GOVERNMENT ENGINEERING COLLEGE
BILASPUR
KHAIRHA UNDER-GROUND MINE VOCATIONAL
TRANING REPORT
NAME- PIYUSH KUMAR DWIVEDI
ROLLNO-30724120.. SUBMITTED TO
BRANCH- ELECTRICAL
DATE- 08/07/2015 TO 07/08/2015
TRAINING
REPORT ON
SOUTH EASTERN COLFILELD LIMITED
Table of contents
ACKNOWLEDGEMENT i
LIST OF FIGURES ii
1. Introduction 1-2
1.1 About 33/11 KV substation 1
2. Transformers 3-5
2.1 Types of Transformers 3-5
2.1.1 Power transformer 4
2.1.2 Instrument transformer 4
2.1.3 Autotransformer 5
2.1.4 On the basis of working 5
2.1.5 On the basis of structure 5
3. Specification of C.T. used in 33/11 KV substation Sector-25,Indranagar 6
4. Substation 7-13
4.1 Types of substation 8
4.1.1 According to the service requirement 8
4.1.2 According to the constructional features 8
4.2 Substation characteristics 10
4.3 Steps in designing substation 10
4.3.1 Earthing and bonding 10
4.3.2 Substation earthing calculation methodology 11
4.3.3 Earthing material 11
4.3.4 Switch yard fence earthing 12
4.4 Conductors used in substation designing 12
5. Chronological training diary 14-17
5.1 Power line carrier communication(PLCC) 14
5.1.1 Applications 14
5.2 Principle of PLCC 15
5.2.1 Wave trap or line trap 15
5.2.2 Coupling capacitor 16
5.2.3 Protective device of coarse voltage arrester 16
5.2.4 Coupling of filter 16
5.2.5 H.F. cable 16
6. Bus bars 18-19
7. Insulators 20-25
7.1 Circuit breakers 21
7.2 Oil circuit breaker 22
7.3 Air blast circuit breaker 22
7.4 Sulphar hexafluoride circuit breaker (SF6)circuit breaker 23
7.5 Vacuum circuit breaker 24
8. Metering and Indication equipment 26-29
8.1 Relay 26
8.2 Relays used in control panel of substation 27
8.2.1 Differential relay 27
8.2.2 Over current relay 27
8.2.3 Directional relay 28
8.2.4 Tripping relay 28
8.2.5 Auxiliary relay 29
9. Miscellaneous Equipments 30-31
9.1 Capacitor bank 30
9.2 Fuse 31
9.3 Bus coupler 31
10. Protection of substation 32-33
10.1 Transformer protection 32
10.2 Conservation and breather 32
10.3 Marshalling box 32
10.4 Transformer cooling 33
11. Mine Load Centers/Power Centers 34
12. Switchgear 35
13. Motor Control Centers 36
14. Mine Substation 37
15. Capacitor Banks 38
16. Leaky Feeder Radio Systems 39
17. Diesel Generator Set 40
18. Vehicle and Personnel Tracking Systems 41
19. CONCLUSION 43
References 44
ACKNOWLEDGEMENT
Training has an important role in exposing the real life situation in an industry. It was a
great experience for me to work on training at SOUTH EASTERN COLFILELD LIMITED
through which I could learn how to work in a professional environment.
Now, I would like to thank the people who guided me and have been a constant source of
inspiration throughout the tenure of my summer training.
I am sincerely grateful to MR. N.Y.HADKE being the ENGINEER at 33/3.3 KV
substation, KHAIRHA U/G MINE who rendered me his valuable assistance, constant
encouragement and able guidance which made this training actually possible.
Piyush Dwivedi
List of figures
Figure no. Name of figure Page no.
Figure 1.1 33/3.3 KV Substation khairha mine 1
Figure 2.1 Transformer 3
Figure 2.2 Power transformer 4
Figure 2.3 Instrument transformer 4
Figure 2.4 Auto transformer 5
Figure 2.5 Core type 5
Figure 2.6 Shell type 5
Figure 3.1 Current transformer 6
Figure 4.1 View of substation 7
Figure 4.2 Transformer substation 8
Figure 5.1 Power line carrier communication (PLCC) 14
Figure 6.1 Typical representation of bus bars 18
Figure 7.1 Insulators used in substation 20
Figure 7.2 Circuit breaker arrangements 21
Figure 7.3 Oil circuit breaker 22
Figure 7.4 Air blast circuit breaker 23
Figure 7.5 SF6 Circuit breaker 23
Figure 7.6 Vacuum circuit breaker 24
Figure 8.1 Typical view of Relay 26
Figure 8.2 Differential Relay 27
Figure 8.3 Over current Relay 27
Figure 8.4 Directional Relay 28
Figure 8.5 Tripping Relay 28
Figure 8.6 Auxiliary Relay 29
Figure 9.1 Capacitor bank 30
Figure 9.2 Substation fuse 31
Figure 9.3 Bus coupler 32
Figure 9.4 Mine Load Centers/Power Centers 33
Figure 9.5 Switchgear 34
Figure 9.6 Motor Control Centers 35
Figure 9.7 Mine Substation 36
Figure 9.8 Capacitor Banks 37
Figure 9.9 Diesel Generator Set 38
Figure 9.10 Vehicle and Personnel Tracking Systems 39
1. INTRODUCTION
The creation of South Eastern Coalfield Ltd. (SECL) on JULY is the result of power
sector reforms and restructuring in MP (India) which is the focal point of the Power Sector,
responsible for planning and managing the sector through its production,
distribution and supply of Coal.
SECL will be professionally managed utility supplying reliable and cost efficient
electricity to every citizen of the state through highly motivated employees and state of art
technologies, providing an economic return to our owners and maintaining leadership in the
country.
We shall achieve this being a dynamic, forward looking, reliable, safe and trustworthy
organization, sensitive to our customers interests, profitable and sustainable in the long run,
providing uninterrupted supply of quality power, with transparency and integrity in operation
1.1 ABOUT 33/3.3 KV SUBSTATION KHAIRHA MINE
Figure 1.1 33/3.3 KV Substation khairha mine
1.2 UNDER GROUND ELECTRICALCAL POWER SYSTEM IN
KHAIRHA MINE
The main bus 33KV is connected to bus-bar of the substation of KHAIRHA mine. Now
the transmission line first parallel connected with lightning arrester to diverge surge, followed by
CVT connected parallel. CVT measures voltage and steeps down at 110V. A.C. for control
panel, at the location a wave trap is connected to carrier communication at higher frequencies. A
current transformer is connected in series with line which measure current.
Switchgear equipment is provided, which is the combination of a circuit breaker having
an isolator at each end. A transformer is connected to main bus though a bus coupler. The main
bus has total capability of 160 MVA for 3.3 KV, which is subdivided into two transformer
capacity of 80 MVA (40MVA+40MVA) parallel connected for 3.3KV and other two transformer
capacity of 80KV (40KV+40KV) are parallel connected for substation.
At both ends of transformer lightning arrester current transformer and switchgear
equipment provided. Transformer step downs voltage from 33KV to 3.3KV. The main bus is
provided with switchgear equipment & a current transformer. This gives way to two feeders
transmitting power to KHAIRHA underground mine. One feeder is used at a time [BAGWAR]
and 2nd is backup [DAMINI]. The main bus is connected to jack bus or transfer bus through a
bus coupler & 550V is provided with switchgear equipment. A step down transformer of
3.3KV/440V 3.3KV/11OV & 3.3KV/220V is connected to control panel to provide supply to the
equipments of the substation. Capacitor bank is connected to main bus of 3.3KV. It is provided
to improve power factor & voltage profile.
In the surface substation power is step down by 33/3.3kv, 33kv/110v and 33kv/220v
through the step down transformer and in 2nd level underground substation power is step down
by 3.3kv/550v for different kind of uses like lighting, motoring, air conditioning etc
2nd level substation is parallel connected through 19th level substation and hears power is
step down by 3.3kv/550v for lighting, motoring, Air conditioning or HDL machine. HDL
machine is the main machine in the coal mine is operated on 550v DC supply.
2. TRANSFORMERS
Figure: 2.1 Transformer
Transformer is a static machine, which transforms the potential of alternating current at
same frequency. It means the transformer transforms the low voltage into high voltage & high
voltage to low voltage at same frequency. It works on the principle of static induction principle.
When the energy is transformed into a higher voltage, the transformer is called step up
transformer but in case of other is known as step down transformer.
2.1 TYPES OF TRANSFORMER
2.1.1 Power transformer
2.1.2 Instrument transformer
2.1.3 Auto transformer
2.1.4 On the basis of working
2.1.5 On the basis of structure
2.1.1 POWER TRANSFORMER:
Figure 2.2 Power Transformers
Types of power transformer:
2.1.1.1 Single phase transformer
2.1.1.2 Three phase transformer
2.1.2 INSTRUMENT TRANSFORMER:
Fig: 2.3 Instrument Transformers
a) Current transformer
b) Potential transformer
2.1.3AUTO TRANSFORMER:
Fig 2.4 Auto Transformer
a) Single phase transformer
b) Three phase transformer
2.1.4 ON THE BASIS OF WORKING
2.1.4.1Step down: Converts high voltage into low voltage.
2.1.4.2 Step up: Converts low voltage into high voltage.
2.1.5 ON THE BASIS OF STRUCTURE
Figure 2.5 core typeFigure 2.6 Shell type
3. SPECIFICATION OF C.T. USED IN 33/3.3 KV SUB STATION
Figure 3.1 Current transformer
3.1 Standard: IS-2785
3.2 Highest System Voltage: 145 KV
3.3 Frequency: 50Hz
3.4 C.T. Current: 25 KA/1Sec.
3.5 Rated primary current: 800 Ampere
4. SUBSTATIONS
Figure 4.1View of substation
The present day electrical power system is A.C.i.e. electrical power is generated,
transmitted & distributed in the form of the alternating current. The electric power is produced at
power plant stations which are located at favorable places generally quite away from the
consumers. It is delivered to the consumers through a large network of transmission 7
distribution.
At many places in the power system, it may be desirable and necessary to change some
characteristics e.g. voltage, ac to dc, frequency, power factor etc. of electric supply. This
accomplished by suitable apparatus called substation. For example; generation voltage (11 KV or
33 KV) at the power station is set up to high voltage (say 220 KV or 132 KV) for transmission of
electric power. The assembly of apparatus (e.g. transformer etc.) used for this purpose in the
substation. Similarly near the consumer’s localities, the voltage may have to be step down to
utilization level. This job is again accomplished by suitable apparatus called substation.
The assembly of apparatus to change some characteristic of electric power supply is
called substation.
The two most ways to classify substation are:-
4.1 TYPES OF SUBSTATION
4.1.1 According to the service requirement:
4.1.1.1 Transformer substation
4.1.1.2 Switch substation
4.1.1.3 Power factor correction substation
4.1.1.4 Frequency change substation
4.1.1.5 Converting substation
4.1.1.6 Industrial substation
4.1.2 According to the constructionalfeatures:
4.1.2.1 Indoor substation
4.1.2.3 Outdoor substation
4.1.2.4 Underground substation
4.1.2.5 Pole mounted substation
4.1.1.1 TRANSFORMER SUBSTATION
Figure 4.2 Transformer substation
They are known as transformer substations as because transformer is the main
component employed to change the voltage level, depending upon the purposed served
transformer substations may be classified into:
4.1.1.1.1 STEP UP SUBSTATION
The generation voltage is steeped up to high voltage to affect economy in
transmission of electric power. These are generally located in the power houses and are
of outdoor type.
4.1.1.1.2 PRIMARY GRID SUBSTATION
Here, electric power is received by primary substation which reduces the voltage
level to 11KV for secondary transmission. The primary grid substation is generally of
outdoor type.
4.1.1.1.3SECONDARY SUBSTATIONS
At a secondary substation, the voltage is further steeped down to 11KV. The
11KV lines runs along the important road of the city. The secondary substations are also
of outdoor type.
4.1.1.1.3 DISTRIBUTION SUBSTATION
These substations are located near the consumer’s localities and step down to
400V, 3-phase, 4-wire for supplying to the consumers. The voltage between any two
phases is 400V & between any phase and neutral it is 230V.
4.2 SUBSTATION CHARACTERISTICS:
4.2.1 Each circuit is protected by its own circuit breaker and hence plant outage does
not necessarily result in loss of supply.
4.2.2 A fault on the feeder or transformer circuit breaker causes loss of the transformer
and feeder circuit, one of which may be restored after isolating the faulty circuit
breaker.
4.2.3 A fault on the bus section circuit breaker causes complete shutdown of the
substation. All circuits may be restored after isolating the faulty circuit breaker.
4.2.4 Maintenance of a feeder or transformer circuit breaker involves loss of the circuit.
4.2.5 Introduction of bypass isolators between bus bar and circuit isolator allows circuit
breaker maintenance facilities without loss of that circuit.
4.3 STEPS IN DESIGNING SUBSTATION:
The First Step in designing a Substation is to design an Earthing and Bonding System.
4.3.1 Earthing and Bonding:
The function of an earthing and bonding system is to provide an earthing system
connection to which transformer neutrals or earthing impedances may be connected in order to
pass the maximum fault current. The earthing system also ensures that no thermal or mechanical
damage occurs on the equipment within the substation, thereby resulting in safety to operation
and maintenance personnel. The earthing system also guarantees equipotent bonding such that
there are no dangerous potential gradients developed in the substation.
In designing the substation, three voltage have to be considered these are:
4.3.1.1Touch Voltage:
This is the difference in potential between the surface potential and the potential at
earthedequipment whilst a man is standing and touching the earthed structure.
4.3.1.2Step Voltage:
This is the potential difference developed when a man bridges a distance of 1m with his
feet while not touching any other earthed equipment.
4.3.1.3 Mesh Voltage:
This is the maximum touch voltage that is developed in the mesh of the earthing grid.
4.3.2 SubstationEarthing CalculationMethodology
Calculations for earth impedances, touch and step potentials are based on site
measurements of ground resistivity and system fault levels. A grid layout with particular
conductors is then analyzed to determine the effective substation earthing resistance, from which
the earthing voltage is calculated.
In practice, it is normal to take the highest fault level for substation earth grid calculation
purposes. Additionally, it is necessary to ensure a sufficient margin such that expansion of the
system is catered for.
To determine the earth resistivity, probe tests are carried out on the site. These tests are
best performed in dry weather such that conservative resistivity readings are obtained.
4.3.3Earthing Materials
4.3.3.4Conductors:
