© 2013 UTC Fire & Security. All rights reserved. 1 / 6 P/N 3101077 • REV 05 • REB 23JAN13
SB4U Analog Audible Detector Base
Installation Sheet
EN FR
EN: Installation Sheet
Operation
The SB4U Analog Audible Detector Base adds an audible
output function to the listed compatible detectors. The base
can operate as an independent local alarm, or as part of a
zone or system alarm with synchronized audible output.
The output of this detector base is field-configurable for output
tone (steady or temporal) and output volume (low dBA or high
dBA).
Depending on the system supporting the device loop, the base
can:
• Follow the state of the device it supports
• Be controlled and configured for other operating modes
through front panel programming or the configuration utility
The base uses the same address and programming label as
the detector it supports.
Installation
Cautions
• To avoid accidental damage to the control panel,
disconnect all power before wiring the unit.
• Electrical supervision requires the wire run to be broken at
each terminal. Do not loop the signaling circuit field wires
around the terminals.
Note: Always connect the base to a continuous voltage,
whether the output tone is set to steady or temporal.
Sleeping rooms: In sleeping areas, use the high dBA output
and temporal tone settings. However, if the control panel is
producing the three-tone temporal evacuation signal, then the
high dBA output and steady tone settings are permissible.
AB4G-SB: When using the AB4G-SB box, install a reinforcing
plate at every knockout. (Reinforcing plates are included with
the box.) Remove the knockout first and then slide the
reinforcing plate into the plastic housing. After the plate is in
place, install the conduit connector and nut. See Figure 1.
Typically, the base is configured to produce a high dBA
temporal tone and is connected to a notification appliance
circuit that outputs a continuous 24 VDC signal. If the
notification appliance circuit outputs a temporal signal,
configure the tone setting on the base for steady.
To install the base:
1. The unit default is for high dBA output. To set the output to
low dBA, cut the circuit board trace as marked on the back
of the PC board. See Figure 3.
2. The unit default is for temporal pattern output. To set the
output to steady tone, cut the circuit board trace as
marked on the back of the PC board. See Figure 3.
3. Select and install a compatible electrical box, and bring
the field wiring into the box.
4. Install the trim ring and secure using screws. The trim ring
is included with the SB4U base. See Figure 2.
5. Make all wiring connections as shown in Figure 3.
6. Attach the base plate to the electrical box using the
screws provided with the electrical box.
7. Attach the trim ring to the base plate. Align the marks on
the trim ring and base plate, press the trim ring onto the
base plate, and then rotate the trim ring until it locks into
place.
8. Attach the desired detector to the base. Align the arrows
on the detector and trim ring, press the detector into the
base, and then rotate the detector until it locks into place.
9. Apply power and activate the unit to verify that it is
operating properly.
2 / 6 P/N 3101077 • REV 05 • REB 23JAN13
Figure 1: AB4G-SB box installation
1
2
3
4
5
6
7
1. Conduit connector
2. AB4G-SB electrical box
3. Lock tab
4. Trim rings
5. Screw
6. Nut
7. Reinforcing plate
Figure 2: Base installation
1. Detector
2. Trim ring
3. Screw
4. Base plate
5. Compatible electrical box
Wiring
Wire in accordance with NFPA 72 and CAN/ULC-S524. Be
sure to observe the polarity of the terminals on the terminal
block as shown in the diagram.
Break the wire run at each terminal. Do not loop signaling
circuit field wires around terminals.
Refer to the applicable technical reference manual for
application diagrams.
Note: Shielded wire is required only in environments with very
high electrical noise. When you use shielded cable, follow
these recommendations:
• Shield connection to and from the base must be
continuous and must be insulated from ground. Insulate
the shield using tape.
• For Class B wiring, there is no shield connection to ground
at the last device.
Figure 3: Output configuration and wiring diagram
4
SLC + SLC +
AUX_RISER + AUX_RISER +
SLC −
SLC −
AUX_RISER − AUX_RISER −
1. AUX-RISER IN (from power supply or previous base)
2. Volume setting: default is high volume; cut per item 4 for low
volume
3. Tone setting: default is temporal pattern; cut per item 4 for steady
tone
4. To configure output volume or tone, cut the circuit board as
shown
5. AUX_RISER OUT To next base or EOL relay
6. SLC OUT to next intelligent addressable device
7. SLC IN from intelligent addressable controller or previous device
P/N 3101077 • REV 05 • REB 23JAN13 3 / 6
Table 1: Operating current in mA (RMS)
Voltage Low dBA High dBA
16 VDC 17 28
24 VDC 24 41
33 VDC 31 52
16 VFWR 41 48
24 VFWR 51 60
33 VFWR 60 66
VDC = Volts direct current, regulated and filtered
VFWR = Volts full wave rectified
Table 2: Sound level output (dBA) per CAN/ULC-S525
Signal Voltage (VDC) Low dBA High dBA
Reverberant room per UL 464 [1]
Temporal 16 71.3 77.2
24 75.0 79.8
33 77.7 81.5
Steady 16 75.8 80.5
24 79.2 84.1
33 82.0 86.0
Reverberant room per UL 268 [2]
Temporal 16 77.3 83.2
24 81.0 85.8
33 83.7 87.5
Steady 16 81.8 86.5
24 85.2 90.1
33 88.0 92.0
[1] For UL 464 applications, low dBA settings are for private mode only
[2] For UL 268 applications, the high setting must be used for
evacuation
Table 3: Audible directional characteristics
Angle (degrees) Output sound pressure level
90 (reference) 0 dBA
80 and 100 −3 dBA
70 and 110 −6 dBA
Horizontal axis and veritical axis reflect the same pattern
Table 4: Sound pressure level per CAN/ULC-S525
Signal Voltage High dBA Low dBA
Temporal Reg. 24 VDC 95 91
Reg. 24
VFWR
99 95
Steady Reg. 24 VDC 93 89
Reg. 24
VFWR
96 92
Maintenance
Do not change the factory-applied finish.
Specifications
Operating voltage (sounder
power)
24 VDC or 24 VFWR
Current
Operating
Supervisory
See Table 1
DC = 1.46 mA, FWR = 2.15 mA
Default settings
Output volume
Output tone
High dBA
Temporal pattern
Sound level output
UL
ULC
See Table 2
See Table 4
Temporal pattern 0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off,
0.5 s on, 1.5 s off, repeat cycle
Compatible detectors FX-PD, E-PD, FX-PHD, E-PHD,
FX-HD, E-HD, V-PS, V-PHS, V-HRD,
and V-HFD
Compatible electrical boxes AB4G-SB surface box for audible
base
North American 4 in. square x
2-1/2 in. (64 mm) deep box
Standard European 100 mm² box
Wire size 12 to 18 AWG (0.75 to 2.5mm²)
Sizes 16 and 18 AWG are preferred
Base diameter 6.0 in. (152 mm)
Height from box (including
detector)
2.58 in. (66 mm)
Maximum distance from
ceiling (wall mount)
12 in. (305 mm)
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
Storage temperature range –4 to 140°F (–20 to 60°C)
Regulatory information
Manufacturer Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA
Year of
manufacture
The first two digits of the DATE MFG number
(located on the product identification label) are
the year of manufacture.
UL/ULC rating Regulated 24 DC or 24 FWR
North American
standards
Meets: UL 268, UL 464, CAN/ULC-S525, and
CAN/ULC-S529
Follow: CSA C22.1 and CAN/ULC-S524.
This device is prohibited from being installed in a
dwelling unit as defined in the National Building
Code of Canada.
Contact information
For contact information, see www.edwardsutcfs.com.
4 / 6 P/N 3101077 • REV 05 • REB 23JAN13
FR : Fiche D'Installation
Fonctionnement
La base audible analogique SB4U pour détecteur est conçue
pour ajouter une fonction audible aux détecteurs compatibles
répertoriés. Elle peut fonctionner en tant qu’alarme locale
indépendante ou comme partie d’une zone ou d’un système
doté de sorties audibles synchronisées.
Fonctionnement de la base selon le système supportant la
boucle du dispositif :
• Il peut suivre l’état du dispositif qu’il supporte
