Evaluation of the Thermal Performance of Light Roofing Systems
Mrs.M.Ponni1,
Dr.R.Baskar2
1
Research Scholar, 2
Associate professor Department of Civil and Structural Engineering,
Annamali University, Chidambaram-608001, Tamil Nadu, India.
ABSTRACT: Thermal performance of roofs exerts a powerful influence on indoor ambienttemperature.
Thermal gain by single storey houses covered by light roofs is enormous during the peak hours of the day,
which offers thermal shock to the occupants and necessitates high cooling energy demand. This paper presents
a new design for light roofing structure in order to improve the indoor environment. Industrial buildings, ware
houses, workshops and Lower economic group people use the light roof sheets as a roof material. Light roofs
are in the form of Galvanized sheets, Asbestos sheets, and Cool roofs. Higher indoor ambient temperature of
industries leads to fatigue of workers which causes a lower labour productivity. To enhance the labour
productivity, improved indoor environment should be provided. Five different modules are constructed with
identical floor plan and orientation but with different materials for walls and roofs. Single Decker (SID),
Overall Galvanised Sheet (OGS), Overall Asbestos sheet (OAS), Double Decker (DOD), and Poly Urethane
Decker (PUD) are the modules used for this study. The modules utilize no energy for cooling. Effort has been
engaged to fetch a best indoor environment by the roof among the selected modules.
KEYWORDS: Thermal performance, Indoor ambient temperature, Indoor relative humidity, Double
Decker.
I. INTRODUCTION
Energy crisis and Environmental impact is serious, with the development of the world economy. The
fossil fuel is depleting. More than 30% of primary energy is consumed by non-industrial buildings, including
houses, offices, schools, hospitals, and so on [1]. Energy consumed in the production of building materials is
20% of the world fuel consumption. It demands immediate action to develop energy efficient buildings.
The total electrical energy consumed by Indian buildings is 33%. If the Energy Conservation code is enforced
for the construction work, it will yield annual savings approximately 1.7 KWH. Estimates based on computer
simulation models can use 40 – 60% less energy than conventional buildings. The efficiency of a building
strongly depends on the way it is built, managed and used and furthers the selection of roof according to the
purpose apart from the wall and floor plans and the orientation of the building. [2], India has been divided into
five major climatic zones, Cold and Sunny, Cold and Cloudy, Warm and Humid, Hot and Dry, Composite and
Moderate. According to the classification, India is a quite challenging country to the planners, designers and
architects. The human body continuously produces heat by its metabolic processes. This heat must be dissipated
to the environment, or else the body temperature will increase. The body’s thermal balance can be expressed as:
S = M ± Rd ±Cv± Cd – Ev (1)
Where,
S = Change in stored heat, M = metabolic heat production,Rd = net radiation exchange, Cd= conduction
Cv=Convection including respiration,Ev = evaporation including respiration. At equilibrium condition, (S) is
zero, and such equilibrium is a precondition of thermal comfort at the 50% RH and less than 0.15m/ airflow
speed. The comfort band of room temperature is 18˚C – 27˚C [3]. The comfort band of room temperature
is 26˚C – 32.5 ˚C and the relative humidity ranges between 17% - 78% from a field study in Hyderabad,
India[4].Roof is the element which directly receives the most of the solar radiation in different angles than the
other elements of the building. Inadequate roof insulation results in heat transfer from the roof to indoor.
Insulation can be applied between roof rafters or on the rafters. For concrete roofs, outer insulation over the
concrete can be applied [5].
Indian concrete roofs, with 150mm of concrete and 75-100mm of weathering course transfers 50-70%
of heat in to the occupant zone. High reflective coatings can reduce 20-70% heat transfer [6].The heat incoming
into the occupant zone through roof is the main cause of discomfort [7]. The heat transferred into the occupant
zone is true for single storey and top floor of the multi-storeyed buildings [8].Traditional architecture in hot
climates has long recognised that the building colours can reduce cooling loads[9], [10]. A series of simulation
and experimental studies have demonstrated that building reflectance can significantly impact cooling needs
[11], [12], [13], [14].
Evaluation of the Thermal Performance...
www.ijesi.org 27 | Page
The impact of reflective roofing’s on the air conditioning use in Florida and California building field
tests have shown that there is electrical energy savings [15]. Beyond roof reflectance other approaches such as
tile roofs and unvented attics with insulation under the roof can produce cooler attics resulting in energy
improvement, but of unknown comparative magnitude [16], [17]. The attic heat gain to the thermal
distribution system can increase residential cooling loads by up to 30% during peak summer periods [18].
Further benefits arise from the reduction of attic air temperature and its impact on ceiling conductivity [19]. The
selection of roof with high solar reflectance represents one of the most significant energy saving options in hot
climates [20].The cooling energy savings due to the application of heat island mitigation strategies have
calculated (application of cool materials and increase in vegetation cover) for 240 regions in the United States. It
was found that for residential buildings the cooling energy savings vary between 12% and 25%, for office
buildings between 5% and 18%, and for commercial (retail stores) buildings between 7% and 17%[21].
Even though, some advanced cool coloured materials have been available along with NIR reflective pigments to
cool the roof estimated the effect of cool coating on thermal comfort and stated that increasing the roof solar
reflectance reduces the cooling load by 18-93% and the indoor thermal comfort is improved by decreasing the
hour of discomfort by 9-100%[22]. Light colour coating may help to reduce 30% total heat gain in the weather
condition of Australia since the roofing may have much lower absorptivity[23]. Even though the above
methods are more suitable in reducing the heat gain to the Room, the cost incurred for the making such a roof
should be considered. The initial cost associated for making the green roof is higher and it is difficult to
maintain properly. It also requires stronger roof beam to support the various roof layers of the green roof. Also
in the roof with roof coating, the detritions of roof coating over the time are a Major setback. The settlement of
dust over the roof coating may completely spoil the performance of the roof coating [1]. With all these
information present work proposes and analyses a new type of roof DOD to reduce the indoor heat gain.
II. RESEARCH DESCRIPTION
Previous research efforts have investigated the thermal performance of various roofing systems. In this
study an attempt has been made to quantify the roofing influence on cooling performance of the five modules
and the living comfort of the occupants. All the modules have same floor, wall area and orientation. The size of
the module is 3mx 3m x 3m. The galvanized sheets used in the modules have the same thickness of 0.35 mm.
The walls have a thickness of 230 mm made up of brick. Two angles are used as purlins. The slope of the roof is
maintained to be 2˚. Walls of the modules are white washed and the flooring is done with cement mortar.
The first module is Single Decker (SID) in which galvanized sheets are used as roof material. The second
module is overall galvanized sheet module (OGS), in which roof and walls use the galvanized sheets. The third
module is overall Asbestos sheet module (OAS) in which asbestos sheets is used for the roof and the wall. The
fourth module is double decker (DOD) in which wooden insulators and mineral wool is used between two
galvanized sheet roofs. Brick walls are used for SID, DOD and PUD modules. The fifth module is poly
urethane decker (PUD) module in which poly urethane panels are used as roof material.
The construction data of the modules used in this study are tabulated in Table I.
Table I: Construction data of the Research Modules
2.1 First Module (SID)
In Single Decker, Galvanized sheets are used as roof element, where the walls are made by bricks.
When the solar radiation falls on the roof, the sheets are very easily heated even by early morning due to
conduction and it extends for the whole day. During the peak hour the amount of heat transmitted into the
building is massive.
2.2 Second Module (OGS)
The roof and wall of the OGS module is constructed with Trapezoidal shape Galvanized sheets. This
roofing is adopted by the industries, workshops, warehouses and is also followed by the Low economy Group
Sl. No Description Dimension
1 Floor Area 100 sq.ft
2 Net Wall Area 382 sq.ft
3 Ceiling 120 sq.ft
4 Doors 18 sq.ft
5 Overhang 20 sq.ft
Evaluation of the Thermal Performance...
www.ijesi.org 28 | Page
community because of its light weight, easiness in construction and low cost. Being a conductor the sheets
easily permit solar radiation into the occupant zone not only through the roof but also via walls.
2.3 Third Module (OAS)
The third module is constructed by using trapezoidal Asbestos sheets for the roof and wall. Though
asbestos is banned by developed countries, but it is used still in India. This type of roof too allows the solar
radiation into the occupant zone through the roof and walls.
2.4 Fourth Module (DOD)
Design of Double roof is carried out in three steps. In the first step, roof is made using galvanised
sheets by setting the second roof over the first and named as Double Decker (DOD) as shown in (Fig1). In the
double decker the sheets of first roof have contact with the second roof on longitudinal lines and hereafter called
lines of contact. At this condition the shape of the double roof is similar to that of a Stationery wave. In a
stationary wave there are nodes and antinodes. Nodes have zero displacement where antinodes have a maximum
displacement of the particles of the medium. The nodes of a stationery wave are identical with the lines of
contact of double roof. As the area of contact between the two roofs is decreased, the heat transmitted into the
dwelling by conduction is also reduced to about 70%. Cylindrical air gap of 22 mm thickness is formed between
the two lines of contact. In the second step, wooden reapers, of size 3000mm x50 mm x 25 mm are introduced
between the two roofs (Fig2) in 200 mm spacing, consequently the two roofs are separated by 50 mm and
separation of two roofs ranges from 50 mm to 72 mm. In the third step, mineral wool roll of thickness 50 mm is
spread over the wooden reapers and the second roof is made (Fig 3). Now the two roofs are separated by a
thickness of 100 mm to 122 mm. The wooden reapers and the mineral wool are the insulators where they
prevent direct heat transmission by conduction and further the air flow between the gaps reduce heat by
convection.
Figure 1: Diagram of the Double roof
Figure 2: Diagram of the Double roof with wooden reaper
Figure 3: Diagram of double roof with wooden reaper and Mineral wool
2.5 Fifth Module(PUD)
Polyurethane panels of length 3660 mm and breadth 1000 mm used as roof for the fifth module, which
is an industrial product. The half white painted reflective steel sheets of thickness 0.47 mm and the poly
urethane thickness is 35 mm is used by the industry, to make the panels. One side of the surface shape is
trapezoidal and the other side is plain.
Evaluation of the Thermal Performance...
www.ijesi.org 29 | Page
III. EXPERIMENTAL PROCEDURE
The experiments were carried out in Chidambaram, Tamil Nadu, 11˚24´N latitude and longitude
79˚44´E.The location is characterized by hot and humid weather. The modules, used in this study are exactly
identical in terms of their geometry, orientation, area and climate conditions. SID, OGS, DOD, PUD are
reflective roof material but OAS is not a reflective roof material.All the modules are fully instrumented. To
measure the Indoor Ambient Temperature and Relative Humidity Single channel data logger is used. In six
hours interval (6, 12, 18hr) the roof, wall and floor temperatures are measured by means of Infra-Red
Thermometer. The night time temperature does not increase in the hot and humid climates under normal
conditions hence the temperature measurement for 24th hour is not included. Roof, wall, floor and indoor and
outdoor ambient temperature and relative humidity field data have been catalogued for seven months for five
different roofing systems exposed to weathering on an indoor and outdoor test facility. The data are plotted for
