Indonesian Journal of Electrical Engineering and Computer Science
Vol. 8, No. 1, October 2017, pp. 177 ~ 183
DOI: 10.11591/ijeecs.v8.i1.pp177-183  177
Received July 6, 2017; Revised September 1, 2017; Accepted September 13, 2017
Cable Test and Breakdown Voltage Determination of
Joysense Cable Insulation
Muhammad bin Yahya*, Muhammad Nazrolni Azmi bin Izani
Faculty of Electrical Engineering, University Technology of MARA Malaysia, 40450 Shah Alam, Selangor,
Malaysia
*Corresponding author, mohdyahya@salam.uitm.edu.my, nazrolniazmi@hotmail.co.uk
Abstract
Cross-linked Polyethylene (XLPE) has been used as the insulation for polymeric power cables
for its superior advantages. This type of cable insulation are famously known and used for their good
dielectric properties, mechanical properties, thermal properties, and probability to be utilized at high
temperature. This study is of four (4) parts; designing suitable method for cable test, accelerated testing
procedures applied to XLPE insulation for high voltage cables, online partial discharge determination, and
aging test. To study the insulation durability to AC high voltage operation, the breakdown strength and
aging were investigated under different setting of temperature. The breakdown voltages of XLPE were
measured at different temperatures of 300C, 500C and finally at 700C. Lastly, the aging effect of cable
insulation was observed by conducting the AC breakdown voltage test after the aging process. Results
showed that the breakdown voltage and aging of XLPE cables will decrease with increase of temperature
setting.
KeywordsCable Test, AC Breakdown voltage, Aging effect, Thermal stress, Partial Discharges
Copyright © 2017 Institute of Advanced Engineering and Science. All rights reserved.
1. Introduction
Cable plays a vital role to transmit electricity from the generation part to distribution
network. The transmission and distribution networks are using specific cables to distribute the
supply to fulfill the consumers demand [1]. There are many types of cables used in the power
networks. Those cables will be diverse according to their variation of size, length, and usage at
different level of voltages. In fact, cables also have various type of insulation. The usual types of
insulation used in industry nowadays are Polyvinyl chloride (PVC), Polyethylene (PE), Cross-
linked Polyethylene (XLPE), Ethylene Propylene Rubber (EPR) and paper/oil. PE material was
changed by XLPE as a new alternative way [2]. Each of them have their own special
characteristics that later will be chosen by consumers based on their specifications. XLPE
cables can operate at conductor normal temperature of 90
0
C, with 130
0
C being the emergency
condition, and 250
0
C for short circuit condition [3]. However, the cable insulation may
deteriorate due many factors such as electric stress and thermal stress over the lifetime that can
reduce the dielectric strength.
High Voltage (HV) cable is the most significant equipment in transmission line and
distribution network. Thus, the high voltage cable must always be in good condition. They must
have strong durability to withstand stress and should not be torn in short period of time [4]. High
voltage industry now is frequently facing problem to determine the suitable strength capability of
cable to be used at proper place. Researches have been conducted by many groups on
developing the different techniques and tests on testing the properties of cables before the
cables are being installed in the industries, in operating condition of cables in the industries or in
field tests and during the post mortem of cables with failures. The tests have been conducted to
improve the quality and prolong the time services of the cables. This test leads to the better
quality of cables and services in the industries in the future.
Mohammed Hanif proposes “Principles and Applications of Insulation Testing with DC”
where ihe discussed and described the common insulating materials, their application and
desirable properties [5]. The project used several types of test such as Time-Resistance Test,
Step Voltage Test and Discharge Based Test. All of the tests that have been conducted are to
determine and analyze the basic initiators of insulation degradation, to identify the causes and
 ISSN: 2502-4752
IJEECS Vol. 8, No. 1, October 2017 : 177 – 183
178
effects of insulation failures and to test the qualities of the cables insulations. The project shown
that the tests can be used to improve the system performance, system safety, system reliability
and economic asset management although the results shown that the insulation degradation
cannot be eliminated.
Yigang Liu, Chang Xue and Gang Liu, in their paper “Analysis for AC Voltage Withstand
Test of HV XLPE Power Cable” discussed on how effective the AC voltage withstand test were
on exposing all potential defects in cables [6]. The projects were working on to find and analyze
any defect that may be able to occur during the operating, and increasing voltages are being
injected into the cable samples. M.Shafiq, M. Lehtonen, M. Isa and L. Kutt have designed some
tests for their “Online Partial Discharge Diagnostics in Medium Voltage Branched Cable
Networks” project where the project presented a technique on localizing partial discharge for
branched cable network [7]. Due to advance equipment, the project has conducted a test that
was able to detect the location of the partial discharge along the branched cable network. This
project showed that the online discharge determination can be used as a preventative
maintenance tool for cable system.
Cable tests are solutions that deliver information and data from analysis of the cables
that measure the condition of the cables whether the cables are in good condition to be used in
the transmission of electrical power. Hence from this point of interpretation, the breakdown
strength of XLPE insulation type of cables are to be investigated in order to specify the dielectric
strengths and breakdown voltages under different setting of temperature.
This research and study could provide many potential benefits especially to high voltage
industry. It will benefit the industry mostly on economical aspects that will give enhance profits
to the industry, when the cable’s durability and aging conditions were obtained, so they can
make prediction on the cable’s life expectancy. Other than that, the findings of this research
could provide baseline information to future researchers on the properties of breakdown
strength of XLPE type of insulation cable in regard to the aging of these cables. This study will
help them reveal problems and solutions that most of the other researchers were not able to
discover.
To make this study successful, there are 4 goals that must be achieved at the end of
study. First is the cable test designed to be effective to test the breakdown strength of cable
samples. Secondly, to determine the breakdown strength of XLPE insulation type of high
voltage cables under different temperatures, and to determine the aging effect of XLPE
insulation of high voltage cables [8]. Theories stated that the decrease in breakdown voltage for
XLPE cable samples as temperature keep increasing is generally assumed to be the effect of
dwindling aging in XLPE insulation samples. Lastly, the value of partial discharges was
determined during the breakdown tests of the cables.
2. Research Method
2.1 Experiment 1: Cable Test
The cable samples used in the cable tests were Joysense Rare Earth Aluminium XLPE
cables sized 240 mm
2
and 195 mm
2
single cored unarmoured, rated at 0.6/1 kV. The length of
the cable samples were 2 m long. A cable test technique was designed in the High Voltage
Laboratory, Faculty of Electrical Engineering, UiTM, Shah Alam. The AC insulation cable test
was carried out to determine the breakdown voltage or the dielectric strength of the cable
insulation when increasing voltages were injected to the cable sample. In this experiment, the
whole 2 m cable was used.
IJEECS ISSN: 2502-4752 
T Cable Test and Breakdown Voltage Determination of Joysense… (Muhammad bin Yahya)
179
(a) (b)
Figure 1. (a) Schematic diagram of Cable Test set up in High Voltage Laboratory
(b) Actual Cable Test set up in High Voltage Laboratory
The starting AC voltage was 5 kV with increment of 1 kV every 10 seconds until
breakdown was reached. This test was performed on the 240mm
2
cable and repeated with the
195 mm
2
cable. Results were tabulated.
The online partial discharges test is a technique for measuring the damaged that has
taken place in the insulation of the cable when the insulation reached its maximum breakdown
voltage. The sample cable that was injected with increasing voltages until its breakdown voltage
reached has been tapped with earthed wire on the outer insulation, and the online partial
discharges reading can be recorded at the exact moment of the breakdown of the insulation of
the cable. The reading of the online partial discharges will determine whether the cable is
qualified for the real operation in the distribution network.
2.2 Experment 2: Separate Insulation Test at Different Temperatures
The Joysense Rare Earth Aluminium 11 kV XLPE cable sample was used in this
insulation test. The insulation of the 11 kV cable was cut into 5 cm long sections. Then, the PVC
outer cable was removed first followed by the aluminium shield, semi-conductor layer and
conductor. Only the insulation layer and conductor shield was left.
Next, the samples were placed in hot press machine for 5 minutes at pressure of 1000
Psi and temperature setting of 90
o
C. This procedure was performed at Polymer laboratory of
Faculty of Chemical Engineering, UiTM. After the process ended, all of the samples changed
from cylindrical shape to plate-like shape.
Next, the samples were placed at hot press machine for 5 minutes at pressure of 1000
Psi and temperature setting of 90
o
