Contactor & Relay Issues

∙   Field Failures & Customer Complaints
∙   Cost and Improvement
∙   Agencies and Standards
∙   Magnetic Circuit
∙   Coil Design and Issues
∙   Contacts



                            By Mike O’Dell




                                             10/16/2011
Customer Complaints and Field
Failures – in Order of Commonality

∙   Burned contacts
∙   Burned coils
∙   Open coils
∙   Stripped Screws/terminal threads or loose connection
∙   Noise
∙   Loose/misaligned springs
Field Failures
Causes:
Burned Contacts
∙   Mismatch between device current/voltage ratings and load
∙   Low voltage at the coil causing chattering and excessive arcing of contacts
∙   Bad riveting of contacts to carrier
∙   Environmental causes (temperature, humidity, minerals)


Severity of Failure
∙ Arcing may propagate and create further
  damage and fire
∙ Costly to replace in field installed equipment
∙ Critical systems would require backup or
  redundant system
Field Failures Causes:
 Burned Coils
 ∙   Low voltage to the coil – below contactor
     pickup volts
 ∙   High voltage to the coil – exceeding coil
     rating
 ∙   Many nicked wire turns – insulation
     removed causing shorts
 ∙   Environmental causes

 Severity of Failure
 ∙ Burned coils release toxic gases and may potentially contribute to a fire
 ∙ Costly to replace in field installed equipment
 ∙ Critical systems would require backup or redundant system
Field Failures Causes:
 Open Coils
 ∙   Reliability issue with magnet wire termination – bad solder or crimp joint
 ∙   Voltage surge causing terminations to break
 ∙   Coil opens at another location such as outer winding due to previous
     damage
 ∙   Environmental causes



 Severity of Failure
 ∙   Failure to operate may be intermittent depending on nature of break
 ∙   Open coils are not normally a safety problem for the equipment
 ∙   Costly to replace in field installed equipment
 ∙   Critical systems would require backup or redundant system
Field Failures Causes:

 Stripped Screws – Customer Connections
 ∙   Threads not per specification
 ∙   Screws not started correctly
 ∙   Excessive tightening torque
 ∙   Environmental causes (corrosion)


 Severity of Failure
 ∙ Customer connection may not be secure. Potential fire hazard.
 ∙ Costly to replace in field installed equipment
High Cost Components and Processes
in Contractors and Relays


 Silver Contacts


 ∙   Expensive silver alloys formulated and sized for required electrical life.
 ∙   Silver Oxide has low resistance
 ∙   Good mechanical strength and wear resistance
 ∙   Can be brazed or riveted to contact carrier
 ∙   Arc quenching parts/materials are added when needed
High Cost Components and
Processes
in Contractors and Relays
Coils


∙   Mass of copper magnet wire – specific gages for different voltages.
∙   Stamped and formed terminals to meet customer connection requirements.
    Brass terminals typically tin-plated for soldering.
∙   Termination process costly – special tooling for strip/crimp or materials/labor
    for solder termination.
∙   Bobbin molds, material and time to mold add cost.
∙   Overmolds, housings, varnish, sealants
High Cost Components and
Processes
in Contractors and Relays
Contactor / Relay
Magnets

∙   Special alloy core-plated steel selected for specific application.
    Few steel mills produce this type of steel. Typically soft iron
    material that is magnetized when magnetic field created.
∙   Magnets used with AC coils are comprised of thin laminated
    sheets which limit the eddy current and heat.
∙   DC coil may use solid steel due to one way current – no eddy
    current
High Cost Components and
Processes
in Contractors and Relays
Contactor / Relay
Magnets


•   Stamping, assembly and finishing magnet (grinding) is costly.
•   Often have copper/aluminum shading rings for AC.
High Cost Components and
Processes
in Contractors and Relays
    Plastic




∙   Special insulative and track/arc resistive molding compound for
    contact boards and cross-arms.
∙   Molds and material are expensive and time to mold is costly.
High Cost Components and
Processes
in Contractors and Relays
Contact Carrier
Brass or copper, stamped, formed, plated, drilled and tapped



