Metal-Enclosed
Switchgear
Load
Interrupter
Switches
San Francisco IEEE / IAS
Electrical Design and Applications Seminar
April 29,2011
Gary H. Fox, PE
GE Energy
Senior Specification Engineer
T 925 969 3608
C 510 219 6868
E gary.fox@ge.com
www.geindustrial.com/design
2120 Diamond Blvd., Suite 100
Concord, CA 94520
General Electric Company
imagination at work
g
2 /
SF IAS Electrical design Seminar/
2011
What is a Load Interrupter Switch?
Air insulated disconnect
switch
Metal gear enclosure
Provides safe switching and
circuit protection
Infrequent means of
disconnecting is required.
imagination at work
g
3 /
SF IAS Electrical design Seminar/
2011
Fault current protection using various
types of fuses.
On/off control of a transformer
Duplex switching
Selector switch
Grouped in a lineup configuration with
other medium voltage distribution
equipment.
What is a Load Interrupter Switch?
imagination at work
g
4 /
SF IAS Electrical design Seminar/
2011
How the Load Interrupter Switch Works
• Two-position (open/closed), three-pole
switch.
• Quick make/quick break spring-
charged mechanism for both opening
and closing.
• Switch contact speed is independent of
the speed at which the operator handle
is moved.
• Operated externally from the front of
the switch enclosure.
• Switch blades disengage and interrupt
the flow of electricity.
imagination at work
g
5 /
SF IAS Electrical design Seminar/
2011
The Functions of a Load Interrupter
Switch
Load Interrupter switch functions
include:
•Safe interruption of power.
•Fault protection with the use of
fusing.
•Can be used to select alternative
power between two primary
sources.
•Can be used in line-ups of
multiple sections.
imagination at work
g
6 /
SF IAS Electrical design Seminar/
2011
Key Components
Load Interrupter switches consists of
the following components:
•Switch mechanism
•Fuses
•Viewing window
•Ground bus
•Bolted frame enclosure
•Horizontal and interphase barriers
These components more fully on the
following screens.
imagination at work
g
7 /
SF IAS Electrical design Seminar/
2011
Switch Mechanism
imagination at work
g
8 /
SF IAS Electrical design Seminar/
2011
How the Switch Mechanism Operates
The switch interrupts the circuit by
opening in the following manner:
1. Closed position, both the main
moveable blades and the
stationary contacts are
engaged. Virtually all of the load
current flows through the main
moveable blades.
2. As the external operator handle
moves, a helical spring in the
stored energy mechanism
becomes torqued, applying a
separate force on the blades.
imagination at work
g
9 /
SF IAS Electrical design Seminar/
2011
How the Switch Mechanism Operates
1.The stored energy mechanism
overcomes the friction force of the
stationary contacts and the main
moveable blades.
2. The quick-break blades maintain
contact while the main blades separate
with minimal arcing.
3.The quick-break blades separate.
While within the arc chambers, the
distance between the blades and the
stationary contacts is sufficient to
maintain an arc. The arc chambers
reduce the intensity of the arc by
absorbing heat and by evolving a gas
that quenches the arc.
imagination at work
g
10 /
SF IAS Electrical design Seminar/
2011
Fuses
Two different power fuses are available to provide overcurrent
protection. The can be coordinated to meet the overload and short
circuit ratings specified.
Current Limiting Type
Expulsion Type
Equipped with blown fuse indicators on top of the fuse.
Clear fault currents within their ratings without any expulsion of gases or debris.
Interrupting capacity of 50kA RMS Symmetrical at both 5 and 15kV.
They utilize a quartz sand filler to transfer heat away from the fuse element to the fuse body tube,
which is made from either Pyrex glass or filament wound epoxy.
Boric acid expulsion type fuses are specified. Fuses are constructed of a holder, a refill, and a
discharge filter.
Fuse element melts and the spring in the holder pulls an arcing rod through the boric acid cylinder
of the refill.
Heat from the arc decomposes the boric acid and hydrides blast through the arc to de-ionize it.
The steam and boric acid anhydrides then pass through into the discharge filter that absorbs the
heat and muffles the noise of the interruption.
imagination at work
g
11 /
SF IAS Electrical design Seminar/
2011
Viewing Window
Safe means for
inspecting the position
and condition of the
switch mechanism
without opening the
door.
imagination at work
g
12 /
SF IAS Electrical design Seminar/
2011
Ground Bus
An easily-accessible, front
ground bus.
Silver-plated or tin-plated
copper to match the main bus.
Constructed to carry the rated
short time current of the switch
assembly for two seconds.
imagination at work
g
13 /
SF IAS Electrical design Seminar/
2011
Switch Enclosure
• Rigid, bolted frame construction enclosure.
• 11-gauge sheet steel, including the doors,
back panels, and side panels.
• All steel doors have concealed hinges and
captive screw or quarter-turn latches.
• Foot operated doorstop.
• Each switch compartment and the fuse
