Why are Open-Ground Storey Buildings Vulnerable in Earthquakes?
Earthquake Tip 21
Learning
Earthquake Design
and
Construction
Basic Features
Reinforced concrete (RC) frame buildings are
becoming increasingly common in urban India. Many
such buildings constructed in recent times have a
special feature – the ground storey is left open for the
purpose of parking (Figure 1), i.e., columns in the
ground storey do not have any partition walls (of
either masonry or RC) between them. Such buildings
are often called open ground storey buildings or buildings
on stilts.
An open ground storey building, having only
columns in the ground storey and both partition walls
and columns in the upper storeys, have two distinct
characteristics, namely:
(a) It is relatively flexible in the ground storey, i.e., the
relative horizontal displacement it undergoes in the
ground storey is much larger than what each of the
storeys above it does. This flexible ground storey is
also called soft storey.
(b) It is relatively weak in ground storey, i.e., the total
horizontal earthquake force it can carry in the
ground storey is significantly smaller than what
each of the storeys above it can carry. Thus, the
open ground storey may also be a weak storey.
Often, open ground storey buildings are called soft
storey buildings, even though their ground storey may
be soft and weak. Generally, the soft or weak storey
usually exists at the ground storey level, but it could
be at any other storey level too.
Earthquake Behaviour
Open ground storey buildings have consistently
shown poor performance during past earthquakes
across the world (for example during 1999 Turkey, 1999
Taiwan and 2003 Algeria earthquakes); a significant
number of them have collapsed. A large number of
buildings with open ground storey have been built in
India in recent years. For instance, the city of
Ahmedabad alone has about 25,000 five-storey
buildings and about 1,500 eleven-storey buildings;
majority of them have open ground storeys. Further, a
huge number of similarly designed and constructed
buildings exist in the various towns and cities situated
in moderate to severe seismic zones (namely III, IV
and V) of the country. The collapse of more than a
hundred RC frame buildings with open ground
storeys at Ahmedabad (~225km away from epicenter)
during the 2001 Bhuj earthquake has emphasised that
such buildings are extremely vulnerable under
earthquake shaking.
The presence of walls in upper storeys makes
them much stiffer than the open ground storey. Thus,
the upper storeys move almost together as a single
block, and most of the horizontal displacement of the
building occurs in the soft ground storey itself. In
common language, this type of buildings can be
explained as a building on chopsticks. Thus, such
buildings swing back-and-forth like inverted pendulums
during earthquake shaking (Figure 2a), and the
columns in the open ground storey are severely
stressed (Figure 2b). If the columns are weak (do not
have the required strength to resist these high stresses)
or if they do not have adequate ductility (See IIT-
BMTPC Earthquake Tip 9), they may be severely
damaged (Figure 3a) which may even lead to collapse
of the building (Figure 3b).
Figure 2: Upper storeys of open ground storey
buildings move together as a single block –
such buildings are like inverted pendulums.
Stiff upper storeys:
Small displacement between
adjacent floors
Soft ground storey:
Large displacement between
foundation and first floor
Figure 1: Ground storeys of reinforced concrete
buildings are left open to facilitate parking –
this is common in urban areas in India.
Ground storey columns severely stressed(b)
