Kirti Kushwah, Anil K. Chaudhary, C.Veeresh / International Journal of Engineering Research
and Applications (IJERA) ISSN: 2248-9622 www.ijera.com
Vol. 3, Issue 4, Jul-Aug 2013, pp.2109-2114
2109 | P a g e
Modeling Of Frequency Domain Control of Shunt Active Power
Filter Using MATLAB/Simulink and Power System Blockset
Kirti Kushwah1
, Anil K. Chaudhary2,
C.Veeresh3
,
1
(M.Tech Scholar, MIT Mandsaur, M. P
2
(Assistant Professor, MIT Mandsaur, M. P
3
(Assistant Professor, MIT Mandsaur, M. P
ABSTRACT
This paper presents modeling and
simulation of a shunt active power filter in
frequency domain, using MATLAB and its tools
Simulink and Power System Blocket. The
proposed method offers many additional features
over other methods. It attributes the responsibility
of utility and customer at PCC. It provides an
additional feature of compensation of either
harmonics only, or the compensation of both
harmonics and reactive power simultaneously,
based on the desired capacity of the APF.
Keywords - Power Quality, Active Power Filter,
Frequency Domain Control, Harmonics and Reactive
Power Control.
I. INTRODUCTION
Now a day the power electronic equipments
are widely used in distribution networks which act as
nonlinear loads [3]. Many power quality disturbances
such as harmonics pollution, unbalanced load current,
and reactive power problems are caused by the
nonlinear loads. As a result poor power factor,
weakening efficiency, over heating of motors and
transformers, malfunction of sensitive devices etc.
are encountered [2].
Various control algorithms are proposed for the
control of shunt active power filter. The control
strategies of the active filters [7] are implemented
mainly in three steps- Signal conditioning, estimation
of compensating signals and generation of firing
signals for switching devices as shown in Fig.1.
Estimation of compensating signal is the most
important part of the active filter control [1]. It has a
great impact on compensation objectives, rating of
active filters and its transient as well as steady state
performance. The control strategies use either
frequency domain or time domain approaches to
extract compensating signals from the corresponding
distorted currents and/or voltages.
Fig. 1 Control strategy of active power filter
Instantaneous reactive power theory is
widely used for the calculation of the desired
compensation current, which is mainly based of
sensing harmonics and reactive power components of
current, which is very complex and difficult to
implement [11]. Another approach has been proposed
which does not require sensing the harmonic or VAR
requirement of the load, in which reference current
has been estimated by regulating the dc side capacitor
voltage. This method is simple and easy to implement
but compensate both harmonics and reactive power
simultaneously, which is not preferred sometimes due
to increased rating of APF [2]. The size and cost of
APF depends on how much harmonics are to be
compensated. These techniques are based on
instantaneous extraction of compensating commands
from the distorted currents or voltage signals in time
domain.
Although, time-domain compensation has
fast response, easy implementation and less
computation burden, these techniques take
measurements at only one point, they are limited to
single node applications and are not well suited for
overall network correction [3].
On the contrary, control strategy in the
frequency domain is based on the extraction of the
Corresponding compensating signals from the
distorted current or voltage signals based on Fourier
analysis. Various harmonic components are extracted
from polluted signal and are combined to generate
the reference commands using Fourier
transformation, Frequency domain compensation can
handle single node problems and can also be
extended to minimize harmonic distortion throughout
the network [6]. The greatest drawback of this
Kirti Kushwah, Anil K. Chaudhary, C.Veeresh / International Journal of Engineering Research
and Applications (IJERA) ISSN: 2248-9622 www.ijera.com
Vol. 3, Issue 4, Jul-Aug 2013, pp.2109-2114
2110 | P a g e
technique is the requirement of cumbersome
computation time. With the increase in highest
harmonic to be eliminated, number of calculations
also increase, which results in a large response time.
Therefore, compensation in on-line applications has
been limited in references to harmonics at or below
the 20th
multiple. However, recent development in
fast processor and expert systems may help in
improving their response time [4].
This paper presents modeling and simulation
of a control algorithm of active power filter in
frequency domain using MATLAB and its tools
Simulink and Power System Blocket. Frequency
domain control offers an advantage to compensate
only those harmonics, which are generated by the
customer using harmonic generated loads [5]. If
utility voltage is distorted, APF allows similar level
of distortion in the compensated current. Therefore,
the resultant source current will have the same
waveform as that of the supply voltage, thereby
attributing the responsibility of utility and customer
at the point of common coupling (PCC). The
proposed scheme provides an additional feature of
compensation of either harmonics only, or the
compensation of both harmonics and reactive power
simultaneously, based on the desired capacity of the
APF [15].
II. ESTIMATION OF REFERENCE
CURRENT
A new control algorithm is proposed by
S.Jain, characterized as the “compensation of
customer generated harmonics”, for the control of
shunt active power filter. It compensates harmonics
and reactive power requirement of nonlinear loads,
and maintains similar distortion in the compensated
current as present in the mains voltage. Therefore,
load behaves as a linear/resistive load, and the
resultant source current will have the same waveform
as that of the supply voltage.
The non-sinusoidal utility voltage and
current signal can be expressed as a sum of sinusoidal
signal of various frequencies as –
𝑉𝑠 𝑡 = 𝑉𝑛
𝑘
𝑛=1 sin nωt + θn , and (1)
𝑖 𝐿 𝑡 = 𝐼 𝑛
𝑘
𝑛=1 sin⁡(𝑛𝜔𝑡 + ∅ 𝑛 ) (2)
When θn and ϕn are the phase difference of nth order
voltage and current waveform. The reference current
drawn from the source is the portion of the current,
which retains the same level of distortion as of the
voltage, while at the same time accounts for the
entire fundamental frequency component. The
reference current has the same graphical pattern of
variation as the voltage. It might have a time leg or
lead or may be in phase with the voltage, depending
on the harmonic and reactive power compensation
capability. Thus the fundamental frequency
component of load current I1 (plus loss component)
for harmonic compensation, and I1cosϕ1 (plus loss
component) for both harmonic and reactive power
compensation respectively. All other frequency
components will be in the same proportion as their
counterparts in the voltage, which can be
mathematically expressed as-
For Harmonic Compensation
𝑖 𝑠,𝑟𝑒𝑓 𝑡 =
𝐼1
𝑉1
𝑘
𝑛=1 𝑉𝑛 sin⁡(𝑛𝜔𝑡 + 𝜃 𝑛 +
𝑛 ∅1 − 𝜃1 ) (3)
(I1 = I1+ILoss, for n=1)