compartment are provided with individual
or "split" doors.
• Typical indoor depth on the enclosure is 50
inches.
• Optional 60-inch deep enclosures for special
applications or for mounting additional
devices.
• Typical switch section is 35 inches wide.
imagination at work
g
14 /
SF IAS Electrical design Seminar/
2011
Horizontal and Interphase Barriers
• Glass polyester horizontal barriers
are used to separate the switch
mechanism compartment from the
fuse compartment when fuses are
provided to prevent access from
either compartment to the other.
• Interphase barriers between switch
poles
• Optional glass polyester vertical
section barriers to segregate the rear
compartment section from the
switch and fuse sections.
• Rear compartments can contain
arrestors, other equipment and used
for the entry and exit of cables when
required by the user.
imagination at work
g
15 /
SF IAS Electrical design Seminar/
2011
Interlocks
Mechanical switch and door
interlocks are standard.
Prevent the opening of the doors
when the switch is in the "ON"
position.
Prevent switch from closing when
the door is open.
Provisions for up to six optional key
interlocks.
For example, Load Interrupter
switches can be key interlocked
with the main circuit breaker of a
switchboard on the secondary side
of a transformer.
imagination at work
g
16 /
SF IAS Electrical design Seminar/
2011
Terminology
•Rated Withstand Current
•Rated Fault Making Current
•Rated Continuous Current
•Basic Impulse Level (BIL) Withstand Rating
imagination at work
g
17 /
SF IAS Electrical design Seminar/
2011
Rated Momentary Withstand Current
(Momentary Current Withstand Asymmetrical Rating)
Maximum rms total current
including dc offset at the
major peak of the maximum
cycle during a 10 cycles
period.
Standard available options are
40kA and 61kA.
imagination at work
g
18 /
SF IAS Electrical design Seminar/
2011
Rated Fault Making Current
(Fault Close Asymmetrical Current Rating)
The rating is the maximum
fault current the switch can
close and latch into, then carry
for 10 cycles.
The fault close rating shall be
equal to the rated momentary
current.
imagination at work
g
19 /
SF IAS Electrical design Seminar/
2011
Continuous Current Rating
Maximum current that the
switch is able to carry
continuously without
exceeding specified
temperature rise
limitations.
Available options are 600
and 1200 amperes.
imagination at work
g
20 /
SF IAS Electrical design Seminar/
2011
Basic Impulse Level (BIL) Withstand
Rating
This rating is a measurement of the surge voltage withstand
capability of the switch assembly. The assembly can
withstand a surge voltage impulse of the rated value
without failing.
Standard BIL ratings
60kV @ 5kV
95kV @ 15kV
imagination at work
g
21 /
SF IAS Electrical design Seminar/
2011
Product Applications
•Transformer Disconnect
•Duplex Switch
•Selector Switch
•Line-Ups
imagination at work
g
22 /
SF IAS Electrical design Seminar/
2011
Transformer Disconnect
Features
Cable or bus close coupled transition
Standard orientation has load Interrupter switch
on the left side of the transformer when facing
the front of the transformer.
Reverse orientation, switch on the right side.
Customer Applications
The switch is used to isolate the transformer
from the incoming supply or to isolate the load
circuits from the transformer.
Configurations
• Single
• Duplex
• Selector switch
imagination at work
g
23 /
SF IAS Electrical design Seminar/
2011
Duplex Switch
Features
• Provides on/off switching, utilizing two load
break switch sections connected via a
common set of fuses to the load.
• Mechanical interlocks (key interlocks) prevent
both switches from being closed at the same
time.
Functions
• Allow selection of one of two power sources,
such as a normal and alternate power source.
• Load is isolated when both switches are off.
• Application in primary selective systems but
not primary loop systems
Note that incoming cables are terminated in
separate sections.
imagination at work
g
24 /
SF IAS Electrical design Seminar/
2011
Selector Switch
Features
• Provides on/off switching
• Utilizes a non-load break selector switch in
series with a fused load break switch.
• Mechanical interlocks (key interlocks) prevent
operation of selector switch unless load break
switch is open.
• Less width and more depth compared to
duplex.
Functions
• Allow selection of one of two power sources,
such as a normal and alternate power source.
• Load is isolated when both switches are off.
• Application in primary selective systems but
not primary loop systems
Note that both incoming cables are terminated in
same section
imagination at work
g
25 /
SF IAS Electrical design Seminar/
2011
Line-Ups
Features
• 600, 1200, and 2000 ampere horizontal
through bus.
• Incoming line sections
• Main
• Tie (non-fused)
• Branch (feeder) switches
• Auxiliary spaces (both bussed and un-bussed),
• Transitions to other equipment
• Front and rear aligned.
• Main sections require a transition to branch
switches.
• Low cost alternative to other types of
switchgear.

