XVII International Symposium on High Voltage Engineering, Hannover, Germany, August 22-26, 2011




    CONDITION MONITORING OF POWER TRANSFORMERS – WHAT INFORMATION
            CAN WE GET FROM RETURN VOLTAGE MEASUREMENTS
                                                    Rainer Patsch
                                       University of Siegen, Germany
                        Institute of Materials & Diagnostics in Electrical Engineering
                                         rainer.patsch@uni-siegen.de

Abstract: Return Voltage Measurements are an efficient tool to measure the dielectric properties of an
insulating system and thus to characterize the degradation of cellulose-oil insulations. They are widely
used for the diagnosis of paper oil insulated power cables. As a consequence of misinterpretations of the
measurement results in the past, the use of Return Voltage Measurements for the diagnosis of power trans-
formers has been abandoned. Nevertheless – performing a physically meaningful interpretation of the
measured curves – the application on power transformers is also very promising, especially because the
insulation system in a power transformer is close to the conditions described by the Maxwell model for two
dielectrics in series. For the characterization of the degree of ageing and consequently the reliability of the
insulation system a new diagnostic parameter, the r - factor, is presented. The results of measurements of
differently aged power transformers show a correct ranking and also a correlation between the oil humidity
and the r - factor.

1    INTRODUCTION                                                                 ing
                                                                               ind                               Barriers
                                                                           W
For the diagnosis of insulating systems, time de-                       er
pendent polarization/depolarization processes can
                                                                    t
                                                                  Ou


                                                                                        g
be used [1, 2]. In insulating systems consisting of                                  din
                                                                                   in     Oil Ducts
more than one component, boundary polarization                                    W
                                                                           er

can be considered as the dominant polarization
                                                                         Inn



process. This holds especially for the cellulose-oil
insulations that are used in power transformers
with pressboard-oil insulation.                                            Spacers

                                                                                           Barriers
2    EQUIVALENT CIRCUIT OF A TRANSFOR-
     MER INSULATION
                                                                 Fig. 1: Simplified model for a power transformer insula-
Fig. 1 shows a simplified model of a power trans-                tion with solid barriers and liquid oil
former insulation and the basic distribution of oil
and cellulose [3]. Fig. 2 shows a corresponding
electrical equivalent circuit. The equivalent circuit
basically consists of a series connection of two
dielectric materials: Firstly the cellulose insula-
tion of the windings and the pressboard barriers,
secondly the oil ducts filled by an insulating oil.
The main elements are RB, CB, RO and CO. The
elements RS, CS, and RD are of less importance,
where the latter one represents conduction proc-
esses in the oil bypassing the barriers. In most
cases, for dielectric phenomena the influence of RD
is negligible. The same holds for the influence of
                                                                 Fig. 2: Equivalent circuit of a pressboard-oil insulated
RS and CS in comparison to the phenomenon of
                                                                 power transformer insulation; the RC series elements in
boundary polarization. The RC series elements                    the middle are used for formal fits
in parallel to CB and CS characterize additional
polarization processes that are of minor impor-                  importance. Not depending on the actual geomet-
tance for the basic behaviour that is determined by              ric dimensions, the dielectric behaviour is fully
the Maxwell circuit formed by RB, CB, RO and CO.                 determined by the specific conductivities бi and the
                                                                 relative permittivities εri of the two insulating mate-
The fundamental behaviour determined by the two                  rials cellulose and oil. The characteristic voltage
dielectrics cellulose and oil is characterized in the            division between the high and low voltage windings
equivalent circuit by the numerical values of these              and the grounded core and tank results from the
four elements. Interestingly in the Maxwell circuit,             continuity equation of the current density and
the absolute values of these elements are not of                 the laws for the electric field at boundaries.
XVII International Symposium on High Voltage Engineering, Hannover, Germany, August 22-26, 2011


2.1    Dielectric time constants                                 The cellulose cannot be analyzed directly because
                                                                 it is not possible to take a piece of the paper or
For an insulating material the dielectric time con-              pressboard out of the transformer. Hence the con-
stant τ is proportional to the relative permittivity             dition of the cellulose can be determined only
εr and inversely proportional to the specific con-               indirectly from the analysis of the oil by means of
ductivity б. Hence the time constant τ is sensitive             calculations on the basis of the different solubilities
                                                                 of ageing and degradation products under thermo-
to changes of б and εr, whereby for cellulose mate-
                                                                 dynamic equilibrium conditions, or by the use of
rials the specific conductivity б is very sensitive
                                                                 the corresponding dielectric time constants of
on the contents of water or other degradation
                                                                 cellulose and oil, a method that is a unique possi-
products. For a parallel circuit of R and C the di-
                                                                 bility of the Return Voltage Method.
electric time constant is given by τ = RC or - intro-
ducing the characteristic material parameters εr
and б to get rid of the actual geometric dimensions              4    RETURN VOLTAGE MEASUREMENTS
- by τ = ε0 εr / б. Hence the actual time constants
                                                                 Water in the cellulose leads to an increase of the
τB and τO of the two insulating materials cellulose              concentration of mobile carriers, thus to an in-
and oil do not depend on the geometric dimen-                    crease of the specific conductivity бB and hence
sions of the measured test object and conse-
                                                                 a decrease of the dielectric time constant τB. The
quently a diagnostic parameter derived from the
two time constants is meaningful for all transformer             same holds to a lower extent for a decrease of τO
geometries and sizes. In contrast to other diagnos-              due to water and degradation products in the oil. If
tic methods no fits according to the geometry of                 the transformer insulation system behaves like a
the tested object are needed.                                    Maxwell circuit, Return Voltage measurements are
                                                                 a good method to monitor degradation processes
3     AGEING OF TRANSFORMER INSULATION                           in transformer insulations, because the dielectric
      SYSTEMS                                                    time constants of the two dielectrics τB = RBCB
                                                                 and τO= ROCO can be calculated numerically from
In power transformers the ageing of the insulating               the shape of the Return Voltage curve.
system is on one hand due to ageing and degra-
dation processes in the cellulose and on the
other hand due to ageing and degradation of the
oil. Especially the degradation of the cellulose
depends on the temperature of the insulation and
any partial discharge activities. The degradation
or depolymerisation of the cellulose generates also
water molecules that will accelerate this degrada-
tion process. In addition water that comes from the
outside via the surrounding oil may also intensify
the degradation process. So water is on one hand                 Fig. 3: Equivalent circuit of a paper-oil dielectric with
an indicator of degradation and on the other                     τB = τ2 = R2C2 and τO = τ1 = R1C1 with τB > τO and the
hand also a reason for accelerated degradation.                  basic measuring circuit

3.1    Monitoring and maintenance of                             Fig. 3 shows the basic measuring circuit for a Re-
       transformers                                              turn Voltage measurement with τ2 = τB and τ1 = τO.
                                                                 Under the assumption that the measuring resistor
The oil of a transformer may be analyzed during                  Rm is sufficiently higher than the resistors R2 and
service especially by taking a sample and measur-                R1 in the equivalent circuit, the Return Voltage
ing the contents of water or other degradation                   curve Ur(t) can be calculated analytically:
products, mainly dissolved gases by means of
DGA. The oil can be upgraded by drying proc-
esses either continuously or in a separate offline                                  ⎛ −t       −
                                                                                                 t
                                                                                                           ⎞
process or the oil can be exchanged. By this also                    U r (t ) = U s ⎜ e τ 2 − e τ1         ⎟
the water contents of the cellulose can be de-                                      ⎜                      ⎟        (1)
creased, but only by diffusion processes that lead                                  ⎝                      ⎠
to a new equilibrium between the water contents
in the cellulose and the oil. Generally the con-                 with τ 2 = R2 C 2 and τ 1 = R1C1 . Us depends also
centration of water molecules in the cellulose –
                                                                 on the geometric dimensions of the insulating sys-
and also the total amount of water – is much
higher than in the oil. Hence an attempt to dry the              tem, but the time constants τ2 and τ1 are not influ-
cellulose by drying the oil is a very slow process.              enced by its value.
XVII International Symposium on High Voltage Engineering, Hannover, Germany, August 22-26, 2011


