Consumer Unit
 All cables and connections to the consumer unit must be checked and
tested by a qualified electrician. Do not attempt removal or replacement
 unless you are absolutely positive you know what you are doing, and
 even then the above still applies. It is also an offence to interfere with
                    the seals on the electricity meter.

 The modern consumer unit is the centre, or heart, of the wiring system
in the home. The unit distributes the electricity, via fuses of one kind or
  another, to the different circuits in the house. The older fuse wire are
    being replaced gradually by their modern equivalent, the MCB or
                         miniature circuit breaker.

We will deal with the two main types of consumer unit found in the home today . The first one
 is a single load fuse board where the power coming in is taken through a double pole switch
  to a live buss bar. Each fuse, or MCB, is clipped onto a DIN bar and the "teeth" of the buss
 bar are inserted into the MCB's. The cables to the house circuits are connected to the other
side of the MCB's. All of this is explained more thoroughly when we deal with the second type
     of unit, which is the split load unit. The photographs are of a split load fuse board. The
             ordinary consumer unit is exactly the same in principle without the RCD.




   Just as a matter of interest, DIN stands for Deutsche Industrie Norm and, originating in
    Germany, is any of a series of technical standards, used Internationally, to designate
  electrical connections, film speeds and paper sizes. Shown in the consumer unit casing
 above, it is a metal, pressed bar, to which the MCB's clip. They simply push on via a spring
                                   loaded lock at their back.

  A split load board is designed for total safety and incorporates an RCD (Residual Current
      Device, shown as E in the picture above) as well as the double pole switch (D).
The RCD is not just a manually operated isolating switch, but a very sensitive safety device
  which cuts off in fractions of a second if it senses an earth fault. RCDs can be bought in
 different current ratings and various sensitivities to current leakage. You will need to check
                          which ratings are appropriate for your home.

  As they are very sensitive, it is not practical to fit one RCD to protect the whole house. If a
fault develops on one circuit, all circuits would be switched off immediately...This would, most
 often, leave you in the unnecessary position of having no lights or power. Because of this it
      actually contravenes the most recent (16th Edition) wiring regulations. This is easily
 prevented by using an RCD in conjunction with a main, double pole isolating switch so that it
 protects only some of the more vulnerable circuits. This then becomes a split load consumer
                       unit and is shown above. The key to this photo is..

            A: Neutral terminal block for the main isolating switch side of the unit.

                      B: Neutral terminal block for RCD side of the unit

                       C: Earth terminal block (takes both sides of unit)

                             D: Main double pole isolating switch.

             E: Generally 80 - 100 Amp RCD with 100mA (milliamp) sensitivity.

                   F: Neutral link cable from Main switch to terminal block

                            G: Live feed from main switch to RCD.

                    H: Neutral link cable from main terminal block to RCD

                I: Neutral link cable from RCD to RCD neutral terminal block.

The use of RCDs is necessary, on two occasions, to meet the wiring regulations. The first of
these is to protect any socket which may be reasonably expected supply equipment outside
 the house (Strimmers, lawn mowers, hedge trimmers, pond pumps, sheds, lights etc etc).
  This rule pretty much covers every single socket in the house so the ring main should be
                   placed on the RCD protected side of the consumer unit.

 The second condition applies to any circuits where an earth fault current is not sufficient to
  blow the fuse, or trip the switch, in the designated time allowance made in the regulations.
  This generally applies to higher Amp rated appliances (showers, cookers etc) but it should
always be checked with an electrician as to which circuits need to be placed on the RCD side
                                        of the consumer unit.

   The Current ratings which MCBs are designated to deal with are now conforming to the
international equivalent of our old imperial ratings. This standard is called the Renard current
rating and supercedes the imperial ratings as far as MCBs are concerned. A 5 amp fuse can
be replaced with a 6 amp MCB. A 15 amp fuse becomes a 16 amp MCB, a 20 amp fuse can
                                                      be a 20 amp MCB, 30 amp fuse = 32 amp
                                                      MCB and a 45 amp fuse must now be a 40
                                                                      amp MCB.
Top left shows the mains double pole isolating switch and an MCB clipped into place on the
DIN bar. Top right shows two MCBs and the Buss bar. When the MCBs are clipped onto the
DIN bar, the Buss bar is inserted into the live terminal at the bottom of the MCB. When
                                             screwed tight this gives live feed to all the MCBs.




