, “3D photogrammetric
reconstruction by drone scanning for FE analysis
and crack pattern mapping of the bridge of the
towers, Spoleto”, Key Engineering Materials,
vol.747, July 2017, pp.423-430.
[4] G.Ponti, “The role of medium size facilities in the
HPC ecosystem: the case of the new CRESCO4
cluster integrated in the ENEAGRID infrastructure”,
Proc. of the International Conference on High
Performance Computing and Simulation (HPCS),
2014.
[5] M.Mongelli, G.De Canio, I.Roselli, M.Malena,
A.Nacuzi, G.de Felice, “3D Photogrammetric
Reconstruction by Drone Scanning for FE Analysis
and Crack Pattern Mapping of the Bridge of the
Towers, Spoleto”, Key Engineering Materials,
vol.747, pp.423-430.
[6] S.Hum-Hartley, “Nondestructive Testing for
Heritage Structures”, Bulletin of the Association for
Preservation Technology, vol.10, No.3, 1978, pp.4-
20.
[7] UNI 10627-1997. Computed tomography systems
for structural investigations.
[8] C.W.De Silva, “Vibration and Shock Handbook”,
CRC Press, 2005.
[9] G.De Canio, M.Mongelli, I.Roselli, A.Tatì,
D.Addessi, M.Nocera, D.Liberatore, “Numerical and
operational modal analyses of the Ponte delle Torri,
Spoleto, Italy”, Proc. of the 10th International
Conference on Structural Analysis of Historical
Constructions (SAHC), 2016, pp.752-758.
[10] M.R.Gallipoli, M.Mucciarelli, M.Vona, “Empirical
estimate of fundamental frequencies and damping
for Italian buildings”, Earthquake Engineering &
Structural Dynamics, vol.38, No.8, 2009, pp.973–
988.

Contenu connexe

Similaire à Non-destructive tests

Dynamics analysis of structures subjected to earthquake load 53037
Dynamics analysis of structures subjected to earthquake load 53037Dynamics analysis of structures subjected to earthquake load 53037
Dynamics analysis of structures subjected to earthquake load 53037EditorIJAERD
 
Mms lab 2011
Mms lab 2011Mms lab 2011
Mms lab 2011MMSLAB
 
Monte Carlo simulation for seismic analysis of a long span suspension bridge
Monte Carlo simulation for seismic analysis of a long span suspension bridgeMonte Carlo simulation for seismic analysis of a long span suspension bridge
Monte Carlo simulation for seismic analysis of a long span suspension bridgeFranco Bontempi
 
Monte Carlo simulation for seismic analysis of a long span suspension bridge
Monte Carlo simulation for seismic analysis of a long span suspension bridgeMonte Carlo simulation for seismic analysis of a long span suspension bridge
Monte Carlo simulation for seismic analysis of a long span suspension bridgeStroNGER2012
 
Urban Transport Vibation
Urban Transport VibationUrban Transport Vibation
Urban Transport Vibationmauvet52
 
Earthquake Analysis of RCC structure by using Pushover Analysis
Earthquake Analysis of RCC structure by using Pushover AnalysisEarthquake Analysis of RCC structure by using Pushover Analysis
Earthquake Analysis of RCC structure by using Pushover AnalysisIRJET Journal
 
Seismic vulnerability assessment using field survey and Remote Sensing techni...
Seismic vulnerability assessment using field survey and Remote Sensing techni...Seismic vulnerability assessment using field survey and Remote Sensing techni...
Seismic vulnerability assessment using field survey and Remote Sensing techni...Beniamino Murgante
 
Seismic Vulnerability Assessment Using Field Survey and Remote Sensing Techni...
Seismic Vulnerability Assessment Using Field Survey and Remote Sensing Techni...Seismic Vulnerability Assessment Using Field Survey and Remote Sensing Techni...
Seismic Vulnerability Assessment Using Field Survey and Remote Sensing Techni...Maurizio Pollino
 
MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...
MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...
MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...Mintu Choudhury
 
Motion detection applied to
Motion detection applied toMotion detection applied to
Motion detection applied toijcsa
 
EFFECT OF SEISMIC LOAD ON REINFORCED CONCRETE MULTISTORY BUILDING FROM ECONOM...
EFFECT OF SEISMIC LOAD ON REINFORCED CONCRETE MULTISTORY BUILDING FROM ECONOM...EFFECT OF SEISMIC LOAD ON REINFORCED CONCRETE MULTISTORY BUILDING FROM ECONOM...
EFFECT OF SEISMIC LOAD ON REINFORCED CONCRETE MULTISTORY BUILDING FROM ECONOM...IAEME Publication
 
Pellegrini presentation
Pellegrini presentationPellegrini presentation
Pellegrini presentationMMSLAB
 
Kilimanjaro ice core records: Evidence of holocene climate in tropical Africa
Kilimanjaro ice core records: Evidence of holocene climate in tropical AfricaKilimanjaro ice core records: Evidence of holocene climate in tropical Africa
Kilimanjaro ice core records: Evidence of holocene climate in tropical AfricaSimoneBoccuccia
 
TINCE2016 - Post-Fukushima seismic re-assessment of French Reactor Building ...
TINCE2016 -  Post-Fukushima seismic re-assessment of French Reactor Building ...TINCE2016 -  Post-Fukushima seismic re-assessment of French Reactor Building ...
TINCE2016 - Post-Fukushima seismic re-assessment of French Reactor Building ...Gildas POTIN
 

Similaire à Non-destructive tests (20)

Dynamics analysis of structures subjected to earthquake load 53037
Dynamics analysis of structures subjected to earthquake load 53037Dynamics analysis of structures subjected to earthquake load 53037
Dynamics analysis of structures subjected to earthquake load 53037
 