Springs

Labor cost to assemble
Desire Design Changes to Reduce
Cost and Maintain or Increase
Reliability
∙   Reduce or eliminate silver contacts – eliminate Cd
∙   Reduce coil size or eliminate coil completely
∙   Eliminate or reduce coil inrush current
∙   Reduce, reconfigure or eliminate the magnet/armature
    assembly
∙   Reduce housing size
∙   Less mechanical motion – fewer/smaller springs
∙   Survive non-standard voltages to coil
∙   Maintain or improve resistance to environmental issues
Contactor Cutaway

            LINE
                   L1   L2

      CONTROL
       CIRCUIT




                   T1   T2

                             LOAD
Alternate Solutions Currently
Available-list Advantages
∙   Solid State (MOSFET) and Semiconductor (Thyristor) Relays and
    Contactors – issues with heat, leakage and transients
∙   Latching relay – reduces coil size/no hum. Used often for lighting
    control.
Customer & Design Requirements Which
May Limit Design Improvements
 ∙   Grandfathered materials/ratings in UL 508, IEC 60947 or other
     relevant standard such as ARI 780/790
 ∙   Compatibility of field replacement with existing products
 ∙   Coil (control voltage) ratings
 ∙   Customer/end user mounting requirements
 ∙   Number of poles and contact arrangement required in applications.
 ∙   Auxiliary contact requirements
 ∙   Labeling
 ∙   RoHS and REACH
 ∙   Specific Engineering Test Requirements not covered in the
     Standards
Agency Standards

UL 508 – Standard of Safety for Industrial Control Equipment
∙   Intended for control and accessory devices for starting, stopping, regulating, controlling or
    protecting electric motors.
∙   Requirements for construction, electrical clearances, insulation, grounding, marking, wiring.
∙   Overload, endurance, dielectric withstand, short circuit, over &under voltage and temperature are
    important tests.

IEC 60947 (part 4 for contactors)-similar to UL508 with exception of IEC ratings

ARI 780/790-97 – inactive standard intended for Definite Purpose contactors (used in air conditioning
    equipment). OEM’s request testing to the requirements of this standard – the electrical and
    mechanical life test minimums and temperature rise requirements are more stringent than UL 508.

Other standards as applicable to specific product.
Magnetic Flux in Contactor Magnets
                  A SMALL GAP IS LEFT TO BREAK THE MAGNETIC
                  FIELD AND ALLOW ARMATURE TO DROP AWAY
                  FREELY AFTER COIL IS DE-ENERGIZED




                             ARMATURE




   SHADING COIL
                                MAGNET
Magnetic Flux in Contactor Magnets
AC Contactor Coils - Terms

∙   Inrush current – current during the first few cycles of coil energization – before
    the armature closes onto the magnet. Inrush can be simulated by holding the
    armature in position.
∙   Sealed current – Current when armature is pulled in completely at coil rated
    voltage.
∙   Inrush current is much large than sealed current. Magnetic circuit when sealed
    increases impedance in coil circuit thereby reducing current.
∙   Pickup voltage – minimum control voltage which will cause the armature to start
    to move
∙   Seal in voltage – minimum control voltage required to cause the armature to seat
    against the pole faces of the magnet
∙   Drop out voltage – exists when the voltage is reduced to allow the contactor to
    open
AC Contactor Coils - Issues
 ∙   Low voltage – produces low currents and low magnetic pull. When the
     voltage is greater than the pick up voltage and less than the seal voltage
     the contactor may pick up but will not seal. As the coil is not designed to
     carry the greater current continuously, it will get hot and will either be
     damaged or burn out. The armature will chatter – creating noise and
     wearing magnetic pole faces.
 ∙   High voltage – Drawing higher than rated current will cause damage and
     possible failure. The excessive force of the armature closing will wear the
     pole faces prematurely.
 ∙   AC Hum – due to changing magnetic field, inducing mechanical vibration.
     Excessive noise can be caused by: broken shading coil, low voltage to coil,
     wrong coil, misalignment between magnet and armature.
Coil Design – Magnetic Wire