 Top left shows the live (K) and neutral (J) coming into the main double pole switch from the
  meter. These cables are called tails, and in this instance, with this type of unit, are 16mm
cables. This will vary and you should always check with a qualified electrician. Top left shows
         the earth cable from the meter (L). This screws into the earth terminal block.
Top left shows how a circuit cable is introduced to the unit. In this case it is a 2.5mm cable for
 the ring main. The live (O) is fixed into the top of an MCB on the RCD side of the unit, while
  the neutral (M) goes to the RCD neutral terminal block. The earth (N*) (which has been left
unsheathed for clarity ). Each circuit cable is fed into the consumer unit and connected to an
                                  MCB of the appropriate rating.

Contenu connexe

Tendances

New electronics slides
New electronics slidesNew electronics slides
New electronics slides
jogajosh
 
Sensitive intrucer alaram
Sensitive intrucer alaramSensitive intrucer alaram
Sensitive intrucer alaram
Sai Kumar
 
Multiple well cathodic protection
Multiple well cathodic protectionMultiple well cathodic protection
Multiple well cathodic protection
Asif Sheriff
 
C hapter 2 diode applications
C hapter 2 diode applicationsC hapter 2 diode applications
C hapter 2 diode applications
Hazrul156
 
Zener diodes
Zener diodesZener diodes
Zener diodes
Touqeer Jumani
 
Electronic bicycle lock
Electronic bicycle lockElectronic bicycle lock
Electronic bicycle lock
viv3ksharma
 
Basic Electronic Components
Basic Electronic ComponentsBasic Electronic Components
Basic Electronic Components
Akash Agarwal
 
Transistor as a switch
Transistor as a switchTransistor as a switch
Transistor as a switch
Omed Diyari
 

Tendances (20)

New electronics slides
New electronics slidesNew electronics slides
New electronics slides
 
Sensitive intrucer alaram
Sensitive intrucer alaramSensitive intrucer alaram
Sensitive intrucer alaram
 
Basic electronics component
Basic electronics componentBasic electronics component
Basic electronics component
 
Introduction to Basic Electronics
Introduction to Basic ElectronicsIntroduction to Basic Electronics
Introduction to Basic Electronics
 
Project electronics
Project electronicsProject electronics
Project electronics
 
Invisible wire
Invisible wireInvisible wire
Invisible wire
 
Invisible broken wire detector
Invisible broken wire detectorInvisible broken wire detector
Invisible broken wire detector
 
Multiple well cathodic protection
Multiple well cathodic protectionMultiple well cathodic protection
Multiple well cathodic protection
 
C hapter 2 diode applications
C hapter 2 diode applicationsC hapter 2 diode applications
C hapter 2 diode applications
 
Zener diodes
Zener diodesZener diodes
Zener diodes
 
Diode and transistor
Diode and transistorDiode and transistor
Diode and transistor
 
Basic Electronics
Basic Electronics Basic Electronics
Basic Electronics
 
Est 130 passive components inductors
Est 130 passive components inductorsEst 130 passive components inductors
Est 130 passive components inductors
 
Electric field detector
Electric field detectorElectric field detector
Electric field detector
 
Electronic bicycle lock
Electronic bicycle lockElectronic bicycle lock
Electronic bicycle lock
 
Automatic night lamp
Automatic night lampAutomatic night lamp
Automatic night lamp
 
Basic Electronic Components
Basic Electronic ComponentsBasic Electronic Components
Basic Electronic Components
 
Zenerdiodes
ZenerdiodesZenerdiodes
Zenerdiodes
 
basic-analog-electronics
basic-analog-electronicsbasic-analog-electronics
basic-analog-electronics
 
