56 International Journal for Modern Trends in Science and Technology
Volume: 2 | Issue: 10 | October 2016 | ISSN: 2455-3778IJMTST
Modeling Optimization Voltage Index
Unified Power Flow Controller
Equivalent Impedance
P. Priyadarsini1
| Sri M. Sridhar2
1PG Scholar, Department of EEE, Geethanjali College of Engineering & Technology, Kurnool, AP, India.
2Assistant Professor, Department of EEE, Geethanjali College of Engineering & Technology, Kurnool,
AP, India.
This paper presents an active-reactive power control strategy for voltage source converters (VSCs) based on
derivation of the direct and quadrature components of the VSC output current. The proposed method utilizes
a multivariable proportional-integral controller and provides almost completely decoupled control capability
of the active and reactive power with almost full disturbance rejection due to step changes in the power
exchanged between the VSC and the grid. It also imposes fast transient response and zero steady-state error
as compared to the conventional power control approaches. The applicability of the proposed power control
strategy for providing the robust stability of the system against the uncertainties of the load parameters is
also investigated. The superiority of the proposed control strategy over conventional approaches in the new
condition of supplying the load is demonstrated. The theoretical aspects of the proposed multivariable-based
power control strategy and the conventional approaches are reviewed and simulation results are presented
in two separate sections. MATLAB/Simulink 2009a is used to simulate different scenarios of the simulation.
KEYWORDS: Unified power flow controller, equivalent impedance modeling, optimization, voltage index.
Copyright © 2016 International Journal for Modern Trends in Science and Technology
All rights reserved.
I. INTRODUCTION
Utilizing renewable energies such as distributed
generation (DG) has become a great concern for
utility grids to provide sufficient electrical energy to
supply domestic and industrial requirements in a
clean world. There are many types of these
generations, including wind energy [1–5] and
photovoltaic and fuel cells [6–9]. Many of these
technologies adopt voltage source converters
(VSCs) as an interface of distributed generators
because of the nature of the output voltage. VSCs
give us advantages including easy controllability
and the capability to control circuit parameters like
the voltage, current, or output power of the DG
[10–15]. There are three types of control strategies
adopted for the VSCs: 1) active-reactive power
control (called PQ control), 2) active power-voltage
control (PV control), and 3) voltage-frequency
control (VF control). Many approaches utilized
proportional-integral (PI)-based controllers to
regulate the target variable at the desired level. PI
controllers are universally known because of their
simple implementation and tuning and for
providing fast dynamics and zero steady-state error
[16]. These controllers are always used for various
applications of current regulation [17–23].
Regulating a variable in a rotating reference frame
(RRF) is defined when time-varying variables (AC
variables) are transferred to an orthogonal space
like the dq0 domain, in which the frame rotates
with an arbitrary angular speed of ω. This makes
the variables appear as time-invariant quantities.
Therefore, the designed controller can act like a
DC/DC converter with zero steady-state error by
providing an infinite gain at the operating point. In
these methods, the controller should have the
capability of decoupling the dq axis components of
one variable such that the unwanted disturbances
applied to one axis do not generate significant
transients on the other one. This capability
provides independent control of the desired
variable, which could be the output current or the
power of a converter. In [24], a multivariable
ABSTRACT
57 International Journal for Modern Trends in Science and Technology
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent Impedance
PI-based dq current control strategy based on a
different design procedure than the conventional
approaches [25] was proposed to reach the desired
decoupling between the two d and q axis
components of the line current. The presented
method provides much less transient effect against
incoming disturbances and zero steady-state error
on tracking the reference values; moreover, it has a
simple structure and is easy to implement.
However, in the utility grids, due to changes in the
demanded power imposed by the loads, what is
important is that the distributed generators with
power electronic interface could supply the
requested power. This could be possible by
applying the appropriate methods. The decoupling
capability between the two d and q axis
components of the current is also applicable for the
active and reactive power exchanged between the
VSC and grid. In [26], a classical droop control
method was utilized to achieve the grid impedance.
The virtual real and reactive power frame
transformation was then used to result in
decoupling power control capability. Wei and Kao
[27] proposed a power control strategy based on
placing a virtual inductance at the inverter output
in a low-voltage microgrid. The impedance voltage
droop and the local load effects were considered to
prevent the coupling between the active and
reactive output power, but one of the problems of
the conventional droop control method is the
assumption that the output impedance is mainly
inductive. To avoid using extra output inductance,
fast control loops were added to the droop method
[28]. In [29], a control scheme was utilized that
used the voltage and current variation at the point
of common coupling due to small changes of the
VSI power for estimating the grid impedance so
that power flow control could be possible in all
conditions of the grid including on-grid or
autonomous mode.
In this paper, the application of a multivariable
PI-controller in the power control strategy for
VSC-based DG has been presented. In the
proposed method, first the reference values of
direct and quadrature components of the converter
output current are determined directly from
specified power references. Because these values
are proportional to the active and reactive output
power, respectively, a controller is then utilized to
regulate the output power at the desired level. The
capability of the designed controller has been
shown from various points of view: 1) improvement
of the transient response, 2) zero steady-state error
in tracking the power reference values, 3)
capability of minimizing the effect of step changing
in output active or reactive power on one another
for decoupling control capability of these powers,
