SlideShare une entreprise Scribd logo
1  sur  13
Télécharger pour lire hors ligne
Chapter 8
VOLTAGE STABILITY
The small signal and transient angle stability was discussed in Chapter 6 and 7.
Another stability issue which is important, other than angle stability, is voltage
stability. Voltage stability can be defined as the ability of the system to retain system
voltages within acceptable limits when subjected to disturbance. If the disturbance is
large then it is called as large-disturbance voltage stability and if the disturbance is
small it is called as small-signal voltage stability [1]-[2]. Voltage stability can be a
local phenomenon where only a particular bus or buses in a particular region have
voltage stability issue and this may not affect the entire system. Voltage stability can
be a global phenomenon where many of the system buses experience voltage stability
problems which can also trigger angle stability problems and hence can affect the
entire system. Some of the voltage stability problems can start as a local problem and
escalate to global stability problem.
Voltage stability of a system can be analysed either by static analysis or
dynamic analysis. In static analysis the system is assumed to be in steady state and
hence instead of taking the DAE of the system only algebraic equations are
considered. This type of analysis is suitable for small-disturbances in the system. For
large disturbances the DAE are solved and the system response over a certain period
of time is observed. It is important that for voltage stability the loads should be
properly modelled as each type of load will affect the system voltage stability in a
different way. Similarly the tap changing transformers, shunt or series reactive power
compensators, generator reactive power limits, line charging capacitance should be
included in the system representation to get an accurate picture of voltage stability.
8.1 Basic Concept of Voltage Stability
To understand the concept of voltage stability let there be a two bus system with
one end being sending end and the other being receiving end as shown in Fig. 8.1. Let
the voltage of sending end be SV and that of receiving end be RV . The transmission
8.1
line is represented by a short line mode with impedance TZ T . If a load of
impedance LZ L is connected at the receiving end.
Fig. 8.1: Single line diagram of two bus system
The magnitude of current in the transmission line is given as, taking the sending end
voltage as reference,
 2 2
0
T T LZ Z 2 cos
S S
L T L T L T L
V V
I
Z Z Z Z   
 
  

  
(8.1)
The receiving end voltage magnitude is then defined as
 2 2
T LZ Z 2 cos
S L
R
T L T L
V Z
V
Z Z  

 
(8.2)
The real and reactive power consumed by the load is given as
 
 
2
2 2
S L
T L
V Z
Z Z
cos
2 cos
L
L
T L T L
P
Z Z

 

 
(8.3)
 
 
2
2 2
S L
T L
V Z
Z Z
sin
2 cos
L
L
T L T L
Q
Z Z

 

 
(8.4)
SV
TZ
RV
LZ
I
8.2
Let the transmission line impedance be taken as 0.25TZ pu , neglecting
resistance as usually the reactance to resistance ratio is quite high in a transmission
network. Let the sending end voltage be 1 pu . The real and reactive power of the load
can be increased by decreasing the load impedance LZ maintaining a constant power
factor say 0.8. The receiving end voltage is plotted in Fig. 8.2 with varying real power
consumed by the load, with the parameters mentioned above. This curve is called as
P-V curve.
Knee
Point
Fig. 8.2: P-V curve
It can be observed from P-V curve that as the load increases from no load
condition the receiving voltage starts dropping form initial no load voltage of 1 pu .
The increase in the current I due to decrease in the load impedance LZ is more than
the drop in the receiving end voltage magnitude and hence the real power
consumed by the load will increase. The maximum real power, 1
RV
pu , will be delivered
to the load when L TZ Z . Once operating point reaches the maximum power point or
critical point or knee point of the curve any further decrease in load impedance, to
8.3
increase the load, will result in further drop in the receiving end voltage and
simultaneously the real power consumed by the load will also decrease. This is
because after knee point the drop in the voltage is more than the increase in the line
current leading to a decrease in the real power consumed by the load.
8.1.1 Effect of load type on voltage stability
Fig. 8.3: P-V curve with stable and unstable operating points
Consider the P-V curve shown in Fig. 8.3. For a given real power consumed by
the load there are two possible receiving end voltages. As can be seen from operating
points A and B from Fig. 8.3, for a real power of 0.6 pu there are two receiving end
voltages of 0.85 pu and 0.20 pu , approximately. If the load is a constant MVA load
then the operating point A is stable where as the operating point B is unstable. In fact
for a constant MVA load any operating point below the knee point is unstable. This
phenomenon can be understood from the Fig. 8.3. Suppose due to some disturbance
the operating point moves from point A to C. At the operating point C the real power
is more than the real power at operating point A. Since, the load is constant MVA
8.4
load the current will decrease and therefore the operating point move back from C to
A. The operating point may not stop immediately at operating point A but may
oscillate around it and will settle down with enough damping. Hence, the operating
point A is a stable operating point. Now consider the operating point B. Again let the
operating point move to point D due to disturbance. At operating point D the real
power is less than that at operating point B. Since the load is a constant MVA load at
operating point D the current increases, as compared to operating point B, which leads
to a further voltage drop and further increase in the line current. This phenomenon
continues till the voltage at the receiving end becomes zero and hence called as
voltage collapse. Therefore, the operating point B is unstable operating point. It can
be observed from P-V curve that the curve above knee point has negative
that is the change in real power and voltage are in opposite direction, for a increase in
power voltage decreases and for a decrease in power voltage increases. The curve
below the knee point has positive and at the knee point is zero.
/RdV dP
/R LdV dP
L
L/RdV dP
Fig. 8.4: P-V curve for different power factor loads
8.5
Figure 8.4 show the P-V curves for loads with different power factors. It can be
observed from the figure that as the load power factor moves from lagging to leading
the knee point is shifted towards higher real power and higher voltage. This shows
that the voltage stability improves as the power factor moves from lagging to leading
loads.
Fig. 8.5: Q-V curve for different load real powers
Just as the load real power was plotted with respect to the receiving end voltage
for varying load impedances, the load reactive power variation with respect to the
receiving end voltage, with load real power being constant, can also be plotted.
Figure 8.5 shows the variation of receiving end voltage with variation in load reactive
power for three different real power loads. Again the locus of knee point is marked.
On the curve left of the locus of the knee point the reactive power and the voltage
move in opposite directions that is is negative and this region is unstable.
The curve on the right of the locus of the knee point the reactive power and the
voltage move in the same direction and hence is positive and this region is
stable. In the unstable region even if reactive power compensation is done through
shunt capacitance at the receiving end bus, the voltage of the receiving end bus will
/ RdQ dV
/ RdQ dV
8.6
not improve. One way of finding the voltage stability is to check the sensitivity of
each bus voltage with respect to the reactive power injected at that bus and if the
sensitivity is positive then it means the operating point is stable and is on the right
side of the locus of the knee points in Fig. 8.4 and if it is negative then it is on the left
side. This stable region and unstable region are only applicable to constant MVA
loads. In case of constant impedance and constant current loads the loads interact with
the system and settle at a new operating point as there is no requirement of constant
MVA.
8.2 Static Analysis
In static analysis [3] of voltage stability the snapshots of the entire system at
different instants is considered and at each instant the system is assumed to be in
steady state that the rates of changes of the dynamic variables are zero. Hence, instead
of considering all the differential algebraic equations only algebraic power balance
equations are considering assuming that the system is in steady state. At each instant
whether the system is voltage stable or not and also how far the system is from
instability can be assessed. There are two methods for assessing whether system is
voltage stable or not. They are sensitivity analysis [4] and modal analysis [5].
8.2.1 Sensitivity analysis
The power balance equations are taken assuming that the system is in steady
state. For, , assuming bus number 1 is a slack bus, the real power balance
equation is given as
2,......,i  n
 