Contenu connexe

Tendances

“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...rohit nadella
 
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...Ali Sepehri
 
Air circuit breakers
Air circuit breakersAir circuit breakers
Air circuit breakersPrasant Kumar
 
Maintenance schedule of Substation.
Maintenance schedule of Substation.Maintenance schedule of Substation.
Maintenance schedule of Substation.Sheikh Nazmul Islam
 
Power surge protection devices
Power surge protection devices Power surge protection devices
Power surge protection devices Pratik Rasam
 
Vacuum circuit breaker selection of circuit breakers
Vacuum circuit breaker selection of circuit breakersVacuum circuit breaker selection of circuit breakers
Vacuum circuit breaker selection of circuit breakersshubham_bharadia
 
Switchgear and protection lecture 1
Switchgear and protection lecture 1Switchgear and protection lecture 1
Switchgear and protection lecture 1anuphowlader1
 
Electrical substations: 132 KV
Electrical substations: 132 KV Electrical substations: 132 KV
Electrical substations: 132 KV Girish Gupta
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)Power System Operation
 
Circuit Breaker : Types
Circuit Breaker : TypesCircuit Breaker : Types
Circuit Breaker : TypesRidwanul Hoque
 
Principles and Design of LV System
Principles and Design of LV SystemPrinciples and Design of LV System
Principles and Design of LV SystemYE MYO
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersSARAVANAN A
 
Vacuum circuit breaker
Vacuum circuit breakerVacuum circuit breaker
Vacuum circuit breakeropjit88
 
Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601SARAVANAN A
 
Design of substation
Design of substationDesign of substation
Design of substationSayanSarkar55
 

Tendances (20)

“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
 
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
 
Air circuit breakers
Air circuit breakersAir circuit breakers
Air circuit breakers
 
Maintenance schedule of Substation.
Maintenance schedule of Substation.Maintenance schedule of Substation.
Maintenance schedule of Substation.
 
Power surge protection devices
Power surge protection devices Power surge protection devices
Power surge protection devices
 
66 kv substation
66 kv substation66 kv substation
66 kv substation
 
Vacuum circuit breaker selection of circuit breakers
Vacuum circuit breaker selection of circuit breakersVacuum circuit breaker selection of circuit breakers
Vacuum circuit breaker selection of circuit breakers
 
Ashwani kumar
Ashwani kumarAshwani kumar
Ashwani kumar
 
Switchgear and protection lecture 1
Switchgear and protection lecture 1Switchgear and protection lecture 1
Switchgear and protection lecture 1
 
Electrical substations: 132 KV
Electrical substations: 132 KV Electrical substations: 132 KV
Electrical substations: 132 KV
 
SWITCHGEAR
SWITCHGEARSWITCHGEAR
SWITCHGEAR
 
Vacuum circuit breaker
Vacuum circuit breakerVacuum circuit breaker
Vacuum circuit breaker
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
 
Circuit Breaker : Types
Circuit Breaker : TypesCircuit Breaker : Types
Circuit Breaker : Types
 
Principles and Design of LV System
Principles and Design of LV SystemPrinciples and Design of LV System
Principles and Design of LV System
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineers
 