For Return Voltage measurements a DC voltage                       measured curve, thus the measured curve is
Up (1 or 2 kV) is applied for a certain time (e.g.                 nearly identical to the Maxwell-type curve given in
tp = 30 min), then the transformer is short circuited              eqn. (1).
for td = 2 s. After opening the short circuit, a volt-
age will build up across the terminals of the trans-
former. The equivalent circuit of a transformer in-
sulation - i.e. its decisive elements RB, CB, RO and
CO - corresponds very closely to a Maxwell equiva-
lent circuit of a series connection of two
RC parallel elements. The evaluation of the shape
of the Return Voltage curve Ur(t) allows the calcu-
lation of the dielectric time constants τ2(t) and τ1(t)
of the two insulating materials separately [4]. The
voltage Us across the two capacitors after a poling
time tp and a short circuit time td is not only influ-
enced by the time constants τ1 and τ2, but also by
the geometric dimensions of the measured system
[7].

A curve according to eqn. (1) is exactly defined by                Fig. 5: Logarithms of the time constants lg τ2(t) and
just three data points, i.e. the point of origin, the              lg τ1(t) calculated from the Return Voltage curve of a
peak value Um(tm) and one additional point U(t)                    new 31.5 MVA transformer over t/tm
of the curve. Hence the corresponding time con-
                                                                   Fig. 6 shows the corresponding data for a seri-
stants τ1(t) and τ2(t) of the oil and the cellulose                ously aged 100 MVA transformer that had been
respectively can be calculated point by point from                 taken out of service due to a fault. The deviation
the experimentally determined curve. For the char-                 from the Maxwell-type behaviour can be explained
acterisation of the measured Return Voltage curve                  by additional polarization or conduction proc-
of a transformer it is interesting in how far the cal-             esses with time constants in the range of up to a
culated time constants τ1 and τ2 are influenced by                 few 10 seconds. Those effects can be described
the selection of the point U(t). For a Maxwell curve               by additional RC series elements in parallel to the
no such dependence exists. (All normalized curves                  Maxwell circuit. Numerical simulations with a com-
pass per definition through (1;1), hence the use of                puter program on the basis of this assumption
data points around the maximum for the calcula-                    show a similar behaviour [7].
tion of the dielectric time constants is not very
meaningful.)
         1

        0.9
                                                              τ2
                                                        λ =
        0.8                                                   τ1
        0.7

        0.6
    m
 U/U




        0.5

        0.4
                                               ⎛ λ ⎞
        0.3                            tm = τ1 ⎜
                                               ⎜      ⎟ ln λ
                                                      ⎟
                                               ⎝ λ −1 ⎠
        0.2

        0.1

         0
          0   0.5      1       1.5      2        2 .5          3
                               t/tm

Fig. 4 Normalized Return Voltage curve and calculation             Fig. 6: Logarithms of the time constants lg τ2(t) and
of the dielectric time constants τ2(t) and τ1(t) from the          lg τ1(t) calculated from the Return Voltage curve of a
points (0;0) and (1;1) and different points (U;t) of the           seriously aged 100 MVA transformer over t/tm
curve.
                                                                   The effects are be caused by chemical changes
5        MEASUREMENT RESULTS                                       in the insulation components due to ageing and
                                                                   degradation processes. These changes do not
Fig. 5 shows the dielectric time constants τ2(t) of                only lead to an increased conductivity, but also
cellulose and τ1(t) of oil calculated from the meas-               generate polar molecules within the insulation. The
ured Return Voltage curve of a non aged 31.5                       depolarisation of these components leads to a
MVA power transformer. The selection of the                        steeper incline of the Return Voltage curve and to
point U(t) does not significantly influence the actual             higher ratios τ2/τ1 as indicated in Fig. 4. With in-
values of the dielectric time constants of the                     creasing time of the measurement the influence of
XVII International Symposium on High Voltage Engineering, Hannover, Germany, August 22-26, 2011


these processes decreases and the shape of the
measured Return Voltage curve approachs the
Maxwell-type behaviour. Nevertheless compared
to the data from a new transformer (Fig. 5) the
values of the time constants are lower.

For diagnostic purposes the data from t > tm are a
measure for the DC-conductivities of the dielec-
trics, while the data from t < tm are more influenced
by additional, predominantly polar ageing and deg-
radation products. Measurements of transformers
at different temperatures in the range between 15
and 55 °C show for t > tm a temperature depend-
ence of the dielectric time constants as expected
from thermally activated conduction processes
[6, 7], a proof for the validity of the concept of the
                                                                 Fig. 8: Logarithms of the time constants lg τ2(t) and
interpretation of Return Voltage measurements on
power transformers on the basis of the Maxwell-                  lg τ1(t) calculated from Return Voltage curves of an
                                                                 aged 250 MVA transformer after oil drying
model.

5.1   Influence of oil drying                                    The corresponding value of τ2 did not change sig-
                                                                 nificantly. Nevertheless the removal of ageing
A good way to check the reliability of the diagnos-              and degradation products from the oil has a
tic parameters gained from a Return Voltage                      beneficial influence on the further life of the cellu-
curve for the description of the condition of an                 lose, although to be effective, a repetitive or better
insulating system is a measurement before and                    a continuous removal should be preferred.
after drying, oil exchange or a repair. Measure-
ments performed on a 250 MVA power trans-                        6    CORRELATION PLOT τ2(t) OVER τ1(t)
former before (Fig. 7) and after oil drying
(Fig. 8) show the changes.                                       As discussed in the previous chapter the depend-
                                                                 ence τ1(t) and τ2(t) characterizes the degree of
                                                                 ageing and degradation of the insulation system of
                                                                 a power transformer. A step forward is the plot of
                                                                 τ2(t) over τ1(t) with the time t as an implicit pa-
                                                                 rameter. Fig. 9 shows a corresponding plot of the
                                                                 data presented in Figs. 5 to 8. The differences are
                                                                 obvious. For better characterization of the curves,
                                                                 a set of different hyperbolas characterizing lines of
                                                                 constant products of lg τ2 and lg τ1 is displayed.




