International Electrical Engineering Journal (IEEJ)
Vol. 5 (2014) No.4, pp. 1305-1312
ISSN 2078-2365
http://www.ieejournal.com/
1305
Rajkumar and Suganthi Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for
PMSG Wind Turbine Systems
A Hybrid Control Scheme for Fault Ride-Through
Capability using Line-Side Converter and an
Energy Storage System for PMSG Wind Turbine
Systems
S.Rajkumar1
, S.T.Suganthi2
1
Department of EEE,SNS College of Technology, Coimbatore-35
2
Department of EEE,SNS College of Technology,Coimbatore-35
1
rajkumareee89@gmail.com, 2
suganthi.sb@gmail.com
Abstract— As the wind power installations are increasing in
number, Wind Turbine Generators (WTG) are required to have
Fault Ride-Through (FRT) capabilities. Lately developed grid
operating codes demand the WTGs to stay connected during
fault conditions, supporting the grid to recover faster back to its
normal state. In this paper, the generator side converter
incorporates the maximum power point tracking algorithm to
extract maximum energy from wind turbine system. A hybrid
control scheme for energy storage systems (ESS) and braking
choppers for fault ride-through capability and a suppression of
the output power fluctuation is proposed for permanent-magnet
synchronous generator (PMSG) wind turbine systems. During
grid faults, the dc-link voltage is controlled by the ESS instead of
the line-side converter (LSC), whereas the LSC is exploited as a
STATCOM to inject reactive current into the grid for assisting in
the grid voltage recovery. A simple model of the proposed system
is developed and simulated in MATLAB environment. The
effectiveness of the system is validated through extensive
simulation results
Index Terms- Boost converter, Braking Chopper(BC),dc-link control,
energy storage system(ESS),ride through, STATCOM, Permanent
Magnet Synchronous Generator.
I. INTRODUCTION
The development of various wind turbine (WT)
configurations in the last decade has been very dynamic and
has resulted in larger ratings and higher operating speed
ranges allowing them to be tied up to the grid more easily.
Variable speed operation of wind energy conversion systems
(WECS) make them more ‘grid-friendly’. Permanent magnet
synchronous generators (PSMG) based WECS are emerging
as strong competitors to the other variable speed technologies.
The power converter, whose rating is the same as that of the
generator, connected between PMSG and grid allows full
controllability of the system during normal operation and fault
conditions. Further, PMSG operates at higher efficiency and
better power factor than its counterparts especially when it
functions as a direct driven generator [1-3]. WECS based on
PMSG can be connected to the grid by using a voltage source
converter (VSC) on the grid side and by using either a diode
converter with a buck-boost converter or a VSC on the
machine side. Evidently, using VSC on both machine and grid
sides offer full control of active and reactive powers resulting
in the best performance [4-6] in terms of power output, quality
of power and performance during faults.
Different strategies have been presented by various
authors, to enhance fault ride through (FRT) capabilities of
PMSG based WECS. Many devices, such as static var
compensator (SVC), dynamic voltage restorers (DVR), Static
Synchronous Compensators (STATCOM) etc have been
shown to improve FRT of WECS, but they will also increase
the overall cost of the system [7-8]. In [9], a nonlinear
controller design for power converter based WT system is
presented which ensures that current levels remain within
design limits, even at greatly reduced voltage levels. A back to
back connected voltage source- converter (VSC) configuration
is discussed in [10] where the machine side converter (MSC)
controls the speed of the generator by using a flux vector
control technique and the grid side converter (GSC) controls
the power flow by PWM technique Transient analysis of a
grid connected wind driven PMSG is presented in [11] and a
comparison is presented with the other generators at fixed and
variable speeds. An electromagnetic braking resistor
controlled using power electronic switch is used to dissipate
International Electrical Engineering Journal (IEEJ)
Vol. 5 (2014) No.4, pp. 1305-1312
ISSN 2078-2365
http://www.ieejournal.com/
1306
Rajkumar and Suganthi Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for
PMSG Wind Turbine Systems
the excess energy in the DC link Circuit, preventing DC link
over voltage in [12]. Flexible active power control of
distributed generation systems during Grid Faults is discussed
in [13]. Reactive power as well as real power manipulation
using current control is described in [14]. Control of grid
converter in synchronously rotating reference frame is
described in [15-16].
In this paper, the generator side converter
incorporates the maximum power point tracking algorithm to
extract maximum energy from wind turbine system. In
addition, FRT technique of the PMSG wind turbine system is
proposed during the grid fault. By switching the control mode,
the ESS is operated to control the dc-link voltage of the back-
to-back converters during the grid voltage sags. Meanwhile,
the LSC is utilized to supply the reactive current to the grid for
satisfying the reactive current requirements of the grid code.
By this, the grid voltage can be recovered rapidly without an
external STATCOM after fault clearance. Also, the generator
active power can be absorbed fully by the ESS and the BC
during the voltage sags. In addition, the output power
fluctuation of wind turbine systems operating in steady state is
smoothened by the ESS. With this control scheme, the system
can still operate well even though the grid voltage is fully
interrupted. The validity of the proposed control algorithm is
verified by simulation and experimental results.
II. SYSTEM DESCRIPTION
Fig. 1 presents a block diagram of the simulation
model used for the FRT and Maximum Power point tracking.
In this paper, the wind turbine converts the power of the wind
to mechanical power in the rotor shaft. This is then converted
to electricity using a permanent magnet synchronous generator
(PMSG). The output voltage is rectified using a three-phase
diode bridge rectifier. The dc-to-dc converter is used to
control the dc voltage Vdc . The MPPT controller delivers a
voltage reference that is compared to the actual value of Vdc.
The result is fed into a PI controller whose output is compared
to a triangular waveform to determine when to turn the dc -dc
boost converter switch ON or OFF.The ESS consists of a
Electric Double Layer capacitor bank and a bidirectional
DC/DC converter and is also connected to the dc-link. Super
capacitors are suitable for wind power applications, as they
present the features of high efficiency, high power density,
long cycle life and easy maintenance . A BC is connected in
parallel with the dc-link. The BC will be activated to dissipate
the excessive power beyond the capacity of the ESS in cases
of deep voltage sags or high wind speed variations. The
control objective of the DC/DC converter is to maintain the
dc-link voltage magnitude at a constant level, by absorbing
any mismatch between the generated power and the power
transferred to the grid. In normal conditions, the LSC controls
the dc-link voltage , and the ESS is able to smoothen the
power ripples. In grid fault conditions, on the other hand, the
LSC functions as a STATCOM, and the ESS controls the dc-
link voltage. The FRT control scheme is designed according to
the grid code requirements on FRT.
III. MODELLING OF PROPOSED CONTROL SCHEME
A. Maximum Power Extraction Algorithm
Due to its monotonic characteristics, wind turbines can be
controlled to yield maximum power using search control
methods. Before explaining the maximum power tracking
controller, it is important to understand the basic physics of
the system. The generated mechanical power is given by [17-
19]
Pmech=Tmech(t)ωR(t) (1)
Where, Tmech is the mechanical torque. For simplification, the
generated electric power of a one-phase generator is given by
Pe(t)=Va(t)Ia(t) (2)
Fig 1:Block diagram of the proposed MPPT and FRT Method
Va and Ia are the generator voltage and current respectively.
Assuming no losses in the system, then
Tmech(t).ωR(t)= Va(t)Ia(t) (3)
The basic electrical and motion equations are
Te = kIaIf (4)
Ia=(Va-Ea)/Ra (5)
Ea=kIaωe (6)
Where, ωe = (p/2) ωR and p is the number of poles of the
generator.
Maximum power is at =0 (7)
International Electrical Engineering Journal (IEEJ)
Vol. 5 (2014) No.4, pp. 1305-1312
ISSN 2078-2365
http://www.ieejournal.com/
1307
Rajkumar and Suganthi Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for
PMSG Wind Turbine Systems
Fig. 2. Typical power versus speed characteristics of a wind turbine.
The power extracted from the wind can be controlled by
varying the dc bus voltage, which is a function of If and ωe.
Considering the wind turbine characteristics given in Figure 2,
we know that the maximum power point is obtained whe
ω
= 0 (8)
This equation can be written as:
= =0 (9)
According to equation (9),maximum power point is when:
=0 (10)
The function Pmech (Vdc) has a single point where
maximum power extraction is achieved. It also means that the
maximum power can be tracked by searching the rectified dc
power, rather than environmental conditions, such as wind
