APPLICATION NOTE
STANDARD EN 50160
VOLTAGE CHARACTERISTICS OF ELECTRICITY SUPPLIED
BY PUBLIC ELECTRICITY NETWORKS
Antoni Klajn, Marta Bątkiewicz-Pantuła
March 2017
ECI Publication No Cu0147
Available from www.leonardo-energy.org
Publication No Cu0147
Issue Date: March 2017
Page i
Document Issue Control Sheet
Document Title: Application Note – Standard EN 50 160
Publication No: Cu0147
Issue: 03
Release: Public
Content provider(s) Antoni Klajn, Marta Bątkiewicz-Pantuła
Author(s): Antoni Klajn, Marta Bątkiewicz-Pantuła
Editorial and language review Bruno De Wachter (editorial), Noel Montrucchio (language)
Content review: Stefan Fassbinder, David Chapman, Roman Targosz
Document History
Issue Date Purpose
1 July 2004 First publication, in the framework of the Power Quality Application Guide
2 March
2013
Completely rewritten, in the framework of the Good Practice Guide
3 March
2017
Adapted after content review
Disclaimer
While this publication has been prepared with care, European Copper Institute and other contributors provide
no warranty with regards to the content and shall not be liable for any direct, incidental or consequential
damages that may result from the use of the information or the data contained.
Copyright© European Copper Institute.
Reproduction is authorized providing the material is unabridged and the source is acknowledged.
Publication No Cu0147
Issue Date: March 2017
Page ii
CONTENTS
Summary ........................................................................................................................................................ 1
Introduction.................................................................................................................................................... 2
Basic definitions of voltage parameters.......................................................................................................... 4
Statistical philosophy.................................................................................................................................... 13
Low-voltage supply characteristics ............................................................................................................... 19
General ................................................................................................................................................................19
Continuous phenomena .......................................................................................................................................19
Power frequency variation.....................................................................................................................19
Supply voltage variation.........................................................................................................................20
Rapid voltage changes............................................................................................................................20
Supply-voltage unbalance ......................................................................................................................21
Harmonic voltage ...................................................................................................................................21
Interharmonic voltages ..........................................................................................................................23
Mains signaling voltages.........................................................................................................................23
Voltage events......................................................................................................................................................24
Interruptions of the supply voltage........................................................................................................24
Supply voltage dips/swells .....................................................................................................................24
Medium-voltage supply characteristics ........................................................................................................ 27
General ................................................................................................................................................................27
Continuous phenomena .......................................................................................................................................27
Power frequency ....................................................................................................................................27
Supply voltage variations .......................................................................................................................27
Rapid voltage changes............................................................................................................................28
Supply voltage unbalance.......................................................................................................................28
Harmonic voltage ...................................................................................................................................28
Interharmonic voltages ..........................................................................................................................29
Mains signaling voltage ..........................................................................................................................29
Voltage events......................................................................................................................................................29
Supply voltage dips/swells .....................................................................................................................29
Publication No Cu0147
Issue Date: March 2017
Page iii
High-voltage supply characteristics............................................................................................................... 31
General ................................................................................................................................................................31
Continuous phenomena .......................................................................................................................................31
Power frequency variations ...................................................................................................................31
Supply voltage variations .......................................................................................................................31
Rapid voltage changes............................................................................................................................31
Voltage events......................................................................................................................................................33
Supply voltage dips/swells .....................................................................................................................33
Performance criteria for voltage dips/swells ................................................................................................ 34
Electromagnetic environment classification ................................................................................................. 35
Classes of measurement methods ................................................................................................................ 37
Measurement aggregation over time intervals....................................................................................................37
Measurement aggregation algorithm...................................................................................................................37
Conclusions................................................................................................................................................... 38
References.................................................................................................................................................... 38
Publication No Cu0147
Issue Date: March 2017
Page 1
SUMMARY
Three parties exert an influence on the power quality in the electric network: the network operator, the
network user and the manufacturer of the network equipment. Standard EN50160 represents a compromise
between those three parties.
The important advantages of the EN 50160 standard are:
 The definition of the voltage parameters important for power quality
 The quantitative determination of reference values that can be used in the power quality evaluation
EN 50160 deals with the voltage characteristics in statistical or probabilistic terms. It gives recommendations
that, for a percentage of measurements (e.g. 95%) over a given time, the value must be within the specified
limits. This boundary value will be accepted as the compatibility level between the level of disturbances in the
network and the level of immunity of equipment. In this way, the responsibilities of the network operator,
equipment manufacturer and user are matched and clarified.
EN 50160 prescribes separate voltage characteristics that Low Voltage (LV), Medium Voltage (MV) and High
Voltage (HV) public networks should maintain. It makes a distinction in each of these three these categories
between:
 Continuous phenomena, i.e. deviations from the nominal values that occur continuously over time.
Such phenomena occur mainly due to specific load patterns, changes of load, or nonlinear loads. For
some of these phenomena, limits are specified.
 Voltage events, i.e. sudden and significant deviations from normal or desired wave shape. Voltage
events typically occur due to unpredictable events (e.g. faults) or to external causes (e.g. weather
conditions, third party actions). At present, only indicative values can be given for voltage events.
EN 50160 also prescribes minimum performance criteria that electrical equipment should maintain when they
are subjected to voltage dips or swells on the network.
In addition, EN 50160 provides an electromagnetic environment classification system, as well as three classes
of measurement methods. The latter include an algorithm for aggregation of measurement results over time
intervals.
If the customer has higher requirements than the minimum performance criteria prescribed in this standard,
they should instigate their own mitigation measures. Another option is to negotiate a separate agreement for
a higher supply quality with the power supplier.
Publication No Cu0147
Issue Date: March 2017
Page 2
INTRODUCTION
To be optimally useful, the voltage at which electricity is supplied to the user should alternate at a constant
frequency, with a perfect sine wave and with a constant magnitude. In practice, however, there are many
factors which cause deviations from this ideal. These include the way in which the electricity is used.
Moreover, electrical energy is a unique product because it is consumed at the instant at which it is generated.
Consequently, measurement and evaluation of the power quality (PQ) must also be instantaneous. The
technical standard EN 50160 describes the required characteristics of electricity, at the point of supply to the
consumer, in terms of the alternating voltage.
Ensuring PQ is a complex problem, because it is influenced by the actions of three parties:
 The network operator
 The manufacturer of electrical equipment
 The network user (energy consumer), the user of this equipment.
The relationships are illustrated in Figure 1:
Figure 1—Illustration of reciprocal correlation between the three co-originators of power quality.
Each of these parties has a certain influence on PQ as well as attendant duties and responsibilities.
 The network operator should supply energy to meet the demand on the network, maintain the
network in a good condition (e.g. sustain the short-circuit power at a sufficient level), as well as
providing redundancy in network operation in order to meet the requirements of applicable
standards.
 The network user should select equipment and ensure its correct installation and operation to limit
the level of electromagnetic disturbances introduced into the network. They should install
uninterruptible power supplies (UPS) or other backup systems if appropriate. Equipment is influenced
by supply disturbances and by other equipment in the installation, and it is in itself also influencing
the supply quality. Correct operation requires maintaining the level of electromagnetic disturbances
on other equipment below the limit as described in the EN 61000 series of the EMC standard.
 The equipment manufacturer should provide the market with equipment with acceptably low levels
of disturbance emissions onto the network as well as a sufficiently high level of immunity to the level
of disturbances likely to exist in the network.
Publication No Cu0147
Issue Date: March 2017
Page 3
The flow of energy to a network user’s appliances gives rise to proportional electric currents. As these currents
flow through the conductors of the supply system, they cause voltage drops. The magnitude of the supply
voltage for an individual network user at any instant is therefore a function of the cumulative voltage drops on
all of the components of the system through which that network user is supplied, and determined both by the
individual user’s demand and by the simultaneous demands of other network users (Figure 11). The impact of
PQ on individual network users is a complex problem.
The subject of this document is a detailed presentation and analysis of the requirements of the EN 50160
standard. Methods of measuring supply voltage parameters as well as examples of measurements are
presented.
Publication No Cu0147
Issue Date: March 2017
Page 4
BASIC DEFINITIONS OF VOLTAGE PARAMETERS
The following terms and definitions apply for the purposes of the EN 50160 standard:
Definitions concerning the normal (regular) state of the network operation
Network operator—the party responsible for operating, maintaining and, if necessary, developing the supply
network in a given area in order to ensure that the network is able to meet reasonable long-term demands for
electricity supply.
Network user—a party being supplied by or supplying to an electricity supply network.
Nominal voltage Un —the voltage by which a supply network is designated and to which certain operating
characteristics are referred.
Supply terminal—a point in a public supply network at which electrical energy is exchanged between
contractual partners. The terminal is designed for this task and its location is fixed in the contract. The point
may differ from, for example, the electricity metering point or the point of common coupling.
Point of common coupling (PCC)—the point on a public power supply network at which other loads are, or
could be, connected. It is the point in the public network that is electrically the nearest to the connected load.
Supply voltage—the RMS value of the voltage at a given time at the supply terminal, measured over a given
time interval.
Declared supply voltage Uc—the supply voltage agreed by the network operator and the network user.
Generally the declared supply voltage Uc is the same as nominal voltage Un but it may also be different and
defined by an agreement between network operator and the network user.
Reference voltage (for interruptions, voltage dips and voltage swells evaluation)—is a value specified as the
basis on which residual voltage, thresholds and other values are expressed in per unit or percentage terms. For
the purpose of this standard, the reference voltage is the nominal or declared voltage of the supply system.
Frequency of the supply voltage—the repetition rate of the fundamental wave of the supply voltage measured
over a given time interval.
Nominal frequency—the nominal value of the frequency of the supply voltage.
Levels of voltage have been divided as follows:
High voltage—a voltage whose nominal RMS value is 36 kV<Un<150 kV.
Medium voltage—a voltage whose nominal RMS value is 1 kV<Un≤36 kV.
Low voltage—a voltage whose nominal RMS value is Un≤ 1 kV.
In some countries, the boundary between MV and HV may be different as a result of pre-existing network
structures.
Normal operating condition—an operating condition for an electricity network in which load and generation
demands are met, system switching operations are made and faults are cleared by an automatic protection
system, in the absence of exceptional circumstances, such as:
Publication No Cu0147
Issue Date: March 2017
Page 5
A. Temporary supply arrangements
B. Non-compliance of a network user’s installation or equipment with relevant standards or with the
technical requirements for connection
C. Exceptional situations, such as:
1. Exceptional weather conditions and other natural disasters
2. Third party interference
3. Acts by public authorities
4. Industrial actions (subject to legal requirements)
5. Force majeure
6. Power shortages resulting from external events
Flicker—an unsteady visual sensation induced by a light stimulus. Usually, it applies to a cyclic variation of the
light intensity or spectral distribution of a lamp which is caused by a fluctuation of the supply voltage. Flicker is
typically a symptom of voltage disturbance caused by the use of large fluctuating loads, i.e. those that have
rapidly fluctuating active and reactive power demand.
The threshold above which flicker becomes annoying depends on the frequency and amplitude of the
fluctuation. At certain repetition rates even very small amplitudes can be disturbing, often causing headaches,
among other symptoms Figure 2.
Figure 2—Example of an oscillogram showing the phenomenon of flicker.
Flicker severity—the intensity of flicker annoyance is defined in terms of:
- short-term severity (Pst) measured over a period of ten minutes
- long-term severity (Plt) calculated from a rolling sequence of twelve Pst values over a two hour
interval, according to the following expression:
𝑃𝑙𝑡 = √∑
𝑃𝑠𝑡𝑖
3
12
12
𝑖=1
3
Pst is calculated according to a standardized formula which takes into account the response of the human eye
and brain.
Under normal operating conditions, the long-term flicker severity Plt caused by voltage fluctuation should be
less than or equal to 1 for 95% of the time over a period of one week. Reaction to flicker is subjective and can
vary, depending on the perceived cause of the flicker and the period over which it persists. In some cases, Plt =
1 gives rise to annoyance, whereas in other cases higher levels of Plt are observed without annoyance.
Definitions concerning the abnormal (fault) state of the network operation
Conduced disturbance—an electromagnetic phenomenon propagated along the line conductors of a supply
network. In some cases, an electromagnetic phenomenon is propagated across transformer windings and
hence between networks of different voltage levels. These disturbances may degrade the performance of a
device, a piece of individual equipment or system or they may cause damage.
Supply interruption—a condition in which the voltage at the supply terminals is lower than 5% of the
reference voltage.
Publication No Cu0147
Issue Date: March 2017
Page 6
Supply interruption can be classified as:
A. Pre-arranged, when network users are informed in advance. Prearranged interruptions are typically
due to the execution of scheduled work on the electricity network.
B. Accidental, caused by permanent or transient faults, mostly related to external events, equipment
failures or interference. Accidental supply interruptions are unpredictable, largely random events. An
accidental interruption is classified as:
1) A long interruption (longer than 3 min.)
2) A short interruption (up to and including 3 min.)
The effects of a prearranged interruption can be minimized by network users by taking appropriate measures
to avoid disruption.
Normally, accidental interruptions are caused by the operation of switches or protective devices in response to
a short circuit or the failure of a device on the network.
Figure 3 shows a supply interruption where:
tf is the fall time during which the voltage is falling
ts is the duration of reduced voltage
tr is the rise time during which the voltage is recovering
Figure 3—Illustration of a supply interruption [2].
For polyphase systems, an interruption occurs when the voltage drops below 5% of the reference voltage on
all the phases. Otherwise, it is considered to be a dip on the affected phases.
In some countries, the terms Very Short Interruptions (VSI) or transitory interruptions are used to classify
interruptions with durations shorter than 1 to 5 s. Such interruptions are related to the operation of automatic
reclosing devices.
Long interruption of the supply voltage—under normal operating conditions, the annual frequency of voltage
interruptions longer than three minutes varies substantially across areas. This is due to, among other things,
differences in system layout (e.g. cable systems versus overhead line systems) and environmental and climatic
conditions. The local network operator should be consulted in order to obtain information of what can be
expected in a particular location. In some countries, national interruption statistics are available which give
indicative values.
Publication No Cu0147
Issue Date: March 2017
Page 7
Short interruption of supply voltage—the duration of the short interruptions is up to and including 3 minutes.
Often, the duration of short interruptions may be less than a few seconds. When comparing statistical values
for short interruptions, the following issues should be considered:
 Principles for aggregating events (by adding up events)
 The possible exclusion of Very Short Interruptions (VSI) or transitory interruptions.
In some documents, short interruptions are considered to have durations not exceeding 1 minute. Control
schemes are sometimes applied which need operating times of up to 3 minutes in order to avoid long voltage
interruptions.
Figure 4—Example of an oscillogram of a single phase voltage, showing a short interruption.
Rapid voltage change—a single rapid variation of the RMS value of a voltage between two consecutive levels
which are sustained for definite but unspecified durations.
Transient overvoltage—a short duration oscillatory or non-oscillatory overvoltage, usually highly damped and
with a duration of a few milliseconds or less. Transient overvoltages are usually caused by lightning, switching
or the operation of fuses. The rise time of a transient overvoltage can vary from less than a microsecond up to
a few milliseconds.
Voltage dip—a temporary reduction of the RMS voltage below a specified start threshold. For the purpose of
the standard, the dip start threshold is equal to 90% of the reference voltage. Typically, a dip is associated with
the occurrence and termination of a short circuit or with other extreme current variations on the system or an
installation connected to it.
For the purpose of the standard, a voltage dip is a two dimensional electromagnetic disturbance, the level of
which is determined both by the residual voltage and the time duration.
Voltage dip duration—the time between the instant at which the RMS voltage at a particular point in an
electricity supply system drops below the start threshold and the instant at which it rises above the end
threshold. For the purposes of this standard, the duration of a voltage dip is from 10 ms up to and including 1
minute.
For polyphase events, a dip begins when the voltage of at least one phase drops below the dip start threshold
and ends when all voltages are equal to or higher than the dip end threshold.
Voltage dip start threshold—the RMS value of the voltage on an electricity supply system specified for the
purpose of defining the start of a voltage dip.
Voltage dip end threshold—the RMS value of the voltage on an electricity supply system specified for the
purpose of defining the end of a voltage dip.
Voltage dip residual voltage—the minimum value of RMS voltage recorded during a voltage dip. For the
purpose of this standard, the residual voltage is expressed as a percentage of the reference voltage.
Figure 5 shows a dip with a residual voltage of 40%. The symbols are the same as defined for Figure 3.
Publication No Cu0147
Issue Date: March 2017
Page 8
Figure 5—Illustration of a voltage dip with 40% retained voltage [2].
Figure 6 shows the voltage waveform during a dip to 30% residual voltage.
Figure 6—Illustration of voltage dip waveform during a voltage dip [2].
Voltage fluctuation—a series of voltage changes or a cyclic variation of the voltage envelope.
Voltage swell—temporary power frequency overvoltage—a temporary increase of the RMS voltage at a point
in the electrical supply system above a specified start threshold. For the purpose of this standard, the following
will be assumed:
 The swell start threshold is equal to 110% of the reference voltage
 A voltage swell is a two dimensional electromagnetic disturbance, the level being determined by both
voltage and duration
 Voltage swells may appear between live conductors or between live conductors and the earth.
Depending on the neutral arrangement, faults to the ground may also give rise to overvoltages
between healthy phases and the neutral
Voltage swell start threshold—the RMS value of the voltage on an electricity supply system specified for the
purpose of defining the start of a voltage swell.
Publication No Cu0147
Issue Date: March 2017
Page 9
Voltage swell end threshold—the RMS value of the voltage on an electricity supply system specified for the
purpose of defining the end of a voltage swell.
Voltage swell duration—the time between the instant at which the RMS voltage at a particular point of an
electricity supply system exceeds the start threshold and the instant at which it drops below the end
threshold.
For the purpose of this standard, the duration of a voltage swell is from 10 ms up to and including 1 minute.
Voltage unbalance—the condition in a polyphase system in which the RMS values of the line-to-line voltages
(fundamental component) or the phase angles between consecutive line voltages are not all equal.
The degree of the inequality is usually expressed as the ratios of the negative and zero sequence components
to the positive sequence component. In this standard, voltage unbalance is considered in relation to three-
phase systems and negative phase sequence only. Figure 7 shows an example of an unbalanced three-phase
system.
Figure 7—An example of voltage unbalance in a 3-phase system.