Fig. 7: Logarithms of the time constants lg τ2(t) and
lg τ1(t) calculated from Return Voltage curves of an
aged 250 MVA transformer before oil drying

The deviation of the Return Voltage curve from the
ideal Maxwell-type behaviour - indicated by the
dependence of the dielectric time constants τi on
the selection of the point U(t) - has become much
less prominent by the drying process. Water and
ageing products that were responsible for the be-
haviour at t < tm had been removed to a high de-                 Fig. 9: Correlation plots of the logarithms of the time
gree from the oil by the drying process. The value               constants lg τ2(t) over lg τ1(t) for three power trans-
                                                                 formers, from left to right: a seriously aged 100 MVA
of τ1 around 2 tm or later has more than tripled,                transformer (Fig. 6), an aged 250 MVA transformer
because oil drying decreases the oil conductivity                before and after oil drying (Figs. 7 and 8), and a new
and, along with that, increases the dielectric time              31.5 MVA transformer (Fig. 5)
constant.
XVII International Symposium on High Voltage Engineering, Hannover, Germany, August 22-26, 2011



7    RELYABILITY FACTOR r

For the application of the diagnostic method in
practice, starting from Fig. 9 a newly defined pa-
rameter, the r - factor can be used.

     r = lg τ2 x lg τ1
For the non aged transformer r > 5 is found and
there is nearly no change in the time constant τ1.
For the seriously aged transformer r ≈ 2.5 is
found, and a large change in τ1 occurs.
Figs. 10 and 11 show diagrams of the r- factor
over lg τ1 for the data from Fig. 9. For a more de-
tailed analysis the r - factor is displayed in two
separate graphs : for t < tm (Fig. 10) and for t > tm             Fig. 11: r- factor over lg τ1 for t > tm for three power
                                                                  transformers, from left to right: a seriously aged 100
(Fig. 11).
                                                                  MVA transformer (Fig. 6), an aged 250 MVA transformer
                                                                  before and after oil drying (Figs. 7 and 8), and a new
For t > tm (Fig. 11) also for aged transformers the               31.5 MVA transformer (Fig. 5).
r - factor is nearly constant as well as the time
constant τ1, an indication that in this time region               8    CONCLUSIONS
the Return Voltage curve is shaped like expected
from the Maxwell model. The data from this time                   It is possible to calculate the dielectric time con-
region mainly represent the ”DC-conductivities of                 stants of the components in the two-component
the two dielectrics in the insulation system without              insulation system of power transformers by
a relevant influence of polarization den depolariza-              means of Return Voltage measurements using
tion effects. As a first step from this graph the r -             the Maxwell equivalent circuit as a model. This
 factor can be taken as a single numerical value                  allows to monitor the condition of each component
for diagnostic characterization                                   separately, without being influenced by the size
                                                                  and geometry of the insulation of the transformer.
The short time region t < tm (Fig. 10) may show
additional differences due to the degree of ageing                For aged insulation systems marked deviations
and degradation. They are mainly a result of spe-                 from the ideal Maxwell model can be found. Es-
cific polarization and depolarization processes and               pecially the initial incline of the Return Voltage
hence sensitive on polar ageing and degradation                   curve is often very steep. A fit for t < tm leads to
products. The detailed analysis of this region in                 smaller values of τ1 and higher values of τ2. This is
more detail reveals further information about the                 due to degradation products that lead to additional
actual situation of the insulation system.                        conduction and polarisation processes in the range
                                                                  of up to a few 10 seconds. The influence of these
                                                                  effects on the shape of the curve decreases with
                                                                  time and for t > tm i.e. after the peak of the curve
                                                                  nearly no time dependence exists – the system
                                                                  behaves as predicted from the Maxwell-model.

                                                                  In general: The analysis of measurements on dif-
                                                                  ferently degraded or aged power transformers or of
                                                                  transformers before and after oil drying or a re-
                                                                  pair showed that less ageing and degradation i.e.
                                                                  a better condition of the insulation system leads to
                                                                  a smaller deviation of the shape of the Return Volt-
                                                                  age curve from the ideal curve predicted by the
                                                                  Maxwell model. Hence this deviation as well as the
                                                                  numerical values of the time constants τB = τ2 and
                                                                  τO = τ1 can be used as a diagnostic parameter for
Fig. 10: r- factor over lg τ1 for t < tm for three power          ageing and degradation.
transformers, from left to right: a seriously aged 100
MVA transformer (Fig. 6), an aged 250 MVA transformer
before and after oil drying (Figs. 7 and 8), and a new
31.5 MVA transformer (Fig. 5).
XVII International Symposium on High Voltage Engineering, Hannover, Germany, August 22-26, 2011


The plot of the logarithms of the time constants
lg τ2(t) over lg τ1(t) with the time t as implicit pa-
rameter shows significant differentiations be-
tween differently aged and degraded power
transformers. For the numerical characterization
of the degree of ageing and degradation of power
transformers the r-factor is introduced as a mean-
ingful parameter. As a first step the r-factor should
be taken for t > tm, for a more detailed analysis the
data for t < tm should be used also.

The comparison of the r-factor with e.g. the hu-
midity of the oil – data from several measure-
ments of different power transformers not pre-
sented in this paper – shows a good correlation.


9    REFERENCES

[1] Zaengl, W. S.: Dielectric Spectroscopy in Time and
      Frequency Domain for HV Power Equipment, Part I:
      Theoretical Considerations, Part II:.Applications
      IEEE EI-Mag., 19, No. 5, (2003), 5-19 and No.6,
      (2003), 9-22
[2] Patsch, R.; Kouzmine, O.: Diagnostic Parameters in
      Return Voltage Measurements of Oil-Paper Insula-
      tion Systems, WSEAS Trans. on Circuits and
      Systems, Vol. 4, (2005), 1191-9
  [3] Gäfvert, U.: Dielectric Response Analysis of Real
       Insulation Systems, ICSD’04, Toulouse, France,
       (2004), 1-10
[4] Patsch, R.; D.; Menzel, J. Ageing and Degradation of
      Power Transformers – How to Interpret Return Volt-
      age Measurements. ISEIM’08, Yokkaichi, Japan,
      (2008)
 [5] Patsch, R.; Kamenka, D.; Menzel, J. Return Voltage
      Measurements - Diagnostic Interpretations on the
      Basis of the Dielectric Time Constants.
      APTADM’07, Wroclaw, Poland, (2007), 58-64
 [6] Patsch, R.; D.; Menzel, J. Temperature Depend-
      ence of the Dielectric Properties of the Insulation
      System of Power Transformers. EIC’09, Montreal,
      Canada, (2009), 205-9
 [7] Menzel, J.: Diagnosis of Power Transformers Using
       Return Voltage and Partial Discharge Measurement
       Data Evaluation, PhD Thesis, University of Siegen,
       Germany, (2009), in German

Contenu connexe

Similaire à Ramoutsakis

Electrochemical performance of supercapacitor with glass wool separator under...
Electrochemical performance of supercapacitor with glass wool separator under...Electrochemical performance of supercapacitor with glass wool separator under...
Electrochemical performance of supercapacitor with glass wool separator under...journalBEEI
 
Aabc'15 paper
Aabc'15 paperAabc'15 paper
Aabc'15 paperYunasko
 
Bt2423072310
Bt2423072310Bt2423072310
Bt2423072310IJMER
 
Effect of chromium chloride (cr cl2) on the electrical properties for (pva pv...
Effect of chromium chloride (cr cl2) on the electrical properties for (pva pv...Effect of chromium chloride (cr cl2) on the electrical properties for (pva pv...
Effect of chromium chloride (cr cl2) on the electrical properties for (pva pv...Alexander Decker
 
Electrowetting of-water-and-aqueous-solutions-on-poly-ethylene-terephthalate-...
Electrowetting of-water-and-aqueous-solutions-on-poly-ethylene-terephthalate-...Electrowetting of-water-and-aqueous-solutions-on-poly-ethylene-terephthalate-...
Electrowetting of-water-and-aqueous-solutions-on-poly-ethylene-terephthalate-...Bhargavkrishna Kondreddy
 
Estimation of insulation life based on dual temperature aging model (2)
Estimation of insulation life based on dual temperature aging model (2)Estimation of insulation life based on dual temperature aging model (2)
Estimation of insulation life based on dual temperature aging model (2)Simon Koutoua
 