Transistor as a switch
Transistor as a switchTransistor as a switch
Transistor as a switch
 

En vedette (13)

CENTUR~2
CENTUR~2CENTUR~2
CENTUR~2
 
Wallpaper a ceiling
Wallpaper a ceilingWallpaper a ceiling
Wallpaper a ceiling
 
Unit 5 DB and IP
Unit 5 DB and IPUnit 5 DB and IP
Unit 5 DB and IP
 
Backyard pond
Backyard pondBackyard pond
Backyard pond
 
Fit extra electrical sockets
Fit extra electrical socketsFit extra electrical sockets
Fit extra electrical sockets
 
How to avoid the cowboy builder
How to avoid the cowboy builderHow to avoid the cowboy builder
How to avoid the cowboy builder
 
A complete illustrated guide to the pc hardware
A complete illustrated guide to the pc hardwareA complete illustrated guide to the pc hardware
A complete illustrated guide to the pc hardware
 
Afterlife final and checkpoint PHI 101
Afterlife final and checkpoint PHI 101Afterlife final and checkpoint PHI 101
Afterlife final and checkpoint PHI 101
 
Change a door handle
Change a door handleChange a door handle
Change a door handle
 
Waterproof your roof
Waterproof your roofWaterproof your roof
Waterproof your roof
 
Heat guns
Heat gunsHeat guns
Heat guns
 
Wall fixings for hollow & solid surfaces
Wall fixings for hollow & solid surfacesWall fixings for hollow & solid surfaces
Wall fixings for hollow & solid surfaces
 
Praveen Sudarsan
Praveen SudarsanPraveen Sudarsan
Praveen Sudarsan
 

Similaire à Consumer unit

Mcb, rccb, elcb
Mcb, rccb, elcbMcb, rccb, elcb
Mcb, rccb, elcb
Akash Patel
 
Electronics 01
Electronics 01Electronics 01
Electronics 01
snakeaye
 

Similaire à Consumer unit (20)

Consumer unit
Consumer unitConsumer unit
Consumer unit
 
Electrical Installations
Electrical InstallationsElectrical Installations
Electrical Installations
 
Switchgear.pptx
Switchgear.pptxSwitchgear.pptx
Switchgear.pptx
 
KL1034 Lect2 Electrical wiring.pdf
KL1034 Lect2 Electrical wiring.pdfKL1034 Lect2 Electrical wiring.pdf
KL1034 Lect2 Electrical wiring.pdf
 
Mcb, rccb, elcb
Mcb, rccb, elcbMcb, rccb, elcb
Mcb, rccb, elcb
 
Electrical System.ppsx
Electrical System.ppsxElectrical System.ppsx
Electrical System.ppsx
 
homewiring.pdf
homewiring.pdfhomewiring.pdf
homewiring.pdf
 
Failure of fuse & mcb
Failure of fuse & mcbFailure of fuse & mcb
Failure of fuse & mcb
 
Failure of fuse & mcb
Failure of fuse & mcbFailure of fuse & mcb
Failure of fuse & mcb
 
Voltage suppler..
Voltage suppler..Voltage suppler..
Voltage suppler..
 
Bee presentation
Bee presentationBee presentation
Bee presentation
 
Electrical protective devices ec
Electrical protective devices ecElectrical protective devices ec
Electrical protective devices ec
 
Mains operated under voltage over voltage trip switch
Mains operated under voltage over voltage trip switchMains operated under voltage over voltage trip switch
Mains operated under voltage over voltage trip switch
 
MCB & RCCB
MCB & RCCBMCB & RCCB
MCB & RCCB
 
Switchyard final
Switchyard finalSwitchyard final
Switchyard final
 
Simple 100 w inverter circuit
Simple 100 w inverter circuitSimple 100 w inverter circuit
Simple 100 w inverter circuit
 
Wiring devices for illumination
Wiring devices for illuminationWiring devices for illumination
Wiring devices for illumination
 
