How do I work for FREE?
Who Doesn’t Like Saving Money? By saving Energy A   reduction of 4% in data center power consumption can be expected for each degree warmer the temperature is kept. Of course, equipment must be kept within acceptable temperature ranges and never over 75 degrees, even though hardware specifications may rate the equipment to operate at temperatures of up to 95 degrees. Machinery operating outside of the acceptable temperature range wears down more quickly and poses a risk of overheating resulting in possible downtime. An additional problem is created when keeping a server room cooler than surrounding rooms: increased humidity levels. T he recommended humidity levels for data centers are between 45% and 55%. Cooling air too much can increase humidity. Once this happens, condensation can gather within sensitive, essential computer equipment and result in a hardware failure.  I  focus on, easy-to-implement strategies that can result in instant savings. None of these methods relies on any new technology introductions or expense.
Projects I’ve Completed CRAC units 116 and 117 cooling setpoint increased from 70DegF to 74DegF. (Serves common area.)  8-19-09 CRAC units 118 and 119 cooling setpoint increased from 70DegF to 74DegF. (Serves PDU hallway in phase III)  8-12-09 Humidity setpoint increased from 40%-45% to 45%-55% in meet-me room.  CRAC units 98 – 104.  This reduced space humidity and allowed the temperature setpoint to be maintained.  8-21-09 Disabled heating on VAV 1 – 4.  Currently program uses a narrow .5DegF dead-band between the heating and cooling setpoint.  This caused cycling of heat during what should be cooling only mode. Complete 8-5-09 (Program needs to be changed allowing larger dead-band and heating lockout based on outdoor air temperature. WIP) Lighting schedules and motion control enabled in all phases. 8-20-09 Cooling setpoint on both AC units in Power-house increased from 71DegF to 74DegF.  8-13-09 Cooling setpoint on CRAC 105 – 112 serving electrical room increased from 71DegF to 75DegF set to PI control.  9-17-09 Decreased flow in chilled water chemical add tank.  Decreased by-pass. 9-2-09 HVAC units LPC01 and LPC02 serving pump room both ran 24x7 and were set to discharge a constant 55DegF supply temp.  Changed units to allow single unit operation and rotation.  Changed temperature sensor to control space temperature. Setpoint set at 75DegF. 9-17-09 Changed parameters to allow a two (2) chiller operation, when the outdoor temperature is approximately below 65DegF.  Was running minimum of three (3) chillers.  10-13-09 Added  proportional – integral   control to CRAC units, were using proportional control only. 10-19-09. CRAC units in Phase III.  Supply air temperature maximum setpoint was set at 60DegF this caused over-cooling and humidity problems.  Heating setpoint had been set to 85DegF to try and correct this.  Changed Supply air temperature maximum to 70DegF and set heating setpoint to 68DegF.  This stopped running heat on the CRAC units 24 x 7, reduced load to chiller plant and improved humidity control. 10-23-09  $126,144.00 per year (estimated for not running heat) Changed BAS system to only run 4 of the 8 CRAC units in the electrical room.  11-18-09  $20,912.00 per year (estimated) Removed 30 perforated floor tiles from phase 3 reduced the amount of CRAC units running by 2.  VFD command reduced from 58.7Hz to 47.2Hz  12-18-09  $19,089.00 per year (estimated) All estimates are using .08 per KWH .
Now the Results……………………  Nice!
I’m not done yet………….. Chiller loading, increase load setpoint to add chiller, etc. WIP Lower chilled water differential setpoint. Lights off in pump and electrical rooms. Heating lock-out all office areas. Move all night-shift personal to one office area to increase shutdown schedule of AHU 117. All CRAC units, change humidity setpoint.  Currently set to 40% to 45%.  Recommended is 45% to 55%. Calibrate temperature and humidity on all CRAC units. WIP Use X belts on all HVAC equipment.  Estimated 6% reduction of motor energy. Increase floor temp of data center.  Recommended is 70DegF to 75DegF. Currently set at 71DegF.  Increase to 72DegF or 73DegF. Motion sensors in restrooms. Eliminate all direct mixing between chilled water supply and return. (elimination of de-coupler by-pass)  Remove perforated floor tiles and reduce number of CRAC units. WIP Identify Strategic Locations for Thermostats. In most legacy data centers,  thermostats are installed in the CRAC return air stream, where air flow may be  unpredictable. This can result in uneven CRAC unit loading, which in turn leads  to variations in server inlet temperatures. Relocating the thermostats to the  supply air stream, where discharge air can be controlled, will provide more  uniform under-floor and server inlet temperatures. Relocating the thermostat also  enables discharge air temperatures to be increased with more control and  accuracy.
That’s how I work for free. There’s more to me than working for free……………
How about web based interactive documentation?
 