and 4) robust stability of the controller against
uncertainties of load parameters.
MATLAB/Simulink 2009a has been used to
simulate the different scenarios of the simulation.
II. RELATED WORK
For the purpose of this article, we shall define
power quality problems as: ‘Any power problem
that results in failure or disoperation of customer
equipment, manifests itself as an economic burden
to the user, or produces negative impacts onthe
environment.’
When applied to the container crane industry, the
power issues which degrade power quality include:
 Power Factor
 Harmonic Distortion
 Voltage Transients
 Voltage Sags or Dips
 Voltage Swells
The AC and DC variable speed drives utilized on
board container cranes are significant contributors
to total harmonic current and voltage distortion.
Whereas SCR phase control creates the desirable
average power factor, DC SCR drives operate at less
than this. In addition, line notching occurs when
SCR’s commutate, creating transient peak recovery
voltages that can be 3 to 4 times the nominal line
voltage depending upon the system impedance and
the size of the drives. The frequency and severity of
these power system disturbances varies with the
speed of the drive. Harmonic current injection by
AC and DC drives will be highest when the drives
are operating at slow speeds. Power factor will be
lowest when DC drives are operating at slow speeds
or during initial acceleration and deceleration
periods, increasing to its maximum value when the
SCR’s are phased on to produce rated or base
speed. Above base speed, the power factor
essentially remains constant. Unfortunately,
container cranes can spend considerable time at
low speeds as the operator attempts to spot and
land containers. Poor power factor places a greater
kVA demand burden on the utility or
engine-alternator power source. Low power factor
loads can also affect the voltage stability which can
ultimately result in detrimental effects on the
Life of sensitive electronic equipment or even
intermittent malfunction. Voltage transients
created by DC drive SCR line notching, AC drive
voltage chopping, and high frequency harmonic
voltages and currents are all significant sources of
58 International Journal for Modern Trends in Science and Technology
Volume: 2 | Issue: 10 | October 2016 | ISSN: 2455-3778IJMTST
noise and disturbance to sensitive electronic
equipment
It has been our experience that end users often
do not associate power quality problems with
Container cranes, either because they are totally
unaware of such issues or there was no economic
Consequence if power quality was not addressed.
Before the advent of solid-state power supplies,
Power factor was reasonable, and harmonic
current injection was minimal. Not until the crane
Population multiplied, power demands per crane
increased, and static power conversion became the
way of life, did power quality issues begin to
emerge. Even as harmonic distortion and power
Factor issues surfaced, no one was really prepared.
Even today, crane builders and electrical drive
System vendors avoid the issue during competitive
bidding for new cranes. Rather than focus on
Awareness and understanding of the potential
issues, the power quality issue is intentionally or
unintentionally ignored. Power quality problem
solutions are available. Although the solutions are
not free, in most cases, they do represent a good
return on investment. However, if power quality is
not specified, it most likely will not be delivered.
Power quality can be improved through:
 Power factor correction,
 Harmonic filtering,
 Special line notch filtering,
 Transient voltage surge suppression,
 Proper earthing systems.
In most cases, the person specifying and/or
buying a container crane may not be fully aware of
the potential power quality issues. If this article
accomplishes nothing else, we would hope to
provide that awareness.
In many cases, those involved with specification
and procurement of container cranes may not be
cognizant of such issues, do not pay the utility
billings, or consider it someone else’s concern. As a
result, container crane specifications may not
include definitive power quality criteria such as
power factor correction and/or harmonic filtering.
Also, many of those specifications which do require
power quality equipment do not properly define the
criteria. Early in the process of preparing the crane
specification:
 Consult with the utility company to
determine regulatory or contract
requirements that must be satisfied, if any.
 Consult with the electrical drive suppliers
and determine the power quality profiles
that can be expected based on the drive
sizes and technologies proposed for the
specific project.
 Evaluate the economics of power quality
correction not only on the present
situation, but consider the impact of future
utility deregulation and the future
development plans for the terminal
III. IMPLEMENTATION
3.1 System description and modeling:
A single-line diagram of the three-phase test
system adopted for evaluating the performance of
the proposed method is shown in Figure 1. In this
system, a distributed generation unit is connected
to the grid through a VSC interface module, with a
series line reactor as a filter to reduce the
harmonics generated due to the VSC and finally a
coupling transformer to reach the grid voltage level.
The DC side voltage of the VSC considered is
constant like a battery. The internal resistance and
inductance of the filter are considered as Rt and Lt
, respectively. The inductance of the coupling
transformer is latent in the filter inductance. The
numerical values of the test system elements are
given in the Table.
Figure 1. One-line diagram of the test system.
3.2 Mathematical model of the test system
In this section, the mathematical model of the
three-phase test system and its structure diagram
is derived [30]. Based on Figure 1, which shows the
structure of the test system, writing the KVL from
59 International Journal for Modern Trends in Science and Technology
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent Impedance
the PCC bus to the converter terminal results in
the dynamic equation of the VSC in the abc frame
as below:
To design an applicable PI-based current controller
in the rotating reference frame, Eq. (1), which is the
dynamic representation of the system in the
stationary rotating frame, should transform to the
dq reference frame that rotates by the angular
speed of ω. This transform could be done by the
following expression:
Eq. (2) transforms any abc quantities into the
rotating frame, where Ks is defined as below:
Therefore, the dynamic equation of the system in
the RRF could result as in Eq. (4), in which the zero
sequence has been neglected.
