European Copper Institute
WHITE PAPER
INTEGRATED EARTHING SYSTEMS (EARTHING GRID)
Rob Kersten & Frans van Pelt
July 2011
ECI Publication No Cu0102
Available from www.leonardo-energy.org
Publication No Cu0102
Issue Date: July 6, 2011
Page i
Document Issue Control Sheet
Document Title: Integrated Earthing Systems (Earthing Grid)
Publication No: Cu0102
Issue: 01
Release: July 6, 2011
Author(s): Rob Kersten and Frans van Pelt
Reviewer(s): Stefan Fassbinder, Bruno De Wachter, Hans De Keulenaer
Document History
Issue Date Purpose
1 July 6, 2011 Initial publication
2
3
Disclaimer
While this publication has been prepared with care, European Copper Institute and other contributors provide
no warranty with regards to the content and shall not be liable for any direct, incidental or consequential
damages that may result from the use of the information or the data contained.
Copyright© European Copper Institute.
Reproduction is authorised providing the material is unabridged and the source is acknowledged.
Publication No Cu0102
Issue Date: July 6, 2011
Page ii
CONTENTS
Executive Summary ................................................................................................................................................1
What is an Integrated Earthing System? ................................................................................................................1
A short historical overview.....................................................................................................................................2
Growing in importance...........................................................................................................................................2
The state-of-the-art Integrated Earthing System ...................................................................................................3
Applicable standards ..............................................................................................................................................4
IEC 61000 standard series ........................................................................................................................4
The Technical Report IEC TR 61000-5-2 ...................................................................................................4
The new standard for lightning protection IEC 62305 .............................................................................5
Non European Standards .........................................................................................................................6
Copper versus (galvanized) steel ............................................................................................................................7
Upgrade existing installations or not?....................................................................................................................7
Conclusions.............................................................................................................................................................8
Publication No Cu0102
Issue Date: July 6, 2011
Page 1
EXECUTIVE SUMMARY
Businesses and governments will continue to focus on efficiency and quality improvements while at the same
time remaining under pressure to reduce costs. Hence, automation developed to a very high level and the
Internet has become a strategic requirement. The consequent business vulnerability must obviously be
recognized and risk reduced. High availability level to the IT infrastructure is a primary requirement.
The necessity for constant availability of electrical power is well and broadly understood. The electrical
contractor supplies the protective earthing facilities, another specialized company provides lightning
protection, and the IT equipment manufacturer requires a functional earthing system. In the past, this resulted
in the installation of three independent earthing systems. This multiple approach has proved to be the cause
of certain types of operational problems and damage. The introduction of faster technologies and
communication networks increased the number of problems; an alternative was urgently needed.
The Integrated Earthing System discussed in this paper is the result of extensive work by knowledge institutes
and suppliers. This technology is meanwhile embedded in the related safety, lightning protection, and EMC
standards, and its reliability has been field proven in many installations. The following pages explain the
technical principles of this system and the abbreviations used.
The Integrated Earthing System (Earthing Grid) is the current state of the art solution and an indispensable
part of critical IT operations.
WHAT IS AN INTEGRATED EARTHING SYSTEM?
An Integrated Earthing System (Earthing Grid) aims to protect digital/electronic equipment against the effects
of severe electric and magnetic disturbances (such as lightning, short-circuits, et cetera) and enables this
equipment to function properly, both on the short- and long-term.
An earthing grid normally has three different primary functions:
1. Preventing electrocution or fire caused by short-circuits or insulation defects
2. Avoiding human injuries and fatalities in case of a direct or nearby lightning strike
3. Protecting electronic equipment against the effects of electromagnetic disturbances so that it can
continue to function properly on both the short- and long-term
Historically, those three protection functions were developed separately, under the names ‘protective
earthing’, ‘lightning protection’, and ‘functional earthing’. In the course of time it became clear that these
three different earthing systems could influence each other up to the point of hampering each other’s proper
and efficient functioning. As a result, the only way to ensure that all protective functions are well covered, is to
design a single integrated earthing system that deals with all three issues simultaneously. Designing such a
network is a complex task, to be executed by a specialized engineer.
Publication No Cu0102
Issue Date: July 6, 2011
Page 2
A SHORT HISTORICAL OVERVIEW
Lightning protection was invented in 1749 by Benjamin Franklin. It resulted in the establishment of a lightning
protection industry, devoted to the fire protection of buildings. The American National Fire Protection
Association (NFPA) was founded in 1896. Their first code — NFPA 1 — stipulated how to achieve a reasonable
level of fire safety and property protection in buildings.
The electrical power industry had matured considerably by the end of the nineteenth century. The first
practical electrical power distribution network was created in 1882. Protective earthing connections were
developed to reduce the risks of electrocution and fire. The NFPA published their first National Electrical Code
(NEC) in 1897.
Protective earthing and lightning protection were initially developed as totally separated systems, and it took a
while before their interconnection — initially only underground — was accepted as a better solution.
With the advent of electronic equipment and computer systems in the 1960s, awareness grew regarding the
fact that electromagnetic signals can disturb each other. This gave birth to the concept of electromagnetic
compatibility, or in short: EMC. Initially, EMC solutions were developed separately from the lightning and
protective-earthing systems. They were part of the so-called clean or functional earthing system, dedicated to
protecting electronic devices.
Around 1980, extensive studies revealed that the causes of various shortcomings, which were thought to be
inherent to the earthing systems themselves, were actually resulting from the separation of the three systems
and the lack of compatibility between them. Out of this understanding emerged the concept of an integrated
earthing system.
Integrated earthing concepts were introduced in the IEC and IEEE standards by the end of the 1990s, and
European EMC directives were approved that required incorporating those standards (or equivalent
alternative methods). This provoked a short-lived hype of EMC awareness.
Subsequently however, this interest began to fade, and today the implementation of the prevailing standards
and regulations is often still lacking. There is still considerable confusion about earthing systems and their
characteristics, even among specialists. Systems based on outdated technology are still operational, and
engineers who have not adopted the latest insights are still influential.
GROWING IN IMPORTANCE
Integrated earthing for tertiary sector and industrial buildings has been growing in significance over the past
decades due to the rapid development of IT systems. As IT systems take on increasingly crucial functions, their
reliability and that of their energy supply becomes considerably more critical. Paradoxically, IT devices are at
the same time becoming increasingly vulnerable to electromagnetic disturbances. This vulnerability stems
from the fact that signal bandwidths are being increased and signal amplitudes reduced, with the aim of
processing larger amount of data within shorter time periods. Only a well-designed integrated earthing
network can give those IT systems the immunity they require.
IT systems are used more and more in places where reliability is absolutely imperative. Think for instance of
public transport facilities such as digital security systems and airline/railway traffic management. Other
examples include data centres and corporate computer systems. For these kinds of systems, failure is not an
option. The integrity and reliable functioning of such IT systems has grown in importance to the level of human
safety. As a result, functional earthing has become just as ‘vital’ as traditional protective earthing and lightning
protection.
Publication No Cu0102
Issue Date: July 6, 2011
Page 3
THE STATE-OF-THE-ART INTEGRATED EARTHING SYSTEM
The integrated earthing system provides and combines various different functions, which have historically
been tackled in different domains:
1) Protective earthing (humans):
a. Conducting fault currents back to the power source without introducing the risk of local
overheating that might lead to fire.
b. Protection against indirect contact. Indirect contact occurs when a person touches a
conductive (metal) part which is normally not live, but which has become live due to a fault
in the insulation. Protection against indirect contact also requires the use of a Residual
Current Device (RCD) and equipotential bonding. Equipotential bonding is the connection
with each other of all conductive parts of the electrical system and conductive parts
extraneous to the electrical system, and subsequently connecting this bonding network to
the protective earthing network. Extraneous conductive parts include for instance metal
pipes, metal windows, and iron components of reinforced concrete. Equipotential bonding
avoids the situation where two metal parts can hold a different electrical potential, entailing
the risk on electrocution if they were to be touched simultaneously.
2) Lightning protection (humans and equipment):
a. Conduct lightning currents to the earth without introducing any risk of electrocution or
overheating.
b. Prevent direct fires, flashovers. or explosions caused by a lightning strike.
c. Apply the necessary interconnections and surge protection devices (SPD) at the Lightning
Protection Zones (LPZ) transition points to reduce the extreme voltage and current transients
down to the defined levels for the different zones.
3) Functional earthing (equipment):
Ensuring electromagnetic compatibility (EMC). All electric and electronic devices send out
electromagnetic signals (waves). Electromagnetic compatibility is ensured when those signals do