 
Building Automation Graphics
Fire Pump Drawing
 

Contenu connexe

Tendances

Carel ultrasonic humidifier for In-row cooling and Compact Datacenter
Carel ultrasonic humidifier for In-row cooling and Compact DatacenterCarel ultrasonic humidifier for In-row cooling and Compact Datacenter
Carel ultrasonic humidifier for In-row cooling and Compact DatacenterCAREL Industries S.p.A
 
Gaining Data Center Cooling Efficiency Through Airflow Management
Gaining Data Center Cooling Efficiency Through Airflow ManagementGaining Data Center Cooling Efficiency Through Airflow Management
Gaining Data Center Cooling Efficiency Through Airflow ManagementUpsite Technologies
 
Sn 43369-benefits-gf-aa-to-icp-ms-sn43369-en
Sn 43369-benefits-gf-aa-to-icp-ms-sn43369-enSn 43369-benefits-gf-aa-to-icp-ms-sn43369-en
Sn 43369-benefits-gf-aa-to-icp-ms-sn43369-enWei Liu
 
Ian schmahmann hawk eye-800 presentation 3
Ian schmahmann hawk eye-800 presentation 3Ian schmahmann hawk eye-800 presentation 3
Ian schmahmann hawk eye-800 presentation 3ARAaus
 
Natural solutions for semi plug-in showcases
Natural solutions for semi plug-in showcasesNatural solutions for semi plug-in showcases
Natural solutions for semi plug-in showcasesCAREL Industries S.p.A
 
Myths of Data Center Containment:Whats's True and What's Not
Myths of Data Center Containment:Whats's True and What's NotMyths of Data Center Containment:Whats's True and What's Not
Myths of Data Center Containment:Whats's True and What's NotUpsite Technologies
 
The beginners guide to heat treatment control v2
The beginners guide to heat treatment control v2The beginners guide to heat treatment control v2
The beginners guide to heat treatment control v2Peter Sherwin
 
Stefan Jensen high performance energy low charge nh3 systems_160403
Stefan Jensen high performance energy low charge nh3 systems_160403Stefan Jensen high performance energy low charge nh3 systems_160403
Stefan Jensen high performance energy low charge nh3 systems_160403ARAaus
 
Fluke Calibration on How to Calibrate an RTD Using a Dry block Calibrator Web...
Fluke Calibration on How to Calibrate an RTD Using a Dry block Calibrator Web...Fluke Calibration on How to Calibrate an RTD Using a Dry block Calibrator Web...
Fluke Calibration on How to Calibrate an RTD Using a Dry block Calibrator Web...Transcat
 
Temperature calibration
Temperature calibrationTemperature calibration
Temperature calibrationChetan Yadav
 
How IT Decisions Impact Facilities: The Importance of Mutual Understanding
How IT Decisions Impact Facilities: The Importance of Mutual UnderstandingHow IT Decisions Impact Facilities: The Importance of Mutual Understanding
How IT Decisions Impact Facilities: The Importance of Mutual UnderstandingUpsite Technologies
 
How to Calibrate an IR Thermometer Webinar Presented by Fluke Calibration
How to Calibrate an IR Thermometer Webinar Presented by Fluke CalibrationHow to Calibrate an IR Thermometer Webinar Presented by Fluke Calibration
How to Calibrate an IR Thermometer Webinar Presented by Fluke CalibrationTranscat
 
Transcat and Fluke Calibration Webinar: Automating Pressure Calibration
Transcat and Fluke Calibration Webinar: Automating Pressure CalibrationTranscat and Fluke Calibration Webinar: Automating Pressure Calibration
Transcat and Fluke Calibration Webinar: Automating Pressure CalibrationTranscat
 