Bare copper conductor is usually used for the substation earthing grid. The copper bars
themselves usually have a cross-sectional area of 95 square millimeters, and they are laid at a
shallow depthof 0.25-0.5m, in 3-7m squares. In addition to the buried potential earth grid, a
separate above ground earthing ring is usually provided, to which all metallic substation plant is
bonded.
4.3.3.4Connections:
Connections to the grid and other earthing joints should not be soldered because the heat
generated during fault conditions could cause a soldered joint to fail. Joints are usually bolted.
4.3.3.5Earthing Rods:
The earthing grid must be supplemented by earthing rods to assist in the dissipation of earth
faultcurrents and further reduce the overall substation earthing resistance. These rods are usually
made ofsolid copper, or copper clad steel.
4.3.4 Switchyard Fence Earthing:
The switchyard fence earthing practices are possible and are used by different
utilities. These are:
4.3.4.1 Extend the substation earth grid 0.5m-1.5m beyond the fence perimeter. The fence
is thenbonded to the grid at regular intervals.
4.3.4.2 Place the fence beyond the perimeter of the switchyard earthing grid and bond the
fence to its own earthing rod system. This earthing rod system is not coupled to the
main substation earthing grid.
4.4 CONDUCTORS USED IN SUBSTATION DESIGN:
An ideal conductor should fulfills the following requirements:
4.4.1 Should be capable of carrying the specified load currents and short time currents.
4.4.2 Should be able to withstand forces on it due to its situation. These forces comprise self
weight, and weight of other conductors and equipment, short circuit forces and
atmospheric forces such as wind and ice loading.
4.4.3 Should be corona free at rated voltage.
4.4.4 Should have the minimum number of joints.
4.4.5 Should need the minimum number of supporting insulators.
4.4.6 Should be economical.
The most suitable material for the conductor system is copper or aluminums. Steel may
be used but has limitations of poor conductivity and high susceptibility to corrosion.
In an effort to make the conductor ideal, three different types have been utilized, and
these include: Flat surfaced Conductors, Stranded Conductors, and Tubular Conductors
4.5Overhead Line Terminations
Two methods are used to terminate overhead lines at a substation.
4.5.1 Tensioning conductors to substation structures or buildings
4.5.2 Tensioning conductors to ground winches.
The choice is influenced by the height of towers and the proximity to the substation.The
following clearances should be observed:
VOLTAGE LEVEL MINIMUM GROUND CLEARANCE
less than 11kV 6.1m
11kV - 20kV 6.4m
20kV - 30kV 6.7m
greater than 30kV 7.0m
Table 1 Clearance in accordance with voltage value
5. CHRONOLOGICAL TRAINING DIARY
( based on study & observation at different Departments and
sections)
5.1 POWER LINE CARRIER COMMUNICATION
Introduction:
Figure 5.1: PLCC (POWER LINE CARRIER COMMUNICATION)
Reliable & fast communication is necessary for safe efficient &economical power supply.
To reduce the power failure in extent & time, to maintain the interconnected grid system in
optimum working condition; to coordinate the operation of various generating unit
communication network is indispensable for state electricity board.
In state electricity boards, the generating & distribution stations are generally located at a
far distance from cities. Where P & T communication provided through long overhead lines in
neither reliable nor quick.
As we have available very reliable physical paths viz. the power lines, which
interconnected, hence power line carrier communication is found to be most economical and
reliable for electricity boards.
5.1.1 APPLICATIONS:
The PLCC can be used for the following facilities:
5.1.1.1 Telephony
5.1.1.2 Teleprotection
5.1.1.3 Remote control or indication
5.1.1.4 Telemetry
5.1.1.5Teleprinting
5.2 PRINCIPLE OF PLCC:
The principle of PLCC is the simple one:
All type of information is modulated on carried wave at frequency 50Hz to 500 KHz. The
modulated HF carrier fed into the power line conductor at the sending end and filtered out again
at the respective stations. Long earlier system double side band amplitude modulation was more
common but the present amplitude modulated system.
Since high voltage power lines are designed to carry large quantities of energy on the
high voltage and the communication system at low voltage, they cannot be directly connected to
high voltage lines. Suitably designed coupling equipments have therefore to be employed which
will permit the injection of high frequency carrier signal without undue loss and with absolute
protection of communication equipments or operating personal from high voltage hazard.
Therefore, the coupling equipment essentially comprises the following:
5.2.1 Wave trap or line trap:
Wave trap is connected in series with power line between the point of connection of
coupling capacitor and S/S. Wave trap offers negligible impedance to HF carrier. Wave trap
stands electromechanically and thermally for short circuit current in the event of fault on the line.
On the basis of blocking frequency bank, the wave trap can be following type:
5.2.1.1 ALL WAVE
5.2.1.2 SINGAL FREQUENCY
5.2.1.3 DOUBLE FREQUENCY
5.2.1.4 BROAD BAND
5.2.2 Coupling capacitor:
The modulated carrier is let into power line through coupling capacitor specially designed
to with stand line voltage under all weather condition. The upper end of the coupling capacitor is
connected directly to the line and the lower end is connected to the ground through a carrier
frequency chock coil or drain coil. Thus coupling capacitor forms the link between the PLCC
equipment and power line. The coupling capacitor used in UPSEB is 2200pf capacitance.
The coupling capacitor are designed for outdoor use and hence to withstand normal
atmospheric phenomenon such as temperature & humidity changes, rain, snow, anticipated wind
load, nominal wire tension etc. at full rated voltage. In some case capacitive voltage transformers
(CVT) used as a source of line voltage for metering and protection as also used coupling
capacitor for PLCC.
5.2.3 Protective Device of Coarse Voltage Arrester:
This is connected across the primary of the coupling filter i.e. one end is connected to the
bottom of the coupling capacitor and other end is earthed. This is provided to protect the
coupling filter against line surges. An air gap is provided, where voltage of the order of 1.8 to
2KV as observed across due to lighting etc. on line.
5.2.4 Coupling of Filter:
The coupling filter is inserted between the low voltage terminal of the coupling capacitor
and the carrier frequency connection of the carrier terminal. Some time an earth switch is also
provided with this unit. This unit mainly performs two functions; firstly it isolates the connection
of equipment from the power line. Secondly it serves to match characteristic impedance of the
power line to that of the H.F. cable to connection equipments.
5.2.5 H.F. Cable:
H.F. cable normally used to connect the coupling filter to another coupling terminal. The
cable is insulated to withstand the test voltage of 4KV. The impedance of this H.F. cable is so as
to match with the output of the PLCC terminal and secondary impedance of coupling filter.
5.2.5.1 TYPES OF COUPLING:
The following three types of coupling are being used in UPSEB depending on the
requirement:
5.2.5.1.1 Phase to ground coupling
5.2.5.1.2 Phase to phase coupling
5.2.5.1.3 Internal coupling
5.2.5.2 COUPLING LOSSES:
5.2.5.2.1 Composite loss
5.2.5.2.2 Tapping loss
5.2.5.2.3 H.F. cable loss
5.2.5.2.4 Additional loss
6. BUSBARS
Figure 6.1 Typical representation of bus bars
When numbers of generators or feeders operating at the same voltage have to be directly
connected electrically, bus bar is used as the common electrical component. Bus bars are made
up of copper rods operate at constant voltage. The following are the important bus bars
arrangements used at substations:
6.1 Single bus bar system
6.2 Single bus bar system with section alisation.
6.3 Duplicate bus bar system
In large stations it is important that break downs and maintenance should interfere as little
as possible with continuity of supply to achieve this, duplicate bus bar system is used. Such a
system consists of two bus bars, a main bus bar and a spare bus bar with the help of bus coupler,
which consist of the circuit breaker and isolator.
In substations, it is often desired to disconnect a part of the system for general maintenance and
repairs. An isolating switch or isolator accomplishes this. Isolator operates under no load
condition. It does not have any specified current breaking capacity or current making capacity. In
some cases isolators are used to breaking charging currents or transmission lines.
While opening a circuit, the circuit breaker is opened first then isolator while closing a
circuit the isolator is closed first, then circuit breakers. Isolators are necessary on supply side of
circuit breakers, in order to ensure isolation of the circuit breaker from live parts for the purpose
of maintenance.
A transfer isolator is used to transfer main supply from main bus to transfer bus by using
bus coupler (combination of a circuit breaker with two isolators), if repairing or maintenance of
any section is required.
7. INSULATORS
The insulator serves two purposes. They support the conductors (bus bar) and confine the
current to the conductors. The most common used material for the manufacture of insulator is
porcelain. There are several types of insulators (e.g. pin type, suspension type, post insulator etc.)
and their use in substation will depend upon the service requirement. For example, post insulator
is used for bus bars. A post insulator consists of a porcelain body, cast iron cap and flanged cast
iron base. The hole in the cap is threaded so that bus bars can be directly bolted to the cap.
Figure 7.1 Insulators used in substations
With the advantage of power system, the lines and other equipment operate at very high
voltage and carry high current.
The arrangements of switching along with switches cannot serve the desired function of
switchgear in such high capacity circuits. This necessitates employing a more dependable means
of control such as is obtain by the use of the circuit breakers. A circuit breaker can make or break
a circuit either manually or automatically under all condition as no load, full load and short
circuit condition.
A circuit breaker essentially consists of fixed and moving contacts. These contacts can be
opened manually or by remote control whenever desired. When a fault occurs on any part of the
system, the trip coils of breaker get energized and the moving contacts are pulled apart by some
mechanism, thus opening the circuit.
When contacts of a circuit breaker are separated, an arc is struck; the current is thus able
to continue. The production of arcs are not only delays the current interruption, but is also
generates the heat. Therefore, the main problem is to distinguish the arc within the shortest
possible time so that it may not reach a dangerous value.
The general way of classification is on the basis of the medium used for arc extinction.
Figure 7.2 Circuit breaker arrangements
7.1. Circuit breakers
They can be classified into:
7.1.1 Oil circuit breaker
7.1.2 Air-blast circuit breaker
7.1.3 Sulphar hexafluoride circuit breaker (SF6)
7.1.4 Vacuum circuit breakers
Note: SF6 and Vacuum circuit breaker are being used in 33KV distribution substation.
7.2 Oil Circuit Breaker
Figure 7.3 Oil circuit breaker
A high-voltage circuit breaker in which the arc is drawn in oil to dissipate the heat and
extinguish the arc; the intense heat of the arc decomposes the oil, generating a gas whose high
pressure produces a flow of fresh fluid through the arc that furnishes the necessary insulation to
prevent a restrike of the arc.
The arc is then extinguished, both because of its elongation upon parting of contacts and
because of intensive cooling by the gases and oil vapor.
7.3 Air blast circuit breaker
Fast operations, suitability for repeated operation, auto reclosure, unit type multi break
constructions, simple assembly, modest maintenance are some of the main features of air blast
circuit breakers. A compressors plant necessary to maintain high air pressure in the air receiver.
The air blast circuit breakers are especially suitable for railways and arc furnaces, where the
breaker operates repeatedly. Air blast circuit breakers is used for interconnected lines and
important lines where rapid operation is desired.
Figure 7.4 Air blast circuit breaker
High pressure air at a pressure between 20 to 30 kg/ cm2 stored in the air reservoir. Air is
taken from the compressed air system. Three hollow insulator columns are mounted on the
reservoir with valves at their basis. The double arc extinguished chambers are mounted on the
top of the hollow insulator chambers. The current carrying parts connect the three arc extinction
chambers to each other in series and the pole to the neighboring equipment. Since there exists a
very high voltage between the conductor and the air reservoir, the entire arc extinction chambers
assembly is mounted on insulators.
7.4 SF6 CIRCUIT BREAKER:
Figure 7.5 SF6 Circuit breaker
In such circuit breaker, sulphar hexafluoride (SF6) gas is used as the arc quenching
medium. The SF6 is an electronegative gas and has a strong tendency to absorb free electrons.
The SF6 circuit breaker have been found to a very effective for high power and high voltage
service. SF6 circuit breakers have been developed for voltage 115 KV to 230 KV, power rating
10 MVA.
It consists of fixed and moving contacts. It has chamber, contains SF6 gas. When the
contacts are opened, the mechanism permits a high pressure SF6 gas from reservoir to flow
towards the arc interruption chamber. The moving contact permits the SF6 gas to let through
these holes.
7.5 Vacuum Circuit Breaker
Figure 7.6 Vacuum circuit breaker
Vacuum circuit breakers are circuit breakers which are used to protect medium and high
voltage circuits from dangerous electrical situations. Like other types of circuit breakers, vacuum
circuit breakers literally break the circuit so that energy cannot continue flowing through it,
