SlideShare une entreprise Scribd logo
1  sur  7
Télécharger pour lire hors ligne
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE)
e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 7, Issue 5 (Sep. - Oct. 2013), PP 01-07
www.iosrjournals.org
www.iosrjournals.org 1 | Page
Proposal Technique for an Static Var Compensator
1
V.N.Ganesh, 2
S.Periasamy, 3
D.Sivakumar,
EEE department, Assistant professor, SRM University,
EEE Department, Assistant professor, SRM University,
EEE Department, Assistant professor, SRM University,
Abstract: This paper deals with the preliminary design of an SVC, which is the most important part of the
design process, because any specific error in the preliminary design and specifications in requirements
documents may end up with great amount of money, labour and time loss. The following subjects have to be
investigated thoroughly in order to finalize the preliminary design of an SVC. In this paper the following
parameters like Single thyristor operation, Series thyristor operation, Single Piece / Two Pieces Reactor
Arrangements are considered for the design procedure and the fault cases simulated in PSCAD concerning
three phase connections.
I. Introduction
Power quality of the supply busbar is determined by field measurements. The standards concerning
power quality and SVCs should be investigated in order to define and consider any power quality issues.
Currently valid regulations for reactive energy limits and other power quality issues may differ from one
country to another.
1.1 Load Characteristics
Whenever a TCR based SVC project is initiated, it is necessary to define the load characteristics
clearly. The precise load characteristics are evaluated by using: Field measurement by data acquisition,
Monthly electrical energy bills. Flicker performance, shunt filter and reactor sizing depend on these variations.
If the load is varying slowly, the control system design does not have a great impact on the design. Duty cycle
and load unbalance also plays a significant role in the design. The negative sequence compensation is a
challenge in TCR design as mentioned in [1, 2]. The methodology of load identification is also advised in the
standards [3] for Transmission SVCs.
1.2 Project Requirements
The customers may require some flexible solutions because of the future plans for the enterprise that
the SVC is installed. Capacity of the plant may change so that a modular/flexible SVC may be required instead
of a fixed installation capacity.
1.3 Environmental and Operational Conditions
The following environmental conditions are needed to be considered for the robustness of the SVC
installation: Maximum and minimum values of ambient temperature, Humidity, Snow load, Pollution level
1.4 Design of the Power Stage
1.4.1 Single Thyristor Operation
The Thyristor is the “static switch” part of a TCR based SVC. The current flowing through the reactors
is adjusted by thyristor valves. They are connected back-to-back and may share the same snubber. Selection of
the thyristors and snubbers depends on many parameters. In order to verify the selection, a computer simulation
is appropriate. In Fig.1.1, a typical thyristor valve can be seen. A thyristor needs to be triggered into conduction,
therefore the electronic triggering circuit design is also important as well as the thyristor selection. Some failures
may occur if triggering circuit is not designed carefully. A detailed thyristor selection analysis can be found in
[5]. In order to be able to select the thyristors, the following information in thyristor data sheets, such as the one
in[6], should be investigated:
Proposal Technique For An Static Var Compensator
www.iosrjournals.org 2 | Page
Fig1.1 A typical back to back connected thyristor valve
1.5.2 Reverse Blocking Voltage and Off state
V
DRM
is the repetitive peak off state voltage and V
RRM
is the repetitive peak reverse voltage. V
DRM
and
V
RRM
can be different from each other according to the thyristor selected.
1.5.3 di/dt and dv/dt
During the triggering of the thyristor, the region of the gate connection carries the thyristor current and
then spreads over the whole wafer area. In order to avoid excessive dissipations during this operation, the
amplitude of this current should be limited. di/dt is defined for the switching instants, and once the conduction
starts, it is not limited to a specific value. Operating frequency, peak value of permissible on state current for
half sine wave, gate triggering current and the rate of rise of gate current are given in datasheets for the
definition of di/dt. If the dv/dt value defined by the producers is exceeded, the thyristor self triggers which lead
to a break down in the wafer. Therefore, dv/dt should be limited to a safe value by using passive devices such as
snubbers.
1.5.4 Cooling Method
Cooling method is selected according to the level of power dissipation and available resources. The
major cooling types are: Natural air cooling, Forced air cooling and Liquid based cooling (de-ionized water or
other coolant). Heatsink selection depends on the cooling method. The heatsinks carry the thyristor current;
therefore they are selected from good electrical and heat conducting materials, usually aluminum or copper.
1.5.5 Thermal Considerations
Theoretically, a TCR produces reactive power only. However in the practical implementation, there are
many sources of dissipation. In addition to the copper losses of reactor banks, thyristor stack is also source of
dissipation, not only because of the voltage drop on the thyristors, but also because of the passive elements
connected to the stack. The main sources of dissipation can be classified as: Thyristor losses (conduction,
switching and off state losses), Snubber losses, Equalizing resistor losses, Valve reactor losses (if present),
Protection circuit losses, Gate triggering circuit losses, Bus bar or cable losses
The method of calculating the thyristor valve losses are defined in [4] Annex C. In this standard,
however protection circuit, gate triggering circuit and bus bar losses are omitted in the calculation of thyristor
valve losses because in high power applications these issues are negligible. Therefore, thyristor valve total
power loss, P
valve
, is given in [4] as:
P
valve
= P
cvalve
+ P
Tsw
+ P
vd
+ P
sn
+ P
hyst
(1.1)
P
cvalve
is thyristor valve conduction losses, P
Tsw
is thyristor total switching losses, P
vd
is equalizing
losses, P
sn
is snubber circuit losses, and P
hyst
is reactor (hysteresis) losses. Prolonged thermal stress on the
thyristors is not desired. The effects of such thermal stress can lead to thermal fatigue, or an earlier failure of the
thyristor, which is discussed in [9].
1.5.6 Snubber Circuit
The series inductance of the circuit, combined with the rate of rise of the current, produces transient
voltage peaks across the thyristor terminals. If voltage exceeds the thyristor ratings, it may lead to the