C both of them was trimmed by using knife. There are four
samples overall which can be categorized into two. First category is the stand alone XLPE
(Sample 1) while the other is the XLPE sample with PVC cover (Sample 2).
(a) (b)
Figure 2. (a) XLPE cut sample (Sample 1), (b) XLPE with PVC cover cut sample (Sample 2)
Sample 1 and Sample 2 required a special dielectric test. Since the experiment
required both electrical stress and temperature stress, a suitable AC breakdown test was used
for the experiment. The samples were warmed up to 30
o
C, 50
o
C and 70
o
C. While waiting for the
sample to reach specific temperature value, the preparation of AC breakdown test was
 ISSN: 2502-4752
IJEECS Vol. 8, No. 1, October 2017 : 177 – 183
180
performed. Once it had reached the required temperature, the sample was brought directly to
perform AC breakdown test. All of the procedures were performed at High Voltage laboratory.
Figure 3.Preparation Before Conducting AC Breakdown Test of the samples
All the samples in AC breakdown voltage test were to be conducted by using special
equipment preparation. A point-plane electrode and two guard rings including screws were
used. The point-plane electrode was attached on top of the sample and being sandwiched by
the guard rings and then screwed up to ensure there are no excess air flow at the sample.
The time for voltage injection was set to 15 seconds for every increment of 1 kV to
ensure the proper voltage transfer through the sample. Sample 1 and Sample 2 were subjected
to combination of electrical stress and thermal stress. The measurements were conducted at
30oC, 50oC and 70oC accordingly. The AC breakdown voltage data under different
temperature were recorded and analysed.
Thermal aging procedure had to be performed on all of the samples with duration of
three days. The Temperature (and humidity) Chamber, Platinous J series type was used to
conduct the aging test. Various temperature setting can be set in a day. The chamber was set at
30oC for the first six hours and being increased in three hours to reach 60oC. Then, the
temperature was kept steadily at 60oC for another six hours. Then the temperature was
reduced to 40oC at a steady rate within three hours and kept constant for another six hours.
The cycle was to be repeated for another two days. The same AC breakdown test was
performed on the samples after the three days aging process, and the results were recorded
and analyzed.
3. Results and Analysis
Results of the research from the above experiments were tabulated and analyzed and
discussed.
3.1. Experiment 1: Cable Test Results
Table 1 show that the breakdown voltage of the cable had decreased as the test was
repeated. This happened when the earthed wire was placed at the same position throughout
the test. When the earthed wire was tapped at the different parts of the outer insulation of the
cable (for example, at the middle of the cable), the breakdown voltage of the insulation
remained the same value, which was around 21 kV.
Table 1. AC cable test breakdown voltage result
Test Sample 1 (KV) Sample 2 (KV)
1 21.35 20.6
2 20.52 19.77
3 19.68 18.53
4 14.00 13.76
IJEECS ISSN: 2502-4752 
T Cable Test and Breakdown Voltage Determination of Joysense… (Muhammad bin Yahya)
181
Sample 1: 240 mm
2
0.6/1KV single core unarmoured cable with XLPE, binding
tape and outer sheath insulation
Sample 2: 195 mm
2
0.6/1KV single core unarmoured cable with XLPE, binding
tape and outer sheath insulation
Table 2 showed the readings of the online partial discharge measured. All the
readings were taken during the breakdown voltage of each test. The highest partial
discharges readings were recorded at the first test for both cables with 279 pC for the sample
1 and 280 pC for the sample 2. As the tests were repeated, the readings of the online partial
discharges were observed to be decreasing slightly with the lowest reading being 266 pC for
sample 1 with the breakdown voltage recorded at 14.00 kV, and 265 pC for sample 2 at
13.76 kV.
Table 2. AC cable Partial Discharge result
Test Sample 1 (pC) Sample 2 (pC)
1 279 280
2 270 270
3 269 268
4 266 265
It can be seen that the online partial discharges can be said to be the same for both
samples through the experiments and the values lie between 280-265 pC. These values
provide a good indication of the cable insulation, as the limit values of acceptable level of
partial discharges were way below 500 pC for low to medium voltage cables [9].
3.2. Experment 2: Separate Insulation Test at Different Temperatures Results
AC breakdown voltage was affected by variation of temperature setting. Breakdown
voltage will decrease if the temperature is increased [10].
Table 3 below presents the measured AC breakdown voltage data of all the Sample 1 and
Sample 2 with different setting temperature. The results are shown graphically in Figure 4.
Table 3. Measured AC Breakdown Voltage data at Different Temperatures
Temperature (o
C) 30 50 70
Breakdown Voltage (kV) Sample 1 19.2 18.2 17.2
Sample 2 21.2 20.5 19.2
Breakdown Field Strength
(kV/mm)
Sample 1 9.6 9.1 8.6
Sample 2 10.6 10.25 9.6
Figure 4. AC Breakdown Voltage vs Temperature for Samples 1 and 2
 ISSN: 2502-4752
IJEECS Vol. 8, No. 1, October 2017 : 177 – 183
182
For Sample 1, the value of AC breakdown voltage was 19.2 kV at 30
o
C while at 50
o
C,
the breakdown voltage decreased to 18.2 kV, and to 17.2 kV at 70
o
C. Meanwhile, for Sample 2,
the value of AC breakdown voltage at 30
o
C was 21.2 kV. The value then decreased at 20.5 kV
at 50
o
C, and further decreased at 70
o
C to 19.2 kV.
Table 4. AC breakdown voltage after three days thermal aging
Before aging
Breakdown
Voltage (kV)
After aging
Breakdown
Voltage (kV)
Sample 1 19.2 17.2
Sample 2 21.2 19.2
The AC breakdown voltage reading before and after thermal aging was observed and
compared. The result showed a declination in value of AC breakdown voltage after thermal
aging process. AC breakdown voltage test was conducted on all of the samples before the
aging process started and the values were 19.2 kV and 21.2 kV respectively for Sample 1 and
Sample 2.
Meanwhile, the values of AC breakdown voltages for Sample 1 and Sample 2 were
slightly decreased to 17.2 kV and 19.2 kV respectively after the aging process being
performed. The result showed a reduction of 2 kV for both the samples.
4. Conclusion
Tests have been performed on the Joysense Rare-Earth High-Iron Aluminium Alloy
power cables. Technique for a regular cable test was designed in the High Voltage Laboratory
in UiTM Shah Alam. The results show a positive outcome where the cables which are rated
0.6/1 kV have breakdown voltages of around 21 kV. This is way beyond the insulation
strength designation for a 1 kV cable.
Samples of the insulation materials of the 11 kV Joysense Aluminium power cable
were cut and removed, and tested for its AC breakdown voltage with different temperatures.
The AC breakdown voltage with different temperature showed that the strength of
breakdown voltage will decrease when the temperature was increased, which was between
21.2 kV to 19.2 kV (Sample 2), which looked consistent with Experiment 1, the cable test.
The same goes to AC breakdown voltage after thermal aging of three days which
experienced reduction in AC breakdown voltage value showed that the breakdown voltage
decreased by only 2 kV compared to original insulation before thermal aging.
It can be seen that the online partial discharges were the same for both samples
through the experiments and the values lie between 280-265 pC. These values provide a
good indication of the cable insulation, as the limit values of acceptable level of partial
discharges were way below 500 pC for low to medium voltage cables.
As a conclusion, Joysense Rare-Earth High-Iron Aluminium Alloy power cables are
excellent quality Aluminium alloy cables suitable for use in distribution system, and
commercial and domestic electrical installations such as high-rise condominiums.
Acknowledgement
I would like to express my gratitude and appreciation to Mr Rusdi Baharan, the executive
director of Joysense Cable Sdn Bhd for supplying samples of their Rare-Earth High-Iron
Aluminium Alloy power cables which contribute to the success of this research. I would also like
to thank RMI UiTM Shah Alam for sponsorng the presentation of this paper in this conference
using the Lestari grant 600-IRMI/DANA 5/3/LESTARI (0021/2016).
References
[1] A. Smedberg and D. Wald. The Role of Degassing in XLPE Power, vol. 22, no. 6, pp. 5–16, 2006.
[2] L. Cao and S. Grzybowski. Life-Time Characteristics of EPR Cable Insulation Under Electrical and
Thermal Stresses. pp. 632–635, 2013.
IJEECS ISSN: 2502-4752 
T Cable Test and Breakdown Voltage Determination of Joysense… (Muhammad bin Yahya)
183
[3] P. Mvi et al. XLPE Insulated Power Cables. no. M, 1967.
[4] G. Corporation, Analysis for AC Voltage Withstand Test of HV XLPE Power Cable. vol. 0, pp. 666–
668, 2007.
[5] E. M. Hanif,"Insulation Testing with DC" Current, pp.57-63, 2005.
[6] Y. Liu, C. Xue, and G. Liu. Analysis for AC Voltage Withstand Test for HV XLPE cble. 2007 Int
Conf. Solid Dielectric. ICSD, vol 00, pp. 666-668, 2007.
[7] M. Shafiq, M. Lehtonen, M. Isa and L. Kutt. Online Partial Discharge Diagnostics in Medium
Branched Cable Networks. Int. Conf. Power Eng. Energy Electr. Drives. May, pp246-251, 2013.
[8] L. Cao and S. Grzybowski. Aging Phenomenon of 15 kV EPR Cable Insulation by Electrical and
Thermal Stress. pp. 480–483, 2012.
[9] P. Arnold, Attila Kment, Marek Pipa, and Frantisek Janicek. On-site Partial Discharges
Measurement of XLPE Cables. Transaction on Electrical Engineering, Vol.1 (2012). No. 4.
[10] D. Fournier, “Effect Of Pressure And Temperature On Interfacial Breakdown Between Two
Dielectric Surface,” pp. 229–235.
[11] A. Fazal, M. Hao, A. S. Vaughan, G. Chen, J. Cao, and H. Wang. The effect of composition and
processing on electric characteristics of XLPE in HVDC cable applications. no. June, pp. 19–22,
2016.

