SlideShare une entreprise Scribd logo
1  sur  45
Télécharger pour lire hors ligne
Presented by
K.Subramani
Inspection, Testing & Maintenance of Fire Pumps
A fire pump is designed to increase water pressure. The pump intake and
discharge piping must be capable of flowing the required volume to which
the pump will add the needed pressure for fire protection. The pump can
be started manually, but is usually arranged to start automatically upon a
drop in system pressure or the activation of a fire suppression system.
“FIRE PUMP IS THE HEART OF THE FIRE
PROTECTION SYSTEM”
Introduction of Fire Pump
• NFPA 20 Installation of Stationary Pumps
• NFPA 25 Inspection, Testing & Maintenance of Water Base Fire
Protection System, Chapter 8
• UAE Fire & Life Safety Code of Practice
• FM Global (Factory Mutual)
Standards
• End Suction Pumps
• Vertical In-line
• Horizontal Split Case
• Vertical Multi Stage
• Vertical Turbine
Type of Fire Pumps
End Suction Pumps
Vertical In-line Pump
Horizontal Split Case
Vertical Multi Stage Pump
Vertical Turbine Pump
Approvals
• Driven Type : Electrical Motor / Diesel Engine
• Flow Range (GPM)
• Head pressure (ft)
• Horse power (HP)
• Revolution Per Minute (RPM)
Pump Specification
Data Plate
• Pump shaft coupling
• Automatic air release valve
• Pressure gauges
• Circulation relief valve (Electrical Driven Pump)
• Pump relief valve (Diesel Engine Driven pump)
• Alarm sensors and indicators
• Right-angle gear sets (for engine-driven vertical shaft turbine pumps)
• Jockey pump and accessories
Pump accessories
The automatic air relief valve removes the air that may become trapped
inside the pump casing. On some old installations, the air release valve
may be manually operated. An air release valve mounted on top of the
fire pump casing.
Automatic air release valve
“Air in a pressurized pipeline is a serious concern.
Obviously, its removal will result in a more
efficient, cost effective operation and potentially
avoid more serious problems.”
• The circulation relief valve is designed to open and
discharge a small amount of water when the pump is
running at churn. The valve should be 3/4 in. (19 mm) for
pump capacities up to 2500 gpm (9462 L/min) and 1 in. (25
mm) for larger pumps. This valve prevents the pump casing
from overheating and damaging the impeller, packings,
and bearings during extended periods of running at churn.
When the fire pump is operating while discharging water
through the fire protection system, the circulation relief
valve is not needed for cooling and should close. The
circulation relief valve is usually spring-operated and can
fail with the slightest bit of obstructing material in the
valve and or corrosion enters the valve.
• The circulation relief valve should be set to open at the
pump rated pressure.
• Discharge from this valve should be piped to a drain or to
the outdoors, and the discharge should be observed during
the weekly test of the fire pump.
Circulation relief valve
NFPA 20 is very clear that a pressure relief valve
is only needed when a diesel engine fire pump is
installed and where a total of 121 percent of the
net rated shutoff (churn) pressure plus the
maximum static suction pressure, adjusted for
elevation, exceeds the pressure for which the
system components are rated. Pressure relief
valves are also required for variable-speed drive
fire pumps. Pressure relief valves should never
be used on electric drive (constant speed) fire
pumps.
Pump Relief Valve
Jockey pump is a low-flow, high-pressure pump It is designed to maintain
a constant pressure on the system, accounting for minor pressure
fluctuations.
NFPA 20 suggests that the jockey pump be sized 1% of pump flow at 10
psi over pump rated pressure.
Jockey Pump
• Electrical Driven Pump
• Diesel Driven Pump
• Note: The pump driver shall not overload
beyond its rating (including any service factor
allowance) when delivering the necessary
brake horsepower.
Type of Driver
• Automatic and manual controllers for applying
the energy source to the driver shall be
capable of providing this operation for the
type of pump used.
Controller
Packing gland is used to seal water leakage
around shaft and when the pump is not in
operation minimum one drop of water per
second is required for gland lubrication and a
steady trickle of water is needed to keep gland in
cool condition when the pump is operating and
adjustment should also be done if required.
Packing Gland
The mechanical seal has two parts one is Rotary
and another is fixed. This is fix in the pump shaft,
acts as a check valve and a slider bearing. Its is
designed to prevent liquid under pressure from
leaking out of the pump, or from drawing air into
the pump when under vacuum conditions.
Mechanical Seal
Churn:
The pump is operating with no flow.
Rated capacity:
The pump is discharging water at the specified pressure.
Overload:
The pump is discharging water at a rate of 150 percent of
rated flow at a pressure of 65 percent of rated pressure.
The fire pump system, when started by pressure drop, should be arranged as follows (NFPA
minimum Requirement):
1. The jockey pump stop point should equal the pump churn pressure plus the minimum
static supply pressure.
2. The jockey pump start point should be at least 10 psi (0.68 bar) less than the jockey pump
stop point.
3. The fire pump start point should be 5 psi (0.34 bar) less than the jockey pump start point.
Use 10 psi (0.68 bar) increments for each additional pump.
4. Where minimum run timers are provided, the pump will continue to operate after attaining
these pressures.
The final pressures should not exceed the pressure rating of the system.
Fire Pump Setting
The purpose of inspection, Testing & Maintenance
shall be to verify that the pump assembly appears