For both Harmonic and Reactive Power
Compensation
𝑖 𝑠,𝑟𝑒𝑓 𝑡 =
𝐼1
𝑉1
𝑘
𝑛=1 𝑉𝑛 sin⁡(𝑛𝜔𝑡 + 𝜃 𝑛 ) (4)
(I1 = I1cos ϕ1+ILoss, for n=1)
Based on this principle it is possible to
estimate the reference current, which customer
should draw from the utility. The reference current
component can be estimated by measuring the supply
voltage harmonics, fundamental load current and
their respective angles, as in eq. (3) and (4).
III. CONTROL SCHEME
The complete schematic diagram of the
proposed 3-phase shunt active power filter is shown
in Fig.2. A 3-phase thyristor converter is used as a
nonlinear load. A voltage source PWM converter
with a dc bus capacitor is used as an APF. A series
passive filter has been connected at the PCC to
reduce the bandwidth of the APF.
In order to estimate the reference current
command, the source voltages and load currents of
two phases are measured and their harmonic
components are computed. Using fundamental load
current (I1), fundamental voltage (V1), harmonic
components of voltage (V3, V5…..), and their
respective angles (ϕ1, θ1, θ3, θ5…….), reference currents
are obtained (for two phases) as per eq. (3) or (4).
Third reference current can be obtained by a using a
negative adding circuit. DC bus capacitor voltage is
regulated to obtain the loss component and added
with the fundamental component of load current.
Estimated reference currents and the actual mains
currents are then processed in Hysteresis controller,
to obtain the switching signals.
IV. SIMULATION MODEL
The proposed algorithm has been simulated
using MATLAB and its tools Power System Blockset
and Simulink. Simulation model for obtaining
different frequency components of voltage and
currents for only harmonic compensation, and both
harmonic and reactive power compensation are
shown in Fig.3 (a) and (b) respectively. While Fig.
3(c) gives the simulation model for obtaining the
reference current. Figure 3(d) shows the simulation
model for hysteresis controller.
Kirti Kushwah, Anil K. Chaudhary, C.Veeresh / International Journal of Engineering Research
and Applications (IJERA) ISSN: 2248-9622 www.ijera.com
Vol. 3, Issue 4, Jul-Aug 2013, pp.2109-2114
2111 | P a g e
Fig. 2 Schematic diagram of control algorithm
Fig.3 (a) Obtaining different frequency
components of voltage and current for harmonic
compensation
Fig.3 (b) Obtaining different frequency
components for both harmonic and reactive
power compensation
Fig.3 (c) Obtaining reference current
Fig.3 (d) Simulation model of Hysteresis
controller
V. SIMULATION RESULTS
Various simulation results are obtained for
both the cases (compensation of only harmonics, and
compensation of both harmonics and reactive power
simultaneously), under both ideal and distorted mains
conditions. Essential parameters selected for the
simulation study are shown below-
Vs = 230 volts, f = 50 Hz, RB = 0.1 ohm, LB = 0.5
mH, RC = 0.4 ohm, LC = 3.35 mH, Rp = 0.5 ohm, Lp =
5 mH, Cdc = 2000 μF, Vdc, ref = 650/680 volts for only
harmonic compensation, and both harmonics and
reactive power compensation respectively.
Fig. 4 shows various waveforms for phase „A‟, in
steady state for only harmonic compensation case.
After compensation, source currents become balances
and sinusoidal, but they are not in phase with the
respective voltages (i.e. only harmonics are
compensated). THD of the source current is reduced
from 25.3% (with series passive filter) to 1.02%,
which is well below the 5% recommended limit.
Fig. 4 Simulation results in steady state for only
harmonic compensation (with ideal mains)
Kirti Kushwah, Anil K. Chaudhary, C.Veeresh / International Journal of Engineering Research
and Applications (IJERA) ISSN: 2248-9622 www.ijera.com
Vol. 3, Issue 4, Jul-Aug 2013, pp.2109-2114
2112 | P a g e
Table 1 gives the various frequency components
present in the source, load and filter current (for
phase „A‟). a thyristor converter with ideal mains
draw almost balanced currents, therefore only phase
„A‟ parameters are shown. It is observed that the
compensated source current contain only
fundamental component, while all other components
are absorbed by the filter. Difference in the
magnitudes of the load and compensated source
current is due to the loss component.
Table 1
Frequency components of load, source and filter
current
(Only harmonic compensation with ideal mains)
Order of
Harmonic s
Load
current
Source
current
Filter
current
1 14.48-j10.71 15.26-j11.10 -0.79+j0.40
5 3.65-j0.19 -0.01+j0.03 3.64-j0.2
7 0.56-j2.03 0.05+j0.02 0.52-j2.04
11 0.94-j0.83 0.03+j0.05 0.92-j0.88
13 -0.38-j0.85 0.02-j0.06 -0.39-j0.8
17 0.08-j0.53 0.06+j0.04 0.03-j0.57
19 -0.37-j0.18 -0.05-j0.03 -0.32-j0.15
rms
current
13.13A 13.34A 3.3A
Fig.5 shows the three compensated source currents
with their respective source voltages for both
harmonics and reactive power compensation. After
compensation, all the three source currents becomes
balanced and sinusoidal (having same shapes as of
the mains voltage) and in phase with their respective
source voltages. Hence reactive power is completely
compensated. THD of the source current is reduced
from 25.3% to 1.0%.
Fig. 5 Source voltages and source currents of all
the three phases
Table 2
Frequency components of load, source and filter
current
(Both harmonic and reactive power
compensation, ideal mains)
Order of
Harmonic
s
Load
current
Source
current
Filter
current
1 14.48-j10.71 16.85-j0.02 -2.37-
j10.69
5 3.65-j0.19 -0.04+j0.05 3.68-
j0.24
7 0.56-j2.03 0.05-j0.03 0.51-
j2.00
11 0.94-j0.83 0.00+j0.07 0.94-
j0.91
13 -0.38-j0.85 0.01-j0.07 -0.38-
j0.77
17 0.08-j0.53 0.05+j0.05 0.03-
j0.57
19 -0.37-j0.18 -0.03-j0.01 -0.34-
j0.17
rms
current
13.13A 11.92A 8.39A
Table 2 gives various frequency components present
in the source, load and filter current. No fundamental
reactive current component is present in the
compensated source current, as well as all other
frequency components are absorbed by the filter.
APF has loss component and fundamental reactive
power of load as fundamental component. It is
observed that APF compensate all the harmonic and
reactive power. However, APF current is
increased from 3.3A to 8.39A to compensate both
harmonic and reactive power simultaneously, as
compared to only harmonic compensation, for similar
loading.
Fig. 6 shows all the three source currents
with their respective source voltages for only
harmonic compensation case in steady state with
distorted mains. It is observed from the simulation
results that, APF allows similar level of distortion in
the compensated source current as present in the
source voltage. The shape of the source voltages and
currents are same, but they are not in phase, hence no
reactive power is compensated. Fundamental
component present in the APF current is due to the
loss component.
Various frequency components of the load,
source and APF current (phase „A‟), are given in
Table 3, which shows that the APF allows a part of
the 5th
harmonics component in the compensated
source current, as present in the mains voltage. Table
4 shows various power components after
