SlideShare une entreprise Scribd logo
1  sur  28
i. Grounding or Earthing 
ii. System Grounding 
iii. Methods of Neutral Grounding 
iv. Solid Grounding 
v. Resistance Grounding 
vi. Reactance Grounding 
vii. Resonant Groundings/Peterson coil 
Groundings
“The process of connecting the metallic frame 
of electrical equipment or some electrical part 
of the system (e.g. neutral point in a star-connected 
system) to earth (i.e. soil) is called 
grounding or earthing.”
“The process of connecting some electrical part of the 
power system (e.g. neutral point of a star-connected 
system, one conductor of the secondary of a transformer 
etc.) to earth (i.e. soil) is called system grounding.” 
To understand the importance of system grounding, lets 
illustrate it pictorially .
Fig. shows the primary winding of a distribution transformer connected between 
the line and neutral of a 11 kV line. There is capacitance C1 between primary and 
secondary and capacitance C2 between secondary and ground. This capacitance 
coupling can produce a high voltage between the secondary lines and the ground. 
If a person touches either one of the secondary wires, the resulting 
capacitive current IC flowing through the body could be dangerous even in case of 
small transformers.
• Let us now turn to a more serious situation. Fig. shows the 
primary winding of a distribution transformer connected between 
the line and neutral of a 11 kV line. 
• The secondary conductors are ungrounded. 
• Suppose that the high voltage line (11 kV in this case) touches the 
230 V conductor as shown in previous slide. 
• Under these circumstances, a very high voltage is imposed 
between the secondary conductors and ground.
 If one of the secondary lines is grounded as shown in 
Fig.(ii), the accidental contact be-tween a 11 kV conductor 
and a 230 V conductor produces a dead short. 
 The short-circuit current (i.e. fault current) follows the 
dotted path shown in Fig. 26.6 (ii). 
 This large current will blow the fuse on the 11 kV side, thus 
disconnecting the transformer and secondary distribution 
system from the 11 kV line.
The methods commonly used for grounding the neutral 
point of a 3-phase system are : 
 Solid or effective grounding 
 Resistance grounding 
 Reactance grounding 
 Peterson-coil grounding 
The choice of the method of grounding depends upon many 
factors including the size of the system, system voltage and 
the scheme of protection to be used.
“When the neutral point of a 3-phase system (e.g. 3- 
phase generator,3-phase transformer etc.) is directly 
connected to earth (i.e. soil) through a wire of negligible 
resistance and reactance, it is called solid grounding or 
effective grounding.” 
Fig. shows the solid grounding of 
the neutral point. Since the neutral 
point is directly connected to earth 
through a wire, the neutral point is 
held at 
earth potential under all 
conditions.
 The neutral is effectively held at earth potential. 
 When there is an earth fault on any phase of the system, 
the phase to earth voltage of the faulty phase becomes zero. 
However, the phase to earth voltages of the remaining two 
healthy phases remain at normal phase voltage because the 
potential of the neutral is fixed at earth potential. This 
permits to insulate the equipment for phase voltage. 
Therefore, there is a saving in the cost of equipment.
. 
 When earth fault occurs on any phase, the resultant capacitive current IC 
is in phase opposition to the fault current IF. The two currents completely 
cancel each other. Therefore, no arcing ground or over-voltage conditions 
can occur. 
 When there is an earth fault on any phase of the system, the phase to 
earth voltage of the faulty phase becomes zero. However, the phase to 
earth voltages of the remaining two healthy phases remain at normal 
phase voltage because the potential of the neutral is fixed at earth 
potential. This permits to insulate the equipment for phase voltage. 
Therefore, there is a saving in the cost of equipment.
The following are the disadvantages of solid grounding : 
i. 
ii. Since most of the faults on an overhead system are phase 
to earth faults, the system has to bear a large number of 
severe shocks. This causes the system to become 
unstable. 
iii. The solid grounding results in heavy earth fault currents. 
Since the fault has to be cleared by the circuit breakers, 
the heavy earth fault currents may cause the burning of 
circuit breaker contacts. 
iv. The increased earth fault current results in greater 
interference in the neighbouring communication lines.
 Solid grounding is usually employed where the circuit impedance 
is sufficiently high so as to keep the earth fault current within safe 
limits. This system of grounding is used for voltages up to 33 kV 
with total power capacity not exceeding 5000 kVA. 
 At KAPCO all non current carrying mechanical parts e.g. 
generators outer covers, transmission lines poles, mechanical 
supports of CT’s and PT’s are Solid Grounded. 
 Secondary star point 11 KV to 220 KV unit transformer is also 
solid grounded. This is due to the reason that at secondary side 
current is very low because of high voltage and even in case of 
un-balanced load the neutral current is very low.
In order to limit the magnitude of earth fault current, it is a 
common practice to connect the neutral point of a 3-phase 
system to earth through a resistor. This is called resistance 
grounding. 
When the neutral point of a 3-phase system (e.g. 3-phase 
generator, 3-phase transformer etc.) is connected to earth (i.e. 
soil) through a resistor, it is called resistance grounding.
. 
 Fig. shows the grounding of 
neutral point through a resistor 
R. 
 The value of R should neither 
be very low nor very high. 
 If the value of earthing 
resistance R is very low, the 
earth fault current will be large and 
the system becomes similar to the 
solid grounding system. 
 On the other hand, if the earthing 
resistance R is very high, the system 
conditions become similar to 
ungrounded System
. 
The value of R is so chosen such that the earth fault 
current is limited to safe value but still sufficient to 
permit the operation of earth fault protection system. 
In practice, that value of R is selected that limits the 
earth fault current to 2 times the nor-mal full load 
current of the earthed generator or transformer.
The following are the advantages of resistance earthing: 
By adjusting the value of R, the arcing grounds can be 
minimized. 
The earth fault current is small due to the presence of 
earthing resistance. Therefore, interference with 
communication circuits is reduced. 
It improves the stability of the system.
. 
 Suppose earth fault occurs in phase B as shown in Fig. The 
capacitive currents IR and IY flow in the healthy phases R and Y 
respectively. 
 The fault current IF lags behind the phase voltage of the faulted 
phase by a certain angle depending upon the earthing resistance 
R.
. 
 The fault current IF can be resolved into two components viz. 
i. IF1 in phase with the faulty phase voltage. 
ii. IF2 lagging behind the faulty phase voltage by 90°. 
 The lagging component IF2 is in phase opposition to the total 
capacitive current IC. 
 If the value of earthing resistance R is so adjusted that 
IF2= IC, the arcing ground is completely eliminated and the 
operation of the system becomes that of solidly grounded 
system. However, if R is so adjusted 
 