speed and direction. The MPPT algorithm is as follows. One
initiates the maximum power searching process by setting an
arbitrary dc side voltage reference Vref. The controller then
measures both the dc side current and voltage, and calculates
the initial electric power Po = VdcIdc. Next, the reference
voltage Vref is increased by ΔVdc so that.
Vref(k)= Vref(k-1)+ ΔVdc (11)
Then the dc power is calculated with P(k) =
Vdc(k)Idc(k).
If P(k) is bigger than P(k - 1), the maximum power
point has not been reached therefore, the voltage reference
needs to be increased by ΔVdc and the dc power needs to be
compared. This process will repeat until maximum power is
reached.
And if P(k) is less than P(k - 1), the dc voltage
reference is then decreased by ΔVdc. In order to search for
maximum power at any wind speed four conditions must be
met.
1. If P(k)≥ P(k-1) and Vdc(k)≥ Vdc(k-1), the dc side
voltage reference need to be increased by ΔVdc. This condition
is met when the turbine operates on the low speed side of the
power curve, shown on Fig 3.
2. If P(k)≥ P(k-1) and Vdc(k)< Vdc(k-1), the wind
turbine is being operated in the high speed side and the dc
reference voltage needs to be decreased by ΔVdc.
3. When P(k)< P(k-1) and Vdc(k)≥ Vdc(k-1), the
maximum power point is passed and a step back must be
taken, decreasing the reference voltage by ΔVdc. This
condition is met when the turbine is operated in the high
speed side of the dome and the power is decreasing.
4. When P(k)< P(k-1) and Vdc(k)< Vdc(k-1), the
power is decreasing on the low speed side, therefore the
voltage reference is to be increased by ΔVdc.
Fig 3 Maximum Power Tracking Process
In Figure 3, the power-speed plot is shown for three different
wind speeds, where υ1 < υ 2 < υ 3. The arrows show the
trajectory in which the turbine will be operated using the
maximum power tracking algorithm explained above. If the
wind speed is υ1, the controller will search for the maximum
power. If the wind changes to υ3 the turbine is no longer being
operated at the maximum power point so the controller will
search for the new maximum power point.
Fig 4. Flowchart for MPPT Algorithm
International Electrical Engineering Journal (IEEJ)
Vol. 5 (2014) No.4, pp. 1305-1312
ISSN 2078-2365
http://www.ieejournal.com/
1308
Rajkumar and Suganthi Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for
PMSG Wind Turbine Systems
After reaching the maximum point it will operate the
wind turbine at the optimal point until wind changes, thus
searching for maximum power at any wind speed. In order to
optimize the maximum power search algorithm presented
above, a step that combines speed of convergence and
accuracy of results was developed. The variable step method
is based on the Newton Raphson method. The value of the
root can be calculated as,
Xn+1=Xn - (12)
Where Xn is the current known value of X, ƒ(Xn)
represents the value of the function at Xn, and ƒ’(Xn) is the
derivative at Xn. The function ƒ (Xn) can be expressed as:
ƒ(Xn)= ƒ(Vdc(k)) = = = Slope(k) (13)
And ƒ’(Xn) as
ƒ’(Xn)=ƒ’(Vdc(k)= = (14)
Using (12,)(13) and (14), ΔVdc can be express as follows:
ΔVdc = = (15)
This variable step will allow the maximum power
tracker to converge faster to the maximum power point and
will decrease power oscillations due to large values of ΔVdc
when maximum power is achieved. For protection the value of
ΔVdc is limited. The ΔVdc limit can be changed based on the
generator size and design parameters.
B. DC/DC Converter Controller
Fig 5 Typical DC-to-DC Converter Controller
The maximum power tracker will generate a reference voltage
that will be used to control the dc voltage at the rectifier dc
side terminals. The dc-to-dc converter uses a simple feedback
controller. The dc voltage reference is compared to the actual
dc voltage, and the error signal is fed to a PI controller. The
output signal is compared with a fixed frequency repetitive
triangular waveform to deliver a signal that will turn ON or
OFF the switch. This is shown in Fig 5.
C. Control of ESS and BC
The ESS and the BC are used to suppress the
generator output power fluctuation in normal conditions by
absorbing or releasing the pulsated power component from or
to the grid, in which the power command, P*ESS, is obtained
through a high-pass filter to the generator power [20]. The
ESS power is regulated by an outer PI regulator, whereas the
EDLC current is controlled by an inner PI regulator.
Fig. 6. Control block diagram of the ESS and BC.
International Electrical Engineering Journal (IEEJ)
Vol. 5 (2014) No.4, pp. 1305-1312
ISSN 2078-2365
http://www.ieejournal.com/
1309
Rajkumar and Suganthi Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for
PMSG Wind Turbine Systems
Before you begin to format your paper, first write and save
the content as a separate text file. Keep your text and graphic
files separate until after the text has been formatted and styled.
Do not use hard tabs, and limit use of hard returns to only one
return at the end of a paragraph. Do not add any kind of
pagination anywhere in the paper. Do not number text heads-
the template will do that for you.
D. DC-Link Voltage Control
During grid sags, the dc-link voltage of the back-to-
back converters is controlled by the ESS instead of the LSC.
Hence, an outer PI voltage controller is employed, which
produces a current reference for an inner PI current controller.
Fig. 6 shows the overview control block diagram of the ESS
and the BC in both normal and grid sag conditions.
Neglecting the power losses of the converters and considering
the active power negligible flowing into the grid, the dynamic
equation of the dc-link voltage is expressed as
Pgen-PBC-PESS=0.5C(dV2
dc/dt) (16)
where C is the dc-link capacitance, Pgen is the generator
power, PBC is the power dissipated by the BC, and PESS is the
power of the ESS computed from the ESS voltage, VESS, and
the EDLC current, IESS, as
PESS=VESS*IESS (17)
From (16 ) in order to keep the dc-link voltage constant, the
ESS and the BC should be able to absorb the generator
powerfully.
From the control block diagram shown in Fig. 6, the output of
the dc-link voltage controller, I∗ ESS, is given as
I*ESS=Kp2(Vdc*-Vdc)+ (Vdc*-Vdc) + (18)
where Kp2 and KI2 are PI controller gains of the dc-link
voltage control. In Fig. 6, IESS_max represents the maximum
current of the ESS.
By expanding a Taylor series of the dc-link voltage at
operating point Vdc0, the following can be obtained:
V2
dc=V2
dc0+2Vdc0(Vdc-Vdc0) (19)
From (16)–(19), the dc-link voltage equation can be rewritten
in the “s” domain as
CVdc0sVdc=-VESSKp2(Vdc*-Vdc)-VESS (Vdc*-Vdc) (20)
The transfer function of the voltage controller is derived as
[21]
∗
= (21)
where ξ is the damping ratio, and ωn is the natural frequency.
It is indicated in (21) that the transfer function has a zero and
two poles, which are always located in the left-half plane.
Hence, control stability is achieved.
E. EDLC Current Control
To establish the current control law for the dc/dc converter, a
voltage across the inductance, VLf , is investigated.
The dynamic equation of the inductance voltage is expressed
as [22], [23]
VLf=Lf =DESSVdc-VESS (22)
VLf=Lf =DESSVdc-VESS (22)
where Lf is the boost inductance, and DESS is the duty cycle.
As shown in Fig. 6, the output of the current controller, V ∗Lf ,
is given as
V*Lf=Kpc(I*ESS-IESS)+ (I*ESS-IESS) (23)
where Kpc and KIc are PI controller gains of the current
control.
The duty cycle is calculated by
DESS=(VESS+V*Lf)/Vdc (24)
Then, the gating signals for switches S1 and S2 are generated
by comparing the duty cycle with the carrier wave of 2 kHz as
shown in Fig. 6.
F.BC Control
During the grid disturbance, the ESS may not absorb the full
generator power, and then the BC will be activated to dissipate
the rest of power, PBC as
PBC=Pgen-PESS (25)
The BC is controlled by the switch S3 shown in Fig. 6.The
duty ratio DS3 for the switch depends on PBC, which is
expressed as
DS3= PBC (26)
where Rbc is the braking resistance.
International Electrical Engineering Journal (IEEJ)
Vol. 5 (2014) No.4, pp. 1305-1312
ISSN 2078-2365
http://www.ieejournal.com/
1310
Rajkumar and Suganthi Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for
PMSG Wind Turbine Systems
G.Control of LSC
The LSC controls the dc-link voltage, Vdc, to be
constant under normal conditions. Cascaded control structure
with an inner current control loop and the outer dc-link
voltage control loop is applied . During grid voltage sags,
however, the dc-link voltage is controlled by the ESS. Hence,
the LSC is exploited as a STATCOM to supply the reactive
current to the grid according to the requirements of the grid
code. For this, the control strategy of the LSC is a voltage-
controlled current source, in which the LSC is operated as a
current source .
In the case of unbalanced grid sags, the dual-current
controllers for positive- and negative-sequence components
are adopted for the LSC. The control block diagram of the
LSC is shown in Fig. 7. In normal operation, the current
references for positive- and negative-sequence current
controllers are calculated from the output of the dc-link
voltage controller as shown in Fig. 7 . During grid sags, dc-
link voltage control by the LSC is deactivated, and the LSC
injects the reactive current component. Hence, the reference of
the active current component, Ip*
qe is set to zero
Ip*
qe =0 (27)