• Il peut être contrôlé et configuré pour d’autres modes de
fonctionnement en programmant le panneau avant ou
l’unité de configuration
La sortie de la base audible analogique SB4U peut être
configurée sur place pour la tonalité de sortie (statique ou
temporelle) et le volume de sortie (dBA faible ou élevé).
La base ne requiert pas d’adresse séparée parce qu’elle partage
la même que celle à laquelle elle est branchée.
Installation
Avertissements
• Pour éviter tout dommage accidentel au panneau,
débranchez toute alimentation électrique avant de câbler
le dispositif.
• La supervision électrique exige que le câblage soit
interrompu à chaque borne. Ne faites pas de boucle
autour des bornes avec les câbles du champ du circuit de
signalisation.
La basse doit être branchée à un voltage continu que la sortie
de la tonalité soit réglée à statique ou temporelle.
Chambres à coucher : Dans les lieux pour dormir, on doit
utiliser le réglage de sortie dBA élevée et la tonalité temporelle.
Cependant, si le panneau de commande d’alarme incendie
produit un signal d’évacuation à trois tonalités temporelles,
alors on peut utiliser le réglage d’une sortie dBA élevée et
d’une tonalité statique.
AB4G-SB : Lorsque vous utilisez un coffret électrique
AB4G-SB, installez une plaque de renfort à chacune des
alvéoles défonçables que vous utilisez. En premier, enlevez
l’alvéole puis glissez la plaque de renfort dans le boîtier en
plastique. Une fois la plaque en place, installez le connecteur
de conduit ainsi que l’écrou comme illustré. La plaque de
renfort est incluse avec le coffret AB4G-SB.
Installation de la base :
1. Par défaut, l’appareil est réglé à une sortie dBA élevée.
Pour régler la sortie à un DBA faible, coupez le tracé
métallique de la carte de circuits imprimés comme marqué
au dos de celle-ci. Voir Figure 3.
2. Par défaut, l’appareil est réglé pour une sortie temporelle.
Pour régler la sortie à une tonalité statique, coupez le
tracé métallique de la carte de circuits imprimés comme
marqué au dos de celle-ci. Voir Figure 3.
3. Installez un coffret électrique compatible, puis tirez tout le
filage à l’intérieur.
4. Installez l’anneau de garniture et fixez solidement avec les
vis. L’anneau de garniture est inclus avec la base SB4U.
5. Effectuez les connexions comme il est indiqué à Figure 3.
6. Attachez la plaque de la base au coffret électrique à l’aide
de vis fournies avec ce dernier.
7. Attachez l’anneau de garniture à la plaque de la base.
Alignez les marques sur l’anneau de garniture avec celles
de la plaque de la base, pressez l’anneau dans la plaque
et faites pivoter l’anneau jusqu’à ce qu’elle se verrouille en
place.
8. Attachez le détecteur désiré à la base. Alignez les flèches
du détecteur avec celles de l’anneau de garniture, pressez
le détecteur dans la base puis
faites-le pivoter jusqu’à ce qu’il se verrouille en place.
9. Branchez l’alimentation et actionnez le dispositif pour vous
assurer qu’il fonctionne correctement.
Figure 1 : Installation du coffret AB4G-SB
1
2
3
4
5
6
7
1. Connecteur de conduit
2. Coffret électrique AB4G-SB
3. Languette de blocages
4. Anneau de garniture
5. Vis
6. Écrou
7. Plaque de renfort
P/N 3101077 • REV 05 • REB 23JAN13 5 / 6
Figure 2 : Installation de la base
1. Détecteur
2. Anneau de garniture
3. Vis
4. Plaque de la base
5. Coffret électrique compatible
Filage
Câblez conformément aux normes NFPA 72 et
CAN/ULC-S524. Assurez-vous de bien observer la polarité des
bornes sur le bornier, comme indiqué sur le diagramme.
Interrompez le filage à chacune des bornes. Ne faites pas de
boucle autour des bornes avec les câbles du champ du circuit
de signalisation.
Consultez le manuel de référence technique applicable pour
les diagrammes d’application.
Remarque : Le fil protégé est exigé seulement dans les
environnements avec le bruit électrique très élevé. Quand vous
employez le câble protégé, suivez ces recommandations :
• Le branchement armé à la base ou en partant de
celle-ci doit être continu et isolé du sol. Isolez la
connection armée avec du ruban magnétique.
• Pour le filage de classe B, il n’y a pas de connexion armée
au sol au dernier dispositif.
Figure 3 : Output configuration et filage de la base
4
SLC + SLC +
AUX_RISER + AUX_RISER +
SLC −
SLC −
AUX_RISER − AUX_RISER −
1. AUX_Riser IN (de l'alimentation d'énergie ou de la base
précédente)
2. Arrangement de volume : le défaut est à fort débit ; coupez par
point 4 pour le bas volume
3. Arrangement de tonalité : le défaut est modèle temporal ; coupez
par point 4 pour la tonalité régulière
4. Pour configurer pour produire le volume ou la tonalité, coupez la
carte comme montrée
5. AUX_ Riser OUT (pour baser après ou relais d'EOL)
6. SLC OUT au prochain dispositif accessible intelligent
7. SLC IN du contrôleur accessible intelligent ou du dispositif
précédent
Tableau 1 : Courant opérationnel en mA (RMS)
Voltage dBA faible dBA élevé
16 VDC 17 28
24 VDC 24 41
33 VDC 31 52
16 VFWR 41 48
24 VFWR 51 60
33 VFWR 60 66
VDC = voltage de courant continu, réglementé et filtré
VFWR = voltage pleine onde corrigé
6 / 6 P/N 3101077 • REV 05 • REB 23JAN13
Tableau 2 : Sortie du niveau sonore (dBA)
Signal Voltage dBA faible dBA élevé
Salle réverbérante par UL 464 [1]
Temporelle 16 VDC 71,3 77,2
24 VDC 75,0 79,8
33 VDC 77,7 81,5
Statique 16 VDC 75,8 80,5
24 VDC 79,2 84,1
33 VDC 82,0 86,0
Salle réverbérante par UL 268 [2]
Temporelle 16 VDC 77,3 83,2
24 VDC 81,0 85,8
33 VDC 83,7 87,5
Statique 16 VDC 81,8 86,5
24 VDC 85,2 90,1
33 VDC 88,0 92,0
[1] Pour des applications U L 464, les bas arrangements de DBA sont
pour le mode privé seulement
[2 Pour les applications UL 268, l'arrangement élevé doit être employé
pour l'évacuation
Tableau 3 : Caractéristiques directionnelles audibles
Angle (degrés) Niveau de pression acoustique de rendement
(dBA)
90 (référence) 0
80 et 100 −3
70 et 110 −6
L'axe horizontal et l'axe veritical reflètent le même modèle
Tableau 4 : Niveau de pression acoustique (dBA) par
CAN/ULC-S525
Signal Voltage dBA élevé dBA base
Temporelle Reg. 24 VDC 95 91
Reg. 24
VFWR
99 95
Statique Reg. 24 VDC 93 89
Reg. 24
VFWR
96 92
L'entretien
Ne changez pas la finition usine-appliquée.
Coordonnées
Pour obtenir nos coordonnées, consultez le site Web :
www.edwardsutcfs.com.
Fiche technique
Voltage opérationnel
(alimentation du son)
24 VDC ou 24 VFWR
Courant opérationnel Voir le Tableau 1
Courant de surveillance CC = 1,46 mA, FWR = 2,15 mA
Réglage pas défaut
Volume de sortie
Tonalité de sortie
dBA élevé
Circuit temporel
Sortie du niveau sonore
UL
ULC
Voir le Tableau 2
Voir le Tableau 4
Circuit temporel 0,5 sec. ouvert, 0,5 sec. fermé,
0,5 sec. ouvert, 0,5 sec. fermé,
0,5 sec. ouvert, 1,5 sec. fermé,
cycle répétitif
Cadre opérationnel
Température
Hygrométrie
0 à 49°C (32 à 120°F)
0 à 93 % non-condensation
Plage de la température
d’entreposage
−20 à 60°C (−4 à 140°F)
Détecteurs compatibles FX-PD, E-PD, FX-PHD, E-PHD,
FX-HD, E-HD, V-PS, V-PHS, V-HRD
et V-HFD
Dimensions du câble 12, ou 18 AWG (0,75 1,0, 1,5 ou
2.5 mm2
) (16 et 18 AWG de
préférence)
Coffrets électriques
compatibles
Coffret de surface AB4G-SB pour la
base audible
Coffret nord-américain de 10 cm2
(4 po2
) x 64 mm (2-1/2 po) de
profond.
Coffret européen de 100 mm2
Diamètre de la base 152 mm (6 po)
Hauteur à partir du coffret
(détecteur inclus)
66 mm (2,58 po)
Distance maximale du plafond
(montage mural)
305 mm (12 po)
Référencement des agences
Fabricant Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL 34202,
USA
Année de
fabrication
Les deux premiers chiffres du code de date (situé
sur l'étiquette d'identification de produit) sont
l'année de la fabrication.
Coefficient
UL/ULC
24 CC ou 24 FWR réglementé
Normes nord-
américaines
Conforme : UL 268, UL 464, CAN/ ULC-S525 et de
CAN/ULC-S529
Suivez : CSA C22.1 et CAN/ULC-S524.
Il est interdit d’installer ce dispositif dans un
logement comme stipulé dans le code national du
bâtiment du Canada.