 that IF2< IC, the operation of the system becomes that of 
ungrounded neutral system.
The following are the disadvantages of resistance 
grounding: 
Since the system neutral is displaced during earth 
faults, the equipment has to be insulated for higher 
voltages. 
This system is costlier than the solidly grounded 
system. 
 A large amount of energy is produced in the earthing 
resistance during earth faults. Some-times it becomes 
difficult to dissipate this energy to atmosphere.
It is used on a system operating at voltages between 2.2 
kV and 33 kV with power source capacity more than 
5000 kVA. 
At KAPCO the star point of 11 KV 11 KV Auxiliary 
Transformer (BBT) is solid grounded 
So, in case of unbalanced load the high neutral current 
of auxiliary transformer is limited by applying 
resistance ‘R’ between star point and ground(Soil)
 In this system, a reactance is inserted between the 
neutral and ground as shown in Fig. The purpose of 
reactance is to limit the earth fault current. By 
changing the earthing reactance, the earth fault 
current can to changed to obtain the conditions 
similar to that of solid grounding.
This method is not used these days because of the 
following disadvantages : 
In this system, the fault current required to operate the 
protective device is higher than that of resistance 
grounding for the same fault conditions. 
High transient voltages appear under fault conditions.
We have seen that capacitive currents are responsible for producing 
arcing grounds. These capacitive currents flow because capacitance 
exists between each line and earth. 
If inductance L of appropriate value is connected in parallel with the 
capacitance of the system, the fault current IF flowing through L 
will be in phase opposition to the capacitive current IC of the 
system. If L is so adjusted that IL = IC, then resultant current in the 
fault will be zero. 
“When the value of L of arc suppression coil is such that the fault 
current IF exactly balances the capacitive current IC, it is called 
resonant grounding.”
 An arc suppression coil (also called Peterson coil) is an iron-cored 
coil connected between the neutral and earth as shown 
in Fig. 
 The reactor is provided with tappings to change the inductance 
of the coil. By adjusting the tappings on the coil, resonant 
grounding can be achieved
The Peterson coil grounding has the following 
advantages: 
The Peterson coil is completely effective in preventing 
any damage by an arcing ground. 
The Peterson coil has the advantages of ungrounded 
neutral system
The Peterson coil grounding has the following 
disadvantages : 
 Due to varying operational conditions, the 
capacitance of the network changes from time to time. 
Therefore, inductance L of Peterson coil requires 
readjustment. 
The lines should be transposed.
At KAPCO the circuitry of resonant grounding is 
achieved by using the windings of a transformer as 
resonant coil 
The particular value of inductance ‘L’ is obtained by 
using known number of turns in transformer 
windings. 
The Neutral point (star point) of power generator is 
resonant grounded because of above discussed 
advantages.