Fig. 7. Control block diagram of LSC
The dq-axis current references In*
dqe, of negative-sequence
components are set to zero to eliminate the unbalanced current
components flowing into the grid, which are expressed as
In*
qe =0 (28)
In*
de =0 (29)
A proportional-integral (PI) controller is usually used
for dc-link voltage control. Hence, an error accumulation in
the integral regulator should be considered for fast transition
when the dc-link voltage controller is reactivated after fault
clearance. The PI controller is implemented in a discrete time
domain. The actual dc-link voltage is able to track its
reference by ESS control during the sag. Hence, an initial
accumulated error, ΔVdc_I_int, of the integral regulator is set
to zero as
ΔVdc_I_int = 0. (30)
IV SIMULATION RESULTS
To perform the feasibility of the proposed scheme, Matlab
simulations have been performed for a PMSG wind turbine
system. The system parameters for the simulation are listed in
Appendix .
Fig 8 shows the variation of the wind speed and its
corresponding output voltage of the PMSG. With the increase
in wind speed the power fed to the grid also increases which is
indicated by an increase in magnitude of PMSG phase voltage.
At t =2.4 s, wind speed is changed from 8 to 12 m/s in step,
whereas tip-speed ratio is maintained at Cp maximum in
steady state conditions.
Fig 8 (a) wind Speed (b) Phase voltage
International Electrical Engineering Journal (IEEJ)
Vol. 5 (2014) No.4, pp. 1305-1312
ISSN 2078-2365
http://www.ieejournal.com/
1311
Rajkumar and Suganthi Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for
PMSG Wind Turbine Systems
Fig 9 (a) Grid voltage (b) Grid Current
Fig 9 shows the performance of the LSC at voltage sags. Fig.
9(a) shows the grid voltage, where three grid-phase voltages
drop to 20%, 20%, and 50%, respectively, during 0.5 s. Fig
9(b) shows the grid current which increased during the fault
condition
Fig 10(a) Grid Voltage (b) DC-Link Voltage
The two-phase grid voltage interruption is considered
as shown in Fig. 10(a) .With the proposed system, the dc-link
voltage is controlled well by the ESS, which is shown in
Fig.10(b). The increase in the dc-link voltage is less than
1.5%.
Fig. 11 shows the performance of the ESS and the
BC. The dc link voltage is controlled well as shown in Fig.
11(a), in which its transient value is less than 2.5%. Fig. 11(b)
shows the ESS powers, in which the control performance is
good for normal conditions. When the grid fault occurs, the
power controller is deactivated, and the power is absorbed by
the ESS as seen in Fig. 11(b) to maintain the dc-link voltage.
The current control performance is shown in Fig. 11(c). Since
the ESS is not able to absorb the full generator power, the rest
of the power is dissipated by the BC. The BC current is shown
in Fig. 11(d). When the EDLC absorbs the power from the
wind system, the EDLC voltage is increased as shown in Fig.
11(e).
Fig. 11. Performance of ESS and BC under unbalanced sag (a) DC-link
voltage. (b) ESS power. (c) EDLC current. (d) Braking chopper current. (e)
EDLC voltage.
CONCLUSION
This paper has proposed the maximum power point
tracking algorithm to extract maximum energy from wind
turbine system and combines the ESS and the BC for the
LVRT in PMSG wind turbine systems which is an cost
effective solution. The maximum power was tracked by
searching the rectified dc power, rather than environmental
conditions, such as wind speed and direction. Controlling the
dc-link voltage by the ESS, the LSC is able to comply with the
reactive current requirements of the grid code. By this, the
grid voltage can be recovered rapidly without an external
STATCOM after fault clearance. Also, the output power
fluctuation of the wind turbine system operating in steady state
is smoothened by the ESS. This control scheme offers an FRT
International Electrical Engineering Journal (IEEJ)
Vol. 5 (2014) No.4, pp. 1305-1312
ISSN 2078-2365
http://www.ieejournal.com/
1312
Rajkumar and Suganthi Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for
PMSG Wind Turbine Systems
capability for the wind turbines even though the grid voltage is
fully interrupted.
Appendix:
PMSG parameters: Stator resistance Rs=2.1Ω, Stator
Inductance: 0.00083mH, inertia J= 0.01197 kgm2
, magnetic
flux Φ=0.118 Wb and number of poles=4.
Converter parameters: Low voltage side capacitor C1=500μF,
High voltage side capacitor C0=3600μF, Inductor L=200mH,
Switching frequency fd=20kHz, system frequency f=50Hz.
ESS and BC parameters: ESS power ratingPESS-rated -0.6 KW,
Capacitance of EDLCCEDLC-100 F, Operating VoltageVESS-
440 V,Power rating of BCPbc-rated-1.13 KW,Resistance Rbc-1.5
Ω
REFERENCES
[1] Rahul Nema, Anurag Trivedi “Application of Super Capacitor
Based Energy Storage System for Power Quality Improvement
of a Decentralized Power Plant” IEEJ Trans vol 04 no 1 pp 846-
855
[2] H. Li and Z. Chen, “Overview of different wind generator
systems and their comparisons”, in IET Renewable Power
Generation, Vol. 2, No. 2, pp. 123-138, 2008.
[3] Rajveer Mittal, K.S. Sandhu and D.K. Jain., “An Overview of
Some Important Issues Related to Wind Energy Conversion
System (WECS)”, International Journal of Environmental
Science and Development, Vol. 1, No. 4, pp. 351-362, October
2010.
[4] Z. Chen and E. Spooner, “A Modular Permanent Magnet
Generator for Variable Speed Wind Turbines” in proceedings of
IEE EMD, pp. 453- 457, 1995
[5] Alejandro Rolán, Álvaro Luna, Gerardo Vázquez, Daniel Aguilar
and Gustavo Azevado, “Modelling of a Variable Speed Wind
Turbine with a Permanent Magnet Synchronous Generator”, in
proceedings of IEEE International Symposium on Industrial
Electronics ISIE, pp. 734-739, July 2009.
[6] Rajveer Mittal, K.S. Sandhu and D.K. Jain., “Low Voltage Ride
Through of Grid Interfaced Wind Driven PMSG”, ARPN
Journal of Engineering and Applied Sciences, Vol. 4, No. 5, pp.
73-83, 2009
[7] B. Singh, R.Saha, A. Chandra, K. Al. Haddad, “Static
Synchronous Compensators”, IET Power Electronics, Vol. 2,
Issue.4, pp. 297-324, 2009
[8] Yingdong Wei, Lucheng Hong, Qirong Jiang and Zhiyong Wang,
“ A New Dynamic Strategy for Ride Through Capability of
Wind Turbine Generator”, Power and Energy Society General
Meeting, pp. 1-6, 2011
[9] A. Mullane, G. Lightbody and R. Yacamini, "Wind-turbine fault
ride through enhancement," IEEE transactions on Power
Systems, Vol.20, No.4, pp. 1929- 1937, Nov. 2005.
[10] Remus Teodorescu and Frede Blaabjerg, "Flexible Control of
Small Wind Turbines with Grid Failure Detection Operating in
Stand Alone and Grid Connected Mode," IEEE Transactions on
Power Electronics, vol. 19, No.5, pp.1323-1332, September
2004.
[11] Mazen Abdel-Salam, Adel Ahmed and Mahmoud Mahrous,
“Transient Analysis of Grid Connected Wind Driven PMSG,
DFIG and SCIG at Fixed and Variable Speeds”, Innovative
Systems Design and Engineering, Vol. 2, No. 3, 2011
[12] J. F. Conroy and R. Watson, “Low Voltage Ride Through of a
Full Converter Wind Turbine with Permanent Magnet
Generator”, IET Renewable Power Generation, Vol. 1, No. 3,
pp. 182-189, 2007
[13] P. Rodriguez, A.V. Timbus, R. Teodorescu, M. Liserre and F.
Blaabjerg, "Flexible Active Power Control of Distributed Power
Generation Systems During Grid Faults," IEEE Transactions on
Industrial Electronics, vol.54, no.5, pp.2583-2592, Oct. 2007.
[14] P. Rodriguez, A.V. Timbus, R. Teodorescu, M. Liserre and F.
Blaabjerg, "Independent PQ Control for Distributed Power
Generation Systems under Grid Faults," In Proc. of IEEE 32nd
Annual Conference on Industrial Electronics, pp.5185-5190,
Nov. 2006.
[15] P. N. Enjeti and S. A. Choudhury, “A New Control Strategy to
Improve the Performance of a PWM AC to DC Converter Under
Unbalanced Operating Conditions,” IEEE Transactions on
Power Electronics, Vol. 8, pp. 493–500, Oct. 1993.
[16] P. Rioual, H. Pouliquen, and J. Louis, “Regulation of a PWM
Rectifier in the Unbalanced Network State Using a Generalized
Model,” IEEE Transactions on Power Electronics, vol. 11, pp.
495–502, May 1996.
[17] Spera DA. Wind turbine technology: fundamental concept of
wind turbine engineering. New York: ASHE Press; 1994.
[18] Bhadra SN, Kastha D, Banerjee S. Wind electrical systems.
Oxford, UK: Oxford University Press; 2005.
[19] Mohammad H. Rashid. Power electronics-circuit. Devices and
application. 3rd
ed; 2004.
[20] T. H. Nguyen, D.-C. Lee, S.-H. Song, and E.-H. Kim,
“Improvement of power quality for PMSG wind turbine
systems,” in Proc. IEEE ECCE, Sep. 2010, pp. 2763–2770.
[21] T. H. Nguyen and D. C. Lee, “Ride-through technique for
PMSG wind turbine using energy storage systems,” J. Power
Electron., vol. 10, no. 6, pp. 733–738, Nov. 2010.
[22] R. J. Wai and L. C. Shih, “Design of voltage tracking control for
DCDC boost converter via total sliding-mode technique,” IEEE
Trans. Ind. Electron., vol. 58, no. 6, pp. 2502–2511, Jun. 2011.
[23] E. Babaei, M. E. S. Mahmoodieh, and M. Sabahi, “Investigating
buck DCDC converter operation in different operational modes
and obtaining the minimum output voltage ripple considering
filter size,” J. Power Electron., vol. 11, no. 6, pp. 793–800, Nov.
2011.
[24] Shuhui Li and Tim A. Haskew, “Characteristics Study of Vector
– Controlled Direct Driven Permanent Magnet Synchronous
Generator in Wind Power Generation”, in proceedings of IEEE
Power and Energy Society General Meeting - Conversion and
Delivery of Electrical Energy in the 21st Century, pp. 01-09,
2008.

