IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 439
USE OF FLAT SLABS IN MULTI-STOREY COMMERCIAL BUILDING
SITUATED IN HIGH SEISMIC ZONE
Navyashree K1
, Sahana T.S2
1
Post graduation Student, Dept.of civil engineering, SSIT, Tumkur, Karnataka, India
2
Asst. professor, Dept.of civil engineering, SSIT, Tumkur, Karnataka, India
Abstract
In present era, conventional RC Frame buildings are commonly used for the construction. The use of flat slab building provides
many advantages over conventional RC Frame building in terms of architectural flexibility, use of space, easier formwork and
shorter construction time. The structural efficiency of the flat-slab construction is hindered by its poor performance under
earthquake loading. In the present work six number of conventional RC frame and Flat Slab buildings of G+3, G+8, and G+12
storey building models are considered. The performance of flat slab and the vulnerability of purely frame and purely flat slab
models under different load conditions were studied and for the analysis, seismic zone IV is considered. The analysis is done with
using E-Tabs software. It is necessary to analyze seismic behaviour of building for different heights to see what changes are going
to occur if the height of conventional RC Frame building and flat slab building changes. Therefore, the characteristics of the
seismic behaviour of flat slab and conventional RC Frame buildings suggest that additional measures for guiding the conception
and design of these structures in seismic regions are needed and to improve the performance of building having conventional RC
building and flat slabs under seismic loading, The object of the present work is to compare the behaviour of multi-storey
commercial buildings having flat slabs and conventional RC frame with that of having two way slabs with beams and to study the
effect of height of the building on the performance of these two types of buildings under seismic forces. Present work provides a
good source of information on the parameters lateral displacement, storey drift, storey shear, column moments and axial forces,
time period.
Keyword: Reinforced Concrete Frame; ETABS 9.7.4; Flat Slab.
-------------------------------------------------------------------------***-----------------------------------------------------------------------------
1. INTRODUCTION
The scarcity of space in urban areas has led to the
development of vertical growth consisting of low-rise,
medium-rise and tall buildings. Generally framed structures
are used for these buildings. They are subjected to both
vertical and lateral loads. Lateral loads due to wind and
earthquake governs the design rather than the vertical loads.
The buildings designed for vertical load may not have the
capacity to resist the lateral loads. The lateral loads are the
premier ones because in contrast to vertical load that may be
assumed to increase linearly with height; lateral loads are
quite variable and increase rapidly with height. Under a
uniform wind and earthquake loads the overturning moment
at the base is very large and varies in proportion to the
square of the height of the building. The lateral loads are
considerably higher in the top storey rather than the bottom
storey due to which building tends to act as cantilever.
These lateral forces tend to sway the frame. In many of the
seismic prone areas there are several instances of failure of
buildings which have not been designed for earthquake
loads. All these reaction makes the study of the effect of
lateral loads very important.
Pure rigid frame system or frame action obtained by the
interaction of slabs, beam and column is not adequate. The
frame alone fails to provide the required lateral stiffness for
buildings taller than 15 to 20 (50m to 60m) stories. It is
because of the shear taking component of deflection
produced by the bending of columns and slab causes the
building to deflect excessively. There are two ways to
satisfy these requirements. First is to increase the size of
members beyond and above the strength requirements and
second is to change the form of structure into more rigid and
stable to confine deformation. First approach has its own
limits, whereas second one is more elegant which increases
rigidity and stability of the structure and also confine the
deformation requirement. In earthquake engineering, the
structure is designed for critical force condition among the
load combination.
In the present study the response of multi-storey commercial
R.C. frame and R C flat slab to the lateral and vertical loads
have been done.
1.1 Framed Structure
Framed structures can be considered as an assemblage of
one dimensional and two dimensional members. The length
of a one dimensional member of a structure is large
compared to its other dimensions where as the thickness of a
two dimensional member is smaller than its other two
dimensions. A structure made of line members joined
together is referred to as framed structure. In general,
framed structures have three dimensional configurations.
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 440
While transferring loads acting on the structure, the
members of the structure are subjected to internal forces like
axial forces, shearing forces, bending and torsion moments.
Structural Analysis deals with analyzing these internal
forces in the members of the structures. The process of
analysis commences with planning of a structure, primarily
to meet the functional requirement of the user.
Planning a structure involves the selection of the most
suitable type of structure and the choice of its general layout
and overall dimension on the basis of economic, aesthetic,
functional and other criteria. Designing a structure entails
determining the disturbances to which it is expected to be
exposed during its life time and then choosing the
dimensions of its members as well as the details of their
connections. The structure is then analyzed, i.e., the internal
forces and moments in its members and the displacements of
some of its cross sections are computed. The member of
structure must have sufficient strength and rigidity so that
when the structure subjected to the disturbances to which it
is expected to be exposed, the components of stress and
displacement at any of its point do not exceed the maximum
allowable values given in the appropriate design course.
If the results of the analysis show that the members of the
structure do not have sufficient strength and rigidity to
satisfy the aforementioned requirements the structure is
redesigned, i.e., new dimensions of cross section are chosen.
The process is repeated until the structure is obtained which
satisfies all the aforementioned requirements.
1.2 Flat Slab
Common practice of design and construction is to support
the slabs by beams and support the beams by columns. This
may be called as beam-slab construction. The beams reduce
the available net clear ceiling height. Hence in warehouses,
offices and public halls sometimes beams are avoided and
slabs are directly supported by columns. These types of
construction are aesthetically appealing also. These slabs
which are directly supported by columns are called Flat
Slabs.
Fig -1: Typical Flat Slab (Without column head and drop)
The column head is sometimes widened so as to reduce the
punching shear in the slab. The widened portions are called
column heads. The column heads may be provided with any
angle from the consideration of architecture but for the
design, concrete in the portion at 45º on either side of
vertical only is considered as effective for the design.
Fig -2: Slab without drop and column with column head
Moments in the slabs are more near the column. Hence the
slab is thickened near the columns by providing the drops
as. Sometimes the drops are called as capital of the column.
Thus we have the following types of flat slabs.
Fig -3: Slab with drop and column without column head
(i) Slabs without drop and column with column head
(ii) Slabs without drop and column without column head
(iii) Slabs with drop and column with column head
Flat-slab building structures possesses major advantages
over traditional slab-beam-column structures because of the
free design of space, shorter construction time, architectural
–functional and economical aspects. Because of the absence
of deep beams and shear walls, flat-slab structural system is
significantly more flexible for lateral loads then traditional
RC frame system and that make the system more vulnerable
under seismic events.
The system consists of columns resting directly on floor
slabs for which sufficient strength and ductility should be
provided to enable sustaining of large inelastic deformations
without failure. The absence of beams, i.e., the transferring
of their role to the floor RC structure which gains in height
and density of reinforcement in the parts of the hidden
beams, the bearing capacity of the structural system, the
plate-column and plate-wall connection, all the advantages
and disadvantages of the system have been tested through
long years of analytical and experimental investigations. For
the last 20 to 30 years, the investigations have been directed
toward definition of the actual bearing capacity,
deformability and stability of these structural systems
designed and constructed in seismically active regions.
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 441
A flat slab is a highly indeterminate structure and its exact
analysis is difficult. An approximate analysis can be made
by considering an interior panel of slab. IS456-2000
provides an empirical approach Direct Design Method and
Equivalent Frame Analysis for the analysis of flat slab. Via
Direct Design Method this it’s easy to calculate bending
moment and shear force in flat slab without use of computer.
But the Equivalent Frame Analysis gives more exact results.
The behaviour and design of flat slabs structures for gravity
loads are well established but their seismic behaviour is not
well understood and generally found to be unsatisfactory.
Flat slab is susceptible to progressive brittle punching shear
failure under seismic loading. In flat slab building the most
vulnerable part is slab-column joint. Flat slabs with drop
panels or column capitals are generally constructed as these
extra projections provide safety against punching shear and
also reduce the heavy negative moment. If drop panels are
not provided then the system is termed as Flat Plate.
Extensive research has been carried out to find out the
behaviour of slab-column connection. The failure mode
depends upon the type and extent of loading. Punching shear
strength of slab-column connection is of importance which
very much depends on the gravity shear ratio. The
mechanism of transfer of moments from slab to column is
very complex when subjected to lateral loading and
unbalance moments. These unbalanced moments produce
additional shear and torsion at the connections and then get
transferred into the column which results in excessive
cracking of slab leading to further reduction in the stiffness
of the slab.
A flat-plate structure, as shown in Figure 4, consists of a
slab with uniform thickness supported on the columns with
no beams or drop panels. The economy of flat plate
buildings has lead to their wide spread utilization throughout
the world. Conventionally flat-plate structure is generally
used for lightly loaded structures such as apartments, hotels,
and office buildings with relatively short spans, typically
less than 6m. For longer spans or heavier loads, flat-slabs