not disturb the proper functioning of other electronic devices.
Although the requirements for these different aspects are often specified separately, the implementation
requires an integrated systems approach, as the solution for one aspect might influence the proper and
efficient functioning of another solution.
For example, the danger of electrocution by simultaneously touching different earthing networks was initially
solved by connecting a high frequency choke between those networks. It was subsequently discovered
however, that this degrades the lightning protection function.
Integrated earthing means that all of the different earthing functions are integrated into a single system: the
so-called ‘earthing grid’. This earthing grid provides a single metal matrix for the entire facility. It should be
noted that the focus is wider than just a single building within a complex; the earthing grid should cover all
buildings on a particular site or of a facility.
If an integrated approach is not followed, the various individual protective solutions risk a higher investment
cost without ensuring the protection they are designed to provide. In addition, failure of protection can lead to
significant claims and legal complications. European directives and local regulations have been tightened
considerably in recent years, both in terms of technical requirements and liability. Nonetheless, knowledge
Publication No Cu0102
Issue Date: July 6, 2011
Page 4
regarding these new regulations is often lacking. For example, it is often not understood that the owner of a
multi-vendor technical infrastructure is responsible for overall CE compliance. This implies that all equipment
design and the corresponding documentation must conform to all prevailing regulations, including earthing.
One of the barriers for the fast and widespread implementation of the latest earthing standards is that
historically, the three earthing disciplines (Protective Earthing, Functional Earthing, and Lightning Protection)
were supervised by different parties (respectively electrical contractors, equipment manufacturers, and
lightning protection contractors). It will take time for those parties to combine their insights and develop a
common understanding.
It is therefore recommended that an experienced external consultancy be involved to supervise both design
and installation, in order to address all aspects of the inherent complexity of this subject. Strategically
important for your organization is that maintenance, modifications, and extensions are supervised by the same
office.
APPLICABLE STANDARDS
IEC 61000 STANDARD SERIES
The applicable harmonized standards are referenced in the Official Journal of the European Union, thus not in
the European directives themselves. Compliance with these standards should raise a presumption of
conformity with the relevant essential requirements, although other means of demonstrating such conformity
are permitted. Compliance with these directives is enforced by law in all Member Countries; they are
absolutely not voluntary. The applicable standards define different EMC environments, and provide clear
emission and susceptibility requirements.
THE TECHNICAL REPORT IEC TR 61000-5-2
The Technical Report IEC TR 61000-5-2 describes a workmanship code for good EMC. It explains in detail all
kinds of installation and mitigation guidelines to obtain Electro Magnetic Compatibility between various
devices installed in the same building. The Integrated Earthing System is an important mechanism to avoid the
build-up of significant voltage differences between various points in the earthing networks. The following
illustration shows a typical Integrated Earthing System with a three dimensional meshed earthing system for
the entire building, including finer meshed systems for areas with more sensitive equipment.
Source: Figure 7 from IEC TR 61000-5-2 (1997)
The Technical Report also provides recommendations on how to connect equipment to this earthing system,
but it does not demand changes to the internal wiring of the equipment.
Publication No Cu0102
Issue Date: July 6, 2011
Page 5
Notes:
I. Additional earthing connections do not substitute for the power cable protective earthing conductor
(PE). The latter must never be omitted, for safety and EMC reasons. PE and Neutral conductors should
not be combined inside the power cabling network.
II. Likewise, for EMC reasons, the return conductor for electrical signals must never be omitted. This
return conductor must always be included in the corresponding signal cable and not be identical to
the return conductor of the power supply.
III. Figure 8 in TR 61000-5-2 (not shown here) provides a good impression of the Integrated Earthing
System for an industrial plant.
IV. Special note for the (Process) Industry: There is no such thing as intrinsically safe earthing. All
required earthing points must be connected to a common earthing grid. This is to ascertain that each
earthing point is actually at the same potential to prevent arcing and the consequent ignition of an
explosive environment. Building steel is infamous as an unsuitable earthing point due to corrosion, et
cetera.
THE NEW STANDARD FOR LIGHTNING PROTECTION IEC 62305
In 2006, the new IEC 62305 standard for lightning protection of electrical and electronic systems within
buildings was published. Since then, protective earthing, functional earthing, and lightning protection have all
been integrated into a single protection concept.
The IEC 61000-5-2 technical report published earlier explained many general lightning protection aspects.
More specific details covered by IEC 62305 can be found in the following documents:
 IEC 62305-1: General principles
 IEC 62305-2: Risk management
 IEC 62305-3: Physical damage to structures and life hazard
 IEC 62305-4: Electrical and electronic systems within structures
The following illustration shows a typical example of a resulting integrated earthing system (grid):
Source: Figure 5 from IEC 62305-4 (2006)
Publication No Cu0102
Issue Date: July 6, 2011
Page 6
IEC 62305-4 also requires that engineers who are implementing the protection system have mastered
all three disciplines concerned: protective earthing engineering, lightning protection engineering, and
EMC engineering.
Lightning Protection Zones
The lightning protection zone concept shown below is a layered form of protection, fully in line with the
requirements for Surge Protection Devices (SPDs) for the respective Lightning Protection Zone (LPZ). This
mitigates interference from an upstream zone to the design level for the respective lower zone, as indicated in
the next figure. Note that the cable armour should be earthed at the zone transition point.
Source: Figure 1 from IEC 62305-4 (2006)
NON EUROPEAN STANDARDS
Other standards, such as those of the IEEE, may be the (legally) preferred standards in other countries (i.e. the
Middle East and other locations outside the USA). A good guide to this situation is the IEEE Emerald book (IEEE
Std 1100 – 2005) titled Powering and Grounding Electronic Equipment. Section 4.8.5.3 discusses the Integrated
Earthing System using different terminology:
Modern signal reference structures [SRS]. An SRS is the external installed network of conductors used to
interconnect the metal frames, enclosures, and logic or signal level power supply common terminals of the
subject electrical and electronic equipment to one another. This network may be a recommendation from, or
an actual part of, the equipment’s OEM installation package. Most often it may be part of an aftermarket,
field-installed wiring effort. The SRS is also an integral part of any SPD [Surge Protection Device] network
system that is used on either ac or dc power, or signal (including telecommunications) circuits connected to
the electronic equipment that is also attached to the SRS. The SRS is also not intended to be dielectrically or
galvanically insulated or isolated from the building electrical system’s EGC [Equipment Ground Conductor]
system that is part of the fault/personnel protection grounding subsystem.
In figure 4-66 (below), this IEEE standard compares the superior low impedance of a SRS (thus also of the
Integrated Earthing System) with an ordinary earthing conductor (green coloured in the USA).
Publication No Cu0102
Issue Date: July 6, 2011
Page 7
Source: Figure 4-66 from IEEE Std 1100 (2005)
COPPER VERSUS (GALVANIZED) STEEL
The Integrated Earthing System should preferably be constructed from conventional copper-based materials to
obtain a low and long lasting impedance, also for very fast phenomena such as lightning or high frequency
signals. Copper assures that the potential differences are kept to a minimum and prevents corrosion problems.
As a result, in the large majority of the cases, the most reliable and durable solution will be the all copper
Integrated Earthing System.
The commonly used (galvanized) steel has the disadvantage of an increased impedance at higher frequencies,
caused by the higher permeability (magnetic property) of steel. Moreover, protective measures against
electro-corrosion are required when connecting different metal materials with each other.
Flat conductors are to be preferred to round conductors, as they have a lower impedance at higher
frequencies. A minimum thickness is required for ensuring lightning protection and for construction reasons.
UPGRADE EXISTING INSTALLATIONS OR NOT?
Should existing installations that were not conceived according to the latest standards be upgraded
immediately?
They should be upgraded, but caution is advisable. Existing installations are likely to be based on outdated
EMC insight. They should be carefully inspected by specialists understanding both old and new concepts
before any changes are considered. Otherwise, there is a risk of creating involuntary earthing loops in the
signal path, which is to be avoided in every case!
Publication No Cu0102
Issue Date: July 6, 2011
Page 8
CONCLUSIONS
1. Although historically developed as separate systems, protective earthing, functional earthing, and
lightning protection should be provided by a single integrated earthing grid. If not, compatibility
problems between the three protection networks can occur.
2. A well-conceived earthing grid is of growing importance, as electronic devices become increasingly
sensitive to disturbances. Moreover, IT systems are increasingly used for critical operations for which
failure is not an option.
3. The integrated earthing system concept is explained in international standards (i.e. IEC 61000 series,
the technical report IEC TR 61000-5-2, and the IEC 62305 series, et cetera). The Official Journal of the
European Union documents their applicable harmonized standards. Compliance with the standards
(or an equivalent method of demonstrating conformity) is compulsory.
4. Knowledge of the prevailing standards and regulations is often poor, even among engineers. There is
still a great deal of confusion about earthing systems and their characteristics. As a result, the
implementation of the appropriate standards is often lacking. Company standards (suppliers,
contractors, end-users) may still be based on outdated concepts, and the engineers involved
(electrical engineers, process engineers, instrument engineers, lightning engineers, maintenance
engineers, et cetera) may still be unaware of the latest insights. It is therefore recommended that an
external consultant experienced in the matter be contacted and utilized.
5. The Integrated Earthing System should be constructed from conventional copper-based materials to
obtain the lowest resistance and to avoid corrosion problems.
6. Upgrading existing installations should be undertaken with care. Specialists that understand both old
and new earthing concepts should first meticulously inspect them.

