SlideShare une entreprise Scribd logo
1  sur  26
Télécharger pour lire hors ligne
Designed to order. Built to last©
1
Substation Report Training Report
Mavuso United M.
Swaziland Electricity Company
united.mavuso@sec.co.sz Substation Engineer Signature:
02nd
November – 31st
January 2016 Trainee Signature:
Energy For The Future
Designed to order. Built to last©
2
Abstract
The purpose of this report is to reveal the scope of work covered by Substation department as part of
my Engineering Training programme at SEC. The goal of this report is to show a clear understanding
of the work done by the substation department in SEC. It also shows my involvement to the work done
in every day routine to meet its goals. A preamble of the Substation department in general is first
presented followed by a summary of the SEC Substation department. The full details of industrial
exposure and acquired knowledge is then shared under the tasks involved in section. Finally
recommendations are made which may make SEC substation department a better company in the
future.
Designed to order. Built to last©
3
Table of Contents
Abstract...................................................................................................................................................2
Abbreviations .........................................................................................................................................4
Table of Figures.......................................................................................................................................5
1. Preamble.........................................................................................................................................6
2. Why We Need Electrical Power Substations.................................................................................7
2.1 Practical Considerations..............................................................................................................7
2.2 Technical Considerations ............................................................................................................7
3. Equipment Used.............................................................................................................................8
3.1 Voltage Transformer (VT)............................................................................................................8
3.2 Current Transformer (CT)............................................................................................................8
3.3 Power Transformer.....................................................................................................................9
3.3.1 Main Tank .............................................................................................................................10
3.3.2 The Conservator....................................................................................................................10
3.3.3 Tap Changer ..........................................................................................................................11
3.3.4 Guard Unit.............................................................................................................................12
3.4 Circuit Breakers.........................................................................................................................12
3.4.1 Oil Circuit Breaker.................................................................................................................13
3.4.2 SF6 Gas Circuit Breakers ........................................................................................................13
3.4.3 Vacuum Circuit Breaker ........................................................................................................14
3.5 Protection Panel........................................................................................................................15
4. Substations Activities...................................................................................................................16
4.1 Oil Sampling and Testing...........................................................................................................16
4.2 Infra-red Scanning.....................................................................................................................18
4.3 Transformer Movement............................................................................................................19
4.4 Tap Changer Maintenance..............................................................................................................20
4.5 Power Transformer Maintenance.............................................................................................21
5. Tasks Involved In ..........................................................................................................................22
6. Recommendations .......................................................................................................................24
7. Conclusion ....................................................................................................................................26
Designed to order. Built to last©
4
Abbreviations
SEC Swaziland Electricity Company
NCC National Control Centre
ISO International Standards Organisation
SCADA Supervisory Control and Data Acquisition
AC Alternating Current
DC Direct Current
HV High Voltage
VT Voltage Transformer
CT Current Transformer
CB Circuit Breaker
REF Restricted Earth Fault
NCT Neutral Current Transformer
IDMT Inverse Definite Minimum Time
O/C Overcurrent
IED Intelligence Electronic Device
E/F Earth Fault
OLTC On Load Tap Changer
LV Low Voltage
MV Medium Voltage
HV High Voltage
SFRA Sweep Frequency Response Analysis
FAT Factory Acceptance Test
SAT Site Acceptance Test
HIRA Hazard Identification and Risk Assessment
Designed to order. Built to last©
5
Table of Figures
Figure 1: Substation Diagram Mimic.......................................................................................................6
Figure 2: Voltage Transformer (VT) ........................................................................................................8
Figure 3: Current Transformer (CT).........................................................................................................9
Figure 4: Atmoseal Conservator ...........................................................................................................11
Figure 5: Infrared Camera.....................................................................................................................18
Figure 6: Mpaka Power Transformer Movement .................................................................................20
Figure 7: Mpaka Transformer Transportation ......................................................................................22
Figure 8: Stonehenge Cable Laying.......................................................................................................23
Figure 9: Leaking Lobamba Transformer ..............................................................................................24
Figure 10: Positioning of Cable Rollers .................................................................................................25
Designed to order. Built to last©
6
1. Preamble
Substation is a part of an electrical generation, transmission, and distribution system. The main
objective of substation is to transform voltage from high to low, or the reverse. Between the
generating station and consumer, electrical power may flow through several substations at different
voltage levels.
Substations are left unattended, relying on SCADA for remote supervision and control. Substations
generally have switching (switchgear), protection, control equipment, and transformers. Other
equipment found in a substation could be capacitor banks, and voltage regulators. Substations do not
usually have generators, although a power plant may have a substation nearby.
The Swaziland Electricity Company Substation department operates as depicted on figure 1.
Substations is a department which is mainly supported by the linked departments. All this
departments have their equipment which they operate in substations. The critical equipment in a
substation is the transformer, everything that happens in the substation is benchmarked by the
transformer limit levels.
Figure 1: Substation Diagram Mimic
Designed to order. Built to last©
7
2. Why We Need Electrical Power Substations
We build substations for the following reasons:
2.1 Practical Considerations
 To satisfy load growth; when people move to a new location that has no power
supply infrastructure, it might make a case for building a substation close to that
location. Supplying this new load from distant substations is inefficient because most
power will be lost in the transmission lines as heat (Ploss = I2
R) and on distribution
lines.
 To accommodate new generation power plants; either you want to build a solar or
wind farm, you will need a collector substation to tie all generators and connect
them to the power grid.
 To maintain reliability requirements; new transmission lines are constructed by
utilities to address any deficiency in the power grid. When building new transmission
lines, effort is made to connect to an existing substation. When no existing power
substation, a new substation is considered.
2.2 Technical Considerations
 To transform voltage levels; since higher voltages mean lower currents. Lower
currents yield to lower I2
R (copper) losses. Thus more energy can be delivered to do
useful work. Voltages at the distribution end need to be stepped down for customer
utilisation. Substations provide the necessary real – estate to install a transformer
for power transmission and distribution.
 To break power flow; quite often a fault requires complete isolation of the line until
the fault is removed. To safely interrupt hundreds of amperes you will need circuit
breakers that can handle high current magnitudes. All substations contain circuit
breakers which they trip and isolate transmission lines connected to it.
 Provide support to the power flow; unlike DC power flow, AC power flow needs to
overcome not only the resistive impedance but also the impedance offered by the
inductive nature of various equipment (like motor loads, transmission lines,
reactors) connected to the system. For this reason, substations have capacitor banks
connected to all three phases of the lines to ease the power flow. This also improves
the power factor of the electrical system.
Designed to order. Built to last©
8
3. Equipment Used
3.1 Voltage Transformer (VT)
Voltage in power systems is too high to connect measuring instruments or relays directly, coupling
is made through VT. This is a device which is used for stepping down the system voltage (AC) to a
safe value which can be fed to relays. The VT has lower turns winding at its secondary when
compared to its primary windings.
A VT is insulated to withstand over voltages, including impulse voltages, of a level equal to the
withstand value of the high voltage system. Voltage transformers are designed to maintain the
specified accuracy in voltage output at their secondary. Primary of VT is connected across the
phase and ground. If long secondary leads are required, a distribution box is fitted close to the VT
to supply relay and metering instruments over separate leads. Usually the secondary voltage of
voltage transformer is generally 110 V (AC).
Figure 2: Voltage Transformer (VT)
3.2 Current Transformer (CT)
Same as the voltage transformer, current in power systems is high to connect directly to
measuring instruments, CT produce a reduced current accurately proportional to the current in
the circuit as coupling. The CT has the same principle as VT but here is the difference. For a VT or
general transformer, primary current varies with load (secondary current). With CT, primary
current is the system (primary) current transforms to the CT secondary, hence load (burden
current) depends upon primary current of the CT.
Designed to order. Built to last©
9
Again, protection CT has the same principle with metering CT but here is the difference. For
metering CT, accuracy ratio, between primary and secondary currents are essential within normal
working range. The normal accuracy up to 125% of rated current as allowable system current must
be below 125% of rated current. Due to faults the secondary of the CT could be saturated but
saturation is prevented to reach the metering instrument connected to secondary of the CT as
secondary current does not go above desired limit even when primary current rises to a very high
value.
But in the case of protection, the CT is desired not to be saturated during high fault current passing
through primary. So core of protection CT is designed that it would be not saturated for long range
of currents even on secondary of CT.
Figure 3: Current Transformer (CT)
3.3 Power Transformer
This is the main equipment in a substation, rather a critical and expensive component of the power
system. Its working principle is exactly the same as voltage transformer (VT), except of the
transformation voltage ratio level. SEC has 66/11kV, 132/66/11kV, and 11/66kV substation
transformers which are mainly protected against fault currents, over voltages, over loads. The
Designed to order. Built to last©
10