destruction of the device permanently. Therefore, in order to dampen the voltage overshooting a parallel R-C
snubber circuit is connected as a general practice [1].
The snubber values are usually selected to keep the circuit response critically damped. Increasing the
damping level leads to more dissipation. A detailed snubber design can be found in [5].
Proposal Technique For An Static Var Compensator
www.iosrjournals.org 3 | Page
1.5.7 Triggering Circuit
Triggering circuits usually have dual tasks, primarily isolation and secondarily supplying the gate
current necessary to switch on the thyristor. The isolation can be achieved by magnetically or optically. Pulse
transformers suitable for transmitting high current and high frequency pulses are may be used for magnetic
isolation. In medium voltage applications pulses are usually transmitted to the gate by a ferrite core placed
around a single wire carrying the low voltage side current. There is isolation material around the primary
conductor.
Optical isolation is achieved through optical fibres (F/O). However triggering circuit with F/O requires
a gate energy circuit in order to be able to supply the current pulse necessary for the gate.
1.5.8 Overvoltage protection
Overvoltage in an SVC system usually occurs in a temporary fault condition such as a lightning surge.
Temporary overvoltage cases needs fast interaction and protection, therefore they are handled by the
overvoltage protection circuits which are usually placed in or near the thyristor triggering circuits. In a series
thyristor operation, equalizing resistor circuits or some of the series thyristors may breakdown. This may impose
overvoltages on the remaining of the valve circuit. Overvoltage protection triggers rest of the thyristors to
conduction thus protecting them against the overvoltage.
Breakover diodes (BOD), avalanche type diodes or metal oxide varistors (MOV) are used in
overvoltage protection circuits. Such implementations can be found in [7] with a BOD, and in [5] with a MOV.
Continuous operating voltages may sometimes rise above the standard levels defined in [8]. If such an
overvoltage occurs, the control system must react to this type of fault.
1.6 Series Thyristor Operation
Series thyristor operation requires additional design work. Connecting semiconductor devices in series
or in parallel requires special attention on voltage and current sharing. A failure in balancing the current or
voltage may lead to the failure of the whole stack.
Design and implementation of series operation of thyristors are discussed in [5]. The same
design is also used in the utilization of the ISDEMIR ladle furnace compensation system. In Fig.1.2 the series-
connected thyristors are seen. Cooling water flows through the heatsinks, not only cooling the thyristors but also
cooling the snubber circuits. The operation voltage of 6.3kV requires special attention to the insulation. The
distance between the high voltage switches and other equipment is selected by considering the safe values and
pulse transformers are placed at the back of the insulating separator thus avoiding flashovers to the control
circuit.
Fig.1.2 A thyristor stack which consists of series connected thyristors. (a): with antiparallel connected switches.
(b) with positive and negative thyristors grouped
1.7 Single Piece / Two Pieces Reactor Arrangement
In order to protect the Thyristor valves against a short circuit, the reactors can be divided into two series
reactors having the same total phase reactance. Connecting the Thyristor valves in between these series reactors
will limit the maximum fault currents. If one reactor is short circuited, the fault current will be limited. If phase
is short circuited, no fault current will flow through thyristors. In order to observe a total short circuit current,
each reactor placed on top of one another should be
separately short circuited, which has a very low probability in a TCR installation because of the geometry.
Proposal Technique For An Static Var Compensator
www.iosrjournals.org 4 | Page
Fig.1.3 Reactor arrangement; (a) Single piece, (b) two pieces
Several fault cases that can appear in a delta connected TCR are given in Fig. 1.4, 1.5 and 1.6. These
cases are simulated for a 1 kV 1,5 MVAr TCR + 0,75 kVAr Filtre installation with a short circuit 525 MVA .
Filters consist of three 5
th
harmonic and three 7
th
harmonic tuned filters at 1 kV side. A feature of PSCAD called
“Multirun” is used for multiple simulations. The results are given in Table 1.1. The worst case is found to be a
short circuit across the upper or lower piece of the reactor.
Fig.1.4 PSCAD Multirun (Multiple Simulation) for different fault types
Table.1.1. PSCAD Multirun simulation results
Cas
e
Maximum 5th
Harmonic Filter
Current (kA)
Maximum 5th
Harmonic Filter
Capacitor
Voltage (kV)
Maximum 7th
Harmonic Filter
Current (kA)
Maximum 7th
Harmonic Filter
Capacitor
Voltage (kV)
Maximum TCR
Line current
(kA)
Maximum TCR
Thyristor
current (kA)
1 0,4760 0,9582 0,4296 1,0245 26,7383 0,7590
2 0,1383 0,5457 0,0927 0,5009 33,7312 0,9013
3 0,1276 0,8337 0,0832 0,8152 27,5715 0,7833
4 0,2920 0,4659 0,2629 0,4559 39,4042 0,6918
5 0,1333 0,8257 0,0877 0,8005 1,4378 1,6126
6 0,1260 0,8171 0,0826 0,7959 1,7268 1,8834
7 0,1277 0,8336 0,0832 0,8151 1,0207 1,0602
8 0,1300 0,8090 0,0855 0,7799 2,5117 1,8673
9 0,1266 0,8253 0,0828 0,8054 1,1658 1,1886
10 0,1277 0,8336 0,0832 0,8151 1,0207 1,0602
11 0,1303 0,8294 0,0853 0,8070 1,0265 0,7659
12 0,1281 0,8252 0,0836 0,8029 1,2619 1,0690
Fig.1.5 Fault cases simulated in
PSCAD concerning three phase
connections
Fig.1.6 Fault cases simulated
in PSCAD concerning one
phase and two thyristor
terminal connections
belonging different phases
Fig.1.7 Fault cases simulated
in PSCAD concerning three
thyristor terminals belonging
different phases
Proposal Technique For An Static Var Compensator
www.iosrjournals.org 5 | Page
1.8 Reactor Design
Reactor design for the SVC TCR and shunt filters require special attention to current harmonics and
voltage harmonics levels because dissipations in the reactors may be higher than the standard shunt reactors.
The Standard IEC 289 [15] gives the definitions and suggestions for shunt reactors. IEEE standards [10-14] give
detailed information on reactors and their requirements. IEEE Std C57-120-1991 [14] contains the loss
calculations while [12] proposes the test procedures for reactors.
The following should be conducted by the customer to the manufacturer when a reactor is to be designed:
Standard (generally IEC 60289), air-cored / iron cored, Frequency, Rated voltage (line-line or phase, rms,
default IEC 38), Max.continuous operating voltage (kV), Rated inductance per phase (mH), Rated continuous
current (kA), Max. continuous current (kA), TDD, Short circuit power before reactor, Outdoor/indoor
installation, Insulation class, Cooling type, Maximum ambient temperature, Tuning frequency (If connected in