1
( ) cos 0
n
Gi Di i i j ij i j ij
j
P P V VV Y   

    (8.5)
The reactive power balance equations are taken at the load buses, for
1, 2,......,g gi n n n  
8.7
(8.6)
1
( ) sin 0
n
Di i i j ij i j ij
j
Q V VV Y   

   









The linearized form of equations (8.5) and (8.6) is given as
2 2
1 1g g
n nP PV
n nQ QV
n n
P
P J J
Q VJ J
Q V




 
   
  
  
    
        
  
  
     
 
 
or
 
P
J
Q V
   
     



(8.7)
The matrix is the Jacobian matrix used in Newton-Raphson load flow analysis. For
constant real power is zero hence from equation (8.7)
J
P
 
1
P PVJ J

   V


(8.8)
Substituting (8.8) in (8.7) an simplifying leads to
(8.9) 
1
QV P PV QQ J J J J V 

   

Let,  
1
R QV P PV QJ J J J J 

  
 
, then
1
RV J Q
   (8.10)
The diagonal elements of the matrix 1
RJ 
represents the sensitivity of the voltage
with respect to the reactive power injected at that bus. This is nothing but the slope of
8.8
Q-V curve given in Fig. 8.4. Hence, if the V-Q sensitivity of an ith
bus is positive then
the system is voltage stable and if it is negative then the system is voltage unstable. A
small positive value of sensitivity indicates that the system is more voltage stable and
if the sensitivity is small with negative value then the system is highly voltage
unstable.
8.2.2 Modal Analysis
Voltage stability can also be estimated by the eigen values and eigen vectors of
the matrix . The matrix can be expressed in terms of right and left eigen vector
matrices as
1
RJ 
, 
RJ
RJ   (8.11)
1
RJ  
  1
(8.12)
Where, is a diagonal matrix with eigen values along its diagonal. Substituting
(8.12) in (8.10) lead to, noting that

I 
1 1
RV J Q Q 
      (8.13)
1
V 
   Q
Q
(8.14)
Let, v V and , then or  q   1
v q
 
1
i
i
v iq

 (8.15)
Where, is the ith
bus modal voltage and is the modal reactive power. If the
eigen value is positive then the system is voltage stable. The larger the eigen value
with positive sign the better the stability and if the eigen value has very small positive
value then it is very close to
iv iq
0i  , that is the critical point or knee point, and hence
8.9
very close to instability. If the eigen value is negative then the system is voltage
unstable.
8.3 Dynamic Analysis
The voltage stability of a system can also be assessed by the transient simulation
over a period of time [3]. The differential algebraic equations, given in (8.16), of the
system should be solved through numerical methods and the transient simulation
should be carried out for few minutes to completely observer the interaction of
generators, static loads, dynamic loads, tap changing transformer etc.
( , , , )
( , )
0 ( , , )
d q
d q
d q
x f x I V u
I h x V
g x I V
-
-
-
=
=
=

(8.16)
The transient simulation should be done for different fault scenarios and the
system behaviour should be observed. If the system voltages are restored to
acceptable values after fault clearing then the system is voltage stable if not the
system is voltage unstable. The simulations needs to be done for few minutes because
the time constant involved can be very small like generator exciter or very large like
induction motors or tap changing transformers. For voltage stability assessment load
modelling is important hence both static and dynamic loads should be modelled. The
reactive power compensating devices like series / shunt capacitor and static VAr
compensator should also be included in the system model.
8.3.1 Small-disturbance analysis
Small-disturbance (signal) analysis can also be used for voltage stability
analysis. The DAE given in equation (8.16) can be represented as
( , ( , ), , )
0 ( , ( , ), , )
x f x h x V V u
g x h x V V l
=
=
(8.17)
8.10
Where,  in (8.17) is a constant representing the loading of the system, as given in
(8.18)
 
 
0
0
1
1
D D
D D
P P
Q Q


 
 