Mms lab 2011
Mms lab 2011Mms lab 2011
Mms lab 2011
 
Monte Carlo simulation for seismic analysis of a long span suspension bridge
Monte Carlo simulation for seismic analysis of a long span suspension bridgeMonte Carlo simulation for seismic analysis of a long span suspension bridge
Monte Carlo simulation for seismic analysis of a long span suspension bridge
 
Monte Carlo simulation for seismic analysis of a long span suspension bridge
Monte Carlo simulation for seismic analysis of a long span suspension bridgeMonte Carlo simulation for seismic analysis of a long span suspension bridge
Monte Carlo simulation for seismic analysis of a long span suspension bridge
 
Urban Transport Vibation
Urban Transport VibationUrban Transport Vibation
Urban Transport Vibation
 
appr technologies.pdf
appr technologies.pdfappr technologies.pdf
appr technologies.pdf
 
Earthquake Analysis of RCC structure by using Pushover Analysis
Earthquake Analysis of RCC structure by using Pushover AnalysisEarthquake Analysis of RCC structure by using Pushover Analysis
Earthquake Analysis of RCC structure by using Pushover Analysis
 
Seismic vulnerability assessment using field survey and Remote Sensing techni...
Seismic vulnerability assessment using field survey and Remote Sensing techni...Seismic vulnerability assessment using field survey and Remote Sensing techni...
Seismic vulnerability assessment using field survey and Remote Sensing techni...
 
Seismic Vulnerability Assessment Using Field Survey and Remote Sensing Techni...
Seismic Vulnerability Assessment Using Field Survey and Remote Sensing Techni...Seismic Vulnerability Assessment Using Field Survey and Remote Sensing Techni...
Seismic Vulnerability Assessment Using Field Survey and Remote Sensing Techni...
 
K013139190
K013139190K013139190
K013139190
 
MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...
MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...
MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...
 
Motion detection applied to
Motion detection applied toMotion detection applied to
Motion detection applied to
 
55_ESPOSITO_RINAUDO
55_ESPOSITO_RINAUDO55_ESPOSITO_RINAUDO
55_ESPOSITO_RINAUDO
 
Bridge pgd sbornik 2017 web
Bridge pgd sbornik 2017 webBridge pgd sbornik 2017 web
Bridge pgd sbornik 2017 web
 
Iw3315041514
Iw3315041514Iw3315041514
Iw3315041514
 
EFFECT OF SEISMIC LOAD ON REINFORCED CONCRETE MULTISTORY BUILDING FROM ECONOM...
EFFECT OF SEISMIC LOAD ON REINFORCED CONCRETE MULTISTORY BUILDING FROM ECONOM...EFFECT OF SEISMIC LOAD ON REINFORCED CONCRETE MULTISTORY BUILDING FROM ECONOM...
EFFECT OF SEISMIC LOAD ON REINFORCED CONCRETE MULTISTORY BUILDING FROM ECONOM...
 
Pellegrini presentation
Pellegrini presentationPellegrini presentation
Pellegrini presentation
 
Tallbuildings_2013.pdf
Tallbuildings_2013.pdfTallbuildings_2013.pdf
Tallbuildings_2013.pdf
 
Kilimanjaro ice core records: Evidence of holocene climate in tropical Africa
Kilimanjaro ice core records: Evidence of holocene climate in tropical AfricaKilimanjaro ice core records: Evidence of holocene climate in tropical Africa
Kilimanjaro ice core records: Evidence of holocene climate in tropical Africa
 
TINCE2016 - Post-Fukushima seismic re-assessment of French Reactor Building ...
TINCE2016 -  Post-Fukushima seismic re-assessment of French Reactor Building ...TINCE2016 -  Post-Fukushima seismic re-assessment of French Reactor Building ...
TINCE2016 - Post-Fukushima seismic re-assessment of French Reactor Building ...
 

Plus de mauvet52

Sostituzione Cassonetti Lista Strade.pdf
Sostituzione Cassonetti Lista Strade.pdfSostituzione Cassonetti Lista Strade.pdf
Sostituzione Cassonetti Lista Strade.pdfmauvet52
 
Poleis_Liberazioni2023_Programma.pdf
Poleis_Liberazioni2023_Programma.pdfPoleis_Liberazioni2023_Programma.pdf
Poleis_Liberazioni2023_Programma.pdfmauvet52
 
CieloSopraEsquilino-Numero46.pdf
CieloSopraEsquilino-Numero46.pdfCieloSopraEsquilino-Numero46.pdf
CieloSopraEsquilino-Numero46.pdfmauvet52
 
comunicato stampa press release NASI PER L'ARTE .pdf
comunicato stampa press release NASI PER L'ARTE .pdfcomunicato stampa press release NASI PER L'ARTE .pdf
comunicato stampa press release NASI PER L'ARTE .pdfmauvet52
 
OS_n._26_del_24_marzo_2023.pdf
OS_n._26_del_24_marzo_2023.pdfOS_n._26_del_24_marzo_2023.pdf
OS_n._26_del_24_marzo_2023.pdfmauvet52
 
OrdinanzaDomenicaecologica26marzo_24_2023.pdf
OrdinanzaDomenicaecologica26marzo_24_2023.pdfOrdinanzaDomenicaecologica26marzo_24_2023.pdf
OrdinanzaDomenicaecologica26marzo_24_2023.pdfmauvet52
 
CieloSopraEsquilino-Numero45.pdf
CieloSopraEsquilino-Numero45.pdfCieloSopraEsquilino-Numero45.pdf
CieloSopraEsquilino-Numero45.pdfmauvet52
 
OS_domenicaecologica8gennaio.pdf
OS_domenicaecologica8gennaio.pdfOS_domenicaecologica8gennaio.pdf
OS_domenicaecologica8gennaio.pdfmauvet52
 
OS__n._191_del_2_dicembre_2022.pdf
OS__n._191_del_2_dicembre_2022.pdfOS__n._191_del_2_dicembre_2022.pdf
OS__n._191_del_2_dicembre_2022.pdfmauvet52
 