to be in operating condition and is free from
physical
Inspection, Testing & Maintenance
8.2 Inspection.
(1) P ump house conditions:
(a) Heat is adequate, not less than 4.4°C (40°F) [21°C (70°F) for pump room with diesel pumps without
engine heaters].
(b) Ventilating louvers are free to operate.
(2) P ump system conditions:
(a) Pump suction and discharge and bypass valves are fully open.
(b) Piping is free of leaks.
(c) Suction line pressure gauge reading is normal.
(d) System line pressure gauge reading is normal.
(e) Suction reservoir is full.
(f) Wet pit suction screens are unobstructed and in place.
(3) Electrical system conditions:
(a) Controller pilot light (power on) is illuminated.
(b) Transfer switch normal pilot light is illuminated.
(c) Isolating switch is closed — standby (emergency) source.
(d) Reverse phase alarm pilot light is off or normal phase rotation pilot light is on.
(e) Oil level in vertical motor sight glass is normal.
Weekly
(4) Diesel engine system conditions:
(a) Fuel tank is two-thirds full.
(b) Controller selector switch is in auto position.
(c) Batteries’ (2) voltage readings are normal.
(d) Batteries’ (2) charging current readings are normal.
e) Batteries’ (2) pilot lights are on or battery failure (2) pilot lights are off.
(f) All alarm pilot lights are off.
(g) Engine running time meter is reading.
(h) Oil level in right angle gear drive is normal.
(i) Crankcase oil level is normal.
(j) Cooling water level is normal.
(k) Electrolyte level in batteries is normal.
(l) Battery terminals are free from corrosion.
(m) Water-jacket heater is operating.
Weekly Inspection
8.3.1 A weekly test of fire pump assemblies shall be conducted without flowing water.
8.3.1.1 This test shall be conducted by starting the pump automatically.
8.3.1.2 The electric pump shall run a minimum of 10 minutes.(Monthly)
When a pump is started, a great deal of heat is generated from the energy needed to bring the
pump up to speed. Paragraph 8.3.1.2 requires that the electric motor be run for 10 minutes so the motor windings
can cool down after starting across the line. Another reason for the 10 minute requirement is that it allows time to
check the pump packing and bearings to determine if they are overheating or leaking excessively.
8.3.1.3 The diesel pump shall run a minimum of 30 minutes.
A diesel fire pump be operated for 30 minutes. This requirement is intended to allow the pump and driver to reach operating
temperature and will reveal any overheating problems. The 30 minute operating time is also intended to consume fuel to
prevent the fuel from stagnating and to prevent wet stacking in the exhaust system.
8.3.1.4 A valve installed to open as a safety feature shall be permitted to discharge water.
8.3.1.5 The automatic weekly test timer shall be permitted to be substituted for the starting procedure.
8.3* Testing
8.3.2 Weekly Tests.
8.3.2.1* Qualified operating personnel shall be in attendance during the weekly pump operation.
8.3.2.2 The pertinent visual observations or adjustments specified in the following checklists shall be
conducted while the pump is running:
(1) Pump system procedure:
(a) Record the system suction and discharge pressure gauge readings
(b) Check the pump packing glands for slight discharge
(c) Adjust gland nuts if necessary
(d) Check for unusual noise or vibration
(e) Check packing boxes, bearings, or pump casing for overheating
(f) Record the pump starting pressure
(2) Electrical system procedure: (Monthly)
(a) Observe the time for motor to accelerate to full speed
(b) Record the time controller is on first step (for reduced voltage or reduced current starting)
(c) Record the time pump runs after starting (for automatic stop controllers)
(3) Diesel engine system procedure:
(a) Observe the time for engine to crank
(b) Observe the time for engine to reach running speed
(c) Observe the engine oil pressure gauge, speed indicator, water, and oil temperature indicators
periodically while engine is running
(d) Record any abnormalities
(e) Check the heat exchanger for cooling water flow
8.3.3.1 An annual test of each pump assembly shall be conducted under minimum, rated, and peak
flows of the fire pump by controlling the quantity of water discharged through approved test devices.
8.3.3.1.1* If available suction supplies do not allow flowing of 150 percent of the rated pump capacity,
the fire pump shall be permitted to operate at maximum allowable discharge.
8.3.3.1.2* This test shall be conducted as described in 8.3.3.1.2.1, 8.3.3.1.2.2, or 8.3.3.1.2.3.
8.3.3.1.2.1 Use of the Pump Discharge Via the Hose Streams. Pump suction and discharge pressures
and the flow measurements of each hose stream shall determine the total pump output. Care shall be
taken to prevent water damage by verifying there is adequate drainage for the high-pressure water
discharge from hoses.
8.3.3.1.2.2 Use of the Pump Discharge Via the Bypass Flowmeter to Drain or Suction the Reservoir.
Pump suction and discharge pressures and the flowmeter measurements shall determine the total
pump output.
8.3.3.1.2.3 Use of the Pump Discharge Via the Bypass Flowmeter to Pump Suction (Closed-Loop
Metering). Pump suction and discharge pressures and the flowmeter measurements shall determine
the total pump output.
8.3.3.1.3 Where the annual test is conducted periodically in accordance with 8.3.3.1.2.3, a test shall be
conducted every 3 years in accordance with 8.3.3.1.2.1 or 8.3.3.1.2.2 in lieu of the method described in
8.3.3.1.2.3.
8.3.3 Annual Tests
8.3.3.1.4 Where 8.3.3.1.2.2 or 8.3.3.1.2.3 is used, the flow meter shall be adjusted immediately prior to
conducting the test in accordance with the manufacturer’s instructions. If the test results are not
