Technical Paper
Jörg Randermann
Starting and control of
three-phase asynchronous motors
2
The three-phase asynchronous motor is the most widely used electric motor worldwide
in industrial facilities and large buildings. Simple in terms of design and handling, flexible
in diverse fields of application and economical to operate. It is the most favourable drive
solution in terms of price and quality.
Characteristic for the three-phase motor is the high current load on the mains supply
with direct-on-line starting. High starting and surge currents result when the full voltage
is applied, causing troublesome voltage dips on the mains supply and transient torque
effects in mechanical systems.
Since the invention of the three-phase motor – more than a century ago (1889) –,
start-up solution concepts have been devised, which have intended to eliminate the
unpleasant side-effects. Yet exactly which of these solution concepts fulfil the desire
for satisfactory start-up and optimum operating performance is dependent on the
application and ultimately the economic aspects as well.
To facilitate a simplified overview, the four most important and most well-known start-up
methods for starting and controlling three-phase asynchronous motors used in practice
are presented. In the process, we deliberately dispense with the description of the
devices and functions, and general basic knowledge of electrical drive engineering is
assumed.
Preface
3
M
a
F1
3 / N / PE / AC 50/60 Hz
Q1
F2
M1
3~
M
B1
T1Q2
3~
M
d
3~
M
b c
3~
Yd
With regard to its construction and winding
connection of its passive rotor, the three-
phase asynchronous motor is also referred to
as a squirrel-cage motor or squirrel-cage rotor
(motor). Comparable with a rotating trans-
former and in accordance with its mode of
action, the term induction motor is also gener-
ally used. Designs with separate stator wind-
ings are referred to as Dahlander-connection or
pole-changing motors. A further variant is the
slipring rotor (motor). In this case, the wind-
ings of the rotor are connected to three slip
rings and are only interconnected using resis-
tors outside the motor.
Start variants for three-phase
asynchronous motors
Just as diverse as the different forms and des-
ignations with the asynchronous motor is the
diversity of the respective motor feeders for
start-up and control. To facilitate a simplified
overview, the four most well-known and
important motor feeders are examined in the
following. A three-phase AC current incoming
mains supply earthed as the neutral point
(3 / N / PE / AC 50/60 Hz) is assumed.
Eaton Moeller offers a complete range on the
motor feeders for switching, protection and
control of three-phase asynchronous motors for
the entire range of start variants shown here.
Figure 1: Motor start variants
F1 = fuse (short-circuit and line protection)
Q1 = switching (contactors)
F2 = motor protection (protection against thermal overload, overload relay)
M1 = three-phase asynchronous motor
a Direct-on-line motor start.
b Star-delta starter, the most well-known and used starting variant.
c Soft starter (Q2), the continuous and stepless motor start. A modern, electronic alternative to
the star-delta starter.
d Frequency inverter (T1), controlled, stepless motor start with rated-load torque. Frequency
inverters also enable stepless speed control and feature integrated electronic motor protec-
tion (I2t). Depending on the characteristic, they also allow exact speed control (option, pulse
generator B1) on the otherwise slip-dependent asynchronous motors.
4
a b c a
90°0
L1 L2 L3
360°
L1
120° 120° 120°
180°
270°
L1 L2 L3
U1 V2 W3
L1 L2 L3
U1 V2 W3
Star connection Delta connection
1410 min-1
230 / 400 V 14.5 / 8.5 A
50 Hz
IP 54 Iso. KI F
4.0 KWS1 cos v 0.82
d / Y
1410 min-1
400 / 690 V 8.5 / 4.9 A
50 Hz
IP 54 Iso. KI F
4.0 KWS1 cos v 0.82
d / Y
L1 L3L2
V1
V2
U1 W2W2
U2
ULNILN
L1 L3L2
U1
W1
V1
V2
W2
U2
ULNLN
ULN = √3 • UW ILN = IW ULN = UW ILN = √3 • IW
U1 V1 W1
W2 U2 V2
L1 L2 L3
ULNILN
U1 V1 W1
W2 U2 V2
L1 L2 L3
ULNILN
• With its voltage specification of 230/400 V, this motor must
be connected to the three-phase supply (ULN = 400 V) in a
star configuration.
• The voltage in a motor winding is designed for a maximum
of 230 V here.
• The three winding phases (W2-U2-V2) are configured in the
terminal box to the so-called star point. The voltage for the
individual phases to the star point is 230 V.
• With its voltage specification of 400/690 V, this motor must
be connected to the three-phase supply (ULN = 400 V) in a
delta configuration.
• Every motor winding is configured for a maximum phase
voltage of 400 V and can be directly connected.
• For direct-on-line starting, the ends of the phase windings
are connected in the terminal box (U1-W2, V1-U2, W1-V2)
to the individual phases.
Figure 2: Motor connection circuit, clockwise
Figure 3: Clockwise rotation: phase sequence – terminal box –
drive end
Connection of the three-phase motor
When the three-phase motor is connected to the mains, the
data on the rating plate must correspond with the main voltage
and mains frequency. The connection is implemented via six
screw terminals (standard version) in the terminal box of the
motor and distinguishes between two types of circuit, the star
connection and the delta connection. Example for a mains sup-
ply voltage of 3 AC 400 V, 50 Hz (see figure 2).
Generally, the properties of a three-phase motor are defined in
standards (DIN/VDE 0530, IEC/EN 60034). However, the con-
structive design is the manufacturers’ domain. For example, in
the price-sensitive market for smaller motor output ratings
(<4 kW) – particularly those used with pumps and fans – time
and again you will find motors without a terminal box. Here the
windings are connected internally in the motor to a star point,
and only three connection cables are made available for the
assigned rated voltage.
Regardless of the design configuration (with/without terminal
box), the connections of the three-phase motor must be
denoted, so that their alphabetical sequence (e.g. U1, V1, W1)
corresponds with the mains voltage sequence (L1, L2, L3) and
causes the motor to rotate clockwise. The direction of rotation
is specified by looking directly at the drive end (shaft of the
motor). On motors with two shaft ends, the driving end is
denoted with D, the non-driving end with N (D = Drive, N = No
drive). Anti-clockwise rotation of the three-phase motor is
5
MN
nN
n
nS
MA
MM
MB
MK
ML
MS
IA
IN
M, I
0
Figure 4: Characteristic starting curve of the three-phase asyn-
chronous motor
f = [Hz] = 1/sec
n = [min–1
]
1 min = 60 sec
P = [kW]
MN = [Nm]P =
MN
• n
9550
n =
f
• (1 - s)
p
s =
ns - n
• 100%
ns
implemented by exchanging two connection cables (mains
phases).
The operating point (MM) of the three-phase asynchronous
motor is described by the rated voltage range and the corre-
sponding frequency (e.g. 400 V / 50 Hz). The (rotational) speed
is determined by the frequency of the mains supply (n ~ f). It is
load-dependent and is only maintained as long as the motor
torque (MM) and load torque (ML) have the same magnitude.
The electrical and mechanical rating data of the operating point
must be specified on the motor rating plate. The operation data
are unstable during the starting process (acceleration process).
Steady-state operation of the drive is only permissible in the
operating point (MM) range.
IA = starting current
IN = rated current at the operating point
MA = starting torque
MB = acceleration torque (MM > ML)
MK = breakdown torque
ML = load torque
MM= motor torque (operating point)
MN = rated-load torque, steady-state intersection point of the
three-phase speed-torque characteristic with the load
characteristic
n = speed (actual value)
nN = rated speed at the operating point
ns = synchronous speed
(ns – nN = slip speed)
Direct-on-line motor start
The direct-on-line motor start is the easiest method for starting
up three-phase asynchronous motors. The stator windings are
directly connected to the mains supply in a single switching
process.
Large starting currents (surge currents) result by applying the
full mains voltage, which in turn cause troublesome voltage
changes on the mains supply. For this reason, the electricity
supply companies limit the permissible rated powers of motors
connected to the mains supply. These limit values can vary
from grid to grid. In public electrical power grids, these limita-
tions are generally met when the three-phase motor that is
occasionally started has an apparent power of less than 5.2 kVA
or at higher apparent powers, the starting current does not
exceed 60 A. At a mains voltage of 400 V and an 8-fold starting
current, this corresponds with a rated current of 7.5 A or a
delivered motor output of 4 kW (shaft output power).
On motors with occasionally higher starting currents than 60 A
and motors with starting currents of more than 30 A, which
cause feedback disturbances on the public supply, e.g. by a
heavy-duty start, frequent switching or varying current con-
sumption (elevators, reciprocating saws), further measures for
avoidance of the disruptive voltage variations must be under-
taken. Motors with powers exceeding 4 kW and voltages rated
at 400/690 V can be stated in this case using a star-delta config-
uration.
Direct-on-line start imposes the motor windings to thermal
stresses and, when only briefly, to momentary electro-dynamic
forces. Very frequent, direct-on-line starting reduces the life of
the windings on a standard motor (e.g. periodic intermittent
operation).
Blockage of the rotor (locked rotor) is a serious malfunction that
can lead to thermal destruction of the three-phase asynchro-
nous motor. Every motor feeder must be protected by a cur-
rent-dependent protective device to prevent against this type of
thermal overload. An attractively priced solution here is the use
of overload relays, better known as motor protection relays or
bimetal relays.
These overload relays are referred to as motor-protective cir-
cuit-breakers in combination with a contact module. The syno-
nym for this is the PKZM. In the motor feeder, it protects the
switchgear (contactor DILM), incomers and motor windings
against destruction due to thermal overload (locked rotor pro-
tection) and short-circuit, even when one of the main poles (L1,
L2, L3) has been lost. For this purpose, the rated current of the
motor must be set on the motor-protective circuit-breaker, and
the connection cables in the motor feeder must be rated for
this setting value.
The design of the components in the main circuit of the motor
feeder is undertaken in accordance with the rated operational
current (Ie) of the motor and the utilization category AC-3
(standard IEC/EN60947-4-1); AC-3 = squirrel-cage motors:
start-up, switch off during operation.