Type and application of dielectric
Type and application of dielectricType and application of dielectric
Type and application of dielectricraj_sevak
 
Treatment of NOx from Diesel Engine Exhaust by Dielectric Barrier Discharge M...
Treatment of NOx from Diesel Engine Exhaust by Dielectric Barrier Discharge M...Treatment of NOx from Diesel Engine Exhaust by Dielectric Barrier Discharge M...
Treatment of NOx from Diesel Engine Exhaust by Dielectric Barrier Discharge M...IDES Editor
 
G04013845
G04013845G04013845
G04013845IJMER
 
G04013845
G04013845G04013845
G04013845IJMER
 
I0330267076
I0330267076I0330267076
I0330267076theijes
 
Dynamic Analysis and Testing of on-load tap changer
Dynamic Analysis and Testing of on-load tap changerDynamic Analysis and Testing of on-load tap changer
Dynamic Analysis and Testing of on-load tap changerLeonardo Nicolini
 
Dielectrophoresis Effect of Dielectric Liquids with Suspended Cellulose Impur...
Dielectrophoresis Effect of Dielectric Liquids with Suspended Cellulose Impur...Dielectrophoresis Effect of Dielectric Liquids with Suspended Cellulose Impur...
Dielectrophoresis Effect of Dielectric Liquids with Suspended Cellulose Impur...IJECEIAES
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Scienceresearchinventy
 
Microwave dehydrator an environmental friendly step toward improving microwav...
Microwave dehydrator an environmental friendly step toward improving microwav...Microwave dehydrator an environmental friendly step toward improving microwav...
Microwave dehydrator an environmental friendly step toward improving microwav...eSAT Publishing House
 
22 9151 transformer exchangingwithvacuum edit septian
22 9151 transformer exchangingwithvacuum edit septian22 9151 transformer exchangingwithvacuum edit septian
22 9151 transformer exchangingwithvacuum edit septianIAESIJEECS
 

Similaire à Ramoutsakis (20)

Electrochemical performance of supercapacitor with glass wool separator under...
Electrochemical performance of supercapacitor with glass wool separator under...Electrochemical performance of supercapacitor with glass wool separator under...
Electrochemical performance of supercapacitor with glass wool separator under...
 
Aabc'15 paper
Aabc'15 paperAabc'15 paper
Aabc'15 paper
 
Bt2423072310
Bt2423072310Bt2423072310
Bt2423072310
 
Effect of chromium chloride (cr cl2) on the electrical properties for (pva pv...
Effect of chromium chloride (cr cl2) on the electrical properties for (pva pv...Effect of chromium chloride (cr cl2) on the electrical properties for (pva pv...
Effect of chromium chloride (cr cl2) on the electrical properties for (pva pv...
 
מאמר סופי
מאמר סופימאמר סופי
מאמר סופי
 
Electrowetting of-water-and-aqueous-solutions-on-poly-ethylene-terephthalate-...
Electrowetting of-water-and-aqueous-solutions-on-poly-ethylene-terephthalate-...Electrowetting of-water-and-aqueous-solutions-on-poly-ethylene-terephthalate-...
Electrowetting of-water-and-aqueous-solutions-on-poly-ethylene-terephthalate-...
 
Estimation of insulation life based on dual temperature aging model (2)
Estimation of insulation life based on dual temperature aging model (2)Estimation of insulation life based on dual temperature aging model (2)
Estimation of insulation life based on dual temperature aging model (2)
 
Type and application of dielectric
Type and application of dielectricType and application of dielectric
Type and application of dielectric
 
Treatment of NOx from Diesel Engine Exhaust by Dielectric Barrier Discharge M...
Treatment of NOx from Diesel Engine Exhaust by Dielectric Barrier Discharge M...Treatment of NOx from Diesel Engine Exhaust by Dielectric Barrier Discharge M...
Treatment of NOx from Diesel Engine Exhaust by Dielectric Barrier Discharge M...
 
Effect of Coupling Chain Length on the Electric –Optic Properties of Siloxane...
Effect of Coupling Chain Length on the Electric –Optic Properties of Siloxane...Effect of Coupling Chain Length on the Electric –Optic Properties of Siloxane...
Effect of Coupling Chain Length on the Electric –Optic Properties of Siloxane...
 
G04013845
G04013845G04013845
G04013845
 
G04013845
G04013845G04013845
G04013845
 
G04013845
G04013845G04013845
G04013845
 
I0330267076
I0330267076I0330267076
I0330267076
 
Dynamic Analysis and Testing of on-load tap changer
Dynamic Analysis and Testing of on-load tap changerDynamic Analysis and Testing of on-load tap changer
Dynamic Analysis and Testing of on-load tap changer
 
Dielectrophoresis Effect of Dielectric Liquids with Suspended Cellulose Impur...
Dielectrophoresis Effect of Dielectric Liquids with Suspended Cellulose Impur...Dielectrophoresis Effect of Dielectric Liquids with Suspended Cellulose Impur...
Dielectrophoresis Effect of Dielectric Liquids with Suspended Cellulose Impur...
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
 
Microwave dehydrator an environmental friendly step toward improving microwav...
Microwave dehydrator an environmental friendly step toward improving microwav...Microwave dehydrator an environmental friendly step toward improving microwav...
Microwave dehydrator an environmental friendly step toward improving microwav...
 
22 9151 transformer exchangingwithvacuum edit septian
22 9151 transformer exchangingwithvacuum edit septian22 9151 transformer exchangingwithvacuum edit septian
22 9151 transformer exchangingwithvacuum edit septian
 
Hydrogen energy
Hydrogen energyHydrogen energy
Hydrogen energy
 

Dernier

Independent Garulia Escorts ✔ 9332606886✔ Full Night With Room Online Booking...
Independent Garulia Escorts ✔ 9332606886✔ Full Night With Room Online Booking...Independent Garulia Escorts ✔ 9332606886✔ Full Night With Room Online Booking...
Independent Garulia Escorts ✔ 9332606886✔ Full Night With Room Online Booking...Riya Pathan
 
Call Girls In Goa 9316020077 Goa Call Girl By Indian Call Girls Goa
Call Girls In Goa  9316020077 Goa  Call Girl By Indian Call Girls GoaCall Girls In Goa  9316020077 Goa  Call Girl By Indian Call Girls Goa
Call Girls In Goa 9316020077 Goa Call Girl By Indian Call Girls Goasexy call girls service in goa
 
Call Girls in Barasat | 7001035870 At Low Cost Cash Payment Booking
Call Girls in Barasat | 7001035870 At Low Cost Cash Payment BookingCall Girls in Barasat | 7001035870 At Low Cost Cash Payment Booking
Call Girls in Barasat | 7001035870 At Low Cost Cash Payment Bookingnoor ahmed
 
Model Call Girls In Pazhavanthangal WhatsApp Booking 7427069034 call girl ser...
Model Call Girls In Pazhavanthangal WhatsApp Booking 7427069034 call girl ser...Model Call Girls In Pazhavanthangal WhatsApp Booking 7427069034 call girl ser...
Model Call Girls In Pazhavanthangal WhatsApp Booking 7427069034 call girl ser... Shivani Pandey
 
📞 Contact Number 8617697112 VIP Ganderbal Call Girls
📞 Contact Number 8617697112 VIP Ganderbal Call Girls📞 Contact Number 8617697112 VIP Ganderbal Call Girls
📞 Contact Number 8617697112 VIP Ganderbal Call GirlsNitya salvi
 