Figure 8 shows the voltages from Figure 7 as vectors. Note that the angle between vectors is not 120°.
Publication No Cu0147
Issue Date: March 2017
Page 10
Figure 8—Illustration of vector voltages from Figure 7.
Voltage variation—an increase or decrease of the RMS voltage, normally due to load variations. Figure 9
shows an example waveform of a voltage dip and voltage variation (blue plot) and the load (red plot) according
to this voltage variation.
Publication No Cu0147
Issue Date: March 2017
Page 11
Figure 9—Exemplary oscillograms of voltage dip and voltage variation.
The following graph (Figure 10) summarizes the chapter ‘Basic definitions of voltage parameters’. It represents
the most important parameters according to the EN 50160 standard.
Publication No Cu0147
Issue Date: March 2017
Page 12
Figure 10—The most important parameters of the EN 50160 standard in the graphical form.
Harmonic voltage—a sinusoidal voltage with a frequency equal to an integer multiple of the fundamental
frequency of the supply voltage.
Interharmonic voltage—a sinusoidal voltage with a frequency not equal to an integer multiple of the
fundamental. Interharmonic voltages at closely adjacent frequencies can appear at the same time and form a
wide band spectrum.
Publication No Cu0147
Issue Date: March 2017
Page 13
STATISTICAL PHILOSOPHY
The magnitude of the supply voltage for an individual network user at any instant is a function of the
cumulative voltage drops caused by current flows through the components of the system through which the
user is supplied (represented by RS and LS in Figure 11). Consequently, it is a function of current flows on all
other network users (I(t) in Figure 11). The magnitude of the voltage supply is therefore determined both by
the individual user’s demand and by the simultaneous demands of other network users. Since the demands of
every network user and the degree of coincidence between them varies constantly, so does the supply voltage
seen by each user.
Figure 11 shows a notional network with three network users where:
 Ii(t) is the load current of an individual network user
 I(t) is the sum of load currents of all network users supplied from this PCC
 ΔUi is the resulting voltage drop
 RS, LS is the resistance and the inductance of the network.
Figure 11—Illustration of the effect of cumulative voltage drops on an individual network user.
Electricity reaches the user through a large system of generation, transmission and distribution equipment.
Each component in the system is subject to potential damage or failure due to the electrical, mechanical
and/or chemical stresses which arise from several causes, including extreme weather conditions, the ordinary
processes of wear and deterioration with age and interference by human activities, animals, et cetera. Such
damage can affect or even interrupt the supply to one or more network users.
It is also necessary to keep the frequency constant. This requires the capacity to make power generation
match the instantaneous aggregate demand at each instance. Because both power generation capacity and
demand are liable to change in discrete amounts—especially in the event of faults on the generation—
transmission or distribution networks, there is always a risk of a mismatch, resulting in an increase or decrease
of the frequency. The size of frequency variations is reduced by connecting many systems into one large
interconnected system with a total power generation capacity that is very large relative any sudden variations
that are likely to occur.
Publication No Cu0147
Issue Date: March 2017
Page 14
Figure 12—Oscillogram of low voltage at a PCC over the week (1008 of 10 minute measurements).
Figure 13—Statistical distribution of voltage from Figure 12.
Another problem is that of the immunity of equipment to disturbances coming from the network. This is
generally an issue for manufacturers, who can contribute through careful equipment design in accordance
with international standards, and for installation designers, who can contribute by preserving good installation
practices. In some market segments, pre-standards were established by consortiums of manufacturers. An
example of this is the Computer and Business Equipment Manufacturers’ Association (CBEMA) curve shown in
Figure 14. The CBEMA curve, which predates most other standardization in this field, goes back to the era of
analogue power supply. Its low voltage characteristic reflects the energy storage capacity of the filter
capacitor.
Publication No Cu0147
Issue Date: March 2017
Page 15
Figure 14—Immunity of equipment on to supply voltage variations—CBEMA characteristic.
A similar curve of more recent date is that of the Information Technology Industry Council (ITIC). The ITIC curve
(Figure 15) is a straight-line version which is easier to interpret.
Figure 15—Immunity of equipment on to supply voltage variations—ITIC characteristic.
These curves take account only of voltage variations and were originally used to allow manufacturers and
users to understand the capabilities and limitations of computers and business equipment and their voltage
stability requirements.
The CBEMA characteristic can be divided into three areas shown as Type I, II and III in Figure 14. Starting with
Type III, where the duration of the deviation exceeds 2 seconds, both CBEMA and ITIC curves are in agreement
requiring a tolerance of ±15% of Un.
Publication No Cu0147
Issue Date: March 2017
Page 16
The next category, Type II, represents swells or surges and sags or dips. The time period is from one half-cycle
up to the boundary with Type III. For disturbances in this range, energy is supplied or stored by the power
supply reservoir capacitor.
Type I disturbances range from simple spikes at the sub-microsecond end of the range up to one half-cycle.
These disturbances have extremely fast rise and fall times and their high frequency components are easily
trapped by the EMC filters found in modern power supplies.
The EMC filter prevents noise from the power supply reaching equipment and also prevents noise generated
within the equipment from propagating on to the supply. It does not prevent the propagation of low frequency
disturbances such as harmonics.
Apart from the voltage tolerance characteristics addressed by the CBEMA and ITIC curves, there are other
types of network disturbances to which immunity is important, as exemplified by the network testing carried
out by EPRI [6].
Some power quality disturbances arise from unavoidable transient events in the supply system itself, resulting
from faults or switching, or from atmospheric phenomena, e.g. lightning. Others, however, are the result of
various uses of electricity which directly alter the waveform of the voltage, impose a particular pattern on its
magnitude, or superimpose signaling voltages. Coincidentally with the modern proliferation of equipment
which has these effects, there is also an increase in the equipment which is susceptible to the disturbances. It
is a particular feature of electricity that, with respect to some of its characteristics, its quality is affected by the
user as well as by the producer and/or network operator. In these cases the network user is an essential
partner of the network operator in the effort to maintain the quality of electricity.
Modern standardization is based on the concept of compatibility. For each relevant parameter a compatibility
level is established. Standard development aims to establish, among other things, limits for network
disturbances that can be met for a certain percentage of time on each location (e.g. 95%), and standards for
products that can operate reliable with that level of disturbance. The concept is illustrated in Figure 16, where
probability distributions are presented and the idea of the electromagnetic level is explained.
Figure 16—The Concept of Compatibility.
The left-hand bell-curve represents the probability of a particular level of the disturbance existing at a
particular time at a PCC on the network. The compatibility level is the one defined by standards such as EN
Publication No Cu0147
Issue Date: March 2017
Page 17
50160. It can be seen that, at any particular PCC, the disturbance level will be within the requirements of the
compatibility level for a very large proportion of the time. Network operators may design their networks and
the manner in which they arrange customer connections according to a ‘Planning level’. The difference
between the planning and compatibility levels differs for different parameters. For example, for flicker severity
and harmonic pollution—which are generated by users’ equipment and outside the control of the network
operator—the margin will be greater, especially at low voltage, to allow for local conditions. It is important to
point out that keeping the bell curve well to the left—i.e. to keep disturbance on the network low—is highly
desirable, but doing so is also expensive. Setting standards is a compromise between technical excellence and
economic reality.
The right-hand bell-curve illustrates an idealized distribution of the immunity level of the installed equipment
on the network. It indicates that the immunity level of most equipment, for most of the time, will be above the
compatibility level, thus ensuring reliable operation. Immunity level is the level described by equipment
standards, such as the EN 61XXX series.
Diagrams similar to Figure 16 can be prepared for many parameters that may influence the performance of
users’ equipment, such as the harmonic voltage level, flicker severity, voltage tolerance, et cetera.
Consequently, EN 50160 deals with the voltage characteristics in statistical or probabilistic terms. It gives
recommendations that, for a percentage of measurements (e.g. 95%) over a given time, the value must be
within the specified limits. This boundary value will be accepted as the compatibility level between the level of
disturbances in the network and the level of immunity of equipment. In this way, the responsibilities of the
network operator, equipment manufacturer and user are matched and clarified.
It is in the economic interest of the network user that the standard of supply should relate to conditions that
can be expected normally, rather than to rare contingencies, such as an unusual degree of coincidence
between the demands of several appliances or several network users. The standard defines, where possible,
variations of the characteristics that may be normally expected. In other cases, the standard provides the
possible indication of what, in quantitative terms, is to be expected.
In the case of voltage dips, EN 50160 gives guidance only on what may be expected. The level of dips allowed is
far more severe than the immunity level of equipment as defined by Figure 14 and Figure 15, so most
equipment will not be immune. Where an improved performance is required, the user is responsible for
installing the required equipment.
Publication No Cu0147
Issue Date: March 2017
Page 18
Figure 17—Example trace of long-term severity of flicker Plt for one week (1008 10-minute measurements) in a
3-phase system.
Taking the example of flicker severity, Figure 17 shows the recording of long-term flicker over a one week
period. There are 1082 ten-minute readings. In order to easily assess the impact, the readings are reordered in
decreasing order of value, as shown in Figure 18. In such a plot, it is immediately clear whether 95% of the
values are within the standard limit or not.
Figure 18—Ordered diagram of long-term severity of flicker Plt for one phase from Figure 17.
Although this standard has obvious links with the concept of compatibility levels, it is important to note that it
relates only to the voltage characteristics of electricity. It does not specify compatibility and immunity levels of
equipment. The performance of equipment might be impaired if the equipment is subjected to supply
conditions more severe than specified in their product standard.
Publication No Cu0147
Issue Date: March 2017
Page 19
LOW-VOLTAGE SUPPLY CHARACTERISTICS
See also [1].
GENERAL
This clause describes the voltage characteristics of electricity supply by public low voltage networks. In the
following, a distinction is made between:
 Continuous phenomena, i.e. deviations from the nominal values that occur continuously over time.
Such phenomena occur mainly due to specific load patterns, changes of load or nonlinear loads.
 Voltage events, i.e. sudden and significant deviations from normal or desired wave shape. Voltage
events typically occur due to unpredictable events (e.g. faults) or to external causes (e.g. weather
conditions, third party actions).
For some continuous phenomena, limits are specified:
 For single rapid changes, only indicative values are given for the time being
 For some specific parameters, stricter limits may exist in some national regulations
For voltage events, only indicative values can be given at present.
The standard nominal voltage Un for public low voltage is Un = 230 V, either between phase and neutral, or
between two phases:
 For four-wire three phase systems, Un = 230 V between phase and neutral
 For three-wire three phase systems, Un = 230 V between phases.
In low voltage systems the declared and nominal voltages are equal.
CONTINUOUS PHENOMENA
POWER FREQUENCY VARIATION
The nominal frequency of the supply voltage in this European Standard shall be 50 Hz.
Under normal operating conditions, the mean value of the fundamental frequency measured over 10 seconds
shall be within a range as indicated in Table 1. Related monitoring is usually done by the Control Area
Operator.
Table 1—Requirements regarding power frequency variation [1].
Parameter
For systems with
synchronous connection to
an interconnected system
Duration
For systems with no
synchronous connection to
an interconnected system
(e.g. supply system on certain
islands)
Duration
Power
frequency
50 Hz ± 1%
(i.e. 49.5 Hz ÷ 50.5 Hz)
99.5% of a year
50 Hz ± 2%
(i.e. 49 Hz ÷ 51 Hz)
95% of a week
50 Hz + 4%/-6%
(i.e. 47 Hz ÷ 52 Hz)
100% of the time
50 Hz ± 15%
(i.e. 42.5 Hz ÷ 57.5 Hz)
100% of the time
Publication No Cu0147
Issue Date: March 2017
Page 20
SUPPLY VOLTAGE VARIATION
Under normal operating conditions, excluding the periods with interruptions, supply voltage variations should
be within a range as indicated in Table 2.
Table 2—Requirements regarding supply voltage variation [1]
Parameter
For systems with
synchronous connection to
an interconnected system
Duration
For systems with no
synchronous connection to
an interconnected system
(e.g. supply system on certain
islands)
Duration
Supply
voltage
Under normal operating
conditions (excluding
interruptions)
Un ± 10%
95% of the 10-
minute mean RMS
values over each
one week period
All 10-minute mean
RMS values shall be
within the range of
Un +10%/-15%
Incl. special remote users
Un + 10%/-15%
Network users should be
informed of the conditions.
Network user equipment
typically designed to tolerate
supply voltages of ±10% of Un.
95% of the 10-
minute mean RMS
values over each
one week period
should be within
±10% of Un
All 10-minute mean
RMS values shall be
within the range of
Un +10%/-15%
1)
The actual power consumption required by individual network users is fully predictable, in terms of amount
and of simultaneousness. As a consequence, networks are generally designed on a probabilistic basis. If,
following a complaint, measurements carried out by the network operator according to the above
requirements indicate that the magnitude of the supply voltage is outside the limits given in the above
requirements (which can have negative consequences for the network user), the network operator should take
appropriate remedial action in collaboration with network user(s). Such action will of course depend upon a
risk assessment. Pending resolution, voltage variations should be within the range +10%/-15% of Un, unless
otherwise agreed with network users.
In accordance with relevant product and installation standards, network users’ appliances are typically
designed to tolerate supply voltages of ±10% around the nominal system voltage, which is sufficient to cover
an overwhelming majority of supply conditions. Generally, appliances do not need to be designed to handle
wider voltage variations.
Identification of what constitutes a ‘special remote network user’ can vary between countries and take into
account different characteristics of national electric systems such as limitation of power on supply terminal
and/or power factor limits.
RAPID VOLTAGE CHANGES
SINGLE RAPID VOLTAGE CHANGES
Rapid changes of the supply voltage are mainly caused either by load changes in the network users’
installations, by switching operations in the system, or by faults.
If the magnitude of a voltage change crosses the threshold for voltage dips and/or swells, the event is
classified as a voltage dip and/or swell rather than a rapid voltage change.
Publication No Cu0147
Issue Date: March 2017
Page 21
At low voltage—under normal operating conditions—rapid voltage changes generally do not exceed 5% Un.
But changes of up to 10% Un with a short duration of the sustained level might occur a few times per day
under some circumstances.
FLICKER SEVERITY
Under normal operating conditions, during each period of one week, the long-term flicker severity Plt caused
by voltage fluctuation should be less than or equal to 1 for 95% of the measurements.
It is worth noting that the reaction to flicker is subjective. It can vary depending on the perceived cause of the
flicker and the period over which it persists. In some cases Plt = 1 gives rise to annoyance, whereas in other
cases higher levels of Plt may not.
SUPPLY-VOLTAGE UNBALANCE
Under normal operating conditions, during each period of one week, 95% of the 10-minute mean RMS values
of the negative phase sequence component (fundamental) of the supply voltage shall be within the range 0%
to 2% of the positive phase sequence component (fundamental).
In this European Standard, only values for the negative sequence component are given. This component is the
relevant one for the possible interference of appliances connected to the system.
In some areas where there are users with largely single-phase or two-phase loads, unbalance up to
approximately 3% may occur at the three-phase supply terminal.
HARMONIC VOLTAGE
A harmonic voltage is a sinusoidal voltage with a frequency equal to an integer multiple of the fundamental
frequency of the supply voltage.
The content of harmonics in the supply voltage is characterized in two ways:
a) Individually by their relative amplitude (uh), which is the harmonic voltage related to the
fundamental voltage u1, where h is the order of the harmonic (Table 2)
b) Through the total harmonic distortion factor THD, calculated using the following expression:
𝑇𝐻𝐷 = √∑(𝑢ℎ)2
40
ℎ=2
Harmonics of the supply voltage are mainly caused by network users' non-linear loads connected to the supply
network. Indeed, non-linear loads draw harmonic currents and harmonic currents flowing through the
network impedance give rise to harmonic voltages. The harmonic currents and network impedances—and thus
the harmonic voltages at the supply terminals—vary in time.
The limitation to order 40 is conventional. However, in some countries, other values may be used (e.g. order
50 in the UK).
Ad a)
Under normal operation conditions, during each period of one week, 95% of the 10 minute mean RMS values
of each individual harmonic voltage shall be less than or equal to the values given in Table 3. In this table, no
values are given for harmonics of an order higher than 25, as they are usually small and largely unpredictable
due to resonance effects.
Publication No Cu0147
Issue Date: March 2017
Page 22
Table 3—Values of individual harmonic voltages at the supply terminals for harmonic orders up to 25 given as a
percentage of the fundamental voltage u1 [1].
Odd harmonics
Even harmonics
Not multiples of 3 Multiples of 3
Order
h
Relative
amplitude
uh
Order
h
Relative
amplitude
uh
Order
h
Relative
amplitude
uh
5 6.0% 3 5.0% 2 2.0%
7 5.0% 9 1.5% 4 1.0%
11 3.5% 15 0.5% 6 to 24 0.5%
13 3.0% 21 0.5%
17 2.0%
19 1.5%
23 1.5%
25 1.5%
Ad b)
Moreover, the THD of the supply voltage (including all harmonics up to order 40) shall be less than or equal to
8%.
Figure 19—Illustration of the influence of harmonics on the torque (M) during the operation of an electrical
asynchronous motor.
Figure 19 shows an example of the torque characteristics of an asynchronous induction motor connected to a
distorted voltage supply in which
Publication No Cu0147
Issue Date: March 2017
Page 23
M1 = undisturbed torque due to fundamental supply frequency
Mi = torque due to harmonic i
Mm = load torque
Mw = resultant torque
Harmonic voltage components cause harmonic current components in the motor.
If the motor supply is distorted, the corresponding harmonic currents flow in the stator and are therefore
reproduced in the magnetic field. These field components cause a parasitic torque which can result in
vibration, acceleration of bearing wear, excess heating, and/or reduced service life. If the resultant torque
curve, Mw crosses the load torque curve Mm (as indicated in Figure 19), the motor can stall.
INTERHARMONIC VOLTAGES
An interharmonic voltage is a sinusoidal voltage with a frequency not equal to an integer multiple of the
fundamental.
Interharmonic voltages at closely adjacent frequencies can appear at the same time, forming a wide band
spectrum.
The level of interharmonics is increasing due to the development of frequency converters and similar control
equipment. Levels are under consideration, pending more field experience.
In certain cases, interharmonics, even at low levels, give rise to flicker, or cause interference in ripple control
systems.
MAINS SIGNALING VOLTAGES
In some countries, the public networks may be used for the transmission of signals by the network operators.
Three types of signals in the public supply network can be classified:
 Ripple control signals—superimposed sinusoidal voltage signals in the frequency range of 110 Hz to
3000 Hz
 Power-line-carrier signals—superimposed sinusoidal voltage signals in the frequency range of 3 kHz to
148.5 kHz
 Mains marking signals—superimposed short time alterations (transients) at selected points of the
voltage waveform
These may be used in network users’ installations and for the signaling in power line carriers. Voltages with
these frequencies (95 Hz up to 148.5 kHz) of up to 1.4 V RMS have to be taken into account in the public LV
network. However, the transmission of signals between network users is not permitted on the public LV
network. Because of the possibility of mutual influences with neighboring network users’ signaling systems,
the network user may need to apply protection or appropriate mitigation measures for their signaling
installation.
For PLC purposes, frequencies above 148.5 kHz are used in some networks.
For 99% of a day, the 3 seconds mean value of signal voltages shall be less than or equal to the values given
in Figure 20.
Publication No Cu0147
Issue Date: March 2017
Page 24
Figure 20—Voltage levels of signal frequencies in percent of nominal voltage Un used in public LV and MV
networks from EN50160 standard.
VOLTAGE EVENTS
See also [2. 3].
INTERRUPTIONS OF THE SUPPLY VOLTAGE
Interruptions are, by their nature, unpredictable and vary from place to place and from time to time. For the
time being, it is not possible to give fully representative results of interruption frequency measurements
covering the whole of the European network. A reference for the actual interruption values recorded in
European networks, divides them into long and short interruptions, as previously defined.
At the national level, more precise statistics may be available. Furthermore, national regulations may exist.
SUPPLY VOLTAGE DIPS/SWELLS
GENERAL
Voltage dips typically originate from faults occurring in the public network or in network users’ installations.
Voltage swells are typically caused by switching operations and load disconnections. The swells treated in this
clause are those which occur between live conductors.
Both phenomena are unpredictable and largely random. The annual frequency varies greatly depending on the
type of supply system and on the point of observation. Moreover, the distribution over the year can be very
irregular.
VOLTAGE DIP/SWELL MEASUREMENT AND DETECTION
Voltage dips/swells shall be measured and detected by using the nominal supply voltage as a reference. The
voltage dips/swell characteristics of interest for this standard are residual voltage (maximum RMS voltage for
swells) and duration. In this standard, the duration is defined, as well as a value expressed in percentage of the
residual voltage compared to the reference voltage for dips, and in maximum RMS voltage for swells. On LV
networks, for four-wire three phase systems, the line to neutral voltages shall be considered. For three-wire
three phase systems, the line to line voltages shall be considered. In the case of a single phase connection, the
supply voltage (line to line or line to neutral, according to the network user connection) shall be considered.
Publication No Cu0147
Issue Date: March 2017
Page 25
Conventionally, the dip start threshold is equal to 90% of the nominal voltage. The start threshold for swells is
equal to 110% of the nominal voltage
For polyphase measurements, it is recommended that the number of phases affected by each event is
detected and recorded.
VOLTAGE DIPS EVALUATION
The method of analyzing the voltage dips (post treatment) depends on the purpose of the evaluation.
Typically on LV networks:
 If a three-phase system is considered, polyphase aggregation shall be applied. Polyphase aggregation
consists of defining an equivalent event characterized by a single duration and a single residual
voltage.
 Time aggregation applies. Time aggregation consists of defining an equivalent event in the case of
multiple successive events. The method used for the aggregation of multiple events can be set
according to the final use of data.
CLASSIFICATION OF VOLTAGE DIPS
If statistics are collected, voltage dips shall be classified according to Table 4. The figures to be put in the cells
are the number of equivalent events and the residual voltage is then calculated by polyphase aggregation.
Further information is needed to consider events affecting an individual single phase voltage in three-phase
systems. To calculate the latter, a different evaluation method has to be applied.