CieloSopraEsquilino-Numero44.pdf
CieloSopraEsquilino-Numero44.pdfCieloSopraEsquilino-Numero44.pdf
CieloSopraEsquilino-Numero44.pdfmauvet52
 
Ordinanza_N._187_18novembre2022_domenica_20novembre2022.pdf
Ordinanza_N._187_18novembre2022_domenica_20novembre2022.pdfOrdinanza_N._187_18novembre2022_domenica_20novembre2022.pdf
Ordinanza_N._187_18novembre2022_domenica_20novembre2022.pdfmauvet52
 
Tesi Giulia Muccari Battistelli_Cabina elettrica e Torre dell'acqua Via Gioli...
Tesi Giulia Muccari Battistelli_Cabina elettrica e Torre dell'acqua Via Gioli...Tesi Giulia Muccari Battistelli_Cabina elettrica e Torre dell'acqua Via Gioli...
Tesi Giulia Muccari Battistelli_Cabina elettrica e Torre dell'acqua Via Gioli...mauvet52
 
Giovani-Memoria_Programma_orari_Novembre2022.pdf
Giovani-Memoria_Programma_orari_Novembre2022.pdfGiovani-Memoria_Programma_orari_Novembre2022.pdf
Giovani-Memoria_Programma_orari_Novembre2022.pdfmauvet52
 
Rosa Pierno Comunicato stampa .pdf
Rosa Pierno Comunicato stampa .pdfRosa Pierno Comunicato stampa .pdf
Rosa Pierno Comunicato stampa .pdfmauvet52
 
acquarioott22.pdf
acquarioott22.pdfacquarioott22.pdf
acquarioott22.pdfmauvet52
 
CieloSopraEsquilino-Numero43.pdf
CieloSopraEsquilino-Numero43.pdfCieloSopraEsquilino-Numero43.pdf
CieloSopraEsquilino-Numero43.pdfmauvet52
 
I_cantieri_delle_cappelle_Sistina_e_Paol.pdf
I_cantieri_delle_cappelle_Sistina_e_Paol.pdfI_cantieri_delle_cappelle_Sistina_e_Paol.pdf
I_cantieri_delle_cappelle_Sistina_e_Paol.pdfmauvet52
 
Circolare 61-2022_DGMUSEI.pdf
Circolare 61-2022_DGMUSEI.pdfCircolare 61-2022_DGMUSEI.pdf
Circolare 61-2022_DGMUSEI.pdfmauvet52
 
CS-Coesione.pdf
CS-Coesione.pdfCS-Coesione.pdf
CS-Coesione.pdfmauvet52
 
Stati Generali del Patrimonio Industriale PDF contributo Magnani-Gargiulo.pdf
Stati Generali del Patrimonio Industriale PDF contributo Magnani-Gargiulo.pdfStati Generali del Patrimonio Industriale PDF contributo Magnani-Gargiulo.pdf
Stati Generali del Patrimonio Industriale PDF contributo Magnani-Gargiulo.pdfmauvet52
 

Plus de mauvet52 (20)

Sostituzione Cassonetti Lista Strade.pdf
Sostituzione Cassonetti Lista Strade.pdfSostituzione Cassonetti Lista Strade.pdf
Sostituzione Cassonetti Lista Strade.pdf
 
Poleis_Liberazioni2023_Programma.pdf
Poleis_Liberazioni2023_Programma.pdfPoleis_Liberazioni2023_Programma.pdf
Poleis_Liberazioni2023_Programma.pdf
 
CieloSopraEsquilino-Numero46.pdf
CieloSopraEsquilino-Numero46.pdfCieloSopraEsquilino-Numero46.pdf
CieloSopraEsquilino-Numero46.pdf
 
comunicato stampa press release NASI PER L'ARTE .pdf
comunicato stampa press release NASI PER L'ARTE .pdfcomunicato stampa press release NASI PER L'ARTE .pdf
comunicato stampa press release NASI PER L'ARTE .pdf
 
OS_n._26_del_24_marzo_2023.pdf
OS_n._26_del_24_marzo_2023.pdfOS_n._26_del_24_marzo_2023.pdf
OS_n._26_del_24_marzo_2023.pdf
 
OrdinanzaDomenicaecologica26marzo_24_2023.pdf
OrdinanzaDomenicaecologica26marzo_24_2023.pdfOrdinanzaDomenicaecologica26marzo_24_2023.pdf
OrdinanzaDomenicaecologica26marzo_24_2023.pdf
 
CieloSopraEsquilino-Numero45.pdf
CieloSopraEsquilino-Numero45.pdfCieloSopraEsquilino-Numero45.pdf
CieloSopraEsquilino-Numero45.pdf
 
OS_domenicaecologica8gennaio.pdf
OS_domenicaecologica8gennaio.pdfOS_domenicaecologica8gennaio.pdf
OS_domenicaecologica8gennaio.pdf
 
OS__n._191_del_2_dicembre_2022.pdf
OS__n._191_del_2_dicembre_2022.pdfOS__n._191_del_2_dicembre_2022.pdf
OS__n._191_del_2_dicembre_2022.pdf
 
CieloSopraEsquilino-Numero44.pdf
CieloSopraEsquilino-Numero44.pdfCieloSopraEsquilino-Numero44.pdf
CieloSopraEsquilino-Numero44.pdf
 
Ordinanza_N._187_18novembre2022_domenica_20novembre2022.pdf
Ordinanza_N._187_18novembre2022_domenica_20novembre2022.pdfOrdinanza_N._187_18novembre2022_domenica_20novembre2022.pdf
Ordinanza_N._187_18novembre2022_domenica_20novembre2022.pdf
 
Tesi Giulia Muccari Battistelli_Cabina elettrica e Torre dell'acqua Via Gioli...
Tesi Giulia Muccari Battistelli_Cabina elettrica e Torre dell'acqua Via Gioli...Tesi Giulia Muccari Battistelli_Cabina elettrica e Torre dell'acqua Via Gioli...
Tesi Giulia Muccari Battistelli_Cabina elettrica e Torre dell'acqua Via Gioli...
 