Book Paid Sonagachi Call Girls Kolkata 𖠋 8250192130 𖠋Low Budget Full Independ...
Book Paid Sonagachi Call Girls Kolkata 𖠋 8250192130 𖠋Low Budget Full Independ...Book Paid Sonagachi Call Girls Kolkata 𖠋 8250192130 𖠋Low Budget Full Independ...
Book Paid Sonagachi Call Girls Kolkata 𖠋 8250192130 𖠋Low Budget Full Independ...noor ahmed
 
𓀤Call On 6297143586 𓀤 Ultadanga Call Girls In All Kolkata 24/7 Provide Call W...
𓀤Call On 6297143586 𓀤 Ultadanga Call Girls In All Kolkata 24/7 Provide Call W...𓀤Call On 6297143586 𓀤 Ultadanga Call Girls In All Kolkata 24/7 Provide Call W...
𓀤Call On 6297143586 𓀤 Ultadanga Call Girls In All Kolkata 24/7 Provide Call W...rahim quresi
 
Borum Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
Borum Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort ServiceBorum Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
Borum Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort ServiceDamini Dixit
 
Science City Kolkata ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sex...
Science City Kolkata ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sex...Science City Kolkata ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sex...
Science City Kolkata ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sex...rahim quresi
 
Sonagachi ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Rea...
Sonagachi ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Rea...Sonagachi ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Rea...
Sonagachi ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Rea...rahim quresi
 
Behala ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Ready ...
Behala ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Ready ...Behala ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Ready ...
Behala ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Ready ...ritikasharma
 
Hotel And Home Service Available Kolkata Call Girls South End Park ✔ 62971435...
Hotel And Home Service Available Kolkata Call Girls South End Park ✔ 62971435...Hotel And Home Service Available Kolkata Call Girls South End Park ✔ 62971435...
Hotel And Home Service Available Kolkata Call Girls South End Park ✔ 62971435...ritikasharma
 
↑Top Model (Kolkata) Call Girls Behala ⟟ 8250192130 ⟟ High Class Call Girl In...
↑Top Model (Kolkata) Call Girls Behala ⟟ 8250192130 ⟟ High Class Call Girl In...↑Top Model (Kolkata) Call Girls Behala ⟟ 8250192130 ⟟ High Class Call Girl In...
↑Top Model (Kolkata) Call Girls Behala ⟟ 8250192130 ⟟ High Class Call Girl In...noor ahmed
 
Top Rated Pune Call Girls Dhayari ⟟ 6297143586 ⟟ Call Me For Genuine Sex Ser...
Top Rated  Pune Call Girls Dhayari ⟟ 6297143586 ⟟ Call Me For Genuine Sex Ser...Top Rated  Pune Call Girls Dhayari ⟟ 6297143586 ⟟ Call Me For Genuine Sex Ser...
Top Rated Pune Call Girls Dhayari ⟟ 6297143586 ⟟ Call Me For Genuine Sex Ser...Call Girls in Nagpur High Profile
 
Model Call Girls In Ariyalur WhatsApp Booking 7427069034 call girl service 24...
Model Call Girls In Ariyalur WhatsApp Booking 7427069034 call girl service 24...Model Call Girls In Ariyalur WhatsApp Booking 7427069034 call girl service 24...
Model Call Girls In Ariyalur WhatsApp Booking 7427069034 call girl service 24... Shivani Pandey
 
VIP Model Call Girls Koregaon Park ( Pune ) Call ON 8005736733 Starting From ...
VIP Model Call Girls Koregaon Park ( Pune ) Call ON 8005736733 Starting From ...VIP Model Call Girls Koregaon Park ( Pune ) Call ON 8005736733 Starting From ...
VIP Model Call Girls Koregaon Park ( Pune ) Call ON 8005736733 Starting From ...SUHANI PANDEY
 
Top Rated Pune Call Girls Pimpri Chinchwad ⟟ 6297143586 ⟟ Call Me For Genuin...
Top Rated  Pune Call Girls Pimpri Chinchwad ⟟ 6297143586 ⟟ Call Me For Genuin...Top Rated  Pune Call Girls Pimpri Chinchwad ⟟ 6297143586 ⟟ Call Me For Genuin...
Top Rated Pune Call Girls Pimpri Chinchwad ⟟ 6297143586 ⟟ Call Me For Genuin...Call Girls in Nagpur High Profile
 

Dernier (20)

Independent Garulia Escorts ✔ 9332606886✔ Full Night With Room Online Booking...
Independent Garulia Escorts ✔ 9332606886✔ Full Night With Room Online Booking...Independent Garulia Escorts ✔ 9332606886✔ Full Night With Room Online Booking...
Independent Garulia Escorts ✔ 9332606886✔ Full Night With Room Online Booking...
 
Call Girls In Goa 9316020077 Goa Call Girl By Indian Call Girls Goa
Call Girls In Goa  9316020077 Goa  Call Girl By Indian Call Girls GoaCall Girls In Goa  9316020077 Goa  Call Girl By Indian Call Girls Goa
Call Girls In Goa 9316020077 Goa Call Girl By Indian Call Girls Goa
 
Call Girls in Barasat | 7001035870 At Low Cost Cash Payment Booking
Call Girls in Barasat | 7001035870 At Low Cost Cash Payment BookingCall Girls in Barasat | 7001035870 At Low Cost Cash Payment Booking
Call Girls in Barasat | 7001035870 At Low Cost Cash Payment Booking
 
Goa Call "Girls Service 9316020077 Call "Girls in Goa
Goa Call "Girls  Service   9316020077 Call "Girls in GoaGoa Call "Girls  Service   9316020077 Call "Girls in Goa
Goa Call "Girls Service 9316020077 Call "Girls in Goa
 
Model Call Girls In Pazhavanthangal WhatsApp Booking 7427069034 call girl ser...
Model Call Girls In Pazhavanthangal WhatsApp Booking 7427069034 call girl ser...Model Call Girls In Pazhavanthangal WhatsApp Booking 7427069034 call girl ser...
Model Call Girls In Pazhavanthangal WhatsApp Booking 7427069034 call girl ser...
 
📞 Contact Number 8617697112 VIP Ganderbal Call Girls
📞 Contact Number 8617697112 VIP Ganderbal Call Girls📞 Contact Number 8617697112 VIP Ganderbal Call Girls
📞 Contact Number 8617697112 VIP Ganderbal Call Girls
 
Book Paid Sonagachi Call Girls Kolkata 𖠋 8250192130 𖠋Low Budget Full Independ...
Book Paid Sonagachi Call Girls Kolkata 𖠋 8250192130 𖠋Low Budget Full Independ...Book Paid Sonagachi Call Girls Kolkata 𖠋 8250192130 𖠋Low Budget Full Independ...
Book Paid Sonagachi Call Girls Kolkata 𖠋 8250192130 𖠋Low Budget Full Independ...
 
𓀤Call On 6297143586 𓀤 Ultadanga Call Girls In All Kolkata 24/7 Provide Call W...
𓀤Call On 6297143586 𓀤 Ultadanga Call Girls In All Kolkata 24/7 Provide Call W...𓀤Call On 6297143586 𓀤 Ultadanga Call Girls In All Kolkata 24/7 Provide Call W...
𓀤Call On 6297143586 𓀤 Ultadanga Call Girls In All Kolkata 24/7 Provide Call W...
 
