CHAPTER 2
                                   TRANSFORMER

2.1 INTRODUCTION

•   Transformer allow voltage level to be changed throughout the electrical distribution
    system so that the most economical voltage can be used in each part of system .

•   Generators are limited to about 25kV due to the size of insulation required, but
    transmission losses at 25kV would be unacceptable.

•   Thus, voltage are stepped up for transmission.

•   Transformer allow the voltage level to be changed to the most economical level.

•   Compared to rotating machines, the transformer is relatively simple.

•   Transformer comprises two or more electric circuit coupled by magnetic circuit.




               Figure 2.1: An autotransformer with a sliding brush contact




                                                                                       17
2.2 TRANSFORMER CONSTRUCTION




    Primary                                                              Secondary coil
    coil




                                         Figure 2.2




      Figure2.3: An ideal step-down transformer showing magnetic flux in the core

•   Consists of two or more electrical windings that are linked together by a magnetic
    field.

•   Except for special-purpose transformers, the coupling is enhanced with a
    ferromagnetic core.

•   When AC voltage is applied to the primary winding, magnetic flux is established,
    which links the secondary winding.

•   If the flux is sinusoidal, a sinusoidal voltage will be induced in the secondary.




                                                                                          18
•   The primary is the side that is connected to the source (generator or power system),
    and the secondary is the side that is connected to the load.
•   Either side may be the high-voltage or low-voltage side.




                     Figure 2.4: Step up transformer (hydro station)

Core Material
• The core constructed of a high-permeance (low-reluctance) material to minimize the
   magnetixing current.

•   To keep eddy current losses down, the core is made of laminations, the thickness of
    which is inversely proportional to the rated frequency of the transformer.

•   Eddy current losses are proportional to the lamination thickness squared.

•   Thus, halving the thickness would reduce the eddy current losses by 75%.




             Figure 2.5: Three-phase pole-mounted step-down transformer.



                                                                                           19
Core Configuration
• There are two types of transformers cores are used:-
   (i)   Core type
   (ii)  Shell type

•   In the core type, there are winding on each leg of the core (the winding surround the
    core).

•   In the shell type, the winding are on the center leg of the core, and the core surrounds
    the windings.




                       Figure 2.6. Two types of transformer core.

Conductors
• Copper provides the best conductivity and, therefore the minimum volume for the
   coil.
• Aluminum is usually used to reduce the cost.
• The conductor must carry current without overheating.
• The conductors may be round, square, or rectangular, and there may be several
   conductors in parallel to reduce the I2R losses.




                                                                                         20
•   The operating temperature of the coil is extremely important because the insulation
    may deteriorate at increased temperature and the resistance of the coil also increases
    with temperature.




           Figure 2.7: Three-phase oil-cooled transformer with cover cut away

2.3 IDEAL TRANSFORMER OPERATION

•   A transformer makes use of Faraday's law and the ferromagnetic properties of an iron
    core to efficiently raise or lower AC voltages.
•   It of course cannot increase power so that if the voltage is raised, the current is
    proportionally lowered and vice versa.




                                        Figure 2.8



                                                                                         21
Faraday's Law

•   Any change in the magnetic environment of a coil of wire will cause a voltage (emf)
    to be "induced" in the coil.
•   No matter how the change is produced, the voltage will be generated.

                           dΦ
Faraday’s law: e = N                where N = number of turns
                           dt
                                            dΦ
                                                = rate of change of flux
                                            dt
                                           e = instantaneous induced voltage

                e(t ) = 2 Erms sin( wt )
                dΦ e
                      =
                 dt     N
                           t
                         1
                Φ (t ) = ∫ 2 Erms sin( wt )dt
                         N0
                         − 2 Erms
                Φ (t ) =          cos( wt )
                           wN
                         − 2 Erms
                Φ (t ) =          cos( wt )
                          2πfN
                Φ (t ) = −Φ max cos( wt )

                           2πfNΦ max
Therefore       Erms =                 = 4.44 fNΦ max
                                2

Voltage

•   For an ideal transformer, all the flux is confined to the iron core and thus links both
    the primary and secondary.
•   Therefore:             Ep = 4.44fNpΦmax
                       Es = 4.44fNsΦmax

                           Ep Np                   E1 N1
                             =   =a                  =    =a
                           Es Ns                   E2 N 2

•   A transformer is called a step-down transformer if the primary side has more turns
    than the secondary side (a>1).
•   A transformer is called a step-up transformer if the primary side has fewer turns than
    the secondary side (a<1).
•   A step-down transformer has the high voltage facing the power system and low
    voltage facing the load.


                                                                                              22
•   The opposite is true for the step-up transformer.

Current

•   Because the losses are zero in the ideal transformer, the apparent power in and out of
    transformer must be the same:

                       │Sin│=│Sout│=│Vp││Ip│=│Vs││Is│

                        Ip       Vs        Ns 1            I1       V2       N2 1
Therefore                    =         =     =                  =        =     =
                        Is       Vp        Np a            I2       V1       N1 a

•   The ratio of the currents is the inverse of the voltage ratio.
•   If we raise the voltage level to a load with a step-up transformer, then the secondary
    current drawn by the load would have to be less than the primary current, since the
    apparent power is constant.


Impedance

                                      Vs
                             Zs =
                                      Is
•   From Ohm’s Law,                   Vp
                                         Vp
                             ZS = a =
                                 aI p a (a ) I p

                                           Zp
                                  Zs =
                                           a2
                                                       2
                                  Zp      Np      
                                     =a =
                                         N
                                            2
                                                   
                                                   
                                  Zs      s       

Example 1

The nameplate on a single-phase, step-down transformer indicates that is rated
   33.33kVA,
7967V/120V. Find the rated current on the primary and secondary sides.

Solution




                                                                                         23
S 33.33kVA
Is =        =       = 277.8 A
         Vs   120V
    S     33.33kVA
Ip =   =           = 4.184 A
    Vp     7967V
Example 2

An ideal, step-down transformer has 1500 turns in the primary coil and 75 turns in the
secondary coil. If 2400 V is applied to the primary, what is the voltage on the secondary?

Solution

Vp       Np
     =
Vs       Ns
           Ns        75 
Vs = V p      = 2400       = 120V
           Np        1500 



Example 3

An ideal, step-down transformer has 1500 turns in the primary coil and 75 turns in the
secondary coil. If 10.4 A flows in the primary of the transformer, calculate the load
current.

Solution

Ip       Ns
     =
Is       Np
           Np        1500 
Is = I p      = 10.4       = 208 A
           Ns        75 

Example 4

A transformer is rated 75kVA, 7200/240 or 120V. Find the rated current on each side of
the transformer. Find the exciting current if it is 1.7% of rated current.

Solution

The rated current on each side of the transformer :-




                                                                                         24
S rated 75kVA
Ip =           =       = 10.42 A
         Vp      7200V
             S rated 75kVA
I s120V =           =      = 625 A
             Vs120    120V
             S rated 75kVA
I s 240V =          =      = 312.5 A
             Vs 240   240V

The exciting current is on the primary side, so:-

I ex = 0.017Ip = 0.017(10.42) = 0.177A



Example 5

A transformer is rated 75kVA, 7200/240V. A load having an impedance of 1.0Ω is
connected to the secondary.
(i)    What is the current on each side?
(ii)   What is the power delivered to the load?
(iii)  What is the input impedance on the primary side?

Solution

(i)      V = IR
              V   240V
         Is = s =      = 240 A
               R   1Ω
         Ip    N
             = s
         Is N p
                     240
             Ip =        240 = 8 A
                    7200

(ii)         P = I 2 R = 240 2 (1) = 57.6kW

                             2
             Zp  Np     
(iii)          =        
             Zs  Ns
                
                         
                         
                                 2
                   7200 
             Zp =        (1Ω) = 900Ω
                   240 




                                                                                 25
2.4 PRACTICAL TRANSFORMER


The Equivalent Circuit

•   All transformer have winding resistance, a core with finite permeability, leakage flux
    and hysterisis and eddy current losses and are thus nonideal.
•   The transformer as Figure 2.9 which represented by the core and coils, is still not
    ideal because it has magnetizing current flowing into it.




                                        Figure 2.9

•   Adding the magnetizing branch as shown in Figure 2.10, the transformer is now
    become an ideal transformer.




                                       Figure 2.10



                 Rp          jXp                a:1           jXs      Rs

                              jXm        Rm               1.0k
                                                         1.0m
                                                          1.0m
                                                           1.0m


                             Figure 2.11:Equivalent T-circuit



                                                                                        26
2                2
             Rp         jXp                  jXs '=a jXs          Rs '=a Rs    a:1
                           jXm          Rm                 1.0k
                                                           1.0m



                       Figure 2.12: T-circuit referred to the primary



                          Rp                   jXp
                   Rp'=        2
                                       jXp'=       2
                           a                   a                  jXs         Rs
             a:1
                     TR1                    jXm            Rm               1.0k
                                                                             1.0k
                                                                              1.0m
                                                                               1.0m
                                                                            1.0m


                      Figure 2.13: T-circuit referred to the secondary



Reflection In Transformer
• One simplification that introduces only a small error is to move the magnetizing
   branch to the primary terminals and then combine the primary and secondary
   resistance and leakage reactance.
• The combination of the winding resistance is called the equivalent resistance, and the
   combination of the leakage reactance is called the equivalent reactance.
• The combination can be referred to one side only, either primary or secondary.
• The following Figure 2.14 and 2.15, illustrates transformer reflection.