the time period between September and March.
IV. RESULTS AND DISCUSSION
At peak hour, the Average Roof Temperatures of DOD, SID, OAS, OGS and PUD in winter were
26.50˚C, 33.77˚C, 39.20˚C, 44.21˚C and 27.40˚C and further in the early spring the values were 31.59˚C,
37.70˚C, 49.19, 57.33˚C and 34.03˚C are shown in Fig. 4. In winter the DOD is 7.27˚C cooler than SID, and
12.7˚C cooler than OAS, and 17.71˚C cooler than OGS and 0.9˚C cooler than PUD. In the early spring the
DOD is 6.11˚C cooler than SID, and 17.6˚C cooler than OAS, and 25.74˚C cooler than OGS and 2.44˚C cooler
than PUD. The Average Roof Surface Temperature profiles over the monitoring period are shown in Fig. 4. It is
obvious that OGS module gains the highest temperature during both the seasons and the DOD module gains the
lowest value and the PUD gains a moderate value.
Figure 4: Average Roof temperature of 12 Noon
At peak hour, the Average Floor Temperatures of DOD, SID, OAS, OGS and PUD in winter were
25.31˚C, 26.16˚C, 31.76˚C, 31.97˚C and 25.83˚C and further in the early spring the values were 28.74˚C,
31.26˚C, 35.65˚C, 36.65˚C and 29.94˚C are shown in Fig. 5. In inter the DOD is 0.85˚C cooler than SID, and
6.45˚C cooler than OAS, and 6.66˚C cooler than OGS and 0.52˚C cooler than PUD. In the early spring the
DOD is 2.52˚C cooler than SID, and 6.91˚C cooler than OAS, and 7.91˚C cooler than OGS and 1.20˚C cooler
than PUD. The Average Floor Temperature profiles over the monitoring period are shown in Fig. 5. It is
observed that OGS module has the highest floor temperature in both seasons, the DOD module has a lower
value than others and the PUD module has a moderate value.
Figure 5: Average Floor temperature of 12 Noon
Evaluation of the Thermal Performance...
www.ijesi.org 30 | Page
At peak hour, the Average Wall Temperatures of DOD, SID, OAS, OGS and PUD in winter were
25.58˚C, 26.69˚C, 35.40˚C, 38.23˚C and 26.17˚C and further in the early spring the values were 30.59˚C,
32.30˚C, 39.80, 42.95˚C and 31.04˚C are shown in Fig. 6. In winter the DOD is 1.11˚C cooler than SID, and
9.82˚C cooler than OAS, and 12.65˚C cooler than OGS and 0.59˚C cooler than PUD. In the early spring the
DOD is 1.71˚C cooler than SID, and 9.21˚C cooler than OAS, and 12.36˚C cooler than OGS and 1.20˚C cooler
than PUD. The Average Wall Temperature profiles over the monitoring period are shown in Fig. 6. The average
wall temperature is high for OGS and low for DOD and moderate for PUD.
Figure 6: Average Wall Temperature of 12 Noon
At peak hour, the average Indoor Ambient Temperatures of DOD, SID, OAS, OGS and PUD in winter
were 26.37˚C, 27.57˚C, 33.26˚C, 34.17˚C and 27.03˚C and further in the early spring the values were 29.90˚C,
32.61˚C, 35.43˚C, 37.82˚C are shown in Figure 7 and 30.42˚C. In winter the DOD is 0.8˚C cooler than SID, and
6.89˚C cooler than OAS, and 7.80˚C cooler than OGS and 0.66˚C cooler than PUD. In the early spring the
DOD is 2.71˚C cooler than SID, and 5.53˚C cooler than OAS, and 7.92˚C cooler than OGS and 0.52˚C cooler
than PUD. The Average Indoor Ambient Temperature profiles over the monitoring period are shown in Fig. 7.
Figure 7: Average Indoor Ambient Temperature of 12 Noon
At peak hour, the average Indoor Relative Humidity of DOD, SID, OAS, OGS and PUD in winter were
87.03%, 84.90%, 65.77%, 63.39% and 88.04%. In the early spring the values were 69.45%, 60.58%, 47.90%,
42.13% and 70.73% are shown in Figure 8. In the winter the Indoor Relative Humidity of DOD is 2.13% higher
than SID, 21.26% higher than OAS, 23.64% higher than OGS and 1.01% less than PUD. In the early spring the
DOD is 8.87% higher than SID, 21.55% higher than OAS, 27.32% higher than OGS and 1.28% less than PUD.
Average Indoor Relative Humidity profiles over the monitoring period are shown in Fig. 8. The DOD module
provides a low ambient temperature within the comfort band but the OGS module provides a highest value
which is not in the comfort band. The PUD module avails a moderate indoor ambient temperature with in the
comfort band than the rest of the modules.
Evaluation of the Thermal Performance...
www.ijesi.org 31 | Page
Figure 8: Average Indoor Relative Humidity of 12 Noon
The indoor relative humidity is high for the month of November. Relative humidity has a decreased value for
the other months. The IRH value is very low for OGS for the month of March.The mean rise and fall
temperatures of Roofs, Floors, Walls and IAT of all modules and IRH of all modules for 6, 12, 18 hours are
given in Fig. 9,10,11,12,13,14,15,16for both seasons of winter and spring.
Figure 9: Winter mean temp. of roofs Figure 10: Spring mean temp. of roofs
The mean values of the roof temperature for all the modules for 6, 12, 18 hours are provided in Fig.
9 and 10 for the winter and spring seasons. It is clear that the peak hour temperature is very high for the OGS
roof and is low for DOD and is moderate for PUD. The rise in temperature does not fall to the same level in all
type of roofs. To some extent the temperature is retained by the roof due to the continuous reception of solar
radiation.
Figure 11: Winter mean temp. of walls Figure 12: Spring mean temp. of walls
Evaluation of the Thermal Performance...
www.ijesi.org 32 | Page
The mean values of the average wall temperature for all the modules for 6, 12, 18 hours are shown in
Fig.11and 12 for both the seasons. The rise in wall temperature at peak hour does not fall to the same level
by18th
hour. The solar radiation reception is no way obstructed by the east facing modules from 12 to 18th
hours.
Hence it is obvious that the orientation is the main cause for the retention of heat.
Figure 13: Winter Indoor ambient temp. Figure 14: Spring Indoor ambient temp.
The Indoor Ambient Temperature mean values for 6, 12, 18 hours for all the modules for both
the seasons are shown in the Fig.13 and 14. The indoor ambient temperatures for OGS, OAS and SID modules
are high and are less for DOD and PUD. The figures display that the 6th
hour IAT is less and the 18th
hour value
is high. The orientation of modules makes the roof and walls to receive the sun’s radiation continuously
resulting to the higher IAT in the 18th
hour than in the 6th
hour. It is observed that for both the seasons the indoor
ambient temperature is within the comfort band.
Figure 15: The winter IRH Figure 16: The Spring IRH
The mean values of IRH for both the seasons for 6, 12, 18 hours are depicted in the Fig.15 and 16.
From the figure it is perceived that SID, PUD and DOD have a high IRH but the other two modules OGS and
OAS have a lower IRH.
V. CONCLUSION
Thermal performance of roofs exerts a powerful influence on indoor ambient temperature. This study
tested five side by side modules in Chidambaram, Tamil Nadu with identical floor plans and orientations using
different materials for roofs and walls. The data showed that solar heating had a large effect not only on the roof
but also on wall and floor. Light roofs are easily heated by solar radiation during the day time hours causing a
high temperature of the occupant zone. The large influence on cooling demand is primarily due to the impact of
ceiling and wall heat transfer. The orientations of the modules have a control on the indoor temperature gain.
Each of the examined alternative roofing systems were found to be superior to overall galvanized sheet module
both in providing lower indoor ambient temperature and higher indoor relative humidity. The DOD provides a
best performance among the five roofing systems to periods with high solar irradiance. PUD roof provides a
better indoor ambient temperature and relative humidity. In summary, the selection of double roof with mineral
wool is superior in providing comfort level of indoor environment than PUD, SID, OAS and OGS in hot and
Evaluation of the Thermal Performance...
www.ijesi.org 33 | Page
humid climate. The DOD provides a lower indoor ambient temperature of 8-10˚C approximately than OGS.
This research points to the need for double roofs packed with insulating materials for good energy performance.
The modules DOD and PUD need no energy for cooling. The techniques of construction evaluated are
commonly used customary techniques and low cost than others. Further the same roof material strongly reduces
the house peak cooling demand during utility coincident peak hours - a highly desirable attribute.
REFERENCES
[1]. Anink D., Boonstra C., and Mak J. (1996) Handbook of Sustainable Building: an environmental preference method for selection
of materials for use in construction and refurbishment James and James,London p. 8.
[2]. The National Building Code of India, 2005.
[3]. Szokolay.S (2004): Introduction to Architectural Science: The basis of Sustainable Design, Architectural Press, Oxford- 17.
[4]. Madhavi Indraganti(2010): Proceedings of conference: Adapting to change: New thinking on comfort, Cumberland Lodge
Windsor,London, U.K 9-11 April 2010.
[5]. Passive- On Project. The passive house standard in European warm climates: “Design guidelines for comfort low energy homes”
July 2007.
[6]. K.C.K. Vijaykumar, P.S.S. Srinivasan, S. Dhandapani, A performance of hollow clay tile (HCT) laid reinforced cement concrete
(RCC) roof for tropical summer climates,Energy and Buildings, 39 (2007) 886–892.
[7]. Tang, R. & Etzion, Y. 2004. On Thermal Performance of an Improved Roof Pond for Cooling Buildings. Building and
Environment, 39 (2): 201-209.
[8]. Gut, P. & Ackernecht, D. 1993. Climate Responsive Building: Appropriate Building Construction in Tropical and subtropical
Regions. Switzerland: SKAT.
[9]. Langewiesche, W., 1950 “Your House in Florida,” House Beautiful, January, 1950, p. 74.
[10]. Givoni, B. 1976. Man, Climate and Architecture, Applied Science Publishers Ltd., London. Griggs, E.I, and Shipp, P.H., 1988.
"The Impact of Surface Reflectance on the Thermal Performance of Roofs: An Experimental Study," ASHRAE Transactions,
Atlanta,GA, Vol. 94, p. 2.
[11]. Givoni, B. and Hoffman, M.E., 1968. “Effect of Building Materials on Internal Temperatures” Research Report,
BuildingResearch Station, Teknion Haifa.
[12]. Taha, H., Akbari, H., Rosenfeld, A.H. and Huang, J., 1988. "Residential Cooling Loads andthe Urban Heat Island--the Effects of
Albedo" Building and Environment, Permagon Press, Great Britain, Vol. 23,p. 4.
[13]. Griggs, E.I, and Shipp, P.H., 1988. "The Impact of Surface Reflectance on the Thermal Performance of Roofs: An Experimental
Study"ASHRAE Transactions,Atlanta, GA, Vol. 94, p. 2.
[14]. Bansal, N.K., Garg, S.N. and Kothari, S., 1992. "Effect of Exterior Surface Colour on the Thermal Performance of Buildings,"
Building and Environment, Permagon Press, Great Britain, Vol. 27, No. 1, p. 31-37.
[15]. Akbari, H., Taha, H. and Sailor, D., 1992. "Measured Savings in Air Conditioning from Shade Trees and White Surfaces,"
Proceedings of the 1992 ACEEE Summer Study on Energy Efficiency in Buildings, (American Council for an Energy Efficient
Economy), Washington D.C., Vol. 9, p. 1.
[16]. Beal, D. and Chandra, S., 1995. “The Measured Summer Performance of Tile Roof Systemsand Attic Ventilation Strategies in
Hot Humid Climates,” Thermal Performance ofthe Exterior Envelopes of Buildings VI,U.S. DOE/ORNL/BETEC,Clearwater,
FL, December 4-8,1995.
[17]. Rudd, Armin F., Joseph W. Lstiburek and Kohta Ueno, 2000., “Unvented Cathedralized Attics: Where We’ve Been and Where
We’re Going,” Proceedings of the 2000 Summer Study on Energy Efficiency in Buildings, American Council for an Energy
Efficient Economy, Washington D.C,Vol. 1, p. 247.
[18]. Parker, D.S., Fairey, P.W. and GU, L., 1993. “Simulation of the Effects of Duct Leakage and Heat Transfer on Residential Space
Cooling Energy Use” Elsevier Sequoia, Netherlands, Energy and Buildings, 20, p. 97-113.
[19]. Levinson, R., Akbari, H. and Gartland, L.M., 1996. “Impact of the Temperature Dependency of Fiberglass Insulation R-Value on
Cooling Energy Use in Buildings,” in ACEEE 1996 Summer Study on Energy Efficiency in Buildings, American Council for an
Energy Efficient Economy, Washington D.C Vol. 10, p. 85.
[20]. Parker, D.S., Sonne, J. K., Sherwin, J. R. 2002. “Comparative Evaluation of the Impact of Roofing Systems on Residential
Cooling Energy Demand in Florida,” in ACEEE Summer Study on Energy Efficiency in Buildings American Council for an
Energy Efficient Economy, Asilomar Conference Center in Pacific Grove, CA., Aug. 2002.
[21]. Akbari H, and Konopacki, S. (2005).Calculating energy saving potentials of heat-island reduction strategies, Energy Policyvol
33, no 6, pp721 – 756.
[22]. Synnefa. M, Santamouris, Akbari. H, Estimating the effect of using cool coatings on energy loads and thermal comfort in
residential buildings in various climatic conditions, Energy and Buildings, 39, 1167–1174, 2007.
[23]. Suehrcke.H, Peterson.E.L, Selby.N, Effect of roof solar reflectance on the building heat gain in a hot climate, Energy and
Buildings, 40, 2224–2235, 2008.