Contenu connexe

Tendances

Design methodology of smart photovoltaic plant
Design methodology of smart photovoltaic plant Design methodology of smart photovoltaic plant
Design methodology of smart photovoltaic plant IJECEIAES
 
Comparison of Maximum Power Point Technique for Solar Photovoltaic Array
Comparison of Maximum Power Point Technique for Solar Photovoltaic ArrayComparison of Maximum Power Point Technique for Solar Photovoltaic Array
Comparison of Maximum Power Point Technique for Solar Photovoltaic ArrayIRJET Journal
 
Optimizing of the installed capacity of hybrid renewable energy with a modifi...
Optimizing of the installed capacity of hybrid renewable energy with a modifi...Optimizing of the installed capacity of hybrid renewable energy with a modifi...
Optimizing of the installed capacity of hybrid renewable energy with a modifi...IJECEIAES
 
Small Signal Stability Improvement and Congestion Management Using PSO Based ...
Small Signal Stability Improvement and Congestion Management Using PSO Based ...Small Signal Stability Improvement and Congestion Management Using PSO Based ...
Small Signal Stability Improvement and Congestion Management Using PSO Based ...IDES Editor
 
An optimum location of on-grid bifacial based photovoltaic system in Iraq
An optimum location of on-grid bifacial based photovoltaic system in Iraq An optimum location of on-grid bifacial based photovoltaic system in Iraq
An optimum location of on-grid bifacial based photovoltaic system in Iraq IJECEIAES
 
Benchmarking study between capacitive and electronic load technic to track I-...
Benchmarking study between capacitive and electronic load technic to track I-...Benchmarking study between capacitive and electronic load technic to track I-...
Benchmarking study between capacitive and electronic load technic to track I-...IJECEIAES
 
Coordinated planning in improving power quality considering the use of nonlin...
Coordinated planning in improving power quality considering the use of nonlin...Coordinated planning in improving power quality considering the use of nonlin...
Coordinated planning in improving power quality considering the use of nonlin...IJECEIAES
 
The optimal solution for unit commitment problem using binary hybrid grey wol...
The optimal solution for unit commitment problem using binary hybrid grey wol...The optimal solution for unit commitment problem using binary hybrid grey wol...
The optimal solution for unit commitment problem using binary hybrid grey wol...IJECEIAES
 
Power system operation considering detailed modelling of the natural gas supp...
Power system operation considering detailed modelling of the natural gas supp...Power system operation considering detailed modelling of the natural gas supp...
Power system operation considering detailed modelling of the natural gas supp...IJECEIAES
 
IRJET- Energy Management and Control for Grid Connected Hybrid Energy Storage...
IRJET- Energy Management and Control for Grid Connected Hybrid Energy Storage...IRJET- Energy Management and Control for Grid Connected Hybrid Energy Storage...
IRJET- Energy Management and Control for Grid Connected Hybrid Energy Storage...IRJET Journal
 
Frequency regulation service of multiple-areas vehicle to grid application in...
Frequency regulation service of multiple-areas vehicle to grid application in...Frequency regulation service of multiple-areas vehicle to grid application in...
Frequency regulation service of multiple-areas vehicle to grid application in...IJECEIAES
 
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...IDES Editor
 
Power quality improvement based on hybrid coordinated design of renewable ene...
Power quality improvement based on hybrid coordinated design of renewable ene...Power quality improvement based on hybrid coordinated design of renewable ene...
Power quality improvement based on hybrid coordinated design of renewable ene...IJECEIAES
 
Optimal Placement of D-STATCOM Using Hybrid Genetic and Ant Colony Algorithm ...
Optimal Placement of D-STATCOM Using Hybrid Genetic and Ant Colony Algorithm ...Optimal Placement of D-STATCOM Using Hybrid Genetic and Ant Colony Algorithm ...
Optimal Placement of D-STATCOM Using Hybrid Genetic and Ant Colony Algorithm ...IJAPEJOURNAL
 

Tendances (20)

Wind speed modeling based on measurement data to predict future wind speed wi...
Wind speed modeling based on measurement data to predict future wind speed wi...Wind speed modeling based on measurement data to predict future wind speed wi...
Wind speed modeling based on measurement data to predict future wind speed wi...
 
Design methodology of smart photovoltaic plant
Design methodology of smart photovoltaic plant Design methodology of smart photovoltaic plant
Design methodology of smart photovoltaic plant
 
Comparison of Maximum Power Point Technique for Solar Photovoltaic Array
Comparison of Maximum Power Point Technique for Solar Photovoltaic ArrayComparison of Maximum Power Point Technique for Solar Photovoltaic Array
Comparison of Maximum Power Point Technique for Solar Photovoltaic Array
 
Optimizing of the installed capacity of hybrid renewable energy with a modifi...
Optimizing of the installed capacity of hybrid renewable energy with a modifi...Optimizing of the installed capacity of hybrid renewable energy with a modifi...
Optimizing of the installed capacity of hybrid renewable energy with a modifi...
 
Small Signal Stability Improvement and Congestion Management Using PSO Based ...
Small Signal Stability Improvement and Congestion Management Using PSO Based ...Small Signal Stability Improvement and Congestion Management Using PSO Based ...
Small Signal Stability Improvement and Congestion Management Using PSO Based ...
 
Digital Control for a PV Powered BLDC Motor
Digital Control for a PV Powered BLDC MotorDigital Control for a PV Powered BLDC Motor
Digital Control for a PV Powered BLDC Motor
 
An optimum location of on-grid bifacial based photovoltaic system in Iraq
An optimum location of on-grid bifacial based photovoltaic system in Iraq An optimum location of on-grid bifacial based photovoltaic system in Iraq
An optimum location of on-grid bifacial based photovoltaic system in Iraq
 
Benchmarking study between capacitive and electronic load technic to track I-...
Benchmarking study between capacitive and electronic load technic to track I-...Benchmarking study between capacitive and electronic load technic to track I-...
Benchmarking study between capacitive and electronic load technic to track I-...
 
Coordinated planning in improving power quality considering the use of nonlin...
Coordinated planning in improving power quality considering the use of nonlin...Coordinated planning in improving power quality considering the use of nonlin...
Coordinated planning in improving power quality considering the use of nonlin...
 
Development of a position tracking drive system for controlling PMSM motor us...
Development of a position tracking drive system for controlling PMSM motor us...Development of a position tracking drive system for controlling PMSM motor us...
Development of a position tracking drive system for controlling PMSM motor us...
 
Real time implementation of anti-windup PI controller for speed control of in...
Real time implementation of anti-windup PI controller for speed control of in...Real time implementation of anti-windup PI controller for speed control of in...
Real time implementation of anti-windup PI controller for speed control of in...
 
Implementation of speed control of sensorless brushless DC motor drive using ...
Implementation of speed control of sensorless brushless DC motor drive using ...Implementation of speed control of sensorless brushless DC motor drive using ...
Implementation of speed control of sensorless brushless DC motor drive using ...
 
The optimal solution for unit commitment problem using binary hybrid grey wol...
The optimal solution for unit commitment problem using binary hybrid grey wol...The optimal solution for unit commitment problem using binary hybrid grey wol...
The optimal solution for unit commitment problem using binary hybrid grey wol...
 
Power system operation considering detailed modelling of the natural gas supp...
Power system operation considering detailed modelling of the natural gas supp...Power system operation considering detailed modelling of the natural gas supp...
Power system operation considering detailed modelling of the natural gas supp...
 
IRJET- Energy Management and Control for Grid Connected Hybrid Energy Storage...
IRJET- Energy Management and Control for Grid Connected Hybrid Energy Storage...IRJET- Energy Management and Control for Grid Connected Hybrid Energy Storage...
IRJET- Energy Management and Control for Grid Connected Hybrid Energy Storage...
 
Frequency regulation service of multiple-areas vehicle to grid application in...
Frequency regulation service of multiple-areas vehicle to grid application in...Frequency regulation service of multiple-areas vehicle to grid application in...
Frequency regulation service of multiple-areas vehicle to grid application in...
 
Wind Energy
Wind EnergyWind Energy
Wind Energy
 
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
 
Power quality improvement based on hybrid coordinated design of renewable ene...
Power quality improvement based on hybrid coordinated design of renewable ene...Power quality improvement based on hybrid coordinated design of renewable ene...
Power quality improvement based on hybrid coordinated design of renewable ene...
 
Optimal Placement of D-STATCOM Using Hybrid Genetic and Ant Colony Algorithm ...
Optimal Placement of D-STATCOM Using Hybrid Genetic and Ant Colony Algorithm ...Optimal Placement of D-STATCOM Using Hybrid Genetic and Ant Colony Algorithm ...
Optimal Placement of D-STATCOM Using Hybrid Genetic and Ant Colony Algorithm ...
 