type of protection used should minimize the time of disconnection for faults within the
transformer. Any extended operation of the transformer under abnormal condition comprises the
life of the transformer, which means adequate protection should be provided for quicker isolation
of the transformer.
A transformer is made up of many components, that is, main tank, tap changer, guard unit,
conservator, bushings, breathers, cooling system (radiators(ONAN, ONAF)), and the relays.
3.3.1 Main Tank
This is the main component of the transformer where voltage transformation takes place. On its
own, it has different parts which form part of the transformation process. It consists of insulating
oil, laminated core, and paper insulated windings.
 Laminated core; this is done to reduce eddy currents as low as possible since they
interfere with the efficient transfer of energy. The eddy currents cause energy to be lost
from the transformer as they heat up the core and energy getting lost as heat.
 Paper insulated windings; between windings turns is a small voltage difference with the
neighbouring winding turns. The voltage difference between the windings and
neighbouring turns could be excessive and equals the voltage drop across a large number
of turns in one winding layer. Therefore an extra insulation layer using paper strip is used
between windings layers. This is not just an ordinary paper but cellulose paper with
outstanding electrical properties making it appropriate for insulation.
 Insulating oil (SEC uses power oil); it serves mainly as liquid insulation in the transformer,
it also dissipates heat of the transformer, that is, it acts as a coolant. It further preserves
the core and the winding as they are fully immersed inside oil and again the oil prevents
direct contact of atmospheric oxygen (air) with cellulose made paper insulation of
windings, which is susceptible to oxidation.
3.3.2 The Conservator
This is a cylindrical tank mounted on supporting structure on the roof of the transformer main
tank. Its main function is to provide adequate for expansion of oil inside the transformer. When a
transformer is loaded (due to load increase) and when ambient temperature rises, the volume of
oil inside the transformer increases. The conservator provides adequate space to this expanded
transformer oil. When the load decreases and when ambient temperature decrease, the
Designed to order. Built to last©
11
transformer oil contracts due decrease in temperature. This then causes outside air to enter in
the conservator tank of transformer through silica gel breather. The conservator also acts as a
reservoir for transformer insulating oil.
An example of a conservator is shown in figure 4. This is an atmoseal type of a conservator. This
kind of conservator, an air cell is fitted inside the conservator reservoir. The silica gel breather is
connected at the top of this air cell. The oil level in the main tank rises and falls with respect to
the air cell deflation and inflation. When air cell deflates the air inside cell comes out via breather
and if cell inflates, the outside air comes in through breather. This arrangement prevents direct
contact of oil with air, reducing ageing of insulating oil.
Figure 4: Atmoseal Conservator
3.3.3 Tap Changer
In larger electrical power transformers, for proper voltage regulation of transformer, a tap
changer is required. Depending on which type is used, there are two kinds of tap changers which
are on load tap changer (OLTC) and no load tap changer (NLTC). The tapping arrangement is placed
in a separate tank attached to the transformer tank. On load tap changers are recommended since
as the name suggests, permit tap changing and hence voltage regulation with the transformer on-
load. Tap changing is done on HV winding for two reasons:
 Because the currents are lower, the tap changer contacts or leads could be smaller
Designed to order. Built to last©
12
 The HV winding is wound outside the LV winding, it is easier to get the tapping
connections out to the tap changer.
3.3.4 Guard Unit
This is a unit which monitors winding and oil temperatures inside the transformer main tank. This
is generally a precision unit. It is a temperature indicator of power transformer specially designed
for protection of transformer in addition to its temperature indication and cooling control
features. It performs mainly the following:
i. It indicates instantaneous temperature of oil and windings of transformer.
ii. Also records the maximum temperature rise of oil and windings.
iii. The unit operates high temperature alarm at a predetermined value of allowable
temperature limit.
iv. The indicators can further trip the circuit breakers associated with power
transformer when the temperature of oil or winding reaches a predetermined
limit.
v. The unit also controls the cooling system of the power transformer. Switches on
the cooling equipment (cooling fans) when the winding or oil temperature
reaches a pre-set temperature and switch off when temperature decreases.
According to power transformer maintenance manual provided by ABB, the maximum
temperature permitted for oil is of 90°C and the maximum temperature of the hottest point is
110°C. The guard unit will monitor the temperatures as reflected above.
3.4 Circuit Breakers
This is a switching device which can be operated manually or automatically for controlling and
protection of electrical power system. Its primary function is to provide opening and closing
current carrying contacts. It remains at its closed position for maximum period of its life span.
With SEC, we have some which are normally opened for the network stability. So these remain
opened for maximum period of their lives unless there is a fault which will require system
controllers to optimize the network through opening and closing the normally opened points.
The operation of a circuit breaker is then required to be reliable without any delay or sluggishness.
Many parameters come into play in the operation of a circuit breaker, which is, closing and
opening distance of contacts, velocity of moving contacts, and stroke between contacts.
Designed to order. Built to last©
13
At the moment SEC has different kinds of circuit breakers enrolled in the network, that is, oil circuit
breaker, SF6 circuit breaker, and vacuum circuit breakers which are remotely operated (mostly)
for the HV transmission network.
There are different kinds of circuit breakers SEC has in the network, these are:
a. Oil circuit breakers (OCB)
b. SF6 gas circuit breakers (Sulphur Hexafluoride)
c. Vacuum Circuit Breakers (VCB)
3.4.1 Oil Circuit Breaker
The current carrying contacts are immerged inside the insulating oil. Whenever there is a
separation of current carrying contacts in the oil, the arc in circuit breaker is initialised at the
moment of separation of contacts, and due to this arc the oil is decomposed in mostly hydrogen
gas and create hydrogen bubble around the arc. The highly compressed bubble around the arc
prevents re-striking of the arc after current reaches the zero crossing of the cycle.
Advantages of Oil Circuit Breakers
 It is cheaper
Disadvantages of Oil Circuit Breaker
 Oil is flammable and may cause fire hazards. When a defective circuit breaker fails under
pressure, it may cause an explosion.
 The hydrogen generated during arcing, when combined with air, may form an explosive
mixture.
 During arcing, oil decomposes and becomes polluted by carbon particles, which reduces
its dielectric strength. Hence it requires periodic maintenance and replacement.
 Oldest type of circuit breaker.
3.4.2 SF6 Gas Circuit Breakers
This is a circuit breaker in which the current carrying contacts operate in sulphur hexafluoride (SF6)
gas. It has high affinity of absorbing free electron. When a free electron collides with the gas
molecule, it is absorbed by that gas molecule. We know that mobility of charged particle is majorly
responsible for conducting current through a gas. Over all mobility of the charged particle in the
SF6 gas is much less as compared other common gases.
Designed to order. Built to last©
14
For heavier and less mobile charged particles in SF6 gas, it acquires very high dielectric strength.
SF6 gas has a good dielectric strength and a good property of fast recombination after the source
energizing the spark is removed.
Advantages of SF6 Gas Circuit Breakers
 High dielectric strength
 It insulates 2.5 times better than air
 Good heat transfer property
 Fast recombination after the source energizing the spark is removed
 SF6 gas is identified as one of the greenhouse gases which can reradiate back to earth
some of the earth’s natural infrared radiation. It is environmentally friendly, that is, does
not deplete the ozone layer.
 It is not a health hazard.
So due to the SF6 gas having high dielectric strength and high cooling effect, the gas is
approximately 100 times more effective arc quenching media than air. Due to this unique
properties of this gas is used for voltages ranging from 33kV to 800kV and even more.
3.4.3 Vacuum Circuit Breaker
This is a breaker where the arc quenching takes place in a vacuum. The operation of opening and
closing of current carrying contacts and associated arc interruption take place in a vacuum
chamber called vacuum interrupter. It mainly used for medium voltage switchgear.
Advantages of VCB
 No chance of fire hazard compared to OCB
 High insulation strength
 No gas/oil filling required
 No emission of gases, hence pollution free.
 Rapid recovery of very high dielectric strength on current interruption.
Disadvantages of VCB
 Loss of vacuum due to transit damage or failure makes the entire interruption useless and
cannot be repaired on site.
Designed to order. Built to last©
15
3.5 Protection Panel
This is a box where all information provided by either VT’s, CT’s, or power transformers is
interpreted as to be safe enough for the equipment operation. The panel could either be for the
bus-zone or power transformer or transmission lines (feeders), which simply means that panel has
relays which interprets information with respect to the mentioned equipment.
Different protection relays are used for different purposes in SEC with respect to the kind of
protection scheme enrolled. A protection relay is an automatic device which senses an abnormal
condition of electrical circuit and closes its contact so to isolate the abnormal condition.
The basic characteristics which ensures high performance of protection equipment are as follows:
1. Reliability – this is an assurance that protection will perform correctly when required.
2. Selectivity – this is an assurance that protection will trip only those circuit breakers whose
operation is required to isolate fault condition.
3. Speed – this is to ensure isolation of faulty conditions on the power system as rapidly as
possible before fault leads to collapse of entire system.
4. Sensitivity – protection equipment should be high sensitive, that is, should have minimal
operating time during abnormal conditions.
In wiring a protection panel, different codes (ferruling) are used depending whether it is an AC or
DC signal being wired. Furthermore, the ferruling depends on the kind of connection you are
doing, could be SCADA controls, metering, bus bar protection, inter alia. Below is a summarised
table for codes of practice for power system protection.
CODE Signal type Used for
A AC CT secondary for main protection
B Bus bar protection
C Protection circuits (O/C and Earth fault)
D Metering circuit
E Voltage transformer secondary
H Auxiliary transformer secondary
P Bus bar controls
J DC DC incoming from charger
K DC voltage controls – Closing, tripping
L DC voltage indications – Alarms, indications, annunciations
M DC voltage for motor spring circuit
Designed to order. Built to last©
16
N DC voltage for OLTC circuit
X Scada controls and indications
1 Positive signal
2 Negative signal
Table 1: Codes of Practice for Power System Protection
There are further rules that apply with regards to panel wiring under protection. Which are:
 Entire wiring of circuitry should be of permanent wiring
 Leads should be marked and identified near terminals (ferruling).
 Every lead should end at a terminal point and no junction by twisting is allowed.
 DC and AC supplies should not be taken through different cores of the same cable. Totally
different cables should be used for DC and AC supplies.
 The cable entries in protection panels should be through appropriate size of cable glands. No
other means.
 Wherever CT cores are not used “shorting loops” should be provided in CT secondary
terminals and not at panels.
The mentioned are some of the many rules that apply under power system protection.
Oil sampling, infra-red scanning, substation inspection, transformer/substations maintenance,
projects, faults,
4. Substations Activities
Substation department is equipped in doing some activities which may inform better the status of her
assets on the ground, that is, in terms of asset maintenance, substation yard maintenance, inter alia.
4.1 Oil Sampling and Testing
The department engages itself to do oil sampling and testing in all substation transformers (54
functional substations) once every year. This is done since ABB (1ZCL000002EG-EN – rev. 1) manual has
mentioned that we should do it at least once a year. This activity is outsourced to South African companies (the likes
of TSS, wear-check, inter alia).
After the sampling, samples are tested for the following:
1) Oil Condition
Designed to order. Built to last©
17
a. Karl Fischer (Moisture content determination, should be less than 20 ppm
according to the manual (ABB))
b. Acidity (should be less than 0.3 mg KOH/gram of oil)
c. Dielectric Strength (kV, minimum of 30kV)
d. PCB (Polychlorinated Biphenyls)
e. Oil temperature (maximum of 90°C)
f. Dissolved Gas Analysis (each gas is a prediction of a certain kind of fault as
depicted in Table 2)
Table 2: Power Transformer Gases Interpretation
Gas Normal
Condition
Abnormal
Condition
Temperature
(°C)
Interpretation
H2
(Hydrogen)
< 150 ppm > 1000 ppm > 900 Arcing Corona, Partial
discharge, present in all
types of faults but mainly
corona and arcing
CH4
(Methane)
< 25 ppm > 80 ppm 150 > Temp >
300
Sparking, Core bolts
faults, Under designed
core.
C2H6 (Ethane) < 10 ppm > 35 ppm 250 > Temp >
500
Local Overheating, tap
selector contacts, core
bolt faults
C2H4
(Ethylene)
< 20 ppm > 100 ppm 500 > Temp >
900
Severe Overheating,
bushing connections
C2H2
(Acetylene)
< 15 ppm > 70 ppm > 900 Arcing
CO (Carbon
Monoxide)
< 500 ppm > 1000 ppm > 900 Severe Overloading
CO2 (Carbon
Dioxide)
< 10 000 ppm > 15 000 ppm > 900 Severe Overloading
Table 2 shows is called the California State University Guidelines type of analysis.
2) Transformer Condition
Designed to order. Built to last©
18
a. Paint condition
b. Silica Gel Condition
c. Oil Level
3) Additional Tests
a. Sludge condition
b. Flash point
c. Furanic value
d. Degree of polarization (for a healthy transformer should be 700 – 1200. It
basically reflects the insulation paper condition)
After the tests, the contractor will mention its recommendations as action plans to be considered by
substation department.
4.2 Infra-red Scanning
Increased resistance and heat are the primary reasons most electrical equipment fail. Before any
failure, the equipment will heat up. This activity (Infrared scanning) is used to inspect electrical
equipment because excess heat is usually the first sign of trouble. Loose connections imbalanced or
overloaded circuits, defective breakers, damaged switches, faulty fuses, and material defects all lead
to equipment failure. Using infrared scanning as an early warning tool for potential electrical
equipment/system failure is an important part of maintaining mission critical uptime.
SEC substation department has committed herself in performing the activity for every substation
within the SEC.
Figure 5: Infrared Camera
Figure 5 shows an infrared camera which is used for the activity. The great thing about this camera, it
produces its own report on completion of job.
Designed to order. Built to last©
19
The early detection will allow maintenance personnel to take corrective action before equipment
failure, minimizing damage to the components and reducing repair costs.
4.3 Transformer Movement
This is mainly a relocation of power transformers with their associated equipment in a safe and
controlled movement; ensuring the integrity of the transformer. The activity include uplifting and
movement of old/new power transformers to new location either for installation or repairs or
refurbishments. In transformer movement there are key considerations to be taken with their
activities. These are:
 Planning activity; transport routes, lifting plans, tools to be used (hydraulic jacks, turfors,
winch truck, rail slippers, rails, pulleys, slings)
 Mechanical dismantle of auxiliary equipment, that is, bushings, conservator, buchholz relay,
inter alia.
 Uplifting, loading, transport, offloading, and final positioning at new location.
 Depending on where you transporting the unit, for new installation you should consider
testing (SFRA) after offloading.
Figure 6 shows a 3 MVA Mpaka transformer being transported by a winch truck. The transformer had
to go for refurbishment since it had a high leakage between main tank and tap changer which had an
impact to the environment.
Designed to order. Built to last©
20
Figure 6: Mpaka Power Transformer Movement
4.4 Tap Changer Maintenance
The tap changer operation has been discussed in 3.3.3 but SEC has a commitment to maintain power
transformer tap changers. This maintenance is done so to reduce arcing times and extend contact life.
The switching contacts are made of copper/tungsten, or in the case of tap changers for lower currents,
the contacts are made of copper. After a certain number of operations the tap changer is expected to
be maintained to see if it still has good oil, good contacts. It is worth noting that a tap changer gives a
service life that equals to power transformer service life. The major parts which need attention during
maintenance are:
 The contacts which may need replacement
 The motor drive mechanism
Prior to the maintenance is an annual inspection which has to be performed to read counting devices.
The readings are used to determine when overhaul is due, which is done every seven years. During
overhaul, the following is done:
 Checking dielectric strength of the oil
 Filtering the oil
Designed to order. Built to last©
21
 Checking motor drive mechanism
 Checking the pressure relay
 And checking the contact wear.
SEC substation department usually outsource this activity to the company which designed the tap
changers. The maintenance is mainly done just because during tapping (switching), arcs are generated
on the main switching and transition contacts of the diverter switch. The arcs cause carbonisation of
the switching oil and lead to wear.
4.5Power Transformer Maintenance
A power transformer is the most costly and essential equipment found in a substation. For getting
high performance and long functional life of the transformer, it is desired to perform various
maintenance actions including measurement and testing of different parameters of the transformer.
This maintenance is done mainly for the objectives stated in 2.1 and 2.2. Loss of a transformer in a
substation will result in many customers being affected.
Two types of transformer maintenances are available: for getting smooth performance from a
transformer we have to perform maintenance in regular basis, and the other type is performed as in
when it is required. If regular maintenance (condition maintenance) is performed properly, one may
not have any provision of performing emergency maintenance. This could avoid emergency and
breakdown maintenance.
Before any maintenance within SEC substations, there is a substation inspection which is done which
informs the power transformer maintenance for that substation. Mainly for power transformer
maintenance the following is considered:
 The oil level in oil cap under silica gel breather, if high than expected level oil should be topped
up.
 Colour of silica gel in breather depending on what kind of silica gel is used.
 Oil leakage from any point of the transformer.
 Reading of oil level gauge of main tank and tap changer. If oil is less, should be topped up.
 Transformer bushings be cleaned and inspected for any cracks
 Mechanical inspection of buchholz relay
 Insulation resistance of transformer must be checked
 Transformer oil dielectric strength be done
Designed to order. Built to last©
22
Amongst others, the above should be done for every transformer maintenance performed within SEC.
Other activities in SEC substation are H.V yard maintenance, Circuit breaker maintenance, H.V cable
termination, H.V isolator installation and commissioning, and FAT’s and SAT’s.
5. Tasks Involved In
In my attachment with SEC substation department, listed below are the tasks I was involved in:
 Transformer movement from Mpaka substation. The 3 MVA developed a leak while in service
and was taken out of service and the oil was drained.
o 3MVA, 66/11 kV, S/N: Y16113, Yz11, Yorkshire transformer, year of manufacture:
1966, 2678 gallons of oil.
o Tools used: winch (low belt), slings, pulleys, 2 hydraulic jacks, two railroads, 2 turfors
(5 & 3.5 tonnes), rail slippers. It was the first time to experience such, moving such a
massive, with all the weight and height, it was pretty impressive. Unfortunately there
was no procedure to move the transformer. Transformer was loaded safely but the
challenge was that tap changer was too big such that it overlapped on to the road.
Yes we used an abnormal truck to move the transformer but it was not good enough.
We were a hazard to the other traffic going opposite us.
Figure 7: Mpaka Transformer Transportation
3MVA Transformer
Trainee & Technician
Railroad
Low belt truck
Designed to order. Built to last©
23
 Cable laying at Stonehenge (4 x 120 mm2
XLPE cables). These cables were from low voltage
side (11kV bushings) of 10 MVA transformer 3 and 4 to incomer breakers. The job took 2 full
days to complete it.
Figure 8: Stonehenge Cable Laying
 High voltage cable termination at Mkinkomo substation. After conducting HIRA and obtaining
permit to work from the NCC we laid and terminated a 120 mm2
x 3 core cable which
connected a PFC panel. Cable termination has its own procedure which when not followed
properly it might lead to sever faults which could be electrical treeing, water treeing, inter
alia.
 Maloma substation maintenance; this involves transformer maintenance, circuit breaker
maintenance, and H.V yard maintenance.
 Refilling of SF6 gas into Sikhuphe substation breaker. The breaker due to decrease in gas level
inside, tends to lock out and require refill and resetting for it to operate again.
 At Nhlangano I substation, a project was ongoing, that is, the removal of outdoor circuit
breakers into indoor circuit breakers. I was involved in the assembling of the indoor 11 kV
panels inside the control room.
 At Lobamba substation: transformer 2 had a leak around the core bushing. We had to re-
gasket the bushing. This activity required us to drain about 10 drums of oil from the main tank.
We missed the fact that we were supposed to close the conservator valve which leads into
the main tank. This then delayed the whole process, which led the team spending most of the
day on site. Figure 9 shows where the leak had occurred.
Designed to order. Built to last©
24
Figure 9: Leaking Lobamba Transformer
6. Recommendations
The substations department in SEC is responsible for 54 substations and a number of switchyards
country wide, this then makes the management of the substations difficult. The management part of
the substations involves a lot of responsibility on substation engineer. For improvement, the
substation department requires to have maintenance engineer which will ensure maintenance is
executed effectively. The importance of maintenance is very effective such that for 100% condition
maintenance you will expect 0% breakdown of any equipment.
Faults amongst the department occur now and then repeatedly but with the workload on the team, it
is difficult to find time to find the root cause of every fault. As a transmission department in whole, I
believe with a fault analysis team (amongst the existing resources) in place we could avoid having the
same faults occurring repeatedly. This will further improve the substation (or even SEC at large) team
competency in understanding the departments’ equipment operation.
Infrared scanning being done on substations yard only, it is worth noting that even the panels require
scanning as there are lots of connection done. I believe that every time an electrical panel is accessed,
it should be infrared scanned. Anyone authorized to work in an electrical panel or high voltage cabling
needs to be trained on infrared scanning.
Core Bushing
Designed to order. Built to last©
25
Substation department needs to make sure that for every meter or indicator used in a substation is
calibrated or rather verified for its accuracy and operation. Mainly for oil temperature and winding
temperature indicators (OTI and WTI) at least once in two years.
The cable laying process is a tiring job without cable rollers. Substations need to have cable rollers as
shown in Figure 10. The rollers are necessary to avoid abrasion of the cable by keeping it clear of the
ground and to reduce friction during pulling.
Figure 10: Positioning of Cable Rollers
The ISO standards should be communicated in every monthly meetings and further explained its
existence and implementation.
In my time in the department, we have lost track of keeping engineering standards. These include the
following;
Designed to order. Built to last©
26
 Yard stone cover; a 100mm thick layer of clean, washed, hard granite crusher stone of
minimum sieve grid size of between 25mm and 36mm spread the entire substation yard and
extend 1000mm beyond the substation fence. The lack of this motivates vegetation growth
within the substation.
7. Conclusion
I believe for future purposes substation department could do much better if the recommendations
mentioned could be considered.
Analysing insulating oil taken from transformers is a unique way of identifying problems occurring
within a transformer. By identifying and quantifying the gases found in transformer oil, the condition
of the transformer can be monitored.
The interpretation of transformer oil gas analysis is still an art and not an exact science (the facts
around DP tests). The interpretation should be left to a specialist and his advice and recommendations
should be followed. Samples should be taken regularly and records kept.
This is a huge department under transmission but I believe that if we could follow the management
systems in place for every work executed we could achieve much better performance.