Contenu connexe

Tendances

Optimum insulation thickness for building envelope a review
Optimum insulation thickness for building envelope  a reviewOptimum insulation thickness for building envelope  a review
Optimum insulation thickness for building envelope a revieweSAT Journals
 
Development of a Solar Drier for Domestic Applications
Development of a Solar Drier for Domestic ApplicationsDevelopment of a Solar Drier for Domestic Applications
Development of a Solar Drier for Domestic ApplicationsIJAEMSJORNAL
 
Intelligent building envelopes
Intelligent building envelopesIntelligent building envelopes
Intelligent building envelopesRajat Nainwal
 
CONSTRUCTION OF GREENHOUSE
CONSTRUCTION OF GREENHOUSECONSTRUCTION OF GREENHOUSE
CONSTRUCTION OF GREENHOUSEpramodrai30
 
IRJET- Energy Efficient and Sustainable Buildings
IRJET-  	  Energy Efficient and Sustainable BuildingsIRJET-  	  Energy Efficient and Sustainable Buildings
IRJET- Energy Efficient and Sustainable BuildingsIRJET Journal
 
Opportunities for Energy Conservation in Residential Buildings of Bhopal: A C...
Opportunities for Energy Conservation in Residential Buildings of Bhopal: A C...Opportunities for Energy Conservation in Residential Buildings of Bhopal: A C...
Opportunities for Energy Conservation in Residential Buildings of Bhopal: A C...Pratish Rawat
 
Lecture 5 designing building envelope
Lecture 5 designing building envelopeLecture 5 designing building envelope
Lecture 5 designing building envelopeNedhal Al-Tamimi
 
Integration of Double Skin Facade with HVAC Systems: The State of the Art on ...
Integration of Double Skin Facade with HVAC Systems: The State of the Art on ...Integration of Double Skin Facade with HVAC Systems: The State of the Art on ...
Integration of Double Skin Facade with HVAC Systems: The State of the Art on ...paperpublications3
 
Pgb unit iii b kameswara rao marthi
Pgb unit iii b   kameswara rao marthiPgb unit iii b   kameswara rao marthi
Pgb unit iii b kameswara rao marthiMallikarjunaRao52
 