Vacuum circuit breaker
Vacuum circuit breakerVacuum circuit breaker
Vacuum circuit breaker
 
Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601
 
Design of substation
Design of substationDesign of substation
Design of substation
 
Four Quadrant Metering
Four Quadrant MeteringFour Quadrant Metering
Four Quadrant Metering
 

En vedette

En vedette (16)

Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Getting the Most out of your Electrical Room
Getting the Most out of your Electrical RoomGetting the Most out of your Electrical Room
Getting the Most out of your Electrical Room
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
20120504 LISAT slides Dube
20120504 LISAT slides Dube20120504 LISAT slides Dube
20120504 LISAT slides Dube
 
Circuit Breakers
Circuit BreakersCircuit Breakers
Circuit Breakers
 
SF6 CIRCUIT BREAKER
SF6 CIRCUIT BREAKERSF6 CIRCUIT BREAKER
SF6 CIRCUIT BREAKER
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakers
 
Study of circuit breakers
Study of circuit breakersStudy of circuit breakers
Study of circuit breakers
 
Circuit breakers
Circuit breakers Circuit breakers
Circuit breakers
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakers
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakers
 
Er. rahul sharma circuit breaker
Er. rahul sharma circuit breakerEr. rahul sharma circuit breaker
Er. rahul sharma circuit breaker
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Slideshare ppt
Slideshare pptSlideshare ppt
Slideshare ppt
 

Similaire à Metal-Enclosed Switchgear Load Interrupter Switches

Air insulated sf6 ring main unit 36kv
Air insulated sf6 ring main unit 36kvAir insulated sf6 ring main unit 36kv
Air insulated sf6 ring main unit 36kvAUTO RECLOSER
 
Induction Coil Suppliers: Copper Furnace Components & Manufacturers
Induction Coil Suppliers: Copper Furnace Components & ManufacturersInduction Coil Suppliers: Copper Furnace Components & Manufacturers
Induction Coil Suppliers: Copper Furnace Components & Manufacturerslawthermsteel
 
Lv switchgear & lv cable sizing
Lv switchgear & lv cable sizingLv switchgear & lv cable sizing
Lv switchgear & lv cable sizingAsif Eqbal
 
Switchgear Equipment in a Substation
Switchgear Equipment in a SubstationSwitchgear Equipment in a Substation
Switchgear Equipment in a SubstationMd. Atiqur Rahman
 
Industrial electronics 1 marks- polytechnic
Industrial electronics  1 marks- polytechnicIndustrial electronics  1 marks- polytechnic
Industrial electronics 1 marks- polytechnicSukesh R
 
Industrial electronics question bank
Industrial electronics question bankIndustrial electronics question bank
Industrial electronics question bankSukesh R
 
Training on Electrical Starter & Switch Gear.ppt
Training on Electrical Starter & Switch Gear.pptTraining on Electrical Starter & Switch Gear.ppt
Training on Electrical Starter & Switch Gear.pptAmiya Kumar Samal
 
Electrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCBElectrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCBMANOJ964697
 
Pole mounted substaion in kerala
Pole mounted substaion in keralaPole mounted substaion in kerala
Pole mounted substaion in keralasebinkb
 
Switchyard final
Switchyard finalSwitchyard final
Switchyard finalHAIDER ALI
 
Electrical-Symbol-magnetic-ContactorsRelays.ppt
Electrical-Symbol-magnetic-ContactorsRelays.pptElectrical-Symbol-magnetic-ContactorsRelays.ppt
Electrical-Symbol-magnetic-ContactorsRelays.pptNotROYALgaming
 
Basic electrical comp upload1
Basic electrical comp upload1Basic electrical comp upload1
Basic electrical comp upload1Ganesh Kumar
 

Similaire à Metal-Enclosed Switchgear Load Interrupter Switches (20)

Air insulated sf6 ring main unit 36kv
Air insulated sf6 ring main unit 36kvAir insulated sf6 ring main unit 36kv
Air insulated sf6 ring main unit 36kv
 
Induction Coil Suppliers: Copper Furnace Components & Manufacturers
Induction Coil Suppliers: Copper Furnace Components & ManufacturersInduction Coil Suppliers: Copper Furnace Components & Manufacturers
Induction Coil Suppliers: Copper Furnace Components & Manufacturers
 
