ELECTRICAL MACHINES AND DRIVES
REPORT ON
Dynamic Behavior of the Doubly Fed
Induction Generator during Three-
Phase Voltage Dips
2015
SUBMITTED BY:
EBBIN DANIEL
U80380223
1
ABSTRACT
The use of doubly fed induction generators (DFIGs) in large wind turbines
has become quite common over the last few years. These machines
provide variable speed and are driven with a power converter which is
sized for a small percentage of the turbine-rated power.
A drawback of the DFIG is that it is very sensitive to grid disturbances,
especially to voltage dips. However, the operation of the machine in these
situations has only been studied in the literature by means of simulations.
This paper develops a theoretical analysis of the dynamic behavior of the
induction machine during three-phase voltage dips.
The proposed analysis contributes to understanding the causes of the
problem and represents a very useful tool to improve the existing solutions
and propose new alternatives. Experimental results are in good agreement
with those obtained theoretically and validate the proposed analysis.
2
CONTENTS
CHAPTER NO: TITLE PAGE NO
1 INTRODUCTION
1.1 Introduction 3
1.2 Proposed system 4
2 PROJECT DESCRIPTION
2.1 System description
2.1.1 Doubly fed induction generator 5
2.1.1.1 Wind Turbine 6
2.1.1.2 Asynchronous machine 7
2.1.2 Rotor Side Control 9
2.1.3 Stator Side Control 11
2.2 Model description 13
2.3 Output 15
3 CONCLUSION 16
4 REFERENCES 17
3
CHAPTER-1
INTRODUCTION
WIND energy is now considered as an actual alternative to the conventional and
pollutant energy sources such as oil, gas, and coal. Global wind power reached
47GWin 2004 with a 20% growth in this year. Due to their advantageous
characteristics, most of the grid-connected wind turbines operate at a variable
speed. Among the different alternatives to obtain variable speed, the doubly fed
induction generator (DFIG) is the most used.
The control of the machine can be carried out with a converter that is sized for a
power around 25%–35% of the rated power of the turbine. In addition to the
common advantages in cost, size, and weight associated with a small converter,
losses are also smaller compared to the system with a full power converter
connected to the stator.
However, wind turbines based on the DFIG are very sensitive to grid disturbances,
especially to voltage dips. The abrupt drop of the grid voltage causes overvoltage
and overcurrent in the rotor windings that could even destroy the converter if no
protection elements are included.
This paper tries to help understand the dynamic behavior of the DFIG in the typical
case of three-phase voltage dips.
In this paper, simulation tests and experiments are proposed on a small machine.
The objective is to provide a qualitative analysis of the system behavior during
voltage dips.
4
PROPOSED SYSTEM
Doubly fed induction generators are electric generators that have windings on
both stationary and rotating parts, where both windings transfer significant active
power between shaft and electrical system.
Here the stator winding is directly connected to the three-phase grid and the three-
phase rotor winding is fed from the grid through a rotating or static frequency
converter.
It has two converters which can be used for control,
 The Rotor side converter and the
 Grid side converter.
5
CHAPTER 2
PROJECT DESCRIPTION
2.1 SYSTEM DESCRIPTION
2.1.1 DOUBLY FED INDUCTION GENERATOR
Wind turbines using a doubly-fed induction generator (DFIG) consist of a wound
rotor induction generator and an AC/DC/AC converter modeled by voltage
sources. The stator winding is connected directly to the grid while the rotor is fed
at variable frequency through the AC/DC/AC converter. The DFIG technology
allows extracting maximum energy from the wind for low wind speeds by
optimizing the turbine speed, while minimizing mechanical stresses on the turbine
during gusts of wind.
6
2.1.1.1 WIND TURBINE
The model is based on the steady-state power characteristics of the turbine. The
stiffness of the drive train is infinite and the friction factor and the inertia of the
turbine must be combined with those of the generator coupled to the turbine. The
output power of the turbine is given by the following equation.
Inputs and Outputs
Generator speed (pu)
Simulink input of the generator speed in pu based on the nominal speed of the
Generator.
Pitch angle (deg)
Simulink input of the pitch angle.
