PERCETANGE IMPEDENCE OF TRANSFORMER
&
IT'S IMPORATANCE IN POWER SYSTEM STUDIES.
---------------------------------------------------------------------------------------------------------
BY :
ASHISH KUMAR GANGULI
Bachelor of Engineering - Electrical
MOBILE : 0091-9109782929
EMAIL : ashish_ganguli06@yahoo.co.in
---------------------------------------------------------------------------------------------------------
Ashish Kumar Ganguli
Date: 21.01.2017
DEFINITAION:
Percentage impedance of a transformer is the percentage of rated voltage applied at one
side (primary winding) to circulate rated current on transformer keeping its other side
(secondary winding) under short circuit conditions. It is marked on transformer
nameplate.
EXPLANATION:
If we apply rated voltage at primary winding of a transformer keeping its secondary
winding short circuited, then amount of current at both windings will be extremely
high as compared to the rated current. This current is called short circuit current and its
magnitude is very high due to zero impedance offered by the load (secondary winding
is short circuited).
Consider,
V : Rated Primary Voltage of Transformer
Z% : Percentage Impedance of Transformer
Irated : Rated Primary Current of Transformer
Zactual : Actual Impedance of Transformer (referred to primary winding)
Based on above explanation, we are applying a percentage (Z %) of rated primary
voltage. Therefore applied voltage is equal to V x Z% / 100. This voltage drives rated
current in transformer winding.
By Ohms Law:
Voltage = Current x Actual Impedance
V x Z% /100 = Irated x Zactual
Z% = Irated Zactual x 100 / V
Now, if we reduce the applied voltage on the
transformer primary i.e. we apply percentage of
rated voltage in transformer primary, current on
both windings will also reduce. At a particular
percentage of rated voltage, rated current will flow
on transformer windings. This percentage of rated
voltage at one side of transformer which circulates
rated current on transformer windings keeping its
other side winding short circuited, is called
percentage impedance of transformer.
Ashish Kumar Ganguli
Date: 21.01.2017
ROLE OF Z% IN SHORT CIRCUIT CALCULATION
Percentage impedance of transformer plays extremely vital role is network calculation
i.e. short circuit calculation and voltage drop calculation.
We can find the short circuit contribution of a transformer as per below explanation:
As considered above, secondary winding of transformer is short circuited.
Now,
If Voltage (V Z% /100) is applied on Transformer Primary, Rated Current (Irated) flows.
If Voltage (V) is applied on Transformer Primary, Current (Irated x 100 / Z%) will flow.
Therefore, when we apply rated voltage at primary winding of a transformer whose
secondary winding is short circuited, short circuit current (Irated x 100 / Z%) will flow on
transformer windings. Value of Z% is same for both windings as it is percentage of
rated voltage. However value of Irated will be different for primary and secondary
winding. Accordingly value of short circuit current will also be different for primary
and secondary windings.
Short Circuit Current (Isc) = Irated x 100 / Z%
If percentage impedance of a transformer is less, its short circuit current will be more
which will produce more stress in insulation. This is a negative factor. On the other
hand, if percentage impedance of a transformer is less, voltage drop on transformer
winding will be less which will facilitate better voltage regulation. This is a positive
factor. Therefore, percentage impedance of transformer has to be precisely selected to
maintain a proper balance between fault level and voltage regulation.
PERMITTED TOLERANCE IN Z%
Percentage impedance of transformer is specified at the time of ordering. But it must
be noted that IEC 76 permits +/- 10% tolerance in percentage impedance at
manufacturer's end. Therefore, if we order a transformer with 8% percentage
impedance, its actual percentage impedance after manufacturing may be any value
between 7.2% (-10% of 8) to 8.8% (+10% of 8), unless it is specifically agreed with
manufacturer at the time of ordering. Tolerance in percentage impedance must be
considered for power system calculations and accordingly system fault level & voltage
regulation must be finalized.
Ashish Kumar Ganguli
Date: 21.01.2017
ROLE OF Z% IN PARALLEL OPERATION OF TRANSFORMERS
If the ratios of kVA rating to percent impedance of two transformers operating in
parallel are equal, they will share equal load. However if ratio is different, they will
share unequal load. This may result in overloading of one transformer.
In order to analyses this criterion; let us consider two transformers operating in parallel
as shown in below diagram.
I1 : Load current from transformer 1
I2 : Load current from transformer 2
IL : Total load current (IL = I1 + I2)
Z1 : Actual impedance of transformer 1
Z2 : Actual impedance of transformer 2
Z1% : Percentage Impedance of transformer 2
Z2% : Percentage Impedance of transformer 2
kVA1 : kVA rating of transformer 1
kVA2 : kVA rating of transformer 2
kVAL : Total load kVA
Ashish Kumar Ganguli
Date: 21.01.2017
We know that
V x Z% / 100 = Irated Zactual
Therefore,
Z1 = (V x Z%1)/ (100 x I1)
Z2 = (V x Z%2)/ (100 x I2)
If we substitute value of actual impedance (Z1 & Z2) as per above equation, we get
If we multiply both sides with kV, we get
If ratio kVA1 / Z1% and kVA2 / Z2% are equal, then kVA1 and kVA2 will be same. That
means, both transformers will share equal load i.e. 50% of total load. This factor must
be analyzed before paralleling two transformers to avoid unequal load sharing and
overloading of one transformer.