compensation, from which it is clear that no reactive
power is compensated, therefore capacity of APF
installed is reduced as compared to both harmonics
and reactive power compensation case.
Kirti Kushwah, Anil K. Chaudhary, C.Veeresh / International Journal of Engineering Research
and Applications (IJERA) ISSN: 2248-9622 www.ijera.com
Vol. 3, Issue 4, Jul-Aug 2013, pp.2109-2114
2113 | P a g e
Fig. 6 Three- phase source currents with their
respective source voltages (only harmonic
compensation under distorted mains)
Table 3
Frequency components of load, source and filter
current
(Phase ‘A’)
(Only harmonic compensation with distorted
mains)
Order of
Harmonic
s
Load
current
Source
current
Filter
current
1 14.96-j11 15.80-
j11.40
-0.89+j0.37
3 -0.58-
j1.12
0.06-j0.02 -0.65-j1.10
5 2.93-
j0.48
-1.83+j0.15 4.76-j0.62
7 0.55-
j2.35
0.03-j0.05 0.53-j0.88
9 -0.76-
j0.60
0.07-j0.06 -0.83-j0.55
rms
current
13.52A 13.84A 4.14A
Table 4
Various power components after compensation
(Phase ‘A’)
(Only harmonic compensation with distorted
mains)
Power
component
Load Source APF
Active power,
P
2477.9 2544.2 72.83
Reactive
power, Q
1804.0 1847.5 50.97
VA rating 3109.6 3183.2 952.2
Fundamental
power
2433.9 2571.6 144.2
Harmonic
power
43.98 -27.37 -71.36
Table 5 gives various frequency components presents
in the load, source and APF current (of phase A), for
the compensation of both harmonics and reactive
power simultaneously under distorted mains. This
shows that the APF allows a part of the 5th
harmonic
component in the source current, as present in the
mains voltage. At the same time, it is observes that
the reactive components in all frequency components
of the source current are negligible; hence the
reactive power is fully compensated. Table 6 shows
the various power components after compensation.
Table 5
Frequency components of load, source and filter
current
(Phase ‘A’)
(Both harmonic and reactive power
compensation with
distorted mains)
Order of
Harmonics
Load current Source
current
Filter
current
1 14.96-j11 18.24-j0.02 -3.28-j11.06
3 -0.58-j1.12 0.00-j0.00 -0.58-j1.12
5 2.93-j0.48 1.75-j0.03 1.18-j0.45
7 0.55-j2.35 0.06+j0.00 0.49-j2.35
9 -0.76-j0.60 -0.01-j0.01 -0.75-j0.60
11 0.26-j0.50 -0.04+j0.02 0.29-j0.52
13 -0.53-j0.83 0.04-j0.03 -0.56-j0.80
rms
current
13.52A 12.96A 8.52A
Table 6
Various power components
(Phase ‘A’)
(Both harmonic and reactive power
compensation
With distorted mains)
Power
component
Load Source APF
Active power, P 2477.9 2990.6 512.7
Reactive power,
Q
1804.0 -0.15 -1805.0
VA rating 3109.6 2980.8 1959.6
Fundamental
power
2433.9 2964.3 530.4
Harmonic
power
43.98 26.26 -17.72
VI. CONCLUSION
Paper presents the modeling and simulation
of frequency domain control of shunt active power
filter using MATLAB and its tools Simulink and
Kirti Kushwah, Anil K. Chaudhary, C.Veeresh / International Journal of Engineering Research
and Applications (IJERA) ISSN: 2248-9622 www.ijera.com
Vol. 3, Issue 4, Jul-Aug 2013, pp.2109-2114
2114 | P a g e
Power System Blocksets. Simulation results shows
that, algorithm based on frequency domain require
cumbersome calculation time, but offers many
advantages over other methods. Therefore more
attention and detailed investigations are required on
this issue.
REFERENCES
[1] Jarupula Somlal, Venu Gopala Rao
Mannam,"Analysis of discrete & space
vector PWM controlled hybrid active filters
for power quality enhancement", IJATE, Jan
2012, ISSN: 2231-1963.
[2] M.Anbarasan, Rashmiranjandas,"A
simplified indirect control scheme for shunt
active power filters", IJPEC, ISSN: 2277-
2596, Vol: 1, No: 1.
[3] N. Senthilnathan,T.manigandan, “A Novel
control strategy for line harmonic reduction
using three phase shunt active filter with
balanced and unbalanced
supply",EJSR,Vol.67,Nov.3,pp456-466.
[4] J.H.Sung, S.Park and K.nam,"New parallel
hybrid filters configuration minimizing
active filter size"IEEE Proc.-Electr.Power
Appl, Vol. 147, No. 2, March 2000.
[5] R.M. Potdar,Chhetal Chowhan,”
Comparison of topologies of shunt active
power filter implemented on three phase
four wire system”, Vol-1, Issue-5, Nov.
2011.
[6] M. Chakravarthy, Dr. S.N. Saxena, Dr. B.V.
Sanker Ram, “Control of shunt active power
filters in power system using
MATLAB/SIMULINK” Vol. 1,Issue 7, pp
226, Sep.2012.
[7] M.Chandra Sekhar,B.Kiran Babu,"
Enhancement of power quality using active
power filter in a Medium-Voltage
distribution network switching
loads"IJMER,Vol.2,Issue.2,MAr-Apr 2012
pp-431-435 ISSN:2249-6645.
[8] Zubair Ahmed Memon, Muhammad Aslam
Uqaili, Mukhtiar Ali Unar,"Estimation of
compensation current reference using Fuzzy
logic controller for three-phase hybrid active
power filter" International Journal of
Computer Applications(0975-8887) Vol 43-
No.11,April 2012.
[9] S. Srinath, S. Prabakaran, K.mohan, M.P.
Selvan," Implementation of single phase
shunt active filter for low voltage
distribution system"16th National power
systems conference, 15th-17th
December,2010.
[10] Mr. D.R. obariya, Prof. P.S. Modi, Prof. s.k.
Joshi, “MATLAB/SIMULINK simulation
of hybrid active power filters using
instantaneous reactive power theory".
[11] Moleykutty George, Kartik Prasad Basu,"
Modeling and control of three-phase shunt
active power filter", American Journal of
Applied Science 5(8):1064-1070, 2008.
[12] P.M. Balasubramaniam, G. Gurusamy,"
Three phase active conditioner for harmonic
mitigation" Bonfring International Journal
of Power Systems and Integrated Circuits,
Vol.2, No.3, September 2012.
[13] Bhim singh," Star /Hexagon transformer
based three-phase four-wire DSTATCOM
for power quality improvement”,
International Journal of Emerging Electric
Power Systems, Article 1, Vol.9,Issue
6,2008.
[14] N.Srinivasa Rao, H.J. Jayatheertha,"
Modeling and simulation of various SRF
methods for shunt active power filter and
application to BLDC drives “International
Journal of Advanced Engineering Research
and Studies, E-ISSN2249-8974.
[15] Ibrahim A. Altawil, Khaled A. Mahafzah,
“Shunt active power filter based on diode
clamped inverter and hysteresis band current
controller”, pp84.
[16] Mihaela Popescu, Alexandru Bitoleanu &
Mircea Dobriceanu," On the AC-side
interface filter in three-phase SAPF system"
[17] S.V.Ravi Kumarand S.Siva Nagaraju,"
Simulation of D-STATCOM and DVR in
power system"ARPN Journal of
Engineering and Applied Sciences, Vol.2,
No.3, June 2007.
[18] Bhim Singh, D. P. Kothari, P. Jayaprakash
& T.R. Somayajulu, "Reduced rating VSC
with a zig-zag transformer for current
compensation in a three-phase four-wire
distribution system"IEEE Transactions on
power delivery, Vol.24,No.1,January 2009.
[19] George Adam, Alina G.Stan (Baciu) and
Gheorghe Livint, “A MATLAB/
SIMMULINK approach to shunt active
filter".
[20] Suresh Mikkili & Anup Kumar Panda,
“Simulation and RTDS hardware
implementation of SHAF for mitigation of
current harmonics with p-q and Id-Iq
control strategies using PI controller", Vol.1,
No.3, 2011.
[21] Vaibhav Purwar, “Simulation of shunt
active power line conditioner (APLC) for
three phases AC or DC converter”, IJEECE,
Vol.1 (9), 2011, 504-513.