(a)
Inverted
Pendulum
Earthquake
oscillations
IITK-BMTPC Earthquake Tip 21
Why are Open-Ground Storey Buildings Vulnerable in Earthquakes? page 2
The Problem
Open ground storey buildings are inherently poor
systems with sudden drop in stiffness and strength in
the ground storey. In the current practice, stiff masonry
walls (Figure 4a) are neglected and only bare frames are
considered in design calculations (Figure 4b). Thus,
the inverted pendulum effect is not captured in design.
Improved design strategies
After the collapses of RC buildings in 2001 Bhuj
earthquake, the Indian Seismic Code IS:1893 (Part 1) -
2002 has included special design provisions related to
soft storey buildings. Firstly, it specifies when a
building should be considered as a soft and a weak
storey building. Secondly, it specifies higher design
forces for the soft storey as compared to the rest of the
structure. The Code suggests that the forces in the
columns, beams and shear walls (if any) under the
action of seismic loads specified in the code, may be
obtained by considering the bare frame building
(without any infills) (Figure 4b). However, beams and
columns in the open ground storey are required to be
designed for 2.5 times the forces obtained from this
bare frame analysis.
For all new RC frame buildings, the best option is to
avoid such sudden and large decrease in stiffness
and/or strength in any storey; it would be ideal to
build walls (either masonry or RC walls) in the ground
storey also (Figure 5). Designers can avoid dangerous
effects of flexible and weak ground storeys by
ensuring that too many walls are not discontinued in
the ground storey, i.e., the drop in stiffness and
strength in the ground storey level is not abrupt due to
the absence of infill walls.
The existing open ground storey buildings need to be
strengthened suitably so as to prevent them from
collapsing during strong earthquake shaking. The
owners should seek the services of qualified structural
engineers who are able to suggest appropriate
solutions to increase seismic safety of these buildings.
Related - Earthquake Tip
Tip 6: How Architectural Features Affect Buildings During
Earthquakes?
Tip17: What are the Earthquake Effects on Reinforced Concrete
Buildings?
Resource Material
IS 1893(Part 1) (2002), Indian Standard Code of Practice for Criteria for
Design of Earthquake Resistant Structures, Bureau of Indian
Standards, New Delhi.
Next Upcoming Tip
Why are short columns more damaged during earthquakes?
Authored by:
C.V.R.Murty
Indian Institute of Technology Kanpur
Kanpur, India
Sponsored by:
Building Materials and Technology Promotion
Council, New Delhi, India
This release is a property of IIT Kanpur and BMTPC New
Delhi. It may be reproduced without changing its contents
and with due acknowledgement. Suggestions/comments
may be sent to: eqtips@iitk.ac.in. Visit www.nicee.org or
www.bmtpc.org, to see previous IITK-BMTPC Earthquake Tips.
December 2003
Figure 3: Consequences of open ground storeys
in RC frame buildings – severe damage to
ground storey columns and building collapses.
(a) 1971 San Fernando Earthquake
Photo Courtesy: The EERI Annotated Slide Set CD, Earthquake
Engineering Research Institute, Oakland (CA), USA, 1998.
(a) Actual building Building being assumed
in current design practice
Figure 4: Open ground storey building –
assumptions made in current design practice
are not consistent with the actual structure.
Infill walls not
considered in
upper storeys
(b)
Figure 5: Avoiding open ground storey problem –
continuity of walls in ground storey is preferred.
Direct flow of forces
through walls
(b) 2001 Bhuj Earthquake