                                   Re q p    jXe q p
                                                           a:1
                                                                                1.0k
                                                                                1.0m
                                                                               1.0k
                                                                               1.0m
            jXm                Rm


                   Figure 2.14: Cantilever circuit referred to the primary

                                     Req,p = Rp + a2Rs = Rp+Rs’

                                     Xeq,p = Xp + a2Xs = Xp+Xs’


                                                                                       27
Re q s      jXe q s
               a:1

                           jXm           Rm                          1.0m
                                                                    1.0m
                                                                      1.0k
                                                                    1.0k



               Figure 2.15: Cantilever circuit referred to the secondary

                            Req,s = (Rp/a2 ) + Rs = R’p + Rs

                            Xeq,s = (Xp/a2 ) + Xs = X’p+ Xs




                                     Figure 2.16


Example 6

A step-down transformer is rated 100kVA, 7200/277 V and has the following equivalent
circuit parameter:

       Rp = 2.92Ω    Rs = 0.00432Ω         Rm = 51840Ω
       Xp = 14.6Ω    Xs = 0.0216Ω          Xm = 12960Ω




                                                                                  28
Find the equivalent winding impedance referred to the high voltage side. Repeat for the
low voltage side.

Solution

Equivalent impedance referred to the high/primary side:

     Vp         7200
a=          =        = 25.99
     Vs          277
Req , p = R p + a 2 Rs
Req , p = 2.92 + (25.99) 2 (0.00432) = 5.839Ω


X eq , p = X p + a 2 X s
X eq , p = 14.6 + (25.99) 2 (0.0216) = 29.19Ω
Z eq , p = (5.839 + j 29.2)Ω

Equivalent impedance referred to the low/secondary side:

a = 25.99
         Rp
Req ,s = 2 + Rs
         a
           2.92
Req ,s =        2
                  + (0.00432) = 8.643x10 −3 Ω
         25.99


            Xp
X eq ,s =       + Xs
            a2
             14.6
X eq ,s =           + (0.0216) = 0.0432Ω
            25.99 2
Z eq , s = (0.86 + j 4.3) x10 −2 Ω




Example 7

A step-down transformer is rated 140kVA, 400/1000 V and has the following equivalent
circuit parameter:

            Rp = 10Ω       Rs = 50Ω             Rm = 5000 Ω
            Xp = 20Ω       Xs = 80Ω             Xm = 12000Ω


                                                                                          29
Draw the equivalent winding impedance referred to the high voltage side and low voltage
side.

Solution

     N1   400
a=      =     = 0.4
     N 2 1000

Refer to the high voltage side/secondary side
       R1           10
Req = 2 + R2 =           + 50 = 112.5Ω
       a           0.4 2
        X            20
X eq = 21 + X 2 =         + 80 = 205Ω
        a           0.4 2
Z eq = 112.5 + j 205Ω

           112.5 ohm      j205 ohm


                            1,0m
                           1,0k



Refer to the low voltage side/primary side
Req = R1 + a 2 R2 = 10 + 0.4 2 (50) = 18Ω
X eq = X 1 + a 2 X 2 = 20 + 0.4 2 (80) = 32.8Ω
Z eq = 18 + j 32.8Ω

       18 ohm             j32.8 ohm


                            1,0m
                           1,0k




                                                                                    30
2.5 DETERMINING CIRCUIT PARAMETER

There are 2 simple test that can provide the data required to calculate values for the
elements of the transformer equivalent circuit:-
   (i)     Short-Circuit Test
   (ii)    Open-Circuit Test

(i) Short-Circuit Test (normally at low voltage side)


                     Rp            jXp              jXs '               Rs '

            HV side                  jXm       Rm            1.0k
                                                              1.0m
                                                              1.0k


                          Figure 2.17: Short-circuit test arrangement

•   One-side of the transformer is shorted, and voltage is applied on the other side until
    rated current flows in the windings.

•   Measured the
              1. applied voltage (Vsc),
              2. winding current (Isc),
              3. input power (Psc)

•   Generally, the low-voltage side of the transformer is shorted and voltage is applied to
    the high-voltage side.

•   The measurements are used to calculate Req and jXeq which referred to the high
    voltage side.

•   With the low-voltage winding shorted, the input impedance is:-
       Zin = (Rp + jXp) + [(R’s + jX’s)║[Rm║jXm]] ,without ignored Rm and jXm

•   If Rm and jXm>>>R’s and jX’s, therefore Rm and jXm ignored.
        Zin = (Rp + jXp) + [(R’s + jX’s)

•   From short circuit test, Vsc, Isc and Psc are measured. Therefore:-
                                         Vsc
               │Z eq │= │Z sc │=
                                         Isc
               R eq = Psc/(I2sc)

               X eq =√ (│Z eq│2 – R2eq)


                                                                                             31
(ii) Open-Circuit Test(normally at high voltage side)


                  Rp             jXp             jXs '                   Rs '

         LV side                    jXm     Rm                1.0k
                                                              1.0m
                                                               1.0k


                        Figure 2.18: Open-circuit test arrangement

•   High-voltage side of the transformer is opened and rated voltage is applied to the
    low-voltage side.

•   Readings of Voc, Ioc and Poc are taken on the low voltage side. Then Rm and Xm
    can be calculated.

•   Measured the
              1. applied voltage (Voc),
              2. winding current (Ioc),
              3. input power (Poc)

•   Therefore Rm and Xm which referred to the low voltage side can be calculate.

•   The input impedance during the open-circuit test is the primary winding in series with
    the exciting branch:
                Zin = (Rp + jXp) + (Rm║jXm)

•   The leakage reactance and winding resistance on the primary side can be negligible as
    they are too low compare to Rm and Xm,

               Rm and jXm>>>Rp and jXp,

    Therefore, Zin = (Rm║jXm)

•   From open-circuit test, Voc, Ioc and Poc are measured. Therefore:-

               Poc = VocIoccosθoc

               θoc = cos-1(Poc/IocVoc)

               IR = Ioccos θoc

               IX = Iocsin θoc



                                                                                       32
Rm and Xm can be calculated by:

                 Rm = Voc/IR

                 Xm = Voc/IX

Example 8

Short-circuit and open-circuit tests were performed on a 100kVA transformer, rated
7200V/277V, with the results listed below. Assuming step-down operation, determine the
equivalent circuit parameters of the transformer referred to the high voltage side.

                 Vsc = 414 V             Voc = 277 V
                 Isc = 13.89 A           I oc = 14.88 A
                 Psc = 1126 W            Poc = 1000 W


Solution

Short circuit(HV) (Req,Xeq)
              Vsc    414
        Zeq =      =       = 29.8Ω
               I sc 13.89

                Psc 1126W
        Req =       =        = 5.836Ω
                I sc 13.89 2
                  2




                     2         2
        Xeq =     Z eq − Req = 29.23Ω


Open circuit(LV) (Rm,Xm)

               P                1000W 
θ oc = cos −1  oc  = cos −1 
              V I               277(14.88)  = 75.96°
                                              
                 oc oc                     
I R = I oc cos θ oc = 14.88(cos 75.96°) = 3.61A
I x = I oc sin θ oc = 14.88(sin 75.96°) = 14.435 A
       V        277
Rm = oc =             = 76.73Ω
        I R 3.61
        V          277
X m = oc =                = 19.19Ω
         I x 14.435




                                                                                   33
Referred to the high voltage side/primary side

Req ,hv = 5.836Ω
X eq ,hv = 29.23Ω


Rm ,lv = 76.73Ω
                   2
          7200 
Rm ,hv =        (76.73Ω) = 51.84kΩ
          277 

X m ,lv = 19.19Ω
                    2
           7200 
X m ,hv =        (19.19Ω) = 12.97 kΩ
           277 



Example 9

Short-circuit and open-circuit tests were performed on a 100kVA transformer, 50 Hz,
rated at 120V/2400V, and the results are listed as follows:
               Vsc = 40 V             Voc = 120 V
               Isc = 41.67 A          I oc = 6 A
               Psc = 380 W            Poc = 40 W

(i) Draw the equivalent circuit with the necessary parameters of the transformer referred
to the low voltage side.

(ii) Draw the equivalent circuit with the necessary parameters of the transformer referred
to the high voltage side


Solution


Short circuit(HV) (Req,Xeq)
              Vsc     40
        Zeq =      =       = 0.96Ω
               I sc 41.67

                Psc   380W
        Req =       =        = 0.22Ω
                I sc 41.67 2
                  2




                           2     2
        Xeq =           Z eq − Req = 0.96 2 − 0.22 2 = 0.93Ω



                                                                                        34
Open circuit(LV) (Rm,Xm)

               P               40W 
θ oc = cos −1  oc  = cos −1 
              V I              120(6)  = 86.82°
                                         
                 oc oc                
I R = I oc cos θ oc = 6(cos 86.82°) = 0.33 A
I x = I oc sin θ oc = 6(sin 86.82°) = 5.99 A
       V        120
Rm = oc =             = 363.64Ω
        I R 0.33
        V        120
X m = oc =             = 20.03Ω
         Ix     5.99


(i) Referred to the low voltage side/primary side

Rm ,lv = 363.64Ω
X m,lv = 20.03Ω


Req ,hv = 0.22Ω
                   2
             120 
Req ,lv    =       (0.22Ω) = 0.55mΩ
             2400 

X eq ,hv = 0.93Ω
                    2
             120 
X eq ,lv   =       (0.93Ω) = 2.325mΩ
             2400 

The equivalent circuit:-

                         0.55m ohm         j2.325m ohm
                                                          1,0m
                                                           1,0k




      363.64 ohm                                          1,0k
                          j20.03 ohm                     1,0m




                                                                  35
(ii) Referred to the high voltage side/secondary side
 Req ,hv = 0.22Ω
X eq ,hv = 0.93Ω


Rm,lv = 363.64Ω
                   2
          2400 
Rm,hv   =       (363.64Ω) = 145456Ω
          120 

X m,lv = 20.03Ω
                   2
          2400 
X m,hv =        (20.03Ω) = 8012Ω
          120 


                              0.22 ohm       j0.93 ohm




                                                          1,0m
                                                           1,0k
        145 456 ohm                                       1,0k
                           j8012 ohm                     1,0m




                                                                  36
2.6 TRANSFORMER LOSSES

Generally, in any machine there will be two types of losses namely:

       (i)     iron losses

               P iron = IRm2Rm = VocIoccosθoc

       (ii)    copper losses

               P copper = I12R1 + I22R2
                           = I12R eq,p = I22Req,s


2.7 TRANSFORMER EFFICIENCY


              η = OutputPower =
                   InputPower
                                                    Pout
                                                         =
                                                           Pin −Ploss
                                                    Pin        Pin

Output Power , P out     = VAcosθ2

Input Power , P in = Output Power + Total Losses

Total Losses , P loss    =       P copper losses          +   P core losses
                               Energy dissipated in             Hysteresis and
                                the resistance of             eddy current losses
                                    winding




2.8 VOLTAGE REGULATION

The purpose of voltage regulation is actually to see what is the voltage being dropped in
the secondary winding between no-load and full-load condition.