Contenu connexe

Tendances

Representation of short & medium transmission lines
Representation of short & medium transmission linesRepresentation of short & medium transmission lines
Representation of short & medium transmission linesvishalgohel12195
 
Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)RP6997
 
Power system stability
Power system stabilityPower system stability
Power system stabilityBalaram Das
 
Unit I design of electrical machines
Unit I   design of electrical machinesUnit I   design of electrical machines
Unit I design of electrical machinesnganesh90
 
measurement of high voltage and high currents
 measurement of high voltage and high currents  measurement of high voltage and high currents
measurement of high voltage and high currents mukund mukund.m
 
TDU - Unit 02 - HVDC, FACTS and sub-stations
TDU - Unit  02 - HVDC, FACTS and sub-stations TDU - Unit  02 - HVDC, FACTS and sub-stations
TDU - Unit 02 - HVDC, FACTS and sub-stations PremanandDesai
 
GENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGEGENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGEJamil Abdullah
 
Ferranti effect
Ferranti effectFerranti effect
Ferranti effecttarun1504
 
Transient in Power system
Transient in Power systemTransient in Power system
Transient in Power systemPreet_patel
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
 
Measurement of high_voltage_and_high_currentunit_iv_full_version
Measurement of high_voltage_and_high_currentunit_iv_full_versionMeasurement of high_voltage_and_high_currentunit_iv_full_version
Measurement of high_voltage_and_high_currentunit_iv_full_versionAman Ansari
 
Parallel Operation of Transformers
Parallel Operation of TransformersParallel Operation of Transformers
Parallel Operation of TransformersRama Jalamanchili
 
Instrument transformer CT & PT
Instrument transformer CT & PTInstrument transformer CT & PT
Instrument transformer CT & PTChandan Singh
 
open circuit and short circuit test on transformer
open circuit and short circuit test on transformeropen circuit and short circuit test on transformer
open circuit and short circuit test on transformerMILAN MANAVAR
 

Tendances (20)

Representation of short & medium transmission lines
Representation of short & medium transmission linesRepresentation of short & medium transmission lines
Representation of short & medium transmission lines
 
Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)
 
Power system stability
Power system stabilityPower system stability
Power system stability
 
Unit I design of electrical machines
Unit I   design of electrical machinesUnit I   design of electrical machines
Unit I design of electrical machines
 
measurement of high voltage and high currents
 measurement of high voltage and high currents  measurement of high voltage and high currents
measurement of high voltage and high currents
 
TDU - Unit 02 - HVDC, FACTS and sub-stations
TDU - Unit  02 - HVDC, FACTS and sub-stations TDU - Unit  02 - HVDC, FACTS and sub-stations
TDU - Unit 02 - HVDC, FACTS and sub-stations
 
Spinning reserve
Spinning reserveSpinning reserve
Spinning reserve
 
GENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGEGENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGE
 
Transformer
TransformerTransformer
Transformer
 
EE6501 - Power System Analysis
EE6501 - Power System AnalysisEE6501 - Power System Analysis
EE6501 - Power System Analysis
 
Ferranti effect
Ferranti effectFerranti effect
Ferranti effect
 
Corona Effect
Corona EffectCorona Effect
Corona Effect
 
Transformer
TransformerTransformer
Transformer
 
Transient in Power system
Transient in Power systemTransient in Power system
Transient in Power system
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Transformer basic
Transformer basicTransformer basic
Transformer basic
 
Measurement of high_voltage_and_high_currentunit_iv_full_version
Measurement of high_voltage_and_high_currentunit_iv_full_versionMeasurement of high_voltage_and_high_currentunit_iv_full_version
Measurement of high_voltage_and_high_currentunit_iv_full_version
 