The selection of a suitable motor-protective circuit-breaker is
decisive for the functional safety and service life of a motor.
The motor-starter combination (MSC) offers an ideal complete
solution for direct start on the motor feeder. The MSC in its
standard design consists of a motor-protective circuit-breaker
PKZM0 with plug connector and a contactor DILM. In the ver-
6
L1
L2
L3
V1 W1U1
PE
I >I >I >
M
3 ~
L1
L2
L3
V1
W1
U1
W2
V2
U2
PE
I >I >I >
M
3 ~
Figure 5: Motor feeder, direct-on-line starter, clockwise
(forward) rotation, example of MSC
Figure 6: Motor feeder, star-delta starter, clockwise (forward) rotation, example of SDAINL
Motor contactor in star and
delta configuration
Bimetall relay
0.58 x Ie
ta Յ 15 s
sion MSC-DE, the electronic motor-protective circuit-breaker
PKE for motor currents up to 65 A offers an innovative alterna-
tive to bimetal solutions (PKZM0). With its high-level of flexibil-
ity and the same accessory components, the MSC-DE fulfils
the customer demands for exchangeable “standard“ devices.
Star-delta motor start
With a star-delta motor start, the start-up of the three-phase
asynchronous motor is implemented by a changeover of the
windings. The jumpers in the motor terminal box are omitted,
and all 6 winding connections are connected to the mains sup-
ply using a so-called star-delta switch (manually actuated
switch or automatic contactor circuit).
During the operating connection, the windings of the motor are
connected in delta. The winding voltage (UW) must therefore be
equal to the phase voltage (ULN) of the three-phase system. For
example, at a mains supply voltage of 3 AC 400 V the voltage
ratings on the rating plate of the motor must be specified as
400/690 V.
In a star connection, the mains voltage (ULN) on the individual
motor windings is reduced by a factor of 1/͙3 (~ 0.58). For
example: 400 V и 1/͙3 = 230 V. Starting torque and inrush cur-
rent are (in the star connection) reduced to about a third of the
values for the delta connection. Typical starting current:
2...2.5 Ie.
Due to the reduced starting torque, the star-delta configuration
is only suitable for drives with smaller load torques or load tor-
ques (ML) that increase with speed, such as is the case with
pumps and fans (ventilators/blowers). They are also used
where the drive is only subject to a load after it has accelerated
up to speed, for example, with presses and centrifuges.
With the changeover of the circuit configuration from star to
delta, the current drops to zero, and the speed of the motor
reduces depending on the load. The changeover to delta then
causes a dramatic rise in the current, as the full mains voltage
is now applied to the motor windings. Voltage dips will result
on unreliable or weak supply systems. The motor torque also
jumps to a higher value during changeover, which causes addi-
tional loading on the entire drive system. If, for example,
pumps are operated with star-delta starters, a mechanical
damper is often used to provide system damping and to pre-
vent a critical “water hammer” to the system.
Automatic changeover from star to delta is usually controlled by
a timing relay on the contactor circuit. The time required for
starting in the star connection is dependent on the load on the
motor and should continue until the motor has reached about
75 to 80 % of its operating speed (nN) to ensure that the least
possible post-acceleration is necessary after changeover to
delta. This post-acceleration is associated in delta configuration
with high currents just as is the case with direct-on-line start-
ing.
Switching over too quickly between star and delta can result in
disconnection arcing (on the switching contacts) and can cause
7
TOR
Figure 7: Phase angle control and bypass contact
L1 L2 L3
M
3 ~
L1 L2 L3
M
3 ~
• Two-phase controlled
• Simple handling, with
three setting values
(tStart, UStart, tStop),
• Time-controlled, linear
voltage ramp
• Generally with internal
bypass contacts
• Attractively priced
alternative to the star-delta
starter
• Only in-line configuration
possible
• For smaller to medium
motor ratings (< 250 kW)
• Three-phase controlled
• For demanding tasks
• Preset applications
(characteristics)
• Programmable
• Control and closed-loop
circuits
• With current limitation (I2
t)
and motor protection
functions
• Communication enabled
(Fieldbus interface)
• In-line and in-delta
configuration possible
• For motor ratings from
approx. 7.5 kW
Figure 8: Features of the soft starter variants
a short-circuit. The changeover time interval should be selected
so that it is long enough to quench the arcs. At the same time,
the speed of the drive should be reduced as little as possible.
Special timing relays for star-delta changeover fulfil these
demands.
The correct phase sequence (see figure 6) for the changeover
from star to delta must be observed when connecting the con-
ductors to the motor and starter. The operating direction of the
motor must be considered and observed. Incorrect connection
of the phases can cause very high peak currents at restart,
because of the slight drop in speed during the de-energized
changeover interval. The current peaks endanger the motor
windings and stress the switchgear contacts unnecessarily.
When starting in the star connection, the star contactor first of
all connects the winding ends U2, V2, W2. Then the main con-
tactor applies the mains voltage (ULN) to the winding ends U1,
V1, W1. After the set starting time has timed out, the timing
relay switches off the star contactor, and the delta contactor
connects terminals U2, V2 and W2 to the mains voltage.
The design of the components in the main circuit of the motor
feeder is undertaken in accordance with the rated operational
current (Ie) of the motor and the utilization category AC-3
(standard IEC/EN60947-4-1); AC-3 = squirrel-cage motors:
start-up, switch off during operation. The overload relay is then
switched into the winding phase of the main contactor. The
current to be set is therefore factor 1/͙3 (~ 0.58 и Ie) less than
the rated current of the motor. The main and delta contactors
are also selected with this reduction factor (~ 0.58 и Ie). The star
contactor is designed for starting times up to 15 seconds for a
third (~ 0.33 и Ie) of the rated motor current. At starting times
(>15 s) of up to 60 seconds, the star contactor must be
selected to be equal to the magnitude of the main contactor.
Soft starters
In many cases, the direct-on-line start and the staged star-delta
start of the three-phase asynchronous motor is not the best
solution, as high peak currents influence the electrical supply,
and torque surges subject the mechanical components of the
machine or system to high levels of stress.
The soft starter provides a remedy. It enables a continuous and
surge-free increase in torque and also offers the opportunity for
a selective reduction in starting current. The motor voltage is
also increased within the adjustable starting time from a
selected starting voltage to the rated motor voltage. The soft
starter can also control the run down of the drive by reduction
of the voltage.
The characteristic curve of the three-phase asynchronous
motor only applies when the full mains voltage (ULN) is availa-
ble. If a lower voltage is applied, there is a quadratic reduction
in torque (M ~ U2). When compared, for example, to the star-
delta start-up, the motor voltage is reduced to 58 % (~ 1/͙3),
and the torque is reduced to about 33 % (one third).
The difference between the load characteristic (ML) and torque
characteristic of the motor (MM), and accordingly the accelera-
tion force, can be influenced by adjusting the motor voltage.
The soft starter should be preferred for all applications with
start-up under load (load cannot be connected after start-up)
to the star-delta configuration. It is a good replacement for the
star-delta configuration for economic reasons and also for
energy-conservation reasons, particularly for high-power drives.
The motor voltage in a soft starter is modified by phase angle
control of the sinusoidal half waves. For this purpose, two thyr-
istors in the phases are connected in anti-parallel; one of them
for the positive half wave and the other for the negative half
wave.
After the set start time (tStart) has timed out, the thyristors are
fully controlled (full sinusoidal half wave => Top Of Ramp: TOR).
As the thyristors are only active during the acceleration phase
or during the deceleration phase, they can be bypassed by so-
called bypass contacts during continuous operation. The losses
on the soft starter can be reduced by the considerably lower
contact resistance of the mechanical switching contacts.
On soft starters, a differentiation is made today between two
principle variants in the configuration of the power sections (fig-
ure 8).
8
L1
L2
L3
V1 W1U1
PE
I >I >I >
M
3 ~
L1
L2
L3
PE
Ie
In
U-Start
U
t-Start t-Stop
t
Figure 10: Motor feeder, soft starter DS7, in-line configuration,
combined with PKZM0
Figure 11: In-delta configuration
Figure 9: Voltage curve in a soft starter
The acceleration time of a drive with a soft starter results from
the settings of the start voltage (UStart) and the ramp time (tStart)
for the linear increase up to full mains voltage (ULN). The start
voltage determines the breakaway torque of the motor. High
start voltages and short ramp times correspond approximately
to the direct-on-line start. In practice, the required breakaway
torque (UStart) and then the shortest possible ramp time (tStart)
are initially set for the required soft start.
The set ramp time (tStart) is not the actual acceleration time of
the drive. This is dependent on the load and the breakaway
torque. The ramp time only controls the change in the voltage.
In the process, the current rises to its maximum and then falls
to the rated current, after the rated motor speed is achieved.
The maximum current now sets to suit the drive (motor plus
load) and cannot be determined in advance. As a result, drives
subject to high loads in conjunction with long ramp times can
lead to highly excessive thermal loading of the thyristors.
If a determined current level is not to be exceeded, a soft
starter featuring a current limit must be selected. This start-up
variant is frequently stipulated by the electricity supply compa-
nies, when large drives are connected to the public supply (e.g.
elevating pumps, fans for tunnel ventilation systems).
Soft starters also enable a time-controlled reduction of the
motor voltages and thus a controlled run down of the motors.
The set stopping time (tStop) must be longer than the load-
dependent, free run down time of the machine. This process is
also load-dependent just as the acceleration. The thyristors of
the soft starter are also subject to the same thermal stresses
that were present during the start-up process. If, for example,