Contenu connexe

Tendances

A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...
IJMTST Journal
 

Tendances (20)

Minimization of Power Loss in Distribution System using SVC and STATCOM
Minimization of Power Loss in Distribution System using SVC and STATCOMMinimization of Power Loss in Distribution System using SVC and STATCOM
Minimization of Power Loss in Distribution System using SVC and STATCOM
 
IRJET- Review on Cascaded Quasi-Z-Source Network
IRJET-  	  Review on Cascaded Quasi-Z-Source NetworkIRJET-  	  Review on Cascaded Quasi-Z-Source Network
IRJET- Review on Cascaded Quasi-Z-Source Network
 
Design and Simulation of DC-DC Converters
Design and Simulation of DC-DC ConvertersDesign and Simulation of DC-DC Converters
Design and Simulation of DC-DC Converters
 
Voltage Stability Improvement Using VSC Based D-STATCOM with Fuzzy Controller
Voltage Stability Improvement Using VSC Based D-STATCOM with Fuzzy ControllerVoltage Stability Improvement Using VSC Based D-STATCOM with Fuzzy Controller
Voltage Stability Improvement Using VSC Based D-STATCOM with Fuzzy Controller
 
Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...
Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...
Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...
 
Fuzzy Logic Controller Based on Voltage Source Converter-HVDC with MMC Topology
Fuzzy Logic Controller Based on Voltage Source Converter-HVDC with MMC TopologyFuzzy Logic Controller Based on Voltage Source Converter-HVDC with MMC Topology
Fuzzy Logic Controller Based on Voltage Source Converter-HVDC with MMC Topology
 
INTELLIGENT AUTOMATIC POWER FACTOR CORRECTION
INTELLIGENT AUTOMATIC POWER FACTOR CORRECTIONINTELLIGENT AUTOMATIC POWER FACTOR CORRECTION
INTELLIGENT AUTOMATIC POWER FACTOR CORRECTION
 
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...
 
Fuzzy based control of Transformer less Coupled inductor based DC-DC converter
Fuzzy based control of Transformer less Coupled inductor based DC-DC converterFuzzy based control of Transformer less Coupled inductor based DC-DC converter
Fuzzy based control of Transformer less Coupled inductor based DC-DC converter
 
POWER COMPARISON OF CMOS AND ADIABATIC FULL ADDER CIRCUITS
POWER COMPARISON OF CMOS AND ADIABATIC FULL ADDER CIRCUITSPOWER COMPARISON OF CMOS AND ADIABATIC FULL ADDER CIRCUITS
POWER COMPARISON OF CMOS AND ADIABATIC FULL ADDER CIRCUITS
 
Simulation of H6 full bridge Inverter for grid connected PV system using SPWM...
Simulation of H6 full bridge Inverter for grid connected PV system using SPWM...Simulation of H6 full bridge Inverter for grid connected PV system using SPWM...
Simulation of H6 full bridge Inverter for grid connected PV system using SPWM...
 
“POWER FACTOR IMPROVEMENT BY SIMULATION AND IMPLEMENTATION OF FC-TCR”
“POWER FACTOR IMPROVEMENT BY SIMULATION AND IMPLEMENTATION OF FC-TCR”“POWER FACTOR IMPROVEMENT BY SIMULATION AND IMPLEMENTATION OF FC-TCR”
“POWER FACTOR IMPROVEMENT BY SIMULATION AND IMPLEMENTATION OF FC-TCR”
 
IRJET- Single Switched Capacitor High Gain Boost Quasi-Z Source Converter
IRJET- Single Switched Capacitor High Gain Boost Quasi-Z Source ConverterIRJET- Single Switched Capacitor High Gain Boost Quasi-Z Source Converter
IRJET- Single Switched Capacitor High Gain Boost Quasi-Z Source Converter
 
Smart Power Transmission System Using FACTS Device
Smart Power Transmission System Using FACTS DeviceSmart Power Transmission System Using FACTS Device
Smart Power Transmission System Using FACTS Device
 
Automated load shedding using microcontroller
Automated load shedding using microcontrollerAutomated load shedding using microcontroller
Automated load shedding using microcontroller
 
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...
 
IRJET- Modified Cascaded H - Bridge Multilevel Inverter for Household Appliances
IRJET- Modified Cascaded H - Bridge Multilevel Inverter for Household AppliancesIRJET- Modified Cascaded H - Bridge Multilevel Inverter for Household Appliances
IRJET- Modified Cascaded H - Bridge Multilevel Inverter for Household Appliances
 
automatic power factor correction report
automatic power factor correction reportautomatic power factor correction report
automatic power factor correction report
 
IRJET- Diode Clamped Multilevel Inverter for Induction Motor Drive
IRJET- Diode Clamped Multilevel Inverter for Induction Motor DriveIRJET- Diode Clamped Multilevel Inverter for Induction Motor Drive
IRJET- Diode Clamped Multilevel Inverter for Induction Motor Drive
 
IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...
IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...
IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...
 