consistent with the previous annual test, 8.3.3.1.2.1 shall be used. If testing in accordance with
8.3.3.1.2.1 is not possible, a flowmeter calibration shall be performed and the test shall be repeated.
8.3.3.2 The pertinent visual observations, measurements, and adjustments specified in the following
checklists shall be conducted annually
while the pump is running and flowing water under the specified output condition:
(1) At no-flow condition (churn):
(a) Check the circulation relief valve for operation to discharge water
(b) Check the pressure relief valve (if installed) for proper operation
(c) Continue the test for ½ hour
(2) At each flow condition:
(a) Record the electric motor voltage and current (all lines)
(b) Record the pump speed in rpm
(c) Record the simultaneous (approximately) readings of pump suction and discharge pressures and
pump discharge flow
8.3.3.3* For installations having a pressure relief valve, the operation of the relief valve shall be closely
observed during each flow condition to determine if the pump discharge pressure exceeds the normal
operating pressure of the system components.
8.3.3.3.1 The pressure relief valve shall also be observed during each flow condition to determine if the
pressure relief valve closes at the proper pressure.
8.3.3.3.2 A pressure relief valve that is open during a flow condition will affect test results.
8.3.3.3.3 The pressure relief valve shall be closed during flow conditions if necessary to achieve
minimum rated characteristics for the pump and reset to normal position at the conclusion of the
pump test.
8.3.3.4 For installations having an automatic transfer switch, the following test shall be performed to
ensure that the overcurrent protective devices (i.e., fuses or circuit breakers) do not open:
(1) Simulate a power failure condition while the pump is operating at peak load
(2) Verify that the transfer switch transfers power to the alternate power source
(3) Verify that the pump continues to perform at peak load
(4) Remove the power failure condition and verify that after a time delay, the pump is reconnected to
the normal power source
8.3.5.5 Current and voltage readings whose product does not exceed the product of the rated voltage
and rated full-load current multiplied by the permitted motor service factor shall be considered
acceptable. Voltage readings at the motor within 5 percent below or 10 percent above threated (i.e.,
nameplate) voltage shall be considered acceptable.
0
50
100
150
200
250
300
350
400
0 750 1125
NETPRESSURE(PSI)
FLOW (GPM)
PERFORMANCE CURVE
Actual Pressure
Rated Pressure
Characteristic Curve
A copy of the manufacturer’s certified pump
test characteristic curve shall be available
for comparison of the results of the field
acceptance test. [NFPA 20-10: 14.2.4.1]
The fire pump as installed shall equal the
performance as indicated on the
manufacturer’s certified shop test
characteristic curve within the accuracy
limits of the test equipment. [NFPA 20-10:
14.2.4.2]
The fire pump shall perform at minimum,
rated, and peak loads without objectionable
overheating of any component. [NFPA 20-
10: 14.2.5.2.1]
8.4 Reports.
8.4.1 Any abnormality observed during inspection or testing shall be reported
promptly to the person responsible for correcting the abnormality.
8.4.2* Test results shall be recorded and retained for comparison purposes in
accordance with Section 4.3.
8.4.2.1 All time delay intervals associated with the pump’s starting, stopping,
and energy source transfer shall be recorded.
8.5 Maintenance.
8.5.1* A preventive maintenance program shall be established on all
components of the pump assembly in accordance with the manufacturer’s
recommendations.
8.5.2 Records shall be maintained on all work performed on the pump, driver,
controller, and auxiliary equipment.
8.5.3 In the absence of manufacturer’s recommendations for preventive
maintenance,
All rotating machines, pumps included, vibrate to some extent due to various reasons, the most
common of which are typically the following:
• Improper installation at site
• Improper balancing of pump rotor
• Excessively turbulent fluid flow
• Pressure fluctuations
• Cavitation or internal recirculation in pumps
• Normal pump wear after prolonged operation.
Pump Vibration
Pump Vibration Level
Misalignment will affect the Pump performance
and damage the pump.
ACCEPTABLE PUMP ALIGNMENT TOLERANCES
RPM 1800 RPM 3600 RPM
Parallel alignment 0.002“ 0.004"
Angular 0.004“ 0.006"
Alignment
• Cooling System filled with premixed water and coolant conditioner.
• Batteries serviced and charged 24 hours connected to the engine
• Only distilled water shall be used.
• Electrolyte shall be added to the batteries a minimum of 24 hours prior to the time the engine has to be started.
• Battery plates shall be kept submerged at all times.
• The fuel storage tanks shall be kept as full as practical at all times, but never below 66% of tank capacity. A fuel
level indicator shall be provided to activate at the 2/3rds tank level.
• The fire pump shall be started and brought up to rated speed without interruption within 20 seconds.
• Rain cap on outlet if necessary; tight connections.
• Fire diesel engine pump exhaust system need to fix gravity louvers to avoid any damages as there is chance of
water entry to engine through exhaust system and also any hard particle may go through.
• Engines shall be regulated to have no more the 10% speed difference between shutoff and maximum load.
• Engines shall be provided with an overspeed shutdown at 20% above rated engine speed with a manual reset.
(Only overspeed shutdown or a signal from the diesel controller will shut down an engine.)
Diesel Engine Observation
Questions and Answer
KEEP REMEMBER
“FIRE PUMP IS THE HEART OF THE FIRE
PROTECTION SYSTEM”
Thank you