Parallel Operation of Transformers
Parallel Operation of TransformersParallel Operation of Transformers
Parallel Operation of Transformers
 
Instrument transformer CT & PT
Instrument transformer CT & PTInstrument transformer CT & PT
Instrument transformer CT & PT
 
open circuit and short circuit test on transformer
open circuit and short circuit test on transformeropen circuit and short circuit test on transformer
open circuit and short circuit test on transformer
 

En vedette

Types of transformer
Types of transformerTypes of transformer
Types of transformerRaafat Ismael
 
power transformer and its usage
power transformer and its usage power transformer and its usage
power transformer and its usage gourav1245
 
Power transformer
Power transformerPower transformer
Power transformerZunAib Ali
 
Power Transformer ( Summer Training presentation BHEL )
Power Transformer ( Summer Training presentation BHEL )Power Transformer ( Summer Training presentation BHEL )
Power Transformer ( Summer Training presentation BHEL )Dheeraj Upadhyay
 
Transformer testing
Transformer testingTransformer testing
Transformer testingajayknows
 

En vedette (7)

Types of transformer
Types of transformerTypes of transformer
Types of transformer
 
power transformer and its usage
power transformer and its usage power transformer and its usage
power transformer and its usage
 
Power transformer
Power transformerPower transformer
Power transformer
 
Power transformer
Power transformerPower transformer
Power transformer
 
Power Transformer ( Summer Training presentation BHEL )
Power Transformer ( Summer Training presentation BHEL )Power Transformer ( Summer Training presentation BHEL )
Power Transformer ( Summer Training presentation BHEL )
 
Transformer testing
Transformer testingTransformer testing
Transformer testing
 
Transformer
TransformerTransformer
Transformer
 

Similaire à Percentage Impedance of Transformer

Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Power System Operation
 
C0212014018
C0212014018C0212014018
C0212014018theijes
 
New zv zcs full bridge dc-dc converter with fuzzy & pi control
New zv zcs full bridge dc-dc converter with fuzzy & pi controlNew zv zcs full bridge dc-dc converter with fuzzy & pi control
New zv zcs full bridge dc-dc converter with fuzzy & pi controlIAEME Publication
 
symmetrical_fault_analysis.pdf
symmetrical_fault_analysis.pdfsymmetrical_fault_analysis.pdf
symmetrical_fault_analysis.pdfShanmukhSaiR
 
project report on plc based load sharing
project report on plc based load sharingproject report on plc based load sharing
project report on plc based load sharingVivek Arun
 
Voltage Regulators IC
Voltage Regulators ICVoltage Regulators IC
Voltage Regulators ICDr.Raja R
 
Short circuit test in brief
Short circuit test in briefShort circuit test in brief
Short circuit test in briefMuthar Hussain
 
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of ExcitationPerformance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitationpaperpublications3
 
IRJET- Series and Shunt Compensation in UPFC using Cascaded Multilevel Invert...
IRJET- Series and Shunt Compensation in UPFC using Cascaded Multilevel Invert...IRJET- Series and Shunt Compensation in UPFC using Cascaded Multilevel Invert...
IRJET- Series and Shunt Compensation in UPFC using Cascaded Multilevel Invert...IRJET Journal
 
Sizing generators-for-leading-power-factor white-paper-24_feb14
Sizing generators-for-leading-power-factor white-paper-24_feb14Sizing generators-for-leading-power-factor white-paper-24_feb14
Sizing generators-for-leading-power-factor white-paper-24_feb14Insanul Aziz
 
Comulatively Compounded DC Generator
Comulatively Compounded DC GeneratorComulatively Compounded DC Generator
Comulatively Compounded DC GeneratorAsim Raza
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Electrical Machines - II
Electrical Machines - IIElectrical Machines - II
Electrical Machines - IIkarthi1017
 
Earth Faults and Reverse Power in Transmission Lines
Earth Faults and Reverse Power in Transmission LinesEarth Faults and Reverse Power in Transmission Lines
Earth Faults and Reverse Power in Transmission LinesToshaliMohapatra
 
On line nonlinearity compensation technique for pwm inverter drives
On   line nonlinearity compensation technique for pwm inverter drivesOn   line nonlinearity compensation technique for pwm inverter drives
On line nonlinearity compensation technique for pwm inverter drivesIAEME Publication
 

Similaire à Percentage Impedance of Transformer (20)

Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
 
Ms3621652169
Ms3621652169Ms3621652169
Ms3621652169
 
C0212014018
C0212014018C0212014018
C0212014018
 
New zv zcs full bridge dc-dc converter with fuzzy & pi control
New zv zcs full bridge dc-dc converter with fuzzy & pi controlNew zv zcs full bridge dc-dc converter with fuzzy & pi control
New zv zcs full bridge dc-dc converter with fuzzy & pi control
 
symmetrical_fault_analysis.pdf
symmetrical_fault_analysis.pdfsymmetrical_fault_analysis.pdf
symmetrical_fault_analysis.pdf
 
project report on plc based load sharing
project report on plc based load sharingproject report on plc based load sharing
project report on plc based load sharing
 
Voltage Regulators IC
Voltage Regulators ICVoltage Regulators IC
Voltage Regulators IC
 
Short circuit test in brief
Short circuit test in briefShort circuit test in brief
Short circuit test in brief
 
8925273.ppt
8925273.ppt8925273.ppt
8925273.ppt
 
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of ExcitationPerformance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
 
IRJET- Series and Shunt Compensation in UPFC using Cascaded Multilevel Invert...
IRJET- Series and Shunt Compensation in UPFC using Cascaded Multilevel Invert...IRJET- Series and Shunt Compensation in UPFC using Cascaded Multilevel Invert...
IRJET- Series and Shunt Compensation in UPFC using Cascaded Multilevel Invert...
 
P.u systems.pptx
P.u systems.pptxP.u systems.pptx
P.u systems.pptx
 
Sizing generators-for-leading-power-factor white-paper-24_feb14
Sizing generators-for-leading-power-factor white-paper-24_feb14Sizing generators-for-leading-power-factor white-paper-24_feb14
Sizing generators-for-leading-power-factor white-paper-24_feb14
 
ALL DAY EFFICIENCY
ALL DAY EFFICIENCYALL DAY EFFICIENCY
ALL DAY EFFICIENCY
 
Swing equation
Swing equationSwing equation
Swing equation
 
Comulatively Compounded DC Generator
Comulatively Compounded DC GeneratorComulatively Compounded DC Generator
Comulatively Compounded DC Generator
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
Electrical Machines - II
Electrical Machines - IIElectrical Machines - II
Electrical Machines - II
 
Earth Faults and Reverse Power in Transmission Lines
Earth Faults and Reverse Power in Transmission LinesEarth Faults and Reverse Power in Transmission Lines
Earth Faults and Reverse Power in Transmission Lines
 
On line nonlinearity compensation technique for pwm inverter drives
On   line nonlinearity compensation technique for pwm inverter drivesOn   line nonlinearity compensation technique for pwm inverter drives
On line nonlinearity compensation technique for pwm inverter drives
 

Dernier

Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Servicemeghakumariji156
 
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxOrlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxMuhammadAsimMuhammad6
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsvanyagupta248
 
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxmaisarahman1
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptxJIT KUMAR GUPTA
 
Verification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptxVerification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptxchumtiyababu
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayEpec Engineered Technologies
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptNANDHAKUMARA10
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTbhaskargani46
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdfKamal Acharya
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...Amil baba
 
Moment Distribution Method For Btech Civil
Moment Distribution Method For Btech CivilMoment Distribution Method For Btech Civil
Moment Distribution Method For Btech CivilVinayVitekari
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxJuliansyahHarahap1
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxSCMS School of Architecture
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Arindam Chakraborty, Ph.D., P.E. (CA, TX)
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueBhangaleSonal
 
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKARHAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKARKOUSTAV SARKAR
 
Wadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptxWadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptxNadaHaitham1
 

Dernier (20)

Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
 
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxOrlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
Verification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptxVerification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptx
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Moment Distribution Method For Btech Civil
Moment Distribution Method For Btech CivilMoment Distribution Method For Btech Civil
Moment Distribution Method For Btech Civil
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKARHAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
 
Wadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptxWadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptx
 