system with shear capitals or drop panels would be more
feasible.
Fig -4: Flat-plate structure
Flat-plates have been widely used due to the reduced
construction cost associated with the simple formwork and
simple arrangement of flexural reinforcement. An additional
advantage of a flat-plate is reduced building storey heights
that result in more usable space in a building for a given or
limited height and reduces lateral loads acting on the system,
as well as mechanical, electrical, and cladding costs.
2. OBJECTIVES
The objectives of the study are:
 The main objective of the analysis is to study the
different forces acting on a building. The analysis
is carried out in ETABS 9.7.4. Software. Results of
conventional R.C.C structure i.e. slab, beam and
column and flat slab R.C.C structure for different
heights are discussed below.
 Conventional R.C.C structure and flat slab R.C.C
for different height are modeled and analyzed for
the different combinations of Dynamic loading.
The comparison is made between the conventional
R.C.C structure and flat slab R.C.C. Buildings are
situated in seismic zone IV.
 To study the vulnerability of purely frame and
purely flat-slab models under different factors
which are Storey drift, lateral displacement, time
period and base shear have been obtained for
SPECX (EX) and SPECY (EY) in zone IV. The
axial load and moments in columns have been
obtained for various load combination in zone IV.
3. BUILDING DETAILS, PROGRAM AND
PRELIMINARY DESIGN
Fig -5: Plan of the Commercial building
Following are details of the number of floors considered in
both RC frame and Flat slab building that have taken up for
the analysis and design.
 Model 1 and 2 : Four storey (i.e. G+3)
 Model 3 and 4 : Nine storey (i.e. G+8)
 Model 5 and 6 : Thirteenth storey(i.e. G+12)
6000 6000 6000 6000 6000
60006000600060006000
PROPOSED LAYOUT PLAN OF COMMERCIAL BUILDING
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 442
The height of each floor is 3.0m. The total height of Ground
plus three, eight and twelve storey building is 12.0 m, 27.0
m and 39.0 m. The plinth beam is provided above the
ground at the height of 1.5m from below ground level. 3D
Models of RC frame and flat plate for Ground plus three,
eight and twelve storey buildings is shown in figure 6 to 11
Fig -6: Model 1: 3D of RC Frame of G+3 storey building
Fig -7: Model 2: 3D Model of flat plate of G+3 storey
building
Fig -8: Model 3: 3D Model of RC frame of G+8 storey
building
Fig -9: Model 4: 3D Model of flat plate of G+8 storey
building
Fig -10: Model 5: 3D Model of RC frame of G+12 storey
building
Fig -11: Model 6: 3D Model of flat plate of G+12 storey flat
plate building
3.1 Preliminary Sections
The preliminary sections of columns and beams have been
fixed on the basis of deflection criteria [i.e. span to depth
ratio]. The sections were found to be satisfactory for the
given loads for a four storey model. These sections were
maintained uniform throughout the height. Similarly, all
other models, nine and thirteenth stories, were analyzed and
designed to meet the current Codes (IS 456:2000 and IS
1893:2002) and their structural member sizes chosen for the
study are given in below Table
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 443
Table -1: Sizes of structural element
Sl
No
Name of element
Width
(mm)
Depth
(mm)
1
Column
(floor & roof) for
four, eight and
thirteenth storey
350 350
2
Beam
(floor & roof) for
four, eight and
thirteenth storey
300 600
3
Slabs for both four;
eight and thirteenth
storey
200
3.2 Materials
The Young’s modulus of elasticity of concrete was 35,000
MPa while the Poisson’s ratio was 0.2. The densities were
22 kN/m3
and 25 kN/m3
for solid concrete block and
concrete members respectively. For structural components
M 35and Fe 500 grade was considered.
3.3 Positions and Orientation of Columns
Figure 12 shows the position and orientation of columns and
beams. The building consists of 36 columns. The
orientations of member are chosen so that maximum
moment of inertia is achieved.
Fig -12: Position of the columns
Fig -13: Layout Plan of the Conventional frame Building
Fig -14: Layout Plan of the Flat plate Building
3.4 Program
The program consists of analyzing each of the multi-storey
buildings by using ETABS 9.7.4. In particular, the effects of
following with respect to the behaviour of columns, drift,
displacement, time period have been studied.
 Flat plate (FP)
 Height of the buildings
 Convention RC frame (CF)
4. ANALYSIS OF THE BUILDING
4.1 Loads Considered:
Dead Load: The loads realized due to the following has
been considered
 Self weight of structural members
 Wall load
 Unknown partition
 Floor finish
The self weight of the members is calculated by assuming
the density as 25 kN/m3
and 22 kN/m3 for
concrete and solid
concrete block. Grade of Concrete is M35 and Grade of
Steel (Fy) is Fe500.
The self weight of slab =0.2 x 1 x 1 x 25 = 5 kN/m2
Load due to Unknown partition =1 kN/m2
Load due to floor finish= 1 kN/m2
Load due to wall: 0.2x (3.0-0.6) x22 = 10.56 kN/m2
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 444
Live Load
Live load on floor slab and roof: 4kN/m2
. Allowance for the
reduction in live load is considered for determining the
column moments.
Earthquake Load
This load has been taken into account by specifying the zone
in which the building is located. Table 2 shows the details of
the earthquake parameters as the earthquake zone is
concerned.
Table -2: Earthquake Parameters
Zone (Z) IV
Response Reduction Factor (RF) 5
Importance Factor (I) 1
Rock and Soil Factor (SS) 2
Type of structures 1
Damping Ratio (DM) 0.05
Time Period Ta=0.075h0.75
4.2 Load Combinations:
The following combination of loads with appropriate partial
safety factor satisfying the Indian standard code provision
i.e. IS456:2000, table 18, clause 18.2.3.1 and IS 1893:2002,
clause6.3.2.1 are as follows,
1.5[DL + LL]
1.2[DL + LL+SPECX]
1.2[DL + LL+ SPECY]
1.2[DL + LL - SPECX]
1.2[DL + LL - SPECY]
1.5[DL + SPECX]
1.5[DL + SPECY]
1.5[DL - SPECX]
1.5[DL - SPECY]
0.9[DL] + 1.5[SPECX]
0.9[DL] + 1.5[SPECY]
0.9[DL] - 1.5[SPECX]
0.9[DL] -1.5[SPECY]
Fig -15: Storey Shear of EQX for Flat plate (Typical)
Fig -16: Storey Shear of Specx for Flat plate (Typical)
Fig -17: Displacement of Flat plate
Fig -18: Storey Shear of EQX for conventional Frame
(Typical)
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 445
Fig -19: Storey Shear of Specx for conventional Frame
(Typical)
Fig -20: Displacement of conventional frame
Fig -21: Column axial load (Typical)
Fig -22: Slab moments along Mx for Conventional frame
System
Fig -23: Slab moments along Mx for Flat plate System
5. RESULTS AND DISCUSSION
The forces and displacements developed in each of the
members of the structure are got from the analysis. These
results obtained from the analysis have been discussed detail
in this chapter. Further these results have been used for the
understanding of the behaviour of the structure between the
conventional RC frames and flat plate under the effects of
lateral loads.
5.1 Column Moments
The critical columns i.e. type I have been chosen for the
study. Chart 1-7 shows the details of the column moments
and axial load obtained for columns. Chart 1-7 represents
the column results obtained for the structures which are
subjected to lateral loads only. The lateral load analysis for
flat plate is done to compare the same with that of
Conventional RC frame.
From the lateral load analysis results it can be observed that
in four storey building the moments (Mz) is maximum at
first and terrace level for types I of column. Thus a column
at first and terrace level attracts maximum steel as compared
to the other positions. From the results it can be observed
that the column moment for flat plate analysis is more than
that of the column moments of conventional RC frame
analysis in zone IV. The difference between the two varies
from 15 to 25(%).
From the lateral load analysis results it can be observed that
in nine storey building the moments (Mz) is maximum at
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 446
second level for types I of column. Thus a column at second
level attracts maximum steel as compared to the other
positions. From the results it can be observed that the
column moment for flat plate analysis is more than that of
the column moments of conventional RC frame analysis in
zone IV. The difference between the two varies from 15-
20(%).
From the lateral load analysis results it can be observed that
in thirteenth storey building the moments (Mz) is maximum
at plinth and first level for types I of column. After second
level the moment’s decreases and increases as the height of
the building increases. Thus a column at plinth and first
level attracts maximum steel as compared to the other
positions. From the results it can be observed that the
column moment for flat plate analysis is more than that of
the column moments of conventional RC frame analysis in
zone IV. The difference between the two varies from 15-
30(%).
From the lateral load analysis results it can be observed that,
the axial load is more in flat plate compared to conventional
RC frame. The difference between the two varies up to
10(%).For all columns the columns have been designed for
the combination of dead load and earthquake load this
shows that earthquake combination is the worst combination
giving rise to the most critical sections. Earthquake is more
predominant than other loads. The behaviour of column
moments changes as the height of the building increases.
Height of the Building
The effect of height of the building is studied by considering
a thirteenth storey building. This study has been made for
conventional RC frame and flat plate. The results have been
represented in Chart 1-7. From the Charts it can be observed
that at level plinth, first, second and terrace the moments are
maximum in the column is most critical. Further after level
2 as the height increases the column moments criticality
decreases and increases at the top storey. The base shear,
time period, displacement and storey drift increases
drastically as the height increases
Chart -1: Design moments, three storey building Subjected
to vertical loads
Chart -2: Design moments, nine storey building Subjected
to vertical loads
Chart -3: Design moments, thirteen storey building
Subjected to vertical loads
Chart -4: Axial force, four storey building Subjected to
vertical load
0
50
100
150
200
250
300
ColumnMoments(Mz)kN-m
Storey
Storey Vs Column Moments (Mz)
CFG+3
FPG+3
0
200
400
600
800
1000
1200
TERRACE
8
7
6
5
4
3
2
1
PLINTH
Columnments(Mz)kN-m
Storey
Storey Vs Column Moments(Mz)
CFG+8
FPG+8
-300
-200
-100
0
100
200
300
400
500
PLINTH
1
2
3
4
5
6
7
8
9
10
11
12
TERRACE
ColumnMoments(Mz)kN-m
Storey
Storey Vs Column Moments (Mz)
CFG+12
FPG+12
0
2000
4000
6000
8000
10000
AxialLoadinkN
Storey
Storey Vs Column Axial Force (Pu)
CFG+3
FPG+3
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 447
Chart -5: Axial force, thirteen storey building Subjected to
vertical loads
Chart -6: Axial force, nine storey building Subjected to
vertical loads
Chart -7: Axial force, four, nine and thirteen storey
building Subjected to vertical loads
5.2 Storey Shear
The results have been represented in Chart 8-11. From the
Chart it can be observed that the base shear is maximum at
plinth level for all types of column. After plinth level the
base shear decreases as the height of the building increases.
Due to the symmetric of the building the base shear will
same in both directions (Vx and Vy). Chart 8-11 it can be