Giovani-Memoria_Programma_orari_Novembre2022.pdf
Giovani-Memoria_Programma_orari_Novembre2022.pdfGiovani-Memoria_Programma_orari_Novembre2022.pdf
Giovani-Memoria_Programma_orari_Novembre2022.pdf
 
Rosa Pierno Comunicato stampa .pdf
Rosa Pierno Comunicato stampa .pdfRosa Pierno Comunicato stampa .pdf
Rosa Pierno Comunicato stampa .pdf
 
acquarioott22.pdf
acquarioott22.pdfacquarioott22.pdf
acquarioott22.pdf
 
CieloSopraEsquilino-Numero43.pdf
CieloSopraEsquilino-Numero43.pdfCieloSopraEsquilino-Numero43.pdf
CieloSopraEsquilino-Numero43.pdf
 
I_cantieri_delle_cappelle_Sistina_e_Paol.pdf
I_cantieri_delle_cappelle_Sistina_e_Paol.pdfI_cantieri_delle_cappelle_Sistina_e_Paol.pdf
I_cantieri_delle_cappelle_Sistina_e_Paol.pdf
 
Circolare 61-2022_DGMUSEI.pdf
Circolare 61-2022_DGMUSEI.pdfCircolare 61-2022_DGMUSEI.pdf
Circolare 61-2022_DGMUSEI.pdf
 
CS-Coesione.pdf
CS-Coesione.pdfCS-Coesione.pdf
CS-Coesione.pdf
 
Stati Generali del Patrimonio Industriale PDF contributo Magnani-Gargiulo.pdf
Stati Generali del Patrimonio Industriale PDF contributo Magnani-Gargiulo.pdfStati Generali del Patrimonio Industriale PDF contributo Magnani-Gargiulo.pdf
Stati Generali del Patrimonio Industriale PDF contributo Magnani-Gargiulo.pdf
 

Dernier

VidaXL dropshipping via API with DroFx.pptx
VidaXL dropshipping via API with DroFx.pptxVidaXL dropshipping via API with DroFx.pptx
VidaXL dropshipping via API with DroFx.pptxolyaivanovalion
 
VIP Model Call Girls Hinjewadi ( Pune ) Call ON 8005736733 Starting From 5K t...
VIP Model Call Girls Hinjewadi ( Pune ) Call ON 8005736733 Starting From 5K t...VIP Model Call Girls Hinjewadi ( Pune ) Call ON 8005736733 Starting From 5K t...
VIP Model Call Girls Hinjewadi ( Pune ) Call ON 8005736733 Starting From 5K t...SUHANI PANDEY
 
BPAC WITH UFSBI GENERAL PRESENTATION 18_05_2017-1.pptx
BPAC WITH UFSBI GENERAL PRESENTATION 18_05_2017-1.pptxBPAC WITH UFSBI GENERAL PRESENTATION 18_05_2017-1.pptx
BPAC WITH UFSBI GENERAL PRESENTATION 18_05_2017-1.pptxMohammedJunaid861692
 
Chintamani Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore ...
Chintamani Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore ...Chintamani Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore ...
Chintamani Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore ...amitlee9823
 
Zuja dropshipping via API with DroFx.pptx
Zuja dropshipping via API with DroFx.pptxZuja dropshipping via API with DroFx.pptx
Zuja dropshipping via API with DroFx.pptxolyaivanovalion
 
Call Girls Hsr Layout Just Call 👗 7737669865 👗 Top Class Call Girl Service Ba...
Call Girls Hsr Layout Just Call 👗 7737669865 👗 Top Class Call Girl Service Ba...Call Girls Hsr Layout Just Call 👗 7737669865 👗 Top Class Call Girl Service Ba...
Call Girls Hsr Layout Just Call 👗 7737669865 👗 Top Class Call Girl Service Ba...amitlee9823
 
Junnasandra Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
Junnasandra Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...Junnasandra Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
Junnasandra Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...amitlee9823
 
Delhi Call Girls CP 9711199171 ☎✔👌✔ Whatsapp Hard And Sexy Vip Call
Delhi Call Girls CP 9711199171 ☎✔👌✔ Whatsapp Hard And Sexy Vip CallDelhi Call Girls CP 9711199171 ☎✔👌✔ Whatsapp Hard And Sexy Vip Call
Delhi Call Girls CP 9711199171 ☎✔👌✔ Whatsapp Hard And Sexy Vip Callshivangimorya083
 
Cheap Rate Call girls Sarita Vihar Delhi 9205541914 shot 1500 night
Cheap Rate Call girls Sarita Vihar Delhi 9205541914 shot 1500 nightCheap Rate Call girls Sarita Vihar Delhi 9205541914 shot 1500 night
Cheap Rate Call girls Sarita Vihar Delhi 9205541914 shot 1500 nightDelhi Call girls
 
April 2024 - Crypto Market Report's Analysis
April 2024 - Crypto Market Report's AnalysisApril 2024 - Crypto Market Report's Analysis
April 2024 - Crypto Market Report's Analysismanisha194592
 
BigBuy dropshipping via API with DroFx.pptx
BigBuy dropshipping via API with DroFx.pptxBigBuy dropshipping via API with DroFx.pptx
BigBuy dropshipping via API with DroFx.pptxolyaivanovalion
 
Call Girls Bannerghatta Road Just Call 👗 7737669865 👗 Top Class Call Girl Ser...
Call Girls Bannerghatta Road Just Call 👗 7737669865 👗 Top Class Call Girl Ser...Call Girls Bannerghatta Road Just Call 👗 7737669865 👗 Top Class Call Girl Ser...
Call Girls Bannerghatta Road Just Call 👗 7737669865 👗 Top Class Call Girl Ser...amitlee9823
 