Magnet Wire

∙   Copper & Aluminum wire
∙   Round, Rectangular or Square X-Section
∙   Ratings from 105C to 220C
∙   Many insulation materials ranging from Polyvinyl (105) to Aromatic
    Polyamide (220)
∙   Insulation thickness can vary
∙   Wire gages from 4/0 to 46 AWG
Coil
Design
Windings
∙   Precision wound – turns are laid side by side & wire traverses
    from one end of the bobbin to the other and back again during
    winding. Reduces voltage gradient with the coils and prevent
    accidental shorts. Winding thickness consistent




∙ Random wound – Wire traverses back and forth across the bobbin
  but consecutive turns are not always adjacent. Winding thickness
  varies. Packs more copper in smaller space due to tighter nesting.
  Less costly because of higher winding speed.
Coil Design
∙   Coils can be encapsulated, over molded, varnished
∙   AC coils must withstand inrush current until the contactor closes
∙   Volts/turn useful parameter to help select wire gage and number of
    turns based on limits of bobbin design
∙   I²R heating, surface area and wire insulation affect wire size
    selection
∙   Various coil voltages are used in the same coil/contactor family
∙   UL listed insulation systems often required for contactors in N.A.
DC Coil Design
∙   Very common today at low voltage <12 volts. Design become costly at
    higher voltages.
∙   Depends on magnet/armature design – ideally a DC coil will have a solid
    magnet/armature (not always the case due to product extensions).
∙   DC coil needs high resistance due to lack of inductance in magnet circuit –
    thinner magnet wire than equivalent AC coil.
∙   Higher numbers of amp-turns are needed than in AC coils due to lower
    current.
∙   Diodes often used to reduce DC spike during de-energization of coil
Design Methods – DC Coils
∙   “True” DC coil
∙   One large (tall) single winding to absorb/dissipate heat.
∙   Two winding DC coil
∙   One “pickup” winding to absorb inrush current.
∙   One “hold” winding capable of lower power after contactor closes.
∙   Late break auxiliary contact removes pickup winding from circuit during
    contact closure.
∙   Electronic DC coil
∙   Primarily 24VDC product
Controlling Arcing
∙   Arcing phenomena varies with electrode/contact material and contamination
∙   To breakdown a large air gap a minimum of 320V is needed
∙   Very small gaps will generate an arc with an intense electric field
∙   Minimum voltage to sustain an arc in air with small gaps is around 12 volts
    for most contact materials (less for Gold)


Above the minimum arc voltage:
∙ Properly designed and operating device some
  arcing when contacts come together and
  more arcing at contact separation
∙ DC arc can be sustained at gaps roughly
  proportional to voltage – 10 to 20 V/cm.
AC Contacts

AC arc suppression
∙ Arcing occurs at greater than 12VAC and is greatest when opening contacts
∙ AC may have several sets of contacts to make/break all legs
∙ Self extinguishing due to current crossing zero.
∙ Anode/Cathode side is random – movable and stationary contacts erode at
  equal rates
∙ Higher currents and voltage require additional means to quench the arc after
  the first half cycle
DC Contacts

DC arc suppression
∙   DC requires only one set of contacts per device
∙   Rapid opening of contacts with enough air gap is necessary to break arc
∙   Arc splitters commonly used with low voltage contactors
∙   Rapid closing may cause contact bounce and accelerated erosion
∙   Current flows in one direction and one contact will be anode and the other
    will be cathode

Contenu connexe

Tendances

cricuit breaker report
cricuit breaker reportcricuit breaker report
cricuit breaker report
Ankit Vij
 
P-rex presentation (to send out)
P-rex presentation (to send out)P-rex presentation (to send out)
P-rex presentation (to send out)
mitchconquer
 
Electrical Accessories
Electrical AccessoriesElectrical Accessories
Electrical Accessories
Noman Khan
 

Tendances (20)

Electrical services
Electrical servicesElectrical services
Electrical services
 
cricuit breaker report
cricuit breaker reportcricuit breaker report
cricuit breaker report
 