Contenu connexe

Tendances

Rkn base d_ingenierie_et_d_installation_v2
Rkn base d_ingenierie_et_d_installation_v2Rkn base d_ingenierie_et_d_installation_v2
Rkn base d_ingenierie_et_d_installation_v2e-genieclimatique
 
Rkn régulateur documentation_sommaire
Rkn régulateur documentation_sommaireRkn régulateur documentation_sommaire
Rkn régulateur documentation_sommairee-genieclimatique
 
Nod on asp-3-1-x0_z-wave_datasheet_20150326_fr
Nod on asp-3-1-x0_z-wave_datasheet_20150326_frNod on asp-3-1-x0_z-wave_datasheet_20150326_fr
Nod on asp-3-1-x0_z-wave_datasheet_20150326_frDomotica daVinci
 
Réussir votre installation électrique
Réussir votre installation électrique Réussir votre installation électrique
Réussir votre installation électrique GENICIMO
 
Ecosense Slim Cove INT Installation Guide
Ecosense Slim Cove INT Installation GuideEcosense Slim Cove INT Installation Guide
Ecosense Slim Cove INT Installation Guidevalorlighting
 
Micromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manuel francais
Micromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manuel francaisMicromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manuel francais
Micromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manuel francaisDomotica daVinci
 
Codeur incrémental programmable IP58 / IQ58 de Lika Electronic en français
Codeur incrémental programmable IP58 / IQ58 de Lika Electronic en françaisCodeur incrémental programmable IP58 / IQ58 de Lika Electronic en français
Codeur incrémental programmable IP58 / IQ58 de Lika Electronic en françaisLika Electronic
 
La pose de vos spots à encastrer
La pose de vos spots à encastrerLa pose de vos spots à encastrer
La pose de vos spots à encastrerGENICIMO
 
Edwards Signaling B4U Installation Manual
Edwards Signaling B4U Installation ManualEdwards Signaling B4U Installation Manual
Edwards Signaling B4U Installation ManualJMAC Supply
 
Smoke detector Fibaro certified CE EN 14604
Smoke detector Fibaro certified CE EN 14604Smoke detector Fibaro certified CE EN 14604
Smoke detector Fibaro certified CE EN 14604Domotica daVinci
 
Eripm vdpcrgb2
Eripm vdpcrgb2Eripm vdpcrgb2
Eripm vdpcrgb2Sprl Eripm
 
Nodon asp-3-1-x0-z-wave user-guide_150320-fr
Nodon asp-3-1-x0-z-wave user-guide_150320-frNodon asp-3-1-x0-z-wave user-guide_150320-fr
Nodon asp-3-1-x0-z-wave user-guide_150320-frDomotica daVinci
 

Tendances (20)

Rkn base d_ingenierie_et_d_installation_v2
Rkn base d_ingenierie_et_d_installation_v2Rkn base d_ingenierie_et_d_installation_v2
Rkn base d_ingenierie_et_d_installation_v2
 
Rkn régulateur documentation_sommaire
Rkn régulateur documentation_sommaireRkn régulateur documentation_sommaire
Rkn régulateur documentation_sommaire
 
Masterpact NW800 - 6300A
Masterpact NW800 - 6300AMasterpact NW800 - 6300A
Masterpact NW800 - 6300A
 
Electricite
ElectriciteElectricite
Electricite
 
Nod on asp-3-1-x0_z-wave_datasheet_20150326_fr
Nod on asp-3-1-x0_z-wave_datasheet_20150326_frNod on asp-3-1-x0_z-wave_datasheet_20150326_fr
Nod on asp-3-1-x0_z-wave_datasheet_20150326_fr
 
Réussir votre installation électrique
Réussir votre installation électrique Réussir votre installation électrique
Réussir votre installation électrique
 
Sez 61.5
Sez 61.5Sez 61.5
Sez 61.5
 
Manual GCE-X-4VR
Manual GCE-X-4VRManual GCE-X-4VR
Manual GCE-X-4VR
 
Rwi65.01 régulateur
Rwi65.01 régulateurRwi65.01 régulateur
Rwi65.01 régulateur
 
Sqs65 fiche produit_fr
Sqs65 fiche produit_frSqs65 fiche produit_fr
Sqs65 fiche produit_fr
 
Ecosense Slim Cove INT Installation Guide
Ecosense Slim Cove INT Installation GuideEcosense Slim Cove INT Installation Guide
Ecosense Slim Cove INT Installation Guide
 
Micromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manuel francais
Micromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manuel francaisMicromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manuel francais
Micromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manuel francais
 
Codeur incrémental programmable IP58 / IQ58 de Lika Electronic en français
Codeur incrémental programmable IP58 / IQ58 de Lika Electronic en françaisCodeur incrémental programmable IP58 / IQ58 de Lika Electronic en français
Codeur incrémental programmable IP58 / IQ58 de Lika Electronic en français
 
Seh62.1 fiche produit_fr
Seh62.1 fiche produit_frSeh62.1 fiche produit_fr
Seh62.1 fiche produit_fr
 