V4I2-IJERTV4IS020774
V4I2-IJERTV4IS020774V4I2-IJERTV4IS020774
V4I2-IJERTV4IS020774Vijesh Ravi
 
Materials for construction of green houses
Materials for construction of green housesMaterials for construction of green houses
Materials for construction of green housesAjay Singh Lodhi
 
Energy Efficient Garmentfactories in Bangladesh
Energy Efficient Garmentfactories in BangladeshEnergy Efficient Garmentfactories in Bangladesh
Energy Efficient Garmentfactories in BangladeshFarah Naz
 
Final case study tropical box house
Final case study tropical box houseFinal case study tropical box house
Final case study tropical box houseWm Chia
 
The impact of outdoor thermal environment on iraqi building
The impact of outdoor thermal environment on iraqi buildingThe impact of outdoor thermal environment on iraqi building
The impact of outdoor thermal environment on iraqi buildingAlexander Decker
 
Reduction of reflection losses in solar cell by using tial2 and zr anti refle...
Reduction of reflection losses in solar cell by using tial2 and zr anti refle...Reduction of reflection losses in solar cell by using tial2 and zr anti refle...
Reduction of reflection losses in solar cell by using tial2 and zr anti refle...eSAT Publishing House
 

Tendances (19)

Optimum insulation thickness for building envelope a review
Optimum insulation thickness for building envelope  a reviewOptimum insulation thickness for building envelope  a review
Optimum insulation thickness for building envelope a review
 
Development of a Solar Drier for Domestic Applications
Development of a Solar Drier for Domestic ApplicationsDevelopment of a Solar Drier for Domestic Applications
Development of a Solar Drier for Domestic Applications
 
Intelligent building envelopes
Intelligent building envelopesIntelligent building envelopes
Intelligent building envelopes
 
CONSTRUCTION OF GREENHOUSE
CONSTRUCTION OF GREENHOUSECONSTRUCTION OF GREENHOUSE
CONSTRUCTION OF GREENHOUSE
 
IRJET- Energy Efficient and Sustainable Buildings
IRJET-  	  Energy Efficient and Sustainable BuildingsIRJET-  	  Energy Efficient and Sustainable Buildings
IRJET- Energy Efficient and Sustainable Buildings
 
Class 2 Types of green house
Class 2 Types of green houseClass 2 Types of green house
Class 2 Types of green house
 
INTELLIGENT BUILDING FACADES
 INTELLIGENT BUILDING FACADES INTELLIGENT BUILDING FACADES
INTELLIGENT BUILDING FACADES
 
Opportunities for Energy Conservation in Residential Buildings of Bhopal: A C...
Opportunities for Energy Conservation in Residential Buildings of Bhopal: A C...Opportunities for Energy Conservation in Residential Buildings of Bhopal: A C...
Opportunities for Energy Conservation in Residential Buildings of Bhopal: A C...
 
Lecture 5 designing building envelope
Lecture 5 designing building envelopeLecture 5 designing building envelope
Lecture 5 designing building envelope
 
Integration of Double Skin Facade with HVAC Systems: The State of the Art on ...
Integration of Double Skin Facade with HVAC Systems: The State of the Art on ...Integration of Double Skin Facade with HVAC Systems: The State of the Art on ...
Integration of Double Skin Facade with HVAC Systems: The State of the Art on ...
 
Pgb unit iii b kameswara rao marthi
Pgb unit iii b   kameswara rao marthiPgb unit iii b   kameswara rao marthi
Pgb unit iii b kameswara rao marthi
 
Green house
Green houseGreen house
Green house
 
V4I2-IJERTV4IS020774
V4I2-IJERTV4IS020774V4I2-IJERTV4IS020774
V4I2-IJERTV4IS020774
 
Materials for construction of green houses
Materials for construction of green housesMaterials for construction of green houses
Materials for construction of green houses
 
Ibiyeye et al., 2015
Ibiyeye et al., 2015Ibiyeye et al., 2015
Ibiyeye et al., 2015
 
Energy Efficient Garmentfactories in Bangladesh
Energy Efficient Garmentfactories in BangladeshEnergy Efficient Garmentfactories in Bangladesh
Energy Efficient Garmentfactories in Bangladesh
 
Final case study tropical box house
Final case study tropical box houseFinal case study tropical box house
Final case study tropical box house
 
The impact of outdoor thermal environment on iraqi building
The impact of outdoor thermal environment on iraqi buildingThe impact of outdoor thermal environment on iraqi building
The impact of outdoor thermal environment on iraqi building
 
Reduction of reflection losses in solar cell by using tial2 and zr anti refle...
Reduction of reflection losses in solar cell by using tial2 and zr anti refle...Reduction of reflection losses in solar cell by using tial2 and zr anti refle...
Reduction of reflection losses in solar cell by using tial2 and zr anti refle...
 

En vedette

Portfolio Digital de Pablo Tozzi
Portfolio Digital de Pablo TozziPortfolio Digital de Pablo Tozzi
Portfolio Digital de Pablo Tozziezetozzi
 
Imagebroschüre LOKHALLE Göttingen
Imagebroschüre LOKHALLE GöttingenImagebroschüre LOKHALLE Göttingen
Imagebroschüre LOKHALLE GöttingenLOKHALLE
 
Genetic Diagnosis, ethnography and patient driven research
Genetic Diagnosis, ethnography and patient driven researchGenetic Diagnosis, ethnography and patient driven research
Genetic Diagnosis, ethnography and patient driven researchCarlos Bezos Daleske
 
Banking Industry Whitepaper: Implications of the Lease Accounting Changes
Banking Industry Whitepaper: Implications of the Lease Accounting ChangesBanking Industry Whitepaper: Implications of the Lease Accounting Changes
Banking Industry Whitepaper: Implications of the Lease Accounting Changesjmeedzan
 
Consumidores Digitais: Brasil Conectado-Hábitos de consumo de mídia 2013 (IAB)
Consumidores Digitais: Brasil Conectado-Hábitos de consumo de mídia 2013 (IAB)Consumidores Digitais: Brasil Conectado-Hábitos de consumo de mídia 2013 (IAB)
Consumidores Digitais: Brasil Conectado-Hábitos de consumo de mídia 2013 (IAB)Consumidores Digitais
 
ALD Automotive Luxembourg se mobilise pour une noble cause
ALD Automotive Luxembourg se mobilise pour une noble cause ALD Automotive Luxembourg se mobilise pour une noble cause
ALD Automotive Luxembourg se mobilise pour une noble cause ALD Luxembourg
 
Palmares de 3 años corriendo desde 2009 2012
Palmares de 3 años corriendo desde 2009   2012Palmares de 3 años corriendo desde 2009   2012
Palmares de 3 años corriendo desde 2009 2012Abraham Pastor Tomas
 
1950s Presentation PDF
1950s Presentation PDF1950s Presentation PDF
1950s Presentation PDFAubrey Kanagy
 
História do porto jardins do porto - jardim do passeio alegre
História do porto   jardins do porto - jardim do passeio alegreHistória do porto   jardins do porto - jardim do passeio alegre
História do porto jardins do porto - jardim do passeio alegreArtur Filipe dos Santos
 
Património Cultural 98 Anos das Aparições de Fátima aula 2 - Capelinha das ...
Património Cultural   98 Anos das Aparições de Fátima aula 2 - Capelinha das ...Património Cultural   98 Anos das Aparições de Fátima aula 2 - Capelinha das ...
Património Cultural 98 Anos das Aparições de Fátima aula 2 - Capelinha das ...Universidade Sénior Contemporânea do Porto
 
Eigrp calculo feasible successor
Eigrp calculo feasible successorEigrp calculo feasible successor
Eigrp calculo feasible successorAtilio Espinoza
 
AS NOSAS ÁRBORES
AS NOSAS ÁRBORESAS NOSAS ÁRBORES
AS NOSAS ÁRBORESisaff
 

En vedette (20)

Portfolio Digital de Pablo Tozzi
Portfolio Digital de Pablo TozziPortfolio Digital de Pablo Tozzi
Portfolio Digital de Pablo Tozzi
 
Imagebroschüre LOKHALLE Göttingen
Imagebroschüre LOKHALLE GöttingenImagebroschüre LOKHALLE Göttingen
Imagebroschüre LOKHALLE Göttingen
 
BuddyBuy
BuddyBuy BuddyBuy
BuddyBuy
 
Genetic Diagnosis, ethnography and patient driven research
Genetic Diagnosis, ethnography and patient driven researchGenetic Diagnosis, ethnography and patient driven research
Genetic Diagnosis, ethnography and patient driven research
 
Banking Industry Whitepaper: Implications of the Lease Accounting Changes
Banking Industry Whitepaper: Implications of the Lease Accounting ChangesBanking Industry Whitepaper: Implications of the Lease Accounting Changes
Banking Industry Whitepaper: Implications of the Lease Accounting Changes
 
Consumidores Digitais: Brasil Conectado-Hábitos de consumo de mídia 2013 (IAB)
Consumidores Digitais: Brasil Conectado-Hábitos de consumo de mídia 2013 (IAB)Consumidores Digitais: Brasil Conectado-Hábitos de consumo de mídia 2013 (IAB)
Consumidores Digitais: Brasil Conectado-Hábitos de consumo de mídia 2013 (IAB)
 