(8.18)
0 , 0D DP Q are the real and reactive power loads at all the load buses for base case.
The idea is to increase the loading factor  in steps and at each step find the eigen
values of the linearized system given in (8.17). The linearized form of the system
given in (8.17) is given as
0
Vf f f f
x x u
x V u
Vg g g
x
x V
qq
qq
é ùDé ù¶ ¶ ¶ ¶
ê úê úD = D + + D
ê úê ú D¶ ¶ ¶ ¶ë û ë û
é ùDé ù¶ ¶ ¶
ê úê ú= D +
ê úê ú D¶ ¶ ¶ë û ë û

(8.19)
Here, 1 1 1
T T
nV V V V V n n        hence the linearized form shown in
(8.19). On further simplification of (8.19) the following expression can be derived
1
sysJ
sys
f f f g g g f
x x u
x V V x u
f
J x u
u
q q
-é ùé ù é ù é ù é ù é ù¶ ¶ ¶ ¶ ¶ ¶ ¶ê úê ú ê ú ê ú ê ú ê úD = - D + Dê úê ú ê ú ê ú ê ú ê ú¶ ¶ ¶ ¶ ¶ ¶ ¶ë û ë û ë û ë û ë ûê úë û
é ù¶
ê ú= D + D
ê ú¶ë û


(8.20)
The matrix sysJ is called as the system Jacobian and is different from the load
flow Jacobian. The eigen value of the system Jacobian sysJ for different loading
conditions, obtained by varying the loading factor  , are computed. If a one of the
eigen value becomes zero or a pair of complex conjugate eigen values are on the
imaginary axis for a particular loading factor  then the load corresponding to the
8.11
loading factor  is a critical load at which the system becomes voltage unstable. If a
complex conjugate pair of eigen values are on imaginary axis then that operating
point is called as Hopf-bifurcation point. If one of the eigen value is on the origin then
that operating point is called as saddle node point. The saddle node bifurcation point
represents the knee point. Hopf-bifurcation point occurs at a load which is less than
the load at which the saddle node bifurcation point occurs. Hence, due to the
dynamics involved the system can become voltage unstable even before the operating
point reaches the knee point.
8.12
8.13
References
1. IEEE, Special publication 90TH0358-2-PWR, Voltage stability of power
systems: concepts, analytical tools, and industry experience, 1990.
2. CIGE task force 38-02-10, Modelling of voltage collapse including dynamic
phenomena, 1993.
3. G. K. Morison, B. Gao, and P. Kundur, “Voltage stability evaluation using
static and dynamic approaches,” IEEE PES summer meeting, July 2-16, 1992,
Seattle, Washington.
4. N. Flatabo, R. Ognedal and T. Carlsen, “Voltage stability conditions in a
power transmission system calculated by sensitivity methods,” IEEE Trans.,
Vol. PWRS-5, No. 4, pp. 1286-1293, November.
5. 1990G. K. Morison, B. Gao, and P. Kundur, “Voltage stability evaluation
using modal analysis,” IEEE Trans., Vol. PWRS-7, No. 4, pp. 1529-1542,
November 1992.

Contenu connexe

Tendances

Classification Of Power System Stability
Classification Of Power System StabilityClassification Of Power System Stability
Classification Of Power System StabilityAravind Shaji
 
Power system stability
Power  system  stabilityPower  system  stability
Power system stabilityrohit kumar
 
Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)SHIMI S L
 
Voltage stability using Series FACTS devices
Voltage stability using Series FACTS devicesVoltage stability using Series FACTS devices
Voltage stability using Series FACTS devicesSAI SREE
 
Control of active power & reactive power
Control of active power & reactive powerControl of active power & reactive power
Control of active power & reactive powerPavithran Selvam
 
Stability Modeling Of Storage Devices In FACTS Applications
Stability Modeling Of Storage Devices In FACTS ApplicationsStability Modeling Of Storage Devices In FACTS Applications
Stability Modeling Of Storage Devices In FACTS Applicationspreeti naga
 
Transient enhancement technique
Transient enhancement techniqueTransient enhancement technique
Transient enhancement techniqueVipin Pandey
 
Study of various FACTS devices for Steady and Dynamic state stability of Powe...
Study of various FACTS devices for Steady and Dynamic state stability of Powe...Study of various FACTS devices for Steady and Dynamic state stability of Powe...
Study of various FACTS devices for Steady and Dynamic state stability of Powe...Palak Tulsyan
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptMamta Bagoria
 
Power system stability and control using facts devices
Power system stability and control using facts devicesPower system stability and control using facts devices
Power system stability and control using facts devicesAjit Singh Rajawat
 
Power System Analysis Unit - V
Power System Analysis Unit - VPower System Analysis Unit - V
Power System Analysis Unit - Varunatshare
 
transient stability analysis
transient stability analysistransient stability analysis
transient stability analysisKaransinh Parmar
 
Transient Stability Assessment and Enhancement in Power System
Transient Stability Assessment and Enhancement in Power  SystemTransient Stability Assessment and Enhancement in Power  System
Transient Stability Assessment and Enhancement in Power SystemIJMER
 
Transient stability analysis on a multi machine system in psat
Transient stability analysis on a multi machine system in psatTransient stability analysis on a multi machine system in psat
Transient stability analysis on a multi machine system in psateSAT Journals
 

Tendances (20)

Classification Of Power System Stability
Classification Of Power System StabilityClassification Of Power System Stability
Classification Of Power System Stability
 
Power system stability
Power  system  stabilityPower  system  stability
Power system stability
 
Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)
 
Power system stability
Power system stability Power system stability
Power system stability
 
Power System Stablity
Power System StablityPower System Stablity
Power System Stablity
 
Voltage stability using Series FACTS devices
Voltage stability using Series FACTS devicesVoltage stability using Series FACTS devices
Voltage stability using Series FACTS devices
 
Control of active power & reactive power
Control of active power & reactive powerControl of active power & reactive power
Control of active power & reactive power
 
Stability Modeling Of Storage Devices In FACTS Applications
Stability Modeling Of Storage Devices In FACTS ApplicationsStability Modeling Of Storage Devices In FACTS Applications
Stability Modeling Of Storage Devices In FACTS Applications
 