The real and imaginary parts of Eq. (4) could be
separated to achieve the dynamic equation of the
system on the d and q direct axis in the RRF, such
as in Eqs. (5) and (6). The block diagram of the test
system is obtained in the dq frame by adopting
Eqs. (5) and (6) and it is shown in Figure 2.
Figure 2. Structure diagram of the test system model [3].
IV. EXPERIMENTAL WORK
The control results by different converter
structures and control strategies are validated on a
downscale dc–ac converter. As shown in Fig. 3, the
circuit configurations and setup photo are both
illustrated. A three-phase two-level converter with
corresponding LCL filter is used to interconnect
two dc voltage sources and a programmable
three-phase ac voltage source. The detail
parameters of the experimental setup are shown in
Table III. It is noted that the converter is controlled
to operate at the inverter mode, where the active
power is flowing from the dc source to the ac
source. By opening and closing a switch shown in
Fig. 3(a), the converter can be shifted between the
typical three-wire system and four-wire system
with the zero-sequence current path. The
amplitude of the phase A voltage in the pro-
grammable ac source is adjusted to 0.1 p.u. (22
Vrms) in order to establish an adverse unbalanced
condition.
The control performance of the converter with
the three-wire structure is shown in Fig. 4, where
the given conditions and the two control strategies
mentioned in Figs. 5 and 7 are applied,
respectively. It can be seen that the experimental
results agree well with the analysis and simulation
results, where either the significant power
oscillations or the overloaded current in the faulty
phase are presented After enabling the zero current
path and proposed controls, the performances of
the given converter are shown again in Fig. 17,
where the same conditions and two control
strategies mentioned in Figs. 11 and 13 are
applied, respectively. It can be seen that the
experimental results also agree well with the
simulation results, where the power oscillations
are much more reduced or even totally cancelled;
meanwhile, the current stress in the faulty phase is
significantly relieved. These critical performances
are hard to be achieved by a single three-wire
converter structure using existing control
strategies.
The capability to control the reactive power is
also a critical performance for the converter under
the unbalanced ac source, the proposed two
control methods are also tested under the
conditions to deliver the inductive/capacitive
reactive power. As shown in Figs. 18 and 19, the No
P & No Q oscillation control and No
negative-sequence current & No P oscillation control
are applied, respectively, to deliver the inductive
and capacitive reactive power with phase A voltage
dipping to 0.5 p.u. It can be seen that the
advantages of the smaller/eliminated power
oscillation and the relieved current loading in the
faulty phase are still maintained. It is noted that
the power delivering under the unbalanced AC
60 International Journal for Modern Trends in Science and Technology
Volume: 2 | Issue: 10 | October 2016 | ISSN: 2455-3778IJMTST
source should give priority to the current limits of
the power devices. This topic has been well
discussed in the existing control methods based on
the three-wire structure [30], and it is also an
important consideration in the proposed control
methods which utilize the zero-sequence
components.
Fig. 3. Experimental control performance of the converter
in Fig. 3(a) with only three wires (units are nominalized by
parameters in Table III, reference given: Pref = 0.5 p.u., Qref
= 0 p.u., ac source condition: amplitude of the phase voltage
VA = 0.1 p.u., VB =VC = 1 p.u.). (a) No negative-sequence
current control (b) No P oscillation control.
V. CONCLUSION
In a typical three-phase three-wire converter
structure, there are four current control freedoms,
and it may be not enough to achieve satisfactory
performances under the unbalanced ac source,
because either significantly the oscillated power or
the overloaded current will be presented. In the
three phase converter structure with the zero
sequence current path, there are six current
control freedoms. The extra two control freedoms
coming from the zero sequence current can be
utilized to extend the controllability of the
converter and improve the control performance
under the unbalanced ac source. By the proposed
fuzzy logic control strategies, it is possible to totally
cancel the oscillation in both the active and the
reactive power, or reduced the oscillation
amplitude in the reactive power. Meanwhile, the
current amplitude of the faulty phase is
significantly relieved without further increasing the
current amplitude in the normal phases. The
advantage and features of the proposed controls
can be still maintained under various conditions
when delivering the reactive power. The analysis
and proposed control methods are well agreed by
experimental validations.
REFERENCES
[1] F. Blaabjerg, M. Liserre, and K. Ma, Power
electronics converters for wind turbine systems,
IEEE Trans. Ind. Appl., vol. 48, no. 2, pp. 708– 719,
Mar./Apr. 2012
[2] R. Teodorescu, M. Liserre, and P. Rodriguez, Grid
Converters for Photovoltaic and Wind Power
Systems. New York, NY, USA: Wiley-IEEE, 2011.
[3] J. Rocabert, G. M. S. Azevedo, A. Luna, J. M.
Guerrero, J. I. Candela, and P. Rodriguez, Intelligent
connection agent for three-phase grid-connected
microgrids, IEEE Trans. Power Electron, vol. 26, no.
10, pp. 2993–3005, Oct. 2011.
[4] J. W. Kolar and T. Friedli, ―The essence of
three-phase PFC rectifier systems— Part I,IEEE
Trans. Power Electron., vol. 28, no. 1, pp. 176– 198,
Jan. 2013.
[5] J. Hu, L. Shang, Y. He, and Z. Z. Zhu, ―Direct active
and reactive power regulation of grid-connected
dc/ac converters using sliding mode control
approach,‖ IEEE Trans. Power Electron., vol. 26, no.
1, pp. 210–222, Jan. 2011.
[6] C. Wessels, F. Gebhardt, and F. W. Fuchs, ―Fault
ridethrough of a DFIG wind turbine using a dynamic
voltage restorer during symmetrical and
asymmetrical grid faults, IEEE Trans. Power
Electron., vol. 26, no. 3, pp. 807–815, Mar. 2011.
[7] F. Aghili, ―Fault-tolerant torque control of BLDC
motors,IEEE Trans. Power Electron., vol. 26, no. 2,
pp. 355–363, Feb. 2011.
[8] Y. Xiangwu, G. Venkataramanan, W. Yang, D. Qing,
and Z. Bo, ―Gridfault tolerant operation of a DFIG
wind turbine generator using a passive resistance
network, IEEE Trans. Power Electron., vol. 26, no.
10, pp. 2896–2905, Oct. 2011.
[9] B. A. Welchko, T. A. Lipo, T. M. Jahns, and S. E.
Schulz, ―Fault tolerant three-phase AC motor drive
topologies: A comparison of features, cost, and
limitations, IEEE Trans. Power Electron., vol. 19, no.
4, pp. 1108– 1116, Jul. 2004.