Contenu connexe

Tendances

A survey on supercapacitors and their applications
A survey on supercapacitors and their applicationsA survey on supercapacitors and their applications
A survey on supercapacitors and their applicationseSAT Journals
 
Sam cables presentation
Sam cables presentation Sam cables presentation
Sam cables presentation Ankit Joshi
 
Experimental investigation on thermal electric and dielectric characterizatio...
Experimental investigation on thermal electric and dielectric characterizatio...Experimental investigation on thermal electric and dielectric characterizatio...
Experimental investigation on thermal electric and dielectric characterizatio...IAEME Publication
 
Evaluation of Flashover Voltage Levels of Contaminated Hydrophobic Polymer In...
Evaluation of Flashover Voltage Levels of Contaminated Hydrophobic Polymer In...Evaluation of Flashover Voltage Levels of Contaminated Hydrophobic Polymer In...
Evaluation of Flashover Voltage Levels of Contaminated Hydrophobic Polymer In...TELKOMNIKA JOURNAL
 
Networking
NetworkingNetworking
NetworkingRanglaz
 
Power Cables Operation, Maintenance, Location and Fault Detection
Power Cables Operation, Maintenance, Location and Fault DetectionPower Cables Operation, Maintenance, Location and Fault Detection
Power Cables Operation, Maintenance, Location and Fault DetectionLiving Online
 
Wire Manufacturer In Pune - Elcab Conductors
Wire Manufacturer In Pune - Elcab ConductorsWire Manufacturer In Pune - Elcab Conductors
Wire Manufacturer In Pune - Elcab Conductorsbizporto.com
 
Partial Discharges using Variable Frequency PRPDA Technique
Partial Discharges using Variable Frequency PRPDA TechniquePartial Discharges using Variable Frequency PRPDA Technique
Partial Discharges using Variable Frequency PRPDA TechniqueIJCSIS Research Publications
 
IRJET- Dielectric Properties of Titanium Substituted Manganese -Zinc Ferr...
IRJET-  	  Dielectric Properties of Titanium Substituted Manganese -Zinc Ferr...IRJET-  	  Dielectric Properties of Titanium Substituted Manganese -Zinc Ferr...
IRJET- Dielectric Properties of Titanium Substituted Manganese -Zinc Ferr...IRJET Journal
 
Analysis of Stranded Multi-Conductor Cable in Multilayered Dielectric Media
Analysis of Stranded Multi-Conductor Cable in Multilayered Dielectric MediaAnalysis of Stranded Multi-Conductor Cable in Multilayered Dielectric Media
Analysis of Stranded Multi-Conductor Cable in Multilayered Dielectric MediaJimmi James
 
Twisted pair cable
Twisted pair cableTwisted pair cable
Twisted pair cableHareem Naz
 
Study on the effect of the substrate material type and thickness on the perfo...
Study on the effect of the substrate material type and thickness on the perfo...Study on the effect of the substrate material type and thickness on the perfo...
Study on the effect of the substrate material type and thickness on the perfo...TELKOMNIKA JOURNAL
 