Elesa Slideshow ENG
Elesa Slideshow ENGElesa Slideshow ENG
Elesa Slideshow ENG
 
air type circuit breaker
air type circuit breakerair type circuit breaker
air type circuit breaker
 
Eat 105 Chapter 3
Eat 105  Chapter 3Eat 105  Chapter 3
Eat 105 Chapter 3
 
P-rex presentation (to send out)
P-rex presentation (to send out)P-rex presentation (to send out)
P-rex presentation (to send out)
 
MRR improvement in electrical discharge machining
MRR improvement in electrical discharge machiningMRR improvement in electrical discharge machining
MRR improvement in electrical discharge machining
 
Projoy DC Isolator and DC Switch Product profolios
Projoy DC Isolator and DC Switch Product profoliosProjoy DC Isolator and DC Switch Product profolios
Projoy DC Isolator and DC Switch Product profolios
 
SMT Poke-In Lighting Connector
SMT Poke-In Lighting ConnectorSMT Poke-In Lighting Connector
SMT Poke-In Lighting Connector
 
Instalaciones avionicas
Instalaciones avionicasInstalaciones avionicas
Instalaciones avionicas
 
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...
 
Electrical Installation PPT (Basic Electrical Engineering)
Electrical Installation PPT (Basic Electrical Engineering)Electrical Installation PPT (Basic Electrical Engineering)
Electrical Installation PPT (Basic Electrical Engineering)
 
Choosing Electrical Panels
Choosing Electrical PanelsChoosing Electrical Panels
Choosing Electrical Panels
 
Electrical Accessories
Electrical AccessoriesElectrical Accessories
Electrical Accessories
 
System of wiring
System of wiringSystem of wiring
System of wiring
 
SMAW
SMAWSMAW
SMAW
 
Earth Bonding Leads - Copper
Earth Bonding Leads - CopperEarth Bonding Leads - Copper
Earth Bonding Leads - Copper
 
Wiring System and Working Principle of Fluorescence Tube
 Wiring System and Working Principle of Fluorescence Tube Wiring System and Working Principle of Fluorescence Tube
Wiring System and Working Principle of Fluorescence Tube
 
Sonobond Ultrasonics Battery Assembly
Sonobond Ultrasonics Battery AssemblySonobond Ultrasonics Battery Assembly
Sonobond Ultrasonics Battery Assembly
 
RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) |AKBAR TRADING EST. SAUDI ARABIA...
RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) |AKBAR TRADING EST. SAUDI ARABIA...RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) |AKBAR TRADING EST. SAUDI ARABIA...
RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) |AKBAR TRADING EST. SAUDI ARABIA...
 

En vedette

Parts of the computer (mouse and printer)
Parts of the computer (mouse and printer)Parts of the computer (mouse and printer)
Parts of the computer (mouse and printer)
Mi L
 
14+synchronous+motors
14+synchronous+motors14+synchronous+motors
14+synchronous+motors
huseyin28
 

En vedette (20)

Contactors
ContactorsContactors
Contactors
 
Presentation 12 contactors-handouts
Presentation 12  contactors-handoutsPresentation 12  contactors-handouts
Presentation 12 contactors-handouts
 
Contactors and Thermal Overload Relays - FJ Series - Fuji Electric
Contactors and Thermal Overload Relays - FJ Series - Fuji ElectricContactors and Thermal Overload Relays - FJ Series - Fuji Electric
Contactors and Thermal Overload Relays - FJ Series - Fuji Electric
 
Membrane contactors
Membrane contactorsMembrane contactors
Membrane contactors
 
Output devices
Output devicesOutput devices
Output devices
 
Control system
Control systemControl system
Control system
 
Handtools
HandtoolsHandtools
Handtools
 
OUTPUT DEVICES
OUTPUT DEVICESOUTPUT DEVICES
OUTPUT DEVICES
 
Parts of computer, keyboarding, mouse
Parts of computer, keyboarding, mouseParts of computer, keyboarding, mouse
Parts of computer, keyboarding, mouse
 
Mini-Contactors and Thermal Overload Relays - SK Series
Mini-Contactors and Thermal Overload Relays - SK SeriesMini-Contactors and Thermal Overload Relays - SK Series
Mini-Contactors and Thermal Overload Relays - SK Series
 