the delay time is also activated for a soft starter with 10 permis-
sible starts per hour, 5 starts per hour (plus 5 stops per hour)
are permitted. The stop ramp time (tStop) can be selected inde-
pendently of the start time, which is frequently required on
pumps to prevent pressure waves (water hammer). Jerky
movements during an uncontrolled run down, which, for exam-
ple, can cause higher wear on drive belts, drive chains and
bearings, can also be prevented.
The design of the switchgear and protection devices (electro-
mechanical components) in the main circuit of the motor feeder
is undertaken in accordance with the rated operational current
(Ie) of the motor and the utilization category AC-3 (standard IEC
60947-4-1). The design of the soft starter is undertaken in
accordance with the rated operational current (Ie) of the motor
and the utilization category AC-53a or AC-53b (standard IEC/
EN60947-4-2):
• AC-3 = squirrel-cage motors: start-up, switch off during oper-
ation.
• AC-53a = control of a squirrel-cage motor: eight-hour duty
with starting currents for start processes, manoeuvring,
operation.
• AC-53b = control of a squirrel-cage motor: intermittent oper-
ation (intermittent operation means that the soft starter is
bypassed externally during continuous operation, e.g. by a
bypass contactor).
The in-line configuration corresponds with the motor feeder
during direct-on-line start. Only three cables lead to the motor
and are connected to U1, V1 and W1 in the terminal box. The
winding ends are switched as star or delta in accordance with
the available motor and supply voltage.
The in-delta configuration to this effect is only possible with
three-phase controlled soft starters. Hereby, the individual
motor windings are connected in series with the delta thyris-
tors. The soft starter design in this configuration can be a factor
1/͙3 (~ 0.58 и Ie) less than the rated current of the motor. From
9
L1
L2
L3
V1
W1
U1
V2
W2
U2
PE
I >I >I >
M
3 ~
PES
L1
L2
L3
PE
I >I >I >
M
3 ~
Figure 12: Motor feeder, soft starter, in-delta configuration
Figure 13: Motor feeder, frequency inverter, with the M-Max as
an example
an economic standpoint, this is an interesting connection vari-
ant with higher motor ratings.
The overload relay used can also be included in the winding
phase of the soft starter and can also be reduced by the factor
1/͙3 (~ 0.58 и Ie) lower rated current of the motor. If the over-
load relay is installed on the mains supply incomer, it will need
to be rated just like the contactor or the switchgear on the
mains supply side to the rated operational current (Ie) of the
motor.
Frequency inverters
The frequency inverter is ultimately the best solution for contin-
uous and stepless starting of the three-phase asynchronous
motor. The adjustable current limitation prevents high current
peaks in the electrical mains supply and abrupt loads in the
mechanical parts of the machine and systems.
In addition to the smooth start-up, the frequency inverter also
enables stepless speed (frequency) control of the three-phase
asynchronous motor. Whereas motors connected directly to
the mains supply can only achieve the ideal operating condi-
tions at the steady state operation point (= rating plate specifi-
cations), they can be utilized over the entire speed range with
frequency control, for example, from 4 V at 0.5 Hz to 400 V at
50 Hz. The constant ratio of voltage to frequency (U/f) guaran-
tee independent operating points with rated-load torque (MM).
When compared to the previously described solutions, the fre-
quency inverters appear to be the most expensive solution at
first glance. Higher acquisition costs and the necessary addi-
tional installation measures (shielded motor cables and RFI fil-
ter for electromagnetic compatibility, EMC) are the main rea-
sons. But during operation at the very latest, the soft motor
start in addition to the energy efficiency and process optimisa-
tion shows the economic benefits. This is especially true for
pumps and fans. By the matching of rotation speed to the pro-
duction process and the compensation for external interfer-
ence, the frequency controlled drive unit guarantees a longer
service life and functional security.
Further advantages of the frequency inverters include the
higher speed stability with fluctuations in the load (speed fluc-
tuations less than about one percent) and the option for a direct
change in the direction of rotation. As the rotating field in the
frequency inverter is generated electronically, a simple control
command is all that is required to change the phase sequence
and the direction of motor rotation. The electronic motor pro-
tection (I2
t control) integrated into frequency inverters also
assures safe operation without the need for additional safety
measures (overload relays). Depending on the method of imple-
mentation, parameterised temperature models in the frequency
inverter provide a higher level of motor heat protection. So-
called full motor protection is also possible in conjunction with
thermistors. Overload and underload detection also enhance
the operational safety of the drive unit.
The frequency inverter operates as a power converter in the
main circuit of a motor feeder. Separated from the power of the
DC link, the power converter draws active power via the recti-
fier from the mains supply and supplies the connected motor
with active and reactive power via the inverter. The reactive
power required for motor operation is provided by the capaci-
tors in the DC link. As far as the electrical supply is concerned,
the frequency-controlled drive behaves virtually like a resistive
load (cos ␸ ~ 1).
The power conversion and the associated current types must
be considered in the design of the switchgear and protective
devices on the motor feeder. For this purpose, the electro-
mechanical components (e.g. fuses, line reactors, mains con-
tactors) on the mains supply side of the frequency inverter are
dimensioned in accordance with the input current (active cur-
rent) and the utilization category AC-1 (standard IEC60947-4-1).
The components on the frequency inverter output (e.g. motor
reactors, sinewave filters, motor cables) are dimensioned in
accordance with the rated operational current of the connected
motor and the utilization category AC-3.
During motor operation, the frequency inverters differ through
the method of operation of the inverter that can be adjusted by
the user. In addition to the standard U/f control with a linear or
10
M
3 h
+ U
V
W
L1
L2/N
L3
• Rectifier for single-phase (up to about
2.2 kW) or three-phase mains supply
• Integrated radio interference filter for
electromagnetic compatibility (EMC)
• DC link
• DC link capacitors smooth the pulsed
voltage of the rectifier and provide
the required reactive power for motor
operation
• Control current supply of the frequency
inverter (switching mode power
supply)
• Inverter with IGBT (Insulated Gate
Bipolar Transistor)
• Switched-mode DC voltage with
sinusoidal-weighted pulse width
modulation (PWM)
• Shielded motor cables
• U/f characteristic control, slip control,
vector control
Figure 14: Main components of the frequency inverter
squared curve characteristic, sensorless speed control with slip
compensation and the torque-increasing vector control are
known methods currently in use today. Whereas U/f control
enables parallel operation of several motors – even with differ-
ent output ratings – on the output of the frequency inverter,
speed and vector control are only intended for operation with
individual motors. Hereby, the load-dependent operating behav-
iour of the (individual) three-phase asynchronous motor is opti-
mised automatically by the frequency inverter through an elec-
tronic motor model.
The detailed description of this specific operation procedure
with frequency inverters would however exceed the desired
simplified overview of the most well-known starting methods
for starting and controlling three-phase asynchronous motors.
11
Summary
Usage and application determine the selection of the start variant on the motor feeder for a three-phase asynchronous motor.
Comparison of the characteristic features of the starting methods described here:
DOL motor starter Star-delta starter Soft starter Frequency inverter
Block diagram
M
3 h
3
M
3 h
D y
3
M
3 h
3
M
3 h
3
Voltage curve
100 %
t
U
100 %
58 %
t
U
D
y
t
100 %
30 %
U
UStart
tStart
t
100 %
U
UBoost
t-acc
Load on mains at
start-up
high medium low to medium low
Current curve
2
3
4
5
6
I/Ie
n/nN
IN1
0.25 0.5 0.75 1
2
3
4
5
6
I/Ie
n/nN
IN1
0.25 0.5 0.75 1
2
3
4
5
6
I/Ie
n/nN
IN1
0.25 0.5 0.75 1
2
3
4
5
6
I/Ie
n/nN
IN1
0.25 0.5 0.75 1
Relative starting
current
4 … 8x Ie
(motor-dependent)
1.3 … 3x Ie
(~1/3 compared to
direct-on-line-start)
2 … 6x Ie
(reduced by voltage
control)
Յ1 (… 2x) Ie
(adjustable)
Torque
characteristic
2
3
I/Ie
n/nN
MN1
0.25 0.5 0.75 1
ML
2
3
I/Ie
n/nN
MN
ML
1
0.25 0.5 0.75 1
2
3
I/Ie
n/nN
MN1
0.25 0.5 0.75 1
ML
2
3
I/Ie
n/nN
MN1
0.25 0.5 0.75 1
ML
Relative starting
torque
1.5 … 3x MN
(motor-dependent)
0.5 … 1x MN
(~ 1/3 compared to
direct-on-line-start)
0.1 … 1x MN
(M ~ U2
, square-law,
reduced by voltage
control)
~0.1 … 2x MN
(M ~ U/f, adjustable
torque)
Features – High acceleration with
high starting current
– High mechanical
loading
– Start-up with reduced
current and torque
– Current and torque
peak at changeover
– Adjustable starting
characteristic
– Controller run out
possible
– High torque at low
current
– Adjustable starting
characteristic
Area of
application
Drives on stable supplies
that allow high starting
currents (torques)
Drives that are only
subject to load after
acceleration up to speed
Drives that require soft
torque progression or
current reduction
Drives that require
controlled soft start
and stepless speed
adjustment
Eaton Corporation
Eaton is a leading energy
management company. Eaton
operates worldwide with products,
systems and services in the
electrical, hydraulic, aerospace,
truck and automotive sectors.
Eatons Electrical Sector
Eatons Electrical Sector is the
worldwide leader in products,
systems and services for energy
distribution, safe electricity supply
and automation in industrial,
residential and purpose-built
buildings, public facilities, energy
providers, commerce and OEMs.
Eaton Electrical Sector includes the
brands Cutler-Hammer®
, Moeller®
,
Micro Innovation, Powerware®
,
Holec®
, MEM®
, Santak®
and MGE
Office Protection Systems™.
www.eaton.com
Addresses worldwide:
www.moeller.net/address
E-Mail: info-int@eaton.com
Internet: www.moeller.net
www.eaton.com
Publisher:
Eaton Corporation
Electrical Sector – EMEA
Eaton Industries GmbH
Hein-Moeller-Str. 7–11
D-53115 Bonn
© 2010 by Eaton Industries GmbH
Subject to alterations
VER8200-968en ip 04/10
Printed in Germany (04/10)
Article No.: 144056