observed that, the base shear will increase drastically as the
height increases. Base shear of flat plate building is less than
the conventional R.C.C building. The difference between the
two varies from 8 to 12(%)
Chart -8: Effect of storey shear on behaviour of column of
four storey building
Chart -9: Effect of storey shear on behaviour of column of
nine storey building
0
5000
10000
15000
20000
25000
30000 TE…
12
11
10
9
8
7
6
5
4
3
2
1
PLI…
AxialLoadinkN
Storey vs Column Axial force
CFG+12
FPG+12
Storey
0
5000
10000
15000
20000
AxialLoadinkN
Storey
Storey Vs Column Axial Force (Pu)
CFG+8
FPG+8
0
5000
10000
15000
20000
25000
30000
G+3 G+8 G+12
AxialLoadinkN
No of Story
No of Storey Vs Axial Force
Convnetion Frame
Flat Plate
0
500
1000
1500
2000
2500
3000
3500
StoreyshearkN
Storey
Storey Vs Storey Shear
CFG+3
FPG+3
0
500
1000
1500
2000
2500
3000
3500
4000
PLINTH
1
2
3
4
5
6
7
8
TERRA…
StoryshearkN
Story
Storey Vs Story Shear
CFG+8
FPG+8
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 448
Chart -10: Effect of storey shear on behaviour of column of
thirteen storey building
Chart -11: Effect of storey shear on behaviour of column of
four, nine and thirteen storey building
5.3 Lateral Displacement
The results have been represented in Chart 12-15. From the
Chart it can be observed that the lateral displacement (both
Ux and Uy) is maximum at terrace level for all types of
column. Lateral displacement increases as the storey level
increases. Lateral displacement will be minimum at plinth
level and maximum at terrace level. Due to the symmetric of
the building the lateral displacement will be same in both
directions (Ux and Uy). From Chart it can be observed that,
the lateral displacement will increase drastically as the
height increases. Lateral displacement of conventional
R.C.C building is less than the flat plate building. The
difference between the two varies from 28 to 57(%).
Chart -12: Effect of lateral displacement on behaviour of
column of fourth storey building
Chart -13: Effect of lateral displacement on behaviour of
column of nine storey building
Chart -14: Effect of lateral displacement on behaviour of
column of thirteen storey building
0
500
1000
1500
2000
2500
3000
3500
4000
4500
PLI…
1
2
3
4
5
6
7
8
9
10
11
12
TER…
StoreyshearkN
Storey
Storey Vs Storey Shear
CFG+12
FPG+12
0
10000
20000
30000
40000
50000
60000
70000
80000
G+3 G+8 G+12
StoryShearikN
No of Story
No of Storey Vs Story Shear
Convnetion Frame
Flat Plate
0
10
20
30
40
50
60
LateralDisplacmentinmm
Storey
Storey vs Lateral Displacement
CFG+3
FPG+3
0
10
20
30
40
50
60
70
80
LateralDisplacmentinmm
Story
Storey Vs Lateral Displacement
CFG+8
FPG+8
0
20
40
60
80
100
120
140
PLINTH
1
2
3
4
5
6
7
8
9
10
11
12
TERRA…
LateralDisplacmentinmm
Storey
Storey Vs Lateral Displacement
CFG+12
FPG+12
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 449
Chart -15: Effect of lateral displacement on behaviour of
column of four, nine and thirteen storey building
5.4 Time Period
The results have been represented in Chart 16-19. From the
Chart it can be observed that the time period (both Tx and
Ty) is maximum at mode 1 and 2. The natural time period
increases as the height increases (No of stories). Due to the
symmetric of the building the time period will be same in
both directions (Tx and Ty). From Chart 19 it can be
observed that, the time period will increase drastically as the
height increases. In comparison of the conventional R.C.C
building and flat slab building, the time period is more for
flat slab building than conventional building. The difference
between the two varies from 14 to 33(%).
Chart -16: Effect of time period on behaviour of modes
shapes on fourth storey building
Chart -17: Effect of time period on behaviour of modes
shapes on nine storey building
Chart -18: Effect of time period on behaviour of modes
shapes on thirteen storey building
Chart -19: Effect of time period on behaviour of modes
shapes on fourth, nine and thirteen storey building
5.5 Storey Drift
The results have been represented in Chart 20-23. From the
Chart it can be observed that the storey drift (both Ux and
Uy) is maximum at second level for all types of column.
After second level the storey drift decreases as the height of
the building increases. Due to the symmetric of the building
the lateral displacement will be same in both directions (Ux
and Uy). From Chart it can be observed that, the storey drift
will increase drastically as the height increases. Storey drift
in building with flat slab construction is significantly more
0
20
40
60
80
100
120
140
G+3 G+8 G+12
LateralDisplacementinmm
No of Story
No of Storey Vs Lateral Displacemenet
Convnetion Frame
Flat Plate
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1 2 3 4 5 6 7 8 9 10 11 12
TimeperiodinSec
No of Modes
No of Modes Vs Time Period in Sec
CFG+3
FPG+3
0
0.5
1
1.5
2
2.5
3
1 2 3 4 5 6 7 8 9 10 11 12
TimeperiodinSec
No of Modes
No of modes Vs Time Period
CFG+8
FPG+8
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1 2 3 4 5 6 7 8 9 10 11 12
TimeperiodinSec
No of Modes
No of Modes Vs Time Period
CFG+12
FPG+12
0
1
2
3
4
G+3 G+8 G+12
TimePeriodinSec
No of Story
No of Storey Vs Time Period
Convnetion Frame
Flat Plate
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 450
as compared to conventional R.C.C building. As a result of
this, additional moments are developed. Therefore, the
columns of such buildings should be designed by
considering additional moments caused by the drift. The
difference between the two varies from 28-60(%).
Chart -20: Effect of storey drift on behaviour on fourth
storey building
Chart -21: Effect of storey drift on behaviour on nine storey
building
Chart -22: Effect of storey drift on behaviour on thirteen
storey building
Chart -23: Effect of storey drift on behaviour on four, nine
and thirteen storey building
6. CONCLUSIONS
This study presents a summary of the project work, for
conventional R.C.C building and flat slab building for
different floor height in the seismic region. The effect of
seismic load has been studied for the two types of building
with different height. On the basis of the results following
conclusions have been drawn:
1. The moment is maximum at plinth, first and second
level. After second level moments decreases and
increases at the top storey.
2. The column behavior changes as height of the building
increases.
3. The columns have been designed for the combination of
dead load and earthquake load for all cases and the load
combination 1.5[DL±EX] is the most critical.
4. The column moments are more in flat plate compared to
conventional R.C.C building.
5. Column moments in flat plate vary from 10 to 20 (%) as
compared to that of conventional R.C.C frames
depending upon the storey.
6. The base shears is maximum at plinth level for all types
of column. After plinth level the base shear decreases as
the height of the building increases. The base shear will
increase drastically as the height increases. Base shear
of flat plate building is less than the conventional R.C.C
building. The difference between the two varies from 8-
13(%).
7. The lateral displacement (both Ux and Uy) is maximum
at terrace level for all types of column. Lateral
displacement increases as the storey level increases.
The lateral displacement will increase drastically as the
height increases. Lateral displacement of conventional
R.C.C building is less than the flat plate building. The
difference between the two varies from 28-57(%).
8. The natural time period increases as the height increases
(No of stories).
9. In comparison of the conventional R.C.C building and
flat slab building, the time period is more for flat slab
building than conventional building. The difference
between the two varies from 14-33(%).
10. The time period will be maximum at mode 1 and 2.
After mode 2, time period will reduce drastically.
0
0.001
0.002
0.003
0.004
0.005
0.006
StoreyDrift
Storey
Storey Vs Storey Drift
CFG+3
FPG+3
0
0.001
0.002
0.003
0.004
0.005
PLINTH
1
2
3
4
5
6
7
8
TERR…
StoreyDrift
Storey
Storey Vs Storey Drift
CFG…
FPG…
0
0.0005
0.001
0.0015
0.002
0.0025
0.003
0.0035
0.004
0.0045
0.005
PLI…
1
2
3
4
5
6
7
8
9
10
11
StoreyDrift
Storey
Storey Vs Storey Drift
CFG+12
FPG+12
0
0.001
0.002
0.003
0.004
0.005
0.006
G+3 G+8 G+12
Drift
No of Storey
No of Storey Vs Drift
Convnetion Frame
Flat Plate
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 451
11. The storey drift (both Ux and Uy) is maximum at
second level for all types of column. After second level
the storey drift decreases as the height of the building
increases.
12. Storey drift in building with flat slab construction is
significantly more as compared to conventional R.C.C
building. As a result of this, additional moments are
developed. Therefore, the columns of such buildings
should be designed by considering additional moments
caused by the drift. The difference between the two
varies from 28-60(%).
13. The earthquake forces is more predominant than others
loads.
14. Lateral displacement will be minimum at plinth level
and maximum at terrace level
SCOPE OF FUTURE STUDIES
1. The structure can be compared with post tensioned slab
designed methods
2. The structure behaviour different Seismic zones and its
Behaviour of Buildings having Flat Slabs with Drops.
3. The structure can be analysed with effect of Shear
Wall,
REFERENCES
1. Agarwal. P. and Shirkhande.M, “Earthquake resistant
Design of Structures” Printice- Hall of India Private
Ltd. New Delhi, India.
2. Alpa Sheth“Effect of perimeter frames in seismic
performance of tall concrete buildings with shear wall
core and flat slab system” The 14th
World Conference
on Earthquake Engineering October 12-17, 2008,
Beijing, China.
3. Apostolska1 R.P and Necevska-Cvetanovska G. S,
“Seismic performance of flat-slab building structural
systems” The 14th
World Conference on Earthquake
Engineering October 12-17, 2008, Beijing, China.
4. Bhavikatti S.S, “Advance R.C.C. Design” , New Age
International (p) Limited, Publishers, New Delhi, India.
5. Ema COELHO, Paulo CANDEIAS, Raul
ZAHARIAand Artur V. PINTO, “Assessment of the
seismic behavior of R C flat slab building structures”,
13th World Conference on Earthquake Engineering
Vancouver, B.C., Canada August 1-6, 2004 Paper No.
2630
6. Garg c.s, Yogendrasingh, Pradeep Bhargava and
Bhandari N.M, “Seismic performance of flat slab shear
wall system”, Journal of structural Engineering, Vol.37,
No.3, August-September2010, PP.203-207.
7. Lan N .Robertson, “Analysis flat slab structures
subjected to combined lateral and gravity load”, ACI
Structural Journal.
8. Pankaj Agarwal and Manish Shrikande (2007),
“Earthquake Resistant Design of Structures”, Prentice
Hall of India Private Limited, New Delhi, India.
9. Shyh-jiann Hwang and Jack p. moehle, “Models for
laterally loaded slab-column frames”, ACI Structural
Journal, March-April 2000.
10. IS: 456:2000, “Indian Standard Code for Plain and
Reinforced Concrete”, Bureau of Indian Standards,
New Delhi.
11. Prof. K S Sable, Er. V A Ghodechor, Prof. S B
Kandekar,“ Comparative Study of Seismic
Behavior of Multistorey Flat Slab and Conventional
Reinforced Concrete Framed Structures”, Volume 2,
Issue 3, June 2012
BIOGRAPHIES
Mrs. Navyashree K resident of Mysore
received her degree in Civil Engineering
from NIE, Mysore in the year August
2010.
Mrs. Sahana T.S (Asst.Professor)
received her M.E (Pre-stressed
concrete) from Banglore University.
Her area of interest includes
Earthquake engineering and Dynamics
of Structures. She has 5 years of
teaching experience.