Wind speed (m/s)
Simulink input of the wind speed in m/s.
Tm (pu)
Simulink output of the mechanical torque of the wind turbine, in pu of the nominal
generator torque. The nominal torque of the generator is based on the nominal
generator power and speed.
7
2.1.1.2 ASYNCHRONOUS MACHINE
The Asynchronous Machine block implements a three-phase asynchronous
machine (wound rotor, single squirrel-cage or double squirrel-cage). It operates in
either generator or motor mode. The mode of operation is dictated by the sign of
the mechanical torque:
If Tm is positive, the machine acts as a motor.
If Tm is negative, the machine acts as a generator.
The electrical part of the machine is represented by a fourth-order (or sixth-order
for the double squirrel-cage machine) state-space model, and the mechanical part
by a second-order system.
All electrical variables and parameters are referred to the stator. This is indicated
by the prime signs in the machine equations given below. All stator and rotor
quantities are in the arbitrary
two-axis reference frame
(dq frame). The subscripts used
are defined as follows:
8
Electrical system for wound rotor:
Parameters:
9
2.1.2 ROTOR SIDE CONTROL
During nonsevere fault conditions, the crowbar protection is not activated and the
rotor windings of a doubly fed induction generator (DFIG) are still excited by the
ac/dc/ac converter.
In these cases, the dynamic response of a rotor-side converter (RSC) has a large
influence on the fault current characteristics of the DFIG.
The synchronous dq reference frame is chosen to model the DFIG based on the
fifth-order two-axis representation, and the model of DFIG is commonly known as
“Park model”.
Using generator convention for the stator windings and motor convention for the
rotor windings, the voltage equations and flux linkage equations are expressed as:
10
Consequently, the voltage equations of the rotor windings can be rewritten as:
Then, the voltage control equations of the rotor windings can be expressed with
application of the PI controller and feed forward compensation:
11
2.1.3 GRID SIDE CONTROL
Concerning the use of three-phase series RL choke between stator- and stator-side
converter, a cross-coupling model is required to derive the voltage signal of stator-
side converter.
where the subscripts sc and ch denote the variables of stator side converter and
choke.
The coupling part of voltage signals V 2 ch and V 2qch is expressed as,
12
GRID SIDE CONTROL:
13
2.2 MODEL DECRIPTION
Wind turbines using a doubly-fed induction generator (DFIG) consist of a wound
rotor induction generator and an AC/DC/AC converter modeled by voltage
sources.
The stator winding is connected directly to the grid while the rotor is fed at
variable frequency through the AC/DC/AC converter.
14
The voltage dips is provided by two different sources each connected by a circuit
breaker which opens and closes at t= 0.45s.
The system is controlled by two converters:
 Rotor side converter
 Grid side converter
The DFIG system consists of the wind turbine, the drive train which is connected
to the Asynchronous motor, which acts as a generator where the value of Tm is
negative.
15
2.3 OUTPUT
Three Phase Grid Voltage after a voltage dip:
Stator Flux after a voltage dip:
16
CHAPTER 3
CONCLUSION
A theoretical analysis of the behavior of the DFIG during full- or partial-
voltage dips has been proposed.
The paper proposes a rigorous approach to these complex transient
phenomena in order to analyze the dynamic behavior of a doubly fed
induction machine during a voltage dip.
The analysis is, in particular, for an instantaneous voltage dip, which is
representative of the abrupt voltage dips that usually appear in real
situations.
It opens interesting prospects toward the search of hardware and
software solutions allowing to face the grid interactions of DFIG-based
wind power systems.
17
4. REFERENCE
Dynamic Behavior of the Doubly Fed Induction
Generator During Three-Phase Voltage Dips
Jes´us L´opez, Member, IEEE, Pablo Sanchis, Member, IEEE, Xavier Roboam, Member, IEEE,
and Luis Marroyo, Member, IEEE
Simulation Comparisons and Implementation of
Induction Generator Wind Power Systems
Yu Zou, Malik E. Elbuluk, Senior Member, IEEE, and Yilmaz Sozer, Member, IEEE
Study of Fault Current Characteristics of the DFIG :
Considering Dynamic Response of the RSC
Xiangping Kong, Zhe Zhang, Xianggen Yin, Member, IEEE, and Minghao Wen

