Installation method of fire alarm detectors in fire security system
The installation of fire detectors and manual call points is one of the main part of the installation of fire alarm and
linkage system.
With the development of intelligent fire-fighting technology, there are more types of fire detectors and manual
push buttons, and the installation and wiring method may be different.
1. Method for determining the installation position of fire detectors
Although the fire detector type, quantity and general distribution are determined in the design drawing, the
location of the fire detector should be determined according to the specific situation of the site in the construction
process.
When determining the installation position and direction of the fire detector, the need of the function should be
first considered. In addition, aesthetics, the arrangement of surrounding lamps, air outlet and beam should also be
considered.
(1) The horizontal distance between the detector and the wall and beam should not be less than 0.5m, as shown
in the figure below
(2) There should be no shielding within 0.5m around the detector.
(3) The detector should be installed near the air inlet. The horizontal distance between the detector and the air
outlet of the air conditioner should not be less than 1.5m, as shown in the following figure
(4) When a detector is installed on the ceiling of an inner walkway less than 3m in width, it should be installed in
the center. The installation spacing of the heat detector shall not exceed 10m. The installation spacing of the
smoke detector shall not exceed 15m. The distance between the detector and the wall end shall not be greater
than half of the installation spacing of the detector. As shown in the following figure.
(5) When the roof slope θ>15°, the detector shall be installed at the highest point under the gabled roof, as shown
in the figure below
(6) When the roof slope θ<=45°, the detector can be directly installed on the roof panel, as shown in the figure
below
(7) For serrated roof, when the roof slope θ>15°, the detectors should be installed under each sawtooth ridge, as
shown in the figure below
(8) When the roof slope θ>45°, the detector shall be mounted with bracket and installed horizontally, as shown in
the figure below
(9) The detector confirmation LED indication should face to the main entrance direction for easy observation. This
is shown below
(10) For the elevator well, pipe well, lift well, you can only install a smoke detector on the roof of the machine
room above the well. For the stairwell, ramp walkway, you can install a smoke detector every 15m of the vertical
distance. As shown in the following figure
(11) In the large truss structure warehouse with no ceiling, the detector should be suspended and installed by
pipe rack, and the droop height should be determined according to the actual needs. When using a smoke
detector, a smoke hood should be added. As shown in the following figure
(12) When the room is divided by bookshelves, equipment, etc., if the distance from the top of the divider to the
ceiling or beam is less than 5% of the room's clear height, each divided part shall have at least one detector
installed.
2. Method for determining the installation position of fire manual call points
There shall be at least one manual alarm button for each fire partition in the alarm area.
The walking distance from any location within a fire partition to an adjacent manual alarm button should not be
greater than 30m.
Manual fire alarm button should be set in the obvious and easy to operate position, that is, the building's safety
exit, safety stairs entrance.
Usually the manual alarm button and the fire alarm bell are installed next to the fire hydrant. They are installed on
the wall at a height of 1.5m above the ground or floor and should be clearly marked.
When installing manual alarm button, embedded junction box may needed at some situation. The manual alarm
button shall be firmly installed and shall not be tilted.In order to facilitate debugging and maintenance, the
external lead of manual alarm button should be left with a margin of more than 10cm, and its end should be
clearly marked.
3. Installation method of fire detector
The installation method of the fire detector base varies according to the installation location of the building
structure. There are junction box embedded installation, installation under the ceiling and under the raised floor,
etc.
(1) Junction box embedded installation
The installation method of the embedded box is to preset the embedded hole seat in the civil engineering process
in advance, and when placing it, the wires are inserted into the junction box from the embedded wire pipe, as
shown in the figure below
Fix the detector base or detector wiring block on the junction box, and connect the power line or signal line from
the box to the corresponding junction post on the detector base (or weld to the corresponding patch on the base).
Connection points should be firm and reliable. The junction box shall be insulated between the base to ensure
good insulation between the two. After the installation and wiring of the base is finished, it should be checked
carefully. No wrong connection, short circuit or virtual welding are allowed. As shown in the following figure
After the installation of detector base is completed, do not remove the detector protection cover. Until the system
debugging stage, the protection cover is removed. The installation and assembly of the detector is shown in the
figure below. When the detector is installed, the confirmation indicator on the outer cover should be pointed in
the direction of the main entrance and exit for personnel to observe.
(2) Installation under the ceiling
In many cases, the detector is installed under the ceiling. There are two main cases according to the structure of
the building. One is to install the detector directly on the junction box inside the ceiling, as shown in FIG. 6-15.The
other is to install the detector on the keel and connect it to the junction box in the ceiling through the metal hose,
as shown in figure 6-16.
When the detector is installed under the roof, there are two ways to thread the pipeline, one is the dark piping, as
shown in FIG. 6-17. Another way is open piping method, as shown in FIG. 6-18.
(3) Installation under raised floor
Some fire alarm detectors need to be installed under a raised floor.The detector can be installed by special junction
box or standard junction box. If necessary, the installation hole spacing can be adjusted by adding adjustment
board.As shown in the following figure
Wiring and Layout
1. Method of terminal connection
The fire alarm system generally adopts copper core cable or wire. The single-core copper wire after
stripping off the insulation layer can be directly connected to the terminal block. The length of the
insulation layer stripped off is generally 1mm longer than the length inserted into the terminal block.
For multi-core copper wire, the insulation layer should be stripped off first, lined with tin and then
connected to the terminal block.
If the wire and cable are to be connected under the screw head, the single copper wire should be
bent in the shape shown in FIG. 6-20. The direction should be same as the screw is screwed in. For
multi-core copper wires, the terminals shall be pressed and the pressed joint shall be welded with
solder. The terminal should be in line with the wire diameter.
The cables or wires connected to the alarm controller shall meet the following requirements:
(1) The wiring should be neat, clear, beautiful, avoid crossing, and should be fixed firmly, terminal
plate should not bear external mechanical stress.
(2) The cable core and the end of the cable shall be numbered.
(3) No more than two wires shall be connected to each terminal of the terminal board.
(4) The cable core and conductor shall have a buffer of not less than 200mm.
(5) The wires should be put into plastic grooves or tied into bundles.
(6) After the wire is threaded, the inlet pipe should be blocked.