Contenu connexe

Tendances

Earthquake resistant building
Earthquake resistant buildingEarthquake resistant building
Earthquake resistant buildingPrashant Borge
 
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube Structure
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube StructureIRJET- Comparative Study of Tube in Tube Structure and Frame Tube Structure
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube StructureIRJET Journal
 
Earthquake Resistant Building
Earthquake Resistant Building  Earthquake Resistant Building
Earthquake Resistant Building akhil reddy
 
Earthquake Resistance Structures
Earthquake Resistance  StructuresEarthquake Resistance  Structures
Earthquake Resistance Structuresakhiarane
 
Earthquake building designs final
Earthquake building designs finalEarthquake building designs final
Earthquake building designs finalhamza3195
 
Earthquake Resistant Building Construction
Earthquake Resistant Building ConstructionEarthquake Resistant Building Construction
Earthquake Resistant Building ConstructionRohan Narvekar
 
Structure Reinforced Concrete
Structure Reinforced ConcreteStructure Reinforced Concrete
Structure Reinforced ConcreteNik M Farid
 
Seismic Retrofitting Techniques
Seismic Retrofitting TechniquesSeismic Retrofitting Techniques
Seismic Retrofitting TechniquesAritra Banerjee
 
Earthquake and building resistant
Earthquake and building resistantEarthquake and building resistant
Earthquake and building resistantLydia Lyven
 
Seismic analysis of multi storey reinforced concrete buildings frame”
Seismic analysis of multi storey reinforced concrete buildings frame”Seismic analysis of multi storey reinforced concrete buildings frame”
Seismic analysis of multi storey reinforced concrete buildings frame”ankialok
 
DESIGN AND ANALYSIS OF EARTH-QUAKE RESISTANT FOR MULTI-STORIED BUILDING ON A ...
DESIGN AND ANALYSIS OF EARTH-QUAKE RESISTANT FOR MULTI-STORIED BUILDING ON A ...DESIGN AND ANALYSIS OF EARTH-QUAKE RESISTANT FOR MULTI-STORIED BUILDING ON A ...
DESIGN AND ANALYSIS OF EARTH-QUAKE RESISTANT FOR MULTI-STORIED BUILDING ON A ...Ijripublishers Ijri
 
Seismic design philosophy
Seismic design philosophySeismic design philosophy
Seismic design philosophySwatiPandey131
 
EarthQuake Reistant Building
EarthQuake Reistant BuildingEarthQuake Reistant Building
EarthQuake Reistant BuildingHemant Srivastava
 
Aij standard for structural design of reinforced concrete boxed shaped wall s...
Aij standard for structural design of reinforced concrete boxed shaped wall s...Aij standard for structural design of reinforced concrete boxed shaped wall s...
Aij standard for structural design of reinforced concrete boxed shaped wall s...Putika Ashfar Khoiri
 
12 fundamentals for_seismic_design_of_rcc_buildings_by_prof_arya
12 fundamentals for_seismic_design_of_rcc_buildings_by_prof_arya12 fundamentals for_seismic_design_of_rcc_buildings_by_prof_arya
12 fundamentals for_seismic_design_of_rcc_buildings_by_prof_aryaAbdul Khader Shahadaf TH
 

Tendances (20)

Earthquake resistant building
Earthquake resistant buildingEarthquake resistant building
Earthquake resistant building
 
14
1414
14
 
11
1111
11
 
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube Structure
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube StructureIRJET- Comparative Study of Tube in Tube Structure and Frame Tube Structure
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube Structure
 
Earthquake Resistant Building
Earthquake Resistant Building  Earthquake Resistant Building
Earthquake Resistant Building
 
Earthquake Resistance Structures
Earthquake Resistance  StructuresEarthquake Resistance  Structures
Earthquake Resistance Structures
 
Earthquake building designs final
Earthquake building designs finalEarthquake building designs final
Earthquake building designs final
 
Earthquake Resistant Building Construction
Earthquake Resistant Building ConstructionEarthquake Resistant Building Construction
Earthquake Resistant Building Construction
 
Structure Reinforced Concrete
Structure Reinforced ConcreteStructure Reinforced Concrete
Structure Reinforced Concrete
 
Seismic Retrofitting Techniques
Seismic Retrofitting TechniquesSeismic Retrofitting Techniques
Seismic Retrofitting Techniques
 
Earthquake and building resistant
Earthquake and building resistantEarthquake and building resistant
Earthquake and building resistant
 
Earthquake
EarthquakeEarthquake
Earthquake
 
Synopsis of project
Synopsis of projectSynopsis of project
Synopsis of project
 
Seismic analysis of multi storey reinforced concrete buildings frame”
Seismic analysis of multi storey reinforced concrete buildings frame”Seismic analysis of multi storey reinforced concrete buildings frame”
Seismic analysis of multi storey reinforced concrete buildings frame”
 
DESIGN AND ANALYSIS OF EARTH-QUAKE RESISTANT FOR MULTI-STORIED BUILDING ON A ...
DESIGN AND ANALYSIS OF EARTH-QUAKE RESISTANT FOR MULTI-STORIED BUILDING ON A ...DESIGN AND ANALYSIS OF EARTH-QUAKE RESISTANT FOR MULTI-STORIED BUILDING ON A ...
DESIGN AND ANALYSIS OF EARTH-QUAKE RESISTANT FOR MULTI-STORIED BUILDING ON A ...
 