Contenu connexe

Tendances

Electrical drives and_controls
Electrical drives and_controlsElectrical drives and_controls
Electrical drives and_controlsddsshukla
 
Betz speed limit and tip speed ratio
Betz speed limit and tip speed ratioBetz speed limit and tip speed ratio
Betz speed limit and tip speed ratioSonuKumarBairwa
 
Induction motor
Induction motorInduction motor
Induction motorAL- AMIN
 
Synchronous generators
Synchronous generatorsSynchronous generators
Synchronous generatorstes4
 
analysis of induction motor drive using slip power recovery scheme
analysis of induction motor drive using slip power recovery schemeanalysis of induction motor drive using slip power recovery scheme
analysis of induction motor drive using slip power recovery schemePrakash_13209
 
induction generator final.pptx
induction generator final.pptxinduction generator final.pptx
induction generator final.pptxTEJAS MANIAR
 
Inter Connected Power System(Turbine Speed Governing Mechanism )
Inter Connected Power System(Turbine Speed Governing Mechanism)Inter Connected Power System(Turbine Speed Governing Mechanism)
Inter Connected Power System(Turbine Speed Governing Mechanism )Raviraj solanki
 
speed control of three phase induction motor
speed control of three phase induction motorspeed control of three phase induction motor
speed control of three phase induction motorAshvani Shukla
 
Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1JayakalyanReddy
 
Converter control in wind turbine
Converter control in wind turbineConverter control in wind turbine
Converter control in wind turbineSonuKumarBairwa
 
Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...
Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...
Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...Naila Syed
 

Tendances (20)

Electrical drives and_controls
Electrical drives and_controlsElectrical drives and_controls
Electrical drives and_controls
 
Unit 4
Unit 4Unit 4
Unit 4
 
Betz speed limit and tip speed ratio
Betz speed limit and tip speed ratioBetz speed limit and tip speed ratio
Betz speed limit and tip speed ratio
 
Induction motor
Induction motorInduction motor
Induction motor
 
Lec # 03 equivalent circuit of a synchronous generator
Lec # 03 equivalent circuit of a synchronous generatorLec # 03 equivalent circuit of a synchronous generator
Lec # 03 equivalent circuit of a synchronous generator
 
Induction motor
Induction motorInduction motor
Induction motor
 
Synchronous generator
Synchronous generatorSynchronous generator
Synchronous generator
 
Synchronous generators
Synchronous generatorsSynchronous generators
Synchronous generators
 
analysis of induction motor drive using slip power recovery scheme
analysis of induction motor drive using slip power recovery schemeanalysis of induction motor drive using slip power recovery scheme
analysis of induction motor drive using slip power recovery scheme
 
Induction machines
Induction machinesInduction machines
Induction machines
 
induction generator final.pptx
induction generator final.pptxinduction generator final.pptx
induction generator final.pptx
 
Inter Connected Power System(Turbine Speed Governing Mechanism )
Inter Connected Power System(Turbine Speed Governing Mechanism)Inter Connected Power System(Turbine Speed Governing Mechanism)
Inter Connected Power System(Turbine Speed Governing Mechanism )
 
Synchronous generator
Synchronous generatorSynchronous generator
Synchronous generator
 
speed control of three phase induction motor
speed control of three phase induction motorspeed control of three phase induction motor
speed control of three phase induction motor
 
Overview of different wind generator systems and their comparison
Overview of different wind generator systems and their comparisonOverview of different wind generator systems and their comparison
Overview of different wind generator systems and their comparison
 
PMSM
PMSMPMSM
PMSM
 
Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1
 
Converter control in wind turbine
Converter control in wind turbineConverter control in wind turbine
Converter control in wind turbine
 
SYNCHRONOUS MACHINES
SYNCHRONOUS MACHINESSYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES
 
Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...
Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...
Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...
 

En vedette

improved reactive power capability of grid connected doubly fed induction gen...
improved reactive power capability of grid connected doubly fed induction gen...improved reactive power capability of grid connected doubly fed induction gen...
improved reactive power capability of grid connected doubly fed induction gen...vinay kumar mali
 
Improved reactive power capability with grid connected doubly fed induction g...
Improved reactive power capability with grid connected doubly fed induction g...Improved reactive power capability with grid connected doubly fed induction g...
Improved reactive power capability with grid connected doubly fed induction g...Uday Wankar
 
Dynamic response of grid connected wind turbine with dfig
Dynamic response of grid connected wind turbine with dfigDynamic response of grid connected wind turbine with dfig
Dynamic response of grid connected wind turbine with dfigJose SanLeandro
 
Power electronics in Wind Turbine Systems
Power electronics in Wind Turbine SystemsPower electronics in Wind Turbine Systems
Power electronics in Wind Turbine SystemsManasa K
 