218001 control system technology lecture 1
218001 control system technology   lecture 1218001 control system technology   lecture 1
218001 control system technology lecture 1
 
8254 Programmable Interval Timer by vijay
8254 Programmable Interval Timer by vijay8254 Programmable Interval Timer by vijay
8254 Programmable Interval Timer by vijay
 
Output devices
Output devicesOutput devices
Output devices
 
Shift register
Shift registerShift register
Shift register
 
Parts of the computer (mouse and printer)
Parts of the computer (mouse and printer)Parts of the computer (mouse and printer)
Parts of the computer (mouse and printer)
 
Presentation on mouse, keyboard and scanners
Presentation on mouse, keyboard and scannersPresentation on mouse, keyboard and scanners
Presentation on mouse, keyboard and scanners
 
Synchronous motors
Synchronous motorsSynchronous motors
Synchronous motors
 
14+synchronous+motors
14+synchronous+motors14+synchronous+motors
14+synchronous+motors
 
555 timer ppt by vishnu
555 timer ppt by vishnu555 timer ppt by vishnu
555 timer ppt by vishnu
 
Synchronous motor
Synchronous motorSynchronous motor
Synchronous motor
 

Similaire à Contactor generalizations

ME 12A8 - WELDING TECHNOLOGY for industries.pptx
ME 12A8 - WELDING TECHNOLOGY for industries.pptxME 12A8 - WELDING TECHNOLOGY for industries.pptx
ME 12A8 - WELDING TECHNOLOGY for industries.pptx
RamasamyN4
 
Understanding overcurrent protection
Understanding overcurrent protectionUnderstanding overcurrent protection
Understanding overcurrent protection
michaeljmack
 

Similaire à Contactor generalizations (20)

Contactor generalizations
Contactor generalizationsContactor generalizations
Contactor generalizations
 
Contactor generalizations
Contactor generalizationsContactor generalizations
Contactor generalizations
 
Contactor Generalizations
Contactor GeneralizationsContactor Generalizations
Contactor Generalizations
 
ME 12A8 - WELDING TECHNOLOGY for industries.pptx
ME 12A8 - WELDING TECHNOLOGY for industries.pptxME 12A8 - WELDING TECHNOLOGY for industries.pptx
ME 12A8 - WELDING TECHNOLOGY for industries.pptx
 
Arc welding types( carbon,TIG &MIG )
Arc welding types( carbon,TIG &MIG )Arc welding types( carbon,TIG &MIG )
Arc welding types( carbon,TIG &MIG )
 
Design_of_Power_Transformers.ppt
Design_of_Power_Transformers.pptDesign_of_Power_Transformers.ppt
Design_of_Power_Transformers.ppt
 
Welding of non ferrous alloys
Welding of non ferrous alloysWelding of non ferrous alloys
Welding of non ferrous alloys
 
Understanding overcurrent protection
Understanding overcurrent protectionUnderstanding overcurrent protection
Understanding overcurrent protection
 
THERMAL AND ELECTRICAL BASED PROCESSES
THERMAL AND ELECTRICAL BASED PROCESSESTHERMAL AND ELECTRICAL BASED PROCESSES
THERMAL AND ELECTRICAL BASED PROCESSES
 
Electrical fundamental course
Electrical fundamental courseElectrical fundamental course
Electrical fundamental course
 
UNIT 2.pptx
UNIT 2.pptxUNIT 2.pptx
UNIT 2.pptx
 
Unit 2
Unit 2Unit 2
Unit 2
 
Unit 2
Unit 2Unit 2
Unit 2
 
UNIT 2 THERMAL AND ELECTRICAL ENERGY BASED PROCESSES.pptx
UNIT 2 THERMAL AND ELECTRICAL  ENERGY  BASED  PROCESSES.pptxUNIT 2 THERMAL AND ELECTRICAL  ENERGY  BASED  PROCESSES.pptx
UNIT 2 THERMAL AND ELECTRICAL ENERGY BASED PROCESSES.pptx
 