Contenu connexe

Tendances

ABB Medium Voltage MV Indoor and Outdoor Current Transformers - ABB CT's Cur...
ABB Medium Voltage MV Indoor and Outdoor Current Transformers -  ABB CT's Cur...ABB Medium Voltage MV Indoor and Outdoor Current Transformers -  ABB CT's Cur...
ABB Medium Voltage MV Indoor and Outdoor Current Transformers - ABB CT's Cur...Thorne & Derrick International
 
Effect of converter dc fault on the transient stability of a multi machine po...
Effect of converter dc fault on the transient stability of a multi machine po...Effect of converter dc fault on the transient stability of a multi machine po...
Effect of converter dc fault on the transient stability of a multi machine po...Indra S Wahyudi
 
Lecture notes 2(Electrical machine-1)
Lecture notes 2(Electrical machine-1)Lecture notes 2(Electrical machine-1)
Lecture notes 2(Electrical machine-1)Nexus
 
ELB044 Lecture 18. Introduction to Induction Machines
ELB044 Lecture 18. Introduction to Induction MachinesELB044 Lecture 18. Introduction to Induction Machines
ELB044 Lecture 18. Introduction to Induction MachinesFrancisco Gonzalez-Longatt
 
Power transmission _distribution_line_trainer_tl_04_26
Power transmission _distribution_line_trainer_tl_04_26Power transmission _distribution_line_trainer_tl_04_26
Power transmission _distribution_line_trainer_tl_04_26Aidil Ab Gani
 
INDUCTION MOTOR
INDUCTION MOTORINDUCTION MOTOR
INDUCTION MOTORstudent
 
Dc machines electrical machines – i
Dc machines   electrical machines – iDc machines   electrical machines – i
Dc machines electrical machines – iSoumyadeep Nag
 
Three Phase Separately Exited Drives
Three Phase Separately Exited DrivesThree Phase Separately Exited Drives
Three Phase Separately Exited DrivesPreet_patel
 
4 the dc generator
4 the dc generator4 the dc generator
4 the dc generatorAngelic Sher
 

Tendances (20)

Basics of rotating machines
Basics of rotating machinesBasics of rotating machines
Basics of rotating machines
 
RGPV EX503 UNIT III
RGPV EX503 UNIT IIIRGPV EX503 UNIT III
RGPV EX503 UNIT III
 
Electric motors
Electric motorsElectric motors
Electric motors
 
ABB Medium Voltage MV Indoor and Outdoor Current Transformers - ABB CT's Cur...
ABB Medium Voltage MV Indoor and Outdoor Current Transformers -  ABB CT's Cur...ABB Medium Voltage MV Indoor and Outdoor Current Transformers -  ABB CT's Cur...
ABB Medium Voltage MV Indoor and Outdoor Current Transformers - ABB CT's Cur...
 
machine Lecture 6
machine Lecture 6machine Lecture 6
machine Lecture 6
 
Effect of converter dc fault on the transient stability of a multi machine po...
Effect of converter dc fault on the transient stability of a multi machine po...Effect of converter dc fault on the transient stability of a multi machine po...
Effect of converter dc fault on the transient stability of a multi machine po...
 
Generator ppt 1
Generator ppt 1Generator ppt 1
Generator ppt 1
 
Electrical machine slide share
Electrical machine slide shareElectrical machine slide share
Electrical machine slide share
 
Lecture notes 2(Electrical machine-1)
Lecture notes 2(Electrical machine-1)Lecture notes 2(Electrical machine-1)
Lecture notes 2(Electrical machine-1)
 
ELB044 Lecture 18. Introduction to Induction Machines
ELB044 Lecture 18. Introduction to Induction MachinesELB044 Lecture 18. Introduction to Induction Machines
ELB044 Lecture 18. Introduction to Induction Machines
 
Power transmission _distribution_line_trainer_tl_04_26
Power transmission _distribution_line_trainer_tl_04_26Power transmission _distribution_line_trainer_tl_04_26
Power transmission _distribution_line_trainer_tl_04_26
 
Electrical Machines
Electrical MachinesElectrical Machines
Electrical Machines
 
INDUCTION MOTOR
INDUCTION MOTORINDUCTION MOTOR
INDUCTION MOTOR
 
Dc machines electrical machines – i
Dc machines   electrical machines – iDc machines   electrical machines – i
Dc machines electrical machines – i
 
Principios de generación de voltaje
Principios de generación de voltajePrincipios de generación de voltaje
Principios de generación de voltaje
 
Unit 1
Unit 1Unit 1
Unit 1
 
Three Phase Separately Exited Drives
Three Phase Separately Exited DrivesThree Phase Separately Exited Drives
Three Phase Separately Exited Drives
 
Dcmotor
DcmotorDcmotor
Dcmotor
 
4 the dc generator
4 the dc generator4 the dc generator
4 the dc generator
 
Mag ch of dc shunt generator
Mag ch of dc shunt generatorMag ch of dc shunt generator
Mag ch of dc shunt generator
 

Similaire à Starting and control methods for three-phase asynchronous motors

ENERGY EFFICIENT VARIABLE SPEED HIGH POWER FACTOR THREE PHASE INDUCTION MOTOR...
ENERGY EFFICIENT VARIABLE SPEED HIGH POWER FACTOR THREE PHASE INDUCTION MOTOR...ENERGY EFFICIENT VARIABLE SPEED HIGH POWER FACTOR THREE PHASE INDUCTION MOTOR...
ENERGY EFFICIENT VARIABLE SPEED HIGH POWER FACTOR THREE PHASE INDUCTION MOTOR...Journal For Research
 
POWER SYSTEM ANALYSIS-3
POWER SYSTEM ANALYSIS-3POWER SYSTEM ANALYSIS-3
POWER SYSTEM ANALYSIS-3M Ugur Kebir
 
Major project
Major projectMajor project
Major projectMusi Raju
 
Ccccccccccccccccccc
CccccccccccccccccccCcccccccccccccccccc
CccccccccccccccccccMusi Raju
 
Machines dc motors
Machines   dc motorsMachines   dc motors
Machines dc motorssld1950
 
USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SU...
USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SU...USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SU...
USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SU...IAEME Publication
 
Motors and motor starters
Motors and motor startersMotors and motor starters
Motors and motor startersRamesh Meti
 
Single phase-induction-motor(eee499.blogspot.com)
Single phase-induction-motor(eee499.blogspot.com)Single phase-induction-motor(eee499.blogspot.com)
Single phase-induction-motor(eee499.blogspot.com)slmnsvn
 
Electrical and electronics form five notes
Electrical and electronics form five notesElectrical and electronics form five notes
Electrical and electronics form five notesRobert Benjamin
 
CH-2_3 Induction Machines.ppt
CH-2_3 Induction Machines.pptCH-2_3 Induction Machines.ppt
CH-2_3 Induction Machines.pptDaaniyyeeAbdiisaa
 
Introduction to single phase induction motor
Introduction to single phase induction motorIntroduction to single phase induction motor
Introduction to single phase induction motorprajpurkait
 
Single Phase Induction Motor
Single Phase Induction MotorSingle Phase Induction Motor
Single Phase Induction Motorprajpurkait
 
SOLID STATE AC DRIVES ,UNIT V,ME (PE&D),ANNAUNIVERSITY SYLLABUS
SOLID STATE AC DRIVES ,UNIT V,ME (PE&D),ANNAUNIVERSITY SYLLABUSSOLID STATE AC DRIVES ,UNIT V,ME (PE&D),ANNAUNIVERSITY SYLLABUS
SOLID STATE AC DRIVES ,UNIT V,ME (PE&D),ANNAUNIVERSITY SYLLABUSDr SOUNDIRARAJ N
 
Report On diode clamp three level inverter
Report On diode clamp three level inverterReport On diode clamp three level inverter
Report On diode clamp three level inverterVinay Singh
 
Electrical energy issues presented by arshad khan chiniot power limited
Electrical energy issues presented by arshad khan chiniot  power limitedElectrical energy issues presented by arshad khan chiniot  power limited
Electrical energy issues presented by arshad khan chiniot power limitedarshadkhanmarwat
 
Lab maquinas 2 practica 6 generador sincrono i
Lab maquinas 2 practica 6 generador sincrono iLab maquinas 2 practica 6 generador sincrono i
Lab maquinas 2 practica 6 generador sincrono iDuperlyLopezGamboa1
 
synchronous motor, Starting Torque, Types, Equivalent Circuit, Torque-speed c...
synchronous motor, Starting Torque, Types, Equivalent Circuit, Torque-speed c...synchronous motor, Starting Torque, Types, Equivalent Circuit, Torque-speed c...
synchronous motor, Starting Torque, Types, Equivalent Circuit, Torque-speed c...Waqas Afzal
 

Similaire à Starting and control methods for three-phase asynchronous motors (20)

Mech EE6365 EE lab_manual
Mech EE6365 EE lab_manualMech EE6365 EE lab_manual
Mech EE6365 EE lab_manual
 
ENERGY EFFICIENT VARIABLE SPEED HIGH POWER FACTOR THREE PHASE INDUCTION MOTOR...
ENERGY EFFICIENT VARIABLE SPEED HIGH POWER FACTOR THREE PHASE INDUCTION MOTOR...ENERGY EFFICIENT VARIABLE SPEED HIGH POWER FACTOR THREE PHASE INDUCTION MOTOR...
ENERGY EFFICIENT VARIABLE SPEED HIGH POWER FACTOR THREE PHASE INDUCTION MOTOR...
 
POWER SYSTEM ANALYSIS-3
POWER SYSTEM ANALYSIS-3POWER SYSTEM ANALYSIS-3
POWER SYSTEM ANALYSIS-3
 
Major project
Major projectMajor project
Major project
 
Ccccccccccccccccccc
CccccccccccccccccccCcccccccccccccccccc
Ccccccccccccccccccc
 
EMEC-II, unit 1
EMEC-II, unit 1EMEC-II, unit 1
EMEC-II, unit 1
 
Machines dc motors
Machines   dc motorsMachines   dc motors
Machines dc motors
 
ac_machinery_im.pdf
ac_machinery_im.pdfac_machinery_im.pdf
ac_machinery_im.pdf
 
USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SU...
USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SU...USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SU...
USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SU...
 