Similaire à United_Mavuso_Substation_Detailed_Report_20151102 - 20160131-Rev 1

Power factor correction
Power factor correctionPower factor correction
Power factor correction
slmnsvn
 
Design of CMOS Inverter for Low Power and High Speed using Mentor Graphics
Design of CMOS Inverter for Low Power and High Speed using Mentor GraphicsDesign of CMOS Inverter for Low Power and High Speed using Mentor Graphics
Design of CMOS Inverter for Low Power and High Speed using Mentor Graphics
IJEEE
 
Mosfet based ups cum-eps
Mosfet based ups cum-epsMosfet based ups cum-eps
Mosfet based ups cum-eps
jayonline_4u
 
Design of transformer less power supply for low power application
Design of transformer less power supply for low power applicationDesign of transformer less power supply for low power application
Design of transformer less power supply for low power application
eSAT Journals
 
Doc a.7-tlc report
Doc a.7-tlc reportDoc a.7-tlc report
Doc a.7-tlc report
9951081577
 

Similaire à United_Mavuso_Substation_Detailed_Report_20151102 - 20160131-Rev 1 (20)

Automatic Power Factor Detection And Correction using Arduino
Automatic Power Factor Detection And Correction using ArduinoAutomatic Power Factor Detection And Correction using Arduino
Automatic Power Factor Detection And Correction using Arduino
 
Simulation based minor project on Buck converter( DC to Dc step down Converter)
Simulation based minor project on Buck converter( DC to Dc step down Converter)Simulation based minor project on Buck converter( DC to Dc step down Converter)
Simulation based minor project on Buck converter( DC to Dc step down Converter)
 
MINI INVERTER
MINI INVERTERMINI INVERTER
MINI INVERTER
 
NTDC 220kV Transmission gird station Internship report
NTDC 220kV Transmission gird station Internship reportNTDC 220kV Transmission gird station Internship report
NTDC 220kV Transmission gird station Internship report
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
 
IRJET- A Novel High Speed Power Efficient Double Tail Comparator in 180nm...
IRJET-  	  A Novel High Speed Power Efficient Double Tail Comparator in 180nm...IRJET-  	  A Novel High Speed Power Efficient Double Tail Comparator in 180nm...
IRJET- A Novel High Speed Power Efficient Double Tail Comparator in 180nm...
 
POWER CONSUMPTION AT CIRCUIT OR LOGIC LEVEL IN CIRCUIT
POWER CONSUMPTION AT CIRCUIT OR LOGIC LEVEL IN CIRCUITPOWER CONSUMPTION AT CIRCUIT OR LOGIC LEVEL IN CIRCUIT
POWER CONSUMPTION AT CIRCUIT OR LOGIC LEVEL IN CIRCUIT
 
132 33kv substation documentation
132 33kv substation documentation132 33kv substation documentation
132 33kv substation documentation
 
Design of CMOS Inverter for Low Power and High Speed using Mentor Graphics
Design of CMOS Inverter for Low Power and High Speed using Mentor GraphicsDesign of CMOS Inverter for Low Power and High Speed using Mentor Graphics
Design of CMOS Inverter for Low Power and High Speed using Mentor Graphics
 
IRJET- Implementation of Low Power 32-Bit Carry-Look Ahead Adder using Ad...
IRJET-  	  Implementation of Low Power 32-Bit Carry-Look Ahead Adder using Ad...IRJET-  	  Implementation of Low Power 32-Bit Carry-Look Ahead Adder using Ad...
IRJET- Implementation of Low Power 32-Bit Carry-Look Ahead Adder using Ad...
 
automatic phase changer in three phase supply
automatic phase changer in three phase supplyautomatic phase changer in three phase supply
automatic phase changer in three phase supply
 
Mosfet based ups cum-eps
Mosfet based ups cum-epsMosfet based ups cum-eps
Mosfet based ups cum-eps
 
IRJET- Design and Analysis of Single Ended Primary Inductance Converter (SEPI...
IRJET- Design and Analysis of Single Ended Primary Inductance Converter (SEPI...IRJET- Design and Analysis of Single Ended Primary Inductance Converter (SEPI...
IRJET- Design and Analysis of Single Ended Primary Inductance Converter (SEPI...
 
IRJET- Automated Energy Monitering System and Power Factor Improvement
IRJET-  	  Automated Energy Monitering System and Power Factor ImprovementIRJET-  	  Automated Energy Monitering System and Power Factor Improvement
IRJET- Automated Energy Monitering System and Power Factor Improvement
 
Design of transformer less power supply for low power application
Design of transformer less power supply for low power applicationDesign of transformer less power supply for low power application
Design of transformer less power supply for low power application
 
Buck converterdesignnote
Buck converterdesignnoteBuck converterdesignnote
Buck converterdesignnote
 
Project report soofi
Project report soofiProject report soofi
Project report soofi
 
Doc a.7-tlc report
Doc a.7-tlc reportDoc a.7-tlc report
Doc a.7-tlc report
 
IRJET- Implementation of Low Power Flash ADC using Adiabatic Logic based Doub...
IRJET- Implementation of Low Power Flash ADC using Adiabatic Logic based Doub...IRJET- Implementation of Low Power Flash ADC using Adiabatic Logic based Doub...
IRJET- Implementation of Low Power Flash ADC using Adiabatic Logic based Doub...
 
DigSILENT PF - 06 irena additional exercises
DigSILENT PF - 06 irena  additional exercisesDigSILENT PF - 06 irena  additional exercises
DigSILENT PF - 06 irena additional exercises
 