thereby preventing fires, power surges, and other problems which may emerge. These devices
have been utilized since the 1920s, and several companies have introduced refinements to make
them even safer and more effective.
7.2.1 Rating of 132 KV SF6 circuit breaker:
7.2.1.1 Breaking current: 50A
7.2.1.2 Making capacity: 80KA
7.2.1.3 Total break time < 60msec
7.2.1.4 Rated short circuit breaking current:
7.2.1.4.1 Symmetrical: 31.5 KA
7.2.1.4.2 Asymmetrical: 36.86 KA
7.2.1.5 Rated duration of short circuit current: 3sec
7.2.1.6 Rated nominal current: 1250 A
7.2.1.7 Rated voltage: 145 KV
7.2.1.8 Rated SF6 gas pressure: 6 KG
8. METERING AND INDICATION EQUIPMENT
8.1 RELAY:
Figure 8.1 Relay
In a power system it is inevitable that immediately or later some failure does occur
somewhere in the system. When a failure occurs on any part of the system, it must be quickly
detected and disconnected from the system. Rapid disconnection of faulted apparatus limits the
amount of damage to it and prevents the effects of fault from spreading into the system. For high
voltage circuits relays are employed to serve the desired function of automatic protective gear.
The relays detect the fault and supply the information to the circuit breaker.
The electrical quantities which may change under fault condition are voltage, frequency,
current, phase angle. When a short circuit occurs at any point on the transmission line the current
flowing in the line increases to the enormous value.This result in a heavy current flow through
the relay coil, causing the relay to operate by closing its contacts. This in turn closes the trip
circuit of the breaker making the circuit breaker open and isolating the faulty section from the
rest of the system. In this way, the relay ensures the safety of the circuit equipment from the
damage and normal working of the healthy portion of the system. Basically relay work on the
following two main operating principles:
8.1.1 Electromagnetic attraction relay
8.1.2 Electromagnetic induction relay
8.2 Relays used in control panel of the substation;
8.1.3 DIFFERENTIAL RELAY:
Figure 8.2 Differential Relay
A differential relay is one that operates when vector difference of the two or more
electrical quantities exceeds a predetermined value. If this differential quantity is equal or greater
than the pickup value, the relay will operate and open the circuit breaker to isolate the faulty
section.
8.1.4 OVER CURRENT RELAY:
Figure 8.3 Overcurrent Relay
This type of relay works when current in the circuit exceeds the predetermined value. The
actuating source is the current in the circuit supplied to the relay from a current transformer.
These relay are used on A.C. circuit only and can operate for fault flow in the either direction.
This relay operates when phase to phase fault occurs.
8.1.5 DIRECTIONAL RELAY:
Figure8.4 DirectionalRelay
This relay operates during earth faults. If one phase touch the earth due to any fault. A
directional power relay is so designed that it obtains its operating torque by the interaction of
magnetic field derived from both voltage and current source of the circuit it protects. The
direction of torque depends upon the current relative to voltage.
8.1.6 TRIPPING RELAY:
Figure 8.5 Tripping Relay
This type of relay is in the conjunction with main relay. When main relay sense any fault in
the system, it immediately operates the trip relay to disconnect the faulty section from the section
8.1.7 AUXILIARY RELAY:
Figure 8.6 Auxiliary Relay
An auxiliary relay is used to indicate the fault by glowing bulb alert the employee.
9. MISCELLANOUS EQUIPMENT
9.1 CAPACITOR BANK:
Figure 9.1 Capacitor bank
The load on the power system is varying being high during morning and evening which
increases the magnetization current. This result in the decreased power factor. The low power
factor is mainly due to the fact most of the power loads are inductive and therefore take lagging
currents. The low power factor is highly undesirable as it causes increases in current, resulting in
additional losses. So in order to ensure most favorable conditions for a supply system from
engineering and economical stand point it is important to have power factor as close to unity as
possible. In order to improve the power factor come device taking leading power should be
connected in parallel with the load. One of the such device can be capacitor bank. The capacitor
draws a leading current and partly or completely neutralize the lagging reactive component of
load current.
Capacitor bank accomplishes following operations:
9.1.1 Supply reactive power
9.1.2 Increases terminal voltage
9.1.3 Improve power factor
9.2 FUSE:
Figure 9.2 Substation Fuse
A fuse is a short piece of wire or thin strip which melts when excessive current through it
for sufficient time. It is inserted in series with the circuit under normal operating conditions; the
fuse element is at a nature below its melting point. Therefore it carries the normal load current
overheating. It is worthwhile to note that a fuse performs both detection and interruption
functions.
9.3 BUS COUPLER:
Figure 9.3 bus coupler
The bus coupler consists of circuit breaker and isolator. Each generator and feeder may
be connected to either main bus bar or spar bus bar with the help of bus coupler. Repairing,
maintenance and testing of feeder circuit or other section can be done by putting them on spar
bus bar, thus keeping the main bus bar undisturbed.
10. PROTECTION OF SUBSTATION:
10.1 Transformer protection:
Transformers are totally enclosed static devices and generally oil immersed. Therefore
chances of fault occurring on them are very easy rare, however the consequences of even a rare
fault may be very serious unless the transformer is quickly disconnected from the system. This
provides adequate automatic protection for transformers against possible faults.
10.2 Conservator and Breather:
When the oil expands or contacts by the change in the temperature, the oil level goes
either up or down in main tank. A conservator is used to maintain the oil level up to
predetermined value in the transformer main tank by placing it above the level of the top of the
tank.
Breather is connected to conservator tank for the purpose of extracting moisture as it
spoils the insulating properties of the oil. During the contraction and expansion of oil air is
drawn in or out through breather silica gel crystals impregnated with cobalt chloride. Silica gel is
checked regularly and dried and replaced when necessary.
10.3 Marshalling box:
It has two meter which indicate the temperature of the oil and winding of main tank. If
temperature of oil or winding exceeds than specified value, relay operates to sound an alarm. If
there is further increase in temperature then relay completes the trip circuit to open the circuit
breaker controlling the transformer.
10.4 Transformer cooling:
When the transformer is in operation heat is generated due to iron losses the removal of
heat is called cooling.
There are several types of cooling methods, they are as follows:
10.4.1 Air natural cooling;
In a dry type of self cooled transformers, the natural circulation of surrounding air is used
for its cooling. This type of cooling is satisfactory for low voltage small transformers.
10.4.2 Air blast cooling:
It is similar to that of dry type self cooled transformers with to addition that continuous
blast of filtered cool air is forced through the core and winding for better cooling. A fan produces
the blast.
10.4.3 Oil natural cooling:
Medium and large rating have their winding and core immersed in oil, which act both as
a cooling medium and an insulating medium. The heat produce in the cores and winding is
passed to the oil becomes lighter and rises to the top and place is taken by cool oil from the
bottom of the cooling tank.
10.4.4 Oil blast cooling:
In this type of cooling, forced air is directed over cooling elements of transformers
immersed in oil.
10.4.5 Forced oil and forced air flow (OFB) cooling:
Oil is circulated from the top of the transformers tank to a cooling tank to a cooling plant.
Oil is then returned to the bottom of the tank.
10.4.6 Forced oil and water (OWF) cooling:
In this type of cooling oil flow with water cooling of the oil in external water heat
exchanger takes place. The water is circulated in cooling tubes in the heat exchanger.
11.Mine Load Centers/Power Centers
Mine Load Centers are used to transform high voltage input to low voltage outputs.
Intermountain Electronics provides durable and reliable Power Centers of the highest quality,
custom designed to meet the customer’s specific requirements.
 Input usually in 5 kV to 25 kV classes
 Output with typical voltage ratings of 480 to 1000 volts
 Generally provided with appropriate overcurrent protection, monitoring, metering,
and means for disconnection
Figure 9.4 Mine Load Centers/Power Centers
12.Switchgear
safe and efficient protection of your high voltage distribution system.
 Low-profile switchgear for underground
 Full height “walk-in” switchgear
 Indoor or outdoor switchgear
Figure 9.5 Switchgear
13. Motor Control Centers
Motor Control Centers (MCCs) are required throughout the mining environment to energize and
control drive motors for equipment such as conveyors, pumps, and fans. These applications can
range up to thousands of horsepower with low, medium, or high voltage motors.
 Simple Across-the-line (ATL) arrangements
 Sophisticated PLC controlled Variable Frequency Drives (VFDs)
 Soft-Starts or some combination
Figure 9.6 Motor Control Centers
14. Substation
Figure 9.7 Substation
Substations are used by underground and surface mines to transform utility or generator supplied
electrical power to the required voltage.
 House supporting bus, switches, arrestors, insulators, breakers, and other electrical
components
 Permanent substation design with individual stand-alone components
 Fixed indoor, outdoor, walk-in substation design
 Portable substation skid-mounted design
 Durable, heavy duty substation design for trucking or skidding to various locations
Intermountain Electronics has full metal fabrication capabilities for design and assembly of steel
structures for substations and switchgear (see our section on ELECTRICAL BUILDINGS). Our
portable substations have been operating for years in harsh mining environments ranging from
the extreme heat and blowing sand of the Mojave Desert, the frigid temperatures, snow and ice
of the U.S. Continental Divide, the high humidity lowlands of Alabama and Louisiana, and the
extremes of the high altitude Andes Mountains in Chile.
15.Capacitor Banks
Capacitor Banks are used to improve the power factor of the electrical
distribution system which can greatly reduce the costs of power from your
utility company.
Capacitor Banks can improve the efficiency and ease of starting motors.
 Open pole-top assemblies
 Enclosed banks for indoor, outdoor or underground applications
 Fixed for continuous operation Figure 9.8 CapacitorBanks
 Switched for utilization as required
 A combination of fixed and switched capacitors
Intermountain Electronics can assist in the analysis of your electrical system to determine your
capacitor requirements. We can then provide these capacitors in a package to suit your specific
need
16.Leaky Feeder Radio Systems
Leaky Feeder Radio Systems utilize a partially shielded coaxial cable to distribute radio
frequency (RF) signals throughout underground mine and tunnel environments. The leaky feeder
network has proven to be a superior method for underground wireless voice, data, and video
communications and can interface with other surface and underground communication systems.
 Improved emergency/ production/breakdown response of key personnel
 Remote monitoring by video and/or data of underground equipment
 Remote control of equipment
Intermountain Electronics has teamed with Tunnel Radio to provide the latest technology in
Tunnel Wireless Communication Systems and can analyze your specific situation to determine
the most effective solution for your communication needs.
17.Diesel Generator Set
Diesel powered generator sets provide a portable power source
for applications where utility supplied power is not available.
 Mine start-up
 Back-up for ventilation fans
 Large generators for moving shovels and drills in
surface mines
 Compact, low-profile, skid-mounted generators in
underground mines
Figure 9.9 DieselGeneratorSet
Intermountain Electronics is an industry leader in providing these custom-built generator sets
that comply with all applicable standards and regulations for safe and efficient operation.
Intermountain Electronics has teamed with CleanAIR Systems to provide Emissions
Control Technology and Retrofit Technology and will advise you on meeting MSHA and EPA
clean air standards
18. Vehicle and Personnel Tracking Systems
Vehicle and Personnel Tracking is a Radio Frequency Identification
System consisting of RFID tags, RFID readers, RF network, computer,
and software that provides a graphical representation of items such as
personnel, vehicles, products, and equipment. Vehicle and Personnel
Tracking provides timely and accurate location data that can be used to
meet safety, production, and cost reduction targets. Benefits include…
 Location positioning of personnel and vehicles
 Monitor and review of production vehicle cycles
 Adjusting ventilation based on number of cycles and type of vehicles Figure 9.10
 Resource tracking history.
Intermountain Electronics has teamed with AMR Inc. and can analyze your situation and tailor a
Vehicle and Personnel Tracking System to meet your specific needs.
19. CONCLUSION
Now from this report we can conclude that electricity plays an important role in our life.
We are made aware of how the transmission of electricity is done. We too came to know about
the various parts of the Substation system.
The South Eastern Coalfield Limited has got radio communication in microwave range
in order to transmit and receive data with various Substations in Uttar Pradesh to get reliable
transmission and distribution of electricity.
References
1. www.yahooanswers.com
2. www.britannica.com
3. www.webopedia.com
4. www.encyclopedia.com
5. www.worldbook.com
6. www.encyclopediadramatica.com/