High Reliability Keypad Design and Assembly
High Reliability Keypad Design and AssemblyHigh Reliability Keypad Design and Assembly
High Reliability Keypad Design and Assembly
 
ppt.pptx
ppt.pptxppt.pptx
ppt.pptx
 
Lv switchgear & lv cable sizing
Lv switchgear & lv cable sizingLv switchgear & lv cable sizing
Lv switchgear & lv cable sizing
 
5 power house
5 power house5 power house
5 power house
 
Switchgear Equipment in a Substation
Switchgear Equipment in a SubstationSwitchgear Equipment in a Substation
Switchgear Equipment in a Substation
 
Industrial electronics 1 marks- polytechnic
Industrial electronics  1 marks- polytechnicIndustrial electronics  1 marks- polytechnic
Industrial electronics 1 marks- polytechnic
 
Industrial electronics question bank
Industrial electronics question bankIndustrial electronics question bank
Industrial electronics question bank
 
Training on Electrical Starter & Switch Gear.ppt
Training on Electrical Starter & Switch Gear.pptTraining on Electrical Starter & Switch Gear.ppt
Training on Electrical Starter & Switch Gear.ppt
 
Electrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCBElectrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCB
 
Pole mounted substaion in kerala
Pole mounted substaion in keralaPole mounted substaion in kerala
Pole mounted substaion in kerala
 
400 kv nelmangala
400 kv nelmangala400 kv nelmangala
400 kv nelmangala
 
Switchyard final
Switchyard finalSwitchyard final
Switchyard final
 
Relay
RelayRelay
Relay
 
Circuit Breaker
Circuit BreakerCircuit Breaker
Circuit Breaker
 
Electrical-Symbol-magnetic-ContactorsRelays.ppt
Electrical-Symbol-magnetic-ContactorsRelays.pptElectrical-Symbol-magnetic-ContactorsRelays.ppt
Electrical-Symbol-magnetic-ContactorsRelays.ppt
 
Basic electrical comp upload1
Basic electrical comp upload1Basic electrical comp upload1
Basic electrical comp upload1
 
Welding equipments
Welding equipmentsWelding equipments
Welding equipments
 
Gis91
Gis91Gis91
Gis91
 

Plus de michaeljmack

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993michaeljmack
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbookmichaeljmack
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbookmichaeljmack
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systemsmichaeljmack
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flashmichaeljmack
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrushmichaeljmack
 
Building information modeling
Building information modelingBuilding information modeling
Building information modelingmichaeljmack
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protectionmichaeljmack
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systemsmichaeljmack
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spacesmichaeljmack
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708michaeljmack
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distributionmichaeljmack
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performancemichaeljmack
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulatormichaeljmack
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plantsmichaeljmack
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Storiesmichaeljmack
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Sheddingmichaeljmack
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentalsmichaeljmack
 

Plus de michaeljmack (20)

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbook
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbook
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systems
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Building information modeling
Building information modelingBuilding information modeling
Building information modeling
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spaces
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distribution
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulator
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plants
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Stories
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentals
 
Arc Flash
Arc FlashArc Flash
Arc Flash
 

Dernier

Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VDineshKumar4165
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756dollysharma2066
 
Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Christo Ananth
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfRagavanV2
 
Vivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design SpainVivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design Spaintimesproduction05
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxfenichawla
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdfSuman Jyoti
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 

Dernier (20)

Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Vivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design SpainVivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design Spain
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 