Electronics 01
Electronics 01Electronics 01
Electronics 01
 
buildinggroupppt-130512115915-phpapp02.pptx
buildinggroupppt-130512115915-phpapp02.pptxbuildinggroupppt-130512115915-phpapp02.pptx
buildinggroupppt-130512115915-phpapp02.pptx
 
Electrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCBElectrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCB
 

Plus de Praveen Sudarsan

Plus de Praveen Sudarsan (20)

How to install pvc downpipes
How to install pvc downpipesHow to install pvc downpipes
How to install pvc downpipes
 
How to hang wallpaper
How to hang wallpaperHow to hang wallpaper
How to hang wallpaper
 
How to construct a suimple garden pond
How to construct a suimple garden pondHow to construct a suimple garden pond
How to construct a suimple garden pond
 
How to build a retaining wall
How to build a retaining wallHow to build a retaining wall
How to build a retaining wall
 
How to build a raised formal pool
How to build a raised formal poolHow to build a raised formal pool
How to build a raised formal pool
 
How to build a deck
How to build a deckHow to build a deck
How to build a deck
 
How a lighting circuit works
How a lighting circuit worksHow a lighting circuit works
How a lighting circuit works
 
Home security
Home securityHome security
Home security
 
Hanging wallpaper
Hanging wallpaperHanging wallpaper
Hanging wallpaper
 
Hanging a door
Hanging a doorHanging a door
Hanging a door
 
Handrail anatomy
Handrail anatomyHandrail anatomy
Handrail anatomy
 
Upvc fascia
Upvc fasciaUpvc fascia
Upvc fascia
 
Timber care
Timber careTimber care
Timber care
 
General do it yourself safety comments
General do it yourself safety commentsGeneral do it yourself safety comments
General do it yourself safety comments
 
Garage floor insulation
Garage floor insulationGarage floor insulation
Garage floor insulation
 
Foundations for light garden walls
Foundations for light garden wallsFoundations for light garden walls
Foundations for light garden walls
 
Fixing to plasterboard and plasterboard fixings
Fixing to plasterboard and plasterboard fixingsFixing to plasterboard and plasterboard fixings
Fixing to plasterboard and plasterboard fixings
 
Fixing to lathe & plaster
Fixing to lathe & plasterFixing to lathe & plaster
Fixing to lathe & plaster
 
Fitting a mortice latch
Fitting a mortice latchFitting a mortice latch
Fitting a mortice latch
 
Fit a toilet and bidet
Fit a toilet and bidetFit a toilet and bidet
Fit a toilet and bidet
 

Dernier

The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai KuwaitThe Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
daisycvs
 
Challenges and Opportunities: A Qualitative Study on Tax Compliance in Pakistan
Challenges and Opportunities: A Qualitative Study on Tax Compliance in PakistanChallenges and Opportunities: A Qualitative Study on Tax Compliance in Pakistan
Challenges and Opportunities: A Qualitative Study on Tax Compliance in Pakistan
vineshkumarsajnani12
 
Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al MizharAl Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
allensay1
 
Mckinsey foundation level Handbook for Viewing
Mckinsey foundation level Handbook for ViewingMckinsey foundation level Handbook for Viewing
Mckinsey foundation level Handbook for Viewing
Nauman Safdar
 
Jual Obat Aborsi ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan Cytotec
Jual Obat Aborsi ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan CytotecJual Obat Aborsi ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan Cytotec
Jual Obat Aborsi ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan Cytotec
ZurliaSoop
 
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
daisycvs
 

Dernier (20)

The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai KuwaitThe Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
 
WheelTug Short Pitch Deck 2024 | Byond Insights
WheelTug Short Pitch Deck 2024 | Byond InsightsWheelTug Short Pitch Deck 2024 | Byond Insights
WheelTug Short Pitch Deck 2024 | Byond Insights
 
Challenges and Opportunities: A Qualitative Study on Tax Compliance in Pakistan
Challenges and Opportunities: A Qualitative Study on Tax Compliance in PakistanChallenges and Opportunities: A Qualitative Study on Tax Compliance in Pakistan
Challenges and Opportunities: A Qualitative Study on Tax Compliance in Pakistan
 