Contenu connexe

Tendances

Shunt active power filter
Shunt active power filterShunt active power filter
Shunt active power filter
Ranganath
 

Tendances (20)

Alternator protection
Alternator protectionAlternator protection
Alternator protection
 
Series & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs DevicesSeries & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs Devices
 
speed control of three phase induction motor
speed control of three phase induction motorspeed control of three phase induction motor
speed control of three phase induction motor
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma
 
surge diverters
surge diverterssurge diverters
surge diverters
 
Shunt active power filter
Shunt active power filterShunt active power filter
Shunt active power filter
 
Hv module 3 Impulse voltage generation
Hv module 3 Impulse voltage generationHv module 3 Impulse voltage generation
Hv module 3 Impulse voltage generation
 
EXCITATION SYSTEMS
EXCITATION SYSTEMSEXCITATION SYSTEMS
EXCITATION SYSTEMS
 
Effect of grounding
Effect of groundingEffect of grounding
Effect of grounding
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
BUSBAR PROTECTION
BUSBAR PROTECTIONBUSBAR PROTECTION
BUSBAR PROTECTION
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
INTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERINTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLER
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Tcsc ppt
Tcsc pptTcsc ppt
Tcsc ppt
 
Two area system
Two area systemTwo area system
Two area system
 
Lightning Arrester Working Principle & Types
Lightning Arrester Working Principle & TypesLightning Arrester Working Principle & Types
Lightning Arrester Working Principle & Types
 
Instrument transformer CT & PT
Instrument transformer CT & PTInstrument transformer CT & PT
Instrument transformer CT & PT
 
Static relay
Static relayStatic relay
Static relay
 

Similaire à Neutral grounding

Electrical grounding and earthing systems
Electrical grounding and earthing systemsElectrical grounding and earthing systems
Electrical grounding and earthing systems
Biswajit Pratihari
 

Similaire à Neutral grounding (20)

Earthing of epg
Earthing  of epg Earthing  of epg
Earthing of epg
 
Neutral Grounding
Neutral GroundingNeutral Grounding
Neutral Grounding
 
Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
E1103032933
E1103032933E1103032933
E1103032933
 
High voltage grounding methods
High voltage grounding methods High voltage grounding methods
High voltage grounding methods
 
IS : 3043 -1987 CODE OF PRACTICE FOR EARTHING(REACTANCE GROUNDING)
IS : 3043 -1987 CODE OF PRACTICE FOR EARTHING(REACTANCE GROUNDING)IS : 3043 -1987 CODE OF PRACTICE FOR EARTHING(REACTANCE GROUNDING)
IS : 3043 -1987 CODE OF PRACTICE FOR EARTHING(REACTANCE GROUNDING)
 
Electrical grounding and earthing systems
Electrical grounding and earthing systemsElectrical grounding and earthing systems
Electrical grounding and earthing systems
 
Protection Devices and the Lightning
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the Lightning
 
Substation Neutral Earthing
Substation Neutral EarthingSubstation Neutral Earthing
Substation Neutral Earthing
 
System neutral-earthing
System neutral-earthingSystem neutral-earthing
System neutral-earthing
 
Power system earthing.pptx
Power system earthing.pptxPower system earthing.pptx
Power system earthing.pptx
 
Grounding, neutral &amp; earthing
Grounding, neutral &amp; earthingGrounding, neutral &amp; earthing
Grounding, neutral &amp; earthing
 
Earthing
EarthingEarthing
Earthing
 
Earthing and grounding.pptx
Earthing and grounding.pptxEarthing and grounding.pptx
Earthing and grounding.pptx
 
Grounding, neutral &amp; earthing
Grounding, neutral &amp; earthingGrounding, neutral &amp; earthing
Grounding, neutral &amp; earthing
 
Presentation best practice earthing and protection
Presentation   best practice earthing and protectionPresentation   best practice earthing and protection
Presentation best practice earthing and protection
 
Electrical q
Electrical qElectrical q
Electrical q
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDINGPROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
 

Dernier

Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
Kamal Acharya
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
MayuraD1
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 

Dernier (20)

Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
 
Engineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planesEngineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planes
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
Online electricity billing project report..pdf
Online electricity billing project report..pdfOnline electricity billing project report..pdf
Online electricity billing project report..pdf
 
Moment Distribution Method For Btech Civil
Moment Distribution Method For Btech CivilMoment Distribution Method For Btech Civil
Moment Distribution Method For Btech Civil
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKARHAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 

Neutral grounding

  • 1.
  • 2. i. Grounding or Earthing ii. System Grounding iii. Methods of Neutral Grounding iv. Solid Grounding v. Resistance Grounding vi. Reactance Grounding vii. Resonant Groundings/Peterson coil Groundings
  • 3. “The process of connecting the metallic frame of electrical equipment or some electrical part of the system (e.g. neutral point in a star-connected system) to earth (i.e. soil) is called grounding or earthing.”
  • 4. “The process of connecting some electrical part of the power system (e.g. neutral point of a star-connected system, one conductor of the secondary of a transformer etc.) to earth (i.e. soil) is called system grounding.” To understand the importance of system grounding, lets illustrate it pictorially .
  • 5. Fig. shows the primary winding of a distribution transformer connected between the line and neutral of a 11 kV line. There is capacitance C1 between primary and secondary and capacitance C2 between secondary and ground. This capacitance coupling can produce a high voltage between the secondary lines and the ground. If a person touches either one of the secondary wires, the resulting capacitive current IC flowing through the body could be dangerous even in case of small transformers.
  • 6. • Let us now turn to a more serious situation. Fig. shows the primary winding of a distribution transformer connected between the line and neutral of a 11 kV line. • The secondary conductors are ungrounded. • Suppose that the high voltage line (11 kV in this case) touches the 230 V conductor as shown in previous slide. • Under these circumstances, a very high voltage is imposed between the secondary conductors and ground.
  • 7.  If one of the secondary lines is grounded as shown in Fig.(ii), the accidental contact be-tween a 11 kV conductor and a 230 V conductor produces a dead short.  The short-circuit current (i.e. fault current) follows the dotted path shown in Fig. 26.6 (ii).  This large current will blow the fuse on the 11 kV side, thus disconnecting the transformer and secondary distribution system from the 11 kV line.
  • 8. The methods commonly used for grounding the neutral point of a 3-phase system are :  Solid or effective grounding  Resistance grounding  Reactance grounding  Peterson-coil grounding The choice of the method of grounding depends upon many factors including the size of the system, system voltage and the scheme of protection to be used.
  • 9. “When the neutral point of a 3-phase system (e.g. 3- phase generator,3-phase transformer etc.) is directly connected to earth (i.e. soil) through a wire of negligible resistance and reactance, it is called solid grounding or effective grounding.” Fig. shows the solid grounding of the neutral point. Since the neutral point is directly connected to earth through a wire, the neutral point is held at earth potential under all conditions.
  • 10.  The neutral is effectively held at earth potential.  When there is an earth fault on any phase of the system, the phase to earth voltage of the faulty phase becomes zero. However, the phase to earth voltages of the remaining two healthy phases remain at normal phase voltage because the potential of the neutral is fixed at earth potential. This permits to insulate the equipment for phase voltage. Therefore, there is a saving in the cost of equipment.
  • 11. .  When earth fault occurs on any phase, the resultant capacitive current IC is in phase opposition to the fault current IF. The two currents completely cancel each other. Therefore, no arcing ground or over-voltage conditions can occur.  When there is an earth fault on any phase of the system, the phase to earth voltage of the faulty phase becomes zero. However, the phase to earth voltages of the remaining two healthy phases remain at normal phase voltage because the potential of the neutral is fixed at earth potential. This permits to insulate the equipment for phase voltage. Therefore, there is a saving in the cost of equipment.
  • 12. The following are the disadvantages of solid grounding : i. ii. Since most of the faults on an overhead system are phase to earth faults, the system has to bear a large number of severe shocks. This causes the system to become unstable. iii. The solid grounding results in heavy earth fault currents. Since the fault has to be cleared by the circuit breakers, the heavy earth fault currents may cause the burning of circuit breaker contacts. iv. The increased earth fault current results in greater interference in the neighbouring communication lines.
  • 13.  Solid grounding is usually employed where the circuit impedance is sufficiently high so as to keep the earth fault current within safe limits. This system of grounding is used for voltages up to 33 kV with total power capacity not exceeding 5000 kVA.  At KAPCO all non current carrying mechanical parts e.g. generators outer covers, transmission lines poles, mechanical supports of CT’s and PT’s are Solid Grounded.  Secondary star point 11 KV to 220 KV unit transformer is also solid grounded. This is due to the reason that at secondary side current is very low because of high voltage and even in case of un-balanced load the neutral current is very low.