a shunt filter, Hz), Quantity and construction details (including terminal connections and mounting style such as
top-to-top or independent). The reactor ratings should be verified by a power system simulation tool. In the
simulation, worst case scenarios such as misfiring (where conduction per thyristor is longer than 180o) and short
circuits can be investigated. The manufacturers determine the minimum safe distance to other magnetic material
and closed loop conductors. These magnetic clearances around the reactor depend on the individual reactor
design and. should be taken into account in the layout of the overall system.
1.9 Harmonic Filter Design
The SVC topology is important in the decision for filtering. The complete SVC topology should be
selected before starting the frequency response analysis.
1.9.1 Frequency Response of the Filters
Thyristor controlled reactor (TCR) acts as a harmonic current source and produces its own odd
harmonic current components (3
rd
, 5
th
, 7
th
, 9
th
, 11
th
, etc.) for symmetrical triggering in the steady-state. However,
during control, firing angle will change from positive half-cycle to negative half-cycle resulting in production of
even harmonics (2
nd
, 4
th
, etc.). These even harmonics are taken as temporary overloads on filter reactors and
capacitors. In a delta connected TCR, triple harmonics do not appear in the line currents for symmetrical
triggering in the steady state. They will circulate through the delta connected reactor bank. However, in transient
state owing to control, unbalanced portion of triple harmonics will be reflected to the line side. These temporary
overloads on filter elements are taken into account by safety margins in the design. An important phenomenon
of TCR operation during firing angle control from positive half-cycle to negative half-cycle is the generation of
direct current component. This may move the magnetic operating point on the B-H characteristics of SVC
transformer and thyristor controlled reactors for the iron core case. Therefore, the linearity of TCR core is
essential for iron-core solution. Simulations should be carried out according to this assumption in order to find
out harmonic loadings on filter elements. Filter circuits can be designed according to the rules described in IEC
61642 [16]. The loads are taken as harmonic current sources in simulation, which inject 1.0 A rms at all
harmonic frequencies.
1.10 TCR Control
Thyristor controlled reactor is a variable susceptance that can be controlled by triggering delay of the
thyristor gate signals. The control system varies according to the desired method of TCR implementation. These
methods are discussed in the below section.
1.11 Control System Overview
Control system that is only designed for reactive power compensation is a simple controller that
calculates the necessary firing angle of each phase. It is also acceptable if all three phases are fired with the
same angle. This type of control achieves reactive power compensation; however it is capable of neither load
balancing nor voltage regulation. Control system design can easily be implemented by using proportional-
integral (PI) controller in such an SVC. This type of control can be seen in Fig.1.8. In order to be able to achieve
load balancing, the negative sequence of the load current must be removed entirely.
Reactive current component calculation and reactive power calculations can be evaluated by using 50
Hz averaging. This method will cause responses in the TCR because 50Hz averaging method will require time
to take the average value of the signal.
Proposal Technique For An Static Var Compensator
www.iosrjournals.org 6 | Page
Fig.1.8 Simple reactive power compensation by PI controller
Fig.1.9 Reactive power compensation with load balancing by PI controller
Fig.1.10 Flicker Compensation System with feed-forward and feed-back control
1.12 Thyristor Valve Control and Misfiring
Ideal TCR line currents are 90
o
displaced from the line voltage and they are symmetrical and balanced
if the firing delay angle is in the range of 90
o
-180
o
for positive half cycle and 270
o
-360
o
in the negative half
cycle. These are the safe operating regions of TCR, which are the 2
nd
and the 4
th
regions shown in Fig.1.11.
Whenever the conduction angle of a thyristor exceeds 180
o
, a DC current component exists. In a non-ideal TCR
which includes an internal resistor, the firing delay angle can be reduced below 90
o
. The exact angle can be
calculated from the inductive reactance and the resistance of the TCR.
Fig.1.11. Firing Delay Angle (α) versus TCR line voltage. The safe operating regions 2 and 4 of TCR are
marked and Unsafe operating regions 1and 3 are marked.
II. Conclusion:
From the implemented tests and procedure, it can be concluded that the design of SVC in
transmission lines offers controlling the power flow in an efficient manner. The TCR simulation for a 1 kV 1,5
MVAr TCR + 0,75 kVAr Filter installation with a short circuit 525 MVA was tested and shown in this paper
Proposal Technique For An Static Var Compensator
www.iosrjournals.org 7 | Page
using PSCAD “Multirun” simulator. In order to be able to achieve load balancing, the negative sequence of the
load current must be eliminated completely. Control system design can easily be implemented by using
proportional-integral (PI) controller in such an SVC.
References
[1] T.J.E. Miller, “Reactive Power Control In Electric Systems,”, John Wiley&Sons, 1982.
[2] J.Arrilaga, N.R. Watson, “Power System Harmonics”, Wiley, 1982
[3] “IEEE Guide for the Functional Specification of Transmission Static Var Compensators” IEEE Std 1031-1991)
[4] “IEEE Guide for the Functional Specification of Transmission Static Var Compensators” IEEE Std 1031-2000 (Revision ofIEEE
Std 1031-1991)
[5] M.V. Utalay, “Design and Implementation of a Medium Voltage Thyristor Controlled Reactor”, MSc. Thesis, METU, Jan.1996
[6] Semikron Power Electronics Catalogue,Semikron Inc. Germany, 10/1998.
[7] Lawatsch, H.M.; Vitins, J.; “Protection of thyristors against overvoltage with breakover diyotes”, IEEE Transactions on Industry
Applications Volume 24, Issue 3, May-June 1988 pp. 444 – 448
[8] TS 831, “Standard Voltages in THE Distribution Systems” , 1979
[9] “Effects of Temperature on Thyristor Performance” Application Note AN4870, Dynex Semiconductors, January 2000.
[10] ANSI/IEEE Std. C37.109, “IEEE Guide for the Protection of Shunt Reactors” 1988
[11] IEEE Std. C57-114, “IEEE Seismic Guide for Power Transformers and Reactors”, 1990
[12] IEEE Standard Requirements,Terminology, and Test Code for Shunt Reactors Rated Over 500 kVA, IEEE Std. C57.21-1990
[13] IEEE Std. C57-125, “IEEE Guide for Failure Investigation, Documentation,and Analysis for Power Transformers and Shunt
Reactors” 1991
[14] “IEEE Loss Evalution Guide for Power Transformers and Reactors” IEEE Std C57-120-1991
[15] IEC 60289 “Reactors”,1988
[16] IEC 61642 Industrial a.c. Networks Affected by Harmonics - Application of Filters and Shunt Capacitors