Similaire à A Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for PMSG Wind Turbine Systems

Flux Based Sensorless Speed Sensing and Real and Reactive Power Flow Control ...
Flux Based Sensorless Speed Sensing and Real and Reactive Power Flow Control ...Flux Based Sensorless Speed Sensing and Real and Reactive Power Flow Control ...
Flux Based Sensorless Speed Sensing and Real and Reactive Power Flow Control ...ijeei-iaes
 
STATCOM Based Wind Energy System by using Hybrid Fuzzy Logic Controller
STATCOM Based Wind Energy System by using Hybrid Fuzzy Logic ControllerSTATCOM Based Wind Energy System by using Hybrid Fuzzy Logic Controller
STATCOM Based Wind Energy System by using Hybrid Fuzzy Logic ControllerIJMTST Journal
 
APPLICATION OF STATCOM to IMPROVED DYNAMIC PERFORMANCE OF POWER SYSTEM
APPLICATION OF STATCOM to IMPROVED DYNAMIC PERFORMANCE OF POWER SYSTEMAPPLICATION OF STATCOM to IMPROVED DYNAMIC PERFORMANCE OF POWER SYSTEM
APPLICATION OF STATCOM to IMPROVED DYNAMIC PERFORMANCE OF POWER SYSTEMijsrd.com
 
Design of Integrated Generator-Rectifier System to Determine the Maximum Powe...
Design of Integrated Generator-Rectifier System to Determine the Maximum Powe...Design of Integrated Generator-Rectifier System to Determine the Maximum Powe...
Design of Integrated Generator-Rectifier System to Determine the Maximum Powe...IRJET Journal
 
Performance evolution of a PMSG based WECS using maximum power point tracking...
Performance evolution of a PMSG based WECS using maximum power point tracking...Performance evolution of a PMSG based WECS using maximum power point tracking...
Performance evolution of a PMSG based WECS using maximum power point tracking...theijes
 
Performance analysis of various parameters by comparison of conventional pitc...
Performance analysis of various parameters by comparison of conventional pitc...Performance analysis of various parameters by comparison of conventional pitc...
Performance analysis of various parameters by comparison of conventional pitc...eSAT Publishing House
 
Performance analysis of various parameters by comparison of conventional pitc...
Performance analysis of various parameters by comparison of conventional pitc...Performance analysis of various parameters by comparison of conventional pitc...
Performance analysis of various parameters by comparison of conventional pitc...eSAT Journals
 
Intelligent Control for Doubly Fed Induction Generator Connected to the Elect...
Intelligent Control for Doubly Fed Induction Generator Connected to the Elect...Intelligent Control for Doubly Fed Induction Generator Connected to the Elect...
Intelligent Control for Doubly Fed Induction Generator Connected to the Elect...IJPEDS-IAES
 
Development of DC voltage control from wind turbines using proportions and in...
Development of DC voltage control from wind turbines using proportions and in...Development of DC voltage control from wind turbines using proportions and in...
Development of DC voltage control from wind turbines using proportions and in...IJECEIAES
 
11.modeling and performance analysis of a small scale direct driven pmsg base...
11.modeling and performance analysis of a small scale direct driven pmsg base...11.modeling and performance analysis of a small scale direct driven pmsg base...
11.modeling and performance analysis of a small scale direct driven pmsg base...Alexander Decker
 
Modeling and performance analysis of a small scale direct driven pmsg based w...
Modeling and performance analysis of a small scale direct driven pmsg based w...Modeling and performance analysis of a small scale direct driven pmsg based w...
Modeling and performance analysis of a small scale direct driven pmsg based w...Alexander Decker
 
4.power quality improvement in dg system using shunt active filter
4.power quality improvement in dg system using shunt active filter4.power quality improvement in dg system using shunt active filter
4.power quality improvement in dg system using shunt active filterEditorJST
 

Similaire à A Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for PMSG Wind Turbine Systems (20)

Flux Based Sensorless Speed Sensing and Real and Reactive Power Flow Control ...
Flux Based Sensorless Speed Sensing and Real and Reactive Power Flow Control ...Flux Based Sensorless Speed Sensing and Real and Reactive Power Flow Control ...
Flux Based Sensorless Speed Sensing and Real and Reactive Power Flow Control ...
 
STATCOM Based Wind Energy System by using Hybrid Fuzzy Logic Controller
STATCOM Based Wind Energy System by using Hybrid Fuzzy Logic ControllerSTATCOM Based Wind Energy System by using Hybrid Fuzzy Logic Controller
STATCOM Based Wind Energy System by using Hybrid Fuzzy Logic Controller
 
APPLICATION OF STATCOM to IMPROVED DYNAMIC PERFORMANCE OF POWER SYSTEM
APPLICATION OF STATCOM to IMPROVED DYNAMIC PERFORMANCE OF POWER SYSTEMAPPLICATION OF STATCOM to IMPROVED DYNAMIC PERFORMANCE OF POWER SYSTEM
APPLICATION OF STATCOM to IMPROVED DYNAMIC PERFORMANCE OF POWER SYSTEM
 
Design of Integrated Generator-Rectifier System to Determine the Maximum Powe...
Design of Integrated Generator-Rectifier System to Determine the Maximum Powe...Design of Integrated Generator-Rectifier System to Determine the Maximum Powe...
Design of Integrated Generator-Rectifier System to Determine the Maximum Powe...
 
40220140506002
4022014050600240220140506002
40220140506002
 
Performance evolution of a PMSG based WECS using maximum power point tracking...
Performance evolution of a PMSG based WECS using maximum power point tracking...Performance evolution of a PMSG based WECS using maximum power point tracking...
Performance evolution of a PMSG based WECS using maximum power point tracking...
 
Performance analysis of various parameters by comparison of conventional pitc...
Performance analysis of various parameters by comparison of conventional pitc...Performance analysis of various parameters by comparison of conventional pitc...
Performance analysis of various parameters by comparison of conventional pitc...
 
Performance analysis of various parameters by comparison of conventional pitc...
Performance analysis of various parameters by comparison of conventional pitc...Performance analysis of various parameters by comparison of conventional pitc...
Performance analysis of various parameters by comparison of conventional pitc...
 
40220140505006
4022014050500640220140505006
40220140505006
 
40220140505006
4022014050500640220140505006
40220140505006
 
Bc33315326
Bc33315326Bc33315326
Bc33315326
 
Bc33315326
Bc33315326Bc33315326
Bc33315326
 
Intelligent Control for Doubly Fed Induction Generator Connected to the Elect...
Intelligent Control for Doubly Fed Induction Generator Connected to the Elect...Intelligent Control for Doubly Fed Induction Generator Connected to the Elect...
Intelligent Control for Doubly Fed Induction Generator Connected to the Elect...
 
Development of DC voltage control from wind turbines using proportions and in...
Development of DC voltage control from wind turbines using proportions and in...Development of DC voltage control from wind turbines using proportions and in...
Development of DC voltage control from wind turbines using proportions and in...
 
Super-twisting SMC for MPPT and grid-connected WECS based on SCIG
Super-twisting SMC for MPPT and grid-connected WECS based on SCIGSuper-twisting SMC for MPPT and grid-connected WECS based on SCIG
Super-twisting SMC for MPPT and grid-connected WECS based on SCIG
 
E010343239
E010343239E010343239
E010343239
 
Cy36602610
Cy36602610Cy36602610
Cy36602610
 
11.modeling and performance analysis of a small scale direct driven pmsg base...
11.modeling and performance analysis of a small scale direct driven pmsg base...11.modeling and performance analysis of a small scale direct driven pmsg base...
11.modeling and performance analysis of a small scale direct driven pmsg base...
 
Modeling and performance analysis of a small scale direct driven pmsg based w...
Modeling and performance analysis of a small scale direct driven pmsg based w...Modeling and performance analysis of a small scale direct driven pmsg based w...
Modeling and performance analysis of a small scale direct driven pmsg based w...
 
4.power quality improvement in dg system using shunt active filter
4.power quality improvement in dg system using shunt active filter4.power quality improvement in dg system using shunt active filter
4.power quality improvement in dg system using shunt active filter
 

Plus de Suganthi Thangaraj

MITIGATION OF UNBALANCED FAULTS IN DISTRIBUTION SYSTEM USING FD-STATCOM WITH ...
MITIGATION OF UNBALANCED FAULTS IN DISTRIBUTION SYSTEM USING FD-STATCOM WITH ...MITIGATION OF UNBALANCED FAULTS IN DISTRIBUTION SYSTEM USING FD-STATCOM WITH ...
MITIGATION OF UNBALANCED FAULTS IN DISTRIBUTION SYSTEM USING FD-STATCOM WITH ...Suganthi Thangaraj
 
ENHANCING RELIABILITY BY RECONFIGURATION OF POWER DISTRIBUTION SYSTEMS CONSID...
ENHANCING RELIABILITY BY RECONFIGURATION OF POWER DISTRIBUTION SYSTEMS CONSID...ENHANCING RELIABILITY BY RECONFIGURATION OF POWER DISTRIBUTION SYSTEMS CONSID...
ENHANCING RELIABILITY BY RECONFIGURATION OF POWER DISTRIBUTION SYSTEMS CONSID...Suganthi Thangaraj
 
An Improved Differential Evolution Algorithm for Congestion Management Consid...
An Improved Differential Evolution Algorithm for Congestion Management Consid...An Improved Differential Evolution Algorithm for Congestion Management Consid...
An Improved Differential Evolution Algorithm for Congestion Management Consid...Suganthi Thangaraj
 

Plus de Suganthi Thangaraj (6)

1 s2.0-s1364032117311607-main
1 s2.0-s1364032117311607-main1 s2.0-s1364032117311607-main
1 s2.0-s1364032117311607-main
 
MITIGATION OF UNBALANCED FAULTS IN DISTRIBUTION SYSTEM USING FD-STATCOM WITH ...
MITIGATION OF UNBALANCED FAULTS IN DISTRIBUTION SYSTEM USING FD-STATCOM WITH ...MITIGATION OF UNBALANCED FAULTS IN DISTRIBUTION SYSTEM USING FD-STATCOM WITH ...
MITIGATION OF UNBALANCED FAULTS IN DISTRIBUTION SYSTEM USING FD-STATCOM WITH ...
 
