5. CALCULATION FOR FREEZER REFRIGERATION LOAD :
SPECIFICATION:
50mm thick tray
Capacity = 28 kg per day
Evaporating temperature = -30°C
Fish initial temperature = 10°C
Specific heat of fish above freezing = 3.18 KJ/kgK
Specific heat of fish below freezing = 1.67 KJ/kgK
Latent heat of fish = 276 KJ/kg
Using these values, the above calculation for fish refrigeration load
will be,
6. LOAD CALCULATION:
1. CHILLING LOAD :
T1 = 10°C ; T2 = -2°C
Q = m Cp ∆T
= 1.5 x 3.18 x (10-(-2))
=57.2 KJ/hr
2. Latent heat to remove :
= m x latent heat of fish
= 1.5 x 276
= 414 KJ/hr
3. FREEZING LOAD :
T1 = -2°C ; T2 = -28°C
Q = m Cp ∆T
= 1.5 x 1.67 x (-2-(-28))
= 65.13 KJ/hr
7. 4. Wall gain Load :
Volume of the space = 0.65x0.66x0.56 m3 = 0.24 m3 (240 litre)
Total surface area = 2.325 m2
k- Thermal conductivity of insulation material (PUF) = 0.033 W/mK
S - Surface area of the outer wall of the storage chamber
∆ X - Thickness of insulating material
Temperature outside, T1 = 30°C
Temperature inside, T2 = -28°C
= 0.058KW
8. Total heat to remove from fish
Q=Q1 +Q2+Q3+QW
= 0.206 KW
Total refrigeration requirement with allowance :
ADD 40% = 0.206 x 1.4 = 0.2884KW.
HENCE,
REFRIGERATION CAPACITY:
R.C = 0.2884 ÷ 3.516
R.C = 0.08 TR
9. From the P-H chart of R-134a we get,
h1 = 413 KJ/kg
h2 = 485 KJ/kg
h3 = h4 = 241.17KJ/kg
10. REFRIGERATION EFFECT :
R.E = h1 - h4
=413-241.171
=171.283 KJ/kg
WORK DONE BY COMPRESSOR :
W.D = h2 - h1
= 485-413
=72 KJ/kg
NOW,
R.C = m x R.E
m = 1.46 x 10-3 kg/sec
Power of Compressor = m x W.D
= 1.46 x 10-3 x 72
= 0.105 Kw
11. Based on design, a R134a compressor of
1/3 hp was selected
SELECTED COMPRESSOR SPECIFICATIONS
CONDENSER CAPACITY:
Q = m x( h2 – h3)
= 1.46 x 10-3 x (485 – 241.17)
= 0.356 Kw
Compressor model = KCN411LAG (Kirloskar make)
Compressor power = 1/3 hp
Motor specifications = Power- 245W, Single Phase, 50Hz,
230V, 2.7 A
12. For the given compressor and condenser
capacity the available condenser is of
specification
Heat to be Rejected : 0.356 Kw
Inside diameter of Tube : 3/10’’
Outside Diameter of Tube : 3/8’’
Mass flow rate = 1.46 x 10-3 kg/sec
Inlet temperature = 55°C
Outlet Temperature = 32°C
Type of Condenser : 12 x 13 x 3 rows
Condenser Fan Motor : 1/36 Hp
Condenser RPM : 1350
Condenser Fan : 9’’ Diameter
13. Selecting Expansion Device as,
THERMOSTATIC EXPANSION VALVE
Inlet diameter of valve: 3/8’’
Outlet diameter of valve: 1/2’’
Advantages of Thermostatic Expansion Valves.
1) Maximum Efficiency over a wide temperature and load
range.
2) Improved refrigerant return to the compressor thus
reducing the possibility of liquid slugging which can destroy
the compressor.
3) Variation in refrigerant charge, particularly in smaller unit.
14. EVAPORATOR PLATES DESIGN :
Temperature = -30°C
Outer Dia. =3/8’’
Inner Dia. = 3/10’’
Taking Properties of R-134a at -30°C
Density = 1386 kg/m3
Viscosity = 397 x 10-6 pa. sec
Specific Heat = 1.25 x 103 j/kg.k
Thermal Conductivity = K = 0.105 W/m.K
Prandlt No. = 4.84
Reynolds No. = 201.40
Nusselt No. = 3.063
Refrigerant Side H.T Coefficient = (Nu x k )/ Di
= 40.62 W/m2 .K
Overall H.T Coefficient:
Mean temp of Glycol = 27°C
Thermal Conductivity Of Glycol = 248.9 W/m.K
LMTD = 28.8°C
Therefore Overall H.T Coefficient =
15. Therefore, U = 40.56 W/m2K
Q= U x A x LMTD
A =
A = 0.214 m2
Length of Pipe =
Length = 7.62 m
= 25 ft
16. Therefore, Based on the above calculation.
EVAPORATOR SPECIFICATION:
Evaporator Capacity = 0.2884 Kw
Inside diameter of Tube : 3/10’’
Outside Diameter of Tube : 3/8’’
Length of tube in
one Evaporator plate = 25 ft
Evaporator plate Material= Aluminum
Area of plate = 45 x 61
cm2
Thickness of Plate = 2mm
17. SOLENOID VALVE
A solenoid valve is an electromechanical valve used
to control the flow of liquid or gas
Their function is simply to turn refrigerant flow on and
off.
Solenoid valves offer fast and safe switching,
reliability, long life and compact design.
When the solenoid coil is electrically energized, it
produces a magnetic field that attracts iron and
many of its alloys, then the iron armature or plunger is
drawn up into the core of the solenoid.
When the solenoid valve is de-energized, the plunger
falls, and the poppet closes the valve port.