GUWAHATI 💋 Call Girl 9827461493 Call Girls in Escort service book now
GUWAHATI 💋 Call Girl 9827461493 Call Girls in  Escort service book nowGUWAHATI 💋 Call Girl 9827461493 Call Girls in  Escort service book now
GUWAHATI 💋 Call Girl 9827461493 Call Girls in Escort service book now
 
Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al MizharAl Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
 
Falcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business GrowthFalcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business Growth
 
Call 7737669865 Vadodara Call Girls Service at your Door Step Available All Time
Call 7737669865 Vadodara Call Girls Service at your Door Step Available All TimeCall 7737669865 Vadodara Call Girls Service at your Door Step Available All Time
Call 7737669865 Vadodara Call Girls Service at your Door Step Available All Time
 
Falcon Invoice Discounting: Unlock Your Business Potential
Falcon Invoice Discounting: Unlock Your Business PotentialFalcon Invoice Discounting: Unlock Your Business Potential
Falcon Invoice Discounting: Unlock Your Business Potential
 
Berhampur 70918*19311 CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Berhampur 70918*19311 CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDINGBerhampur 70918*19311 CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Berhampur 70918*19311 CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
 
Marel Q1 2024 Investor Presentation from May 8, 2024
Marel Q1 2024 Investor Presentation from May 8, 2024Marel Q1 2024 Investor Presentation from May 8, 2024
Marel Q1 2024 Investor Presentation from May 8, 2024
 
joint cost.pptx COST ACCOUNTING Sixteenth Edition ...
joint cost.pptx  COST ACCOUNTING  Sixteenth Edition                          ...joint cost.pptx  COST ACCOUNTING  Sixteenth Edition                          ...
joint cost.pptx COST ACCOUNTING Sixteenth Edition ...
 
Falcon Invoice Discounting: The best investment platform in india for investors
Falcon Invoice Discounting: The best investment platform in india for investorsFalcon Invoice Discounting: The best investment platform in india for investors
Falcon Invoice Discounting: The best investment platform in india for investors
 
Mckinsey foundation level Handbook for Viewing
Mckinsey foundation level Handbook for ViewingMckinsey foundation level Handbook for Viewing
Mckinsey foundation level Handbook for Viewing
 
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDINGParadip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
 
Jual Obat Aborsi ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan Cytotec
Jual Obat Aborsi ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan CytotecJual Obat Aborsi ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan Cytotec
Jual Obat Aborsi ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan Cytotec
 
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
 
JAJPUR CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JAJPUR ESCORTS
JAJPUR CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JAJPUR  ESCORTSJAJPUR CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JAJPUR  ESCORTS
JAJPUR CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JAJPUR ESCORTS
 
Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...
Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...
Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...
 
Nashik Call Girl Just Call 7091819311 Top Class Call Girl Service Available
Nashik Call Girl Just Call 7091819311 Top Class Call Girl Service AvailableNashik Call Girl Just Call 7091819311 Top Class Call Girl Service Available
Nashik Call Girl Just Call 7091819311 Top Class Call Girl Service Available
 
CROSS CULTURAL NEGOTIATION BY PANMISEM NS
CROSS CULTURAL NEGOTIATION BY PANMISEM NSCROSS CULTURAL NEGOTIATION BY PANMISEM NS
CROSS CULTURAL NEGOTIATION BY PANMISEM NS
 