ENHANCING RELIABILITY BY RECONFIGURATION OF POWER DISTRIBUTION SYSTEMS CONSID...
ENHANCING RELIABILITY BY RECONFIGURATION OF POWER DISTRIBUTION SYSTEMS CONSID...ENHANCING RELIABILITY BY RECONFIGURATION OF POWER DISTRIBUTION SYSTEMS CONSID...
ENHANCING RELIABILITY BY RECONFIGURATION OF POWER DISTRIBUTION SYSTEMS CONSID...
 
An Improved Differential Evolution Algorithm for Congestion Management Consid...
An Improved Differential Evolution Algorithm for Congestion Management Consid...An Improved Differential Evolution Algorithm for Congestion Management Consid...
An Improved Differential Evolution Algorithm for Congestion Management Consid...
 
co-ordinate systems
 co-ordinate systems co-ordinate systems
co-ordinate systems
 
Electro magnetic waves
Electro magnetic wavesElectro magnetic waves
Electro magnetic waves
 

Dernier

Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesPrabhanshu Chaturvedi
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 

Dernier (20)

Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 

A Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for PMSG Wind Turbine Systems

  • 1. International Electrical Engineering Journal (IEEJ) Vol. 5 (2014) No.4, pp. 1305-1312 ISSN 2078-2365 http://www.ieejournal.com/ 1305 Rajkumar and Suganthi Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for PMSG Wind Turbine Systems A Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for PMSG Wind Turbine Systems S.Rajkumar1 , S.T.Suganthi2 1 Department of EEE,SNS College of Technology, Coimbatore-35 2 Department of EEE,SNS College of Technology,Coimbatore-35 1 rajkumareee89@gmail.com, 2 suganthi.sb@gmail.com Abstract— As the wind power installations are increasing in number, Wind Turbine Generators (WTG) are required to have Fault Ride-Through (FRT) capabilities. Lately developed grid operating codes demand the WTGs to stay connected during fault conditions, supporting the grid to recover faster back to its normal state. In this paper, the generator side converter incorporates the maximum power point tracking algorithm to extract maximum energy from wind turbine system. A hybrid control scheme for energy storage systems (ESS) and braking choppers for fault ride-through capability and a suppression of the output power fluctuation is proposed for permanent-magnet synchronous generator (PMSG) wind turbine systems. During grid faults, the dc-link voltage is controlled by the ESS instead of the line-side converter (LSC), whereas the LSC is exploited as a STATCOM to inject reactive current into the grid for assisting in the grid voltage recovery. A simple model of the proposed system is developed and simulated in MATLAB environment. The effectiveness of the system is validated through extensive simulation results Index Terms- Boost converter, Braking Chopper(BC),dc-link control, energy storage system(ESS),ride through, STATCOM, Permanent Magnet Synchronous Generator. I. INTRODUCTION The development of various wind turbine (WT) configurations in the last decade has been very dynamic and has resulted in larger ratings and higher operating speed ranges allowing them to be tied up to the grid more easily. Variable speed operation of wind energy conversion systems (WECS) make them more ‘grid-friendly’. Permanent magnet synchronous generators (PSMG) based WECS are emerging as strong competitors to the other variable speed technologies. The power converter, whose rating is the same as that of the generator, connected between PMSG and grid allows full controllability of the system during normal operation and fault conditions. Further, PMSG operates at higher efficiency and better power factor than its counterparts especially when it functions as a direct driven generator [1-3]. WECS based on PMSG can be connected to the grid by using a voltage source converter (VSC) on the grid side and by using either a diode converter with a buck-boost converter or a VSC on the machine side. Evidently, using VSC on both machine and grid sides offer full control of active and reactive powers resulting in the best performance [4-6] in terms of power output, quality of power and performance during faults. Different strategies have been presented by various authors, to enhance fault ride through (FRT) capabilities of PMSG based WECS. Many devices, such as static var compensator (SVC), dynamic voltage restorers (DVR), Static Synchronous Compensators (STATCOM) etc have been shown to improve FRT of WECS, but they will also increase the overall cost of the system [7-8]. In [9], a nonlinear controller design for power converter based WT system is presented which ensures that current levels remain within design limits, even at greatly reduced voltage levels. A back to back connected voltage source- converter (VSC) configuration is discussed in [10] where the machine side converter (MSC) controls the speed of the generator by using a flux vector control technique and the grid side converter (GSC) controls the power flow by PWM technique Transient analysis of a grid connected wind driven PMSG is presented in [11] and a comparison is presented with the other generators at fixed and variable speeds. An electromagnetic braking resistor controlled using power electronic switch is used to dissipate
  • 2. International Electrical Engineering Journal (IEEJ) Vol. 5 (2014) No.4, pp. 1305-1312 ISSN 2078-2365 http://www.ieejournal.com/ 1306 Rajkumar and Suganthi Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for PMSG Wind Turbine Systems the excess energy in the DC link Circuit, preventing DC link over voltage in [12]. Flexible active power control of distributed generation systems during Grid Faults is discussed in [13]. Reactive power as well as real power manipulation using current control is described in [14]. Control of grid converter in synchronously rotating reference frame is described in [15-16]. In this paper, the generator side converter incorporates the maximum power point tracking algorithm to extract maximum energy from wind turbine system. In addition, FRT technique of the PMSG wind turbine system is proposed during the grid fault. By switching the control mode, the ESS is operated to control the dc-link voltage of the back- to-back converters during the grid voltage sags. Meanwhile, the LSC is utilized to supply the reactive current to the grid for satisfying the reactive current requirements of the grid code. By this, the grid voltage can be recovered rapidly without an external STATCOM after fault clearance. Also, the generator active power can be absorbed fully by the ESS and the BC during the voltage sags. In addition, the output power fluctuation of wind turbine systems operating in steady state is smoothened by the ESS. With this control scheme, the system can still operate well even though the grid voltage is fully interrupted. The validity of the proposed control algorithm is verified by simulation and experimental results. II. SYSTEM DESCRIPTION Fig. 1 presents a block diagram of the simulation model used for the FRT and Maximum Power point tracking. In this paper, the wind turbine converts the power of the wind to mechanical power in the rotor shaft. This is then converted to electricity using a permanent magnet synchronous generator (PMSG). The output voltage is rectified using a three-phase diode bridge rectifier. The dc-to-dc converter is used to control the dc voltage Vdc . The MPPT controller delivers a voltage reference that is compared to the actual value of Vdc. The result is fed into a PI controller whose output is compared to a triangular waveform to determine when to turn the dc -dc boost converter switch ON or OFF.The ESS consists of a Electric Double Layer capacitor bank and a bidirectional DC/DC converter and is also connected to the dc-link. Super capacitors are suitable for wind power applications, as they present the features of high efficiency, high power density, long cycle life and easy maintenance . A BC is connected in parallel with the dc-link. The BC will be activated to dissipate the excessive power beyond the capacity of the ESS in cases of deep voltage sags or high wind speed variations. The control objective of the DC/DC converter is to maintain the dc-link voltage magnitude at a constant level, by absorbing any mismatch between the generated power and the power transferred to the grid. In normal conditions, the LSC controls the dc-link voltage , and the ESS is able to smoothen the power ripples. In grid fault conditions, on the other hand, the LSC functions as a STATCOM, and the ESS controls the dc- link voltage. The FRT control scheme is designed according to the grid code requirements on FRT. III. MODELLING OF PROPOSED CONTROL SCHEME A. Maximum Power Extraction Algorithm Due to its monotonic characteristics, wind turbines can be controlled to yield maximum power using search control methods. Before explaining the maximum power tracking controller, it is important to understand the basic physics of the system. The generated mechanical power is given by [17- 19] Pmech=Tmech(t)ωR(t) (1) Where, Tmech is the mechanical torque. For simplification, the generated electric power of a one-phase generator is given by Pe(t)=Va(t)Ia(t) (2) Fig 1:Block diagram of the proposed MPPT and FRT Method Va and Ia are the generator voltage and current respectively. Assuming no losses in the system, then Tmech(t).ωR(t)= Va(t)Ia(t) (3) The basic electrical and motion equations are Te = kIaIf (4) Ia=(Va-Ea)/Ra (5) Ea=kIaωe (6) Where, ωe = (p/2) ωR and p is the number of poles of the generator. Maximum power is at =0 (7)