Develop a simple equation to calculate the heat loss due to flue gases in boiler
Develop a simple equation to calculate the heat loss due to flue gases in boilerDevelop a simple equation to calculate the heat loss due to flue gases in boiler
Develop a simple equation to calculate the heat loss due to flue gases in boilerSalah Salem
 
Rencana kerja dan pemeliharaan peralatan
Rencana kerja dan pemeliharaan peralatan Rencana kerja dan pemeliharaan peralatan
Rencana kerja dan pemeliharaan peralatan hero1964
 
Ams2750 e presentation
Ams2750 e presentationAms2750 e presentation
Ams2750 e presentationPeter Sherwin
 
Batch process conrol
Batch process conrol Batch process conrol
Batch process conrol Sadiq Rahim
 
Bubble injection inside cooling system
Bubble injection inside cooling systemBubble injection inside cooling system
Bubble injection inside cooling systemShamil Pc
 

Tendances (20)

Carel ultrasonic humidifier for In-row cooling and Compact Datacenter
Carel ultrasonic humidifier for In-row cooling and Compact DatacenterCarel ultrasonic humidifier for In-row cooling and Compact Datacenter
Carel ultrasonic humidifier for In-row cooling and Compact Datacenter
 
Gaining Data Center Cooling Efficiency Through Airflow Management
Gaining Data Center Cooling Efficiency Through Airflow ManagementGaining Data Center Cooling Efficiency Through Airflow Management
Gaining Data Center Cooling Efficiency Through Airflow Management
 
Sn 43369-benefits-gf-aa-to-icp-ms-sn43369-en
Sn 43369-benefits-gf-aa-to-icp-ms-sn43369-enSn 43369-benefits-gf-aa-to-icp-ms-sn43369-en
Sn 43369-benefits-gf-aa-to-icp-ms-sn43369-en
 
Ian schmahmann hawk eye-800 presentation 3
Ian schmahmann hawk eye-800 presentation 3Ian schmahmann hawk eye-800 presentation 3
Ian schmahmann hawk eye-800 presentation 3
 
Natural solutions for semi plug-in showcases
Natural solutions for semi plug-in showcasesNatural solutions for semi plug-in showcases
Natural solutions for semi plug-in showcases
 
Myths of Data Center Containment:Whats's True and What's Not
Myths of Data Center Containment:Whats's True and What's NotMyths of Data Center Containment:Whats's True and What's Not
Myths of Data Center Containment:Whats's True and What's Not
 
Homeowner report
Homeowner reportHomeowner report
Homeowner report
 
The beginners guide to heat treatment control v2
The beginners guide to heat treatment control v2The beginners guide to heat treatment control v2
The beginners guide to heat treatment control v2
 
Stefan Jensen high performance energy low charge nh3 systems_160403
Stefan Jensen high performance energy low charge nh3 systems_160403Stefan Jensen high performance energy low charge nh3 systems_160403
Stefan Jensen high performance energy low charge nh3 systems_160403
 
Fluke Calibration on How to Calibrate an RTD Using a Dry block Calibrator Web...
Fluke Calibration on How to Calibrate an RTD Using a Dry block Calibrator Web...Fluke Calibration on How to Calibrate an RTD Using a Dry block Calibrator Web...
Fluke Calibration on How to Calibrate an RTD Using a Dry block Calibrator Web...
 
Temperature calibration
Temperature calibrationTemperature calibration
Temperature calibration
 
How IT Decisions Impact Facilities: The Importance of Mutual Understanding
How IT Decisions Impact Facilities: The Importance of Mutual UnderstandingHow IT Decisions Impact Facilities: The Importance of Mutual Understanding
How IT Decisions Impact Facilities: The Importance of Mutual Understanding
 
Calibration
CalibrationCalibration
Calibration
 
How to Calibrate an IR Thermometer Webinar Presented by Fluke Calibration
How to Calibrate an IR Thermometer Webinar Presented by Fluke CalibrationHow to Calibrate an IR Thermometer Webinar Presented by Fluke Calibration
How to Calibrate an IR Thermometer Webinar Presented by Fluke Calibration
 