La pose de vos spots à encastrer
La pose de vos spots à encastrerLa pose de vos spots à encastrer
La pose de vos spots à encastrer
 
Edwards Signaling B4U Installation Manual
Edwards Signaling B4U Installation ManualEdwards Signaling B4U Installation Manual
Edwards Signaling B4U Installation Manual
 
Smoke detector Fibaro certified CE EN 14604
Smoke detector Fibaro certified CE EN 14604Smoke detector Fibaro certified CE EN 14604
Smoke detector Fibaro certified CE EN 14604
 
Eripm vdpcrgb2
Eripm vdpcrgb2Eripm vdpcrgb2
Eripm vdpcrgb2
 
Qaw70 a fiche-produit_fr
Qaw70 a fiche-produit_frQaw70 a fiche-produit_fr
Qaw70 a fiche-produit_fr
 
Nodon asp-3-1-x0-z-wave user-guide_150320-fr
Nodon asp-3-1-x0-z-wave user-guide_150320-frNodon asp-3-1-x0-z-wave user-guide_150320-fr
Nodon asp-3-1-x0-z-wave user-guide_150320-fr
 

En vedette

Lodha New Project Estrella Cuffe Parade Wadala Mumbai South Call-09990065550v
Lodha New Project Estrella Cuffe Parade Wadala Mumbai South Call-09990065550vLodha New Project Estrella Cuffe Parade Wadala Mumbai South Call-09990065550v
Lodha New Project Estrella Cuffe Parade Wadala Mumbai South Call-09990065550vSettlers India.com
 
La planta anamaria marcovich tuesta 6''c''
La  planta anamaria marcovich  tuesta  6''c''La  planta anamaria marcovich  tuesta  6''c''
La planta anamaria marcovich tuesta 6''c''ani1415
 
Las plantas
Las plantasLas plantas
Las plantasmcielorv
 
Trabajo de la planta
Trabajo de la plantaTrabajo de la planta
Trabajo de la plantaslenderrr
 
Edwards Signaling G4LFRF-H Installation Manual
Edwards Signaling G4LFRF-H Installation ManualEdwards Signaling G4LFRF-H Installation Manual
Edwards Signaling G4LFRF-H Installation ManualJMAC Supply
 
Presentation1
Presentation1Presentation1
Presentation1KEANAHO
 
Jaymon alcala.. pangkabuhayan
Jaymon alcala.. pangkabuhayanJaymon alcala.. pangkabuhayan
Jaymon alcala.. pangkabuhayanAlice Bernardo
 
Powerpoint Presentation ammu1
Powerpoint Presentation ammu1Powerpoint Presentation ammu1
Powerpoint Presentation ammu1ammurajendran
 
Edwards Signaling G4LFWN-H Installation Manual
Edwards Signaling G4LFWN-H Installation ManualEdwards Signaling G4LFWN-H Installation Manual
Edwards Signaling G4LFWN-H Installation ManualJMAC Supply
 
Que es una pila3
Que es una pila3Que es una pila3
Que es una pila3oscar610
 
Plantas angie
Plantas angiePlantas angie
Plantas angie2angie
 
Cual es la diferencia entre web
Cual es la diferencia entre webCual es la diferencia entre web
Cual es la diferencia entre webjosemanuel1997
 
Edwards Signaling G4LFWN-HVM Installation Manual
Edwards Signaling G4LFWN-HVM Installation ManualEdwards Signaling G4LFWN-HVM Installation Manual
Edwards Signaling G4LFWN-HVM Installation ManualJMAC Supply
 
Presentación sin título
Presentación sin títuloPresentación sin título
Presentación sin títuloLoliitha Velez
 
Edwards Signaling G4LFWF-HVM Installation Manual
Edwards Signaling G4LFWF-HVM Installation ManualEdwards Signaling G4LFWF-HVM Installation Manual
Edwards Signaling G4LFWF-HVM Installation ManualJMAC Supply
 
Edwards Signaling SDSJ Installation Manual
Edwards Signaling SDSJ Installation ManualEdwards Signaling SDSJ Installation Manual
Edwards Signaling SDSJ Installation ManualJMAC Supply
 
Trabajo de la planta
Trabajo de la plantaTrabajo de la planta
Trabajo de la plantaslenderrr
 

En vedette (20)

Lodha New Project Estrella Cuffe Parade Wadala Mumbai South Call-09990065550v
Lodha New Project Estrella Cuffe Parade Wadala Mumbai South Call-09990065550vLodha New Project Estrella Cuffe Parade Wadala Mumbai South Call-09990065550v
Lodha New Project Estrella Cuffe Parade Wadala Mumbai South Call-09990065550v
 
La planta anamaria marcovich tuesta 6''c''
La  planta anamaria marcovich  tuesta  6''c''La  planta anamaria marcovich  tuesta  6''c''
La planta anamaria marcovich tuesta 6''c''
 
Las plantas
Las plantasLas plantas
Las plantas
 
Trabajo de la planta
Trabajo de la plantaTrabajo de la planta
Trabajo de la planta
 
Las plantas trabajo 1 de l.d
Las plantas trabajo 1 de l.dLas plantas trabajo 1 de l.d
Las plantas trabajo 1 de l.d
 
Edwards Signaling G4LFRF-H Installation Manual
Edwards Signaling G4LFRF-H Installation ManualEdwards Signaling G4LFRF-H Installation Manual
Edwards Signaling G4LFRF-H Installation Manual
 
Presentation1
Presentation1Presentation1
Presentation1
 
Jaymon alcala.. pangkabuhayan
Jaymon alcala.. pangkabuhayanJaymon alcala.. pangkabuhayan
Jaymon alcala.. pangkabuhayan
 
Powerpoint Presentation ammu1
Powerpoint Presentation ammu1Powerpoint Presentation ammu1
Powerpoint Presentation ammu1
 
Celador Anthony
Celador AnthonyCelador Anthony
Celador Anthony
 
Edwards Signaling G4LFWN-H Installation Manual
Edwards Signaling G4LFWN-H Installation ManualEdwards Signaling G4LFWN-H Installation Manual
Edwards Signaling G4LFWN-H Installation Manual
 
Que es una pila3
Que es una pila3Que es una pila3
Que es una pila3
 
Plantas angie
Plantas angiePlantas angie
Plantas angie
 
Cual es la diferencia entre web
Cual es la diferencia entre webCual es la diferencia entre web
Cual es la diferencia entre web
 
Edwards Signaling G4LFWN-HVM Installation Manual
Edwards Signaling G4LFWN-HVM Installation ManualEdwards Signaling G4LFWN-HVM Installation Manual
Edwards Signaling G4LFWN-HVM Installation Manual
 
Presentación sin título
Presentación sin títuloPresentación sin título
Presentación sin título
 
Randstad
RandstadRandstad
Randstad
 
Edwards Signaling G4LFWF-HVM Installation Manual
Edwards Signaling G4LFWF-HVM Installation ManualEdwards Signaling G4LFWF-HVM Installation Manual
Edwards Signaling G4LFWF-HVM Installation Manual
 
Edwards Signaling SDSJ Installation Manual
Edwards Signaling SDSJ Installation ManualEdwards Signaling SDSJ Installation Manual
Edwards Signaling SDSJ Installation Manual
 
Trabajo de la planta
Trabajo de la plantaTrabajo de la planta
Trabajo de la planta
 

Similaire à Edwards Signaling SB4U Installation Manual

Edwards Signaling WG4RF-HVMHC Installation Manual
Edwards Signaling WG4RF-HVMHC Installation ManualEdwards Signaling WG4RF-HVMHC Installation Manual
Edwards Signaling WG4RF-HVMHC Installation ManualJMAC Supply
 