Table 4 is to be taken as a recommendation for existing measurement equipment and/or monitoring systems.
Table 4—Classification of dips according to residual voltage and duration.
Residual
voltage u
%
Duration t
ms
10 ≤ t ≤ 200 200< t ≤500 500< t ≤1000 1000< t≤5000 5000<t ≤60000
90 > u ≥ 80 CELL A1 CELL A2 CELL A3 CELL A4 CELL A5
80 > u ≥ 70 CELL B1 CELL B2 CELL B3 CELL B4 CELL B5
70 > u ≥ 40 CELL C1 CELL C2 CELL C3 CELL C4 CELL C5
40 > u ≥ 5 CELL D1 CELL D2 CELL D3 CELL D4 CELL D5
5 > u CELL X1 CELL X2 CELL X3 CELL X4 CELL X5
Voltage dips are, by their nature, unpredictable and variable from place to place and from time to time. At
present, it is not possible to give fully representative results of voltage dip frequency measurements covering
the whole of the European network. It should be noted that due to the measurement method adopted, a
measurement uncertainty affecting the results has to be taken into account. This is particularly relevant for
shorter events.
Generally, the duration of a voltage dip depends on the protection strategy adopted on the network. This may
differ from network to network, depending upon the network structure and on neutral earthing. As a
consequence, typical durations do not necessarily match the boundaries of the columns in Table 4.
Publication No Cu0147
Issue Date: March 2017
Page 26
VOLTAGE SWELLS EVALUATION
Typically, on LV networks:
 If a three phase system is considered, polyphase aggregation shall be applied. Polyphase aggregation
consists of defining an equivalent event characterized by a single duration and a single maximum RMS
voltage.
 Time aggregation applies. Time aggregation consists of defining an equivalent event in the case of
multiple successive events. The method used for the aggregation of multiple events can be set
according to the final use of data.
For low voltage systems, under certain circumstances, a fault occurring upstream of a transformer may
produce temporary overvoltages on the LV side for the time during which the fault current flows. Such
overvoltages will generally not exceed 1.5 kV RMS.
CLASSIFICATION OF VOLTAGE SWELLS
If statistics are collected, voltage swells shall be classified according to the following table. For existing
measurement equipment and/or monitoring systems, Table 5 is to be taken as a recommendation.
Table 5—Classification of swells according to maximum voltage and duration.
Swell voltage u
%
Duration t
ms
10 ≤ t ≤ 500 500< t ≤5000 5000< t ≤60000
u ≥ 120 CELL S1 CELL S2 CELL S3
120 > u ≥ 110 CELL T1 CELL T2 CELL T3
Typically, faults in the public LV network or in a network user's installation give rise to temporary power
frequency overvoltages between live conductors and the earth. Such overvoltages disappear when the fault is
cleared.
Publication No Cu0147
Issue Date: March 2017
Page 27
MEDIUM-VOLTAGE SUPPLY CHARACTERISTICS
GENERAL
The standard distinguishes between:
 Continuous phenomena, i.e. deviations from the nominal value that occurs continuously over time.
Such phenomena occur mainly due to load pattern, changes of load, or nonlinear loads.
 Voltage events, i.e. sudden and significant deviations from the normal or desired wave shape. Voltage
events typically occur due to unpredictable events (e.g. faults) or external causes (e.g. weather
conditions, third party actions, et cetera).
CONTINUOUS PHENOMENA
POWER FREQUENCY
The nominal frequency of the supply voltage in this European Standard shall be 50 Hz.
Under normal operating conditions, the mean value of the fundamental frequency measured over 10 seconds
shall be within the range given in Table 6. Monitoring is the responsibility of the Control Area Operator.
Table 6—Requirements regarding power frequency and supply voltage variation.
Parameter
For systems with
synchronous connection to
an interconnected system
Duration
For systems with no
synchronous connection to
an interconnected system
(e.g. supply system on
certain islands)
Duration
Power
frequency
50 Hz ± 1%
(i.e. 49.5 Hz ÷ 50.5 Hz)
99.5% of a year
50 Hz ± 2%
(i.e. 49 Hz ÷ 51 Hz)
95% of a week
50 Hz + 4%/-6%
(i.e. 47 Hz ÷ 52 Hz)
100% of the time
50 Hz ± 15%
(i.e. 42.5 Hz ÷ 57.5 Hz)
100% of the time
SUPPLY VOLTAGE VARIATIONS
Under normal operation condition, during each period of one week excluding the periods with interruptions,
supply voltage variations should not exceed ± 10% of the declared voltage Uc. as indicate in Table 7—
Requirements regarding supply voltage variation.
Publication No Cu0147
Issue Date: March 2017
Page 28
Table 7—Requirements regarding supply voltage variation.
Parameter
For systems with
synchronous connection to
an interconnected system
Duration
For systems with no
synchronous connection to
an interconnected system
(e.g. supply system on
certain islands)
Duration
Supply voltage
Under normal operating
conditions, excluding
periods of interruption,
supply voltage variations
should not exceed ±10% of
the declared voltage Uc.
99% of the 10-
minute mean RMS
value over one
week
none of the 10-
minute mean RMS
values shall exceed
± 15% of Uc.
(Incl. special remote users)
Un + 10%/-15%.
Network users should be
informed of the conditions.
99% of the 10-
minute mean RMS
value over one
week
none of the 10-
minute mean RMS
values shall exceed
± 15% of Uc.
RAPID VOLTAGE CHANGES
SINGLE RAPID VOLTAGE CHANGE
Rapid voltage changes in the supply voltage are mainly caused by either load changes in the network users'
installations, by switching in the system or by faults. If the voltage during a change crosses the voltage dip
and/or the voltage swell threshold, the event is classified as a voltage dip and/or swell rather than a rapid
voltage change.
For medium voltage, under normal operating conditions, rapid voltage changes generally do not exceed 4% Uc.
However changes of up to 6% Uc with a short duration of the sustained level may occur a few times per day
under some circumstances.
FLICKER SEVERITY
Under normal operation conditions, during each period of one week, the long-term flicker severity Plt caused
by voltage fluctuations should be less or equal to 1 for 95% of the time.
This value was chosen on the assumption that the transfer coefficient between MV and LV system is 1. In
practice, the transfer coefficients between MV levels and LV levels can be less than 1.
In the event of complaints, the MV limit and appropriate HV, MV and LV mitigation measures shall be chosen
in such a way that at LV the Plt values do not exceed 1.
SUPPLY VOLTAGE UNBALANCE
Under normal operation condition, during each period of one week, 95% of the 10-minute RMS values of the
negative phase sequence component of the supply voltage shall be within the range 0% to 2% of the positive
phase sequence component.
In some areas, unbalances of up to approximately 3% occur at three-phase supply terminals.
HARMONIC VOLTAGE
Under normal operation condition, during each period of one week, 95% of 10-minute mean RMS values of
each individual harmonic voltage shall be less than or equal to the values given in Table 3.
Moreover, the THD of the supply voltage (including all harmonics up to order 40) shall be less than or equal to
8%.
Publication No Cu0147
Issue Date: March 2017
Page 29
INTERHARMONIC VOLTAGES
The level of interharmonics is increasing due to the development of frequency converters and similar control
equipment. Levels are under consideration, pending more field experience.
In certain cases, interharmonics—even at low levels—give rise to flicker or cause interference in ripple control
systems.
MAINS SIGNALING VOLTAGE
In some countries, the public networks may be used by the network operators for the transmission of signals.
For 99% of a day, the 3 seconds mean value of the signal voltages shall be less or equal to the values given in
Figure 20.
It is assumed that network users do not use the public MV network for signaling purposes.
Frequencies above 148.5 kHz are also used in some networks for PLC purposes.
VOLTAGE EVENTS
See also [2. 3].
SUPPLY VOLTAGE DIPS/SWELLS
GENERAL
Voltage dips typically originate from faults occurring in the public network or in network users’ installations.
Voltage swells are typically caused by switching operations and load disconnections.
Both phenomena are unpredictable and largely random. The annual frequency varies greatly, depending on
the type of supply system and on the point of observation. Moreover, distribution over the year can be very
irregular.
VOLTAGE DIP/SWELL MEASUREMENT AND DETECTION
Voltage dips/swells shall be measured and detected using the nominal supply voltage as the reference. The
voltage dips/swell characteristics of interest for this standard are residual voltage (maximum RMS voltage for
swells) and duration. In this standard, values are expressed as a percentage of the residual voltage.
Typically, on MV networks, the line-to-line voltages shall be considered.
Conventionally, the dip start threshold is equal to 90% of the nominal voltage. The start threshold for swells is
equal to 110% of the nominal voltage. The hysteresis is typically 2%.
For polyphase measurements, it is recommended that the number of phases affected by each event is
detected and stored.
VOLTAGE DIPS EVALUATION
The method of analyzing the voltage dips (post treatment) depends on the purpose of the evaluation.
Typically on MV networks:
 Polyphase aggregation applies. This method consists of defining an equivalent event characterized by
a single duration and a single maximum RMS voltage.
Publication No Cu0147
Issue Date: March 2017
Page 30
 Time aggregation applies. This method consists of defining a single equivalent event in the case of
multiple successive events. The method used for the aggregation of multiple events can be set
according to the final use of the data.
CLASSIFICATION OF VOLTAGE DIPS
If statistics are collected, voltage dips shall be classified according to Table 4. For existing measurement
equipment and/or monitoring systems, the same table (Table 4) which is used for LV networks is to be taken as
a recommendation for MV networks as well.
VOLTAGE SWELLS EVALUATION
Typically, on MV networks:
 Polyphase aggregation applies. This method consists of defining a mono-phase event, characterized
by a single duration and a single RMS voltage, that is equivalent to the actual polyphase event.
 Time aggregation applies. This method consists of defining a single event that is equivalent to the
actual multiple successive events. The method used for the aggregation can be set according to the
final use of the data.
Under certain circumstances, a fault occurring upstream of a transformer may produce temporary
overvoltages on medium voltage systems. The expected value of such an overvoltage depends on the type of
earthing of the system. The overvoltage shall generally not exceed 1.7 Uc in systems with a solidly or
impedance earthed neutral. The overvoltage shall generally not exceed 2.0 Uc in isolated or resonant earthed
systems. The type of earthing will be indicated by the network operator.
CLASSIFICATION OF VOLTAGE SWELLS
If statistics are collected, voltage swells shall be classified according to Table 5. The same table as the one
indicated for LV networks is recommended in this instance as well for existing measurement equipment
and/or monitoring systems.
Publication No Cu0147
Issue Date: March 2017
Page 31
HIGH-VOLTAGE SUPPLY CHARACTERISTICS
GENERAL
Network users with demands exceeding the capacity of a medium voltage network are generally supplied at
nominal voltages above 36 kV. This clause applies to such electricity supplies at nominal voltages up to and
including 150 kV.
CONTINUOUS PHENOMENA
POWER FREQUENCY VARIATIONS
The nominal frequency of the supply voltage in this European Standard shall be 50 Hz.
Under normal operating conditions, the mean value of the fundamental frequency measured over 10 seconds
shall be within a range given in Table 8.
Table 8—Requirements regarding power frequency and supply voltage variation.
Parameter
For systems with
synchronous connection to
an interconnected system
Duration
For systems with no
synchronous connection to
an interconnected system
(e.g. supply system on
certain islands)
Duration
Power
frequency
50 Hz ± 1%
(i.e. 49.5 Hz ÷ 50.5 Hz)
99.5% of a year
50 Hz ± 2%
(i.e. 49 Hz ÷ 51 Hz)
95% of a week
50 Hz + 4%/-6%
(i.e. 47 Hz ÷ 52 Hz)
100% of the time
50 Hz ± 15%
(i.e. 42.5 Hz ÷ 57.5 Hz)
100% of the time
SUPPLY VOLTAGE VARIATIONS
Under normal operation conditions, during each period of one week excluding the periods with interruptions,
supply voltage variations should not exceed ± 10% of the declared voltage Uc. as indicated in Table 9.
Table 9—Requirements regarding supply voltage variation.
Parameter
For systems with
synchronous connection to
an interconnected system
Duration
For systems with no
synchronous connection to
an interconnected system
(e.g. supply system on
certain islands)
Duration
Supply voltage
As the number of network users supplied directly from HV networks is limited and normally subject to
individual contracts, no limits for supply voltage variations are given in this standard. Existing product
standards for HV equipment should be considered.
RAPID VOLTAGE CHANGES
SINGLE RAPID VOLTAGE CHANGE
Rapid voltage changes in the supply voltage are mainly caused either by load changes in the network users'
installations, by switching in the system, or by faults.
Publication No Cu0147
Issue Date: March 2017
Page 32
If the voltage during a change crosses the voltage dip and/or the voltage swell threshold, the event is classified
as a voltage dip and/or swell rather than a rapid voltage change.
FLICKER SEVERITY
Under normal operation conditions, during each period of one week, the long-term flicker severity Plt caused
by voltage fluctuations should be less than or equal to 1 for 95% of the time.
This value was chosen on the assumption that the transfer coefficient between HV and LV system is 1. In
practice, the transfer coefficients between HV levels and LV levels can be less than 1.
In the case of complaints, the HV limit and appropriate HV, MV and LV mitigation measures shall be chosen in
such a way that the Plt values at LV do not exceed 1.
SUPPLY VOLTAGE UNBALANCE
Under normal operation conditions, during each period of one week, 95% of the 10 minute mean RMS values
of the negative phase sequence component of the supply voltage should be within the range 0% to 2% of the
positive phase sequence component.
In some areas, unbalances of up to approximately 3% occur at three-phase supply terminals.
HARMONIC VOLTAGE
Under normal operating conditions, during each period of one week, 95% of the 10 minute mean RMS. values
of each individual harmonic voltage should be less than or equal to the indicative values given in Table 10.
Resonances may cause higher voltages for an individual harmonic.
No values are considered for harmonics of an order higher than 25 since they are usually small and largely
unpredictable due to resonance effects.
Table 10—Values of individual harmonic voltages at supply HV terminals for orders up to 25 given in
percentage of the fundamental voltage u1.
Odd harmonics
Even harmonics
Not multiples of 3 Multiples of 3
Order
h
Relative
amplitude
uh
Order
h
Relative
amplitude (%)
uh
Order
h
Relative
amplitude (%)
uh
5 5.0 3 3.0 2 1.9
7 4.0 9 1.3 4 1.0
11 3.0 15 0.5 6 to 24 0.5
13 2.5 21 0.5
17 u.c.
19 u.c.
23 u.c.
25 u.c.
Harmonics of orders higher than 13 and not a multiple of 3 are under consideration.
In the case of complaints, limits for harmonics in HV networks should be chosen on the basis of MV network
limits suitably modified by a quantity (D) as resulting from the following formula:
Publication No Cu0147
Issue Date: March 2017
Page 33
HV LIMIT = MV LIMIT - D
D should be agreed between the HV network operator and the connected network user—if necessary—in
order to maintain harmonic levels of the connected network below the relevant limits. D can be chosen
differently, depending on the use (harmonic transmission from HV public networks to HV public networks,
from HV public networks to MV public networks or from HV public networks to network users).
INTERHARMONIC VOLTAGE
Due to the low resonance frequency of the HV network, no threshold values are given for the interharmonic
voltage. Due to the very low resonant frequency in HV grids (200 Hz to 500 Hz) caused by high* capacitances
and inductances, interharmonics are of minor relevance in HV networks.
VOLTAGE EVENTS
See also [2. 3].
SUPPLY VOLTAGE DIPS/SWELLS
VOLTAGE DIP/SWELL MEASUREMENT AND DETECTION
Voltage dips/swells shall be measured and detected using the nominal supply voltage as a reference. The
voltage dips/swell characteristics of interest for this standard are residual voltage (maximum RMS voltage for
swells) and duration. In this standard, values are expressed in terms of percentage of the residual.
Typically, the line-to-line voltages shall be considered on HV networks. Conventionally, the dip start threshold
is equal to 90% of the nominal voltage. The start threshold for a swell is equal to 110% of the nominal voltage.
The hysteresis is typically 2%.
For polyphase measurements, it is recommended that the number of phases that are affected by each event is
detected and stored.
VOLTAGE DIPS EVALUATION
The method for analyzing voltage dips depends upon the purpose of the evaluation.
Typically on HV networks:
 Polyphase aggregation applies
 Time aggregation applies
CLASSIFICATION OF VOLTAGE DIPS
If statistics are collected, voltage dips shall be classified according to Table 4. For existing measurement
equipment and/or monitoring systems, Table 4 applies as well (the same one that is used for LV and MV
networks).
VOLTAGE SWELLS EVALUATION
Typically, on HV networks:
 Polyphase aggregation applies
 Time aggregation applies
CLASSIFICATION OF VOLTAGE SWELLS
If statistics are collected, voltage swells shall be classified according to Table 5. For existing measurement
equipment and/or monitoring systems the same table as the one indicated for LV and MV networks is
recommended here as well.
Publication No Cu0147
Issue Date: March 2017
Page 34
PERFORMANCE CRITERIA FOR VOLTAGE DIPS/SWELLS
Performance criterion A. The apparatus shall continue to operate as intended during and after the test. There
must be no degradation of performance or loss of function below a performance level specified by the
manufacturer. A permissible loss of performance is acceptable. If the minimum performance level or
permissible performance loss is not specified by the manufacturer, either of these may be derived from the
product description and documentation and what the user may reasonably expect from the apparatus if used
as intended.
Performance criterion B. The apparatus shall continue to operate as intended after the test. No degradation
of performance or loss of function is allowed below a performance level specified by the manufacturer. During
the test however, degradation of performance is allowed. No change of actual operating state or stored data is
allowed.
If the minimum performance level or the permissible performance loss is not specified by the manufacturer,
either of these may be derived from the product description and documentation and what the user may
reasonably expect from the apparatus if used as intended.
Performance criterion C. Temporary loss of function is allowed provided the function is self-recoverable or can
be restored by operation of the controls.
Publication No Cu0147
Issue Date: March 2017
Page 35
ELECTROMAGNETIC ENVIRONMENT CLASSIFICATION
As detailed in product standards, voltage dip and swells—according to their severity—can impair the operation
of equipment. For reference, the electromagnetic environment is characterized by following classes:
Class 1
This class refers to protected supply systems. In this instance, the compatibility levels are lower than in the
public supply network. It refers to environments where equipment is used that is highly sensitive to such
disturbances, e.g. in technical laboratories, measurement facilities, computer centers and certain automation
and protection equipment. Class 1 environments normally contain equipment which requires protection by
apparatus such as uninterruptible power systems (UPS), filters or surge suppressers.
Class 2
This class applies generally to PCCs and to IPCs in the environments of industrial and other non-public power
supplies. The compatibility levels of this class are generally identical to those of public networks. Therefore,
components designed for supply from public networks may be used in this class of industrial environments.
Class 3
This class refers to internal points of common coupling (IPCC) in an industrial environment.
For certain disturbances, the compatibility levels are higher than in class 2. For example, the consideration of
this class is recommended if any of the following conditions are fulfilled:
 A major part of the load is fed through converters
 Welding machines are present
 Large motors are frequently started
 Loads vary rapidly
The supply to highly disturbing loads such as arc-furnaces and large converters—these are generally supplied
from a segregated busbar—frequently has disturbance levels in excess of class 3 (harsh environment). In such
special situations, the compatibility levels should be agreed upon.
Different classes can be relevant for different phenomena in any given network and should take into account
the diversity of industrial environments.
Although the cells of Table 4 are not precisely coincident with the test levels table, it can be expected that
equipment tested according to the relevant product standard should cope with voltage dips as indicated in the
cells:
 A1, B1, A2, B2 for class 2
 A1, B1, C1, A2, B2, A3, A4 for class 3
Publication No Cu0147
Issue Date: March 2017
Page 36
Table 11—Recommended test level and duration of the voltage dips.
Class Test level and duration of the voltage dips (50 Hz / 60 Hz)
Class 1 Dependent on the case. according to the requirements of equipment
Class 2
0% during ½
cycle
0% during 1
cycle
70% during 25/30
c)
cycles
Class 3
0% during ½
cycle
0% during 1
cycle
40% during
10/12 cycles
70% during 25/30
cycles
80% during 250/300
cycles
b) —25/30 cycles, means “25 cycles for test at 50 Hz” as well as “30 cycles for test at 60 Hz”.
Table 12—Recommended test level and duration of the short interruptions.
Class Test level and duration of the voltage dips (50 Hz/60 Hz)
Class 1 Dependent on the case, according to the requirements of equipment
Class 2 0% during 250/300 cycles
Class 3 0% during 250/300 cycles
Publication No Cu0147
Issue Date: March 2017
Page 37
CLASSES OF MEASUREMENT METHODS
See also [3, 7].
Three classes (A, S and B) are defined for each parameter measured. Measurement methods and appropriate
performance requirements for each class are included.
Class A
This class is used where precise measurements are necessary. For example, in contractual applications that
may require resolving disputes, verifying compliance with standards, et cetera.
Any measurements of the same parameter on the same signal carried out with two different instruments
complying with the requirements of class A will produce matching results within the specified uncertainty for
that parameter.
Class S
This class is used for statistical applications such as surveys or power quality assessments with a limited subset
of parameters. Class S processing requirements are lower although it uses equivalent intervals of
measurement as class A.
Class B
This class is defined in order to avoid making many existing instrument designs obsolete. Class B methods shall
not be employed for new instruments. All new instrument designs will comply with either Class A or Class S.
Class B may be relevant for legacy instruments that are still in use [7]. Hereby: “A” stands for “Advanced”. “S”
stands for “Surveys” and “B” for “Basic” methods.
MEASUREMENT AGGREGATION OVER TIME INTERVALS
The following measurement aggregations apply:
Class A:
The basic measurement time interval for parameter magnitudes (supply voltage, harmonics, interharmonics,
unbalance) shall be a 10-cycle time interval for a 50 Hz power system or a 12-cycle time interval for a 60 Hz
power system. The 10/12-cycle values are then aggregated over 3 additional intervals:
 150/180-cycle interval (150 cycles for 50 Hz nominal or 180 cycles for 60 Hz nominal)
 10 minute interval
 2 hour interval
Class S:
The same time intervals as for class A prevail. The 10/12-cycle measurement shall be re-synchronized.
Class B:
The manufacturer shall specify the number and duration of aggregation time intervals.
MEASUREMENT AGGREGATION ALGORITHM
Aggregation shall be performed using the square root of the arithmetic mean of the squared input values. See
also [3].
Publication No Cu0147
Issue Date: March 2017
Page 38
CONCLUSIONS
Standard EN 50160 should be understood as representing a compromise between the three parties which
exert an influence on the power quality, i.e. network operator, network user and equipment manufacturer.
Each of these three parties has an interest in performing their role. It is essential that electricity suppliers
provide—as a minimum—a nominally adequate quality of supply. If the customer has higher requirements,
they should instigate their own mitigation measures. Another option is to negotiate a separate agreement for
a higher supply quality with the supplier.
The important advantages of the EN 50160 standard are:
 The definition of the voltage parameters important for power quality
 The quantitative determination of reference values that can be used in the evaluation of power
quality
It is the task of the electricity regulator to set a level of quality that requires best practice from the supplier
while not at the same time setting the level so high that the price of electricity increases for everybody.
REFERENCES
[1] EN 50160: July 2010. Voltage characteristics of electricity supplied by public electricity networks.
[2] EN 61000-3-3: 2008. Electromagnetic compatibility (EMC). Part 3-3: Limits—Limitation of voltage changes,
voltage fluctuations and flicker in public low-voltage supply systems, for equipment with rated current ≤16
A per phase and not subject to conditional connection.
[3] EN 61000-4-30:2009. Electromagnetic compatibility (EMC). Part 4-30: Testing and measurement
techniques—Power quality measurement methods.
[4] Asensi R. Harmonics. How should the compatibility level be understood? Power Quality Application Guide.
Part 3.4.1. 2005.
[5] http://www.marcspages.co.uk/pq/5130.htm
[6] http://f47testing.epri.com/faq.html
[7] EN 61000-4-30:2015 Electromagnetic compatibility (EMC). Part 4-30: Testing and measurement
techniques—Power quality measurement methods.