                                                Vnl − Vfl
                                     VR =
                                                    Vnl




                                                                                        37
If transformer equivalent circuit referred to:-
        (i)    primary side,

                                   R 01              X01
                                                 1             2




                                                                        aV2




                                                V 1 − aV 2
                                        VR =
                                                      V1

       (ii)    secondary side,


                                 R 02          X02
                                          1                2




                                                                   V2




                                             V1 − V 2
                                               a
                                        VR =
                                               V1
                                                  a

Example 10

By referring to the Example 9,calculate the terminal voltage, V1 and voltage
       regulation,
VR if a load at 0.8 power factor lagging is connected to 2400 V side. (neglect the
magnetizing impedance).

Solution

Load is connected to secondary side:-




                                                                                     38
S 100kVA
I2 =  =        = 41.67∠ − cos −1 (0.8) = 41.67∠ − 36.87° = 33.34 − j 25 A
   V2     2400
   120
a=      = 0.05
   2400

If referred primary side:

          I1   0.55m ohm       j2.325m ohm I2'=I2/a


    V1                                         V2'=aV 2
                                  1,0m
                                 1,0k



                                         I2
V 1 = I 2' (0.55m + j 2.325m) + V 2' =      (0.55m + j 2.325m) + aV 2
                                         a
  (33.34 − j 25)
=                (0.55m + j 2.325m) + 0.05(2400)
      0.05
= 121.53 + j1.28V = 121.54∠0.6°V

        V 1 − aV 2       121.54 − 0.05(2400)
VR =                 =                       x100% = 1.27%
               V1              121.54

If referred to secondary side:

    I1'=aI1     0.22 ohm        j0.93 ohm      I2


       V1'=V1/a                                V2
                                  1,0m
                                 1,0k




V 1' = I 2(0.22 + j 0.93) + V 2
= (33.34 − j 25)(0.22 + j 0.93) + 2400
= 2430.58 + 25.51
V 1 = V 1' (a) = 0.05( 2430.58 + 25.51)
= 121.53 − j1.28V = 121.54∠0.6°V

     V 1 − V 2 121.54      − 2400
        a             0.05
VR =          =                   x100% = 1.27%
        V1        121.54
           a             0.05




                                                                            39
2.9 AUTOTRANFORMERS



                               OR




                                                             1.0m
     1.0m




                     LOAD                                       LOAD


                         Figure 2.19: Autotransformer schematic

•   Figure 2.19 show the autotransformer schematic.
•   Autotransformer is a transformer with only one winding.
•   The low-voltage coil is essentially placed on top of the high-voltage coil and is called
    the series coil.
•   The connection is called an autotransformer and can be used as a step-up or a step-
    down transformer.
•   The advantages of autotransformer are:-
    (i)     cheaper
    (ii)    more efficient, because losses stay the same while the rating goes up
            compared to a conventional transformer
    (iii)   lower exciting current
    (iv)    better voltage regulation

•   The disadvantages of autotransformer are:-
    (i)    larger short circuit current available
    (ii)   no isolation between the primary and secondary




                                                                                          40
Example 11

A 220/440V, 25kVA and 50 Hz transformer is connected as an autotransformer to
transform 660V to 220V.
(i)     Determine the ratio ‘a’.
(ii)    Determine the kVA rating of the auto transformer.
(iii)   With a load of 25 kVA, 0.8 lagging power factor connected to 220 V terminals,
        determine the currents in the load and the two transformer windings.

Solution
                         I1
                                        1,0m
                                        1,0m
                                        1,0m




                         N1            I2
        V1=660V

                              N2      I2-I1      V2=220V



                 N 1 660
(i)       a=        =    =3
                 N 2 220

                 25kVA
(ii)      I1 =         = 37.87 A
                  660

                      660(37.87)
          kVAauto =              = 25kVA
                        1000

                 25kVA
(iii)     I2 =         = 113.64 A
                  220

          I 2 − I 1 = 113.64 − 37.87 = 75.77 A




                                                                                        41
2.10 THREE PHASE TRANSFORMERS

Introduction:

   •    Three phase transformers are used throughout industry to change values of three
        phase voltage and current.
   •    Since three phase power is the most common way in which power is produced,
        transmitted, an used, an understanding of how three phase transformer
        connections are made is essential.

Construction:

   •    A three phase transformer is constructed by winding three single phase
        transformers on a single core.
   •    These transformers are put into an enclosure which is then filled with dielectric
        oil.
   •    The dielectric oil performs several functions.
   •    Since it is a dielectric, a nonconductor of electricity, it provides electrical
        insulation between the windings and the case.
   •    It is also used to help provide cooling and to prevent the formation of moisture,
        which can deteriorate the winding insulation.

Connections:

   •    There are only 4 possible transformer combinations:

   1.   Delta to Delta - use: industrial applications
   2.   Delta to Wye - use : most common; commercial and industrial
   3.   Wye to Delta - use : high voltage transmissions
   4.   Wye to Wye - use : rare, don't use causes harmonics and balancing problems.

   •    Three-phase transformers are connected in delta or wye configurations.
   •    A wye-delta transformer has its primary winding connected in a wye and its
        secondary winding connected in a delta (see Figure 2.20).
   •    A delta-wye transformer has its primary winding connected in delta and its
        secondary winding connected in a wye (see Figure 2.21).




                                                                                            42
Figure 2.20:Wye-Delta connection




                          Figure 2.21:Delta-Wye connection

Delta Conections:

   •   A delta system is a good short-distance distribution system.
   •   It is used for neighborhood and small commercial loads close to the supplying
       substation.
   •   Only one voltage is available between any two wires in a delta system.
   •   The delta system can be illustrated by a simple triangle.
   •   A wire from each point of the triangle would represent a three-phase, three-wire
       delta system.
   •   The voltage would be the same between any two wires (see Figure 2.22).




                                      Figure 2.22




                                                                                      43
Wye Connections:

   •   In a wye system the voltage between any two wires will always give the same
       amount of voltage on a three phase system.
   •   However, the voltage between any one of the phase conductors (X1, X2, X3) and
       the neutral (X0) will be less than the power conductors.
   •   For example, if the voltage between the power conductors of any two phases of a
       three wire system is 208v, then the voltage from any phase conductor to ground
       will be 120v.
   •   This is due to the square root of three phase power.
   •   In a wye system, the voltage between any two power conductors will always be
       1.732 (which is the square root of 3) times the voltage between the neutral and
       any one of the power phase conductors.
   •   The phase-to-ground voltage can be found by dividing the phase-to-phase voltage
       by 1.732 (see Figure 2.23).




                                     Figure 2.23

Connecting Single-Phase Transformers into a Three-Phase Bank:

   •   If three phase transformation is need and a three phase transformer of the proper
       size and turns ratio is not available, three single phase transformers can be
       connected to form a three phase bank.
   •   When three single phase transformers are used to make a three phase transformer
       bank, their primary and secondary windings are connected in a wye or delta
       connection.
   •   The three transformer windings in Figure 2.24 are labeled H1 and the other end is
       labeled H2.
   •   One end of each secondary lead is labeled X1 and the other end is labeled X2.




                                                                                     44
Figure 2.24



•   Figure 2.25 shows three single phase transformers labeled A, B, and C.
•   The primary leads of each transformer are labeled H1 and H2 and the secondary
    leads are labeled X1 and X2.
•   The schematic diagram of Figure 2.24 will be used to connect the three single
    phase transformers into a three phase wye-delta connection as shown in Figure
    2.26.




                                  Figure 2.25




                                                                                45
Figure 2.26



•   The primary winding will be tied into a wye connection first.
•   The schematic in Figure 2.24 shows, that the H2 leads of the three primary
    windings are connected together, and the H1 lead of each winding is open for
    connection to the incoming power line.
•   Notice in Figure 2.26 that the H2 leads of the primary windings are connected
    together, and the H1 lead of each winding has been connected to the incoming
    primary power line.
•   Figure 2.24 shows that the X1 lead of the transformer A is connected to the X2
    lead of transformer c.
•   Notice that this same connection has been made in Figure 2.26.
•   The X1 lead of transformer B is connected to X1, lead of transformer A, and the
    X1 lead of transformer B is connected to X2 lead of transformer A, and the X1
    lead of transformer C is connected to X2 lead of transformer B.
•   The load is connected to the points of the delta connection.




                                                                                  46
Tutorial 2

1. A step-down transformer is rated 25kVA, 660-240 V and has the following equivalent
circuit parameter:

       Rp = 15Ω       Rs = 10Ω             Rm = 50000Ω
       Xp = 20Ω       Xs = 8Ω              Xm = 13000Ω
Find the equivalent winding impedance referred to the high side and the low side.