Transient enhancement technique
Transient enhancement techniqueTransient enhancement technique
Transient enhancement technique
 
SMALL SIGNAL STABILITY
SMALL SIGNAL STABILITYSMALL SIGNAL STABILITY
SMALL SIGNAL STABILITY
 
Study of various FACTS devices for Steady and Dynamic state stability of Powe...
Study of various FACTS devices for Steady and Dynamic state stability of Powe...Study of various FACTS devices for Steady and Dynamic state stability of Powe...
Study of various FACTS devices for Steady and Dynamic state stability of Powe...
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
 
Power system stability and control using facts devices
Power system stability and control using facts devicesPower system stability and control using facts devices
Power system stability and control using facts devices
 
Under voltage load shedding
Under voltage load sheddingUnder voltage load shedding
Under voltage load shedding
 
MajorProject2016
MajorProject2016MajorProject2016
MajorProject2016
 
PPT ON POWER SYSTEM STABILITY
PPT ON POWER SYSTEM STABILITYPPT ON POWER SYSTEM STABILITY
PPT ON POWER SYSTEM STABILITY
 
Power System Analysis Unit - V
Power System Analysis Unit - VPower System Analysis Unit - V
Power System Analysis Unit - V
 
transient stability analysis
transient stability analysistransient stability analysis
transient stability analysis
 
Transient Stability Assessment and Enhancement in Power System
Transient Stability Assessment and Enhancement in Power  SystemTransient Stability Assessment and Enhancement in Power  System
Transient Stability Assessment and Enhancement in Power System
 
Transient stability analysis on a multi machine system in psat
Transient stability analysis on a multi machine system in psatTransient stability analysis on a multi machine system in psat
Transient stability analysis on a multi machine system in psat
 

En vedette

93321970 ansys-modal-analysis
93321970 ansys-modal-analysis93321970 ansys-modal-analysis
93321970 ansys-modal-analysisSamuel Ogbodo
 
Power System Stability & Control
Power System Stability & ControlPower System Stability & Control
Power System Stability & ControlAzimah Aziz
 
Tutorial: Introduction to Transient Analysis using DIgSILENT PowerFactory.
Tutorial: Introduction to Transient Analysis using DIgSILENT PowerFactory.Tutorial: Introduction to Transient Analysis using DIgSILENT PowerFactory.
Tutorial: Introduction to Transient Analysis using DIgSILENT PowerFactory.Francisco Gonzalez-Longatt
 
Power system stability
Power system  stabilityPower system  stability
Power system stabilityDeepak John
 
Power System Stabilizer
Power System StabilizerPower System Stabilizer
Power System StabilizerSuman Sourabh
 
Small signal stability analysis
Small signal stability analysisSmall signal stability analysis
Small signal stability analysisbhupendra kumar
 

En vedette (6)

93321970 ansys-modal-analysis
93321970 ansys-modal-analysis93321970 ansys-modal-analysis
93321970 ansys-modal-analysis
 
Power System Stability & Control
Power System Stability & ControlPower System Stability & Control
Power System Stability & Control
 
Tutorial: Introduction to Transient Analysis using DIgSILENT PowerFactory.
Tutorial: Introduction to Transient Analysis using DIgSILENT PowerFactory.Tutorial: Introduction to Transient Analysis using DIgSILENT PowerFactory.
Tutorial: Introduction to Transient Analysis using DIgSILENT PowerFactory.
 
Power system stability
Power system  stabilityPower system  stability
Power system stability
 
Power System Stabilizer
Power System StabilizerPower System Stabilizer
Power System Stabilizer
 
Small signal stability analysis
Small signal stability analysisSmall signal stability analysis
Small signal stability analysis
 

Similaire à Chapter8

MY CONTINUATION RESEARCH 1
MY CONTINUATION RESEARCH 1MY CONTINUATION RESEARCH 1
MY CONTINUATION RESEARCH 1Binod Panthee
 
Lab manual psd v sem experiment no 5
Lab manual psd v sem experiment no 5Lab manual psd v sem experiment no 5
Lab manual psd v sem experiment no 5Sachin Airan
 
Phase angles as a proxy for voltage stability
Phase angles as a proxy for voltage stabilityPhase angles as a proxy for voltage stability
Phase angles as a proxy for voltage stabilityPower System Operation
 
An Optimal Power Flow (OPF) Method with Improved Voltage Stability Analysis
An Optimal Power Flow (OPF) Method withImproved Voltage Stability AnalysisAn Optimal Power Flow (OPF) Method withImproved Voltage Stability Analysis
An Optimal Power Flow (OPF) Method with Improved Voltage Stability AnalysisNiraj Solanki
 
Combined use of tap-changing transformer and static VAR compensator for enhan...
Combined use of tap-changing transformer and static VAR compensator for enhan...Combined use of tap-changing transformer and static VAR compensator for enhan...
Combined use of tap-changing transformer and static VAR compensator for enhan...ijsrd.com
 
Up/Down Converter Linear Model with Feed Forward and Feedback Stability Analysis
Up/Down Converter Linear Model with Feed Forward and Feedback Stability AnalysisUp/Down Converter Linear Model with Feed Forward and Feedback Stability Analysis
Up/Down Converter Linear Model with Feed Forward and Feedback Stability AnalysisCSCJournals
 
EE454_Power Flow Programming
EE454_Power Flow ProgrammingEE454_Power Flow Programming
EE454_Power Flow Programmingki hei chan
 
Fundamentals of power system
Fundamentals of power systemFundamentals of power system
Fundamentals of power systemBalaram Das
 
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Power System Operation
 
Power Flow & Voltage Stability Analysis using MATLAB
Power Flow & Voltage Stability Analysis using MATLAB Power Flow & Voltage Stability Analysis using MATLAB
Power Flow & Voltage Stability Analysis using MATLAB IRJET Journal
 