Contenu connexe

Tendances

Comparision between NFPA and TAc rules for Power plants
Comparision between NFPA and TAc rules for Power plantsComparision between NFPA and TAc rules for Power plants
Comparision between NFPA and TAc rules for Power plants
vakil jagdish
 

Tendances (20)

Introductory training on fire water pumping system
Introductory training  on fire water pumping systemIntroductory training  on fire water pumping system
Introductory training on fire water pumping system
 
Fire pump tutorial
 Fire pump tutorial Fire pump tutorial
Fire pump tutorial
 
Fw pump basis nfpa
Fw pump basis   nfpaFw pump basis   nfpa
Fw pump basis nfpa
 
Fire pumps
Fire pumpsFire pumps
Fire pumps
 
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptxFIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
 
Basic fire alarm training (1)
Basic fire alarm training (1)Basic fire alarm training (1)
Basic fire alarm training (1)
 
Basic training water based fire protection
Basic training  water based fire protectionBasic training  water based fire protection
Basic training water based fire protection
 
Fire pumps in brief
Fire pumps in briefFire pumps in brief
Fire pumps in brief
 
Chapter 04
Chapter 04Chapter 04
Chapter 04
 
BASICS OF FIRE PROTECTION SYSTEM, HYDRANT SYSTEM.ppt
BASICS OF FIRE PROTECTION SYSTEM, HYDRANT SYSTEM.pptBASICS OF FIRE PROTECTION SYSTEM, HYDRANT SYSTEM.ppt
BASICS OF FIRE PROTECTION SYSTEM, HYDRANT SYSTEM.ppt
 
Comparision between NFPA and TAc rules for Power plants
Comparision between NFPA and TAc rules for Power plantsComparision between NFPA and TAc rules for Power plants
Comparision between NFPA and TAc rules for Power plants
 
Electrical Safety, Personal Protective Equipment, & Z462 Compliance
Electrical Safety, Personal Protective Equipment, & Z462 ComplianceElectrical Safety, Personal Protective Equipment, & Z462 Compliance
Electrical Safety, Personal Protective Equipment, & Z462 Compliance
 
Fire_Fighting_Course_Prepared_by.pdf
Fire_Fighting_Course_Prepared_by.pdfFire_Fighting_Course_Prepared_by.pdf
Fire_Fighting_Course_Prepared_by.pdf
 
Water mist prepared by salah ramadan
Water mist prepared by salah ramadanWater mist prepared by salah ramadan
Water mist prepared by salah ramadan
 
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTFIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
 
High Expansion Foam System
High Expansion Foam SystemHigh Expansion Foam System
High Expansion Foam System
 
Fire fighting -2 By Er. Ezaz
Fire fighting -2 By Er. EzazFire fighting -2 By Er. Ezaz
Fire fighting -2 By Er. Ezaz
 
Fire Detection and Alarm System (FDAS).pptx
Fire Detection and Alarm System (FDAS).pptxFire Detection and Alarm System (FDAS).pptx
Fire Detection and Alarm System (FDAS).pptx
 
Fire Protection System Design
Fire Protection System DesignFire Protection System Design
Fire Protection System Design
 
Clean Agent & Inert Gas Fire Suppression
Clean Agent & Inert Gas Fire SuppressionClean Agent & Inert Gas Fire Suppression
Clean Agent & Inert Gas Fire Suppression
 

Similaire à Inspection, Testing and Maintenance of fire pump

Hyundai hsl650 7 skid steer loader service repair manual
Hyundai hsl650 7 skid steer loader service repair manualHyundai hsl650 7 skid steer loader service repair manual
Hyundai hsl650 7 skid steer loader service repair manual
fjjsekdmme
 

Similaire à Inspection, Testing and Maintenance of fire pump (20)

Hyundai hsl650 7 skid steer loader service repair manual
Hyundai hsl650 7 skid steer loader service repair manualHyundai hsl650 7 skid steer loader service repair manual
Hyundai hsl650 7 skid steer loader service repair manual
 
Hyundai hsl650 7 skid steer loader service repair manual
Hyundai hsl650 7 skid steer loader service repair manualHyundai hsl650 7 skid steer loader service repair manual
Hyundai hsl650 7 skid steer loader service repair manual
 
Hydraulic ppt.pptx
Hydraulic ppt.pptxHydraulic ppt.pptx
Hydraulic ppt.pptx
 
hydroelectric power plant_overview.ppt
hydroelectric power plant_overview.ppthydroelectric power plant_overview.ppt
hydroelectric power plant_overview.ppt
 
New holland t8010 tractor service repair manual
New holland t8010 tractor service repair manualNew holland t8010 tractor service repair manual
New holland t8010 tractor service repair manual
 
New holland t8020 tractor service repair manual
New holland t8020 tractor service repair manualNew holland t8020 tractor service repair manual
New holland t8020 tractor service repair manual
 
New holland t8040 tractor service repair manual
New holland t8040 tractor service repair manualNew holland t8040 tractor service repair manual
New holland t8040 tractor service repair manual
 
New Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdfNew Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdf
 
New holland t8040 tractor service repair manual instant download
New holland t8040 tractor service repair manual instant downloadNew holland t8040 tractor service repair manual instant download
New holland t8040 tractor service repair manual instant download
 