Borum Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
Borum Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort ServiceBorum Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
Borum Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
 
Goa Call Girls 9316020077 Call Girls In Goa By Russian Call Girl in goa
Goa Call Girls 9316020077 Call Girls  In Goa By Russian Call Girl in goaGoa Call Girls 9316020077 Call Girls  In Goa By Russian Call Girl in goa
Goa Call Girls 9316020077 Call Girls In Goa By Russian Call Girl in goa
 
Science City Kolkata ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sex...
Science City Kolkata ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sex...Science City Kolkata ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sex...
Science City Kolkata ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sex...
 
Sonagachi ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Rea...
Sonagachi ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Rea...Sonagachi ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Rea...
Sonagachi ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Rea...
 
Behala ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Ready ...
Behala ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Ready ...Behala ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Ready ...
Behala ( Call Girls ) Kolkata ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Ready ...
 
Hotel And Home Service Available Kolkata Call Girls South End Park ✔ 62971435...
Hotel And Home Service Available Kolkata Call Girls South End Park ✔ 62971435...Hotel And Home Service Available Kolkata Call Girls South End Park ✔ 62971435...
Hotel And Home Service Available Kolkata Call Girls South End Park ✔ 62971435...
 
Desi Bhabhi Call Girls In Goa 💃 730 02 72 001💃desi Bhabhi Escort Goa
Desi Bhabhi Call Girls  In Goa  💃 730 02 72 001💃desi Bhabhi Escort GoaDesi Bhabhi Call Girls  In Goa  💃 730 02 72 001💃desi Bhabhi Escort Goa
Desi Bhabhi Call Girls In Goa 💃 730 02 72 001💃desi Bhabhi Escort Goa
 
↑Top Model (Kolkata) Call Girls Behala ⟟ 8250192130 ⟟ High Class Call Girl In...
↑Top Model (Kolkata) Call Girls Behala ⟟ 8250192130 ⟟ High Class Call Girl In...↑Top Model (Kolkata) Call Girls Behala ⟟ 8250192130 ⟟ High Class Call Girl In...
↑Top Model (Kolkata) Call Girls Behala ⟟ 8250192130 ⟟ High Class Call Girl In...
 
Top Rated Pune Call Girls Dhayari ⟟ 6297143586 ⟟ Call Me For Genuine Sex Ser...
Top Rated  Pune Call Girls Dhayari ⟟ 6297143586 ⟟ Call Me For Genuine Sex Ser...Top Rated  Pune Call Girls Dhayari ⟟ 6297143586 ⟟ Call Me For Genuine Sex Ser...
Top Rated Pune Call Girls Dhayari ⟟ 6297143586 ⟟ Call Me For Genuine Sex Ser...
 
Model Call Girls In Ariyalur WhatsApp Booking 7427069034 call girl service 24...
Model Call Girls In Ariyalur WhatsApp Booking 7427069034 call girl service 24...Model Call Girls In Ariyalur WhatsApp Booking 7427069034 call girl service 24...
Model Call Girls In Ariyalur WhatsApp Booking 7427069034 call girl service 24...
 
VIP Model Call Girls Koregaon Park ( Pune ) Call ON 8005736733 Starting From ...
VIP Model Call Girls Koregaon Park ( Pune ) Call ON 8005736733 Starting From ...VIP Model Call Girls Koregaon Park ( Pune ) Call ON 8005736733 Starting From ...
VIP Model Call Girls Koregaon Park ( Pune ) Call ON 8005736733 Starting From ...
 
Top Rated Pune Call Girls Pimpri Chinchwad ⟟ 6297143586 ⟟ Call Me For Genuin...
Top Rated  Pune Call Girls Pimpri Chinchwad ⟟ 6297143586 ⟟ Call Me For Genuin...Top Rated  Pune Call Girls Pimpri Chinchwad ⟟ 6297143586 ⟟ Call Me For Genuin...
Top Rated Pune Call Girls Pimpri Chinchwad ⟟ 6297143586 ⟟ Call Me For Genuin...
 