IRJET-Power Flow & Voltage Stability Analysis using MATLAB
IRJET-Power Flow & Voltage Stability Analysis using MATLAB IRJET-Power Flow & Voltage Stability Analysis using MATLAB
IRJET-Power Flow & Voltage Stability Analysis using MATLAB IRJET Journal
 
Ee6378 linear regulators
Ee6378 linear regulatorsEe6378 linear regulators
Ee6378 linear regulatorsssuser2038c9
 
Application of SVC on IEEE 6 Bus System for Optimization of Voltage Stability
Application of SVC on IEEE 6 Bus System for Optimization of Voltage StabilityApplication of SVC on IEEE 6 Bus System for Optimization of Voltage Stability
Application of SVC on IEEE 6 Bus System for Optimization of Voltage Stabilityijeei-iaes
 
Power Circuits and Transforers-Unit 5 Labvolt Student Manual
Power Circuits and Transforers-Unit 5 Labvolt Student ManualPower Circuits and Transforers-Unit 5 Labvolt Student Manual
Power Circuits and Transforers-Unit 5 Labvolt Student Manualphase3-120A
 
Ekeeda - First Year Enginering - Basic Electrical Engineering
Ekeeda - First Year Enginering - Basic Electrical EngineeringEkeeda - First Year Enginering - Basic Electrical Engineering
Ekeeda - First Year Enginering - Basic Electrical EngineeringEkeedaPvtLtd
 

Similaire à Chapter8 (20)

MY CONTINUATION RESEARCH 1
MY CONTINUATION RESEARCH 1MY CONTINUATION RESEARCH 1
MY CONTINUATION RESEARCH 1
 
Lab manual psd v sem experiment no 5
Lab manual psd v sem experiment no 5Lab manual psd v sem experiment no 5
Lab manual psd v sem experiment no 5
 
Phase angles as a proxy for voltage stability
Phase angles as a proxy for voltage stabilityPhase angles as a proxy for voltage stability
Phase angles as a proxy for voltage stability
 
An Optimal Power Flow (OPF) Method with Improved Voltage Stability Analysis
An Optimal Power Flow (OPF) Method withImproved Voltage Stability AnalysisAn Optimal Power Flow (OPF) Method withImproved Voltage Stability Analysis
An Optimal Power Flow (OPF) Method with Improved Voltage Stability Analysis
 
Combined use of tap-changing transformer and static VAR compensator for enhan...
Combined use of tap-changing transformer and static VAR compensator for enhan...Combined use of tap-changing transformer and static VAR compensator for enhan...
Combined use of tap-changing transformer and static VAR compensator for enhan...
 
Unit-1 Per Unit System.pptx
Unit-1  Per Unit System.pptxUnit-1  Per Unit System.pptx
Unit-1 Per Unit System.pptx
 
Up/Down Converter Linear Model with Feed Forward and Feedback Stability Analysis
Up/Down Converter Linear Model with Feed Forward and Feedback Stability AnalysisUp/Down Converter Linear Model with Feed Forward and Feedback Stability Analysis
Up/Down Converter Linear Model with Feed Forward and Feedback Stability Analysis
 
EE454_Power Flow Programming
EE454_Power Flow ProgrammingEE454_Power Flow Programming
EE454_Power Flow Programming
 
Fundamentals of power system
Fundamentals of power systemFundamentals of power system
Fundamentals of power system
 
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
 
Load flow study
Load flow studyLoad flow study
Load flow study
 
Power Flow & Voltage Stability Analysis using MATLAB
Power Flow & Voltage Stability Analysis using MATLAB Power Flow & Voltage Stability Analysis using MATLAB
Power Flow & Voltage Stability Analysis using MATLAB
 
IRJET-Power Flow & Voltage Stability Analysis using MATLAB
IRJET-Power Flow & Voltage Stability Analysis using MATLAB IRJET-Power Flow & Voltage Stability Analysis using MATLAB
IRJET-Power Flow & Voltage Stability Analysis using MATLAB
 
Ee6378 linear regulators
Ee6378 linear regulatorsEe6378 linear regulators
Ee6378 linear regulators
 
Multivibrators cct
Multivibrators cctMultivibrators cct
Multivibrators cct
 
Load flow study
Load flow studyLoad flow study
Load flow study
 
Application of SVC on IEEE 6 Bus System for Optimization of Voltage Stability
Application of SVC on IEEE 6 Bus System for Optimization of Voltage StabilityApplication of SVC on IEEE 6 Bus System for Optimization of Voltage Stability
Application of SVC on IEEE 6 Bus System for Optimization of Voltage Stability
 
Thyristor switched capacitor
Thyristor switched capacitorThyristor switched capacitor
Thyristor switched capacitor
 
Power Circuits and Transforers-Unit 5 Labvolt Student Manual
Power Circuits and Transforers-Unit 5 Labvolt Student ManualPower Circuits and Transforers-Unit 5 Labvolt Student Manual
Power Circuits and Transforers-Unit 5 Labvolt Student Manual
 
Ekeeda - First Year Enginering - Basic Electrical Engineering
Ekeeda - First Year Enginering - Basic Electrical EngineeringEkeeda - First Year Enginering - Basic Electrical Engineering
Ekeeda - First Year Enginering - Basic Electrical Engineering
 

Plus de DHEERAJ DHAKAR

Power System Modeling and Simulation lab manual
Power System Modeling and Simulation lab manualPower System Modeling and Simulation lab manual
Power System Modeling and Simulation lab manualDHEERAJ DHAKAR
 
A detailed review of technology of hybrid electric vehicle
A detailed review of technology of hybrid electric vehicleA detailed review of technology of hybrid electric vehicle
A detailed review of technology of hybrid electric vehicleDHEERAJ DHAKAR
 
Facts controllers for power flow control a brief review
Facts controllers for power flow control a brief reviewFacts controllers for power flow control a brief review
Facts controllers for power flow control a brief reviewDHEERAJ DHAKAR
 