Bray seashore
Bray seashoreBray seashore
Bray seashore
 
ALD Automotive Luxembourg se mobilise pour une noble cause
ALD Automotive Luxembourg se mobilise pour une noble cause ALD Automotive Luxembourg se mobilise pour une noble cause
ALD Automotive Luxembourg se mobilise pour une noble cause
 
Palmares de 3 años corriendo desde 2009 2012
Palmares de 3 años corriendo desde 2009   2012Palmares de 3 años corriendo desde 2009   2012
Palmares de 3 años corriendo desde 2009 2012
 
1950s Presentation PDF
1950s Presentation PDF1950s Presentation PDF
1950s Presentation PDF
 
História do porto jardins do porto - jardim do passeio alegre
História do porto   jardins do porto - jardim do passeio alegreHistória do porto   jardins do porto - jardim do passeio alegre
História do porto jardins do porto - jardim do passeio alegre
 
Die Qualität der Walliser und Schweizer Hotellerie aus Kundensicht (Teil 2) A...
Die Qualität der Walliser und Schweizer Hotellerie aus Kundensicht (Teil 2) A...Die Qualität der Walliser und Schweizer Hotellerie aus Kundensicht (Teil 2) A...
Die Qualität der Walliser und Schweizer Hotellerie aus Kundensicht (Teil 2) A...
 
Resultats inca
Resultats incaResultats inca
Resultats inca
 
Fullife
FullifeFullife
Fullife
 
Reforme de la tutelle
Reforme de la tutelleReforme de la tutelle
Reforme de la tutelle
 
01 sqlplus
01 sqlplus01 sqlplus
01 sqlplus
 
Sujets
SujetsSujets
Sujets
 
Património Cultural 98 Anos das Aparições de Fátima aula 2 - Capelinha das ...
Património Cultural   98 Anos das Aparições de Fátima aula 2 - Capelinha das ...Património Cultural   98 Anos das Aparições de Fátima aula 2 - Capelinha das ...
Património Cultural 98 Anos das Aparições de Fátima aula 2 - Capelinha das ...
 
Eigrp calculo feasible successor
Eigrp calculo feasible successorEigrp calculo feasible successor
Eigrp calculo feasible successor
 
AS NOSAS ÁRBORES
AS NOSAS ÁRBORESAS NOSAS ÁRBORES
AS NOSAS ÁRBORES
 

Similaire à D0354026033

IRJET- Design and Analysis of Concrete Building without Insulation and with I...
IRJET- Design and Analysis of Concrete Building without Insulation and with I...IRJET- Design and Analysis of Concrete Building without Insulation and with I...
IRJET- Design and Analysis of Concrete Building without Insulation and with I...IRJET Journal
 
Karpagam Academy of Higher Education.pdf
Karpagam Academy of Higher Education.pdfKarpagam Academy of Higher Education.pdf
Karpagam Academy of Higher Education.pdf35VigneshDhanapal
 
A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...
A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...
A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...IRJET Journal
 
Comparison of Intelligent Façade’s Energy Efficiency in Hot and Humid Climate...
Comparison of Intelligent Façade’s Energy Efficiency in Hot and Humid Climate...Comparison of Intelligent Façade’s Energy Efficiency in Hot and Humid Climate...
Comparison of Intelligent Façade’s Energy Efficiency in Hot and Humid Climate...paperpublications3
 
Passive Cooling Techniques in Buildings: An Overview
Passive Cooling Techniques in Buildings: An OverviewPassive Cooling Techniques in Buildings: An Overview
Passive Cooling Techniques in Buildings: An OverviewPratish Rawat
 
Shading Devices in High Rise Buildings in the Tropics
Shading Devices in High Rise Buildings in the TropicsShading Devices in High Rise Buildings in the Tropics
Shading Devices in High Rise Buildings in the Tropicspaperpublications3
 
Asian architecture 0321577 foo weimin
Asian architecture 0321577 foo weiminAsian architecture 0321577 foo weimin
Asian architecture 0321577 foo weiminWmin fOO
 
Impact of Window wall ratio on he\at gain
Impact of Window wall ratio on he\at gainImpact of Window wall ratio on he\at gain
Impact of Window wall ratio on he\at gainMemoona Shees
 
Lecture 6 thermal insulation in buildings
Lecture 6 thermal insulation in buildingsLecture 6 thermal insulation in buildings
Lecture 6 thermal insulation in buildingsNedhal Al-Tamimi
 
Asian architecture- Implementation of Sun Shading strategies in 8D House
Asian architecture- Implementation of Sun Shading strategies in 8D HouseAsian architecture- Implementation of Sun Shading strategies in 8D House
Asian architecture- Implementation of Sun Shading strategies in 8D HouseWmin fOO
 
Review of Retrofitting of Academic Building by Energy Efficient Techniques
Review of Retrofitting of Academic Building by Energy Efficient TechniquesReview of Retrofitting of Academic Building by Energy Efficient Techniques
Review of Retrofitting of Academic Building by Energy Efficient TechniquesIRJET Journal
 
IRJET- Green Technology Applications in Buildings
IRJET- Green Technology Applications in BuildingsIRJET- Green Technology Applications in Buildings
IRJET- Green Technology Applications in BuildingsIRJET Journal
 
Application of Passive Cooling Techniques in Residential Buildings: A Case St...
Application of Passive Cooling Techniques in Residential Buildings: A Case St...Application of Passive Cooling Techniques in Residential Buildings: A Case St...
Application of Passive Cooling Techniques in Residential Buildings: A Case St...IJERA Editor
 
Impact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studyImpact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studyScottishWindowTintingCOSprings
 
Impact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studyImpact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studyFortWorthWindowFilm1
 
Impact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studyImpact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studyScottishWindowTinting1
 
Impact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studyImpact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studywindowfilmkansascity
 
Impact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studyImpact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studyScottishWindowTintingFtCollins
 
Impact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studyImpact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studydallaswindowfilm
 

Similaire à D0354026033 (20)

IRJET- Design and Analysis of Concrete Building without Insulation and with I...
IRJET- Design and Analysis of Concrete Building without Insulation and with I...IRJET- Design and Analysis of Concrete Building without Insulation and with I...
IRJET- Design and Analysis of Concrete Building without Insulation and with I...
 
Karpagam Academy of Higher Education.pdf
Karpagam Academy of Higher Education.pdfKarpagam Academy of Higher Education.pdf
Karpagam Academy of Higher Education.pdf
 
A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...
A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...
A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...
 
De32662675
De32662675De32662675
De32662675
 
Comparison of Intelligent Façade’s Energy Efficiency in Hot and Humid Climate...
Comparison of Intelligent Façade’s Energy Efficiency in Hot and Humid Climate...Comparison of Intelligent Façade’s Energy Efficiency in Hot and Humid Climate...
Comparison of Intelligent Façade’s Energy Efficiency in Hot and Humid Climate...
 
Passive Cooling Techniques in Buildings: An Overview
Passive Cooling Techniques in Buildings: An OverviewPassive Cooling Techniques in Buildings: An Overview
Passive Cooling Techniques in Buildings: An Overview
 
Shading Devices in High Rise Buildings in the Tropics
Shading Devices in High Rise Buildings in the TropicsShading Devices in High Rise Buildings in the Tropics
Shading Devices in High Rise Buildings in the Tropics
 
Asian architecture 0321577 foo weimin
Asian architecture 0321577 foo weiminAsian architecture 0321577 foo weimin
Asian architecture 0321577 foo weimin
 
Impact of Window wall ratio on he\at gain
Impact of Window wall ratio on he\at gainImpact of Window wall ratio on he\at gain
Impact of Window wall ratio on he\at gain
 
Lecture 6 thermal insulation in buildings
Lecture 6 thermal insulation in buildingsLecture 6 thermal insulation in buildings
Lecture 6 thermal insulation in buildings
 
Asian architecture- Implementation of Sun Shading strategies in 8D House
Asian architecture- Implementation of Sun Shading strategies in 8D HouseAsian architecture- Implementation of Sun Shading strategies in 8D House
Asian architecture- Implementation of Sun Shading strategies in 8D House
 
Review of Retrofitting of Academic Building by Energy Efficient Techniques
Review of Retrofitting of Academic Building by Energy Efficient TechniquesReview of Retrofitting of Academic Building by Energy Efficient Techniques
Review of Retrofitting of Academic Building by Energy Efficient Techniques
 
IRJET- Green Technology Applications in Buildings
IRJET- Green Technology Applications in BuildingsIRJET- Green Technology Applications in Buildings
IRJET- Green Technology Applications in Buildings
 
Application of Passive Cooling Techniques in Residential Buildings: A Case St...
Application of Passive Cooling Techniques in Residential Buildings: A Case St...Application of Passive Cooling Techniques in Residential Buildings: A Case St...
Application of Passive Cooling Techniques in Residential Buildings: A Case St...
 