Independent Control Of Active And Reactive Powers From DFIG By Logic Fuzzy
Independent Control Of Active And Reactive Powers From DFIG By Logic FuzzyIndependent Control Of Active And Reactive Powers From DFIG By Logic Fuzzy
Independent Control Of Active And Reactive Powers From DFIG By Logic FuzzyIJRES Journal
 
Capacity building 2010 day 2 yehia shankir sweg
Capacity building 2010 day 2 yehia shankir swegCapacity building 2010 day 2 yehia shankir sweg
Capacity building 2010 day 2 yehia shankir swegRCREEE
 
Dynamic behavior of DFIG wind turbine under grid fault conditions (1)
Dynamic behavior of DFIG wind turbine under grid fault conditions (1)Dynamic behavior of DFIG wind turbine under grid fault conditions (1)
Dynamic behavior of DFIG wind turbine under grid fault conditions (1)Asoka Technologies
 
Modeling and simulation of dfig to grid connected wind power generation using...
Modeling and simulation of dfig to grid connected wind power generation using...Modeling and simulation of dfig to grid connected wind power generation using...
Modeling and simulation of dfig to grid connected wind power generation using...IAEME Publication
 
DFIG control of WECS using indirect matrix converter
DFIG control of WECS using indirect matrix converter DFIG control of WECS using indirect matrix converter
DFIG control of WECS using indirect matrix converter Kuldeep Behera
 
Mtech IEEE Conference Presentation
Mtech IEEE Conference PresentationMtech IEEE Conference Presentation
Mtech IEEE Conference PresentationJanardhan Reddy
 
Power electronics technology in wind turbine system
Power electronics technology in wind turbine systemPower electronics technology in wind turbine system
Power electronics technology in wind turbine systempranavi kasina
 
Power control of a wind energy conversion system
Power control of a wind energy conversion systemPower control of a wind energy conversion system
Power control of a wind energy conversion system7597861730
 
Advance Power Electronic Converters for Renewable Energy Systems
Advance Power Electronic Converters for Renewable Energy SystemsAdvance Power Electronic Converters for Renewable Energy Systems
Advance Power Electronic Converters for Renewable Energy SystemsTexas A&M University
 
Mfc based doubled fed induction generator in wind energy conversion system
Mfc based doubled fed induction generator in wind energy conversion systemMfc based doubled fed induction generator in wind energy conversion system
Mfc based doubled fed induction generator in wind energy conversion systemnagarajaan
 
Fuzzy Logic Final Report
Fuzzy Logic Final ReportFuzzy Logic Final Report
Fuzzy Logic Final ReportShikhar Agarwal
 
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSEditor IJMTER
 
IEEE Background presentation
IEEE Background  presentationIEEE Background  presentation
IEEE Background presentationArief Gunawan
 
Design and Simulation Analysis of Outer Stator Inner Rotor DFIG by 2d and 3d ...
Design and Simulation Analysis of Outer Stator Inner Rotor DFIG by 2d and 3d ...Design and Simulation Analysis of Outer Stator Inner Rotor DFIG by 2d and 3d ...
Design and Simulation Analysis of Outer Stator Inner Rotor DFIG by 2d and 3d ...Mellah Hacene
 

En vedette (20)

improved reactive power capability of grid connected doubly fed induction gen...
improved reactive power capability of grid connected doubly fed induction gen...improved reactive power capability of grid connected doubly fed induction gen...
improved reactive power capability of grid connected doubly fed induction gen...
 
Improved reactive power capability with grid connected doubly fed induction g...
Improved reactive power capability with grid connected doubly fed induction g...Improved reactive power capability with grid connected doubly fed induction g...
Improved reactive power capability with grid connected doubly fed induction g...
 