Ramoutsakis

  • 1. XVII International Symposium on High Voltage Engineering, Hannover, Germany, August 22-26, 2011 CONDITION MONITORING OF POWER TRANSFORMERS – WHAT INFORMATION CAN WE GET FROM RETURN VOLTAGE MEASUREMENTS Rainer Patsch University of Siegen, Germany Institute of Materials & Diagnostics in Electrical Engineering rainer.patsch@uni-siegen.de Abstract: Return Voltage Measurements are an efficient tool to measure the dielectric properties of an insulating system and thus to characterize the degradation of cellulose-oil insulations. They are widely used for the diagnosis of paper oil insulated power cables. As a consequence of misinterpretations of the measurement results in the past, the use of Return Voltage Measurements for the diagnosis of power trans- formers has been abandoned. Nevertheless – performing a physically meaningful interpretation of the measured curves – the application on power transformers is also very promising, especially because the insulation system in a power transformer is close to the conditions described by the Maxwell model for two dielectrics in series. For the characterization of the degree of ageing and consequently the reliability of the insulation system a new diagnostic parameter, the r - factor, is presented. The results of measurements of differently aged power transformers show a correct ranking and also a correlation between the oil humidity and the r - factor. 1 INTRODUCTION ing ind Barriers W For the diagnosis of insulating systems, time de- er pendent polarization/depolarization processes can t Ou g be used [1, 2]. In insulating systems consisting of din in Oil Ducts more than one component, boundary polarization W er can be considered as the dominant polarization Inn process. This holds especially for the cellulose-oil insulations that are used in power transformers with pressboard-oil insulation. Spacers Barriers 2 EQUIVALENT CIRCUIT OF A TRANSFOR- MER INSULATION Fig. 1: Simplified model for a power transformer insula- Fig. 1 shows a simplified model of a power trans- tion with solid barriers and liquid oil former insulation and the basic distribution of oil and cellulose [3]. Fig. 2 shows a corresponding electrical equivalent circuit. The equivalent circuit basically consists of a series connection of two dielectric materials: Firstly the cellulose insula- tion of the windings and the pressboard barriers, secondly the oil ducts filled by an insulating oil. The main elements are RB, CB, RO and CO. The elements RS, CS, and RD are of less importance, where the latter one represents conduction proc- esses in the oil bypassing the barriers. In most cases, for dielectric phenomena the influence of RD is negligible. The same holds for the influence of Fig. 2: Equivalent circuit of a pressboard-oil insulated RS and CS in comparison to the phenomenon of power transformer insulation; the RC series elements in boundary polarization. The RC series elements the middle are used for formal fits in parallel to CB and CS characterize additional polarization processes that are of minor impor- importance. Not depending on the actual geomet- tance for the basic behaviour that is determined by ric dimensions, the dielectric behaviour is fully the Maxwell circuit formed by RB, CB, RO and CO. determined by the specific conductivities бi and the relative permittivities εri of the two insulating mate- The fundamental behaviour determined by the two rials cellulose and oil. The characteristic voltage dielectrics cellulose and oil is characterized in the division between the high and low voltage windings equivalent circuit by the numerical values of these and the grounded core and tank results from the four elements. Interestingly in the Maxwell circuit, continuity equation of the current density and the absolute values of these elements are not of the laws for the electric field at boundaries.
  • 2. XVII International Symposium on High Voltage Engineering, Hannover, Germany, August 22-26, 2011 2.1 Dielectric time constants The cellulose cannot be analyzed directly because it is not possible to take a piece of the paper or For an insulating material the dielectric time con- pressboard out of the transformer. Hence the con- stant τ is proportional to the relative permittivity dition of the cellulose can be determined only εr and inversely proportional to the specific con- indirectly from the analysis of the oil by means of ductivity б. Hence the time constant τ is sensitive calculations on the basis of the different solubilities of ageing and degradation products under thermo- to changes of б and εr, whereby for cellulose mate- dynamic equilibrium conditions, or by the use of rials the specific conductivity б is very sensitive the corresponding dielectric time constants of on the contents of water or other degradation cellulose and oil, a method that is a unique possi- products. For a parallel circuit of R and C the di- bility of the Return Voltage Method. electric time constant is given by τ = RC or - intro- ducing the characteristic material parameters εr and б to get rid of the actual geometric dimensions 4 RETURN VOLTAGE MEASUREMENTS - by τ = ε0 εr / б. Hence the actual time constants Water in the cellulose leads to an increase of the τB and τO of the two insulating materials cellulose concentration of mobile carriers, thus to an in- and oil do not depend on the geometric dimen- crease of the specific conductivity бB and hence sions of the measured test object and conse- a decrease of the dielectric time constant τB. The quently a diagnostic parameter derived from the two time constants is meaningful for all transformer same holds to a lower extent for a decrease of τO geometries and sizes. In contrast to other diagnos- due to water and degradation products in the oil. If tic methods no fits according to the geometry of the transformer insulation system behaves like a the tested object are needed. Maxwell circuit, Return Voltage measurements are a good method to monitor degradation processes 3 AGEING OF TRANSFORMER INSULATION in transformer insulations, because the dielectric SYSTEMS time constants of the two dielectrics τB = RBCB and τO= ROCO can be calculated numerically from In power transformers the ageing of the insulating the shape of the Return Voltage curve. system is on one hand due to ageing and degra- dation processes in the cellulose and on the other hand due to ageing and degradation of the oil. Especially the degradation of the cellulose depends on the temperature of the insulation and any partial discharge activities. The degradation or depolymerisation of the cellulose generates also water molecules that will accelerate this degrada- tion process. In addition water that comes from the outside via the surrounding oil may also intensify the degradation process. So water is on one hand Fig. 3: Equivalent circuit of a paper-oil dielectric with an indicator of degradation and on the other τB = τ2 = R2C2 and τO = τ1 = R1C1 with τB > τO and the hand also a reason for accelerated degradation. basic measuring circuit 3.1 Monitoring and maintenance of Fig. 3 shows the basic measuring circuit for a Re- transformers turn Voltage measurement with τ2 = τB and τ1 = τO. Under the assumption that the measuring resistor The oil of a transformer may be analyzed during Rm is sufficiently higher than the resistors R2 and service especially by taking a sample and measur- R1 in the equivalent circuit, the Return Voltage ing the contents of water or other degradation curve Ur(t) can be calculated analytically: products, mainly dissolved gases by means of DGA. The oil can be upgraded by drying proc- esses either continuously or in a separate offline ⎛ −t − t ⎞ process or the oil can be exchanged. By this also U r (t ) = U s ⎜ e τ 2 − e τ1 ⎟ the water contents of the cellulose can be de- ⎜ ⎟ (1) creased, but only by diffusion processes that lead ⎝ ⎠ to a new equilibrium between the water contents in the cellulose and the oil. Generally the con- with τ 2 = R2 C 2 and τ 1 = R1C1 . Us depends also centration of water molecules in the cellulose – on the geometric dimensions of the insulating sys- and also the total amount of water – is much higher than in the oil. Hence an attempt to dry the tem, but the time constants τ2 and τ1 are not influ- cellulose by drying the oil is a very slow process. enced by its value.
  • 3. XVII International Symposium on High Voltage Engineering, Hannover, Germany, August 22-26, 2011 For Return Voltage measurements a DC voltage measured curve, thus the measured curve is Up (1 or 2 kV) is applied for a certain time (e.g. nearly identical to the Maxwell-type curve given in tp = 30 min), then the transformer is short circuited eqn. (1). for td = 2 s. After opening the short circuit, a volt- age will build up across the terminals of the trans- former. The equivalent circuit of a transformer in- sulation - i.e. its decisive elements RB, CB, RO and CO - corresponds very closely to a Maxwell equiva- lent circuit of a series connection of two RC parallel elements. The evaluation of the shape of the Return Voltage curve Ur(t) allows the calcu- lation of the dielectric time constants τ2(t) and τ1(t) of the two insulating materials separately [4]. The voltage Us across the two capacitors after a poling time tp and a short circuit time td is not only influ- enced by the time constants τ1 and τ2, but also by the geometric dimensions of the measured system [7]. A curve according to eqn. (1) is exactly defined by Fig. 5: Logarithms of the time constants lg τ2(t) and just three data points, i.e. the point of origin, the lg τ1(t) calculated from the Return Voltage curve of a peak value Um(tm) and one additional point U(t) new 31.5 MVA transformer over t/tm of the curve. Hence the corresponding time con- Fig. 6 shows the corresponding data for a seri- stants τ1(t) and τ2(t) of the oil and the cellulose ously aged 100 MVA transformer that had been respectively can be calculated point by point from taken out of service due to a fault. The deviation the experimentally determined curve. For the char- from the Maxwell-type behaviour can be explained acterisation of the measured Return Voltage curve by additional polarization or conduction proc- of a transformer it is interesting in how far the cal- esses with time constants in the range of up to a culated time constants τ1 and τ2 are influenced by few 10 seconds. Those effects can be described the selection of the point U(t). For a Maxwell curve by additional RC series elements in parallel to the no such dependence exists. (All normalized curves Maxwell circuit. Numerical simulations with a com- pass per definition through (1;1), hence the use of puter program on the basis of this assumption data points around the maximum for the calcula- show a similar behaviour [7]. tion of the dielectric time constants is not very meaningful.) 