Recognizing and Eliminating Flux Concentrator Failures
Recognizing and Eliminating Flux Concentrator FailuresRecognizing and Eliminating Flux Concentrator Failures
Recognizing and Eliminating Flux Concentrator Failures
 
Electrical fundamental course
Electrical fundamental courseElectrical fundamental course
Electrical fundamental course
 
Jmv Presentation Airport and JMV LPS LTD
Jmv Presentation Airport and JMV LPS LTDJmv Presentation Airport and JMV LPS LTD
Jmv Presentation Airport and JMV LPS LTD
 
Transformer Designing
Transformer Designing Transformer Designing
Transformer Designing
 
ELECTRICAL INSTALLATIONS PPT (1).pptx
ELECTRICAL INSTALLATIONS PPT (1).pptxELECTRICAL INSTALLATIONS PPT (1).pptx
ELECTRICAL INSTALLATIONS PPT (1).pptx
 
Gas Metal Arc Welding
Gas Metal Arc WeldingGas Metal Arc Welding
Gas Metal Arc Welding
 

Contactor generalizations

  • 1. Contactor & Relay Issues ∙ Field Failures & Customer Complaints ∙ Cost and Improvement ∙ Agencies and Standards ∙ Magnetic Circuit ∙ Coil Design and Issues ∙ Contacts By Mike O’Dell 10/16/2011
  • 2. Customer Complaints and Field Failures – in Order of Commonality ∙ Burned contacts ∙ Burned coils ∙ Open coils ∙ Stripped Screws/terminal threads or loose connection ∙ Noise ∙ Loose/misaligned springs
  • 3. Field Failures Causes: Burned Contacts ∙ Mismatch between device current/voltage ratings and load ∙ Low voltage at the coil causing chattering and excessive arcing of contacts ∙ Bad riveting of contacts to carrier ∙ Environmental causes (temperature, humidity, minerals) Severity of Failure ∙ Arcing may propagate and create further damage and fire ∙ Costly to replace in field installed equipment ∙ Critical systems would require backup or redundant system
  • 4. Field Failures Causes: Burned Coils ∙ Low voltage to the coil – below contactor pickup volts ∙ High voltage to the coil – exceeding coil rating ∙ Many nicked wire turns – insulation removed causing shorts ∙ Environmental causes Severity of Failure ∙ Burned coils release toxic gases and may potentially contribute to a fire ∙ Costly to replace in field installed equipment ∙ Critical systems would require backup or redundant system
  • 5. Field Failures Causes: Open Coils ∙ Reliability issue with magnet wire termination – bad solder or crimp joint ∙ Voltage surge causing terminations to break ∙ Coil opens at another location such as outer winding due to previous damage ∙ Environmental causes Severity of Failure ∙ Failure to operate may be intermittent depending on nature of break ∙ Open coils are not normally a safety problem for the equipment ∙ Costly to replace in field installed equipment ∙ Critical systems would require backup or redundant system
  • 6. Field Failures Causes: Stripped Screws – Customer Connections ∙ Threads not per specification ∙ Screws not started correctly ∙ Excessive tightening torque ∙ Environmental causes (corrosion) Severity of Failure ∙ Customer connection may not be secure. Potential fire hazard. ∙ Costly to replace in field installed equipment
  • 7. High Cost Components and Processes in Contractors and Relays Silver Contacts ∙ Expensive silver alloys formulated and sized for required electrical life. ∙ Silver Oxide has low resistance ∙ Good mechanical strength and wear resistance ∙ Can be brazed or riveted to contact carrier ∙ Arc quenching parts/materials are added when needed
  • 8. High Cost Components and Processes in Contractors and Relays Coils ∙ Mass of copper magnet wire – specific gages for different voltages. ∙ Stamped and formed terminals to meet customer connection requirements. Brass terminals typically tin-plated for soldering. ∙ Termination process costly – special tooling for strip/crimp or materials/labor for solder termination. ∙ Bobbin molds, material and time to mold add cost. ∙ Overmolds, housings, varnish, sealants
  • 9. High Cost Components and Processes in Contractors and Relays Contactor / Relay Magnets ∙ Special alloy core-plated steel selected for specific application. Few steel mills produce this type of steel. Typically soft iron material that is magnetized when magnetic field created. ∙ Magnets used with AC coils are comprised of thin laminated sheets which limit the eddy current and heat. ∙ DC coil may use solid steel due to one way current – no eddy current