IRJET - Efficient Analysis of Different Dielectric Materials
IRJET - Efficient Analysis of Different Dielectric MaterialsIRJET - Efficient Analysis of Different Dielectric Materials
IRJET - Efficient Analysis of Different Dielectric MaterialsIRJET Journal
 
Belden Ieee Paper On Vfd Cables
Belden Ieee Paper On Vfd CablesBelden Ieee Paper On Vfd Cables
Belden Ieee Paper On Vfd Cablescarlhasselbring
 
2020 application of electrochemical impedance spectroscopy to commercial li...
2020   application of electrochemical impedance spectroscopy to commercial li...2020   application of electrochemical impedance spectroscopy to commercial li...
2020 application of electrochemical impedance spectroscopy to commercial li...Ary Assuncao
 
A LITERATURE SURVEY ON ELECTROMAGNETIC SHIELDING
A LITERATURE SURVEY ON ELECTROMAGNETIC SHIELDINGA LITERATURE SURVEY ON ELECTROMAGNETIC SHIELDING
A LITERATURE SURVEY ON ELECTROMAGNETIC SHIELDINGIJEEE
 
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...IRJET Journal
 
IRJET- A Survey Approach: Device for Biosensing Application
IRJET-  	  A Survey Approach: Device for Biosensing ApplicationIRJET-  	  A Survey Approach: Device for Biosensing Application
IRJET- A Survey Approach: Device for Biosensing ApplicationIRJET Journal
 
Electric field effect in the formation of water treeing in mv power cables
Electric field effect in the formation of water treeing in mv power cablesElectric field effect in the formation of water treeing in mv power cables
Electric field effect in the formation of water treeing in mv power cableseSAT Publishing House
 

Tendances (20)

A survey on supercapacitors and their applications
A survey on supercapacitors and their applicationsA survey on supercapacitors and their applications
A survey on supercapacitors and their applications
 
Sam cables presentation
Sam cables presentation Sam cables presentation
Sam cables presentation
 
Experimental investigation on thermal electric and dielectric characterizatio...
Experimental investigation on thermal electric and dielectric characterizatio...Experimental investigation on thermal electric and dielectric characterizatio...
Experimental investigation on thermal electric and dielectric characterizatio...
 
Evaluation of Flashover Voltage Levels of Contaminated Hydrophobic Polymer In...
Evaluation of Flashover Voltage Levels of Contaminated Hydrophobic Polymer In...Evaluation of Flashover Voltage Levels of Contaminated Hydrophobic Polymer In...
Evaluation of Flashover Voltage Levels of Contaminated Hydrophobic Polymer In...
 
Networking
NetworkingNetworking
Networking
 
Power Cables Operation, Maintenance, Location and Fault Detection
Power Cables Operation, Maintenance, Location and Fault DetectionPower Cables Operation, Maintenance, Location and Fault Detection
Power Cables Operation, Maintenance, Location and Fault Detection
 
Wire Manufacturer In Pune - Elcab Conductors
Wire Manufacturer In Pune - Elcab ConductorsWire Manufacturer In Pune - Elcab Conductors
Wire Manufacturer In Pune - Elcab Conductors
 
Partial Discharges using Variable Frequency PRPDA Technique
Partial Discharges using Variable Frequency PRPDA TechniquePartial Discharges using Variable Frequency PRPDA Technique
Partial Discharges using Variable Frequency PRPDA Technique
 
IRJET- Dielectric Properties of Titanium Substituted Manganese -Zinc Ferr...
IRJET-  	  Dielectric Properties of Titanium Substituted Manganese -Zinc Ferr...IRJET-  	  Dielectric Properties of Titanium Substituted Manganese -Zinc Ferr...
IRJET- Dielectric Properties of Titanium Substituted Manganese -Zinc Ferr...
 
Analysis of Stranded Multi-Conductor Cable in Multilayered Dielectric Media
Analysis of Stranded Multi-Conductor Cable in Multilayered Dielectric MediaAnalysis of Stranded Multi-Conductor Cable in Multilayered Dielectric Media
Analysis of Stranded Multi-Conductor Cable in Multilayered Dielectric Media
 
Twisted pair cable
Twisted pair cableTwisted pair cable
Twisted pair cable
 
Study on the effect of the substrate material type and thickness on the perfo...
Study on the effect of the substrate material type and thickness on the perfo...Study on the effect of the substrate material type and thickness on the perfo...
Study on the effect of the substrate material type and thickness on the perfo...
 
Wireless power transfer through metal using inductive link
Wireless power transfer through metal using inductive linkWireless power transfer through metal using inductive link
Wireless power transfer through metal using inductive link
 
IRJET - Efficient Analysis of Different Dielectric Materials
IRJET - Efficient Analysis of Different Dielectric MaterialsIRJET - Efficient Analysis of Different Dielectric Materials
IRJET - Efficient Analysis of Different Dielectric Materials
 
Belden Ieee Paper On Vfd Cables
Belden Ieee Paper On Vfd CablesBelden Ieee Paper On Vfd Cables
Belden Ieee Paper On Vfd Cables
 
2020 application of electrochemical impedance spectroscopy to commercial li...
2020   application of electrochemical impedance spectroscopy to commercial li...2020   application of electrochemical impedance spectroscopy to commercial li...
2020 application of electrochemical impedance spectroscopy to commercial li...
 
A LITERATURE SURVEY ON ELECTROMAGNETIC SHIELDING
A LITERATURE SURVEY ON ELECTROMAGNETIC SHIELDINGA LITERATURE SURVEY ON ELECTROMAGNETIC SHIELDING
A LITERATURE SURVEY ON ELECTROMAGNETIC SHIELDING
 
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...
 
IRJET- A Survey Approach: Device for Biosensing Application
IRJET-  	  A Survey Approach: Device for Biosensing ApplicationIRJET-  	  A Survey Approach: Device for Biosensing Application
IRJET- A Survey Approach: Device for Biosensing Application
 
Electric field effect in the formation of water treeing in mv power cables
Electric field effect in the formation of water treeing in mv power cablesElectric field effect in the formation of water treeing in mv power cables
Electric field effect in the formation of water treeing in mv power cables
 

Similaire à 22 9752 cable paper id 0022 edit septian

Improvement of dielectric strength and properties of cross-linked polyethylene
Improvement of dielectric strength and properties of cross-linked polyethyleneImprovement of dielectric strength and properties of cross-linked polyethylene
Improvement of dielectric strength and properties of cross-linked polyethyleneIJECEIAES
 
Presentation on cables
Presentation on cablesPresentation on cables
Presentation on cablesFaizanAli244
 
Comparative study of power cables and testing as per indian standards
Comparative study of power cables and testing as per indian standardsComparative study of power cables and testing as per indian standards
Comparative study of power cables and testing as per indian standardsIAEME Publication
 
Module 04 - Cables.pptx
Module 04 - Cables.pptxModule 04 - Cables.pptx
Module 04 - Cables.pptxZahid Yousaf
 