(7) The power supply wire of the alarm controller shall be directly connected to the fire protection
power supply. Do not use the power plug.The power supply shall be clearly marked.
(8) The controller shall be firmly grounded and clearly marked.
The wiring terminal is equipped with a label plate, which is used to distinguish various wiring and
terminal labels, so as to facilitate maintenance and inspection. Figure 6-21 is the package label. The
label must be printed and fitted on the wire before the wire is connected to the terminal. If there is
no plastic casing marking machine, you can also use carbon ink with an appropriate amount of
dichloroethane and gentian violet to write to prevent fading.
2. Method of wiring in the box
The detector, manual alarm button, sound device, door light and alarm bell have been wired up
while being installed. And a large number of cables and wires are summarized in the box (cabinet) of
the regional alarm controller and central alarm. According to the position of the wiring terminals
and the distribution of components in the box (cabinet), the reasonable wiring line in the box
(cabinet) shall be determined, and the line shall be drawn with a ruler.
Cables and wires are laid in the alarm control box, including plastic wire groove fixing method,
plastic spiral tube fixing method and binding method.
The toothed plastic line groove (line groove) is shown in FIG. 6-22. The line groove should be fixed
along the bottom plate or side of the box.The wire can be laid in the line groove, and the wire can be
drawn out from the perforation and connected to the terminal. If there are too many lead wires and
not available to layout, you can remove one or two teeth. After laying, the groove cover shall be well
covered.
The fixation method of plastic spiral tube is shown in FIG. 6-23. Arrange the wires neatly in the box
and lay the wires horizontally or vertically. After the wires are laid, open the plastic spiral tube and
wrap it around the wires. Tie the wires into a bundle by virtue of the elasticity of the plastic spiral
tube.
The cable wiring harness laid in the box can also be fastened with the binding belt made of
insulating material, and the spacing of the binding belt should be 100mm.The bending radius of the
wire should not be less than 3 times of its outer diameter, there should be no middle head in the
alarm control box, and the insulation sheath should not be damaged.The tying method of cables and
wires laid in the box is shown in FIG. 6-24.
3. Wiring method of shielding layer
Shielded cables are used as transmission lines in some fire alarm and linkage systems to improve the
anti-interference ability of the system. The wiring of the shielding layer shall follow the schematic
diagram of the fire alarm system. Most use the shield layer as the ground line. In the alarm control
box, all the shielded wires are welded with terminal and connected to the wiring terminal row.
However, in some systems, the shield layer plays a certain role in signal transmission, it can not be
grounded. Such a system, the plastic hose should be added to the shield layer after stripping before
connection and the shield layer is forbidden to be grounded. The wiring of shielding layer must be
firm and reliable. When stripping the insulation layer, the shielding layer should not be damaged.
The quality of shielding treatment will directly affect the transmission quality.
4. The function and working mode of manual alarm button.
Manual alarm button is one of the necessary equipment in fire alarm and linkage system. It has the
function of confirming the fire or sending out the fire signal manually.When people find the fire,
they can make manual alarm through the manual alarm button installed in the corridor, stairs, etc.
Manual alarm button is the key installed in the metal box, the metal box is generally embedded in
the wall, exposed red border of the protective cover. After manually confirming the fire, knock out
the protective cover and press the button. At this time, on the one hand, the alarm equipment on
the scene (such as fire alarm siren strobe, fire alarm bell) alarms. On the other hand, the manual
signal is sent to the area alarm to send out the fire alarm. Like the detector, the manual alarm
button also has a point in the system. Some alarm buttons also have the function of action
indication, receiving feedback signal and so on.
Alarm emergency degree triggered by manual alarm button is higher than that triggered by a
detector and alarm triggered by manual alarm button does not need confirmation. So manual
buttons require more reliability, more certainty, and the alarm triggered needs faster dealing. The
manual alarm button should be connected with the central alarm and occupy a point number
separately. Because the centralized alarm controller is placed in the fire security guard room, it can
take measures more quickly. So if there is no centralized alarm, and the manual alarm button is
connected to the area alarm panel, it should occupy a point number.
The installation of combustible gas sensor
The installation height of combustible gas detector shall be determined according to the type and
density of the detected gas. For gases’ density heavier than air, such as liquefied petroleum gas, the
detector shall be installed 10cm above the ground, and for gases' density lighter than air, such as
urban artificial gas and natural gas, the detector shall be installed within 30cm from the ceiling.As
shown in the following figure.
When the beam height is greater than 0.6m, the combustible gas detector should be installed on
the side with the gas cooker, as shown in the figure below
The combustible gas detector shall be installed under the roof within 8m from the gas stove as
shown in the figure below
Installation of infrared beam smoke detector
The transmitter and receiver of the infrared beam smoke detector should be installed opposite to
each other at both ends of the protection space and on the same horizontal line. The vertical
distance between the beam axis of the infrared beam smoke detector and the ceiling should be
0.3~1.0m, and the distance from the ground should not exceed 20m. The horizontal distance
between two adjacent infrared beam smoke detectors should not be greater than 14m.The
horizontal distance between the detector and the side wall shall not be greater than 7m and shall
not be less than 0.5m. The distance between the transmitter and receiver of the detector should not
exceed 100m. When the height of the room is 8-14m, besides the beam smoke detector installed
under the ceiling, the beam smoke detector should also be installed at 1/2 of the height of the room.
When the room height is 14-20m, the detector should be set in three layers. (under the ceiling, at
1/3 of the room height, at 2/3 of the room height) The working principle of infrared beam smoke
detector is shown in the following figure.
The installation position of infrared beam smoke detector should be far away from the strong
magnetic field, without direct sunlight, and no dust retention in the detector using environment.
There should not have fixed and flowing obstacle between the transmitter and receiver of the
detector. The base of the detector must be firmly installed and will not come loose. The installation
method of the detector in the ceiling is shown in FIG. 6-30, and the installation method in the wall is
shown in FIG. 6-31.
Installation of cable sensor
When the cable type linear constant heat detector is installed on the cable bridge or bracket,
contact arrangement should be adopted. When setting up on various belt conveying devices, it is
advised to set up near the hot spot of the device. When the air tube type linear rate-of-rise
temperature detector is installed under the ceiling, it should be installed 0.1m from the ceiling. The
horizontal distance between adjacent pipelines should not be greater than 5m. The distance
between the pipeline and the wall should be 1-1.5m. The installation of cable fixed temperature
detector in cable tunnel and cable trench with single side support is shown in FIG. 6-32