Contenu connexe

Tendances

Evaluation of the Seismic Response Parameters for Infilled Reinforced Concret...
Evaluation of the Seismic Response Parameters for Infilled Reinforced Concret...Evaluation of the Seismic Response Parameters for Infilled Reinforced Concret...
Evaluation of the Seismic Response Parameters for Infilled Reinforced Concret...
IOSRJMCE
 
Virtual Outriggers in Tall Buildings
Virtual Outriggers in Tall BuildingsVirtual Outriggers in Tall Buildings
Virtual Outriggers in Tall Buildings
Andrew J Horton
 
Rc4 lecture 2- eng. samer akil
Rc4  lecture 2- eng. samer akilRc4  lecture 2- eng. samer akil
Rc4 lecture 2- eng. samer akil
AminZuraiqi2
 
Effect of Wind Load on Structural Performance of Dimensionally Regular & Irre...
Effect of Wind Load on Structural Performance of Dimensionally Regular & Irre...Effect of Wind Load on Structural Performance of Dimensionally Regular & Irre...
Effect of Wind Load on Structural Performance of Dimensionally Regular & Irre...
Dr. Amarjeet Singh
 

Tendances (20)

Evaluation of the Seismic Response Parameters for Infilled Reinforced Concret...
Evaluation of the Seismic Response Parameters for Infilled Reinforced Concret...Evaluation of the Seismic Response Parameters for Infilled Reinforced Concret...
Evaluation of the Seismic Response Parameters for Infilled Reinforced Concret...
 
Diagrid Systems : Future of Tall buildings, Technical Paper by Jagmohan Garg ...
Diagrid Systems : Future of Tall buildings, Technical Paper by Jagmohan Garg ...Diagrid Systems : Future of Tall buildings, Technical Paper by Jagmohan Garg ...
Diagrid Systems : Future of Tall buildings, Technical Paper by Jagmohan Garg ...
 
Virtual Outriggers in Tall Buildings
Virtual Outriggers in Tall BuildingsVirtual Outriggers in Tall Buildings
Virtual Outriggers in Tall Buildings
 
Seismic study and performance of 30 storey high rise building with beam slab,...
Seismic study and performance of 30 storey high rise building with beam slab,...Seismic study and performance of 30 storey high rise building with beam slab,...
Seismic study and performance of 30 storey high rise building with beam slab,...
 
effect of non seismic walls
effect of non seismic wallseffect of non seismic walls
effect of non seismic walls
 
Diagrid structural system strategies to reduce lateral forces on high rise bu...
Diagrid structural system strategies to reduce lateral forces on high rise bu...Diagrid structural system strategies to reduce lateral forces on high rise bu...
Diagrid structural system strategies to reduce lateral forces on high rise bu...
 
Topology optimisation of braced frames for high rise buildings
Topology optimisation of braced frames for high rise buildingsTopology optimisation of braced frames for high rise buildings
Topology optimisation of braced frames for high rise buildings
 
Rc4 lecture 2- eng. samer akil
Rc4  lecture 2- eng. samer akilRc4  lecture 2- eng. samer akil
Rc4 lecture 2- eng. samer akil
 
Effect of concentric and eccentric type of bracings on performance based seis...
Effect of concentric and eccentric type of bracings on performance based seis...Effect of concentric and eccentric type of bracings on performance based seis...
Effect of concentric and eccentric type of bracings on performance based seis...
 
Seismic performance of a rc frame with soft storey criteria
Seismic performance of a rc frame with soft storey criteriaSeismic performance of a rc frame with soft storey criteria
Seismic performance of a rc frame with soft storey criteria
 
A comparative review on behavioural aspect of post tensioning voided flat sl...
A comparative review on behavioural aspect of post  tensioning voided flat sl...A comparative review on behavioural aspect of post  tensioning voided flat sl...
A comparative review on behavioural aspect of post tensioning voided flat sl...
 
Seismic Drift Consideration in soft storied RCC buildings: A Critical Review
Seismic Drift Consideration in soft storied RCC buildings: A Critical ReviewSeismic Drift Consideration in soft storied RCC buildings: A Critical Review
Seismic Drift Consideration in soft storied RCC buildings: A Critical Review
 
Analysis of outrigger system for tall vertical irregularites structures subje...
Analysis of outrigger system for tall vertical irregularites structures subje...Analysis of outrigger system for tall vertical irregularites structures subje...
Analysis of outrigger system for tall vertical irregularites structures subje...
 
Design And Analysis Of Precast Load Bearing Walls For Multi Storey Building ...
Design And Analysis Of Precast Load Bearing Walls For Multi  Storey Building ...Design And Analysis Of Precast Load Bearing Walls For Multi  Storey Building ...
Design And Analysis Of Precast Load Bearing Walls For Multi Storey Building ...
 
OPTIMAL DIAGRID ANGLE TO MINIMIZE DRIFT IN HIGH-RISE STEEL BUILDINGS SUBJECTE...
OPTIMAL DIAGRID ANGLE TO MINIMIZE DRIFT IN HIGH-RISE STEEL BUILDINGS SUBJECTE...OPTIMAL DIAGRID ANGLE TO MINIMIZE DRIFT IN HIGH-RISE STEEL BUILDINGS SUBJECTE...
OPTIMAL DIAGRID ANGLE TO MINIMIZE DRIFT IN HIGH-RISE STEEL BUILDINGS SUBJECTE...
 
Significance of shear wall in flat slab multi storied building - A Review
Significance of shear wall in flat slab multi storied building - A ReviewSignificance of shear wall in flat slab multi storied building - A Review
Significance of shear wall in flat slab multi storied building - A Review
 
Effect of Wind Load on Structural Performance of Dimensionally Regular & Irre...
Effect of Wind Load on Structural Performance of Dimensionally Regular & Irre...Effect of Wind Load on Structural Performance of Dimensionally Regular & Irre...
Effect of Wind Load on Structural Performance of Dimensionally Regular & Irre...
 
A study on behaviour of outrigger system on high rise steel structure by vary...
A study on behaviour of outrigger system on high rise steel structure by vary...A study on behaviour of outrigger system on high rise steel structure by vary...
A study on behaviour of outrigger system on high rise steel structure by vary...
 
F012515059
F012515059F012515059
F012515059
 
structure, technology and materials of highrise buildings
structure, technology and materials of highrise buildingsstructure, technology and materials of highrise buildings
structure, technology and materials of highrise buildings
 

En vedette

Intelligent two axis dual-ccd image-servo shooting platform design
Intelligent two axis dual-ccd image-servo shooting platform designIntelligent two axis dual-ccd image-servo shooting platform design
Intelligent two axis dual-ccd image-servo shooting platform design
eSAT Publishing House
 
Assessment of the leachability and mechanical stability of mud from a zinc pl...
Assessment of the leachability and mechanical stability of mud from a zinc pl...Assessment of the leachability and mechanical stability of mud from a zinc pl...
Assessment of the leachability and mechanical stability of mud from a zinc pl...
eSAT Publishing House
 
Mac protocols for cooperative diversity in wlan
Mac protocols for cooperative diversity in wlanMac protocols for cooperative diversity in wlan
Mac protocols for cooperative diversity in wlan
eSAT Publishing House
 
Real time reservoir operation (validation phase)
Real time reservoir operation (validation phase)Real time reservoir operation (validation phase)
Real time reservoir operation (validation phase)
eSAT Publishing House
 

En vedette (20)

Flat slab design
Flat slab designFlat slab design
Flat slab design
 
Evaluation of punching shear in flat slabs
Evaluation of punching shear in flat slabsEvaluation of punching shear in flat slabs
Evaluation of punching shear in flat slabs
 
Flat slab and it's importance
Flat slab and it's importanceFlat slab and it's importance
Flat slab and it's importance
 
Flat slab ppt
Flat slab pptFlat slab ppt
Flat slab ppt
 
DESIGN OF FLAT SLABS
DESIGN OF FLAT SLABSDESIGN OF FLAT SLABS
DESIGN OF FLAT SLABS
 
Intelligent two axis dual-ccd image-servo shooting platform design
Intelligent two axis dual-ccd image-servo shooting platform designIntelligent two axis dual-ccd image-servo shooting platform design
Intelligent two axis dual-ccd image-servo shooting platform design
 
Assessment of composting, energy and gas generation
Assessment of composting, energy and gas generationAssessment of composting, energy and gas generation
Assessment of composting, energy and gas generation
 
Assessment of the leachability and mechanical stability of mud from a zinc pl...
Assessment of the leachability and mechanical stability of mud from a zinc pl...Assessment of the leachability and mechanical stability of mud from a zinc pl...
Assessment of the leachability and mechanical stability of mud from a zinc pl...
 