Transcat and Fluke Calibration Webinar: Automating Pressure Calibration
Transcat and Fluke Calibration Webinar: Automating Pressure CalibrationTranscat and Fluke Calibration Webinar: Automating Pressure Calibration
Transcat and Fluke Calibration Webinar: Automating Pressure Calibration
 
Develop a simple equation to calculate the heat loss due to flue gases in boiler
Develop a simple equation to calculate the heat loss due to flue gases in boilerDevelop a simple equation to calculate the heat loss due to flue gases in boiler
Develop a simple equation to calculate the heat loss due to flue gases in boiler
 
Rencana kerja dan pemeliharaan peralatan
Rencana kerja dan pemeliharaan peralatan Rencana kerja dan pemeliharaan peralatan
Rencana kerja dan pemeliharaan peralatan
 
Ams2750 e presentation
Ams2750 e presentationAms2750 e presentation
Ams2750 e presentation
 
Batch process conrol
Batch process conrol Batch process conrol
Batch process conrol
 
Bubble injection inside cooling system
Bubble injection inside cooling systemBubble injection inside cooling system
Bubble injection inside cooling system
 

Similaire à I Work for free

NER Aurora Thermal_Monitoring_Whitepaper
NER Aurora Thermal_Monitoring_WhitepaperNER Aurora Thermal_Monitoring_Whitepaper
NER Aurora Thermal_Monitoring_WhitepaperGreg Stover
 
CASE STUDY Hybrid Cooling IIT Delhi 13.2.2019.pdf
CASE STUDY Hybrid Cooling IIT Delhi 13.2.2019.pdfCASE STUDY Hybrid Cooling IIT Delhi 13.2.2019.pdf
CASE STUDY Hybrid Cooling IIT Delhi 13.2.2019.pdfUtkarshSingh554039
 
Mitch cfd video demo
Mitch cfd video demoMitch cfd video demo
Mitch cfd video demoplzandthx
 
5128A RHapid-Cal Humidity Generator Brochure
5128A RHapid-Cal Humidity Generator Brochure5128A RHapid-Cal Humidity Generator Brochure
5128A RHapid-Cal Humidity Generator BrochurePT. Siwali Swantika
 
What's Next in Cooling: Capacity, Containment, & More
What's Next in Cooling: Capacity, Containment, & MoreWhat's Next in Cooling: Capacity, Containment, & More
What's Next in Cooling: Capacity, Containment, & MoreUpsite Technologies
 
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...RDH Building Science
 
Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)Beeteco
 
Slides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingSlides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingGraybar
 
Gard analytics DOE energy modeling
Gard analytics DOE energy modelingGard analytics DOE energy modeling
Gard analytics DOE energy modelingSteve Klein
 
High Efficiency Solutions EEV & Monitoring Systems
High Efficiency Solutions  EEV & Monitoring SystemsHigh Efficiency Solutions  EEV & Monitoring Systems
High Efficiency Solutions EEV & Monitoring SystemsCAREL Industries S.p.A
 
Hvac systems presentation_slides
Hvac systems presentation_slidesHvac systems presentation_slides
Hvac systems presentation_slidesguy ygal
 
Low Carbon System Design “70ºC flow / 40ºC return” - a whole system approach
Low Carbon System Design “70ºC flow / 40ºC return” - a whole system approach Low Carbon System Design “70ºC flow / 40ºC return” - a whole system approach
Low Carbon System Design “70ºC flow / 40ºC return” - a whole system approach SAVSystems
 
General Sales Brochure 2016
General Sales Brochure 2016General Sales Brochure 2016
General Sales Brochure 2016Alan Beresford
 
General Sales Brochure 2016
General Sales Brochure 2016General Sales Brochure 2016
General Sales Brochure 2016Emma Beresford
 
75F Outside Air Optimization and Economizer Control
75F Outside Air Optimization and Economizer Control75F Outside Air Optimization and Economizer Control
75F Outside Air Optimization and Economizer ControlBrendonMartin3
 
Performance and Optimization of Residential Condensing Combi Systems
Performance and Optimization of Residential Condensing Combi SystemsPerformance and Optimization of Residential Condensing Combi Systems
Performance and Optimization of Residential Condensing Combi SystemsCenter for Energy and Environment
 