Contenu connexe

Tendances

A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...ijiert bestjournal
 
Comparison of Soft Computing Techniques applied in High Frequency Aircraft Sy...
Comparison of Soft Computing Techniques applied in High Frequency Aircraft Sy...Comparison of Soft Computing Techniques applied in High Frequency Aircraft Sy...
Comparison of Soft Computing Techniques applied in High Frequency Aircraft Sy...ijeei-iaes
 
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...IOSR Journals
 
COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRI...
COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRI...COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRI...
COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRI...cscpconf
 
Comparison analysis of shunt active filter and transformerless parallel hybri...
Comparison analysis of shunt active filter and transformerless parallel hybri...Comparison analysis of shunt active filter and transformerless parallel hybri...
Comparison analysis of shunt active filter and transformerless parallel hybri...csandit
 
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...IJERA Editor
 
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...IRJET Journal
 
Artificial Intelligence Technique based Reactive Power Planning Incorporating...
Artificial Intelligence Technique based Reactive Power Planning Incorporating...Artificial Intelligence Technique based Reactive Power Planning Incorporating...
Artificial Intelligence Technique based Reactive Power Planning Incorporating...IDES Editor
 
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...IDES Editor
 
T04201162168Optimal Allocation of FACTS Device with Multiple Objectives Using...
T04201162168Optimal Allocation of FACTS Device with Multiple Objectives Using...T04201162168Optimal Allocation of FACTS Device with Multiple Objectives Using...
T04201162168Optimal Allocation of FACTS Device with Multiple Objectives Using...IJMER
 
Performance Evaluation of GA optimized Shunt Active Power Filter for Constant...
Performance Evaluation of GA optimized Shunt Active Power Filter for Constant...Performance Evaluation of GA optimized Shunt Active Power Filter for Constant...
Performance Evaluation of GA optimized Shunt Active Power Filter for Constant...ijeei-iaes
 
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...IJMTST Journal
 
Evaluation of Fundamental d-q Synchronous Reference Frame Harmonic Detection ...
Evaluation of Fundamental d-q Synchronous Reference Frame Harmonic Detection ...Evaluation of Fundamental d-q Synchronous Reference Frame Harmonic Detection ...
Evaluation of Fundamental d-q Synchronous Reference Frame Harmonic Detection ...IJPEDS-IAES
 

Tendances (18)

E04562332
E04562332E04562332
E04562332
 
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...
 
Comparison of Soft Computing Techniques applied in High Frequency Aircraft Sy...
Comparison of Soft Computing Techniques applied in High Frequency Aircraft Sy...Comparison of Soft Computing Techniques applied in High Frequency Aircraft Sy...
Comparison of Soft Computing Techniques applied in High Frequency Aircraft Sy...
 
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
 
COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRI...
COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRI...COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRI...
COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRI...
 
Comparison analysis of shunt active filter and transformerless parallel hybri...
Comparison analysis of shunt active filter and transformerless parallel hybri...Comparison analysis of shunt active filter and transformerless parallel hybri...
Comparison analysis of shunt active filter and transformerless parallel hybri...
 
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
 
Predictive Approach for Power Quality Improvement Based Direct Power Control
Predictive Approach for Power Quality Improvement Based Direct Power ControlPredictive Approach for Power Quality Improvement Based Direct Power Control
Predictive Approach for Power Quality Improvement Based Direct Power Control
 
B011140509
B011140509B011140509
B011140509
 
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
 
Ag33180185
Ag33180185Ag33180185
Ag33180185
 
Artificial Intelligence Technique based Reactive Power Planning Incorporating...
Artificial Intelligence Technique based Reactive Power Planning Incorporating...Artificial Intelligence Technique based Reactive Power Planning Incorporating...
Artificial Intelligence Technique based Reactive Power Planning Incorporating...
 
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
 
T04201162168Optimal Allocation of FACTS Device with Multiple Objectives Using...
T04201162168Optimal Allocation of FACTS Device with Multiple Objectives Using...T04201162168Optimal Allocation of FACTS Device with Multiple Objectives Using...
T04201162168Optimal Allocation of FACTS Device with Multiple Objectives Using...
 
Performance Evaluation of GA optimized Shunt Active Power Filter for Constant...
Performance Evaluation of GA optimized Shunt Active Power Filter for Constant...Performance Evaluation of GA optimized Shunt Active Power Filter for Constant...
Performance Evaluation of GA optimized Shunt Active Power Filter for Constant...
 
An34236241
An34236241An34236241
An34236241
 
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
 
Evaluation of Fundamental d-q Synchronous Reference Frame Harmonic Detection ...
Evaluation of Fundamental d-q Synchronous Reference Frame Harmonic Detection ...Evaluation of Fundamental d-q Synchronous Reference Frame Harmonic Detection ...
Evaluation of Fundamental d-q Synchronous Reference Frame Harmonic Detection ...
 

En vedette (20)

Ge3111891192
Ge3111891192Ge3111891192
Ge3111891192
 
Fp3111131118
Fp3111131118Fp3111131118
Fp3111131118
 
Caça à multa bigtime
Caça à multa bigtimeCaça à multa bigtime
Caça à multa bigtime
 
TRABAJO DE SENA
TRABAJO DE SENA TRABAJO DE SENA
TRABAJO DE SENA
 
Apresentacao arkrypton
Apresentacao arkryptonApresentacao arkrypton
Apresentacao arkrypton
 
1 o mand. noviazgo
1 o mand. noviazgo1 o mand. noviazgo
1 o mand. noviazgo
 
enpresarean
enpresareanenpresarean
enpresarean
 
Mercedes 120 jaar autosport techno classica 2014 2 pdf
Mercedes 120 jaar autosport techno classica 2014   2 pdfMercedes 120 jaar autosport techno classica 2014   2 pdf
Mercedes 120 jaar autosport techno classica 2014 2 pdf
 
Sales paper final
Sales paper finalSales paper final
Sales paper final
 
Documentos necesarios para el ejercicio profesional odontologico
Documentos necesarios para el ejercicio profesional odontologicoDocumentos necesarios para el ejercicio profesional odontologico
Documentos necesarios para el ejercicio profesional odontologico
 
Artigo gestão em conhecimento
Artigo   gestão em conhecimentoArtigo   gestão em conhecimento
Artigo gestão em conhecimento
 
Autobiografía
AutobiografíaAutobiografía
Autobiografía
 
Mercedes 120 jaar autosport techno classica 2014 pdf
Mercedes 120 jaar autosport techno classica 2014 pdfMercedes 120 jaar autosport techno classica 2014 pdf
Mercedes 120 jaar autosport techno classica 2014 pdf
 