Contenu connexe

Tendances

Power System Protection Technique: A Review
Power System Protection Technique: A ReviewPower System Protection Technique: A Review
Power System Protection Technique: A Reviewsahid raja khan
 
Airborne Wind Turbines - A report
Airborne Wind Turbines - A reportAirborne Wind Turbines - A report
Airborne Wind Turbines - A reportParag Deshpande
 
Streamer theory of breakdown
Streamer theory of breakdownStreamer theory of breakdown
Streamer theory of breakdownvishalgohel12195
 
Lab manual psd v sem experiment no 7
Lab manual psd v sem experiment no 7Lab manual psd v sem experiment no 7
Lab manual psd v sem experiment no 7Sachin Airan
 
Fault Location Of Transmission Line
Fault Location Of Transmission LineFault Location Of Transmission Line
Fault Location Of Transmission LineCHIRANJEEB DASH
 
Distribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss CalculationDistribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss CalculationAmeen San
 
Different Kinds of Maximum Power Point Tracking Control Method for Photovolta...
Different Kinds of Maximum Power Point Tracking Control Method for Photovolta...Different Kinds of Maximum Power Point Tracking Control Method for Photovolta...
Different Kinds of Maximum Power Point Tracking Control Method for Photovolta...yash yadav
 
PROPOSED FAULT DETECTION ON OVERHEAD TRANSMISSION LINE USING PARTICLE SWARM ...
PROPOSED FAULT DETECTION ON OVERHEAD TRANSMISSION LINE  USING PARTICLE SWARM ...PROPOSED FAULT DETECTION ON OVERHEAD TRANSMISSION LINE  USING PARTICLE SWARM ...
PROPOSED FAULT DETECTION ON OVERHEAD TRANSMISSION LINE USING PARTICLE SWARM ...Politeknik Negeri Ujung Pandang
 
PPT ON 220KV GSS
PPT ON 220KV GSSPPT ON 220KV GSS
PPT ON 220KV GSSMohitkalal4
 
Impacts of Distributed Generation on Power Quality
Impacts of Distributed Generation on Power QualityImpacts of Distributed Generation on Power Quality
Impacts of Distributed Generation on Power QualityParth Patel
 
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54Subhash Mahla
 
POWER QUALITY ISSUES (POWER SYSTEM AND POWER ELECTRONICS)
POWER QUALITY ISSUES (POWER SYSTEM AND POWER ELECTRONICS)POWER QUALITY ISSUES (POWER SYSTEM AND POWER ELECTRONICS)
POWER QUALITY ISSUES (POWER SYSTEM AND POWER ELECTRONICS)Rohit vijay
 

Tendances (20)

Power System Protection Technique: A Review
Power System Protection Technique: A ReviewPower System Protection Technique: A Review
Power System Protection Technique: A Review
 
Airborne Wind Turbines - A report
Airborne Wind Turbines - A reportAirborne Wind Turbines - A report
Airborne Wind Turbines - A report
 
Power quality ppt
Power quality pptPower quality ppt
Power quality ppt
 
Fundamentals of substaion
Fundamentals of substaionFundamentals of substaion
Fundamentals of substaion
 
Streamer theory of breakdown
Streamer theory of breakdownStreamer theory of breakdown
Streamer theory of breakdown
 
Lab manual psd v sem experiment no 7
Lab manual psd v sem experiment no 7Lab manual psd v sem experiment no 7
Lab manual psd v sem experiment no 7
 
Fault Location Of Transmission Line
Fault Location Of Transmission LineFault Location Of Transmission Line
Fault Location Of Transmission Line
 
Et601 chapter1 ayu
Et601  chapter1 ayuEt601  chapter1 ayu
Et601 chapter1 ayu
 
Distribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss CalculationDistribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss Calculation
 
Different Kinds of Maximum Power Point Tracking Control Method for Photovolta...
Different Kinds of Maximum Power Point Tracking Control Method for Photovolta...Different Kinds of Maximum Power Point Tracking Control Method for Photovolta...
Different Kinds of Maximum Power Point Tracking Control Method for Photovolta...
 
FEEDER PROTECTION RELAY
FEEDER PROTECTION RELAYFEEDER PROTECTION RELAY
FEEDER PROTECTION RELAY
 
PROPOSED FAULT DETECTION ON OVERHEAD TRANSMISSION LINE USING PARTICLE SWARM ...
PROPOSED FAULT DETECTION ON OVERHEAD TRANSMISSION LINE  USING PARTICLE SWARM ...PROPOSED FAULT DETECTION ON OVERHEAD TRANSMISSION LINE  USING PARTICLE SWARM ...
PROPOSED FAULT DETECTION ON OVERHEAD TRANSMISSION LINE USING PARTICLE SWARM ...
 
PPT ON 220KV GSS
PPT ON 220KV GSSPPT ON 220KV GSS
PPT ON 220KV GSS
 
Computer Application in Power system chapter one - introduction
Computer Application in Power system chapter one - introductionComputer Application in Power system chapter one - introduction
Computer Application in Power system chapter one - introduction
 
Floating power stations
Floating power stationsFloating power stations
Floating power stations
 
UPS Presentation
UPS PresentationUPS Presentation
UPS Presentation
 
Impacts of Distributed Generation on Power Quality
Impacts of Distributed Generation on Power QualityImpacts of Distributed Generation on Power Quality
Impacts of Distributed Generation on Power Quality
 
EE6711 Power System Simulation Lab manual
EE6711 Power System Simulation Lab manualEE6711 Power System Simulation Lab manual
EE6711 Power System Simulation Lab manual
 
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
 
POWER QUALITY ISSUES (POWER SYSTEM AND POWER ELECTRONICS)
POWER QUALITY ISSUES (POWER SYSTEM AND POWER ELECTRONICS)POWER QUALITY ISSUES (POWER SYSTEM AND POWER ELECTRONICS)
POWER QUALITY ISSUES (POWER SYSTEM AND POWER ELECTRONICS)
 

Similaire à Training report of secl , khairha coal mine , sohagpur area for electrical

Trainingreport 120930165750-phpapp01
Trainingreport 120930165750-phpapp01Trainingreport 120930165750-phpapp01
Trainingreport 120930165750-phpapp01Vinay Vashisht
 
33-11-kv-substation-training-report (1) (1).pdf
33-11-kv-substation-training-report (1) (1).pdf33-11-kv-substation-training-report (1) (1).pdf
33-11-kv-substation-training-report (1) (1).pdfSagarRana91
 
Trainingreport 132 KV
Trainingreport 132 KVTrainingreport 132 KV
Trainingreport 132 KVAbrar Ahamed
 
BSES - Maintaince of EHV Equipments
BSES - Maintaince of EHV Equipments BSES - Maintaince of EHV Equipments
BSES - Maintaince of EHV Equipments Anuj Gupta
 
sub-station training report
sub-station training reportsub-station training report
sub-station training reportsitesh95074
 
Sub-station training REPORT
Sub-station training REPORTSub-station training REPORT
Sub-station training REPORTsitesh95074
 
220 kv Sub-station Summer Training ppt
220 kv Sub-station Summer Training ppt220 kv Sub-station Summer Training ppt
220 kv Sub-station Summer Training pptShubham Patel
 
132 33kv substation documentation
132 33kv substation documentation132 33kv substation documentation
132 33kv substation documentationRajashekar Gurrala
 
Summer Training Report Ntpc barh (ajeet)
Summer Training Report Ntpc barh (ajeet)Summer Training Report Ntpc barh (ajeet)
Summer Training Report Ntpc barh (ajeet)Ajeet Chaurasia
 