  • 3. International Electrical Engineering Journal (IEEJ) Vol. 5 (2014) No.4, pp. 1305-1312 ISSN 2078-2365 http://www.ieejournal.com/ 1307 Rajkumar and Suganthi Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for PMSG Wind Turbine Systems Fig. 2. Typical power versus speed characteristics of a wind turbine. The power extracted from the wind can be controlled by varying the dc bus voltage, which is a function of If and ωe. Considering the wind turbine characteristics given in Figure 2, we know that the maximum power point is obtained whe ω = 0 (8) This equation can be written as: = =0 (9) According to equation (9),maximum power point is when: =0 (10) The function Pmech (Vdc) has a single point where maximum power extraction is achieved. It also means that the maximum power can be tracked by searching the rectified dc power, rather than environmental conditions, such as wind speed and direction. The MPPT algorithm is as follows. One initiates the maximum power searching process by setting an arbitrary dc side voltage reference Vref. The controller then measures both the dc side current and voltage, and calculates the initial electric power Po = VdcIdc. Next, the reference voltage Vref is increased by ΔVdc so that. Vref(k)= Vref(k-1)+ ΔVdc (11) Then the dc power is calculated with P(k) = Vdc(k)Idc(k). If P(k) is bigger than P(k - 1), the maximum power point has not been reached therefore, the voltage reference needs to be increased by ΔVdc and the dc power needs to be compared. This process will repeat until maximum power is reached. And if P(k) is less than P(k - 1), the dc voltage reference is then decreased by ΔVdc. In order to search for maximum power at any wind speed four conditions must be met. 1. If P(k)≥ P(k-1) and Vdc(k)≥ Vdc(k-1), the dc side voltage reference need to be increased by ΔVdc. This condition is met when the turbine operates on the low speed side of the power curve, shown on Fig 3. 2. If P(k)≥ P(k-1) and Vdc(k)< Vdc(k-1), the wind turbine is being operated in the high speed side and the dc reference voltage needs to be decreased by ΔVdc. 3. When P(k)< P(k-1) and Vdc(k)≥ Vdc(k-1), the maximum power point is passed and a step back must be taken, decreasing the reference voltage by ΔVdc. This condition is met when the turbine is operated in the high speed side of the dome and the power is decreasing. 4. When P(k)< P(k-1) and Vdc(k)< Vdc(k-1), the power is decreasing on the low speed side, therefore the voltage reference is to be increased by ΔVdc. Fig 3 Maximum Power Tracking Process In Figure 3, the power-speed plot is shown for three different wind speeds, where υ1 < υ 2 < υ 3. The arrows show the trajectory in which the turbine will be operated using the maximum power tracking algorithm explained above. If the wind speed is υ1, the controller will search for the maximum power. If the wind changes to υ3 the turbine is no longer being operated at the maximum power point so the controller will search for the new maximum power point. Fig 4. Flowchart for MPPT Algorithm
  • 4. International Electrical Engineering Journal (IEEJ) Vol. 5 (2014) No.4, pp. 1305-1312 ISSN 2078-2365 http://www.ieejournal.com/ 1308 Rajkumar and Suganthi Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for PMSG Wind Turbine Systems After reaching the maximum point it will operate the wind turbine at the optimal point until wind changes, thus searching for maximum power at any wind speed. In order to optimize the maximum power search algorithm presented above, a step that combines speed of convergence and accuracy of results was developed. The variable step method is based on the Newton Raphson method. The value of the root can be calculated as, Xn+1=Xn - (12) Where Xn is the current known value of X, ƒ(Xn) represents the value of the function at Xn, and ƒ’(Xn) is the derivative at Xn. The function ƒ (Xn) can be expressed as: ƒ(Xn)= ƒ(Vdc(k)) = = = Slope(k) (13) And ƒ’(Xn) as ƒ’(Xn)=ƒ’(Vdc(k)= = (14) Using (12,)(13) and (14), ΔVdc can be express as follows: ΔVdc = = (15) This variable step will allow the maximum power tracker to converge faster to the maximum power point and will decrease power oscillations due to large values of ΔVdc when maximum power is achieved. For protection the value of ΔVdc is limited. The ΔVdc limit can be changed based on the generator size and design parameters. B. DC/DC Converter Controller Fig 5 Typical DC-to-DC Converter Controller The maximum power tracker will generate a reference voltage that will be used to control the dc voltage at the rectifier dc side terminals. The dc-to-dc converter uses a simple feedback controller. The dc voltage reference is compared to the actual dc voltage, and the error signal is fed to a PI controller. The output signal is compared with a fixed frequency repetitive triangular waveform to deliver a signal that will turn ON or OFF the switch. This is shown in Fig 5. C. Control of ESS and BC The ESS and the BC are used to suppress the generator output power fluctuation in normal conditions by absorbing or releasing the pulsated power component from or to the grid, in which the power command, P*ESS, is obtained through a high-pass filter to the generator power [20]. The ESS power is regulated by an outer PI regulator, whereas the EDLC current is controlled by an inner PI regulator. Fig. 6. Control block diagram of the ESS and BC.
  • 5. International Electrical Engineering Journal (IEEJ) Vol. 5 (2014) No.4, pp. 1305-1312 ISSN 2078-2365 http://www.ieejournal.com/ 1309 Rajkumar and Suganthi Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for PMSG Wind Turbine Systems Before you begin to format your paper, first write and save the content as a separate text file. Keep your text and graphic files separate until after the text has been formatted and styled. Do not use hard tabs, and limit use of hard returns to only one return at the end of a paragraph. Do not add any kind of pagination anywhere in the paper. Do not number text heads- the template will do that for you. D. DC-Link Voltage Control During grid sags, the dc-link voltage of the back-to- back converters is controlled by the ESS instead of the LSC. Hence, an outer PI voltage controller is employed, which produces a current reference for an inner PI current controller. Fig. 6 shows the overview control block diagram of the ESS and the BC in both normal and grid sag conditions. Neglecting the power losses of the converters and considering the active power negligible flowing into the grid, the dynamic equation of the dc-link voltage is expressed as Pgen-PBC-PESS=0.5C(dV2 dc/dt) (16) where C is the dc-link capacitance, Pgen is the generator power, PBC is the power dissipated by the BC, and PESS is the power of the ESS computed from the ESS voltage, VESS, and the EDLC current, IESS, as PESS=VESS*IESS (17) From (16 ) in order to keep the dc-link voltage constant, the ESS and the BC should be able to absorb the generator powerfully. From the control block diagram shown in Fig. 6, the output of the dc-link voltage controller, I∗ ESS, is given as I*ESS=Kp2(Vdc*-Vdc)+ (Vdc*-Vdc) + (18) where Kp2 and KI2 are PI controller gains of the dc-link voltage control. In Fig. 6, IESS_max represents the maximum current of the ESS. By expanding a Taylor series of the dc-link voltage at operating point Vdc0, the following can be obtained: V2 dc=V2 dc0+2Vdc0(Vdc-Vdc0) (19) From (16)–(19), the dc-link voltage equation can be rewritten in the “s” domain as CVdc0sVdc=-VESSKp2(Vdc*-Vdc)-VESS (Vdc*-Vdc) (20) The transfer function of the voltage controller is derived as [21] ∗ = (21) where ξ is the damping ratio, and ωn is the natural frequency. It is indicated in (21) that the transfer function has a zero and two poles, which are always located in the left-half plane. Hence, control stability is achieved. E. EDLC Current Control To establish the current control law for the dc/dc converter, a voltage across the inductance, VLf , is investigated. The dynamic equation of the inductance voltage is expressed as [22], [23] VLf=Lf =DESSVdc-VESS (22) VLf=Lf =DESSVdc-VESS (22) where Lf is the boost inductance, and DESS is the duty cycle. As shown in Fig. 6, the output of the current controller, V ∗Lf , is given as V*Lf=Kpc(I*ESS-IESS)+ (I*ESS-IESS) (23) where Kpc and KIc are PI controller gains of the current control. The duty cycle is calculated by DESS=(VESS+V*Lf)/Vdc (24) Then, the gating signals for switches S1 and S2 are generated by comparing the duty cycle with the carrier wave of 2 kHz as shown in Fig. 6. F.BC Control During the grid disturbance, the ESS may not absorb the full generator power, and then the BC will be activated to dissipate the rest of power, PBC as PBC=Pgen-PESS (25) The BC is controlled by the switch S3 shown in Fig. 6.The duty ratio DS3 for the switch depends on PBC, which is expressed as DS3= PBC (26) where Rbc is the braking resistance.
