SlideShare une entreprise Scribd logo
1  sur  21
Performances of distribution
transformer installed in
metallic enclosures - An
Australian experience




                     Neha kardam
                     M.Tech (power
                     system)
                     11/pps/010
Introduction
   Highly restrictive local environmental and urban
    planning regulations have resulted in the
    development of very compact packaged substation
    with extremely arduous service conditions for built
    in transformer.

   In this oil immersed, ONAN cooled, and
    hermetically sealed distribution transformers rated
    750-2000 KVA is used, highlighting their distinct
    features as follows:-
     1.Unique design
     2. loading capability
     3. reliability performance
     4. safety features
Development of kiosk substation

 The packaged substation in Australia
  are better known as pad mounted or
  kiosk substations.
 Prefabricated substations as type
  tested equipment comprising
  transformer, low voltage, and high
  voltage (HV) switchgear, connections,
  and auxiliary equipment in an
  enclosure to supply low voltage
  energy from high voltage system.
 In Europe, distribution power transformers
  and MV and LV switchgear are fully
  standardized and type-tested ―off-shelf‖
  products.
 The first IEC standard for prefabricated
  HV/LV substations was published in 1995.
Performance of kiosk transformer
A. Factors affecting life of distribution
   transformer
 Australian electrical utilities expect that an
  average design life for a modern oil-
  immersed distribution transformer should
  be in excess of 20–30 years.
 Distribution transformers are relatively
  inexpensive, very reliable, and easy to
  replace.
   First, there is a very emaciated possibility of
    using a non optimal rating of those
    transformers.

    Second, degradation of insulating materials
    caused by increased ambient temperatures
    due to restricted air flow around the
    transformer is considered to be much more
    critical for its lifetime than the external
    influences.
B. Loading of distribution
 transformers
   The maximum intermittent loading of
    distribution transformers for normal cycling,
    long-term, and short-term loading as 1.5, 1.8,
    and 2.0 p.u. of the rated current, respectively.

   The ―distribution transformers‖ should be
   further classified into the following three
   categories:
• small distribution transformers: below 500 KVA;
• medium distribution transformers: 500–1500
   KVA;
• large distribution transformers: above 1500
   KVA.
Design features
 Distribution transformers in Australia
  have bushings mounted on the side tank
  walls.
 The kiosk transformers are extremely
  compact and usually very narrow and tall.
 Kiosk transformers have very low
  electrical losses.
 It employ very efficient cooling systems.
Ambient temperature
   Function of the hot-spot temperature and
    the top-oil temperature.

   varies as a function of the climate, the
    season, the time of the day, etc.
Normal service condition for
transformer in free air
  Maximum ambient temperature          40 c
  Average daily ambient temperature    30 c
  Average yearly ambient temperature   20 c




• Australiankiosks employ both–the
hermetically sealed and the free-breathing
distribution transformers.
Impact of enclosure on transformer
temperature rises
 the enclosure is defined by its rated
  maximum power.
 It is clearly stated that the maximum power,
  expected to be delivered from the kiosk, is
  lower than the free-air rating of the
  transformer.
 The Australian standard recommends two
  methods in assessing the impact of the
  enclosure on the transformer hot-spot
  temperature and the top-oil temperature
Correction for an increase in an
ambient temperature due to kiosk
enclosure with 1 transformer
Temperature            Transformer size (KVA)
increase in            250    500    700    1000
ambient due to
                       10     15     20       -
enclosure (c)
The authors have thoroughly investigated both
variations of the second method and it appears
that Table III , which provides recommendations
for correction for increase in ambient
temperature due to the enclosure, should be
extended by considering the following :-
 constructional features of the enclosure,
  including equipment arrangement, ventilation
  systems, and protection (IP) level.
 losses in transformer and switchgear; with a
  large number of transformer-switchgear
  arrangements, the range of losses released in
  the kiosk-substation could be very wide.
 external conditions (solar radiation, wind,
  slope sites)
 Larger distribution transformers (1000–2500
  kVA)
 Provision for enclosures manufactured from
  alternative materials.
Enclosure
 The kiosk consists of a metallic enclosure
  with transformer and switchgear
  compartments and base.
 The enclosure and compartments are made
  of 2.5-mm-thick galvanized mild steel sheets.
 The kiosk base is made of a reinforced
  concrete or hot-dip-galvanized steel
  channels.
 The transformer compartment is in the
  middle, completely segregated from the LV
  and the MV switchgear compartments.
 The standard required degree of
  protection for switchgear and
  transformer compartments is IP24D.
 Ventilation openings are arranged to
  prevent any undesired condensation on
  electrical equipment and inner wall
  surfaces.
 The optimum airflow is achieved
Metallic enclosure with ventilation
opening on side walls
Air-Temperature diagram along
sidewall for 1000kVA kiosk
substation
The authors adopted temperatures at two
  heights as relevant for transformer
  loading assessment as follows:
 Top height
 mid height
Conclusion
 The reliability of the entire LV network and, thus,
  most activities in residential, industrial, and
  commercial areas depends on the reliability of
  kiosk substations and their most important
  part—the distribution transformer.
 A design investigation was formulated to show
  the performance of optimized distribution
  transformer designs when installed in kiosk
  substations. Simple methodology was developed
  to forecast temperature rises in transformer
  compartments at two different levels: - mid height
  and top height of the transformer compartment.
  Heat-run tests confirmed calculated temperature
  rises under different overload conditions
Thank you