Contenu connexe

Tendances

Bundle conductors in transmission line
Bundle conductors in transmission line Bundle conductors in transmission line
Bundle conductors in transmission line chandan kumar
 
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Power System Operation
 
ETAP - Short circuit ansi standard
ETAP - Short circuit ansi standardETAP - Short circuit ansi standard
ETAP - Short circuit ansi standardHimmelstern
 
Skin effect on transmission line.
Skin effect on transmission line.Skin effect on transmission line.
Skin effect on transmission line.Parth Patel
 
Power transformer losses
Power transformer lossesPower transformer losses
Power transformer lossesLeonardo ENERGY
 
Unit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlUnit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlSANTOSH GADEKAR
 
Power Quality Issues
Power Quality IssuesPower Quality Issues
Power Quality Issuesmaneesh001
 
Digital transformer protection systems
Digital transformer protection systemsDigital transformer protection systems
Digital transformer protection systemsmichaeljmack
 
ETAP - unbalanced load flow
ETAP - unbalanced load flowETAP - unbalanced load flow
ETAP - unbalanced load flowHimmelstern
 
Harmonics and mitigation techniques
Harmonics and mitigation techniquesHarmonics and mitigation techniques
Harmonics and mitigation techniquesrifat maryum
 
power system analysis lecture 1
power system analysis lecture 1power system analysis lecture 1
power system analysis lecture 1Audih Alfaoury
 
Loading Capability Limits of Transmission Lines
Loading Capability Limits of Transmission LinesLoading Capability Limits of Transmission Lines
Loading Capability Limits of Transmission LinesRaja Adapa
 
Introduction to Power Quality
Introduction to Power QualityIntroduction to Power Quality
Introduction to Power QualitySteve Johnson
 

Tendances (20)

FREQUENCY STABILITY
FREQUENCY STABILITYFREQUENCY STABILITY
FREQUENCY STABILITY
 
Bundle conductors in transmission line
Bundle conductors in transmission line Bundle conductors in transmission line
Bundle conductors in transmission line
 
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
 
ETAP - Short circuit ansi standard
ETAP - Short circuit ansi standardETAP - Short circuit ansi standard
ETAP - Short circuit ansi standard
 
Skin effect on transmission line.
Skin effect on transmission line.Skin effect on transmission line.
Skin effect on transmission line.
 
Power transformer losses
Power transformer lossesPower transformer losses
Power transformer losses
 
Unit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlUnit 4 Automatic Generation Control
Unit 4 Automatic Generation Control
 
Power Quality Issues
Power Quality IssuesPower Quality Issues
Power Quality Issues
 
EXCITATION SYSTEMS
EXCITATION SYSTEMSEXCITATION SYSTEMS
EXCITATION SYSTEMS
 
Transmission lines
Transmission linesTransmission lines
Transmission lines
 
Short and long interruptions- UNIT-II-POWER QUALITY
Short and long interruptions- UNIT-II-POWER QUALITYShort and long interruptions- UNIT-II-POWER QUALITY
Short and long interruptions- UNIT-II-POWER QUALITY
 
Digital transformer protection systems
Digital transformer protection systemsDigital transformer protection systems
Digital transformer protection systems
 
ETAP - unbalanced load flow
ETAP - unbalanced load flowETAP - unbalanced load flow
ETAP - unbalanced load flow
 
Out of step
Out of stepOut of step
Out of step
 
Phasor Measurement Unit (PMU)
 Phasor Measurement Unit (PMU) Phasor Measurement Unit (PMU)
Phasor Measurement Unit (PMU)
 
Harmonics and mitigation techniques
Harmonics and mitigation techniquesHarmonics and mitigation techniques
Harmonics and mitigation techniques
 
power system analysis lecture 1
power system analysis lecture 1power system analysis lecture 1
power system analysis lecture 1
 
Power quality
Power qualityPower quality
Power quality
 
Loading Capability Limits of Transmission Lines
Loading Capability Limits of Transmission LinesLoading Capability Limits of Transmission Lines
Loading Capability Limits of Transmission Lines
 
Introduction to Power Quality
Introduction to Power QualityIntroduction to Power Quality
Introduction to Power Quality
 

Similaire à Voltage characteristics of grid electricity (EN 50160)

Predicting and Monitoring PV Energy Production
Predicting  and Monitoring PV Energy ProductionPredicting  and Monitoring PV Energy Production
Predicting and Monitoring PV Energy ProductionLeonardo ENERGY
 
Infrared thermal energy scanning for energy efficiency assessment
Infrared thermal energy scanning for energy efficiency assessmentInfrared thermal energy scanning for energy efficiency assessment
Infrared thermal energy scanning for energy efficiency assessmentLeonardo ENERGY
 
New loads on old switches, relays and contractors
New loads on old switches, relays and contractorsNew loads on old switches, relays and contractors
New loads on old switches, relays and contractorsLeonardo ENERGY
 
White paper - Residential Electrical Safety
White paper - Residential Electrical SafetyWhite paper - Residential Electrical Safety
White paper - Residential Electrical SafetyLeonardo ENERGY
 
Electrical storage systems: efficiency and lifetime
Electrical storage systems: efficiency and lifetimeElectrical storage systems: efficiency and lifetime
Electrical storage systems: efficiency and lifetimeBruno De Wachter
 
Guide toen50160
Guide toen50160Guide toen50160
Guide toen50160Manojlooki
 
12 39 rapport_screen
12 39 rapport_screen12 39 rapport_screen
12 39 rapport_screenKabraham Kb
 
Small hydroelectric power
Small hydroelectric powerSmall hydroelectric power
Small hydroelectric powerLeonardo ENERGY
 
Introduction to power quality (PQ)
Introduction to power quality (PQ)Introduction to power quality (PQ)
Introduction to power quality (PQ)Bruno De Wachter
 
Best Protection Practices for HV and EHV AC-Transmission Systems of ENTSO-E E...
Best Protection Practices for HV and EHV AC-Transmission Systems of ENTSO-E E...Best Protection Practices for HV and EHV AC-Transmission Systems of ENTSO-E E...
Best Protection Practices for HV and EHV AC-Transmission Systems of ENTSO-E E...Power System Operation
 
Best Protection Practices for HV and EHV AC-Transmission Systems of ENTSO-E E...
Best Protection Practices for HV and EHV AC-Transmission Systems of ENTSO-E E...Best Protection Practices for HV and EHV AC-Transmission Systems of ENTSO-E E...
Best Protection Practices for HV and EHV AC-Transmission Systems of ENTSO-E E...Power System Operation
 
OPC LUX: Climate Policy Observatory, Luxembourg, Annual Report 2022
OPC LUX: Climate Policy Observatory, Luxembourg, Annual Report 2022OPC LUX: Climate Policy Observatory, Luxembourg, Annual Report 2022
OPC LUX: Climate Policy Observatory, Luxembourg, Annual Report 2022Marie-Astrid Heyde
 
Transient overvoltages and currents: lightning surges
Transient overvoltages and currents: lightning surgesTransient overvoltages and currents: lightning surges
Transient overvoltages and currents: lightning surgesBruno De Wachter
 
Transient overvoltages and currents: detection and measurement
Transient overvoltages and currents: detection and measurementTransient overvoltages and currents: detection and measurement
Transient overvoltages and currents: detection and measurementBruno De Wachter
 
Energy efficiency self-assessment in buildings
Energy efficiency self-assessment in buildingsEnergy efficiency self-assessment in buildings
Energy efficiency self-assessment in buildingsLeonardo ENERGY
 

Similaire à Voltage characteristics of grid electricity (EN 50160) (20)

Interharmonics
InterharmonicsInterharmonics
Interharmonics
 
Predicting and Monitoring PV Energy Production
Predicting  and Monitoring PV Energy ProductionPredicting  and Monitoring PV Energy Production
Predicting and Monitoring PV Energy Production
 
Infrared thermal energy scanning for energy efficiency assessment
Infrared thermal energy scanning for energy efficiency assessmentInfrared thermal energy scanning for energy efficiency assessment
Infrared thermal energy scanning for energy efficiency assessment
 
New loads on old switches, relays and contractors
New loads on old switches, relays and contractorsNew loads on old switches, relays and contractors
New loads on old switches, relays and contractors
 
White paper - Residential Electrical Safety
White paper - Residential Electrical SafetyWhite paper - Residential Electrical Safety
White paper - Residential Electrical Safety
 
Electrical storage systems: efficiency and lifetime
Electrical storage systems: efficiency and lifetimeElectrical storage systems: efficiency and lifetime
Electrical storage systems: efficiency and lifetime
 
Guide toen50160
Guide toen50160Guide toen50160
Guide toen50160
 
Glass
GlassGlass
Glass
 
12 39 rapport_screen
12 39 rapport_screen12 39 rapport_screen
12 39 rapport_screen
 
Small hydroelectric power
Small hydroelectric powerSmall hydroelectric power
Small hydroelectric power
 
Future Inspection of Overhead Transmission Lines
 Future Inspection of Overhead Transmission Lines Future Inspection of Overhead Transmission Lines
Future Inspection of Overhead Transmission Lines
 
Introduction to power quality (PQ)
Introduction to power quality (PQ)Introduction to power quality (PQ)
Introduction to power quality (PQ)
 
Best Protection Practices for HV and EHV AC-Transmission Systems of ENTSO-E E...
Best Protection Practices for HV and EHV AC-Transmission Systems of ENTSO-E E...Best Protection Practices for HV and EHV AC-Transmission Systems of ENTSO-E E...
Best Protection Practices for HV and EHV AC-Transmission Systems of ENTSO-E E...
 