New holland t8030 tractor service repair manual
New holland t8030 tractor service repair manualNew holland t8030 tractor service repair manual
New holland t8030 tractor service repair manual
 
New holland t8010 tractor service repair manual
New holland t8010 tractor service repair manualNew holland t8010 tractor service repair manual
New holland t8010 tractor service repair manual
 
New holland t8050 tractor service repair manual
New holland t8050 tractor service repair manualNew holland t8050 tractor service repair manual
New holland t8050 tractor service repair manual
 
New holland t8030 tractor service repair manual
New holland t8030 tractor service repair manualNew holland t8030 tractor service repair manual
New holland t8030 tractor service repair manual
 
New Holland T8020 Tractor Service Repair Manual.pdf
New Holland T8020 Tractor Service Repair Manual.pdfNew Holland T8020 Tractor Service Repair Manual.pdf
New Holland T8020 Tractor Service Repair Manual.pdf
 
New Holland T8030 Tractor Service Repair Manual.pdf
New Holland T8030 Tractor Service Repair Manual.pdfNew Holland T8030 Tractor Service Repair Manual.pdf
New Holland T8030 Tractor Service Repair Manual.pdf
 
New Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdfNew Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdf
 
New Holland T8010 Tractor Service Repair Manual.pdf
New Holland T8010 Tractor Service Repair Manual.pdfNew Holland T8010 Tractor Service Repair Manual.pdf
New Holland T8010 Tractor Service Repair Manual.pdf
 
New Holland T8040 Tractor Service Repair Manual.pdf
New Holland T8040 Tractor Service Repair Manual.pdfNew Holland T8040 Tractor Service Repair Manual.pdf
New Holland T8040 Tractor Service Repair Manual.pdf
 
New holland t8010 tractor service repair manual
New holland t8010 tractor service repair manualNew holland t8010 tractor service repair manual
New holland t8010 tractor service repair manual
 
New Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdfNew Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdf
 

Dernier

Beyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global ImpactBeyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global Impact
PECB
 
The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptx
heathfieldcps1
 
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in DelhiRussian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
kauryashika82
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdf
QucHHunhnh
 
Seal of Good Local Governance (SGLG) 2024Final.pptx
Seal of Good Local Governance (SGLG) 2024Final.pptxSeal of Good Local Governance (SGLG) 2024Final.pptx
Seal of Good Local Governance (SGLG) 2024Final.pptx
negromaestrong
 
Gardella_PRCampaignConclusion Pitch Letter
Gardella_PRCampaignConclusion Pitch LetterGardella_PRCampaignConclusion Pitch Letter
Gardella_PRCampaignConclusion Pitch Letter
MateoGardella
 
Activity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfActivity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdf
ciinovamais
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdf
QucHHunhnh
 

Dernier (20)

Measures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeMeasures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and Mode
 
This PowerPoint helps students to consider the concept of infinity.
This PowerPoint helps students to consider the concept of infinity.This PowerPoint helps students to consider the concept of infinity.
This PowerPoint helps students to consider the concept of infinity.
 
psychiatric nursing HISTORY COLLECTION .docx
psychiatric  nursing HISTORY  COLLECTION  .docxpsychiatric  nursing HISTORY  COLLECTION  .docx
psychiatric nursing HISTORY COLLECTION .docx
 
Beyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global ImpactBeyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global Impact
 
The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptx
 
Basic Civil Engineering first year Notes- Chapter 4 Building.pptx
Basic Civil Engineering first year Notes- Chapter 4 Building.pptxBasic Civil Engineering first year Notes- Chapter 4 Building.pptx
Basic Civil Engineering first year Notes- Chapter 4 Building.pptx
 
Holdier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdfHoldier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdf
 
Unit-IV- Pharma. Marketing Channels.pptx
Unit-IV- Pharma. Marketing Channels.pptxUnit-IV- Pharma. Marketing Channels.pptx
Unit-IV- Pharma. Marketing Channels.pptx
 
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in DelhiRussian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdf
 
Seal of Good Local Governance (SGLG) 2024Final.pptx
Seal of Good Local Governance (SGLG) 2024Final.pptxSeal of Good Local Governance (SGLG) 2024Final.pptx
Seal of Good Local Governance (SGLG) 2024Final.pptx
 
Gardella_PRCampaignConclusion Pitch Letter
Gardella_PRCampaignConclusion Pitch LetterGardella_PRCampaignConclusion Pitch Letter
Gardella_PRCampaignConclusion Pitch Letter
 
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxSOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
 
Mehran University Newsletter Vol-X, Issue-I, 2024
Mehran University Newsletter Vol-X, Issue-I, 2024Mehran University Newsletter Vol-X, Issue-I, 2024
Mehran University Newsletter Vol-X, Issue-I, 2024
 
Application orientated numerical on hev.ppt
Application orientated numerical on hev.pptApplication orientated numerical on hev.ppt
Application orientated numerical on hev.ppt
 
Activity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfActivity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdf
 
APM Welcome, APM North West Network Conference, Synergies Across Sectors
APM Welcome, APM North West Network Conference, Synergies Across SectorsAPM Welcome, APM North West Network Conference, Synergies Across Sectors
APM Welcome, APM North West Network Conference, Synergies Across Sectors
 