Effects of different mole spacings on the yield of summer groundnut
Effects of different mole spacings on the yield of summer groundnutEffects of different mole spacings on the yield of summer groundnut
Effects of different mole spacings on the yield of summer groundnut
 
Mac protocols for cooperative diversity in wlan
Mac protocols for cooperative diversity in wlanMac protocols for cooperative diversity in wlan
Mac protocols for cooperative diversity in wlan
 
Zero rotation aproach for droop improvement in
Zero rotation aproach for droop improvement inZero rotation aproach for droop improvement in
Zero rotation aproach for droop improvement in
 
Composites from natural fibres
Composites from natural fibresComposites from natural fibres
Composites from natural fibres
 
Study of shape of intermediate sill on the design of stilling basin model
Study of shape of intermediate sill on the design of stilling basin modelStudy of shape of intermediate sill on the design of stilling basin model
Study of shape of intermediate sill on the design of stilling basin model
 
Hydrogen production from glycerol using microbial electrolysis cell
Hydrogen production from glycerol using microbial electrolysis cellHydrogen production from glycerol using microbial electrolysis cell
Hydrogen production from glycerol using microbial electrolysis cell
 
Experimental investigation, optimization and performance prediction of wind t...
Experimental investigation, optimization and performance prediction of wind t...Experimental investigation, optimization and performance prediction of wind t...
Experimental investigation, optimization and performance prediction of wind t...
 
Lab view study of electrical power distribution system
Lab view study of electrical power distribution systemLab view study of electrical power distribution system
Lab view study of electrical power distribution system
 
Enhancement of qos in lte downlink systems using
Enhancement of qos in lte downlink systems usingEnhancement of qos in lte downlink systems using
Enhancement of qos in lte downlink systems using
 
Real time reservoir operation (validation phase)
Real time reservoir operation (validation phase)Real time reservoir operation (validation phase)
Real time reservoir operation (validation phase)
 
Optimized sensor nodes by fault node recovery algorithm
Optimized sensor nodes by fault node recovery algorithmOptimized sensor nodes by fault node recovery algorithm
Optimized sensor nodes by fault node recovery algorithm
 
Sdci scalable distributed cache indexing for cache consistency for mobile env...
Sdci scalable distributed cache indexing for cache consistency for mobile env...Sdci scalable distributed cache indexing for cache consistency for mobile env...
Sdci scalable distributed cache indexing for cache consistency for mobile env...
 

Similaire à Use of flat slabs in multi storey commercial building situated in high seismic zone

Dynamic analysis of steel tube structure with bracing systems
Dynamic analysis of steel tube structure with bracing systemsDynamic analysis of steel tube structure with bracing systems
Dynamic analysis of steel tube structure with bracing systems
eSAT Journals
 
Study of lateral load resisting systems of variable heights in all soil types...
Study of lateral load resisting systems of variable heights in all soil types...Study of lateral load resisting systems of variable heights in all soil types...
Study of lateral load resisting systems of variable heights in all soil types...
eSAT Publishing House
 
Behavior of plan irregularites using composite members by varying column spac...
Behavior of plan irregularites using composite members by varying column spac...Behavior of plan irregularites using composite members by varying column spac...
Behavior of plan irregularites using composite members by varying column spac...
eSAT Journals
 
Behavior of plan irregularites using composite members by varying column spac...
Behavior of plan irregularites using composite members by varying column spac...Behavior of plan irregularites using composite members by varying column spac...
Behavior of plan irregularites using composite members by varying column spac...
eSAT Journals
 

Similaire à Use of flat slabs in multi storey commercial building situated in high seismic zone (20)

Dynamic analysis of steel tube structure with bracing systems
Dynamic analysis of steel tube structure with bracing systemsDynamic analysis of steel tube structure with bracing systems
Dynamic analysis of steel tube structure with bracing systems
 
Study of lateral load resisting systems of variable heights in all soil types...
Study of lateral load resisting systems of variable heights in all soil types...Study of lateral load resisting systems of variable heights in all soil types...
Study of lateral load resisting systems of variable heights in all soil types...
 
Study of lateral load resisting systems of variable heights in all soil types...
Study of lateral load resisting systems of variable heights in all soil types...Study of lateral load resisting systems of variable heights in all soil types...
Study of lateral load resisting systems of variable heights in all soil types...
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
 
Behavior of plan irregularites using composite members by varying column spac...
Behavior of plan irregularites using composite members by varying column spac...Behavior of plan irregularites using composite members by varying column spac...
Behavior of plan irregularites using composite members by varying column spac...
 
Behavior of plan irregularites using composite members by varying column spac...
Behavior of plan irregularites using composite members by varying column spac...Behavior of plan irregularites using composite members by varying column spac...
Behavior of plan irregularites using composite members by varying column spac...
 
IRJET- Comparative Study of Flat Slab and Conventional Slab Structure wit...
IRJET-  	  Comparative Study of Flat Slab and Conventional Slab Structure wit...IRJET-  	  Comparative Study of Flat Slab and Conventional Slab Structure wit...
IRJET- Comparative Study of Flat Slab and Conventional Slab Structure wit...
 
IRJET- Analysis of Various Effects on Multistory Building (G+27) by Staad Pro...
IRJET- Analysis of Various Effects on Multistory Building (G+27) by Staad Pro...IRJET- Analysis of Various Effects on Multistory Building (G+27) by Staad Pro...
IRJET- Analysis of Various Effects on Multistory Building (G+27) by Staad Pro...
 
Seismic Response of Structure with Single Core
Seismic Response of Structure with Single CoreSeismic Response of Structure with Single Core
Seismic Response of Structure with Single Core
 
Optimization of Circular RC Frame Structure by Using Shear Wall at a Differen...
Optimization of Circular RC Frame Structure by Using Shear Wall at a Differen...Optimization of Circular RC Frame Structure by Using Shear Wall at a Differen...
Optimization of Circular RC Frame Structure by Using Shear Wall at a Differen...
 
Comparative Study of Seismic Analysis of RC Frame Structure with and without ...
Comparative Study of Seismic Analysis of RC Frame Structure with and without ...Comparative Study of Seismic Analysis of RC Frame Structure with and without ...
Comparative Study of Seismic Analysis of RC Frame Structure with and without ...
 
IRJET- Study on Shear Wall and Bracing in Irregular Structure and Regular Str...
IRJET- Study on Shear Wall and Bracing in Irregular Structure and Regular Str...IRJET- Study on Shear Wall and Bracing in Irregular Structure and Regular Str...
IRJET- Study on Shear Wall and Bracing in Irregular Structure and Regular Str...
 
ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...
ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...
ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...
 
IRJET- Analytical Study of Punching Shear in Flat Slab - Review Paper
IRJET-  	  Analytical Study of Punching Shear in Flat Slab - Review PaperIRJET-  	  Analytical Study of Punching Shear in Flat Slab - Review Paper
IRJET- Analytical Study of Punching Shear in Flat Slab - Review Paper
 
IRJET- Effective Location of Shear Wall, its Significance and Displacement An...
IRJET- Effective Location of Shear Wall, its Significance and Displacement An...IRJET- Effective Location of Shear Wall, its Significance and Displacement An...
IRJET- Effective Location of Shear Wall, its Significance and Displacement An...
 
Linear Analysis of RCC High-Rise Structures with Multiple Combinations of Out...
Linear Analysis of RCC High-Rise Structures with Multiple Combinations of Out...Linear Analysis of RCC High-Rise Structures with Multiple Combinations of Out...
Linear Analysis of RCC High-Rise Structures with Multiple Combinations of Out...
 
IRJET- A Performance Study of High Raise Building with Flat Slab System u...
IRJET-  	  A Performance Study of High Raise Building with Flat Slab System u...IRJET-  	  A Performance Study of High Raise Building with Flat Slab System u...
IRJET- A Performance Study of High Raise Building with Flat Slab System u...
 
IRJET- Comparative Analysis of RCC Structure and Tube-in-Tube Structure
IRJET-  	  Comparative Analysis of RCC Structure and Tube-in-Tube StructureIRJET-  	  Comparative Analysis of RCC Structure and Tube-in-Tube Structure
IRJET- Comparative Analysis of RCC Structure and Tube-in-Tube Structure
 
seismic response of multi storey building equipped with steel bracing
 seismic response of multi storey building equipped with steel bracing seismic response of multi storey building equipped with steel bracing
seismic response of multi storey building equipped with steel bracing
 
Seismic Response of Multi storey Flat Slab Building with and without Shear Wall
Seismic Response of Multi storey Flat Slab Building with and without Shear WallSeismic Response of Multi storey Flat Slab Building with and without Shear Wall
Seismic Response of Multi storey Flat Slab Building with and without Shear Wall
 

Plus de eSAT Publishing House

Likely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnamLikely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnam
eSAT Publishing House
 
Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...
eSAT Publishing House
 
Hudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnamHudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnam
eSAT Publishing House
 
Groundwater investigation using geophysical methods a case study of pydibhim...
Groundwater investigation using geophysical methods  a case study of pydibhim...Groundwater investigation using geophysical methods  a case study of pydibhim...
Groundwater investigation using geophysical methods a case study of pydibhim...
eSAT Publishing House
 
Flood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, indiaFlood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, india
eSAT Publishing House
 
Enhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity buildingEnhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity building
eSAT Publishing House
 
Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...
eSAT Publishing House
 
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
eSAT Publishing House
 
Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...
eSAT Publishing House
 
Shear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a reviewShear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a review
eSAT Publishing House
 
Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...
eSAT Publishing House
 
Risk analysis and environmental hazard management
Risk analysis and environmental hazard managementRisk analysis and environmental hazard management
Risk analysis and environmental hazard management
eSAT Publishing House
 
Review study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear wallsReview study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear walls
eSAT Publishing House
 
Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...
eSAT Publishing House
 
Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...
eSAT Publishing House
 
Coastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of indiaCoastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of india
eSAT Publishing House
 
Can fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structuresCan fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structures
eSAT Publishing House
 
Assessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildingsAssessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildings
eSAT Publishing House
 
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
eSAT Publishing House
 
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
eSAT Publishing House
 

Plus de eSAT Publishing House (20)

Likely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnamLikely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnam
 
Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...
 
Hudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnamHudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnam
 
Groundwater investigation using geophysical methods a case study of pydibhim...
Groundwater investigation using geophysical methods  a case study of pydibhim...Groundwater investigation using geophysical methods  a case study of pydibhim...
Groundwater investigation using geophysical methods a case study of pydibhim...
 
Flood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, indiaFlood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, india
 
Enhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity buildingEnhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity building
 
Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...
 
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
 
Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...
 
Shear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a reviewShear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a review
 
Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...
 
Risk analysis and environmental hazard management
Risk analysis and environmental hazard managementRisk analysis and environmental hazard management
Risk analysis and environmental hazard management
 
Review study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear wallsReview study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear walls
 
Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...
 
Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...
 
Coastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of indiaCoastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of india
 
Can fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structuresCan fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structures
 
Assessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildingsAssessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildings
 
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
 
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
 

Dernier

Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Christo Ananth
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
ankushspencer015
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
Tonystark477637
 

Dernier (20)

Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 

Use of flat slabs in multi storey commercial building situated in high seismic zone

  • 1. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 439 USE OF FLAT SLABS IN MULTI-STOREY COMMERCIAL BUILDING SITUATED IN HIGH SEISMIC ZONE Navyashree K1 , Sahana T.S2 1 Post graduation Student, Dept.of civil engineering, SSIT, Tumkur, Karnataka, India 2 Asst. professor, Dept.of civil engineering, SSIT, Tumkur, Karnataka, India Abstract In present era, conventional RC Frame buildings are commonly used for the construction. The use of flat slab building provides many advantages over conventional RC Frame building in terms of architectural flexibility, use of space, easier formwork and shorter construction time. The structural efficiency of the flat-slab construction is hindered by its poor performance under earthquake loading. In the present work six number of conventional RC frame and Flat Slab buildings of G+3, G+8, and G+12 storey building models are considered. The performance of flat slab and the vulnerability of purely frame and purely flat slab models under different load conditions were studied and for the analysis, seismic zone IV is considered. The analysis is done with using E-Tabs software. It is necessary to analyze seismic behaviour of building for different heights to see what changes are going to occur if the height of conventional RC Frame building and flat slab building changes. Therefore, the characteristics of the seismic behaviour of flat slab and conventional RC Frame buildings suggest that additional measures for guiding the conception and design of these structures in seismic regions are needed and to improve the performance of building having conventional RC building and flat slabs under seismic loading, The object of the present work is to compare the behaviour of multi-storey commercial buildings having flat slabs and conventional RC frame with that of having two way slabs with beams and to study the effect of height of the building on the performance of these two types of buildings under seismic forces. Present work provides a good source of information on the parameters lateral displacement, storey drift, storey shear, column moments and axial forces, time period. Keyword: Reinforced Concrete Frame; ETABS 9.7.4; Flat Slab. -------------------------------------------------------------------------***----------------------------------------------------------------------------- 1. INTRODUCTION The scarcity of space in urban areas has led to the development of vertical growth consisting of low-rise, medium-rise and tall buildings. Generally framed structures are used for these buildings. They are subjected to both vertical and lateral loads. Lateral loads due to wind and earthquake governs the design rather than the vertical loads. The buildings designed for vertical load may not have the capacity to resist the lateral loads. The lateral loads are the premier ones because in contrast to vertical load that may be assumed to increase linearly with height; lateral loads are quite variable and increase rapidly with height. Under a uniform wind and earthquake loads the overturning moment at the base is very large and varies in proportion to the square of the height of the building. The lateral loads are considerably higher in the top storey rather than the bottom storey due to which building tends to act as cantilever. These lateral forces tend to sway the frame. In many of the seismic prone areas there are several instances of failure of buildings which have not been designed for earthquake loads. All these reaction makes the study of the effect of lateral loads very important. Pure rigid frame system or frame action obtained by the interaction of slabs, beam and column is not adequate. The frame alone fails to provide the required lateral stiffness for buildings taller than 15 to 20 (50m to 60m) stories. It is because of the shear taking component of deflection produced by the bending of columns and slab causes the building to deflect excessively. There are two ways to satisfy these requirements. First is to increase the size of members beyond and above the strength requirements and second is to change the form of structure into more rigid and stable to confine deformation. First approach has its own limits, whereas second one is more elegant which increases rigidity and stability of the structure and also confine the deformation requirement. In earthquake engineering, the structure is designed for critical force condition among the load combination. In the present study the response of multi-storey commercial R.C. frame and R C flat slab to the lateral and vertical loads have been done. 1.1 Framed Structure Framed structures can be considered as an assemblage of one dimensional and two dimensional members. The length of a one dimensional member of a structure is large compared to its other dimensions where as the thickness of a two dimensional member is smaller than its other two dimensions. A structure made of line members joined together is referred to as framed structure. In general, framed structures have three dimensional configurations.
  • 2. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 440 While transferring loads acting on the structure, the members of the structure are subjected to internal forces like axial forces, shearing forces, bending and torsion moments. Structural Analysis deals with analyzing these internal forces in the members of the structures. The process of analysis commences with planning of a structure, primarily to meet the functional requirement of the user. Planning a structure involves the selection of the most suitable type of structure and the choice of its general layout and overall dimension on the basis of economic, aesthetic, functional and other criteria. Designing a structure entails determining the disturbances to which it is expected to be exposed during its life time and then choosing the dimensions of its members as well as the details of their connections. The structure is then analyzed, i.e., the internal forces and moments in its members and the displacements of some of its cross sections are computed. The member of structure must have sufficient strength and rigidity so that when the structure subjected to the disturbances to which it is expected to be exposed, the components of stress and displacement at any of its point do not exceed the maximum allowable values given in the appropriate design course. If the results of the analysis show that the members of the structure do not have sufficient strength and rigidity to satisfy the aforementioned requirements the structure is redesigned, i.e., new dimensions of cross section are chosen. The process is repeated until the structure is obtained which satisfies all the aforementioned requirements. 1.2 Flat Slab Common practice of design and construction is to support the slabs by beams and support the beams by columns. This may be called as beam-slab construction. The beams reduce the available net clear ceiling height. Hence in warehouses, offices and public halls sometimes beams are avoided and slabs are directly supported by columns. These types of construction are aesthetically appealing also. These slabs which are directly supported by columns are called Flat Slabs. Fig -1: Typical Flat Slab (Without column head and drop) The column head is sometimes widened so as to reduce the punching shear in the slab. The widened portions are called column heads. The column heads may be provided with any angle from the consideration of architecture but for the design, concrete in the portion at 45º on either side of vertical only is considered as effective for the design. Fig -2: Slab without drop and column with column head Moments in the slabs are more near the column. Hence the slab is thickened near the columns by providing the drops as. Sometimes the drops are called as capital of the column. Thus we have the following types of flat slabs. Fig -3: Slab with drop and column without column head (i) Slabs without drop and column with column head (ii) Slabs without drop and column without column head (iii) Slabs with drop and column with column head Flat-slab building structures possesses major advantages over traditional slab-beam-column structures because of the free design of space, shorter construction time, architectural –functional and economical aspects. Because of the absence of deep beams and shear walls, flat-slab structural system is significantly more flexible for lateral loads then traditional RC frame system and that make the system more vulnerable under seismic events. The system consists of columns resting directly on floor slabs for which sufficient strength and ductility should be provided to enable sustaining of large inelastic deformations without failure. The absence of beams, i.e., the transferring of their role to the floor RC structure which gains in height and density of reinforcement in the parts of the hidden beams, the bearing capacity of the structural system, the plate-column and plate-wall connection, all the advantages and disadvantages of the system have been tested through long years of analytical and experimental investigations. For the last 20 to 30 years, the investigations have been directed toward definition of the actual bearing capacity, deformability and stability of these structural systems designed and constructed in seismically active regions.