DLW Varanasi Training report
DLW Varanasi Training reportDLW Varanasi Training report
DLW Varanasi Training reportGyanendra Prakash
 
Internship doc 33 11 kv substation
Internship doc 33 11 kv substation  Internship doc 33 11 kv substation
Internship doc 33 11 kv substation Madeen Kumar
 
132 KV GSS NPH jodhpur treaning report
132 KV GSS NPH jodhpur treaning report 132 KV GSS NPH jodhpur treaning report
132 KV GSS NPH jodhpur treaning report imkanhaiyalal
 
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...Devendra Kumar
 
Stand alone regulated single phase five level inverter with coupled inductor
Stand alone regulated single phase five level inverter with coupled inductorStand alone regulated single phase five level inverter with coupled inductor
Stand alone regulated single phase five level inverter with coupled inductorIAEME Publication
 
substation 220 kv
substation 220 kv substation 220 kv
substation 220 kv student
 

Similaire à Training report of secl , khairha coal mine , sohagpur area for electrical (20)

33/11 KV SUBSTATION
33/11 KV SUBSTATION33/11 KV SUBSTATION
33/11 KV SUBSTATION
 
33 kv substation vt report
33 kv substation vt report33 kv substation vt report
33 kv substation vt report
 
Trainingreport 120930165750-phpapp01
Trainingreport 120930165750-phpapp01Trainingreport 120930165750-phpapp01
Trainingreport 120930165750-phpapp01
 
33-11-kv-substation-training-report (1) (1).pdf
33-11-kv-substation-training-report (1) (1).pdf33-11-kv-substation-training-report (1) (1).pdf
33-11-kv-substation-training-report (1) (1).pdf
 
Trainingreport 132 KV
Trainingreport 132 KVTrainingreport 132 KV
Trainingreport 132 KV
 
BSES - Maintaince of EHV Equipments
BSES - Maintaince of EHV Equipments BSES - Maintaince of EHV Equipments
BSES - Maintaince of EHV Equipments
 
132kv G.S.S. Jalore
132kv G.S.S. Jalore132kv G.S.S. Jalore
132kv G.S.S. Jalore
 
sub-station training report
sub-station training reportsub-station training report
sub-station training report
 
finalseminar.docx
finalseminar.docxfinalseminar.docx
finalseminar.docx
 
Sub-station training REPORT
Sub-station training REPORTSub-station training REPORT
Sub-station training REPORT
 
220 kv Sub-station Summer Training ppt
220 kv Sub-station Summer Training ppt220 kv Sub-station Summer Training ppt
220 kv Sub-station Summer Training ppt
 
132 33kv substation documentation
132 33kv substation documentation132 33kv substation documentation
132 33kv substation documentation
 
Summer Training Report Ntpc barh (ajeet)
Summer Training Report Ntpc barh (ajeet)Summer Training Report Ntpc barh (ajeet)
Summer Training Report Ntpc barh (ajeet)
 
DLW Varanasi Training report
DLW Varanasi Training reportDLW Varanasi Training report
DLW Varanasi Training report
 
Internship doc 33 11 kv substation
Internship doc 33 11 kv substation  Internship doc 33 11 kv substation
Internship doc 33 11 kv substation
 
132 KV GSS NPH jodhpur treaning report
132 KV GSS NPH jodhpur treaning report 132 KV GSS NPH jodhpur treaning report
132 KV GSS NPH jodhpur treaning report
 
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
 
DPL Training .doc file
DPL Training .doc file DPL Training .doc file
DPL Training .doc file
 
Stand alone regulated single phase five level inverter with coupled inductor
Stand alone regulated single phase five level inverter with coupled inductorStand alone regulated single phase five level inverter with coupled inductor
Stand alone regulated single phase five level inverter with coupled inductor
 
substation 220 kv
substation 220 kv substation 220 kv
substation 220 kv
 

Dernier

Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17  How to Extend Models Using Mixin ClassesMixin Classes in Odoo 17  How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17 How to Extend Models Using Mixin ClassesCeline George
 
Sports & Fitness Value Added Course FY..
Sports & Fitness Value Added Course FY..Sports & Fitness Value Added Course FY..
Sports & Fitness Value Added Course FY..Disha Kariya
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdfQucHHunhnh
 
Paris 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityParis 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityGeoBlogs
 
Measures of Dispersion and Variability: Range, QD, AD and SD
Measures of Dispersion and Variability: Range, QD, AD and SDMeasures of Dispersion and Variability: Range, QD, AD and SD
Measures of Dispersion and Variability: Range, QD, AD and SDThiyagu K
 
Grant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingGrant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingTechSoup
 
Unit-IV- Pharma. Marketing Channels.pptx
Unit-IV- Pharma. Marketing Channels.pptxUnit-IV- Pharma. Marketing Channels.pptx
Unit-IV- Pharma. Marketing Channels.pptxVishalSingh1417
 
Activity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfActivity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfciinovamais
 
Measures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeMeasures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeThiyagu K
 
Accessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactAccessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactdawncurless
 
Web & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfWeb & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfJayanti Pande
 
An Overview of Mutual Funds Bcom Project.pdf
An Overview of Mutual Funds Bcom Project.pdfAn Overview of Mutual Funds Bcom Project.pdf
An Overview of Mutual Funds Bcom Project.pdfSanaAli374401
 
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...EduSkills OECD
 
Holdier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdfHoldier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdfagholdier
 
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in DelhiRussian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhikauryashika82
 
Making and Justifying Mathematical Decisions.pdf
Making and Justifying Mathematical Decisions.pdfMaking and Justifying Mathematical Decisions.pdf
Making and Justifying Mathematical Decisions.pdfChris Hunter
 

Dernier (20)

Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17  How to Extend Models Using Mixin ClassesMixin Classes in Odoo 17  How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
 
Sports & Fitness Value Added Course FY..
Sports & Fitness Value Added Course FY..Sports & Fitness Value Added Course FY..
Sports & Fitness Value Added Course FY..
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdf
 
Mattingly "AI & Prompt Design: The Basics of Prompt Design"
Mattingly "AI & Prompt Design: The Basics of Prompt Design"Mattingly "AI & Prompt Design: The Basics of Prompt Design"
Mattingly "AI & Prompt Design: The Basics of Prompt Design"
 
Paris 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityParis 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activity
 
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptxINDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
 
Código Creativo y Arte de Software | Unidad 1
Código Creativo y Arte de Software | Unidad 1Código Creativo y Arte de Software | Unidad 1
Código Creativo y Arte de Software | Unidad 1
 
Measures of Dispersion and Variability: Range, QD, AD and SD
Measures of Dispersion and Variability: Range, QD, AD and SDMeasures of Dispersion and Variability: Range, QD, AD and SD
Measures of Dispersion and Variability: Range, QD, AD and SD
 
Grant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingGrant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy Consulting
 
Unit-IV- Pharma. Marketing Channels.pptx
Unit-IV- Pharma. Marketing Channels.pptxUnit-IV- Pharma. Marketing Channels.pptx
Unit-IV- Pharma. Marketing Channels.pptx
 
Activity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfActivity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdf
 
Mattingly "AI & Prompt Design: Structured Data, Assistants, & RAG"
Mattingly "AI & Prompt Design: Structured Data, Assistants, & RAG"Mattingly "AI & Prompt Design: Structured Data, Assistants, & RAG"
Mattingly "AI & Prompt Design: Structured Data, Assistants, & RAG"
 
Measures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeMeasures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and Mode
 
Accessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactAccessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impact
 
Web & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfWeb & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdf
 
An Overview of Mutual Funds Bcom Project.pdf
An Overview of Mutual Funds Bcom Project.pdfAn Overview of Mutual Funds Bcom Project.pdf
An Overview of Mutual Funds Bcom Project.pdf
 
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
 
Holdier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdfHoldier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdf
 
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in DelhiRussian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
 
Making and Justifying Mathematical Decisions.pdf
Making and Justifying Mathematical Decisions.pdfMaking and Justifying Mathematical Decisions.pdf
Making and Justifying Mathematical Decisions.pdf
 