Examn termo
Examn termo Examn termo
Examn termo
 
Sindome metabolico
Sindome metabolicoSindome metabolico
Sindome metabolico
 
Fcc
FccFcc
Fcc
 
Computacionmovil2
Computacionmovil2Computacionmovil2
Computacionmovil2
 
Nuestro paso por la escuela
Nuestro paso por la escuelaNuestro paso por la escuela
Nuestro paso por la escuela
 
Vou reabilitar o trabalho
Vou reabilitar o trabalhoVou reabilitar o trabalho
Vou reabilitar o trabalho
 
Derechos y Deberes del aprendiz
Derechos y Deberes del aprendizDerechos y Deberes del aprendiz
Derechos y Deberes del aprendiz
 

Similaire à Lr3421092114

Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...IJERA Editor
 
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...idescitation
 
Power System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power FilterPower System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power FilterIJERA Editor
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Analysis and mitigation of unbalance due to load in distribution system by us...
Analysis and mitigation of unbalance due to load in distribution system by us...Analysis and mitigation of unbalance due to load in distribution system by us...
Analysis and mitigation of unbalance due to load in distribution system by us...eSAT Journals
 
Analysis and mitigation of unbalance due to load in
Analysis and mitigation of unbalance due to load inAnalysis and mitigation of unbalance due to load in
Analysis and mitigation of unbalance due to load ineSAT Publishing House
 
NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER
NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER
NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER elelijjournal
 
Harmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active FilterHarmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active Filteridescitation
 
Power system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filterPower system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filtereSAT Publishing House
 
Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...
Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...
Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...IRJET Journal
 
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEME
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEMEHYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEME
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEMEBlossoms Anjali
 
A seven level cascaded multilevel dstatcom for compensation of reactive power...
A seven level cascaded multilevel dstatcom for compensation of reactive power...A seven level cascaded multilevel dstatcom for compensation of reactive power...
A seven level cascaded multilevel dstatcom for compensation of reactive power...IAEME Publication
 
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...INFOGAIN PUBLICATION
 
Fuzzybased Transformerless Single-Phase Universal Apf for Harmonic and Reacti...
Fuzzybased Transformerless Single-Phase Universal Apf for Harmonic and Reacti...Fuzzybased Transformerless Single-Phase Universal Apf for Harmonic and Reacti...
Fuzzybased Transformerless Single-Phase Universal Apf for Harmonic and Reacti...IRJET Journal
 
Unified Power Quality Conditioner Model Based with Series and Shunt Filters
Unified Power Quality Conditioner Model Based with Series and Shunt FiltersUnified Power Quality Conditioner Model Based with Series and Shunt Filters
Unified Power Quality Conditioner Model Based with Series and Shunt FiltersIAES-IJPEDS
 

Similaire à Lr3421092114 (20)

Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
 
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
 
Review of the Most Applicable Regulator Collections to Control the Parallel A...
Review of the Most Applicable Regulator Collections to Control the Parallel A...Review of the Most Applicable Regulator Collections to Control the Parallel A...
Review of the Most Applicable Regulator Collections to Control the Parallel A...
 
Power System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power FilterPower System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power Filter
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
Adaptive Method for Power Quality Improvement through Minimization of Harmoni...
Adaptive Method for Power Quality Improvement through Minimization of Harmoni...Adaptive Method for Power Quality Improvement through Minimization of Harmoni...
Adaptive Method for Power Quality Improvement through Minimization of Harmoni...
 
Analysis and mitigation of unbalance due to load in distribution system by us...
Analysis and mitigation of unbalance due to load in distribution system by us...Analysis and mitigation of unbalance due to load in distribution system by us...
Analysis and mitigation of unbalance due to load in distribution system by us...
 
Analysis and mitigation of unbalance due to load in
Analysis and mitigation of unbalance due to load inAnalysis and mitigation of unbalance due to load in
Analysis and mitigation of unbalance due to load in
 
A011140104
A011140104A011140104
A011140104
 
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
 
NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER
NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER
NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER
 
Harmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active FilterHarmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active Filter
 
Power system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filterPower system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filter
 
Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...
Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...
Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...
 
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEME
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEMEHYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEME
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEME
 
A seven level cascaded multilevel dstatcom for compensation of reactive power...
A seven level cascaded multilevel dstatcom for compensation of reactive power...A seven level cascaded multilevel dstatcom for compensation of reactive power...
A seven level cascaded multilevel dstatcom for compensation of reactive power...
 
G1101045767
G1101045767G1101045767
G1101045767
 
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
 
Fuzzybased Transformerless Single-Phase Universal Apf for Harmonic and Reacti...
Fuzzybased Transformerless Single-Phase Universal Apf for Harmonic and Reacti...Fuzzybased Transformerless Single-Phase Universal Apf for Harmonic and Reacti...
Fuzzybased Transformerless Single-Phase Universal Apf for Harmonic and Reacti...
 
Unified Power Quality Conditioner Model Based with Series and Shunt Filters
Unified Power Quality Conditioner Model Based with Series and Shunt FiltersUnified Power Quality Conditioner Model Based with Series and Shunt Filters
Unified Power Quality Conditioner Model Based with Series and Shunt Filters
 

Dernier

Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!Manik S Magar
 
H2O.ai CEO/Founder: Sri Ambati Keynote at Wells Fargo Day
H2O.ai CEO/Founder: Sri Ambati Keynote at Wells Fargo DayH2O.ai CEO/Founder: Sri Ambati Keynote at Wells Fargo Day
H2O.ai CEO/Founder: Sri Ambati Keynote at Wells Fargo DaySri Ambati
 
Powerpoint exploring the locations used in television show Time Clash
Powerpoint exploring the locations used in television show Time ClashPowerpoint exploring the locations used in television show Time Clash
Powerpoint exploring the locations used in television show Time Clashcharlottematthew16
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Commit University
 
TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024Lonnie McRorey
 
DSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningDSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningLars Bell
 
Advanced Computer Architecture – An Introduction
Advanced Computer Architecture – An IntroductionAdvanced Computer Architecture – An Introduction
Advanced Computer Architecture – An IntroductionDilum Bandara
 
Commit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyCommit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyAlfredo García Lavilla
 
Developer Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQLDeveloper Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQLScyllaDB
 
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024BookNet Canada
 
"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii SoldatenkoFwdays
 
Vertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering TipsVertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering TipsMiki Katsuragi
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc
 
Leverage Zilliz Serverless - Up to 50X Saving for Your Vector Storage Cost
Leverage Zilliz Serverless - Up to 50X Saving for Your Vector Storage CostLeverage Zilliz Serverless - Up to 50X Saving for Your Vector Storage Cost
Leverage Zilliz Serverless - Up to 50X Saving for Your Vector Storage CostZilliz
 
Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfAddepto
 
What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024Stephanie Beckett
 
Dev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebDev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebUiPathCommunity
 
SAP Build Work Zone - Overview L2-L3.pptx
SAP Build Work Zone - Overview L2-L3.pptxSAP Build Work Zone - Overview L2-L3.pptx
SAP Build Work Zone - Overview L2-L3.pptxNavinnSomaal
 
Artificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxArtificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxhariprasad279825
 

Dernier (20)

Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!
 