Week-01-2.ppt BBB human Computer interaction
Week-01-2.ppt BBB human Computer interactionWeek-01-2.ppt BBB human Computer interaction
Week-01-2.ppt BBB human Computer interactionfulawalesam
 
Edukaciniai dropshipping via API with DroFx
Edukaciniai dropshipping via API with DroFxEdukaciniai dropshipping via API with DroFx
Edukaciniai dropshipping via API with DroFxolyaivanovalion
 
Data-Analysis for Chicago Crime Data 2023
Data-Analysis for Chicago Crime Data  2023Data-Analysis for Chicago Crime Data  2023
Data-Analysis for Chicago Crime Data 2023ymrp368
 
Call me @ 9892124323 Cheap Rate Call Girls in Vashi with Real Photo 100% Secure
Call me @ 9892124323  Cheap Rate Call Girls in Vashi with Real Photo 100% SecureCall me @ 9892124323  Cheap Rate Call Girls in Vashi with Real Photo 100% Secure
Call me @ 9892124323 Cheap Rate Call Girls in Vashi with Real Photo 100% SecurePooja Nehwal
 

Dernier (20)

VidaXL dropshipping via API with DroFx.pptx
VidaXL dropshipping via API with DroFx.pptxVidaXL dropshipping via API with DroFx.pptx
VidaXL dropshipping via API with DroFx.pptx
 
VIP Model Call Girls Hinjewadi ( Pune ) Call ON 8005736733 Starting From 5K t...
VIP Model Call Girls Hinjewadi ( Pune ) Call ON 8005736733 Starting From 5K t...VIP Model Call Girls Hinjewadi ( Pune ) Call ON 8005736733 Starting From 5K t...
VIP Model Call Girls Hinjewadi ( Pune ) Call ON 8005736733 Starting From 5K t...
 
BPAC WITH UFSBI GENERAL PRESENTATION 18_05_2017-1.pptx
BPAC WITH UFSBI GENERAL PRESENTATION 18_05_2017-1.pptxBPAC WITH UFSBI GENERAL PRESENTATION 18_05_2017-1.pptx
BPAC WITH UFSBI GENERAL PRESENTATION 18_05_2017-1.pptx
 
Chintamani Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore ...
Chintamani Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore ...Chintamani Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore ...
Chintamani Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore ...
 
Zuja dropshipping via API with DroFx.pptx
Zuja dropshipping via API with DroFx.pptxZuja dropshipping via API with DroFx.pptx
Zuja dropshipping via API with DroFx.pptx
 
Call Girls Hsr Layout Just Call 👗 7737669865 👗 Top Class Call Girl Service Ba...
Call Girls Hsr Layout Just Call 👗 7737669865 👗 Top Class Call Girl Service Ba...Call Girls Hsr Layout Just Call 👗 7737669865 👗 Top Class Call Girl Service Ba...
Call Girls Hsr Layout Just Call 👗 7737669865 👗 Top Class Call Girl Service Ba...
 
Abortion pills in Doha Qatar (+966572737505 ! Get Cytotec
Abortion pills in Doha Qatar (+966572737505 ! Get CytotecAbortion pills in Doha Qatar (+966572737505 ! Get Cytotec
Abortion pills in Doha Qatar (+966572737505 ! Get Cytotec
 
Junnasandra Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
Junnasandra Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...Junnasandra Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
Junnasandra Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
 
Delhi Call Girls CP 9711199171 ☎✔👌✔ Whatsapp Hard And Sexy Vip Call
Delhi Call Girls CP 9711199171 ☎✔👌✔ Whatsapp Hard And Sexy Vip CallDelhi Call Girls CP 9711199171 ☎✔👌✔ Whatsapp Hard And Sexy Vip Call
Delhi Call Girls CP 9711199171 ☎✔👌✔ Whatsapp Hard And Sexy Vip Call
 
Cheap Rate Call girls Sarita Vihar Delhi 9205541914 shot 1500 night
Cheap Rate Call girls Sarita Vihar Delhi 9205541914 shot 1500 nightCheap Rate Call girls Sarita Vihar Delhi 9205541914 shot 1500 night
Cheap Rate Call girls Sarita Vihar Delhi 9205541914 shot 1500 night
 
(NEHA) Call Girls Katra Call Now 8617697112 Katra Escorts 24x7
(NEHA) Call Girls Katra Call Now 8617697112 Katra Escorts 24x7(NEHA) Call Girls Katra Call Now 8617697112 Katra Escorts 24x7
(NEHA) Call Girls Katra Call Now 8617697112 Katra Escorts 24x7
 
April 2024 - Crypto Market Report's Analysis
April 2024 - Crypto Market Report's AnalysisApril 2024 - Crypto Market Report's Analysis
April 2024 - Crypto Market Report's Analysis
 
BigBuy dropshipping via API with DroFx.pptx
BigBuy dropshipping via API with DroFx.pptxBigBuy dropshipping via API with DroFx.pptx
BigBuy dropshipping via API with DroFx.pptx
 
Call Girls In Shalimar Bagh ( Delhi) 9953330565 Escorts Service
Call Girls In Shalimar Bagh ( Delhi) 9953330565 Escorts ServiceCall Girls In Shalimar Bagh ( Delhi) 9953330565 Escorts Service
Call Girls In Shalimar Bagh ( Delhi) 9953330565 Escorts Service
 
Call Girls Bannerghatta Road Just Call 👗 7737669865 👗 Top Class Call Girl Ser...
Call Girls Bannerghatta Road Just Call 👗 7737669865 👗 Top Class Call Girl Ser...Call Girls Bannerghatta Road Just Call 👗 7737669865 👗 Top Class Call Girl Ser...
Call Girls Bannerghatta Road Just Call 👗 7737669865 👗 Top Class Call Girl Ser...
 