Training report of secl , khairha coal mine , sohagpur area for electrical

  • 1. GOVERNMENT ENGINEERING COLLEGE BILASPUR KHAIRHA UNDER-GROUND MINE VOCATIONAL TRANING REPORT NAME- PIYUSH KUMAR DWIVEDI ROLLNO-30724120.. SUBMITTED TO BRANCH- ELECTRICAL DATE- 08/07/2015 TO 07/08/2015
  • 2. TRAINING REPORT ON SOUTH EASTERN COLFILELD LIMITED Table of contents ACKNOWLEDGEMENT i LIST OF FIGURES ii 1. Introduction 1-2 1.1 About 33/11 KV substation 1 2. Transformers 3-5 2.1 Types of Transformers 3-5 2.1.1 Power transformer 4 2.1.2 Instrument transformer 4 2.1.3 Autotransformer 5 2.1.4 On the basis of working 5 2.1.5 On the basis of structure 5 3. Specification of C.T. used in 33/11 KV substation Sector-25,Indranagar 6 4. Substation 7-13 4.1 Types of substation 8 4.1.1 According to the service requirement 8 4.1.2 According to the constructional features 8 4.2 Substation characteristics 10 4.3 Steps in designing substation 10 4.3.1 Earthing and bonding 10 4.3.2 Substation earthing calculation methodology 11 4.3.3 Earthing material 11
  • 3. 4.3.4 Switch yard fence earthing 12 4.4 Conductors used in substation designing 12 5. Chronological training diary 14-17 5.1 Power line carrier communication(PLCC) 14 5.1.1 Applications 14 5.2 Principle of PLCC 15 5.2.1 Wave trap or line trap 15 5.2.2 Coupling capacitor 16 5.2.3 Protective device of coarse voltage arrester 16 5.2.4 Coupling of filter 16 5.2.5 H.F. cable 16 6. Bus bars 18-19 7. Insulators 20-25 7.1 Circuit breakers 21 7.2 Oil circuit breaker 22 7.3 Air blast circuit breaker 22 7.4 Sulphar hexafluoride circuit breaker (SF6)circuit breaker 23 7.5 Vacuum circuit breaker 24 8. Metering and Indication equipment 26-29 8.1 Relay 26 8.2 Relays used in control panel of substation 27 8.2.1 Differential relay 27
  • 4. 8.2.2 Over current relay 27 8.2.3 Directional relay 28 8.2.4 Tripping relay 28 8.2.5 Auxiliary relay 29 9. Miscellaneous Equipments 30-31 9.1 Capacitor bank 30 9.2 Fuse 31 9.3 Bus coupler 31 10. Protection of substation 32-33 10.1 Transformer protection 32 10.2 Conservation and breather 32 10.3 Marshalling box 32 10.4 Transformer cooling 33 11. Mine Load Centers/Power Centers 34 12. Switchgear 35 13. Motor Control Centers 36 14. Mine Substation 37 15. Capacitor Banks 38 16. Leaky Feeder Radio Systems 39 17. Diesel Generator Set 40 18. Vehicle and Personnel Tracking Systems 41 19. CONCLUSION 43 References 44
  • 5. ACKNOWLEDGEMENT Training has an important role in exposing the real life situation in an industry. It was a great experience for me to work on training at SOUTH EASTERN COLFILELD LIMITED through which I could learn how to work in a professional environment. Now, I would like to thank the people who guided me and have been a constant source of inspiration throughout the tenure of my summer training. I am sincerely grateful to MR. N.Y.HADKE being the ENGINEER at 33/3.3 KV substation, KHAIRHA U/G MINE who rendered me his valuable assistance, constant encouragement and able guidance which made this training actually possible. Piyush Dwivedi
  • 6. List of figures Figure no. Name of figure Page no. Figure 1.1 33/3.3 KV Substation khairha mine 1 Figure 2.1 Transformer 3 Figure 2.2 Power transformer 4 Figure 2.3 Instrument transformer 4 Figure 2.4 Auto transformer 5 Figure 2.5 Core type 5 Figure 2.6 Shell type 5 Figure 3.1 Current transformer 6 Figure 4.1 View of substation 7 Figure 4.2 Transformer substation 8 Figure 5.1 Power line carrier communication (PLCC) 14 Figure 6.1 Typical representation of bus bars 18 Figure 7.1 Insulators used in substation 20 Figure 7.2 Circuit breaker arrangements 21 Figure 7.3 Oil circuit breaker 22 Figure 7.4 Air blast circuit breaker 23 Figure 7.5 SF6 Circuit breaker 23 Figure 7.6 Vacuum circuit breaker 24 Figure 8.1 Typical view of Relay 26 Figure 8.2 Differential Relay 27 Figure 8.3 Over current Relay 27 Figure 8.4 Directional Relay 28 Figure 8.5 Tripping Relay 28 Figure 8.6 Auxiliary Relay 29 Figure 9.1 Capacitor bank 30 Figure 9.2 Substation fuse 31 Figure 9.3 Bus coupler 32
  • 7. Figure 9.4 Mine Load Centers/Power Centers 33 Figure 9.5 Switchgear 34 Figure 9.6 Motor Control Centers 35 Figure 9.7 Mine Substation 36 Figure 9.8 Capacitor Banks 37 Figure 9.9 Diesel Generator Set 38 Figure 9.10 Vehicle and Personnel Tracking Systems 39
  • 8. 1. INTRODUCTION The creation of South Eastern Coalfield Ltd. (SECL) on JULY is the result of power sector reforms and restructuring in MP (India) which is the focal point of the Power Sector, responsible for planning and managing the sector through its production, distribution and supply of Coal. SECL will be professionally managed utility supplying reliable and cost efficient electricity to every citizen of the state through highly motivated employees and state of art technologies, providing an economic return to our owners and maintaining leadership in the country. We shall achieve this being a dynamic, forward looking, reliable, safe and trustworthy organization, sensitive to our customers interests, profitable and sustainable in the long run, providing uninterrupted supply of quality power, with transparency and integrity in operation 1.1 ABOUT 33/3.3 KV SUBSTATION KHAIRHA MINE Figure 1.1 33/3.3 KV Substation khairha mine
  • 9. 1.2 UNDER GROUND ELECTRICALCAL POWER SYSTEM IN KHAIRHA MINE
  • 10. The main bus 33KV is connected to bus-bar of the substation of KHAIRHA mine. Now the transmission line first parallel connected with lightning arrester to diverge surge, followed by CVT connected parallel. CVT measures voltage and steeps down at 110V. A.C. for control panel, at the location a wave trap is connected to carrier communication at higher frequencies. A current transformer is connected in series with line which measure current. Switchgear equipment is provided, which is the combination of a circuit breaker having an isolator at each end. A transformer is connected to main bus though a bus coupler. The main bus has total capability of 160 MVA for 3.3 KV, which is subdivided into two transformer capacity of 80 MVA (40MVA+40MVA) parallel connected for 3.3KV and other two transformer capacity of 80KV (40KV+40KV) are parallel connected for substation. At both ends of transformer lightning arrester current transformer and switchgear equipment provided. Transformer step downs voltage from 33KV to 3.3KV. The main bus is provided with switchgear equipment & a current transformer. This gives way to two feeders transmitting power to KHAIRHA underground mine. One feeder is used at a time [BAGWAR] and 2nd is backup [DAMINI]. The main bus is connected to jack bus or transfer bus through a bus coupler & 550V is provided with switchgear equipment. A step down transformer of 3.3KV/440V 3.3KV/11OV & 3.3KV/220V is connected to control panel to provide supply to the equipments of the substation. Capacitor bank is connected to main bus of 3.3KV. It is provided to improve power factor & voltage profile. In the surface substation power is step down by 33/3.3kv, 33kv/110v and 33kv/220v through the step down transformer and in 2nd level underground substation power is step down by 3.3kv/550v for different kind of uses like lighting, motoring, air conditioning etc 2nd level substation is parallel connected through 19th level substation and hears power is step down by 3.3kv/550v for lighting, motoring, Air conditioning or HDL machine. HDL machine is the main machine in the coal mine is operated on 550v DC supply.
  • 11. 2. TRANSFORMERS Figure: 2.1 Transformer Transformer is a static machine, which transforms the potential of alternating current at same frequency. It means the transformer transforms the low voltage into high voltage & high voltage to low voltage at same frequency. It works on the principle of static induction principle. When the energy is transformed into a higher voltage, the transformer is called step up transformer but in case of other is known as step down transformer. 2.1 TYPES OF TRANSFORMER 2.1.1 Power transformer 2.1.2 Instrument transformer 2.1.3 Auto transformer 2.1.4 On the basis of working 2.1.5 On the basis of structure
  • 12. 2.1.1 POWER TRANSFORMER: Figure 2.2 Power Transformers Types of power transformer: 2.1.1.1 Single phase transformer 2.1.1.2 Three phase transformer 2.1.2 INSTRUMENT TRANSFORMER: Fig: 2.3 Instrument Transformers a) Current transformer b) Potential transformer
  • 13. 2.1.3AUTO TRANSFORMER: Fig 2.4 Auto Transformer a) Single phase transformer b) Three phase transformer 2.1.4 ON THE BASIS OF WORKING 2.1.4.1Step down: Converts high voltage into low voltage. 2.1.4.2 Step up: Converts low voltage into high voltage. 2.1.5 ON THE BASIS OF STRUCTURE Figure 2.5 core typeFigure 2.6 Shell type
  • 14. 3. SPECIFICATION OF C.T. USED IN 33/3.3 KV SUB STATION Figure 3.1 Current transformer 3.1 Standard: IS-2785 3.2 Highest System Voltage: 145 KV 3.3 Frequency: 50Hz 3.4 C.T. Current: 25 KA/1Sec. 3.5 Rated primary current: 800 Ampere
  • 15. 4. SUBSTATIONS Figure 4.1View of substation The present day electrical power system is A.C.i.e. electrical power is generated, transmitted & distributed in the form of the alternating current. The electric power is produced at power plant stations which are located at favorable places generally quite away from the consumers. It is delivered to the consumers through a large network of transmission 7 distribution. At many places in the power system, it may be desirable and necessary to change some characteristics e.g. voltage, ac to dc, frequency, power factor etc. of electric supply. This accomplished by suitable apparatus called substation. For example; generation voltage (11 KV or 33 KV) at the power station is set up to high voltage (say 220 KV or 132 KV) for transmission of electric power. The assembly of apparatus (e.g. transformer etc.) used for this purpose in the substation. Similarly near the consumer’s localities, the voltage may have to be step down to utilization level. This job is again accomplished by suitable apparatus called substation. The assembly of apparatus to change some characteristic of electric power supply is called substation. The two most ways to classify substation are:-
  • 16. 4.1 TYPES OF SUBSTATION 4.1.1 According to the service requirement: 4.1.1.1 Transformer substation 4.1.1.2 Switch substation 4.1.1.3 Power factor correction substation 4.1.1.4 Frequency change substation 4.1.1.5 Converting substation 4.1.1.6 Industrial substation 4.1.2 According to the constructionalfeatures: 4.1.2.1 Indoor substation 4.1.2.3 Outdoor substation 4.1.2.4 Underground substation 4.1.2.5 Pole mounted substation 4.1.1.1 TRANSFORMER SUBSTATION Figure 4.2 Transformer substation They are known as transformer substations as because transformer is the main component employed to change the voltage level, depending upon the purposed served
  • 17. transformer substations may be classified into: 4.1.1.1.1 STEP UP SUBSTATION The generation voltage is steeped up to high voltage to affect economy in transmission of electric power. These are generally located in the power houses and are of outdoor type. 4.1.1.1.2 PRIMARY GRID SUBSTATION Here, electric power is received by primary substation which reduces the voltage level to 11KV for secondary transmission. The primary grid substation is generally of outdoor type. 4.1.1.1.3SECONDARY SUBSTATIONS At a secondary substation, the voltage is further steeped down to 11KV. The 11KV lines runs along the important road of the city. The secondary substations are also of outdoor type. 4.1.1.1.3 DISTRIBUTION SUBSTATION These substations are located near the consumer’s localities and step down to 400V, 3-phase, 4-wire for supplying to the consumers. The voltage between any two phases is 400V & between any phase and neutral it is 230V. 4.2 SUBSTATION CHARACTERISTICS: 4.2.1 Each circuit is protected by its own circuit breaker and hence plant outage does not necessarily result in loss of supply. 4.2.2 A fault on the feeder or transformer circuit breaker causes loss of the transformer and feeder circuit, one of which may be restored after isolating the faulty circuit breaker.
  • 18. 4.2.3 A fault on the bus section circuit breaker causes complete shutdown of the substation. All circuits may be restored after isolating the faulty circuit breaker. 4.2.4 Maintenance of a feeder or transformer circuit breaker involves loss of the circuit. 4.2.5 Introduction of bypass isolators between bus bar and circuit isolator allows circuit breaker maintenance facilities without loss of that circuit. 4.3 STEPS IN DESIGNING SUBSTATION: The First Step in designing a Substation is to design an Earthing and Bonding System. 4.3.1 Earthing and Bonding: The function of an earthing and bonding system is to provide an earthing system connection to which transformer neutrals or earthing impedances may be connected in order to pass the maximum fault current. The earthing system also ensures that no thermal or mechanical damage occurs on the equipment within the substation, thereby resulting in safety to operation and maintenance personnel. The earthing system also guarantees equipotent bonding such that there are no dangerous potential gradients developed in the substation. In designing the substation, three voltage have to be considered these are: 4.3.1.1Touch Voltage: This is the difference in potential between the surface potential and the potential at earthedequipment whilst a man is standing and touching the earthed structure. 4.3.1.2Step Voltage: This is the potential difference developed when a man bridges a distance of 1m with his feet while not touching any other earthed equipment. 4.3.1.3 Mesh Voltage: This is the maximum touch voltage that is developed in the mesh of the earthing grid.
  • 19. 4.3.2 SubstationEarthing CalculationMethodology Calculations for earth impedances, touch and step potentials are based on site measurements of ground resistivity and system fault levels. A grid layout with particular conductors is then analyzed to determine the effective substation earthing resistance, from which the earthing voltage is calculated. In practice, it is normal to take the highest fault level for substation earth grid calculation purposes. Additionally, it is necessary to ensure a sufficient margin such that expansion of the system is catered for. To determine the earth resistivity, probe tests are carried out on the site. These tests are best performed in dry weather such that conservative resistivity readings are obtained. 4.3.3Earthing Materials 4.3.3.4Conductors: Bare copper conductor is usually used for the substation earthing grid. The copper bars themselves usually have a cross-sectional area of 95 square millimeters, and they are laid at a shallow depthof 0.25-0.5m, in 3-7m squares. In addition to the buried potential earth grid, a separate above ground earthing ring is usually provided, to which all metallic substation plant is bonded. 4.3.3.4Connections: Connections to the grid and other earthing joints should not be soldered because the heat generated during fault conditions could cause a soldered joint to fail. Joints are usually bolted. 4.3.3.5Earthing Rods:
  • 20. The earthing grid must be supplemented by earthing rods to assist in the dissipation of earth faultcurrents and further reduce the overall substation earthing resistance. These rods are usually made ofsolid copper, or copper clad steel. 4.3.4 Switchyard Fence Earthing: The switchyard fence earthing practices are possible and are used by different utilities. These are: 4.3.4.1 Extend the substation earth grid 0.5m-1.5m beyond the fence perimeter. The fence is thenbonded to the grid at regular intervals. 4.3.4.2 Place the fence beyond the perimeter of the switchyard earthing grid and bond the fence to its own earthing rod system. This earthing rod system is not coupled to the main substation earthing grid. 4.4 CONDUCTORS USED IN SUBSTATION DESIGN: An ideal conductor should fulfills the following requirements: 4.4.1 Should be capable of carrying the specified load currents and short time currents. 4.4.2 Should be able to withstand forces on it due to its situation. These forces comprise self weight, and weight of other conductors and equipment, short circuit forces and atmospheric forces such as wind and ice loading. 4.4.3 Should be corona free at rated voltage. 4.4.4 Should have the minimum number of joints. 4.4.5 Should need the minimum number of supporting insulators. 4.4.6 Should be economical. The most suitable material for the conductor system is copper or aluminums. Steel may be used but has limitations of poor conductivity and high susceptibility to corrosion. In an effort to make the conductor ideal, three different types have been utilized, and these include: Flat surfaced Conductors, Stranded Conductors, and Tubular Conductors
  • 21. 4.5Overhead Line Terminations Two methods are used to terminate overhead lines at a substation. 4.5.1 Tensioning conductors to substation structures or buildings 4.5.2 Tensioning conductors to ground winches. The choice is influenced by the height of towers and the proximity to the substation.The following clearances should be observed: VOLTAGE LEVEL MINIMUM GROUND CLEARANCE less than 11kV 6.1m 11kV - 20kV 6.4m 20kV - 30kV 6.7m greater than 30kV 7.0m Table 1 Clearance in accordance with voltage value
  • 22. 5. CHRONOLOGICAL TRAINING DIARY ( based on study & observation at different Departments and sections) 5.1 POWER LINE CARRIER COMMUNICATION Introduction: Figure 5.1: PLCC (POWER LINE CARRIER COMMUNICATION) Reliable & fast communication is necessary for safe efficient &economical power supply. To reduce the power failure in extent & time, to maintain the interconnected grid system in optimum working condition; to coordinate the operation of various generating unit communication network is indispensable for state electricity board. In state electricity boards, the generating & distribution stations are generally located at a far distance from cities. Where P & T communication provided through long overhead lines in neither reliable nor quick. As we have available very reliable physical paths viz. the power lines, which interconnected, hence power line carrier communication is found to be most economical and reliable for electricity boards.
  • 23. 5.1.1 APPLICATIONS: The PLCC can be used for the following facilities: 5.1.1.1 Telephony 5.1.1.2 Teleprotection 5.1.1.3 Remote control or indication 5.1.1.4 Telemetry 5.1.1.5Teleprinting 5.2 PRINCIPLE OF PLCC: The principle of PLCC is the simple one: All type of information is modulated on carried wave at frequency 50Hz to 500 KHz. The modulated HF carrier fed into the power line conductor at the sending end and filtered out again at the respective stations. Long earlier system double side band amplitude modulation was more common but the present amplitude modulated system. Since high voltage power lines are designed to carry large quantities of energy on the high voltage and the communication system at low voltage, they cannot be directly connected to high voltage lines. Suitably designed coupling equipments have therefore to be employed which will permit the injection of high frequency carrier signal without undue loss and with absolute protection of communication equipments or operating personal from high voltage hazard. Therefore, the coupling equipment essentially comprises the following: 5.2.1 Wave trap or line trap: Wave trap is connected in series with power line between the point of connection of coupling capacitor and S/S. Wave trap offers negligible impedance to HF carrier. Wave trap stands electromechanically and thermally for short circuit current in the event of fault on the line. On the basis of blocking frequency bank, the wave trap can be following type: 5.2.1.1 ALL WAVE 5.2.1.2 SINGAL FREQUENCY 5.2.1.3 DOUBLE FREQUENCY 5.2.1.4 BROAD BAND
  • 24. 5.2.2 Coupling capacitor: The modulated carrier is let into power line through coupling capacitor specially designed to with stand line voltage under all weather condition. The upper end of the coupling capacitor is connected directly to the line and the lower end is connected to the ground through a carrier frequency chock coil or drain coil. Thus coupling capacitor forms the link between the PLCC equipment and power line. The coupling capacitor used in UPSEB is 2200pf capacitance. The coupling capacitor are designed for outdoor use and hence to withstand normal atmospheric phenomenon such as temperature & humidity changes, rain, snow, anticipated wind load, nominal wire tension etc. at full rated voltage. In some case capacitive voltage transformers (CVT) used as a source of line voltage for metering and protection as also used coupling capacitor for PLCC. 5.2.3 Protective Device of Coarse Voltage Arrester: This is connected across the primary of the coupling filter i.e. one end is connected to the bottom of the coupling capacitor and other end is earthed. This is provided to protect the coupling filter against line surges. An air gap is provided, where voltage of the order of 1.8 to 2KV as observed across due to lighting etc. on line. 5.2.4 Coupling of Filter: The coupling filter is inserted between the low voltage terminal of the coupling capacitor and the carrier frequency connection of the carrier terminal. Some time an earth switch is also provided with this unit. This unit mainly performs two functions; firstly it isolates the connection of equipment from the power line. Secondly it serves to match characteristic impedance of the power line to that of the H.F. cable to connection equipments. 5.2.5 H.F. Cable: H.F. cable normally used to connect the coupling filter to another coupling terminal. The cable is insulated to withstand the test voltage of 4KV. The impedance of this H.F. cable is so as to match with the output of the PLCC terminal and secondary impedance of coupling filter.
  • 25. 5.2.5.1 TYPES OF COUPLING: The following three types of coupling are being used in UPSEB depending on the requirement: 5.2.5.1.1 Phase to ground coupling 5.2.5.1.2 Phase to phase coupling 5.2.5.1.3 Internal coupling 5.2.5.2 COUPLING LOSSES: 5.2.5.2.1 Composite loss 5.2.5.2.2 Tapping loss 5.2.5.2.3 H.F. cable loss 5.2.5.2.4 Additional loss
  • 26. 6. BUSBARS Figure 6.1 Typical representation of bus bars When numbers of generators or feeders operating at the same voltage have to be directly connected electrically, bus bar is used as the common electrical component. Bus bars are made up of copper rods operate at constant voltage. The following are the important bus bars arrangements used at substations: 6.1 Single bus bar system 6.2 Single bus bar system with section alisation. 6.3 Duplicate bus bar system In large stations it is important that break downs and maintenance should interfere as little as possible with continuity of supply to achieve this, duplicate bus bar system is used. Such a system consists of two bus bars, a main bus bar and a spare bus bar with the help of bus coupler, which consist of the circuit breaker and isolator. In substations, it is often desired to disconnect a part of the system for general maintenance and repairs. An isolating switch or isolator accomplishes this. Isolator operates under no load condition. It does not have any specified current breaking capacity or current making capacity. In
  • 27. some cases isolators are used to breaking charging currents or transmission lines. While opening a circuit, the circuit breaker is opened first then isolator while closing a circuit the isolator is closed first, then circuit breakers. Isolators are necessary on supply side of circuit breakers, in order to ensure isolation of the circuit breaker from live parts for the purpose of maintenance. A transfer isolator is used to transfer main supply from main bus to transfer bus by using bus coupler (combination of a circuit breaker with two isolators), if repairing or maintenance of any section is required.
  • 28. 7. INSULATORS The insulator serves two purposes. They support the conductors (bus bar) and confine the current to the conductors. The most common used material for the manufacture of insulator is porcelain. There are several types of insulators (e.g. pin type, suspension type, post insulator etc.) and their use in substation will depend upon the service requirement. For example, post insulator is used for bus bars. A post insulator consists of a porcelain body, cast iron cap and flanged cast iron base. The hole in the cap is threaded so that bus bars can be directly bolted to the cap. Figure 7.1 Insulators used in substations With the advantage of power system, the lines and other equipment operate at very high voltage and carry high current. The arrangements of switching along with switches cannot serve the desired function of switchgear in such high capacity circuits. This necessitates employing a more dependable means of control such as is obtain by the use of the circuit breakers. A circuit breaker can make or break a circuit either manually or automatically under all condition as no load, full load and short circuit condition. A circuit breaker essentially consists of fixed and moving contacts. These contacts can be opened manually or by remote control whenever desired. When a fault occurs on any part of the system, the trip coils of breaker get energized and the moving contacts are pulled apart by some
  • 29. mechanism, thus opening the circuit. When contacts of a circuit breaker are separated, an arc is struck; the current is thus able to continue. The production of arcs are not only delays the current interruption, but is also generates the heat. Therefore, the main problem is to distinguish the arc within the shortest possible time so that it may not reach a dangerous value. The general way of classification is on the basis of the medium used for arc extinction. Figure 7.2 Circuit breaker arrangements 7.1. Circuit breakers They can be classified into: 7.1.1 Oil circuit breaker 7.1.2 Air-blast circuit breaker 7.1.3 Sulphar hexafluoride circuit breaker (SF6) 7.1.4 Vacuum circuit breakers Note: SF6 and Vacuum circuit breaker are being used in 33KV distribution substation.
  • 30. 7.2 Oil Circuit Breaker Figure 7.3 Oil circuit breaker A high-voltage circuit breaker in which the arc is drawn in oil to dissipate the heat and extinguish the arc; the intense heat of the arc decomposes the oil, generating a gas whose high pressure produces a flow of fresh fluid through the arc that furnishes the necessary insulation to prevent a restrike of the arc. The arc is then extinguished, both because of its elongation upon parting of contacts and because of intensive cooling by the gases and oil vapor. 7.3 Air blast circuit breaker Fast operations, suitability for repeated operation, auto reclosure, unit type multi break constructions, simple assembly, modest maintenance are some of the main features of air blast circuit breakers. A compressors plant necessary to maintain high air pressure in the air receiver. The air blast circuit breakers are especially suitable for railways and arc furnaces, where the breaker operates repeatedly. Air blast circuit breakers is used for interconnected lines and
  • 31. important lines where rapid operation is desired. Figure 7.4 Air blast circuit breaker High pressure air at a pressure between 20 to 30 kg/ cm2 stored in the air reservoir. Air is taken from the compressed air system. Three hollow insulator columns are mounted on the reservoir with valves at their basis. The double arc extinguished chambers are mounted on the top of the hollow insulator chambers. The current carrying parts connect the three arc extinction chambers to each other in series and the pole to the neighboring equipment. Since there exists a very high voltage between the conductor and the air reservoir, the entire arc extinction chambers assembly is mounted on insulators. 7.4 SF6 CIRCUIT BREAKER: Figure 7.5 SF6 Circuit breaker
  • 32. In such circuit breaker, sulphar hexafluoride (SF6) gas is used as the arc quenching medium. The SF6 is an electronegative gas and has a strong tendency to absorb free electrons. The SF6 circuit breaker have been found to a very effective for high power and high voltage service. SF6 circuit breakers have been developed for voltage 115 KV to 230 KV, power rating 10 MVA. It consists of fixed and moving contacts. It has chamber, contains SF6 gas. When the contacts are opened, the mechanism permits a high pressure SF6 gas from reservoir to flow towards the arc interruption chamber. The moving contact permits the SF6 gas to let through these holes. 7.5 Vacuum Circuit Breaker Figure 7.6 Vacuum circuit breaker Vacuum circuit breakers are circuit breakers which are used to protect medium and high voltage circuits from dangerous electrical situations. Like other types of circuit breakers, vacuum circuit breakers literally break the circuit so that energy cannot continue flowing through it, thereby preventing fires, power surges, and other problems which may emerge. These devices have been utilized since the 1920s, and several companies have introduced refinements to make them even safer and more effective.