  • 10. High Cost Components and Processes in Contractors and Relays Contactor / Relay Magnets • Stamping, assembly and finishing magnet (grinding) is costly. • Often have copper/aluminum shading rings for AC.
  • 11. High Cost Components and Processes in Contractors and Relays Plastic ∙ Special insulative and track/arc resistive molding compound for contact boards and cross-arms. ∙ Molds and material are expensive and time to mold is costly.
  • 12. High Cost Components and Processes in Contractors and Relays Contact Carrier Brass or copper, stamped, formed, plated, drilled and tapped Springs Labor cost to assemble
  • 13. Desire Design Changes to Reduce Cost and Maintain or Increase Reliability ∙ Reduce or eliminate silver contacts – eliminate Cd ∙ Reduce coil size or eliminate coil completely ∙ Eliminate or reduce coil inrush current ∙ Reduce, reconfigure or eliminate the magnet/armature assembly ∙ Reduce housing size ∙ Less mechanical motion – fewer/smaller springs ∙ Survive non-standard voltages to coil ∙ Maintain or improve resistance to environmental issues
  • 14. Contactor Cutaway LINE L1 L2 CONTROL CIRCUIT T1 T2 LOAD
  • 15. Alternate Solutions Currently Available-list Advantages ∙ Solid State (MOSFET) and Semiconductor (Thyristor) Relays and Contactors – issues with heat, leakage and transients ∙ Latching relay – reduces coil size/no hum. Used often for lighting control.
  • 16. Customer & Design Requirements Which May Limit Design Improvements ∙ Grandfathered materials/ratings in UL 508, IEC 60947 or other relevant standard such as ARI 780/790 ∙ Compatibility of field replacement with existing products ∙ Coil (control voltage) ratings ∙ Customer/end user mounting requirements ∙ Number of poles and contact arrangement required in applications. ∙ Auxiliary contact requirements ∙ Labeling ∙ RoHS and REACH ∙ Specific Engineering Test Requirements not covered in the Standards
  • 17. Agency Standards UL 508 – Standard of Safety for Industrial Control Equipment ∙ Intended for control and accessory devices for starting, stopping, regulating, controlling or protecting electric motors. ∙ Requirements for construction, electrical clearances, insulation, grounding, marking, wiring. ∙ Overload, endurance, dielectric withstand, short circuit, over &under voltage and temperature are important tests. IEC 60947 (part 4 for contactors)-similar to UL508 with exception of IEC ratings ARI 780/790-97 – inactive standard intended for Definite Purpose contactors (used in air conditioning equipment). OEM’s request testing to the requirements of this standard – the electrical and mechanical life test minimums and temperature rise requirements are more stringent than UL 508. Other standards as applicable to specific product.
  • 18. Magnetic Flux in Contactor Magnets A SMALL GAP IS LEFT TO BREAK THE MAGNETIC FIELD AND ALLOW ARMATURE TO DROP AWAY FREELY AFTER COIL IS DE-ENERGIZED ARMATURE SHADING COIL MAGNET
  • 19. Magnetic Flux in Contactor Magnets
  • 20. AC Contactor Coils - Terms ∙ Inrush current – current during the first few cycles of coil energization – before the armature closes onto the magnet. Inrush can be simulated by holding the armature in position. ∙ Sealed current – Current when armature is pulled in completely at coil rated voltage. ∙ Inrush current is much large than sealed current. Magnetic circuit when sealed increases impedance in coil circuit thereby reducing current. ∙ Pickup voltage – minimum control voltage which will cause the armature to start to move ∙ Seal in voltage – minimum control voltage required to cause the armature to seat against the pole faces of the magnet ∙ Drop out voltage – exists when the voltage is reduced to allow the contactor to open