Seismic design philosophy
Seismic design philosophySeismic design philosophy
Seismic design philosophy
 
EarthQuake Reistant Building
EarthQuake Reistant BuildingEarthQuake Reistant Building
EarthQuake Reistant Building
 
8
88
8
 
Aij standard for structural design of reinforced concrete boxed shaped wall s...
Aij standard for structural design of reinforced concrete boxed shaped wall s...Aij standard for structural design of reinforced concrete boxed shaped wall s...
Aij standard for structural design of reinforced concrete boxed shaped wall s...
 
12 fundamentals for_seismic_design_of_rcc_buildings_by_prof_arya
12 fundamentals for_seismic_design_of_rcc_buildings_by_prof_arya12 fundamentals for_seismic_design_of_rcc_buildings_by_prof_arya
12 fundamentals for_seismic_design_of_rcc_buildings_by_prof_arya
 

Similaire à 21

ijamtes Md Asif Akbari 9521930692
ijamtes Md Asif Akbari 9521930692ijamtes Md Asif Akbari 9521930692
ijamtes Md Asif Akbari 9521930692MD ASIF AKBARI
 
12 fundamentals for_seismic_design_of_rcc_buildings_by_prof_arya
12 fundamentals for_seismic_design_of_rcc_buildings_by_prof_arya12 fundamentals for_seismic_design_of_rcc_buildings_by_prof_arya
12 fundamentals for_seismic_design_of_rcc_buildings_by_prof_aryaimaduddin91
 
Behavior of rc structure under earthquake loading
Behavior of rc structure under earthquake loadingBehavior of rc structure under earthquake loading
Behavior of rc structure under earthquake loadingBinay Shrestha
 
IRJET- Performance of Framed Building with Soft Storey at Different Levels
IRJET- Performance of Framed Building with Soft Storey at Different LevelsIRJET- Performance of Framed Building with Soft Storey at Different Levels
IRJET- Performance of Framed Building with Soft Storey at Different LevelsIRJET Journal
 
ANALYSIS OF SOFT STOREY FOR MULTI STORYED BUILDING IN ZONE-4
ANALYSIS OF SOFT STOREY FOR MULTI STORYED BUILDING IN ZONE-4ANALYSIS OF SOFT STOREY FOR MULTI STORYED BUILDING IN ZONE-4
ANALYSIS OF SOFT STOREY FOR MULTI STORYED BUILDING IN ZONE-4Ijripublishers Ijri
 
Seismic Drift Control in soft storied RCC buildings
Seismic Drift Control in soft storied RCC buildingsSeismic Drift Control in soft storied RCC buildings
Seismic Drift Control in soft storied RCC buildingsIJERA Editor
 
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...IRJET Journal
 
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...IRJET Journal
 
Comparative Seismic Analysis of G+20 RC Framed Structure Building for Maximum...
Comparative Seismic Analysis of G+20 RC Framed Structure Building for Maximum...Comparative Seismic Analysis of G+20 RC Framed Structure Building for Maximum...
Comparative Seismic Analysis of G+20 RC Framed Structure Building for Maximum...IRJET Journal
 
The seismic performance of the frame shear wall tall building with and withou...
The seismic performance of the frame shear wall tall building with and withou...The seismic performance of the frame shear wall tall building with and withou...
The seismic performance of the frame shear wall tall building with and withou...eSAT Journals
 
Seismic Drift Consideration in soft storied RCC buildings: A Critical Review
Seismic Drift Consideration in soft storied RCC buildings: A Critical ReviewSeismic Drift Consideration in soft storied RCC buildings: A Critical Review
Seismic Drift Consideration in soft storied RCC buildings: A Critical ReviewIJERD Editor
 