Week-01-2.ppt BBB human Computer interaction
Week-01-2.ppt BBB human Computer interactionWeek-01-2.ppt BBB human Computer interaction
Week-01-2.ppt BBB human Computer interaction
 
Edukaciniai dropshipping via API with DroFx
Edukaciniai dropshipping via API with DroFxEdukaciniai dropshipping via API with DroFx
Edukaciniai dropshipping via API with DroFx
 
Data-Analysis for Chicago Crime Data 2023
Data-Analysis for Chicago Crime Data  2023Data-Analysis for Chicago Crime Data  2023
Data-Analysis for Chicago Crime Data 2023
 
CHEAP Call Girls in Saket (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICE
CHEAP Call Girls in Saket (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICECHEAP Call Girls in Saket (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICE
CHEAP Call Girls in Saket (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICE
 
Call me @ 9892124323 Cheap Rate Call Girls in Vashi with Real Photo 100% Secure
Call me @ 9892124323  Cheap Rate Call Girls in Vashi with Real Photo 100% SecureCall me @ 9892124323  Cheap Rate Call Girls in Vashi with Real Photo 100% Secure
Call me @ 9892124323 Cheap Rate Call Girls in Vashi with Real Photo 100% Secure
 

Non-destructive tests

  • 1. IMEKO International Conference on Metrology for Archaeology and Cultural Heritage Lecce, Italy, October 23-25, 2017 Non-destructive tests for structural diagnosis of the so-called Temple of Minerva Medica, Rome Ivan Roselli1 , Angelo Tatì1 , Vincenzo Fioriti1 , Irene Bellagamba1 , Marialuisa Mongelli1 , Mariarosaria Barbera2 , Marina Magnani Cinetti2 , Roberto Romano1 , Gerardo De Canio1 1 ENEA Casaccia Research Center, via Anguillarese 301 – 00123 Rome, Italy, ivan.roselli@enea.it 2 MIBACT, Soprintendenza speciale per i Beni Archeologici di Roma, Piazza dei Cinquecento, 67 – 00185 Rome, Italy Abstract – The structural diagnosis of historic buildings should integrate on-site and in-the- laboratory experimental testing techniques, with no harmful effects on the structural and aesthetic health of the monument. In the present paper several non- destructive tests (NDTs) were conducted to study an archeological ruined building located in Rome, the so- called Temple of Minerva Medica. In particular, the experimental program comprised 3D geometric surveys by laser scanning and stereo- photogrammetry, thermal imaging, microclimatic parameters acquisition, sonic testing and ambient vibration monitoring. The above NDTs were executed from summer of 2016 until summer of 2017, in order to investigate the seasonal effects and/or the eventual changes in the structural response of the building, after the 2016-2017 Central Italy seismic sequence. The acquired data were stored in a repository that is available to the end-users for future studies and analyses. I. INTRODUCTION The restoration and conservation of the archeological heritage is a very crucial task in Italy, where the concentration of historical and monumental buildings in urban areas is the greatest worldwide, as documented by UNESCO. In particular, in big cities rich in archaeological assets, such as Rome, historic buildings are subjected to potential degradation phenomena caused by urban pollution, traffic vibrations and excavation works that might threaten their structural stability. Moreover, natural hazards, such as earthquakes can add further concerns in seismic areas, like central Italy. Consequently, a vital step to their preservation is a deep knowledge of the mechanical behavior of such structures through the study of their geometry, material properties and state of conservation. The relevance of obtaining data on the mechanical behavior of historic buildings can guide in the choice of appropriate mathematical models for structural analysis and in the proposal of repair and strengthening techniques. Such diagnosis of the state of the structure should result from both on-site and in-the-laboratory experimental investigation with no impact on structural health and aesthetic of the monument. In this context, non-destructive tests (NDTs) for structural diagnosis have changed the way engineers approach structural assessment studies, as a wide range of NDTs and in situ diagnostics are available and becoming a common component of structural evaluation projects. In the present paper a variety of NDTs able to provide valuable information on the mechanical behavior and state of conservation of the structure were applied to the so-called Temple of Minerva Medica. The experimental program was conducted within the CO.B.RA. project, which focuses on the development of advanced technologies and methods for the conservation of cultural heritage assets. A particular focus was put on the dynamic characterization of the main hall, as it is subjected to relevant vibration intensity induced by the surrounding tramways and railways traffic [1]. Firstly, a 3D geometric reconstruction of the monument was obtained by integrating information from laser scanner surveys and stereo-photogrammetry. Subsequently, thermographic images by infrared camera were collected, as well as microclimatic parameters, such as air temperature and humidity, in order to evaluate the thermal behavior of the masonry, which is known to influence also the dynamic behavior of the structure. Moreover, sonic testing was performed to investigate the interior consistency of the pillars masonry. Finally, ambient vibration acquisitions were carried out to characterize the dynamic response of the structure and its dependency on the microclimatic conditions. All the above parameters were stored into an integrated information system (repository) that preserves the collected data able to characterize the monument in terms of dynamic response and mechanical properties. II. THE MONUMENT The studied monument is an ancient ruined building located in the city-center of Rome, on the Esquiline Hill, between the via Labicana and Aurelian Walls.