Best Protection Practices for HV and EHV AC-Transmission Systems of ENTSO-E E...
Best Protection Practices for HV and EHV AC-Transmission Systems of ENTSO-E E...Best Protection Practices for HV and EHV AC-Transmission Systems of ENTSO-E E...
Best Protection Practices for HV and EHV AC-Transmission Systems of ENTSO-E E...
 
Earthing Configurations
Earthing ConfigurationsEarthing Configurations
Earthing Configurations
 
OPC LUX: Climate Policy Observatory, Luxembourg, Annual Report 2022
OPC LUX: Climate Policy Observatory, Luxembourg, Annual Report 2022OPC LUX: Climate Policy Observatory, Luxembourg, Annual Report 2022
OPC LUX: Climate Policy Observatory, Luxembourg, Annual Report 2022
 
Transient overvoltages and currents: lightning surges
Transient overvoltages and currents: lightning surgesTransient overvoltages and currents: lightning surges
Transient overvoltages and currents: lightning surges
 
Transient overvoltages and currents: detection and measurement
Transient overvoltages and currents: detection and measurementTransient overvoltages and currents: detection and measurement
Transient overvoltages and currents: detection and measurement
 
Energy efficiency self-assessment in buildings
Energy efficiency self-assessment in buildingsEnergy efficiency self-assessment in buildings
Energy efficiency self-assessment in buildings
 
Wind Barriers - Administrative and grid access barriers to wind power
Wind Barriers - Administrative and grid access barriers to wind powerWind Barriers - Administrative and grid access barriers to wind power
Wind Barriers - Administrative and grid access barriers to wind power
 

Plus de Leonardo ENERGY

A new generation of instruments and tools to monitor buildings performance
A new generation of instruments and tools to monitor buildings performanceA new generation of instruments and tools to monitor buildings performance
A new generation of instruments and tools to monitor buildings performanceLeonardo ENERGY
 
Addressing the Energy Efficiency First Principle in a National Energy and Cli...
Addressing the Energy Efficiency First Principle in a National Energy and Cli...Addressing the Energy Efficiency First Principle in a National Energy and Cli...
Addressing the Energy Efficiency First Principle in a National Energy and Cli...Leonardo ENERGY
 
Auctions for energy efficiency and the experience of renewables
 Auctions for energy efficiency and the experience of renewables Auctions for energy efficiency and the experience of renewables
Auctions for energy efficiency and the experience of renewablesLeonardo ENERGY
 
Energy efficiency first – retrofitting the building stock final
Energy efficiency first – retrofitting the building stock finalEnergy efficiency first – retrofitting the building stock final
Energy efficiency first – retrofitting the building stock finalLeonardo ENERGY
 
How auction design affects the financing of renewable energy projects
How auction design affects the financing of renewable energy projects How auction design affects the financing of renewable energy projects
How auction design affects the financing of renewable energy projects Leonardo ENERGY
 
Energy Efficiency Funds in Europe (updated)
Energy Efficiency Funds in Europe (updated)Energy Efficiency Funds in Europe (updated)
Energy Efficiency Funds in Europe (updated)Leonardo ENERGY
 
Energy Efficiency Funds in Europe
Energy Efficiency Funds in EuropeEnergy Efficiency Funds in Europe
Energy Efficiency Funds in EuropeLeonardo ENERGY
 
Five actions fit for 55: streamlining energy savings calculations
Five actions fit for 55: streamlining energy savings calculationsFive actions fit for 55: streamlining energy savings calculations
Five actions fit for 55: streamlining energy savings calculationsLeonardo ENERGY
 
Recent energy efficiency trends in the EU
Recent energy efficiency trends in the EURecent energy efficiency trends in the EU
Recent energy efficiency trends in the EULeonardo ENERGY
 
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...Energy and mobility poverty: Will the Social Climate Fund be enough to delive...
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...Leonardo ENERGY
 
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?Leonardo ENERGY
 
Energy efficiency, structural change and energy savings in the manufacturing ...
Energy efficiency, structural change and energy savings in the manufacturing ...Energy efficiency, structural change and energy savings in the manufacturing ...
Energy efficiency, structural change and energy savings in the manufacturing ...Leonardo ENERGY
 
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)Leonardo ENERGY
 
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...Leonardo ENERGY
 
Modelling and optimisation of electric motors with hairpin windings
Modelling and optimisation of electric motors with hairpin windingsModelling and optimisation of electric motors with hairpin windings
Modelling and optimisation of electric motors with hairpin windingsLeonardo ENERGY
 
Casting zero porosity rotors
Casting zero porosity rotorsCasting zero porosity rotors
Casting zero porosity rotorsLeonardo ENERGY
 
Direct coil cooling through hollow wire
Direct coil cooling through hollow wireDirect coil cooling through hollow wire
Direct coil cooling through hollow wireLeonardo ENERGY
 
Motor renovation - Potential savings and views from various EU Member States
Motor renovation - Potential savings and views from various EU Member StatesMotor renovation - Potential savings and views from various EU Member States
Motor renovation - Potential savings and views from various EU Member StatesLeonardo ENERGY
 
The need for an updated European Motor Study - key findings from the 2021 US...
The need for  an updated European Motor Study - key findings from the 2021 US...The need for  an updated European Motor Study - key findings from the 2021 US...
The need for an updated European Motor Study - key findings from the 2021 US...Leonardo ENERGY
 
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...Leonardo ENERGY
 

Plus de Leonardo ENERGY (20)

A new generation of instruments and tools to monitor buildings performance
A new generation of instruments and tools to monitor buildings performanceA new generation of instruments and tools to monitor buildings performance
A new generation of instruments and tools to monitor buildings performance
 
Addressing the Energy Efficiency First Principle in a National Energy and Cli...
Addressing the Energy Efficiency First Principle in a National Energy and Cli...Addressing the Energy Efficiency First Principle in a National Energy and Cli...
Addressing the Energy Efficiency First Principle in a National Energy and Cli...
 
Auctions for energy efficiency and the experience of renewables
 Auctions for energy efficiency and the experience of renewables Auctions for energy efficiency and the experience of renewables
Auctions for energy efficiency and the experience of renewables
 
Energy efficiency first – retrofitting the building stock final
Energy efficiency first – retrofitting the building stock finalEnergy efficiency first – retrofitting the building stock final
Energy efficiency first – retrofitting the building stock final
 
How auction design affects the financing of renewable energy projects
How auction design affects the financing of renewable energy projects How auction design affects the financing of renewable energy projects
How auction design affects the financing of renewable energy projects
 
Energy Efficiency Funds in Europe (updated)
Energy Efficiency Funds in Europe (updated)Energy Efficiency Funds in Europe (updated)
Energy Efficiency Funds in Europe (updated)
 
Energy Efficiency Funds in Europe
Energy Efficiency Funds in EuropeEnergy Efficiency Funds in Europe
Energy Efficiency Funds in Europe
 
Five actions fit for 55: streamlining energy savings calculations
Five actions fit for 55: streamlining energy savings calculationsFive actions fit for 55: streamlining energy savings calculations
Five actions fit for 55: streamlining energy savings calculations
 
Recent energy efficiency trends in the EU
Recent energy efficiency trends in the EURecent energy efficiency trends in the EU
Recent energy efficiency trends in the EU
 
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...Energy and mobility poverty: Will the Social Climate Fund be enough to delive...
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...
 
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?
 
Energy efficiency, structural change and energy savings in the manufacturing ...
Energy efficiency, structural change and energy savings in the manufacturing ...Energy efficiency, structural change and energy savings in the manufacturing ...
Energy efficiency, structural change and energy savings in the manufacturing ...
 
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)
 
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...
 
Modelling and optimisation of electric motors with hairpin windings
Modelling and optimisation of electric motors with hairpin windingsModelling and optimisation of electric motors with hairpin windings
Modelling and optimisation of electric motors with hairpin windings
 
Casting zero porosity rotors
Casting zero porosity rotorsCasting zero porosity rotors
Casting zero porosity rotors
 
Direct coil cooling through hollow wire
Direct coil cooling through hollow wireDirect coil cooling through hollow wire
Direct coil cooling through hollow wire
 
Motor renovation - Potential savings and views from various EU Member States
Motor renovation - Potential savings and views from various EU Member StatesMotor renovation - Potential savings and views from various EU Member States
Motor renovation - Potential savings and views from various EU Member States
 
The need for an updated European Motor Study - key findings from the 2021 US...
The need for  an updated European Motor Study - key findings from the 2021 US...The need for  an updated European Motor Study - key findings from the 2021 US...
The need for an updated European Motor Study - key findings from the 2021 US...
 
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...
 

Dernier

UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 

Dernier (20)

UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 

Voltage characteristics of grid electricity (EN 50160)