Contenu connexe

Tendances

A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
ijtsrd
 

Tendances (20)

A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
 
Implementation of UPFC for Improvement of Power Stability
Implementation of UPFC for Improvement of Power StabilityImplementation of UPFC for Improvement of Power Stability
Implementation of UPFC for Improvement of Power Stability
 
Indian wind energy status
Indian wind energy statusIndian wind energy status
Indian wind energy status
 
IRJET- Improving Power Quality by using MC-UPQC
IRJET- Improving Power Quality by using MC-UPQCIRJET- Improving Power Quality by using MC-UPQC
IRJET- Improving Power Quality by using MC-UPQC
 
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
 
An Approach of D-STATCOM in Single Phase System with Power Quality Improvement
An Approach of D-STATCOM in Single Phase System with Power Quality ImprovementAn Approach of D-STATCOM in Single Phase System with Power Quality Improvement
An Approach of D-STATCOM in Single Phase System with Power Quality Improvement
 
Comparison of facts devices for two area power system stability enhancement u...
Comparison of facts devices for two area power system stability enhancement u...Comparison of facts devices for two area power system stability enhancement u...
Comparison of facts devices for two area power system stability enhancement u...
 
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
 
Enhancement of power quality in distribution system by using D-STATCOM
Enhancement of power quality in distribution system by using D-STATCOMEnhancement of power quality in distribution system by using D-STATCOM
Enhancement of power quality in distribution system by using D-STATCOM
 
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
 
B04931120
B04931120B04931120
B04931120
 
www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 
Power Quality Enhancement using DSTATCOM by Immune Feedback Control Algorithm
Power Quality Enhancement using DSTATCOM by Immune Feedback Control AlgorithmPower Quality Enhancement using DSTATCOM by Immune Feedback Control Algorithm
Power Quality Enhancement using DSTATCOM by Immune Feedback Control Algorithm
 
TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (...
TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (...TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (...
TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (...
 
Reparation of Inductive Power in Power System by the use of FACTS devices
Reparation of Inductive Power in Power System by the use of FACTS devicesReparation of Inductive Power in Power System by the use of FACTS devices
Reparation of Inductive Power in Power System by the use of FACTS devices
 
Online voltage stability margin assessment
Online voltage stability margin assessmentOnline voltage stability margin assessment
Online voltage stability margin assessment
 
26 k. subramanian
26 k. subramanian26 k. subramanian
26 k. subramanian
 
Ann based voltage stability margin assessment
Ann based voltage stability margin assessmentAnn based voltage stability margin assessment
Ann based voltage stability margin assessment
 
Power compensation for vector-based current control of a modular multilevel c...
Power compensation for vector-based current control of a modular multilevel c...Power compensation for vector-based current control of a modular multilevel c...
Power compensation for vector-based current control of a modular multilevel c...
 
Segan
SeganSegan
Segan
 

En vedette

Mapaconceptual
MapaconceptualMapaconceptual
Mapaconceptual
37sole
 
教案(第三教節) 投影片
教案(第三教節) 投影片教案(第三教節) 投影片
教案(第三教節) 投影片
s0914448
 
INTERPRETACION PREVIA DE LA ESCENA DEL SUCESO Slideshare armando goyo
INTERPRETACION PREVIA DE LA ESCENA DEL SUCESO  Slideshare armando goyoINTERPRETACION PREVIA DE LA ESCENA DEL SUCESO  Slideshare armando goyo
INTERPRETACION PREVIA DE LA ESCENA DEL SUCESO Slideshare armando goyo
armandopoyo
 
Síntesis de proteínas
Síntesis de proteínasSíntesis de proteínas
Síntesis de proteínas
Ramón Castro
 

En vedette (20)

Evoluzione economia novembre2004
Evoluzione economia novembre2004Evoluzione economia novembre2004
Evoluzione economia novembre2004
 
Jenny zulay vii
Jenny zulay viiJenny zulay vii
Jenny zulay vii
 
2016-05-13 18-35-14
2016-05-13 18-35-142016-05-13 18-35-14
2016-05-13 18-35-14
 
Ikea
IkeaIkea
Ikea
 
Hello join me
Hello join meHello join me
Hello join me
 
Flashback Byline
Flashback BylineFlashback Byline
Flashback Byline
 
Parasha 6 toldot
Parasha 6  toldotParasha 6  toldot
Parasha 6 toldot
 
Ikea
IkeaIkea
Ikea
 
Slideshare
SlideshareSlideshare
Slideshare
 
Mich ....
Mich ....Mich ....
Mich ....
 
Trade Test
Trade TestTrade Test
Trade Test
 
Ain El Nombre
Ain El NombreAin El Nombre
Ain El Nombre
 
Mapaconceptual
MapaconceptualMapaconceptual
Mapaconceptual
 
De cara con el atlantico
De cara con el atlanticoDe cara con el atlantico
De cara con el atlantico
 
教案(第三教節) 投影片
教案(第三教節) 投影片教案(第三教節) 投影片
教案(第三教節) 投影片
 
Periodismo digital miguel u.
Periodismo digital miguel u.Periodismo digital miguel u.
Periodismo digital miguel u.
 