Dynamic response of grid connected wind turbine with dfig
Dynamic response of grid connected wind turbine with dfigDynamic response of grid connected wind turbine with dfig
Dynamic response of grid connected wind turbine with dfig
 
Power electronics in Wind Turbine Systems
Power electronics in Wind Turbine SystemsPower electronics in Wind Turbine Systems
Power electronics in Wind Turbine Systems
 
Independent Control Of Active And Reactive Powers From DFIG By Logic Fuzzy
Independent Control Of Active And Reactive Powers From DFIG By Logic FuzzyIndependent Control Of Active And Reactive Powers From DFIG By Logic Fuzzy
Independent Control Of Active And Reactive Powers From DFIG By Logic Fuzzy
 
Capacity building 2010 day 2 yehia shankir sweg
Capacity building 2010 day 2 yehia shankir swegCapacity building 2010 day 2 yehia shankir sweg
Capacity building 2010 day 2 yehia shankir sweg
 
Dynamic behavior of DFIG wind turbine under grid fault conditions (1)
Dynamic behavior of DFIG wind turbine under grid fault conditions (1)Dynamic behavior of DFIG wind turbine under grid fault conditions (1)
Dynamic behavior of DFIG wind turbine under grid fault conditions (1)
 
Modeling and simulation of dfig to grid connected wind power generation using...
Modeling and simulation of dfig to grid connected wind power generation using...Modeling and simulation of dfig to grid connected wind power generation using...
Modeling and simulation of dfig to grid connected wind power generation using...
 
DFIG control of WECS using indirect matrix converter
DFIG control of WECS using indirect matrix converter DFIG control of WECS using indirect matrix converter
DFIG control of WECS using indirect matrix converter
 
236 rakhi
236 rakhi236 rakhi
236 rakhi
 
Mtech IEEE Conference Presentation
Mtech IEEE Conference PresentationMtech IEEE Conference Presentation
Mtech IEEE Conference Presentation
 
Power electronics technology in wind turbine system
Power electronics technology in wind turbine systemPower electronics technology in wind turbine system
Power electronics technology in wind turbine system
 
Power control of a wind energy conversion system
Power control of a wind energy conversion systemPower control of a wind energy conversion system
Power control of a wind energy conversion system
 
Advance Power Electronic Converters for Renewable Energy Systems
Advance Power Electronic Converters for Renewable Energy SystemsAdvance Power Electronic Converters for Renewable Energy Systems
Advance Power Electronic Converters for Renewable Energy Systems
 
Mfc based doubled fed induction generator in wind energy conversion system
Mfc based doubled fed induction generator in wind energy conversion systemMfc based doubled fed induction generator in wind energy conversion system
Mfc based doubled fed induction generator in wind energy conversion system
 
Wind Energy
Wind EnergyWind Energy
Wind Energy
 
Fuzzy Logic Final Report
Fuzzy Logic Final ReportFuzzy Logic Final Report
Fuzzy Logic Final Report
 
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
 
IEEE Background presentation
IEEE Background  presentationIEEE Background  presentation
IEEE Background presentation
 
Design and Simulation Analysis of Outer Stator Inner Rotor DFIG by 2d and 3d ...
Design and Simulation Analysis of Outer Stator Inner Rotor DFIG by 2d and 3d ...Design and Simulation Analysis of Outer Stator Inner Rotor DFIG by 2d and 3d ...
Design and Simulation Analysis of Outer Stator Inner Rotor DFIG by 2d and 3d ...
 

Similaire à DFIG_report

International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Load Frequency Control of DFIG-isolated and Grid Connected Mode
Load Frequency Control of DFIG-isolated and Grid Connected ModeLoad Frequency Control of DFIG-isolated and Grid Connected Mode
Load Frequency Control of DFIG-isolated and Grid Connected ModeIJAPEJOURNAL
 
International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)inventionjournals
 
doubley fed induction motor
doubley fed induction motordoubley fed induction motor
doubley fed induction motorusic123
 
dfigppt-221029141308-fdd782dd.pptx
dfigppt-221029141308-fdd782dd.pptxdfigppt-221029141308-fdd782dd.pptx
dfigppt-221029141308-fdd782dd.pptxSudeepgowda16
 
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...ecij
 
International Refereed Journal of Engineering and Science (IRJES)
International Refereed Journal of Engineering and Science (IRJES)International Refereed Journal of Engineering and Science (IRJES)
International Refereed Journal of Engineering and Science (IRJES)irjes
 
IRJET- Decoupled Control Technique of DFIG with Dual PWM Converters for Wind ...
IRJET- Decoupled Control Technique of DFIG with Dual PWM Converters for Wind ...IRJET- Decoupled Control Technique of DFIG with Dual PWM Converters for Wind ...
IRJET- Decoupled Control Technique of DFIG with Dual PWM Converters for Wind ...IRJET Journal
 