Metal-Enclosed Switchgear Load Interrupter Switches

  • 1. imagination at work g GE Confidential Metal-Enclosed Switchgear Load Interrupter Switches San Francisco IEEE / IAS Electrical Design and Applications Seminar April 29,2011 Gary H. Fox, PE GE Energy Senior Specification Engineer T 925 969 3608 C 510 219 6868 E gary.fox@ge.com www.geindustrial.com/design 2120 Diamond Blvd., Suite 100 Concord, CA 94520 General Electric Company
  • 2. imagination at work g 2 / SF IAS Electrical design Seminar/ 2011 What is a Load Interrupter Switch? Air insulated disconnect switch Metal gear enclosure Provides safe switching and circuit protection Infrequent means of disconnecting is required.
  • 3. imagination at work g 3 / SF IAS Electrical design Seminar/ 2011 Fault current protection using various types of fuses. On/off control of a transformer Duplex switching Selector switch Grouped in a lineup configuration with other medium voltage distribution equipment. What is a Load Interrupter Switch?
  • 4. imagination at work g 4 / SF IAS Electrical design Seminar/ 2011 How the Load Interrupter Switch Works • Two-position (open/closed), three-pole switch. • Quick make/quick break spring- charged mechanism for both opening and closing. • Switch contact speed is independent of the speed at which the operator handle is moved. • Operated externally from the front of the switch enclosure. • Switch blades disengage and interrupt the flow of electricity.
  • 5. imagination at work g 5 / SF IAS Electrical design Seminar/ 2011 The Functions of a Load Interrupter Switch Load Interrupter switch functions include: •Safe interruption of power. •Fault protection with the use of fusing. •Can be used to select alternative power between two primary sources. •Can be used in line-ups of multiple sections.
  • 6. imagination at work g 6 / SF IAS Electrical design Seminar/ 2011 Key Components Load Interrupter switches consists of the following components: •Switch mechanism •Fuses •Viewing window •Ground bus •Bolted frame enclosure •Horizontal and interphase barriers These components more fully on the following screens.
  • 7. imagination at work g 7 / SF IAS Electrical design Seminar/ 2011 Switch Mechanism
  • 8. imagination at work g 8 / SF IAS Electrical design Seminar/ 2011 How the Switch Mechanism Operates The switch interrupts the circuit by opening in the following manner: 1. Closed position, both the main moveable blades and the stationary contacts are engaged. Virtually all of the load current flows through the main moveable blades. 2. As the external operator handle moves, a helical spring in the stored energy mechanism becomes torqued, applying a separate force on the blades.
  • 9. imagination at work g 9 / SF IAS Electrical design Seminar/ 2011 How the Switch Mechanism Operates 1.The stored energy mechanism overcomes the friction force of the stationary contacts and the main moveable blades. 2. The quick-break blades maintain contact while the main blades separate with minimal arcing. 3.The quick-break blades separate. While within the arc chambers, the distance between the blades and the stationary contacts is sufficient to maintain an arc. The arc chambers reduce the intensity of the arc by absorbing heat and by evolving a gas that quenches the arc.
  • 10. imagination at work g 10 / SF IAS Electrical design Seminar/ 2011 Fuses Two different power fuses are available to provide overcurrent protection. The can be coordinated to meet the overload and short circuit ratings specified. Current Limiting Type Expulsion Type Equipped with blown fuse indicators on top of the fuse. Clear fault currents within their ratings without any expulsion of gases or debris. Interrupting capacity of 50kA RMS Symmetrical at both 5 and 15kV. They utilize a quartz sand filler to transfer heat away from the fuse element to the fuse body tube, which is made from either Pyrex glass or filament wound epoxy. Boric acid expulsion type fuses are specified. Fuses are constructed of a holder, a refill, and a discharge filter. Fuse element melts and the spring in the holder pulls an arcing rod through the boric acid cylinder of the refill. Heat from the arc decomposes the boric acid and hydrides blast through the arc to de-ionize it. The steam and boric acid anhydrides then pass through into the discharge filter that absorbs the heat and muffles the noise of the interruption.
  • 11. imagination at work g 11 / SF IAS Electrical design Seminar/ 2011 Viewing Window Safe means for inspecting the position and condition of the switch mechanism without opening the door.
  • 12. imagination at work g 12 / SF IAS Electrical design Seminar/ 2011 Ground Bus An easily-accessible, front ground bus. Silver-plated or tin-plated copper to match the main bus. Constructed to carry the rated short time current of the switch assembly for two seconds.
  • 13. imagination at work g 13 / SF IAS Electrical design Seminar/ 2011 Switch Enclosure • Rigid, bolted frame construction enclosure. • 11-gauge sheet steel, including the doors, back panels, and side panels. • All steel doors have concealed hinges and captive screw or quarter-turn latches. • Foot operated doorstop. • Each switch compartment and the fuse compartment are provided with individual or "split" doors. • Typical indoor depth on the enclosure is 50 inches. • Optional 60-inch deep enclosures for special applications or for mounting additional devices. • Typical switch section is 35 inches wide.