United_Mavuso_Substation_Detailed_Report_20151102 - 20160131-Rev 1

  • 1. Designed to order. Built to last© 1 Substation Report Training Report Mavuso United M. Swaziland Electricity Company united.mavuso@sec.co.sz Substation Engineer Signature: 02nd November – 31st January 2016 Trainee Signature: Energy For The Future
  • 2. Designed to order. Built to last© 2 Abstract The purpose of this report is to reveal the scope of work covered by Substation department as part of my Engineering Training programme at SEC. The goal of this report is to show a clear understanding of the work done by the substation department in SEC. It also shows my involvement to the work done in every day routine to meet its goals. A preamble of the Substation department in general is first presented followed by a summary of the SEC Substation department. The full details of industrial exposure and acquired knowledge is then shared under the tasks involved in section. Finally recommendations are made which may make SEC substation department a better company in the future.
  • 3. Designed to order. Built to last© 3 Table of Contents Abstract...................................................................................................................................................2 Abbreviations .........................................................................................................................................4 Table of Figures.......................................................................................................................................5 1. Preamble.........................................................................................................................................6 2. Why We Need Electrical Power Substations.................................................................................7 2.1 Practical Considerations..............................................................................................................7 2.2 Technical Considerations ............................................................................................................7 3. Equipment Used.............................................................................................................................8 3.1 Voltage Transformer (VT)............................................................................................................8 3.2 Current Transformer (CT)............................................................................................................8 3.3 Power Transformer.....................................................................................................................9 3.3.1 Main Tank .............................................................................................................................10 3.3.2 The Conservator....................................................................................................................10 3.3.3 Tap Changer ..........................................................................................................................11 3.3.4 Guard Unit.............................................................................................................................12 3.4 Circuit Breakers.........................................................................................................................12 3.4.1 Oil Circuit Breaker.................................................................................................................13 3.4.2 SF6 Gas Circuit Breakers ........................................................................................................13 3.4.3 Vacuum Circuit Breaker ........................................................................................................14 3.5 Protection Panel........................................................................................................................15 4. Substations Activities...................................................................................................................16 4.1 Oil Sampling and Testing...........................................................................................................16 4.2 Infra-red Scanning.....................................................................................................................18 4.3 Transformer Movement............................................................................................................19 4.4 Tap Changer Maintenance..............................................................................................................20 4.5 Power Transformer Maintenance.............................................................................................21 5. Tasks Involved In ..........................................................................................................................22 6. Recommendations .......................................................................................................................24 7. Conclusion ....................................................................................................................................26
  • 4. Designed to order. Built to last© 4 Abbreviations SEC Swaziland Electricity Company NCC National Control Centre ISO International Standards Organisation SCADA Supervisory Control and Data Acquisition AC Alternating Current DC Direct Current HV High Voltage VT Voltage Transformer CT Current Transformer CB Circuit Breaker REF Restricted Earth Fault NCT Neutral Current Transformer IDMT Inverse Definite Minimum Time O/C Overcurrent IED Intelligence Electronic Device E/F Earth Fault OLTC On Load Tap Changer LV Low Voltage MV Medium Voltage HV High Voltage SFRA Sweep Frequency Response Analysis FAT Factory Acceptance Test SAT Site Acceptance Test HIRA Hazard Identification and Risk Assessment
  • 5. Designed to order. Built to last© 5 Table of Figures Figure 1: Substation Diagram Mimic.......................................................................................................6 Figure 2: Voltage Transformer (VT) ........................................................................................................8 Figure 3: Current Transformer (CT).........................................................................................................9 Figure 4: Atmoseal Conservator ...........................................................................................................11 Figure 5: Infrared Camera.....................................................................................................................18 Figure 6: Mpaka Power Transformer Movement .................................................................................20 Figure 7: Mpaka Transformer Transportation ......................................................................................22 Figure 8: Stonehenge Cable Laying.......................................................................................................23 Figure 9: Leaking Lobamba Transformer ..............................................................................................24 Figure 10: Positioning of Cable Rollers .................................................................................................25
  • 6. Designed to order. Built to last© 6 1. Preamble Substation is a part of an electrical generation, transmission, and distribution system. The main objective of substation is to transform voltage from high to low, or the reverse. Between the generating station and consumer, electrical power may flow through several substations at different voltage levels. Substations are left unattended, relying on SCADA for remote supervision and control. Substations generally have switching (switchgear), protection, control equipment, and transformers. Other equipment found in a substation could be capacitor banks, and voltage regulators. Substations do not usually have generators, although a power plant may have a substation nearby. The Swaziland Electricity Company Substation department operates as depicted on figure 1. Substations is a department which is mainly supported by the linked departments. All this departments have their equipment which they operate in substations. The critical equipment in a substation is the transformer, everything that happens in the substation is benchmarked by the transformer limit levels. Figure 1: Substation Diagram Mimic
  • 7. Designed to order. Built to last© 7 2. Why We Need Electrical Power Substations We build substations for the following reasons: 2.1 Practical Considerations  To satisfy load growth; when people move to a new location that has no power supply infrastructure, it might make a case for building a substation close to that location. Supplying this new load from distant substations is inefficient because most power will be lost in the transmission lines as heat (Ploss = I2 R) and on distribution lines.  To accommodate new generation power plants; either you want to build a solar or wind farm, you will need a collector substation to tie all generators and connect them to the power grid.  To maintain reliability requirements; new transmission lines are constructed by utilities to address any deficiency in the power grid. When building new transmission lines, effort is made to connect to an existing substation. When no existing power substation, a new substation is considered. 2.2 Technical Considerations  To transform voltage levels; since higher voltages mean lower currents. Lower currents yield to lower I2 R (copper) losses. Thus more energy can be delivered to do useful work. Voltages at the distribution end need to be stepped down for customer utilisation. Substations provide the necessary real – estate to install a transformer for power transmission and distribution.  To break power flow; quite often a fault requires complete isolation of the line until the fault is removed. To safely interrupt hundreds of amperes you will need circuit breakers that can handle high current magnitudes. All substations contain circuit breakers which they trip and isolate transmission lines connected to it.  Provide support to the power flow; unlike DC power flow, AC power flow needs to overcome not only the resistive impedance but also the impedance offered by the inductive nature of various equipment (like motor loads, transmission lines, reactors) connected to the system. For this reason, substations have capacitor banks connected to all three phases of the lines to ease the power flow. This also improves the power factor of the electrical system.
  • 8. Designed to order. Built to last© 8 3. Equipment Used 3.1 Voltage Transformer (VT) Voltage in power systems is too high to connect measuring instruments or relays directly, coupling is made through VT. This is a device which is used for stepping down the system voltage (AC) to a safe value which can be fed to relays. The VT has lower turns winding at its secondary when compared to its primary windings. A VT is insulated to withstand over voltages, including impulse voltages, of a level equal to the withstand value of the high voltage system. Voltage transformers are designed to maintain the specified accuracy in voltage output at their secondary. Primary of VT is connected across the phase and ground. If long secondary leads are required, a distribution box is fitted close to the VT to supply relay and metering instruments over separate leads. Usually the secondary voltage of voltage transformer is generally 110 V (AC). Figure 2: Voltage Transformer (VT) 3.2 Current Transformer (CT) Same as the voltage transformer, current in power systems is high to connect directly to measuring instruments, CT produce a reduced current accurately proportional to the current in the circuit as coupling. The CT has the same principle as VT but here is the difference. For a VT or general transformer, primary current varies with load (secondary current). With CT, primary current is the system (primary) current transforms to the CT secondary, hence load (burden current) depends upon primary current of the CT.
  • 9. Designed to order. Built to last© 9 Again, protection CT has the same principle with metering CT but here is the difference. For metering CT, accuracy ratio, between primary and secondary currents are essential within normal working range. The normal accuracy up to 125% of rated current as allowable system current must be below 125% of rated current. Due to faults the secondary of the CT could be saturated but saturation is prevented to reach the metering instrument connected to secondary of the CT as secondary current does not go above desired limit even when primary current rises to a very high value. But in the case of protection, the CT is desired not to be saturated during high fault current passing through primary. So core of protection CT is designed that it would be not saturated for long range of currents even on secondary of CT. Figure 3: Current Transformer (CT) 3.3 Power Transformer This is the main equipment in a substation, rather a critical and expensive component of the power system. Its working principle is exactly the same as voltage transformer (VT), except of the transformation voltage ratio level. SEC has 66/11kV, 132/66/11kV, and 11/66kV substation transformers which are mainly protected against fault currents, over voltages, over loads. The