Réussir votre installation électrique www.cours-online.com
Réussir votre installation électrique www.cours-online.comRéussir votre installation électrique www.cours-online.com
Réussir votre installation électrique www.cours-online.commorin moli
 
DT-830B_M.pdf
DT-830B_M.pdfDT-830B_M.pdf
DT-830B_M.pdfdddqeg
 
Symboles normalisés pour schémas d'installations électriques
Symboles normalisés pour schémas d'installations électriquesSymboles normalisés pour schémas d'installations électriques
Symboles normalisés pour schémas d'installations électriquesmorin moli
 
Detnov ccd 112 manual-t
Detnov ccd 112 manual-tDetnov ccd 112 manual-t
Detnov ccd 112 manual-tjelogon
 
s2-1_sh-formation_pv_réseau_2020-04-2.pdf
s2-1_sh-formation_pv_réseau_2020-04-2.pdfs2-1_sh-formation_pv_réseau_2020-04-2.pdf
s2-1_sh-formation_pv_réseau_2020-04-2.pdfNioulLopoldJunior
 
Formation PV Onduleurs Schémas elec.pdf
Formation PV Onduleurs Schémas elec.pdfFormation PV Onduleurs Schémas elec.pdf
Formation PV Onduleurs Schémas elec.pdfMohamed854100
 
Disjoncteur hager
Disjoncteur hagerDisjoncteur hager
Disjoncteur hagerAmina MALIH
 
Ar fx3 pro-data_modem_quick-start-guide_v1
Ar fx3 pro-data_modem_quick-start-guide_v1Ar fx3 pro-data_modem_quick-start-guide_v1
Ar fx3 pro-data_modem_quick-start-guide_v1Advantec Distribution
 
Ar fx3 pro-data_modem_quick-start-guide_v1
Ar fx3 pro-data_modem_quick-start-guide_v1Ar fx3 pro-data_modem_quick-start-guide_v1
Ar fx3 pro-data_modem_quick-start-guide_v1Advantec Distribution
 
Digital Multimeter
Digital MultimeterDigital Multimeter
Digital MultimeterJames Bushor
 

Similaire à Edwards Signaling SB4U Installation Manual (20)

Edwards Signaling WG4RF-HVMHC Installation Manual
Edwards Signaling WG4RF-HVMHC Installation ManualEdwards Signaling WG4RF-HVMHC Installation Manual
Edwards Signaling WG4RF-HVMHC Installation Manual
 
Réussir votre installation électrique www.cours-online.com
Réussir votre installation électrique www.cours-online.comRéussir votre installation électrique www.cours-online.com
Réussir votre installation électrique www.cours-online.com
 
DT-830B_M.pdf
DT-830B_M.pdfDT-830B_M.pdf
DT-830B_M.pdf
 
Vive
ViveVive
Vive
 
Symboles normalisés pour schémas d'installations électriques
Symboles normalisés pour schémas d'installations électriquesSymboles normalisés pour schémas d'installations électriques
Symboles normalisés pour schémas d'installations électriques
 
Detnov ccd 112 manual-t
Detnov ccd 112 manual-tDetnov ccd 112 manual-t
Detnov ccd 112 manual-t
 
s2-1_sh-formation_pv_réseau_2020-04-2.pdf
s2-1_sh-formation_pv_réseau_2020-04-2.pdfs2-1_sh-formation_pv_réseau_2020-04-2.pdf
s2-1_sh-formation_pv_réseau_2020-04-2.pdf
 
Manual GCE-X-PWM
Manual GCE-X-PWMManual GCE-X-PWM
Manual GCE-X-PWM
 
Formation PV Onduleurs Schémas elec.pdf
Formation PV Onduleurs Schémas elec.pdfFormation PV Onduleurs Schémas elec.pdf
Formation PV Onduleurs Schémas elec.pdf
 
Disjoncteur hager
Disjoncteur hagerDisjoncteur hager
Disjoncteur hager
 
5225349.pdf
5225349.pdf5225349.pdf
5225349.pdf
 
Electronique de puissance
Electronique de puissanceElectronique de puissance
Electronique de puissance
 
Lgb
LgbLgb
Lgb
 
Qac3161 fiche produit_fr
Qac3161 fiche produit_frQac3161 fiche produit_fr
Qac3161 fiche produit_fr
 
Ar fx3 pro-data_modem_quick-start-guide_v1
Ar fx3 pro-data_modem_quick-start-guide_v1Ar fx3 pro-data_modem_quick-start-guide_v1
Ar fx3 pro-data_modem_quick-start-guide_v1
 
Ar fx3 pro-data_modem_quick-start-guide_v1
Ar fx3 pro-data_modem_quick-start-guide_v1Ar fx3 pro-data_modem_quick-start-guide_v1
Ar fx3 pro-data_modem_quick-start-guide_v1
 
10620.pdf
10620.pdf10620.pdf
10620.pdf
 
Analyseur
AnalyseurAnalyseur
Analyseur
 
Digital Multimeter
Digital MultimeterDigital Multimeter
Digital Multimeter
 
Somitel
SomitelSomitel
Somitel
 

Plus de JMAC Supply

Bosch ALTV244UL Data Sheet
Bosch ALTV244UL Data SheetBosch ALTV244UL Data Sheet
Bosch ALTV244UL Data SheetJMAC Supply
 
Bosch AL1002WAL Data Sheet
Bosch AL1002WAL Data SheetBosch AL1002WAL Data Sheet
Bosch AL1002WAL Data SheetJMAC Supply
 
Bosch AIM-AEC21-CVT Data Sheet
Bosch AIM-AEC21-CVT Data SheetBosch AIM-AEC21-CVT Data Sheet
Bosch AIM-AEC21-CVT Data SheetJMAC Supply
 
Bosch AI1 Data Sheet
Bosch AI1 Data SheetBosch AI1 Data Sheet
Bosch AI1 Data SheetJMAC Supply
 
Bosch AH-24WP-R Data Sheet
Bosch AH-24WP-R Data SheetBosch AH-24WP-R Data Sheet
Bosch AH-24WP-R Data SheetJMAC Supply
 
Bosch AEC-8I8O-EXT Data Sheet
Bosch AEC-8I8O-EXT Data SheetBosch AEC-8I8O-EXT Data Sheet
Bosch AEC-8I8O-EXT Data SheetJMAC Supply
 
Bosch AE774 Data Sheet
Bosch AE774 Data SheetBosch AE774 Data Sheet
Bosch AE774 Data SheetJMAC Supply
 
Bosch AE203R Data Sheet
Bosch AE203R Data SheetBosch AE203R Data Sheet
Bosch AE203R Data SheetJMAC Supply
 
Bosch AE101 Data Sheet
Bosch AE101 Data SheetBosch AE101 Data Sheet
Bosch AE101 Data SheetJMAC Supply
 
Bosch AE4 Data Sheet
Bosch AE4 Data SheetBosch AE4 Data Sheet
Bosch AE4 Data SheetJMAC Supply
 
Bosch AE1 Data Sheet
Bosch AE1 Data SheetBosch AE1 Data Sheet
Bosch AE1 Data SheetJMAC Supply
 
Bosch ACD-IC16K37-50 Data Sheet
Bosch ACD-IC16K37-50 Data SheetBosch ACD-IC16K37-50 Data Sheet
Bosch ACD-IC16K37-50 Data SheetJMAC Supply
 