2. Short-circuit and open-circuit tests were performed on a 10kVA transformer,50 Hz,
rated 400V-240V, with the results listed below.
                Vsc = 10 V                           Voc = 240 V
                Isc = 10kVA/400V=25A                 I oc = 4 A
                Psc = 120 W                          Poc = 80 W

(i)     Draw the equivalent circuit parameters of the transformer referred to the high
        side.
(ii)    Draw the equivalent circuit parameters of the transformer referred to the low side.


3. The coil possesses 400 turns and links an ac flux having peak value of 2mWb. If the
frequency is 60Hz, calculate the induced voltage E.


4. A transformer having 90 turns on the primary and 2250 turns on the secondary is
connected to a 120V, 60Hz source. Calculate:
(i) The effective voltage for the secondary side.
(ii) The peak voltage for the secondary side.


5. An ideal-transformer having 90 turns on the primary and 2250 turns on the secondary
is connected to a 200V, 50 Hz source. The load across the secondary draws a current of
2A at a power factor of 0.8 lagging. Calculate:
 (i) The effective value of the primary current.
(ii) The primary current if the secondary current is 100mA.
(iii) The peak flux linked by the secondary winding.


6. The secondary winding of a transformer has a terminal voltage of
Vs (t ) = 282.8 sin 377t V. The turn ratio of the transformer is 50/200. If the secondary
current of the transformer is is (t ) = 7.07 sin(377t − 36.87 ) A, calculate:
                                                             0


(i)     the primary current of the transformer
(ii)    voltage regulation




                                                                                            47
The impedances of this transformer referred to the primary side are
       Req = 0.05Ω            Rc = 75Ω
        X eq = 0.225Ω          X m = 20Ω


7. A 20kVA 8000/277V distribution transformer has the following equivalent circuit
parameter:
                 R p = 32Ω                    Rs = 0.05Ω
                    X p = 45Ω                      X s = 0.06Ω
                     Rc = 250kΩ                    X m = 30kΩ
(i) Draw the equivalent circuit of this transformer referred to the high voltage side.
(ii) Calculate the voltage regulation if:-
        (a) the transformer is supplying rated load at 277V and 0.8 pf lagging,
        (b) the transformer is supplying load at 200V,100W and 0.85 pf lagging.
        (c) the transformer is supplying load at 18kVA, 250V and 0.8 pf leading.


8. Short-circuit and open-circuit tests were performed on a 1000VA transformer, 50 Hz,
rated at 230V/115V, and the results are listed as follows:
                       Vsc = 13.2 V           Voc = 115 V
                       Isc = 4.35 A           I oc = 0.45 A
                       Psc = 20.1 W           Poc = 30 W

(i) Draw the equivalent circuit with the necessary parameters of the transformer referred
to the low voltage side.
(ii) Find the input voltage of the transformer if the transformer is connected to a 140Var,
110V at 0.75 pf lagging




                                                                                         48

Contenu connexe

Tendances

Chapter 4 synchronous machine
Chapter 4 synchronous machineChapter 4 synchronous machine
Chapter 4 synchronous machine
mkazree
 
1-ф to 1-ф Cycloconverter ppt
1-ф to 1-ф Cycloconverter ppt1-ф to 1-ф Cycloconverter ppt
1-ф to 1-ф Cycloconverter ppt
Utsav Yagnik
 
Power electronic dc to dc converter
Power electronic dc to dc converterPower electronic dc to dc converter
Power electronic dc to dc converter
moazalhosne
 

Tendances (20)

Unit 2 - DC-Motor-Drives-pptx.pptx
Unit 2 - DC-Motor-Drives-pptx.pptxUnit 2 - DC-Motor-Drives-pptx.pptx
Unit 2 - DC-Motor-Drives-pptx.pptx
 
Synchronous generator construction
Synchronous generator constructionSynchronous generator construction
Synchronous generator construction
 
Inverter topologies
Inverter topologiesInverter topologies
Inverter topologies
 
Silicon control rectifier
Silicon control rectifierSilicon control rectifier
Silicon control rectifier
 
Unit5:- D.C Machines
Unit5:- D.C MachinesUnit5:- D.C Machines
Unit5:- D.C Machines
 
Chapter 4 synchronous machine
Chapter 4 synchronous machineChapter 4 synchronous machine
Chapter 4 synchronous machine
 
O.C & S.C Test, Sumpner or back to back Test, Condition for maximum efficienc...
O.C & S.C Test, Sumpner or back to back Test, Condition for maximum efficienc...O.C & S.C Test, Sumpner or back to back Test, Condition for maximum efficienc...
O.C & S.C Test, Sumpner or back to back Test, Condition for maximum efficienc...
 
Dc to Dc Converter (chopper)
Dc to Dc Converter (chopper)Dc to Dc Converter (chopper)
Dc to Dc Converter (chopper)
 
Power Electronics introduction
Power Electronics introductionPower Electronics introduction
Power Electronics introduction
 
Gauss seidel method
Gauss seidel methodGauss seidel method
Gauss seidel method
 
Sumpner Test on Transformers
Sumpner Test on TransformersSumpner Test on Transformers
Sumpner Test on Transformers
 
Unit-2 AC-DC converter
Unit-2 AC-DC converter Unit-2 AC-DC converter
Unit-2 AC-DC converter
 
1-ф to 1-ф Cycloconverter ppt
1-ф to 1-ф Cycloconverter ppt1-ф to 1-ф Cycloconverter ppt
1-ф to 1-ф Cycloconverter ppt
 
Dc machines
Dc machinesDc machines
Dc machines
 
Line to Line & Double Line to Ground Fault On Power System
Line to Line & Double Line to Ground Fault On Power SystemLine to Line & Double Line to Ground Fault On Power System
Line to Line & Double Line to Ground Fault On Power System
 
Voltage commutated chopper
Voltage commutated chopperVoltage commutated chopper
Voltage commutated chopper
 
Structure of power system
Structure of power systemStructure of power system
Structure of power system
 
Power electronic dc to dc converter
Power electronic dc to dc converterPower electronic dc to dc converter
Power electronic dc to dc converter
 
No-load & blocked rotor test, Equivalent circuit, Phasor diagram
No-load & blocked rotor test, Equivalent circuit, Phasor diagramNo-load & blocked rotor test, Equivalent circuit, Phasor diagram
No-load & blocked rotor test, Equivalent circuit, Phasor diagram
 
Single phase full bridge inverter
Single phase full bridge inverterSingle phase full bridge inverter
Single phase full bridge inverter
 

Similaire à Chapter 2 transformer new

Transformer by vinay chawla
Transformer by vinay chawlaTransformer by vinay chawla
Transformer by vinay chawla
vinaychawla28
 
UNIT -I per unit calculation,EQUIVALENT CIRCUIT
UNIT -I per unit calculation,EQUIVALENT CIRCUITUNIT -I per unit calculation,EQUIVALENT CIRCUIT
UNIT -I per unit calculation,EQUIVALENT CIRCUIT
Abinaya Saraswathy T
 

Similaire à Chapter 2 transformer new (20)

Engineering science lesson 10
Engineering science lesson 10Engineering science lesson 10
Engineering science lesson 10
 
Engineering science lesson 10 1
Engineering science lesson 10 1Engineering science lesson 10 1
Engineering science lesson 10 1
 
Chapter 7 transformers
Chapter 7 transformersChapter 7 transformers
Chapter 7 transformers
 
Transformers_SNH.pptx
Transformers_SNH.pptxTransformers_SNH.pptx
Transformers_SNH.pptx
 
Single phase transformer
Single phase transformerSingle phase transformer
Single phase transformer
 
Transformer by vinay chawla
Transformer by vinay chawlaTransformer by vinay chawla
Transformer by vinay chawla
 
Electrical drives and control unit 2
Electrical drives and control unit 2Electrical drives and control unit 2
Electrical drives and control unit 2
 
Transformers 31.03.2020.pptx
Transformers 31.03.2020.pptxTransformers 31.03.2020.pptx
Transformers 31.03.2020.pptx
 
Transformer
TransformerTransformer
Transformer
 
Transformers 25.02.2020.pptx
Transformers 25.02.2020.pptxTransformers 25.02.2020.pptx
Transformers 25.02.2020.pptx
 
EEE 233_Lecture-5 to 14.pptx
EEE 233_Lecture-5 to 14.pptxEEE 233_Lecture-5 to 14.pptx
EEE 233_Lecture-5 to 14.pptx
 
UNIT -I per unit calculation,EQUIVALENT CIRCUIT
UNIT -I per unit calculation,EQUIVALENT CIRCUITUNIT -I per unit calculation,EQUIVALENT CIRCUIT
UNIT -I per unit calculation,EQUIVALENT CIRCUIT
 
lec 8 and 9 single phase transformer.pptx
lec 8 and 9 single phase transformer.pptxlec 8 and 9 single phase transformer.pptx
lec 8 and 9 single phase transformer.pptx
 
Transformers (Especially For 12th Std)
Transformers (Especially For 12th Std)Transformers (Especially For 12th Std)
Transformers (Especially For 12th Std)
 
Transformer
TransformerTransformer
Transformer
 
Physicstrans
PhysicstransPhysicstrans
Physicstrans
 
Wk 17 p1 wk 18-p6_24.1-24.4_alternating currents
Wk 17 p1 wk 18-p6_24.1-24.4_alternating currentsWk 17 p1 wk 18-p6_24.1-24.4_alternating currents
Wk 17 p1 wk 18-p6_24.1-24.4_alternating currents
 
Transformers
TransformersTransformers
Transformers
 
UNIT - II Transformers.pptx
UNIT - II Transformers.pptxUNIT - II Transformers.pptx
UNIT - II Transformers.pptx
 