Contenu connexe

Tendances

Fire Fighting systems - Advanced Services
Fire Fighting systems - Advanced ServicesFire Fighting systems - Advanced Services
Fire Fighting systems - Advanced ServicesPratibha Mohan
 
Fire Safety and Building Materials
Fire Safety and Building MaterialsFire Safety and Building Materials
Fire Safety and Building MaterialsSorab Mishra
 
Deisgn of Fire Escapes
Deisgn of Fire EscapesDeisgn of Fire Escapes
Deisgn of Fire EscapesIshan Garg
 
Heat and smoke detectors
Heat and smoke detectors Heat and smoke detectors
Heat and smoke detectors wasim shaikh
 
Presentation Highlighting Implication of NBC, Part-IV 2016
Presentation Highlighting Implication of NBC, Part-IV 2016Presentation Highlighting Implication of NBC, Part-IV 2016
Presentation Highlighting Implication of NBC, Part-IV 2016Anil Kumar R
 
Construction Safety Training_Session 05_Access Equipment and Fall Protection
Construction Safety Training_Session 05_Access Equipment and Fall ProtectionConstruction Safety Training_Session 05_Access Equipment and Fall Protection
Construction Safety Training_Session 05_Access Equipment and Fall ProtectionMuizz Anibire
 
Fire Detection and Alarm Systems
Fire Detection and Alarm SystemsFire Detection and Alarm Systems
Fire Detection and Alarm SystemsJ.T.A.JONES
 
High-Rise Firefighting
High-Rise FirefightingHigh-Rise Firefighting
High-Rise FirefightingTim Sweat
 
Active and passive fire protection system
Active and passive fire protection systemActive and passive fire protection system
Active and passive fire protection systemKamran Hassan
 
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTFIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTMEP ENGINEER'S SERVICES
 
FIRE SAFETY PLAN IN A BUILDING
FIRE SAFETY PLAN IN A BUILDINGFIRE SAFETY PLAN IN A BUILDING
FIRE SAFETY PLAN IN A BUILDINGKuldeep Kumar
 

Tendances (20)