Bosch ACD-IC2K37-50 Data Sheet
Bosch ACD-IC2K37-50 Data SheetBosch ACD-IC2K37-50 Data Sheet
Bosch ACD-IC2K37-50 Data SheetJMAC Supply
 
Bosch ACA-IC2K26-10 Data Sheet
Bosch ACA-IC2K26-10 Data SheetBosch ACA-IC2K26-10 Data Sheet
Bosch ACA-IC2K26-10 Data SheetJMAC Supply
 
Bosch 9208B Data Sheet
Bosch 9208B Data SheetBosch 9208B Data Sheet
Bosch 9208B Data SheetJMAC Supply
 
Bosch 7110XC Data Sheet
Bosch 7110XC Data SheetBosch 7110XC Data Sheet
Bosch 7110XC Data SheetJMAC Supply
 
Samsung Techwin SNB-1000 Data Sheet
Samsung Techwin SNB-1000 Data SheetSamsung Techwin SNB-1000 Data Sheet
Samsung Techwin SNB-1000 Data SheetJMAC Supply
 
Samsung Techwin SMT-4031 Data Sheet
Samsung Techwin SMT-4031 Data SheetSamsung Techwin SMT-4031 Data Sheet
Samsung Techwin SMT-4031 Data SheetJMAC Supply
 
Samsung Techwin SMT-4023 Data Sheet
Samsung Techwin SMT-4023 Data SheetSamsung Techwin SMT-4023 Data Sheet
Samsung Techwin SMT-4023 Data SheetJMAC Supply
 
Samsung Techwin SMT-3232 Data Sheet
Samsung Techwin SMT-3232 Data SheetSamsung Techwin SMT-3232 Data Sheet
Samsung Techwin SMT-3232 Data SheetJMAC Supply
 

Plus de JMAC Supply (20)

Bosch ALTV244UL Data Sheet
Bosch ALTV244UL Data SheetBosch ALTV244UL Data Sheet
Bosch ALTV244UL Data Sheet
 
Bosch AL1002WAL Data Sheet
Bosch AL1002WAL Data SheetBosch AL1002WAL Data Sheet
Bosch AL1002WAL Data Sheet
 
Bosch AIM-AEC21-CVT Data Sheet
Bosch AIM-AEC21-CVT Data SheetBosch AIM-AEC21-CVT Data Sheet
Bosch AIM-AEC21-CVT Data Sheet
 
Bosch AI1 Data Sheet
Bosch AI1 Data SheetBosch AI1 Data Sheet
Bosch AI1 Data Sheet
 
Bosch AH-24WP-R Data Sheet
Bosch AH-24WP-R Data SheetBosch AH-24WP-R Data Sheet
Bosch AH-24WP-R Data Sheet
 
Bosch AEC-8I8O-EXT Data Sheet
Bosch AEC-8I8O-EXT Data SheetBosch AEC-8I8O-EXT Data Sheet
Bosch AEC-8I8O-EXT Data Sheet
 
Bosch AE774 Data Sheet
Bosch AE774 Data SheetBosch AE774 Data Sheet
Bosch AE774 Data Sheet
 
Bosch AE203R Data Sheet
Bosch AE203R Data SheetBosch AE203R Data Sheet
Bosch AE203R Data Sheet
 
Bosch AE101 Data Sheet
Bosch AE101 Data SheetBosch AE101 Data Sheet
Bosch AE101 Data Sheet
 
Bosch AE4 Data Sheet
Bosch AE4 Data SheetBosch AE4 Data Sheet
Bosch AE4 Data Sheet
 
Bosch AE1 Data Sheet
Bosch AE1 Data SheetBosch AE1 Data Sheet
Bosch AE1 Data Sheet
 
Bosch ACD-IC16K37-50 Data Sheet
Bosch ACD-IC16K37-50 Data SheetBosch ACD-IC16K37-50 Data Sheet
Bosch ACD-IC16K37-50 Data Sheet
 
Bosch ACD-IC2K37-50 Data Sheet
Bosch ACD-IC2K37-50 Data SheetBosch ACD-IC2K37-50 Data Sheet
Bosch ACD-IC2K37-50 Data Sheet
 
Bosch ACA-IC2K26-10 Data Sheet
Bosch ACA-IC2K26-10 Data SheetBosch ACA-IC2K26-10 Data Sheet
Bosch ACA-IC2K26-10 Data Sheet
 
Bosch 9208B Data Sheet
Bosch 9208B Data SheetBosch 9208B Data Sheet
Bosch 9208B Data Sheet
 
Bosch 7110XC Data Sheet
Bosch 7110XC Data SheetBosch 7110XC Data Sheet
Bosch 7110XC Data Sheet
 
Samsung Techwin SNB-1000 Data Sheet
Samsung Techwin SNB-1000 Data SheetSamsung Techwin SNB-1000 Data Sheet
Samsung Techwin SNB-1000 Data Sheet
 
Samsung Techwin SMT-4031 Data Sheet
Samsung Techwin SMT-4031 Data SheetSamsung Techwin SMT-4031 Data Sheet
Samsung Techwin SMT-4031 Data Sheet
 
Samsung Techwin SMT-4023 Data Sheet
Samsung Techwin SMT-4023 Data SheetSamsung Techwin SMT-4023 Data Sheet
Samsung Techwin SMT-4023 Data Sheet
 
Samsung Techwin SMT-3232 Data Sheet
Samsung Techwin SMT-3232 Data SheetSamsung Techwin SMT-3232 Data Sheet
Samsung Techwin SMT-3232 Data Sheet
 