H2O.ai CEO/Founder: Sri Ambati Keynote at Wells Fargo Day
H2O.ai CEO/Founder: Sri Ambati Keynote at Wells Fargo DayH2O.ai CEO/Founder: Sri Ambati Keynote at Wells Fargo Day
H2O.ai CEO/Founder: Sri Ambati Keynote at Wells Fargo Day
 
Powerpoint exploring the locations used in television show Time Clash
Powerpoint exploring the locations used in television show Time ClashPowerpoint exploring the locations used in television show Time Clash
Powerpoint exploring the locations used in television show Time Clash
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!
 
TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024
 
DSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningDSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine Tuning
 
Advanced Computer Architecture – An Introduction
Advanced Computer Architecture – An IntroductionAdvanced Computer Architecture – An Introduction
Advanced Computer Architecture – An Introduction
 
Commit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyCommit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easy
 
Developer Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQLDeveloper Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQL
 
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
 
"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko
 
Vertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering TipsVertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering Tips
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
 
Leverage Zilliz Serverless - Up to 50X Saving for Your Vector Storage Cost
Leverage Zilliz Serverless - Up to 50X Saving for Your Vector Storage CostLeverage Zilliz Serverless - Up to 50X Saving for Your Vector Storage Cost
Leverage Zilliz Serverless - Up to 50X Saving for Your Vector Storage Cost
 
Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdf
 
What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024
 
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptxE-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
 
Dev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebDev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio Web
 
SAP Build Work Zone - Overview L2-L3.pptx
SAP Build Work Zone - Overview L2-L3.pptxSAP Build Work Zone - Overview L2-L3.pptx
SAP Build Work Zone - Overview L2-L3.pptx
 
Artificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxArtificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptx
 