Contenu connexe

Tendances

Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substationsharique_64
 
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWARFACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWARashwini kumar
 
GAS INSULATED SUB-STATION
GAS INSULATED SUB-STATIONGAS INSULATED SUB-STATION
GAS INSULATED SUB-STATIONsujitmandalsk
 
Challenges in Transformer Technology -by Mr. Krishnaiah (Kryfs)
Challenges in Transformer Technology -by Mr. Krishnaiah (Kryfs)Challenges in Transformer Technology -by Mr. Krishnaiah (Kryfs)
Challenges in Transformer Technology -by Mr. Krishnaiah (Kryfs)ProSIM R & D Pvt. Ltd.
 
27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substationsMugdha Jhanjhote
 
Rio LLC District Cooling
Rio LLC  District CoolingRio LLC  District Cooling
Rio LLC District Coolingguestba4f28
 
End of-life factors in high voltage gas insulated switchgear with sf6 or with...
End of-life factors in high voltage gas insulated switchgear with sf6 or with...End of-life factors in high voltage gas insulated switchgear with sf6 or with...
End of-life factors in high voltage gas insulated switchgear with sf6 or with...Ali Sepehri
 
Gis substation
Gis substationGis substation
Gis substationAsif Eqbal
 
Gas insulated substation 2
Gas insulated substation 2Gas insulated substation 2
Gas insulated substation 2naga pooja
 
GIS (Gas-Insulated Substation) by Bharat & Shanni
GIS (Gas-Insulated Substation) by Bharat & ShanniGIS (Gas-Insulated Substation) by Bharat & Shanni
GIS (Gas-Insulated Substation) by Bharat & ShanniBHARATKUMAR RATHOD
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substationMOHDFAIZAN75
 
District Cooling Service - Presentation to Qatar Rail
District Cooling Service - Presentation to Qatar RailDistrict Cooling Service - Presentation to Qatar Rail
District Cooling Service - Presentation to Qatar RailJaygopal Kottilil
 
Industrial training report
Industrial training report Industrial training report
Industrial training report Pritam Samanta
 
Bus Ducts or Hollow conductors
Bus Ducts or Hollow conductorsBus Ducts or Hollow conductors
Bus Ducts or Hollow conductorsAjay Meena
 
Seminar on Gas Insulated Substation
Seminar on Gas Insulated SubstationSeminar on Gas Insulated Substation
Seminar on Gas Insulated SubstationSoumya Raj Poddar
 
Electrical Power Experience1
Electrical Power Experience1Electrical Power Experience1
Electrical Power Experience1Kendall Pinder
 

Tendances (20)

Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWARFACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
 
GAS INSULATED SUB-STATION
GAS INSULATED SUB-STATIONGAS INSULATED SUB-STATION
GAS INSULATED SUB-STATION
 
Challenges in Transformer Technology -by Mr. Krishnaiah (Kryfs)
Challenges in Transformer Technology -by Mr. Krishnaiah (Kryfs)Challenges in Transformer Technology -by Mr. Krishnaiah (Kryfs)
Challenges in Transformer Technology -by Mr. Krishnaiah (Kryfs)
 
27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations
 
Rio LLC District Cooling
Rio LLC  District CoolingRio LLC  District Cooling
Rio LLC District Cooling
 
End of-life factors in high voltage gas insulated switchgear with sf6 or with...
End of-life factors in high voltage gas insulated switchgear with sf6 or with...End of-life factors in high voltage gas insulated switchgear with sf6 or with...
End of-life factors in high voltage gas insulated switchgear with sf6 or with...
 