Contenu connexe

Tendances

FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
Power System Operation
 
Understanding overcurrent protection
Understanding overcurrent protectionUnderstanding overcurrent protection
Understanding overcurrent protection
michaeljmack
 
Generator protection by a. kato
Generator protection by a. katoGenerator protection by a. kato
Generator protection by a. kato
Agrey Kato
 

Tendances (20)

protection of feeders in distribution substation
protection of feeders in distribution substationprotection of feeders in distribution substation
protection of feeders in distribution substation
 
Substation Neutral Earthing
Substation Neutral EarthingSubstation Neutral Earthing
Substation Neutral Earthing
 
Transformer Failures and Case Studies
Transformer Failures and Case StudiesTransformer Failures and Case Studies
Transformer Failures and Case Studies
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
 
Presentation on switchgear
Presentation on switchgear Presentation on switchgear
Presentation on switchgear
 
Understanding overcurrent protection
Understanding overcurrent protectionUnderstanding overcurrent protection
Understanding overcurrent protection
 
D010512129
D010512129D010512129
D010512129
 
Dynamic Analysis and Testing of on-load tap changer
Dynamic Analysis and Testing of on-load tap changerDynamic Analysis and Testing of on-load tap changer
Dynamic Analysis and Testing of on-load tap changer
 
Short-Circuit Protective Device Coordination & Arc Flash Analysis
Short-Circuit Protective Device Coordination & Arc Flash AnalysisShort-Circuit Protective Device Coordination & Arc Flash Analysis
Short-Circuit Protective Device Coordination & Arc Flash Analysis
 
Ge busbar protection numerical relays
Ge busbar protection numerical relaysGe busbar protection numerical relays
Ge busbar protection numerical relays
 
Protection schemes and zones
Protection schemes and zonesProtection schemes and zones
Protection schemes and zones
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Generator protection by a. kato
Generator protection by a. katoGenerator protection by a. kato
Generator protection by a. kato
 
Introduction to Fieldbus
Introduction to FieldbusIntroduction to Fieldbus
Introduction to Fieldbus
 
Power system protection
Power system protectionPower system protection
Power system protection
 
Out of phase current switching in High Voltage Circuit Breakers
Out of phase current switching in High Voltage Circuit BreakersOut of phase current switching in High Voltage Circuit Breakers
Out of phase current switching in High Voltage Circuit Breakers
 
Transfomer diagnostics/sanjeet-1308143
Transfomer diagnostics/sanjeet-1308143Transfomer diagnostics/sanjeet-1308143
Transfomer diagnostics/sanjeet-1308143
 
Switchgear and protection 2
Switchgear and protection 2Switchgear and protection 2
Switchgear and protection 2
 
Power system protection devices
Power system protection devicesPower system protection devices
Power system protection devices
 
protection and relay scheme
protection and relay schemeprotection and relay scheme
protection and relay scheme
 

En vedette

Workshop notes new 2009
Workshop notes new 2009Workshop notes new 2009
Workshop notes new 2009
melissataggart
 

En vedette (20)

M0937681
M0937681M0937681
M0937681
 
Workshop notes new 2009
Workshop notes new 2009Workshop notes new 2009
Workshop notes new 2009
 
H0944649
H0944649H0944649
H0944649
 
B0520710
B0520710B0520710
B0520710
 
C0552124
C0552124C0552124
C0552124
 
The Commonwealth Fund 2015 International Health Care Policy Survey of Primary...
The Commonwealth Fund 2015 International Health Care Policy Survey of Primary...The Commonwealth Fund 2015 International Health Care Policy Survey of Primary...
The Commonwealth Fund 2015 International Health Care Policy Survey of Primary...
 