Contenu connexe

Tendances

Advanced metering infrastructure (AMI)
Advanced metering infrastructure (AMI)Advanced metering infrastructure (AMI)
Advanced metering infrastructure (AMI)
Arul Kumar
 
Factors considered for High Voltage Cable Joint design
Factors considered for High Voltage Cable Joint design Factors considered for High Voltage Cable Joint design
Factors considered for High Voltage Cable Joint design
Shahab Khan
 
Key Elements of Australian Wiring Standards
Key Elements of Australian Wiring StandardsKey Elements of Australian Wiring Standards
Key Elements of Australian Wiring Standards
Living Online
 
Fire Cable Sizing
Fire Cable SizingFire Cable Sizing
Fire Cable Sizing
Leonardo ENERGY
 
transformer Sales, after sales & service presentation
transformer Sales, after sales & service presentationtransformer Sales, after sales & service presentation
transformer Sales, after sales & service presentation
Fawaz Baik
 
EV CHARGING CABLE – STANDARDS, TESTING, AND CERTIFICATION
EV CHARGING CABLE – STANDARDS, TESTING, AND CERTIFICATIONEV CHARGING CABLE – STANDARDS, TESTING, AND CERTIFICATION
EV CHARGING CABLE – STANDARDS, TESTING, AND CERTIFICATION
iQHub
 

Tendances (20)

Electrothermography en
Electrothermography enElectrothermography en
Electrothermography en
 
Electrical Safety Training by ISRI
Electrical Safety Training by ISRIElectrical Safety Training by ISRI
Electrical Safety Training by ISRI
 
Tariff, Wiring and Lighting Systems
Tariff, Wiring and Lighting SystemsTariff, Wiring and Lighting Systems
Tariff, Wiring and Lighting Systems
 
DSM
DSMDSM
DSM
 
A History of Medium & High Voltage Cables - Georgia Tech & NEETRAC
A History of Medium & High Voltage Cables - Georgia Tech & NEETRACA History of Medium & High Voltage Cables - Georgia Tech & NEETRAC
A History of Medium & High Voltage Cables - Georgia Tech & NEETRAC
 
Advanced metering infrastructure (AMI)
Advanced metering infrastructure (AMI)Advanced metering infrastructure (AMI)
Advanced metering infrastructure (AMI)
 