Fire Fighting systems - Advanced Services
Fire Fighting systems - Advanced ServicesFire Fighting systems - Advanced Services
Fire Fighting systems - Advanced Services
 
Fire Safety and Building Materials
Fire Safety and Building MaterialsFire Safety and Building Materials
Fire Safety and Building Materials
 
Fire safety
Fire safety Fire safety
Fire safety
 
Deisgn of Fire Escapes
Deisgn of Fire EscapesDeisgn of Fire Escapes
Deisgn of Fire Escapes
 
Heat and smoke detectors
Heat and smoke detectors Heat and smoke detectors
Heat and smoke detectors
 
2. Hydrant System.pdf
2. Hydrant System.pdf2. Hydrant System.pdf
2. Hydrant System.pdf
 
Fire protection system ppt.
Fire protection system ppt.Fire protection system ppt.
Fire protection system ppt.
 
Fire alarm systems
Fire alarm systems Fire alarm systems
Fire alarm systems
 
Presentation Highlighting Implication of NBC, Part-IV 2016
Presentation Highlighting Implication of NBC, Part-IV 2016Presentation Highlighting Implication of NBC, Part-IV 2016
Presentation Highlighting Implication of NBC, Part-IV 2016
 
Fire Detection and Alarm System (FDAS).pptx
Fire Detection and Alarm System (FDAS).pptxFire Detection and Alarm System (FDAS).pptx
Fire Detection and Alarm System (FDAS).pptx
 
Construction Safety Training_Session 05_Access Equipment and Fall Protection
Construction Safety Training_Session 05_Access Equipment and Fall ProtectionConstruction Safety Training_Session 05_Access Equipment and Fall Protection
Construction Safety Training_Session 05_Access Equipment and Fall Protection
 
Fire Detection and Alarm Systems
Fire Detection and Alarm SystemsFire Detection and Alarm Systems
Fire Detection and Alarm Systems
 
High-Rise Firefighting
High-Rise FirefightingHigh-Rise Firefighting
High-Rise Firefighting
 
Active and passive fire protection system
Active and passive fire protection systemActive and passive fire protection system
Active and passive fire protection system
 
Fire safety
Fire safetyFire safety
Fire safety
 
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTFIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
 
Fire Fighting system
Fire Fighting systemFire Fighting system
Fire Fighting system
 
Fire fighting -1 By Er. Ezaz
Fire fighting -1 By Er. EzazFire fighting -1 By Er. Ezaz
Fire fighting -1 By Er. Ezaz
 
1 Fire safety design principles
1  Fire safety design principles1  Fire safety design principles
1 Fire safety design principles
 
FIRE SAFETY PLAN IN A BUILDING
FIRE SAFETY PLAN IN A BUILDINGFIRE SAFETY PLAN IN A BUILDING
FIRE SAFETY PLAN IN A BUILDING
 

Similaire à How to install fire alarm system

MSAN Huawei T500 (MA5600T) Quick Installation Guide
MSAN Huawei T500 (MA5600T) Quick Installation GuideMSAN Huawei T500 (MA5600T) Quick Installation Guide
MSAN Huawei T500 (MA5600T) Quick Installation Guideibrahimnabil17
 
BTS Reserves for Installation, Preventative Maintenance and Acceptance
BTS Reserves for Installation, Preventative Maintenance and AcceptanceBTS Reserves for Installation, Preventative Maintenance and Acceptance
BTS Reserves for Installation, Preventative Maintenance and Acceptanceibrahimnabil17
 
Pluto Installation Manual
Pluto Installation Manual Pluto Installation Manual
Pluto Installation Manual kristenjames
 
Electrification of multistore building
Electrification of multistore buildingElectrification of multistore building
Electrification of multistore buildingddsshukla
 
Indoor environmental-quality-in-healthcare-3-2
Indoor environmental-quality-in-healthcare-3-2Indoor environmental-quality-in-healthcare-3-2
Indoor environmental-quality-in-healthcare-3-2Jessyca Than
 
EtisalatTelecom Model 2016 modified.pptx
EtisalatTelecom Model 2016 modified.pptxEtisalatTelecom Model 2016 modified.pptx
EtisalatTelecom Model 2016 modified.pptxssuser8298f2
 
Indoor environmental-quality-in-healthcare (3)
Indoor environmental-quality-in-healthcare (3)Indoor environmental-quality-in-healthcare (3)
Indoor environmental-quality-in-healthcare (3)Yong Sy
 
Adjustable Differential type Vacuum Switch MA series
Adjustable Differential type Vacuum Switch MA seriesAdjustable Differential type Vacuum Switch MA series
Adjustable Differential type Vacuum Switch MA seriesNK Instruments Pvt. Ltd.
 