Motors and motor starters
Motors and motor startersMotors and motor starters
Motors and motor starters
 
Single phase-induction-motor(eee499.blogspot.com)
Single phase-induction-motor(eee499.blogspot.com)Single phase-induction-motor(eee499.blogspot.com)
Single phase-induction-motor(eee499.blogspot.com)
 
Electrical and electronics form five notes
Electrical and electronics form five notesElectrical and electronics form five notes
Electrical and electronics form five notes
 
CH-2_3 Induction Machines.ppt
CH-2_3 Induction Machines.pptCH-2_3 Induction Machines.ppt
CH-2_3 Induction Machines.ppt
 
Introduction to single phase induction motor
Introduction to single phase induction motorIntroduction to single phase induction motor
Introduction to single phase induction motor
 
Single Phase Induction Motor
Single Phase Induction MotorSingle Phase Induction Motor
Single Phase Induction Motor
 
SOLID STATE AC DRIVES ,UNIT V,ME (PE&D),ANNAUNIVERSITY SYLLABUS
SOLID STATE AC DRIVES ,UNIT V,ME (PE&D),ANNAUNIVERSITY SYLLABUSSOLID STATE AC DRIVES ,UNIT V,ME (PE&D),ANNAUNIVERSITY SYLLABUS
SOLID STATE AC DRIVES ,UNIT V,ME (PE&D),ANNAUNIVERSITY SYLLABUS
 
Report On diode clamp three level inverter
Report On diode clamp three level inverterReport On diode clamp three level inverter
Report On diode clamp three level inverter
 
Electrical energy issues presented by arshad khan chiniot power limited
Electrical energy issues presented by arshad khan chiniot  power limitedElectrical energy issues presented by arshad khan chiniot  power limited
Electrical energy issues presented by arshad khan chiniot power limited
 
Lab maquinas 2 practica 6 generador sincrono i
Lab maquinas 2 practica 6 generador sincrono iLab maquinas 2 practica 6 generador sincrono i
Lab maquinas 2 practica 6 generador sincrono i
 
synchronous motor, Starting Torque, Types, Equivalent Circuit, Torque-speed c...
synchronous motor, Starting Torque, Types, Equivalent Circuit, Torque-speed c...synchronous motor, Starting Torque, Types, Equivalent Circuit, Torque-speed c...
synchronous motor, Starting Torque, Types, Equivalent Circuit, Torque-speed c...
 

Plus de morin moli

Motor control fundamentals
Motor control fundamentals Motor control fundamentals
Motor control fundamentals morin moli
 
Cours et exercices generale en electricite
Cours et exercices generale en electriciteCours et exercices generale en electricite
Cours et exercices generale en electricitemorin moli
 
DE L’AUTOMATE PROGRAMMABLE
 DE L’AUTOMATE PROGRAMMABLE  DE L’AUTOMATE PROGRAMMABLE
DE L’AUTOMATE PROGRAMMABLE morin moli
 
Electronics a first course
Electronics a first course Electronics a first course
Electronics a first course morin moli
 
Cours electricite : le moteur asynchrone triphase
Cours electricite : le moteur asynchrone triphaseCours electricite : le moteur asynchrone triphase
Cours electricite : le moteur asynchrone triphasemorin moli
 
Exercices corriges en electricite triphase
Exercices corriges en electricite triphaseExercices corriges en electricite triphase
Exercices corriges en electricite triphasemorin moli
 
MATÉRIAUX ET APPAREILLAGE ÉLECTRIQUE
MATÉRIAUX ET APPAREILLAGE ÉLECTRIQUEMATÉRIAUX ET APPAREILLAGE ÉLECTRIQUE
MATÉRIAUX ET APPAREILLAGE ÉLECTRIQUEmorin moli
 
logique combinatoire
logique combinatoire logique combinatoire
logique combinatoire morin moli
 
COURS APPAREILLAGES ET SCHEMAS ELECTRIQUES
COURS APPAREILLAGES ET SCHEMAS ELECTRIQUESCOURS APPAREILLAGES ET SCHEMAS ELECTRIQUES
COURS APPAREILLAGES ET SCHEMAS ELECTRIQUESmorin moli
 
basic electrical and electronics engineering
basic electrical and electronics engineeringbasic electrical and electronics engineering
basic electrical and electronics engineeringmorin moli
 
cours machines electriques
cours machines electriquescours machines electriques
cours machines electriquesmorin moli
 
Induction motors
Induction motorsInduction motors
Induction motorsmorin moli
 
Basic electronics
Basic electronicsBasic electronics
Basic electronicsmorin moli
 
Les installations électriques industrielles
Les  installations  électriques  industriellesLes  installations  électriques  industrielles
Les installations électriques industriellesmorin moli
 
Starting of 3-Phase Induction Motors
Starting of 3-Phase Induction MotorsStarting of 3-Phase Induction Motors
Starting of 3-Phase Induction Motorsmorin moli
 
Introduction to Programmable Logic Controllers (PLC's)
Introduction to Programmable Logic Controllers (PLC's)Introduction to Programmable Logic Controllers (PLC's)
Introduction to Programmable Logic Controllers (PLC's)morin moli
 
Câblage Entrées / Sorties Automate programmable
Câblage Entrées / Sorties Automate programmable Câblage Entrées / Sorties Automate programmable
Câblage Entrées / Sorties Automate programmable morin moli
 
Étude des constituants d’un départ moteur.
Étude des constituants d’un départ moteur.Étude des constituants d’un départ moteur.
Étude des constituants d’un départ moteur.morin moli
 
Cours et travaux diriges sur l'automatisme et les systemes automatises
Cours et travaux diriges sur l'automatisme et les systemes automatisesCours et travaux diriges sur l'automatisme et les systemes automatises
Cours et travaux diriges sur l'automatisme et les systemes automatisesmorin moli
 

Plus de morin moli (20)

Motor control fundamentals
Motor control fundamentals Motor control fundamentals
Motor control fundamentals
 
Cours et exercices generale en electricite
Cours et exercices generale en electriciteCours et exercices generale en electricite
Cours et exercices generale en electricite
 
DE L’AUTOMATE PROGRAMMABLE
 DE L’AUTOMATE PROGRAMMABLE  DE L’AUTOMATE PROGRAMMABLE
DE L’AUTOMATE PROGRAMMABLE
 
Electronics a first course
Electronics a first course Electronics a first course
Electronics a first course
 
Cours electricite : le moteur asynchrone triphase
Cours electricite : le moteur asynchrone triphaseCours electricite : le moteur asynchrone triphase
Cours electricite : le moteur asynchrone triphase
 
Exercices corriges en electricite triphase
Exercices corriges en electricite triphaseExercices corriges en electricite triphase
Exercices corriges en electricite triphase
 
MATÉRIAUX ET APPAREILLAGE ÉLECTRIQUE
MATÉRIAUX ET APPAREILLAGE ÉLECTRIQUEMATÉRIAUX ET APPAREILLAGE ÉLECTRIQUE
MATÉRIAUX ET APPAREILLAGE ÉLECTRIQUE
 
logique combinatoire
logique combinatoire logique combinatoire
logique combinatoire
 
Grafcet cours
Grafcet coursGrafcet cours
Grafcet cours
 
COURS APPAREILLAGES ET SCHEMAS ELECTRIQUES
COURS APPAREILLAGES ET SCHEMAS ELECTRIQUESCOURS APPAREILLAGES ET SCHEMAS ELECTRIQUES
COURS APPAREILLAGES ET SCHEMAS ELECTRIQUES
 
basic electrical and electronics engineering
basic electrical and electronics engineeringbasic electrical and electronics engineering
basic electrical and electronics engineering
 
cours machines electriques
cours machines electriquescours machines electriques
cours machines electriques
 
Induction motors
Induction motorsInduction motors
Induction motors
 
Basic electronics
Basic electronicsBasic electronics
Basic electronics
 
Les installations électriques industrielles
Les  installations  électriques  industriellesLes  installations  électriques  industrielles
Les installations électriques industrielles
 
Starting of 3-Phase Induction Motors
Starting of 3-Phase Induction MotorsStarting of 3-Phase Induction Motors
Starting of 3-Phase Induction Motors
 
Introduction to Programmable Logic Controllers (PLC's)
Introduction to Programmable Logic Controllers (PLC's)Introduction to Programmable Logic Controllers (PLC's)
Introduction to Programmable Logic Controllers (PLC's)
 
Câblage Entrées / Sorties Automate programmable
Câblage Entrées / Sorties Automate programmable Câblage Entrées / Sorties Automate programmable
Câblage Entrées / Sorties Automate programmable
 
Étude des constituants d’un départ moteur.
Étude des constituants d’un départ moteur.Étude des constituants d’un départ moteur.
Étude des constituants d’un départ moteur.
 
Cours et travaux diriges sur l'automatisme et les systemes automatises
Cours et travaux diriges sur l'automatisme et les systemes automatisesCours et travaux diriges sur l'automatisme et les systemes automatises
Cours et travaux diriges sur l'automatisme et les systemes automatises
 

Dernier

Web & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfWeb & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfJayanti Pande
 
Measures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeMeasures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeThiyagu K
 
Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)eniolaolutunde
 
A Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformA Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformChameera Dedduwage
 
BASLIQ CURRENT LOOKBOOK LOOKBOOK(1) (1).pdf
BASLIQ CURRENT LOOKBOOK  LOOKBOOK(1) (1).pdfBASLIQ CURRENT LOOKBOOK  LOOKBOOK(1) (1).pdf
BASLIQ CURRENT LOOKBOOK LOOKBOOK(1) (1).pdfSoniaTolstoy
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdfQucHHunhnh
 
Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Sapana Sha
 
The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13Steve Thomason
 
Beyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global ImpactBeyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global ImpactPECB
 
Interactive Powerpoint_How to Master effective communication
Interactive Powerpoint_How to Master effective communicationInteractive Powerpoint_How to Master effective communication
Interactive Powerpoint_How to Master effective communicationnomboosow
 
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...Marc Dusseiller Dusjagr
 
Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104misteraugie
 
Sanyam Choudhary Chemistry practical.pdf
Sanyam Choudhary Chemistry practical.pdfSanyam Choudhary Chemistry practical.pdf
Sanyam Choudhary Chemistry practical.pdfsanyamsingh5019
 
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...RKavithamani
 
How to Make a Pirate ship Primary Education.pptx
How to Make a Pirate ship Primary Education.pptxHow to Make a Pirate ship Primary Education.pptx
How to Make a Pirate ship Primary Education.pptxmanuelaromero2013
 
Student login on Anyboli platform.helpin
Student login on Anyboli platform.helpinStudent login on Anyboli platform.helpin
Student login on Anyboli platform.helpinRaunakKeshri1
 
Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17Celine George
 
Organic Name Reactions for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions  for the students and aspirants of Chemistry12th.pptxOrganic Name Reactions  for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions for the students and aspirants of Chemistry12th.pptxVS Mahajan Coaching Centre
 

Dernier (20)

Web & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfWeb & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdf
 
Measures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeMeasures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and Mode
 
Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)
 
A Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformA Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy Reform
 
BASLIQ CURRENT LOOKBOOK LOOKBOOK(1) (1).pdf
BASLIQ CURRENT LOOKBOOK  LOOKBOOK(1) (1).pdfBASLIQ CURRENT LOOKBOOK  LOOKBOOK(1) (1).pdf
BASLIQ CURRENT LOOKBOOK LOOKBOOK(1) (1).pdf
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdf
 
Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111
 
The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13
 
Beyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global ImpactBeyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global Impact
 
Interactive Powerpoint_How to Master effective communication
Interactive Powerpoint_How to Master effective communicationInteractive Powerpoint_How to Master effective communication
Interactive Powerpoint_How to Master effective communication
 
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
 
Staff of Color (SOC) Retention Efforts DDSD
Staff of Color (SOC) Retention Efforts DDSDStaff of Color (SOC) Retention Efforts DDSD
Staff of Color (SOC) Retention Efforts DDSD
 
Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104
 
Sanyam Choudhary Chemistry practical.pdf
Sanyam Choudhary Chemistry practical.pdfSanyam Choudhary Chemistry practical.pdf
Sanyam Choudhary Chemistry practical.pdf
 
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptxINDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
 
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...
 
How to Make a Pirate ship Primary Education.pptx
How to Make a Pirate ship Primary Education.pptxHow to Make a Pirate ship Primary Education.pptx
How to Make a Pirate ship Primary Education.pptx
 
Student login on Anyboli platform.helpin
Student login on Anyboli platform.helpinStudent login on Anyboli platform.helpin
Student login on Anyboli platform.helpin
 
Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17
 
Organic Name Reactions for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions  for the students and aspirants of Chemistry12th.pptxOrganic Name Reactions  for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions for the students and aspirants of Chemistry12th.pptx
 