Factors considered for High Voltage Cable Joint design
Factors considered for High Voltage Cable Joint design Factors considered for High Voltage Cable Joint design
Factors considered for High Voltage Cable Joint design
 
ETAP - Ugs Underground Raceway Systems
ETAP - Ugs Underground Raceway SystemsETAP - Ugs Underground Raceway Systems
ETAP - Ugs Underground Raceway Systems
 
ELECTRIC HEATING AND HEATING METHODS
ELECTRIC HEATING AND HEATING METHODSELECTRIC HEATING AND HEATING METHODS
ELECTRIC HEATING AND HEATING METHODS
 
Unit 6
Unit 6Unit 6
Unit 6
 
Key Elements of Australian Wiring Standards
Key Elements of Australian Wiring StandardsKey Elements of Australian Wiring Standards
Key Elements of Australian Wiring Standards
 
2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards
 
Fire Cable Sizing
Fire Cable SizingFire Cable Sizing
Fire Cable Sizing
 
Insulation resistance test
Insulation resistance testInsulation resistance test
Insulation resistance test
 
transformer Sales, after sales & service presentation
transformer Sales, after sales & service presentationtransformer Sales, after sales & service presentation
transformer Sales, after sales & service presentation
 
Electrical Wiring:Types of wires and Cables and the circuit control on domest...
Electrical Wiring:Types of wires and Cables and the circuit control on domest...Electrical Wiring:Types of wires and Cables and the circuit control on domest...
Electrical Wiring:Types of wires and Cables and the circuit control on domest...
 
ppt of Elcb( earth leakage circuit breaker)
ppt of Elcb( earth leakage circuit breaker)ppt of Elcb( earth leakage circuit breaker)
ppt of Elcb( earth leakage circuit breaker)
 
Sarvayogam corp presentation on chemical earthing
Sarvayogam corp  presentation on chemical earthingSarvayogam corp  presentation on chemical earthing
Sarvayogam corp presentation on chemical earthing
 
IS : 3043 -1987 CODE OF PRACTICE FOR EARTHING(REACTANCE GROUNDING)
IS : 3043 -1987 CODE OF PRACTICE FOR EARTHING(REACTANCE GROUNDING)IS : 3043 -1987 CODE OF PRACTICE FOR EARTHING(REACTANCE GROUNDING)
IS : 3043 -1987 CODE OF PRACTICE FOR EARTHING(REACTANCE GROUNDING)
 
EV CHARGING CABLE – STANDARDS, TESTING, AND CERTIFICATION
EV CHARGING CABLE – STANDARDS, TESTING, AND CERTIFICATIONEV CHARGING CABLE – STANDARDS, TESTING, AND CERTIFICATION
EV CHARGING CABLE – STANDARDS, TESTING, AND CERTIFICATION
 

Similaire à Integrated Earthing Systems

ARDUINO MICROCONTROLLER BASED UNDERGROUND CABLE FAULT DISTANCE LOCATOR
ARDUINO MICROCONTROLLER BASED UNDERGROUND CABLE FAULT DISTANCE LOCATORARDUINO MICROCONTROLLER BASED UNDERGROUND CABLE FAULT DISTANCE LOCATOR
ARDUINO MICROCONTROLLER BASED UNDERGROUND CABLE FAULT DISTANCE LOCATOR
IAEME Publication
 
Smart grid networks and security architecture: Threat analysis, threat scenar...
Smart grid networks and security architecture: Threat analysis, threat scenar...Smart grid networks and security architecture: Threat analysis, threat scenar...
Smart grid networks and security architecture: Threat analysis, threat scenar...
John-André Bjørkhaug
 
An automatic system for detecting voltage leaks in houses to save people's l...
An automatic system for detecting voltage leaks in houses to  save people's l...An automatic system for detecting voltage leaks in houses to  save people's l...
An automatic system for detecting voltage leaks in houses to save people's l...
nooriasukmaningtyas
 

Similaire à Integrated Earthing Systems (20)

Earthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspectsEarthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspects
 
28 9760 a review paper id 0028 (ed l)
28 9760 a review paper id 0028 (ed l)28 9760 a review paper id 0028 (ed l)
28 9760 a review paper id 0028 (ed l)
 
ARDUINO MICROCONTROLLER BASED UNDERGROUND CABLE FAULT DISTANCE LOCATOR
ARDUINO MICROCONTROLLER BASED UNDERGROUND CABLE FAULT DISTANCE LOCATORARDUINO MICROCONTROLLER BASED UNDERGROUND CABLE FAULT DISTANCE LOCATOR
ARDUINO MICROCONTROLLER BASED UNDERGROUND CABLE FAULT DISTANCE LOCATOR
 
Fundamentals of electromagnetic compatibility (EMC)
Fundamentals of electromagnetic compatibility (EMC)Fundamentals of electromagnetic compatibility (EMC)
Fundamentals of electromagnetic compatibility (EMC)
 
Transient overvoltages and currents: system interaction and effects on equipment
Transient overvoltages and currents: system interaction and effects on equipmentTransient overvoltages and currents: system interaction and effects on equipment
Transient overvoltages and currents: system interaction and effects on equipment
 
Make India Safer with JMV LPS Ltd Electrical Equipment & Human Safety
Make India Safer with JMV LPS Ltd  Electrical Equipment & Human SafetyMake India Safer with JMV LPS Ltd  Electrical Equipment & Human Safety
Make India Safer with JMV LPS Ltd Electrical Equipment & Human Safety
 
Factors Affecting the Electrical Safety of 20 residential buildings of Bulua,...
Factors Affecting the Electrical Safety of 20 residential buildings of Bulua,...Factors Affecting the Electrical Safety of 20 residential buildings of Bulua,...
Factors Affecting the Electrical Safety of 20 residential buildings of Bulua,...
 
Earthing Configurations
Earthing ConfigurationsEarthing Configurations
Earthing Configurations
 
Single electron transistor technology based on chip implementation of smoke d...
Single electron transistor technology based on chip implementation of smoke d...Single electron transistor technology based on chip implementation of smoke d...
Single electron transistor technology based on chip implementation of smoke d...
 
Emission security- Tempest Attacks
Emission security- Tempest AttacksEmission security- Tempest Attacks
Emission security- Tempest Attacks
 
Emission security-tempest attacks
Emission security-tempest attacksEmission security-tempest attacks
Emission security-tempest attacks
 
Emission Security
Emission SecurityEmission Security
Emission Security
 
Lightning threat and protection from lightning information and product by jm...
Lightning threat and  protection from lightning information and product by jm...Lightning threat and  protection from lightning information and product by jm...
Lightning threat and protection from lightning information and product by jm...
 