Lr3421092114

  • 1. Kirti Kushwah, Anil K. Chaudhary, C.Veeresh / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 4, Jul-Aug 2013, pp.2109-2114 2109 | P a g e Modeling Of Frequency Domain Control of Shunt Active Power Filter Using MATLAB/Simulink and Power System Blockset Kirti Kushwah1 , Anil K. Chaudhary2, C.Veeresh3 , 1 (M.Tech Scholar, MIT Mandsaur, M. P 2 (Assistant Professor, MIT Mandsaur, M. P 3 (Assistant Professor, MIT Mandsaur, M. P ABSTRACT This paper presents modeling and simulation of a shunt active power filter in frequency domain, using MATLAB and its tools Simulink and Power System Blocket. The proposed method offers many additional features over other methods. It attributes the responsibility of utility and customer at PCC. It provides an additional feature of compensation of either harmonics only, or the compensation of both harmonics and reactive power simultaneously, based on the desired capacity of the APF. Keywords - Power Quality, Active Power Filter, Frequency Domain Control, Harmonics and Reactive Power Control. I. INTRODUCTION Now a day the power electronic equipments are widely used in distribution networks which act as nonlinear loads [3]. Many power quality disturbances such as harmonics pollution, unbalanced load current, and reactive power problems are caused by the nonlinear loads. As a result poor power factor, weakening efficiency, over heating of motors and transformers, malfunction of sensitive devices etc. are encountered [2]. Various control algorithms are proposed for the control of shunt active power filter. The control strategies of the active filters [7] are implemented mainly in three steps- Signal conditioning, estimation of compensating signals and generation of firing signals for switching devices as shown in Fig.1. Estimation of compensating signal is the most important part of the active filter control [1]. It has a great impact on compensation objectives, rating of active filters and its transient as well as steady state performance. The control strategies use either frequency domain or time domain approaches to extract compensating signals from the corresponding distorted currents and/or voltages. Fig. 1 Control strategy of active power filter Instantaneous reactive power theory is widely used for the calculation of the desired compensation current, which is mainly based of sensing harmonics and reactive power components of current, which is very complex and difficult to implement [11]. Another approach has been proposed which does not require sensing the harmonic or VAR requirement of the load, in which reference current has been estimated by regulating the dc side capacitor voltage. This method is simple and easy to implement but compensate both harmonics and reactive power simultaneously, which is not preferred sometimes due to increased rating of APF [2]. The size and cost of APF depends on how much harmonics are to be compensated. These techniques are based on instantaneous extraction of compensating commands from the distorted currents or voltage signals in time domain. Although, time-domain compensation has fast response, easy implementation and less computation burden, these techniques take measurements at only one point, they are limited to single node applications and are not well suited for overall network correction [3]. On the contrary, control strategy in the frequency domain is based on the extraction of the Corresponding compensating signals from the distorted current or voltage signals based on Fourier analysis. Various harmonic components are extracted from polluted signal and are combined to generate the reference commands using Fourier transformation, Frequency domain compensation can handle single node problems and can also be extended to minimize harmonic distortion throughout the network [6]. The greatest drawback of this
  • 2. Kirti Kushwah, Anil K. Chaudhary, C.Veeresh / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 4, Jul-Aug 2013, pp.2109-2114 2110 | P a g e technique is the requirement of cumbersome computation time. With the increase in highest harmonic to be eliminated, number of calculations also increase, which results in a large response time. Therefore, compensation in on-line applications has been limited in references to harmonics at or below the 20th multiple. However, recent development in fast processor and expert systems may help in improving their response time [4]. This paper presents modeling and simulation of a control algorithm of active power filter in frequency domain using MATLAB and its tools Simulink and Power System Blocket. Frequency domain control offers an advantage to compensate only those harmonics, which are generated by the customer using harmonic generated loads [5]. If utility voltage is distorted, APF allows similar level of distortion in the compensated current. Therefore, the resultant source current will have the same waveform as that of the supply voltage, thereby attributing the responsibility of utility and customer at the point of common coupling (PCC). The proposed scheme provides an additional feature of compensation of either harmonics only, or the compensation of both harmonics and reactive power simultaneously, based on the desired capacity of the APF [15]. II. ESTIMATION OF REFERENCE CURRENT A new control algorithm is proposed by S.Jain, characterized as the “compensation of customer generated harmonics”, for the control of shunt active power filter. It compensates harmonics and reactive power requirement of nonlinear loads, and maintains similar distortion in the compensated current as present in the mains voltage. Therefore, load behaves as a linear/resistive load, and the resultant source current will have the same waveform as that of the supply voltage. The non-sinusoidal utility voltage and current signal can be expressed as a sum of sinusoidal signal of various frequencies as – 𝑉𝑠 𝑡 = 𝑉𝑛 𝑘 𝑛=1 sin nωt + θn , and (1) 𝑖 𝐿 𝑡 = 𝐼 𝑛 𝑘 𝑛=1 sin⁡(𝑛𝜔𝑡 + ∅ 𝑛 ) (2) When θn and ϕn are the phase difference of nth order voltage and current waveform. The reference current drawn from the source is the portion of the current, which retains the same level of distortion as of the voltage, while at the same time accounts for the entire fundamental frequency component. The reference current has the same graphical pattern of variation as the voltage. It might have a time leg or lead or may be in phase with the voltage, depending on the harmonic and reactive power compensation capability. Thus the fundamental frequency component of load current I1 (plus loss component) for harmonic compensation, and I1cosϕ1 (plus loss component) for both harmonic and reactive power compensation respectively. All other frequency components will be in the same proportion as their counterparts in the voltage, which can be mathematically expressed as- For Harmonic Compensation 𝑖 𝑠,𝑟𝑒𝑓 𝑡 = 𝐼1 𝑉1 𝑘 𝑛=1 𝑉𝑛 sin⁡(𝑛𝜔𝑡 + 𝜃 𝑛 + 𝑛 ∅1 − 𝜃1 ) (3) (I1 = I1+ILoss, for n=1) For both Harmonic and Reactive Power Compensation 𝑖 𝑠,𝑟𝑒𝑓 𝑡 = 𝐼1 𝑉1 𝑘 𝑛=1 𝑉𝑛 sin⁡(𝑛𝜔𝑡 + 𝜃 𝑛 ) (4) (I1 = I1cos ϕ1+ILoss, for n=1) Based on this principle it is possible to estimate the reference current, which customer should draw from the utility. The reference current component can be estimated by measuring the supply voltage harmonics, fundamental load current and their respective angles, as in eq. (3) and (4). III. CONTROL SCHEME The complete schematic diagram of the proposed 3-phase shunt active power filter is shown in Fig.2. A 3-phase thyristor converter is used as a nonlinear load. A voltage source PWM converter with a dc bus capacitor is used as an APF. A series passive filter has been connected at the PCC to reduce the bandwidth of the APF. In order to estimate the reference current command, the source voltages and load currents of two phases are measured and their harmonic components are computed. Using fundamental load current (I1), fundamental voltage (V1), harmonic components of voltage (V3, V5…..), and their respective angles (ϕ1, θ1, θ3, θ5…….), reference currents are obtained (for two phases) as per eq. (3) or (4). Third reference current can be obtained by a using a negative adding circuit. DC bus capacitor voltage is regulated to obtain the loss component and added with the fundamental component of load current. Estimated reference currents and the actual mains currents are then processed in Hysteresis controller, to obtain the switching signals. IV. SIMULATION MODEL The proposed algorithm has been simulated using MATLAB and its tools Power System Blockset and Simulink. Simulation model for obtaining different frequency components of voltage and currents for only harmonic compensation, and both harmonic and reactive power compensation are shown in Fig.3 (a) and (b) respectively. While Fig. 3(c) gives the simulation model for obtaining the reference current. Figure 3(d) shows the simulation model for hysteresis controller.
  • 3. Kirti Kushwah, Anil K. Chaudhary, C.Veeresh / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 4, Jul-Aug 2013, pp.2109-2114 2111 | P a g e Fig. 2 Schematic diagram of control algorithm Fig.3 (a) Obtaining different frequency components of voltage and current for harmonic compensation Fig.3 (b) Obtaining different frequency components for both harmonic and reactive power compensation Fig.3 (c) Obtaining reference current Fig.3 (d) Simulation model of Hysteresis controller V. SIMULATION RESULTS Various simulation results are obtained for both the cases (compensation of only harmonics, and compensation of both harmonics and reactive power simultaneously), under both ideal and distorted mains conditions. Essential parameters selected for the simulation study are shown below- Vs = 230 volts, f = 50 Hz, RB = 0.1 ohm, LB = 0.5 mH, RC = 0.4 ohm, LC = 3.35 mH, Rp = 0.5 ohm, Lp = 5 mH, Cdc = 2000 μF, Vdc, ref = 650/680 volts for only harmonic compensation, and both harmonics and reactive power compensation respectively. Fig. 4 shows various waveforms for phase „A‟, in steady state for only harmonic compensation case. After compensation, source currents become balances and sinusoidal, but they are not in phase with the respective voltages (i.e. only harmonics are compensated). THD of the source current is reduced from 25.3% (with series passive filter) to 1.02%, which is well below the 5% recommended limit. Fig. 4 Simulation results in steady state for only harmonic compensation (with ideal mains)