Analysis of Co-Axial Cable Response to 700m Long Digital Data Transmission.
Analysis of Co-Axial Cable Response to 700m Long Digital Data Transmission.Analysis of Co-Axial Cable Response to 700m Long Digital Data Transmission.
Analysis of Co-Axial Cable Response to 700m Long Digital Data Transmission.iosrjce
 
Mixed Bonding Method of High Voltage Cable
Mixed Bonding Method of High Voltage CableMixed Bonding Method of High Voltage Cable
Mixed Bonding Method of High Voltage Cableijtsrd
 
MV Cable Catalogue
MV Cable CatalogueMV Cable Catalogue
MV Cable CatalogueRajat Mehta
 
Project on Cable and its classification
Project on Cable and its classificationProject on Cable and its classification
Project on Cable and its classificationSOMNATH DAS
 
composites applications in electrical and electronics
composites applications in electrical and electronicscomposites applications in electrical and electronics
composites applications in electrical and electronicsgirish_raghunathan4488
 
The_insulation_of_HVDC_extruded_cable_sy.pdf
The_insulation_of_HVDC_extruded_cable_sy.pdfThe_insulation_of_HVDC_extruded_cable_sy.pdf
The_insulation_of_HVDC_extruded_cable_sy.pdfAhmed Refai ,M. Sc.,Ph. D
 
Composites in electrical and electronic applications
Composites in electrical and electronic applicationsComposites in electrical and electronic applications
Composites in electrical and electronic applicationsgirish_raghunathan4488
 
Tuning the Ionic and Dielectric Properties of Electrospun Nanocomposite Fiber...
Tuning the Ionic and Dielectric Properties of Electrospun Nanocomposite Fiber...Tuning the Ionic and Dielectric Properties of Electrospun Nanocomposite Fiber...
Tuning the Ionic and Dielectric Properties of Electrospun Nanocomposite Fiber...IJERA Editor
 

Similaire à 22 9752 cable paper id 0022 edit septian (20)

Hipot cable-testing
Hipot cable-testingHipot cable-testing
Hipot cable-testing
 
Underground cables
Underground cablesUnderground cables
Underground cables
 
Improvement of dielectric strength and properties of cross-linked polyethylene
Improvement of dielectric strength and properties of cross-linked polyethyleneImprovement of dielectric strength and properties of cross-linked polyethylene
Improvement of dielectric strength and properties of cross-linked polyethylene
 
Power cables
Power cablesPower cables
Power cables
 
76-09.pdf
76-09.pdf76-09.pdf
76-09.pdf
 
Presentation on cables
Presentation on cablesPresentation on cables
Presentation on cables
 
Comparative study of power cables and testing as per indian standards
Comparative study of power cables and testing as per indian standardsComparative study of power cables and testing as per indian standards
Comparative study of power cables and testing as per indian standards
 
Power house report
Power house reportPower house report
Power house report
 
Power house report
Power house reportPower house report
Power house report
 
Module 04 - Cables.pptx
Module 04 - Cables.pptxModule 04 - Cables.pptx
Module 04 - Cables.pptx
 
Analysis of Co-Axial Cable Response to 700m Long Digital Data Transmission.
Analysis of Co-Axial Cable Response to 700m Long Digital Data Transmission.Analysis of Co-Axial Cable Response to 700m Long Digital Data Transmission.
Analysis of Co-Axial Cable Response to 700m Long Digital Data Transmission.
 
H010625867
H010625867H010625867
H010625867
 
Chapter 8N.pptx
Chapter 8N.pptxChapter 8N.pptx
Chapter 8N.pptx
 
Mixed Bonding Method of High Voltage Cable
Mixed Bonding Method of High Voltage CableMixed Bonding Method of High Voltage Cable
Mixed Bonding Method of High Voltage Cable
 
MV Cable Catalogue
MV Cable CatalogueMV Cable Catalogue
MV Cable Catalogue
 
Project on Cable and its classification
Project on Cable and its classificationProject on Cable and its classification
Project on Cable and its classification
 
composites applications in electrical and electronics
composites applications in electrical and electronicscomposites applications in electrical and electronics
composites applications in electrical and electronics
 
The_insulation_of_HVDC_extruded_cable_sy.pdf
The_insulation_of_HVDC_extruded_cable_sy.pdfThe_insulation_of_HVDC_extruded_cable_sy.pdf
The_insulation_of_HVDC_extruded_cable_sy.pdf
 
Composites in electrical and electronic applications
Composites in electrical and electronic applicationsComposites in electrical and electronic applications
Composites in electrical and electronic applications
 
Tuning the Ionic and Dielectric Properties of Electrospun Nanocomposite Fiber...
Tuning the Ionic and Dielectric Properties of Electrospun Nanocomposite Fiber...Tuning the Ionic and Dielectric Properties of Electrospun Nanocomposite Fiber...
Tuning the Ionic and Dielectric Properties of Electrospun Nanocomposite Fiber...
 

Plus de IAESIJEECS

08 20314 electronic doorbell...
08 20314 electronic doorbell...08 20314 electronic doorbell...
08 20314 electronic doorbell...IAESIJEECS
 
07 20278 augmented reality...
07 20278 augmented reality...07 20278 augmented reality...
07 20278 augmented reality...IAESIJEECS
 
06 17443 an neuro fuzzy...
06 17443 an neuro fuzzy...06 17443 an neuro fuzzy...
06 17443 an neuro fuzzy...IAESIJEECS
 
05 20275 computational solution...
05 20275 computational solution...05 20275 computational solution...
05 20275 computational solution...IAESIJEECS
 
04 20268 power loss reduction ...
04 20268 power loss reduction ...04 20268 power loss reduction ...
04 20268 power loss reduction ...IAESIJEECS
 
03 20237 arduino based gas-
03 20237 arduino based gas-03 20237 arduino based gas-
03 20237 arduino based gas-IAESIJEECS
 
02 20274 improved ichi square...
02 20274 improved ichi square...02 20274 improved ichi square...
02 20274 improved ichi square...IAESIJEECS
 
01 20264 diminution of real power...
01 20264 diminution of real power...01 20264 diminution of real power...
01 20264 diminution of real power...IAESIJEECS
 
08 20272 academic insight on application
08 20272 academic insight on application08 20272 academic insight on application
08 20272 academic insight on applicationIAESIJEECS
 
07 20252 cloud computing survey
07 20252 cloud computing survey07 20252 cloud computing survey
07 20252 cloud computing surveyIAESIJEECS
 
06 20273 37746-1-ed
06 20273 37746-1-ed06 20273 37746-1-ed
06 20273 37746-1-edIAESIJEECS
 
05 20261 real power loss reduction
05 20261 real power loss reduction05 20261 real power loss reduction
05 20261 real power loss reductionIAESIJEECS
 
04 20259 real power loss
04 20259 real power loss04 20259 real power loss
04 20259 real power lossIAESIJEECS
 
03 20270 true power loss reduction
03 20270 true power loss reduction03 20270 true power loss reduction
03 20270 true power loss reductionIAESIJEECS
 
02 15034 neural network
02 15034 neural network02 15034 neural network
02 15034 neural networkIAESIJEECS
 
01 8445 speech enhancement
01 8445 speech enhancement01 8445 speech enhancement
01 8445 speech enhancementIAESIJEECS
 
08 17079 ijict
08 17079 ijict08 17079 ijict
08 17079 ijictIAESIJEECS
 
07 20269 ijict
07 20269 ijict07 20269 ijict
07 20269 ijictIAESIJEECS
 
06 10154 ijict
06 10154 ijict06 10154 ijict
06 10154 ijictIAESIJEECS
 
05 20255 ijict
05 20255 ijict05 20255 ijict
05 20255 ijictIAESIJEECS
 

Plus de IAESIJEECS (20)

08 20314 electronic doorbell...
08 20314 electronic doorbell...08 20314 electronic doorbell...
08 20314 electronic doorbell...
 