  • 6. International Electrical Engineering Journal (IEEJ) Vol. 5 (2014) No.4, pp. 1305-1312 ISSN 2078-2365 http://www.ieejournal.com/ 1310 Rajkumar and Suganthi Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for PMSG Wind Turbine Systems G.Control of LSC The LSC controls the dc-link voltage, Vdc, to be constant under normal conditions. Cascaded control structure with an inner current control loop and the outer dc-link voltage control loop is applied . During grid voltage sags, however, the dc-link voltage is controlled by the ESS. Hence, the LSC is exploited as a STATCOM to supply the reactive current to the grid according to the requirements of the grid code. For this, the control strategy of the LSC is a voltage- controlled current source, in which the LSC is operated as a current source . In the case of unbalanced grid sags, the dual-current controllers for positive- and negative-sequence components are adopted for the LSC. The control block diagram of the LSC is shown in Fig. 7. In normal operation, the current references for positive- and negative-sequence current controllers are calculated from the output of the dc-link voltage controller as shown in Fig. 7 . During grid sags, dc- link voltage control by the LSC is deactivated, and the LSC injects the reactive current component. Hence, the reference of the active current component, Ip* qe is set to zero Ip* qe =0 (27) Fig. 7. Control block diagram of LSC The dq-axis current references In* dqe, of negative-sequence components are set to zero to eliminate the unbalanced current components flowing into the grid, which are expressed as In* qe =0 (28) In* de =0 (29) A proportional-integral (PI) controller is usually used for dc-link voltage control. Hence, an error accumulation in the integral regulator should be considered for fast transition when the dc-link voltage controller is reactivated after fault clearance. The PI controller is implemented in a discrete time domain. The actual dc-link voltage is able to track its reference by ESS control during the sag. Hence, an initial accumulated error, ΔVdc_I_int, of the integral regulator is set to zero as ΔVdc_I_int = 0. (30) IV SIMULATION RESULTS To perform the feasibility of the proposed scheme, Matlab simulations have been performed for a PMSG wind turbine system. The system parameters for the simulation are listed in Appendix . Fig 8 shows the variation of the wind speed and its corresponding output voltage of the PMSG. With the increase in wind speed the power fed to the grid also increases which is indicated by an increase in magnitude of PMSG phase voltage. At t =2.4 s, wind speed is changed from 8 to 12 m/s in step, whereas tip-speed ratio is maintained at Cp maximum in steady state conditions. Fig 8 (a) wind Speed (b) Phase voltage
  • 7. International Electrical Engineering Journal (IEEJ) Vol. 5 (2014) No.4, pp. 1305-1312 ISSN 2078-2365 http://www.ieejournal.com/ 1311 Rajkumar and Suganthi Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for PMSG Wind Turbine Systems Fig 9 (a) Grid voltage (b) Grid Current Fig 9 shows the performance of the LSC at voltage sags. Fig. 9(a) shows the grid voltage, where three grid-phase voltages drop to 20%, 20%, and 50%, respectively, during 0.5 s. Fig 9(b) shows the grid current which increased during the fault condition Fig 10(a) Grid Voltage (b) DC-Link Voltage The two-phase grid voltage interruption is considered as shown in Fig. 10(a) .With the proposed system, the dc-link voltage is controlled well by the ESS, which is shown in Fig.10(b). The increase in the dc-link voltage is less than 1.5%. Fig. 11 shows the performance of the ESS and the BC. The dc link voltage is controlled well as shown in Fig. 11(a), in which its transient value is less than 2.5%. Fig. 11(b) shows the ESS powers, in which the control performance is good for normal conditions. When the grid fault occurs, the power controller is deactivated, and the power is absorbed by the ESS as seen in Fig. 11(b) to maintain the dc-link voltage. The current control performance is shown in Fig. 11(c). Since the ESS is not able to absorb the full generator power, the rest of the power is dissipated by the BC. The BC current is shown in Fig. 11(d). When the EDLC absorbs the power from the wind system, the EDLC voltage is increased as shown in Fig. 11(e). Fig. 11. Performance of ESS and BC under unbalanced sag (a) DC-link voltage. (b) ESS power. (c) EDLC current. (d) Braking chopper current. (e) EDLC voltage. CONCLUSION This paper has proposed the maximum power point tracking algorithm to extract maximum energy from wind turbine system and combines the ESS and the BC for the LVRT in PMSG wind turbine systems which is an cost effective solution. The maximum power was tracked by searching the rectified dc power, rather than environmental conditions, such as wind speed and direction. Controlling the dc-link voltage by the ESS, the LSC is able to comply with the reactive current requirements of the grid code. By this, the grid voltage can be recovered rapidly without an external STATCOM after fault clearance. Also, the output power fluctuation of the wind turbine system operating in steady state is smoothened by the ESS. This control scheme offers an FRT
  • 8. International Electrical Engineering Journal (IEEJ) Vol. 5 (2014) No.4, pp. 1305-1312 ISSN 2078-2365 http://www.ieejournal.com/ 1312 Rajkumar and Suganthi Hybrid Control Scheme for Fault Ride-Through Capability using Line-Side Converter and an Energy Storage System for PMSG Wind Turbine Systems capability for the wind turbines even though the grid voltage is fully interrupted. Appendix: PMSG parameters: Stator resistance Rs=2.1Ω, Stator Inductance: 0.00083mH, inertia J= 0.01197 kgm2 , magnetic flux Φ=0.118 Wb and number of poles=4. Converter parameters: Low voltage side capacitor C1=500μF, High voltage side capacitor C0=3600μF, Inductor L=200mH, Switching frequency fd=20kHz, system frequency f=50Hz. ESS and BC parameters: ESS power ratingPESS-rated -0.6 KW, Capacitance of EDLCCEDLC-100 F, Operating VoltageVESS- 440 V,Power rating of BCPbc-rated-1.13 KW,Resistance Rbc-1.5 Ω REFERENCES [1] Rahul Nema, Anurag Trivedi “Application of Super Capacitor Based Energy Storage System for Power Quality Improvement of a Decentralized Power Plant” IEEJ Trans vol 04 no 1 pp 846- 855 [2] H. Li and Z. Chen, “Overview of different wind generator systems and their comparisons”, in IET Renewable Power Generation, Vol. 2, No. 2, pp. 123-138, 2008. [3] Rajveer Mittal, K.S. Sandhu and D.K. Jain., “An Overview of Some Important Issues Related to Wind Energy Conversion System (WECS)”, International Journal of Environmental Science and Development, Vol. 1, No. 4, pp. 351-362, October 2010. [4] Z. Chen and E. Spooner, “A Modular Permanent Magnet Generator for Variable Speed Wind Turbines” in proceedings of IEE EMD, pp. 453- 457, 1995 [5] Alejandro Rolán, Álvaro Luna, Gerardo Vázquez, Daniel Aguilar and Gustavo Azevado, “Modelling of a Variable Speed Wind Turbine with a Permanent Magnet Synchronous Generator”, in proceedings of IEEE International Symposium on Industrial Electronics ISIE, pp. 734-739, July 2009. [6] Rajveer Mittal, K.S. Sandhu and D.K. Jain., “Low Voltage Ride Through of Grid Interfaced Wind Driven PMSG”, ARPN Journal of Engineering and Applied Sciences, Vol. 4, No. 5, pp. 73-83, 2009 [7] B. Singh, R.Saha, A. Chandra, K. Al. Haddad, “Static Synchronous Compensators”, IET Power Electronics, Vol. 2, Issue.4, pp. 297-324, 2009 [8] Yingdong Wei, Lucheng Hong, Qirong Jiang and Zhiyong Wang, “ A New Dynamic Strategy for Ride Through Capability of Wind Turbine Generator”, Power and Energy Society General Meeting, pp. 1-6, 2011 [9] A. Mullane, G. Lightbody and R. Yacamini, "Wind-turbine fault ride through enhancement," IEEE transactions on Power Systems, Vol.20, No.4, pp. 1929- 1937, Nov. 2005. [10] Remus Teodorescu and Frede Blaabjerg, "Flexible Control of Small Wind Turbines with Grid Failure Detection Operating in Stand Alone and Grid Connected Mode," IEEE Transactions on Power Electronics, vol. 19, No.5, pp.1323-1332, September 2004. [11] Mazen Abdel-Salam, Adel Ahmed and Mahmoud Mahrous, “Transient Analysis of Grid Connected Wind Driven PMSG, DFIG and SCIG at Fixed and Variable Speeds”, Innovative Systems Design and Engineering, Vol. 2, No. 3, 2011 [12] J. F. Conroy and R. Watson, “Low Voltage Ride Through of a Full Converter Wind Turbine with Permanent Magnet Generator”, IET Renewable Power Generation, Vol. 1, No. 3, pp. 182-189, 2007 [13] P. Rodriguez, A.V. Timbus, R. Teodorescu, M. Liserre and F. Blaabjerg, "Flexible Active Power Control of Distributed Power Generation Systems During Grid Faults," IEEE Transactions on Industrial Electronics, vol.54, no.5, pp.2583-2592, Oct. 2007. [14] P. Rodriguez, A.V. Timbus, R. Teodorescu, M. Liserre and F. Blaabjerg, "Independent PQ Control for Distributed Power Generation Systems under Grid Faults," In Proc. of IEEE 32nd Annual Conference on Industrial Electronics, pp.5185-5190, Nov. 2006. [15] P. N. Enjeti and S. A. Choudhury, “A New Control Strategy to Improve the Performance of a PWM AC to DC Converter Under Unbalanced Operating Conditions,” IEEE Transactions on Power Electronics, Vol. 8, pp. 493–500, Oct. 1993. [16] P. Rioual, H. Pouliquen, and J. Louis, “Regulation of a PWM Rectifier in the Unbalanced Network State Using a Generalized Model,” IEEE Transactions on Power Electronics, vol. 11, pp. 495–502, May 1996. [17] Spera DA. Wind turbine technology: fundamental concept of wind turbine engineering. New York: ASHE Press; 1994. [18] Bhadra SN, Kastha D, Banerjee S. Wind electrical systems. Oxford, UK: Oxford University Press; 2005. [19] Mohammad H. Rashid. Power electronics-circuit. Devices and application. 3rd ed; 2004. [20] T. H. Nguyen, D.-C. Lee, S.-H. Song, and E.-H. Kim, “Improvement of power quality for PMSG wind turbine systems,” in Proc. IEEE ECCE, Sep. 2010, pp. 2763–2770. [21] T. H. Nguyen and D. C. Lee, “Ride-through technique for PMSG wind turbine using energy storage systems,” J. Power Electron., vol. 10, no. 6, pp. 733–738, Nov. 2010. [22] R. J. Wai and L. C. Shih, “Design of voltage tracking control for DCDC boost converter via total sliding-mode technique,” IEEE Trans. Ind. Electron., vol. 58, no. 6, pp. 2502–2511, Jun. 2011. [23] E. Babaei, M. E. S. Mahmoodieh, and M. Sabahi, “Investigating buck DCDC converter operation in different operational modes and obtaining the minimum output voltage ripple considering filter size,” J. Power Electron., vol. 11, no. 6, pp. 793–800, Nov. 2011. [24] Shuhui Li and Tim A. Haskew, “Characteristics Study of Vector – Controlled Direct Driven Permanent Magnet Synchronous Generator in Wind Power Generation”, in proceedings of IEEE Power and Energy Society General Meeting - Conversion and Delivery of Electrical Energy in the 21st Century, pp. 01-09, 2008.