Unit-V; Pricing (Pharma Marketing Management).pptx
Unit-V; Pricing (Pharma Marketing Management).pptxUnit-V; Pricing (Pharma Marketing Management).pptx
Unit-V; Pricing (Pharma Marketing Management).pptx
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdf
 
Grant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingGrant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy Consulting
 

Inspection, Testing and Maintenance of fire pump

  • 1. Presented by K.Subramani Inspection, Testing & Maintenance of Fire Pumps
  • 2. A fire pump is designed to increase water pressure. The pump intake and discharge piping must be capable of flowing the required volume to which the pump will add the needed pressure for fire protection. The pump can be started manually, but is usually arranged to start automatically upon a drop in system pressure or the activation of a fire suppression system. “FIRE PUMP IS THE HEART OF THE FIRE PROTECTION SYSTEM” Introduction of Fire Pump
  • 3. • NFPA 20 Installation of Stationary Pumps • NFPA 25 Inspection, Testing & Maintenance of Water Base Fire Protection System, Chapter 8 • UAE Fire & Life Safety Code of Practice • FM Global (Factory Mutual) Standards
  • 4. • End Suction Pumps • Vertical In-line • Horizontal Split Case • Vertical Multi Stage • Vertical Turbine Type of Fire Pumps
  • 11. • Driven Type : Electrical Motor / Diesel Engine • Flow Range (GPM) • Head pressure (ft) • Horse power (HP) • Revolution Per Minute (RPM) Pump Specification
  • 13. • Pump shaft coupling • Automatic air release valve • Pressure gauges • Circulation relief valve (Electrical Driven Pump) • Pump relief valve (Diesel Engine Driven pump) • Alarm sensors and indicators • Right-angle gear sets (for engine-driven vertical shaft turbine pumps) • Jockey pump and accessories Pump accessories
  • 14. The automatic air relief valve removes the air that may become trapped inside the pump casing. On some old installations, the air release valve may be manually operated. An air release valve mounted on top of the fire pump casing. Automatic air release valve
  • 15. “Air in a pressurized pipeline is a serious concern. Obviously, its removal will result in a more efficient, cost effective operation and potentially avoid more serious problems.”
  • 16. • The circulation relief valve is designed to open and discharge a small amount of water when the pump is running at churn. The valve should be 3/4 in. (19 mm) for pump capacities up to 2500 gpm (9462 L/min) and 1 in. (25 mm) for larger pumps. This valve prevents the pump casing from overheating and damaging the impeller, packings, and bearings during extended periods of running at churn. When the fire pump is operating while discharging water through the fire protection system, the circulation relief valve is not needed for cooling and should close. The circulation relief valve is usually spring-operated and can fail with the slightest bit of obstructing material in the valve and or corrosion enters the valve. • The circulation relief valve should be set to open at the pump rated pressure. • Discharge from this valve should be piped to a drain or to the outdoors, and the discharge should be observed during the weekly test of the fire pump. Circulation relief valve
  • 17. NFPA 20 is very clear that a pressure relief valve is only needed when a diesel engine fire pump is installed and where a total of 121 percent of the net rated shutoff (churn) pressure plus the maximum static suction pressure, adjusted for elevation, exceeds the pressure for which the system components are rated. Pressure relief valves are also required for variable-speed drive fire pumps. Pressure relief valves should never be used on electric drive (constant speed) fire pumps. Pump Relief Valve
  • 18. Jockey pump is a low-flow, high-pressure pump It is designed to maintain a constant pressure on the system, accounting for minor pressure fluctuations. NFPA 20 suggests that the jockey pump be sized 1% of pump flow at 10 psi over pump rated pressure. Jockey Pump
  • 19. • Electrical Driven Pump • Diesel Driven Pump • Note: The pump driver shall not overload beyond its rating (including any service factor allowance) when delivering the necessary brake horsepower. Type of Driver
  • 20. • Automatic and manual controllers for applying the energy source to the driver shall be capable of providing this operation for the type of pump used. Controller
  • 21. Packing gland is used to seal water leakage around shaft and when the pump is not in operation minimum one drop of water per second is required for gland lubrication and a steady trickle of water is needed to keep gland in cool condition when the pump is operating and adjustment should also be done if required. Packing Gland
  • 22. The mechanical seal has two parts one is Rotary and another is fixed. This is fix in the pump shaft, acts as a check valve and a slider bearing. Its is designed to prevent liquid under pressure from leaking out of the pump, or from drawing air into the pump when under vacuum conditions. Mechanical Seal
  • 23. Churn: The pump is operating with no flow. Rated capacity: The pump is discharging water at the specified pressure. Overload: The pump is discharging water at a rate of 150 percent of rated flow at a pressure of 65 percent of rated pressure.
  • 24. The fire pump system, when started by pressure drop, should be arranged as follows (NFPA minimum Requirement): 1. The jockey pump stop point should equal the pump churn pressure plus the minimum static supply pressure. 2. The jockey pump start point should be at least 10 psi (0.68 bar) less than the jockey pump stop point. 3. The fire pump start point should be 5 psi (0.34 bar) less than the jockey pump start point. Use 10 psi (0.68 bar) increments for each additional pump. 4. Where minimum run timers are provided, the pump will continue to operate after attaining these pressures. The final pressures should not exceed the pressure rating of the system. Fire Pump Setting