EWER: “ELECTROMAGNETIC WAVE EXPOSURE REDUCTION” SERVICE FOR SENSITIVE USERS W...
EWER: “ELECTROMAGNETIC WAVE EXPOSURE REDUCTION” SERVICE FOR SENSITIVE USERS W...EWER: “ELECTROMAGNETIC WAVE EXPOSURE REDUCTION” SERVICE FOR SENSITIVE USERS W...
EWER: “ELECTROMAGNETIC WAVE EXPOSURE REDUCTION” SERVICE FOR SENSITIVE USERS W...
 
ITU-T Study Group 5 Introduction
ITU-T Study Group 5 IntroductionITU-T Study Group 5 Introduction
ITU-T Study Group 5 Introduction
 
Smart grid networks and security architecture: Threat analysis, threat scenar...
Smart grid networks and security architecture: Threat analysis, threat scenar...Smart grid networks and security architecture: Threat analysis, threat scenar...
Smart grid networks and security architecture: Threat analysis, threat scenar...
 
An automatic system for detecting voltage leaks in houses to save people's l...
An automatic system for detecting voltage leaks in houses to  save people's l...An automatic system for detecting voltage leaks in houses to  save people's l...
An automatic system for detecting voltage leaks in houses to save people's l...
 
Design for electrical safety
Design for electrical safetyDesign for electrical safety
Design for electrical safety
 
TAKO SINCE 1979 STOP RM250 MILLION LOSSES WITH MS IEC 62305 LIGHTNING PROTECT...
TAKO SINCE 1979 STOP RM250 MILLION LOSSES WITH MS IEC 62305 LIGHTNING PROTECT...TAKO SINCE 1979 STOP RM250 MILLION LOSSES WITH MS IEC 62305 LIGHTNING PROTECT...
TAKO SINCE 1979 STOP RM250 MILLION LOSSES WITH MS IEC 62305 LIGHTNING PROTECT...
 
G41044251
G41044251G41044251
G41044251
 

Plus de Leonardo ENERGY

Plus de Leonardo ENERGY (20)

A new generation of instruments and tools to monitor buildings performance
A new generation of instruments and tools to monitor buildings performanceA new generation of instruments and tools to monitor buildings performance
A new generation of instruments and tools to monitor buildings performance
 
Addressing the Energy Efficiency First Principle in a National Energy and Cli...
Addressing the Energy Efficiency First Principle in a National Energy and Cli...Addressing the Energy Efficiency First Principle in a National Energy and Cli...
Addressing the Energy Efficiency First Principle in a National Energy and Cli...
 
Auctions for energy efficiency and the experience of renewables
 Auctions for energy efficiency and the experience of renewables Auctions for energy efficiency and the experience of renewables
Auctions for energy efficiency and the experience of renewables
 
Energy efficiency first – retrofitting the building stock final
Energy efficiency first – retrofitting the building stock finalEnergy efficiency first – retrofitting the building stock final
Energy efficiency first – retrofitting the building stock final
 
How auction design affects the financing of renewable energy projects
How auction design affects the financing of renewable energy projects How auction design affects the financing of renewable energy projects
How auction design affects the financing of renewable energy projects
 
Energy Efficiency Funds in Europe (updated)
Energy Efficiency Funds in Europe (updated)Energy Efficiency Funds in Europe (updated)
Energy Efficiency Funds in Europe (updated)
 
Energy Efficiency Funds in Europe
Energy Efficiency Funds in EuropeEnergy Efficiency Funds in Europe
Energy Efficiency Funds in Europe
 
Five actions fit for 55: streamlining energy savings calculations
Five actions fit for 55: streamlining energy savings calculationsFive actions fit for 55: streamlining energy savings calculations
Five actions fit for 55: streamlining energy savings calculations
 
Recent energy efficiency trends in the EU
Recent energy efficiency trends in the EURecent energy efficiency trends in the EU
Recent energy efficiency trends in the EU
 
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...Energy and mobility poverty: Will the Social Climate Fund be enough to delive...
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...
 
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?
 
Energy efficiency, structural change and energy savings in the manufacturing ...
Energy efficiency, structural change and energy savings in the manufacturing ...Energy efficiency, structural change and energy savings in the manufacturing ...
Energy efficiency, structural change and energy savings in the manufacturing ...
 
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)
 
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...
 
Modelling and optimisation of electric motors with hairpin windings
Modelling and optimisation of electric motors with hairpin windingsModelling and optimisation of electric motors with hairpin windings
Modelling and optimisation of electric motors with hairpin windings
 
Casting zero porosity rotors
Casting zero porosity rotorsCasting zero porosity rotors
Casting zero porosity rotors
 
Direct coil cooling through hollow wire
Direct coil cooling through hollow wireDirect coil cooling through hollow wire
Direct coil cooling through hollow wire
 
Motor renovation - Potential savings and views from various EU Member States
Motor renovation - Potential savings and views from various EU Member StatesMotor renovation - Potential savings and views from various EU Member States
Motor renovation - Potential savings and views from various EU Member States
 
The need for an updated European Motor Study - key findings from the 2021 US...
The need for  an updated European Motor Study - key findings from the 2021 US...The need for  an updated European Motor Study - key findings from the 2021 US...
The need for an updated European Motor Study - key findings from the 2021 US...
 
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...
 

Dernier

Mckinsey foundation level Handbook for Viewing
Mckinsey foundation level Handbook for ViewingMckinsey foundation level Handbook for Viewing
Mckinsey foundation level Handbook for Viewing
Nauman Safdar
 
!~+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUD...
!~+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUD...!~+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUD...
!~+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUD...
DUBAI (+971)581248768 BUY ABORTION PILLS IN ABU dhabi...Qatar
 

Dernier (20)

Call 7737669865 Vadodara Call Girls Service at your Door Step Available All Time
Call 7737669865 Vadodara Call Girls Service at your Door Step Available All TimeCall 7737669865 Vadodara Call Girls Service at your Door Step Available All Time
Call 7737669865 Vadodara Call Girls Service at your Door Step Available All Time
 
Falcon Invoice Discounting: Aviate Your Cash Flow Challenges
Falcon Invoice Discounting: Aviate Your Cash Flow ChallengesFalcon Invoice Discounting: Aviate Your Cash Flow Challenges
Falcon Invoice Discounting: Aviate Your Cash Flow Challenges
 
Marel Q1 2024 Investor Presentation from May 8, 2024
Marel Q1 2024 Investor Presentation from May 8, 2024Marel Q1 2024 Investor Presentation from May 8, 2024
Marel Q1 2024 Investor Presentation from May 8, 2024
 
Mckinsey foundation level Handbook for Viewing
Mckinsey foundation level Handbook for ViewingMckinsey foundation level Handbook for Viewing
Mckinsey foundation level Handbook for Viewing
 
Falcon Invoice Discounting: Unlock Your Business Potential
Falcon Invoice Discounting: Unlock Your Business PotentialFalcon Invoice Discounting: Unlock Your Business Potential
Falcon Invoice Discounting: Unlock Your Business Potential
 
Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...
Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...
Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...
 