UNIT - II Transformers.pptx
UNIT - II Transformers.pptxUNIT - II Transformers.pptx
UNIT - II Transformers.pptx
 

Plus de mkazree

Communication Engineering - Chapter 6 - Noise
Communication Engineering - Chapter 6 - NoiseCommunication Engineering - Chapter 6 - Noise
Communication Engineering - Chapter 6 - Noise
mkazree
 
Tutorial chapter 2 robotic
Tutorial chapter 2 roboticTutorial chapter 2 robotic
Tutorial chapter 2 robotic
mkazree
 
Dek3223 chapter 2 robotic
Dek3223 chapter 2 roboticDek3223 chapter 2 robotic
Dek3223 chapter 2 robotic
mkazree
 
Chapter 3 am receivers
Chapter 3 am receiversChapter 3 am receivers
Chapter 3 am receivers
mkazree
 
Dek3223 chapter 3 industrial robotic
Dek3223 chapter 3 industrial roboticDek3223 chapter 3 industrial robotic
Dek3223 chapter 3 industrial robotic
mkazree
 
Tutorial chapter 3 robotic
Tutorial chapter 3 roboticTutorial chapter 3 robotic
Tutorial chapter 3 robotic
mkazree
 
Tutorial 2 amplitude modulation
Tutorial 2 amplitude  modulationTutorial 2 amplitude  modulation
Tutorial 2 amplitude modulation
mkazree
 
Chapter 3 am receivers
Chapter 3 am receiversChapter 3 am receivers
Chapter 3 am receivers
mkazree
 
Comm introduction
Comm introductionComm introduction
Comm introduction
mkazree
 
Chapter2 cont
Chapter2 contChapter2 cont
Chapter2 cont
mkazree
 
Chapter 2 amplitude_modulation
Chapter 2 amplitude_modulationChapter 2 amplitude_modulation
Chapter 2 amplitude_modulation
mkazree
 
Chapter5 dek 3143 dae 32303 9 (nota tambahan)
Chapter5 dek 3143 dae 32303 9 (nota tambahan)Chapter5 dek 3143 dae 32303 9 (nota tambahan)
Chapter5 dek 3143 dae 32303 9 (nota tambahan)
mkazree
 
120102011
120102011120102011
120102011
mkazree
 
Ii20102011
Ii20102011Ii20102011
Ii20102011
mkazree
 
Chapter 3 induction machine
Chapter 3 induction machineChapter 3 induction machine
Chapter 3 induction machine
mkazree
 

Plus de mkazree (20)

Coal Fired Power Plant
Coal Fired Power PlantCoal Fired Power Plant
Coal Fired Power Plant
 
Contoh kertas kerja program
Contoh kertas kerja programContoh kertas kerja program
Contoh kertas kerja program
 
Foster-seely and Ratio Detector (Discriminator )
Foster-seely and Ratio Detector (Discriminator )Foster-seely and Ratio Detector (Discriminator )
Foster-seely and Ratio Detector (Discriminator )
 
Communication Engineering - Chapter 6 - Noise
Communication Engineering - Chapter 6 - NoiseCommunication Engineering - Chapter 6 - Noise
Communication Engineering - Chapter 6 - Noise
 
Chapter 5 fm receivers
Chapter 5  fm receiversChapter 5  fm receivers
Chapter 5 fm receivers
 
The Electronic Hobby Kit
The Electronic Hobby KitThe Electronic Hobby Kit
The Electronic Hobby Kit
 
Tutorial chapter 2 robotic
Tutorial chapter 2 roboticTutorial chapter 2 robotic
Tutorial chapter 2 robotic
 
Dek3223 chapter 2 robotic
Dek3223 chapter 2 roboticDek3223 chapter 2 robotic
Dek3223 chapter 2 robotic
 
Chapter 3 am receivers
Chapter 3 am receiversChapter 3 am receivers
Chapter 3 am receivers
 
Dek3223 chapter 3 industrial robotic
Dek3223 chapter 3 industrial roboticDek3223 chapter 3 industrial robotic
Dek3223 chapter 3 industrial robotic
 
Tutorial chapter 3 robotic
Tutorial chapter 3 roboticTutorial chapter 3 robotic
Tutorial chapter 3 robotic
 
Tutorial 2 amplitude modulation
Tutorial 2 amplitude  modulationTutorial 2 amplitude  modulation
Tutorial 2 amplitude modulation
 
Chapter 3 am receivers
Chapter 3 am receiversChapter 3 am receivers
Chapter 3 am receivers
 
Comm introduction
Comm introductionComm introduction
Comm introduction
 
Chapter2 cont
Chapter2 contChapter2 cont
Chapter2 cont
 
Chapter 2 amplitude_modulation
Chapter 2 amplitude_modulationChapter 2 amplitude_modulation
Chapter 2 amplitude_modulation
 
Chapter5 dek 3143 dae 32303 9 (nota tambahan)
Chapter5 dek 3143 dae 32303 9 (nota tambahan)Chapter5 dek 3143 dae 32303 9 (nota tambahan)
Chapter5 dek 3143 dae 32303 9 (nota tambahan)
 
120102011
120102011120102011
120102011
 
Ii20102011
Ii20102011Ii20102011
Ii20102011
 
Chapter 3 induction machine
Chapter 3 induction machineChapter 3 induction machine
Chapter 3 induction machine
 

Dernier

Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al MizharAl Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
allensay1
 
Mifty kit IN Salmiya (+918133066128) Abortion pills IN Salmiyah Cytotec pills
Mifty kit IN Salmiya (+918133066128) Abortion pills IN Salmiyah Cytotec pillsMifty kit IN Salmiya (+918133066128) Abortion pills IN Salmiyah Cytotec pills
Mifty kit IN Salmiya (+918133066128) Abortion pills IN Salmiyah Cytotec pills
Abortion pills in Kuwait Cytotec pills in Kuwait
 
Mifepristone Available in Muscat +918761049707^^ €€ Buy Abortion Pills in Oman
Mifepristone Available in Muscat +918761049707^^ €€ Buy Abortion Pills in OmanMifepristone Available in Muscat +918761049707^^ €€ Buy Abortion Pills in Oman
Mifepristone Available in Muscat +918761049707^^ €€ Buy Abortion Pills in Oman
instagramfab782445
 
Mckinsey foundation level Handbook for Viewing
Mckinsey foundation level Handbook for ViewingMckinsey foundation level Handbook for Viewing
Mckinsey foundation level Handbook for Viewing
Nauman Safdar
 
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai KuwaitThe Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
daisycvs
 

Dernier (20)

Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al MizharAl Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
 
Mifty kit IN Salmiya (+918133066128) Abortion pills IN Salmiyah Cytotec pills
Mifty kit IN Salmiya (+918133066128) Abortion pills IN Salmiyah Cytotec pillsMifty kit IN Salmiya (+918133066128) Abortion pills IN Salmiyah Cytotec pills
Mifty kit IN Salmiya (+918133066128) Abortion pills IN Salmiyah Cytotec pills
 
Rice Manufacturers in India | Shree Krishna Exports
Rice Manufacturers in India | Shree Krishna ExportsRice Manufacturers in India | Shree Krishna Exports
Rice Manufacturers in India | Shree Krishna Exports
 
Katrina Personal Brand Project and portfolio 1
Katrina Personal Brand Project and portfolio 1Katrina Personal Brand Project and portfolio 1
Katrina Personal Brand Project and portfolio 1
 
Cannabis Legalization World Map: 2024 Updated
Cannabis Legalization World Map: 2024 UpdatedCannabis Legalization World Map: 2024 Updated
Cannabis Legalization World Map: 2024 Updated
 
Unveiling Falcon Invoice Discounting: Leading the Way as India's Premier Bill...
Unveiling Falcon Invoice Discounting: Leading the Way as India's Premier Bill...Unveiling Falcon Invoice Discounting: Leading the Way as India's Premier Bill...
Unveiling Falcon Invoice Discounting: Leading the Way as India's Premier Bill...
 
Lucknow Housewife Escorts by Sexy Bhabhi Service 8250092165
Lucknow Housewife Escorts  by Sexy Bhabhi Service 8250092165Lucknow Housewife Escorts  by Sexy Bhabhi Service 8250092165
Lucknow Housewife Escorts by Sexy Bhabhi Service 8250092165
 
Mifepristone Available in Muscat +918761049707^^ €€ Buy Abortion Pills in Oman
Mifepristone Available in Muscat +918761049707^^ €€ Buy Abortion Pills in OmanMifepristone Available in Muscat +918761049707^^ €€ Buy Abortion Pills in Oman
Mifepristone Available in Muscat +918761049707^^ €€ Buy Abortion Pills in Oman
 
Mckinsey foundation level Handbook for Viewing
Mckinsey foundation level Handbook for ViewingMckinsey foundation level Handbook for Viewing
Mckinsey foundation level Handbook for Viewing
 
Buy Verified TransferWise Accounts From Seosmmearth
Buy Verified TransferWise Accounts From SeosmmearthBuy Verified TransferWise Accounts From Seosmmearth
Buy Verified TransferWise Accounts From Seosmmearth
 
joint cost.pptx COST ACCOUNTING Sixteenth Edition ...
joint cost.pptx  COST ACCOUNTING  Sixteenth Edition                          ...joint cost.pptx  COST ACCOUNTING  Sixteenth Edition                          ...
joint cost.pptx COST ACCOUNTING Sixteenth Edition ...
 