  • 25. The purpose of inspection, Testing & Maintenance shall be to verify that the pump assembly appears to be in operating condition and is free from physical Inspection, Testing & Maintenance
  • 26. 8.2 Inspection. (1) P ump house conditions: (a) Heat is adequate, not less than 4.4°C (40°F) [21°C (70°F) for pump room with diesel pumps without engine heaters]. (b) Ventilating louvers are free to operate. (2) P ump system conditions: (a) Pump suction and discharge and bypass valves are fully open. (b) Piping is free of leaks. (c) Suction line pressure gauge reading is normal. (d) System line pressure gauge reading is normal. (e) Suction reservoir is full. (f) Wet pit suction screens are unobstructed and in place. (3) Electrical system conditions: (a) Controller pilot light (power on) is illuminated. (b) Transfer switch normal pilot light is illuminated. (c) Isolating switch is closed — standby (emergency) source. (d) Reverse phase alarm pilot light is off or normal phase rotation pilot light is on. (e) Oil level in vertical motor sight glass is normal. Weekly
  • 27. (4) Diesel engine system conditions: (a) Fuel tank is two-thirds full. (b) Controller selector switch is in auto position. (c) Batteries’ (2) voltage readings are normal. (d) Batteries’ (2) charging current readings are normal. e) Batteries’ (2) pilot lights are on or battery failure (2) pilot lights are off. (f) All alarm pilot lights are off. (g) Engine running time meter is reading. (h) Oil level in right angle gear drive is normal. (i) Crankcase oil level is normal. (j) Cooling water level is normal. (k) Electrolyte level in batteries is normal. (l) Battery terminals are free from corrosion. (m) Water-jacket heater is operating. Weekly Inspection
  • 28. 8.3.1 A weekly test of fire pump assemblies shall be conducted without flowing water. 8.3.1.1 This test shall be conducted by starting the pump automatically. 8.3.1.2 The electric pump shall run a minimum of 10 minutes.(Monthly) When a pump is started, a great deal of heat is generated from the energy needed to bring the pump up to speed. Paragraph 8.3.1.2 requires that the electric motor be run for 10 minutes so the motor windings can cool down after starting across the line. Another reason for the 10 minute requirement is that it allows time to check the pump packing and bearings to determine if they are overheating or leaking excessively. 8.3.1.3 The diesel pump shall run a minimum of 30 minutes. A diesel fire pump be operated for 30 minutes. This requirement is intended to allow the pump and driver to reach operating temperature and will reveal any overheating problems. The 30 minute operating time is also intended to consume fuel to prevent the fuel from stagnating and to prevent wet stacking in the exhaust system. 8.3.1.4 A valve installed to open as a safety feature shall be permitted to discharge water. 8.3.1.5 The automatic weekly test timer shall be permitted to be substituted for the starting procedure. 8.3* Testing
  • 29. 8.3.2 Weekly Tests. 8.3.2.1* Qualified operating personnel shall be in attendance during the weekly pump operation. 8.3.2.2 The pertinent visual observations or adjustments specified in the following checklists shall be conducted while the pump is running: (1) Pump system procedure: (a) Record the system suction and discharge pressure gauge readings (b) Check the pump packing glands for slight discharge (c) Adjust gland nuts if necessary (d) Check for unusual noise or vibration (e) Check packing boxes, bearings, or pump casing for overheating (f) Record the pump starting pressure (2) Electrical system procedure: (Monthly) (a) Observe the time for motor to accelerate to full speed (b) Record the time controller is on first step (for reduced voltage or reduced current starting) (c) Record the time pump runs after starting (for automatic stop controllers)
  • 30. (3) Diesel engine system procedure: (a) Observe the time for engine to crank (b) Observe the time for engine to reach running speed (c) Observe the engine oil pressure gauge, speed indicator, water, and oil temperature indicators periodically while engine is running (d) Record any abnormalities (e) Check the heat exchanger for cooling water flow
  • 31. 8.3.3.1 An annual test of each pump assembly shall be conducted under minimum, rated, and peak flows of the fire pump by controlling the quantity of water discharged through approved test devices. 8.3.3.1.1* If available suction supplies do not allow flowing of 150 percent of the rated pump capacity, the fire pump shall be permitted to operate at maximum allowable discharge. 8.3.3.1.2* This test shall be conducted as described in 8.3.3.1.2.1, 8.3.3.1.2.2, or 8.3.3.1.2.3. 8.3.3.1.2.1 Use of the Pump Discharge Via the Hose Streams. Pump suction and discharge pressures and the flow measurements of each hose stream shall determine the total pump output. Care shall be taken to prevent water damage by verifying there is adequate drainage for the high-pressure water discharge from hoses. 8.3.3.1.2.2 Use of the Pump Discharge Via the Bypass Flowmeter to Drain or Suction the Reservoir. Pump suction and discharge pressures and the flowmeter measurements shall determine the total pump output. 8.3.3.1.2.3 Use of the Pump Discharge Via the Bypass Flowmeter to Pump Suction (Closed-Loop Metering). Pump suction and discharge pressures and the flowmeter measurements shall determine the total pump output. 8.3.3.1.3 Where the annual test is conducted periodically in accordance with 8.3.3.1.2.3, a test shall be conducted every 3 years in accordance with 8.3.3.1.2.1 or 8.3.3.1.2.2 in lieu of the method described in 8.3.3.1.2.3. 8.3.3 Annual Tests