4033 chiminazzo lionela_tp10
4033 chiminazzo lionela_tp104033 chiminazzo lionela_tp10
4033 chiminazzo lionela_tp10
 
Presentation4
Presentation4Presentation4
Presentation4
 
R094108112
R094108112R094108112
R094108112
 
I0935053
I0935053I0935053
I0935053
 
K0966468
K0966468K0966468
K0966468
 
C0951520
C0951520C0951520
C0951520
 
Estimation of Metric Distance of Observations from the Average Score
Estimation of Metric Distance of Observations from the Average ScoreEstimation of Metric Distance of Observations from the Average Score
Estimation of Metric Distance of Observations from the Average Score
 
Pandemic Planning
Pandemic PlanningPandemic Planning
Pandemic Planning
 
A0950110
A0950110A0950110
A0950110
 
CLUBNIK угадай-ка
CLUBNIK угадай-каCLUBNIK угадай-ка
CLUBNIK угадай-ка
 
A Secure Model for Cloud Computing Based Storage and Retrieval
A Secure Model for Cloud Computing Based Storage and  RetrievalA Secure Model for Cloud Computing Based Storage and  Retrieval
A Secure Model for Cloud Computing Based Storage and Retrieval
 
Focused Exploration of Geospatial Context on Linked Open Data
Focused Exploration of Geospatial Context on Linked Open DataFocused Exploration of Geospatial Context on Linked Open Data
Focused Exploration of Geospatial Context on Linked Open Data
 
G01044345
G01044345G01044345
G01044345
 
C0621115
C0621115C0621115
C0621115
 

Similaire à Proposal Technique for an Static Var Compensator

Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
Priten Vasa
 
Why transformers fail_final
Why transformers fail_finalWhy transformers fail_final
Why transformers fail_final
Snehangshu Ghosh
 

Similaire à Proposal Technique for an Static Var Compensator (20)

IRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
IRJET- Study Over Current Relay (MCGG53) Response using Matlab ModelIRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
IRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
 
Overview of custom power devices
Overview of custom power devicesOverview of custom power devices
Overview of custom power devices
 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppt
 
DigSILENT PF - 06 (es) short circuit theory
DigSILENT PF - 06 (es) short circuit theoryDigSILENT PF - 06 (es) short circuit theory
DigSILENT PF - 06 (es) short circuit theory
 
DigSILENT PF - 05 short circuit theory
DigSILENT PF - 05 short circuit theoryDigSILENT PF - 05 short circuit theory
DigSILENT PF - 05 short circuit theory
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
 
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
 
D010622334
D010622334D010622334
D010622334
 
Executive summary
Executive summaryExecutive summary
Executive summary
 
Busbar protection LEC 2.pptx
Busbar protection LEC 2.pptxBusbar protection LEC 2.pptx
Busbar protection LEC 2.pptx
 
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfH7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
 
Devlopement of the dynamic resistance measurement (drm) method for condition ...
Devlopement of the dynamic resistance measurement (drm) method for condition ...Devlopement of the dynamic resistance measurement (drm) method for condition ...
Devlopement of the dynamic resistance measurement (drm) method for condition ...
 
Alternator protection
Alternator protectionAlternator protection
Alternator protection
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers
 
Why transformers fail_final
Why transformers fail_finalWhy transformers fail_final
Why transformers fail_final
 
MTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptxMTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptx
 
Analsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substationsAnalsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substations
 
Analsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substationsAnalsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substations
 

Plus de IOSR Journals

Plus de IOSR Journals (20)

A011140104
A011140104A011140104
A011140104
 
M0111397100
M0111397100M0111397100
M0111397100
 
L011138596
L011138596L011138596
L011138596
 
K011138084
K011138084K011138084
K011138084
 
J011137479
J011137479J011137479
J011137479
 
I011136673
I011136673I011136673
I011136673
 
G011134454
G011134454G011134454
G011134454
 
H011135565
H011135565H011135565
H011135565
 
F011134043
F011134043F011134043
F011134043
 
E011133639
E011133639E011133639
E011133639
 
D011132635
D011132635D011132635
D011132635
 
C011131925
C011131925C011131925
C011131925
 
B011130918
B011130918B011130918
B011130918
 
A011130108
A011130108A011130108
A011130108
 
I011125160
I011125160I011125160
I011125160
 
H011124050
H011124050H011124050
H011124050
 
G011123539
G011123539G011123539
G011123539
 
F011123134
F011123134F011123134
F011123134
 
E011122530
E011122530E011122530
E011122530
 
D011121524
D011121524D011121524
D011121524
 

Dernier

Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
amitlee9823
 
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
dharasingh5698
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 

Dernier (20)

Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdf
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 