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai KuwaitThe Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
 
Power point presentation on enterprise performance management
Power point presentation on enterprise performance managementPower point presentation on enterprise performance management
Power point presentation on enterprise performance management
 
HomeRoots Pitch Deck | Investor Insights | April 2024
HomeRoots Pitch Deck | Investor Insights | April 2024HomeRoots Pitch Deck | Investor Insights | April 2024
HomeRoots Pitch Deck | Investor Insights | April 2024
 
TVB_The Vietnam Believer Newsletter_May 6th, 2024_ENVol. 006.pdf
TVB_The Vietnam Believer Newsletter_May 6th, 2024_ENVol. 006.pdfTVB_The Vietnam Believer Newsletter_May 6th, 2024_ENVol. 006.pdf
TVB_The Vietnam Believer Newsletter_May 6th, 2024_ENVol. 006.pdf
 
Cracking the 'Career Pathing' Slideshare
Cracking the 'Career Pathing' SlideshareCracking the 'Career Pathing' Slideshare
Cracking the 'Career Pathing' Slideshare
 
Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...
Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...
Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...
 
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60% in 6 Months
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60%  in 6 MonthsSEO Case Study: How I Increased SEO Traffic & Ranking by 50-60%  in 6 Months
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60% in 6 Months
 
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDINGParadip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
 
Over the Top (OTT) Market Size & Growth Outlook 2024-2030
Over the Top (OTT) Market Size & Growth Outlook 2024-2030Over the Top (OTT) Market Size & Growth Outlook 2024-2030
Over the Top (OTT) Market Size & Growth Outlook 2024-2030
 