COMPARATIVE STUDY ON SEISMIC ANALYSIS OF CONVENTIONAL SLAB AND FLAT SLAB STRU...
COMPARATIVE STUDY ON SEISMIC ANALYSIS OF CONVENTIONAL SLAB AND FLAT SLAB STRU...COMPARATIVE STUDY ON SEISMIC ANALYSIS OF CONVENTIONAL SLAB AND FLAT SLAB STRU...
COMPARATIVE STUDY ON SEISMIC ANALYSIS OF CONVENTIONAL SLAB AND FLAT SLAB STRU...IRJET Journal
 
IRJET- Numerical Study on Behaviour of Non-Tower Building Attached with Tower
IRJET- Numerical Study on Behaviour of Non-Tower Building Attached with TowerIRJET- Numerical Study on Behaviour of Non-Tower Building Attached with Tower
IRJET- Numerical Study on Behaviour of Non-Tower Building Attached with TowerIRJET Journal
 
IRJET- Performance of Multi-Story RCC Structure with Floating Column
IRJET-  	  Performance of Multi-Story RCC Structure with Floating ColumnIRJET-  	  Performance of Multi-Story RCC Structure with Floating Column
IRJET- Performance of Multi-Story RCC Structure with Floating ColumnIRJET Journal
 

Similaire à 21 (20)

ijamtes Md Asif Akbari 9521930692
ijamtes Md Asif Akbari 9521930692ijamtes Md Asif Akbari 9521930692
ijamtes Md Asif Akbari 9521930692
 
Shear wall
Shear wallShear wall
Shear wall
 
12 fundamentals for_seismic_design_of_rcc_buildings_by_prof_arya
12 fundamentals for_seismic_design_of_rcc_buildings_by_prof_arya12 fundamentals for_seismic_design_of_rcc_buildings_by_prof_arya
12 fundamentals for_seismic_design_of_rcc_buildings_by_prof_arya
 
Behavior of rc structure under earthquake loading
Behavior of rc structure under earthquake loadingBehavior of rc structure under earthquake loading
Behavior of rc structure under earthquake loading
 
IRJET- Performance of Framed Building with Soft Storey at Different Levels
IRJET- Performance of Framed Building with Soft Storey at Different LevelsIRJET- Performance of Framed Building with Soft Storey at Different Levels
IRJET- Performance of Framed Building with Soft Storey at Different Levels
 
6
66
6
 
ANALYSIS OF SOFT STOREY FOR MULTI STORYED BUILDING IN ZONE-4
ANALYSIS OF SOFT STOREY FOR MULTI STORYED BUILDING IN ZONE-4ANALYSIS OF SOFT STOREY FOR MULTI STORYED BUILDING IN ZONE-4
ANALYSIS OF SOFT STOREY FOR MULTI STORYED BUILDING IN ZONE-4
 
Seismic Drift Control in soft storied RCC buildings
Seismic Drift Control in soft storied RCC buildingsSeismic Drift Control in soft storied RCC buildings
Seismic Drift Control in soft storied RCC buildings
 
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...
 
Dg33646652
Dg33646652Dg33646652
Dg33646652
 
Dg33646652
Dg33646652Dg33646652
Dg33646652
 
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...
 
Comparative Seismic Analysis of G+20 RC Framed Structure Building for Maximum...
Comparative Seismic Analysis of G+20 RC Framed Structure Building for Maximum...Comparative Seismic Analysis of G+20 RC Framed Structure Building for Maximum...
Comparative Seismic Analysis of G+20 RC Framed Structure Building for Maximum...
 
The seismic performance of the frame shear wall tall building with and withou...
The seismic performance of the frame shear wall tall building with and withou...The seismic performance of the frame shear wall tall building with and withou...
The seismic performance of the frame shear wall tall building with and withou...
 