INTERPRETACION PREVIA DE LA ESCENA DEL SUCESO Slideshare armando goyo
INTERPRETACION PREVIA DE LA ESCENA DEL SUCESO  Slideshare armando goyoINTERPRETACION PREVIA DE LA ESCENA DEL SUCESO  Slideshare armando goyo
INTERPRETACION PREVIA DE LA ESCENA DEL SUCESO Slideshare armando goyo
 
Síntesis de proteínas
Síntesis de proteínasSíntesis de proteínas
Síntesis de proteínas
 
2016-05-13 18-36-30
2016-05-13 18-36-302016-05-13 18-36-30
2016-05-13 18-36-30
 
Trisngulo magico abarcxa mikelddd
Trisngulo magico abarcxa mikeldddTrisngulo magico abarcxa mikelddd
Trisngulo magico abarcxa mikelddd
 

Similaire à Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent Impedance

Optimization Technique for Power Quality Improvement using DSTATCOM Neural Ne...
Optimization Technique for Power Quality Improvement using DSTATCOM Neural Ne...Optimization Technique for Power Quality Improvement using DSTATCOM Neural Ne...
Optimization Technique for Power Quality Improvement using DSTATCOM Neural Ne...
ijtsrd
 
A Review on Power Quality Issues and their Mitigation Techniques in Microgrid...
A Review on Power Quality Issues and their Mitigation Techniques in Microgrid...A Review on Power Quality Issues and their Mitigation Techniques in Microgrid...
A Review on Power Quality Issues and their Mitigation Techniques in Microgrid...
ijtsrd
 
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
eSAT Journals
 
Improved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading ConditionsImproved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading Conditions
IJMTST Journal
 
Application of Unified Power Flow Controller in Nigeria Power System for Impr...
Application of Unified Power Flow Controller in Nigeria Power System for Impr...Application of Unified Power Flow Controller in Nigeria Power System for Impr...
Application of Unified Power Flow Controller in Nigeria Power System for Impr...
ijtsrd
 

Similaire à Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent Impedance (20)

IRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
IRJET- Level of Service & Throughput Maximization at Operational Toll PlazasIRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
IRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
 
IRJET- Different Control Strategies for Power Control of Voltage Source Conve...
IRJET- Different Control Strategies for Power Control of Voltage Source Conve...IRJET- Different Control Strategies for Power Control of Voltage Source Conve...
IRJET- Different Control Strategies for Power Control of Voltage Source Conve...
 
Mitigation of Voltage Imbalance in A Two Feeder Distribution System Using Iupqc
Mitigation of Voltage Imbalance in A Two Feeder Distribution System Using IupqcMitigation of Voltage Imbalance in A Two Feeder Distribution System Using Iupqc
Mitigation of Voltage Imbalance in A Two Feeder Distribution System Using Iupqc
 
Optimization Technique for Power Quality Improvement using DSTATCOM Neural Ne...
Optimization Technique for Power Quality Improvement using DSTATCOM Neural Ne...Optimization Technique for Power Quality Improvement using DSTATCOM Neural Ne...
Optimization Technique for Power Quality Improvement using DSTATCOM Neural Ne...
 
Enhanced dynamic performance of grid feeding distributed generation under va...
Enhanced dynamic performance of grid feeding distributed  generation under va...Enhanced dynamic performance of grid feeding distributed  generation under va...
Enhanced dynamic performance of grid feeding distributed generation under va...
 
G046033742
G046033742G046033742
G046033742
 
www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 
Distribution Network Power Quality Improvement by D-STATCOM & DVR Under Vario...
Distribution Network Power Quality Improvement by D-STATCOM & DVR Under Vario...Distribution Network Power Quality Improvement by D-STATCOM & DVR Under Vario...
Distribution Network Power Quality Improvement by D-STATCOM & DVR Under Vario...
 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultsComparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
 
A Review on Power Quality Issues and their Mitigation Techniques in Microgrid...
A Review on Power Quality Issues and their Mitigation Techniques in Microgrid...A Review on Power Quality Issues and their Mitigation Techniques in Microgrid...
A Review on Power Quality Issues and their Mitigation Techniques in Microgrid...
 
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
 
Y04408126132
Y04408126132Y04408126132
Y04408126132
 
A044040108
A044040108A044040108
A044040108
 
Improved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading ConditionsImproved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading Conditions
 
Control strategies for seamless transfer between the grid-connected and isla...
Control strategies for seamless transfer between  the grid-connected and isla...Control strategies for seamless transfer between  the grid-connected and isla...
Control strategies for seamless transfer between the grid-connected and isla...
 
IRJET- Voltage Stability Improvement and Reactive Power Compensation using ST...
IRJET- Voltage Stability Improvement and Reactive Power Compensation using ST...IRJET- Voltage Stability Improvement and Reactive Power Compensation using ST...
IRJET- Voltage Stability Improvement and Reactive Power Compensation using ST...
 
Gr3412151231
Gr3412151231Gr3412151231
Gr3412151231
 
P-Q Theory Based UPQC for Reactive Power Compensation with UCAP
P-Q Theory Based UPQC for Reactive Power Compensation with UCAPP-Q Theory Based UPQC for Reactive Power Compensation with UCAP
P-Q Theory Based UPQC for Reactive Power Compensation with UCAP
 
Application of Unified Power Flow Controller in Nigeria Power System for Impr...
Application of Unified Power Flow Controller in Nigeria Power System for Impr...Application of Unified Power Flow Controller in Nigeria Power System for Impr...
Application of Unified Power Flow Controller in Nigeria Power System for Impr...
 