  • 2. Fig. 1. View from North of the so-called Temple of Minerva Medica. In 16th century, it was erroneously interpreted as a temple dedicated to Minerva Medica (“Minerva the Doctor”), as mentioned by Cicero and other ancient sources. Recent studies hypothesized the structure might be an ancient nymphaeum of Imperial Rome (early 4th century A.D.), probably part of the Horti Liciniani, but attribution is still discussed [2]. After initial misinterpretation it was widely known, and still today, as the Temple of Minerva Medica. The structure is a majestic building with decagonal polylobate plan, a diameter of 25 m and a overall height originally of 32 m, currently reduced to only 24 m after the dome partial collapses during the centuries (Fig. 1). Initially, the structure was entirely built using the typical roman technique called opus latericium. Soon after the construction the building presented structural problems. Consequently, it was restored and reinforced through works in opus mixtum of tuff bricks and Roman bricks. Also, the lateral niches were closed and some walls with the function of buttresses were built in the southeast side of the monument. The need for such additional buttresses testify the presence of structural weakness in this part of the structure. As a confirmation, the major historically documented damages were concentrated at the south side, where recent investigations indicated the presence of weaker foundations [2]. After several collapses during centuries of abandon, a major restoration intervention was carried out in 1846 for the reconstruction of first floor arcade of the southeast side. More recently, another relevant restoration intervention reconstructed also the upper floor arcade of the southeast side in 2012-2013. As a consequence of such a long history of collapses and reconstructions the current masonry results quite heterogeneous in materials and shapes. III. NON-DESTRUCTIVE TESTING PROGRAM The NDTs were executed in a period of time that went from summer of 2016 until summer of 2017, in order to investigate the seasonal effects and/or the eventual changes in the structural response of the building, in consideration also of the possible effects of the seismic sequence that hit Central Italy from August 2016 to February 2017. The experimental program can be summarized as follows:  Geometric survey;  Thermal images and microclimatic parameters;  Sonic testing;  Ambient vibration acquisitions. A. Geometric survey Laser scanner acquisitions and photogrammetric mapping for 3D reconstruction and geometry survey of the structure were performed. The laser scanner measurements were acquired in summer of 2016 (August 5th ) and in winter of 2016 (December 20th ), when air temperatures were supposed to be the highest and the lowest of the year, respectively. Both acquisitions were carried out in late morning at similar daytime in order to analyze the seasonal effects neglecting the day/night cycle effect in terms of thermal expansion phenomena. In particular, they were performed using a Riegl Z360 equipped with a Nikon D100 digital camera (see Fig. 2a). The instrument nominal angular resolution is 0.0025° horizontal and 0.002° vertical, while range accuracy can achieve +/- 6 mm. Retro-reflecting targets fixed at each pillar at the height 2.5 m from ground level were used as reference positions in order to compare the two surveys. Such a detailed 3D geometrical survey was the base both for measurements of distances between walls at unreachable points and for the mathematical modelling for successive structural analyses (see Fig. 2b). For instance, several internal walls distances from summer and winter surveys were compared in order to assess the effects of masonry thermal expansion. In addition, also a stereo-photogrammetric survey was executed with the use of a Nikon D60 camera and comprised about 500 digital images (10 Mpx each). The above images were post-processed with Structure from Motion (SfM) methodology [3]. Fig. 2. Laser scanner setup (a). 3D reconstruction of the monument by acquisitions in summer 2016 (b). a) b)
  • 3. Fig. 3. Decagonal plan of the main hall. Fig. 4. Thermal image of upper floor arcade on the northwest side (S3) of the monument. Data processing for SfM was performed by Agisoft PhotoScan software via ENEAGRID, available on CRESCO (Computational Research Center for Complex Systems) HPC infrastructure [4]. A dense cloud of 30 million points was obtained and mesh returned more than 200,000 tria element. Stereo-photogrammetry by SfM is complementary to laser scanning, since it is less accurate in 3D geometry reconstruction, but is able to provide more detailed documentation of the crack pattern [5]. B. Thermal images and microclimatic parameters Thermographic data of the inner walls of the monument were acquired using a Flir T440 thermal infrared camera from the center of the main hall at around midday. The building images were subdivided in 10 ground floor and 10 upper floor views, corresponding to the sides of the decagonal plan (Fig. 3). The thermal images were captured on the same two dates as the laser scanner surveys and in August 2017. The thermographic measurements were calibrated by correlation with the temperatures resulting from two microclimatic monitoring stations, which provided also the air humidity and pressure data. In particular, air temperature and humidity were monitored by two MSR145 mini data loggers positioned on the west side (pillar P4) and on the east side (pillar P8), respectively. A difference of about 30° C was recorded between the maximum temperature values of the masonry in August and in December surveys. A temperature diagram was obtained as a function of the walls solar exposure (ground and upper floor sides) for all three acquired seasons, putting into evidence the thermal differences between walls. The temperature of the walls was higher in the upper arcade and particularly in sides S1, S2 and S3 (northwestern sides of the monument), where temperatures reached 40° C in August (Fig. 4), as a result of the direct solar beam exposure of their upper inner wall-faces due to the big hole left by the collapsed dome. Walls on the eastern and southern sides (S7, S8, S9 and S10) revealed maximum values of only 34-35° C. In December the walls temperature resulted more uniform, increasing only slightly, from 8° C at the bottom to 12° C at the upper arcade. C. Sonic testing The base of each pillar was investigated through sonic tests in order to verify the state of compacity of the masonry and to estimate its compression strength. The sonic tests were executed in February 2017 using the sonic transmission procedure, i.e. through the thickness of the wall [6]. This technique is especially useful for investigating heterogeneities in construction materials, such as historic masonry, allowing the identification of layering of the sections, the presence of voids, cavities and anomalies in material density. Equipment comprised an instrumented hammer with a PCB ICP accelerometer, as well as the probe, both cabled to the acquisition unit. Data were acquired with a sampling frequency of 500 kHz. the sonic measurements was made reference to the UNI 10627-1997 [7]. In (Fig. 5) a diagram showing the sonic test velocity recorded at each pillar, labeled as in Fig 3, in function of the distance d from internal pillar face (see measurement configurations in Fig. 6), is depicted. Initial values (d = 0) tend to decrease at higher values of d, indicating poorer material properties of the core (opus caementicium) with respect to the wall-face brickwork layers (opus latericium or mixtum). The low initial value of pillar P4 is due to a crack in the wall-face layer. The lowest values were measured in pillars P9 and P10 at d in the range 80-120 cm. For d > 120 cm the lowest values were obtained for pillars P1 and P2, which were rebuilt in mid-19th century. D. Ambient vibration acquisitions Ambient vibrations were acquired by digital recorders equipped with triaxial velocimeters provided with a GPS antenna for time synchronization.