  • 3. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 441 A flat slab is a highly indeterminate structure and its exact analysis is difficult. An approximate analysis can be made by considering an interior panel of slab. IS456-2000 provides an empirical approach Direct Design Method and Equivalent Frame Analysis for the analysis of flat slab. Via Direct Design Method this it’s easy to calculate bending moment and shear force in flat slab without use of computer. But the Equivalent Frame Analysis gives more exact results. The behaviour and design of flat slabs structures for gravity loads are well established but their seismic behaviour is not well understood and generally found to be unsatisfactory. Flat slab is susceptible to progressive brittle punching shear failure under seismic loading. In flat slab building the most vulnerable part is slab-column joint. Flat slabs with drop panels or column capitals are generally constructed as these extra projections provide safety against punching shear and also reduce the heavy negative moment. If drop panels are not provided then the system is termed as Flat Plate. Extensive research has been carried out to find out the behaviour of slab-column connection. The failure mode depends upon the type and extent of loading. Punching shear strength of slab-column connection is of importance which very much depends on the gravity shear ratio. The mechanism of transfer of moments from slab to column is very complex when subjected to lateral loading and unbalance moments. These unbalanced moments produce additional shear and torsion at the connections and then get transferred into the column which results in excessive cracking of slab leading to further reduction in the stiffness of the slab. A flat-plate structure, as shown in Figure 4, consists of a slab with uniform thickness supported on the columns with no beams or drop panels. The economy of flat plate buildings has lead to their wide spread utilization throughout the world. Conventionally flat-plate structure is generally used for lightly loaded structures such as apartments, hotels, and office buildings with relatively short spans, typically less than 6m. For longer spans or heavier loads, flat-slabs system with shear capitals or drop panels would be more feasible. Fig -4: Flat-plate structure Flat-plates have been widely used due to the reduced construction cost associated with the simple formwork and simple arrangement of flexural reinforcement. An additional advantage of a flat-plate is reduced building storey heights that result in more usable space in a building for a given or limited height and reduces lateral loads acting on the system, as well as mechanical, electrical, and cladding costs. 2. OBJECTIVES The objectives of the study are:  The main objective of the analysis is to study the different forces acting on a building. The analysis is carried out in ETABS 9.7.4. Software. Results of conventional R.C.C structure i.e. slab, beam and column and flat slab R.C.C structure for different heights are discussed below.  Conventional R.C.C structure and flat slab R.C.C for different height are modeled and analyzed for the different combinations of Dynamic loading. The comparison is made between the conventional R.C.C structure and flat slab R.C.C. Buildings are situated in seismic zone IV.  To study the vulnerability of purely frame and purely flat-slab models under different factors which are Storey drift, lateral displacement, time period and base shear have been obtained for SPECX (EX) and SPECY (EY) in zone IV. The axial load and moments in columns have been obtained for various load combination in zone IV. 3. BUILDING DETAILS, PROGRAM AND PRELIMINARY DESIGN Fig -5: Plan of the Commercial building Following are details of the number of floors considered in both RC frame and Flat slab building that have taken up for the analysis and design.  Model 1 and 2 : Four storey (i.e. G+3)  Model 3 and 4 : Nine storey (i.e. G+8)  Model 5 and 6 : Thirteenth storey(i.e. G+12) 6000 6000 6000 6000 6000 60006000600060006000 PROPOSED LAYOUT PLAN OF COMMERCIAL BUILDING
  • 4. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 442 The height of each floor is 3.0m. The total height of Ground plus three, eight and twelve storey building is 12.0 m, 27.0 m and 39.0 m. The plinth beam is provided above the ground at the height of 1.5m from below ground level. 3D Models of RC frame and flat plate for Ground plus three, eight and twelve storey buildings is shown in figure 6 to 11 Fig -6: Model 1: 3D of RC Frame of G+3 storey building Fig -7: Model 2: 3D Model of flat plate of G+3 storey building Fig -8: Model 3: 3D Model of RC frame of G+8 storey building Fig -9: Model 4: 3D Model of flat plate of G+8 storey building Fig -10: Model 5: 3D Model of RC frame of G+12 storey building Fig -11: Model 6: 3D Model of flat plate of G+12 storey flat plate building 3.1 Preliminary Sections The preliminary sections of columns and beams have been fixed on the basis of deflection criteria [i.e. span to depth ratio]. The sections were found to be satisfactory for the given loads for a four storey model. These sections were maintained uniform throughout the height. Similarly, all other models, nine and thirteenth stories, were analyzed and designed to meet the current Codes (IS 456:2000 and IS 1893:2002) and their structural member sizes chosen for the study are given in below Table
  • 5. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 443 Table -1: Sizes of structural element Sl No Name of element Width (mm) Depth (mm) 1 Column (floor & roof) for four, eight and thirteenth storey 350 350 2 Beam (floor & roof) for four, eight and thirteenth storey 300 600 3 Slabs for both four; eight and thirteenth storey 200 3.2 Materials The Young’s modulus of elasticity of concrete was 35,000 MPa while the Poisson’s ratio was 0.2. The densities were 22 kN/m3 and 25 kN/m3 for solid concrete block and concrete members respectively. For structural components M 35and Fe 500 grade was considered. 3.3 Positions and Orientation of Columns Figure 12 shows the position and orientation of columns and beams. The building consists of 36 columns. The orientations of member are chosen so that maximum moment of inertia is achieved. Fig -12: Position of the columns Fig -13: Layout Plan of the Conventional frame Building Fig -14: Layout Plan of the Flat plate Building 3.4 Program The program consists of analyzing each of the multi-storey buildings by using ETABS 9.7.4. In particular, the effects of following with respect to the behaviour of columns, drift, displacement, time period have been studied.  Flat plate (FP)  Height of the buildings  Convention RC frame (CF) 4. ANALYSIS OF THE BUILDING 4.1 Loads Considered: Dead Load: The loads realized due to the following has been considered  Self weight of structural members  Wall load  Unknown partition  Floor finish The self weight of the members is calculated by assuming the density as 25 kN/m3 and 22 kN/m3 for concrete and solid concrete block. Grade of Concrete is M35 and Grade of Steel (Fy) is Fe500. The self weight of slab =0.2 x 1 x 1 x 25 = 5 kN/m2 Load due to Unknown partition =1 kN/m2 Load due to floor finish= 1 kN/m2 Load due to wall: 0.2x (3.0-0.6) x22 = 10.56 kN/m2
  • 6. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 444 Live Load Live load on floor slab and roof: 4kN/m2 . Allowance for the reduction in live load is considered for determining the column moments. Earthquake Load This load has been taken into account by specifying the zone in which the building is located. Table 2 shows the details of the earthquake parameters as the earthquake zone is concerned. Table -2: Earthquake Parameters Zone (Z) IV Response Reduction Factor (RF) 5 Importance Factor (I) 1 Rock and Soil Factor (SS) 2 Type of structures 1 Damping Ratio (DM) 0.05 Time Period Ta=0.075h0.75 4.2 Load Combinations: The following combination of loads with appropriate partial safety factor satisfying the Indian standard code provision i.e. IS456:2000, table 18, clause 18.2.3.1 and IS 1893:2002, clause6.3.2.1 are as follows, 1.5[DL + LL] 1.2[DL + LL+SPECX] 1.2[DL + LL+ SPECY] 1.2[DL + LL - SPECX] 1.2[DL + LL - SPECY] 1.5[DL + SPECX] 1.5[DL + SPECY] 1.5[DL - SPECX] 1.5[DL - SPECY] 0.9[DL] + 1.5[SPECX] 0.9[DL] + 1.5[SPECY] 0.9[DL] - 1.5[SPECX] 0.9[DL] -1.5[SPECY] Fig -15: Storey Shear of EQX for Flat plate (Typical) Fig -16: Storey Shear of Specx for Flat plate (Typical) Fig -17: Displacement of Flat plate Fig -18: Storey Shear of EQX for conventional Frame (Typical)
  • 7. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 445 Fig -19: Storey Shear of Specx for conventional Frame (Typical) Fig -20: Displacement of conventional frame Fig -21: Column axial load (Typical) Fig -22: Slab moments along Mx for Conventional frame System Fig -23: Slab moments along Mx for Flat plate System 5. RESULTS AND DISCUSSION The forces and displacements developed in each of the members of the structure are got from the analysis. These results obtained from the analysis have been discussed detail in this chapter. Further these results have been used for the understanding of the behaviour of the structure between the conventional RC frames and flat plate under the effects of lateral loads. 5.1 Column Moments The critical columns i.e. type I have been chosen for the study. Chart 1-7 shows the details of the column moments and axial load obtained for columns. Chart 1-7 represents the column results obtained for the structures which are subjected to lateral loads only. The lateral load analysis for flat plate is done to compare the same with that of Conventional RC frame. From the lateral load analysis results it can be observed that in four storey building the moments (Mz) is maximum at first and terrace level for types I of column. Thus a column at first and terrace level attracts maximum steel as compared to the other positions. From the results it can be observed that the column moment for flat plate analysis is more than that of the column moments of conventional RC frame analysis in zone IV. The difference between the two varies from 15 to 25(%). From the lateral load analysis results it can be observed that in nine storey building the moments (Mz) is maximum at
  • 8. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 446 second level for types I of column. Thus a column at second level attracts maximum steel as compared to the other positions. From the results it can be observed that the column moment for flat plate analysis is more than that of the column moments of conventional RC frame analysis in zone IV. The difference between the two varies from 15- 20(%). From the lateral load analysis results it can be observed that in thirteenth storey building the moments (Mz) is maximum at plinth and first level for types I of column. After second level the moment’s decreases and increases as the height of the building increases. Thus a column at plinth and first level attracts maximum steel as compared to the other positions. From the results it can be observed that the column moment for flat plate analysis is more than that of the column moments of conventional RC frame analysis in zone IV. The difference between the two varies from 15- 30(%). From the lateral load analysis results it can be observed that, the axial load is more in flat plate compared to conventional RC frame. The difference between the two varies up to 10(%).For all columns the columns have been designed for the combination of dead load and earthquake load this shows that earthquake combination is the worst combination giving rise to the most critical sections. Earthquake is more predominant than other loads. The behaviour of column moments changes as the height of the building increases. Height of the Building The effect of height of the building is studied by considering a thirteenth storey building. This study has been made for conventional RC frame and flat plate. The results have been represented in Chart 1-7. From the Charts it can be observed that at level plinth, first, second and terrace the moments are maximum in the column is most critical. Further after level 2 as the height increases the column moments criticality decreases and increases at the top storey. The base shear, time period, displacement and storey drift increases drastically as the height increases Chart -1: Design moments, three storey building Subjected to vertical loads Chart -2: Design moments, nine storey building Subjected to vertical loads Chart -3: Design moments, thirteen storey building Subjected to vertical loads Chart -4: Axial force, four storey building Subjected to vertical load 0 50 100 150 200 250 300 ColumnMoments(Mz)kN-m Storey Storey Vs Column Moments (Mz) CFG+3 FPG+3 0 200 400 600 800 1000 1200 TERRACE 8 7 6 5 4 3 2 1 PLINTH Columnments(Mz)kN-m Storey Storey Vs Column Moments(Mz) CFG+8 FPG+8 -300 -200 -100 0 100 200 300 400 500 PLINTH 1 2 3 4 5 6 7 8 9 10 11 12 TERRACE ColumnMoments(Mz)kN-m Storey Storey Vs Column Moments (Mz) CFG+12 FPG+12 0 2000 4000 6000 8000 10000 AxialLoadinkN Storey Storey Vs Column Axial Force (Pu) CFG+3 FPG+3