Improved reactive power capability with grid connected doubly fed induction g...
Improved reactive power capability with grid connected doubly fed induction g...Improved reactive power capability with grid connected doubly fed induction g...
Improved reactive power capability with grid connected doubly fed induction g...Uday Wankar
 
C04011117
C04011117C04011117
C04011117IJMER
 
Fault Analysis of DFIG under Grid Disturbances
Fault Analysis of DFIG under Grid DisturbancesFault Analysis of DFIG under Grid Disturbances
Fault Analysis of DFIG under Grid DisturbancesIJERA Editor
 

Similaire à DFIG_report (20)

Mh3621022106
Mh3621022106Mh3621022106
Mh3621022106
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Load Frequency Control of DFIG-isolated and Grid Connected Mode
Load Frequency Control of DFIG-isolated and Grid Connected ModeLoad Frequency Control of DFIG-isolated and Grid Connected Mode
Load Frequency Control of DFIG-isolated and Grid Connected Mode
 
International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)
 
doubley fed induction motor
doubley fed induction motordoubley fed induction motor
doubley fed induction motor
 
Ijtra130511
Ijtra130511Ijtra130511
Ijtra130511
 
G010234652
G010234652G010234652
G010234652
 
dfigppt-221029141308-fdd782dd.pptx
dfigppt-221029141308-fdd782dd.pptxdfigppt-221029141308-fdd782dd.pptx
dfigppt-221029141308-fdd782dd.pptx
 
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
 
International Refereed Journal of Engineering and Science (IRJES)
International Refereed Journal of Engineering and Science (IRJES)International Refereed Journal of Engineering and Science (IRJES)
International Refereed Journal of Engineering and Science (IRJES)
 
IRJET- Decoupled Control Technique of DFIG with Dual PWM Converters for Wind ...
IRJET- Decoupled Control Technique of DFIG with Dual PWM Converters for Wind ...IRJET- Decoupled Control Technique of DFIG with Dual PWM Converters for Wind ...
IRJET- Decoupled Control Technique of DFIG with Dual PWM Converters for Wind ...
 
Improved reactive power capability with grid connected doubly fed induction g...
Improved reactive power capability with grid connected doubly fed induction g...Improved reactive power capability with grid connected doubly fed induction g...
Improved reactive power capability with grid connected doubly fed induction g...
 
Evaluation of Synchronization and MPPT Algorithms in a DFIG Wind Turbine Cont...
Evaluation of Synchronization and MPPT Algorithms in a DFIG Wind Turbine Cont...Evaluation of Synchronization and MPPT Algorithms in a DFIG Wind Turbine Cont...
Evaluation of Synchronization and MPPT Algorithms in a DFIG Wind Turbine Cont...
 
D03701028034
D03701028034D03701028034
D03701028034
 
Seminar2
Seminar2Seminar2
Seminar2
 
C04011117
C04011117C04011117
C04011117
 
C04011117
C04011117C04011117
C04011117
 
Matlab Modeling and Simulation of DFIG with Dump Resistor during Faulty Condi...
Matlab Modeling and Simulation of DFIG with Dump Resistor during Faulty Condi...Matlab Modeling and Simulation of DFIG with Dump Resistor during Faulty Condi...
Matlab Modeling and Simulation of DFIG with Dump Resistor during Faulty Condi...
 
Fault Analysis of DFIG under Grid Disturbances
Fault Analysis of DFIG under Grid DisturbancesFault Analysis of DFIG under Grid Disturbances
Fault Analysis of DFIG under Grid Disturbances
 
40220140505011
4022014050501140220140505011
40220140505011
 

Plus de ebbin daniel

Plus de ebbin daniel (11)

nov1
nov1nov1
nov1
 
oct17
oct17oct17
oct17
 
Ebbin_oct11
Ebbin_oct11Ebbin_oct11
Ebbin_oct11
 
Ebbin_oct3
Ebbin_oct3Ebbin_oct3
Ebbin_oct3
 
New Microsoft PowerPoint Presentation
New Microsoft PowerPoint PresentationNew Microsoft PowerPoint Presentation
New Microsoft PowerPoint Presentation
 