  • 21. AC Contactor Coils - Issues ∙ Low voltage – produces low currents and low magnetic pull. When the voltage is greater than the pick up voltage and less than the seal voltage the contactor may pick up but will not seal. As the coil is not designed to carry the greater current continuously, it will get hot and will either be damaged or burn out. The armature will chatter – creating noise and wearing magnetic pole faces. ∙ High voltage – Drawing higher than rated current will cause damage and possible failure. The excessive force of the armature closing will wear the pole faces prematurely. ∙ AC Hum – due to changing magnetic field, inducing mechanical vibration. Excessive noise can be caused by: broken shading coil, low voltage to coil, wrong coil, misalignment between magnet and armature.
  • 22. Coil Design – Magnetic Wire Magnet Wire ∙ Copper & Aluminum wire ∙ Round, Rectangular or Square X-Section ∙ Ratings from 105C to 220C ∙ Many insulation materials ranging from Polyvinyl (105) to Aromatic Polyamide (220) ∙ Insulation thickness can vary ∙ Wire gages from 4/0 to 46 AWG
  • 23. Coil Design Windings ∙ Precision wound – turns are laid side by side & wire traverses from one end of the bobbin to the other and back again during winding. Reduces voltage gradient with the coils and prevent accidental shorts. Winding thickness consistent ∙ Random wound – Wire traverses back and forth across the bobbin but consecutive turns are not always adjacent. Winding thickness varies. Packs more copper in smaller space due to tighter nesting. Less costly because of higher winding speed.
  • 24. Coil Design ∙ Coils can be encapsulated, over molded, varnished ∙ AC coils must withstand inrush current until the contactor closes ∙ Volts/turn useful parameter to help select wire gage and number of turns based on limits of bobbin design ∙ I²R heating, surface area and wire insulation affect wire size selection ∙ Various coil voltages are used in the same coil/contactor family ∙ UL listed insulation systems often required for contactors in N.A.
  • 25. DC Coil Design ∙ Very common today at low voltage <12 volts. Design become costly at higher voltages. ∙ Depends on magnet/armature design – ideally a DC coil will have a solid magnet/armature (not always the case due to product extensions). ∙ DC coil needs high resistance due to lack of inductance in magnet circuit – thinner magnet wire than equivalent AC coil. ∙ Higher numbers of amp-turns are needed than in AC coils due to lower current. ∙ Diodes often used to reduce DC spike during de-energization of coil
  • 26. Design Methods – DC Coils ∙ “True” DC coil ∙ One large (tall) single winding to absorb/dissipate heat. ∙ Two winding DC coil ∙ One “pickup” winding to absorb inrush current. ∙ One “hold” winding capable of lower power after contactor closes. ∙ Late break auxiliary contact removes pickup winding from circuit during contact closure. ∙ Electronic DC coil ∙ Primarily 24VDC product
  • 27. Controlling Arcing ∙ Arcing phenomena varies with electrode/contact material and contamination ∙ To breakdown a large air gap a minimum of 320V is needed ∙ Very small gaps will generate an arc with an intense electric field ∙ Minimum voltage to sustain an arc in air with small gaps is around 12 volts for most contact materials (less for Gold) Above the minimum arc voltage: ∙ Properly designed and operating device some arcing when contacts come together and more arcing at contact separation ∙ DC arc can be sustained at gaps roughly proportional to voltage – 10 to 20 V/cm.
  • 28. AC Contacts AC arc suppression ∙ Arcing occurs at greater than 12VAC and is greatest when opening contacts ∙ AC may have several sets of contacts to make/break all legs ∙ Self extinguishing due to current crossing zero. ∙ Anode/Cathode side is random – movable and stationary contacts erode at equal rates ∙ Higher currents and voltage require additional means to quench the arc after the first half cycle
  • 29. DC Contacts DC arc suppression ∙ DC requires only one set of contacts per device ∙ Rapid opening of contacts with enough air gap is necessary to break arc ∙ Arc splitters commonly used with low voltage contactors ∙ Rapid closing may cause contact bounce and accelerated erosion ∙ Current flows in one direction and one contact will be anode and the other will be cathode