  • 1. APPLICATION NOTE STANDARD EN 50160 VOLTAGE CHARACTERISTICS OF ELECTRICITY SUPPLIED BY PUBLIC ELECTRICITY NETWORKS Antoni Klajn, Marta Bątkiewicz-Pantuła March 2017 ECI Publication No Cu0147 Available from www.leonardo-energy.org
  • 2. Publication No Cu0147 Issue Date: March 2017 Page i Document Issue Control Sheet Document Title: Application Note – Standard EN 50 160 Publication No: Cu0147 Issue: 03 Release: Public Content provider(s) Antoni Klajn, Marta Bątkiewicz-Pantuła Author(s): Antoni Klajn, Marta Bątkiewicz-Pantuła Editorial and language review Bruno De Wachter (editorial), Noel Montrucchio (language) Content review: Stefan Fassbinder, David Chapman, Roman Targosz Document History Issue Date Purpose 1 July 2004 First publication, in the framework of the Power Quality Application Guide 2 March 2013 Completely rewritten, in the framework of the Good Practice Guide 3 March 2017 Adapted after content review Disclaimer While this publication has been prepared with care, European Copper Institute and other contributors provide no warranty with regards to the content and shall not be liable for any direct, incidental or consequential damages that may result from the use of the information or the data contained. Copyright© European Copper Institute. Reproduction is authorized providing the material is unabridged and the source is acknowledged.
  • 3. Publication No Cu0147 Issue Date: March 2017 Page ii CONTENTS Summary ........................................................................................................................................................ 1 Introduction.................................................................................................................................................... 2 Basic definitions of voltage parameters.......................................................................................................... 4 Statistical philosophy.................................................................................................................................... 13 Low-voltage supply characteristics ............................................................................................................... 19 General ................................................................................................................................................................19 Continuous phenomena .......................................................................................................................................19 Power frequency variation.....................................................................................................................19 Supply voltage variation.........................................................................................................................20 Rapid voltage changes............................................................................................................................20 Supply-voltage unbalance ......................................................................................................................21 Harmonic voltage ...................................................................................................................................21 Interharmonic voltages ..........................................................................................................................23 Mains signaling voltages.........................................................................................................................23 Voltage events......................................................................................................................................................24 Interruptions of the supply voltage........................................................................................................24 Supply voltage dips/swells .....................................................................................................................24 Medium-voltage supply characteristics ........................................................................................................ 27 General ................................................................................................................................................................27 Continuous phenomena .......................................................................................................................................27 Power frequency ....................................................................................................................................27 Supply voltage variations .......................................................................................................................27 Rapid voltage changes............................................................................................................................28 Supply voltage unbalance.......................................................................................................................28 Harmonic voltage ...................................................................................................................................28 Interharmonic voltages ..........................................................................................................................29 Mains signaling voltage ..........................................................................................................................29 Voltage events......................................................................................................................................................29 Supply voltage dips/swells .....................................................................................................................29
  • 4. Publication No Cu0147 Issue Date: March 2017 Page iii High-voltage supply characteristics............................................................................................................... 31 General ................................................................................................................................................................31 Continuous phenomena .......................................................................................................................................31 Power frequency variations ...................................................................................................................31 Supply voltage variations .......................................................................................................................31 Rapid voltage changes............................................................................................................................31 Voltage events......................................................................................................................................................33 Supply voltage dips/swells .....................................................................................................................33 Performance criteria for voltage dips/swells ................................................................................................ 34 Electromagnetic environment classification ................................................................................................. 35 Classes of measurement methods ................................................................................................................ 37 Measurement aggregation over time intervals....................................................................................................37 Measurement aggregation algorithm...................................................................................................................37 Conclusions................................................................................................................................................... 38 References.................................................................................................................................................... 38
  • 5. Publication No Cu0147 Issue Date: March 2017 Page 1 SUMMARY Three parties exert an influence on the power quality in the electric network: the network operator, the network user and the manufacturer of the network equipment. Standard EN50160 represents a compromise between those three parties. The important advantages of the EN 50160 standard are:  The definition of the voltage parameters important for power quality  The quantitative determination of reference values that can be used in the power quality evaluation EN 50160 deals with the voltage characteristics in statistical or probabilistic terms. It gives recommendations that, for a percentage of measurements (e.g. 95%) over a given time, the value must be within the specified limits. This boundary value will be accepted as the compatibility level between the level of disturbances in the network and the level of immunity of equipment. In this way, the responsibilities of the network operator, equipment manufacturer and user are matched and clarified. EN 50160 prescribes separate voltage characteristics that Low Voltage (LV), Medium Voltage (MV) and High Voltage (HV) public networks should maintain. It makes a distinction in each of these three these categories between:  Continuous phenomena, i.e. deviations from the nominal values that occur continuously over time. Such phenomena occur mainly due to specific load patterns, changes of load, or nonlinear loads. For some of these phenomena, limits are specified.  Voltage events, i.e. sudden and significant deviations from normal or desired wave shape. Voltage events typically occur due to unpredictable events (e.g. faults) or to external causes (e.g. weather conditions, third party actions). At present, only indicative values can be given for voltage events. EN 50160 also prescribes minimum performance criteria that electrical equipment should maintain when they are subjected to voltage dips or swells on the network. In addition, EN 50160 provides an electromagnetic environment classification system, as well as three classes of measurement methods. The latter include an algorithm for aggregation of measurement results over time intervals. If the customer has higher requirements than the minimum performance criteria prescribed in this standard, they should instigate their own mitigation measures. Another option is to negotiate a separate agreement for a higher supply quality with the power supplier.
  • 6. Publication No Cu0147 Issue Date: March 2017 Page 2 INTRODUCTION To be optimally useful, the voltage at which electricity is supplied to the user should alternate at a constant frequency, with a perfect sine wave and with a constant magnitude. In practice, however, there are many factors which cause deviations from this ideal. These include the way in which the electricity is used. Moreover, electrical energy is a unique product because it is consumed at the instant at which it is generated. Consequently, measurement and evaluation of the power quality (PQ) must also be instantaneous. The technical standard EN 50160 describes the required characteristics of electricity, at the point of supply to the consumer, in terms of the alternating voltage. Ensuring PQ is a complex problem, because it is influenced by the actions of three parties:  The network operator  The manufacturer of electrical equipment  The network user (energy consumer), the user of this equipment. The relationships are illustrated in Figure 1: Figure 1—Illustration of reciprocal correlation between the three co-originators of power quality. Each of these parties has a certain influence on PQ as well as attendant duties and responsibilities.  The network operator should supply energy to meet the demand on the network, maintain the network in a good condition (e.g. sustain the short-circuit power at a sufficient level), as well as providing redundancy in network operation in order to meet the requirements of applicable standards.  The network user should select equipment and ensure its correct installation and operation to limit the level of electromagnetic disturbances introduced into the network. They should install uninterruptible power supplies (UPS) or other backup systems if appropriate. Equipment is influenced by supply disturbances and by other equipment in the installation, and it is in itself also influencing the supply quality. Correct operation requires maintaining the level of electromagnetic disturbances on other equipment below the limit as described in the EN 61000 series of the EMC standard.  The equipment manufacturer should provide the market with equipment with acceptably low levels of disturbance emissions onto the network as well as a sufficiently high level of immunity to the level of disturbances likely to exist in the network.
  • 7. Publication No Cu0147 Issue Date: March 2017 Page 3 The flow of energy to a network user’s appliances gives rise to proportional electric currents. As these currents flow through the conductors of the supply system, they cause voltage drops. The magnitude of the supply voltage for an individual network user at any instant is therefore a function of the cumulative voltage drops on all of the components of the system through which that network user is supplied, and determined both by the individual user’s demand and by the simultaneous demands of other network users (Figure 11). The impact of PQ on individual network users is a complex problem. The subject of this document is a detailed presentation and analysis of the requirements of the EN 50160 standard. Methods of measuring supply voltage parameters as well as examples of measurements are presented.
  • 8. Publication No Cu0147 Issue Date: March 2017 Page 4 BASIC DEFINITIONS OF VOLTAGE PARAMETERS The following terms and definitions apply for the purposes of the EN 50160 standard: Definitions concerning the normal (regular) state of the network operation Network operator—the party responsible for operating, maintaining and, if necessary, developing the supply network in a given area in order to ensure that the network is able to meet reasonable long-term demands for electricity supply. Network user—a party being supplied by or supplying to an electricity supply network. Nominal voltage Un —the voltage by which a supply network is designated and to which certain operating characteristics are referred. Supply terminal—a point in a public supply network at which electrical energy is exchanged between contractual partners. The terminal is designed for this task and its location is fixed in the contract. The point may differ from, for example, the electricity metering point or the point of common coupling. Point of common coupling (PCC)—the point on a public power supply network at which other loads are, or could be, connected. It is the point in the public network that is electrically the nearest to the connected load. Supply voltage—the RMS value of the voltage at a given time at the supply terminal, measured over a given time interval. Declared supply voltage Uc—the supply voltage agreed by the network operator and the network user. Generally the declared supply voltage Uc is the same as nominal voltage Un but it may also be different and defined by an agreement between network operator and the network user. Reference voltage (for interruptions, voltage dips and voltage swells evaluation)—is a value specified as the basis on which residual voltage, thresholds and other values are expressed in per unit or percentage terms. For the purpose of this standard, the reference voltage is the nominal or declared voltage of the supply system. Frequency of the supply voltage—the repetition rate of the fundamental wave of the supply voltage measured over a given time interval. Nominal frequency—the nominal value of the frequency of the supply voltage. Levels of voltage have been divided as follows: High voltage—a voltage whose nominal RMS value is 36 kV<Un<150 kV. Medium voltage—a voltage whose nominal RMS value is 1 kV<Un≤36 kV. Low voltage—a voltage whose nominal RMS value is Un≤ 1 kV. In some countries, the boundary between MV and HV may be different as a result of pre-existing network structures. Normal operating condition—an operating condition for an electricity network in which load and generation demands are met, system switching operations are made and faults are cleared by an automatic protection system, in the absence of exceptional circumstances, such as:
  • 9. Publication No Cu0147 Issue Date: March 2017 Page 5 A. Temporary supply arrangements B. Non-compliance of a network user’s installation or equipment with relevant standards or with the technical requirements for connection C. Exceptional situations, such as: 1. Exceptional weather conditions and other natural disasters 2. Third party interference 3. Acts by public authorities 4. Industrial actions (subject to legal requirements) 5. Force majeure 6. Power shortages resulting from external events Flicker—an unsteady visual sensation induced by a light stimulus. Usually, it applies to a cyclic variation of the light intensity or spectral distribution of a lamp which is caused by a fluctuation of the supply voltage. Flicker is typically a symptom of voltage disturbance caused by the use of large fluctuating loads, i.e. those that have rapidly fluctuating active and reactive power demand. The threshold above which flicker becomes annoying depends on the frequency and amplitude of the fluctuation. At certain repetition rates even very small amplitudes can be disturbing, often causing headaches, among other symptoms Figure 2. Figure 2—Example of an oscillogram showing the phenomenon of flicker. Flicker severity—the intensity of flicker annoyance is defined in terms of: - short-term severity (Pst) measured over a period of ten minutes - long-term severity (Plt) calculated from a rolling sequence of twelve Pst values over a two hour interval, according to the following expression: 𝑃𝑙𝑡 = √∑ 𝑃𝑠𝑡𝑖 3 12 12 𝑖=1 3 Pst is calculated according to a standardized formula which takes into account the response of the human eye and brain. Under normal operating conditions, the long-term flicker severity Plt caused by voltage fluctuation should be less than or equal to 1 for 95% of the time over a period of one week. Reaction to flicker is subjective and can vary, depending on the perceived cause of the flicker and the period over which it persists. In some cases, Plt = 1 gives rise to annoyance, whereas in other cases higher levels of Plt are observed without annoyance. Definitions concerning the abnormal (fault) state of the network operation Conduced disturbance—an electromagnetic phenomenon propagated along the line conductors of a supply network. In some cases, an electromagnetic phenomenon is propagated across transformer windings and hence between networks of different voltage levels. These disturbances may degrade the performance of a device, a piece of individual equipment or system or they may cause damage. Supply interruption—a condition in which the voltage at the supply terminals is lower than 5% of the reference voltage.
  • 10. Publication No Cu0147 Issue Date: March 2017 Page 6 Supply interruption can be classified as: A. Pre-arranged, when network users are informed in advance. Prearranged interruptions are typically due to the execution of scheduled work on the electricity network. B. Accidental, caused by permanent or transient faults, mostly related to external events, equipment failures or interference. Accidental supply interruptions are unpredictable, largely random events. An accidental interruption is classified as: 1) A long interruption (longer than 3 min.) 2) A short interruption (up to and including 3 min.) The effects of a prearranged interruption can be minimized by network users by taking appropriate measures to avoid disruption. Normally, accidental interruptions are caused by the operation of switches or protective devices in response to a short circuit or the failure of a device on the network. Figure 3 shows a supply interruption where: tf is the fall time during which the voltage is falling ts is the duration of reduced voltage tr is the rise time during which the voltage is recovering Figure 3—Illustration of a supply interruption [2]. For polyphase systems, an interruption occurs when the voltage drops below 5% of the reference voltage on all the phases. Otherwise, it is considered to be a dip on the affected phases. In some countries, the terms Very Short Interruptions (VSI) or transitory interruptions are used to classify interruptions with durations shorter than 1 to 5 s. Such interruptions are related to the operation of automatic reclosing devices. Long interruption of the supply voltage—under normal operating conditions, the annual frequency of voltage interruptions longer than three minutes varies substantially across areas. This is due to, among other things, differences in system layout (e.g. cable systems versus overhead line systems) and environmental and climatic conditions. The local network operator should be consulted in order to obtain information of what can be expected in a particular location. In some countries, national interruption statistics are available which give indicative values.
  • 11. Publication No Cu0147 Issue Date: March 2017 Page 7 Short interruption of supply voltage—the duration of the short interruptions is up to and including 3 minutes. Often, the duration of short interruptions may be less than a few seconds. When comparing statistical values for short interruptions, the following issues should be considered:  Principles for aggregating events (by adding up events)  The possible exclusion of Very Short Interruptions (VSI) or transitory interruptions. In some documents, short interruptions are considered to have durations not exceeding 1 minute. Control schemes are sometimes applied which need operating times of up to 3 minutes in order to avoid long voltage interruptions. Figure 4—Example of an oscillogram of a single phase voltage, showing a short interruption. Rapid voltage change—a single rapid variation of the RMS value of a voltage between two consecutive levels which are sustained for definite but unspecified durations. Transient overvoltage—a short duration oscillatory or non-oscillatory overvoltage, usually highly damped and with a duration of a few milliseconds or less. Transient overvoltages are usually caused by lightning, switching or the operation of fuses. The rise time of a transient overvoltage can vary from less than a microsecond up to a few milliseconds. Voltage dip—a temporary reduction of the RMS voltage below a specified start threshold. For the purpose of the standard, the dip start threshold is equal to 90% of the reference voltage. Typically, a dip is associated with the occurrence and termination of a short circuit or with other extreme current variations on the system or an installation connected to it. For the purpose of the standard, a voltage dip is a two dimensional electromagnetic disturbance, the level of which is determined both by the residual voltage and the time duration. Voltage dip duration—the time between the instant at which the RMS voltage at a particular point in an electricity supply system drops below the start threshold and the instant at which it rises above the end threshold. For the purposes of this standard, the duration of a voltage dip is from 10 ms up to and including 1 minute. For polyphase events, a dip begins when the voltage of at least one phase drops below the dip start threshold and ends when all voltages are equal to or higher than the dip end threshold. Voltage dip start threshold—the RMS value of the voltage on an electricity supply system specified for the purpose of defining the start of a voltage dip. Voltage dip end threshold—the RMS value of the voltage on an electricity supply system specified for the purpose of defining the end of a voltage dip. Voltage dip residual voltage—the minimum value of RMS voltage recorded during a voltage dip. For the purpose of this standard, the residual voltage is expressed as a percentage of the reference voltage. Figure 5 shows a dip with a residual voltage of 40%. The symbols are the same as defined for Figure 3.
  • 12. Publication No Cu0147 Issue Date: March 2017 Page 8 Figure 5—Illustration of a voltage dip with 40% retained voltage [2]. Figure 6 shows the voltage waveform during a dip to 30% residual voltage. Figure 6—Illustration of voltage dip waveform during a voltage dip [2]. Voltage fluctuation—a series of voltage changes or a cyclic variation of the voltage envelope. Voltage swell—temporary power frequency overvoltage—a temporary increase of the RMS voltage at a point in the electrical supply system above a specified start threshold. For the purpose of this standard, the following will be assumed:  The swell start threshold is equal to 110% of the reference voltage  A voltage swell is a two dimensional electromagnetic disturbance, the level being determined by both voltage and duration  Voltage swells may appear between live conductors or between live conductors and the earth. Depending on the neutral arrangement, faults to the ground may also give rise to overvoltages between healthy phases and the neutral Voltage swell start threshold—the RMS value of the voltage on an electricity supply system specified for the purpose of defining the start of a voltage swell.
  • 13. Publication No Cu0147 Issue Date: March 2017 Page 9 Voltage swell end threshold—the RMS value of the voltage on an electricity supply system specified for the purpose of defining the end of a voltage swell. Voltage swell duration—the time between the instant at which the RMS voltage at a particular point of an electricity supply system exceeds the start threshold and the instant at which it drops below the end threshold. For the purpose of this standard, the duration of a voltage swell is from 10 ms up to and including 1 minute. Voltage unbalance—the condition in a polyphase system in which the RMS values of the line-to-line voltages (fundamental component) or the phase angles between consecutive line voltages are not all equal. The degree of the inequality is usually expressed as the ratios of the negative and zero sequence components to the positive sequence component. In this standard, voltage unbalance is considered in relation to three- phase systems and negative phase sequence only. Figure 7 shows an example of an unbalanced three-phase system. Figure 7—An example of voltage unbalance in a 3-phase system. Figure 8 shows the voltages from Figure 7 as vectors. Note that the angle between vectors is not 120°.