TCIL_PROJECT
TCIL_PROJECTTCIL_PROJECT
TCIL_PROJECT
 
POWER ELECTRONICS
POWER ELECTRONICSPOWER ELECTRONICS
POWER ELECTRONICS
 
Presentation1
Presentation1Presentation1
Presentation1
 
EDS_REPORT_FINAL
EDS_REPORT_FINALEDS_REPORT_FINAL
EDS_REPORT_FINAL
 
tremron_ebbin
tremron_ebbintremron_ebbin
tremron_ebbin
 
TREMRON_PROJECT_summer
TREMRON_PROJECT_summerTREMRON_PROJECT_summer
TREMRON_PROJECT_summer
 

DFIG_report

  • 1. ELECTRICAL MACHINES AND DRIVES REPORT ON Dynamic Behavior of the Doubly Fed Induction Generator during Three- Phase Voltage Dips 2015 SUBMITTED BY: EBBIN DANIEL U80380223
  • 2. 1 ABSTRACT The use of doubly fed induction generators (DFIGs) in large wind turbines has become quite common over the last few years. These machines provide variable speed and are driven with a power converter which is sized for a small percentage of the turbine-rated power. A drawback of the DFIG is that it is very sensitive to grid disturbances, especially to voltage dips. However, the operation of the machine in these situations has only been studied in the literature by means of simulations. This paper develops a theoretical analysis of the dynamic behavior of the induction machine during three-phase voltage dips. The proposed analysis contributes to understanding the causes of the problem and represents a very useful tool to improve the existing solutions and propose new alternatives. Experimental results are in good agreement with those obtained theoretically and validate the proposed analysis.
  • 3. 2 CONTENTS CHAPTER NO: TITLE PAGE NO 1 INTRODUCTION 1.1 Introduction 3 1.2 Proposed system 4 2 PROJECT DESCRIPTION 2.1 System description 2.1.1 Doubly fed induction generator 5 2.1.1.1 Wind Turbine 6 2.1.1.2 Asynchronous machine 7 2.1.2 Rotor Side Control 9 2.1.3 Stator Side Control 11 2.2 Model description 13 2.3 Output 15 3 CONCLUSION 16 4 REFERENCES 17
  • 4. 3 CHAPTER-1 INTRODUCTION WIND energy is now considered as an actual alternative to the conventional and pollutant energy sources such as oil, gas, and coal. Global wind power reached 47GWin 2004 with a 20% growth in this year. Due to their advantageous characteristics, most of the grid-connected wind turbines operate at a variable speed. Among the different alternatives to obtain variable speed, the doubly fed induction generator (DFIG) is the most used. The control of the machine can be carried out with a converter that is sized for a power around 25%–35% of the rated power of the turbine. In addition to the common advantages in cost, size, and weight associated with a small converter, losses are also smaller compared to the system with a full power converter connected to the stator. However, wind turbines based on the DFIG are very sensitive to grid disturbances, especially to voltage dips. The abrupt drop of the grid voltage causes overvoltage and overcurrent in the rotor windings that could even destroy the converter if no protection elements are included. This paper tries to help understand the dynamic behavior of the DFIG in the typical case of three-phase voltage dips. In this paper, simulation tests and experiments are proposed on a small machine. The objective is to provide a qualitative analysis of the system behavior during voltage dips.
  • 5. 4 PROPOSED SYSTEM Doubly fed induction generators are electric generators that have windings on both stationary and rotating parts, where both windings transfer significant active power between shaft and electrical system. Here the stator winding is directly connected to the three-phase grid and the three- phase rotor winding is fed from the grid through a rotating or static frequency converter. It has two converters which can be used for control,  The Rotor side converter and the  Grid side converter.
  • 6. 5 CHAPTER 2 PROJECT DESCRIPTION 2.1 SYSTEM DESCRIPTION 2.1.1 DOUBLY FED INDUCTION GENERATOR Wind turbines using a doubly-fed induction generator (DFIG) consist of a wound rotor induction generator and an AC/DC/AC converter modeled by voltage sources. The stator winding is connected directly to the grid while the rotor is fed at variable frequency through the AC/DC/AC converter. The DFIG technology allows extracting maximum energy from the wind for low wind speeds by optimizing the turbine speed, while minimizing mechanical stresses on the turbine during gusts of wind.