Edwards Signaling SB4U Installation Manual

  • 1. © 2013 UTC Fire & Security. All rights reserved. 1 / 6 P/N 3101077 • REV 05 • REB 23JAN13 SB4U Analog Audible Detector Base Installation Sheet EN FR EN: Installation Sheet Operation The SB4U Analog Audible Detector Base adds an audible output function to the listed compatible detectors. The base can operate as an independent local alarm, or as part of a zone or system alarm with synchronized audible output. The output of this detector base is field-configurable for output tone (steady or temporal) and output volume (low dBA or high dBA). Depending on the system supporting the device loop, the base can: • Follow the state of the device it supports • Be controlled and configured for other operating modes through front panel programming or the configuration utility The base uses the same address and programming label as the detector it supports. Installation Cautions • To avoid accidental damage to the control panel, disconnect all power before wiring the unit. • Electrical supervision requires the wire run to be broken at each terminal. Do not loop the signaling circuit field wires around the terminals. Note: Always connect the base to a continuous voltage, whether the output tone is set to steady or temporal. Sleeping rooms: In sleeping areas, use the high dBA output and temporal tone settings. However, if the control panel is producing the three-tone temporal evacuation signal, then the high dBA output and steady tone settings are permissible. AB4G-SB: When using the AB4G-SB box, install a reinforcing plate at every knockout. (Reinforcing plates are included with the box.) Remove the knockout first and then slide the reinforcing plate into the plastic housing. After the plate is in place, install the conduit connector and nut. See Figure 1. Typically, the base is configured to produce a high dBA temporal tone and is connected to a notification appliance circuit that outputs a continuous 24 VDC signal. If the notification appliance circuit outputs a temporal signal, configure the tone setting on the base for steady. To install the base: 1. The unit default is for high dBA output. To set the output to low dBA, cut the circuit board trace as marked on the back of the PC board. See Figure 3. 2. The unit default is for temporal pattern output. To set the output to steady tone, cut the circuit board trace as marked on the back of the PC board. See Figure 3. 3. Select and install a compatible electrical box, and bring the field wiring into the box. 4. Install the trim ring and secure using screws. The trim ring is included with the SB4U base. See Figure 2. 5. Make all wiring connections as shown in Figure 3. 6. Attach the base plate to the electrical box using the screws provided with the electrical box. 7. Attach the trim ring to the base plate. Align the marks on the trim ring and base plate, press the trim ring onto the base plate, and then rotate the trim ring until it locks into place. 8. Attach the desired detector to the base. Align the arrows on the detector and trim ring, press the detector into the base, and then rotate the detector until it locks into place. 9. Apply power and activate the unit to verify that it is operating properly.
  • 2. 2 / 6 P/N 3101077 • REV 05 • REB 23JAN13 Figure 1: AB4G-SB box installation 1 2 3 4 5 6 7 1. Conduit connector 2. AB4G-SB electrical box 3. Lock tab 4. Trim rings 5. Screw 6. Nut 7. Reinforcing plate Figure 2: Base installation 1. Detector 2. Trim ring 3. Screw 4. Base plate 5. Compatible electrical box Wiring Wire in accordance with NFPA 72 and CAN/ULC-S524. Be sure to observe the polarity of the terminals on the terminal block as shown in the diagram. Break the wire run at each terminal. Do not loop signaling circuit field wires around terminals. Refer to the applicable technical reference manual for application diagrams. Note: Shielded wire is required only in environments with very high electrical noise. When you use shielded cable, follow these recommendations: • Shield connection to and from the base must be continuous and must be insulated from ground. Insulate the shield using tape. • For Class B wiring, there is no shield connection to ground at the last device. Figure 3: Output configuration and wiring diagram 4 SLC + SLC + AUX_RISER + AUX_RISER + SLC − SLC − AUX_RISER − AUX_RISER − 1. AUX-RISER IN (from power supply or previous base) 2. Volume setting: default is high volume; cut per item 4 for low volume 3. Tone setting: default is temporal pattern; cut per item 4 for steady tone 4. To configure output volume or tone, cut the circuit board as shown 5. AUX_RISER OUT To next base or EOL relay 6. SLC OUT to next intelligent addressable device 7. SLC IN from intelligent addressable controller or previous device
  • 3. P/N 3101077 • REV 05 • REB 23JAN13 3 / 6 Table 1: Operating current in mA (RMS) Voltage Low dBA High dBA 16 VDC 17 28 24 VDC 24 41 33 VDC 31 52 16 VFWR 41 48 24 VFWR 51 60 33 VFWR 60 66 VDC = Volts direct current, regulated and filtered VFWR = Volts full wave rectified Table 2: Sound level output (dBA) per CAN/ULC-S525 Signal Voltage (VDC) Low dBA High dBA Reverberant room per UL 464 [1] Temporal 16 71.3 77.2 24 75.0 79.8 33 77.7 81.5 Steady 16 75.8 80.5 24 79.2 84.1 33 82.0 86.0 Reverberant room per UL 268 [2] Temporal 16 77.3 83.2 24 81.0 85.8 33 83.7 87.5 Steady 16 81.8 86.5 24 85.2 90.1 33 88.0 92.0 [1] For UL 464 applications, low dBA settings are for private mode only [2] For UL 268 applications, the high setting must be used for evacuation Table 3: Audible directional characteristics Angle (degrees) Output sound pressure level 90 (reference) 0 dBA 80 and 100 −3 dBA 70 and 110 −6 dBA Horizontal axis and veritical axis reflect the same pattern Table 4: Sound pressure level per CAN/ULC-S525 Signal Voltage High dBA Low dBA Temporal Reg. 24 VDC 95 91 Reg. 24 VFWR 99 95 Steady Reg. 24 VDC 93 89 Reg. 24 VFWR 96 92 Maintenance Do not change the factory-applied finish. Specifications Operating voltage (sounder power) 24 VDC or 24 VFWR Current Operating Supervisory See Table 1 DC = 1.46 mA, FWR = 2.15 mA Default settings Output volume Output tone High dBA Temporal pattern Sound level output UL ULC See Table 2 See Table 4 Temporal pattern 0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 0.5 s on, 1.5 s off, repeat cycle Compatible detectors FX-PD, E-PD, FX-PHD, E-PHD, FX-HD, E-HD, V-PS, V-PHS, V-HRD, and V-HFD Compatible electrical boxes AB4G-SB surface box for audible base North American 4 in. square x 2-1/2 in. (64 mm) deep box Standard European 100 mm² box Wire size 12 to 18 AWG (0.75 to 2.5mm²) Sizes 16 and 18 AWG are preferred Base diameter 6.0 in. (152 mm) Height from box (including detector) 2.58 in. (66 mm) Maximum distance from ceiling (wall mount) 12 in. (305 mm) Operating environment Temperature Relative humidity 32 to 120°F (0 to 49°C) 0 to 93% noncondensing Storage temperature range –4 to 140°F (–20 to 60°C) Regulatory information Manufacturer Edwards, A Division of UTC Fire & Security Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA Year of manufacture The first two digits of the DATE MFG number (located on the product identification label) are the year of manufacture. UL/ULC rating Regulated 24 DC or 24 FWR North American standards Meets: UL 268, UL 464, CAN/ULC-S525, and CAN/ULC-S529 Follow: CSA C22.1 and CAN/ULC-S524. This device is prohibited from being installed in a dwelling unit as defined in the National Building Code of Canada. Contact information For contact information, see www.edwardsutcfs.com.