  • 14. Publication No Cu0147 Issue Date: March 2017 Page 10 Figure 8—Illustration of vector voltages from Figure 7. Voltage variation—an increase or decrease of the RMS voltage, normally due to load variations. Figure 9 shows an example waveform of a voltage dip and voltage variation (blue plot) and the load (red plot) according to this voltage variation.
  • 15. Publication No Cu0147 Issue Date: March 2017 Page 11 Figure 9—Exemplary oscillograms of voltage dip and voltage variation. The following graph (Figure 10) summarizes the chapter ‘Basic definitions of voltage parameters’. It represents the most important parameters according to the EN 50160 standard.
  • 16. Publication No Cu0147 Issue Date: March 2017 Page 12 Figure 10—The most important parameters of the EN 50160 standard in the graphical form. Harmonic voltage—a sinusoidal voltage with a frequency equal to an integer multiple of the fundamental frequency of the supply voltage. Interharmonic voltage—a sinusoidal voltage with a frequency not equal to an integer multiple of the fundamental. Interharmonic voltages at closely adjacent frequencies can appear at the same time and form a wide band spectrum.
  • 17. Publication No Cu0147 Issue Date: March 2017 Page 13 STATISTICAL PHILOSOPHY The magnitude of the supply voltage for an individual network user at any instant is a function of the cumulative voltage drops caused by current flows through the components of the system through which the user is supplied (represented by RS and LS in Figure 11). Consequently, it is a function of current flows on all other network users (I(t) in Figure 11). The magnitude of the voltage supply is therefore determined both by the individual user’s demand and by the simultaneous demands of other network users. Since the demands of every network user and the degree of coincidence between them varies constantly, so does the supply voltage seen by each user. Figure 11 shows a notional network with three network users where:  Ii(t) is the load current of an individual network user  I(t) is the sum of load currents of all network users supplied from this PCC  ΔUi is the resulting voltage drop  RS, LS is the resistance and the inductance of the network. Figure 11—Illustration of the effect of cumulative voltage drops on an individual network user. Electricity reaches the user through a large system of generation, transmission and distribution equipment. Each component in the system is subject to potential damage or failure due to the electrical, mechanical and/or chemical stresses which arise from several causes, including extreme weather conditions, the ordinary processes of wear and deterioration with age and interference by human activities, animals, et cetera. Such damage can affect or even interrupt the supply to one or more network users. It is also necessary to keep the frequency constant. This requires the capacity to make power generation match the instantaneous aggregate demand at each instance. Because both power generation capacity and demand are liable to change in discrete amounts—especially in the event of faults on the generation— transmission or distribution networks, there is always a risk of a mismatch, resulting in an increase or decrease of the frequency. The size of frequency variations is reduced by connecting many systems into one large interconnected system with a total power generation capacity that is very large relative any sudden variations that are likely to occur.
  • 18. Publication No Cu0147 Issue Date: March 2017 Page 14 Figure 12—Oscillogram of low voltage at a PCC over the week (1008 of 10 minute measurements). Figure 13—Statistical distribution of voltage from Figure 12. Another problem is that of the immunity of equipment to disturbances coming from the network. This is generally an issue for manufacturers, who can contribute through careful equipment design in accordance with international standards, and for installation designers, who can contribute by preserving good installation practices. In some market segments, pre-standards were established by consortiums of manufacturers. An example of this is the Computer and Business Equipment Manufacturers’ Association (CBEMA) curve shown in Figure 14. The CBEMA curve, which predates most other standardization in this field, goes back to the era of analogue power supply. Its low voltage characteristic reflects the energy storage capacity of the filter capacitor.
  • 19. Publication No Cu0147 Issue Date: March 2017 Page 15 Figure 14—Immunity of equipment on to supply voltage variations—CBEMA characteristic. A similar curve of more recent date is that of the Information Technology Industry Council (ITIC). The ITIC curve (Figure 15) is a straight-line version which is easier to interpret. Figure 15—Immunity of equipment on to supply voltage variations—ITIC characteristic. These curves take account only of voltage variations and were originally used to allow manufacturers and users to understand the capabilities and limitations of computers and business equipment and their voltage stability requirements. The CBEMA characteristic can be divided into three areas shown as Type I, II and III in Figure 14. Starting with Type III, where the duration of the deviation exceeds 2 seconds, both CBEMA and ITIC curves are in agreement requiring a tolerance of ±15% of Un.
  • 20. Publication No Cu0147 Issue Date: March 2017 Page 16 The next category, Type II, represents swells or surges and sags or dips. The time period is from one half-cycle up to the boundary with Type III. For disturbances in this range, energy is supplied or stored by the power supply reservoir capacitor. Type I disturbances range from simple spikes at the sub-microsecond end of the range up to one half-cycle. These disturbances have extremely fast rise and fall times and their high frequency components are easily trapped by the EMC filters found in modern power supplies. The EMC filter prevents noise from the power supply reaching equipment and also prevents noise generated within the equipment from propagating on to the supply. It does not prevent the propagation of low frequency disturbances such as harmonics. Apart from the voltage tolerance characteristics addressed by the CBEMA and ITIC curves, there are other types of network disturbances to which immunity is important, as exemplified by the network testing carried out by EPRI [6]. Some power quality disturbances arise from unavoidable transient events in the supply system itself, resulting from faults or switching, or from atmospheric phenomena, e.g. lightning. Others, however, are the result of various uses of electricity which directly alter the waveform of the voltage, impose a particular pattern on its magnitude, or superimpose signaling voltages. Coincidentally with the modern proliferation of equipment which has these effects, there is also an increase in the equipment which is susceptible to the disturbances. It is a particular feature of electricity that, with respect to some of its characteristics, its quality is affected by the user as well as by the producer and/or network operator. In these cases the network user is an essential partner of the network operator in the effort to maintain the quality of electricity. Modern standardization is based on the concept of compatibility. For each relevant parameter a compatibility level is established. Standard development aims to establish, among other things, limits for network disturbances that can be met for a certain percentage of time on each location (e.g. 95%), and standards for products that can operate reliable with that level of disturbance. The concept is illustrated in Figure 16, where probability distributions are presented and the idea of the electromagnetic level is explained. Figure 16—The Concept of Compatibility. The left-hand bell-curve represents the probability of a particular level of the disturbance existing at a particular time at a PCC on the network. The compatibility level is the one defined by standards such as EN
  • 21. Publication No Cu0147 Issue Date: March 2017 Page 17 50160. It can be seen that, at any particular PCC, the disturbance level will be within the requirements of the compatibility level for a very large proportion of the time. Network operators may design their networks and the manner in which they arrange customer connections according to a ‘Planning level’. The difference between the planning and compatibility levels differs for different parameters. For example, for flicker severity and harmonic pollution—which are generated by users’ equipment and outside the control of the network operator—the margin will be greater, especially at low voltage, to allow for local conditions. It is important to point out that keeping the bell curve well to the left—i.e. to keep disturbance on the network low—is highly desirable, but doing so is also expensive. Setting standards is a compromise between technical excellence and economic reality. The right-hand bell-curve illustrates an idealized distribution of the immunity level of the installed equipment on the network. It indicates that the immunity level of most equipment, for most of the time, will be above the compatibility level, thus ensuring reliable operation. Immunity level is the level described by equipment standards, such as the EN 61XXX series. Diagrams similar to Figure 16 can be prepared for many parameters that may influence the performance of users’ equipment, such as the harmonic voltage level, flicker severity, voltage tolerance, et cetera. Consequently, EN 50160 deals with the voltage characteristics in statistical or probabilistic terms. It gives recommendations that, for a percentage of measurements (e.g. 95%) over a given time, the value must be within the specified limits. This boundary value will be accepted as the compatibility level between the level of disturbances in the network and the level of immunity of equipment. In this way, the responsibilities of the network operator, equipment manufacturer and user are matched and clarified. It is in the economic interest of the network user that the standard of supply should relate to conditions that can be expected normally, rather than to rare contingencies, such as an unusual degree of coincidence between the demands of several appliances or several network users. The standard defines, where possible, variations of the characteristics that may be normally expected. In other cases, the standard provides the possible indication of what, in quantitative terms, is to be expected. In the case of voltage dips, EN 50160 gives guidance only on what may be expected. The level of dips allowed is far more severe than the immunity level of equipment as defined by Figure 14 and Figure 15, so most equipment will not be immune. Where an improved performance is required, the user is responsible for installing the required equipment.
  • 22. Publication No Cu0147 Issue Date: March 2017 Page 18 Figure 17—Example trace of long-term severity of flicker Plt for one week (1008 10-minute measurements) in a 3-phase system. Taking the example of flicker severity, Figure 17 shows the recording of long-term flicker over a one week period. There are 1082 ten-minute readings. In order to easily assess the impact, the readings are reordered in decreasing order of value, as shown in Figure 18. In such a plot, it is immediately clear whether 95% of the values are within the standard limit or not. Figure 18—Ordered diagram of long-term severity of flicker Plt for one phase from Figure 17. Although this standard has obvious links with the concept of compatibility levels, it is important to note that it relates only to the voltage characteristics of electricity. It does not specify compatibility and immunity levels of equipment. The performance of equipment might be impaired if the equipment is subjected to supply conditions more severe than specified in their product standard.
  • 23. Publication No Cu0147 Issue Date: March 2017 Page 19 LOW-VOLTAGE SUPPLY CHARACTERISTICS See also [1]. GENERAL This clause describes the voltage characteristics of electricity supply by public low voltage networks. In the following, a distinction is made between:  Continuous phenomena, i.e. deviations from the nominal values that occur continuously over time. Such phenomena occur mainly due to specific load patterns, changes of load or nonlinear loads.  Voltage events, i.e. sudden and significant deviations from normal or desired wave shape. Voltage events typically occur due to unpredictable events (e.g. faults) or to external causes (e.g. weather conditions, third party actions). For some continuous phenomena, limits are specified:  For single rapid changes, only indicative values are given for the time being  For some specific parameters, stricter limits may exist in some national regulations For voltage events, only indicative values can be given at present. The standard nominal voltage Un for public low voltage is Un = 230 V, either between phase and neutral, or between two phases:  For four-wire three phase systems, Un = 230 V between phase and neutral  For three-wire three phase systems, Un = 230 V between phases. In low voltage systems the declared and nominal voltages are equal. CONTINUOUS PHENOMENA POWER FREQUENCY VARIATION The nominal frequency of the supply voltage in this European Standard shall be 50 Hz. Under normal operating conditions, the mean value of the fundamental frequency measured over 10 seconds shall be within a range as indicated in Table 1. Related monitoring is usually done by the Control Area Operator. Table 1—Requirements regarding power frequency variation [1]. Parameter For systems with synchronous connection to an interconnected system Duration For systems with no synchronous connection to an interconnected system (e.g. supply system on certain islands) Duration Power frequency 50 Hz ± 1% (i.e. 49.5 Hz ÷ 50.5 Hz) 99.5% of a year 50 Hz ± 2% (i.e. 49 Hz ÷ 51 Hz) 95% of a week 50 Hz + 4%/-6% (i.e. 47 Hz ÷ 52 Hz) 100% of the time 50 Hz ± 15% (i.e. 42.5 Hz ÷ 57.5 Hz) 100% of the time
  • 24. Publication No Cu0147 Issue Date: March 2017 Page 20 SUPPLY VOLTAGE VARIATION Under normal operating conditions, excluding the periods with interruptions, supply voltage variations should be within a range as indicated in Table 2. Table 2—Requirements regarding supply voltage variation [1] Parameter For systems with synchronous connection to an interconnected system Duration For systems with no synchronous connection to an interconnected system (e.g. supply system on certain islands) Duration Supply voltage Under normal operating conditions (excluding interruptions) Un ± 10% 95% of the 10- minute mean RMS values over each one week period All 10-minute mean RMS values shall be within the range of Un +10%/-15% Incl. special remote users Un + 10%/-15% Network users should be informed of the conditions. Network user equipment typically designed to tolerate supply voltages of ±10% of Un. 95% of the 10- minute mean RMS values over each one week period should be within ±10% of Un All 10-minute mean RMS values shall be within the range of Un +10%/-15% 1) The actual power consumption required by individual network users is fully predictable, in terms of amount and of simultaneousness. As a consequence, networks are generally designed on a probabilistic basis. If, following a complaint, measurements carried out by the network operator according to the above requirements indicate that the magnitude of the supply voltage is outside the limits given in the above requirements (which can have negative consequences for the network user), the network operator should take appropriate remedial action in collaboration with network user(s). Such action will of course depend upon a risk assessment. Pending resolution, voltage variations should be within the range +10%/-15% of Un, unless otherwise agreed with network users. In accordance with relevant product and installation standards, network users’ appliances are typically designed to tolerate supply voltages of ±10% around the nominal system voltage, which is sufficient to cover an overwhelming majority of supply conditions. Generally, appliances do not need to be designed to handle wider voltage variations. Identification of what constitutes a ‘special remote network user’ can vary between countries and take into account different characteristics of national electric systems such as limitation of power on supply terminal and/or power factor limits. RAPID VOLTAGE CHANGES SINGLE RAPID VOLTAGE CHANGES Rapid changes of the supply voltage are mainly caused either by load changes in the network users’ installations, by switching operations in the system, or by faults. If the magnitude of a voltage change crosses the threshold for voltage dips and/or swells, the event is classified as a voltage dip and/or swell rather than a rapid voltage change.
  • 25. Publication No Cu0147 Issue Date: March 2017 Page 21 At low voltage—under normal operating conditions—rapid voltage changes generally do not exceed 5% Un. But changes of up to 10% Un with a short duration of the sustained level might occur a few times per day under some circumstances. FLICKER SEVERITY Under normal operating conditions, during each period of one week, the long-term flicker severity Plt caused by voltage fluctuation should be less than or equal to 1 for 95% of the measurements. It is worth noting that the reaction to flicker is subjective. It can vary depending on the perceived cause of the flicker and the period over which it persists. In some cases Plt = 1 gives rise to annoyance, whereas in other cases higher levels of Plt may not. SUPPLY-VOLTAGE UNBALANCE Under normal operating conditions, during each period of one week, 95% of the 10-minute mean RMS values of the negative phase sequence component (fundamental) of the supply voltage shall be within the range 0% to 2% of the positive phase sequence component (fundamental). In this European Standard, only values for the negative sequence component are given. This component is the relevant one for the possible interference of appliances connected to the system. In some areas where there are users with largely single-phase or two-phase loads, unbalance up to approximately 3% may occur at the three-phase supply terminal. HARMONIC VOLTAGE A harmonic voltage is a sinusoidal voltage with a frequency equal to an integer multiple of the fundamental frequency of the supply voltage. The content of harmonics in the supply voltage is characterized in two ways: a) Individually by their relative amplitude (uh), which is the harmonic voltage related to the fundamental voltage u1, where h is the order of the harmonic (Table 2) b) Through the total harmonic distortion factor THD, calculated using the following expression: 𝑇𝐻𝐷 = √∑(𝑢ℎ)2 40 ℎ=2 Harmonics of the supply voltage are mainly caused by network users' non-linear loads connected to the supply network. Indeed, non-linear loads draw harmonic currents and harmonic currents flowing through the network impedance give rise to harmonic voltages. The harmonic currents and network impedances—and thus the harmonic voltages at the supply terminals—vary in time. The limitation to order 40 is conventional. However, in some countries, other values may be used (e.g. order 50 in the UK). Ad a) Under normal operation conditions, during each period of one week, 95% of the 10 minute mean RMS values of each individual harmonic voltage shall be less than or equal to the values given in Table 3. In this table, no values are given for harmonics of an order higher than 25, as they are usually small and largely unpredictable due to resonance effects.
  • 26. Publication No Cu0147 Issue Date: March 2017 Page 22 Table 3—Values of individual harmonic voltages at the supply terminals for harmonic orders up to 25 given as a percentage of the fundamental voltage u1 [1]. Odd harmonics Even harmonics Not multiples of 3 Multiples of 3 Order h Relative amplitude uh Order h Relative amplitude uh Order h Relative amplitude uh 5 6.0% 3 5.0% 2 2.0% 7 5.0% 9 1.5% 4 1.0% 11 3.5% 15 0.5% 6 to 24 0.5% 13 3.0% 21 0.5% 17 2.0% 19 1.5% 23 1.5% 25 1.5% Ad b) Moreover, the THD of the supply voltage (including all harmonics up to order 40) shall be less than or equal to 8%. Figure 19—Illustration of the influence of harmonics on the torque (M) during the operation of an electrical asynchronous motor. Figure 19 shows an example of the torque characteristics of an asynchronous induction motor connected to a distorted voltage supply in which
  • 27. Publication No Cu0147 Issue Date: March 2017 Page 23 M1 = undisturbed torque due to fundamental supply frequency Mi = torque due to harmonic i Mm = load torque Mw = resultant torque Harmonic voltage components cause harmonic current components in the motor. If the motor supply is distorted, the corresponding harmonic currents flow in the stator and are therefore reproduced in the magnetic field. These field components cause a parasitic torque which can result in vibration, acceleration of bearing wear, excess heating, and/or reduced service life. If the resultant torque curve, Mw crosses the load torque curve Mm (as indicated in Figure 19), the motor can stall. INTERHARMONIC VOLTAGES An interharmonic voltage is a sinusoidal voltage with a frequency not equal to an integer multiple of the fundamental. Interharmonic voltages at closely adjacent frequencies can appear at the same time, forming a wide band spectrum. The level of interharmonics is increasing due to the development of frequency converters and similar control equipment. Levels are under consideration, pending more field experience. In certain cases, interharmonics, even at low levels, give rise to flicker, or cause interference in ripple control systems. MAINS SIGNALING VOLTAGES In some countries, the public networks may be used for the transmission of signals by the network operators. Three types of signals in the public supply network can be classified:  Ripple control signals—superimposed sinusoidal voltage signals in the frequency range of 110 Hz to 3000 Hz  Power-line-carrier signals—superimposed sinusoidal voltage signals in the frequency range of 3 kHz to 148.5 kHz  Mains marking signals—superimposed short time alterations (transients) at selected points of the voltage waveform These may be used in network users’ installations and for the signaling in power line carriers. Voltages with these frequencies (95 Hz up to 148.5 kHz) of up to 1.4 V RMS have to be taken into account in the public LV network. However, the transmission of signals between network users is not permitted on the public LV network. Because of the possibility of mutual influences with neighboring network users’ signaling systems, the network user may need to apply protection or appropriate mitigation measures for their signaling installation. For PLC purposes, frequencies above 148.5 kHz are used in some networks. For 99% of a day, the 3 seconds mean value of signal voltages shall be less than or equal to the values given in Figure 20.
  • 28. Publication No Cu0147 Issue Date: March 2017 Page 24 Figure 20—Voltage levels of signal frequencies in percent of nominal voltage Un used in public LV and MV networks from EN50160 standard. VOLTAGE EVENTS See also [2. 3]. INTERRUPTIONS OF THE SUPPLY VOLTAGE Interruptions are, by their nature, unpredictable and vary from place to place and from time to time. For the time being, it is not possible to give fully representative results of interruption frequency measurements covering the whole of the European network. A reference for the actual interruption values recorded in European networks, divides them into long and short interruptions, as previously defined. At the national level, more precise statistics may be available. Furthermore, national regulations may exist. SUPPLY VOLTAGE DIPS/SWELLS GENERAL Voltage dips typically originate from faults occurring in the public network or in network users’ installations. Voltage swells are typically caused by switching operations and load disconnections. The swells treated in this clause are those which occur between live conductors. Both phenomena are unpredictable and largely random. The annual frequency varies greatly depending on the type of supply system and on the point of observation. Moreover, the distribution over the year can be very irregular. VOLTAGE DIP/SWELL MEASUREMENT AND DETECTION Voltage dips/swells shall be measured and detected by using the nominal supply voltage as a reference. The voltage dips/swell characteristics of interest for this standard are residual voltage (maximum RMS voltage for swells) and duration. In this standard, the duration is defined, as well as a value expressed in percentage of the residual voltage compared to the reference voltage for dips, and in maximum RMS voltage for swells. On LV networks, for four-wire three phase systems, the line to neutral voltages shall be considered. For three-wire three phase systems, the line to line voltages shall be considered. In the case of a single phase connection, the supply voltage (line to line or line to neutral, according to the network user connection) shall be considered.
  • 29. Publication No Cu0147 Issue Date: March 2017 Page 25 Conventionally, the dip start threshold is equal to 90% of the nominal voltage. The start threshold for swells is equal to 110% of the nominal voltage For polyphase measurements, it is recommended that the number of phases affected by each event is detected and recorded. VOLTAGE DIPS EVALUATION The method of analyzing the voltage dips (post treatment) depends on the purpose of the evaluation. Typically on LV networks:  If a three-phase system is considered, polyphase aggregation shall be applied. Polyphase aggregation consists of defining an equivalent event characterized by a single duration and a single residual voltage.  Time aggregation applies. Time aggregation consists of defining an equivalent event in the case of multiple successive events. The method used for the aggregation of multiple events can be set according to the final use of data. CLASSIFICATION OF VOLTAGE DIPS If statistics are collected, voltage dips shall be classified according to Table 4. The figures to be put in the cells are the number of equivalent events and the residual voltage is then calculated by polyphase aggregation. Further information is needed to consider events affecting an individual single phase voltage in three-phase systems. To calculate the latter, a different evaluation method has to be applied. Table 4 is to be taken as a recommendation for existing measurement equipment and/or monitoring systems. Table 4—Classification of dips according to residual voltage and duration. Residual voltage u % Duration t ms 10 ≤ t ≤ 200 200< t ≤500 500< t ≤1000 1000< t≤5000 5000<t ≤60000 90 > u ≥ 80 CELL A1 CELL A2 CELL A3 CELL A4 CELL A5 80 > u ≥ 70 CELL B1 CELL B2 CELL B3 CELL B4 CELL B5 70 > u ≥ 40 CELL C1 CELL C2 CELL C3 CELL C4 CELL C5 40 > u ≥ 5 CELL D1 CELL D2 CELL D3 CELL D4 CELL D5 5 > u CELL X1 CELL X2 CELL X3 CELL X4 CELL X5 Voltage dips are, by their nature, unpredictable and variable from place to place and from time to time. At present, it is not possible to give fully representative results of voltage dip frequency measurements covering the whole of the European network. It should be noted that due to the measurement method adopted, a measurement uncertainty affecting the results has to be taken into account. This is particularly relevant for shorter events. Generally, the duration of a voltage dip depends on the protection strategy adopted on the network. This may differ from network to network, depending upon the network structure and on neutral earthing. As a consequence, typical durations do not necessarily match the boundaries of the columns in Table 4.