Proposal Technique for an Static Var Compensator

  • 1. IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 7, Issue 5 (Sep. - Oct. 2013), PP 01-07 www.iosrjournals.org www.iosrjournals.org 1 | Page Proposal Technique for an Static Var Compensator 1 V.N.Ganesh, 2 S.Periasamy, 3 D.Sivakumar, EEE department, Assistant professor, SRM University, EEE Department, Assistant professor, SRM University, EEE Department, Assistant professor, SRM University, Abstract: This paper deals with the preliminary design of an SVC, which is the most important part of the design process, because any specific error in the preliminary design and specifications in requirements documents may end up with great amount of money, labour and time loss. The following subjects have to be investigated thoroughly in order to finalize the preliminary design of an SVC. In this paper the following parameters like Single thyristor operation, Series thyristor operation, Single Piece / Two Pieces Reactor Arrangements are considered for the design procedure and the fault cases simulated in PSCAD concerning three phase connections. I. Introduction Power quality of the supply busbar is determined by field measurements. The standards concerning power quality and SVCs should be investigated in order to define and consider any power quality issues. Currently valid regulations for reactive energy limits and other power quality issues may differ from one country to another. 1.1 Load Characteristics Whenever a TCR based SVC project is initiated, it is necessary to define the load characteristics clearly. The precise load characteristics are evaluated by using: Field measurement by data acquisition, Monthly electrical energy bills. Flicker performance, shunt filter and reactor sizing depend on these variations. If the load is varying slowly, the control system design does not have a great impact on the design. Duty cycle and load unbalance also plays a significant role in the design. The negative sequence compensation is a challenge in TCR design as mentioned in [1, 2]. The methodology of load identification is also advised in the standards [3] for Transmission SVCs. 1.2 Project Requirements The customers may require some flexible solutions because of the future plans for the enterprise that the SVC is installed. Capacity of the plant may change so that a modular/flexible SVC may be required instead of a fixed installation capacity. 1.3 Environmental and Operational Conditions The following environmental conditions are needed to be considered for the robustness of the SVC installation: Maximum and minimum values of ambient temperature, Humidity, Snow load, Pollution level 1.4 Design of the Power Stage 1.4.1 Single Thyristor Operation The Thyristor is the “static switch” part of a TCR based SVC. The current flowing through the reactors is adjusted by thyristor valves. They are connected back-to-back and may share the same snubber. Selection of the thyristors and snubbers depends on many parameters. In order to verify the selection, a computer simulation is appropriate. In Fig.1.1, a typical thyristor valve can be seen. A thyristor needs to be triggered into conduction, therefore the electronic triggering circuit design is also important as well as the thyristor selection. Some failures may occur if triggering circuit is not designed carefully. A detailed thyristor selection analysis can be found in [5]. In order to be able to select the thyristors, the following information in thyristor data sheets, such as the one in[6], should be investigated:
  • 2. Proposal Technique For An Static Var Compensator www.iosrjournals.org 2 | Page Fig1.1 A typical back to back connected thyristor valve 1.5.2 Reverse Blocking Voltage and Off state V DRM is the repetitive peak off state voltage and V RRM is the repetitive peak reverse voltage. V DRM and V RRM can be different from each other according to the thyristor selected. 1.5.3 di/dt and dv/dt During the triggering of the thyristor, the region of the gate connection carries the thyristor current and then spreads over the whole wafer area. In order to avoid excessive dissipations during this operation, the amplitude of this current should be limited. di/dt is defined for the switching instants, and once the conduction starts, it is not limited to a specific value. Operating frequency, peak value of permissible on state current for half sine wave, gate triggering current and the rate of rise of gate current are given in datasheets for the definition of di/dt. If the dv/dt value defined by the producers is exceeded, the thyristor self triggers which lead to a break down in the wafer. Therefore, dv/dt should be limited to a safe value by using passive devices such as snubbers. 1.5.4 Cooling Method Cooling method is selected according to the level of power dissipation and available resources. The major cooling types are: Natural air cooling, Forced air cooling and Liquid based cooling (de-ionized water or other coolant). Heatsink selection depends on the cooling method. The heatsinks carry the thyristor current; therefore they are selected from good electrical and heat conducting materials, usually aluminum or copper. 1.5.5 Thermal Considerations Theoretically, a TCR produces reactive power only. However in the practical implementation, there are many sources of dissipation. In addition to the copper losses of reactor banks, thyristor stack is also source of dissipation, not only because of the voltage drop on the thyristors, but also because of the passive elements connected to the stack. The main sources of dissipation can be classified as: Thyristor losses (conduction, switching and off state losses), Snubber losses, Equalizing resistor losses, Valve reactor losses (if present), Protection circuit losses, Gate triggering circuit losses, Bus bar or cable losses The method of calculating the thyristor valve losses are defined in [4] Annex C. In this standard, however protection circuit, gate triggering circuit and bus bar losses are omitted in the calculation of thyristor valve losses because in high power applications these issues are negligible. Therefore, thyristor valve total power loss, P valve , is given in [4] as: P valve = P cvalve + P Tsw + P vd + P sn + P hyst (1.1) P cvalve is thyristor valve conduction losses, P Tsw is thyristor total switching losses, P vd is equalizing losses, P sn is snubber circuit losses, and P hyst is reactor (hysteresis) losses. Prolonged thermal stress on the thyristors is not desired. The effects of such thermal stress can lead to thermal fatigue, or an earlier failure of the thyristor, which is discussed in [9]. 1.5.6 Snubber Circuit The series inductance of the circuit, combined with the rate of rise of the current, produces transient voltage peaks across the thyristor terminals. If voltage exceeds the thyristor ratings, it may lead to the destruction of the device permanently. Therefore, in order to dampen the voltage overshooting a parallel R-C snubber circuit is connected as a general practice [1]. The snubber values are usually selected to keep the circuit response critically damped. Increasing the damping level leads to more dissipation. A detailed snubber design can be found in [5].