Impact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studyImpact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption study
 
Impact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studyImpact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption study
 
Impact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studyImpact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption study
 
Impact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studyImpact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption study
 
Impact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studyImpact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption study
 
Impact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption studyImpact of window films on the overall energy consumption study
Impact of window films on the overall energy consumption study
 

Dernier

Transforming Data Streams with Kafka Connect: An Introduction to Single Messa...
Transforming Data Streams with Kafka Connect: An Introduction to Single Messa...Transforming Data Streams with Kafka Connect: An Introduction to Single Messa...
Transforming Data Streams with Kafka Connect: An Introduction to Single Messa...HostedbyConfluent
 
Understanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitectureUnderstanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitecturePixlogix Infotech
 
Maximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptxMaximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptxOnBoard
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Igalia
 
My Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationMy Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationRidwan Fadjar
 
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Alan Dix
 
Google AI Hackathon: LLM based Evaluator for RAG
Google AI Hackathon: LLM based Evaluator for RAGGoogle AI Hackathon: LLM based Evaluator for RAG
Google AI Hackathon: LLM based Evaluator for RAGSujit Pal
 
SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024Scott Keck-Warren
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfEnterprise Knowledge
 
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024BookNet Canada
 
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...gurkirankumar98700
 
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 3652toLead Limited
 
Unblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesUnblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesSinan KOZAK
 
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...shyamraj55
 
08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking MenDelhi Call girls
 
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Drew Madelung
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)Gabriella Davis
 
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking MenDelhi Call girls
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsEnterprise Knowledge
 
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024BookNet Canada
 

Dernier (20)

Transforming Data Streams with Kafka Connect: An Introduction to Single Messa...
Transforming Data Streams with Kafka Connect: An Introduction to Single Messa...Transforming Data Streams with Kafka Connect: An Introduction to Single Messa...
Transforming Data Streams with Kafka Connect: An Introduction to Single Messa...
 
Understanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitectureUnderstanding the Laravel MVC Architecture
Understanding the Laravel MVC Architecture
 
Maximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptxMaximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptx
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
 
My Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationMy Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 Presentation
 
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
 
Google AI Hackathon: LLM based Evaluator for RAG
Google AI Hackathon: LLM based Evaluator for RAGGoogle AI Hackathon: LLM based Evaluator for RAG
Google AI Hackathon: LLM based Evaluator for RAG
 
SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
 
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
 
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
 
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
 
Unblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesUnblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen Frames
 
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
 
08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men
 
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)
 