Gis substation
Gis substationGis substation
Gis substation
 
Gas insulated substation 2
Gas insulated substation 2Gas insulated substation 2
Gas insulated substation 2
 
GIS (Gas-Insulated Substation) by Bharat & Shanni
GIS (Gas-Insulated Substation) by Bharat & ShanniGIS (Gas-Insulated Substation) by Bharat & Shanni
GIS (Gas-Insulated Substation) by Bharat & Shanni
 
GIS-NESCL-6
GIS-NESCL-6GIS-NESCL-6
GIS-NESCL-6
 
Gas insulated substation.
Gas insulated substation.Gas insulated substation.
Gas insulated substation.
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 
Ppt
PptPpt
Ppt
 
District Cooling Service - Presentation to Qatar Rail
District Cooling Service - Presentation to Qatar RailDistrict Cooling Service - Presentation to Qatar Rail
District Cooling Service - Presentation to Qatar Rail
 
Industrial training report
Industrial training report Industrial training report
Industrial training report
 
CHILLED BEAM
CHILLED BEAMCHILLED BEAM
CHILLED BEAM
 
Bus Ducts or Hollow conductors
Bus Ducts or Hollow conductorsBus Ducts or Hollow conductors
Bus Ducts or Hollow conductors
 
Seminar on Gas Insulated Substation
Seminar on Gas Insulated SubstationSeminar on Gas Insulated Substation
Seminar on Gas Insulated Substation
 
Electrical Power Experience1
Electrical Power Experience1Electrical Power Experience1
Electrical Power Experience1
 

En vedette

Ve modify-compact-substation
Ve modify-compact-substationVe modify-compact-substation
Ve modify-compact-substationKamran Uddin
 
transformer protection from over heating
transformer protection from over heatingtransformer protection from over heating
transformer protection from over heatingbishow kandel
 
Peco distribution-transformer
Peco distribution-transformerPeco distribution-transformer
Peco distribution-transformercomsats
 
Testing,maintenance&protection
Testing,maintenance&protectionTesting,maintenance&protection
Testing,maintenance&protectionRakesh Joshi
 
Power Transformer Differential protection
Power Transformer Differential protectionPower Transformer Differential protection
Power Transformer Differential protectionRishi Tandon
 
Protection of transformer
Protection of transformerProtection of transformer
Protection of transformerSumeet Ratnawat
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protectionashwin fcc
 

En vedette (9)

Ve modify-compact-substation
Ve modify-compact-substationVe modify-compact-substation
Ve modify-compact-substation
 
transformer protection from over heating
transformer protection from over heatingtransformer protection from over heating
transformer protection from over heating
 
Peco distribution-transformer
Peco distribution-transformerPeco distribution-transformer
Peco distribution-transformer
 
Distribution transformer
Distribution transformerDistribution transformer
Distribution transformer
 
Testing,maintenance&protection
Testing,maintenance&protectionTesting,maintenance&protection
Testing,maintenance&protection
 
Power Transformer Differential protection
Power Transformer Differential protectionPower Transformer Differential protection
Power Transformer Differential protection
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Protection of transformer
Protection of transformerProtection of transformer
Protection of transformer
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
 

Similaire à Performances of distribution transformer installed in metallic enclosures

Prefabricated compact transformer
Prefabricated compact transformerPrefabricated compact transformer
Prefabricated compact transformerJoeChueng
 
EPE Profile 13.01.16 (Digital Links)
EPE Profile 13.01.16 (Digital Links)EPE Profile 13.01.16 (Digital Links)
EPE Profile 13.01.16 (Digital Links)Hayden Sherwood
 
Instrument transformer __cvt_transformer
Instrument transformer __cvt_transformerInstrument transformer __cvt_transformer
Instrument transformer __cvt_transformerjodhpur university
 
Ac Test Transformer
Ac Test TransformerAc Test Transformer
Ac Test Transformerkennypowerhv
 
How to reduced transformer losses report
How to reduced transformer losses reportHow to reduced transformer losses report
How to reduced transformer losses reportkamal soni
 
Ramendra summer training presentation
Ramendra summer training presentationRamendra summer training presentation
Ramendra summer training presentationRamendra Dhiman
 
Engineering Final Year Project Report on "Electrical Safety and Protection of...
Engineering Final Year Project Report on "Electrical Safety and Protection of...Engineering Final Year Project Report on "Electrical Safety and Protection of...
Engineering Final Year Project Report on "Electrical Safety and Protection of...Pratap Bhunia
 