Chapter 2 transformer new

  • 1. CHAPTER 2 TRANSFORMER 2.1 INTRODUCTION • Transformer allow voltage level to be changed throughout the electrical distribution system so that the most economical voltage can be used in each part of system . • Generators are limited to about 25kV due to the size of insulation required, but transmission losses at 25kV would be unacceptable. • Thus, voltage are stepped up for transmission. • Transformer allow the voltage level to be changed to the most economical level. • Compared to rotating machines, the transformer is relatively simple. • Transformer comprises two or more electric circuit coupled by magnetic circuit. Figure 2.1: An autotransformer with a sliding brush contact 17
  • 2. 2.2 TRANSFORMER CONSTRUCTION Primary Secondary coil coil Figure 2.2 Figure2.3: An ideal step-down transformer showing magnetic flux in the core • Consists of two or more electrical windings that are linked together by a magnetic field. • Except for special-purpose transformers, the coupling is enhanced with a ferromagnetic core. • When AC voltage is applied to the primary winding, magnetic flux is established, which links the secondary winding. • If the flux is sinusoidal, a sinusoidal voltage will be induced in the secondary. 18
  • 3. The primary is the side that is connected to the source (generator or power system), and the secondary is the side that is connected to the load. • Either side may be the high-voltage or low-voltage side. Figure 2.4: Step up transformer (hydro station) Core Material • The core constructed of a high-permeance (low-reluctance) material to minimize the magnetixing current. • To keep eddy current losses down, the core is made of laminations, the thickness of which is inversely proportional to the rated frequency of the transformer. • Eddy current losses are proportional to the lamination thickness squared. • Thus, halving the thickness would reduce the eddy current losses by 75%. Figure 2.5: Three-phase pole-mounted step-down transformer. 19
  • 4. Core Configuration • There are two types of transformers cores are used:- (i) Core type (ii) Shell type • In the core type, there are winding on each leg of the core (the winding surround the core). • In the shell type, the winding are on the center leg of the core, and the core surrounds the windings. Figure 2.6. Two types of transformer core. Conductors • Copper provides the best conductivity and, therefore the minimum volume for the coil. • Aluminum is usually used to reduce the cost. • The conductor must carry current without overheating. • The conductors may be round, square, or rectangular, and there may be several conductors in parallel to reduce the I2R losses. 20
  • 5. The operating temperature of the coil is extremely important because the insulation may deteriorate at increased temperature and the resistance of the coil also increases with temperature. Figure 2.7: Three-phase oil-cooled transformer with cover cut away 2.3 IDEAL TRANSFORMER OPERATION • A transformer makes use of Faraday's law and the ferromagnetic properties of an iron core to efficiently raise or lower AC voltages. • It of course cannot increase power so that if the voltage is raised, the current is proportionally lowered and vice versa. Figure 2.8 21
  • 6. Faraday's Law • Any change in the magnetic environment of a coil of wire will cause a voltage (emf) to be "induced" in the coil. • No matter how the change is produced, the voltage will be generated. dΦ Faraday’s law: e = N where N = number of turns dt dΦ = rate of change of flux dt e = instantaneous induced voltage e(t ) = 2 Erms sin( wt ) dΦ e = dt N t 1 Φ (t ) = ∫ 2 Erms sin( wt )dt N0 − 2 Erms Φ (t ) = cos( wt ) wN − 2 Erms Φ (t ) = cos( wt ) 2πfN Φ (t ) = −Φ max cos( wt ) 2πfNΦ max Therefore Erms = = 4.44 fNΦ max 2 Voltage • For an ideal transformer, all the flux is confined to the iron core and thus links both the primary and secondary. • Therefore: Ep = 4.44fNpΦmax Es = 4.44fNsΦmax Ep Np E1 N1 = =a = =a Es Ns E2 N 2 • A transformer is called a step-down transformer if the primary side has more turns than the secondary side (a>1). • A transformer is called a step-up transformer if the primary side has fewer turns than the secondary side (a<1). • A step-down transformer has the high voltage facing the power system and low voltage facing the load. 22
  • 7. The opposite is true for the step-up transformer. Current • Because the losses are zero in the ideal transformer, the apparent power in and out of transformer must be the same: │Sin│=│Sout│=│Vp││Ip│=│Vs││Is│ Ip Vs Ns 1 I1 V2 N2 1 Therefore = = = = = = Is Vp Np a I2 V1 N1 a • The ratio of the currents is the inverse of the voltage ratio. • If we raise the voltage level to a load with a step-up transformer, then the secondary current drawn by the load would have to be less than the primary current, since the apparent power is constant. Impedance Vs Zs = Is • From Ohm’s Law, Vp Vp ZS = a = aI p a (a ) I p Zp Zs = a2 2 Zp  Np  =a = N 2   Zs  s  Example 1 The nameplate on a single-phase, step-down transformer indicates that is rated 33.33kVA, 7967V/120V. Find the rated current on the primary and secondary sides. Solution 23
  • 8. S 33.33kVA Is = = = 277.8 A Vs 120V S 33.33kVA Ip = = = 4.184 A Vp 7967V Example 2 An ideal, step-down transformer has 1500 turns in the primary coil and 75 turns in the secondary coil. If 2400 V is applied to the primary, what is the voltage on the secondary? Solution Vp Np = Vs Ns Ns  75  Vs = V p = 2400  = 120V Np  1500  Example 3 An ideal, step-down transformer has 1500 turns in the primary coil and 75 turns in the secondary coil. If 10.4 A flows in the primary of the transformer, calculate the load current. Solution Ip Ns = Is Np Np  1500  Is = I p = 10.4  = 208 A Ns  75  Example 4 A transformer is rated 75kVA, 7200/240 or 120V. Find the rated current on each side of the transformer. Find the exciting current if it is 1.7% of rated current. Solution The rated current on each side of the transformer :- 24
  • 9. S rated 75kVA Ip = = = 10.42 A Vp 7200V S rated 75kVA I s120V = = = 625 A Vs120 120V S rated 75kVA I s 240V = = = 312.5 A Vs 240 240V The exciting current is on the primary side, so:- I ex = 0.017Ip = 0.017(10.42) = 0.177A Example 5 A transformer is rated 75kVA, 7200/240V. A load having an impedance of 1.0Ω is connected to the secondary. (i) What is the current on each side? (ii) What is the power delivered to the load? (iii) What is the input impedance on the primary side? Solution (i) V = IR V 240V Is = s = = 240 A R 1Ω Ip N = s Is N p 240 Ip = 240 = 8 A 7200 (ii) P = I 2 R = 240 2 (1) = 57.6kW 2 Zp  Np  (iii) =  Zs  Ns    2  7200  Zp =   (1Ω) = 900Ω  240  25
  • 10. 2.4 PRACTICAL TRANSFORMER The Equivalent Circuit • All transformer have winding resistance, a core with finite permeability, leakage flux and hysterisis and eddy current losses and are thus nonideal. • The transformer as Figure 2.9 which represented by the core and coils, is still not ideal because it has magnetizing current flowing into it. Figure 2.9 • Adding the magnetizing branch as shown in Figure 2.10, the transformer is now become an ideal transformer. Figure 2.10 Rp jXp a:1 jXs Rs jXm Rm 1.0k 1.0m 1.0m 1.0m Figure 2.11:Equivalent T-circuit 26
  • 11. 2 2 Rp jXp jXs '=a jXs Rs '=a Rs a:1 jXm Rm 1.0k 1.0m Figure 2.12: T-circuit referred to the primary Rp jXp Rp'= 2 jXp'= 2 a a jXs Rs a:1 TR1 jXm Rm 1.0k 1.0k 1.0m 1.0m 1.0m Figure 2.13: T-circuit referred to the secondary Reflection In Transformer • One simplification that introduces only a small error is to move the magnetizing branch to the primary terminals and then combine the primary and secondary resistance and leakage reactance. • The combination of the winding resistance is called the equivalent resistance, and the combination of the leakage reactance is called the equivalent reactance. • The combination can be referred to one side only, either primary or secondary. • The following Figure 2.14 and 2.15, illustrates transformer reflection. Re q p jXe q p a:1 1.0k 1.0m 1.0k 1.0m jXm Rm Figure 2.14: Cantilever circuit referred to the primary Req,p = Rp + a2Rs = Rp+Rs’ Xeq,p = Xp + a2Xs = Xp+Xs’ 27
  • 12. Re q s jXe q s a:1 jXm Rm 1.0m 1.0m 1.0k 1.0k Figure 2.15: Cantilever circuit referred to the secondary Req,s = (Rp/a2 ) + Rs = R’p + Rs Xeq,s = (Xp/a2 ) + Xs = X’p+ Xs Figure 2.16 Example 6 A step-down transformer is rated 100kVA, 7200/277 V and has the following equivalent circuit parameter: Rp = 2.92Ω Rs = 0.00432Ω Rm = 51840Ω Xp = 14.6Ω Xs = 0.0216Ω Xm = 12960Ω 28
  • 13. Find the equivalent winding impedance referred to the high voltage side. Repeat for the low voltage side. Solution Equivalent impedance referred to the high/primary side: Vp 7200 a= = = 25.99 Vs 277 Req , p = R p + a 2 Rs Req , p = 2.92 + (25.99) 2 (0.00432) = 5.839Ω X eq , p = X p + a 2 X s X eq , p = 14.6 + (25.99) 2 (0.0216) = 29.19Ω Z eq , p = (5.839 + j 29.2)Ω Equivalent impedance referred to the low/secondary side: a = 25.99 Rp Req ,s = 2 + Rs a 2.92 Req ,s = 2 + (0.00432) = 8.643x10 −3 Ω 25.99 Xp X eq ,s = + Xs a2 14.6 X eq ,s = + (0.0216) = 0.0432Ω 25.99 2 Z eq , s = (0.86 + j 4.3) x10 −2 Ω Example 7 A step-down transformer is rated 140kVA, 400/1000 V and has the following equivalent circuit parameter: Rp = 10Ω Rs = 50Ω Rm = 5000 Ω Xp = 20Ω Xs = 80Ω Xm = 12000Ω 29
  • 14. Draw the equivalent winding impedance referred to the high voltage side and low voltage side. Solution N1 400 a= = = 0.4 N 2 1000 Refer to the high voltage side/secondary side R1 10 Req = 2 + R2 = + 50 = 112.5Ω a 0.4 2 X 20 X eq = 21 + X 2 = + 80 = 205Ω a 0.4 2 Z eq = 112.5 + j 205Ω 112.5 ohm j205 ohm 1,0m 1,0k Refer to the low voltage side/primary side Req = R1 + a 2 R2 = 10 + 0.4 2 (50) = 18Ω X eq = X 1 + a 2 X 2 = 20 + 0.4 2 (80) = 32.8Ω Z eq = 18 + j 32.8Ω 18 ohm j32.8 ohm 1,0m 1,0k 30
  • 15. 2.5 DETERMINING CIRCUIT PARAMETER There are 2 simple test that can provide the data required to calculate values for the elements of the transformer equivalent circuit:- (i) Short-Circuit Test (ii) Open-Circuit Test (i) Short-Circuit Test (normally at low voltage side) Rp jXp jXs ' Rs ' HV side jXm Rm 1.0k 1.0m 1.0k Figure 2.17: Short-circuit test arrangement • One-side of the transformer is shorted, and voltage is applied on the other side until rated current flows in the windings. • Measured the 1. applied voltage (Vsc), 2. winding current (Isc), 3. input power (Psc) • Generally, the low-voltage side of the transformer is shorted and voltage is applied to the high-voltage side. • The measurements are used to calculate Req and jXeq which referred to the high voltage side. • With the low-voltage winding shorted, the input impedance is:- Zin = (Rp + jXp) + [(R’s + jX’s)║[Rm║jXm]] ,without ignored Rm and jXm • If Rm and jXm>>>R’s and jX’s, therefore Rm and jXm ignored. Zin = (Rp + jXp) + [(R’s + jX’s) • From short circuit test, Vsc, Isc and Psc are measured. Therefore:- Vsc │Z eq │= │Z sc │= Isc R eq = Psc/(I2sc) X eq =√ (│Z eq│2 – R2eq) 31
  • 16. (ii) Open-Circuit Test(normally at high voltage side) Rp jXp jXs ' Rs ' LV side jXm Rm 1.0k 1.0m 1.0k Figure 2.18: Open-circuit test arrangement • High-voltage side of the transformer is opened and rated voltage is applied to the low-voltage side. • Readings of Voc, Ioc and Poc are taken on the low voltage side. Then Rm and Xm can be calculated. • Measured the 1. applied voltage (Voc), 2. winding current (Ioc), 3. input power (Poc) • Therefore Rm and Xm which referred to the low voltage side can be calculate. • The input impedance during the open-circuit test is the primary winding in series with the exciting branch: Zin = (Rp + jXp) + (Rm║jXm) • The leakage reactance and winding resistance on the primary side can be negligible as they are too low compare to Rm and Xm, Rm and jXm>>>Rp and jXp, Therefore, Zin = (Rm║jXm) • From open-circuit test, Voc, Ioc and Poc are measured. Therefore:- Poc = VocIoccosθoc θoc = cos-1(Poc/IocVoc) IR = Ioccos θoc IX = Iocsin θoc 32
  • 17. Rm and Xm can be calculated by: Rm = Voc/IR Xm = Voc/IX Example 8 Short-circuit and open-circuit tests were performed on a 100kVA transformer, rated 7200V/277V, with the results listed below. Assuming step-down operation, determine the equivalent circuit parameters of the transformer referred to the high voltage side. Vsc = 414 V Voc = 277 V Isc = 13.89 A I oc = 14.88 A Psc = 1126 W Poc = 1000 W Solution Short circuit(HV) (Req,Xeq) Vsc 414 Zeq = = = 29.8Ω I sc 13.89 Psc 1126W Req = = = 5.836Ω I sc 13.89 2 2 2 2 Xeq = Z eq − Req = 29.23Ω Open circuit(LV) (Rm,Xm)  P   1000W  θ oc = cos −1  oc  = cos −1  V I   277(14.88)  = 75.96°   oc oc    I R = I oc cos θ oc = 14.88(cos 75.96°) = 3.61A I x = I oc sin θ oc = 14.88(sin 75.96°) = 14.435 A V 277 Rm = oc = = 76.73Ω I R 3.61 V 277 X m = oc = = 19.19Ω I x 14.435 33