  • 10. Designed to order. Built to last© 10 type of protection used should minimize the time of disconnection for faults within the transformer. Any extended operation of the transformer under abnormal condition comprises the life of the transformer, which means adequate protection should be provided for quicker isolation of the transformer. A transformer is made up of many components, that is, main tank, tap changer, guard unit, conservator, bushings, breathers, cooling system (radiators(ONAN, ONAF)), and the relays. 3.3.1 Main Tank This is the main component of the transformer where voltage transformation takes place. On its own, it has different parts which form part of the transformation process. It consists of insulating oil, laminated core, and paper insulated windings.  Laminated core; this is done to reduce eddy currents as low as possible since they interfere with the efficient transfer of energy. The eddy currents cause energy to be lost from the transformer as they heat up the core and energy getting lost as heat.  Paper insulated windings; between windings turns is a small voltage difference with the neighbouring winding turns. The voltage difference between the windings and neighbouring turns could be excessive and equals the voltage drop across a large number of turns in one winding layer. Therefore an extra insulation layer using paper strip is used between windings layers. This is not just an ordinary paper but cellulose paper with outstanding electrical properties making it appropriate for insulation.  Insulating oil (SEC uses power oil); it serves mainly as liquid insulation in the transformer, it also dissipates heat of the transformer, that is, it acts as a coolant. It further preserves the core and the winding as they are fully immersed inside oil and again the oil prevents direct contact of atmospheric oxygen (air) with cellulose made paper insulation of windings, which is susceptible to oxidation. 3.3.2 The Conservator This is a cylindrical tank mounted on supporting structure on the roof of the transformer main tank. Its main function is to provide adequate for expansion of oil inside the transformer. When a transformer is loaded (due to load increase) and when ambient temperature rises, the volume of oil inside the transformer increases. The conservator provides adequate space to this expanded transformer oil. When the load decreases and when ambient temperature decrease, the
  • 11. Designed to order. Built to last© 11 transformer oil contracts due decrease in temperature. This then causes outside air to enter in the conservator tank of transformer through silica gel breather. The conservator also acts as a reservoir for transformer insulating oil. An example of a conservator is shown in figure 4. This is an atmoseal type of a conservator. This kind of conservator, an air cell is fitted inside the conservator reservoir. The silica gel breather is connected at the top of this air cell. The oil level in the main tank rises and falls with respect to the air cell deflation and inflation. When air cell deflates the air inside cell comes out via breather and if cell inflates, the outside air comes in through breather. This arrangement prevents direct contact of oil with air, reducing ageing of insulating oil. Figure 4: Atmoseal Conservator 3.3.3 Tap Changer In larger electrical power transformers, for proper voltage regulation of transformer, a tap changer is required. Depending on which type is used, there are two kinds of tap changers which are on load tap changer (OLTC) and no load tap changer (NLTC). The tapping arrangement is placed in a separate tank attached to the transformer tank. On load tap changers are recommended since as the name suggests, permit tap changing and hence voltage regulation with the transformer on- load. Tap changing is done on HV winding for two reasons:  Because the currents are lower, the tap changer contacts or leads could be smaller
  • 12. Designed to order. Built to last© 12  The HV winding is wound outside the LV winding, it is easier to get the tapping connections out to the tap changer. 3.3.4 Guard Unit This is a unit which monitors winding and oil temperatures inside the transformer main tank. This is generally a precision unit. It is a temperature indicator of power transformer specially designed for protection of transformer in addition to its temperature indication and cooling control features. It performs mainly the following: i. It indicates instantaneous temperature of oil and windings of transformer. ii. Also records the maximum temperature rise of oil and windings. iii. The unit operates high temperature alarm at a predetermined value of allowable temperature limit. iv. The indicators can further trip the circuit breakers associated with power transformer when the temperature of oil or winding reaches a predetermined limit. v. The unit also controls the cooling system of the power transformer. Switches on the cooling equipment (cooling fans) when the winding or oil temperature reaches a pre-set temperature and switch off when temperature decreases. According to power transformer maintenance manual provided by ABB, the maximum temperature permitted for oil is of 90°C and the maximum temperature of the hottest point is 110°C. The guard unit will monitor the temperatures as reflected above. 3.4 Circuit Breakers This is a switching device which can be operated manually or automatically for controlling and protection of electrical power system. Its primary function is to provide opening and closing current carrying contacts. It remains at its closed position for maximum period of its life span. With SEC, we have some which are normally opened for the network stability. So these remain opened for maximum period of their lives unless there is a fault which will require system controllers to optimize the network through opening and closing the normally opened points. The operation of a circuit breaker is then required to be reliable without any delay or sluggishness. Many parameters come into play in the operation of a circuit breaker, which is, closing and opening distance of contacts, velocity of moving contacts, and stroke between contacts.
  • 13. Designed to order. Built to last© 13 At the moment SEC has different kinds of circuit breakers enrolled in the network, that is, oil circuit breaker, SF6 circuit breaker, and vacuum circuit breakers which are remotely operated (mostly) for the HV transmission network. There are different kinds of circuit breakers SEC has in the network, these are: a. Oil circuit breakers (OCB) b. SF6 gas circuit breakers (Sulphur Hexafluoride) c. Vacuum Circuit Breakers (VCB) 3.4.1 Oil Circuit Breaker The current carrying contacts are immerged inside the insulating oil. Whenever there is a separation of current carrying contacts in the oil, the arc in circuit breaker is initialised at the moment of separation of contacts, and due to this arc the oil is decomposed in mostly hydrogen gas and create hydrogen bubble around the arc. The highly compressed bubble around the arc prevents re-striking of the arc after current reaches the zero crossing of the cycle. Advantages of Oil Circuit Breakers  It is cheaper Disadvantages of Oil Circuit Breaker  Oil is flammable and may cause fire hazards. When a defective circuit breaker fails under pressure, it may cause an explosion.  The hydrogen generated during arcing, when combined with air, may form an explosive mixture.  During arcing, oil decomposes and becomes polluted by carbon particles, which reduces its dielectric strength. Hence it requires periodic maintenance and replacement.  Oldest type of circuit breaker. 3.4.2 SF6 Gas Circuit Breakers This is a circuit breaker in which the current carrying contacts operate in sulphur hexafluoride (SF6) gas. It has high affinity of absorbing free electron. When a free electron collides with the gas molecule, it is absorbed by that gas molecule. We know that mobility of charged particle is majorly responsible for conducting current through a gas. Over all mobility of the charged particle in the SF6 gas is much less as compared other common gases.
  • 14. Designed to order. Built to last© 14 For heavier and less mobile charged particles in SF6 gas, it acquires very high dielectric strength. SF6 gas has a good dielectric strength and a good property of fast recombination after the source energizing the spark is removed. Advantages of SF6 Gas Circuit Breakers  High dielectric strength  It insulates 2.5 times better than air  Good heat transfer property  Fast recombination after the source energizing the spark is removed  SF6 gas is identified as one of the greenhouse gases which can reradiate back to earth some of the earth’s natural infrared radiation. It is environmentally friendly, that is, does not deplete the ozone layer.  It is not a health hazard. So due to the SF6 gas having high dielectric strength and high cooling effect, the gas is approximately 100 times more effective arc quenching media than air. Due to this unique properties of this gas is used for voltages ranging from 33kV to 800kV and even more. 3.4.3 Vacuum Circuit Breaker This is a breaker where the arc quenching takes place in a vacuum. The operation of opening and closing of current carrying contacts and associated arc interruption take place in a vacuum chamber called vacuum interrupter. It mainly used for medium voltage switchgear. Advantages of VCB  No chance of fire hazard compared to OCB  High insulation strength  No gas/oil filling required  No emission of gases, hence pollution free.  Rapid recovery of very high dielectric strength on current interruption. Disadvantages of VCB  Loss of vacuum due to transit damage or failure makes the entire interruption useless and cannot be repaired on site.
  • 15. Designed to order. Built to last© 15 3.5 Protection Panel This is a box where all information provided by either VT’s, CT’s, or power transformers is interpreted as to be safe enough for the equipment operation. The panel could either be for the bus-zone or power transformer or transmission lines (feeders), which simply means that panel has relays which interprets information with respect to the mentioned equipment. Different protection relays are used for different purposes in SEC with respect to the kind of protection scheme enrolled. A protection relay is an automatic device which senses an abnormal condition of electrical circuit and closes its contact so to isolate the abnormal condition. The basic characteristics which ensures high performance of protection equipment are as follows: 1. Reliability – this is an assurance that protection will perform correctly when required. 2. Selectivity – this is an assurance that protection will trip only those circuit breakers whose operation is required to isolate fault condition. 3. Speed – this is to ensure isolation of faulty conditions on the power system as rapidly as possible before fault leads to collapse of entire system. 4. Sensitivity – protection equipment should be high sensitive, that is, should have minimal operating time during abnormal conditions. In wiring a protection panel, different codes (ferruling) are used depending whether it is an AC or DC signal being wired. Furthermore, the ferruling depends on the kind of connection you are doing, could be SCADA controls, metering, bus bar protection, inter alia. Below is a summarised table for codes of practice for power system protection. CODE Signal type Used for A AC CT secondary for main protection B Bus bar protection C Protection circuits (O/C and Earth fault) D Metering circuit E Voltage transformer secondary H Auxiliary transformer secondary P Bus bar controls J DC DC incoming from charger K DC voltage controls – Closing, tripping L DC voltage indications – Alarms, indications, annunciations M DC voltage for motor spring circuit
  • 16. Designed to order. Built to last© 16 N DC voltage for OLTC circuit X Scada controls and indications 1 Positive signal 2 Negative signal Table 1: Codes of Practice for Power System Protection There are further rules that apply with regards to panel wiring under protection. Which are:  Entire wiring of circuitry should be of permanent wiring  Leads should be marked and identified near terminals (ferruling).  Every lead should end at a terminal point and no junction by twisting is allowed.  DC and AC supplies should not be taken through different cores of the same cable. Totally different cables should be used for DC and AC supplies.  The cable entries in protection panels should be through appropriate size of cable glands. No other means.  Wherever CT cores are not used “shorting loops” should be provided in CT secondary terminals and not at panels. The mentioned are some of the many rules that apply under power system protection. Oil sampling, infra-red scanning, substation inspection, transformer/substations maintenance, projects, faults, 4. Substations Activities Substation department is equipped in doing some activities which may inform better the status of her assets on the ground, that is, in terms of asset maintenance, substation yard maintenance, inter alia. 4.1 Oil Sampling and Testing The department engages itself to do oil sampling and testing in all substation transformers (54 functional substations) once every year. This is done since ABB (1ZCL000002EG-EN – rev. 1) manual has mentioned that we should do it at least once a year. This activity is outsourced to South African companies (the likes of TSS, wear-check, inter alia). After the sampling, samples are tested for the following: 1) Oil Condition