Power Quality Improvement Using GUPFC
Power Quality Improvement Using GUPFCPower Quality Improvement Using GUPFC
Power Quality Improvement Using GUPFC
 

Dernier

Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
amitlee9823
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 

Dernier (20)

PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 

Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent Impedance

  • 1. 56 International Journal for Modern Trends in Science and Technology Volume: 2 | Issue: 10 | October 2016 | ISSN: 2455-3778IJMTST Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent Impedance P. Priyadarsini1 | Sri M. Sridhar2 1PG Scholar, Department of EEE, Geethanjali College of Engineering & Technology, Kurnool, AP, India. 2Assistant Professor, Department of EEE, Geethanjali College of Engineering & Technology, Kurnool, AP, India. This paper presents an active-reactive power control strategy for voltage source converters (VSCs) based on derivation of the direct and quadrature components of the VSC output current. The proposed method utilizes a multivariable proportional-integral controller and provides almost completely decoupled control capability of the active and reactive power with almost full disturbance rejection due to step changes in the power exchanged between the VSC and the grid. It also imposes fast transient response and zero steady-state error as compared to the conventional power control approaches. The applicability of the proposed power control strategy for providing the robust stability of the system against the uncertainties of the load parameters is also investigated. The superiority of the proposed control strategy over conventional approaches in the new condition of supplying the load is demonstrated. The theoretical aspects of the proposed multivariable-based power control strategy and the conventional approaches are reviewed and simulation results are presented in two separate sections. MATLAB/Simulink 2009a is used to simulate different scenarios of the simulation. KEYWORDS: Unified power flow controller, equivalent impedance modeling, optimization, voltage index. Copyright © 2016 International Journal for Modern Trends in Science and Technology All rights reserved. I. INTRODUCTION Utilizing renewable energies such as distributed generation (DG) has become a great concern for utility grids to provide sufficient electrical energy to supply domestic and industrial requirements in a clean world. There are many types of these generations, including wind energy [1–5] and photovoltaic and fuel cells [6–9]. Many of these technologies adopt voltage source converters (VSCs) as an interface of distributed generators because of the nature of the output voltage. VSCs give us advantages including easy controllability and the capability to control circuit parameters like the voltage, current, or output power of the DG [10–15]. There are three types of control strategies adopted for the VSCs: 1) active-reactive power control (called PQ control), 2) active power-voltage control (PV control), and 3) voltage-frequency control (VF control). Many approaches utilized proportional-integral (PI)-based controllers to regulate the target variable at the desired level. PI controllers are universally known because of their simple implementation and tuning and for providing fast dynamics and zero steady-state error [16]. These controllers are always used for various applications of current regulation [17–23]. Regulating a variable in a rotating reference frame (RRF) is defined when time-varying variables (AC variables) are transferred to an orthogonal space like the dq0 domain, in which the frame rotates with an arbitrary angular speed of ω. This makes the variables appear as time-invariant quantities. Therefore, the designed controller can act like a DC/DC converter with zero steady-state error by providing an infinite gain at the operating point. In these methods, the controller should have the capability of decoupling the dq axis components of one variable such that the unwanted disturbances applied to one axis do not generate significant transients on the other one. This capability provides independent control of the desired variable, which could be the output current or the power of a converter. In [24], a multivariable ABSTRACT
  • 2. 57 International Journal for Modern Trends in Science and Technology Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent Impedance PI-based dq current control strategy based on a different design procedure than the conventional approaches [25] was proposed to reach the desired decoupling between the two d and q axis components of the line current. The presented method provides much less transient effect against incoming disturbances and zero steady-state error on tracking the reference values; moreover, it has a simple structure and is easy to implement. However, in the utility grids, due to changes in the demanded power imposed by the loads, what is important is that the distributed generators with power electronic interface could supply the requested power. This could be possible by applying the appropriate methods. The decoupling capability between the two d and q axis components of the current is also applicable for the active and reactive power exchanged between the VSC and grid. In [26], a classical droop control method was utilized to achieve the grid impedance. The virtual real and reactive power frame transformation was then used to result in decoupling power control capability. Wei and Kao [27] proposed a power control strategy based on placing a virtual inductance at the inverter output in a low-voltage microgrid. The impedance voltage droop and the local load effects were considered to prevent the coupling between the active and reactive output power, but one of the problems of the conventional droop control method is the assumption that the output impedance is mainly inductive. To avoid using extra output inductance, fast control loops were added to the droop method [28]. In [29], a control scheme was utilized that used the voltage and current variation at the point of common coupling due to small changes of the VSI power for estimating the grid impedance so that power flow control could be possible in all conditions of the grid including on-grid or autonomous mode. In this paper, the application of a multivariable PI-controller in the power control strategy for VSC-based DG has been presented. In the proposed method, first the reference values of direct and quadrature components of the converter output current are determined directly from specified power references. Because these values are proportional to the active and reactive output power, respectively, a controller is then utilized to regulate the output power at the desired level. The capability of the designed controller has been shown from various points of view: 1) improvement of the transient response, 2) zero steady-state error in tracking the power reference values, 3) capability of minimizing the effect of step changing in output active or reactive power on one another for decoupling control capability of these powers, and 4) robust stability of the controller against uncertainties of load parameters. MATLAB/Simulink 2009a has been used to simulate the different scenarios of the simulation. II. RELATED WORK For the purpose of this article, we shall define power quality problems as: ‘Any power problem that results in failure or disoperation of customer equipment, manifests itself as an economic burden to the user, or produces negative impacts onthe environment.’ When applied to the container crane industry, the power issues which degrade power quality include:  Power Factor  Harmonic Distortion  Voltage Transients  Voltage Sags or Dips  Voltage Swells The AC and DC variable speed drives utilized on board container cranes are significant contributors to total harmonic current and voltage distortion. Whereas SCR phase control creates the desirable average power factor, DC SCR drives operate at less than this. In addition, line notching occurs when SCR’s commutate, creating transient peak recovery voltages that can be 3 to 4 times the nominal line voltage depending upon the system impedance and the size of the drives. The frequency and severity of these power system disturbances varies with the speed of the drive. Harmonic current injection by AC and DC drives will be highest when the drives are operating at slow speeds. Power factor will be lowest when DC drives are operating at slow speeds or during initial acceleration and deceleration periods, increasing to its maximum value when the SCR’s are phased on to produce rated or base speed. Above base speed, the power factor essentially remains constant. Unfortunately, container cranes can spend considerable time at low speeds as the operator attempts to spot and land containers. Poor power factor places a greater kVA demand burden on the utility or engine-alternator power source. Low power factor loads can also affect the voltage stability which can ultimately result in detrimental effects on the Life of sensitive electronic equipment or even intermittent malfunction. Voltage transients created by DC drive SCR line notching, AC drive voltage chopping, and high frequency harmonic voltages and currents are all significant sources of
  • 3. 58 International Journal for Modern Trends in Science and Technology Volume: 2 | Issue: 10 | October 2016 | ISSN: 2455-3778IJMTST noise and disturbance to sensitive electronic equipment It has been our experience that end users often do not associate power quality problems with Container cranes, either because they are totally unaware of such issues or there was no economic Consequence if power quality was not addressed. Before the advent of solid-state power supplies, Power factor was reasonable, and harmonic current injection was minimal. Not until the crane Population multiplied, power demands per crane increased, and static power conversion became the way of life, did power quality issues begin to emerge. Even as harmonic distortion and power Factor issues surfaced, no one was really prepared. Even today, crane builders and electrical drive System vendors avoid the issue during competitive bidding for new cranes. Rather than focus on Awareness and understanding of the potential issues, the power quality issue is intentionally or unintentionally ignored. Power quality problem solutions are available. Although the solutions are not free, in most cases, they do represent a good return on investment. However, if power quality is not specified, it most likely will not be delivered. Power quality can be improved through:  Power factor correction,  Harmonic filtering,  Special line notch filtering,  Transient voltage surge suppression,  Proper earthing systems. In most cases, the person specifying and/or buying a container crane may not be fully aware of the potential power quality issues. If this article accomplishes nothing else, we would hope to provide that awareness. In many cases, those involved with specification and procurement of container cranes may not be cognizant of such issues, do not pay the utility billings, or consider it someone else’s concern. As a result, container crane specifications may not include definitive power quality criteria such as power factor correction and/or harmonic filtering. Also, many of those specifications which do require power quality equipment do not properly define the criteria. Early in the process of preparing the crane specification:  Consult with the utility company to determine regulatory or contract requirements that must be satisfied, if any.  Consult with the electrical drive suppliers and determine the power quality profiles that can be expected based on the drive sizes and technologies proposed for the specific project.  Evaluate the economics of power quality correction not only on the present situation, but consider the impact of future utility deregulation and the future development plans for the terminal III. IMPLEMENTATION 3.1 System description and modeling: A single-line diagram of the three-phase test system adopted for evaluating the performance of the proposed method is shown in Figure 1. In this system, a distributed generation unit is connected to the grid through a VSC interface module, with a series line reactor as a filter to reduce the harmonics generated due to the VSC and finally a coupling transformer to reach the grid voltage level. The DC side voltage of the VSC considered is constant like a battery. The internal resistance and inductance of the filter are considered as Rt and Lt , respectively. The inductance of the coupling transformer is latent in the filter inductance. The numerical values of the test system elements are given in the Table. Figure 1. One-line diagram of the test system. 3.2 Mathematical model of the test system In this section, the mathematical model of the three-phase test system and its structure diagram is derived [30]. Based on Figure 1, which shows the structure of the test system, writing the KVL from