PHX May 2024 Corporate Presentation Final
PHX May 2024 Corporate Presentation FinalPHX May 2024 Corporate Presentation Final
PHX May 2024 Corporate Presentation Final
 
Power point presentation on enterprise performance management
Power point presentation on enterprise performance managementPower point presentation on enterprise performance management
Power point presentation on enterprise performance management
 
Lucknow Housewife Escorts by Sexy Bhabhi Service 8250092165
Lucknow Housewife Escorts  by Sexy Bhabhi Service 8250092165Lucknow Housewife Escorts  by Sexy Bhabhi Service 8250092165
Lucknow Housewife Escorts by Sexy Bhabhi Service 8250092165
 
Phases of Negotiation .pptx
 Phases of Negotiation .pptx Phases of Negotiation .pptx
Phases of Negotiation .pptx
 
Buy gmail accounts.pdf buy Old Gmail Accounts
Buy gmail accounts.pdf buy Old Gmail AccountsBuy gmail accounts.pdf buy Old Gmail Accounts
Buy gmail accounts.pdf buy Old Gmail Accounts
 
Falcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business GrowthFalcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business Growth
 
Famous Olympic Siblings from the 21st Century
Famous Olympic Siblings from the 21st CenturyFamous Olympic Siblings from the 21st Century
Famous Olympic Siblings from the 21st Century
 
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60% in 6 Months
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60%  in 6 MonthsSEO Case Study: How I Increased SEO Traffic & Ranking by 50-60%  in 6 Months
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60% in 6 Months
 
Lundin Gold - Q1 2024 Conference Call Presentation (Revised)
Lundin Gold - Q1 2024 Conference Call Presentation (Revised)Lundin Gold - Q1 2024 Conference Call Presentation (Revised)
Lundin Gold - Q1 2024 Conference Call Presentation (Revised)
 
!~+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUD...
!~+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUD...!~+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUD...
!~+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUD...
 
TVB_The Vietnam Believer Newsletter_May 6th, 2024_ENVol. 006.pdf
TVB_The Vietnam Believer Newsletter_May 6th, 2024_ENVol. 006.pdfTVB_The Vietnam Believer Newsletter_May 6th, 2024_ENVol. 006.pdf
TVB_The Vietnam Believer Newsletter_May 6th, 2024_ENVol. 006.pdf
 
Rice Manufacturers in India | Shree Krishna Exports
Rice Manufacturers in India | Shree Krishna ExportsRice Manufacturers in India | Shree Krishna Exports
Rice Manufacturers in India | Shree Krishna Exports
 
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDINGParadip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
 
How to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League CityHow to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League City
 