Technical data sheet heat exchanger BOUL
Technical data sheet heat exchanger BOULTechnical data sheet heat exchanger BOUL
Technical data sheet heat exchanger BOULBoulKharkiv
 
UK Plus Brochure
UK Plus Brochure UK Plus Brochure
UK Plus Brochure Schiedel UK
 
Annex 4 part 1-fdh (i) installation guide
Annex 4 part 1-fdh (i) installation guideAnnex 4 part 1-fdh (i) installation guide
Annex 4 part 1-fdh (i) installation guideIgors Cardoso
 
Electrical layout of
Electrical layout ofElectrical layout of
Electrical layout ofBhakti Stm
 
D.04 Solar Photovoltaic Systems 12 24 08
D.04 Solar Photovoltaic Systems 12 24 08D.04 Solar Photovoltaic Systems 12 24 08
D.04 Solar Photovoltaic Systems 12 24 08guestaa3f06
 
Telecommunication for high rise building
Telecommunication for high rise buildingTelecommunication for high rise building
Telecommunication for high rise buildingJäkê Čhŷį Śêrñ
 

Similaire à How to install fire alarm system (20)

MSAN Huawei T500 (MA5600T) Quick Installation Guide
MSAN Huawei T500 (MA5600T) Quick Installation GuideMSAN Huawei T500 (MA5600T) Quick Installation Guide
MSAN Huawei T500 (MA5600T) Quick Installation Guide
 
Guided Wave Radar Level Meter.pdf
Guided Wave Radar Level Meter.pdfGuided Wave Radar Level Meter.pdf
Guided Wave Radar Level Meter.pdf
 
BTS Reserves for Installation, Preventative Maintenance and Acceptance
BTS Reserves for Installation, Preventative Maintenance and AcceptanceBTS Reserves for Installation, Preventative Maintenance and Acceptance
BTS Reserves for Installation, Preventative Maintenance and Acceptance
 
Pluto Installation Manual
Pluto Installation Manual Pluto Installation Manual
Pluto Installation Manual
 
Electrification of multistore building
Electrification of multistore buildingElectrification of multistore building
Electrification of multistore building
 
Indoor environmental-quality-in-healthcare-3-2
Indoor environmental-quality-in-healthcare-3-2Indoor environmental-quality-in-healthcare-3-2
Indoor environmental-quality-in-healthcare-3-2
 
EtisalatTelecom Model 2016 modified.pptx
EtisalatTelecom Model 2016 modified.pptxEtisalatTelecom Model 2016 modified.pptx
EtisalatTelecom Model 2016 modified.pptx
 
Indoor environmental-quality-in-healthcare (3)
Indoor environmental-quality-in-healthcare (3)Indoor environmental-quality-in-healthcare (3)
Indoor environmental-quality-in-healthcare (3)
 
Cistermiser Sensazone - Installation Guide
Cistermiser Sensazone - Installation GuideCistermiser Sensazone - Installation Guide
Cistermiser Sensazone - Installation Guide
 
Adjustable Differential type Vacuum Switch MA series
Adjustable Differential type Vacuum Switch MA seriesAdjustable Differential type Vacuum Switch MA series
Adjustable Differential type Vacuum Switch MA series
 
Technical data sheet heat exchanger BOUL
Technical data sheet heat exchanger BOULTechnical data sheet heat exchanger BOUL
Technical data sheet heat exchanger BOUL
 
UK Plus Brochure
UK Plus Brochure UK Plus Brochure
UK Plus Brochure
 
Sensor data of ultrasonic flow meter
Sensor data of ultrasonic flow meterSensor data of ultrasonic flow meter
Sensor data of ultrasonic flow meter
 
Annex 4 part 1-fdh (i) installation guide
Annex 4 part 1-fdh (i) installation guideAnnex 4 part 1-fdh (i) installation guide
Annex 4 part 1-fdh (i) installation guide
 
Electrical layout of
Electrical layout ofElectrical layout of
Electrical layout of
 
D.04 Solar Photovoltaic Systems 12 24 08
D.04 Solar Photovoltaic Systems 12 24 08D.04 Solar Photovoltaic Systems 12 24 08
D.04 Solar Photovoltaic Systems 12 24 08
 
bts3900e-install-r13c01
bts3900e-install-r13c01bts3900e-install-r13c01
bts3900e-install-r13c01
 
Ho manual
Ho manualHo manual
Ho manual
 
Telecommunication for high rise building
Telecommunication for high rise buildingTelecommunication for high rise building
Telecommunication for high rise building
 
Manual Intercom - Fibaro
Manual Intercom - FibaroManual Intercom - Fibaro
Manual Intercom - Fibaro
 

Plus de Vedard Security Alarm System Store

Plus de Vedard Security Alarm System Store (20)

linkage of gas fire extinguishing system with fire alarm
linkage of gas fire extinguishing system with fire alarmlinkage of gas fire extinguishing system with fire alarm
linkage of gas fire extinguishing system with fire alarm
 