07 20278 augmented reality...
07 20278 augmented reality...07 20278 augmented reality...
07 20278 augmented reality...
 
06 17443 an neuro fuzzy...
06 17443 an neuro fuzzy...06 17443 an neuro fuzzy...
06 17443 an neuro fuzzy...
 
05 20275 computational solution...
05 20275 computational solution...05 20275 computational solution...
05 20275 computational solution...
 
04 20268 power loss reduction ...
04 20268 power loss reduction ...04 20268 power loss reduction ...
04 20268 power loss reduction ...
 
03 20237 arduino based gas-
03 20237 arduino based gas-03 20237 arduino based gas-
03 20237 arduino based gas-
 
02 20274 improved ichi square...
02 20274 improved ichi square...02 20274 improved ichi square...
02 20274 improved ichi square...
 
01 20264 diminution of real power...
01 20264 diminution of real power...01 20264 diminution of real power...
01 20264 diminution of real power...
 
08 20272 academic insight on application
08 20272 academic insight on application08 20272 academic insight on application
08 20272 academic insight on application
 
07 20252 cloud computing survey
07 20252 cloud computing survey07 20252 cloud computing survey
07 20252 cloud computing survey
 
06 20273 37746-1-ed
06 20273 37746-1-ed06 20273 37746-1-ed
06 20273 37746-1-ed
 
05 20261 real power loss reduction
05 20261 real power loss reduction05 20261 real power loss reduction
05 20261 real power loss reduction
 
04 20259 real power loss
04 20259 real power loss04 20259 real power loss
04 20259 real power loss
 
03 20270 true power loss reduction
03 20270 true power loss reduction03 20270 true power loss reduction
03 20270 true power loss reduction
 
02 15034 neural network
02 15034 neural network02 15034 neural network
02 15034 neural network
 
01 8445 speech enhancement
01 8445 speech enhancement01 8445 speech enhancement
01 8445 speech enhancement
 
08 17079 ijict
08 17079 ijict08 17079 ijict
08 17079 ijict
 
07 20269 ijict
07 20269 ijict07 20269 ijict
07 20269 ijict
 
06 10154 ijict
06 10154 ijict06 10154 ijict
06 10154 ijict
 
05 20255 ijict
05 20255 ijict05 20255 ijict
05 20255 ijict
 

Dernier

Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Standamitlee9823
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756dollysharma2066
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapRishantSharmaFr
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayEpec Engineered Technologies
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfRagavanV2
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptxJIT KUMAR GUPTA
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptDineshKumar4165
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueBhangaleSonal
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdfKamal Acharya
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...soginsider
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...tanu pandey
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXssuser89054b
 

Dernier (20)

Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdf
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 