Starting and control methods for three-phase asynchronous motors

  • 1. www.eaton.com www.moeller.net Technical Paper Jörg Randermann Starting and control of three-phase asynchronous motors
  • 2. 2 The three-phase asynchronous motor is the most widely used electric motor worldwide in industrial facilities and large buildings. Simple in terms of design and handling, flexible in diverse fields of application and economical to operate. It is the most favourable drive solution in terms of price and quality. Characteristic for the three-phase motor is the high current load on the mains supply with direct-on-line starting. High starting and surge currents result when the full voltage is applied, causing troublesome voltage dips on the mains supply and transient torque effects in mechanical systems. Since the invention of the three-phase motor – more than a century ago (1889) –, start-up solution concepts have been devised, which have intended to eliminate the unpleasant side-effects. Yet exactly which of these solution concepts fulfil the desire for satisfactory start-up and optimum operating performance is dependent on the application and ultimately the economic aspects as well. To facilitate a simplified overview, the four most important and most well-known start-up methods for starting and controlling three-phase asynchronous motors used in practice are presented. In the process, we deliberately dispense with the description of the devices and functions, and general basic knowledge of electrical drive engineering is assumed. Preface
  • 3. 3 M a F1 3 / N / PE / AC 50/60 Hz Q1 F2 M1 3~ M B1 T1Q2 3~ M d 3~ M b c 3~ Yd With regard to its construction and winding connection of its passive rotor, the three- phase asynchronous motor is also referred to as a squirrel-cage motor or squirrel-cage rotor (motor). Comparable with a rotating trans- former and in accordance with its mode of action, the term induction motor is also gener- ally used. Designs with separate stator wind- ings are referred to as Dahlander-connection or pole-changing motors. A further variant is the slipring rotor (motor). In this case, the wind- ings of the rotor are connected to three slip rings and are only interconnected using resis- tors outside the motor. Start variants for three-phase asynchronous motors Just as diverse as the different forms and des- ignations with the asynchronous motor is the diversity of the respective motor feeders for start-up and control. To facilitate a simplified overview, the four most well-known and important motor feeders are examined in the following. A three-phase AC current incoming mains supply earthed as the neutral point (3 / N / PE / AC 50/60 Hz) is assumed. Eaton Moeller offers a complete range on the motor feeders for switching, protection and control of three-phase asynchronous motors for the entire range of start variants shown here. Figure 1: Motor start variants F1 = fuse (short-circuit and line protection) Q1 = switching (contactors) F2 = motor protection (protection against thermal overload, overload relay) M1 = three-phase asynchronous motor a Direct-on-line motor start. b Star-delta starter, the most well-known and used starting variant. c Soft starter (Q2), the continuous and stepless motor start. A modern, electronic alternative to the star-delta starter. d Frequency inverter (T1), controlled, stepless motor start with rated-load torque. Frequency inverters also enable stepless speed control and feature integrated electronic motor protec- tion (I2t). Depending on the characteristic, they also allow exact speed control (option, pulse generator B1) on the otherwise slip-dependent asynchronous motors.
  • 4. 4 a b c a 90°0 L1 L2 L3 360° L1 120° 120° 120° 180° 270° L1 L2 L3 U1 V2 W3 L1 L2 L3 U1 V2 W3 Star connection Delta connection 1410 min-1 230 / 400 V 14.5 / 8.5 A 50 Hz IP 54 Iso. KI F 4.0 KWS1 cos v 0.82 d / Y 1410 min-1 400 / 690 V 8.5 / 4.9 A 50 Hz IP 54 Iso. KI F 4.0 KWS1 cos v 0.82 d / Y L1 L3L2 V1 V2 U1 W2W2 U2 ULNILN L1 L3L2 U1 W1 V1 V2 W2 U2 ULNLN ULN = √3 • UW ILN = IW ULN = UW ILN = √3 • IW U1 V1 W1 W2 U2 V2 L1 L2 L3 ULNILN U1 V1 W1 W2 U2 V2 L1 L2 L3 ULNILN • With its voltage specification of 230/400 V, this motor must be connected to the three-phase supply (ULN = 400 V) in a star configuration. • The voltage in a motor winding is designed for a maximum of 230 V here. • The three winding phases (W2-U2-V2) are configured in the terminal box to the so-called star point. The voltage for the individual phases to the star point is 230 V. • With its voltage specification of 400/690 V, this motor must be connected to the three-phase supply (ULN = 400 V) in a delta configuration. • Every motor winding is configured for a maximum phase voltage of 400 V and can be directly connected. • For direct-on-line starting, the ends of the phase windings are connected in the terminal box (U1-W2, V1-U2, W1-V2) to the individual phases. Figure 2: Motor connection circuit, clockwise Figure 3: Clockwise rotation: phase sequence – terminal box – drive end Connection of the three-phase motor When the three-phase motor is connected to the mains, the data on the rating plate must correspond with the main voltage and mains frequency. The connection is implemented via six screw terminals (standard version) in the terminal box of the motor and distinguishes between two types of circuit, the star connection and the delta connection. Example for a mains sup- ply voltage of 3 AC 400 V, 50 Hz (see figure 2). Generally, the properties of a three-phase motor are defined in standards (DIN/VDE 0530, IEC/EN 60034). However, the con- structive design is the manufacturers’ domain. For example, in the price-sensitive market for smaller motor output ratings (<4 kW) – particularly those used with pumps and fans – time and again you will find motors without a terminal box. Here the windings are connected internally in the motor to a star point, and only three connection cables are made available for the assigned rated voltage. Regardless of the design configuration (with/without terminal box), the connections of the three-phase motor must be denoted, so that their alphabetical sequence (e.g. U1, V1, W1) corresponds with the mains voltage sequence (L1, L2, L3) and causes the motor to rotate clockwise. The direction of rotation is specified by looking directly at the drive end (shaft of the motor). On motors with two shaft ends, the driving end is denoted with D, the non-driving end with N (D = Drive, N = No drive). Anti-clockwise rotation of the three-phase motor is
  • 5. 5 MN nN n nS MA MM MB MK ML MS IA IN M, I 0 Figure 4: Characteristic starting curve of the three-phase asyn- chronous motor f = [Hz] = 1/sec n = [min–1 ] 1 min = 60 sec P = [kW] MN = [Nm]P = MN • n 9550 n = f • (1 - s) p s = ns - n • 100% ns implemented by exchanging two connection cables (mains phases). The operating point (MM) of the three-phase asynchronous motor is described by the rated voltage range and the corre- sponding frequency (e.g. 400 V / 50 Hz). The (rotational) speed is determined by the frequency of the mains supply (n ~ f). It is load-dependent and is only maintained as long as the motor torque (MM) and load torque (ML) have the same magnitude. The electrical and mechanical rating data of the operating point must be specified on the motor rating plate. The operation data are unstable during the starting process (acceleration process). Steady-state operation of the drive is only permissible in the operating point (MM) range. IA = starting current IN = rated current at the operating point MA = starting torque MB = acceleration torque (MM > ML) MK = breakdown torque ML = load torque MM= motor torque (operating point) MN = rated-load torque, steady-state intersection point of the three-phase speed-torque characteristic with the load characteristic n = speed (actual value) nN = rated speed at the operating point ns = synchronous speed (ns – nN = slip speed) Direct-on-line motor start The direct-on-line motor start is the easiest method for starting up three-phase asynchronous motors. The stator windings are directly connected to the mains supply in a single switching process. Large starting currents (surge currents) result by applying the full mains voltage, which in turn cause troublesome voltage changes on the mains supply. For this reason, the electricity supply companies limit the permissible rated powers of motors connected to the mains supply. These limit values can vary from grid to grid. In public electrical power grids, these limita- tions are generally met when the three-phase motor that is occasionally started has an apparent power of less than 5.2 kVA or at higher apparent powers, the starting current does not exceed 60 A. At a mains voltage of 400 V and an 8-fold starting current, this corresponds with a rated current of 7.5 A or a delivered motor output of 4 kW (shaft output power). On motors with occasionally higher starting currents than 60 A and motors with starting currents of more than 30 A, which cause feedback disturbances on the public supply, e.g. by a heavy-duty start, frequent switching or varying current con- sumption (elevators, reciprocating saws), further measures for avoidance of the disruptive voltage variations must be under- taken. Motors with powers exceeding 4 kW and voltages rated at 400/690 V can be stated in this case using a star-delta config- uration. Direct-on-line start imposes the motor windings to thermal stresses and, when only briefly, to momentary electro-dynamic forces. Very frequent, direct-on-line starting reduces the life of the windings on a standard motor (e.g. periodic intermittent operation). Blockage of the rotor (locked rotor) is a serious malfunction that can lead to thermal destruction of the three-phase asynchro- nous motor. Every motor feeder must be protected by a cur- rent-dependent protective device to prevent against this type of thermal overload. An attractively priced solution here is the use of overload relays, better known as motor protection relays or bimetal relays. These overload relays are referred to as motor-protective cir- cuit-breakers in combination with a contact module. The syno- nym for this is the PKZM. In the motor feeder, it protects the switchgear (contactor DILM), incomers and motor windings against destruction due to thermal overload (locked rotor pro- tection) and short-circuit, even when one of the main poles (L1, L2, L3) has been lost. For this purpose, the rated current of the motor must be set on the motor-protective circuit-breaker, and the connection cables in the motor feeder must be rated for this setting value. The design of the components in the main circuit of the motor feeder is undertaken in accordance with the rated operational current (Ie) of the motor and the utilization category AC-3 (standard IEC/EN60947-4-1); AC-3 = squirrel-cage motors: start-up, switch off during operation. The selection of a suitable motor-protective circuit-breaker is decisive for the functional safety and service life of a motor. The motor-starter combination (MSC) offers an ideal complete solution for direct start on the motor feeder. The MSC in its standard design consists of a motor-protective circuit-breaker PKZM0 with plug connector and a contactor DILM. In the ver-
  • 6. 6 L1 L2 L3 V1 W1U1 PE I >I >I > M 3 ~ L1 L2 L3 V1 W1 U1 W2 V2 U2 PE I >I >I > M 3 ~ Figure 5: Motor feeder, direct-on-line starter, clockwise (forward) rotation, example of MSC Figure 6: Motor feeder, star-delta starter, clockwise (forward) rotation, example of SDAINL Motor contactor in star and delta configuration Bimetall relay 0.58 x Ie ta Յ 15 s sion MSC-DE, the electronic motor-protective circuit-breaker PKE for motor currents up to 65 A offers an innovative alterna- tive to bimetal solutions (PKZM0). With its high-level of flexibil- ity and the same accessory components, the MSC-DE fulfils the customer demands for exchangeable “standard“ devices. Star-delta motor start With a star-delta motor start, the start-up of the three-phase asynchronous motor is implemented by a changeover of the windings. The jumpers in the motor terminal box are omitted, and all 6 winding connections are connected to the mains sup- ply using a so-called star-delta switch (manually actuated switch or automatic contactor circuit). During the operating connection, the windings of the motor are connected in delta. The winding voltage (UW) must therefore be equal to the phase voltage (ULN) of the three-phase system. For example, at a mains supply voltage of 3 AC 400 V the voltage ratings on the rating plate of the motor must be specified as 400/690 V. In a star connection, the mains voltage (ULN) on the individual motor windings is reduced by a factor of 1/͙3 (~ 0.58). For example: 400 V и 1/͙3 = 230 V. Starting torque and inrush cur- rent are (in the star connection) reduced to about a third of the values for the delta connection. Typical starting current: 2...2.5 Ie. Due to the reduced starting torque, the star-delta configuration is only suitable for drives with smaller load torques or load tor- ques (ML) that increase with speed, such as is the case with pumps and fans (ventilators/blowers). They are also used where the drive is only subject to a load after it has accelerated up to speed, for example, with presses and centrifuges. With the changeover of the circuit configuration from star to delta, the current drops to zero, and the speed of the motor reduces depending on the load. The changeover to delta then causes a dramatic rise in the current, as the full mains voltage is now applied to the motor windings. Voltage dips will result on unreliable or weak supply systems. The motor torque also jumps to a higher value during changeover, which causes addi- tional loading on the entire drive system. If, for example, pumps are operated with star-delta starters, a mechanical damper is often used to provide system damping and to pre- vent a critical “water hammer” to the system. Automatic changeover from star to delta is usually controlled by a timing relay on the contactor circuit. The time required for starting in the star connection is dependent on the load on the motor and should continue until the motor has reached about 75 to 80 % of its operating speed (nN) to ensure that the least possible post-acceleration is necessary after changeover to delta. This post-acceleration is associated in delta configuration with high currents just as is the case with direct-on-line start- ing. Switching over too quickly between star and delta can result in disconnection arcing (on the switching contacts) and can cause