  • 32. 8.3.3.1.4 Where 8.3.3.1.2.2 or 8.3.3.1.2.3 is used, the flow meter shall be adjusted immediately prior to conducting the test in accordance with the manufacturer’s instructions. If the test results are not consistent with the previous annual test, 8.3.3.1.2.1 shall be used. If testing in accordance with 8.3.3.1.2.1 is not possible, a flowmeter calibration shall be performed and the test shall be repeated. 8.3.3.2 The pertinent visual observations, measurements, and adjustments specified in the following checklists shall be conducted annually while the pump is running and flowing water under the specified output condition: (1) At no-flow condition (churn): (a) Check the circulation relief valve for operation to discharge water (b) Check the pressure relief valve (if installed) for proper operation (c) Continue the test for ½ hour (2) At each flow condition: (a) Record the electric motor voltage and current (all lines) (b) Record the pump speed in rpm (c) Record the simultaneous (approximately) readings of pump suction and discharge pressures and pump discharge flow 8.3.3.3* For installations having a pressure relief valve, the operation of the relief valve shall be closely observed during each flow condition to determine if the pump discharge pressure exceeds the normal operating pressure of the system components. 8.3.3.3.1 The pressure relief valve shall also be observed during each flow condition to determine if the pressure relief valve closes at the proper pressure.
  • 33. 8.3.3.3.2 A pressure relief valve that is open during a flow condition will affect test results. 8.3.3.3.3 The pressure relief valve shall be closed during flow conditions if necessary to achieve minimum rated characteristics for the pump and reset to normal position at the conclusion of the pump test. 8.3.3.4 For installations having an automatic transfer switch, the following test shall be performed to ensure that the overcurrent protective devices (i.e., fuses or circuit breakers) do not open: (1) Simulate a power failure condition while the pump is operating at peak load (2) Verify that the transfer switch transfers power to the alternate power source (3) Verify that the pump continues to perform at peak load (4) Remove the power failure condition and verify that after a time delay, the pump is reconnected to the normal power source 8.3.5.5 Current and voltage readings whose product does not exceed the product of the rated voltage and rated full-load current multiplied by the permitted motor service factor shall be considered acceptable. Voltage readings at the motor within 5 percent below or 10 percent above threated (i.e., nameplate) voltage shall be considered acceptable.
  • 34. 0 50 100 150 200 250 300 350 400 0 750 1125 NETPRESSURE(PSI) FLOW (GPM) PERFORMANCE CURVE Actual Pressure Rated Pressure Characteristic Curve A copy of the manufacturer’s certified pump test characteristic curve shall be available for comparison of the results of the field acceptance test. [NFPA 20-10: 14.2.4.1] The fire pump as installed shall equal the performance as indicated on the manufacturer’s certified shop test characteristic curve within the accuracy limits of the test equipment. [NFPA 20-10: 14.2.4.2] The fire pump shall perform at minimum, rated, and peak loads without objectionable overheating of any component. [NFPA 20- 10: 14.2.5.2.1]
  • 35. 8.4 Reports. 8.4.1 Any abnormality observed during inspection or testing shall be reported promptly to the person responsible for correcting the abnormality. 8.4.2* Test results shall be recorded and retained for comparison purposes in accordance with Section 4.3. 8.4.2.1 All time delay intervals associated with the pump’s starting, stopping, and energy source transfer shall be recorded. 8.5 Maintenance. 8.5.1* A preventive maintenance program shall be established on all components of the pump assembly in accordance with the manufacturer’s recommendations. 8.5.2 Records shall be maintained on all work performed on the pump, driver, controller, and auxiliary equipment. 8.5.3 In the absence of manufacturer’s recommendations for preventive maintenance,
  • 36.
  • 37.
  • 38.
  • 39. All rotating machines, pumps included, vibrate to some extent due to various reasons, the most common of which are typically the following: • Improper installation at site • Improper balancing of pump rotor • Excessively turbulent fluid flow • Pressure fluctuations • Cavitation or internal recirculation in pumps • Normal pump wear after prolonged operation. Pump Vibration
  • 41. Misalignment will affect the Pump performance and damage the pump. ACCEPTABLE PUMP ALIGNMENT TOLERANCES RPM 1800 RPM 3600 RPM Parallel alignment 0.002“ 0.004" Angular 0.004“ 0.006" Alignment
  • 42. • Cooling System filled with premixed water and coolant conditioner. • Batteries serviced and charged 24 hours connected to the engine • Only distilled water shall be used. • Electrolyte shall be added to the batteries a minimum of 24 hours prior to the time the engine has to be started. • Battery plates shall be kept submerged at all times. • The fuel storage tanks shall be kept as full as practical at all times, but never below 66% of tank capacity. A fuel level indicator shall be provided to activate at the 2/3rds tank level. • The fire pump shall be started and brought up to rated speed without interruption within 20 seconds. • Rain cap on outlet if necessary; tight connections. • Fire diesel engine pump exhaust system need to fix gravity louvers to avoid any damages as there is chance of water entry to engine through exhaust system and also any hard particle may go through. • Engines shall be regulated to have no more the 10% speed difference between shutoff and maximum load. • Engines shall be provided with an overspeed shutdown at 20% above rated engine speed with a manual reset. (Only overspeed shutdown or a signal from the diesel controller will shut down an engine.) Diesel Engine Observation
  • 44. KEEP REMEMBER “FIRE PUMP IS THE HEART OF THE FIRE PROTECTION SYSTEM”