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI Solutions
 
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
 

D0354026033

  • 1. International Journal of Engineering Science Invention ISSN (Online): 2319 – 6734, ISSN (Print): 2319 – 6726 www.ijesi.org Volume 3 Issue 5ǁ May 2014 ǁ PP.26-33 www.ijesi.org 26 | Page Evaluation of the Thermal Performance of Light Roofing Systems Mrs.M.Ponni1, Dr.R.Baskar2 1 Research Scholar, 2 Associate professor Department of Civil and Structural Engineering, Annamali University, Chidambaram-608001, Tamil Nadu, India. ABSTRACT: Thermal performance of roofs exerts a powerful influence on indoor ambienttemperature. Thermal gain by single storey houses covered by light roofs is enormous during the peak hours of the day, which offers thermal shock to the occupants and necessitates high cooling energy demand. This paper presents a new design for light roofing structure in order to improve the indoor environment. Industrial buildings, ware houses, workshops and Lower economic group people use the light roof sheets as a roof material. Light roofs are in the form of Galvanized sheets, Asbestos sheets, and Cool roofs. Higher indoor ambient temperature of industries leads to fatigue of workers which causes a lower labour productivity. To enhance the labour productivity, improved indoor environment should be provided. Five different modules are constructed with identical floor plan and orientation but with different materials for walls and roofs. Single Decker (SID), Overall Galvanised Sheet (OGS), Overall Asbestos sheet (OAS), Double Decker (DOD), and Poly Urethane Decker (PUD) are the modules used for this study. The modules utilize no energy for cooling. Effort has been engaged to fetch a best indoor environment by the roof among the selected modules. KEYWORDS: Thermal performance, Indoor ambient temperature, Indoor relative humidity, Double Decker. I. INTRODUCTION Energy crisis and Environmental impact is serious, with the development of the world economy. The fossil fuel is depleting. More than 30% of primary energy is consumed by non-industrial buildings, including houses, offices, schools, hospitals, and so on [1]. Energy consumed in the production of building materials is 20% of the world fuel consumption. It demands immediate action to develop energy efficient buildings. The total electrical energy consumed by Indian buildings is 33%. If the Energy Conservation code is enforced for the construction work, it will yield annual savings approximately 1.7 KWH. Estimates based on computer simulation models can use 40 – 60% less energy than conventional buildings. The efficiency of a building strongly depends on the way it is built, managed and used and furthers the selection of roof according to the purpose apart from the wall and floor plans and the orientation of the building. [2], India has been divided into five major climatic zones, Cold and Sunny, Cold and Cloudy, Warm and Humid, Hot and Dry, Composite and Moderate. According to the classification, India is a quite challenging country to the planners, designers and architects. The human body continuously produces heat by its metabolic processes. This heat must be dissipated to the environment, or else the body temperature will increase. The body’s thermal balance can be expressed as: S = M ± Rd ±Cv± Cd – Ev (1) Where, S = Change in stored heat, M = metabolic heat production,Rd = net radiation exchange, Cd= conduction Cv=Convection including respiration,Ev = evaporation including respiration. At equilibrium condition, (S) is zero, and such equilibrium is a precondition of thermal comfort at the 50% RH and less than 0.15m/ airflow speed. The comfort band of room temperature is 18˚C – 27˚C [3]. The comfort band of room temperature is 26˚C – 32.5 ˚C and the relative humidity ranges between 17% - 78% from a field study in Hyderabad, India[4].Roof is the element which directly receives the most of the solar radiation in different angles than the other elements of the building. Inadequate roof insulation results in heat transfer from the roof to indoor. Insulation can be applied between roof rafters or on the rafters. For concrete roofs, outer insulation over the concrete can be applied [5]. Indian concrete roofs, with 150mm of concrete and 75-100mm of weathering course transfers 50-70% of heat in to the occupant zone. High reflective coatings can reduce 20-70% heat transfer [6].The heat incoming into the occupant zone through roof is the main cause of discomfort [7]. The heat transferred into the occupant zone is true for single storey and top floor of the multi-storeyed buildings [8].Traditional architecture in hot climates has long recognised that the building colours can reduce cooling loads[9], [10]. A series of simulation and experimental studies have demonstrated that building reflectance can significantly impact cooling needs [11], [12], [13], [14].
  • 2. Evaluation of the Thermal Performance... www.ijesi.org 27 | Page The impact of reflective roofing’s on the air conditioning use in Florida and California building field tests have shown that there is electrical energy savings [15]. Beyond roof reflectance other approaches such as tile roofs and unvented attics with insulation under the roof can produce cooler attics resulting in energy improvement, but of unknown comparative magnitude [16], [17]. The attic heat gain to the thermal distribution system can increase residential cooling loads by up to 30% during peak summer periods [18]. Further benefits arise from the reduction of attic air temperature and its impact on ceiling conductivity [19]. The selection of roof with high solar reflectance represents one of the most significant energy saving options in hot climates [20].The cooling energy savings due to the application of heat island mitigation strategies have calculated (application of cool materials and increase in vegetation cover) for 240 regions in the United States. It was found that for residential buildings the cooling energy savings vary between 12% and 25%, for office buildings between 5% and 18%, and for commercial (retail stores) buildings between 7% and 17%[21]. Even though, some advanced cool coloured materials have been available along with NIR reflective pigments to cool the roof estimated the effect of cool coating on thermal comfort and stated that increasing the roof solar reflectance reduces the cooling load by 18-93% and the indoor thermal comfort is improved by decreasing the hour of discomfort by 9-100%[22]. Light colour coating may help to reduce 30% total heat gain in the weather condition of Australia since the roofing may have much lower absorptivity[23]. Even though the above methods are more suitable in reducing the heat gain to the Room, the cost incurred for the making such a roof should be considered. The initial cost associated for making the green roof is higher and it is difficult to maintain properly. It also requires stronger roof beam to support the various roof layers of the green roof. Also in the roof with roof coating, the detritions of roof coating over the time are a Major setback. The settlement of dust over the roof coating may completely spoil the performance of the roof coating [1]. With all these information present work proposes and analyses a new type of roof DOD to reduce the indoor heat gain. II. RESEARCH DESCRIPTION Previous research efforts have investigated the thermal performance of various roofing systems. In this study an attempt has been made to quantify the roofing influence on cooling performance of the five modules and the living comfort of the occupants. All the modules have same floor, wall area and orientation. The size of the module is 3mx 3m x 3m. The galvanized sheets used in the modules have the same thickness of 0.35 mm. The walls have a thickness of 230 mm made up of brick. Two angles are used as purlins. The slope of the roof is maintained to be 2˚. Walls of the modules are white washed and the flooring is done with cement mortar. The first module is Single Decker (SID) in which galvanized sheets are used as roof material. The second module is overall galvanized sheet module (OGS), in which roof and walls use the galvanized sheets. The third module is overall Asbestos sheet module (OAS) in which asbestos sheets is used for the roof and the wall. The fourth module is double decker (DOD) in which wooden insulators and mineral wool is used between two galvanized sheet roofs. Brick walls are used for SID, DOD and PUD modules. The fifth module is poly urethane decker (PUD) module in which poly urethane panels are used as roof material. The construction data of the modules used in this study are tabulated in Table I. Table I: Construction data of the Research Modules 2.1 First Module (SID) In Single Decker, Galvanized sheets are used as roof element, where the walls are made by bricks. When the solar radiation falls on the roof, the sheets are very easily heated even by early morning due to conduction and it extends for the whole day. During the peak hour the amount of heat transmitted into the building is massive. 2.2 Second Module (OGS) The roof and wall of the OGS module is constructed with Trapezoidal shape Galvanized sheets. This roofing is adopted by the industries, workshops, warehouses and is also followed by the Low economy Group Sl. No Description Dimension 1 Floor Area 100 sq.ft 2 Net Wall Area 382 sq.ft 3 Ceiling 120 sq.ft 4 Doors 18 sq.ft 5 Overhang 20 sq.ft
  • 3. Evaluation of the Thermal Performance... www.ijesi.org 28 | Page community because of its light weight, easiness in construction and low cost. Being a conductor the sheets easily permit solar radiation into the occupant zone not only through the roof but also via walls. 2.3 Third Module (OAS) The third module is constructed by using trapezoidal Asbestos sheets for the roof and wall. Though asbestos is banned by developed countries, but it is used still in India. This type of roof too allows the solar radiation into the occupant zone through the roof and walls. 2.4 Fourth Module (DOD) Design of Double roof is carried out in three steps. In the first step, roof is made using galvanised sheets by setting the second roof over the first and named as Double Decker (DOD) as shown in (Fig1). In the double decker the sheets of first roof have contact with the second roof on longitudinal lines and hereafter called lines of contact. At this condition the shape of the double roof is similar to that of a Stationery wave. In a stationary wave there are nodes and antinodes. Nodes have zero displacement where antinodes have a maximum displacement of the particles of the medium. The nodes of a stationery wave are identical with the lines of contact of double roof. As the area of contact between the two roofs is decreased, the heat transmitted into the dwelling by conduction is also reduced to about 70%. Cylindrical air gap of 22 mm thickness is formed between the two lines of contact. In the second step, wooden reapers, of size 3000mm x50 mm x 25 mm are introduced between the two roofs (Fig2) in 200 mm spacing, consequently the two roofs are separated by 50 mm and separation of two roofs ranges from 50 mm to 72 mm. In the third step, mineral wool roll of thickness 50 mm is spread over the wooden reapers and the second roof is made (Fig 3). Now the two roofs are separated by a thickness of 100 mm to 122 mm. The wooden reapers and the mineral wool are the insulators where they prevent direct heat transmission by conduction and further the air flow between the gaps reduce heat by convection. Figure 1: Diagram of the Double roof Figure 2: Diagram of the Double roof with wooden reaper Figure 3: Diagram of double roof with wooden reaper and Mineral wool 2.5 Fifth Module(PUD) Polyurethane panels of length 3660 mm and breadth 1000 mm used as roof for the fifth module, which is an industrial product. The half white painted reflective steel sheets of thickness 0.47 mm and the poly urethane thickness is 35 mm is used by the industry, to make the panels. One side of the surface shape is trapezoidal and the other side is plain.