  • 4. Fig. 5. Sonic test velocity recorded at each pillar in function of the distance from internal face (d). Fig. 6. Sonic test configurations at pillar P1. Data were acquired both at ground level, to obtain indications on the points where the base excitation due to the nearby traffic (road, trains and trams) is stronger, and on the façade, to assess the amplification to the structure and the dynamic behavior of the building. Each position was acquired for at least 20 minutes at a sampling frequency of 200 Hz. Vibrations were acquired in four sessions carried out on separate dates over a one-year span in order to evaluate the seasonal effects, listed in chronological order as follows:  Session 1: summer 2016 (4 July 2016);  Session 2: winter 2017 (1 February 2017);  Session 3: spring 2017 (19 April 2017);  Session 4: summer 2017 (13 July 2017). Several time/frequency domain calculations and modal analysis techniques were applied for mutual validation of results. In particular, the Frequency Response Function (FRF) was calculated using the Transmissibility Function H [8], the Frequency Domain Decomposition (FDD), the Enhanced Frequency Domain Decomposition (EFDD), the Cristal Clear Subspace Stochastic Identification (CCI- SSI) [9] and the Horizontal Vertical Spectral Ratios (HVSR) [10] were calculated at windows and on top of the façade. Fig. 7. Modal frequencies of the monument from July 2016 (session 1) to July 2017 (Session 4). Fig. 8. Influence of air temperature on the second modal frequency of the monument. In Fig. 7 the average values of the calculated modal frequencies are depicted for each acquisition session, demonstrating the substantial seasonal stability of the dynamic response of the structure. In fact, the modal frequencies slightly increase with the temperature (Fig. 8), but recorded variations are limited in the range of 2-6 %. A remarkable correlation was found between modal frequencies and air temperature, as showed in Fig. 8. E. Repository The architecture of COBRA repository is designed so that acquired data are transferred to a storage area by synchronization with the dedicated OwnCloud partition specifically created for the project. This mechanism runs automatically allowing researchers to acquire their data in the usual modes and formats. In this way the great amount of data produced during the surveys is stored in full safety and integrity. Stored data can be permanently retrieved by the authorized users. A staging area is provided, where raw data can be enriched with metadata and then be stored in the repository as structured data to be possibly submitted
  • 5. to dedicated analysis software. Further, a software system that allows real-time remote monitoring of monument’s parameters and image flows was developed. The CO.B.RA. repository is accessible upon registration from the CO.B.RA. project site (http://cobra.enea.it/). The end-user is provided with credentials to freely download data of the monitoring campaigns and other useful information on the monument. IV. CONCLUSIONS In the present paper the results of a variety of NDT techniques applied to the study of the so-called Temple of Minerva Medica are shown. The several investigated physical properties of the monument were integrated in an effective database for a comprehensive understanding of the overall structural behavior. On the one hand, the influence of the geometry and of the environmental conditions (especially, in terms of solar exposure) on the thermal behavior of the structure was highlighted. On the other hand, the thermal properties resulted the main factor affecting the dynamic behavior of the structure, as proved by slight variations of modal parameters highly correlated with the air temperature. Consequently, no evidence was found of any relevant impact of the Central Italy seismic sequence on the dynamic behavior of the monument. The mechanical properties of the masonry, investigated by sonic tests and the surveyed crack pattern will be fundamental for the production of representative numerical models, e.g. finite element models (FEMs), to be used for future structural analysis. REFERENCES [1] I.Roselli, V.Fioriti, I.Bellagamba, M.Mongelli, A.Tatì, M.Barbera, M.Magnani Cianetti, G.De Canio, “Impact of traffic vibration on the temple of Minerva Medica, Rome: preliminary study within the CO.B.RA. project”, International Journal of Heritage Architecture, vol.2, No.1, 2018, pp.102- 114. [2] M.Barbera, M.Magnani Cianetti, S.Barrano, “Da Massenzio a Costantino: le indagini in corso nel c. d. tempio di Minerva Medica”, Proc. of the International Conference of CISEM - La villa restaurata e i nuovi studi sull'edilizia residenziale tardoantica (in Italian), 2014, pp.1613-1624. [3] M.Mongelli, G.De Canio, I.Roselli, M.Malena, A.Nacuzi, G.De Felice, “3D photogrammetric reconstruction by drone scanning for FE analysis and crack pattern mapping of the bridge of the towers, Spoleto”, Key Engineering Materials, vol.747, July 2017, pp.423-430. [4] G.Ponti, “The role of medium size facilities in the HPC ecosystem: the case of the new CRESCO4 cluster integrated in the ENEAGRID infrastructure”, Proc. of the International Conference on High Performance Computing and Simulation (HPCS), 2014. [5] M.Mongelli, G.De Canio, I.Roselli, M.Malena, A.Nacuzi, G.de Felice, “3D Photogrammetric Reconstruction by Drone Scanning for FE Analysis and Crack Pattern Mapping of the Bridge of the Towers, Spoleto”, Key Engineering Materials, vol.747, pp.423-430. [6] S.Hum-Hartley, “Nondestructive Testing for Heritage Structures”, Bulletin of the Association for Preservation Technology, vol.10, No.3, 1978, pp.4- 20. [7] UNI 10627-1997. Computed tomography systems for structural investigations. [8] C.W.De Silva, “Vibration and Shock Handbook”, CRC Press, 2005. [9] G.De Canio, M.Mongelli, I.Roselli, A.Tatì, D.Addessi, M.Nocera, D.Liberatore, “Numerical and operational modal analyses of the Ponte delle Torri, Spoleto, Italy”, Proc. of the 10th International Conference on Structural Analysis of Historical Constructions (SAHC), 2016, pp.752-758. [10] M.R.Gallipoli, M.Mucciarelli, M.Vona, “Empirical estimate of fundamental frequencies and damping for Italian buildings”, Earthquake Engineering & Structural Dynamics, vol.38, No.8, 2009, pp.973– 988.