  • 4. Kirti Kushwah, Anil K. Chaudhary, C.Veeresh / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 4, Jul-Aug 2013, pp.2109-2114 2112 | P a g e Table 1 gives the various frequency components present in the source, load and filter current (for phase „A‟). a thyristor converter with ideal mains draw almost balanced currents, therefore only phase „A‟ parameters are shown. It is observed that the compensated source current contain only fundamental component, while all other components are absorbed by the filter. Difference in the magnitudes of the load and compensated source current is due to the loss component. Table 1 Frequency components of load, source and filter current (Only harmonic compensation with ideal mains) Order of Harmonic s Load current Source current Filter current 1 14.48-j10.71 15.26-j11.10 -0.79+j0.40 5 3.65-j0.19 -0.01+j0.03 3.64-j0.2 7 0.56-j2.03 0.05+j0.02 0.52-j2.04 11 0.94-j0.83 0.03+j0.05 0.92-j0.88 13 -0.38-j0.85 0.02-j0.06 -0.39-j0.8 17 0.08-j0.53 0.06+j0.04 0.03-j0.57 19 -0.37-j0.18 -0.05-j0.03 -0.32-j0.15 rms current 13.13A 13.34A 3.3A Fig.5 shows the three compensated source currents with their respective source voltages for both harmonics and reactive power compensation. After compensation, all the three source currents becomes balanced and sinusoidal (having same shapes as of the mains voltage) and in phase with their respective source voltages. Hence reactive power is completely compensated. THD of the source current is reduced from 25.3% to 1.0%. Fig. 5 Source voltages and source currents of all the three phases Table 2 Frequency components of load, source and filter current (Both harmonic and reactive power compensation, ideal mains) Order of Harmonic s Load current Source current Filter current 1 14.48-j10.71 16.85-j0.02 -2.37- j10.69 5 3.65-j0.19 -0.04+j0.05 3.68- j0.24 7 0.56-j2.03 0.05-j0.03 0.51- j2.00 11 0.94-j0.83 0.00+j0.07 0.94- j0.91 13 -0.38-j0.85 0.01-j0.07 -0.38- j0.77 17 0.08-j0.53 0.05+j0.05 0.03- j0.57 19 -0.37-j0.18 -0.03-j0.01 -0.34- j0.17 rms current 13.13A 11.92A 8.39A Table 2 gives various frequency components present in the source, load and filter current. No fundamental reactive current component is present in the compensated source current, as well as all other frequency components are absorbed by the filter. APF has loss component and fundamental reactive power of load as fundamental component. It is observed that APF compensate all the harmonic and reactive power. However, APF current is increased from 3.3A to 8.39A to compensate both harmonic and reactive power simultaneously, as compared to only harmonic compensation, for similar loading. Fig. 6 shows all the three source currents with their respective source voltages for only harmonic compensation case in steady state with distorted mains. It is observed from the simulation results that, APF allows similar level of distortion in the compensated source current as present in the source voltage. The shape of the source voltages and currents are same, but they are not in phase, hence no reactive power is compensated. Fundamental component present in the APF current is due to the loss component. Various frequency components of the load, source and APF current (phase „A‟), are given in Table 3, which shows that the APF allows a part of the 5th harmonics component in the compensated source current, as present in the mains voltage. Table 4 shows various power components after compensation, from which it is clear that no reactive power is compensated, therefore capacity of APF installed is reduced as compared to both harmonics and reactive power compensation case.
  • 5. Kirti Kushwah, Anil K. Chaudhary, C.Veeresh / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 4, Jul-Aug 2013, pp.2109-2114 2113 | P a g e Fig. 6 Three- phase source currents with their respective source voltages (only harmonic compensation under distorted mains) Table 3 Frequency components of load, source and filter current (Phase ‘A’) (Only harmonic compensation with distorted mains) Order of Harmonic s Load current Source current Filter current 1 14.96-j11 15.80- j11.40 -0.89+j0.37 3 -0.58- j1.12 0.06-j0.02 -0.65-j1.10 5 2.93- j0.48 -1.83+j0.15 4.76-j0.62 7 0.55- j2.35 0.03-j0.05 0.53-j0.88 9 -0.76- j0.60 0.07-j0.06 -0.83-j0.55 rms current 13.52A 13.84A 4.14A Table 4 Various power components after compensation (Phase ‘A’) (Only harmonic compensation with distorted mains) Power component Load Source APF Active power, P 2477.9 2544.2 72.83 Reactive power, Q 1804.0 1847.5 50.97 VA rating 3109.6 3183.2 952.2 Fundamental power 2433.9 2571.6 144.2 Harmonic power 43.98 -27.37 -71.36 Table 5 gives various frequency components presents in the load, source and APF current (of phase A), for the compensation of both harmonics and reactive power simultaneously under distorted mains. This shows that the APF allows a part of the 5th harmonic component in the source current, as present in the mains voltage. At the same time, it is observes that the reactive components in all frequency components of the source current are negligible; hence the reactive power is fully compensated. Table 6 shows the various power components after compensation. Table 5 Frequency components of load, source and filter current (Phase ‘A’) (Both harmonic and reactive power compensation with distorted mains) Order of Harmonics Load current Source current Filter current 1 14.96-j11 18.24-j0.02 -3.28-j11.06 3 -0.58-j1.12 0.00-j0.00 -0.58-j1.12 5 2.93-j0.48 1.75-j0.03 1.18-j0.45 7 0.55-j2.35 0.06+j0.00 0.49-j2.35 9 -0.76-j0.60 -0.01-j0.01 -0.75-j0.60 11 0.26-j0.50 -0.04+j0.02 0.29-j0.52 13 -0.53-j0.83 0.04-j0.03 -0.56-j0.80 rms current 13.52A 12.96A 8.52A Table 6 Various power components (Phase ‘A’) (Both harmonic and reactive power compensation With distorted mains) Power component Load Source APF Active power, P 2477.9 2990.6 512.7 Reactive power, Q 1804.0 -0.15 -1805.0 VA rating 3109.6 2980.8 1959.6 Fundamental power 2433.9 2964.3 530.4 Harmonic power 43.98 26.26 -17.72 VI. CONCLUSION Paper presents the modeling and simulation of frequency domain control of shunt active power filter using MATLAB and its tools Simulink and
  • 6. Kirti Kushwah, Anil K. Chaudhary, C.Veeresh / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 4, Jul-Aug 2013, pp.2109-2114 2114 | P a g e Power System Blocksets. Simulation results shows that, algorithm based on frequency domain require cumbersome calculation time, but offers many advantages over other methods. Therefore more attention and detailed investigations are required on this issue. REFERENCES [1] Jarupula Somlal, Venu Gopala Rao Mannam,"Analysis of discrete & space vector PWM controlled hybrid active filters for power quality enhancement", IJATE, Jan 2012, ISSN: 2231-1963. [2] M.Anbarasan, Rashmiranjandas,"A simplified indirect control scheme for shunt active power filters", IJPEC, ISSN: 2277- 2596, Vol: 1, No: 1. [3] N. Senthilnathan,T.manigandan, “A Novel control strategy for line harmonic reduction using three phase shunt active filter with balanced and unbalanced supply",EJSR,Vol.67,Nov.3,pp456-466. [4] J.H.Sung, S.Park and K.nam,"New parallel hybrid filters configuration minimizing active filter size"IEEE Proc.-Electr.Power Appl, Vol. 147, No. 2, March 2000. [5] R.M. Potdar,Chhetal Chowhan,” Comparison of topologies of shunt active power filter implemented on three phase four wire system”, Vol-1, Issue-5, Nov. 2011. [6] M. Chakravarthy, Dr. S.N. Saxena, Dr. B.V. Sanker Ram, “Control of shunt active power filters in power system using MATLAB/SIMULINK” Vol. 1,Issue 7, pp 226, Sep.2012. [7] M.Chandra Sekhar,B.Kiran Babu," Enhancement of power quality using active power filter in a Medium-Voltage distribution network switching loads"IJMER,Vol.2,Issue.2,MAr-Apr 2012 pp-431-435 ISSN:2249-6645. [8] Zubair Ahmed Memon, Muhammad Aslam Uqaili, Mukhtiar Ali Unar,"Estimation of compensation current reference using Fuzzy logic controller for three-phase hybrid active power filter" International Journal of Computer Applications(0975-8887) Vol 43- No.11,April 2012. [9] S. Srinath, S. Prabakaran, K.mohan, M.P. Selvan," Implementation of single phase shunt active filter for low voltage distribution system"16th National power systems conference, 15th-17th December,2010. [10] Mr. D.R. obariya, Prof. P.S. Modi, Prof. s.k. Joshi, “MATLAB/SIMULINK simulation of hybrid active power filters using instantaneous reactive power theory". [11] Moleykutty George, Kartik Prasad Basu," Modeling and control of three-phase shunt active power filter", American Journal of Applied Science 5(8):1064-1070, 2008. [12] P.M. Balasubramaniam, G. Gurusamy," Three phase active conditioner for harmonic mitigation" Bonfring International Journal of Power Systems and Integrated Circuits, Vol.2, No.3, September 2012. [13] Bhim singh," Star /Hexagon transformer based three-phase four-wire DSTATCOM for power quality improvement”, International Journal of Emerging Electric Power Systems, Article 1, Vol.9,Issue 6,2008. [14] N.Srinivasa Rao, H.J. Jayatheertha," Modeling and simulation of various SRF methods for shunt active power filter and application to BLDC drives “International Journal of Advanced Engineering Research and Studies, E-ISSN2249-8974. [15] Ibrahim A. Altawil, Khaled A. Mahafzah, “Shunt active power filter based on diode clamped inverter and hysteresis band current controller”, pp84. [16] Mihaela Popescu, Alexandru Bitoleanu & Mircea Dobriceanu," On the AC-side interface filter in three-phase SAPF system" [17] S.V.Ravi Kumarand S.Siva Nagaraju," Simulation of D-STATCOM and DVR in power system"ARPN Journal of Engineering and Applied Sciences, Vol.2, No.3, June 2007. [18] Bhim Singh, D. P. Kothari, P. Jayaprakash & T.R. Somayajulu, "Reduced rating VSC with a zig-zag transformer for current compensation in a three-phase four-wire distribution system"IEEE Transactions on power delivery, Vol.24,No.1,January 2009. [19] George Adam, Alina G.Stan (Baciu) and Gheorghe Livint, “A MATLAB/ SIMMULINK approach to shunt active filter". [20] Suresh Mikkili & Anup Kumar Panda, “Simulation and RTDS hardware implementation of SHAF for mitigation of current harmonics with p-q and Id-Iq control strategies using PI controller", Vol.1, No.3, 2011. [21] Vaibhav Purwar, “Simulation of shunt active power line conditioner (APLC) for three phases AC or DC converter”, IJEECE, Vol.1 (9), 2011, 504-513.