  • 4. Evaluation of the Thermal Performance... www.ijesi.org 29 | Page III. EXPERIMENTAL PROCEDURE The experiments were carried out in Chidambaram, Tamil Nadu, 11˚24´N latitude and longitude 79˚44´E.The location is characterized by hot and humid weather. The modules, used in this study are exactly identical in terms of their geometry, orientation, area and climate conditions. SID, OGS, DOD, PUD are reflective roof material but OAS is not a reflective roof material.All the modules are fully instrumented. To measure the Indoor Ambient Temperature and Relative Humidity Single channel data logger is used. In six hours interval (6, 12, 18hr) the roof, wall and floor temperatures are measured by means of Infra-Red Thermometer. The night time temperature does not increase in the hot and humid climates under normal conditions hence the temperature measurement for 24th hour is not included. Roof, wall, floor and indoor and outdoor ambient temperature and relative humidity field data have been catalogued for seven months for five different roofing systems exposed to weathering on an indoor and outdoor test facility. The data are plotted for the time period between September and March. IV. RESULTS AND DISCUSSION At peak hour, the Average Roof Temperatures of DOD, SID, OAS, OGS and PUD in winter were 26.50˚C, 33.77˚C, 39.20˚C, 44.21˚C and 27.40˚C and further in the early spring the values were 31.59˚C, 37.70˚C, 49.19, 57.33˚C and 34.03˚C are shown in Fig. 4. In winter the DOD is 7.27˚C cooler than SID, and 12.7˚C cooler than OAS, and 17.71˚C cooler than OGS and 0.9˚C cooler than PUD. In the early spring the DOD is 6.11˚C cooler than SID, and 17.6˚C cooler than OAS, and 25.74˚C cooler than OGS and 2.44˚C cooler than PUD. The Average Roof Surface Temperature profiles over the monitoring period are shown in Fig. 4. It is obvious that OGS module gains the highest temperature during both the seasons and the DOD module gains the lowest value and the PUD gains a moderate value. Figure 4: Average Roof temperature of 12 Noon At peak hour, the Average Floor Temperatures of DOD, SID, OAS, OGS and PUD in winter were 25.31˚C, 26.16˚C, 31.76˚C, 31.97˚C and 25.83˚C and further in the early spring the values were 28.74˚C, 31.26˚C, 35.65˚C, 36.65˚C and 29.94˚C are shown in Fig. 5. In inter the DOD is 0.85˚C cooler than SID, and 6.45˚C cooler than OAS, and 6.66˚C cooler than OGS and 0.52˚C cooler than PUD. In the early spring the DOD is 2.52˚C cooler than SID, and 6.91˚C cooler than OAS, and 7.91˚C cooler than OGS and 1.20˚C cooler than PUD. The Average Floor Temperature profiles over the monitoring period are shown in Fig. 5. It is observed that OGS module has the highest floor temperature in both seasons, the DOD module has a lower value than others and the PUD module has a moderate value. Figure 5: Average Floor temperature of 12 Noon
  • 5. Evaluation of the Thermal Performance... www.ijesi.org 30 | Page At peak hour, the Average Wall Temperatures of DOD, SID, OAS, OGS and PUD in winter were 25.58˚C, 26.69˚C, 35.40˚C, 38.23˚C and 26.17˚C and further in the early spring the values were 30.59˚C, 32.30˚C, 39.80, 42.95˚C and 31.04˚C are shown in Fig. 6. In winter the DOD is 1.11˚C cooler than SID, and 9.82˚C cooler than OAS, and 12.65˚C cooler than OGS and 0.59˚C cooler than PUD. In the early spring the DOD is 1.71˚C cooler than SID, and 9.21˚C cooler than OAS, and 12.36˚C cooler than OGS and 1.20˚C cooler than PUD. The Average Wall Temperature profiles over the monitoring period are shown in Fig. 6. The average wall temperature is high for OGS and low for DOD and moderate for PUD. Figure 6: Average Wall Temperature of 12 Noon At peak hour, the average Indoor Ambient Temperatures of DOD, SID, OAS, OGS and PUD in winter were 26.37˚C, 27.57˚C, 33.26˚C, 34.17˚C and 27.03˚C and further in the early spring the values were 29.90˚C, 32.61˚C, 35.43˚C, 37.82˚C are shown in Figure 7 and 30.42˚C. In winter the DOD is 0.8˚C cooler than SID, and 6.89˚C cooler than OAS, and 7.80˚C cooler than OGS and 0.66˚C cooler than PUD. In the early spring the DOD is 2.71˚C cooler than SID, and 5.53˚C cooler than OAS, and 7.92˚C cooler than OGS and 0.52˚C cooler than PUD. The Average Indoor Ambient Temperature profiles over the monitoring period are shown in Fig. 7. Figure 7: Average Indoor Ambient Temperature of 12 Noon At peak hour, the average Indoor Relative Humidity of DOD, SID, OAS, OGS and PUD in winter were 87.03%, 84.90%, 65.77%, 63.39% and 88.04%. In the early spring the values were 69.45%, 60.58%, 47.90%, 42.13% and 70.73% are shown in Figure 8. In the winter the Indoor Relative Humidity of DOD is 2.13% higher than SID, 21.26% higher than OAS, 23.64% higher than OGS and 1.01% less than PUD. In the early spring the DOD is 8.87% higher than SID, 21.55% higher than OAS, 27.32% higher than OGS and 1.28% less than PUD. Average Indoor Relative Humidity profiles over the monitoring period are shown in Fig. 8. The DOD module provides a low ambient temperature within the comfort band but the OGS module provides a highest value which is not in the comfort band. The PUD module avails a moderate indoor ambient temperature with in the comfort band than the rest of the modules.
  • 6. Evaluation of the Thermal Performance... www.ijesi.org 31 | Page Figure 8: Average Indoor Relative Humidity of 12 Noon The indoor relative humidity is high for the month of November. Relative humidity has a decreased value for the other months. The IRH value is very low for OGS for the month of March.The mean rise and fall temperatures of Roofs, Floors, Walls and IAT of all modules and IRH of all modules for 6, 12, 18 hours are given in Fig. 9,10,11,12,13,14,15,16for both seasons of winter and spring. Figure 9: Winter mean temp. of roofs Figure 10: Spring mean temp. of roofs The mean values of the roof temperature for all the modules for 6, 12, 18 hours are provided in Fig. 9 and 10 for the winter and spring seasons. It is clear that the peak hour temperature is very high for the OGS roof and is low for DOD and is moderate for PUD. The rise in temperature does not fall to the same level in all type of roofs. To some extent the temperature is retained by the roof due to the continuous reception of solar radiation. Figure 11: Winter mean temp. of walls Figure 12: Spring mean temp. of walls
  • 7. Evaluation of the Thermal Performance... www.ijesi.org 32 | Page The mean values of the average wall temperature for all the modules for 6, 12, 18 hours are shown in Fig.11and 12 for both the seasons. The rise in wall temperature at peak hour does not fall to the same level by18th hour. The solar radiation reception is no way obstructed by the east facing modules from 12 to 18th hours. Hence it is obvious that the orientation is the main cause for the retention of heat. Figure 13: Winter Indoor ambient temp. Figure 14: Spring Indoor ambient temp. The Indoor Ambient Temperature mean values for 6, 12, 18 hours for all the modules for both the seasons are shown in the Fig.13 and 14. The indoor ambient temperatures for OGS, OAS and SID modules are high and are less for DOD and PUD. The figures display that the 6th hour IAT is less and the 18th hour value is high. The orientation of modules makes the roof and walls to receive the sun’s radiation continuously resulting to the higher IAT in the 18th hour than in the 6th hour. It is observed that for both the seasons the indoor ambient temperature is within the comfort band. Figure 15: The winter IRH Figure 16: The Spring IRH The mean values of IRH for both the seasons for 6, 12, 18 hours are depicted in the Fig.15 and 16. From the figure it is perceived that SID, PUD and DOD have a high IRH but the other two modules OGS and OAS have a lower IRH. V. CONCLUSION Thermal performance of roofs exerts a powerful influence on indoor ambient temperature. This study tested five side by side modules in Chidambaram, Tamil Nadu with identical floor plans and orientations using different materials for roofs and walls. The data showed that solar heating had a large effect not only on the roof but also on wall and floor. Light roofs are easily heated by solar radiation during the day time hours causing a high temperature of the occupant zone. The large influence on cooling demand is primarily due to the impact of ceiling and wall heat transfer. The orientations of the modules have a control on the indoor temperature gain. Each of the examined alternative roofing systems were found to be superior to overall galvanized sheet module both in providing lower indoor ambient temperature and higher indoor relative humidity. The DOD provides a best performance among the five roofing systems to periods with high solar irradiance. PUD roof provides a better indoor ambient temperature and relative humidity. In summary, the selection of double roof with mineral wool is superior in providing comfort level of indoor environment than PUD, SID, OAS and OGS in hot and
  • 8. Evaluation of the Thermal Performance... www.ijesi.org 33 | Page humid climate. The DOD provides a lower indoor ambient temperature of 8-10˚C approximately than OGS. This research points to the need for double roofs packed with insulating materials for good energy performance. The modules DOD and PUD need no energy for cooling. The techniques of construction evaluated are commonly used customary techniques and low cost than others. Further the same roof material strongly reduces the house peak cooling demand during utility coincident peak hours - a highly desirable attribute. REFERENCES [1]. Anink D., Boonstra C., and Mak J. (1996) Handbook of Sustainable Building: an environmental preference method for selection of materials for use in construction and refurbishment James and James,London p. 8. [2]. The National Building Code of India, 2005. [3]. Szokolay.S (2004): Introduction to Architectural Science: The basis of Sustainable Design, Architectural Press, Oxford- 17. [4]. Madhavi Indraganti(2010): Proceedings of conference: Adapting to change: New thinking on comfort, Cumberland Lodge Windsor,London, U.K 9-11 April 2010. [5]. Passive- On Project. The passive house standard in European warm climates: “Design guidelines for comfort low energy homes” July 2007. [6]. K.C.K. Vijaykumar, P.S.S. Srinivasan, S. Dhandapani, A performance of hollow clay tile (HCT) laid reinforced cement concrete (RCC) roof for tropical summer climates,Energy and Buildings, 39 (2007) 886–892. [7]. Tang, R. & Etzion, Y. 2004. On Thermal Performance of an Improved Roof Pond for Cooling Buildings. Building and Environment, 39 (2): 201-209. [8]. Gut, P. & Ackernecht, D. 1993. Climate Responsive Building: Appropriate Building Construction in Tropical and subtropical Regions. Switzerland: SKAT. [9]. Langewiesche, W., 1950 “Your House in Florida,” House Beautiful, January, 1950, p. 74. [10]. Givoni, B. 1976. Man, Climate and Architecture, Applied Science Publishers Ltd., London. Griggs, E.I, and Shipp, P.H., 1988. "The Impact of Surface Reflectance on the Thermal Performance of Roofs: An Experimental Study," ASHRAE Transactions, Atlanta,GA, Vol. 94, p. 2. [11]. Givoni, B. and Hoffman, M.E., 1968. “Effect of Building Materials on Internal Temperatures” Research Report, BuildingResearch Station, Teknion Haifa. [12]. Taha, H., Akbari, H., Rosenfeld, A.H. and Huang, J., 1988. "Residential Cooling Loads andthe Urban Heat Island--the Effects of Albedo" Building and Environment, Permagon Press, Great Britain, Vol. 23,p. 4. [13]. Griggs, E.I, and Shipp, P.H., 1988. "The Impact of Surface Reflectance on the Thermal Performance of Roofs: An Experimental Study"ASHRAE Transactions,Atlanta, GA, Vol. 94, p. 2. [14]. Bansal, N.K., Garg, S.N. and Kothari, S., 1992. "Effect of Exterior Surface Colour on the Thermal Performance of Buildings," Building and Environment, Permagon Press, Great Britain, Vol. 27, No. 1, p. 31-37. [15]. Akbari, H., Taha, H. and Sailor, D., 1992. "Measured Savings in Air Conditioning from Shade Trees and White Surfaces," Proceedings of the 1992 ACEEE Summer Study on Energy Efficiency in Buildings, (American Council for an Energy Efficient Economy), Washington D.C., Vol. 9, p. 1. [16]. Beal, D. and Chandra, S., 1995. “The Measured Summer Performance of Tile Roof Systemsand Attic Ventilation Strategies in Hot Humid Climates,” Thermal Performance ofthe Exterior Envelopes of Buildings VI,U.S. DOE/ORNL/BETEC,Clearwater, FL, December 4-8,1995. [17]. Rudd, Armin F., Joseph W. Lstiburek and Kohta Ueno, 2000., “Unvented Cathedralized Attics: Where We’ve Been and Where We’re Going,” Proceedings of the 2000 Summer Study on Energy Efficiency in Buildings, American Council for an Energy Efficient Economy, Washington D.C,Vol. 1, p. 247. [18]. Parker, D.S., Fairey, P.W. and GU, L., 1993. “Simulation of the Effects of Duct Leakage and Heat Transfer on Residential Space Cooling Energy Use” Elsevier Sequoia, Netherlands, Energy and Buildings, 20, p. 97-113. [19]. Levinson, R., Akbari, H. and Gartland, L.M., 1996. “Impact of the Temperature Dependency of Fiberglass Insulation R-Value on Cooling Energy Use in Buildings,” in ACEEE 1996 Summer Study on Energy Efficiency in Buildings, American Council for an Energy Efficient Economy, Washington D.C Vol. 10, p. 85. [20]. Parker, D.S., Sonne, J. K., Sherwin, J. R. 2002. “Comparative Evaluation of the Impact of Roofing Systems on Residential Cooling Energy Demand in Florida,” in ACEEE Summer Study on Energy Efficiency in Buildings American Council for an Energy Efficient Economy, Asilomar Conference Center in Pacific Grove, CA., Aug. 2002. [21]. Akbari H, and Konopacki, S. (2005).Calculating energy saving potentials of heat-island reduction strategies, Energy Policyvol 33, no 6, pp721 – 756. [22]. Synnefa. M, Santamouris, Akbari. H, Estimating the effect of using cool coatings on energy loads and thermal comfort in residential buildings in various climatic conditions, Energy and Buildings, 39, 1167–1174, 2007. [23]. Suehrcke.H, Peterson.E.L, Selby.N, Effect of roof solar reflectance on the building heat gain in a hot climate, Energy and Buildings, 40, 2224–2235, 2008.