Hts transformer
Hts transformerHts transformer
Hts transformerARGHA SAHA
 
Inovative Solution by Transformers Manufacturers in India
Inovative Solution by Transformers Manufacturers in IndiaInovative Solution by Transformers Manufacturers in India
Inovative Solution by Transformers Manufacturers in IndiaSynergy Transformers
 
Edwin Newsletter on transformer failures on 13 October 2015
Edwin Newsletter on transformer failures on 13 October 2015Edwin Newsletter on transformer failures on 13 October 2015
Edwin Newsletter on transformer failures on 13 October 2015Edwin Low
 
Power factor corrector
Power factor correctorPower factor corrector
Power factor correctorJoeChueng
 
transformer Sales, after sales & service presentation
transformer Sales, after sales & service presentationtransformer Sales, after sales & service presentation
transformer Sales, after sales & service presentationFawaz Baik
 

Similaire à Performances of distribution transformer installed in metallic enclosures (20)

Mike's presentation
Mike's presentationMike's presentation
Mike's presentation
 
KPX Promotionnal Catalogue
KPX Promotionnal CatalogueKPX Promotionnal Catalogue
KPX Promotionnal Catalogue
 
Makpower - Furnace Transformer Manufacturer in India
Makpower - Furnace Transformer Manufacturer in IndiaMakpower - Furnace Transformer Manufacturer in India
Makpower - Furnace Transformer Manufacturer in India
 
Prefabricated compact transformer
Prefabricated compact transformerPrefabricated compact transformer
Prefabricated compact transformer
 
EPE Profile 13.01.16 (Digital Links)
EPE Profile 13.01.16 (Digital Links)EPE Profile 13.01.16 (Digital Links)
EPE Profile 13.01.16 (Digital Links)
 
Instrument transformer __cvt_transformer
Instrument transformer __cvt_transformerInstrument transformer __cvt_transformer
Instrument transformer __cvt_transformer
 
Ac Test Transformer
Ac Test TransformerAc Test Transformer
Ac Test Transformer
 
Standing type outdoor full sf6 gas insualted ring main unit
Standing type outdoor full sf6 gas insualted ring main unitStanding type outdoor full sf6 gas insualted ring main unit
Standing type outdoor full sf6 gas insualted ring main unit
 
Standing type GIS RMU
Standing type GIS RMUStanding type GIS RMU
Standing type GIS RMU
 
Transformer ppt
Transformer pptTransformer ppt
Transformer ppt
 
How to reduced transformer losses report
How to reduced transformer losses reportHow to reduced transformer losses report
How to reduced transformer losses report
 
Ramendra summer training presentation
Ramendra summer training presentationRamendra summer training presentation
Ramendra summer training presentation
 
Engineering Final Year Project Report on "Electrical Safety and Protection of...
Engineering Final Year Project Report on "Electrical Safety and Protection of...Engineering Final Year Project Report on "Electrical Safety and Protection of...
Engineering Final Year Project Report on "Electrical Safety and Protection of...
 
5 power house
5 power house5 power house
5 power house
 
Hts transformer
Hts transformerHts transformer
Hts transformer
 
Inovative Solution by Transformers Manufacturers in India
Inovative Solution by Transformers Manufacturers in IndiaInovative Solution by Transformers Manufacturers in India
Inovative Solution by Transformers Manufacturers in India
 
Edwin Newsletter on transformer failures on 13 October 2015
Edwin Newsletter on transformer failures on 13 October 2015Edwin Newsletter on transformer failures on 13 October 2015
Edwin Newsletter on transformer failures on 13 October 2015
 
Power factor corrector
Power factor correctorPower factor corrector
Power factor corrector
 
transformer Sales, after sales & service presentation
transformer Sales, after sales & service presentationtransformer Sales, after sales & service presentation
transformer Sales, after sales & service presentation
 