22 9752 cable paper id 0022 edit septian

  • 1. Indonesian Journal of Electrical Engineering and Computer Science Vol. 8, No. 1, October 2017, pp. 177 ~ 183 DOI: 10.11591/ijeecs.v8.i1.pp177-183  177 Received July 6, 2017; Revised September 1, 2017; Accepted September 13, 2017 Cable Test and Breakdown Voltage Determination of Joysense Cable Insulation Muhammad bin Yahya*, Muhammad Nazrolni Azmi bin Izani Faculty of Electrical Engineering, University Technology of MARA Malaysia, 40450 Shah Alam, Selangor, Malaysia *Corresponding author, mohdyahya@salam.uitm.edu.my, nazrolniazmi@hotmail.co.uk Abstract Cross-linked Polyethylene (XLPE) has been used as the insulation for polymeric power cables for its superior advantages. This type of cable insulation are famously known and used for their good dielectric properties, mechanical properties, thermal properties, and probability to be utilized at high temperature. This study is of four (4) parts; designing suitable method for cable test, accelerated testing procedures applied to XLPE insulation for high voltage cables, online partial discharge determination, and aging test. To study the insulation durability to AC high voltage operation, the breakdown strength and aging were investigated under different setting of temperature. The breakdown voltages of XLPE were measured at different temperatures of 300C, 500C and finally at 700C. Lastly, the aging effect of cable insulation was observed by conducting the AC breakdown voltage test after the aging process. Results showed that the breakdown voltage and aging of XLPE cables will decrease with increase of temperature setting. KeywordsCable Test, AC Breakdown voltage, Aging effect, Thermal stress, Partial Discharges Copyright © 2017 Institute of Advanced Engineering and Science. All rights reserved. 1. Introduction Cable plays a vital role to transmit electricity from the generation part to distribution network. The transmission and distribution networks are using specific cables to distribute the supply to fulfill the consumers demand [1]. There are many types of cables used in the power networks. Those cables will be diverse according to their variation of size, length, and usage at different level of voltages. In fact, cables also have various type of insulation. The usual types of insulation used in industry nowadays are Polyvinyl chloride (PVC), Polyethylene (PE), Cross- linked Polyethylene (XLPE), Ethylene Propylene Rubber (EPR) and paper/oil. PE material was changed by XLPE as a new alternative way [2]. Each of them have their own special characteristics that later will be chosen by consumers based on their specifications. XLPE cables can operate at conductor normal temperature of 90 0 C, with 130 0 C being the emergency condition, and 250 0 C for short circuit condition [3]. However, the cable insulation may deteriorate due many factors such as electric stress and thermal stress over the lifetime that can reduce the dielectric strength. High Voltage (HV) cable is the most significant equipment in transmission line and distribution network. Thus, the high voltage cable must always be in good condition. They must have strong durability to withstand stress and should not be torn in short period of time [4]. High voltage industry now is frequently facing problem to determine the suitable strength capability of cable to be used at proper place. Researches have been conducted by many groups on developing the different techniques and tests on testing the properties of cables before the cables are being installed in the industries, in operating condition of cables in the industries or in field tests and during the post mortem of cables with failures. The tests have been conducted to improve the quality and prolong the time services of the cables. This test leads to the better quality of cables and services in the industries in the future. Mohammed Hanif proposes “Principles and Applications of Insulation Testing with DC” where ihe discussed and described the common insulating materials, their application and desirable properties [5]. The project used several types of test such as Time-Resistance Test, Step Voltage Test and Discharge Based Test. All of the tests that have been conducted are to determine and analyze the basic initiators of insulation degradation, to identify the causes and
  • 2.  ISSN: 2502-4752 IJEECS Vol. 8, No. 1, October 2017 : 177 – 183 178 effects of insulation failures and to test the qualities of the cables insulations. The project shown that the tests can be used to improve the system performance, system safety, system reliability and economic asset management although the results shown that the insulation degradation cannot be eliminated. Yigang Liu, Chang Xue and Gang Liu, in their paper “Analysis for AC Voltage Withstand Test of HV XLPE Power Cable” discussed on how effective the AC voltage withstand test were on exposing all potential defects in cables [6]. The projects were working on to find and analyze any defect that may be able to occur during the operating, and increasing voltages are being injected into the cable samples. M.Shafiq, M. Lehtonen, M. Isa and L. Kutt have designed some tests for their “Online Partial Discharge Diagnostics in Medium Voltage Branched Cable Networks” project where the project presented a technique on localizing partial discharge for branched cable network [7]. Due to advance equipment, the project has conducted a test that was able to detect the location of the partial discharge along the branched cable network. This project showed that the online discharge determination can be used as a preventative maintenance tool for cable system. Cable tests are solutions that deliver information and data from analysis of the cables that measure the condition of the cables whether the cables are in good condition to be used in the transmission of electrical power. Hence from this point of interpretation, the breakdown strength of XLPE insulation type of cables are to be investigated in order to specify the dielectric strengths and breakdown voltages under different setting of temperature. This research and study could provide many potential benefits especially to high voltage industry. It will benefit the industry mostly on economical aspects that will give enhance profits to the industry, when the cable’s durability and aging conditions were obtained, so they can make prediction on the cable’s life expectancy. Other than that, the findings of this research could provide baseline information to future researchers on the properties of breakdown strength of XLPE type of insulation cable in regard to the aging of these cables. This study will help them reveal problems and solutions that most of the other researchers were not able to discover. To make this study successful, there are 4 goals that must be achieved at the end of study. First is the cable test designed to be effective to test the breakdown strength of cable samples. Secondly, to determine the breakdown strength of XLPE insulation type of high voltage cables under different temperatures, and to determine the aging effect of XLPE insulation of high voltage cables [8]. Theories stated that the decrease in breakdown voltage for XLPE cable samples as temperature keep increasing is generally assumed to be the effect of dwindling aging in XLPE insulation samples. Lastly, the value of partial discharges was determined during the breakdown tests of the cables. 2. Research Method 2.1 Experiment 1: Cable Test The cable samples used in the cable tests were Joysense Rare Earth Aluminium XLPE cables sized 240 mm 2 and 195 mm 2 single cored unarmoured, rated at 0.6/1 kV. The length of the cable samples were 2 m long. A cable test technique was designed in the High Voltage Laboratory, Faculty of Electrical Engineering, UiTM, Shah Alam. The AC insulation cable test was carried out to determine the breakdown voltage or the dielectric strength of the cable insulation when increasing voltages were injected to the cable sample. In this experiment, the whole 2 m cable was used.
  • 3. IJEECS ISSN: 2502-4752  T Cable Test and Breakdown Voltage Determination of Joysense… (Muhammad bin Yahya) 179 (a) (b) Figure 1. (a) Schematic diagram of Cable Test set up in High Voltage Laboratory (b) Actual Cable Test set up in High Voltage Laboratory The starting AC voltage was 5 kV with increment of 1 kV every 10 seconds until breakdown was reached. This test was performed on the 240mm 2 cable and repeated with the 195 mm 2 cable. Results were tabulated. The online partial discharges test is a technique for measuring the damaged that has taken place in the insulation of the cable when the insulation reached its maximum breakdown voltage. The sample cable that was injected with increasing voltages until its breakdown voltage reached has been tapped with earthed wire on the outer insulation, and the online partial discharges reading can be recorded at the exact moment of the breakdown of the insulation of the cable. The reading of the online partial discharges will determine whether the cable is qualified for the real operation in the distribution network. 2.2 Experment 2: Separate Insulation Test at Different Temperatures The Joysense Rare Earth Aluminium 11 kV XLPE cable sample was used in this insulation test. The insulation of the 11 kV cable was cut into 5 cm long sections. Then, the PVC outer cable was removed first followed by the aluminium shield, semi-conductor layer and conductor. Only the insulation layer and conductor shield was left. Next, the samples were placed in hot press machine for 5 minutes at pressure of 1000 Psi and temperature setting of 90 o C. This procedure was performed at Polymer laboratory of Faculty of Chemical Engineering, UiTM. After the process ended, all of the samples changed from cylindrical shape to plate-like shape. Next, the samples were placed at hot press machine for 5 minutes at pressure of 1000 Psi and temperature setting of 90 o C both of them was trimmed by using knife. There are four samples overall which can be categorized into two. First category is the stand alone XLPE (Sample 1) while the other is the XLPE sample with PVC cover (Sample 2). (a) (b) Figure 2. (a) XLPE cut sample (Sample 1), (b) XLPE with PVC cover cut sample (Sample 2) Sample 1 and Sample 2 required a special dielectric test. Since the experiment required both electrical stress and temperature stress, a suitable AC breakdown test was used for the experiment. The samples were warmed up to 30 o C, 50 o C and 70 o C. While waiting for the sample to reach specific temperature value, the preparation of AC breakdown test was