Percentage Impedance of Transformer

  • 1. Ashish Kumar Ganguli Date: 21.01.2017 PERCETANGE IMPEDENCE OF TRANSFORMER & IT'S IMPORATANCE IN POWER SYSTEM STUDIES. --------------------------------------------------------------------------------------------------------- BY : ASHISH KUMAR GANGULI Bachelor of Engineering - Electrical MOBILE : 0091-9109782929 EMAIL : ashish_ganguli06@yahoo.co.in ---------------------------------------------------------------------------------------------------------
  • 2. Ashish Kumar Ganguli Date: 21.01.2017 DEFINITAION: Percentage impedance of a transformer is the percentage of rated voltage applied at one side (primary winding) to circulate rated current on transformer keeping its other side (secondary winding) under short circuit conditions. It is marked on transformer nameplate. EXPLANATION: If we apply rated voltage at primary winding of a transformer keeping its secondary winding short circuited, then amount of current at both windings will be extremely high as compared to the rated current. This current is called short circuit current and its magnitude is very high due to zero impedance offered by the load (secondary winding is short circuited). Consider, V : Rated Primary Voltage of Transformer Z% : Percentage Impedance of Transformer Irated : Rated Primary Current of Transformer Zactual : Actual Impedance of Transformer (referred to primary winding) Based on above explanation, we are applying a percentage (Z %) of rated primary voltage. Therefore applied voltage is equal to V x Z% / 100. This voltage drives rated current in transformer winding. By Ohms Law: Voltage = Current x Actual Impedance V x Z% /100 = Irated x Zactual Z% = Irated Zactual x 100 / V Now, if we reduce the applied voltage on the transformer primary i.e. we apply percentage of rated voltage in transformer primary, current on both windings will also reduce. At a particular percentage of rated voltage, rated current will flow on transformer windings. This percentage of rated voltage at one side of transformer which circulates rated current on transformer windings keeping its other side winding short circuited, is called percentage impedance of transformer.
  • 3. Ashish Kumar Ganguli Date: 21.01.2017 ROLE OF Z% IN SHORT CIRCUIT CALCULATION Percentage impedance of transformer plays extremely vital role is network calculation i.e. short circuit calculation and voltage drop calculation. We can find the short circuit contribution of a transformer as per below explanation: As considered above, secondary winding of transformer is short circuited. Now, If Voltage (V Z% /100) is applied on Transformer Primary, Rated Current (Irated) flows. If Voltage (V) is applied on Transformer Primary, Current (Irated x 100 / Z%) will flow. Therefore, when we apply rated voltage at primary winding of a transformer whose secondary winding is short circuited, short circuit current (Irated x 100 / Z%) will flow on transformer windings. Value of Z% is same for both windings as it is percentage of rated voltage. However value of Irated will be different for primary and secondary winding. Accordingly value of short circuit current will also be different for primary and secondary windings. Short Circuit Current (Isc) = Irated x 100 / Z% If percentage impedance of a transformer is less, its short circuit current will be more which will produce more stress in insulation. This is a negative factor. On the other hand, if percentage impedance of a transformer is less, voltage drop on transformer winding will be less which will facilitate better voltage regulation. This is a positive factor. Therefore, percentage impedance of transformer has to be precisely selected to maintain a proper balance between fault level and voltage regulation. PERMITTED TOLERANCE IN Z% Percentage impedance of transformer is specified at the time of ordering. But it must be noted that IEC 76 permits +/- 10% tolerance in percentage impedance at manufacturer's end. Therefore, if we order a transformer with 8% percentage impedance, its actual percentage impedance after manufacturing may be any value between 7.2% (-10% of 8) to 8.8% (+10% of 8), unless it is specifically agreed with manufacturer at the time of ordering. Tolerance in percentage impedance must be considered for power system calculations and accordingly system fault level & voltage regulation must be finalized.
  • 4. Ashish Kumar Ganguli Date: 21.01.2017 ROLE OF Z% IN PARALLEL OPERATION OF TRANSFORMERS If the ratios of kVA rating to percent impedance of two transformers operating in parallel are equal, they will share equal load. However if ratio is different, they will share unequal load. This may result in overloading of one transformer. In order to analyses this criterion; let us consider two transformers operating in parallel as shown in below diagram. I1 : Load current from transformer 1 I2 : Load current from transformer 2 IL : Total load current (IL = I1 + I2) Z1 : Actual impedance of transformer 1 Z2 : Actual impedance of transformer 2 Z1% : Percentage Impedance of transformer 2 Z2% : Percentage Impedance of transformer 2 kVA1 : kVA rating of transformer 1 kVA2 : kVA rating of transformer 2 kVAL : Total load kVA
  • 5. Ashish Kumar Ganguli Date: 21.01.2017 We know that V x Z% / 100 = Irated Zactual Therefore, Z1 = (V x Z%1)/ (100 x I1) Z2 = (V x Z%2)/ (100 x I2) If we substitute value of actual impedance (Z1 & Z2) as per above equation, we get If we multiply both sides with kV, we get If ratio kVA1 / Z1% and kVA2 / Z2% are equal, then kVA1 and kVA2 will be same. That means, both transformers will share equal load i.e. 50% of total load. This factor must be analyzed before paralleling two transformers to avoid unequal load sharing and overloading of one transformer.