Power factor correction using bridgeless boost topology
Power factor correction using bridgeless boost topologyPower factor correction using bridgeless boost topology
Power factor correction using bridgeless boost topologyDHEERAJ DHAKAR
 
A REVIEW PAPER ON A D-FACTS CONTROLLER: ENHANCED POWER FLOW CONTROLLER
A REVIEW PAPER ON A D-FACTS CONTROLLER: ENHANCED POWER FLOW CONTROLLERA REVIEW PAPER ON A D-FACTS CONTROLLER: ENHANCED POWER FLOW CONTROLLER
A REVIEW PAPER ON A D-FACTS CONTROLLER: ENHANCED POWER FLOW CONTROLLERDHEERAJ DHAKAR
 
Current affairs-june-2014
Current affairs-june-2014Current affairs-june-2014
Current affairs-june-2014DHEERAJ DHAKAR
 
Current affairs-july-2014
Current affairs-july-2014Current affairs-july-2014
Current affairs-july-2014DHEERAJ DHAKAR
 
Current affairs-december-2014
Current affairs-december-2014Current affairs-december-2014
Current affairs-december-2014DHEERAJ DHAKAR
 
Bank exam-study-material-2014
Bank exam-study-material-2014Bank exam-study-material-2014
Bank exam-study-material-2014DHEERAJ DHAKAR
 
Electrical machine lab
Electrical machine labElectrical machine lab
Electrical machine labDHEERAJ DHAKAR
 
Microprocessorlabmanual ee0310
Microprocessorlabmanual ee0310Microprocessorlabmanual ee0310
Microprocessorlabmanual ee0310DHEERAJ DHAKAR
 

Plus de DHEERAJ DHAKAR (17)

Power System Modeling and Simulation lab manual
Power System Modeling and Simulation lab manualPower System Modeling and Simulation lab manual
Power System Modeling and Simulation lab manual
 
A detailed review of technology of hybrid electric vehicle
A detailed review of technology of hybrid electric vehicleA detailed review of technology of hybrid electric vehicle
A detailed review of technology of hybrid electric vehicle
 
Facts controllers for power flow control a brief review
Facts controllers for power flow control a brief reviewFacts controllers for power flow control a brief review
Facts controllers for power flow control a brief review
 
Power factor correction using bridgeless boost topology
Power factor correction using bridgeless boost topologyPower factor correction using bridgeless boost topology
Power factor correction using bridgeless boost topology
 
Review ijaet
Review ijaetReview ijaet
Review ijaet
 
Psms lab manual
Psms lab manualPsms lab manual
Psms lab manual
 
A REVIEW PAPER ON A D-FACTS CONTROLLER: ENHANCED POWER FLOW CONTROLLER
A REVIEW PAPER ON A D-FACTS CONTROLLER: ENHANCED POWER FLOW CONTROLLERA REVIEW PAPER ON A D-FACTS CONTROLLER: ENHANCED POWER FLOW CONTROLLER
A REVIEW PAPER ON A D-FACTS CONTROLLER: ENHANCED POWER FLOW CONTROLLER
 
Control systems
Control systemsControl systems
Control systems
 
Chapter5
Chapter5Chapter5
Chapter5
 
Current affairs-june-2014
Current affairs-june-2014Current affairs-june-2014
Current affairs-june-2014
 
Current affairs-july-2014
Current affairs-july-2014Current affairs-july-2014
Current affairs-july-2014
 
Current affairs-december-2014
Current affairs-december-2014Current affairs-december-2014
Current affairs-december-2014
 
Ca questions
Ca questionsCa questions
Ca questions
 
Bank exam-study-material-2014
Bank exam-study-material-2014Bank exam-study-material-2014
Bank exam-study-material-2014
 
Electrical machine lab
Electrical machine labElectrical machine lab
Electrical machine lab
 
Microprocessorlabmanual ee0310
Microprocessorlabmanual ee0310Microprocessorlabmanual ee0310
Microprocessorlabmanual ee0310
 
Machine lab manual
Machine lab manualMachine lab manual
Machine lab manual
 

Dernier

UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 

Dernier (20)

UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 

Chapter8

  • 1. Chapter 8 VOLTAGE STABILITY The small signal and transient angle stability was discussed in Chapter 6 and 7. Another stability issue which is important, other than angle stability, is voltage stability. Voltage stability can be defined as the ability of the system to retain system voltages within acceptable limits when subjected to disturbance. If the disturbance is large then it is called as large-disturbance voltage stability and if the disturbance is small it is called as small-signal voltage stability [1]-[2]. Voltage stability can be a local phenomenon where only a particular bus or buses in a particular region have voltage stability issue and this may not affect the entire system. Voltage stability can be a global phenomenon where many of the system buses experience voltage stability problems which can also trigger angle stability problems and hence can affect the entire system. Some of the voltage stability problems can start as a local problem and escalate to global stability problem. Voltage stability of a system can be analysed either by static analysis or dynamic analysis. In static analysis the system is assumed to be in steady state and hence instead of taking the DAE of the system only algebraic equations are considered. This type of analysis is suitable for small-disturbances in the system. For large disturbances the DAE are solved and the system response over a certain period of time is observed. It is important that for voltage stability the loads should be properly modelled as each type of load will affect the system voltage stability in a different way. Similarly the tap changing transformers, shunt or series reactive power compensators, generator reactive power limits, line charging capacitance should be included in the system representation to get an accurate picture of voltage stability. 8.1 Basic Concept of Voltage Stability To understand the concept of voltage stability let there be a two bus system with one end being sending end and the other being receiving end as shown in Fig. 8.1. Let the voltage of sending end be SV and that of receiving end be RV . The transmission 8.1
  • 2. line is represented by a short line mode with impedance TZ T . If a load of impedance LZ L is connected at the receiving end. Fig. 8.1: Single line diagram of two bus system The magnitude of current in the transmission line is given as, taking the sending end voltage as reference,  2 2 0 T T LZ Z 2 cos S S L T L T L T L V V I Z Z Z Z             (8.1) The receiving end voltage magnitude is then defined as  2 2 T LZ Z 2 cos S L R T L T L V Z V Z Z      (8.2) The real and reactive power consumed by the load is given as     2 2 2 S L T L V Z Z Z cos 2 cos L L T L T L P Z Z       (8.3)     2 2 2 S L T L V Z Z Z sin 2 cos L L T L T L Q Z Z       (8.4) SV TZ RV LZ I 8.2
  • 3. Let the transmission line impedance be taken as 0.25TZ pu , neglecting resistance as usually the reactance to resistance ratio is quite high in a transmission network. Let the sending end voltage be 1 pu . The real and reactive power of the load can be increased by decreasing the load impedance LZ maintaining a constant power factor say 0.8. The receiving end voltage is plotted in Fig. 8.2 with varying real power consumed by the load, with the parameters mentioned above. This curve is called as P-V curve. Knee Point Fig. 8.2: P-V curve It can be observed from P-V curve that as the load increases from no load condition the receiving voltage starts dropping form initial no load voltage of 1 pu . The increase in the current I due to decrease in the load impedance LZ is more than the drop in the receiving end voltage magnitude and hence the real power consumed by the load will increase. The maximum real power, 1 RV pu , will be delivered to the load when L TZ Z . Once operating point reaches the maximum power point or critical point or knee point of the curve any further decrease in load impedance, to 8.3
  • 4. increase the load, will result in further drop in the receiving end voltage and simultaneously the real power consumed by the load will also decrease. This is because after knee point the drop in the voltage is more than the increase in the line current leading to a decrease in the real power consumed by the load. 8.1.1 Effect of load type on voltage stability Fig. 8.3: P-V curve with stable and unstable operating points Consider the P-V curve shown in Fig. 8.3. For a given real power consumed by the load there are two possible receiving end voltages. As can be seen from operating points A and B from Fig. 8.3, for a real power of 0.6 pu there are two receiving end voltages of 0.85 pu and 0.20 pu , approximately. If the load is a constant MVA load then the operating point A is stable where as the operating point B is unstable. In fact for a constant MVA load any operating point below the knee point is unstable. This phenomenon can be understood from the Fig. 8.3. Suppose due to some disturbance the operating point moves from point A to C. At the operating point C the real power is more than the real power at operating point A. Since, the load is constant MVA 8.4
  • 5. load the current will decrease and therefore the operating point move back from C to A. The operating point may not stop immediately at operating point A but may oscillate around it and will settle down with enough damping. Hence, the operating point A is a stable operating point. Now consider the operating point B. Again let the operating point move to point D due to disturbance. At operating point D the real power is less than that at operating point B. Since the load is a constant MVA load at operating point D the current increases, as compared to operating point B, which leads to a further voltage drop and further increase in the line current. This phenomenon continues till the voltage at the receiving end becomes zero and hence called as voltage collapse. Therefore, the operating point B is unstable operating point. It can be observed from P-V curve that the curve above knee point has negative that is the change in real power and voltage are in opposite direction, for a increase in power voltage decreases and for a decrease in power voltage increases. The curve below the knee point has positive and at the knee point is zero. /RdV dP /R LdV dP L L/RdV dP Fig. 8.4: P-V curve for different power factor loads 8.5
  • 6. Figure 8.4 show the P-V curves for loads with different power factors. It can be observed from the figure that as the load power factor moves from lagging to leading the knee point is shifted towards higher real power and higher voltage. This shows that the voltage stability improves as the power factor moves from lagging to leading loads. Fig. 8.5: Q-V curve for different load real powers Just as the load real power was plotted with respect to the receiving end voltage for varying load impedances, the load reactive power variation with respect to the receiving end voltage, with load real power being constant, can also be plotted. Figure 8.5 shows the variation of receiving end voltage with variation in load reactive power for three different real power loads. Again the locus of knee point is marked. On the curve left of the locus of the knee point the reactive power and the voltage move in opposite directions that is is negative and this region is unstable. The curve on the right of the locus of the knee point the reactive power and the voltage move in the same direction and hence is positive and this region is stable. In the unstable region even if reactive power compensation is done through shunt capacitance at the receiving end bus, the voltage of the receiving end bus will / RdQ dV / RdQ dV 8.6