  • 4. 4 / 6 P/N 3101077 • REV 05 • REB 23JAN13 FR : Fiche D'Installation Fonctionnement La base audible analogique SB4U pour détecteur est conçue pour ajouter une fonction audible aux détecteurs compatibles répertoriés. Elle peut fonctionner en tant qu’alarme locale indépendante ou comme partie d’une zone ou d’un système doté de sorties audibles synchronisées. Fonctionnement de la base selon le système supportant la boucle du dispositif : • Il peut suivre l’état du dispositif qu’il supporte • Il peut être contrôlé et configuré pour d’autres modes de fonctionnement en programmant le panneau avant ou l’unité de configuration La sortie de la base audible analogique SB4U peut être configurée sur place pour la tonalité de sortie (statique ou temporelle) et le volume de sortie (dBA faible ou élevé). La base ne requiert pas d’adresse séparée parce qu’elle partage la même que celle à laquelle elle est branchée. Installation Avertissements • Pour éviter tout dommage accidentel au panneau, débranchez toute alimentation électrique avant de câbler le dispositif. • La supervision électrique exige que le câblage soit interrompu à chaque borne. Ne faites pas de boucle autour des bornes avec les câbles du champ du circuit de signalisation. La basse doit être branchée à un voltage continu que la sortie de la tonalité soit réglée à statique ou temporelle. Chambres à coucher : Dans les lieux pour dormir, on doit utiliser le réglage de sortie dBA élevée et la tonalité temporelle. Cependant, si le panneau de commande d’alarme incendie produit un signal d’évacuation à trois tonalités temporelles, alors on peut utiliser le réglage d’une sortie dBA élevée et d’une tonalité statique. AB4G-SB : Lorsque vous utilisez un coffret électrique AB4G-SB, installez une plaque de renfort à chacune des alvéoles défonçables que vous utilisez. En premier, enlevez l’alvéole puis glissez la plaque de renfort dans le boîtier en plastique. Une fois la plaque en place, installez le connecteur de conduit ainsi que l’écrou comme illustré. La plaque de renfort est incluse avec le coffret AB4G-SB. Installation de la base : 1. Par défaut, l’appareil est réglé à une sortie dBA élevée. Pour régler la sortie à un DBA faible, coupez le tracé métallique de la carte de circuits imprimés comme marqué au dos de celle-ci. Voir Figure 3. 2. Par défaut, l’appareil est réglé pour une sortie temporelle. Pour régler la sortie à une tonalité statique, coupez le tracé métallique de la carte de circuits imprimés comme marqué au dos de celle-ci. Voir Figure 3. 3. Installez un coffret électrique compatible, puis tirez tout le filage à l’intérieur. 4. Installez l’anneau de garniture et fixez solidement avec les vis. L’anneau de garniture est inclus avec la base SB4U. 5. Effectuez les connexions comme il est indiqué à Figure 3. 6. Attachez la plaque de la base au coffret électrique à l’aide de vis fournies avec ce dernier. 7. Attachez l’anneau de garniture à la plaque de la base. Alignez les marques sur l’anneau de garniture avec celles de la plaque de la base, pressez l’anneau dans la plaque et faites pivoter l’anneau jusqu’à ce qu’elle se verrouille en place. 8. Attachez le détecteur désiré à la base. Alignez les flèches du détecteur avec celles de l’anneau de garniture, pressez le détecteur dans la base puis faites-le pivoter jusqu’à ce qu’il se verrouille en place. 9. Branchez l’alimentation et actionnez le dispositif pour vous assurer qu’il fonctionne correctement. Figure 1 : Installation du coffret AB4G-SB 1 2 3 4 5 6 7 1. Connecteur de conduit 2. Coffret électrique AB4G-SB 3. Languette de blocages 4. Anneau de garniture 5. Vis 6. Écrou 7. Plaque de renfort
  • 5. P/N 3101077 • REV 05 • REB 23JAN13 5 / 6 Figure 2 : Installation de la base 1. Détecteur 2. Anneau de garniture 3. Vis 4. Plaque de la base 5. Coffret électrique compatible Filage Câblez conformément aux normes NFPA 72 et CAN/ULC-S524. Assurez-vous de bien observer la polarité des bornes sur le bornier, comme indiqué sur le diagramme. Interrompez le filage à chacune des bornes. Ne faites pas de boucle autour des bornes avec les câbles du champ du circuit de signalisation. Consultez le manuel de référence technique applicable pour les diagrammes d’application. Remarque : Le fil protégé est exigé seulement dans les environnements avec le bruit électrique très élevé. Quand vous employez le câble protégé, suivez ces recommandations : • Le branchement armé à la base ou en partant de celle-ci doit être continu et isolé du sol. Isolez la connection armée avec du ruban magnétique. • Pour le filage de classe B, il n’y a pas de connexion armée au sol au dernier dispositif. Figure 3 : Output configuration et filage de la base 4 SLC + SLC + AUX_RISER + AUX_RISER + SLC − SLC − AUX_RISER − AUX_RISER − 1. AUX_Riser IN (de l'alimentation d'énergie ou de la base précédente) 2. Arrangement de volume : le défaut est à fort débit ; coupez par point 4 pour le bas volume 3. Arrangement de tonalité : le défaut est modèle temporal ; coupez par point 4 pour la tonalité régulière 4. Pour configurer pour produire le volume ou la tonalité, coupez la carte comme montrée 5. AUX_ Riser OUT (pour baser après ou relais d'EOL) 6. SLC OUT au prochain dispositif accessible intelligent 7. SLC IN du contrôleur accessible intelligent ou du dispositif précédent Tableau 1 : Courant opérationnel en mA (RMS) Voltage dBA faible dBA élevé 16 VDC 17 28 24 VDC 24 41 33 VDC 31 52 16 VFWR 41 48 24 VFWR 51 60 33 VFWR 60 66 VDC = voltage de courant continu, réglementé et filtré VFWR = voltage pleine onde corrigé
  • 6. 6 / 6 P/N 3101077 • REV 05 • REB 23JAN13 Tableau 2 : Sortie du niveau sonore (dBA) Signal Voltage dBA faible dBA élevé Salle réverbérante par UL 464 [1] Temporelle 16 VDC 71,3 77,2 24 VDC 75,0 79,8 33 VDC 77,7 81,5 Statique 16 VDC 75,8 80,5 24 VDC 79,2 84,1 33 VDC 82,0 86,0 Salle réverbérante par UL 268 [2] Temporelle 16 VDC 77,3 83,2 24 VDC 81,0 85,8 33 VDC 83,7 87,5 Statique 16 VDC 81,8 86,5 24 VDC 85,2 90,1 33 VDC 88,0 92,0 [1] Pour des applications U L 464, les bas arrangements de DBA sont pour le mode privé seulement [2 Pour les applications UL 268, l'arrangement élevé doit être employé pour l'évacuation Tableau 3 : Caractéristiques directionnelles audibles Angle (degrés) Niveau de pression acoustique de rendement (dBA) 90 (référence) 0 80 et 100 −3 70 et 110 −6 L'axe horizontal et l'axe veritical reflètent le même modèle Tableau 4 : Niveau de pression acoustique (dBA) par CAN/ULC-S525 Signal Voltage dBA élevé dBA base Temporelle Reg. 24 VDC 95 91 Reg. 24 VFWR 99 95 Statique Reg. 24 VDC 93 89 Reg. 24 VFWR 96 92 L'entretien Ne changez pas la finition usine-appliquée. Coordonnées Pour obtenir nos coordonnées, consultez le site Web : www.edwardsutcfs.com. Fiche technique Voltage opérationnel (alimentation du son) 24 VDC ou 24 VFWR Courant opérationnel Voir le Tableau 1 Courant de surveillance CC = 1,46 mA, FWR = 2,15 mA Réglage pas défaut Volume de sortie Tonalité de sortie dBA élevé Circuit temporel Sortie du niveau sonore UL ULC Voir le Tableau 2 Voir le Tableau 4 Circuit temporel 0,5 sec. ouvert, 0,5 sec. fermé, 0,5 sec. ouvert, 0,5 sec. fermé, 0,5 sec. ouvert, 1,5 sec. fermé, cycle répétitif Cadre opérationnel Température Hygrométrie 0 à 49°C (32 à 120°F) 0 à 93 % non-condensation Plage de la température d’entreposage −20 à 60°C (−4 à 140°F) Détecteurs compatibles FX-PD, E-PD, FX-PHD, E-PHD, FX-HD, E-HD, V-PS, V-PHS, V-HRD et V-HFD Dimensions du câble 12, ou 18 AWG (0,75 1,0, 1,5 ou 2.5 mm2 ) (16 et 18 AWG de préférence) Coffrets électriques compatibles Coffret de surface AB4G-SB pour la base audible Coffret nord-américain de 10 cm2 (4 po2 ) x 64 mm (2-1/2 po) de profond. Coffret européen de 100 mm2 Diamètre de la base 152 mm (6 po) Hauteur à partir du coffret (détecteur inclus) 66 mm (2,58 po) Distance maximale du plafond (montage mural) 305 mm (12 po) Référencement des agences Fabricant Edwards, A Division of UTC Fire & Security Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA Année de fabrication Les deux premiers chiffres du code de date (situé sur l'étiquette d'identification de produit) sont l'année de la fabrication. Coefficient UL/ULC 24 CC ou 24 FWR réglementé Normes nord- américaines Conforme : UL 268, UL 464, CAN/ ULC-S525 et de CAN/ULC-S529 Suivez : CSA C22.1 et CAN/ULC-S524. Il est interdit d’installer ce dispositif dans un logement comme stipulé dans le code national du bâtiment du Canada.