  • 18. Referred to the high voltage side/primary side Req ,hv = 5.836Ω X eq ,hv = 29.23Ω Rm ,lv = 76.73Ω 2  7200  Rm ,hv =   (76.73Ω) = 51.84kΩ  277  X m ,lv = 19.19Ω 2  7200  X m ,hv =   (19.19Ω) = 12.97 kΩ  277  Example 9 Short-circuit and open-circuit tests were performed on a 100kVA transformer, 50 Hz, rated at 120V/2400V, and the results are listed as follows: Vsc = 40 V Voc = 120 V Isc = 41.67 A I oc = 6 A Psc = 380 W Poc = 40 W (i) Draw the equivalent circuit with the necessary parameters of the transformer referred to the low voltage side. (ii) Draw the equivalent circuit with the necessary parameters of the transformer referred to the high voltage side Solution Short circuit(HV) (Req,Xeq) Vsc 40 Zeq = = = 0.96Ω I sc 41.67 Psc 380W Req = = = 0.22Ω I sc 41.67 2 2 2 2 Xeq = Z eq − Req = 0.96 2 − 0.22 2 = 0.93Ω 34
  • 19. Open circuit(LV) (Rm,Xm)  P   40W  θ oc = cos −1  oc  = cos −1  V I   120(6)  = 86.82°   oc oc    I R = I oc cos θ oc = 6(cos 86.82°) = 0.33 A I x = I oc sin θ oc = 6(sin 86.82°) = 5.99 A V 120 Rm = oc = = 363.64Ω I R 0.33 V 120 X m = oc = = 20.03Ω Ix 5.99 (i) Referred to the low voltage side/primary side Rm ,lv = 363.64Ω X m,lv = 20.03Ω Req ,hv = 0.22Ω 2  120  Req ,lv =  (0.22Ω) = 0.55mΩ  2400  X eq ,hv = 0.93Ω 2  120  X eq ,lv =  (0.93Ω) = 2.325mΩ  2400  The equivalent circuit:- 0.55m ohm j2.325m ohm 1,0m 1,0k 363.64 ohm 1,0k j20.03 ohm 1,0m 35
  • 20. (ii) Referred to the high voltage side/secondary side Req ,hv = 0.22Ω X eq ,hv = 0.93Ω Rm,lv = 363.64Ω 2  2400  Rm,hv =  (363.64Ω) = 145456Ω  120  X m,lv = 20.03Ω 2  2400  X m,hv =   (20.03Ω) = 8012Ω  120  0.22 ohm j0.93 ohm 1,0m 1,0k 145 456 ohm 1,0k j8012 ohm 1,0m 36
  • 21. 2.6 TRANSFORMER LOSSES Generally, in any machine there will be two types of losses namely: (i) iron losses P iron = IRm2Rm = VocIoccosθoc (ii) copper losses P copper = I12R1 + I22R2 = I12R eq,p = I22Req,s 2.7 TRANSFORMER EFFICIENCY η = OutputPower = InputPower Pout = Pin −Ploss Pin Pin Output Power , P out = VAcosθ2 Input Power , P in = Output Power + Total Losses Total Losses , P loss = P copper losses + P core losses Energy dissipated in Hysteresis and the resistance of eddy current losses winding 2.8 VOLTAGE REGULATION The purpose of voltage regulation is actually to see what is the voltage being dropped in the secondary winding between no-load and full-load condition. Vnl − Vfl VR = Vnl 37
  • 22. If transformer equivalent circuit referred to:- (i) primary side, R 01 X01 1 2 aV2 V 1 − aV 2 VR = V1 (ii) secondary side, R 02 X02 1 2 V2 V1 − V 2 a VR = V1 a Example 10 By referring to the Example 9,calculate the terminal voltage, V1 and voltage regulation, VR if a load at 0.8 power factor lagging is connected to 2400 V side. (neglect the magnetizing impedance). Solution Load is connected to secondary side:- 38
  • 23. S 100kVA I2 = = = 41.67∠ − cos −1 (0.8) = 41.67∠ − 36.87° = 33.34 − j 25 A V2 2400 120 a= = 0.05 2400 If referred primary side: I1 0.55m ohm j2.325m ohm I2'=I2/a V1 V2'=aV 2 1,0m 1,0k I2 V 1 = I 2' (0.55m + j 2.325m) + V 2' = (0.55m + j 2.325m) + aV 2 a (33.34 − j 25) = (0.55m + j 2.325m) + 0.05(2400) 0.05 = 121.53 + j1.28V = 121.54∠0.6°V V 1 − aV 2 121.54 − 0.05(2400) VR = = x100% = 1.27% V1 121.54 If referred to secondary side: I1'=aI1 0.22 ohm j0.93 ohm I2 V1'=V1/a V2 1,0m 1,0k V 1' = I 2(0.22 + j 0.93) + V 2 = (33.34 − j 25)(0.22 + j 0.93) + 2400 = 2430.58 + 25.51 V 1 = V 1' (a) = 0.05( 2430.58 + 25.51) = 121.53 − j1.28V = 121.54∠0.6°V V 1 − V 2 121.54 − 2400 a 0.05 VR = = x100% = 1.27% V1 121.54 a 0.05 39
  • 24. 2.9 AUTOTRANFORMERS OR 1.0m 1.0m LOAD LOAD Figure 2.19: Autotransformer schematic • Figure 2.19 show the autotransformer schematic. • Autotransformer is a transformer with only one winding. • The low-voltage coil is essentially placed on top of the high-voltage coil and is called the series coil. • The connection is called an autotransformer and can be used as a step-up or a step- down transformer. • The advantages of autotransformer are:- (i) cheaper (ii) more efficient, because losses stay the same while the rating goes up compared to a conventional transformer (iii) lower exciting current (iv) better voltage regulation • The disadvantages of autotransformer are:- (i) larger short circuit current available (ii) no isolation between the primary and secondary 40
  • 25. Example 11 A 220/440V, 25kVA and 50 Hz transformer is connected as an autotransformer to transform 660V to 220V. (i) Determine the ratio ‘a’. (ii) Determine the kVA rating of the auto transformer. (iii) With a load of 25 kVA, 0.8 lagging power factor connected to 220 V terminals, determine the currents in the load and the two transformer windings. Solution I1 1,0m 1,0m 1,0m N1 I2 V1=660V N2 I2-I1 V2=220V N 1 660 (i) a= = =3 N 2 220 25kVA (ii) I1 = = 37.87 A 660 660(37.87) kVAauto = = 25kVA 1000 25kVA (iii) I2 = = 113.64 A 220 I 2 − I 1 = 113.64 − 37.87 = 75.77 A 41
  • 26. 2.10 THREE PHASE TRANSFORMERS Introduction: • Three phase transformers are used throughout industry to change values of three phase voltage and current. • Since three phase power is the most common way in which power is produced, transmitted, an used, an understanding of how three phase transformer connections are made is essential. Construction: • A three phase transformer is constructed by winding three single phase transformers on a single core. • These transformers are put into an enclosure which is then filled with dielectric oil. • The dielectric oil performs several functions. • Since it is a dielectric, a nonconductor of electricity, it provides electrical insulation between the windings and the case. • It is also used to help provide cooling and to prevent the formation of moisture, which can deteriorate the winding insulation. Connections: • There are only 4 possible transformer combinations: 1. Delta to Delta - use: industrial applications 2. Delta to Wye - use : most common; commercial and industrial 3. Wye to Delta - use : high voltage transmissions 4. Wye to Wye - use : rare, don't use causes harmonics and balancing problems. • Three-phase transformers are connected in delta or wye configurations. • A wye-delta transformer has its primary winding connected in a wye and its secondary winding connected in a delta (see Figure 2.20). • A delta-wye transformer has its primary winding connected in delta and its secondary winding connected in a wye (see Figure 2.21). 42
  • 27. Figure 2.20:Wye-Delta connection Figure 2.21:Delta-Wye connection Delta Conections: • A delta system is a good short-distance distribution system. • It is used for neighborhood and small commercial loads close to the supplying substation. • Only one voltage is available between any two wires in a delta system. • The delta system can be illustrated by a simple triangle. • A wire from each point of the triangle would represent a three-phase, three-wire delta system. • The voltage would be the same between any two wires (see Figure 2.22). Figure 2.22 43
  • 28. Wye Connections: • In a wye system the voltage between any two wires will always give the same amount of voltage on a three phase system. • However, the voltage between any one of the phase conductors (X1, X2, X3) and the neutral (X0) will be less than the power conductors. • For example, if the voltage between the power conductors of any two phases of a three wire system is 208v, then the voltage from any phase conductor to ground will be 120v. • This is due to the square root of three phase power. • In a wye system, the voltage between any two power conductors will always be 1.732 (which is the square root of 3) times the voltage between the neutral and any one of the power phase conductors. • The phase-to-ground voltage can be found by dividing the phase-to-phase voltage by 1.732 (see Figure 2.23). Figure 2.23 Connecting Single-Phase Transformers into a Three-Phase Bank: • If three phase transformation is need and a three phase transformer of the proper size and turns ratio is not available, three single phase transformers can be connected to form a three phase bank. • When three single phase transformers are used to make a three phase transformer bank, their primary and secondary windings are connected in a wye or delta connection. • The three transformer windings in Figure 2.24 are labeled H1 and the other end is labeled H2. • One end of each secondary lead is labeled X1 and the other end is labeled X2. 44
  • 29. Figure 2.24 • Figure 2.25 shows three single phase transformers labeled A, B, and C. • The primary leads of each transformer are labeled H1 and H2 and the secondary leads are labeled X1 and X2. • The schematic diagram of Figure 2.24 will be used to connect the three single phase transformers into a three phase wye-delta connection as shown in Figure 2.26. Figure 2.25 45
  • 30. Figure 2.26 • The primary winding will be tied into a wye connection first. • The schematic in Figure 2.24 shows, that the H2 leads of the three primary windings are connected together, and the H1 lead of each winding is open for connection to the incoming power line. • Notice in Figure 2.26 that the H2 leads of the primary windings are connected together, and the H1 lead of each winding has been connected to the incoming primary power line. • Figure 2.24 shows that the X1 lead of the transformer A is connected to the X2 lead of transformer c. • Notice that this same connection has been made in Figure 2.26. • The X1 lead of transformer B is connected to X1, lead of transformer A, and the X1 lead of transformer B is connected to X2 lead of transformer A, and the X1 lead of transformer C is connected to X2 lead of transformer B. • The load is connected to the points of the delta connection. 46
  • 31. Tutorial 2 1. A step-down transformer is rated 25kVA, 660-240 V and has the following equivalent circuit parameter: Rp = 15Ω Rs = 10Ω Rm = 50000Ω Xp = 20Ω Xs = 8Ω Xm = 13000Ω Find the equivalent winding impedance referred to the high side and the low side. 2. Short-circuit and open-circuit tests were performed on a 10kVA transformer,50 Hz, rated 400V-240V, with the results listed below. Vsc = 10 V Voc = 240 V Isc = 10kVA/400V=25A I oc = 4 A Psc = 120 W Poc = 80 W (i) Draw the equivalent circuit parameters of the transformer referred to the high side. (ii) Draw the equivalent circuit parameters of the transformer referred to the low side. 3. The coil possesses 400 turns and links an ac flux having peak value of 2mWb. If the frequency is 60Hz, calculate the induced voltage E. 4. A transformer having 90 turns on the primary and 2250 turns on the secondary is connected to a 120V, 60Hz source. Calculate: (i) The effective voltage for the secondary side. (ii) The peak voltage for the secondary side. 5. An ideal-transformer having 90 turns on the primary and 2250 turns on the secondary is connected to a 200V, 50 Hz source. The load across the secondary draws a current of 2A at a power factor of 0.8 lagging. Calculate: (i) The effective value of the primary current. (ii) The primary current if the secondary current is 100mA. (iii) The peak flux linked by the secondary winding. 6. The secondary winding of a transformer has a terminal voltage of Vs (t ) = 282.8 sin 377t V. The turn ratio of the transformer is 50/200. If the secondary current of the transformer is is (t ) = 7.07 sin(377t − 36.87 ) A, calculate: 0 (i) the primary current of the transformer (ii) voltage regulation 47
  • 32. The impedances of this transformer referred to the primary side are Req = 0.05Ω Rc = 75Ω X eq = 0.225Ω X m = 20Ω 7. A 20kVA 8000/277V distribution transformer has the following equivalent circuit parameter: R p = 32Ω Rs = 0.05Ω X p = 45Ω X s = 0.06Ω Rc = 250kΩ X m = 30kΩ (i) Draw the equivalent circuit of this transformer referred to the high voltage side. (ii) Calculate the voltage regulation if:- (a) the transformer is supplying rated load at 277V and 0.8 pf lagging, (b) the transformer is supplying load at 200V,100W and 0.85 pf lagging. (c) the transformer is supplying load at 18kVA, 250V and 0.8 pf leading. 8. Short-circuit and open-circuit tests were performed on a 1000VA transformer, 50 Hz, rated at 230V/115V, and the results are listed as follows: Vsc = 13.2 V Voc = 115 V Isc = 4.35 A I oc = 0.45 A Psc = 20.1 W Poc = 30 W (i) Draw the equivalent circuit with the necessary parameters of the transformer referred to the low voltage side. (ii) Find the input voltage of the transformer if the transformer is connected to a 140Var, 110V at 0.75 pf lagging 48