Shivesh ntpc ppt
Shivesh ntpc pptShivesh ntpc ppt
Shivesh ntpc ppt
 

Performances of distribution transformer installed in metallic enclosures

  • 1. Performances of distribution transformer installed in metallic enclosures - An Australian experience Neha kardam M.Tech (power system) 11/pps/010
  • 2. Introduction  Highly restrictive local environmental and urban planning regulations have resulted in the development of very compact packaged substation with extremely arduous service conditions for built in transformer.  In this oil immersed, ONAN cooled, and hermetically sealed distribution transformers rated 750-2000 KVA is used, highlighting their distinct features as follows:- 1.Unique design 2. loading capability 3. reliability performance 4. safety features
  • 3. Development of kiosk substation  The packaged substation in Australia are better known as pad mounted or kiosk substations.  Prefabricated substations as type tested equipment comprising transformer, low voltage, and high voltage (HV) switchgear, connections, and auxiliary equipment in an enclosure to supply low voltage energy from high voltage system.
  • 4.  In Europe, distribution power transformers and MV and LV switchgear are fully standardized and type-tested ―off-shelf‖ products.  The first IEC standard for prefabricated HV/LV substations was published in 1995.
  • 5. Performance of kiosk transformer A. Factors affecting life of distribution transformer  Australian electrical utilities expect that an average design life for a modern oil- immersed distribution transformer should be in excess of 20–30 years.  Distribution transformers are relatively inexpensive, very reliable, and easy to replace.
  • 6. First, there is a very emaciated possibility of using a non optimal rating of those transformers.  Second, degradation of insulating materials caused by increased ambient temperatures due to restricted air flow around the transformer is considered to be much more critical for its lifetime than the external influences.
  • 7. B. Loading of distribution transformers  The maximum intermittent loading of distribution transformers for normal cycling, long-term, and short-term loading as 1.5, 1.8, and 2.0 p.u. of the rated current, respectively.  The ―distribution transformers‖ should be further classified into the following three categories: • small distribution transformers: below 500 KVA; • medium distribution transformers: 500–1500 KVA; • large distribution transformers: above 1500 KVA.
  • 8. Design features  Distribution transformers in Australia have bushings mounted on the side tank walls.  The kiosk transformers are extremely compact and usually very narrow and tall.  Kiosk transformers have very low electrical losses.  It employ very efficient cooling systems.
  • 9. Ambient temperature  Function of the hot-spot temperature and the top-oil temperature.  varies as a function of the climate, the season, the time of the day, etc.
  • 10. Normal service condition for transformer in free air Maximum ambient temperature 40 c Average daily ambient temperature 30 c Average yearly ambient temperature 20 c • Australiankiosks employ both–the hermetically sealed and the free-breathing distribution transformers.
  • 11. Impact of enclosure on transformer temperature rises  the enclosure is defined by its rated maximum power.  It is clearly stated that the maximum power, expected to be delivered from the kiosk, is lower than the free-air rating of the transformer.  The Australian standard recommends two methods in assessing the impact of the enclosure on the transformer hot-spot temperature and the top-oil temperature
  • 12. Correction for an increase in an ambient temperature due to kiosk enclosure with 1 transformer Temperature Transformer size (KVA) increase in 250 500 700 1000 ambient due to 10 15 20 - enclosure (c) The authors have thoroughly investigated both variations of the second method and it appears that Table III , which provides recommendations for correction for increase in ambient temperature due to the enclosure, should be extended by considering the following :-
  • 13.  constructional features of the enclosure, including equipment arrangement, ventilation systems, and protection (IP) level.  losses in transformer and switchgear; with a large number of transformer-switchgear arrangements, the range of losses released in the kiosk-substation could be very wide.  external conditions (solar radiation, wind, slope sites)  Larger distribution transformers (1000–2500 kVA)  Provision for enclosures manufactured from alternative materials.
  • 14. Enclosure  The kiosk consists of a metallic enclosure with transformer and switchgear compartments and base.  The enclosure and compartments are made of 2.5-mm-thick galvanized mild steel sheets.  The kiosk base is made of a reinforced concrete or hot-dip-galvanized steel channels.  The transformer compartment is in the middle, completely segregated from the LV and the MV switchgear compartments.
  • 15.  The standard required degree of protection for switchgear and transformer compartments is IP24D.  Ventilation openings are arranged to prevent any undesired condensation on electrical equipment and inner wall surfaces.  The optimum airflow is achieved
  • 16. Metallic enclosure with ventilation opening on side walls
  • 17. Air-Temperature diagram along sidewall for 1000kVA kiosk substation
  • 18. The authors adopted temperatures at two heights as relevant for transformer loading assessment as follows:  Top height  mid height
  • 19.
  • 20. Conclusion  The reliability of the entire LV network and, thus, most activities in residential, industrial, and commercial areas depends on the reliability of kiosk substations and their most important part—the distribution transformer.  A design investigation was formulated to show the performance of optimized distribution transformer designs when installed in kiosk substations. Simple methodology was developed to forecast temperature rises in transformer compartments at two different levels: - mid height and top height of the transformer compartment. Heat-run tests confirmed calculated temperature rises under different overload conditions