  • 4.  ISSN: 2502-4752 IJEECS Vol. 8, No. 1, October 2017 : 177 – 183 180 performed. Once it had reached the required temperature, the sample was brought directly to perform AC breakdown test. All of the procedures were performed at High Voltage laboratory. Figure 3.Preparation Before Conducting AC Breakdown Test of the samples All the samples in AC breakdown voltage test were to be conducted by using special equipment preparation. A point-plane electrode and two guard rings including screws were used. The point-plane electrode was attached on top of the sample and being sandwiched by the guard rings and then screwed up to ensure there are no excess air flow at the sample. The time for voltage injection was set to 15 seconds for every increment of 1 kV to ensure the proper voltage transfer through the sample. Sample 1 and Sample 2 were subjected to combination of electrical stress and thermal stress. The measurements were conducted at 30oC, 50oC and 70oC accordingly. The AC breakdown voltage data under different temperature were recorded and analysed. Thermal aging procedure had to be performed on all of the samples with duration of three days. The Temperature (and humidity) Chamber, Platinous J series type was used to conduct the aging test. Various temperature setting can be set in a day. The chamber was set at 30oC for the first six hours and being increased in three hours to reach 60oC. Then, the temperature was kept steadily at 60oC for another six hours. Then the temperature was reduced to 40oC at a steady rate within three hours and kept constant for another six hours. The cycle was to be repeated for another two days. The same AC breakdown test was performed on the samples after the three days aging process, and the results were recorded and analyzed. 3. Results and Analysis Results of the research from the above experiments were tabulated and analyzed and discussed. 3.1. Experiment 1: Cable Test Results Table 1 show that the breakdown voltage of the cable had decreased as the test was repeated. This happened when the earthed wire was placed at the same position throughout the test. When the earthed wire was tapped at the different parts of the outer insulation of the cable (for example, at the middle of the cable), the breakdown voltage of the insulation remained the same value, which was around 21 kV. Table 1. AC cable test breakdown voltage result Test Sample 1 (KV) Sample 2 (KV) 1 21.35 20.6 2 20.52 19.77 3 19.68 18.53 4 14.00 13.76
  • 5. IJEECS ISSN: 2502-4752  T Cable Test and Breakdown Voltage Determination of Joysense… (Muhammad bin Yahya) 181 Sample 1: 240 mm 2 0.6/1KV single core unarmoured cable with XLPE, binding tape and outer sheath insulation Sample 2: 195 mm 2 0.6/1KV single core unarmoured cable with XLPE, binding tape and outer sheath insulation Table 2 showed the readings of the online partial discharge measured. All the readings were taken during the breakdown voltage of each test. The highest partial discharges readings were recorded at the first test for both cables with 279 pC for the sample 1 and 280 pC for the sample 2. As the tests were repeated, the readings of the online partial discharges were observed to be decreasing slightly with the lowest reading being 266 pC for sample 1 with the breakdown voltage recorded at 14.00 kV, and 265 pC for sample 2 at 13.76 kV. Table 2. AC cable Partial Discharge result Test Sample 1 (pC) Sample 2 (pC) 1 279 280 2 270 270 3 269 268 4 266 265 It can be seen that the online partial discharges can be said to be the same for both samples through the experiments and the values lie between 280-265 pC. These values provide a good indication of the cable insulation, as the limit values of acceptable level of partial discharges were way below 500 pC for low to medium voltage cables [9]. 3.2. Experment 2: Separate Insulation Test at Different Temperatures Results AC breakdown voltage was affected by variation of temperature setting. Breakdown voltage will decrease if the temperature is increased [10]. Table 3 below presents the measured AC breakdown voltage data of all the Sample 1 and Sample 2 with different setting temperature. The results are shown graphically in Figure 4. Table 3. Measured AC Breakdown Voltage data at Different Temperatures Temperature (o C) 30 50 70 Breakdown Voltage (kV) Sample 1 19.2 18.2 17.2 Sample 2 21.2 20.5 19.2 Breakdown Field Strength (kV/mm) Sample 1 9.6 9.1 8.6 Sample 2 10.6 10.25 9.6 Figure 4. AC Breakdown Voltage vs Temperature for Samples 1 and 2
  • 6.  ISSN: 2502-4752 IJEECS Vol. 8, No. 1, October 2017 : 177 – 183 182 For Sample 1, the value of AC breakdown voltage was 19.2 kV at 30 o C while at 50 o C, the breakdown voltage decreased to 18.2 kV, and to 17.2 kV at 70 o C. Meanwhile, for Sample 2, the value of AC breakdown voltage at 30 o C was 21.2 kV. The value then decreased at 20.5 kV at 50 o C, and further decreased at 70 o C to 19.2 kV. Table 4. AC breakdown voltage after three days thermal aging Before aging Breakdown Voltage (kV) After aging Breakdown Voltage (kV) Sample 1 19.2 17.2 Sample 2 21.2 19.2 The AC breakdown voltage reading before and after thermal aging was observed and compared. The result showed a declination in value of AC breakdown voltage after thermal aging process. AC breakdown voltage test was conducted on all of the samples before the aging process started and the values were 19.2 kV and 21.2 kV respectively for Sample 1 and Sample 2. Meanwhile, the values of AC breakdown voltages for Sample 1 and Sample 2 were slightly decreased to 17.2 kV and 19.2 kV respectively after the aging process being performed. The result showed a reduction of 2 kV for both the samples. 4. Conclusion Tests have been performed on the Joysense Rare-Earth High-Iron Aluminium Alloy power cables. Technique for a regular cable test was designed in the High Voltage Laboratory in UiTM Shah Alam. The results show a positive outcome where the cables which are rated 0.6/1 kV have breakdown voltages of around 21 kV. This is way beyond the insulation strength designation for a 1 kV cable. Samples of the insulation materials of the 11 kV Joysense Aluminium power cable were cut and removed, and tested for its AC breakdown voltage with different temperatures. The AC breakdown voltage with different temperature showed that the strength of breakdown voltage will decrease when the temperature was increased, which was between 21.2 kV to 19.2 kV (Sample 2), which looked consistent with Experiment 1, the cable test. The same goes to AC breakdown voltage after thermal aging of three days which experienced reduction in AC breakdown voltage value showed that the breakdown voltage decreased by only 2 kV compared to original insulation before thermal aging. It can be seen that the online partial discharges were the same for both samples through the experiments and the values lie between 280-265 pC. These values provide a good indication of the cable insulation, as the limit values of acceptable level of partial discharges were way below 500 pC for low to medium voltage cables. As a conclusion, Joysense Rare-Earth High-Iron Aluminium Alloy power cables are excellent quality Aluminium alloy cables suitable for use in distribution system, and commercial and domestic electrical installations such as high-rise condominiums. Acknowledgement I would like to express my gratitude and appreciation to Mr Rusdi Baharan, the executive director of Joysense Cable Sdn Bhd for supplying samples of their Rare-Earth High-Iron Aluminium Alloy power cables which contribute to the success of this research. I would also like to thank RMI UiTM Shah Alam for sponsorng the presentation of this paper in this conference using the Lestari grant 600-IRMI/DANA 5/3/LESTARI (0021/2016). References [1] A. Smedberg and D. Wald. The Role of Degassing in XLPE Power, vol. 22, no. 6, pp. 5–16, 2006. [2] L. Cao and S. Grzybowski. Life-Time Characteristics of EPR Cable Insulation Under Electrical and Thermal Stresses. pp. 632–635, 2013.
  • 7. IJEECS ISSN: 2502-4752  T Cable Test and Breakdown Voltage Determination of Joysense… (Muhammad bin Yahya) 183 [3] P. Mvi et al. XLPE Insulated Power Cables. no. M, 1967. [4] G. Corporation, Analysis for AC Voltage Withstand Test of HV XLPE Power Cable. vol. 0, pp. 666– 668, 2007. [5] E. M. Hanif,"Insulation Testing with DC" Current, pp.57-63, 2005. [6] Y. Liu, C. Xue, and G. Liu. Analysis for AC Voltage Withstand Test for HV XLPE cble. 2007 Int Conf. Solid Dielectric. ICSD, vol 00, pp. 666-668, 2007. [7] M. Shafiq, M. Lehtonen, M. Isa and L. Kutt. Online Partial Discharge Diagnostics in Medium Branched Cable Networks. Int. Conf. Power Eng. Energy Electr. Drives. May, pp246-251, 2013. [8] L. Cao and S. Grzybowski. Aging Phenomenon of 15 kV EPR Cable Insulation by Electrical and Thermal Stress. pp. 480–483, 2012. [9] P. Arnold, Attila Kment, Marek Pipa, and Frantisek Janicek. On-site Partial Discharges Measurement of XLPE Cables. Transaction on Electrical Engineering, Vol.1 (2012). No. 4. [10] D. Fournier, “Effect Of Pressure And Temperature On Interfacial Breakdown Between Two Dielectric Surface,” pp. 229–235. [11] A. Fazal, M. Hao, A. S. Vaughan, G. Chen, J. Cao, and H. Wang. The effect of composition and processing on electric characteristics of XLPE in HVDC cable applications. no. June, pp. 19–22, 2016.