Integrated Earthing Systems

  • 1. European Copper Institute WHITE PAPER INTEGRATED EARTHING SYSTEMS (EARTHING GRID) Rob Kersten & Frans van Pelt July 2011 ECI Publication No Cu0102 Available from www.leonardo-energy.org
  • 2. Publication No Cu0102 Issue Date: July 6, 2011 Page i Document Issue Control Sheet Document Title: Integrated Earthing Systems (Earthing Grid) Publication No: Cu0102 Issue: 01 Release: July 6, 2011 Author(s): Rob Kersten and Frans van Pelt Reviewer(s): Stefan Fassbinder, Bruno De Wachter, Hans De Keulenaer Document History Issue Date Purpose 1 July 6, 2011 Initial publication 2 3 Disclaimer While this publication has been prepared with care, European Copper Institute and other contributors provide no warranty with regards to the content and shall not be liable for any direct, incidental or consequential damages that may result from the use of the information or the data contained. Copyright© European Copper Institute. Reproduction is authorised providing the material is unabridged and the source is acknowledged.
  • 3. Publication No Cu0102 Issue Date: July 6, 2011 Page ii CONTENTS Executive Summary ................................................................................................................................................1 What is an Integrated Earthing System? ................................................................................................................1 A short historical overview.....................................................................................................................................2 Growing in importance...........................................................................................................................................2 The state-of-the-art Integrated Earthing System ...................................................................................................3 Applicable standards ..............................................................................................................................................4 IEC 61000 standard series ........................................................................................................................4 The Technical Report IEC TR 61000-5-2 ...................................................................................................4 The new standard for lightning protection IEC 62305 .............................................................................5 Non European Standards .........................................................................................................................6 Copper versus (galvanized) steel ............................................................................................................................7 Upgrade existing installations or not?....................................................................................................................7 Conclusions.............................................................................................................................................................8
  • 4. Publication No Cu0102 Issue Date: July 6, 2011 Page 1 EXECUTIVE SUMMARY Businesses and governments will continue to focus on efficiency and quality improvements while at the same time remaining under pressure to reduce costs. Hence, automation developed to a very high level and the Internet has become a strategic requirement. The consequent business vulnerability must obviously be recognized and risk reduced. High availability level to the IT infrastructure is a primary requirement. The necessity for constant availability of electrical power is well and broadly understood. The electrical contractor supplies the protective earthing facilities, another specialized company provides lightning protection, and the IT equipment manufacturer requires a functional earthing system. In the past, this resulted in the installation of three independent earthing systems. This multiple approach has proved to be the cause of certain types of operational problems and damage. The introduction of faster technologies and communication networks increased the number of problems; an alternative was urgently needed. The Integrated Earthing System discussed in this paper is the result of extensive work by knowledge institutes and suppliers. This technology is meanwhile embedded in the related safety, lightning protection, and EMC standards, and its reliability has been field proven in many installations. The following pages explain the technical principles of this system and the abbreviations used. The Integrated Earthing System (Earthing Grid) is the current state of the art solution and an indispensable part of critical IT operations. WHAT IS AN INTEGRATED EARTHING SYSTEM? An Integrated Earthing System (Earthing Grid) aims to protect digital/electronic equipment against the effects of severe electric and magnetic disturbances (such as lightning, short-circuits, et cetera) and enables this equipment to function properly, both on the short- and long-term. An earthing grid normally has three different primary functions: 1. Preventing electrocution or fire caused by short-circuits or insulation defects 2. Avoiding human injuries and fatalities in case of a direct or nearby lightning strike 3. Protecting electronic equipment against the effects of electromagnetic disturbances so that it can continue to function properly on both the short- and long-term Historically, those three protection functions were developed separately, under the names ‘protective earthing’, ‘lightning protection’, and ‘functional earthing’. In the course of time it became clear that these three different earthing systems could influence each other up to the point of hampering each other’s proper and efficient functioning. As a result, the only way to ensure that all protective functions are well covered, is to design a single integrated earthing system that deals with all three issues simultaneously. Designing such a network is a complex task, to be executed by a specialized engineer.
  • 5. Publication No Cu0102 Issue Date: July 6, 2011 Page 2 A SHORT HISTORICAL OVERVIEW Lightning protection was invented in 1749 by Benjamin Franklin. It resulted in the establishment of a lightning protection industry, devoted to the fire protection of buildings. The American National Fire Protection Association (NFPA) was founded in 1896. Their first code — NFPA 1 — stipulated how to achieve a reasonable level of fire safety and property protection in buildings. The electrical power industry had matured considerably by the end of the nineteenth century. The first practical electrical power distribution network was created in 1882. Protective earthing connections were developed to reduce the risks of electrocution and fire. The NFPA published their first National Electrical Code (NEC) in 1897. Protective earthing and lightning protection were initially developed as totally separated systems, and it took a while before their interconnection — initially only underground — was accepted as a better solution. With the advent of electronic equipment and computer systems in the 1960s, awareness grew regarding the fact that electromagnetic signals can disturb each other. This gave birth to the concept of electromagnetic compatibility, or in short: EMC. Initially, EMC solutions were developed separately from the lightning and protective-earthing systems. They were part of the so-called clean or functional earthing system, dedicated to protecting electronic devices. Around 1980, extensive studies revealed that the causes of various shortcomings, which were thought to be inherent to the earthing systems themselves, were actually resulting from the separation of the three systems and the lack of compatibility between them. Out of this understanding emerged the concept of an integrated earthing system. Integrated earthing concepts were introduced in the IEC and IEEE standards by the end of the 1990s, and European EMC directives were approved that required incorporating those standards (or equivalent alternative methods). This provoked a short-lived hype of EMC awareness. Subsequently however, this interest began to fade, and today the implementation of the prevailing standards and regulations is often still lacking. There is still considerable confusion about earthing systems and their characteristics, even among specialists. Systems based on outdated technology are still operational, and engineers who have not adopted the latest insights are still influential. GROWING IN IMPORTANCE Integrated earthing for tertiary sector and industrial buildings has been growing in significance over the past decades due to the rapid development of IT systems. As IT systems take on increasingly crucial functions, their reliability and that of their energy supply becomes considerably more critical. Paradoxically, IT devices are at the same time becoming increasingly vulnerable to electromagnetic disturbances. This vulnerability stems from the fact that signal bandwidths are being increased and signal amplitudes reduced, with the aim of processing larger amount of data within shorter time periods. Only a well-designed integrated earthing network can give those IT systems the immunity they require. IT systems are used more and more in places where reliability is absolutely imperative. Think for instance of public transport facilities such as digital security systems and airline/railway traffic management. Other examples include data centres and corporate computer systems. For these kinds of systems, failure is not an option. The integrity and reliable functioning of such IT systems has grown in importance to the level of human safety. As a result, functional earthing has become just as ‘vital’ as traditional protective earthing and lightning protection.
  • 6. Publication No Cu0102 Issue Date: July 6, 2011 Page 3 THE STATE-OF-THE-ART INTEGRATED EARTHING SYSTEM The integrated earthing system provides and combines various different functions, which have historically been tackled in different domains: 1) Protective earthing (humans): a. Conducting fault currents back to the power source without introducing the risk of local overheating that might lead to fire. b. Protection against indirect contact. Indirect contact occurs when a person touches a conductive (metal) part which is normally not live, but which has become live due to a fault in the insulation. Protection against indirect contact also requires the use of a Residual Current Device (RCD) and equipotential bonding. Equipotential bonding is the connection with each other of all conductive parts of the electrical system and conductive parts extraneous to the electrical system, and subsequently connecting this bonding network to the protective earthing network. Extraneous conductive parts include for instance metal pipes, metal windows, and iron components of reinforced concrete. Equipotential bonding avoids the situation where two metal parts can hold a different electrical potential, entailing the risk on electrocution if they were to be touched simultaneously. 2) Lightning protection (humans and equipment): a. Conduct lightning currents to the earth without introducing any risk of electrocution or overheating. b. Prevent direct fires, flashovers. or explosions caused by a lightning strike. c. Apply the necessary interconnections and surge protection devices (SPD) at the Lightning Protection Zones (LPZ) transition points to reduce the extreme voltage and current transients down to the defined levels for the different zones. 3) Functional earthing (equipment): Ensuring electromagnetic compatibility (EMC). All electric and electronic devices send out electromagnetic signals (waves). Electromagnetic compatibility is ensured when those signals do not disturb the proper functioning of other electronic devices. Although the requirements for these different aspects are often specified separately, the implementation requires an integrated systems approach, as the solution for one aspect might influence the proper and efficient functioning of another solution. For example, the danger of electrocution by simultaneously touching different earthing networks was initially solved by connecting a high frequency choke between those networks. It was subsequently discovered however, that this degrades the lightning protection function. Integrated earthing means that all of the different earthing functions are integrated into a single system: the so-called ‘earthing grid’. This earthing grid provides a single metal matrix for the entire facility. It should be noted that the focus is wider than just a single building within a complex; the earthing grid should cover all buildings on a particular site or of a facility. If an integrated approach is not followed, the various individual protective solutions risk a higher investment cost without ensuring the protection they are designed to provide. In addition, failure of protection can lead to significant claims and legal complications. European directives and local regulations have been tightened considerably in recent years, both in terms of technical requirements and liability. Nonetheless, knowledge