  • 30. Publication No Cu0147 Issue Date: March 2017 Page 26 VOLTAGE SWELLS EVALUATION Typically, on LV networks:  If a three phase system is considered, polyphase aggregation shall be applied. Polyphase aggregation consists of defining an equivalent event characterized by a single duration and a single maximum RMS voltage.  Time aggregation applies. Time aggregation consists of defining an equivalent event in the case of multiple successive events. The method used for the aggregation of multiple events can be set according to the final use of data. For low voltage systems, under certain circumstances, a fault occurring upstream of a transformer may produce temporary overvoltages on the LV side for the time during which the fault current flows. Such overvoltages will generally not exceed 1.5 kV RMS. CLASSIFICATION OF VOLTAGE SWELLS If statistics are collected, voltage swells shall be classified according to the following table. For existing measurement equipment and/or monitoring systems, Table 5 is to be taken as a recommendation. Table 5—Classification of swells according to maximum voltage and duration. Swell voltage u % Duration t ms 10 ≤ t ≤ 500 500< t ≤5000 5000< t ≤60000 u ≥ 120 CELL S1 CELL S2 CELL S3 120 > u ≥ 110 CELL T1 CELL T2 CELL T3 Typically, faults in the public LV network or in a network user's installation give rise to temporary power frequency overvoltages between live conductors and the earth. Such overvoltages disappear when the fault is cleared.
  • 31. Publication No Cu0147 Issue Date: March 2017 Page 27 MEDIUM-VOLTAGE SUPPLY CHARACTERISTICS GENERAL The standard distinguishes between:  Continuous phenomena, i.e. deviations from the nominal value that occurs continuously over time. Such phenomena occur mainly due to load pattern, changes of load, or nonlinear loads.  Voltage events, i.e. sudden and significant deviations from the normal or desired wave shape. Voltage events typically occur due to unpredictable events (e.g. faults) or external causes (e.g. weather conditions, third party actions, et cetera). CONTINUOUS PHENOMENA POWER FREQUENCY The nominal frequency of the supply voltage in this European Standard shall be 50 Hz. Under normal operating conditions, the mean value of the fundamental frequency measured over 10 seconds shall be within the range given in Table 6. Monitoring is the responsibility of the Control Area Operator. Table 6—Requirements regarding power frequency and supply voltage variation. Parameter For systems with synchronous connection to an interconnected system Duration For systems with no synchronous connection to an interconnected system (e.g. supply system on certain islands) Duration Power frequency 50 Hz ± 1% (i.e. 49.5 Hz ÷ 50.5 Hz) 99.5% of a year 50 Hz ± 2% (i.e. 49 Hz ÷ 51 Hz) 95% of a week 50 Hz + 4%/-6% (i.e. 47 Hz ÷ 52 Hz) 100% of the time 50 Hz ± 15% (i.e. 42.5 Hz ÷ 57.5 Hz) 100% of the time SUPPLY VOLTAGE VARIATIONS Under normal operation condition, during each period of one week excluding the periods with interruptions, supply voltage variations should not exceed ± 10% of the declared voltage Uc. as indicate in Table 7— Requirements regarding supply voltage variation.
  • 32. Publication No Cu0147 Issue Date: March 2017 Page 28 Table 7—Requirements regarding supply voltage variation. Parameter For systems with synchronous connection to an interconnected system Duration For systems with no synchronous connection to an interconnected system (e.g. supply system on certain islands) Duration Supply voltage Under normal operating conditions, excluding periods of interruption, supply voltage variations should not exceed ±10% of the declared voltage Uc. 99% of the 10- minute mean RMS value over one week none of the 10- minute mean RMS values shall exceed ± 15% of Uc. (Incl. special remote users) Un + 10%/-15%. Network users should be informed of the conditions. 99% of the 10- minute mean RMS value over one week none of the 10- minute mean RMS values shall exceed ± 15% of Uc. RAPID VOLTAGE CHANGES SINGLE RAPID VOLTAGE CHANGE Rapid voltage changes in the supply voltage are mainly caused by either load changes in the network users' installations, by switching in the system or by faults. If the voltage during a change crosses the voltage dip and/or the voltage swell threshold, the event is classified as a voltage dip and/or swell rather than a rapid voltage change. For medium voltage, under normal operating conditions, rapid voltage changes generally do not exceed 4% Uc. However changes of up to 6% Uc with a short duration of the sustained level may occur a few times per day under some circumstances. FLICKER SEVERITY Under normal operation conditions, during each period of one week, the long-term flicker severity Plt caused by voltage fluctuations should be less or equal to 1 for 95% of the time. This value was chosen on the assumption that the transfer coefficient between MV and LV system is 1. In practice, the transfer coefficients between MV levels and LV levels can be less than 1. In the event of complaints, the MV limit and appropriate HV, MV and LV mitigation measures shall be chosen in such a way that at LV the Plt values do not exceed 1. SUPPLY VOLTAGE UNBALANCE Under normal operation condition, during each period of one week, 95% of the 10-minute RMS values of the negative phase sequence component of the supply voltage shall be within the range 0% to 2% of the positive phase sequence component. In some areas, unbalances of up to approximately 3% occur at three-phase supply terminals. HARMONIC VOLTAGE Under normal operation condition, during each period of one week, 95% of 10-minute mean RMS values of each individual harmonic voltage shall be less than or equal to the values given in Table 3. Moreover, the THD of the supply voltage (including all harmonics up to order 40) shall be less than or equal to 8%.
  • 33. Publication No Cu0147 Issue Date: March 2017 Page 29 INTERHARMONIC VOLTAGES The level of interharmonics is increasing due to the development of frequency converters and similar control equipment. Levels are under consideration, pending more field experience. In certain cases, interharmonics—even at low levels—give rise to flicker or cause interference in ripple control systems. MAINS SIGNALING VOLTAGE In some countries, the public networks may be used by the network operators for the transmission of signals. For 99% of a day, the 3 seconds mean value of the signal voltages shall be less or equal to the values given in Figure 20. It is assumed that network users do not use the public MV network for signaling purposes. Frequencies above 148.5 kHz are also used in some networks for PLC purposes. VOLTAGE EVENTS See also [2. 3]. SUPPLY VOLTAGE DIPS/SWELLS GENERAL Voltage dips typically originate from faults occurring in the public network or in network users’ installations. Voltage swells are typically caused by switching operations and load disconnections. Both phenomena are unpredictable and largely random. The annual frequency varies greatly, depending on the type of supply system and on the point of observation. Moreover, distribution over the year can be very irregular. VOLTAGE DIP/SWELL MEASUREMENT AND DETECTION Voltage dips/swells shall be measured and detected using the nominal supply voltage as the reference. The voltage dips/swell characteristics of interest for this standard are residual voltage (maximum RMS voltage for swells) and duration. In this standard, values are expressed as a percentage of the residual voltage. Typically, on MV networks, the line-to-line voltages shall be considered. Conventionally, the dip start threshold is equal to 90% of the nominal voltage. The start threshold for swells is equal to 110% of the nominal voltage. The hysteresis is typically 2%. For polyphase measurements, it is recommended that the number of phases affected by each event is detected and stored. VOLTAGE DIPS EVALUATION The method of analyzing the voltage dips (post treatment) depends on the purpose of the evaluation. Typically on MV networks:  Polyphase aggregation applies. This method consists of defining an equivalent event characterized by a single duration and a single maximum RMS voltage.
  • 34. Publication No Cu0147 Issue Date: March 2017 Page 30  Time aggregation applies. This method consists of defining a single equivalent event in the case of multiple successive events. The method used for the aggregation of multiple events can be set according to the final use of the data. CLASSIFICATION OF VOLTAGE DIPS If statistics are collected, voltage dips shall be classified according to Table 4. For existing measurement equipment and/or monitoring systems, the same table (Table 4) which is used for LV networks is to be taken as a recommendation for MV networks as well. VOLTAGE SWELLS EVALUATION Typically, on MV networks:  Polyphase aggregation applies. This method consists of defining a mono-phase event, characterized by a single duration and a single RMS voltage, that is equivalent to the actual polyphase event.  Time aggregation applies. This method consists of defining a single event that is equivalent to the actual multiple successive events. The method used for the aggregation can be set according to the final use of the data. Under certain circumstances, a fault occurring upstream of a transformer may produce temporary overvoltages on medium voltage systems. The expected value of such an overvoltage depends on the type of earthing of the system. The overvoltage shall generally not exceed 1.7 Uc in systems with a solidly or impedance earthed neutral. The overvoltage shall generally not exceed 2.0 Uc in isolated or resonant earthed systems. The type of earthing will be indicated by the network operator. CLASSIFICATION OF VOLTAGE SWELLS If statistics are collected, voltage swells shall be classified according to Table 5. The same table as the one indicated for LV networks is recommended in this instance as well for existing measurement equipment and/or monitoring systems.
  • 35. Publication No Cu0147 Issue Date: March 2017 Page 31 HIGH-VOLTAGE SUPPLY CHARACTERISTICS GENERAL Network users with demands exceeding the capacity of a medium voltage network are generally supplied at nominal voltages above 36 kV. This clause applies to such electricity supplies at nominal voltages up to and including 150 kV. CONTINUOUS PHENOMENA POWER FREQUENCY VARIATIONS The nominal frequency of the supply voltage in this European Standard shall be 50 Hz. Under normal operating conditions, the mean value of the fundamental frequency measured over 10 seconds shall be within a range given in Table 8. Table 8—Requirements regarding power frequency and supply voltage variation. Parameter For systems with synchronous connection to an interconnected system Duration For systems with no synchronous connection to an interconnected system (e.g. supply system on certain islands) Duration Power frequency 50 Hz ± 1% (i.e. 49.5 Hz ÷ 50.5 Hz) 99.5% of a year 50 Hz ± 2% (i.e. 49 Hz ÷ 51 Hz) 95% of a week 50 Hz + 4%/-6% (i.e. 47 Hz ÷ 52 Hz) 100% of the time 50 Hz ± 15% (i.e. 42.5 Hz ÷ 57.5 Hz) 100% of the time SUPPLY VOLTAGE VARIATIONS Under normal operation conditions, during each period of one week excluding the periods with interruptions, supply voltage variations should not exceed ± 10% of the declared voltage Uc. as indicated in Table 9. Table 9—Requirements regarding supply voltage variation. Parameter For systems with synchronous connection to an interconnected system Duration For systems with no synchronous connection to an interconnected system (e.g. supply system on certain islands) Duration Supply voltage As the number of network users supplied directly from HV networks is limited and normally subject to individual contracts, no limits for supply voltage variations are given in this standard. Existing product standards for HV equipment should be considered. RAPID VOLTAGE CHANGES SINGLE RAPID VOLTAGE CHANGE Rapid voltage changes in the supply voltage are mainly caused either by load changes in the network users' installations, by switching in the system, or by faults.
  • 36. Publication No Cu0147 Issue Date: March 2017 Page 32 If the voltage during a change crosses the voltage dip and/or the voltage swell threshold, the event is classified as a voltage dip and/or swell rather than a rapid voltage change. FLICKER SEVERITY Under normal operation conditions, during each period of one week, the long-term flicker severity Plt caused by voltage fluctuations should be less than or equal to 1 for 95% of the time. This value was chosen on the assumption that the transfer coefficient between HV and LV system is 1. In practice, the transfer coefficients between HV levels and LV levels can be less than 1. In the case of complaints, the HV limit and appropriate HV, MV and LV mitigation measures shall be chosen in such a way that the Plt values at LV do not exceed 1. SUPPLY VOLTAGE UNBALANCE Under normal operation conditions, during each period of one week, 95% of the 10 minute mean RMS values of the negative phase sequence component of the supply voltage should be within the range 0% to 2% of the positive phase sequence component. In some areas, unbalances of up to approximately 3% occur at three-phase supply terminals. HARMONIC VOLTAGE Under normal operating conditions, during each period of one week, 95% of the 10 minute mean RMS. values of each individual harmonic voltage should be less than or equal to the indicative values given in Table 10. Resonances may cause higher voltages for an individual harmonic. No values are considered for harmonics of an order higher than 25 since they are usually small and largely unpredictable due to resonance effects. Table 10—Values of individual harmonic voltages at supply HV terminals for orders up to 25 given in percentage of the fundamental voltage u1. Odd harmonics Even harmonics Not multiples of 3 Multiples of 3 Order h Relative amplitude uh Order h Relative amplitude (%) uh Order h Relative amplitude (%) uh 5 5.0 3 3.0 2 1.9 7 4.0 9 1.3 4 1.0 11 3.0 15 0.5 6 to 24 0.5 13 2.5 21 0.5 17 u.c. 19 u.c. 23 u.c. 25 u.c. Harmonics of orders higher than 13 and not a multiple of 3 are under consideration. In the case of complaints, limits for harmonics in HV networks should be chosen on the basis of MV network limits suitably modified by a quantity (D) as resulting from the following formula:
  • 37. Publication No Cu0147 Issue Date: March 2017 Page 33 HV LIMIT = MV LIMIT - D D should be agreed between the HV network operator and the connected network user—if necessary—in order to maintain harmonic levels of the connected network below the relevant limits. D can be chosen differently, depending on the use (harmonic transmission from HV public networks to HV public networks, from HV public networks to MV public networks or from HV public networks to network users). INTERHARMONIC VOLTAGE Due to the low resonance frequency of the HV network, no threshold values are given for the interharmonic voltage. Due to the very low resonant frequency in HV grids (200 Hz to 500 Hz) caused by high* capacitances and inductances, interharmonics are of minor relevance in HV networks. VOLTAGE EVENTS See also [2. 3]. SUPPLY VOLTAGE DIPS/SWELLS VOLTAGE DIP/SWELL MEASUREMENT AND DETECTION Voltage dips/swells shall be measured and detected using the nominal supply voltage as a reference. The voltage dips/swell characteristics of interest for this standard are residual voltage (maximum RMS voltage for swells) and duration. In this standard, values are expressed in terms of percentage of the residual. Typically, the line-to-line voltages shall be considered on HV networks. Conventionally, the dip start threshold is equal to 90% of the nominal voltage. The start threshold for a swell is equal to 110% of the nominal voltage. The hysteresis is typically 2%. For polyphase measurements, it is recommended that the number of phases that are affected by each event is detected and stored. VOLTAGE DIPS EVALUATION The method for analyzing voltage dips depends upon the purpose of the evaluation. Typically on HV networks:  Polyphase aggregation applies  Time aggregation applies CLASSIFICATION OF VOLTAGE DIPS If statistics are collected, voltage dips shall be classified according to Table 4. For existing measurement equipment and/or monitoring systems, Table 4 applies as well (the same one that is used for LV and MV networks). VOLTAGE SWELLS EVALUATION Typically, on HV networks:  Polyphase aggregation applies  Time aggregation applies CLASSIFICATION OF VOLTAGE SWELLS If statistics are collected, voltage swells shall be classified according to Table 5. For existing measurement equipment and/or monitoring systems the same table as the one indicated for LV and MV networks is recommended here as well.
  • 38. Publication No Cu0147 Issue Date: March 2017 Page 34 PERFORMANCE CRITERIA FOR VOLTAGE DIPS/SWELLS Performance criterion A. The apparatus shall continue to operate as intended during and after the test. There must be no degradation of performance or loss of function below a performance level specified by the manufacturer. A permissible loss of performance is acceptable. If the minimum performance level or permissible performance loss is not specified by the manufacturer, either of these may be derived from the product description and documentation and what the user may reasonably expect from the apparatus if used as intended. Performance criterion B. The apparatus shall continue to operate as intended after the test. No degradation of performance or loss of function is allowed below a performance level specified by the manufacturer. During the test however, degradation of performance is allowed. No change of actual operating state or stored data is allowed. If the minimum performance level or the permissible performance loss is not specified by the manufacturer, either of these may be derived from the product description and documentation and what the user may reasonably expect from the apparatus if used as intended. Performance criterion C. Temporary loss of function is allowed provided the function is self-recoverable or can be restored by operation of the controls.
  • 39. Publication No Cu0147 Issue Date: March 2017 Page 35 ELECTROMAGNETIC ENVIRONMENT CLASSIFICATION As detailed in product standards, voltage dip and swells—according to their severity—can impair the operation of equipment. For reference, the electromagnetic environment is characterized by following classes: Class 1 This class refers to protected supply systems. In this instance, the compatibility levels are lower than in the public supply network. It refers to environments where equipment is used that is highly sensitive to such disturbances, e.g. in technical laboratories, measurement facilities, computer centers and certain automation and protection equipment. Class 1 environments normally contain equipment which requires protection by apparatus such as uninterruptible power systems (UPS), filters or surge suppressers. Class 2 This class applies generally to PCCs and to IPCs in the environments of industrial and other non-public power supplies. The compatibility levels of this class are generally identical to those of public networks. Therefore, components designed for supply from public networks may be used in this class of industrial environments. Class 3 This class refers to internal points of common coupling (IPCC) in an industrial environment. For certain disturbances, the compatibility levels are higher than in class 2. For example, the consideration of this class is recommended if any of the following conditions are fulfilled:  A major part of the load is fed through converters  Welding machines are present  Large motors are frequently started  Loads vary rapidly The supply to highly disturbing loads such as arc-furnaces and large converters—these are generally supplied from a segregated busbar—frequently has disturbance levels in excess of class 3 (harsh environment). In such special situations, the compatibility levels should be agreed upon. Different classes can be relevant for different phenomena in any given network and should take into account the diversity of industrial environments. Although the cells of Table 4 are not precisely coincident with the test levels table, it can be expected that equipment tested according to the relevant product standard should cope with voltage dips as indicated in the cells:  A1, B1, A2, B2 for class 2  A1, B1, C1, A2, B2, A3, A4 for class 3
  • 40. Publication No Cu0147 Issue Date: March 2017 Page 36 Table 11—Recommended test level and duration of the voltage dips. Class Test level and duration of the voltage dips (50 Hz / 60 Hz) Class 1 Dependent on the case. according to the requirements of equipment Class 2 0% during ½ cycle 0% during 1 cycle 70% during 25/30 c) cycles Class 3 0% during ½ cycle 0% during 1 cycle 40% during 10/12 cycles 70% during 25/30 cycles 80% during 250/300 cycles b) —25/30 cycles, means “25 cycles for test at 50 Hz” as well as “30 cycles for test at 60 Hz”. Table 12—Recommended test level and duration of the short interruptions. Class Test level and duration of the voltage dips (50 Hz/60 Hz) Class 1 Dependent on the case, according to the requirements of equipment Class 2 0% during 250/300 cycles Class 3 0% during 250/300 cycles
  • 41. Publication No Cu0147 Issue Date: March 2017 Page 37 CLASSES OF MEASUREMENT METHODS See also [3, 7]. Three classes (A, S and B) are defined for each parameter measured. Measurement methods and appropriate performance requirements for each class are included. Class A This class is used where precise measurements are necessary. For example, in contractual applications that may require resolving disputes, verifying compliance with standards, et cetera. Any measurements of the same parameter on the same signal carried out with two different instruments complying with the requirements of class A will produce matching results within the specified uncertainty for that parameter. Class S This class is used for statistical applications such as surveys or power quality assessments with a limited subset of parameters. Class S processing requirements are lower although it uses equivalent intervals of measurement as class A. Class B This class is defined in order to avoid making many existing instrument designs obsolete. Class B methods shall not be employed for new instruments. All new instrument designs will comply with either Class A or Class S. Class B may be relevant for legacy instruments that are still in use [7]. Hereby: “A” stands for “Advanced”. “S” stands for “Surveys” and “B” for “Basic” methods. MEASUREMENT AGGREGATION OVER TIME INTERVALS The following measurement aggregations apply: Class A: The basic measurement time interval for parameter magnitudes (supply voltage, harmonics, interharmonics, unbalance) shall be a 10-cycle time interval for a 50 Hz power system or a 12-cycle time interval for a 60 Hz power system. The 10/12-cycle values are then aggregated over 3 additional intervals:  150/180-cycle interval (150 cycles for 50 Hz nominal or 180 cycles for 60 Hz nominal)  10 minute interval  2 hour interval Class S: The same time intervals as for class A prevail. The 10/12-cycle measurement shall be re-synchronized. Class B: The manufacturer shall specify the number and duration of aggregation time intervals. MEASUREMENT AGGREGATION ALGORITHM Aggregation shall be performed using the square root of the arithmetic mean of the squared input values. See also [3].
  • 42. Publication No Cu0147 Issue Date: March 2017 Page 38 CONCLUSIONS Standard EN 50160 should be understood as representing a compromise between the three parties which exert an influence on the power quality, i.e. network operator, network user and equipment manufacturer. Each of these three parties has an interest in performing their role. It is essential that electricity suppliers provide—as a minimum—a nominally adequate quality of supply. If the customer has higher requirements, they should instigate their own mitigation measures. Another option is to negotiate a separate agreement for a higher supply quality with the supplier. The important advantages of the EN 50160 standard are:  The definition of the voltage parameters important for power quality  The quantitative determination of reference values that can be used in the evaluation of power quality It is the task of the electricity regulator to set a level of quality that requires best practice from the supplier while not at the same time setting the level so high that the price of electricity increases for everybody. REFERENCES [1] EN 50160: July 2010. Voltage characteristics of electricity supplied by public electricity networks. [2] EN 61000-3-3: 2008. Electromagnetic compatibility (EMC). Part 3-3: Limits—Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply systems, for equipment with rated current ≤16 A per phase and not subject to conditional connection. [3] EN 61000-4-30:2009. Electromagnetic compatibility (EMC). Part 4-30: Testing and measurement techniques—Power quality measurement methods. [4] Asensi R. Harmonics. How should the compatibility level be understood? Power Quality Application Guide. Part 3.4.1. 2005. [5] http://www.marcspages.co.uk/pq/5130.htm [6] http://f47testing.epri.com/faq.html [7] EN 61000-4-30:2015 Electromagnetic compatibility (EMC). Part 4-30: Testing and measurement techniques—Power quality measurement methods.