Fire alarm and gas extinguishing system instruction
Fire alarm and gas extinguishing system instructionFire alarm and gas extinguishing system instruction
Fire alarm and gas extinguishing system instruction
 
test of gas fire extinguishing system
test of gas fire extinguishing systemtest of gas fire extinguishing system
test of gas fire extinguishing system
 
electric fire temperature detectors
electric fire temperature detectorselectric fire temperature detectors
electric fire temperature detectors
 
independent electric fire detection system
independent electric fire detection systemindependent electric fire detection system
independent electric fire detection system
 
fire alarm linkage smoke exhaust
fire alarm linkage smoke exhaustfire alarm linkage smoke exhaust
fire alarm linkage smoke exhaust
 
linkage fire alarm system parts
linkage fire alarm system partslinkage fire alarm system parts
linkage fire alarm system parts
 
addressable fire alarm system loop
addressable fire alarm system loopaddressable fire alarm system loop
addressable fire alarm system loop
 
addressable fire alarm system bus loop
addressable fire alarm system bus loopaddressable fire alarm system bus loop
addressable fire alarm system bus loop
 
fire alarm system types
fire alarm system typesfire alarm system types
fire alarm system types
 
fire alarm system fire graphic display device
fire alarm system fire graphic display devicefire alarm system fire graphic display device
fire alarm system fire graphic display device
 
overview of automatic fire-alarm systems
overview of automatic fire-alarm systemsoverview of automatic fire-alarm systems
overview of automatic fire-alarm systems
 
division of fire alarm areas
division of fire alarm areasdivision of fire alarm areas
division of fire alarm areas
 
addressable fire alarm bus short circuit isolator
addressable fire alarm bus short circuit isolatoraddressable fire alarm bus short circuit isolator
addressable fire alarm bus short circuit isolator
 
fire manual call and hydrant button
fire manual call and hydrant buttonfire manual call and hydrant button
fire manual call and hydrant button
 
addressable fire alarm system input module
addressable fire alarm system input moduleaddressable fire alarm system input module
addressable fire alarm system input module
 
carbon monoxide detection system
carbon monoxide detection systemcarbon monoxide detection system
carbon monoxide detection system
 
gas fire extinguish system
gas fire extinguish systemgas fire extinguish system
gas fire extinguish system
 
Residual current electrical fire detector
Residual current electrical fire detectorResidual current electrical fire detector
Residual current electrical fire detector
 
Linear infrared beam smoke detector
Linear infrared beam smoke detectorLinear infrared beam smoke detector
Linear infrared beam smoke detector
 

Dernier

UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 

Dernier (20)

UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 

How to install fire alarm system

  • 1. Installation method of fire alarm detectors in fire security system The installation of fire detectors and manual call points is one of the main part of the installation of fire alarm and linkage system. With the development of intelligent fire-fighting technology, there are more types of fire detectors and manual push buttons, and the installation and wiring method may be different. 1. Method for determining the installation position of fire detectors Although the fire detector type, quantity and general distribution are determined in the design drawing, the location of the fire detector should be determined according to the specific situation of the site in the construction process. When determining the installation position and direction of the fire detector, the need of the function should be first considered. In addition, aesthetics, the arrangement of surrounding lamps, air outlet and beam should also be considered. (1) The horizontal distance between the detector and the wall and beam should not be less than 0.5m, as shown in the figure below (2) There should be no shielding within 0.5m around the detector. (3) The detector should be installed near the air inlet. The horizontal distance between the detector and the air outlet of the air conditioner should not be less than 1.5m, as shown in the following figure (4) When a detector is installed on the ceiling of an inner walkway less than 3m in width, it should be installed in the center. The installation spacing of the heat detector shall not exceed 10m. The installation spacing of the smoke detector shall not exceed 15m. The distance between the detector and the wall end shall not be greater than half of the installation spacing of the detector. As shown in the following figure.
  • 2. (5) When the roof slope θ>15°, the detector shall be installed at the highest point under the gabled roof, as shown in the figure below (6) When the roof slope θ<=45°, the detector can be directly installed on the roof panel, as shown in the figure below
  • 3. (7) For serrated roof, when the roof slope θ>15°, the detectors should be installed under each sawtooth ridge, as shown in the figure below (8) When the roof slope θ>45°, the detector shall be mounted with bracket and installed horizontally, as shown in the figure below (9) The detector confirmation LED indication should face to the main entrance direction for easy observation. This is shown below
  • 4. (10) For the elevator well, pipe well, lift well, you can only install a smoke detector on the roof of the machine room above the well. For the stairwell, ramp walkway, you can install a smoke detector every 15m of the vertical distance. As shown in the following figure (11) In the large truss structure warehouse with no ceiling, the detector should be suspended and installed by pipe rack, and the droop height should be determined according to the actual needs. When using a smoke detector, a smoke hood should be added. As shown in the following figure
  • 5. (12) When the room is divided by bookshelves, equipment, etc., if the distance from the top of the divider to the ceiling or beam is less than 5% of the room's clear height, each divided part shall have at least one detector installed. 2. Method for determining the installation position of fire manual call points There shall be at least one manual alarm button for each fire partition in the alarm area. The walking distance from any location within a fire partition to an adjacent manual alarm button should not be greater than 30m. Manual fire alarm button should be set in the obvious and easy to operate position, that is, the building's safety exit, safety stairs entrance. Usually the manual alarm button and the fire alarm bell are installed next to the fire hydrant. They are installed on the wall at a height of 1.5m above the ground or floor and should be clearly marked. When installing manual alarm button, embedded junction box may needed at some situation. The manual alarm button shall be firmly installed and shall not be tilted.In order to facilitate debugging and maintenance, the external lead of manual alarm button should be left with a margin of more than 10cm, and its end should be clearly marked. 3. Installation method of fire detector The installation method of the fire detector base varies according to the installation location of the building structure. There are junction box embedded installation, installation under the ceiling and under the raised floor, etc. (1) Junction box embedded installation The installation method of the embedded box is to preset the embedded hole seat in the civil engineering process in advance, and when placing it, the wires are inserted into the junction box from the embedded wire pipe, as shown in the figure below
  • 6. Fix the detector base or detector wiring block on the junction box, and connect the power line or signal line from the box to the corresponding junction post on the detector base (or weld to the corresponding patch on the base). Connection points should be firm and reliable. The junction box shall be insulated between the base to ensure good insulation between the two. After the installation and wiring of the base is finished, it should be checked carefully. No wrong connection, short circuit or virtual welding are allowed. As shown in the following figure After the installation of detector base is completed, do not remove the detector protection cover. Until the system debugging stage, the protection cover is removed. The installation and assembly of the detector is shown in the figure below. When the detector is installed, the confirmation indicator on the outer cover should be pointed in the direction of the main entrance and exit for personnel to observe.
  • 7. (2) Installation under the ceiling In many cases, the detector is installed under the ceiling. There are two main cases according to the structure of the building. One is to install the detector directly on the junction box inside the ceiling, as shown in FIG. 6-15.The other is to install the detector on the keel and connect it to the junction box in the ceiling through the metal hose, as shown in figure 6-16. When the detector is installed under the roof, there are two ways to thread the pipeline, one is the dark piping, as shown in FIG. 6-17. Another way is open piping method, as shown in FIG. 6-18.
  • 8. (3) Installation under raised floor Some fire alarm detectors need to be installed under a raised floor.The detector can be installed by special junction box or standard junction box. If necessary, the installation hole spacing can be adjusted by adding adjustment board.As shown in the following figure Wiring and Layout 1. Method of terminal connection The fire alarm system generally adopts copper core cable or wire. The single-core copper wire after stripping off the insulation layer can be directly connected to the terminal block. The length of the insulation layer stripped off is generally 1mm longer than the length inserted into the terminal block. For multi-core copper wire, the insulation layer should be stripped off first, lined with tin and then connected to the terminal block. If the wire and cable are to be connected under the screw head, the single copper wire should be bent in the shape shown in FIG. 6-20. The direction should be same as the screw is screwed in. For multi-core copper wires, the terminals shall be pressed and the pressed joint shall be welded with solder. The terminal should be in line with the wire diameter. The cables or wires connected to the alarm controller shall meet the following requirements:
  • 9. (1) The wiring should be neat, clear, beautiful, avoid crossing, and should be fixed firmly, terminal plate should not bear external mechanical stress. (2) The cable core and the end of the cable shall be numbered. (3) No more than two wires shall be connected to each terminal of the terminal board. (4) The cable core and conductor shall have a buffer of not less than 200mm. (5) The wires should be put into plastic grooves or tied into bundles. (6) After the wire is threaded, the inlet pipe should be blocked. (7) The power supply wire of the alarm controller shall be directly connected to the fire protection power supply. Do not use the power plug.The power supply shall be clearly marked. (8) The controller shall be firmly grounded and clearly marked. The wiring terminal is equipped with a label plate, which is used to distinguish various wiring and terminal labels, so as to facilitate maintenance and inspection. Figure 6-21 is the package label. The label must be printed and fitted on the wire before the wire is connected to the terminal. If there is no plastic casing marking machine, you can also use carbon ink with an appropriate amount of dichloroethane and gentian violet to write to prevent fading. 2. Method of wiring in the box The detector, manual alarm button, sound device, door light and alarm bell have been wired up while being installed. And a large number of cables and wires are summarized in the box (cabinet) of the regional alarm controller and central alarm. According to the position of the wiring terminals and the distribution of components in the box (cabinet), the reasonable wiring line in the box (cabinet) shall be determined, and the line shall be drawn with a ruler. Cables and wires are laid in the alarm control box, including plastic wire groove fixing method, plastic spiral tube fixing method and binding method. The toothed plastic line groove (line groove) is shown in FIG. 6-22. The line groove should be fixed along the bottom plate or side of the box.The wire can be laid in the line groove, and the wire can be drawn out from the perforation and connected to the terminal. If there are too many lead wires and not available to layout, you can remove one or two teeth. After laying, the groove cover shall be well covered.
  • 10. The fixation method of plastic spiral tube is shown in FIG. 6-23. Arrange the wires neatly in the box and lay the wires horizontally or vertically. After the wires are laid, open the plastic spiral tube and wrap it around the wires. Tie the wires into a bundle by virtue of the elasticity of the plastic spiral tube. The cable wiring harness laid in the box can also be fastened with the binding belt made of insulating material, and the spacing of the binding belt should be 100mm.The bending radius of the wire should not be less than 3 times of its outer diameter, there should be no middle head in the alarm control box, and the insulation sheath should not be damaged.The tying method of cables and wires laid in the box is shown in FIG. 6-24.
  • 11. 3. Wiring method of shielding layer Shielded cables are used as transmission lines in some fire alarm and linkage systems to improve the anti-interference ability of the system. The wiring of the shielding layer shall follow the schematic diagram of the fire alarm system. Most use the shield layer as the ground line. In the alarm control box, all the shielded wires are welded with terminal and connected to the wiring terminal row. However, in some systems, the shield layer plays a certain role in signal transmission, it can not be grounded. Such a system, the plastic hose should be added to the shield layer after stripping before connection and the shield layer is forbidden to be grounded. The wiring of shielding layer must be firm and reliable. When stripping the insulation layer, the shielding layer should not be damaged. The quality of shielding treatment will directly affect the transmission quality. 4. The function and working mode of manual alarm button. Manual alarm button is one of the necessary equipment in fire alarm and linkage system. It has the function of confirming the fire or sending out the fire signal manually.When people find the fire, they can make manual alarm through the manual alarm button installed in the corridor, stairs, etc. Manual alarm button is the key installed in the metal box, the metal box is generally embedded in the wall, exposed red border of the protective cover. After manually confirming the fire, knock out the protective cover and press the button. At this time, on the one hand, the alarm equipment on the scene (such as fire alarm siren strobe, fire alarm bell) alarms. On the other hand, the manual signal is sent to the area alarm to send out the fire alarm. Like the detector, the manual alarm button also has a point in the system. Some alarm buttons also have the function of action indication, receiving feedback signal and so on. Alarm emergency degree triggered by manual alarm button is higher than that triggered by a detector and alarm triggered by manual alarm button does not need confirmation. So manual buttons require more reliability, more certainty, and the alarm triggered needs faster dealing. The manual alarm button should be connected with the central alarm and occupy a point number separately. Because the centralized alarm controller is placed in the fire security guard room, it can take measures more quickly. So if there is no centralized alarm, and the manual alarm button is
  • 12. connected to the area alarm panel, it should occupy a point number. The installation of combustible gas sensor The installation height of combustible gas detector shall be determined according to the type and density of the detected gas. For gases’ density heavier than air, such as liquefied petroleum gas, the detector shall be installed 10cm above the ground, and for gases' density lighter than air, such as urban artificial gas and natural gas, the detector shall be installed within 30cm from the ceiling.As shown in the following figure. When the beam height is greater than 0.6m, the combustible gas detector should be installed on the side with the gas cooker, as shown in the figure below
  • 13. The combustible gas detector shall be installed under the roof within 8m from the gas stove as shown in the figure below Installation of infrared beam smoke detector The transmitter and receiver of the infrared beam smoke detector should be installed opposite to each other at both ends of the protection space and on the same horizontal line. The vertical distance between the beam axis of the infrared beam smoke detector and the ceiling should be 0.3~1.0m, and the distance from the ground should not exceed 20m. The horizontal distance between two adjacent infrared beam smoke detectors should not be greater than 14m.The horizontal distance between the detector and the side wall shall not be greater than 7m and shall not be less than 0.5m. The distance between the transmitter and receiver of the detector should not exceed 100m. When the height of the room is 8-14m, besides the beam smoke detector installed under the ceiling, the beam smoke detector should also be installed at 1/2 of the height of the room. When the room height is 14-20m, the detector should be set in three layers. (under the ceiling, at 1/3 of the room height, at 2/3 of the room height) The working principle of infrared beam smoke detector is shown in the following figure. The installation position of infrared beam smoke detector should be far away from the strong
  • 14. magnetic field, without direct sunlight, and no dust retention in the detector using environment. There should not have fixed and flowing obstacle between the transmitter and receiver of the detector. The base of the detector must be firmly installed and will not come loose. The installation method of the detector in the ceiling is shown in FIG. 6-30, and the installation method in the wall is shown in FIG. 6-31. Installation of cable sensor When the cable type linear constant heat detector is installed on the cable bridge or bracket, contact arrangement should be adopted. When setting up on various belt conveying devices, it is advised to set up near the hot spot of the device. When the air tube type linear rate-of-rise temperature detector is installed under the ceiling, it should be installed 0.1m from the ceiling. The horizontal distance between adjacent pipelines should not be greater than 5m. The distance between the pipeline and the wall should be 1-1.5m. The installation of cable fixed temperature detector in cable tunnel and cable trench with single side support is shown in FIG. 6-32