Seismic Drift Consideration in soft storied RCC buildings: A Critical Review
Seismic Drift Consideration in soft storied RCC buildings: A Critical ReviewSeismic Drift Consideration in soft storied RCC buildings: A Critical Review
Seismic Drift Consideration in soft storied RCC buildings: A Critical Review
 
COMPARATIVE STUDY ON SEISMIC ANALYSIS OF CONVENTIONAL SLAB AND FLAT SLAB STRU...
COMPARATIVE STUDY ON SEISMIC ANALYSIS OF CONVENTIONAL SLAB AND FLAT SLAB STRU...COMPARATIVE STUDY ON SEISMIC ANALYSIS OF CONVENTIONAL SLAB AND FLAT SLAB STRU...
COMPARATIVE STUDY ON SEISMIC ANALYSIS OF CONVENTIONAL SLAB AND FLAT SLAB STRU...
 
IRJET- Numerical Study on Behaviour of Non-Tower Building Attached with Tower
IRJET- Numerical Study on Behaviour of Non-Tower Building Attached with TowerIRJET- Numerical Study on Behaviour of Non-Tower Building Attached with Tower
IRJET- Numerical Study on Behaviour of Non-Tower Building Attached with Tower
 
IRJET- Performance of Multi-Story RCC Structure with Floating Column
IRJET-  	  Performance of Multi-Story RCC Structure with Floating ColumnIRJET-  	  Performance of Multi-Story RCC Structure with Floating Column
IRJET- Performance of Multi-Story RCC Structure with Floating Column
 
B04810713
B04810713B04810713
B04810713
 
Bw32461468
Bw32461468Bw32461468
Bw32461468
 

Plus de Someshwar Sriramoju (12)