Thermal Management of Edge Data Centers
Thermal Management of Edge Data Centers Thermal Management of Edge Data Centers
Thermal Management of Edge Data Centers Raptor Power Systems
 

Similaire à I Work for free (20)

NER Aurora Thermal_Monitoring_Whitepaper
NER Aurora Thermal_Monitoring_WhitepaperNER Aurora Thermal_Monitoring_Whitepaper
NER Aurora Thermal_Monitoring_Whitepaper
 
CASE STUDY Hybrid Cooling IIT Delhi 13.2.2019.pdf
CASE STUDY Hybrid Cooling IIT Delhi 13.2.2019.pdfCASE STUDY Hybrid Cooling IIT Delhi 13.2.2019.pdf
CASE STUDY Hybrid Cooling IIT Delhi 13.2.2019.pdf
 
Mitch cfd video demo
Mitch cfd video demoMitch cfd video demo
Mitch cfd video demo
 
Frenic hvac catalog
Frenic hvac catalogFrenic hvac catalog
Frenic hvac catalog
 
5128A RHapid-Cal Humidity Generator Brochure
5128A RHapid-Cal Humidity Generator Brochure5128A RHapid-Cal Humidity Generator Brochure
5128A RHapid-Cal Humidity Generator Brochure
 
HIU Design Guide
HIU Design GuideHIU Design Guide
HIU Design Guide
 
What's Next in Cooling: Capacity, Containment, & More
What's Next in Cooling: Capacity, Containment, & MoreWhat's Next in Cooling: Capacity, Containment, & More
What's Next in Cooling: Capacity, Containment, & More
 
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
 
Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)
 
Slides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingSlides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for Cooling
 
Gard analytics DOE energy modeling
Gard analytics DOE energy modelingGard analytics DOE energy modeling
Gard analytics DOE energy modeling
 
High Efficiency Solutions EEV & Monitoring Systems
High Efficiency Solutions  EEV & Monitoring SystemsHigh Efficiency Solutions  EEV & Monitoring Systems
High Efficiency Solutions EEV & Monitoring Systems
 
Hvac systems presentation_slides
Hvac systems presentation_slidesHvac systems presentation_slides
Hvac systems presentation_slides
 
Low Carbon System Design “70ºC flow / 40ºC return” - a whole system approach
Low Carbon System Design “70ºC flow / 40ºC return” - a whole system approach Low Carbon System Design “70ºC flow / 40ºC return” - a whole system approach
Low Carbon System Design “70ºC flow / 40ºC return” - a whole system approach
 
General Sales Brochure 2016
General Sales Brochure 2016General Sales Brochure 2016
General Sales Brochure 2016
 
General Sales Brochure 2016
General Sales Brochure 2016General Sales Brochure 2016
General Sales Brochure 2016
 
75F Outside Air Optimization and Economizer Control
75F Outside Air Optimization and Economizer Control75F Outside Air Optimization and Economizer Control
75F Outside Air Optimization and Economizer Control
 
Performance and Optimization of Residential Condensing Combi Systems
Performance and Optimization of Residential Condensing Combi SystemsPerformance and Optimization of Residential Condensing Combi Systems
Performance and Optimization of Residential Condensing Combi Systems
 
Eco cooling
Eco cooling Eco cooling
Eco cooling
 
Thermal Management of Edge Data Centers
Thermal Management of Edge Data Centers Thermal Management of Edge Data Centers
Thermal Management of Edge Data Centers
 