  • 4. 59 International Journal for Modern Trends in Science and Technology Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent Impedance the PCC bus to the converter terminal results in the dynamic equation of the VSC in the abc frame as below: To design an applicable PI-based current controller in the rotating reference frame, Eq. (1), which is the dynamic representation of the system in the stationary rotating frame, should transform to the dq reference frame that rotates by the angular speed of ω. This transform could be done by the following expression: Eq. (2) transforms any abc quantities into the rotating frame, where Ks is defined as below: Therefore, the dynamic equation of the system in the RRF could result as in Eq. (4), in which the zero sequence has been neglected. The real and imaginary parts of Eq. (4) could be separated to achieve the dynamic equation of the system on the d and q direct axis in the RRF, such as in Eqs. (5) and (6). The block diagram of the test system is obtained in the dq frame by adopting Eqs. (5) and (6) and it is shown in Figure 2. Figure 2. Structure diagram of the test system model [3]. IV. EXPERIMENTAL WORK The control results by different converter structures and control strategies are validated on a downscale dc–ac converter. As shown in Fig. 3, the circuit configurations and setup photo are both illustrated. A three-phase two-level converter with corresponding LCL filter is used to interconnect two dc voltage sources and a programmable three-phase ac voltage source. The detail parameters of the experimental setup are shown in Table III. It is noted that the converter is controlled to operate at the inverter mode, where the active power is flowing from the dc source to the ac source. By opening and closing a switch shown in Fig. 3(a), the converter can be shifted between the typical three-wire system and four-wire system with the zero-sequence current path. The amplitude of the phase A voltage in the pro- grammable ac source is adjusted to 0.1 p.u. (22 Vrms) in order to establish an adverse unbalanced condition. The control performance of the converter with the three-wire structure is shown in Fig. 4, where the given conditions and the two control strategies mentioned in Figs. 5 and 7 are applied, respectively. It can be seen that the experimental results agree well with the analysis and simulation results, where either the significant power oscillations or the overloaded current in the faulty phase are presented After enabling the zero current path and proposed controls, the performances of the given converter are shown again in Fig. 17, where the same conditions and two control strategies mentioned in Figs. 11 and 13 are applied, respectively. It can be seen that the experimental results also agree well with the simulation results, where the power oscillations are much more reduced or even totally cancelled; meanwhile, the current stress in the faulty phase is significantly relieved. These critical performances are hard to be achieved by a single three-wire converter structure using existing control strategies. The capability to control the reactive power is also a critical performance for the converter under the unbalanced ac source, the proposed two control methods are also tested under the conditions to deliver the inductive/capacitive reactive power. As shown in Figs. 18 and 19, the No P & No Q oscillation control and No negative-sequence current & No P oscillation control are applied, respectively, to deliver the inductive and capacitive reactive power with phase A voltage dipping to 0.5 p.u. It can be seen that the advantages of the smaller/eliminated power oscillation and the relieved current loading in the faulty phase are still maintained. It is noted that the power delivering under the unbalanced AC
  • 5. 60 International Journal for Modern Trends in Science and Technology Volume: 2 | Issue: 10 | October 2016 | ISSN: 2455-3778IJMTST source should give priority to the current limits of the power devices. This topic has been well discussed in the existing control methods based on the three-wire structure [30], and it is also an important consideration in the proposed control methods which utilize the zero-sequence components. Fig. 3. Experimental control performance of the converter in Fig. 3(a) with only three wires (units are nominalized by parameters in Table III, reference given: Pref = 0.5 p.u., Qref = 0 p.u., ac source condition: amplitude of the phase voltage VA = 0.1 p.u., VB =VC = 1 p.u.). (a) No negative-sequence current control (b) No P oscillation control. V. CONCLUSION In a typical three-phase three-wire converter structure, there are four current control freedoms, and it may be not enough to achieve satisfactory performances under the unbalanced ac source, because either significantly the oscillated power or the overloaded current will be presented. In the three phase converter structure with the zero sequence current path, there are six current control freedoms. The extra two control freedoms coming from the zero sequence current can be utilized to extend the controllability of the converter and improve the control performance under the unbalanced ac source. By the proposed fuzzy logic control strategies, it is possible to totally cancel the oscillation in both the active and the reactive power, or reduced the oscillation amplitude in the reactive power. Meanwhile, the current amplitude of the faulty phase is significantly relieved without further increasing the current amplitude in the normal phases. The advantage and features of the proposed controls can be still maintained under various conditions when delivering the reactive power. The analysis and proposed control methods are well agreed by experimental validations. REFERENCES [1] F. Blaabjerg, M. Liserre, and K. Ma, Power electronics converters for wind turbine systems, IEEE Trans. Ind. Appl., vol. 48, no. 2, pp. 708– 719, Mar./Apr. 2012 [2] R. Teodorescu, M. Liserre, and P. Rodriguez, Grid Converters for Photovoltaic and Wind Power Systems. New York, NY, USA: Wiley-IEEE, 2011. [3] J. Rocabert, G. M. S. Azevedo, A. Luna, J. M. Guerrero, J. I. Candela, and P. Rodriguez, Intelligent connection agent for three-phase grid-connected microgrids, IEEE Trans. Power Electron, vol. 26, no. 10, pp. 2993–3005, Oct. 2011. [4] J. W. Kolar and T. Friedli, ―The essence of three-phase PFC rectifier systems— Part I,IEEE Trans. Power Electron., vol. 28, no. 1, pp. 176– 198, Jan. 2013. [5] J. Hu, L. Shang, Y. He, and Z. Z. Zhu, ―Direct active and reactive power regulation of grid-connected dc/ac converters using sliding mode control approach,‖ IEEE Trans. Power Electron., vol. 26, no. 1, pp. 210–222, Jan. 2011. [6] C. Wessels, F. Gebhardt, and F. W. Fuchs, ―Fault ridethrough of a DFIG wind turbine using a dynamic voltage restorer during symmetrical and asymmetrical grid faults, IEEE Trans. Power Electron., vol. 26, no. 3, pp. 807–815, Mar. 2011. [7] F. Aghili, ―Fault-tolerant torque control of BLDC motors,IEEE Trans. Power Electron., vol. 26, no. 2, pp. 355–363, Feb. 2011. [8] Y. Xiangwu, G. Venkataramanan, W. Yang, D. Qing, and Z. Bo, ―Gridfault tolerant operation of a DFIG wind turbine generator using a passive resistance network, IEEE Trans. Power Electron., vol. 26, no. 10, pp. 2896–2905, Oct. 2011. [9] B. A. Welchko, T. A. Lipo, T. M. Jahns, and S. E. Schulz, ―Fault tolerant three-phase AC motor drive topologies: A comparison of features, cost, and limitations, IEEE Trans. Power Electron., vol. 19, no. 4, pp. 1108– 1116, Jul. 2004.