20
2020
20
 
19
1919
19
 
18
1818
18
 
17
1717
17
 
16
1616
16
 
10
1010
10
 
7
77
7
 
5
55
5
 
4
44
4
 
3
33
3
 
2
22
2
 
1
11
1
 

21

  • 1. Why are Open-Ground Storey Buildings Vulnerable in Earthquakes? Earthquake Tip 21 Learning Earthquake Design and Construction Basic Features Reinforced concrete (RC) frame buildings are becoming increasingly common in urban India. Many such buildings constructed in recent times have a special feature – the ground storey is left open for the purpose of parking (Figure 1), i.e., columns in the ground storey do not have any partition walls (of either masonry or RC) between them. Such buildings are often called open ground storey buildings or buildings on stilts. An open ground storey building, having only columns in the ground storey and both partition walls and columns in the upper storeys, have two distinct characteristics, namely: (a) It is relatively flexible in the ground storey, i.e., the relative horizontal displacement it undergoes in the ground storey is much larger than what each of the storeys above it does. This flexible ground storey is also called soft storey. (b) It is relatively weak in ground storey, i.e., the total horizontal earthquake force it can carry in the ground storey is significantly smaller than what each of the storeys above it can carry. Thus, the open ground storey may also be a weak storey. Often, open ground storey buildings are called soft storey buildings, even though their ground storey may be soft and weak. Generally, the soft or weak storey usually exists at the ground storey level, but it could be at any other storey level too. Earthquake Behaviour Open ground storey buildings have consistently shown poor performance during past earthquakes across the world (for example during 1999 Turkey, 1999 Taiwan and 2003 Algeria earthquakes); a significant number of them have collapsed. A large number of buildings with open ground storey have been built in India in recent years. For instance, the city of Ahmedabad alone has about 25,000 five-storey buildings and about 1,500 eleven-storey buildings; majority of them have open ground storeys. Further, a huge number of similarly designed and constructed buildings exist in the various towns and cities situated in moderate to severe seismic zones (namely III, IV and V) of the country. The collapse of more than a hundred RC frame buildings with open ground storeys at Ahmedabad (~225km away from epicenter) during the 2001 Bhuj earthquake has emphasised that such buildings are extremely vulnerable under earthquake shaking. The presence of walls in upper storeys makes them much stiffer than the open ground storey. Thus, the upper storeys move almost together as a single block, and most of the horizontal displacement of the building occurs in the soft ground storey itself. In common language, this type of buildings can be explained as a building on chopsticks. Thus, such buildings swing back-and-forth like inverted pendulums during earthquake shaking (Figure 2a), and the columns in the open ground storey are severely stressed (Figure 2b). If the columns are weak (do not have the required strength to resist these high stresses) or if they do not have adequate ductility (See IIT- BMTPC Earthquake Tip 9), they may be severely damaged (Figure 3a) which may even lead to collapse of the building (Figure 3b). Figure 2: Upper storeys of open ground storey buildings move together as a single block – such buildings are like inverted pendulums. Stiff upper storeys: Small displacement between adjacent floors Soft ground storey: Large displacement between foundation and first floor Figure 1: Ground storeys of reinforced concrete buildings are left open to facilitate parking – this is common in urban areas in India. Ground storey columns severely stressed(b) (a) Inverted Pendulum Earthquake oscillations
  • 2. IITK-BMTPC Earthquake Tip 21 Why are Open-Ground Storey Buildings Vulnerable in Earthquakes? page 2 The Problem Open ground storey buildings are inherently poor systems with sudden drop in stiffness and strength in the ground storey. In the current practice, stiff masonry walls (Figure 4a) are neglected and only bare frames are considered in design calculations (Figure 4b). Thus, the inverted pendulum effect is not captured in design. Improved design strategies After the collapses of RC buildings in 2001 Bhuj earthquake, the Indian Seismic Code IS:1893 (Part 1) - 2002 has included special design provisions related to soft storey buildings. Firstly, it specifies when a building should be considered as a soft and a weak storey building. Secondly, it specifies higher design forces for the soft storey as compared to the rest of the structure. The Code suggests that the forces in the columns, beams and shear walls (if any) under the action of seismic loads specified in the code, may be obtained by considering the bare frame building (without any infills) (Figure 4b). However, beams and columns in the open ground storey are required to be designed for 2.5 times the forces obtained from this bare frame analysis. For all new RC frame buildings, the best option is to avoid such sudden and large decrease in stiffness and/or strength in any storey; it would be ideal to build walls (either masonry or RC walls) in the ground storey also (Figure 5). Designers can avoid dangerous effects of flexible and weak ground storeys by ensuring that too many walls are not discontinued in the ground storey, i.e., the drop in stiffness and strength in the ground storey level is not abrupt due to the absence of infill walls. The existing open ground storey buildings need to be strengthened suitably so as to prevent them from collapsing during strong earthquake shaking. The owners should seek the services of qualified structural engineers who are able to suggest appropriate solutions to increase seismic safety of these buildings. Related - Earthquake Tip Tip 6: How Architectural Features Affect Buildings During Earthquakes? Tip17: What are the Earthquake Effects on Reinforced Concrete Buildings? Resource Material IS 1893(Part 1) (2002), Indian Standard Code of Practice for Criteria for Design of Earthquake Resistant Structures, Bureau of Indian Standards, New Delhi. Next Upcoming Tip Why are short columns more damaged during earthquakes? Authored by: C.V.R.Murty Indian Institute of Technology Kanpur Kanpur, India Sponsored by: Building Materials and Technology Promotion Council, New Delhi, India This release is a property of IIT Kanpur and BMTPC New Delhi. It may be reproduced without changing its contents and with due acknowledgement. Suggestions/comments may be sent to: eqtips@iitk.ac.in. Visit www.nicee.org or www.bmtpc.org, to see previous IITK-BMTPC Earthquake Tips. December 2003 Figure 3: Consequences of open ground storeys in RC frame buildings – severe damage to ground storey columns and building collapses. (a) 1971 San Fernando Earthquake Photo Courtesy: The EERI Annotated Slide Set CD, Earthquake Engineering Research Institute, Oakland (CA), USA, 1998. (a) Actual building Building being assumed in current design practice Figure 4: Open ground storey building – assumptions made in current design practice are not consistent with the actual structure. Infill walls not considered in upper storeys (b) Figure 5: Avoiding open ground storey problem – continuity of walls in ground storey is preferred. Direct flow of forces through walls (b) 2001 Bhuj Earthquake