  • 14. imagination at work g 14 / SF IAS Electrical design Seminar/ 2011 Horizontal and Interphase Barriers • Glass polyester horizontal barriers are used to separate the switch mechanism compartment from the fuse compartment when fuses are provided to prevent access from either compartment to the other. • Interphase barriers between switch poles • Optional glass polyester vertical section barriers to segregate the rear compartment section from the switch and fuse sections. • Rear compartments can contain arrestors, other equipment and used for the entry and exit of cables when required by the user.
  • 15. imagination at work g 15 / SF IAS Electrical design Seminar/ 2011 Interlocks Mechanical switch and door interlocks are standard. Prevent the opening of the doors when the switch is in the "ON" position. Prevent switch from closing when the door is open. Provisions for up to six optional key interlocks. For example, Load Interrupter switches can be key interlocked with the main circuit breaker of a switchboard on the secondary side of a transformer.
  • 16. imagination at work g 16 / SF IAS Electrical design Seminar/ 2011 Terminology •Rated Withstand Current •Rated Fault Making Current •Rated Continuous Current •Basic Impulse Level (BIL) Withstand Rating
  • 17. imagination at work g 17 / SF IAS Electrical design Seminar/ 2011 Rated Momentary Withstand Current (Momentary Current Withstand Asymmetrical Rating) Maximum rms total current including dc offset at the major peak of the maximum cycle during a 10 cycles period. Standard available options are 40kA and 61kA.
  • 18. imagination at work g 18 / SF IAS Electrical design Seminar/ 2011 Rated Fault Making Current (Fault Close Asymmetrical Current Rating) The rating is the maximum fault current the switch can close and latch into, then carry for 10 cycles. The fault close rating shall be equal to the rated momentary current.
  • 19. imagination at work g 19 / SF IAS Electrical design Seminar/ 2011 Continuous Current Rating Maximum current that the switch is able to carry continuously without exceeding specified temperature rise limitations. Available options are 600 and 1200 amperes.
  • 20. imagination at work g 20 / SF IAS Electrical design Seminar/ 2011 Basic Impulse Level (BIL) Withstand Rating This rating is a measurement of the surge voltage withstand capability of the switch assembly. The assembly can withstand a surge voltage impulse of the rated value without failing. Standard BIL ratings 60kV @ 5kV 95kV @ 15kV
  • 21. imagination at work g 21 / SF IAS Electrical design Seminar/ 2011 Product Applications •Transformer Disconnect •Duplex Switch •Selector Switch •Line-Ups
  • 22. imagination at work g 22 / SF IAS Electrical design Seminar/ 2011 Transformer Disconnect Features Cable or bus close coupled transition Standard orientation has load Interrupter switch on the left side of the transformer when facing the front of the transformer. Reverse orientation, switch on the right side. Customer Applications The switch is used to isolate the transformer from the incoming supply or to isolate the load circuits from the transformer. Configurations • Single • Duplex • Selector switch
  • 23. imagination at work g 23 / SF IAS Electrical design Seminar/ 2011 Duplex Switch Features • Provides on/off switching, utilizing two load break switch sections connected via a common set of fuses to the load. • Mechanical interlocks (key interlocks) prevent both switches from being closed at the same time. Functions • Allow selection of one of two power sources, such as a normal and alternate power source. • Load is isolated when both switches are off. • Application in primary selective systems but not primary loop systems Note that incoming cables are terminated in separate sections.
  • 24. imagination at work g 24 / SF IAS Electrical design Seminar/ 2011 Selector Switch Features • Provides on/off switching • Utilizes a non-load break selector switch in series with a fused load break switch. • Mechanical interlocks (key interlocks) prevent operation of selector switch unless load break switch is open. • Less width and more depth compared to duplex. Functions • Allow selection of one of two power sources, such as a normal and alternate power source. • Load is isolated when both switches are off. • Application in primary selective systems but not primary loop systems Note that both incoming cables are terminated in same section
  • 25. imagination at work g 25 / SF IAS Electrical design Seminar/ 2011 Line-Ups Features • 600, 1200, and 2000 ampere horizontal through bus. • Incoming line sections • Main • Tie (non-fused) • Branch (feeder) switches • Auxiliary spaces (both bussed and un-bussed), • Transitions to other equipment • Front and rear aligned. • Main sections require a transition to branch switches. • Low cost alternative to other types of switchgear.