  • 7. 7 TOR Figure 7: Phase angle control and bypass contact L1 L2 L3 M 3 ~ L1 L2 L3 M 3 ~ • Two-phase controlled • Simple handling, with three setting values (tStart, UStart, tStop), • Time-controlled, linear voltage ramp • Generally with internal bypass contacts • Attractively priced alternative to the star-delta starter • Only in-line configuration possible • For smaller to medium motor ratings (< 250 kW) • Three-phase controlled • For demanding tasks • Preset applications (characteristics) • Programmable • Control and closed-loop circuits • With current limitation (I2 t) and motor protection functions • Communication enabled (Fieldbus interface) • In-line and in-delta configuration possible • For motor ratings from approx. 7.5 kW Figure 8: Features of the soft starter variants a short-circuit. The changeover time interval should be selected so that it is long enough to quench the arcs. At the same time, the speed of the drive should be reduced as little as possible. Special timing relays for star-delta changeover fulfil these demands. The correct phase sequence (see figure 6) for the changeover from star to delta must be observed when connecting the con- ductors to the motor and starter. The operating direction of the motor must be considered and observed. Incorrect connection of the phases can cause very high peak currents at restart, because of the slight drop in speed during the de-energized changeover interval. The current peaks endanger the motor windings and stress the switchgear contacts unnecessarily. When starting in the star connection, the star contactor first of all connects the winding ends U2, V2, W2. Then the main con- tactor applies the mains voltage (ULN) to the winding ends U1, V1, W1. After the set starting time has timed out, the timing relay switches off the star contactor, and the delta contactor connects terminals U2, V2 and W2 to the mains voltage. The design of the components in the main circuit of the motor feeder is undertaken in accordance with the rated operational current (Ie) of the motor and the utilization category AC-3 (standard IEC/EN60947-4-1); AC-3 = squirrel-cage motors: start-up, switch off during operation. The overload relay is then switched into the winding phase of the main contactor. The current to be set is therefore factor 1/͙3 (~ 0.58 и Ie) less than the rated current of the motor. The main and delta contactors are also selected with this reduction factor (~ 0.58 и Ie). The star contactor is designed for starting times up to 15 seconds for a third (~ 0.33 и Ie) of the rated motor current. At starting times (>15 s) of up to 60 seconds, the star contactor must be selected to be equal to the magnitude of the main contactor. Soft starters In many cases, the direct-on-line start and the staged star-delta start of the three-phase asynchronous motor is not the best solution, as high peak currents influence the electrical supply, and torque surges subject the mechanical components of the machine or system to high levels of stress. The soft starter provides a remedy. It enables a continuous and surge-free increase in torque and also offers the opportunity for a selective reduction in starting current. The motor voltage is also increased within the adjustable starting time from a selected starting voltage to the rated motor voltage. The soft starter can also control the run down of the drive by reduction of the voltage. The characteristic curve of the three-phase asynchronous motor only applies when the full mains voltage (ULN) is availa- ble. If a lower voltage is applied, there is a quadratic reduction in torque (M ~ U2). When compared, for example, to the star- delta start-up, the motor voltage is reduced to 58 % (~ 1/͙3), and the torque is reduced to about 33 % (one third). The difference between the load characteristic (ML) and torque characteristic of the motor (MM), and accordingly the accelera- tion force, can be influenced by adjusting the motor voltage. The soft starter should be preferred for all applications with start-up under load (load cannot be connected after start-up) to the star-delta configuration. It is a good replacement for the star-delta configuration for economic reasons and also for energy-conservation reasons, particularly for high-power drives. The motor voltage in a soft starter is modified by phase angle control of the sinusoidal half waves. For this purpose, two thyr- istors in the phases are connected in anti-parallel; one of them for the positive half wave and the other for the negative half wave. After the set start time (tStart) has timed out, the thyristors are fully controlled (full sinusoidal half wave => Top Of Ramp: TOR). As the thyristors are only active during the acceleration phase or during the deceleration phase, they can be bypassed by so- called bypass contacts during continuous operation. The losses on the soft starter can be reduced by the considerably lower contact resistance of the mechanical switching contacts. On soft starters, a differentiation is made today between two principle variants in the configuration of the power sections (fig- ure 8).
  • 8. 8 L1 L2 L3 V1 W1U1 PE I >I >I > M 3 ~ L1 L2 L3 PE Ie In U-Start U t-Start t-Stop t Figure 10: Motor feeder, soft starter DS7, in-line configuration, combined with PKZM0 Figure 11: In-delta configuration Figure 9: Voltage curve in a soft starter The acceleration time of a drive with a soft starter results from the settings of the start voltage (UStart) and the ramp time (tStart) for the linear increase up to full mains voltage (ULN). The start voltage determines the breakaway torque of the motor. High start voltages and short ramp times correspond approximately to the direct-on-line start. In practice, the required breakaway torque (UStart) and then the shortest possible ramp time (tStart) are initially set for the required soft start. The set ramp time (tStart) is not the actual acceleration time of the drive. This is dependent on the load and the breakaway torque. The ramp time only controls the change in the voltage. In the process, the current rises to its maximum and then falls to the rated current, after the rated motor speed is achieved. The maximum current now sets to suit the drive (motor plus load) and cannot be determined in advance. As a result, drives subject to high loads in conjunction with long ramp times can lead to highly excessive thermal loading of the thyristors. If a determined current level is not to be exceeded, a soft starter featuring a current limit must be selected. This start-up variant is frequently stipulated by the electricity supply compa- nies, when large drives are connected to the public supply (e.g. elevating pumps, fans for tunnel ventilation systems). Soft starters also enable a time-controlled reduction of the motor voltages and thus a controlled run down of the motors. The set stopping time (tStop) must be longer than the load- dependent, free run down time of the machine. This process is also load-dependent just as the acceleration. The thyristors of the soft starter are also subject to the same thermal stresses that were present during the start-up process. If, for example, the delay time is also activated for a soft starter with 10 permis- sible starts per hour, 5 starts per hour (plus 5 stops per hour) are permitted. The stop ramp time (tStop) can be selected inde- pendently of the start time, which is frequently required on pumps to prevent pressure waves (water hammer). Jerky movements during an uncontrolled run down, which, for exam- ple, can cause higher wear on drive belts, drive chains and bearings, can also be prevented. The design of the switchgear and protection devices (electro- mechanical components) in the main circuit of the motor feeder is undertaken in accordance with the rated operational current (Ie) of the motor and the utilization category AC-3 (standard IEC 60947-4-1). The design of the soft starter is undertaken in accordance with the rated operational current (Ie) of the motor and the utilization category AC-53a or AC-53b (standard IEC/ EN60947-4-2): • AC-3 = squirrel-cage motors: start-up, switch off during oper- ation. • AC-53a = control of a squirrel-cage motor: eight-hour duty with starting currents for start processes, manoeuvring, operation. • AC-53b = control of a squirrel-cage motor: intermittent oper- ation (intermittent operation means that the soft starter is bypassed externally during continuous operation, e.g. by a bypass contactor). The in-line configuration corresponds with the motor feeder during direct-on-line start. Only three cables lead to the motor and are connected to U1, V1 and W1 in the terminal box. The winding ends are switched as star or delta in accordance with the available motor and supply voltage. The in-delta configuration to this effect is only possible with three-phase controlled soft starters. Hereby, the individual motor windings are connected in series with the delta thyris- tors. The soft starter design in this configuration can be a factor 1/͙3 (~ 0.58 и Ie) less than the rated current of the motor. From
  • 9. 9 L1 L2 L3 V1 W1 U1 V2 W2 U2 PE I >I >I > M 3 ~ PES L1 L2 L3 PE I >I >I > M 3 ~ Figure 12: Motor feeder, soft starter, in-delta configuration Figure 13: Motor feeder, frequency inverter, with the M-Max as an example an economic standpoint, this is an interesting connection vari- ant with higher motor ratings. The overload relay used can also be included in the winding phase of the soft starter and can also be reduced by the factor 1/͙3 (~ 0.58 и Ie) lower rated current of the motor. If the over- load relay is installed on the mains supply incomer, it will need to be rated just like the contactor or the switchgear on the mains supply side to the rated operational current (Ie) of the motor. Frequency inverters The frequency inverter is ultimately the best solution for contin- uous and stepless starting of the three-phase asynchronous motor. The adjustable current limitation prevents high current peaks in the electrical mains supply and abrupt loads in the mechanical parts of the machine and systems. In addition to the smooth start-up, the frequency inverter also enables stepless speed (frequency) control of the three-phase asynchronous motor. Whereas motors connected directly to the mains supply can only achieve the ideal operating condi- tions at the steady state operation point (= rating plate specifi- cations), they can be utilized over the entire speed range with frequency control, for example, from 4 V at 0.5 Hz to 400 V at 50 Hz. The constant ratio of voltage to frequency (U/f) guaran- tee independent operating points with rated-load torque (MM). When compared to the previously described solutions, the fre- quency inverters appear to be the most expensive solution at first glance. Higher acquisition costs and the necessary addi- tional installation measures (shielded motor cables and RFI fil- ter for electromagnetic compatibility, EMC) are the main rea- sons. But during operation at the very latest, the soft motor start in addition to the energy efficiency and process optimisa- tion shows the economic benefits. This is especially true for pumps and fans. By the matching of rotation speed to the pro- duction process and the compensation for external interfer- ence, the frequency controlled drive unit guarantees a longer service life and functional security. Further advantages of the frequency inverters include the higher speed stability with fluctuations in the load (speed fluc- tuations less than about one percent) and the option for a direct change in the direction of rotation. As the rotating field in the frequency inverter is generated electronically, a simple control command is all that is required to change the phase sequence and the direction of motor rotation. The electronic motor pro- tection (I2 t control) integrated into frequency inverters also assures safe operation without the need for additional safety measures (overload relays). Depending on the method of imple- mentation, parameterised temperature models in the frequency inverter provide a higher level of motor heat protection. So- called full motor protection is also possible in conjunction with thermistors. Overload and underload detection also enhance the operational safety of the drive unit. The frequency inverter operates as a power converter in the main circuit of a motor feeder. Separated from the power of the DC link, the power converter draws active power via the recti- fier from the mains supply and supplies the connected motor with active and reactive power via the inverter. The reactive power required for motor operation is provided by the capaci- tors in the DC link. As far as the electrical supply is concerned, the frequency-controlled drive behaves virtually like a resistive load (cos ␸ ~ 1). The power conversion and the associated current types must be considered in the design of the switchgear and protective devices on the motor feeder. For this purpose, the electro- mechanical components (e.g. fuses, line reactors, mains con- tactors) on the mains supply side of the frequency inverter are dimensioned in accordance with the input current (active cur- rent) and the utilization category AC-1 (standard IEC60947-4-1). The components on the frequency inverter output (e.g. motor reactors, sinewave filters, motor cables) are dimensioned in accordance with the rated operational current of the connected motor and the utilization category AC-3. During motor operation, the frequency inverters differ through the method of operation of the inverter that can be adjusted by the user. In addition to the standard U/f control with a linear or
  • 10. 10 M 3 h + U V W L1 L2/N L3 • Rectifier for single-phase (up to about 2.2 kW) or three-phase mains supply • Integrated radio interference filter for electromagnetic compatibility (EMC) • DC link • DC link capacitors smooth the pulsed voltage of the rectifier and provide the required reactive power for motor operation • Control current supply of the frequency inverter (switching mode power supply) • Inverter with IGBT (Insulated Gate Bipolar Transistor) • Switched-mode DC voltage with sinusoidal-weighted pulse width modulation (PWM) • Shielded motor cables • U/f characteristic control, slip control, vector control Figure 14: Main components of the frequency inverter squared curve characteristic, sensorless speed control with slip compensation and the torque-increasing vector control are known methods currently in use today. Whereas U/f control enables parallel operation of several motors – even with differ- ent output ratings – on the output of the frequency inverter, speed and vector control are only intended for operation with individual motors. Hereby, the load-dependent operating behav- iour of the (individual) three-phase asynchronous motor is opti- mised automatically by the frequency inverter through an elec- tronic motor model. The detailed description of this specific operation procedure with frequency inverters would however exceed the desired simplified overview of the most well-known starting methods for starting and controlling three-phase asynchronous motors.
  • 11. 11 Summary Usage and application determine the selection of the start variant on the motor feeder for a three-phase asynchronous motor. Comparison of the characteristic features of the starting methods described here: DOL motor starter Star-delta starter Soft starter Frequency inverter Block diagram M 3 h 3 M 3 h D y 3 M 3 h 3 M 3 h 3 Voltage curve 100 % t U 100 % 58 % t U D y t 100 % 30 % U UStart tStart t 100 % U UBoost t-acc Load on mains at start-up high medium low to medium low Current curve 2 3 4 5 6 I/Ie n/nN IN1 0.25 0.5 0.75 1 2 3 4 5 6 I/Ie n/nN IN1 0.25 0.5 0.75 1 2 3 4 5 6 I/Ie n/nN IN1 0.25 0.5 0.75 1 2 3 4 5 6 I/Ie n/nN IN1 0.25 0.5 0.75 1 Relative starting current 4 … 8x Ie (motor-dependent) 1.3 … 3x Ie (~1/3 compared to direct-on-line-start) 2 … 6x Ie (reduced by voltage control) Յ1 (… 2x) Ie (adjustable) Torque characteristic 2 3 I/Ie n/nN MN1 0.25 0.5 0.75 1 ML 2 3 I/Ie n/nN MN ML 1 0.25 0.5 0.75 1 2 3 I/Ie n/nN MN1 0.25 0.5 0.75 1 ML 2 3 I/Ie n/nN MN1 0.25 0.5 0.75 1 ML Relative starting torque 1.5 … 3x MN (motor-dependent) 0.5 … 1x MN (~ 1/3 compared to direct-on-line-start) 0.1 … 1x MN (M ~ U2 , square-law, reduced by voltage control) ~0.1 … 2x MN (M ~ U/f, adjustable torque) Features – High acceleration with high starting current – High mechanical loading – Start-up with reduced current and torque – Current and torque peak at changeover – Adjustable starting characteristic – Controller run out possible – High torque at low current – Adjustable starting characteristic Area of application Drives on stable supplies that allow high starting currents (torques) Drives that are only subject to load after acceleration up to speed Drives that require soft torque progression or current reduction Drives that require controlled soft start and stepless speed adjustment
  • 12. Eaton Corporation Eaton is a leading energy management company. Eaton operates worldwide with products, systems and services in the electrical, hydraulic, aerospace, truck and automotive sectors. Eatons Electrical Sector Eatons Electrical Sector is the worldwide leader in products, systems and services for energy distribution, safe electricity supply and automation in industrial, residential and purpose-built buildings, public facilities, energy providers, commerce and OEMs. Eaton Electrical Sector includes the brands Cutler-Hammer® , Moeller® , Micro Innovation, Powerware® , Holec® , MEM® , Santak® and MGE Office Protection Systems™. www.eaton.com Addresses worldwide: www.moeller.net/address E-Mail: info-int@eaton.com Internet: www.moeller.net www.eaton.com Publisher: Eaton Corporation Electrical Sector – EMEA Eaton Industries GmbH Hein-Moeller-Str. 7–11 D-53115 Bonn © 2010 by Eaton Industries GmbH Subject to alterations VER8200-968en ip 04/10 Printed in Germany (04/10) Article No.: 144056