I Work for free

  • 1. How do I work for FREE?
  • 2. Who Doesn’t Like Saving Money? By saving Energy A reduction of 4% in data center power consumption can be expected for each degree warmer the temperature is kept. Of course, equipment must be kept within acceptable temperature ranges and never over 75 degrees, even though hardware specifications may rate the equipment to operate at temperatures of up to 95 degrees. Machinery operating outside of the acceptable temperature range wears down more quickly and poses a risk of overheating resulting in possible downtime. An additional problem is created when keeping a server room cooler than surrounding rooms: increased humidity levels. T he recommended humidity levels for data centers are between 45% and 55%. Cooling air too much can increase humidity. Once this happens, condensation can gather within sensitive, essential computer equipment and result in a hardware failure. I focus on, easy-to-implement strategies that can result in instant savings. None of these methods relies on any new technology introductions or expense.
  • 3. Projects I’ve Completed CRAC units 116 and 117 cooling setpoint increased from 70DegF to 74DegF. (Serves common area.) 8-19-09 CRAC units 118 and 119 cooling setpoint increased from 70DegF to 74DegF. (Serves PDU hallway in phase III) 8-12-09 Humidity setpoint increased from 40%-45% to 45%-55% in meet-me room. CRAC units 98 – 104. This reduced space humidity and allowed the temperature setpoint to be maintained. 8-21-09 Disabled heating on VAV 1 – 4. Currently program uses a narrow .5DegF dead-band between the heating and cooling setpoint. This caused cycling of heat during what should be cooling only mode. Complete 8-5-09 (Program needs to be changed allowing larger dead-band and heating lockout based on outdoor air temperature. WIP) Lighting schedules and motion control enabled in all phases. 8-20-09 Cooling setpoint on both AC units in Power-house increased from 71DegF to 74DegF. 8-13-09 Cooling setpoint on CRAC 105 – 112 serving electrical room increased from 71DegF to 75DegF set to PI control. 9-17-09 Decreased flow in chilled water chemical add tank. Decreased by-pass. 9-2-09 HVAC units LPC01 and LPC02 serving pump room both ran 24x7 and were set to discharge a constant 55DegF supply temp. Changed units to allow single unit operation and rotation. Changed temperature sensor to control space temperature. Setpoint set at 75DegF. 9-17-09 Changed parameters to allow a two (2) chiller operation, when the outdoor temperature is approximately below 65DegF. Was running minimum of three (3) chillers. 10-13-09 Added proportional – integral control to CRAC units, were using proportional control only. 10-19-09. CRAC units in Phase III. Supply air temperature maximum setpoint was set at 60DegF this caused over-cooling and humidity problems. Heating setpoint had been set to 85DegF to try and correct this. Changed Supply air temperature maximum to 70DegF and set heating setpoint to 68DegF. This stopped running heat on the CRAC units 24 x 7, reduced load to chiller plant and improved humidity control. 10-23-09 $126,144.00 per year (estimated for not running heat) Changed BAS system to only run 4 of the 8 CRAC units in the electrical room. 11-18-09 $20,912.00 per year (estimated) Removed 30 perforated floor tiles from phase 3 reduced the amount of CRAC units running by 2. VFD command reduced from 58.7Hz to 47.2Hz 12-18-09 $19,089.00 per year (estimated) All estimates are using .08 per KWH .
  • 5. I’m not done yet………….. Chiller loading, increase load setpoint to add chiller, etc. WIP Lower chilled water differential setpoint. Lights off in pump and electrical rooms. Heating lock-out all office areas. Move all night-shift personal to one office area to increase shutdown schedule of AHU 117. All CRAC units, change humidity setpoint. Currently set to 40% to 45%. Recommended is 45% to 55%. Calibrate temperature and humidity on all CRAC units. WIP Use X belts on all HVAC equipment. Estimated 6% reduction of motor energy. Increase floor temp of data center. Recommended is 70DegF to 75DegF. Currently set at 71DegF. Increase to 72DegF or 73DegF. Motion sensors in restrooms. Eliminate all direct mixing between chilled water supply and return. (elimination of de-coupler by-pass) Remove perforated floor tiles and reduce number of CRAC units. WIP Identify Strategic Locations for Thermostats. In most legacy data centers, thermostats are installed in the CRAC return air stream, where air flow may be unpredictable. This can result in uneven CRAC unit loading, which in turn leads to variations in server inlet temperatures. Relocating the thermostats to the supply air stream, where discharge air can be controlled, will provide more uniform under-floor and server inlet temperatures. Relocating the thermostat also enables discharge air temperatures to be increased with more control and accuracy.
  • 6. That’s how I work for free. There’s more to me than working for free……………
  • 7. How about web based interactive documentation?
  • 8.  
  • 9.  
  • 12.