1 0.9 τ2 λ = 0.8 τ1 0.7 0.6 m U/U 0.5 0.4 ⎛ λ ⎞ 0.3 tm = τ1 ⎜ ⎜ ⎟ ln λ ⎟ ⎝ λ −1 ⎠ 0.2 0.1 0 0 0.5 1 1.5 2 2 .5 3 t/tm Fig. 4 Normalized Return Voltage curve and calculation Fig. 6: Logarithms of the time constants lg τ2(t) and of the dielectric time constants τ2(t) and τ1(t) from the lg τ1(t) calculated from the Return Voltage curve of a points (0;0) and (1;1) and different points (U;t) of the seriously aged 100 MVA transformer over t/tm curve. The effects are be caused by chemical changes 5 MEASUREMENT RESULTS in the insulation components due to ageing and degradation processes. These changes do not Fig. 5 shows the dielectric time constants τ2(t) of only lead to an increased conductivity, but also cellulose and τ1(t) of oil calculated from the meas- generate polar molecules within the insulation. The ured Return Voltage curve of a non aged 31.5 depolarisation of these components leads to a MVA power transformer. The selection of the steeper incline of the Return Voltage curve and to point U(t) does not significantly influence the actual higher ratios τ2/τ1 as indicated in Fig. 4. With in- values of the dielectric time constants of the creasing time of the measurement the influence of
  • 4. XVII International Symposium on High Voltage Engineering, Hannover, Germany, August 22-26, 2011 these processes decreases and the shape of the measured Return Voltage curve approachs the Maxwell-type behaviour. Nevertheless compared to the data from a new transformer (Fig. 5) the values of the time constants are lower. For diagnostic purposes the data from t > tm are a measure for the DC-conductivities of the dielec- trics, while the data from t < tm are more influenced by additional, predominantly polar ageing and deg- radation products. Measurements of transformers at different temperatures in the range between 15 and 55 °C show for t > tm a temperature depend- ence of the dielectric time constants as expected from thermally activated conduction processes [6, 7], a proof for the validity of the concept of the Fig. 8: Logarithms of the time constants lg τ2(t) and interpretation of Return Voltage measurements on power transformers on the basis of the Maxwell- lg τ1(t) calculated from Return Voltage curves of an aged 250 MVA transformer after oil drying model. 5.1 Influence of oil drying The corresponding value of τ2 did not change sig- nificantly. Nevertheless the removal of ageing A good way to check the reliability of the diagnos- and degradation products from the oil has a tic parameters gained from a Return Voltage beneficial influence on the further life of the cellu- curve for the description of the condition of an lose, although to be effective, a repetitive or better insulating system is a measurement before and a continuous removal should be preferred. after drying, oil exchange or a repair. Measure- ments performed on a 250 MVA power trans- 6 CORRELATION PLOT τ2(t) OVER τ1(t) former before (Fig. 7) and after oil drying (Fig. 8) show the changes. As discussed in the previous chapter the depend- ence τ1(t) and τ2(t) characterizes the degree of ageing and degradation of the insulation system of a power transformer. A step forward is the plot of τ2(t) over τ1(t) with the time t as an implicit pa- rameter. Fig. 9 shows a corresponding plot of the data presented in Figs. 5 to 8. The differences are obvious. For better characterization of the curves, a set of different hyperbolas characterizing lines of constant products of lg τ2 and lg τ1 is displayed. Fig. 7: Logarithms of the time constants lg τ2(t) and lg τ1(t) calculated from Return Voltage curves of an aged 250 MVA transformer before oil drying The deviation of the Return Voltage curve from the ideal Maxwell-type behaviour - indicated by the dependence of the dielectric time constants τi on the selection of the point U(t) - has become much less prominent by the drying process. Water and ageing products that were responsible for the be- haviour at t < tm had been removed to a high de- Fig. 9: Correlation plots of the logarithms of the time gree from the oil by the drying process. The value constants lg τ2(t) over lg τ1(t) for three power trans- formers, from left to right: a seriously aged 100 MVA of τ1 around 2 tm or later has more than tripled, transformer (Fig. 6), an aged 250 MVA transformer because oil drying decreases the oil conductivity before and after oil drying (Figs. 7 and 8), and a new and, along with that, increases the dielectric time 31.5 MVA transformer (Fig. 5) constant.
  • 5. XVII International Symposium on High Voltage Engineering, Hannover, Germany, August 22-26, 2011 7 RELYABILITY FACTOR r For the application of the diagnostic method in practice, starting from Fig. 9 a newly defined pa- rameter, the r - factor can be used. r = lg τ2 x lg τ1 For the non aged transformer r > 5 is found and there is nearly no change in the time constant τ1. For the seriously aged transformer r ≈ 2.5 is found, and a large change in τ1 occurs. Figs. 10 and 11 show diagrams of the r- factor over lg τ1 for the data from Fig. 9. For a more de- tailed analysis the r - factor is displayed in two separate graphs : for t < tm (Fig. 10) and for t > tm Fig. 11: r- factor over lg τ1 for t > tm for three power transformers, from left to right: a seriously aged 100 (Fig. 11). MVA transformer (Fig. 6), an aged 250 MVA transformer before and after oil drying (Figs. 7 and 8), and a new For t > tm (Fig. 11) also for aged transformers the 31.5 MVA transformer (Fig. 5). r - factor is nearly constant as well as the time constant τ1, an indication that in this time region 8 CONCLUSIONS the Return Voltage curve is shaped like expected from the Maxwell model. The data from this time It is possible to calculate the dielectric time con- region mainly represent the ”DC-conductivities of stants of the components in the two-component the two dielectrics in the insulation system without insulation system of power transformers by a relevant influence of polarization den depolariza- means of Return Voltage measurements using tion effects. As a first step from this graph the r - the Maxwell equivalent circuit as a model. This factor can be taken as a single numerical value allows to monitor the condition of each component for diagnostic characterization separately, without being influenced by the size and geometry of the insulation of the transformer. The short time region t < tm (Fig. 10) may show additional differences due to the degree of ageing For aged insulation systems marked deviations and degradation. They are mainly a result of spe- from the ideal Maxwell model can be found. Es- cific polarization and depolarization processes and pecially the initial incline of the Return Voltage hence sensitive on polar ageing and degradation curve is often very steep. A fit for t < tm leads to products. The detailed analysis of this region in smaller values of τ1 and higher values of τ2. This is more detail reveals further information about the due to degradation products that lead to additional actual situation of the insulation system. conduction and polarisation processes in the range of up to a few 10 seconds. The influence of these effects on the shape of the curve decreases with time and for t > tm i.e. after the peak of the curve nearly no time dependence exists – the system behaves as predicted from the Maxwell-model. In general: The analysis of measurements on dif- ferently degraded or aged power transformers or of transformers before and after oil drying or a re- pair showed that less ageing and degradation i.e. a better condition of the insulation system leads to a smaller deviation of the shape of the Return Volt- age curve from the ideal curve predicted by the Maxwell model. Hence this deviation as well as the numerical values of the time constants τB = τ2 and τO = τ1 can be used as a diagnostic parameter for Fig. 10: r- factor over lg τ1 for t < tm for three power ageing and degradation. transformers, from left to right: a seriously aged 100 MVA transformer (Fig. 6), an aged 250 MVA transformer before and after oil drying (Figs. 7 and 8), and a new 31.5 MVA transformer (Fig. 5).
  • 6. XVII International Symposium on High Voltage Engineering, Hannover, Germany, August 22-26, 2011 The plot of the logarithms of the time constants lg τ2(t) over lg τ1(t) with the time t as implicit pa- rameter shows significant differentiations be- tween differently aged and degraded power transformers. For the numerical characterization of the degree of ageing and degradation of power transformers the r-factor is introduced as a mean- ingful parameter. As a first step the r-factor should be taken for t > tm, for a more detailed analysis the data for t < tm should be used also. The comparison of the r-factor with e.g. the hu- midity of the oil – data from several measure- ments of different power transformers not pre- sented in this paper – shows a good correlation. 9 REFERENCES [1] Zaengl, W. S.: Dielectric Spectroscopy in Time and Frequency Domain for HV Power Equipment, Part I: Theoretical Considerations, Part II:.Applications IEEE EI-Mag., 19, No. 5, (2003), 5-19 and No.6, (2003), 9-22 [2] Patsch, R.; Kouzmine, O.: Diagnostic Parameters in Return Voltage Measurements of Oil-Paper Insula- tion Systems, WSEAS Trans. on Circuits and Systems, Vol. 4, (2005), 1191-9 [3] Gäfvert, U.: Dielectric Response Analysis of Real Insulation Systems, ICSD’04, Toulouse, France, (2004), 1-10 [4] Patsch, R.; D.; Menzel, J. Ageing and Degradation of Power Transformers – How to Interpret Return Volt- age Measurements. ISEIM’08, Yokkaichi, Japan, (2008) [5] Patsch, R.; Kamenka, D.; Menzel, J. Return Voltage Measurements - Diagnostic Interpretations on the Basis of the Dielectric Time Constants. APTADM’07, Wroclaw, Poland, (2007), 58-64 [6] Patsch, R.; D.; Menzel, J. Temperature Depend- ence of the Dielectric Properties of the Insulation System of Power Transformers. EIC’09, Montreal, Canada, (2009), 205-9 [7] Menzel, J.: Diagnosis of Power Transformers Using Return Voltage and Partial Discharge Measurement Data Evaluation, PhD Thesis, University of Siegen, Germany, (2009), in German