Consumer unit

  • 1. Consumer Unit All cables and connections to the consumer unit must be checked and tested by a qualified electrician. Do not attempt removal or replacement unless you are absolutely positive you know what you are doing, and even then the above still applies. It is also an offence to interfere with the seals on the electricity meter. The modern consumer unit is the centre, or heart, of the wiring system in the home. The unit distributes the electricity, via fuses of one kind or another, to the different circuits in the house. The older fuse wire are being replaced gradually by their modern equivalent, the MCB or miniature circuit breaker. We will deal with the two main types of consumer unit found in the home today . The first one is a single load fuse board where the power coming in is taken through a double pole switch to a live buss bar. Each fuse, or MCB, is clipped onto a DIN bar and the "teeth" of the buss bar are inserted into the MCB's. The cables to the house circuits are connected to the other side of the MCB's. All of this is explained more thoroughly when we deal with the second type of unit, which is the split load unit. The photographs are of a split load fuse board. The ordinary consumer unit is exactly the same in principle without the RCD. Just as a matter of interest, DIN stands for Deutsche Industrie Norm and, originating in Germany, is any of a series of technical standards, used Internationally, to designate electrical connections, film speeds and paper sizes. Shown in the consumer unit casing above, it is a metal, pressed bar, to which the MCB's clip. They simply push on via a spring loaded lock at their back. A split load board is designed for total safety and incorporates an RCD (Residual Current Device, shown as E in the picture above) as well as the double pole switch (D).
  • 2. The RCD is not just a manually operated isolating switch, but a very sensitive safety device which cuts off in fractions of a second if it senses an earth fault. RCDs can be bought in different current ratings and various sensitivities to current leakage. You will need to check which ratings are appropriate for your home. As they are very sensitive, it is not practical to fit one RCD to protect the whole house. If a fault develops on one circuit, all circuits would be switched off immediately...This would, most often, leave you in the unnecessary position of having no lights or power. Because of this it actually contravenes the most recent (16th Edition) wiring regulations. This is easily prevented by using an RCD in conjunction with a main, double pole isolating switch so that it protects only some of the more vulnerable circuits. This then becomes a split load consumer unit and is shown above. The key to this photo is.. A: Neutral terminal block for the main isolating switch side of the unit. B: Neutral terminal block for RCD side of the unit C: Earth terminal block (takes both sides of unit) D: Main double pole isolating switch. E: Generally 80 - 100 Amp RCD with 100mA (milliamp) sensitivity. F: Neutral link cable from Main switch to terminal block G: Live feed from main switch to RCD. H: Neutral link cable from main terminal block to RCD I: Neutral link cable from RCD to RCD neutral terminal block. The use of RCDs is necessary, on two occasions, to meet the wiring regulations. The first of these is to protect any socket which may be reasonably expected supply equipment outside the house (Strimmers, lawn mowers, hedge trimmers, pond pumps, sheds, lights etc etc). This rule pretty much covers every single socket in the house so the ring main should be placed on the RCD protected side of the consumer unit. The second condition applies to any circuits where an earth fault current is not sufficient to blow the fuse, or trip the switch, in the designated time allowance made in the regulations. This generally applies to higher Amp rated appliances (showers, cookers etc) but it should always be checked with an electrician as to which circuits need to be placed on the RCD side of the consumer unit. The Current ratings which MCBs are designated to deal with are now conforming to the international equivalent of our old imperial ratings. This standard is called the Renard current rating and supercedes the imperial ratings as far as MCBs are concerned. A 5 amp fuse can be replaced with a 6 amp MCB. A 15 amp fuse becomes a 16 amp MCB, a 20 amp fuse can be a 20 amp MCB, 30 amp fuse = 32 amp MCB and a 45 amp fuse must now be a 40 amp MCB.
  • 3. Top left shows the mains double pole isolating switch and an MCB clipped into place on the DIN bar. Top right shows two MCBs and the Buss bar. When the MCBs are clipped onto the DIN bar, the Buss bar is inserted into the live terminal at the bottom of the MCB. When screwed tight this gives live feed to all the MCBs. Top left shows the live (K) and neutral (J) coming into the main double pole switch from the meter. These cables are called tails, and in this instance, with this type of unit, are 16mm cables. This will vary and you should always check with a qualified electrician. Top left shows the earth cable from the meter (L). This screws into the earth terminal block.
  • 4. Top left shows how a circuit cable is introduced to the unit. In this case it is a 2.5mm cable for the ring main. The live (O) is fixed into the top of an MCB on the RCD side of the unit, while the neutral (M) goes to the RCD neutral terminal block. The earth (N*) (which has been left unsheathed for clarity ). Each circuit cable is fed into the consumer unit and connected to an MCB of the appropriate rating.