  • 7. Publication No Cu0102 Issue Date: July 6, 2011 Page 4 regarding these new regulations is often lacking. For example, it is often not understood that the owner of a multi-vendor technical infrastructure is responsible for overall CE compliance. This implies that all equipment design and the corresponding documentation must conform to all prevailing regulations, including earthing. One of the barriers for the fast and widespread implementation of the latest earthing standards is that historically, the three earthing disciplines (Protective Earthing, Functional Earthing, and Lightning Protection) were supervised by different parties (respectively electrical contractors, equipment manufacturers, and lightning protection contractors). It will take time for those parties to combine their insights and develop a common understanding. It is therefore recommended that an experienced external consultancy be involved to supervise both design and installation, in order to address all aspects of the inherent complexity of this subject. Strategically important for your organization is that maintenance, modifications, and extensions are supervised by the same office. APPLICABLE STANDARDS IEC 61000 STANDARD SERIES The applicable harmonized standards are referenced in the Official Journal of the European Union, thus not in the European directives themselves. Compliance with these standards should raise a presumption of conformity with the relevant essential requirements, although other means of demonstrating such conformity are permitted. Compliance with these directives is enforced by law in all Member Countries; they are absolutely not voluntary. The applicable standards define different EMC environments, and provide clear emission and susceptibility requirements. THE TECHNICAL REPORT IEC TR 61000-5-2 The Technical Report IEC TR 61000-5-2 describes a workmanship code for good EMC. It explains in detail all kinds of installation and mitigation guidelines to obtain Electro Magnetic Compatibility between various devices installed in the same building. The Integrated Earthing System is an important mechanism to avoid the build-up of significant voltage differences between various points in the earthing networks. The following illustration shows a typical Integrated Earthing System with a three dimensional meshed earthing system for the entire building, including finer meshed systems for areas with more sensitive equipment. Source: Figure 7 from IEC TR 61000-5-2 (1997) The Technical Report also provides recommendations on how to connect equipment to this earthing system, but it does not demand changes to the internal wiring of the equipment.
  • 8. Publication No Cu0102 Issue Date: July 6, 2011 Page 5 Notes: I. Additional earthing connections do not substitute for the power cable protective earthing conductor (PE). The latter must never be omitted, for safety and EMC reasons. PE and Neutral conductors should not be combined inside the power cabling network. II. Likewise, for EMC reasons, the return conductor for electrical signals must never be omitted. This return conductor must always be included in the corresponding signal cable and not be identical to the return conductor of the power supply. III. Figure 8 in TR 61000-5-2 (not shown here) provides a good impression of the Integrated Earthing System for an industrial plant. IV. Special note for the (Process) Industry: There is no such thing as intrinsically safe earthing. All required earthing points must be connected to a common earthing grid. This is to ascertain that each earthing point is actually at the same potential to prevent arcing and the consequent ignition of an explosive environment. Building steel is infamous as an unsuitable earthing point due to corrosion, et cetera. THE NEW STANDARD FOR LIGHTNING PROTECTION IEC 62305 In 2006, the new IEC 62305 standard for lightning protection of electrical and electronic systems within buildings was published. Since then, protective earthing, functional earthing, and lightning protection have all been integrated into a single protection concept. The IEC 61000-5-2 technical report published earlier explained many general lightning protection aspects. More specific details covered by IEC 62305 can be found in the following documents:  IEC 62305-1: General principles  IEC 62305-2: Risk management  IEC 62305-3: Physical damage to structures and life hazard  IEC 62305-4: Electrical and electronic systems within structures The following illustration shows a typical example of a resulting integrated earthing system (grid): Source: Figure 5 from IEC 62305-4 (2006)
  • 9. Publication No Cu0102 Issue Date: July 6, 2011 Page 6 IEC 62305-4 also requires that engineers who are implementing the protection system have mastered all three disciplines concerned: protective earthing engineering, lightning protection engineering, and EMC engineering. Lightning Protection Zones The lightning protection zone concept shown below is a layered form of protection, fully in line with the requirements for Surge Protection Devices (SPDs) for the respective Lightning Protection Zone (LPZ). This mitigates interference from an upstream zone to the design level for the respective lower zone, as indicated in the next figure. Note that the cable armour should be earthed at the zone transition point. Source: Figure 1 from IEC 62305-4 (2006) NON EUROPEAN STANDARDS Other standards, such as those of the IEEE, may be the (legally) preferred standards in other countries (i.e. the Middle East and other locations outside the USA). A good guide to this situation is the IEEE Emerald book (IEEE Std 1100 – 2005) titled Powering and Grounding Electronic Equipment. Section 4.8.5.3 discusses the Integrated Earthing System using different terminology: Modern signal reference structures [SRS]. An SRS is the external installed network of conductors used to interconnect the metal frames, enclosures, and logic or signal level power supply common terminals of the subject electrical and electronic equipment to one another. This network may be a recommendation from, or an actual part of, the equipment’s OEM installation package. Most often it may be part of an aftermarket, field-installed wiring effort. The SRS is also an integral part of any SPD [Surge Protection Device] network system that is used on either ac or dc power, or signal (including telecommunications) circuits connected to the electronic equipment that is also attached to the SRS. The SRS is also not intended to be dielectrically or galvanically insulated or isolated from the building electrical system’s EGC [Equipment Ground Conductor] system that is part of the fault/personnel protection grounding subsystem. In figure 4-66 (below), this IEEE standard compares the superior low impedance of a SRS (thus also of the Integrated Earthing System) with an ordinary earthing conductor (green coloured in the USA).
  • 10. Publication No Cu0102 Issue Date: July 6, 2011 Page 7 Source: Figure 4-66 from IEEE Std 1100 (2005) COPPER VERSUS (GALVANIZED) STEEL The Integrated Earthing System should preferably be constructed from conventional copper-based materials to obtain a low and long lasting impedance, also for very fast phenomena such as lightning or high frequency signals. Copper assures that the potential differences are kept to a minimum and prevents corrosion problems. As a result, in the large majority of the cases, the most reliable and durable solution will be the all copper Integrated Earthing System. The commonly used (galvanized) steel has the disadvantage of an increased impedance at higher frequencies, caused by the higher permeability (magnetic property) of steel. Moreover, protective measures against electro-corrosion are required when connecting different metal materials with each other. Flat conductors are to be preferred to round conductors, as they have a lower impedance at higher frequencies. A minimum thickness is required for ensuring lightning protection and for construction reasons. UPGRADE EXISTING INSTALLATIONS OR NOT? Should existing installations that were not conceived according to the latest standards be upgraded immediately? They should be upgraded, but caution is advisable. Existing installations are likely to be based on outdated EMC insight. They should be carefully inspected by specialists understanding both old and new concepts before any changes are considered. Otherwise, there is a risk of creating involuntary earthing loops in the signal path, which is to be avoided in every case!
  • 11. Publication No Cu0102 Issue Date: July 6, 2011 Page 8 CONCLUSIONS 1. Although historically developed as separate systems, protective earthing, functional earthing, and lightning protection should be provided by a single integrated earthing grid. If not, compatibility problems between the three protection networks can occur. 2. A well-conceived earthing grid is of growing importance, as electronic devices become increasingly sensitive to disturbances. Moreover, IT systems are increasingly used for critical operations for which failure is not an option. 3. The integrated earthing system concept is explained in international standards (i.e. IEC 61000 series, the technical report IEC TR 61000-5-2, and the IEC 62305 series, et cetera). The Official Journal of the European Union documents their applicable harmonized standards. Compliance with the standards (or an equivalent method of demonstrating conformity) is compulsory. 4. Knowledge of the prevailing standards and regulations is often poor, even among engineers. There is still a great deal of confusion about earthing systems and their characteristics. As a result, the implementation of the appropriate standards is often lacking. Company standards (suppliers, contractors, end-users) may still be based on outdated concepts, and the engineers involved (electrical engineers, process engineers, instrument engineers, lightning engineers, maintenance engineers, et cetera) may still be unaware of the latest insights. It is therefore recommended that an external consultant experienced in the matter be contacted and utilized. 5. The Integrated Earthing System should be constructed from conventional copper-based materials to obtain the lowest resistance and to avoid corrosion problems. 6. Upgrading existing installations should be undertaken with care. Specialists that understand both old and new earthing concepts should first meticulously inspect them.