  • 7. 6 2.1.1.1 WIND TURBINE The model is based on the steady-state power characteristics of the turbine. The stiffness of the drive train is infinite and the friction factor and the inertia of the turbine must be combined with those of the generator coupled to the turbine. The output power of the turbine is given by the following equation. Inputs and Outputs Generator speed (pu) Simulink input of the generator speed in pu based on the nominal speed of the Generator. Pitch angle (deg) Simulink input of the pitch angle. Wind speed (m/s) Simulink input of the wind speed in m/s. Tm (pu) Simulink output of the mechanical torque of the wind turbine, in pu of the nominal generator torque. The nominal torque of the generator is based on the nominal generator power and speed.
  • 8. 7 2.1.1.2 ASYNCHRONOUS MACHINE The Asynchronous Machine block implements a three-phase asynchronous machine (wound rotor, single squirrel-cage or double squirrel-cage). It operates in either generator or motor mode. The mode of operation is dictated by the sign of the mechanical torque: If Tm is positive, the machine acts as a motor. If Tm is negative, the machine acts as a generator. The electrical part of the machine is represented by a fourth-order (or sixth-order for the double squirrel-cage machine) state-space model, and the mechanical part by a second-order system. All electrical variables and parameters are referred to the stator. This is indicated by the prime signs in the machine equations given below. All stator and rotor quantities are in the arbitrary two-axis reference frame (dq frame). The subscripts used are defined as follows:
  • 9. 8 Electrical system for wound rotor: Parameters:
  • 10. 9 2.1.2 ROTOR SIDE CONTROL During nonsevere fault conditions, the crowbar protection is not activated and the rotor windings of a doubly fed induction generator (DFIG) are still excited by the ac/dc/ac converter. In these cases, the dynamic response of a rotor-side converter (RSC) has a large influence on the fault current characteristics of the DFIG. The synchronous dq reference frame is chosen to model the DFIG based on the fifth-order two-axis representation, and the model of DFIG is commonly known as “Park model”. Using generator convention for the stator windings and motor convention for the rotor windings, the voltage equations and flux linkage equations are expressed as:
  • 11. 10 Consequently, the voltage equations of the rotor windings can be rewritten as: Then, the voltage control equations of the rotor windings can be expressed with application of the PI controller and feed forward compensation:
  • 12. 11 2.1.3 GRID SIDE CONTROL Concerning the use of three-phase series RL choke between stator- and stator-side converter, a cross-coupling model is required to derive the voltage signal of stator- side converter. where the subscripts sc and ch denote the variables of stator side converter and choke. The coupling part of voltage signals V 2 ch and V 2qch is expressed as,
  • 14. 13 2.2 MODEL DECRIPTION Wind turbines using a doubly-fed induction generator (DFIG) consist of a wound rotor induction generator and an AC/DC/AC converter modeled by voltage sources. The stator winding is connected directly to the grid while the rotor is fed at variable frequency through the AC/DC/AC converter.
  • 15. 14 The voltage dips is provided by two different sources each connected by a circuit breaker which opens and closes at t= 0.45s. The system is controlled by two converters:  Rotor side converter  Grid side converter The DFIG system consists of the wind turbine, the drive train which is connected to the Asynchronous motor, which acts as a generator where the value of Tm is negative.
  • 16. 15 2.3 OUTPUT Three Phase Grid Voltage after a voltage dip: Stator Flux after a voltage dip:
  • 17. 16 CHAPTER 3 CONCLUSION A theoretical analysis of the behavior of the DFIG during full- or partial- voltage dips has been proposed. The paper proposes a rigorous approach to these complex transient phenomena in order to analyze the dynamic behavior of a doubly fed induction machine during a voltage dip. The analysis is, in particular, for an instantaneous voltage dip, which is representative of the abrupt voltage dips that usually appear in real situations. It opens interesting prospects toward the search of hardware and software solutions allowing to face the grid interactions of DFIG-based wind power systems.
  • 18. 17 4. REFERENCE Dynamic Behavior of the Doubly Fed Induction Generator During Three-Phase Voltage Dips Jes´us L´opez, Member, IEEE, Pablo Sanchis, Member, IEEE, Xavier Roboam, Member, IEEE, and Luis Marroyo, Member, IEEE Simulation Comparisons and Implementation of Induction Generator Wind Power Systems Yu Zou, Malik E. Elbuluk, Senior Member, IEEE, and Yilmaz Sozer, Member, IEEE Study of Fault Current Characteristics of the DFIG : Considering Dynamic Response of the RSC Xiangping Kong, Zhe Zhang, Xianggen Yin, Member, IEEE, and Minghao Wen