  • 17. Designed to order. Built to last© 17 a. Karl Fischer (Moisture content determination, should be less than 20 ppm according to the manual (ABB)) b. Acidity (should be less than 0.3 mg KOH/gram of oil) c. Dielectric Strength (kV, minimum of 30kV) d. PCB (Polychlorinated Biphenyls) e. Oil temperature (maximum of 90°C) f. Dissolved Gas Analysis (each gas is a prediction of a certain kind of fault as depicted in Table 2) Table 2: Power Transformer Gases Interpretation Gas Normal Condition Abnormal Condition Temperature (°C) Interpretation H2 (Hydrogen) < 150 ppm > 1000 ppm > 900 Arcing Corona, Partial discharge, present in all types of faults but mainly corona and arcing CH4 (Methane) < 25 ppm > 80 ppm 150 > Temp > 300 Sparking, Core bolts faults, Under designed core. C2H6 (Ethane) < 10 ppm > 35 ppm 250 > Temp > 500 Local Overheating, tap selector contacts, core bolt faults C2H4 (Ethylene) < 20 ppm > 100 ppm 500 > Temp > 900 Severe Overheating, bushing connections C2H2 (Acetylene) < 15 ppm > 70 ppm > 900 Arcing CO (Carbon Monoxide) < 500 ppm > 1000 ppm > 900 Severe Overloading CO2 (Carbon Dioxide) < 10 000 ppm > 15 000 ppm > 900 Severe Overloading Table 2 shows is called the California State University Guidelines type of analysis. 2) Transformer Condition
  • 18. Designed to order. Built to last© 18 a. Paint condition b. Silica Gel Condition c. Oil Level 3) Additional Tests a. Sludge condition b. Flash point c. Furanic value d. Degree of polarization (for a healthy transformer should be 700 – 1200. It basically reflects the insulation paper condition) After the tests, the contractor will mention its recommendations as action plans to be considered by substation department. 4.2 Infra-red Scanning Increased resistance and heat are the primary reasons most electrical equipment fail. Before any failure, the equipment will heat up. This activity (Infrared scanning) is used to inspect electrical equipment because excess heat is usually the first sign of trouble. Loose connections imbalanced or overloaded circuits, defective breakers, damaged switches, faulty fuses, and material defects all lead to equipment failure. Using infrared scanning as an early warning tool for potential electrical equipment/system failure is an important part of maintaining mission critical uptime. SEC substation department has committed herself in performing the activity for every substation within the SEC. Figure 5: Infrared Camera Figure 5 shows an infrared camera which is used for the activity. The great thing about this camera, it produces its own report on completion of job.
  • 19. Designed to order. Built to last© 19 The early detection will allow maintenance personnel to take corrective action before equipment failure, minimizing damage to the components and reducing repair costs. 4.3 Transformer Movement This is mainly a relocation of power transformers with their associated equipment in a safe and controlled movement; ensuring the integrity of the transformer. The activity include uplifting and movement of old/new power transformers to new location either for installation or repairs or refurbishments. In transformer movement there are key considerations to be taken with their activities. These are:  Planning activity; transport routes, lifting plans, tools to be used (hydraulic jacks, turfors, winch truck, rail slippers, rails, pulleys, slings)  Mechanical dismantle of auxiliary equipment, that is, bushings, conservator, buchholz relay, inter alia.  Uplifting, loading, transport, offloading, and final positioning at new location.  Depending on where you transporting the unit, for new installation you should consider testing (SFRA) after offloading. Figure 6 shows a 3 MVA Mpaka transformer being transported by a winch truck. The transformer had to go for refurbishment since it had a high leakage between main tank and tap changer which had an impact to the environment.
  • 20. Designed to order. Built to last© 20 Figure 6: Mpaka Power Transformer Movement 4.4 Tap Changer Maintenance The tap changer operation has been discussed in 3.3.3 but SEC has a commitment to maintain power transformer tap changers. This maintenance is done so to reduce arcing times and extend contact life. The switching contacts are made of copper/tungsten, or in the case of tap changers for lower currents, the contacts are made of copper. After a certain number of operations the tap changer is expected to be maintained to see if it still has good oil, good contacts. It is worth noting that a tap changer gives a service life that equals to power transformer service life. The major parts which need attention during maintenance are:  The contacts which may need replacement  The motor drive mechanism Prior to the maintenance is an annual inspection which has to be performed to read counting devices. The readings are used to determine when overhaul is due, which is done every seven years. During overhaul, the following is done:  Checking dielectric strength of the oil  Filtering the oil
  • 21. Designed to order. Built to last© 21  Checking motor drive mechanism  Checking the pressure relay  And checking the contact wear. SEC substation department usually outsource this activity to the company which designed the tap changers. The maintenance is mainly done just because during tapping (switching), arcs are generated on the main switching and transition contacts of the diverter switch. The arcs cause carbonisation of the switching oil and lead to wear. 4.5Power Transformer Maintenance A power transformer is the most costly and essential equipment found in a substation. For getting high performance and long functional life of the transformer, it is desired to perform various maintenance actions including measurement and testing of different parameters of the transformer. This maintenance is done mainly for the objectives stated in 2.1 and 2.2. Loss of a transformer in a substation will result in many customers being affected. Two types of transformer maintenances are available: for getting smooth performance from a transformer we have to perform maintenance in regular basis, and the other type is performed as in when it is required. If regular maintenance (condition maintenance) is performed properly, one may not have any provision of performing emergency maintenance. This could avoid emergency and breakdown maintenance. Before any maintenance within SEC substations, there is a substation inspection which is done which informs the power transformer maintenance for that substation. Mainly for power transformer maintenance the following is considered:  The oil level in oil cap under silica gel breather, if high than expected level oil should be topped up.  Colour of silica gel in breather depending on what kind of silica gel is used.  Oil leakage from any point of the transformer.  Reading of oil level gauge of main tank and tap changer. If oil is less, should be topped up.  Transformer bushings be cleaned and inspected for any cracks  Mechanical inspection of buchholz relay  Insulation resistance of transformer must be checked  Transformer oil dielectric strength be done
  • 22. Designed to order. Built to last© 22 Amongst others, the above should be done for every transformer maintenance performed within SEC. Other activities in SEC substation are H.V yard maintenance, Circuit breaker maintenance, H.V cable termination, H.V isolator installation and commissioning, and FAT’s and SAT’s. 5. Tasks Involved In In my attachment with SEC substation department, listed below are the tasks I was involved in:  Transformer movement from Mpaka substation. The 3 MVA developed a leak while in service and was taken out of service and the oil was drained. o 3MVA, 66/11 kV, S/N: Y16113, Yz11, Yorkshire transformer, year of manufacture: 1966, 2678 gallons of oil. o Tools used: winch (low belt), slings, pulleys, 2 hydraulic jacks, two railroads, 2 turfors (5 & 3.5 tonnes), rail slippers. It was the first time to experience such, moving such a massive, with all the weight and height, it was pretty impressive. Unfortunately there was no procedure to move the transformer. Transformer was loaded safely but the challenge was that tap changer was too big such that it overlapped on to the road. Yes we used an abnormal truck to move the transformer but it was not good enough. We were a hazard to the other traffic going opposite us. Figure 7: Mpaka Transformer Transportation 3MVA Transformer Trainee & Technician Railroad Low belt truck
  • 23. Designed to order. Built to last© 23  Cable laying at Stonehenge (4 x 120 mm2 XLPE cables). These cables were from low voltage side (11kV bushings) of 10 MVA transformer 3 and 4 to incomer breakers. The job took 2 full days to complete it. Figure 8: Stonehenge Cable Laying  High voltage cable termination at Mkinkomo substation. After conducting HIRA and obtaining permit to work from the NCC we laid and terminated a 120 mm2 x 3 core cable which connected a PFC panel. Cable termination has its own procedure which when not followed properly it might lead to sever faults which could be electrical treeing, water treeing, inter alia.  Maloma substation maintenance; this involves transformer maintenance, circuit breaker maintenance, and H.V yard maintenance.  Refilling of SF6 gas into Sikhuphe substation breaker. The breaker due to decrease in gas level inside, tends to lock out and require refill and resetting for it to operate again.  At Nhlangano I substation, a project was ongoing, that is, the removal of outdoor circuit breakers into indoor circuit breakers. I was involved in the assembling of the indoor 11 kV panels inside the control room.  At Lobamba substation: transformer 2 had a leak around the core bushing. We had to re- gasket the bushing. This activity required us to drain about 10 drums of oil from the main tank. We missed the fact that we were supposed to close the conservator valve which leads into the main tank. This then delayed the whole process, which led the team spending most of the day on site. Figure 9 shows where the leak had occurred.
  • 24. Designed to order. Built to last© 24 Figure 9: Leaking Lobamba Transformer 6. Recommendations The substations department in SEC is responsible for 54 substations and a number of switchyards country wide, this then makes the management of the substations difficult. The management part of the substations involves a lot of responsibility on substation engineer. For improvement, the substation department requires to have maintenance engineer which will ensure maintenance is executed effectively. The importance of maintenance is very effective such that for 100% condition maintenance you will expect 0% breakdown of any equipment. Faults amongst the department occur now and then repeatedly but with the workload on the team, it is difficult to find time to find the root cause of every fault. As a transmission department in whole, I believe with a fault analysis team (amongst the existing resources) in place we could avoid having the same faults occurring repeatedly. This will further improve the substation (or even SEC at large) team competency in understanding the departments’ equipment operation. Infrared scanning being done on substations yard only, it is worth noting that even the panels require scanning as there are lots of connection done. I believe that every time an electrical panel is accessed, it should be infrared scanned. Anyone authorized to work in an electrical panel or high voltage cabling needs to be trained on infrared scanning. Core Bushing
  • 25. Designed to order. Built to last© 25 Substation department needs to make sure that for every meter or indicator used in a substation is calibrated or rather verified for its accuracy and operation. Mainly for oil temperature and winding temperature indicators (OTI and WTI) at least once in two years. The cable laying process is a tiring job without cable rollers. Substations need to have cable rollers as shown in Figure 10. The rollers are necessary to avoid abrasion of the cable by keeping it clear of the ground and to reduce friction during pulling. Figure 10: Positioning of Cable Rollers The ISO standards should be communicated in every monthly meetings and further explained its existence and implementation. In my time in the department, we have lost track of keeping engineering standards. These include the following;
  • 26. Designed to order. Built to last© 26  Yard stone cover; a 100mm thick layer of clean, washed, hard granite crusher stone of minimum sieve grid size of between 25mm and 36mm spread the entire substation yard and extend 1000mm beyond the substation fence. The lack of this motivates vegetation growth within the substation. 7. Conclusion I believe for future purposes substation department could do much better if the recommendations mentioned could be considered. Analysing insulating oil taken from transformers is a unique way of identifying problems occurring within a transformer. By identifying and quantifying the gases found in transformer oil, the condition of the transformer can be monitored. The interpretation of transformer oil gas analysis is still an art and not an exact science (the facts around DP tests). The interpretation should be left to a specialist and his advice and recommendations should be followed. Samples should be taken regularly and records kept. This is a huge department under transmission but I believe that if we could follow the management systems in place for every work executed we could achieve much better performance.