  • 33. 7.2.1 Rating of 132 KV SF6 circuit breaker: 7.2.1.1 Breaking current: 50A 7.2.1.2 Making capacity: 80KA 7.2.1.3 Total break time < 60msec 7.2.1.4 Rated short circuit breaking current: 7.2.1.4.1 Symmetrical: 31.5 KA 7.2.1.4.2 Asymmetrical: 36.86 KA 7.2.1.5 Rated duration of short circuit current: 3sec 7.2.1.6 Rated nominal current: 1250 A 7.2.1.7 Rated voltage: 145 KV 7.2.1.8 Rated SF6 gas pressure: 6 KG
  • 34. 8. METERING AND INDICATION EQUIPMENT 8.1 RELAY: Figure 8.1 Relay In a power system it is inevitable that immediately or later some failure does occur somewhere in the system. When a failure occurs on any part of the system, it must be quickly detected and disconnected from the system. Rapid disconnection of faulted apparatus limits the amount of damage to it and prevents the effects of fault from spreading into the system. For high voltage circuits relays are employed to serve the desired function of automatic protective gear. The relays detect the fault and supply the information to the circuit breaker. The electrical quantities which may change under fault condition are voltage, frequency, current, phase angle. When a short circuit occurs at any point on the transmission line the current flowing in the line increases to the enormous value.This result in a heavy current flow through the relay coil, causing the relay to operate by closing its contacts. This in turn closes the trip circuit of the breaker making the circuit breaker open and isolating the faulty section from the rest of the system. In this way, the relay ensures the safety of the circuit equipment from the damage and normal working of the healthy portion of the system. Basically relay work on the following two main operating principles: 8.1.1 Electromagnetic attraction relay 8.1.2 Electromagnetic induction relay
  • 35. 8.2 Relays used in control panel of the substation; 8.1.3 DIFFERENTIAL RELAY: Figure 8.2 Differential Relay A differential relay is one that operates when vector difference of the two or more electrical quantities exceeds a predetermined value. If this differential quantity is equal or greater than the pickup value, the relay will operate and open the circuit breaker to isolate the faulty section. 8.1.4 OVER CURRENT RELAY: Figure 8.3 Overcurrent Relay This type of relay works when current in the circuit exceeds the predetermined value. The actuating source is the current in the circuit supplied to the relay from a current transformer. These relay are used on A.C. circuit only and can operate for fault flow in the either direction. This relay operates when phase to phase fault occurs.
  • 36. 8.1.5 DIRECTIONAL RELAY: Figure8.4 DirectionalRelay This relay operates during earth faults. If one phase touch the earth due to any fault. A directional power relay is so designed that it obtains its operating torque by the interaction of magnetic field derived from both voltage and current source of the circuit it protects. The direction of torque depends upon the current relative to voltage. 8.1.6 TRIPPING RELAY: Figure 8.5 Tripping Relay This type of relay is in the conjunction with main relay. When main relay sense any fault in the system, it immediately operates the trip relay to disconnect the faulty section from the section
  • 37. 8.1.7 AUXILIARY RELAY: Figure 8.6 Auxiliary Relay An auxiliary relay is used to indicate the fault by glowing bulb alert the employee.
  • 38. 9. MISCELLANOUS EQUIPMENT 9.1 CAPACITOR BANK: Figure 9.1 Capacitor bank The load on the power system is varying being high during morning and evening which increases the magnetization current. This result in the decreased power factor. The low power factor is mainly due to the fact most of the power loads are inductive and therefore take lagging currents. The low power factor is highly undesirable as it causes increases in current, resulting in additional losses. So in order to ensure most favorable conditions for a supply system from engineering and economical stand point it is important to have power factor as close to unity as possible. In order to improve the power factor come device taking leading power should be connected in parallel with the load. One of the such device can be capacitor bank. The capacitor draws a leading current and partly or completely neutralize the lagging reactive component of load current. Capacitor bank accomplishes following operations: 9.1.1 Supply reactive power 9.1.2 Increases terminal voltage 9.1.3 Improve power factor
  • 39. 9.2 FUSE: Figure 9.2 Substation Fuse A fuse is a short piece of wire or thin strip which melts when excessive current through it for sufficient time. It is inserted in series with the circuit under normal operating conditions; the fuse element is at a nature below its melting point. Therefore it carries the normal load current overheating. It is worthwhile to note that a fuse performs both detection and interruption functions. 9.3 BUS COUPLER: Figure 9.3 bus coupler The bus coupler consists of circuit breaker and isolator. Each generator and feeder may be connected to either main bus bar or spar bus bar with the help of bus coupler. Repairing, maintenance and testing of feeder circuit or other section can be done by putting them on spar bus bar, thus keeping the main bus bar undisturbed.
  • 40. 10. PROTECTION OF SUBSTATION: 10.1 Transformer protection: Transformers are totally enclosed static devices and generally oil immersed. Therefore chances of fault occurring on them are very easy rare, however the consequences of even a rare fault may be very serious unless the transformer is quickly disconnected from the system. This provides adequate automatic protection for transformers against possible faults. 10.2 Conservator and Breather: When the oil expands or contacts by the change in the temperature, the oil level goes either up or down in main tank. A conservator is used to maintain the oil level up to predetermined value in the transformer main tank by placing it above the level of the top of the tank. Breather is connected to conservator tank for the purpose of extracting moisture as it spoils the insulating properties of the oil. During the contraction and expansion of oil air is drawn in or out through breather silica gel crystals impregnated with cobalt chloride. Silica gel is checked regularly and dried and replaced when necessary. 10.3 Marshalling box: It has two meter which indicate the temperature of the oil and winding of main tank. If temperature of oil or winding exceeds than specified value, relay operates to sound an alarm. If there is further increase in temperature then relay completes the trip circuit to open the circuit breaker controlling the transformer. 10.4 Transformer cooling: When the transformer is in operation heat is generated due to iron losses the removal of heat is called cooling.
  • 41. There are several types of cooling methods, they are as follows: 10.4.1 Air natural cooling; In a dry type of self cooled transformers, the natural circulation of surrounding air is used for its cooling. This type of cooling is satisfactory for low voltage small transformers. 10.4.2 Air blast cooling: It is similar to that of dry type self cooled transformers with to addition that continuous blast of filtered cool air is forced through the core and winding for better cooling. A fan produces the blast. 10.4.3 Oil natural cooling: Medium and large rating have their winding and core immersed in oil, which act both as a cooling medium and an insulating medium. The heat produce in the cores and winding is passed to the oil becomes lighter and rises to the top and place is taken by cool oil from the bottom of the cooling tank. 10.4.4 Oil blast cooling: In this type of cooling, forced air is directed over cooling elements of transformers immersed in oil. 10.4.5 Forced oil and forced air flow (OFB) cooling: Oil is circulated from the top of the transformers tank to a cooling tank to a cooling plant. Oil is then returned to the bottom of the tank. 10.4.6 Forced oil and water (OWF) cooling: In this type of cooling oil flow with water cooling of the oil in external water heat exchanger takes place. The water is circulated in cooling tubes in the heat exchanger.
  • 42. 11.Mine Load Centers/Power Centers Mine Load Centers are used to transform high voltage input to low voltage outputs. Intermountain Electronics provides durable and reliable Power Centers of the highest quality, custom designed to meet the customer’s specific requirements.  Input usually in 5 kV to 25 kV classes  Output with typical voltage ratings of 480 to 1000 volts  Generally provided with appropriate overcurrent protection, monitoring, metering, and means for disconnection Figure 9.4 Mine Load Centers/Power Centers
  • 43. 12.Switchgear safe and efficient protection of your high voltage distribution system.  Low-profile switchgear for underground  Full height “walk-in” switchgear  Indoor or outdoor switchgear Figure 9.5 Switchgear
  • 44. 13. Motor Control Centers Motor Control Centers (MCCs) are required throughout the mining environment to energize and control drive motors for equipment such as conveyors, pumps, and fans. These applications can range up to thousands of horsepower with low, medium, or high voltage motors.  Simple Across-the-line (ATL) arrangements  Sophisticated PLC controlled Variable Frequency Drives (VFDs)  Soft-Starts or some combination Figure 9.6 Motor Control Centers
  • 45. 14. Substation Figure 9.7 Substation Substations are used by underground and surface mines to transform utility or generator supplied electrical power to the required voltage.  House supporting bus, switches, arrestors, insulators, breakers, and other electrical components  Permanent substation design with individual stand-alone components  Fixed indoor, outdoor, walk-in substation design  Portable substation skid-mounted design  Durable, heavy duty substation design for trucking or skidding to various locations Intermountain Electronics has full metal fabrication capabilities for design and assembly of steel structures for substations and switchgear (see our section on ELECTRICAL BUILDINGS). Our
  • 46. portable substations have been operating for years in harsh mining environments ranging from the extreme heat and blowing sand of the Mojave Desert, the frigid temperatures, snow and ice of the U.S. Continental Divide, the high humidity lowlands of Alabama and Louisiana, and the extremes of the high altitude Andes Mountains in Chile. 15.Capacitor Banks Capacitor Banks are used to improve the power factor of the electrical distribution system which can greatly reduce the costs of power from your utility company. Capacitor Banks can improve the efficiency and ease of starting motors.  Open pole-top assemblies  Enclosed banks for indoor, outdoor or underground applications  Fixed for continuous operation Figure 9.8 CapacitorBanks  Switched for utilization as required  A combination of fixed and switched capacitors Intermountain Electronics can assist in the analysis of your electrical system to determine your capacitor requirements. We can then provide these capacitors in a package to suit your specific need 16.Leaky Feeder Radio Systems Leaky Feeder Radio Systems utilize a partially shielded coaxial cable to distribute radio frequency (RF) signals throughout underground mine and tunnel environments. The leaky feeder network has proven to be a superior method for underground wireless voice, data, and video communications and can interface with other surface and underground communication systems.  Improved emergency/ production/breakdown response of key personnel  Remote monitoring by video and/or data of underground equipment  Remote control of equipment Intermountain Electronics has teamed with Tunnel Radio to provide the latest technology in Tunnel Wireless Communication Systems and can analyze your specific situation to determine the most effective solution for your communication needs.
  • 47. 17.Diesel Generator Set Diesel powered generator sets provide a portable power source for applications where utility supplied power is not available.  Mine start-up  Back-up for ventilation fans  Large generators for moving shovels and drills in surface mines  Compact, low-profile, skid-mounted generators in underground mines Figure 9.9 DieselGeneratorSet Intermountain Electronics is an industry leader in providing these custom-built generator sets that comply with all applicable standards and regulations for safe and efficient operation. Intermountain Electronics has teamed with CleanAIR Systems to provide Emissions Control Technology and Retrofit Technology and will advise you on meeting MSHA and EPA clean air standards 18. Vehicle and Personnel Tracking Systems Vehicle and Personnel Tracking is a Radio Frequency Identification System consisting of RFID tags, RFID readers, RF network, computer, and software that provides a graphical representation of items such as personnel, vehicles, products, and equipment. Vehicle and Personnel Tracking provides timely and accurate location data that can be used to meet safety, production, and cost reduction targets. Benefits include…  Location positioning of personnel and vehicles  Monitor and review of production vehicle cycles  Adjusting ventilation based on number of cycles and type of vehicles Figure 9.10  Resource tracking history. Intermountain Electronics has teamed with AMR Inc. and can analyze your situation and tailor a Vehicle and Personnel Tracking System to meet your specific needs.
  • 48. 19. CONCLUSION Now from this report we can conclude that electricity plays an important role in our life. We are made aware of how the transmission of electricity is done. We too came to know about the various parts of the Substation system. The South Eastern Coalfield Limited has got radio communication in microwave range in order to transmit and receive data with various Substations in Uttar Pradesh to get reliable transmission and distribution of electricity.
  • 49. References 1. www.yahooanswers.com 2. www.britannica.com 3. www.webopedia.com 4. www.encyclopedia.com 5. www.worldbook.com 6. www.encyclopediadramatica.com/