  • 7. not improve. One way of finding the voltage stability is to check the sensitivity of each bus voltage with respect to the reactive power injected at that bus and if the sensitivity is positive then it means the operating point is stable and is on the right side of the locus of the knee points in Fig. 8.4 and if it is negative then it is on the left side. This stable region and unstable region are only applicable to constant MVA loads. In case of constant impedance and constant current loads the loads interact with the system and settle at a new operating point as there is no requirement of constant MVA. 8.2 Static Analysis In static analysis [3] of voltage stability the snapshots of the entire system at different instants is considered and at each instant the system is assumed to be in steady state that the rates of changes of the dynamic variables are zero. Hence, instead of considering all the differential algebraic equations only algebraic power balance equations are considering assuming that the system is in steady state. At each instant whether the system is voltage stable or not and also how far the system is from instability can be assessed. There are two methods for assessing whether system is voltage stable or not. They are sensitivity analysis [4] and modal analysis [5]. 8.2.1 Sensitivity analysis The power balance equations are taken assuming that the system is in steady state. For, , assuming bus number 1 is a slack bus, the real power balance equation is given as 2,......,i  n   1 ( ) cos 0 n Gi Di i i j ij i j ij j P P V VV Y         (8.5) The reactive power balance equations are taken at the load buses, for 1, 2,......,g gi n n n   8.7
  • 8. (8.6) 1 ( ) sin 0 n Di i i j ij i j ij j Q V VV Y                  The linearized form of equations (8.5) and (8.6) is given as 2 2 1 1g g n nP PV n nQ QV n n P P J J Q VJ J Q V                                               or   P J Q V              (8.7) The matrix is the Jacobian matrix used in Newton-Raphson load flow analysis. For constant real power is zero hence from equation (8.7) J P   1 P PVJ J     V   (8.8) Substituting (8.8) in (8.7) an simplifying leads to (8.9)  1 QV P PV QQ J J J J V        Let,   1 R QV P PV QJ J J J J        , then 1 RV J Q    (8.10) The diagonal elements of the matrix 1 RJ  represents the sensitivity of the voltage with respect to the reactive power injected at that bus. This is nothing but the slope of 8.8
  • 9. Q-V curve given in Fig. 8.4. Hence, if the V-Q sensitivity of an ith bus is positive then the system is voltage stable and if it is negative then the system is voltage unstable. A small positive value of sensitivity indicates that the system is more voltage stable and if the sensitivity is small with negative value then the system is highly voltage unstable. 8.2.2 Modal Analysis Voltage stability can also be estimated by the eigen values and eigen vectors of the matrix . The matrix can be expressed in terms of right and left eigen vector matrices as 1 RJ  ,  RJ RJ   (8.11) 1 RJ     1 (8.12) Where, is a diagonal matrix with eigen values along its diagonal. Substituting (8.12) in (8.10) lead to, noting that  I  1 1 RV J Q Q        (8.13) 1 V     Q Q (8.14) Let, v V and , then or  q   1 v q   1 i i v iq   (8.15) Where, is the ith bus modal voltage and is the modal reactive power. If the eigen value is positive then the system is voltage stable. The larger the eigen value with positive sign the better the stability and if the eigen value has very small positive value then it is very close to iv iq 0i  , that is the critical point or knee point, and hence 8.9
  • 10. very close to instability. If the eigen value is negative then the system is voltage unstable. 8.3 Dynamic Analysis The voltage stability of a system can also be assessed by the transient simulation over a period of time [3]. The differential algebraic equations, given in (8.16), of the system should be solved through numerical methods and the transient simulation should be carried out for few minutes to completely observer the interaction of generators, static loads, dynamic loads, tap changing transformer etc. ( , , , ) ( , ) 0 ( , , ) d q d q d q x f x I V u I h x V g x I V - - - = = =  (8.16) The transient simulation should be done for different fault scenarios and the system behaviour should be observed. If the system voltages are restored to acceptable values after fault clearing then the system is voltage stable if not the system is voltage unstable. The simulations needs to be done for few minutes because the time constant involved can be very small like generator exciter or very large like induction motors or tap changing transformers. For voltage stability assessment load modelling is important hence both static and dynamic loads should be modelled. The reactive power compensating devices like series / shunt capacitor and static VAr compensator should also be included in the system model. 8.3.1 Small-disturbance analysis Small-disturbance (signal) analysis can also be used for voltage stability analysis. The DAE given in equation (8.16) can be represented as ( , ( , ), , ) 0 ( , ( , ), , ) x f x h x V V u g x h x V V l = = (8.17) 8.10
  • 11. Where,  in (8.17) is a constant representing the loading of the system, as given in (8.18)     0 0 1 1 D D D D P P Q Q       (8.18) 0 , 0D DP Q are the real and reactive power loads at all the load buses for base case. The idea is to increase the loading factor  in steps and at each step find the eigen values of the linearized system given in (8.17). The linearized form of the system given in (8.17) is given as 0 Vf f f f x x u x V u Vg g g x x V qq qq é ùDé ù¶ ¶ ¶ ¶ ê úê úD = D + + D ê úê ú D¶ ¶ ¶ ¶ë û ë û é ùDé ù¶ ¶ ¶ ê úê ú= D + ê úê ú D¶ ¶ ¶ë û ë û  (8.19) Here, 1 1 1 T T nV V V V V n n        hence the linearized form shown in (8.19). On further simplification of (8.19) the following expression can be derived 1 sysJ sys f f f g g g f x x u x V V x u f J x u u q q -é ùé ù é ù é ù é ù é ù¶ ¶ ¶ ¶ ¶ ¶ ¶ê úê ú ê ú ê ú ê ú ê úD = - D + Dê úê ú ê ú ê ú ê ú ê ú¶ ¶ ¶ ¶ ¶ ¶ ¶ë û ë û ë û ë û ë ûê úë û é ù¶ ê ú= D + D ê ú¶ë û   (8.20) The matrix sysJ is called as the system Jacobian and is different from the load flow Jacobian. The eigen value of the system Jacobian sysJ for different loading conditions, obtained by varying the loading factor  , are computed. If a one of the eigen value becomes zero or a pair of complex conjugate eigen values are on the imaginary axis for a particular loading factor  then the load corresponding to the 8.11
  • 12. loading factor  is a critical load at which the system becomes voltage unstable. If a complex conjugate pair of eigen values are on imaginary axis then that operating point is called as Hopf-bifurcation point. If one of the eigen value is on the origin then that operating point is called as saddle node point. The saddle node bifurcation point represents the knee point. Hopf-bifurcation point occurs at a load which is less than the load at which the saddle node bifurcation point occurs. Hence, due to the dynamics involved the system can become voltage unstable even before the operating point reaches the knee point. 8.12
  • 13. 8.13 References 1. IEEE, Special publication 90TH0358-2-PWR, Voltage stability of power systems: concepts, analytical tools, and industry experience, 1990. 2. CIGE task force 38-02-10, Modelling of voltage collapse including dynamic phenomena, 1993. 3. G. K. Morison, B. Gao, and P. Kundur, “Voltage stability evaluation using static and dynamic approaches,” IEEE PES summer meeting, July 2-16, 1992, Seattle, Washington. 4. N. Flatabo, R. Ognedal and T. Carlsen, “Voltage stability conditions in a power transmission system calculated by sensitivity methods,” IEEE Trans., Vol. PWRS-5, No. 4, pp. 1286-1293, November. 5. 1990G. K. Morison, B. Gao, and P. Kundur, “Voltage stability evaluation using modal analysis,” IEEE Trans., Vol. PWRS-7, No. 4, pp. 1529-1542, November 1992.