  • 14. In order to limit the magnitude of earth fault current, it is a common practice to connect the neutral point of a 3-phase system to earth through a resistor. This is called resistance grounding. When the neutral point of a 3-phase system (e.g. 3-phase generator, 3-phase transformer etc.) is connected to earth (i.e. soil) through a resistor, it is called resistance grounding.
  • 15. .  Fig. shows the grounding of neutral point through a resistor R.  The value of R should neither be very low nor very high.  If the value of earthing resistance R is very low, the earth fault current will be large and the system becomes similar to the solid grounding system.  On the other hand, if the earthing resistance R is very high, the system conditions become similar to ungrounded System
  • 16. . The value of R is so chosen such that the earth fault current is limited to safe value but still sufficient to permit the operation of earth fault protection system. In practice, that value of R is selected that limits the earth fault current to 2 times the nor-mal full load current of the earthed generator or transformer.
  • 17. The following are the advantages of resistance earthing: By adjusting the value of R, the arcing grounds can be minimized. The earth fault current is small due to the presence of earthing resistance. Therefore, interference with communication circuits is reduced. It improves the stability of the system.
  • 18. .  Suppose earth fault occurs in phase B as shown in Fig. The capacitive currents IR and IY flow in the healthy phases R and Y respectively.  The fault current IF lags behind the phase voltage of the faulted phase by a certain angle depending upon the earthing resistance R.
  • 19. .  The fault current IF can be resolved into two components viz. i. IF1 in phase with the faulty phase voltage. ii. IF2 lagging behind the faulty phase voltage by 90°.  The lagging component IF2 is in phase opposition to the total capacitive current IC.  If the value of earthing resistance R is so adjusted that IF2= IC, the arcing ground is completely eliminated and the operation of the system becomes that of solidly grounded system. However, if R is so adjusted   that IF2< IC, the operation of the system becomes that of ungrounded neutral system.
  • 20. The following are the disadvantages of resistance grounding: Since the system neutral is displaced during earth faults, the equipment has to be insulated for higher voltages. This system is costlier than the solidly grounded system.  A large amount of energy is produced in the earthing resistance during earth faults. Some-times it becomes difficult to dissipate this energy to atmosphere.
  • 21. It is used on a system operating at voltages between 2.2 kV and 33 kV with power source capacity more than 5000 kVA. At KAPCO the star point of 11 KV 11 KV Auxiliary Transformer (BBT) is solid grounded So, in case of unbalanced load the high neutral current of auxiliary transformer is limited by applying resistance ‘R’ between star point and ground(Soil)
  • 22.  In this system, a reactance is inserted between the neutral and ground as shown in Fig. The purpose of reactance is to limit the earth fault current. By changing the earthing reactance, the earth fault current can to changed to obtain the conditions similar to that of solid grounding.
  • 23. This method is not used these days because of the following disadvantages : In this system, the fault current required to operate the protective device is higher than that of resistance grounding for the same fault conditions. High transient voltages appear under fault conditions.
  • 24. We have seen that capacitive currents are responsible for producing arcing grounds. These capacitive currents flow because capacitance exists between each line and earth. If inductance L of appropriate value is connected in parallel with the capacitance of the system, the fault current IF flowing through L will be in phase opposition to the capacitive current IC of the system. If L is so adjusted that IL = IC, then resultant current in the fault will be zero. “When the value of L of arc suppression coil is such that the fault current IF exactly balances the capacitive current IC, it is called resonant grounding.”
  • 25.  An arc suppression coil (also called Peterson coil) is an iron-cored coil connected between the neutral and earth as shown in Fig.  The reactor is provided with tappings to change the inductance of the coil. By adjusting the tappings on the coil, resonant grounding can be achieved
  • 26. The Peterson coil grounding has the following advantages: The Peterson coil is completely effective in preventing any damage by an arcing ground. The Peterson coil has the advantages of ungrounded neutral system
  • 27. The Peterson coil grounding has the following disadvantages :  Due to varying operational conditions, the capacitance of the network changes from time to time. Therefore, inductance L of Peterson coil requires readjustment. The lines should be transposed.
  • 28. At KAPCO the circuitry of resonant grounding is achieved by using the windings of a transformer as resonant coil The particular value of inductance ‘L’ is obtained by using known number of turns in transformer windings. The Neutral point (star point) of power generator is resonant grounded because of above discussed advantages.