  • 3. Proposal Technique For An Static Var Compensator www.iosrjournals.org 3 | Page 1.5.7 Triggering Circuit Triggering circuits usually have dual tasks, primarily isolation and secondarily supplying the gate current necessary to switch on the thyristor. The isolation can be achieved by magnetically or optically. Pulse transformers suitable for transmitting high current and high frequency pulses are may be used for magnetic isolation. In medium voltage applications pulses are usually transmitted to the gate by a ferrite core placed around a single wire carrying the low voltage side current. There is isolation material around the primary conductor. Optical isolation is achieved through optical fibres (F/O). However triggering circuit with F/O requires a gate energy circuit in order to be able to supply the current pulse necessary for the gate. 1.5.8 Overvoltage protection Overvoltage in an SVC system usually occurs in a temporary fault condition such as a lightning surge. Temporary overvoltage cases needs fast interaction and protection, therefore they are handled by the overvoltage protection circuits which are usually placed in or near the thyristor triggering circuits. In a series thyristor operation, equalizing resistor circuits or some of the series thyristors may breakdown. This may impose overvoltages on the remaining of the valve circuit. Overvoltage protection triggers rest of the thyristors to conduction thus protecting them against the overvoltage. Breakover diodes (BOD), avalanche type diodes or metal oxide varistors (MOV) are used in overvoltage protection circuits. Such implementations can be found in [7] with a BOD, and in [5] with a MOV. Continuous operating voltages may sometimes rise above the standard levels defined in [8]. If such an overvoltage occurs, the control system must react to this type of fault. 1.6 Series Thyristor Operation Series thyristor operation requires additional design work. Connecting semiconductor devices in series or in parallel requires special attention on voltage and current sharing. A failure in balancing the current or voltage may lead to the failure of the whole stack. Design and implementation of series operation of thyristors are discussed in [5]. The same design is also used in the utilization of the ISDEMIR ladle furnace compensation system. In Fig.1.2 the series- connected thyristors are seen. Cooling water flows through the heatsinks, not only cooling the thyristors but also cooling the snubber circuits. The operation voltage of 6.3kV requires special attention to the insulation. The distance between the high voltage switches and other equipment is selected by considering the safe values and pulse transformers are placed at the back of the insulating separator thus avoiding flashovers to the control circuit. Fig.1.2 A thyristor stack which consists of series connected thyristors. (a): with antiparallel connected switches. (b) with positive and negative thyristors grouped 1.7 Single Piece / Two Pieces Reactor Arrangement In order to protect the Thyristor valves against a short circuit, the reactors can be divided into two series reactors having the same total phase reactance. Connecting the Thyristor valves in between these series reactors will limit the maximum fault currents. If one reactor is short circuited, the fault current will be limited. If phase is short circuited, no fault current will flow through thyristors. In order to observe a total short circuit current, each reactor placed on top of one another should be separately short circuited, which has a very low probability in a TCR installation because of the geometry.
  • 4. Proposal Technique For An Static Var Compensator www.iosrjournals.org 4 | Page Fig.1.3 Reactor arrangement; (a) Single piece, (b) two pieces Several fault cases that can appear in a delta connected TCR are given in Fig. 1.4, 1.5 and 1.6. These cases are simulated for a 1 kV 1,5 MVAr TCR + 0,75 kVAr Filtre installation with a short circuit 525 MVA . Filters consist of three 5 th harmonic and three 7 th harmonic tuned filters at 1 kV side. A feature of PSCAD called “Multirun” is used for multiple simulations. The results are given in Table 1.1. The worst case is found to be a short circuit across the upper or lower piece of the reactor. Fig.1.4 PSCAD Multirun (Multiple Simulation) for different fault types Table.1.1. PSCAD Multirun simulation results Cas e Maximum 5th Harmonic Filter Current (kA) Maximum 5th Harmonic Filter Capacitor Voltage (kV) Maximum 7th Harmonic Filter Current (kA) Maximum 7th Harmonic Filter Capacitor Voltage (kV) Maximum TCR Line current (kA) Maximum TCR Thyristor current (kA) 1 0,4760 0,9582 0,4296 1,0245 26,7383 0,7590 2 0,1383 0,5457 0,0927 0,5009 33,7312 0,9013 3 0,1276 0,8337 0,0832 0,8152 27,5715 0,7833 4 0,2920 0,4659 0,2629 0,4559 39,4042 0,6918 5 0,1333 0,8257 0,0877 0,8005 1,4378 1,6126 6 0,1260 0,8171 0,0826 0,7959 1,7268 1,8834 7 0,1277 0,8336 0,0832 0,8151 1,0207 1,0602 8 0,1300 0,8090 0,0855 0,7799 2,5117 1,8673 9 0,1266 0,8253 0,0828 0,8054 1,1658 1,1886 10 0,1277 0,8336 0,0832 0,8151 1,0207 1,0602 11 0,1303 0,8294 0,0853 0,8070 1,0265 0,7659 12 0,1281 0,8252 0,0836 0,8029 1,2619 1,0690 Fig.1.5 Fault cases simulated in PSCAD concerning three phase connections Fig.1.6 Fault cases simulated in PSCAD concerning one phase and two thyristor terminal connections belonging different phases Fig.1.7 Fault cases simulated in PSCAD concerning three thyristor terminals belonging different phases
  • 5. Proposal Technique For An Static Var Compensator www.iosrjournals.org 5 | Page 1.8 Reactor Design Reactor design for the SVC TCR and shunt filters require special attention to current harmonics and voltage harmonics levels because dissipations in the reactors may be higher than the standard shunt reactors. The Standard IEC 289 [15] gives the definitions and suggestions for shunt reactors. IEEE standards [10-14] give detailed information on reactors and their requirements. IEEE Std C57-120-1991 [14] contains the loss calculations while [12] proposes the test procedures for reactors. The following should be conducted by the customer to the manufacturer when a reactor is to be designed: Standard (generally IEC 60289), air-cored / iron cored, Frequency, Rated voltage (line-line or phase, rms, default IEC 38), Max.continuous operating voltage (kV), Rated inductance per phase (mH), Rated continuous current (kA), Max. continuous current (kA), TDD, Short circuit power before reactor, Outdoor/indoor installation, Insulation class, Cooling type, Maximum ambient temperature, Tuning frequency (If connected in a shunt filter, Hz), Quantity and construction details (including terminal connections and mounting style such as top-to-top or independent). The reactor ratings should be verified by a power system simulation tool. In the simulation, worst case scenarios such as misfiring (where conduction per thyristor is longer than 180o) and short circuits can be investigated. The manufacturers determine the minimum safe distance to other magnetic material and closed loop conductors. These magnetic clearances around the reactor depend on the individual reactor design and. should be taken into account in the layout of the overall system. 