  • 9. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 447 Chart -5: Axial force, thirteen storey building Subjected to vertical loads Chart -6: Axial force, nine storey building Subjected to vertical loads Chart -7: Axial force, four, nine and thirteen storey building Subjected to vertical loads 5.2 Storey Shear The results have been represented in Chart 8-11. From the Chart it can be observed that the base shear is maximum at plinth level for all types of column. After plinth level the base shear decreases as the height of the building increases. Due to the symmetric of the building the base shear will same in both directions (Vx and Vy). Chart 8-11 it can be observed that, the base shear will increase drastically as the height increases. Base shear of flat plate building is less than the conventional R.C.C building. The difference between the two varies from 8 to 12(%) Chart -8: Effect of storey shear on behaviour of column of four storey building Chart -9: Effect of storey shear on behaviour of column of nine storey building 0 5000 10000 15000 20000 25000 30000 TE… 12 11 10 9 8 7 6 5 4 3 2 1 PLI… AxialLoadinkN Storey vs Column Axial force CFG+12 FPG+12 Storey 0 5000 10000 15000 20000 AxialLoadinkN Storey Storey Vs Column Axial Force (Pu) CFG+8 FPG+8 0 5000 10000 15000 20000 25000 30000 G+3 G+8 G+12 AxialLoadinkN No of Story No of Storey Vs Axial Force Convnetion Frame Flat Plate 0 500 1000 1500 2000 2500 3000 3500 StoreyshearkN Storey Storey Vs Storey Shear CFG+3 FPG+3 0 500 1000 1500 2000 2500 3000 3500 4000 PLINTH 1 2 3 4 5 6 7 8 TERRA… StoryshearkN Story Storey Vs Story Shear CFG+8 FPG+8
  • 10. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 448 Chart -10: Effect of storey shear on behaviour of column of thirteen storey building Chart -11: Effect of storey shear on behaviour of column of four, nine and thirteen storey building 5.3 Lateral Displacement The results have been represented in Chart 12-15. From the Chart it can be observed that the lateral displacement (both Ux and Uy) is maximum at terrace level for all types of column. Lateral displacement increases as the storey level increases. Lateral displacement will be minimum at plinth level and maximum at terrace level. Due to the symmetric of the building the lateral displacement will be same in both directions (Ux and Uy). From Chart it can be observed that, the lateral displacement will increase drastically as the height increases. Lateral displacement of conventional R.C.C building is less than the flat plate building. The difference between the two varies from 28 to 57(%). Chart -12: Effect of lateral displacement on behaviour of column of fourth storey building Chart -13: Effect of lateral displacement on behaviour of column of nine storey building Chart -14: Effect of lateral displacement on behaviour of column of thirteen storey building 0 500 1000 1500 2000 2500 3000 3500 4000 4500 PLI… 1 2 3 4 5 6 7 8 9 10 11 12 TER… StoreyshearkN Storey Storey Vs Storey Shear CFG+12 FPG+12 0 10000 20000 30000 40000 50000 60000 70000 80000 G+3 G+8 G+12 StoryShearikN No of Story No of Storey Vs Story Shear Convnetion Frame Flat Plate 0 10 20 30 40 50 60 LateralDisplacmentinmm Storey Storey vs Lateral Displacement CFG+3 FPG+3 0 10 20 30 40 50 60 70 80 LateralDisplacmentinmm Story Storey Vs Lateral Displacement CFG+8 FPG+8 0 20 40 60 80 100 120 140 PLINTH 1 2 3 4 5 6 7 8 9 10 11 12 TERRA… LateralDisplacmentinmm Storey Storey Vs Lateral Displacement CFG+12 FPG+12
  • 11. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 449 Chart -15: Effect of lateral displacement on behaviour of column of four, nine and thirteen storey building 5.4 Time Period The results have been represented in Chart 16-19. From the Chart it can be observed that the time period (both Tx and Ty) is maximum at mode 1 and 2. The natural time period increases as the height increases (No of stories). Due to the symmetric of the building the time period will be same in both directions (Tx and Ty). From Chart 19 it can be observed that, the time period will increase drastically as the height increases. In comparison of the conventional R.C.C building and flat slab building, the time period is more for flat slab building than conventional building. The difference between the two varies from 14 to 33(%). Chart -16: Effect of time period on behaviour of modes shapes on fourth storey building Chart -17: Effect of time period on behaviour of modes shapes on nine storey building Chart -18: Effect of time period on behaviour of modes shapes on thirteen storey building Chart -19: Effect of time period on behaviour of modes shapes on fourth, nine and thirteen storey building 5.5 Storey Drift The results have been represented in Chart 20-23. From the Chart it can be observed that the storey drift (both Ux and Uy) is maximum at second level for all types of column. After second level the storey drift decreases as the height of the building increases. Due to the symmetric of the building the lateral displacement will be same in both directions (Ux and Uy). From Chart it can be observed that, the storey drift will increase drastically as the height increases. Storey drift in building with flat slab construction is significantly more 0 20 40 60 80 100 120 140 G+3 G+8 G+12 LateralDisplacementinmm No of Story No of Storey Vs Lateral Displacemenet Convnetion Frame Flat Plate 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1 2 3 4 5 6 7 8 9 10 11 12 TimeperiodinSec No of Modes No of Modes Vs Time Period in Sec CFG+3 FPG+3 0 0.5 1 1.5 2 2.5 3 1 2 3 4 5 6 7 8 9 10 11 12 TimeperiodinSec No of Modes No of modes Vs Time Period CFG+8 FPG+8 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1 2 3 4 5 6 7 8 9 10 11 12 TimeperiodinSec No of Modes No of Modes Vs Time Period CFG+12 FPG+12 0 1 2 3 4 G+3 G+8 G+12 TimePeriodinSec No of Story No of Storey Vs Time Period Convnetion Frame Flat Plate
  • 12. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 450 as compared to conventional R.C.C building. As a result of this, additional moments are developed. Therefore, the columns of such buildings should be designed by considering additional moments caused by the drift. The difference between the two varies from 28-60(%). Chart -20: Effect of storey drift on behaviour on fourth storey building Chart -21: Effect of storey drift on behaviour on nine storey building Chart -22: Effect of storey drift on behaviour on thirteen storey building Chart -23: Effect of storey drift on behaviour on four, nine and thirteen storey building 6. CONCLUSIONS This study presents a summary of the project work, for conventional R.C.C building and flat slab building for different floor height in the seismic region. The effect of seismic load has been studied for the two types of building with different height. On the basis of the results following conclusions have been drawn: 1. The moment is maximum at plinth, first and second level. After second level moments decreases and increases at the top storey. 2. The column behavior changes as height of the building increases. 3. The columns have been designed for the combination of dead load and earthquake load for all cases and the load combination 1.5[DL±EX] is the most critical. 4. The column moments are more in flat plate compared to conventional R.C.C building. 5. Column moments in flat plate vary from 10 to 20 (%) as compared to that of conventional R.C.C frames depending upon the storey. 6. The base shears is maximum at plinth level for all types of column. After plinth level the base shear decreases as the height of the building increases. The base shear will increase drastically as the height increases. Base shear of flat plate building is less than the conventional R.C.C building. The difference between the two varies from 8- 13(%). 7. The lateral displacement (both Ux and Uy) is maximum at terrace level for all types of column. Lateral displacement increases as the storey level increases. The lateral displacement will increase drastically as the height increases. Lateral displacement of conventional R.C.C building is less than the flat plate building. The difference between the two varies from 28-57(%). 8. The natural time period increases as the height increases (No of stories). 9. In comparison of the conventional R.C.C building and flat slab building, the time period is more for flat slab building than conventional building. The difference between the two varies from 14-33(%). 10. The time period will be maximum at mode 1 and 2. After mode 2, time period will reduce drastically. 0 0.001 0.002 0.003 0.004 0.005 0.006 StoreyDrift Storey Storey Vs Storey Drift CFG+3 FPG+3 0 0.001 0.002 0.003 0.004 0.005 PLINTH 1 2 3 4 5 6 7 8 TERR… StoreyDrift Storey Storey Vs Storey Drift CFG… FPG… 0 0.0005 0.001 0.0015 0.002 0.0025 0.003 0.0035 0.004 0.0045 0.005 PLI… 1 2 3 4 5 6 7 8 9 10 11 StoreyDrift Storey Storey Vs Storey Drift CFG+12 FPG+12 0 0.001 0.002 0.003 0.004 0.005 0.006 G+3 G+8 G+12 Drift No of Storey No of Storey Vs Drift Convnetion Frame Flat Plate
  • 13. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 08 | Aug-2014, Available @ http://www.ijret.org 451 11. The storey drift (both Ux and Uy) is maximum at second level for all types of column. After second level the storey drift decreases as the height of the building increases. 12. Storey drift in building with flat slab construction is significantly more as compared to conventional R.C.C building. As a result of this, additional moments are developed. Therefore, the columns of such buildings should be designed by considering additional moments caused by the drift. The difference between the two varies from 28-60(%). 13. The earthquake forces is more predominant than others loads. 14. Lateral displacement will be minimum at plinth level and maximum at terrace level SCOPE OF FUTURE STUDIES 1. The structure can be compared with post tensioned slab designed methods 2. The structure behaviour different Seismic zones and its Behaviour of Buildings having Flat Slabs with Drops. 3. The structure can be analysed with effect of Shear Wall, REFERENCES 1. Agarwal. P. and Shirkhande.M, “Earthquake resistant Design of Structures” Printice- Hall of India Private Ltd. New Delhi, India. 2. Alpa Sheth“Effect of perimeter frames in seismic performance of tall concrete buildings with shear wall core and flat slab system” The 14th World Conference on Earthquake Engineering October 12-17, 2008, Beijing, China. 3. Apostolska1 R.P and Necevska-Cvetanovska G. S, “Seismic performance of flat-slab building structural systems” The 14th World Conference on Earthquake Engineering October 12-17, 2008, Beijing, China. 4. Bhavikatti S.S, “Advance R.C.C. Design” , New Age International (p) Limited, Publishers, New Delhi, India. 5. Ema COELHO, Paulo CANDEIAS, Raul ZAHARIAand Artur V. PINTO, “Assessment of the seismic behavior of R C flat slab building structures”, 13th World Conference on Earthquake Engineering Vancouver, B.C., Canada August 1-6, 2004 Paper No. 2630 6. Garg c.s, Yogendrasingh, Pradeep Bhargava and Bhandari N.M, “Seismic performance of flat slab shear wall system”, Journal of structural Engineering, Vol.37, No.3, August-September2010, PP.203-207. 7. Lan N .Robertson, “Analysis flat slab structures subjected to combined lateral and gravity load”, ACI Structural Journal. 8. Pankaj Agarwal and Manish Shrikande (2007), “Earthquake Resistant Design of Structures”, Prentice Hall of India Private Limited, New Delhi, India. 9. Shyh-jiann Hwang and Jack p. moehle, “Models for laterally loaded slab-column frames”, ACI Structural Journal, March-April 2000. 10. IS: 456:2000, “Indian Standard Code for Plain and Reinforced Concrete”, Bureau of Indian Standards, New Delhi. 11. Prof. K S Sable, Er. V A Ghodechor, Prof. S B Kandekar,“ Comparative Study of Seismic Behavior of Multistorey Flat Slab and Conventional Reinforced Concrete Framed Structures”, Volume 2, Issue 3, June 2012 BIOGRAPHIES Mrs. Navyashree K resident of Mysore received her degree in Civil Engineering from NIE, Mysore in the year August 2010. Mrs. Sahana T.S (Asst.Professor) received her M.E (Pre-stressed concrete) from Banglore University. Her area of interest includes Earthquake engineering and Dynamics of Structures. She has 5 years of teaching experience.