1.9 Harmonic Filter Design The SVC topology is important in the decision for filtering. The complete SVC topology should be selected before starting the frequency response analysis. 1.9.1 Frequency Response of the Filters Thyristor controlled reactor (TCR) acts as a harmonic current source and produces its own odd harmonic current components (3 rd , 5 th , 7 th , 9 th , 11 th , etc.) for symmetrical triggering in the steady-state. However, during control, firing angle will change from positive half-cycle to negative half-cycle resulting in production of even harmonics (2 nd , 4 th , etc.). These even harmonics are taken as temporary overloads on filter reactors and capacitors. In a delta connected TCR, triple harmonics do not appear in the line currents for symmetrical triggering in the steady state. They will circulate through the delta connected reactor bank. However, in transient state owing to control, unbalanced portion of triple harmonics will be reflected to the line side. These temporary overloads on filter elements are taken into account by safety margins in the design. An important phenomenon of TCR operation during firing angle control from positive half-cycle to negative half-cycle is the generation of direct current component. This may move the magnetic operating point on the B-H characteristics of SVC transformer and thyristor controlled reactors for the iron core case. Therefore, the linearity of TCR core is essential for iron-core solution. Simulations should be carried out according to this assumption in order to find out harmonic loadings on filter elements. Filter circuits can be designed according to the rules described in IEC 61642 [16]. The loads are taken as harmonic current sources in simulation, which inject 1.0 A rms at all harmonic frequencies. 1.10 TCR Control Thyristor controlled reactor is a variable susceptance that can be controlled by triggering delay of the thyristor gate signals. The control system varies according to the desired method of TCR implementation. These methods are discussed in the below section. 1.11 Control System Overview Control system that is only designed for reactive power compensation is a simple controller that calculates the necessary firing angle of each phase. It is also acceptable if all three phases are fired with the same angle. This type of control achieves reactive power compensation; however it is capable of neither load balancing nor voltage regulation. Control system design can easily be implemented by using proportional- integral (PI) controller in such an SVC. This type of control can be seen in Fig.1.8. In order to be able to achieve load balancing, the negative sequence of the load current must be removed entirely. Reactive current component calculation and reactive power calculations can be evaluated by using 50 Hz averaging. This method will cause responses in the TCR because 50Hz averaging method will require time to take the average value of the signal.
  • 6. Proposal Technique For An Static Var Compensator www.iosrjournals.org 6 | Page Fig.1.8 Simple reactive power compensation by PI controller Fig.1.9 Reactive power compensation with load balancing by PI controller Fig.1.10 Flicker Compensation System with feed-forward and feed-back control 1.12 Thyristor Valve Control and Misfiring Ideal TCR line currents are 90 o displaced from the line voltage and they are symmetrical and balanced if the firing delay angle is in the range of 90 o -180 o for positive half cycle and 270 o -360 o in the negative half cycle. These are the safe operating regions of TCR, which are the 2 nd and the 4 th regions shown in Fig.1.11. Whenever the conduction angle of a thyristor exceeds 180 o , a DC current component exists. In a non-ideal TCR which includes an internal resistor, the firing delay angle can be reduced below 90 o . The exact angle can be calculated from the inductive reactance and the resistance of the TCR. Fig.1.11. Firing Delay Angle (α) versus TCR line voltage. The safe operating regions 2 and 4 of TCR are marked and Unsafe operating regions 1and 3 are marked. II. Conclusion: From the implemented tests and procedure, it can be concluded that the design of SVC in transmission lines offers controlling the power flow in an efficient manner. The TCR simulation for a 1 kV 1,5 MVAr TCR + 0,75 kVAr Filter installation with a short circuit 525 MVA was tested and shown in this paper
  • 7. Proposal Technique For An Static Var Compensator www.iosrjournals.org 7 | Page using PSCAD “Multirun” simulator. In order to be able to achieve load balancing, the negative sequence of the load current must be eliminated completely. Control system design can easily be implemented by using proportional-integral (PI) controller in such an SVC. References [1] T.J.E. Miller, “Reactive Power Control In Electric Systems,”, John Wiley&Sons, 1982. [2] J.Arrilaga, N.R. Watson, “Power System Harmonics”, Wiley, 1982 [3] “IEEE Guide for the Functional Specification of Transmission Static Var Compensators” IEEE Std 1031-1991) [4] “IEEE Guide for the Functional Specification of Transmission Static Var Compensators” IEEE Std 1031-2000 (Revision ofIEEE Std 1031-1991) [5] M.V. Utalay, “Design and Implementation of a Medium Voltage Thyristor Controlled Reactor”, MSc. Thesis, METU, Jan.1996 [6] Semikron Power Electronics Catalogue,Semikron Inc. Germany, 10/1998. [7] Lawatsch, H.M.; Vitins, J.; “Protection of thyristors against overvoltage with breakover diyotes”, IEEE Transactions on Industry Applications Volume 24, Issue 3, May-June 1988 pp. 444 – 448 [8] TS 831, “Standard Voltages in THE Distribution Systems” , 1979 [9] “Effects of Temperature on Thyristor Performance” Application Note AN4870, Dynex Semiconductors, January 2000. [10] ANSI/IEEE Std. C37.109, “IEEE Guide for the Protection of Shunt Reactors” 1988 [11] IEEE Std. C57-114, “IEEE Seismic Guide for Power Transformers and Reactors”, 1990 [12] IEEE Standard Requirements,Terminology, and Test Code for Shunt Reactors Rated Over 500 kVA, IEEE Std. C57.21-1990 [13] IEEE Std. C57-125, “IEEE Guide for Failure Investigation, Documentation,and Analysis for Power Transformers and Shunt Reactors” 1991 [14] “IEEE Loss Evalution Guide for Power Transformers and Reactors” IEEE Std C57-120-1991 [15] IEC 60289 “Reactors”,1988 [16] IEC 61642 Industrial a.c. Networks Affected by Harmonics - Application of Filters and Shunt Capacitors